~m~ oesignation: E 90 - 99

Standard Test Method for


Laboratory Measurement of Airborne Sound Transmission
Loss of BuildingPartitions and Elements1
This standard is issued under the fixed designation E 90; the number immediately following the designation indicates the year of original
adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of Iast reapproval. A superscript
epsilon (E) indicates an editorial change since the last revision or reapproval.

INTRODUCTION

This test method is part of a set for evaluating the sound-insulating properties of building elements.
lt is designed to measure the transmission of sound through a partition or partition element in a
Iaboratory. Others in the set cover the measurement of sound isolation in buildings (Test Method
E 336), the laboratory measurement of impact sound transmission through ftoors (Test Method E 492),
the measurement of impact sound transmission in buildings (Test Method E 1007), the measurement
of sound transmission through building facades and facade elements (Guide E 966), the measurement
of sound transmission through a common plenum between two rooms (Test Method E 1414), a quick
method for the determination of airbome sound isolation in multiunit buildings (Practice E 597), and
the measurement of sound transmission through door panels and systems (Test Method E 1408).

l. Scope Airbome Sound Isolation for Use in Multiunit Building


1.1 This test method covers the laboratory measurement of Specifications2
airbome sound transmission loss of building partitions such as E 966 Guide for Field Measurement of Airbome Sound
walls of all kinds, operable partitions, floor-ceiling assemblies, Insulation of Building Facades and Facade Elements
doors, windows, roofs, panels, and other space-dividing ele- E 1007 Test Method for Field Measurement of Tapping
ments. Machine Impact Sound Transmission through Floor-
1.2 Laboratory Accreditation-A procedure for accrediting Ceiling Assemblies and Associated Support Structures
a laboratory for performing this test method is given in Annex E 1289 Specification for Reference Specimen for Sound
A3. Transmission Loss2
1.3 This standard does not purport to address all of the E 1332 Classi:fication for Determination of Outdoor-Indoor
safety concerns, if any, associated with its use. Jt is the Transmission Class2
responsibility of the user of this standard to establish appro- E 1375 Test Method for Measuring the Interzone Attenua-
priate safety and health practices and determine the applica- tion of Fumiture Panels Used as Acoustical Barriers
bility of regulatory limitattons prior to use. E 1408 Test Method for Laboratory Measurement of the
Sound Transmission Loss of Door Panels and Door Sys-
2. Referenced Documents tems"
2.1 ASTM Standards: E 1414 Test Method for Airbome Sound Attenuation Be-
C 634 Terminology Relating to Environmental Acoustics tween Rooms Sharing a Common Ceiling Plenunr
E 336 Test Method for Measurement of Airbome Sound 2.2 ANSI Standards:
lnsulation in Buildings' S 1.4 Specification for Sound-Level Meters'
E 413 Classification for Rating Sound Insulatiorí S 1.6 Standard Preferred Frequencies, Frequency Levels,
E 492 Test Method for Laboratory Measurement of Impact and Band Numbers for Acoustical Measurements'
Sound Transmission Through Floor-Ceiling Assemblies S 1.1 O Pressure Calibration of Laboratory Standard Pressure
U sing the Tapping Method' Microphones'
E 597 Practice for Determining a Single-Number Rating of S 1.11 Specification for Octave-Band and Fractional-
Octave-Band Analog and Digital Filters'
S 12.31 Precision Methods for the Determination of Sound
Power Levels of Broad-Band Noise Sources in Reverbera-
1
This test method is under the jurisdiction of ASTM Committee E-33 on
tion Rooms3
Environmental Acoustics and is the direct responsibility of Subcommittee E33.03 on
Sound Transmission.
Current edition approved June 10, 1999. Published September 1999. Originally
3
published as E 90 - 55. Last previous edition E 90 - 97. Available from the American National Standards Institute, 11 W. 42nd St., 13th
2
Annual Book of ASTM Standards , Vol 04.06. Floor, New York, NY 10036.

Copyright © ASTM, 100 Barr Harbor Orive, West Conshohocken, PA 19428-2959, United States.
~filt} E90
2.3 ISO Standards: NoTE 2-Sound absorption is operationally defined by the Sabine
ISO 717 Rating of Sound lnsulation for Dwellings decay rate equation (see Eq 9).
ISO 3741 Acoustics-Determination of Sound Power 4. Summary of Test Method
Level of Noise Sources-Precision Methods for Broad-
Band Sources in Reverberation Rooms' 4.1 Two adjacent reverberation rooms are arranged with an
opening between them in which the test partition is installed.
3. Terminology Care is taken that the only significant sound transmission path
3.1 Definitions of the acoustical terms used in this test between rooms is by way of the test partition. An approxi-
method are given in Terminology C 634. A few definitions of mately diffuse sound field is produced in one room, the source
special relevance are repeated here for convenience only. room. Sound incident on the test partition causes it to vibrate
3 .1.1 dijfuse sound jield-the sound in a region where the and create a sound field in the second room, the receiving
sound intensity is the same in ali directions and at every point. room. The space- and time-averaged sound pressure levels in
3 .1.2 direct sound field-the sound that arrives directly the two rooms are determined (see Fig. 1). In addition, with the
from a source without refiection. test specimen in place, the sound absorption in the receiving
3.1.3 flanking transmission-transmission of sound from room is determined. The sound pressure levels in the two
the source to a receiving location by a path other than that rooms, the sound absorption in the receiving room and the area
under consideration-in this case other than through the test of the specimen are used to calculate transmission loss as
partition. shown in Section 12. Because transmission loss is a function of
3.1.4 reverberation room-a room so designed that the frequency, measurements are made in a series of frequency
reverberant sound field closely approximates a diffuse sound bands.
field, both in the steady state when the sound source is on, and 4.2 Additional procedures that may be followed when
during decay after the source of sound has stopped. testing doors are given in Test Method E 1408.
3 .1.5 reverberant sound field-the sound in an enclosed or
partially enclosed space that has been refiected repeatedly or 5. Significance and Use
continuously from the boundaries. · 5 .1 Sound transmission loss as defined in 3 .1.7, refers to the
3 .1.6 sound transmission coefficient, T ( 'dimensionless)-of response of specimens exposed to a diffuse incident sound
a partition, in a specified frequency band, the fraction of the field, and this is the test condition approached by this labora-
airbome sound power incident on the partition that is transmit- tory test method. The test results are therefore most directly
ted by the partition and radiated on the other side. (Note that, relevant to the performance of similar specimens exposed to
unless qualified, this term denotes the sound transmission similar sound fields. They provide, however, a useful general
coe:fficient obtained when the specimen is exposed to a diffuse measure of performance for the variety of sound fields to which
sound field as approximated, for example, in reverberation a partition or element may typically be exposed.
rooms meeting the requirements of this test method.) 5.2 This test method is not intended for field tests. Field
3.1.7 sound transmission loss, Tb-of a partition, in a tests should be performed according to Test Method E 336.
specified frequency band, ten times the common logarithm of
the reciprocal of the sound transmission coe:fficient. The
quantity so obtained is expressed in decibels.
3. l. 7 .1 F or the purposes of this test method, transmission
loss is operationally defined as the difference in decibels
between the average sound pressure levels in the reverberant
source and receiving rooms, plus ten times the common •

· ·¡·.
logarithm of the ratio of the area of the common partition to the ~.
sound absorption in the receiving room (see Eq 12).
··· ... ·· .... .::
Nora 1-Sound transmission coefficient and sound transmission loss •

·¡-
are related by either of the two equations:
TL = 10 logf l/r) (1)
T = 10-TUIO (2) / \
MOVING FIXED
3.2 noise reduction, NR-in sound transmission measure- MICROPHONE TEST MICROPHONES
ments, in a specified frequency band, the difference between SPECIMEN
the average sound pressure levels measured in two enclosed FIG. 1 lllustration showing conceptual arrangement of a wall
sound transmission loss suite. This figure is not meant to be a
spaces or rooms due to one or more sound sources in one of design guide but is for illustrative purposes only. As an example,
them. the room on the right has fixed microphones to measure average
3.3 Definitions of Terms Speci.fic to This Standard: sound pressure level; the room on the left has a continuously
3.3.1 sound absorption, A, [i3]--0f a room, in a specified moving microphone to rneasure average sound pressure level.
frequency band, the hypothetical area of a totally absorbing Usually both rooms will have the same microphone system. The
sound sources (loudspeakers) in the rooms generate the
surface without diffraction effects which, if it were the only incident sound fields for the measurement of level differences or
absorbing element in the room, would give the same sound of sound decay rates. As shown, either room could serve as
decay rate as the room under consideration. source or receiving room.

