G60
GENERATOR PROTECTION SYSTEM
KEY BENEFITS
• Secure, high-speed protection elements for complete generator • Increase network availability by reducing failover time to zero
protection, compliant with IEEE® C37.102 through IEC 62439-3 “PRP” support
• Phasor Measurement Unit (synchrophasor) according to IEEE • CyberSentry™ provides high-end cyber security aligned to industry
C37.118 (2011) and IEC® 61850-90-5 support standards and services (NERC® CIP, AAA, Radius, RBAC, Syslog)
• Three independent fiber or copper Ethernet ports for simultaneous/ • Robust network security enabling Critical Infrastructure
dedicated network connections with advanced 1 microsecond time Protection through user command logging, and dual permission
synchronization via LAN with IEEE 1588 support access control
• Reduced relay-to-relay wiring and associated installation costs • Advanced fault and disturbance recording, including internal
through high-speed inter-relay communications relay operating signals, eliminating the need for external
• Available Ethernet Global Data (EGD) eases integration with new recording devices
and existing GE Digital Energy control systems • Complete IEC 61850 Process Bus solution provides resource
optimization and minimizes total P&C life cycle costs
APPLICATIONS
• Medium to large generators typically driven by steam, gas or • Stand-alone protection or component in automated substation
hydraulic turbines control systems
• Pumped storage generators used as pumping motors for • Standard protection product offering on new GE generator
reservoir storage installations
FEATURES
Protection and Control IEC 61850 Process Bus Interface
• Generator stator differential • Robust communications with up to 8 HardFiber Bricks
• 100% stator ground protection 3rd harmonic • Redundant architecture for dependability and security
• Field ground protection
Monitoring and Metering
• 100% stator ground fault protection using • Metering: current, voltage, power, energy, frequency
sub-harmonic injection
• Advanced recording capabilities deliver a 1024 event recorder,
• Loss of excitation configurable and extended waveform capture and data logger
• Power swing blocking and out-of-step tripping • Advanced relay health diagnostics
• Backup distance • P & M class synchrophasors of voltage, current and sequence
• Reverse/low forward power components: 1 to 120 frames/sec
• Restricted ground fault, thermal overload protection, directional,
time, instantaneous, phase, neutral, negative sequence and EnerVista™ Software
ground overcurrent protection • Graphical Logic Designer and Logic Monitor to simplify designing
and testing procedures via EnerVista UR Engineer
• Overexcitation
• Service and update notification toolset ensures device documents
• Generator unbalance
and software are up-to-date via EnerVista Launchpad
• CT failure for each CT bank, VT fuse failure
• EnerVista Integrator providing easy integration of data in the G60
• Breaker failure into new or existing monitoring and control systems
Communications
• Networking interfaces: up to three Ethernet ports 100Mb fiber or
copper, RS485, RS232, RS422, G.703, C37.94
• Multiple protocols: IEC 61850, DNP 3.0 and Modbus® serial/TCP,
IEEE 1588, IEC 60870-5-104 and 103, PRP, SNTP, HTTP, TFTP, EGD
• Direct I/O: secure, high-speed exchange of data between URs for
direct transfer trip (DTT) and I/O extension applications
g imagination at work
G60 Generator Protection System
Generator Protection
sequence differential) extends protection
coverage to the neutral point of the
stator winding, where fault currents may
be below the pickup of the main stator
differential element. The low-impedance
(87G) protection provided by the G60 uses
an optimized adaptive restraint signal
that provides security for external fault
conditions that may cause CT saturation
while still maintaining sensitivity for internal
faults.
GEDigitalEnergy.com 87
G60 Generator Protection System
• Communicates using open standard • Form-A and SSR outputs available with SCADA communications and front panel
Generator Protection
IEC 61850 messaging optional circuit continuity monitoring display. Providing continuous monitoring
and current detection to verify continuity and early detection of possible issues help
• Drastically reduces P&C design,
and health of the associated circuitry improve system uptime.
installation and testing labor by
eliminating individual copper terminations • Mechanically latching outputs • Comprehensive device health
can be used to develop secure diagnostic performed at startup
• Integrates with existing G60’s by
replacing traditional CT/VT inputs with interlocking applications and replace • Monitors the CT/VT input circuitry to
the IEC 61850 Process Bus module electromechanical lockout relays validate the integrity of all signals
• Does not introduce new cyber security • RTDs and DCmA inputs are available to
concerns monitor equipment parameters such as Cyber Security –
temperature and pressure
CyberSentry UR
Visit the HardFiber System product page
CyberSentry UR enabled UR devices deliver
on the GE Digital Energy web site for more Monitoring and Metering full cyber security features that help
details.
