Professional Documents
Culture Documents
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting
up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous
and requires specific knowledge and training. Improperly installed, adjusted or altered
equipment by an unqualified person could result in death or serious injury. When working on
the equipment, observe all precautions in the literature and on the tags, stickers, and labels
that are attached to the equipment.
MS-SVM13A-EN
Warnings, Cautions and Notices
Warnings, Cautions and Notices. Note that warnings, cautions and notices appear at
appropriate intervals throughout this manual. Warnings are provided to alert installing
contractors to potential hazards that could result in personal injury or death, while cautions are
designed to alert personnel to conditions that could result in equipment damage.
Your personal safety and the proper operation of this machine depend upon the strict
observance of these precautions.
WARNING: Indicates a potentially hazardous situation which, if not avoided, could result
in death or serious injury.
CAUTION: Indicates a potentially hazardous situation which, if not avoided, could result
in minor or moderate injury. It could also be used to alert against unsafe practices.
WARNING
Ground Required!
Follow proper local electrical code on requirements for grounding. Failure to follow code could
result in death or serious injury.
WARNING
The units described in this manual use R-410A refrigerant which operates at 50 to 70% higher
pressures than R-22. Use only R-410A approved service equipment. Refrigerant cylinders are
painted with “pink” color to indicate the type of refrigerant and may contain a “dip” tube to allow
for charging of liquid refrigerant into the system. For specific handling concerns with R-410A,
please contact your local Trane representative.
Failure to use R-410A approved service equipment could result in standard equipment
exploding under R-410A higher pressure which could result in death or serious injury.
2
NOTICE
All R-410A mini-split units use a PVE oil (Polyvinyl Ether Oil) that readily absorbs moisture from
the atmosphere. To limit this “hygroscopic” action, the system should remain sealed whenever
possible. If a system has been opened to the atmosphere for more than 4 hours, the
compressor oil must be replaced. Never break a vacuum with air and always change the driers
when opening the system for component replacement. For specific handling concerns with PVE
oil, contact your local Trane representative.
Use ONLY THE FACTORY RECOMMENDED – DAFNE HERMETIC OIL FV50S – for servicing
these units.
IMPORTANT
Environmental Concerns!
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally
occurring stratospheric ozone layer when released to the atmosphere. In particular, several of
the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine,
Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon
(HCFCs). Not all refrigerants containing these compounds have the same potential impact to
the environment. Trane advocates the responsible handing of all refrigerants – including
industry replacements for CFCs such as HCFCs and HFCs.
Trane believes that responsible refrigerant practices are important to the environment, our
customers, and the air conditioning industry. All technicians who handle refrigerant must be
certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in
these service procedures. In addition, some states or municipalities may have additional
requirements that must also be adhered to for responsible management of refrigerants. Know
the applicable laws and follow them.
3
Contents
General Information .…………………………………………………………………. 5
Specifications
Indoor Units ……………………………………………………………………… 6
Outdoor Units ……………………………………………………………………. 13
Performance Data ………………………………………………………………. 15
Dimensions
Indoor Units ……………………………………………………………………… 23
Outdoor Units ……………………………………………………………………. 27
Wiring Diagrams
Indoor Units ……………………………………………………………………… 28
Outdoor Units ………………………………………………………………….... 32
Trouble Shooting
General Sections ……………………………………………………………….. 91
Error Code Descriptions ……………………………………………………….. 96
4
General Information
This installation manual is given as a guide to good practices in the installation and operation of
the Trane U-Match split models. However, it does not contain all the service procedures for the
systems, as these procedures must be performed by a qualified service technician, through the
maintenance contract with a reputable service company.
Read these operation instructions completely before servicing the unit.
Warranty
Warranty is based on the general terms and conditions by country. The warranty is void if the
equipment is modified or repaired without the written approval of The Trane Company, if the
operating limits are exceeded or if the control system or the electrical wiring is modified.
Damage due to inappropriate installation, lack of knowledge or failure to comply with the
manufacturer’s instructions, is not covered by the warranty obligation.
If the installation does not conform to the rules described in the Installation Manual, it may entail
cancellation of warranty and liabilities by The Trane Company.
Reception
On arrival, inspect the unit before signing the delivery note. Specify any damage of the unit on
the delivery note, and send a registered letter of protest to the last carrier of the goods within 72
hours of delivery. Nofity the dealer at the same time.