2
~t E90
6. Test Rooms area of the panels is 5 kg/rrr' (1 lb/ft2) for operation down to
6.1 Room Size and Shape--To produce an acceptable ap- 100 Hz. (Panels of plywood or particleboard measuring 1.2
X 2.4 m are often used.) To be effective at lower frequencies,
proximation to the assumed diffuse sound fields, especially in
the lowest test frequency band, the sound fields in the rooms the size and mass of diffusing panels should be increased in
must satisfy the requirements in Annex A2. They must also proportion to the wavelength. It is likely to be impractical to
satisfy any of the following requirements that are mandatory. use very large diffusing panels at very low frequencies; they
might make the room behave like a number of coupled spaces
6.1.1 Minimum Volume--The volume of the source and
rather than a single room, and it might be difficult to position
receiving rooms must each be 50 rrf (1765 ft3) or more.
microphones.
6.2 Room Absorption-The sound absorption in each of the
6.3.2 Rotating or Moving Diffusers-One or more rotating
rooms should be made as low as possible to achieve the best
or moving panels set at oblique angles to the room surfaces
possible simulation of the ideal diffuse field condition and to
may be installed in either or both rooms. The recommendations
keep the region dominated by the direct field (of the so urce or
for weight and size of the panels given in 6.3 .1 for fixed
of the test specimen) as small as possible (see 8.5). At each
diffusing panels apply also to rotating or moving diffusers. The
frequency, the sound absorption for each room (as fumished
panels should be large enough that during motion they produce
with diffusers) should be no greater than:
a significant variation in the sound field, yet small enough that
(3) they do not effectively partition the room at any point in their
movement.
where:
V = room volume, and NoTE 3-Moving diffusers can generate mechanical noise or wind and
A = sound absorption of the room. wind noise in microphones. This increased background noise may make
measurements difficult in sorne cases.
When V is expressed in cubic metres, A is in square metres.
When V is expressed in cubic feet, A is in sabin (square feet). 6.4 Flanking Transmissiorr-The test rooms shall be con-
At low frequencies somewhat higher room absorption may be structed and arranged to minimize the possibility of transmis-
desirable to accommodate other test requirements (for ex- sion by paths other than that through the test partition. Sound
ample, ANSI Sl2.31, ISO 3741). Sound absorption in the room pressure levels produced by such ft.anking transmission should
is usually increased at frequencies below/ = k2/V113(k2 is an be at least 1 O dB lower than the sound radiated into the
empirical constant equal to 2000 mis when V is in cubic metres, receiving room by the test partition. Supporting one or both
and equal to 6562 ft/s when V is in cubic feet). In any case, the rooms on vibration isolators (resilient materials or springs) is a
sound absorption should be no greater than three times the common method of reducing ft.anking transmission. Structural
value given by Eq 3. F or frequencies abo ve 2000 Hz, atmo- discontinuities are recommended between the source-room and
spheric absorption may make it impossible to avoid a slightly the test specimen and between the receiving room and the test
higher value than that given in Eq 3. specimen to minimize ft.anking transmission between them.
6.2.1 To minimize errors related to atmospheric absorption, NoTE 4--lf the specimen is rigidly connected to the source-room
the temperature and humidity in the receiving room should be structure, there is sorne risk that, in addition to the incident airborne
kept the same during the noise reduction and absorption sound, sound power may enter the specimen at the edges because of
measurements. For monitoring purposes, temperature and hu- vibration ofthe source-roorn structure. Similarly, ifthe specimen is rigidly
midity shall be measured and recorded at least once during connected to the receiving room structure, sound power may flow from the
each test. specimen to the walls of the receiving room and be radiated from them.
6.3 Methods to Reduce the Variability of the Sound Fields- 6.4.1 The limit on specimen transmission loss measurement
Meeting the requirements of 6.1 and 6.2 can be difficult in the due to flanking transmission must be investigated as follows:
lower test bands where results are likely to depend critically on 6.4.1.1 In the test opening, build a partition expected to have
arbitrary features of the test geometry such as positioning of high transmission loss.
the sound sources and individual microphones. Spatial varia- 6.4.1.2 Measure the transmission losses following this test
tions in sound pressure level and decay rate may be reduced by method.
one or both of the following types of diffusing panels. The 6.4.1.3 Increase the expected transmission losses by making
recommendations that follow are only included as guidelines. a substantial improvement to the test partition, for example, by
Satisfaction of the requirements of Annex A2 for confidence adding a heavy shielding structure in front of the test partition.
intervals is the primary criterion, not the size or number of 6.4.1.4 Measure the transmission loss again.
diffusing panels. 6.4.1.5 Repeat steps 6.4.1.3 and 6.4.1.4 until significant
6.3.1 Stationary Diffusing Panels-It is recommended that additions to the test partition no longer significantly increase
each test room be fitted with a set of about 3 to 6 diffusing the measured transmission loss. The sound transmission loss
panels, suspended in random orientations throughout the room measured can then be ascribed to ft.anking paths. The transmis-
space. The appropriate number, distribution, and orientation of sion loss values obtained represent the limit that can be
panels should be determined experimentally by checking to see measured by the facility. Unless steps are taken to eliminate
if spatial variances of sound pressure level or decay rate are them, these paths always exist and will reduce the measured
reduced. Lateral panel dimensions should be about 1/2 to 1 transmission loss for partitions whose inherent transmission
wave-length of the sound at the lowest test band, for example, loss values are within 1 O dB of the flanking limit. The sound
about 1.2 to 2.5 m. The recommended mínimum mass per unit power transmission along a particular suspected flanking path

