You are on page 1of 7

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO.

3, JULY 2007 1613

Power-Flow Control Performance Analysis


of a Unified Power-Flow Controller in a
Novel Control Scheme
Liming Liu, Pengcheng Zhu, Yong Kang, and Jian Chen, Senior Member, IEEE

Abstract—In this paper, real, reactive power, and voltage bal- the transmission-line current leads to real and reactive power ex-
ance of the unified power-flow control (UPFC) system is analyzed. change between the series converter and the power system. The
Two important results related to UPFC control are shown in this parallel converter provides the amount of real power required
paper. First, the shunt converter provides all of the required reac-
by the series converter plus the losses of the UPFC conversion
tive power during the power-flow changes if the UPFC bus voltage
is constant. Second, the UPFC bus voltage can be controlled both system.
from the sending side and from the receiving side. Based on the With its multifunction, the control scheme of the UPFC is
analysis, a novel coordination controller is proposed for the UPFC. complex and meets many problems. To solve these problems,
The basic control strategy is such that the shunt converter controls some coordination control schemes are applied. In [6], the tran-
the transmission-line reactive power flow and the dc-link voltage. sient condition of a UPFC is analyzed and the dc-link capacitor
The series converter controls the transmission-line real power flow design is discussed. In [7], the series converter real power de-
and the UPFC bus voltage. The real/reactive power coordination
controllers in the UPFC control system can obtain good perfor- mand is calculated and sent to the shunt converter as a compen-
mance both during transient and stable conditions. Experimental sated signal to make the dc-link voltage constant during tran-
works have been conducted to verify the effectiveness of the pro- sient conditions, and the reactive power flow changes is added
posed control strategy. to the shunt converter as a compensation signal to maintain the
Index Terms—Novel control scheme, reactive power balance, UPFC bus voltage constant when power flow changes. In [8], a
real power balance, series converter, shunt converter, unified comprehend control scheme of both phase-angle and cross-cou-
power-flow controller (UPFC), voltage balance. pling control is proposed for power-flow adjustment and ob-
tains good performance in a laboratory prototype. In this paper,
a new control scheme has been developed to avoid the insta-
I. INTRODUCTION bility/excessive loss of dc-link voltage and maintain the UPFC

T HE unified power-flow controller (UPFC) is the most com-


prehensive multivariable flexible ac transmission (FACTS)
device. It is able to control, simultaneously or selectively, all
bus voltage constant during transient conditions.
In contrast to the conventional control schemes as listed in
[1]–[8], the new control strategy selected for the UPFC is per-
of the parameters affecting power flow in the transmission line formed a little different. When the shunt converter is controlled
(i.e., voltage, impedance, and phase angle). Alternatively, it can to make the UPFC bus voltage constant, according to the anal-
independently control both real and reactive power flow in the ysis, it can be found that any increase/decrease in the transmis-
transmission line. In some conditions, it also acts as a harmonic sion-line reactive power due to in-phase component of the series
isolator [1]. A small number of experimental prototypes have voltage injected by the series converter causes an equal increase/
been built and tested in labs [1], [2]. In 1998, American Elec- decrease in the shunt converter reactive power. In short, the
tric Power (AEP) installed a 160-MVA UPFC at the Inez sub- shunt converter supplies increasing/decreasing reactive power
station in eastern Kentucky, which is the first practical imple- in the transmission line. So a modified control strategy for the
mentation in the world [3]–[5]. Normally, a UPFC consists of UPFC can be developed. Here, the shunt converter is controlled
two voltage-source integrated (VSI) converters, which are con- to make the dc-link voltage constant and output the reactive
nected back to back through a dc link. One serves as a series con- power for reactive power-flow control, while the series converter
verter and the other serves as a shunt converter. The shunt con- is controlled to maintain the UPFC bus voltage constant and
verter of the UPFC controls the UPFC bus voltage/shunt reactive adjust the real power flow in the transmission line. With this
power and the dc-link voltage. The series converter of the UPFC method, the UPFC bus voltage and transmission-line reactive
controls the transmission-line real/reactive power flow by in- power can be controlled directly and better performance is ex-
jecting a series voltage controllable both in magnitude and phase pected compared to conventional control schemes.
angle. The interaction between the series-injected voltage and In this paper, a UPFC control system that includes both the
shunt converter and the series converter has been designed and
Manuscript received January 27, 2006; revised July 3, 2006. Paper no. its performance has been evaluated. Section II gives the analysis
TPWRD-00042-2006. of the UPFC system. Sections III and IV describes the control
The authors are with the Department of Electrical Engineering, Huazhong scheme for the series and shunt part separately. The experiment
University of Science and Technology, Wuhan 430074, China (e-mail:
hyt_llm@sohu.com; zhu_pc1977@yahoo.com.cn; Ykang@mail.hust.edu.cn;
details of the UPFC are given in Section V. Section VI provides
Jchen@mail.hust.edu.cn). the results of the experimental works with the proposed con-
Digital Object Identifier 10.1109/TPWRD.2006.886799 troller. Brief conclusions are given in Section VII.
0885-8977/$25.00 © 2007 IEEE

