Pressure Transmitter Operation Manual

1
Catalog
Section 1 Introduction..................................................................................................1
Working Principle................................................................................................... 1
Sensor......................................................................................................................1
Circuit Board...........................................................................................................2
Technology Innovative Points.................................................................................3
Main Features..........................................................................................................3
Technical Parameter................................................................................................ 3
Class of accuracy.....................................................................................................4
Accuracy in different ranges................................................................................... 4
Temperature Effect.................................................................................................. 5
Static pressure effect............................................................................................... 5
EMC........................................................................................................................ 5
Section 2 Installation....................................................................................................7
Mounting Requirements..........................................................................................7
Liquid Flow Measurement...................................................................................... 7
Gas Flow Measurement...........................................................................................7
Steam Flow Measurement.......................................................................................7
Commissioning on the bench with HART.............................................................. 8

Section 3 Adjustment.................................................................................9
Menu Tree............................................................................................................... 9
Section 1 Introduction

Working Principle

Smart transmitter mainly consists of sensor and circuit board. The sensor is mainly with pressure
sensitive component, AD switching circuit, temperature sensor and parameter memory EEPROM.
The circuit board is composed of ultra-low power microprocessor, AD signal converter and HART
digital communication chips to convert pressure signal into 4~20mA DC.
Smart transmitter working principle:

Sensor

Sensitive component: The isolated diaphragm and filling oil transfer medium pressure to
measuring diaphragm of & chamber center. The measuring diaphragm is a tight and elastic
component, which is mainly to measure its own differential pressure. The displacement and
differential pressure are directly proportional, with the largest displacement of 0.004 inch
(0.10mm). With the changes of sensor differential pressure, the capacitance C1, C2 between
measuring diaphragm and fixed board also change, which converted by signal conditioner to
voltage signal, then processed by highly precise ADC converter to digital signal for the follow-up
processing.

1
Temperature sensor: Measure the working medium temperature of pressure sensor, then convert
it to digital signal for microprocessor to digital temperature compensation.
Characteristic EEPROM: Save transmitter temperature compensation, sensor characteristic
curve and data, digital fine-tuned data and others. Even though power is off, the data is still
completely stored in the memory.

Circuit Board

● Microprocessor: It mainly controls transmitter’s operation, with AD switching circuit and


temperature sensor to detect working pressure and medium temperature of pressure sensitive
component. It works out working medium pressure value to send to D/A converter and HART
communication through linearizing processing and compensated calculation of characteristic
EEPROM, realizing no influence on transmitter output even with the circuit board and sensor
interchange. Besides, it can also calculate transfer functions and engineering unit, exchange
measuring range, adjust damp and diagnose by itself.
● Memory EEPROM: Save all configuration data which adjusted through remote and local ways.
Even though power is off, the data is still completely stored in the memory.
● D/A Converter: It converts adjusted pressure digital signal into 4~20mA DC to send to output
circuit.
● HART Communication: The digital communication circuit provides interface between
transmitter and HART manipulator or control system. It detects FSK signal which added on
4~20mA DC circuit, the sending part also adds it to 4~20mA DC circuit.

2
Technology Innovative Points

● Transmitter adopts advanced electric isolation technique to realize the isolation between sensor
and circuit board, the insulated voltage is up to 1500VDC, which is very suitable for industrial
circumstances with severe interference.
● The module consists with a 24 bit high precision ADC and a ultra-low power consumption
MCU, with large turndown ratio reaches 100:1.
● LCD display with backlight has both Chinese and English language operation menu, which is
greatly convenient for operators to calibrate.
● Non-contact reed switches can make transmitter easily for anti-explosion and intrinsic safety
occasions.

Main Features

● Measuring medium: Gas, Vapor and Liquid


● Accuracy: ±0.1%F.S
● Measuring range (No migration
Differential pressure: 0-0.6kPa~ 2000kPa
Pressure: 0-1.0kPa~40000kPa
Absolute pressure: 0-10kPa~6900kPa
● Sensor module integrated with thermal component is with humidity proof, vibration and
ambient temperature changes resistance, which greatly improves transmitter temperature property
of its anti-electromagnetic interference, anti-overvoltage so that communication ability enhances
greatly .
● Static pressure: 4MPa,7MPa,14MPa
● Complete HART protocol includes paroxysm function, can fast reading digital current, percent
and main process variables with no loss of accuracy, and can communicate manipulator and DCS
with HART bidirectionally and continuously.
● Long term stability: ±0.1% per year
● Measured medium temperature range: -40℃~+315℃
● Quick dynamic response
● Ample filling liquid: silicon oil, fluorine oil, high temperature silicon oil, etc.
● Adjusting span and zero by magnetic induction local button, no need to open the cover
● Isolated diaphragm material: 316L stainless steel, Hastalloy C, Tantalum, etc.
● LCD Module with backlight has both Chinese and English language operation menu, shows
engineering unit, percent, current value, custom value.