3
~u~ E 90
may be decreased to determine if the measured transmission minimum aging period should be the interval beyond which no
loss increases. This may be done by temporarily adding significant change is observed.
shielding structures in front of the surfaces that are suspected 7 .2.1.1 To decide whether a change is significant, laboratory
of radiating unwanted sound. operators must determine the repeatability of their test proce-
6.4.2 A potential fianking path is through the perimeter of dures. This is done by repeating the complete test procedure
the partition or the mounting frame (1).4 lt is therefore several times without disturbing the specimen or other appa-
important that the partition mounting arrangement used in ratus and with as little time as possible between repeat
determining the transmission loss limit be the same as is used measurements. From the set of transmission loss measure-
for routine testing. ments, calculate the standard deviation of transmission loss at
6.4.3 An extraneous signal similar in effect to fianking each frequency. Standard statistical techniques(2) may then be
transmission may be produced by electrical "cross-talk" be- used to decide if a test differs significantly from a previous test.
tween the electrical system driving the sound source or other In many cases, a visual comparison of two results will be
devices and the receiving mícrophone systems. This possibility enough to verify that there is no significant difference between
should be checked, whenever systems are changed, by mea- two results.
suring the residual signals when the loudspeaker is replaced by 7.3 Testing of Specimens Smaller Than Test Opening-
an equivalent electrical load or by replacing the microphone When the area of the test specimen is smaller than that of the
cartridge with a dummy load. normal test opening, the area of the test opening must be
6.4.4 Laboratories must keep records of data collected to reduced using additional construction. This additional con-
establish the fianking limit of their facilities. struction, or filler wall, should be designed to transmit as little
6.4.5 When the transmission loss measured for a test speci- sound as possible. Nevertheless, a portian ofthe sound may be
men in a particular frequency band is within 1 O dB of the transmitted by way of the filler wall (see Fig. 2). Sound
flanking limit established for the Iaboratory, the transmission transmission through the composite wall can be represented by:
loss value must be clearly identified in the test report as being -r,Sc = T ~s + T¡S¡ (4)
potentially limíted by the laboratory. The true value may be
higher than that measured. or
(5)
7. Test Specimens
where:
7 .1 Size and Mo1:1ntin'g-Anytest specimen that is to typify
a wall or fioor shall be large enough to include all the essential
se area of composite construction ~e = S s + S~,
SS area of test specimen,
constructional elements in their normal size, and in a propor- sf area of filler element,
tion typical of actual use. The mínimum dimension (excluding Te transmission coefficient of composite construction,
thickness) shall be 2.4 m, except that specimens of doors, office Ts transmission coefficient of test specimen, and
screens, and other smaller building elements shall be their Tf transmission coefficient of filler element.
customary size. Preformed panel structures should include at
NoTE 5-The above expressions assume that the two parts of the
least two complete modules (panels plus edge mounting composite construction react to the sound field independently of each
elements ), although single panels can be tested. In ali cases the other.
test specimen shall be installed in a manner similar to actual
construction, with a careful simulation of normal constraint Two general procedures may be used to <leal with this
situation:
and sealing conditions at the perimeter and at joints within the
field of the specimen. Detailed procedures for particular types · 7.3.l Build and Measure a Complete Filler WaU--This is
of building separation elements are recommended in Annex
Test Filler Additional Sound
Al.
specimen wall barrier absorbing
7 .2 Aging of Specimens-Test specimens that incorporate
materials for which there is a curing process (for example \ panels material
adhesives, plasters, concrete, mortar, damping compound)
shall age for a sufficient interval before testing. Manufacturers
1\
may supply information about curing times for their producís.
Aging periods for certain common materials are given in
Annex Al.
7.2.1 For materials whose aging characteristics are not
known, tests shall be repeated over a reasonable time on at
least one specimen to determine an appropriate aging period. A
suggested procedure is to test at intervals in the series 1, 2, 4,
7, 14, and 28 days from the date of construction, until no
signíficant change is observed between successíve tests. The FRONTVIEW SIDE
VIEW
FIG. 2 lllustration showing filler wall and test specimenthat is
smaller than the test opening. This figure is not meant to be a
4
The boldface numbers in parentheses refer to the Iist of references at the end of design guide but is for illustrative purposes only. The side view
this test method. shows the application of additional panels as discussed in 7.3.2.

4
~ITT~ E 90
the preferred method and is usually most convenient when the may require other procedures. It is the responsibility of the
specimen area is smaller than the area of the filler wall. Based testing laboratory to show that transmission through filler walls
on experience and knowledge of the test specimen construc- is negligible.
tion, build a filler wall that is expected to transmit a negligible 7.3 .4 When a small specimen such as a <loor or window
amount of sound relative to that through the specimen. The assembly is mounted in a filler wall, the distance from the
filler wall should be built with support structures for the test surface of the filler wall to the specimen surface should be
specimen already in place. The opening for the specimen shall small compared to the lateral dimensions of the specimen.
be closed and finished with the same construction as the rest of 7.3.5 When a filler wall is used, ensure that sound is not
the filler wall, except as noted in 7.3 .2. transmitted through the structure where the filler wall and the
7.3.1.1 Following the procedures in this test method, mea- test specimen join. Such fianking can occur when the filler wall
sure the sound transmission losses for this complete filler wall. is thicker than the test specimen.
The transmission coefficients, T¡; for the filler wall can be 7.4 O.ffice Screens-The mínimum area of an o:ffice screen
calculated from the corresponding transmission losses using Eq specimen shall be 2.3 m2 (25 fr'), Testing an o:ffice screen
2. according to this test method is only appropriate when the
7. 3. l.2 Remo ve the part of the filler wall surfaces covering property of interest is sound transmission through the main
the opening for the specimen and install the specimen. Make body of the screen. Screens that incorporate electrical raceways
no other significant changes to the filler wall structure. may allow sound to pass through easily in this region. Such
7.3.1.3 Following the procedures in this test method, mea- parts of an office screen should be included as part of the
sure the sound transmission losses for this composite wall. The specimen. For a complete test of the screen as a barrier,
transmission coe:fficients,T0 can be calculated from the corre- including the e:ffects of di:ffraction and leakage, Test Method
sponding transmission losses using Eq 2. The area used in E 1375 is recommended.
calculation is the combined area of the specimen and the filler 7 .5 Operable Door Systems-Measurements may be in
wall, s; accordance with Test Method E 1408 to evaluate <loor systems
7 .3 .1.4 At each test frequency calculate the di:fference: 10 in the operable and fully sealed state, and to measure the force
log(TeS'c) - 10 log(T_,Pf). required to operate the <loor.
7 .3 .1.5 If the di:fference is more than 15 dB, calculate Ts 8. Test Signal Sound Sources
from Eq 5 ignoring the term T_,5'.f
8.1 Signa! Spectrum--The sound signals used for these tests
7.3.1.6 Ifthe di:fference is between 6 and 15 dB, calculater s
shall be random noise having a continuous spectrum within
using Eq 5. This corrects for transmission through the filler
each test frequency band.
wall. Note in the test report where such corrections have been
8.2 Sound Sources-Sound is usually generated in the
made.
rooms using loudspeaker systems although other sources are
7.3.1.7 If the di:fference is less than 6 dB, reliable corree-
acceptable if they satisfy the requirements of this test method.
tions cannot be made. Calculate-r, from Eq 5 ignoring the term
8.2.1 Sources should preferably be ornnidirectional at ali
T_,5' .f Multiply the value obtained by 0.75 and then use Eq 1 to
measurement frequencies to excite the sound field in the room
calculate a lower limit for the transmission loss of the test
as uniformly as possible. Using separate loudspeakers for high
specimen. (This is equivalent to limiting the di:fference to 6
and low frequencies will make the system more ornnidirec-
dB.) Any values of transmission loss that are limited in this
tional. The direct field from the loudspeaker system can be
way must be clearly marked as such in the test report.
further reduced by aiming the loudspeakers into comers of the
7.3.2 Use Additional Structures to Reduce Transmission-: room. Laboratory operators may also find that this orientation
Some test specimens fill a large fraction of the test opening increases the low frequency sound pressure levels in the room.
leaving only a small area for a filler wall. In such cases, it is not Another approach to obtaining an omnidirectional speaker
always convenient to construct and test a complete filler wall system is to use an array of loudspeakers mounted on the faces
and the transmission coe:fficientof the filler wall is not known. of a dodecahedron.
To demonstrate that transmission through the filler wall is 8.2.2 Orientation of Loudspeakers.
negligible, proceed as follows: 8.3 Mu/tiple Sound Source Positions-« Measured values of
7.3.2.1 Measure the sound transmission loss for the com- sound transmission loss, especially at low frequencies, may
posite assembly. change significantly when a loudspeaker position is changed in
7.3.2.2 Cover each face of the filler wall with sound the source room. Where this occurs, sound transmission loss
absorbing material at least 50 mm (2 in.) thick. Cover the should be measured for severa! loudspeaker positions and the
sound absorbing material with barrier panels weighing at least values averaged to provide a less biased result. Sound sources
8 kg/m2 (1.6 lb/ft 2) that are not rigidly attached to the filler can be used either in sequence or simultaneously. If they are
wall (see Fig. 2). Normal good practices should be followed for used simultaneously, they must be driven by separate random
mounting and sealing. noise generators and amplifiers. Multiple, uncorrelated sound
7.3.2.3 Remeasure the sound transmission loss for the sources have also been found to reduce the spatial variance of
composite assembly. sound pressure level in reverberation rooms.
7.3.2.4 If changes are insignificant, it may be assumed that 8.4 Location of Sound Sources-Sound source positions
transmission through the filler wall is negligible. shall be selected to minimize spatial fluctuations in the
7 .3.3 Other combinations of test specimen and filler wall reverberant field in the source room; sources in trihedral