Authorized licensed use limited to: UNIVERSIDAD CENTRAL DE VENEZUELA. Downloaded on March 04,2010 at 15:24:55 EST from IEEE Xplore. Restrictions apply.
1614 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 3, JULY 2007

Fig. 1. Configuration of a UPFC based on two back-to-back three-phase converters.

II. ANALYSIS OF UPFC the power flow changes. That leads to the conventional control
scheme for the shunt converter of the UPFC. However, (4) pro-
A. Voltage Balance of the UPFC System vides a new method to control the UPFC bus voltage . It can
Fig. 1 shows the basic configuration of a UPFC. The UPFC is be seen from (4) that can be controlled by the series con-
inserted into the transmission line through a series transformer. verter output voltage as shown in (8) when the power flow
According to Fig. 1, the voltage balance can be established as changes

(1) (8)
(2)
where is the receiving-end voltage variation on the
If the -axis is in phase with the UPFC bus voltage and
-axis. Ordinary will not change greatly during the trans-
the -axis is in quadrature with , a new voltage balance in
mission-line power-flow variation. So in the stable condition,
synchronous rotating – frame can be expressed as follows: (8) can be simplified as
(3) (9)

(4) Equation (9) indicates that should be proportional to the


variation of to maintain constant. So can be con-
where trolled to make constant when the power flow changes.

power system angular velocity; B. Real Power Balance Analysis


sending-end transmission-line inductance; The power balance of the UPFC system is investigated as
receiving-end transmission-line below.
inductance. For real power balance
In most of the conditions, the UPFC bus voltage amplitude is
maintained constant when UPFC control the power flow [3]–[5]. (10)
Ordinary is small and does not vary greatly. Equation
(3) indicates that should not change to make constant where
because
sending-end output real power;
(5) real power absorbed by the shunt converter;
real power output by the series converter;
And in the same - frame real power flow from the UPFC to the receiving
end.
(6) According to the instantaneous power theory, (10) can be
transformed to
So, to make constant when varies, it should meet the
following condition: (11)

(7) where means the dot product of two vector.


To make the UPFC dc-link voltage constant, it should meet
where and are the -axis component variation of the conditions in (12)
the receiving-end current and the shunt converter current ,
when the power flow changes. It can be inferred from (7) that (12)
the shunt converter should provide corresponding reactive cur-
rent to maintain the UPFC bus voltage constant when where is the loss of the UPFC conversion system.

Authorized licensed use limited to: UNIVERSIDAD CENTRAL DE VENEZUELA. Downloaded on March 04,2010 at 15:24:55 EST from IEEE Xplore. Restrictions apply.
LIU et al.: POWER-FLOW CONTROL PERFORMANCE ANALYSIS 1615

According to (11) and (12), (10) can be transferred to (13) C. Reactive Power Balance Analysis
According to Fig. 1, the reactive power balance can be written
as
(13)

Equation (13) indicates that the sending-end power source (21)


generates all of the real power for transmission and system loss.
According to (2), it can be shown where
sending-end output reactive power;
(14) reactive power consumed by the sending
transmission line;
reactive power absorbed by the shunt part of
Equation (14) can be simplified as the UPFC;
reactive power output by the series part of the
(15) UPFC;
reactive power flow from the UPFC to the
receiving end.
Equation (15) indicates that when and do not vary, Using the instantaneous power theory, (21) can be transferred
only can be used to control the transmission real power. to (22)
However, for the system shown in Fig. 1, the condition is a bit
more complex (22)

