Multilin™

G60
GENERATOR PROTECTION SYSTEM

Comprehensive Protection for Generators

KEY BENEFITS
• Secure, high-speed protection elements for complete generator • Increase network availability by reducing failover time to zero
protection, compliant with IEEE® C37.102 through IEC 62439-3 “PRP” support
• Phasor Measurement Unit (synchrophasor) according to IEEE • CyberSentry™ provides high-end cyber security aligned to industry
C37.118 (2011) and IEC® 61850-90-5 support standards and services (NERC® CIP, AAA, Radius, RBAC, Syslog)
• Three independent fiber or copper Ethernet ports for simultaneous/ • Robust network security enabling Critical Infrastructure
dedicated network connections with advanced 1 microsecond time Protection through user command logging, and dual permission
synchronization via LAN with IEEE 1588 support access control
• Reduced relay-to-relay wiring and associated installation costs • Advanced fault and disturbance recording, including internal
through high-speed inter-relay communications relay operating signals, eliminating the need for external
• Available Ethernet Global Data (EGD) eases integration with new recording devices
and existing GE Digital Energy control systems • Complete IEC 61850 Process Bus solution provides resource
optimization and minimizes total P&C life cycle costs

APPLICATIONS
• Medium to large generators typically driven by steam, gas or • Stand-alone protection or component in automated substation
hydraulic turbines control systems
• Pumped storage generators used as pumping motors for • Standard protection product offering on new GE generator
reservoir storage installations

FEATURES
Protection and Control IEC 61850 Process Bus Interface
• Generator stator differential • Robust communications with up to 8 HardFiber Bricks
• 100% stator ground protection 3rd harmonic • Redundant architecture for dependability and security
• Field ground protection
Monitoring and Metering
• 100% stator ground fault protection using • Metering: current, voltage, power, energy, frequency
sub-harmonic injection
• Advanced recording capabilities deliver a 1024 event recorder,
• Loss of excitation configurable and extended waveform capture and data logger
• Power swing blocking and out-of-step tripping • Advanced relay health diagnostics
• Backup distance • P & M class synchrophasors of voltage, current and sequence
• Reverse/low forward power components: 1 to 120 frames/sec
• Restricted ground fault, thermal overload protection, directional,
time, instantaneous, phase, neutral, negative sequence and EnerVista™ Software
ground overcurrent protection • Graphical Logic Designer and Logic Monitor to simplify designing
and testing procedures via EnerVista UR Engineer
• Overexcitation
• Service and update notification toolset ensures device documents
• Generator unbalance
and software are up-to-date via EnerVista Launchpad
• CT failure for each CT bank, VT fuse failure
• EnerVista Integrator providing easy integration of data in the G60
• Breaker failure into new or existing monitoring and control systems
Communications
• Networking interfaces: up to three Ethernet ports 100Mb fiber or
copper, RS485, RS232, RS422, G.703, C37.94
• Multiple protocols: IEC 61850, DNP 3.0 and Modbus® serial/TCP,
IEEE 1588, IEC 60870-5-104 and 103, PRP, SNTP, HTTP, TFTP, EGD
• Direct I/O: secure, high-speed exchange of data between URs for
direct transfer trip (DTT) and I/O extension applications

g imagination at work
G60 Generator Protection System

Protection and Control G60 - Protection, Metering, Monitoring and Control


Generator Protection

The G60 generator protection system


provides comprehensive protection for
medium and large generators, including
large steam and combustion turbines,
combined-cycle generators and multi-
circuit hydro units. The G60 includes
advanced automation and communication
capabilities, extensive I/O options, and
powerful fault recording features that can
simplify postmortem disturbance analysis
and help minimize generator downtime.
As part of the Universal Relay (UR) family,
the G60 provides superior protection and
control that includes:

Generator Stator Differential


High-speed stator differential protection
The G60 is the single point for protection, control, metering, and monitoring in one integrated device
provides sub-cycle detection and high- that can easily be connected directly into DCS or SCADA monitoring and control systems like Viewpoint
speed clearing of stator phase faults. Monitoring as shown.
Advanced CT saturation and failure
detection algorithms maintain immunity feature that responds to the unbalance Breaker Failure Protection
to high current AC and low current DC of the third harmonic at the machine The breaker failure protection element
saturation conditions that may occur terminals and at the neutral point. This monitors for timely operation of the
due to external disturbances, such as method is insensitive to the absolute connected breaker. If a trip command is
transformer inrush or near generator value of the third harmonic and is not successful in operating the breaker
faults, without sacrificing speed or easily set without the need for on-line and clearing the fault, the breaker failure
sensitivity. measurements. For generators with element can be used to send trip signals to
delta connected PTs, a third harmonic upstream breakers to clear the fault.
100% Stator Ground 3rd Harmonic undervoltage element is also offered for
100% stator ground fault protection is detecting a loss of the third harmonic Field Ground Protection
provided through a voltage differential voltage at the generator neutral. Field ground protection identifies the

Functional Block Diagram ANSI Device Numbers & Functions


Device
Number Function
21P Phase Distance Backup
24 Volts Per Hertz
25 Synchronism Check
SUPERVISED CLOSE 27P Phase Undervoltage
52 25 27TN Third Harmonic Neutral Undervoltage
TRIP 4
27X Auxiliary Undervoltage
24 27P 59P 59_2 59N 81O 81U 81R 32 Sensitive Directional Power
2 3 3 3 3 4 6 4 40 Loss of Field Relay
46 Generator Unbalance
49 Thermal Overload
50G Ground Instantaneous Overcurrent
50N Neutral Instantaneous Overcurrent
32 40 50/27 21P 50P 50N 51PV 50BF 51N 46 49 67P 67_2 67N 68 78 50P Phase Instantaneous Overcurrent
2 3 2 4 2 2 2 50SP Split Phase Instantaneous Overcurrent
50BF Breaker Failure
EX GPM-F 64F 50/27 Accidental Energization
G
51G Ground Time Overcurrent
51PV Phase Time Overcurrent with Voltage Restraint
51N Neutral Time Overcurrent
87S Metering 59N Neutral Overvoltage
59P Phase Overvoltage
59X Auxiliary Overvoltage
59_2 Negative Sequence Overvoltage
64F Field Ground Protection
87G 50G 51G
2
64S Sub-Harmonic Stator Ground Protection
27TN 27X 59X 64TN 100% Stator Ground
GPM-S
2 2 67_2 Negative Sequence Directional Overcurrent
R 64TN 67N Neutral Directional Overcurrent
67P Phase Directional Overcurrent
64S 68 Power Swing Blocking
78 Out-of-Step Protection
G60 Generator Protection System 81O Overfrequency
81R Rate of Change of Frequency
ANSI DEVICE NUMBERS AND FUNCTIONS 81U Underfrequency
DEVICE DEVICE 87G Restricted Ground Fault
NUMBER FUNCTION NUMBER FUNCTION 87S Generator Stator Differential
21P Phase Distance Backup 51P Phase Time Overcurrent
24 Volts Per Hertz 59N Neutral Overvoltage
86 25 Synchrocheck 59P GEDigitalEnergy.com
Phase Overvoltage
27P Phase Undervoltage 59X Auxiliary Overvoltage
27TN Third Harmonic Neutral Undervoltage 59_2 Negative Sequence Overvoltage
G60 Generator Protection System

G60 Percent Differential Element RGF protection (also known as zero-

Generator Protection
sequence differential) extends protection
coverage to the neutral point of the
stator winding, where fault currents may
be below the pickup of the main stator
differential element. The low-impedance
(87G) protection provided by the G60 uses
an optimized adaptive restraint signal
that provides security for external fault
conditions that may cause CT saturation
while still maintaining sensitivity for internal
faults.

