SALA: C2-3830-ER-047 PROTOCOLO DE SEÑALES PUNTO A PUNTO SISTEMA EMS FECHA: 17/02/2022

TAG: A223880FPR04D Proyecto: SAND BOOSTER PUMP UPGRADE PHASE II

IED: REF630

61850 MMS
LN REFERENCE IEC DATA REFERENCE OPC
DESIGNACIÓN DESCRIPCIÓN LD
PREFIJO CLASE INS CLASE DO DA FC
AREA NAME:
Contactor Status (4.16kV) Estado de Interruptor
CB_OPEN (MAX Relay NC) Posicion Abierto Interruptor LD0 SP GGIO 16 SPS Ind stVal ST OK
CB_CLOSED (MAX Relay NO) Posicion Cerrado Interruptor LD0 SP GGIO 17 SPS Ind stVal ST OK
Ready and Healthy (Ready NO) Listo y permisivo LD0 SP GGIO 18 SPS Ind stVal ST OK
Contactor - Close Blocking (86) Bloqueo 86 LD0 TRP PTRC 1 SPS clsLO stVal ST NA
24VDC PowerTrip (NC) LD0 SP GGIO 26 SPS Ind stVal ST OK
Local Status Posicion local relé LD0 QCC BAY 1 SPS Loc stVal ST OK
Remote Status Posicion remoto relé LD0 QCC BAY 1 SPS Rem stVal ST OK
Transformer Signals Indicaciones generales
Sudden Pressure Trip (NC) Sudden Pressure LD0 SP GGIO 20 SPS Ind NA
Oil Temp Trip (NC) Temp Trip LD0 SP GGIO 21 SPS Ind NA
Oil Level Alarm (NC) Level Alarm Max LD0 SP GGIO 24 SPS Ind NA
Oil Temp Alarm (NC) Temp Alarm LD0 SP GGIO 23 SPS Ind NA
Oil Level Alarm / Min (NC) Level Alarm Min LD0 SP GGIO 27 SPS Ind NA
Sudden Gas Pressure Alarm (NC) Sudden Pressure LD0 SP GGIO 25 SPS Ind NA
Presure Relief Trip (NC) Pressure Relief LD0 SP GGIO 28 SPS Ind NA
Flame Detector * Flama LD0 SP GGIO 9 SPS Ind NA
Protection Signals
51 3l> Trip 51P-1 Disparo Sobrecorriente Temporizada de Fase LD0 PHL PTOC 1 ACT Op OK
51 3l> Start 51P-1 Arranque Sobrecorriente Temporizada de Fase LD0 PHL PTOC 1 ACD Str OK
50 3l>>> Trip 50P - Disparo Sobrecorriente Instantáneo de Fase LD0 PHI PTOC 1 ACD Op NA
51 3l>>> Start StartSignalFromGeneral LD0 PHI PTOC 1 ACT Str NA
51N l0> Trip 51N - Disparo Sobrecorriente de Tierra LD0 EFL PTOC 1 ACT Op OK
51N l0> Start 51N - Arranque Sobrecorriente de Tierra LD0 EFL PTOC 1 ACD Str OK
50N l0>> Trip 50N - Disparo Sobrecorriente Instantáneo de Tierra LD0 EFI PTOC 1 ACT Op NA
50N l0>> Start 50N - Arranque Sobrecorriente Instantáneo de Tierra LD0 EFI PTOC 1 ACD Str NA
3-Ph Overvoltage Alarm 59 - Disparo sobretensión trifásica LD0 PHP TOV 1 ACT Op NA
StartSignalFromGeneral LD0 PHP TOV 1 ACD Str
3-Ph Undervoltage Alarm 27 - Disparo subtensión trifásica LD0 PHP TUV 1 ACT Op NA
Contactor Failure Protection OpExt CCBRBRF LD0 CCB RBRF 1 ACT OpIn NA
LD0 CCB RBRF 1 ACT OpEx
Measurements Medidas
Current L1 [A] Corriente R [A] LD0 CPH MMXU 1 WYE A.phsA cVal.mag.f MX OK
Current L2 [A] Corriente S [A] LD0 CPH MMXU 1 WYE A.phsB cVal.mag.f MX OK
Current L3 [A] Corriente T [A] LD0 CPH MMXU 1 WYE A.phsC cVal.mag.f MX OK
Current L0 [A] Corriente Residual [A] LD0 RESC MMXU 1 WYE A.res .phsA cVal.mag.f MX OK
Current L0 [A] Corriente Residual [A] LD0 RESC MMXU 1 WYE A.res.phsB cVal.mag.f MX OK
Current L0 [A] Corriente Residual [A] LD0 RESC MMXU 1 WYE A.res.phsC cVal.mag.f MX OK
Voltage UL12 UM-A [kV] Voltaje RS [kV] LD0 VPP MMXU 1 DEL PPV.phsAB cVal.mag.f MX OK
Voltage UL23 UM-A [kV] Voltaje ST [kV] LD0 VPP MMXU 1 DEL PPV.phsBC cVal.mag.f MX OK
Voltage UL31 UM-A [kV] Voltaje TR [kV] LD0 VPP MMXU 1 DEL PPV.phsCA cVal.mag.f MX OK
Voltage UL1 [kV] Voltaje R [kV] LD0 VPH MMXU 1 WYE PhV.phsA cVal.mag.f MX OK
Voltage UL2 [kV] Voltaje S [kV] LD0 VPH MMXU 1 WYE phV.PhsB cVal.mag.f MX OK
Voltage UL3 [kV] Voltaje T [kV] LD0 VPH MMXU 1 WYE phV.PhsC cVal.mag.f MX OK
Frecuency [Hz] Frecuencia [Hz] LD0 PWR MMXU 1 MV Hz mag.f MX OK
Active power [kW] Potencia activa [kW] LD0 PWR MMXU 1 MV TotW mag.f MX OK
Reactive power [kVAR] Potencia reactiva [kVAR] LD0 PWR MMXU 1 MV TotVar mag.f MX OK
Power factor [Cosphi] Factor de potencia [Cosphi] LD0 PWR MMXU 1 MV TotPF mag.f MX OK
Apparent power [kVA] Potencia aparente [kVA] LD0 PWR MMXU 1 MV TotVA mag.f MX OK
Active Energy Forward [kW-h] Energía Activa Forward [kW-h] LD0 MV GGIO 1 MV AnIn mag.f MX NA
Active Energy Backward [kW-h] Energía Activa Backward [kW-h] LD0 MV GGIO 2 MV AnIn mag.f MX NA
Reactive Energy Forward [kVAR-h] Energía Reactiva Forward [kVAR-h] LD0 MV GGIO 3 MV AnIn mag.f MX NA
Reactive Energy Backward [kVAR-h] Energía Reactiva Backward [kVAR-h] LD0 MV GGIO 4 MV AnIn mag.f MX NA