Through the same transformation as mention before, the new


(16) equation in – frame can be induced

Putting (5) into (16), it can be shown as


(23)

(17) where . Substituting (3) into (23), we can get

(24)
If and do not vary, then the transmission real power
variation can be calculated as When power flow changes and maintains constant, then
and (7) are established. So we can obtain a new
equation when there is power-flow variation

(18)
Transfer (18) to the synchronous rotating - frame (25)

where is the reactive power absorbed


by the shunt part of the UPFC when transmission power flow
(19) changes; and
Equation (19) indicates that the transmission real power vari- is the reactive power absorbed by the series part of the
ation is related to many variables. When the series converter UPFC when transmission power flow changes.
output voltage is utilized to control , because (8) Equation (25) indicates that if do not change, then the
indicates that will cause variation of , is con- shunt part of the UPFC provides the variation part of reactive
trolled to manipulate . So in the control scheme, is power absorbed by the series part and transmission reactive
controlled to change . power variation. Also, (25) indicates that the transmission re-
On the other hand, transferring the variables into the same active power flow can be controlled by or .
- frame as listed above and using (3), then (12) and (13) can be
D. Discussion

(20) It can be concluded from the analysis above that there are two
kinds of solutions to reach the control goals of obtaining proper
power-flow control and maintaining the UPFC bus voltage con-
where means the real power absorbed by stant. One is to control the real power flow with and re-
the series part of UPFC. Equation (20) indicates that should active power flow with , while maintaining the UPFC bus
vary with to meet the active power balance of the UPFC. So voltage constant by adjusting the shunt converter output reactive
a forward component including can be added to the dc-link current . The shunt converter real current is controlled
voltage controller of UPFC and make up a coordination con- to make UPFC dc-link voltage constant and maintain the real
troller. The details are given in the next section. power balance of the UPFC device. That is, the conventional

Authorized licensed use limited to: UNIVERSIDAD CENTRAL DE VENEZUELA. Downloaded on March 04,2010 at 15:24:55 EST from IEEE Xplore. Restrictions apply.
1616 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 3, JULY 2007

Fig. 2. Shunt converter control system diagram in the d–q frame.

Fig. 3. Series converter control system diagram in the d–q frame.

method is applied in the previous papers. However, according the series converter. In the -axis coordination control scheme,
to (7), (8), (19), and (25), a modified control scheme can be de- the transmission-line reactive power-flow variation reference is
veloped to reach the same control goal in a different way. Ac- added to the reactive power-flow PI regulator output with a
cording to (8) and (25), can be controlled to maintain the gain . So the shunt converter can generate an appropriate
UPFC bus voltage constant, and can be used to regulate amount of reactive power to compensate the reactive power-flow
the transmission reactive power. Equation (20) indicates modi- change with a quick response. Further, the inner control system
fied coordination control for dc-link voltage control. The rest of loops are fast-acting PI controllers and ensure fast supply of both
the control system is the same with the traditional one. Since the series converter real power demand and the reactive power
transmission-line reactive power is controlled directly, better needed for reactive power-flow control by the shunt converter.
dynamic response of transmission-line reactive power flow con-
trol is expected. Details of the proposed control diagram are IV. SERIES CONVERTER CONTROL SYSTEM
given in the next two sections. The series converter of the UPFC provides simultaneous con-
trol of the UPFC bus voltage and real power flow in the trans-
III. SHUNT CONVERTER CONTROL SYSTEM mission line. To do so, the series converter injected voltage is
In the proposed control strategy, the shunt converter of the decomposed into two components. The transformation is the
UPFC controls the reactive power flow in the transmission line same as that used in shunt converter control. The -axis injected
and dc-link voltage. The control diagram for the shunt part of component controls the UPFC bus voltage. The -axis-injected
the UPFC is shown in Fig. 2. The control scheme is composed component controls the transmission-line real power flow. The
of two loops—the outer loop and the inner loop. The outer loop detail of this control scheme is shown in Fig. 3. The whole con-
generates the current reference with coordination control, while trol system is composed of two loops as it is in the shunt con-
the inner current loop makes the shunt converter output the nec- verter. The outer loop generates the reference voltage signals
essary currents. The control system is based on the synchronous for the inner loop with coordination control. A current feed-
rotating – frame as mentioned before. The -axis current is forward is added to the -axis outer loop to compensate the
controlled to manage the dc-link voltage and balance the real voltage changes across the line impedance when there is a power
power of the UPFC. The -axis current is controlled to manage flow change. The inner control loop is a typical voltage–current
the transmission-line reactive power flow. The decoupled con- double-loop control scheme for inverters. The same decoupled
trol system [9] has been employed to achieve simultaneous con- control strategy as mentioned in [9] is applied here. With this
trol of the shunt converter input current. Coordination control method, the UPFC bus can be controlled directly and good per-
schemes are applied in both transmission-line reactive power formance is expected.
flow and dc-link voltage control to obtain better dynamic per-
formance. In the -axis coordination control scheme, is V. EXPERIMENTAL CONFIGURATION OF A UPFC
added to the output of the dc-link voltage regulator through a An experimental UPFC system has been built to test the pro-
gain , and it delegates the real power absorbed by posed control scheme as shown in Fig. 1. Recent advances in

