1 Velocity Flowgrid Primary Air
2 Fan Motor
3 Controls Package 3
4 Air Induction Ports
5 Access Panel
5
4
TROX Series Fan VAV Terminal Boxes take primary and Mixing between the primary airstream and the induced
induction air, mix the two thoroughly and provide a constant warm air from the ceiling void is by forward curved blade
air supply to the occupied zone of the building. centrifugal fan with a direct drive motor. This direct drive
Total flow from the diffuser is kept substantially constant thus motor is of the electronically commutated type fitted with
giving very good air distribution even with high turn down of permanently lubricated bearings.
the primary air volume. The primary air damper can be fully TROX Series Fan VAV Terminal Boxes are eminently
shut. suitable for low temperature air applications. If the supply air
TROX Series Fan VAV Terminal Boxes have been designed temperature is low, then the fan volume flow rate must be
and developed to achieve lower room noise levels. higher than the 100% primary air volume flow rate to ensure
Discharge and case radiated sound pressure levels of NR 35 suitable air temperature at the diffuser.
can be achieved in the occupied zone. Design of the SFTB ensures that at 100% primary air,
Pressure independent control of the primary VAV damper is sufficient induced air is mixed with the primary air so that
accomplished by use of a Multi-point flowgrid which gives the air discharged has a conventional cooling differential
accurate control of air flow even with a 90° bend on the inlet which will not cause draught problems in the space being
spigot. conditioned.
2
Construction · Dimensions · Materials
TROX Series Fan VAV Boxes save energy by utilising the enclosure has a single electrical (230 V) mains entry position.
warm air in the building already generated by other sources
and mixing it with primary air before distributing a constant
volume air supply direct to the occupied zone. This reduces Casing
energy consumption, so providing long term operational
The casing is sturdily constructed of galvanised sheet steel.
savings. Available in a range of sizes from 100 l/s to 790 l/s.
The overall construction is reinforced to meet acoustic
TROX Series Fan VAV boxes are suitable for electronic
performance requirements.
control. Volume flow tolerance is dependent on the type of
control system but is typically ±5% to ±10% of set volume. - Casing with acoustic and thermal insulation, erosion
The units are designed for use in VAV systems and in resistant up to 20 m/s.
conjunction with DDC controllers permit communications
between the boxes and a centralised control area. - High pressure side with duct spigot suitable for circular
ducting.
- Low pressure side suitable for angle frames or slide-on
General flanges.
Series Fan VAV terminal VAV boxes are constructed from - Casing leakage rate to DW 144 Class A.
galvanised steel meeting all relevant UK construction
standards. All electrical control components are protected - Drilled mounting holes for support rods are provided in the
by sheet metal enclosures to meet UK practices. The top flange of the casing.
10 DIAMETER
Type SFTB UNIT SUPPORT HOLES
(4-OFF)
UNITS MANUFACTURE WITH
22mm DEEP RECESSED ENDS 11 11
LEFT HAND
ALLOWING 100mm TOTAL
CONTROLS LOCATION
SPIGOT CONNECTION LENGTH
”
‘BW’ OVERALL BODY WIDTH
INTERNALLY
MOUNTED FAN AS ‘S’ SUPPORT
DIAMETER
CENTRES
OUTSIDE
’’
BODY HEIGHT
ENCLOSURE
HEIGHT
‘BH’ O/A
HOLE CRS
AIRFLOW DIRECTION
‘FH’
’’
’’ ’’ ’’ REMOVABLE LID RETAINED VIA 4-OFF 1/4 TURN FASTENERS, REFER TO DUCT
SEPERATE DRAWING FOR SPECIFIC CONTROLS LAYOUT DETAILS SIZE = ‘FW’ - 30mm x ‘FH’ - 30mm
RELEASE FIXINGS
AND SLIDE TO
REMOVE PANEL
‘FAP’ OVERALL
REMOVABLE FAN
ACCESS PANEL LENGTH
x FULL BODY WIDTH
3
Construction · Dimensions · Materials
- The access door is also lined with the same material. - Electronic controllers can be fitted.
- All lining materials have Class ‘O’ fire rating conforming to - Primary air volume flow range adjustment at factory.