Pumped Storage Generator


The G60 can be used for protecting
generators that are also run as pumped
storage motors, without the need for
switching the CT secondary circuitry. The
The G60 percent differential element has enhanced saturation detection algorithms to provide additional
security against AC and DC saturation that can occur during faults near the generator. G60 is able to automatically compensate
for the phase reversal that occurs when
the generator is being run as a motor.
occurrence of a ground fault in a generator blocking input provide security for blown
field winding and helps to prevent serious VT fuses and power swing conditions.
Synchronism Check
damage to the generator, maximizing
operational lifespan. The field ground Power Swing/Out-of-Step The G60 provides four elements to monitor
protection module (GPM-F) works in differences in voltage magnitudes, phase
The power swing blocking element provides
combination with the G60 to detect ground angles, and frequencies to perform
blocking of the backup distance element
faults in the field winding of the generator. synchronism checks across breakers (up to
and other protections under power swing
The solution includes: two-stage field four). The G60 can be used in conjunction
conditions. Negative sequence current
ground detection, injected voltage and with an external synchronizer as an
supervisors provide extended selectivity for
current supervision, brush lift-off detection, independent check of the synchronizer
detecting evolving faults that may appear
field over and undercurrent elements and prior to closing the generator breaker.
as a power swing event (faults with slow
field ground fault location. moving impedance locus). Additionally,
Temperature Protection
the out-of-step tripping element can be
100% Stator Ground Fault (RTD Module Option 5C)
used for tripping the generator when an
Protection Using Sub-Harmonic unstable power swing is detected.
The G60 RTD option provides 8
Injection programmable RTD inputs per module that
Protecting the generator from internal faults Backup Phase Distance are used for temperature monitoring. Each
is critical to maintaining the overall life of the RTD input has 2 operational levels: alarm
Three separate phase distance elements
generator. Using the 100% stator ground and trip. The G60 supports RTD trip voting
provide time-delayed backup protection for
fault protection based on sub-harmonic and provides open RTD failure alarming.
generator faults that have not otherwise been
injection, a 20Hz voltage is injected to Alternatively, a remote RTD module,
cleared by the primary system and generator
detect ground faults at any point across “RRTD”, which supports 12 RTD inputs, can
protection. Each zone can independently
100% of the winding. The stator ground also be used with the G60 for temperature
compensate for power transformers, so
module (GPM-S) works in combination with monitoring. The RRTD provides cost savings
compensation can be applied for zones
the G60 to provide 100% stator ground compared with standard RTD wiring.
reaching out into the system through the
fault protection that is operational during unit transformer, while zones looking into the
generator start-up, running and stopped stator can remain uncompensated. IEC 61850 Process Bus
conditions. The solution includes: two- The IEC 61850 Process Bus module is
stage stator ground detection, injected Sensitive Directional Power designed to interface with the Multilin
voltage and current supervision and ground Two separate directional power elements HardFiber System, allowing bi-directional
overcurrent element. are provided to detect generator motoring IEC 61850 fiber optic communications. The
to protect the prime mover from damage. HardFiber System is designed to integrate
Loss of Excitation Each element responds to either reverse or seamlessly with existing UR applications,
Generator loss of excitation protection low forward power flow and can be used to including protection functions, FlexLogic™,
is provided via two negative offset mho provide independent alarm and trip settings. metering and communications.
characteristics as per IEEE C37.102. The Multilin HardFiber System offers the
Inadvertent pickup time delay settings and Restricted Ground Fault (87G) following benefits:

GEDigitalEnergy.com 87
G60 Generator Protection System

• Communicates using open standard • Form-A and SSR outputs available with SCADA communications and front panel
Generator Protection

IEC 61850 messaging optional circuit continuity monitoring display. Providing continuous monitoring
and current detection to verify continuity and early detection of possible issues help
• Drastically reduces P&C design,
and health of the associated circuitry improve system uptime.
installation and testing labor by
eliminating individual copper terminations • Mechanically latching outputs • Comprehensive device health
can be used to develop secure diagnostic performed at startup
• Integrates with existing G60’s by
replacing traditional CT/VT inputs with interlocking applications and replace • Monitors the CT/VT input circuitry to
the IEC 61850 Process Bus module electromechanical lockout relays validate the integrity of all signals