Authorized licensed use limited to: UNIVERSIDAD CENTRAL DE VENEZUELA. Downloaded on March 04,2010 at 15:24:55 EST from IEEE Xplore. Restrictions apply.
LIU et al.: POWER-FLOW CONTROL PERFORMANCE ANALYSIS 1617

TABLE I
CIRCUIT PARAMETERS OF THE UPFC SYSTEM

high-voltage IGBT technology allow for higher switching fre-


quency with lower loss, and this allows for practical implemen-
tation of PWM control for high-power converters. So in the
experiment, both the shunt converter and the series converter
have been built as a three-phase PWM converter with IGBT
as the power device. The DSP TMS320F240 is selected as the
controller for both converters. The switching and sampling fre-
quency for the converters have been both chosen to be 5 kHz.
Both the shunt transformer and series transformer have a rating
of 7.5 kVA. The UPFC device is inserted into a transmission
line, and with the help of the UPFC, the power flow in the trans-
mission line can be controlled effectively while maintaining the Fig. 4. UPFC changes the line real power flow to +3 kW and back.
UPFC bus voltage constant. The parameters of the whole sys-
tems are given in Table I.
A series of experiments is employed to testify the control To maintain constant, the shunt converter absorbs about
scheme. All of the experimental result waveforms are recorded 2-kVAr reactive power , and the series converter output
by a Yokogawa DL750 scope recorder. The objectives for of about 2-kVAr reactive power to the line. That means
this experiment include the transmission-line real power flow the shunt part absorbs all of the reactive power output by the
( ), the transmission-line reactive power flow ( ), shunt series part to make constant and that leads to the amplitude
converter real power ( ), shunt converter reactive power of unaltered. The real power absorbed by the shunt
( ), series converter real power ( ), series inverter converter is 1 kW, and real power output by the series
reactive power ( ), UPFC bus voltage of phase A ( ), converter is about 800 W. That means the whole system loss is
and the transmission-line voltage of phase A controlled by the about 200 W.
series converter ( ), respectively, with UPFC in the proposed In Fig. 5, the UPFC is commanded to increase the line real
control scheme. power to kW, sustain it for a while, then decrease it to zero.
This is accomplished with about 180 phase shift of the injected
VI. EXPERIMENTAL RESULTS voltage, which makes the voltage lag by about 30 . The
shunt converter absorbs -kVAr reactive power that fits the
A. Case 1. UPFC Changing Real Power (Figs. 4 and 5) series converter output very well. And the real power absorbed
This case starts with the UPFC holding the transmission-line by the shunt part meets the series part output active power with
real and reactive power flow near zero. The series converter reg- a little difference.
ulates to 220 V during the real power-flow change. The ob- Throughout this test, the UPFC bus voltage is tightly reg-
jective for this test is to maintain the and constant, ulated a 220 V and the transmission-line reactive power flow
while making big step changes in . The experimental re- stays constant as zero.
sults are shown in Figs. 4 and 5.
In Fig. 4, the UPFC is commanded to increase the line real B. Case 2. UPFC Changing Reactive Power (Figs. 6 and 7)
power to 3 kW, sustain it for a while, and then decrease it to zero. The initial conditions for this test are similar to the case 1.
It does this by injecting a voltage in series to the transmission The objective of the test is to regulate the UPFC bus voltage at
line that makes the voltage leads about 30 ahead. 220 V and keep constant while making large steps in .

