Professional Documents
Culture Documents
6, Bologna, Italy
Abstract - The deregulation of electricity supply industry has 11. UPFC STEADY - S rATE MO DEL
introduced new opportunity for competition to reduce the cost
The Unified Power Flow Controlbr is the inost versatile and
and cut the price. It is a tremendous challenge for utilities to
maintain an economical and reliable supply in such an complex power electronic equipment that hrrs emerged for the
environment. The PFAC program developed by authors to control and optimization of power lilow and voltage in electric
analyze the power flow in power systems with FACTS devices, power transmission systems. It consists of two back-to-back,
has been tested on the 22OkV-4OOkV network of the Romanian self-commutated, voltage source converters, sharing a shunt
Power Grid. We have taken into consideration several possible capacitor on the DC side [l].Ont: converter is coupled to the
scenarios, leading to two types of congestions: the first type is AC system via a shunt transformer and the other is coupled to
related to nodal power release, and the second to the supply of a the AC system via a series transfornier (Figure 1).
deficit area. Simulations prove the fact that in both cases we can
regulate power flow so that to reduce and eliminate congestions if uk
we use the UPFC device.
Transmission
Keywords: Congestions management, UPFC device. k .Line
Line .i
I. INTRODUCTION
s the energy market is becoming increasingly free, and
A there are more and more open access power systems,
load flow and congestions management is becoming of more
importance as well. Under these circumstances, the paper
t Y--
proposes the implementation of UPFC (Unified Power Flow UPFC Controller
Controller), which is the most efficient FACTS device in this Fig 1 Block diagram oi’ii UPFC device
kind of applications. The first part presents the steady-state
model of the UPFC device and implementation in the PFAC The series converter is control1e:cl to injetzt a synchronous
(Power Flow Analysis and Control) software, developed in voltage in series with the transmission line. In the process of
Visual C t t , using the OOP technology and the Newton- doing this, the series converter will exchange real and reactive
Raphson method. In the second part, this program has been power with the line. The series inverter electronically provides
the reactive power and the real power is transmitted to the DC
used on the 220kV - 400kV network of the Romanian Power
terminals. The shunt inverter is oporated in such a way as to
Grid (SEN). Thus, starting from a base case (a steady-state
demand this DC terminal power (positive or negative) from the
power flow), we have examined 5 other operating modes that
line, thereby regulating the voltage of the DC‘ bus. The net real
could appear in the current operation. Besides, for each new
power absorbed fiom the line by the UPFC i!; thus equal to the
case, we have considered a few incidents that should lead to losses of the two converters and their transformers. Assuming
congestions related to nodal power release and, respectively, a free loss converter operation, the UPFC neither absorbs nor
power supply for a deficient part of the system. The results injects active power with respect to the AC system. Hence, the
obtained by using the UPFC device, which function as real active power supplied to the shunt converter Po, must satisfy
“electronically controlled locks”, prove the fact that we can the active power demanded by the series converter, Ps
redistribute power flow in order to eliminate congestions, thus [3][4][6].The equivalent circuit consists of two ideal voltage
keeping SEN in h c t i o n in normal parameters and to sources USand U, representing the limdameiital Fourier series
increasing reliability and flexibility. component of the switched vo1tq:e waveforms at the AC
converter terminals (Figure 2). The soiurce impedances
C. Bulac is with the Department of Power Engineering POLITEHNICA
included in the model represent the positive sequence leakage
University of Bucharest, Romania (e-mail: cbulac@yahoo.com). inductances and resistances of the coupling UPFC
M. Eremia is with the Department of Power Engineering POLITEHNICA transformers. Although the UPFC I h i ~many possible operating
University of Bucharest, Romania (email: eremial@yahoo.com). modes, we will consider that the shunt converter will be
R. Balaurescu and V. Stefanescu are with the TRANSELECTRICA operated in automatic voltage coinlrol - AI% mode and the
Company, Romania
series converter will be in automatic power flow control -
02003 IEEE
0-7803-7967-5/03/$17.00
APFC mode [ 5 ] . In these modes the shunt converter reactive active power supplied by the shunt inverter
current is automatically regulated to maintain the transmission Po = Re(bDZL)=
line voltage at the point of connection (bus k) to a reference (5)
value, while the series injected voltage is determined u,u,[G, COS (e, -ek)+B, sin@, -~,)]-u;G,
automatically and continuously by a vector control system to
active power supplied by the series inverter
ensure that the desired active and reactive powers are
maintained despite system changes. Ps =Re(b,l$)=
UsUk [G, COS (e, - e, ) + B, sin@, - e, )]- (6)
U,U,[G, cos (0, - B j ) + B, sin(8, - 0 , ) ] - U i G ,
1
modified according with equation (7), and the strategy of
control eauations, with resuect to unknowns
TABLE I
OPERATING
ANALYZED MODESAND CONTINGENCES
Case Changes from RO case Incident Load flowKongestion of
RO Normal operating scheme with power flow in acceptable Overloading of the operating circuit
limits. transmission ling24-57 by 0.8%
R1 Production increases by approx. 210 M W in bus 24. Overloading of the operating circuit of
Tripp of one circuit from transmission ling24-57 by 5%
R2 400kV transmissionline 14-15 is tripped.
~~
220kV power line 24-57 Overloading of the operating circuit of
I
-
(bus 423). followine the withdrawal of a local uower
generator. 400kV transmission line 14-15 is tripped.
transmission lire 24-57 by 14.2%
m
$,fl
(571
4 2
RI R2 R3
Fig.4. Power flow (MW-MVAr) in the neighbourhood of buse 24.
m
(FACTS]
63 TO
0
0
0
RI R2 R3
Fig. 5. Power flow (MW-MVAr) in the neighbourhood of buse 24 the presence of an UPFC
TABLE Il
Controller Regime Scheduled line power Load Steady state of FACTS controller
P [ m Q[MVAr] Line 24-57 AT 14-24 US [p.u] €Is [deg] UO [ p . ~ ] e0 [deg]
RI 310 60 96.40 97.30 0.2488 -108.69 0.9295 5.16
UPFC R2 250 60 76.11 71.50 0.1514 -188.70 1.0760 2.48
R3 250 60 76.50 71.50 0.1825 142.3744 1.0942 2.08
Fig.6. Power flow (MW-MVAr) on 220kV lines for operating mode R5