Professional Documents
Culture Documents
15
15
bearing load
bearing speed
bearing friction torque
~ubricanttype and viscosity
bearing mounting andlor housing design
environment of operation
In the steady-state operation of a rolling bearing, as for any other
machine element, whatever heat is generated internally is dissipated.
Therefore, the steady-state temperature level of one bearing system com-
pared to another system using identical sizes and number of bearings is
a measure of the relative ability of that system’s efficiency of heat dis-
sipation.
Of course, if the rate of heat dissipation is less than the heatgener-
ation rate, then an unsteady state exists and the system temperature
will rise until lubricant distress occurs, with ultimate bearing failure.
The temperature level at which this occurs is determined largely by the
type of lubricant and the bearing material. This dissertation is limited
to the steady-state thermal operation of rolling bearings since this is a
common concern of bearing users regarding satisfactory operation.
Most rolling bearing applications perform at temperature levels that
are relatively cool and therefore do not require any special consideration
regarding thermal adequacy. This is due to either one of the following
conditions:
. The bearing heat generation rate is low because of light load and/
or relatively slow speed.
. The ability to remove heat from the bearing is sufficient becauseof
location of the bearing assembly in a moving air stream or because
or adequate heat conduction through adjacent metal.
For a high speed ball bearing, the local heat generation rate due to slid-
ing at each contact is given by
(15.2)
(15.3)
Equations (15.2) and (15.3) must be evaluated separately for inner and
outer raceway contacts at each rolling element location.
Having established values for the ratesof heat generation due to fric-
tion, it is then possible to determine the bearing temperature structure
by heattransfer analysis. ..
2 = 16 Ex. 6.5
cyi = 48.8" Fig. 9.4
cy, = 33.3" Fig. 9.4
D = 22.23 mm (0.875 in.) Ex. 2.3
dm = 125.3 mm (4.932 in.) Ex. 2.3
~rn-%=
" 1 - y' COS ai - 1 - 0.1774 * cos(48.8") = 0.4498
n (L, 1 + cos(cr, - ao) 1 + COS (48.8" - 33.3")
(8.63)
(8.57)
= "
@o -
-
wrn
- (8.50)
Y' Y'
or
Since 2 = 16,
ROLLING B ~ ~ G
Hf = 16 X HG
= 16 X 52.92 = 846.7 W (2889 Btu/hr)
,+ A4, = 2860 N * mm (25.27 in. * lb) Ex. 14.3
,+=
, 1.047 X nM,,, (15.1)
= 1.05 X X 10,000 X 2860 = 3003 W (10248 Btu/hr)
ot = 3003 + 847 = 3850 W (13140 Btulhr)
Figure 15.1 shows heat generation rates for this bearing for a load
range of 44,500 N (0-10,000 lb) and a shaft speed of 10,000 rpm.
There exist three fundamental modes for the transfer of heat between
masses having different temperature levels. Theseare conduction of heat
within solid structures, convection of heat from solid structures to fluids
in motion (or apparently at rest), and radiation of heat between masses
separated by space. Although other modes exist, such as radiation to
gases and conduction within fluids, their effects are minor for mostbear-
ing applications and may usually be neglected.
etio
eat conduction? which is the simplest form of heat transfer, may be
described for the purpose of this discussion as a linear function of the
difference in temperature level within a solid structure, that is,
(15.4)
The quantity S in equation (15.4) is the area normal to the flow of heat
between two points and 6 is the distance between the same two points.
The thermal conductivity lz is a function of the material an
ever, the latter varia is generally minor for
11 be neglected here. heat conduction in a r
HEAT T ~ ~ F E R 557
N
0 10,000 20,000 30,000 40,000 50,0(
18,000
I I 1
5000
4000
3000
II)
4
.
d
c
i2
2000
1000
0
Bearing thrust load, Ib
F ~ ~ U R15.E1. Friction heat generation vs load; 218 angular-contact ball bearing,10,000
rpm, 5 centistokes oil,jet lubrication.
2 ~ k ? 3 ( T-~To)
He = (15.5)
ln (ti't,/&)
h, = 0.0332kPr1’3 ( ~ ) 1 ’ 2 (15.7)
The use of equation (15.7) taking u, equal to bearing cage surface velocity
and x equal to bearing pitch diameter seems to yield workablevalues for
h,, conside~ngheat transferfrom the bearing to the oil that contacts the
bearing. For heat transfer from the housing inside surface to the oil,
taking u, equal to one-third cage velocityand x equal to housing diameter
yields adequate results. In equation (15.7), vo represents kinematic vis-
cosity and Pr the Prandtl number of the oil.
