with 5% of O2 in exhaust gases 500 300 mg/Nm3 max. working pressure 1600 kPa
water volume in CHP unit circuit 56 dm3
efficiency in the working point 96,3 % water volume in CHP unit circuit 487 dm3
1) Parameters are valid if the dry cooler (optional) is part of delivery
voltage 400 V
Technological Circuit 1)
frequency 50 Hz
water + ethylene
heat carrier
glycol
ethylene glycol's concentration 35 %
circuit's heat power 42 kW
max coolant temperature at the input 42 °C
rated flow rate 2,5 kg/s
pressure reserve at the rated flow rate 70 kPa
max. working pressure 250 kPa
water volume in CHP unit circuit 32 dm3
1) Parameters are valid if the dry cooler (optional) is part of delivery
TS_Cento_530_MAN_NG_C_LB_50Hz_S_EN_11_2019 1
Technical Specification
Cento 530, Natural gas, Container Data Sheet
unused heat removed by the ventilation air 52 kW protection of switchboard's power part
IP 31/00
closed/open
amount of combustion air 2062 Nm3/hr
protection of switchboard's control part
outdoor air temperature, min / max -20/35 °C IP 31/20
closed/open
recommended superior protection 1000 A
Exhaust Gas and Condensate Outlet recommended connection cable 2)
3×(NYY-J
amount of exhaust gases 2142 3
Nm /hr (l< 50m, at t<35°C) 3x150+70)
1) Power factor adjustable from 0,8C ÷ 1 ÷ 0,8L (range from 0.8C ÷ 1
exhaust gas temperature, rated / max 120/150 °C must be verified according to the various types of generators).
L = inductive load - overexcited
max. back-pressure of exhaust gases C = capacitive load - underexcited
10 mbar
downstream the CHP unit flange Operation of the generator with a power factor of less than 0.95
causes a power limitation sets the following table:
speed of exhaust gases at the outlet
27,3 m/s
(DN 200)
power factor [-] 1 0,95 0,8
output [% Pnom] 100 100 98
Lubricant Charges
2) The stated cables are for information only. A check calculation for
amount of lubrication oil in the engine 90 dm3
temperature rise and voltage drop must be made according to the
replenishment oil tank volume 130 dm3 actual length, placement and type of the cable (maximum allowed
voltage drop is 10 V)
Caution
Manufacturer reserves the right to alter this document and the
linked source materials.
TS_Cento_530_MAN_NG_C_LB_50Hz_S_EN_11_2019 2