• Does not introduce new cyber security • RTDs and DCmA inputs are available to
concerns monitor equipment parameters such as Cyber Security –
temperature and pressure
CyberSentry UR
Visit the HardFiber System product page
CyberSentry UR enabled UR devices deliver
on the GE Digital Energy web site for more Monitoring and Metering full cyber security features that help
details.
The G60 includes high accuracy metering customers to comply with NERC CIP and
and recording for all AC signals. Voltage, NIST® IR 7628 cyber security requirements.
Advanced Automation current, and power metering are built into This software option delivers the following
The G60 incorporates advanced automation the relay as a standard feature. Current and core features:
features including powerful FlexLogic voltage parameters are available as total
programmable logic, communication, and RMS magnitude, and as fundamental AAA Server Support (Radius/LDAP)
SCADA capabilities that far surpass what frequency magnitude and angle. Enables integration with centrally managed
is found in the average generator relay. authentication and accounting of all
The G60 integrates seamlessly with other Fault and Disturbance Recording user activities and uses modern industry
UR relays for complete system protection, The advanced disturbance and event best practices and standards that meet
including unit and auxiliary transformers, recording features within the G60 can and exceed NERC CIP requirements for
and balance of plant protection. significantly reduce the time needed for authentication and password management.
postmortem analysis of power system
FlexLogic events and the creation of regulatory Role Based Access Control (RBAC)
FlexLogic is the powerful UR-platform reports. Recording functions include: Efficiently administrate users and roles
programming logic engine that provides the • Sequence of Event (SOE) within UR devices. The new and advanced
ability to create customized protection and - 1024 time stamped events access functions allow users to configure up
control schemes, minimizing the need and to five roles for up to eight configurable users
• Oscillography
associated costs of auxiliary components with independent passwords. The standard
and wiring. Using FlexLogic, the G60 can - 64 digital & up to 40 analog channels
“Remote Authentication Dial In User Service”
be programmed to provide the required - Events up to 45s in length
(Radius) is used for authentication.
tripping logic along with custom scheme • Data Logger and Disturbance Recording
logic for generator breaker control (including - 16 channels up to 1 sample/cycle/ Event Recorder (Syslog for SEM)
interlocking with external synchronizers), channel Capture all cyber security related events
transfer tripping schemes for remote breakers • Fault Reports within a SOE element (login, logout, invalid
and dynamic setting group changes. - Powerful summary report of pre-fault password attempts, remote/local access,
and fault values user in session, settings change, FW
Scalable Hardware
update, etc), and then serve and classify
The G60 is available with a multitude data by security level using standard
The very high sampling rate and large
of I/O configurations to suit the most Syslog data format . This will enable
amount of storage space available for
demanding application needs. The integration with established SEM (Security
data recording in the G60 can eliminate
expandable modular design allows for Event Management) systems.
the need for installing costly stand-alone
easy configuration and future upgrades.
recording equipment.
• Multiple CT/VT configurations allow for Communications
the implementation of many different Advanced Device Health
The G60 provides advanced commun-
schemes, including concurrent split- Diagnostics
ications technologies for remote data and
phase and differential protection
The G60 performs comprehensive device engineering access, making it easy and
• Flexible, modular I/O covering a broad health diagnostic tests at startup and flexible to use and integrate into new and
range of input signals and tripping continuously during run-time to test its own existing infrastructures. Direct support for
schemes major functions and critical hardware. These fiber optic Ethernet provides high-bandwidth
• Types of digital outputs include trip- diagnostic tests monitor for conditions that communications allowing for low-latency
rated Form-A and Solid State Relay (SSR) could impact security and availability of controls and high-speed file transfers of
mechanically latching, and Form-C outputs protection, and present device status via

88 GEDigitalEnergy.com
G60 Generator Protection System

relay fault and event record information. experience with UCA 2.0. • Communication with up to 16 UR relays