5
~t E90
corners of the room excite room modes more effectively. procedure establishes a relationship between electrical output
8.5 Direct Field of Sound Source(s)-The direct sound field and sound pressure level at the microphone. Ali subsequent
from the source(s) at the test partition, or the nearest micro- electrical outputs can thus be converted to sound pressure
phone shall be at least 1 O dB below the sound pressure level of levels at the microphone, taking into account the filter response
the reverberant field. The distance between the source(s) and and any changes of gain in the system.
the partition or microphones required to achieve this condition 9 .4 Microphone Positions=Y or rooms and test signals that
will depend on the room properties, the number and orientation conform to this test method, the sound pressure level will be
of sound sources and frequency. Verify that the distances nearly the same at ali positions within a restricted space
between a single source and the microphones and test partition delineated in 9.4.1-9.4.4. Greater variance in measured data
satisfy the relationship: will be found at lower frequencies. Nevertheless, variations in
the level of the reverberant sound field are still significant and
(6) measurements must be made at severa} positions in each room
to sample adequately the sound field. A moving microphone is
where: one convenient way of doing this. The system adopted for the
A = sound absorption in the room, and measurement of average sound pressure levels must produce
r = distance from the source. results that meet the requirements of Annex A2. For all
When A is in square metres, r is in metres. When A is in microphone systems, microphones must be located according
sabins (square feet), r is in feet. to the following restrictions:
NOTE 6--This expression is for a point source and is obtained by
9.4.1 The shortest distance from any microphone position to
determining the point where the sound pressure leve} of the direct field is any major extended surface shall be greater than 1 m. The same
1 O dB below the sound pressure leve! of the reverberant field (3). The limit applies relative to any fixed diffuser surface (excluding
expression is thus not strictly accurate for Joudspeaker systems especially edges) and relative to any possible position of a rotating or
at high frequencies where the directivity index is greater than unity. moving diffuser.
Neither is it accurate when multiple sources are used, but, for the purposes 9.4.2 For this test method, stationary microphone positions
of this test method, it is deemed acceptable.
shall be at least 1.5 m apart. Rotating microphones shall trace
9. Microphone Requirements a círcle at least 1.2 m in radius.

9 .1 Microphones are used to measure average sound pres- NOTE 7-lf estimates of the confidence interval of average sound
pressure leve! are to be reliable, microphone positions should be suffi-
sure levels in the rooms and sound decay rates in the receiving
ciently far apart to provide independent samples of the sound field. For
room. Various systems of data collection and processing are fixed microphones, this requires that they be spaced at least half a
possible, ranging from a single microphone moving continu- wavelength apart (4). For a moving microphone see Annex A2.
ously or placed in sequence at severa} measurement positions
9.4.3 In the source room, no microphone shall be so close to
to several microphones making símultaneous measurements
any source as to be affected signíficantly by its direct field (see
(see Fig. 1 for two examples). The measurement process must
8.5).
account for level ftuctuations caused by spatial and temporal
9.4.4 In the receiving room, microphones shall be more than
variations. Microphone sensitivity and moving diffusers must
1.5 m from the test partition. This is to reduce the inftuence of
also be accounted for.
the direct field of the specimen.
9.2 Microphone Electrical Requirements= Use micro-
9.5 Number of Stationary Microphone Positions or Size of
phones that are stable and substantially omnidirectional in the
Microphone Traverse-Procedures for determining an accept-
frequency range ofmeasurement. (A 13-mm (0.5-in.) randorn- able number of microphone positions or the size of a micro-
incidence condenser microphone is recommended.) Specifi-
phone traverse are described in detail in Annex A2.
cally, microphones, amplifiers, and electronic circuitry to
process microphone signals must satisfy the requirements of 1 O. Frequency Range and Bandwidth for Analysis
ANSI S 1.4 for Type 1 sound level meters, except that A, B, and 10.1 Bandwidth-For each test band, the overall frequency
C weighting networks are not required since one-third octave response of the electrical system, including the filter or filters
filters are used. Where multiple microphones are used, they in the source or microphone systems, shall satisfy the specifi-
should be of the same model. cations given in ANSI Specification S 1.11 for a one-third
9 .3 Calibration-Calibrate each microphone over the whole octave band filter set, Order 3 or higher, Type 1.
range of test frequencies as often as necessary to ensure the 10.1.1 Filtering may be done either in the source or mea-
required accuracy (see ANSI Sl.10). A record shall be kept of surement system or partly in both, if the required overall
the calibration data and the dates of calibration, Calibration characteristic is achieved. Besides defining the one-third-
checks of the entire measurement system for at least one octave bandwidth of test signals, filters in the microphone
frequency shall be made at least once during each day of system reduce extraneous noise lying outside the test bands,
testing. including possible distortion in the source system; a filter in the
9 .3 .1 Make the sensitivity check of the measurement system source system serves to concentrate the available power in one
using an acoustic or electrostatic calibrator that is known to be test band or a few bands.
stable. The sensitivity check will usually consist of impressing 10.2 Standard Test Frequencies--Measurements shall be
a known sound pressure upon the microphone system, keeping made in all one-third-octave bands with mid-band frequencies
account of ali variable gain settings in the equipment. This specified in ANSI S 1.6 from 100 to 5000 Hz. For sound

6
~t E90
transmission loss measurements on building facades, exterior where:
doors or windows, or other building facade elements where the Lb background noise level, dB,
outdoor-indoor transmission class is to be calculated, the Lsb = level of signal and background combined, dB, and
mínimum frequency range shall be from 80 to 5000 Hz. lt is L, adjusted signal level, dB.
desirable in any case that the frequency range be extended to 11.3 .1 If the output of the sound sources cannot be increased
include bands below 125 Hz. Many applications require so the combined level is at least 5 dB above the background
information on low frequency transmission loss and laboratory level, then subtract 2 dB from the combined level and use this
operators are encouraged to collect and report information as the corrected signal level. In this case, the measurements can
down to at least 63 Hz where feasible. Note that larger room be used only to provide an estímate of the lower limit of the
volumes are recommended when measuring at lower frequen- noise reduction and the sound transmission loss. Identify such
cies (see section X2.4). measurements in the test report.
11. Procedure NoTE 8-Noise measured by the microphone system in the receiving
room when the sound sources are not operating may be due to extraneous
11.1 Measurement of Average Sound Pressure Levels, <L1 > acoustical sources or to electrical noise in the receiving system, or both.
and <Li>-With the sound sources generating the sound field
in the source room, and microphone positions in accordance 11.4 Determination of Receiving Room Absorption, .4-
with 9 .3 .1, measure the space- and time-averaged sound Receiving room absorption is determined at each frequency by
pressure level in the source room, <L1>, and the receiving measuring the rate of decay of sound pressure level in the
room, <L2> using averaging times as follows: room. The determination ofA2 shall be made with the receiving
11.2 Averaging Time, Stationary Microphones-For each room in the same condition as for the measurement of <L1>
sampling position, the averaging time shall be sufficient to and <L2> (see 11.1). Specifically, the test specimen shall
yield an estímate ofthe time-averaged level to within±0.5 dB. remain in place so its effective absorption (which includes
This requires longer averaging times at low frequencies than at transmission back to the source room) is included. Sound
high. For 95 % confidence limits of ±e dB in a one-third sources used for measuring A2 shall be present during the
octave band with mid-band frequency,f, the integration time, measurement of <L2>, so their absorption is present during
T, may be estimated from: both measurements. Determine the sound absorption of the
receiving room, Ai. as follows.
310
T=- (7) 11.4.1 Actívate sound source(s) in the receiving room for
Je2
the few seconds then switch them off and record the curves
Thus at 125 Hz, the mínimum averaging time for confidence giving the decay of sound pressure level in the room at each
limits of± 0.5 dB should be 9.9 s. At 100 Hz, an averaging one-third octave band frequency. This is most effectively done
time of 12.4 s is needed. For more information see Ref(S). for ali bands simultaneously using a real-time analyzer and a
11.2.1 If a moving or rotating diffuser is used, determine the computer. To measure the decay rate for each one-third octave
average sound pressure level at each microphone position band, first select a point on the decay curve as close as practica}
during an integral number of diffuser cycles. Altematively, to 0.1 s after the sound source has been switched off. Select a
average over a time so long that contributions from fractions of second point on the decay curve at least 20 dB but no more
a diffuser cycle are negligible. than 25 dB lower in sound pressure level than the first point.
11.2.2 Averaging Time, Moving Microphones+ The aver- This second point must be at least 1 O dB above the background
aging time for a moving microphone should be long enough noise level. Determine the straight line that best approximates
that differences between repeat measurements are negligibly the portian of the decay curve between these two points. The
small. A typical averaging time around the traverse is 60 s but slope, d, of the straight line gives the rate of decay of sound
operators should determine acceptable times by experiment. pressure level in dB/s. Fitting may be done to individual decay
11.2.2.1 Note that if both moving microphones and moving curves, or to curves that are averages of several.
vanes are used, their periods of rotation and displacement and 11.4.1.1 Instrument decay rates in each frequency band
the averaging time should be chosen so each observation should be at least 3 times the room decay rates so measure-
adequately samples all the possible combinations of micro- ments of sound decay rate are not biased. The instrument decay
phone and vane positions. rate can be measured by attaching a noise generator directly to
11.3 Measurement of Background Noise in the Receiving the input, switching off the generator and then measuring the
Room-With the sound sources not operating, measure the decay.
background noise levels for each frequency in the receiving 11.4.2 Number of Decay Rate Measurements+ Sound de-
room at the same microphone positions used to measure </..,2>. cay rates vary from one decay to the next because of the
At each measurement position corrections must be made unless random nature of the sound excitation. They also vary with the
the background level is more than 1 O dB below the combina- position of the microphone in the room. Moving, stationary, or
tion of signal and background. (The signal is the sound comer microphones may be used to sample the decaying sound
pressure level dueto transmission through the test specimen.) field. For stationary microphones, use at least three microphone
If the background level is between 5 and 1 O dB below the positions and at least 5 decays at each position. For moving and
combined level, correct the signal level using: comer microphones, use at least 10 decays. Procedures for
L, = lO log[lOL,¡/IO - IOL¡/IO] (8) determining adequate sampling procedures are described in
Annex A2.