The unit should be totally inspected within 7 days of delivery. If any concealed damage is
discovered, send a registered letter of protest to the carrier within 7 days of delivery and notify
the local dealer.
Refrigerant
The refrigerant provided by the manufacturer complies with all the requirements for the units.
When using a recycled or reprocessed refrigerant, we recommend its qualities be as good as
those of a new refrigerant. It is necessary to have the refrigerant tested by a qualified laboratory.
Failure to do so could void the warranty.
Important
These instructions do not cover all variations in systems, nor do they provide for every possible
contingency to be met in connection with installation. Should further information be desired or
should particular problems arise which are not covered sufficiently in this manual, the matter
should be referred to your authorized Trane dealer.
5
Indoor Unit Specifications – Concealed
Model 4MXD3512BB 4MXD3518BB 4MXD3524BB
Power Connection
Rated Voltage 220 - 240 ~ 1ph 220 - 240 ~ 1ph 220 - 240 ~ 1ph
Frequency(Hz) 50Hz 50Hz 50Hz
Fuse (A) 5 5 5
Indoor Fan
Air Flow Volume (m3/h) (H/M/L) 840 / 740 / 640 1000 / 800 / 600 1600 / 1400 / 1200
Fan Motor Speed (r/min) (H/M/L) 1110 / 1000 / 910 1310 / 1160 / 1060 1250 / 1220 / 1060
Output of Fan Motor (w) 60 70 150
Fan Motor Capacitor (uF) 2.5 3.5 8
Fan Motor RLA(A) 0.46 1.38 1.65
Fan Type-No. Used Centrifugal fan - 1 Centrifugal fan - 2 Centrifugal fan - 2
Diameter-Length (mm) Ø155 - 175 Ø155 - 175 Ø160 - 201
Indoor Coil
Evaporator Aluminum fin - copper Aluminum fin - copper Aluminum fin - copper
tube tube tube
Pipe Diameter (mm) Ø7 Ø7 Ø9.52
Row-Fin Gap(mm) 3 - 1.6 3 - 1.6 2 - 1.8
Coil length (l) x height (H) x coil width (L) 718 x 254 x 25.4 718 x 254 x 25.4 1002 x 252 x 43
Swing Motor
Swing Motor Model / / /
Output of Swing Motor (W) / / /
6
Indoor Unit Specifications ‐ Concealed
Model 4MWD0536BB 4MWD0548BB 4MWD0560BB
Power Connection
Rated Voltage 380 - 415 ~ 3ph 380 - 415 ~ 3ph 380 - 415 ~ 3ph
Frequency(Hz) 50Hz 50Hz 50Hz
Fuse (A) 5 5 5
Indoor Fan
Air Flow Volume (m3/h) (H/M/L) 2000 / 1900 / 1800 2300 / 2110 / 1850 2500 / 2070 / 1730
Fan Motor Speed (r/min) (H/M/L) 1320 / 1090 / 910 1320 / 1090 / 910 1320 / 1090 / 910
Output of Fan Motor (w) 500 500 500
Fan Motor Capacitor (uF) 12 12 12
Fan Motor RLA(A) 6.71 6.71 6.71
Fan Type-No. Used Centrifugal fan - 2 Centrifugal fan - 2 Centrifugal fan - 2
Diameter-Length (mm) Ø200 - 190 Ø200 - 190 Ø200 - 190
Indoor Coil
Evaporator Aluminum fin - copper Aluminum fin - copper Aluminum fin - copper
tube tube tube
Pipe Diameter (mm) Ø7 Ø9.52 Ø9.52
Row-Fin Gap(mm) 3 - 1.6 3 - 1.8 4 - 1.8
Coil length (l) x height (H) x coil width (L) 980 x 317.2 x 38.1 980 x 317.2 x 66 985 x 368 x 88
Swing Motor
Swing Motor Model / / /
Output of Swing Motor (W) / / /
7
FAN CHARACTERISTICS
12 MBH concealed unit
700 400
600
Air Flow (m3/h)
1200 700
600
500 H-Speed
800 M—Speed 400
600 M-Speed M-Speed
300
L-Speed 200 L-Speed
400
100
200 0
0 0
02
04
06
08
10
12
14
16
18
20
0 5 10 15 20 25 30 35 40 45 50 0.
0.
0.
0.
0.
0.
0.
0.
0.
0.