The G60 includes high accuracy metering customers to comply with NERC CIP and
and recording for all AC signals. Voltage, NIST® IR 7628 cyber security requirements.
Advanced Automation current, and power metering are built into This software option delivers the following
The G60 incorporates advanced automation the relay as a standard feature. Current and core features:
features including powerful FlexLogic voltage parameters are available as total
programmable logic, communication, and RMS magnitude, and as fundamental AAA Server Support (Radius/LDAP)
SCADA capabilities that far surpass what frequency magnitude and angle. Enables integration with centrally managed
is found in the average generator relay. authentication and accounting of all
The G60 integrates seamlessly with other Fault and Disturbance Recording user activities and uses modern industry
UR relays for complete system protection, The advanced disturbance and event best practices and standards that meet
including unit and auxiliary transformers, recording features within the G60 can and exceed NERC CIP requirements for
and balance of plant protection. significantly reduce the time needed for authentication and password management.
postmortem analysis of power system
FlexLogic events and the creation of regulatory Role Based Access Control (RBAC)
FlexLogic is the powerful UR-platform reports. Recording functions include: Efficiently administrate users and roles
programming logic engine that provides the • Sequence of Event (SOE) within UR devices. The new and advanced
ability to create customized protection and - 1024 time stamped events access functions allow users to configure up
control schemes, minimizing the need and to five roles for up to eight configurable users
• Oscillography
associated costs of auxiliary components with independent passwords. The standard
and wiring. Using FlexLogic, the G60 can - 64 digital & up to 40 analog channels
“Remote Authentication Dial In User Service”
be programmed to provide the required - Events up to 45s in length
(Radius) is used for authentication.
tripping logic along with custom scheme • Data Logger and Disturbance Recording
logic for generator breaker control (including - 16 channels up to 1 sample/cycle/ Event Recorder (Syslog for SEM)
interlocking with external synchronizers), channel Capture all cyber security related events
transfer tripping schemes for remote breakers • Fault Reports within a SOE element (login, logout, invalid
and dynamic setting group changes. - Powerful summary report of pre-fault password attempts, remote/local access,
and fault values user in session, settings change, FW
Scalable Hardware
update, etc), and then serve and classify
The G60 is available with a multitude data by security level using standard
The very high sampling rate and large
of I/O configurations to suit the most Syslog data format . This will enable
amount of storage space available for
demanding application needs. The integration with established SEM (Security
data recording in the G60 can eliminate
expandable modular design allows for Event Management) systems.
the need for installing costly stand-alone
easy configuration and future upgrades.
recording equipment.
• Multiple CT/VT configurations allow for Communications
the implementation of many different Advanced Device Health
The G60 provides advanced commun-
schemes, including concurrent split- Diagnostics
ications technologies for remote data and
phase and differential protection
The G60 performs comprehensive device engineering access, making it easy and
• Flexible, modular I/O covering a broad health diagnostic tests at startup and flexible to use and integrate into new and
range of input signals and tripping continuously during run-time to test its own existing infrastructures. Direct support for
schemes major functions and critical hardware. These fiber optic Ethernet provides high-bandwidth
• Types of digital outputs include trip- diagnostic tests monitor for conditions that communications allowing for low-latency
rated Form-A and Solid State Relay (SSR) could impact security and availability of controls and high-speed file transfers of
mechanically latching, and Form-C outputs protection, and present device status via
88 GEDigitalEnergy.com
G60 Generator Protection System
relay fault and event record information. experience with UCA 2.0. • Communication with up to 16 UR relays
Generator Protection
The available three independent Ethernet • Replace expensive copper wiring in single or redundant rings rather than
ports, redundant Ethernet option and between devices with direct transfer of strictly limited to simplistic point-to-point
the embedded managed Ethernet switch data using GOOSE messaging configurations between two devices
provide the means to create fault tolerant
• Configure GE systems based on • Connect to standard DS0 channel
communication architectures in an easy,
IEC 61850 and also monitor and banks through standard RS422, G.703
cost-effective manner without the need
troubleshoot them in real-time with or IEEE C37.94 interfaces or via direct
for intermediary communication hardware.
EnerVista Viewpoint Engineer fiber optic connections
The G60 supports the most popular industry
• Multicast IEEE C37.118 synchrophasor • No external or handheld tester required
standard protocols enabling easy, direct
data between PMU and PDC devices to provide channel diagnostic information
integration into DCS and SCADA systems.
using IEC 61850-90-5
LAN Redundancy
• IEC 61850 with 61850-90-5 support Direct I/O Messaging Substation LAN redundancy has been
• DNP 3.0
Direct I/O allows for the sharing of traditionally accomplished by reconfiguring
• Ethernet Global Data (EGD)
high-speed digital information between the active network topology in case of failure.