7
~ITT~ E 90
11.4.3 Corner Microphones for Measurement of Decay numerical value of the quantity.
Rate-F or measurement of decay rates only, microphones may 12.1.2 Calcu/ation of Space-Averaged Levels, Moving
be placed in comers of the room very close to the intersection Microphones-Where a continuously moving microphone is
of the room surfaces where ali modes have sound pressure used, the space-averaged level may be obtained directly from
maxima. In this case, the restrictions on microphone position in the instrumentation.
9.4.l do not apply. 12.2 Calculation of Mean A2- Calculate the arithmetic
11.4.4 At each frequency, calculate A2 from the Sabine mean of ali the A2 values measured as specified in 11.4.
equation: 12.3 Calculate the sound transmission loss from:

A2 = 0.921 eVd (9)


(12)

where:
where: TL transmission loss, dB,
A2 sound absorption of the room, rrf, <L1> average sound pressure level in the source room,
e speed of sound in air, mis, dB,
V volume of room, nr', and average sound pressure level in the receiving
d rate of decay of sound pressure level in the room, room, dB,
dB/s. s area of test specimen that is exposed in the
When V and e are in cubic feet and feet/second respectively, receiving room, m2, and
A2 is in sabins (square feet). sound absorption of the receiving room with the
11.4.4.1 The speed of sound changes with temperature and test specimen in place, m2 (7).
it shall be calculated for the conditions existing at the time of
test from the equation: NOTE 11-S and A2 may be expressed in square feet so long as both are.
NoTE 12-The difference <L1> - <L2> in Eq 12 is by definition the
e= 20.047 y273.15 +t mis (10) noise reduction, NR.

where: 12.4 This test method specifies the use of one-third octave
t = receiving room temperature, ºC. bands for measurement and calculation of sound transmission
11.4.5 Room Coupling-Because the two test rooms are loss. lt <loes not allow measurement of octave band transmis-
coupled by the test specimen, it is possible that the decay rate sion losses because these are very sensitive to the shape of the
measurements in the receiving room will be influenced by spectrum in the so urce room and to the details of the transmis-
sound energy transmitted into the source room and then back sion loss characteristics of the test panel. In applications where
again during the decay process (6). Decay curves may be octave band transmission loss values, TL0c1, are required, they
markedly curved or have two pronounced slopes. The effect must be calculated using the expression:
will be small if T S is small compared to A 1, the absorption in
TL = -10 log -
I
2:
Be+ 1
[ 3 B = Bc-1
10-n_.¡io
J (13)
the source room, or A2, the absorption in the receiving room, or oct f,

if d ¡ld2, the ratio of decay rates in the two rooms, is sufficiently


Iarge. The Iatter requirement may be met by adding absorption where:
to the source room until no further effect is observed on the fe = preferred octave band mid-band frequency as specified
measured value of d2• in ANSI S 1.6.
12.4.1 The summation is made over three one-third octave
NoTE 9-0pening the doors of the source room is a simple way of band TL values: one at the frequency.fc with band number Be
adding sorne absorption in the source room. Additional absorption in the and the adjacent one-third octave bands, with band numbers
source room is required only during measurement of receiving room
absorption. It should not be present during measurement of <L1> and
Be+ 1 and Be - l. The octave band transmission loss values
<lz>. calculated from this expression approximate what would be
measured if the spectrum in the source room had the same
12. Calculation sound pressure level in each one-third octave band. (Random
12. l Ca/culation of Space-Averaged Levels, Stationary noise with this spectrum is known as "Pink noise.")
Microphones-Following the procedures of 11.1 and 11.2, two 13. Report
sets of sound pressure levels, corresponding to the sampling 13 .1 In elude the following information in the test report:
positions in the two rooms, will be obtained for each frequency 13.1.1 A statement, if true in every respect, that the tests
band. were conducted according to this test method and that data for
12.1.1 For each frequency band calculate the space- flanking limit tests and reference specimen tests are available
averaged Ievel corresponding to each set using: on request. Conformance to the relevant sections of Annex A 1
shall also be reported when applicable.
(11)
13.1.2 A description of the test specimen. The description
must be sufficiently detailed to identify the specimen, at least
where: for those elements that may a:ffect its sound transmission loss,
L; = one set of time-averaged levels taken at n locations. unless the test sponsor wishes to withhold information of a
NoTE 10--The convention used in this test method is that if X is the proprietary nature. The specimen size, including thickness, and
symbol for a physical quantity, log X denotes the common logarithm of the the average mass per unit area shall always be reported.