External Static Pressure (Pa) External Static Pressure(in.wg)
1900
1700 1100
Air Flow (m3/h)
Air Flow(CFM)
1500
H-speed 900 H-speed
1300
M-speed M-speed
1100
L-speed L-speed
900 700
700
500 500
0 5 10 15 20 25 30 35 40 45 50
0
02
04
06
08
10
12
14
16
18
20
0.
0.
0.
0.
0.
0.
0.
0.
0.
0.
2400 1500
2200
Air Flow (m3/h)
Air Flow(CFM)
2000 1300
H-speed H-speed
1800
1600 M-speed M-speed
L-speed 1100
1400 L-speed
1200
1000 900
0 5 10 15 20 25 30 35 40 45 50
0
02
04
06
08
10
12
14
16
18
20
0.
0.
0.
0.
0.
0.
0.
0.
0.
0.
3000 1800
1700
Air Flow(CFM)
Air Flow (m3/h)
1600
2500 1500 H-speed
H-speed
1400 M-speed
2000 M-speed 1300 L-speed
L-speed 1200
1500 1100
1000
1000
04
08
12
16
24
28
32
36
0
4
0.
0.
0 10 20 30 40 50 60 70 80 90 100
0.
0.
0.
0.
0.
0.
0.
0.
8
Indoor Unit Specifications – Cassette
Model 4MXC3512BB 4MXC3518BB 4MXC3524BB
Power Connection
Rated Voltage 220 - 240 ~ 1ph 220 - 240 ~ 1ph 220 - 240 ~ 1ph
Frequency(Hz) 50Hz 50Hz 50Hz
Fuse (A) 3.15 3.15 3.15
Indoor Fan
Air Flow Volume (m3/h) (H/M/L) 550 / 450 / 350 1180 / 1080 / 1000 1400 / 1270 / 1170
Fan Motor Speed (r/min) (H/M/L) 820 / 710 / 620 600 / 550 / 500 670 / 620 / 570
Output of Fan Motor (w) 11 35 40
Fan Motor Capacitor (uF) 2.5 3.5 3.5
Fan Motor RLA(A) 0.23 0.47 0.69
Fan Type-No. Used Centrifugal fan - 1 Centrifugal fan - 1 Centrifugal fan - 1
Diameter-Length (mm) Ø282 - 147 Ø450 - 142 Ø450 - 142
Indoor Coil
Evaporator Aluminum fin - copper Aluminum fin - copper Aluminum fin - copper
tube tube tube
Pipe Diameter (mm) Ø9.52 Ø9.52 Ø9.52
Row-Fin Gap(mm) 2 - 1.5 2 - 1.5 2 - 1.5
Coil length (l) x height (H) x coil width (L) 444.2 x 203.8 x 38.1 1965 x 171.5 x 25.4 1965 x 171.5 x 25.4
Swing Motor
Swing Motor Model MP35EA SM008 SM008
Output of Swing Motor (W) 2 3 3
9
Indoor Unit Specifications – Cassette
Model 4MWC0536BB 4MWC0548BB
Power Connection
Rated Voltage 380 - 415 ~ 3ph 380 - 415 ~ 3ph
Frequency(Hz) 50Hz 50Hz
Fuse (A) 3.15 3.15
Indoor Fan
Air Flow Volume (m3/h) (H/M/L) 1660 / 1570 / 1500 1660 / 1570 / 1500
Fan Motor Speed (r/min) (H/M/L) 710 / 660 / 610 710 / 660 / 610
Output of Fan Motor (w) 60 60
Fan Motor Capacitor (uF) 4.5 4.5
Fan Motor RLA(A) 0.79 0.79
Fan Type-No. Used Centrifugal fan - 1 Centrifugal fan - 1
Diameter-Length (mm) Ø476 - 169.5 Ø476 - 169.5
Indoor Coil
Evaporator Aluminum fin - copper Aluminum fin - copper
tube tube
Pipe Diameter (mm) Ø7 Ø7
Row-Fin Gap(mm) 2 - 1.4 2 - 1.4
Coil length (l) x height (H) x coil width (L) 2900 x 171.5 x 25.4 2900 x 171.5 x 25.4
Swing Motor
Swing Motor Model SM008 SM008
Output of Swing Motor (W) 3 3
10
Indoor Unit Specifications – Convertible
Model 4MXX3512BB 4MXX3518BB 4MXX3524BB
Power Connection
Rated Voltage 220 - 240 ~ 1ph 220 - 240 ~ 1ph 220 - 240 ~ 1ph
Frequency(Hz) 50Hz 50Hz 50Hz
Fuse (A) 5 5 5
Indoor Fan