Generator Protection
The available three independent Ethernet • Replace expensive copper wiring in single or redundant rings rather than
ports, redundant Ethernet option and between devices with direct transfer of strictly limited to simplistic point-to-point
the embedded managed Ethernet switch data using GOOSE messaging configurations between two devices
provide the means to create fault tolerant
• Configure GE systems based on • Connect to standard DS0 channel
communication architectures in an easy,
IEC 61850 and also monitor and banks through standard RS422, G.703
cost-effective manner without the need
troubleshoot them in real-time with or IEEE C37.94 interfaces or via direct
for intermediary communication hardware.
EnerVista Viewpoint Engineer fiber optic connections
The G60 supports the most popular industry
• Multicast IEEE C37.118 synchrophasor • No external or handheld tester required
standard protocols enabling easy, direct
data between PMU and PDC devices to provide channel diagnostic information
integration into DCS and SCADA systems.
using IEC 61850-90-5
LAN Redundancy
• IEC 61850 with 61850-90-5 support Direct I/O Messaging Substation LAN redundancy has been
• DNP 3.0
Direct I/O allows for the sharing of traditionally accomplished by reconfiguring
• Ethernet Global Data (EGD)
high-speed digital information between the active network topology in case of failure.
• IEC 60870-5-103 and IEC 60870-5-104
multiple UR relays via direct back-to-back Regardless of the type of LAN architecture
• IEEE 1588 for time synchronization
connections or multiplexed through a (tree, mesh, etc), reconfiguring the active
• Modbus RTU, Modbus TCP/IP
standard DS0 multiplexer channel bank. LAN requires time to switchover, during
• PRP as per IEC 62439-3
Regardless of the connection method, which the LAN is unavailable. UR devices
direct I/O provides continuous real- deliver redundancy as specified by PRP-IEC
Interoperability with Embedded
time channel monitoring that supplies 62439-3, which eliminates the dependency
IEC 61850
diagnostics information on channel health. on LAN reconfiguration and the associated
Use the G60 with integrated IEC 61850 switchover time. The UR becomes a dual
to lower costs associated with generator Direct I/O provides superior relay-to-relay attached node that transmits data packets
protection, control and automation. GE communications that can be used in over both main and redundant networks
Digital Energy’s leadership in IEC 61850 advanced interlocking, generation rejection simultaneously, so in case of failure, one
comes from thousands of installed devices and other special protection schemes. of the data packets will reach the receiving
and follows on extensive development device with no time delay.

Power System Troubleshooting


The G60 contains many tools and reports that simplify and reduce the amount of time required for troubleshooting power system events.

Record the operation of the internal


G60 elements and external connected
devices with 1ms time-stamped
accuracy to identify the Sequence of
Operation of station devices during
generator faults and disturbances.
Analyze generator faults using both analog and
digital power system quantities that are measured
and recorded up to a rate of 64 samples per cycle.

Log generator operating parameters to allow for analyzing generator


loading and performance over weeks and months.

GEDigitalEnergy.com 89
G60 Generator Protection System

Multi-Language connections, or offline by creating setting testing of GE relays at a system level in


Generator Protection

files to be sent to devices at a later time. an easy-to-use graphical drag-and-drop