If cooling coils are submerged in the oil sump, it is best that they be
aligned parallel to the shaft so that a laminar cross flow obtains. In this
case Eckert El5.11 shows for a cylinder in cross flow, the outside heat
transfer film coefficient may be approsimated by
(15.8)
For forced flow of air of velocity u, over the housing, Reference [15.l]
yields:
hv =; 0.03 - (15.10)
(15.11)
(15.13)
rlgc
Pr = - (15.15)
k
(15.16)
(15.17)
in which
h4S4 + k3S3
-(T3 - To)+ -(T4 - To)= 0 (15.21)
%3 g4
or
i=4
FITl + F2T2+ F3T3+ F4T4- (15.23)
i= 1
(15.24)
&Ti = 0 (15.25)
or
Q Heat generated
ROLLI~GB E ~ TE
~ G
(15.29)
Ti == Tj(0) + ej (15.30)
and new values qi may bedetermined. The processis continued until the
functions qi are virtually zero. Witha system of nonlinear equations sim-
ilar to equation (15.28), such equations must be linearized according to
equation (15.29). Thus, let equation (15.28) be rewritten as follows:
NOW
(15.32)
~ u ~ s t i t u tofi oequations
~ (15.31) and (15.32)into (15.29) yields one
equa-
tion in variables eo, el, and e2.
he syst~mof nonlinear equations is solved for To,
rms error is sufficiently small, for e~ample,less than 0.1".
23072 double-row radial spherical roller bearing
has a 444.5 mm (17.5 in.) pitch diameter and is mounted in thepillow
block shown by Fig. 15.4. The bearing is operated at a shaft speed of
350 rpm while it supports a 489,500 N (110,000 lb) radial load. The
bearing is lubricated by 100 SSU (20 centistokes) oil in a bath at op-
erating temperature. The pillow block that houses the bearing is sit-
uated inan atmosphere of quiescent airat temperature 48.9"C
(120°F). Estimate the bearing and sump oil temperatures.
MI = f1F"dL (14.99)
M I = 0.001. * (~~9500)1.5(444.5)-0.3
= 5.499 lo4 N mm (486.5 in. lb) 0
flow path are obtained from the dimensions of Fig. 15.4, consideringthe
location of each temperature node.
ased on Table 15.1 and Fig. 15.4, a set of nine simultaneous, nonlin-
ear equations with unknown variables Tl-T9 can be developed. Since this
system is nonlinear in temperature because of free convection and ra-
diation from the housing to ambient, the ~ e w t o n - ~ a ~ h smethod
on of
equations (15.29) will be used to obtain a solution. The final values of
temperature are shown in the proper location in Fig. 15.5.
The system chosenfor evaluation was necessarily simple. A more
realistic system would consider variation of bearing temperature in a
circumferential directionalso.For this case,viscous torque maybe
considered constant with respect to angular position;however,load
torque varies as the individual rolling element load on the stationary
ring but may be consideredinvariant with respect to angular position on
the rotatingring. A three-dimensional analysis such as thatindicated by
load torque variation on the stationary ringshould, however, showlittle
(369"F)
For situations in which the bearing is the prime source of heat and in
which the ambient conditions surrounding the housing do not permit an
adequate rate of heat removal, simply placing the housing in a moving
air stream may be sufficient to reduce operating temperatures. For in-
stance, placing the housing of Fig. 15.4 in a fanned air stream of 15.2
m/sec (50 ft/sec) velocity will create a heat transfer coefficient of about
2.386 x W/mm2 * "C (4.2 Btu/hr * ft2 * O F ) on the outside surface of
the housing, which is approximately 4 times that for the natural con-
vection system and gives a maximum bearing temperature of 168°C
(334°F)as opposed to 221°C (429°F)obtained for free convection. Figure
15.6 shows the remaining system temperatures. Thus, in this case, the
system temperatures can be significantly reduced if a fan is used to cir-
culate air over the housing.
If a fan is used, increased heat transfer from the housing to the air
stream may be effected by placing fins on the housing. This increases
the effective area for heat transfer from the housing. Consider that the
external area of the housing of Fig. 15.4 is doubled by use of fins. Using
the filmcoefficient of 2.386 X W/mm2 "C (4.2 Btu/hr * ft2 * O F ) for
the moving air stream and 2 times the external housing area yields a
maximum bearing temperature of 149°C (300°F).Figure 15.7 showsother
system temperatures.
M e n the bearing is not the prime source of heat, cooling of the hous-
ing will generally not suffice to maintain the bearing and lubricant cool.
L A
15.6. Temperature distribution, outside air velocity 15.2 mlsec (50 ftlsec).
IGH TIE E CONS IONS 1
15.7. Temperature distribution, air velocity 15.2 rn/sec (50 ftlsec) finned hous-
ing.
b A
. Temperature distribution, outside air velocity 15.2 mlsec (50 Wsec).
perature is maintained at anaverage of 60°C (140°F)with shaft temper-
ature of 260°C (500°F)as above and ambient temperature of 49°C (120°F)
in quiescent air. Maximum bearing temperature is thereby suppressed
to 93°C (2OO"F),which would appear to be a satisfactory operating level.