Air Flow Volume (m3/h) (H/M/L) 700 / 600 / 500 900 / 800 / 700 1200 / 1050 / 900
Fan Motor Speed (r/min) (H/M/L) 790 / 690 / 580 875 / 770 / 660 1200 / 1000 / 880
Output of Fan Motor (w) 15 20 50
Fan Motor Capacitor (uF) 1 2 2
Fan Motor RLA(A) 0.21 0.28 0.42
Fan Type-No. Used Centrifugal fan - 2 Centrifugal fan - 4 Centrifugal fan - 4
Diameter-Length (mm) Ø137 - 104 Ø137 - 104 Ø137 - 104
Indoor Coil
Evaporator Aluminum fin - copper Aluminum fin - copper Aluminum fin - copper
tube tube tube
Pipe Diameter (mm) Ø8 Ø7 Ø7
Row-Fin Gap(mm) 2 - 1.4 2 - 1.4 3 - 1.6
Coil length (l) x height (H) x coil width (L) 920 x 304 x 25.4 920 x 304 x 25.4 920 x 304 x 25.4
Swing Motor
Swing Motor Model MP35CG MP35CG MP35CG
Output of Swing Motor (W) 3 3 3
11
Indoor Unit Specifications – Convertible
Model 4MWX0536BB 4MWX0548BB
Power Connection
Rated Voltage 380 - 415 ~ 3ph 380 - 415 ~ 3ph
Frequency(Hz) 50Hz 50Hz
Fuse (A) 5 5
Indoor Fan
Air Flow Volume (m3/h) (H/M/L) 1800 / 1630 / 1520 2100 / 1900 / 1800
Fan Motor Speed (r/min) (H/M/L) 1100 / 1000 / 930 1320 / 1280 / 1240
Output of Fan Motor (w) 85 85
Fan Motor Capacitor (uF) 6 10
Fan Motor RLA(A) 0.5 0.8
Fan Type-No. Used Centrifugal fan - 4 Centrifugal fan - 4
Diameter-Length (mm) Ø155 - 175 Ø155 - 175
Indoor Coil
Evaporator Aluminum fin - copper Aluminum fin - copper
tube tube
Pipe Diameter (mm) Ø7 Ø7
Row-Fin Gap(mm) 3 - 1.6 3 - 1.6
Coil length (l) x height (H) x coil width (L) 1340 x 228.6 x 38.1 1340 x 228.6 x 38.1
Swing Motor
Swing Motor Model MP35CA MP35CA
Output of Swing Motor (W) 2 2
12
Outdoor Unit Specifications
Model 4TXK3512BB 4TXK3518BB 4TXK3524BB
Power Connection
Rated Voltage 220 - 240 ~ 1ph 220 - 240 ~ 1ph 220 - 240 ~ 1ph
Frequency (Hz) 50Hz 50Hz 50Hz
Climate Type T1 T1 T1
Isolation I I I
Moisture Protection IP24 IP24 IP24
Compressor
Compressor Manufacturer/trademark LINDA MITSUBISHI
Compressor Model QXA-A104zC190A TNB220FLHMC
Compressor Type Rotary Rotary Rotary
L.R.A. (A) - - -
Compressor RLA (A) 4.8 9.7
Compressor Power Input (W) 1070 2200
Overload Protector External Overload External Overload
ZE3.604.002
Protector Protector
Throttling Method Capillary Electronic expansion Electronic expansion
valve valve
Starting Method Direct Direct Direct
Coil
Condenser Aluminum fin - copper Aluminum fin - copper Aluminum fin - copper
tube tube tube
Pipe Diameter (mm) Ø7.94 Ø7.94
Rows-Fin Gap (mm) 2 - 1.4 2 - 1.4 2 - 1.4
Coil length (l) x height (H) x coil width (W) 595 x 508 x 38.1 823 x 660 x 38.1 1030 x 748 x 38.1
Permissible Excessive Operating 4.2 4.2 4.2
Pressure for the Discharge Side (MPa)
Permissible Excessive Operating 1.5 1.5 1.5
Pressure for the Suction Side (MPa)
Defrosting Method Auto defrost Auto defrost Auto defrost
Fan
Fan Motor Speed (rpm) 850 690 780
Output of Fan Motor (W) 30 60 90