UK building regulations. - Volume measurement can be made on site using the
flowgrid; also adjustment of volume flow through
controller.
- Control and full shut off is achieved with a single damper.
10 DIAMETER
Type SFTB with Hot Water Coil
UNITS MANUFACTURE WITH
UNIT SUPPORT HOLES
(4-OFF)
22mm DEEP RECESSED ENDS 11 11
LEFT HAND
ALLOWING 100mm TOTAL
CONTROLS LOCATION
SPIGOT CONNECTION LENGTH
”
‘BW’ OVERALL BODY WIDTH
INTERNALLY
MOUNTED FAN AS
‘S’ SUPPORT
DIAMETER
CENTRES
OUTSIDE
NOTE: SPECIFIED ON
HOLE
ORDER SCHEDULE
‘D’
’’
BODY HEIGHT
ENCLOSURE
HEIGHT
‘BH’ O/A
HOLE CRS
AIRFLOW DIRECTION
‘FH’
’’
RECOMMENDED CONNECTION
UNIT CONTROLS CONTAINED WITHIN STEEL ENCLOSURE WITH
19
’’ ’’ ’’ DUCT
REMOVABLE LID RETAINED VIA 4-OFF 1/4 TURN FASTENERS, REFER TO 30 DUCT
SIZE = ‘FW’ - 30mm x ‘FH’ - 30mm
SEPERATE DRAWING FOR SPECIFIC CONTROLS LAYOUT DETAILS FLANCE WIDTH
FAN ACCESS PANEL SECURED WITH 6-OFF M8
MACHINE SCREW FIXINGS, RELEASE SCREWS AND
SLIDE ALONG KEYHOLE SLOTS APPROX 30mm
TOWARDS DISCHARGE END TO REMOVE PANEL
RELEASE FIXINGS
AND SLIDE TO
REMOVE PANEL
‘FAP’ OVERALL
REMOVABLE FAN
ACCESS PANEL LENGTH
x FULL BODY WIDTH
4
Construction · Dimensions · Materials
Pressure Differential Flowgrid - The closed damper has a shut off leakage at 500Pa inlet
- Minimum pressure differential signal from 2Pa upwards. pressure of less than 0.5% of rated flow.
- Sensor tubes in aluminium. - The damper blade is positively connected to its drive shaft
which runs in maintenance free plastic (Pocan) long life
- Test pressure tappings are supplied with tight fitting caps. bearings.
- Calibration graphs and constants are provided to relate - Evoprene damper seal, thermoplastic elastomer
volume flow in litres/second to the measured pressure compound seal suitable for temperatures up to 50°C.
differentials.
- The differential pressure generated by the averaging Total Airflow Monitoring
sensor is within ±3% of the calibration chart value over the An optional total flow measuring grid can be fitted in the
range of typical primary air flow rates. airway of the secondary silencer to provide a signal for flow
monitoring.
Control Damper
The single blade damper is mounted in the circular duct
behind the flow measuring grid. The drive spindle is
extended through the casing and a suitable actuator slips
over the shaft and locks directly to it.
10 DIAMETER
Type SFTB with Electric Heater UNIT SUPPORT HOLES
(4-OFF)
UNITS MANUFACTURE WITH
22mm DEEP RECESSED ENDS 11 11
LEFT HAND
ALLOWING 100mm TOTAL
CONTROLS LOCATION
SPIGOT CONNECTION LENGTH
”
‘BW’ OVERALL BODY WIDTH
INTERNALLY
MOUNTED FAN AS ‘S’ SUPPORT
DIAMETER
CENTRES
OUTSIDE
’’
BODY HEIGHT
ENCLOSURE
HEIGHT
‘BH’ O/A
HOLE CRS
AIRFLOW DIRECTION
‘FH’
’’
’’ ’’ ’’ REMOVABLE LID RETAINED VIA 4-OFF 1/4 TURN FASTENERS, REFER TO DUCT ELECTRIC HEATER ELEM
SEPERATE DRAWING FOR SPECIFIC CONTROLS LAYOUT DETAILS SIZE = ‘FW’ - 30mm x ‘FH’ - 30mm FITTED AS SPECIFIED ON
ORDER SCHEDULE SIZE
MEET PERFORMANCE
REQUIREMENTS
125
AND SLIDE TO
REMOVE PANEL
30 FLANCE
(4 SIDES)
‘FAP’ OVERALL
REMOVABLE FAN
ACCESS PANEL LENGTH
x FULL BODY WIDTH
5
Aerodynamic Data
Primary Air Volume Range · Fan Volumes
Primary Inlet .