UR devices support multiple languages:
environment . Viewpoint UR Engineer
English, French, Russian, Chinese, Turkish
Included in Launchpad is a document provides the following configuration and
and German. These language options are
archiving and management system commissioning utilities:
available on the front panel, in the EnerVista
setup software, and in the product manuals. that ensures critical documentation is • Graphical Logic Designer
Easily switch between English and an up-to-date and available when needed. • Graphical System Designer
additional language on the local displays Documents made available include: • Graphical Logic Monitor
without uploading new firmware. • Manuals • Graphical System Monitor
• Application Notes
Viewpoint Maintenance
EnerVista Software • Guideform Specifications
• Brochures Viewpoint Maintenance provides tools that
The EnerVista suite is an industry-leading
• Wiring Diagrams will create reports on the operating status
set of software programs that simplifies
• FAQs of the relay, simplify the steps to download
every aspect of using the G60 relay. The
• Service Bulletins fault and event data, and reduce the work
EnerVista suite provides all the tools
required for cyber security compliance
to monitor the status of the protected Viewpoint Monitoring audits. Tools available in Viewpoint
asset, maintain the relay, and integrate
Viewpoint Monitoring is a simple-to-use Maintenance include:
information measured by the G60 into DCS
and full-featured monitoring and data
or SCADA monitoring systems. Convenient
recording software package for small • Settings Security Audit Report
COMTRADE and SOE viewers are an
systems. Viewpoint Monitoring provides a • Device Health Report
integral part of the UR setup software
complete HMI package with the following • Single-Click Fault Data Retrieval
included with every UR relay, to carry out
functionality:
postmortem event analysis and ensure
EnerVista Integrator
proper protection system operation.
• Plug & Play Device Monitoring EnerVista Integrator is a toolkit that allows
EnerVista Launchpad • System Single-Line Monitoring & Control seamless integration of Multilin devices
• Annunciator Alarm Screens into new or existing automation systems.
EnerVista Launchpad is a powerful
• Trending Reports Included in EnerVista Integrator is:
software package that provides users with
• Automatic Event Retrieval
all of the setup and support tools needed
• Automatic Waveform Retrieval • OPC/DDE Server
for configuring and maintaining Multilin
products. The setup software within • Multilin Drivers
Viewpoint UR Engineer • Automatic Event Retrieval
Launchpad allows for the configuration
of devices in real-time by communicating Viewpoint UR Engineer is a set of powerful • Automatic Waveform Retrieval
using serial, Ethernet , or modem tools that allows the configuration and

Simplifying Commissioning and Testing Simplifying G60 Configuration

The internal operation of the G60 elements, logic, and outputs can be monitored Create G60 setting file templates to ensure critical settings are not altered.
in real-time to simplify commissioning and troubleshooting procedures.

90 GEDigitalEnergy.com
G60 Generator Protection System

User Interface 48 Configurable LED indicators

Generator Protection
The G60 front panel provides extensive
local HMI capabilities. The local display
is used for monitoring, status messaging, Multi-Language
fault diagnosis, and device configuration. Display
User-configurable messages that combine • English
• Russian
text with live data can be displayed when
• French
user-defined conditions are met. • Chinese
• Turkish
• German

User-Programmable Pushbuttons

Typical Wiring

A
B
C

R
F 5a

F 6a

F 7a
F 5c

F 6c

F 7c
M1b

M2a

M2b

M3a

M3b

M4a
M1a

M4b
M1c

M2c

M3c

M4c

F5a

F6a

F7a

F8a

F1a

F1b

F2a

F2b

F3a

F3b

F4a

F4b
F5c

F6c

F7c

F8c

F1c

F2c

F3c

F4c
VX
VB

VC

VB

VC
VA

VA

VX

IG5

IG1
VB

VC

VB

VC

IG
IG5

IG1

VA

VA
IG

IA5

IA1

IB

IC
IA

IC5

IC1
IA5

IA1

IB5

IB1
IB

IC
IA

IC5

IC1
IB5

IB1

H5a 6G I H1a TC 1
H5c H1
V
H1b
H6a H1c
H6c I H2a
H5b H2
V
H2b
H2c
H7a I H3a
H7c TC 2
H3
V
H3b
H8a
H3c
H8c I H4a
H7b
H4
V
H4b
H8b SURGE H4c

B1b Multilin
CRITICAL
1

B1a FAILURE

DC
B2b
B3a G60 GENERATOR MANAGEMENT RELAY
B3b OUTPUT
B5b HI
CONTROL
B6b LO POWER
B6a
RS-232
B8a SURGE (front)
B8b FILTER
DB-9

* Optic
Fibre Tx1 10BaseFL
NORMAL
Rx1

Tx2 10BaseFL COM


ALTERNATE
Rx2 1

Shielded 10BaseT
Remote
Device D1a
RS485
D2a
D3a com
D4b
D4a IRIG-B
Input
Co-axial BNC