Fan Motor RLA(A) 0.5 0.8 1.14
Fan Motor Capacitor (uF) 2.5 3.5 7
Air Flow Volume of Outdoor Unit m3/h 2400 3800
Fan Type-Piece Axial fan – 1 Axial fan – 1 Axial fan – 1
Fan Diameter (mm) Ø401 Ø520 Ø552
Sound Data
Sound Pressure Level dB (A) (H/M/L) 54 59
Sound Power Level dB (A) (H/M/L) 64 69
Dimensions and Weight
Dimension (W/D/H) ( mm) 776 x 320 x 540 955 x 396 x 700 980 x 427 x 790
Dimension of Package (W/L/H)( mm) 848 x 360 x 580 1026 x 455 x 735 1080 x 485 x 840
Net Weight /Gross Weight (kg) 30 / 34 65 / 70
Refrigerant Charge (kg) 1.35 2.4
Connection Pipe
Length (m) 5 5 5
Gas additional charge(g/m) 30 30 60
Outer Diameter (liquid line) Ø1/4" Ø1/4" Ø3/8"
(suction line) Ø3/8" Ø1/2" Ø5/8"
Max Distance Height (m) 15 15 15
Length (m) 20 20 30
13
Outdoor Unit Specifications
Model 4TWK0536BD 4TWK0548BD 4TWK0560BD
Power Connection
Rated Voltage 380 - 415 ~ 3ph 380 - 415 ~ 3ph 380 - 415 ~ 3ph
Frequency(Hz) 50Hz 50Hz 50Hz
Climate Type T1 T1 T1
Isolation I I I
Moisture Protection IP24 IP24 IP24
Compressor
Compressor Manufacturer/trademark SANYO DAIKIN SANYO
Compressor Model C-SBN303H8D JT170G-P8Y1 C-SBN453H8D
Compressor Type Scroll Scroll Scroll
L.R.A. (A) 67 59.4 67
Compressor RLA(A) 6.58 8.9 9.77
Compressor Power Input(W) 3650 4500 5750
Overload Protector / / /
Throttling Method Capillary Capillary Capillary
Starting Method Direct Direct Direct
Coil
Condenser Aluminum fin - copper Aluminum fin - copper Aluminum fin - copper
tube tube tube
Pipe Diameter (mm) Ø9.52 Ø9.52 Ø9.52
Rows-Fin Gap(mm) 2 - 1.4 2 - 1.8 3 - 1.8
Coil length (l) x height (H) x coil width (W) 947 x 813 x 44 738 x 1218 x 44 1218 x 898 x 66
Permissible Excessive Operating Pressure 4.4 4.4 4.4
for the Discharge Side(MPa)
Permissible Excessive Operating Pressure 0.9 0.9 0.9
for the Suction Side(MPa)
Defrosting Method Auto defrost Auto defrost Auto defrost
Fan
Fan Motor Speed (rpm) 920 / 780 940 940
Output of Fan Motor (W) 92 92 92
Fan Motor RLA(A) 2.1 2.4 1.74
Fan Motor Capacitor (uF) 4 4 6
Air Flow Volume of Outdoor Unit m3/h 1610 2300 2500
Fan Type-Piece Axial fan – 1 Axial fan – 2 Axial fan – 2
Fan Diameter (mm) Ø482 Ø472 Ø472
Sound Data
Sound Pressure Level dB (A) (H/M/L) 60 63 64
Sound Power Level dB (A) (H/M/L) 70 73 74
Dimensions and Weight
Dimension (W/D/H) ( mm) 1018 / 412 / 840 1032 / 412 / 1250 1032 / 412 / 1250
Dimension of Package (W/L/H)( mm) 1100 / 450 / 985 1110 / 450 / 1385 1110 / 450 / 1385
Net Weight /Gross Weight (kg) 90 / 100 112 / 123 123 / 134
Refrigerant Charge (kg) 3.2 3.8 5.0
Connection Pipe
Length (m) 5 5 5
Gas additional charge(g/m) 120 120 120
Outer Diameter (liquid line) Ø1/2" Ø1/2" Ø1/2"
(suction line) Ø3/4" Ø3/4" Ø3/4"
Max Distance Height (m) 30 30 30
Length (m) 50 50 50
14
Performance Data ‐ Concealed
Indoor Model 4MXD3512BB 4MXD3518BB
