TECHNICAL SPECIFICATION
Peewee eeer)
“Tvee-phase reccser, electronically controled, manuactued and tested In accordance with IEEE C7.60-2003 (Coopex Power Series)
RRoclosex Pact Number: KN36 4ABBUC,CPRP1 S6D1.SYXANOKE teliecloantion
ees
Nominal Votage (KV).
[Maximum Vottage (kV)
[Basic Impulse Level, Wave 1.2x 60 us (kV)
[Power Frequency Withstand, Dry, Over 1 Minute (kV)
[Power Frequency Withstand, Wel, Over 10 Seconds (kV)
[Radio Novse Liat (uV)
[Rated Continuous Cunent (A)
[Short Grcut Ourent, Symmetical (KA / 1 second)
Frequency (2)
[Making Current, Asymmetrical Peak (A)
\Cable Curent Load (A)
Heater Voltage
Weight (ka)
\Creepage Distance (mm) - Terminal to Terninal
\Creapage Distance (mm) - Lower Terminal to Ground / Earth
[Minimum Nechanical Operation without Maintenance
(Operation Cicle 0-0,38-00-1,85-00-1,86-0L.
[Dimensions (mm) See the Relerence Drawings
[Measure A (mm) 114
[Measure B (mm) 946
Measure C (mm) 63
eee
3 Vacuuminterupting Pole Assembiy with Epox slation|
Intemal Curent Sensors (Installed in the Source Side Bushing) with Ratio 1000:1 A
| Close Macharism
Data Piste
Ling Leas
Open | Close Contact Position Indicator
SS
IRecloser Type
[Supporting Sucre
hype of instalation
[Recloser Tank Material
Tank Finishing
Hecminal Connector
IRecloser Ground Connector
tame Voltage Sensor
[Extemal Votiage Sensor
/Aurliry Contacts
[Accessories Mechanical Operation Counter
[Phase ientifcaton Not Included
[Souree/ Load identification Not Include
[Adsitonal Structure
otal Transformer
‘Surge Arresters|
Labels Language
ree
$200-42-1 (nstalaion ard Operaten istuctons}
Not Included
Not Include
Not Includes
EnglishMICROPROCESSOR-BASED RECLOSER CONTROL TYPE F6P
Recloser miroprocessoc-based conta, manufacled and tested in accordance wih EEE C37,60-2008™ (Cooper Power Series)
(Control Part Number: EP. CCI EMI 1XHXBXO7 XRIKXXKOTE. REA
oo
“Toe: Phase Overcurent Protection 50 St
Fast Trp Ossable
‘Ground Protection 50/ SIN + 51S Hot Line Tag
Negative Sequence Protection 501 510 Fault Location
Drectional Overcurrent Protection 67 / 67N ‘Sequence Coordination
Under / Oveneitage Protection 27 / 59 Programmable Reset
Under / Overrequency Protection B1UiO Breaker Fall
‘Automatic Reeling 79 Target LEDs
Syne-chack 25
(Cals Loa Pickup / rush Curent
gh Current Trp / Block
Lage Workbench ™
‘Keyboard for View | Moly Parameters
ial Dip
‘Cure Modifiers 'ANSI Gunes (inerse, Very Inerse, and Extremely ierse)
TOC Editor 38 Kyle Cures
TEC Curves (verse, Very verse, and Extremely inorse
Deni
Instantaneous / Demand Curent
Instantaneous / Demand Voltage
Real, Reactive and Apparent Power, Single and Throe Phase
Instantaneous Power Factor
Instantaneous Frequency
Event Register
Operation Counters
Harmonics up to 15
Interactive Oseloga
‘Minimum Phase Pickup
Minimum Ground Pickup
SEF Pickup
Reclsing ntenal
Reset itera
‘Operations to Lockout
Sequence Coorinaton Ope
pen
‘Control Power Supply: 220 Vac
‘Auxiliary Supply: 220 Vac
Backup Battery: 02 Balterios (12 Vde + 12 Vdo-12 Ah)
‘Control Cabinet Type: Cabinet with Front and Rear Access:
Material of Control Cabinet: Mid Stel
Fishing: Painted According to ETA.005 - MUNSELL NB.5 Thickness 150 um
‘Cabinet Ground Connector: 10 - 70 m=
Protection Degree: [P53
‘Control Cabinet Accessories: Not included
‘Outlet: 01 American Standard "Type 8" Plug
‘Other Accessories: Not Included
Radio Support 28/12 Ve Converter + Radio Support
‘Auxiary Contacts: Not lnluded
‘Contrel Cable Langit (m7
‘Standard VO: 03 Inputs /05 Outputs Programmable (9290 Vac 7-285 Vac)
‘Asétional VO: Not Included
‘Standard Communication Pots
‘1x RS-232 Frent- Local Configuration
‘x RS-232 Rear - Ramote Superision
[Adional Communication Por Ethamet RIS + RLS
Connector Camertr: Not Included
Communication Protocls: DNP 3.0 MODBUS (Serial) CPS-2179 / EC-8705-101 /EC-870-5-104
Communication Accesseria: Not included
Software Version: Prowew 5:0
Labels Language: English
'$280-70-3 (Cont)
$280-70-21 (F6 Control Programming Guide)