IRIG-B
Co-axial BNC Output
CONNECTOR

minimum
X W V U T S R P N M L K J H G F D B
GROUND 8 6 8 9 1
BUS
7 SGND
3 RXD
2 TXD

PROVIDED CT Inputs/ VT/CT CPU Power


COMPUTER

outputs Supply
20

22
8

5
4
1
2
3
4

7
8
9
5
6

CONNECTOR
UR
1
2
3
4

7
8
9
5
6

G60-H00-HCH-F8F-H6G-M8H-PXX-UXX-WXX
SGND
RXD
TXD

GEDigitalEnergy.com 91
G60 Generator Protection System

Ordering
Generator Protection

G60 - * 00 - H * * - F ** - H ** - M ** - P ** - U ** - W/X ** For full size


Base Unit G60 Base Unit
CPU E RS485 + RS485 (IEC 61850 option not available)
J RS485 + multimode ST 100BaseFX
K RS485 + multimode ST Redundant 100BaseFX
N RS485 + 10/100 BaseT
T RS485 + three multimode SFP LC 100BaseFX. Req FW v7xx or higher
U RS485 + two multimode SFP LC 100BaseFX + one SFP RJ45 100BaseT.
Req FW v7xx or higher
V RS485 + three SFP RJ45 100BaseT. Req FW v7xx or higher
Software Options 00 No Software Options
(see note 1 below) 01 Ethernet Global Data (EGD)
03 IEC 61850
04 Ethernet Global Data (EGD) + IEC 61850
05 Phasor Measurement Unit (PMU)
06 IEC 61850 + Phasor Measurement Unit (PMU)
A0 CyberSentry UR Lvl 1. Req UR FW 7.xx or higher
B0 IEEE 1588. Req UR FW 7.xx or higher
C0 PRP
D0 IEEE 1588 + CyberSentry UR. Req UR FW 7.xx or higher
Mount / Coating H Horizontal (19” rack) - Standard
A Horizontal (19” rack) - Harsh Environment Coating
V Vertical (3/4 size) - Standard
B Vertical (3/4 size) - Harsh Environment Coating
User Interface F Vertical Front Panel with English Display
I Enhanced German Front Panel
J Enhanced German Front Panel with User-Programmable Pushbuttons
K Enhanced English Front Panel
L Enhanced English Front Panel with User-Programmable Pushbuttons
M Enhanced French Front Panel
N Enhanced French Front Panel with User-Programmable Pushbuttons
Q Enhanced Russian Front Panel
T Enhanced Russian Front Panel with User-Programmable Pushbuttons
U Enhanced Chinese Front Panel
V Enhanced Chinese Front Panel with User-Programmable Pushbuttons
W Enhanced Turkish Front Panel
Y Enhanced Turkish Front Panel with User-Programmable Pushbuttons
Power Supply H 125 / 250 V AC/DC
(see note 2 below) H RH 125/250 V AC/DC with redundant 125/250 V AC/DC
L 24 - 48 V (DC only)
CT/VT DSP 8L 8L Standard 4CT/4VT w/ enhanced diagnostics
8M 8M Sensitive Ground 4CT/4VT w/ enhanced diagnostics
8N 8N Standard 8CT w/ enhanced diagnostics
8R 8R Sensitive Ground 8CT w/ enhanced diagnostics
IEC 61850 Process Bus 81 8 Port IEC 61850 Process Bus Module
Digital I/O XX XX XX XX XX No module
4A 4A 4A 4A 4A 4 Solid State (No Monitoring) MOSFET Outputs
4C 4C 4C 4C 4C 4 Solid State (Current w/opt Voltage) MOSFET Outputs
4D 4D 4D 4D 4D 16 Digital Inputs with Auto-Burnish
4L 4L 4L 4L 4L 14 Form-A (No Monitoring) Latchable Outputs
67 67 67 67 67 8 Form-A (No Monitoring) Outputs
6C 6C 6C 6C 6C 8 Form-C Outputs
6D 6D 6D 6D 6D 16 Digital Inputs
6E 6E 6E 6E 6E 4 Form-C Outputs, 8 Digital Inputs
6F 6F 6F 6F 6F 8 Fast Form-C Outputs
6K 6K 6K 6K 6K 4 Form-C & 4 Fast Form-C Outputs
6L 6L 6L 6L 6L 2 Form-A (Current w/ opt Voltage) & 2 Form-C Outputs, 8 Digital Inputs
6M 6M 6M 6M 6M 2 Form-A (Current w/ opt Voltage) & 4 Form-C Outputs, 4 Digital Inputs
6N 6N 6N 6N 6N 4 Form-A (Current w/ opt Voltage) Outputs, 8 Digital Inputs
6P 6P 6P 6P 6P 6 Form-A (Current w/ opt Voltage) Outputs, 4 Digital Inputs
6R 6R 6R 6R 6R 2 Form-A (No Monitoring) & 2 Form-C Outputs, 8 Digital Inputs
6S 6S 6S 6S 6S 2 Form-A (No Monitoring) & 4 Form-C Outputs, 4 Digital Inputs
6T 6T 6T 6T 6T 4 Form-A (No Monitoring) Outputs, 8 Digital Inputs
6U 6U 6U 6U 6U 6 Form-A (No Monitoring) Outputs, 4 Digital Inputs
6V 6V 6V 6V 6V 2 Form-A (Cur w/ opt Volt) 1 Form-C Output, 2 Latching Outputs, 8 Digital Inputs
Transducer I/O 5A 5A 5A 5A 5A 4 dcmA Inputs, 4 dcmA Outputs
5C 5C 5C 5C 5C 8 RTD Inputs
5D 5D 5D 5D 5D 4 RTD Inputs, 4 dcmA Outputs
5E 5E 5E 5E 5E 4 dcmA Inputs, 4 RTD Inputs
5F 5F 5F 5F 5F 8 dcmA Inputs
Inter-Relay Communications 7A 820 nm, multimode, LED, 1 Channel
7B 1300 nm, multimode, LED, 1 Channel
7C 1300 nm, singlemode, ELED, 1 Channel
7H 820 nm, multimode, LED, 2 Channels
7I 1300 nm, multimode, LED, 2 Channels
7J 1300 nm, singlemode, ELED, 2 Channels
7S G.703, 2 Channels
7W RS422, 2 Channels
76 IEEE C37.94, 820 nm, multimode, LED, 1 Channel
77 IEEE C37.94, 820 nm, multimode, LED, 2 Channel