Outdoor Model 4TXK3512BB 4TXK3518BB
Power Supply
Rated Voltage 220 - 240 ~ 1ph 220 - 240 ~ 1ph
Frequency(Hz) 50Hz 50Hz
Performance
Function Cooling Heating Cooling Heating
Total Capacity (W) (High/Standard/Low) 3600/3420/1600 4000/3730/1600
Total Capacity (Btu/h) (High/
Standard/Low) 12300/11700/5500 13600/12700/5500
Rated Power Input (W) 1121 995
Nominal Input Current (A) 4.8 4.32
SEER / HSPF 9.25 11.2
Air Flow Volume (m3/h) (H/M/L) 840 / 740 / 640 1000 / 800 / 600
Dehumidifying Volume (l/h) 0.9
EER / C.O.P (W/W) 3.05/ 3.75
15
Performance Data ‐ Cassette
Indoor Model 4MXC3512BB 4MXC3518BB
Outdoor Model 4TXK3512BB 4TXK3518BB
Power Supply
Rated Voltage 220 - 240 ~ 1ph 220 - 240 ~ 1ph
Frequency(Hz) 50Hz 50Hz
Performance
Function Cooling Heating Cooling Heating
Total Capacity (W) (High/Standard/Low) 3600/3360/1600 4000/3600/1600
Total Capacity (Btu/h) (High/ 12300/11500/5500 13600/12300/5500
Standard/Low)
Rated Power Input (W) 1060 1071
Nominal Input Current (A) 4.57 4.55
SEER / HSPF 9.55 10.1
Air Flow Volume (m3/h) (H/M/L) 550 / 450 / 350 1180 / 1080 / 1000
Dehumidifying Volume (l/h) 0.9
EER / C.O.P (W/W) 3.17 / 3.40
16
Performance Data ‐ Convertible
Indoor Model 4MXX3512BB 4MXX3518BB
Outdoor Model 4TXK3512BB 4TXK3518BB
Power Supply
Rated Voltage 220 - 240 ~ 1ph 220 - 240 ~ 1ph
Frequency(Hz) 50Hz 50Hz
Performance
Function Cooling Heating Cooling Heating
Total Capacity (W) (High/Standard/Low) 3600/3300/1600 4100/3740/1360
Total Capacity (Btu/h) (High/ 12300/11300/5500 13600/12800/5500
Standard/Low)
Rated Power Input (W) 1119 935
Nominal Input Current (A) 4.7 4.11
SEER / HSPF 8.9 11.9
Air Flow Volume (m3/h) (H/M/L) 700 / 600 / 500 900 / 800 / 700
Dehumidifying Volume (l/h) 0.5
EER / C.O.P (W/W) 3.00 / 4.00
17
Capacity Ratio
Ambient Temperature vs. Capacity Correction Factor
Operation Range
Mode Range of Outdoor Temperature (oC)
Cooling 18oC − 43oC
Heating ‐7oC − 24oC
18
Piping Length vs. Capacity Correction Factor
12 & 18 MBH
24 MBH
36, 48 & 60 MBH
19
Connection Pipe
Item
36 MBH
60 MBH
Note:
1. Standard pipe length of the system is 5m. When the length (L) of the connecting pipe is less
than or equals to 7m, there is no need to add additional refrigerant. If the connecting pipe is
longer than 7m, it is required to add additional refrigerant as according to the table above. In
the above table, it indicates the amount of additional refrigerant per extra metre (m) of pipe
length.
2. The connecting pipe shall be able to withstand the pressure of 6.0MPa. The pipe wall
thickness shall be at least 0.5 – 1.0mm.
In order to avoid the oil held inside the riser piping flows back into the compressor when stopped and
cause liquid compression, or deterioration of oil return, it is necessary to provide oil trap at the
appropriate place in the gas piping.