8
~fil~ E 90
Wherever possible, the testing laboratory should observe and 13 .1.1 O The confidence limits found for the laboratory as
report the materials, dimensions, masses per unit area or described in Annex A2 either during the actual test or in
densities, and other relevant physical properties of the major separate measurements.
components. A description of the methods used to combine the 13.1.11 Single Number Ratings:
components, the fastening elements used, (type of screws, nails 13 .1.11.1 Sound Transmission Class-Ai single number rat-
or glue etc.) and the spacing between them should also be ings are given, the sound transmission class described in
given. A designation and description fumished by the sponsor Classification E 413 shall be included.
of the test may be included in the report provided that they are NoTE 13-The airborne sound reduction index described in ISO 717 is
attributed to the sponsor. If sorne details of the specimen a similar rating that may also be given.
construction are withheld at the sponsor' s request, the report
13.1.11.2 Outdoor-Indoor Transmission Class- Where the
shall state this. The curing period, if any, and the condition of
test specimen may be used as part of a facade of a building, the
the specimen as tested (shrinkage, cracks, etc.) shall be
reported. Outdoor-lndoor transmission class should be included. This
single number rating is intended to rate the e:ffectiveness of
13 .1.3 A description of the method of installation of the
building facade elements at reducing transportation noise
specimen in the test opening, including the location of framing
intrusion. The rating is described in Classification E 1332.
members relative to the edges, and the treatment ofthejunction
with the test opening. The use and type of caulking, gaskets,
14. Precision and Bias
tape, or other sealant on perimeter or interior joints shall be
carefully described. 14.1 Precision--Not enough data have been collected to
13 .1.4 The dates of construction and testing. determine the repeatability standard deviation for tests where
13.1.5 If the test specimen is a screen, include a statement, the specimen is removed and reinstalled or a nominally
if true, that sound transmission through raceways and other identical specimen installed. It is estimated, however, that
penetrations are included in the evaluation. repeatability standard deviation in such repeated measurements
13. l. 6 Sound transmission los ses rounded to the nearest will be about 1 dB at ali frequencies. (It is not practical to
decibel for the frequency bands required in 10.2 and any other obtain within laboratory repeatability with multiple specimens
bands measured. taken from a lot.) From round robín testing on copies of the
13. l .6.1 Identify data a:ffected by ftanking transmission or reference specimen described in Specification E 1289, it has
background noise. been determined that the reproducibility standard deviation is 2
13. l. 7 lf results are presented in graphical form, the ab- dB or less at all frequencies from 125 to 4000 Hz.
scissa length for a 1O:1 frequency ratio should equal the 14.2 Bias-There is no bias in this test method since the
ordinate length for 25 dB. Whenever practical, the scales true value is defined by the test method.
should be 50 mm for a 10:1 frequency ratio and 20 mm for 10
dB, and the ordinate scale should start at O dB. 15. Keywords
13.1.8 The temperature and humidity in the rooms during 15.l airbome sound transmission loss; ftanking transmis-
the measurements. sion; sound transmission coe:fficient; sound transmission loss;
13.1.9 The volumes of the test rooms. transmission loss

ANNEXES

(Mandatory Information)

Al. PREPARATION AND DESCRIPTION OF TEST SPECIMENS

Al.1 Scope and plaster must be satisfied.


Al.1.3 Aging-Unless otherwise noted below, ali aging
A 1.1.1 This annex constitutes an interpretation and elabo-
shall be at a room temperature from 18 to 24 ºC and a relative
ration, for certain construction elements, ofthe general require-
humidity from 40 to 70 %.
ments given in Sections 7 and 13. Special details are given for
the preparation, installation, and aging of test specimens and
Al.2 Sealants and Adhesives
the reporting of such matters.
Al .2.1 Adhesives and materials used to caulk or seal gaps
NoTE Al.1-If the recommended aging periods seem inappropriate for and fissures around the periphery of a specimen shall be listed
a particular construction, the repeat test procedure described in 7.2. l may by brand name and type. Methods of application and approxi-
be used.
mate dimensions shall be given.
A 1.1.2 Composite Construction-If a test specimen in- A 1.2.2 Aging-If significant quantities of caulking or adhe-
eludes more than one type of component, the requirements for sive materials are required and no recommended aging period
each type shall be satisfied. For example, for a concrete block is given, appropriate procedures to determine the necessary
wall to which plaster is applied, the requirements for masonry aging period shall be used (see 7.2.1).

9
~ITT~ E90
A 1.3 Fasteners testing (see Note Al.1). Superficial coats (3 mm ~Is in.) thick
A 1.3 .1 Where screws, nails, or other fasteners are used, give or less) shall age at least 3 days.
their type, dimensions, and method of installation. Give also A 1.8 Board Materials
the spacing between fasteners around the periphery and in the A 1.8. l Report the material used, thickness, dimensions of
field of the specimen. panels, mass per unit area and end, edge, and field fastening
Al.4 Concrete and Masonry conditions.
A 1.8.2 Laminating Adhesives--Report type of adhesive,
Al .4.1 Concrete--Report the type, thickness, and density of method of application, and thickness.
the concrete. Al .8.3 Gypsum board panels or the complete test specimen
A 1.4.2 Masomy-Report the materials, dimensions, and shall be conditioned before use or testing by storing for a
average weight of an individual masonry unit. Give the mínimum of 3 days under the conditions in 1.1.3.
thickness of mortar and describe the materials used in its Al.8.3.1 If joints are finished with typical joint and finish-
preparation. ing compounds, the mínimum aging period shall be 12 h.
A 1.4.3 Determine the mass per unit area of completed Al.8.3.2 If Iarninating adhesives are used, before testing the
concrete or masonry specimens by weighing a representative specimen shall age a mínimum of 14 days for water-base
portion after test or by weighing a small specimen prepared adhesives and 3 days for other adhesives.
during construction in the same way as the main specimen.
A 1.4.4 Aging-Following construction, allow concrete or Al.9 Demountable Modular Wall Panel Systems
masonry specimens to age a mínimum of28 days before testing A 1.9 .1 Materials and Construction-The testing laboratory
(see Note Al.l). shall reportas much physical information as can be determined
about the materials and method of assembly of all components
Al.5 Studs, Joists, Trusses, and Wood or Metal Furring of the partition including weights and dimensions of the
A 1.5 .1 Wood Studs, Joists, and Furring-State grade of component parts and the average mass per unit area of the
wood, true as well as nominal dimensions, spacing in test completed partition.
opening, fastening conditions, and mass per unit length. Al.9.2 Installation-- Installation of the test specimen shall
Al.5.2 Studs or Furring Formed from Sheet Material- be carried out or observed by the testing laboratory and
Give manufacturer, model and an accurate description of reported in detail.
dimensions and material, preferably in the form of a drawing.
Give spacing in test opening, fastening conditions, and mass Al.to Operable (Folding or Sliding) Walls
per unit length. A 1.10.1 Materials and Construction-Report as much
Al.5.3 Steel Joists or Wood Trusses-Give an accurate physical information as can be determined about the materials
description of dimensions and material, preferably in the form and method of assembly of all components of the partition
of a drawing. Give spacing in test opening, fastening condi- including weights and dimensions of the component parts and
tions, and mass per unit length. the average mass per unit area ofthe completed partition. If the
specimen consists of an assembly of panels, the number and
Al.6 Sound Absorbing Materials dimensions of panels shall be reported. If the specimen is an
A 1.6.1 Specify the material, density, thickness, mass per accordion-type partition, the number of volutes, their spacing,
unit area of wall, location, and method of installation. and width when extended, shall be reported. Header construc-
tion and dimensions shall be reported. Weights of header and
Al.7 Plaster the hanging portion of the <loor shall be given. Latching and
A l. 7 .1 Plaster-Report the thickness of each layer, the sealing devices shall be fully described.
materials used, and the method of application. The actual A 1.10.2 Jnstallation-- lnstallation of the test specimen
thickness of plaster Iayers should be determined, for exarnple, shall be carried out or observed by the testing laboratory and
by inspection of representative sections after test. Report the reported in detail. Clearances at the perimeter between non-
weight per unit area. deformable portions of door and frarne shall be measured and
A 1. 7 .2 Lathing-Report the dimensions of individual sec- reported. In particular, any features of the installation that
tions and orientation in the test specimen, mass per unit area of require dimensional control closer than 6 mm C/4 in.) on the
wall, number and location of fasteners (see Note Al .2), and height or width or the test specimen shall be reported.
treatment of edges of specimen. Al.10.3 Operation--The specimen shall not be designated
an operable wall unless it opens and doses in a normal manner.
NoTE A 1.2-Resilient fasteners can be short-circuited by plaster that It shall be fully opened and closed at Ieast five times after
oozes through the lath. lf something is done to prevent this or to break the
installation is completed and tested without further adjust-
short-circuits, it should be reported.
ments.
Al.7.3 Construction-- The test specimen may either be A 1.10.4 The specimen area should include the header and
built into a suitable frame, which is then inserted in the test other framing elements if these constitute a portion of the
opening, or built into the opening itself. Report in detail the separating partition in a typical installation.
type of installation and the steps in construction.
Al.7.4 Aging--Thick coats of plaster, forming significant Al.11 Doors
contributions to the structure shall age at least 28 days before Al.11.1 Procedures that may be followed when testing

10
~ITT~ E 90
doors are given in Test Method E 1408. The specimen shall not
be designated a <loor unless it opens and closes in a normal
manner.