(see Fig. 15.9 for other temperatures.)
It was intended to demonstrate in the foregoing discussion that it is
possible to estimate with a reasonable degree of accuracy the tempera-
tures occurring in an oil-lubricated rolling bearing assembly
more, if the bearing and oil temperatures so calculated are excessive, it
is possible to determine the type and degree of cooling capability required
to maintain a satisfactory temperature level.
Several researchers have applied the foregoing methods to effectively
predict temperatures in rolling bearing applications. Initially, Harris
i15.8, 15.91 applied the method to relatively slow speed spherical roller
15.9. Temperature distribution, oil is cooled to 66°C (150°F) average tempera-
ture.
support
bearing
""
Inner ring
(a)
15.10. Bearing system nodal network and heat flow paths for steady-state ther-
-
sis. ( a ) Metal, air, and lubricant temperature nodes: metal or air node; o lu-
bricant node; * lubricant flow path. ( b ) Conduction and convection heat flow paths (from
[15.14]).
280 -
aj t I 1 I
480
440
U-
- c
3
‘5 -
7 440
320 is
420
280
I I I J
0 5 0 0 1 1m m
Total lubricant flow rate, c m 3 h i n
Total iubricant flow rate, cm3/min
1 -2
0
.1 2 .3 .4 .5 0 .1 .2 .3 .4 .5
Total lubricant flow rate, gpm Total lubricant flow rate. gpm
w
4
w 15.11. Comparison of predicted and experimental temperatures using S
e .Oil-out temperature. (d)Bear-
(a>Inner raceway temperature. (b)Outer raceway t e m p e r ~ t ~(c>
ing heat generation (from [15.141).
57 ROLLING BEARING T E ~ E ~ T ~ ~
1-rolling element
6-lubricant out
5-ring
15.12. Rolling element-lubricant-raceway-~ng temperature node system.
Since the lubricant is essentially a solid slug during its time in the con-
tact, heat transfer from the film to the rolling body surfaces is by con-
duction. Then, assuming the minute slug exists atan average
temperature T3,
Finally, the lubricant acts as a heat sink carrying heat away from the
contact.
15.1. E. Eckert, Introduction to the Transfer ofHeat and Mass, McGraw-Hill, New York
(1950).
15.2. M. Jakob and G. Hawkins, Elements ofHeat Transferand Insulation,2nd ed., Wiley,
New York (1950).
15.3. A. Palmgren, Ball and Roller Bearing Engineering, 3rd ed., Burbank, Philadelphia
(1959).
15.4. I?. Kreith, “Convection Heat Transfer in Rotating Systems,’’Adv. in Heat Transfeq
6 , 129-251 (1968).
15.5. G. Dusinberre, Numerical Methods in Heat Transfeq McGraw-Hill,New York(1949).
15.6. 6. Korn and T. Korn, Mathematical Handbook forScientists and Engineers,
McGraw-Hill, New York (1961).
15.7. SKY, General Catalog 4000 US, 2nd ed., 49 (1997).
15.8. T. Harris, “Prediction of Temperature in a Rolling Bearing Assembly,” Lubr. Eng.,
145-150 (April 1964).
15.9. T. Harris, “HOWto Predict Temperature Increases in Rolling Bearings,” Prod. Eng.,
89-98 (Dec. 9, 1963).
15.10. J. Pirvics and R. Kleckner, “Prediction of Ball and Roller Bearing Thermal and
Kinematic Performance by Computer Analysis,” in Adu. Power ~ a n s m i s s ~ oTech.,
n
NASA Conference Publication 2210, 185-201 (1982).
15.11. H. Coe, “Predicted and Experimental Performance of Large-Bore High Speed Ball
and Roller Bearings,” in Adu. Power D a n s ~ i s s i o nTech., NASA Conference Publi-
cation 2210, 203-220 (1982).
15.12. R. Kleckner and G. Dyba, “High Speed Spherical Roller Bearing Analysis and Com-
parison with Experimental Performance,” in Adu. Power Transmission Tech., NASA
Conference Publication 2210, 239-252 (1982).
15.13. VV. Crecelius, “User7s Manual for SKF Computer Program S W E R T H , Steady
State and Transient Thermal Analysis of a Shaft Bearing System Including Ball,
Cylindrical, and Tapered Roller Bearings,” SKF’Report AL77P015, submitted toU.S.
Army Ballistic Research Laboratory (February 1978).
15.14. R. Parker, “Comparison of Predicted and Experi~entalThermal Performance of
Angular-Contact Ball Bearings,”NASA Tech. Paper 2275 (February 1984).
15.15. T. Harris and R. Barnsby, “Tribological Performance Prediction of Aircraft Gas Tur-
bine Mainshaft Ball Bearings,” DiboZogy Dans 41(1), 60-68 (1998).