Oil Trap Installation Spacing
20
System Diagram
PIPING DIAGRAM (Inverter system)
21
Electrical Data
4MXD3512BB0R0AL 0.41 6 16 6 16
220-240V
4TXK3512BB00CAL 4MXC3512BB0R0AL 4.80 − 1 0.35 0.20 6 16 6 16
50Hz/1ph
4MXX3512BB0R0AL 0.10 6 16 6 16
4MXD3518BB0R0AL 0.71 6 20 6 20
220-240V
4TXK3518BB00CAL 4MXC3518BB0R0AL 8.38 − 1 0.58 0.35 6 20 6 20
50Hz/1ph
4MXX3518BB0R0AL 0.21 6 20 6 20
4MXD3524BB0R0AL 1.52 6 20 6 20
220-240V
4TXK3524BB00CAL 4MXC3524BB0R0AL 9.70 − 1 0.85 0.40 6 20 6 20
50Hz/1ph
4MXX3524BB0R0AL 0.51 6 20 6 20
4MWD0536BB0R0AL 4.50 10 16 10 16
380-415V
4TWK0536BD00CAL 4MWC0536BB0R0AL 6.58 67.00 1 0.80 0.54 6 16 6 16
50Hz/3ph
4MWX0536BB0R0AL 1.35 6 16 6 16
4MWD0548BB0R0AL 4.50 10 25 10 25
380-415V
4TWK0548BD00CAL 4MWC0548BB0R0AL 8.00 59.40 1 0.80 0.54 6 25 6 25
50Hz/3ph
4MWX0548BB0R0AL 1.62 6 25 6 25
380-415V
4TWK0560BD00CAL 4MWD0560BB0R0AL 9.77 67.00 1 0.80 4.50 10 25 10 25
50Hz/3ph
Notes:
RLA: Rated Load Amperes
LRA: Locked Rotor Amperes
FLA: Full Load Amperes
OFM: Outdoor Fan Motor
IFM: Indoor Fan Motor
MFS: Maximum Fuse Size
MCA: Minimum Circuit Ampacity
22
Dimensions
Concealed Type Indoor Unit (12 & 18 MBH)
Concealed Type Indoor Unit (24, 30, 36, 42 & 48 MBH)
23
Concealed Type Indoor Unit (60 MBH)
Item (units in mm)
Model
A B C D E F G H I J
12 MBH
932 430 738 892 980 721 738 125 203 266
18 MBH
24 MBH 1101 515 820 1159 1270 530 1002 160 235 268
36 MBH 1011 748 820 1115 1226 775 979 160 231 290
48 MBH 1015 788 820 1115 1226 815 979 160 261 330
60 MBH 1353 632 992 1150 192 343 1463 389 799 −
24
Cassette Type Indoor Unit (12 MBH)
Cassette Type Indoor Unit (18, 24, 36, 48 MBH)
Models H (mm)
12 MBH 250
18 & 24 MBH 260
36 & 48 MBH 340
25
Convertible Type Indoor Unit
Model Item (units in mm)
A B C D H
12 MBH
24 MBH
26
Outdoor Unit
Model Item (units in mm)
A B C D E
48 MBH
1032 412 1250 572 378
60 MBH
27
Wiring Diagrams
Concealed Type Indoor Unit (12, 18 & 24 MBH)
Concealed Type Indoor Unit (36, 48 & 60 MBH)
28
Cassette Type Indoor Unit (12 MBH)
Cassette Type Indoor Unit (18 MBH)
29
Cassette Type Indoor Unit (24 MBH)
Cassette Type Indoor Unit (36 & 48 MBH)
mode of connection 1
mode of connection 2
30
Convertible Type Indoor Unit (12, 18 & 24 MBH)
Bracket Evaporator
63629426
Convertible Type Indoor Unit (36 & 48 MBH)
31
Outdoor Unit (12 MBH)
Outdoor Unit (18 MBH)
32
Outdoor Unit (24 MBH)
Outdoor Unit (36 MBH)
L
L
33
Outdoor Unit (48 & 60 MBH)
L
L
63 625 31 8
34
Operating Functions
Temperature Parameters
ON / OFF
The unit is turned ON by pressing the Remote Controller ON / OFF button. Press this button again
turns the unit OFF. When the power is ON, no matter the compressor is started, the time interval
between two startups cannot be less than 3 minutes.
MODE Selection
Press the Remote Controller MODE button to select and display the following modes:
AUTO Mode
In AUTO mode, the system selects COOL, HEAT and FAN mode automatically according to the
change of ambient temperature. The protection function is the same with that of COOL or HEAT
mode.
For inverter models, the unit will adjust the compressor running frequency automatically according to
the change of ambient temperature. (Note: only inverter units can adjust the compressor running
frequency)
35
COOL Mode
In COOL mode, the reversing valve will not be powered ON and the temperature setting range is
16oC ~ 30oC.