Authorized licensed use limited to: UNIVERSIDAD CENTRAL DE VENEZUELA. Downloaded on March 04,2010 at 15:24:55 EST from IEEE Xplore. Restrictions apply.
1618 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 3, JULY 2007

Fig. 5. UPFC changes the line real power flow to 03 kW and back. Fig. 6. UPFC changes the line reactive power flow to +2 kVAr and back.

In Fig. 6, the UPFC reference for is changed from 0 to In all cases, the dc-link voltage changes very little, which
2 kVAr then back to zero. The shunt part absorbs 3-kVAr proves the effectiveness of the coordination control scheme in
reactive power. The series part provides 1 kVAr. That means real power balance. The amplitude of the UPFC bus voltage
the shunt part provides all of the necessary reactive power for chases the reference tightly during the power flow changes. It
the transmission and series part. To maintain constant, the can be observed that with the proposed control scheme, the re-
injected voltage in series to the transmission line makes de- active power flow obtains better dynamic performance than real
crease to 136 V but in phase with . The shunt part absorbs power flow, and that is the advantage compared to the conven-
1-kW active power from the power system, and the series out- tional cross-coupling control scheme of UPFC.
puts active power is 800 W. The same system loss is shown as
in Fig. 4.
In Fig. 7, the reference is taken from 0 to 3 kVAr. In VII. CONCLUSION
this condition, the shunt converter absorbs about 2600 VAr and
the series converter delivers 400 VAr. increases to about This paper has presented a novel coordination controller for
281 V. The final step makes the reference return to zero. a UPFC. The basic control strategy is such that the shunt con-
In this case, the shunt part absorbs 1 kW from the power system verter of the UPFC controls the transmission-line reactive power
and the series part outputs 500 W. The whole system loss is and the dc-link voltage. The series converter controls the trans-
about 500 W. mission-line real power flow and the UPFC bus voltage. The
It is very interesting to note that the changes of shunt con- contributions of this work can be summarized as follows.
verter reactive power change the line reactive power al- Real, reactive power, and voltage balance of the UPFC system
most equally and effectively. It meets the analysis in Section II are analyzed. Two important results related to the UPFC control
perfectly. And it means that the shunt converter generates all of have been shown. First, it is indicated that the shunt converter
the necessary reactive power for the transmission-line reactive provides all of the required reactive power during the power flow
power-flow change and balances the reactive power output by changes if the UPFC bus voltage is constant. Second, the UPFC
the series converter. bus voltage can be controlled both from the sending side and

Authorized licensed use limited to: UNIVERSIDAD CENTRAL DE VENEZUELA. Downloaded on March 04,2010 at 15:24:55 EST from IEEE Xplore. Restrictions apply.
LIU et al.: POWER-FLOW CONTROL PERFORMANCE ANALYSIS 1619

[6] H. Fujita, Y. Watanabe, and H. Akagi, “Transient analysis of a unified


power flow controller and its application to design of the dc-link capac-
itor,” IEEE Trans. Power Electron., vol. 16, no. 5, pp. 735–740, Sep.
2001.
[7] S. Kannan, S. Jayaram, and M. M. A. Salama, “Real and reactive power
coordination for a unified power flow controller,” IEEE Trans. Power
Syst., vol. 19, no. 3, pp. 1454–1461, Aug. 2004.
[8] H. Fujita, Y. Watanabe, and H. Akagi, “Control and analysis of a uni-
fied power flow controller a,” IEEE Trans. Power Electron., vol. 14, no.
6, pp. 1021–1027, Nov. 1999.
[9] P. Zhu, X. Li, Y. Kang, and J. Chen, “A novel control scheme in
2-phase unified power quality conditioner,” in Proc. 29th Annu.
Conf. IEEE Industrial Electronics Soc., Nov. 2–6, 2003, vol. 2, pp.
1617–1622.