• IEC 60870-5-103 and IEC 60870-5-104
multiple UR relays via direct back-to-back Regardless of the type of LAN architecture
• IEEE 1588 for time synchronization
connections or multiplexed through a (tree, mesh, etc), reconfiguring the active
• Modbus RTU, Modbus TCP/IP
standard DS0 multiplexer channel bank. LAN requires time to switchover, during
• PRP as per IEC 62439-3
Regardless of the connection method, which the LAN is unavailable. UR devices
direct I/O provides continuous real- deliver redundancy as specified by PRP-IEC
Interoperability with Embedded
time channel monitoring that supplies 62439-3, which eliminates the dependency
IEC 61850
diagnostics information on channel health. on LAN reconfiguration and the associated
Use the G60 with integrated IEC 61850 switchover time. The UR becomes a dual
to lower costs associated with generator Direct I/O provides superior relay-to-relay attached node that transmits data packets
protection, control and automation. GE communications that can be used in over both main and redundant networks
Digital Energy’s leadership in IEC 61850 advanced interlocking, generation rejection simultaneously, so in case of failure, one
comes from thousands of installed devices and other special protection schemes. of the data packets will reach the receiving
and follows on extensive development device with no time delay.
GEDigitalEnergy.com 89
G60 Generator Protection System
The internal operation of the G60 elements, logic, and outputs can be monitored Create G60 setting file templates to ensure critical settings are not altered.
in real-time to simplify commissioning and troubleshooting procedures.
90 GEDigitalEnergy.com
G60 Generator Protection System
Generator Protection
The G60 front panel provides extensive
local HMI capabilities. The local display
is used for monitoring, status messaging, Multi-Language
fault diagnosis, and device configuration. Display
User-configurable messages that combine • English
• Russian
text with live data can be displayed when
• French
user-defined conditions are met. • Chinese
• Turkish
• German
User-Programmable Pushbuttons
Typical Wiring
A
B
C
R
F 5a
F 6a
F 7a
F 5c
F 6c
F 7c
M1b
M2a
M2b
M3a
M3b
M4a
M1a
M4b
M1c
M2c
M3c
M4c
F5a
F6a
F7a
F8a
F1a
F1b
F2a
F2b
F3a
F3b
F4a
F4b
F5c
F6c
F7c
F8c
F1c
F2c
F3c
F4c
VX
VB
VC
VB
VC
VA
VA
VX
IG5
IG1
VB
VC
VB
VC
IG
IG5
IG1
VA
VA
IG
IA5
IA1
IB
IC
IA
IC5
IC1
IA5
IA1
IB5
IB1
IB
IC
IA
IC5
IC1
IB5
IB1
H5a 6G I H1a TC 1
H5c H1
V
H1b
H6a H1c
H6c I H2a
H5b H2
V
H2b
H2c
H7a I H3a
H7c TC 2
H3
V
H3b
H8a
H3c
H8c I H4a
H7b
H4
V
H4b
H8b SURGE H4c
B1b Multilin
CRITICAL
1
B1a FAILURE
DC
B2b
B3a G60 GENERATOR MANAGEMENT RELAY
B3b OUTPUT
B5b HI
CONTROL
B6b LO POWER
B6a
RS-232
B8a SURGE (front)
B8b FILTER
DB-9
* Optic
Fibre Tx1 10BaseFL
NORMAL
Rx1
Shielded 10BaseT
Remote
Device D1a
RS485
D2a
D3a com
D4b
D4a IRIG-B
Input
Co-axial BNC
IRIG-B
Co-axial BNC Output
CONNECTOR
minimum
X W V U T S R P N M L K J H G F D B
GROUND 8 6 8 9 1
BUS
7 SGND
3 RXD
2 TXD
outputs Supply
20
22
8
5
4
1
2
3
4
7
8
9
5
6
CONNECTOR
UR
1
2
3
4
7
8
9
5
6
G60-H00-HCH-F8F-H6G-M8H-PXX-UXX-WXX
SGND
RXD
TXD
GEDigitalEnergy.com 91
G60 Generator Protection System
Ordering
Generator Protection
Ordering Notes: 1 . To view all available model order codes, options for G60 or to order the UR Classic Front Panel, please visit GE’s On-Line Store at http://store.gedigitalenergy.com/viewprod.asp?model=G60
2. Redundant power supply only available in horizontal unit. If redundant is chosen, must be same type. Maximum 2 per chassis
• Viewpoint Maintenance VPM-1 GE reserves the right to make changes to specifications of products described at any time without
notice and without obligation to notify any person of such changes.
• Viewpoint Monitoring IEC 61850 VP-1-61850
Copyright 2013, General Electric Company.
GEA-12587G(E)
92 GEDigitalEnergy.com English
131108