Rev. No. Rev. 0
OPERATION MANUAL Rev. Date. 2017.02.06
KT MARINE CO., LTD.
Page. 1 / 14
BWMS
Rectifier
OPERATION MANUAL
Model : REC-20K
Revision History
Contents
1. Summary
2. Equipment Layout
4. Equipment operation
6. Quality guaranteed.
1. Summary
Ballast water refers to seawater filled in the boat for safe and efficient operation of
the ship.
This equipment is a rectifier for power supply of electrolyzer equipment for sterilizing
Contents Specifications
Frequency 50~60Hz
Electricity 20kW
Protective function Input OV, UV, output OV, OC, Over Temp, IGBT Fault
Weight 60kg
2. Equipment Layout
① IN POWER : Blue LED on when AC 3 phase power on and LED off when power off.
② RUN : Green LED on when running rectifier and LED off when stop.
③ FAIL : Red LED on when defected rectifier and LED off when normal status. Red LED
B TXD
C RXD
D F.G
E Reserved
Rectifier for ballast water treatment is adopting RS-485 communication method, enabling multi-
drop (1: N) communication, long communication distance, strong against external noise.
Modbus is applied to the communication protocol inside the rectifier, and the rectifier
can be easily controlled through the external controller and parallel control of several rectifiers is
possible.
Item Description
Communication protocol RS-485
Item Description
Communication Protocol Modbus
Transfer mode RTU(Remote Terminal Unit)
Slave address 0x01 ~ 0x10(REC#1~REC#16)
Data address 4xx01 ~ 4xx13(refer to
communication map)
6~15 Reserved -
Over
REC 4 1 :Over Temperature
Temperature(O.T)
4. Equipment Operation
◆ A place exposed to high electromagnetic fields, If it is located near the main current
circuit breaker, a large area of power or a flashing power, such as an inverter, etc.
◆ A feverish place, A lot of direct sunlight, Places where polluted areas or continuously
vibrating places are highly susceptible to humidity.
◆ Disconnect all connector connections and connect them to the power source, and do
not contact the output booth bar directly after power is connected.
◆ For terminal connections, check and connect the power rating and terminal wiring.
1. The rectifier output voltage is greater than 110 % of the rated current.
OC
4 → Check the Electrolyzer , check interior short. Oxidation / corroded
(Output Over Current)
electrode(Plate) Change, Reset and Restart
6. Quality guaranteed
Quality guaranteed