Spigot Code V1 (l/s) pSI min Pa
15 20
125
110 50
25 20
160
180 40
40 20
200
290 35
60 20
250
440 25
105 20
315
700 20
7
Technical Data · Accessories
Fan and Motor EC Fan VAV boxes are supplied as a constant volume fan with
The Series Fan VAV terminal boxes are fitted with fan a manually adjustable potentiometer fitted to adjust the fan
casings (Scrolls) manufactured from sheet steel. speed to the design air volume during commissioning. The
The fans have a forward curved fan impeller. primary air supply should never exceed 90% of the total fan
All fan motors are soft start and direct drive resiliently volume to prevent primary air blowing out of the air intakes into
mounted via location brackets suitable for 230 volts 50 Hz the ceiling void.
single phase and are supplied with auto reset thermal
overloads. The fan motors are electronically commutated EC Fans are capable of variable speed control when
types fitted with permanently lubricated bearings. connected to a BMS controller enabling a turn down when
All earthing wiring and component selection conforms to peak cooling is not required. Care needs to be taken to ensure
BS/IET wiring requirements. the supply air diffuser remain within an acceptable operating
window to prevent dumping and comfort issues.
Fan Motor Speed Control
All fan motors fitted to Trox Series Fan VAV Terminal Boxes Accessories
are suitable for fan speed control using a 0 - 10V control Provision is made on the induction ports of the unit for the
signal. installation of air filters. These can be metal cleanable filters,
or glass fibre throwaway filters in cardboard frame.
Case Code Fan Code W2 Watts W1 Watts Ar Amps As Amps PF SFP W/l/s
8
Nomenclature
9
Quick Selection
Refer to table on page 6 for relationship of inlet spigot diameter and primary air flow rate.
10
Secondary Attenuator
TSFB
Insulation
- The inside of the TSFB Attenuator is acoustically lined with
a minimum 50mm thickness.
- Face of the mineral wool has a glass fibre tissue covering
securely fixed to the substrate. PU Foam side liners are
incorporated.
M8 THREADED INSERTS
4-OFF CORNERS ON SIZES
AIRFLOW DIRECTION
110, 111, 210, AND 211 6-OFF
FOR ‘-VG*’ UNITS
ON ALL OTHER SIZES
‘H’ UNIT HEIGHT
VELOCITY GRID
CONNECTIONS
TO SUIT 6mm
I/D TUBING
‘X’
= =
‘M’ FIXING CRS
M8 SCREW
‘M’ FIXING CRS
‘TSFB’ UNIT
NOTE:
‘M’ + 26
1)ADDITIONALDUCT 14 DEEP
ADDITIONAL DUCT
DETAILS (OPTION -D1) RECESSED
MANUFACTURED FROM
SUPPLIED FITTED END
1.5mm THICK
TO BOTH ENDS OF UNIT
GALVANISED MILD
STEEL SHEET GASKET OR
SEAL
= =
‘N’ - 34 I/S DUCT ENLARGED TYPICAL
END CONNECTION DETAILS
Table 7:
Case Size L B H N M X
110 750 354 392 284 239 170
210 1000 454 402 384 288 175
310 1200 554 402 484 339 175
410 1500 704 452 634 390 188
11
Water Coil Output Data
12
Electric Heater Data
110 1, 2, 3 –
210 1, 2, 3, 4 3, 4.5, 6
13
Order Details
Order Example
Make : TROX
Recirculated air Recirculated air Type : SFTB-R/110x125xEC1/0/
BC0/120-100-50
Product Type
Not used No entry for standard length
Lining or special length in mm on
LB = Perforated plate lining request
or no entry
Size
Flowgrid 110
VGL = Left Hand 210
VGR = Right Hand 310
or no entry 410
Duct Piece
D1 = Additional ducts fitted
or no entry
14