Technical Parameter

● Measuring range: 0~0.15kPa-40MPa

3
● Output signal: 4~20mADC
● Communication mode: HART
● Power supply: 12~45VDC(24VDC)
● Working temperature:-40~+85℃ (With Display:-25~+75℃)
● Storage temperature: -40~+85℃
● Damping:0~16s(Adjustable)

Class of accuracy

0.1 0.25 0.5


Product Range Code
class class class
2 × √ √
Differential pressure Transmitter
3,4,5,6,7 √ √ √
Pressure Transmitter 3,4,5,6,7,8,9,0 √ √ √
Absolute pressure Transmitter 5,6,7,8 √ √ √
Note: “√” indicates “Yes”;“×” indicates “None”

Accuracy in different ranges

● 0.1%F.S:If TD>10 (TD=Maximum range/Regulating range), maximum error is ±

(0.01xTD)%F.S

● 0.25%F.S:If TD>10 (TD=Maximum range/Regulating range), maximum error is ±

(0.025xTD)%F.S

● 0.5%F.S:If TD>10 (TD=Maximum range/Regulating range), maximum error is ±

(0.05xTD)%F.S

4
Temperature Effect

output variation ≤(%F.S)


Item Remark
0.1 class 0.25 class 0.5 class
Lower limit / 0.2/10℃ 0.2/10℃ 0.2/10℃ -25℃~75℃
Range
0.4/10℃ 0.4/10℃ 0.4/10℃ -40℃~ -25℃,75℃~ 85℃
variation

Static pressure effect (Only for differential pressure transmitter)

Output variation ( ≤%FS)


Maximum Unidirectional static
Static pressure effect
Range code static pressure effect
pressure 0.1 0.25 0.5 0.1 0.25 0.5
class class class class class class
2 4MPa × 0.5 1.0 × 1.0 2.0
3 7MPa 0.25 0.5 1.0 0.5 1.0 2.0
4,5,6,7 14MPa 0.25 0.5 1.0 0.5 1.0 2.0
Note: “×” indicates “None”

EMC

Limit and
NO. Test items Test standards Test Specs
Criteria
Conducted
1 EN 61326-1:2013 0.15MHz~30MHz Class A
Emission
Radiated
2 EN 61326-1:2013 30MHz~1000MHz Class A
Emission
±8kV(air discharge)
±4kV
Electrostatic
3 EN 61326-1:2013 (contact discharge) Criteria A
Discharge
±4kV
(indirect discharge)
10V/m(80MHz~1GHz)
Radiated
4 EN 61326-1:2013 3V/m(1.4GHz~2GHz) Criteria A
Susceptibility
1V/m(2GHz~2.7GHz)

5
Electrical Fast
5 EN 61326-1:2013 ±2kV(5kHz,60s) Criteria B
Transient
Conducted
6 EN 61326-1:2013 3V(0.15MHz~80MHz) Criteria A
Susceptibility
±1kV(L-L)
7 Surge EN 61326-1:2013 ±2kV(L-G) Criteria B
1.2μs/50μs
8 P-F magnetic EN 61326-1:2013 30A/m Criteria A

6
Section 2 Installation

Mounting Requirements

Refer to Figure 2-1 for examples the following mounting configurations:

Liquid Flow Measurement

● Place taps to the side of the line to prevent sediment deposits on the transmitter’s process
isolators.
● Mount the transmitter beside or below the taps so gases can vent into the process line.
● Mount drain/vent valve upward to allow gases to vent.

Gas Flow Measurement

● Place taps in the top or side of the line.


● Mount the transmitter beside or above the taps so liquid will drain into the process line.

Steam Flow Measurement

● Place taps to the side of the line.


● Mount the transmitter below the taps to ensure that the impulse piping will stay filled with
condensate.
● Fill impulse lines with water to prevent the steam from contacting the transmitter directly and to
ensure accurate measurement start-up.

NOTE:
In steam or other elevated temperature services, it is important that temperatures at the coplanar
process flanges not exceed 250°F (121°C) for transmitters with silicone fill or 185°F (85°C) for
inert fill. In vacuum service, these temperature limits are reduced to 220°F (104°C) for silicone fill
and 160°F (71°C) for inert fill.

7
Gas or liquid service Gas service Steam service

Figure 2-1 Installation Examples

Commissioning on the bench with HART

Commissioning consists of testing the transmitter and verifying transmitter configuration data.
You may commission transmitters either before or after installation. Commissioning the
transmitter on the bench before installation using a HART-based communicator or AMS ensures
that all transmitter components are in good working order and acquaints you with the operation of
the device.
To commission on the bench, connect the transmitter and the communicator as shown in Figure
2-2.
For 4–20 mA transmitters, you will need a power supply capable of providing 14 to 45Vdc at the
transmitter, and a meter to measure output current.

Wiring Diagrams

Figure 2-2 Wiring (4~20mA)

8
Section 3 Adjustment

Menu Tree

Test Item
Function
No. Menu
0 Enter “M” key, Entry menu
1 EXIT Exit menu
2 ZSHIFT Display Zero
3 GET0 Output low current (4mA)
4 GET100 Output high current (20mA)
5 DAMPING Setup Damping
DISPLAY Display mode selection
1 PRESS Present pressure / differential pressure
6 2 PERCENT Output signal percentage
3 CURRENT Output current
4 USER Display custom values, e.g.liquid level
UNITS
7 inH2O,inHg,ftH2O,mmH2O,mmHg,psi,bar, Display unit selection
mbar,g/cm2,kg/cm2,Pa,kPa,MPa,torr,ATM
8 Decimal point setting Can set 4 decimal points
9 SET0
10 SET100
11 USER0 Custom low
12 USER100 Custom high
13 USERUNIT Custom display unit
VIEW
Display present pressure / differential
1 PRESS
pressure
14 2 PERCENT Display output signal percentage
3 CURRENT Display output current
4 TEMPAD Display current temperature AD
5 PRESSAD Display current pressure AD
FUNCTUION Linear or square root
15 1 LINER
2 SQRT
WRITEPRO Write protect
16 1 ON
2 OFF
ALARM Alarm selection
17
1 HIGH

9
2 LOW
LANGUAGE
18 1 CHINESE
2 ENGLISH
19 INFORMATION Hardware and software version
20 RECOVER

10