Ordering Notes: 1 . To view all available model order codes, options for G60 or to order the UR Classic Front Panel, please visit GE’s On-Line Store at http://store.gedigitalenergy.com/viewprod.asp?model=G60
2. Redundant power supply only available in horizontal unit. If redundant is chosen, must be same type. Maximum 2 per chassis

IEC is a registered trademark of Commission Electrotechnique Internationale. IEEE is a registered


Accessories for the G60 trademark of the Institute of Electrical Electronics Engineers, Inc. Modbus is a registered trademark
of Schneider Automation. NERC is a registered trademark of North American Electric Reliability
  •  UR Applications I Learning CD TRCD-URA1-C-S-1 Council. NIST is a registered trademark of the National Institute of Standards and Technology.
  •  Multilink Ethernet Switch ML2400-F-HI-HI-A2-A2-A6-F1 GE, the GE monogram, Multilin, FlexLogic, EnerVista and CyberSentry are trademarks of General
 • Viewpoint Engineer VPE-1 Electric Company.

 • Viewpoint Maintenance VPM-1 GE reserves the right to make changes to specifications of products described at any time without
notice and without obligation to notify any person of such changes.
  •  Viewpoint Monitoring IEC 61850 VP-1-61850
Copyright 2013, General Electric Company.

GEA-12587G(E)
92 GEDigitalEnergy.com English