Liming Liu was born in Jiamusi, China, on October


12, 1975. He received the B.S. degree in applied
electronics and the M.S. degree in power electronics
and electric drives from Wuhan University, Wuhan,
China, in 1998 and 2003, respectively. He is cur-
rently pursuing the Ph.D. degree in power electronics
and electric drives at Huazhong University of Sci-
ence and Technology, Wuhan.

Pengcheng Zhu was born in Wuhan, China, on June


19, 1977. He received the B.S. degree in applied elec-
tronics and the M.S. and Ph.D. degrees in power elec-
tronics and electric drives from Huazhong University
of Science and Technology, Wuhan, in 1999, 2002,
and 2005, respectively.
Currently, he is working with the GE China R&D
Center, Shanghai.

Fig. 7. UPFC changes the line reactive power flow to 03 kVAr and back.
Yong Kang was born in Hubei, China, on October
16, 1965. He received the B.S., M.S., and Ph.D.
from the receiving-end side. Inclusion of the real power coor- degrees from Huazhong University of Science and
Technology, Wuhan, China, in 1988, 1991, and
dination controller in the UPFC control system avoids exces- 1994, respectively.
sive dc-link voltage excursions and improves its recovery during In 1994, he joined Huazhong University of Science
transient conditions. and Technology as a Lecturer. In 1996, he was pro-
moted to Associate Professor. In 1998, he became
Experiments have been conducted to verify the effectiveness Full Professor. He is the author of many technical
of the proposed control strategy. papers. His research interest focuses on power-elec-
tronic converters, ac drives, electromagnetic compat-
ibility (EMC), and their digital control techniques.
REFERENCES
[1] J. H. R. Enslin, J. Zhao, and R. Spee, “Operation of the unified power
flow controller as harmonic isolator,” IEEE Trans. Power Electron., vol.
11, no. 6, pp. 776–784, Nov. 1996. Jian Chen (SM’96) was born in Wuhan, China,
[2] L. Dong, M. L. Crow, Z. Yang, C. Shen, L. Zhang, and S. Aticitty, “A on Aug 27, 1935. He graduated from Zhengzhou
reconfigurable FACTS system for university laboratories,” IEEE Trans. Electrical Engineering School and the Department
Power Syst., vol. 19, no. 1, pp. 120–128, Feb. 2004. of Electrical Engineering of Huazhong Institute of
[3] M. Rahman, M. Ahmed, R. Gutman, and R. J. O’Keefe, “UPFC ap- Technology, Wuhan, in 1954 and 1958, respectively.
plication on the AEP system: Planning considerations,” IEEE Trans. He has been with Huazhong Institute of Tech-
Power Syst., vol. 12, no. 4, pp. 1695–1701, Nov. 1997. nology (now Huazhong University of Science
[4] C. Shauder, E. Stacey, M. Lund, A. Keri, A. Mehraban, and A. Edris, and Technology) since 1958. He was promoted to
“AEP UPFC project: Installation, commissioning and operation of the Lecturer in 1963 and Associate Professor in 1978.
6 160 MVA STATCOM (Phase I),” IEEE Trans. Power Del., vol. 13, He has studied power electronics, microprocessors,
no. 4, pp. 1530–1535, Oct. 1998. and their applications at the University of Toronto
[5] B. a. Renz, A. Keri, A. S. Mehraban, C. Shauder, E. Stacey, L. Ko- as a Visiting Scholar from 1980 to 1982. In 1985, he became a Full Professor.
valsky, L. Gyugyi, and A. Edris, “AEP unified power flow controller He is an author of three textbooks and many technical papers. His main
performance,” IEEE Trans. Power Del., vol. 14, no. 4, pp. 1374–1381, research interests include various power-electronic converters, ac drives, and
Oct. 1999. power-electronics applications in electric power systems.

Authorized licensed use limited to: UNIVERSIDAD CENTRAL DE VENEZUELA. Downloaded on March 04,2010 at 15:24:55 EST from IEEE Xplore. Restrictions apply.

You might also like