A2. QUALIFICATION OF ROOM SOUND FIELDS AND MICROPHONE SYSTEMS USED FOR SAMPLING

A2.1 Scope
A2. l. l One principie underlying this test method is that the
s = ~~l
n
±
i= 1
(X; - <X>)2 (A2.l)

reverberant sound fields in the rooms show only small varia-


where:
tions with position in the room. In practice, a certain amount of s standard deviation,
spatial variance must be tolerated and compensated for by X1 individual determination of sound pressure level,
correctly sampling the sound fields. <X> arithmetic mean of the set of sound pressure leve Is,
A2. l .2 This annex prescribes procedures for determining and
whether the sound fields in the rooms and the microphone n number of measurements of sound pressure level in
systems used to sample them give measurement uncertainties the set.
that are low enough for the purposes of this test method. This A2.3.4 Calculate the standard deviation of the measurement
is decided by calculating con:fidence intervals from measure- of A2 using Eq A2. l withX now representing, as appropriate,
ments of sound pressure level and reverberation time. measurements of mean values of A2 or decay rate at each
A2. l .3 Calculations of confidence intervals do not have to microphone position in the receiving room.
be made for each test, although laboratories can do so if they
NoTE A2.l-These calculations of the standard deviation of A2 are not
wish. strictly accurate. Since A2 only appears in the expression for transmission
loss as the term 1 O log A2, however, the error in calculating uncertainty is
A2.2 Required Confidence Interval for Transmission negligible.
Loss Measurements A2.3.5 Calculate the 95 % confidence interval for the indi-
A2.2. l For any pair of rooms and microphone system, the vidual quantities from:
95 % confidence interval, !l.TL, for transmission loss must be LiX= as (A2.2)
no greater than 3 dB for the one-third-octave bands 125 and
160 Hz, 2 dB for bands 200 and 250 Hz, and 1 dB for the bands where the factor a, which depends on the number of
from 315 to 4000 Hz. Confidence intervals that can be attained measurements, is given in Table A2.l and X and s represent á

above and below these frequencies will depend strongly on the the con:fidence interval and standard deviation of <L1>, <L2>,
test suite characteristics. Measurement procedures and calcu- and A2 as appropriate.
lations for calculating confidence limits are given in A2.3. A2.3.6 Calculate the confidence interval for transmission
loss from:
A2.3 Measurement Procedures and Calculations (!1TL)2 = (!1<L1>)2 + (!1<L2>)2 + 18.86(!1Aif<A2>)2
(A2.3)
A2.3 .1 The confidence interval of a sound transmission loss
determination is derived from the confidence intervals for the TABLE A2.1 Factors for 95 % Confidence Limits for Averages
individual acoustical quantities in Eq 11, namely, <L1>, <L2>, Number of Measurements, n Factor a for Confidence Limits, A X ±: as
and A2• (The uncertainty ofthe measurement of areaS is taken 4 1.591
to be zero.) The following paragraphs describe the steps to be 5 1.241
6 1.050
taken to collect the data and calculate the confidence intervals 7 0.925
for the measurement. 8 0.836
A2.3.2 In each room selecta large number (about ten or so) 9 0.769
10 0.715
of microphone positions that satisfy the requirements of 9.4. 11 0.672
The number of available positions depends on room dimen- 12 0.635
sions and the disposition of di:ffusers, loudspeakers, and 13 0.604
14 0.577
specimen; it may be less than ten. Observing the procedural 15 0.554
requirements in the main body of the test method, make the 16 0.533
following measurements, preferably using a reference trans- 17 0.514
18 0.497
mission loss specimen: 19 0.482
A2.3.2. l At each microphone position in the source room, 20 0.468
21 0.455
measure the average sound pressure levels. 22 0.443
A2.3.2.2 At each microphone position in the receiving 23 0.432
room, measure the average sound pressure levels and average 24 0.422
25 0.413
decay rates. n> 25 a= rfl·5/(0.512n - 0.71)
A2.3.3 Calculate the standard deviation for the mean sound A Limits that may be expected to include the "true" average, X, 95 times in 100
pressure level in each room from the expression: in a series of problems, each involving a single sample of observations.

11
~ITT~ E 90
If the absorption of the receiving room has been calculated lowest frequency of interest, then the mínimum size of traverse
from the average decay rate <d>, l 8.86(Li d/<d>)2 may be for each room is calculated from:
substituted for the last tenn of Eq A2.3. rotating microphones:
A2.3. 7 lf the confidence intervals calculated do not meet the
criteria in A2.2. l, then the rooms do not qualify for measure- (A2.4)
ments according to this test method. Changes to loudspeaker or
diffuser arrangements may make the sound fields more uni- where:
form. rmin mínimum radius ofthe circular path traversed by the
A2.3.8 If the confidence intervals calculated meet the crite- microphone.
ria in A2.2. l, then the rooms qualify for measurements linear traverses:
according to this test method and a microphone system can be l min = (nmin - l)A./2 (A2.5)
selected for routine testing as follows:
A2.3.8. l Fixed Microphone Positions-From the array of where:
microphone positions used to determine the confidence limits L111;11 mínimum length of straight line traverse.
above, select a subset of locations that yield the same average A2.3.9 With the dimensions of the microphone path set to
result, within experimental error, and still meet the confidence the minimum required value or more, by experiment, find
requirements of A2.2. l. positions in each room for the rnoving microphones that give
A2.3.8.2 Moving Microphones-Using the standard devia- the same average value of sound pressure level as the extended
tions calculated for the sound pressure levels in the source and array within experimental error. This is done in the source
receiving rooms, find the hypothetical minimum number of room using the normal loudspeaker system as the source of
fixed microphone positions necessary in each room for an sound. In the receiving room, use the sound coming through
acceptable confidence interval in the lowest frequency band. the test specimen as the source.
(This requires repeating the calculations for the transmission
loss confidence interval using the values of standard deviation A2.4 The confidence intervals found by these procedures
found for the large array of microphones and trying different must be remeasured at least annually or whenever significant
values of n and a from Table A2.1 until the confidence limits changes are made to room geometry, loudspeakers, or diffus-
are satisfied.) lf nmin is the mínimum number of microphones ers. The data from which the estimates of confidence intervals
required in the room and A. is the wavelength of sound at the were made must be kept on record.

APPENDIXES

(Nonmandatory Information)

Xl. LABORATORY ACCREDITATION

Xl.1 Scope sections of Guide E 458: Personnel, Facilities and Equipment,


X 1.1.1 This appendix covers procedures for accrediting an Calibration, and Test Methods and Procedures.
acoustical testing laboratory to perform tests in conformance
with this test method. Xl.4 Requirements Specific to This Test Method
Xl.4.1 Physical Facilities-The testing agency shall pro-
Xl .2 Referenced Documents vide information demonstrating that the following comply with
Xl.2.1 ASTM Standards. the provisions of this test method:
E 548 Guide for General Criteria Used for Evaluating Xl.4.1.1 Room Size and Shape(see 6.1}-Provide a sketch
Laboratory Cornpetence' showing room dimensions and calculated volumes. Describe
E 717 Guide for Preparation of the Accreditation Annex of any methods used to increase diffusion in the rooms. Show the
Acoustical Test Standards' position of the test specimen on the sketch.
E 1289 Specification for Reference Specimen for Sound Xl.4.1.2 Room Absorption(see 6.2}-Provide the measured
Transmission LosS2 decay rates and calculated room absorptions for each room for
all relevant frequencies.
Xl .3 General Requirements Xl.4.1.3 Flanking Transmission (see 6.4.2}-Provide data
X 1.3 .1 The accrediting agency shall be allowed to make an showing the measured fl.anking limit for the laboratory.
inspection of the laboratory facilities. Xl.4.1.4 Size and Mounting of Test Specimens(see 7.1}-
Xl.3.2 The testing agency shall make available to the Provide a sketch showing the dimensions of normal test
accrediting authority the information required by the following specimen openings and describe normal installation practices.
Xl.4.1.5 Test Signa/ Spectrum (see section 8.1}-Describe
the means of generating the sound signals used.
5
Annual Book of ASTM Standards , Vol 14.02. XI .4.1.6 Location of Sound Sources (see 8.2}-Provide a

12
~ITT~ E 90
sketch showing the locations of the sound source(s) in the Specification E 1289 should be investigated thoroughly. After
rooms. necessary physical adjustments to the rooms and changes in
Xl.4.1.7 Location of Microphones (see 9.3.1)-Provide a test procedures, laboratories should be able to demonstrate that
sketch showing the locations or paths of the microphones in the their results for the reference specimen are not significantly
rooms. different from those reported in Specification E 1289. Arith-
Xl.4.1.8 Measurement Bandwidth(see 10.1)-Provide data metic corrections to measured data to obtain closer agreement
to show that the measurement bandwidth is satisfactory. with the data in Specification E 1289 must not be made.
Xl.4.1.9 Background Noise (see 11.3)-Provide one-third X 1.5 .2 The Specification E 1289 reference specimen should
octave band data showing typical background noise levels be measured whenever test procedures used in the laboratory
measured in the receiving room. are changed in a way that is likely to inftuence test results.
X 1.4.1.1O Confidence Intervals (see Annex A2)-Provide
Xl.5.3 Laboratories must be able to provide test records in
data to show that the room sound fields and the microphone
report form for the Specification E 1289 reference specimen
sampling system give confidence intervals that satisfy the
and any other reference specimens maintained by the labora-
requirements in Annex A2.
tory,
Xl.4.2 Procedures= The agency shall fumish a report of a
complete test (including raw data) and shall show compliance X 1.5 .4 When a new reference specimen is introduced in a
with the following provisions of this test method: laboratory, a set of test records for that specimen needs to be
X 1.4.2.1 Microphone Calibration (see 9.3), established quickly for use by accreditors as well as the
X 1.4.2.2 Determination of average sound pressure levels laboratory staff. Initially, the reference specimen should be
(see 11.1 ), tested at intervals of about 6 months until 5 sets of data have
X 1.4.2.3 Averaging time (see 11.2), been obtained. Thereafter, annual testing will suffice. Labora-
Xl.4.2.4 Determination of receiving room absorption (see tories are always free to check reference specimens more
11.4), and frequently, but to provide useful information about laboratory
Xl.4.2.5 Averaging procedure (see 12.1). repeatability, the reference specimen should be removed and
reinstalled between tests.
Xl.5 Reference Specimens Xl.5.5 Transmission loss data resulting from repeated tests
X 1.5 .1 To be accredited, laboratories must obtain and test made on reference specimens shall be analyzed by the control
routinely a copy of the reference specimen described in chart method described in Part 3 of ASTM STP 15 D(2). The
Specification E 1289. Additional reference specimens may also analysis shall be according to the subsection entitled
be useful. Significant departures from the mean values given in "Control-No Standard Given."

X2. RECOMMENDATIONS FOR NEW CONSTRUCTIONS

X2. l The following paragraphs are intended as guidance field in the room. The recommendations for 80 and 100 Hz are obtained
for those designing new facilities to satisfy the requirements of by assuming that the same mean modal separation required for measure-
this test method. rnents at 125 Hz will be adequate for measurements at these lower
frequencies.
X2.2 Room volumes of at least 80 m' (2800 ft') are
X2.5 Room Shape.s-It is recommended that no two dimen-
preferred and strongly recommended for new construction.
sions of the pair of rooms be the same or in the ratio of small
X2.3 It is recommended that the volumes ofthe source and whole numbers. The ratio of largest to smallest dimension of
receiving rooms differ by at least 1 O %. either room should be less than two. The intent of this
recommendation is to avoid having resonances at the same
X2.4 For meaningful measurements at frequencies lower frequency in each room in the low frequency bands.
than 125 Hz, larger room volumes are considered necessary to X2.5. l Theoretical studies of rectangular rooms (8, 9, 10)
ensure acceptably uniform sound fields. For example, for suggestthat the proportions 1: 1.26: 1.59 provide a good distri-
measurements down to 100 Hz, a mínimum room volume of bution of modes in the lowest bands. Minor deviations in
125 m3 (4400 ft3) is recommended. Formeasurements down to construction, or the presence of sound diffusing devices, will
80 Hz, a minimum room volume of 180 nf (6400 ft3) is alter the actual distribution.
recommended. For new construction, room volumes of at least
200 nr' (7100 W) are recommended to allow more reliable X2.6 For new test suites, test specimens should preferably
measurements at low frequencies. forma whole room surface (wall or fioor(ll)). Altematively,
NoTE X2. l- The minimum preferred room volume of 80 m3 (2800 ft 3) the depth from the principal surface of each room to the
is derived by assuming that a minimum of approximately 18 modes in the specimen surface should be small compared to the lateral
125 Hz one-third octave band will ensure a satisfactorily diffuse sound dimensions of the specimen, about 0.5 m or less.

13
~ITT~ E 90
REFERENCES

(1) Wamock, A. C. C.," lnfluence of Specimen Frame on Sound Trans- Transmission of Sound Through Partition Walls," Scientific Papers,
mission Loss Measurement," Applied Acoustics, 15, No. 4, p. 307, National Institute of Standards and Technology, Vol 20, s506, 1925, p.
1982. 193.
(2) Manual on Presentation of Data and Control Chart Analysis, ASTM (8) Sepmeyer, L. W., "Computed Frequency and Angular Distribution of
STP l 5D, ASTM, 1976, p. 56. the Normal Modes ofVibration in Rectangular Rooms," Journal of the
(3) Noise and Vibration Control, Ed. by L. L. Beranek, McGraw-Hill, Acoustical Society of America, Vol 37, 1965, pp. 413-423.
1971, p. 228. (9) Morse, P. M. and Bolt, R. H., "Sound Waves in Rooms," Reviews of
( 4) Lubman, D., "Precision of Reverberant Sound Power Measurements," Modern Physics , Vol 16, No. 2, April 1944.
Journal of the Acoustical Society of America, Vol 56, No. 2, 1974, p. (10) Donato, R. J., "Angular Distributions of Lower Room Modes,"
523-33. Journal of the Acoustical Society of America , Vol 41, 1967, pp.
(5) Noise and Vibration Control, Ed. by L. L. Beranek, McGraw-Hill, 1496-1499.
1971, p. 115. (11) Kihlman, T. and Nilsson, A. C., "The Effects of Sorne Laboratory
(6) Mariner, T., "Critique ofthe Reverberant Room Method ofMeasuring Designs and Mounting Conditions on Reduction Index Measure-
Air-Bome Sound Transmission Loss," Journal of the Acoustical ments," Journal of Sound and Vibration, Vol 24, No. 3, 1972, pp.
Society of America, Vol 33, 1961, p. 1131. 349-364.
(7) Buckingham, E., "Theory and Interpretation of Experiments on the

The American Society far Testing and Materials takes no position respecting the validity of any patent rights asserted in connection
with any ítem mentioned in this standard. Users of this standard are expressly advised that determination of the validity of any such
patent rights, and the risk of infringement of such rights, are entirely their own responsibility.

This standard is subject to revision at any time by the responsible technical committee and must be reviewed every five years and
if not revised, either reapproved or withdrawn. Your comments are invited either far revision of this standard or for additional standards
and should be addressed to ASTM Headquarters. Your comments will receive careful considera/ion at a meeting of the responsible
technical committee, which you may attend. Jf you feel that your comments have not received a fair hearing you should make your
views known to the ASTM Committee on Standards, 100 Barr Harbar Drive, West Conshohocken, PA 19428.

This standard is copyrighted by ASTM, 100 Barr Harbar Drive, West Conshohocken, PA 19428-2959, United States. Individual
reprints (single or mu/tiple copies) of this standard may be obtained by contacting ASTM at the ebove address or at 610-832-9585
{phone), 610-832-9555 (fax), or service@astm.org (e-mail); or through the ASTM website (http://www.astm.org).