For inverter models, the unit will adjust compressor running frequency automatically according to the
temperature difference between set-point and return air temperature. (Note, only inverter units can
adjust compressor running frequency). If the temperature difference is high, the compressor running
frequency will be higher. If the temperature difference is low (0 ~ 1oC), the running frequency will be
low.
Antifreezing Protection
Under COOL or DRY mode, after the compressor runs about 10 mins, when the evaporator pipe
temperature is low, the compressor will stop, the outdoor fan will stop after 30 seconds delay, the
indoor fan and swing motor will keep running in the original mode. When the evaporator pipe
temperature is high, the antifreezing protection is eliminated and the compressor has stopped for 3
minutes, the unit will resume running in the original mode.
36
Overcurrent Protection
When total input current rises over the stated value (about two times of compressor RLA as stated on
page 16 of the service manual), error code ‘E5’ will be displayed on wired controller (do not have this
function for remote controller), the compressor will stop, the outdoor fan will stop after 30 seconds
delay. For inverter units, if total input current is high, the compressor will run in limited or dropped
frequency for 3 mins maximumly, and then stop.
DRY Mode
In DRY mode, the reversing valve will not be powered ON and the temperature setting range is 16oC
~ 30oC.
For inverter models, the unit will adjust the compressor running frequency automatically according to
the change of ambient temperature. (Note: only inverter units can adjust compressor running
frequency)
37
Protection function in DRY mode
Antifreezing Protection
Under DRY mode, after the compressor runs about 10 mins, when the evaporator pipe temperature is
low, the compressor will stop, the outdoor fan will stop after 30 seconds delay, the indoor fan and
swing motor will keep running in the original mode. When the evaporator pipe temperature is high, the
antifreezing protection is eliminated and the compressor has stopped for 3 minutes, the unit will
resume running in the original mode.
Overcurrent Protection
When total input current rises over the stated value (about two times of compressor RLA as stated on
page 16 of the service manual), error code ‘E5’ will be displayed on wired controller (do not have this
function for remote controller), the compressor will stop, the outdoor fan will stop after 30 seconds
delay. For inverter units, if total input current is high, the compressor will run in limited or dropped
frequency for 3 mins, and then stop.
FAN Mode
In FAN mode, the indoor fan will run in High, Med, Low or Auto mode. The compressor, outdoor fan
and reversing valve will stop
HEAT Mode
38
For inverter models, the unit will adjust compressor running frequency automatically according to the
temperature difference between set-point and return air temperature. (Note, only inverter units can
adjust compressor running frequency). If the temperature difference is high, the compressor running
frequency will be higher. If the temperature difference is low (0 ~ 1oC), the running frequency will be
low.
When the unit is turned off in HEAT mode, or switched to other mode from HEAT mode, the reversing
valve will be powered OFF after compressor stopped for 2 mins.
39
Overcurrent Protection
When total input current rises over the stated value (about two times of compressor RLA as stated on
page 16 of the service manual), error code ‘E5’ will be displayed on wired controller (do not have this
function for remote controller), the compressor will stop, the outdoor fan will stop after 30 seconds
delay. For inverter units, if total input current is high, the compressor will run in limited or dropped
frequency for 3 mins, and then stop.
Under HEAT mode, when the compressor is stopped due to malfunction, the indoor fan will blow at
low fan speed for 60 seconds and then stop.
40
Timer control
The unit will be ON or OFF according to the timer setting by the remote controller.
Sleep Control
When the unit is in COOL or DRY mode, after SLEEP mode has been set, the preset Tset will be
increased by 1oC after the SLEEP program has run for 1 hour, and the Tset will be increased by
another 1oC after 2 hours. When the Tset has been increased by 2oC total in two hours, the unit will
run at this set temperature and at the set speed.
When the unit is in HEAT mode, after SLEEP mode has been set, the preset Tset will be decreased by
1oC after the SLEEP program has run for 1 hour, and the Tset will be decreased by another 1oC after 2
hours. When the Tset has been decreased by 2oC total in two hours, the unit will run at this set
temperature and at the set speed.
The fan will run at high, medium or low speed as according to the remote controller fan speed (HIGH,
MED or LOW). When the fan speed is set to AUTO, the indoor fan will select fan speed (HIGH, MED
or LOW) automatically to ambient temperature.
41
Swing Control
Use Remote Controller SWING button to control SWING ON and OFF, the indoor louver will swing
only when the indoor fan is running.
Buzzer Control
When the unit is powered ON, or receives signal from remote controller, or AUTO key is pressed, the
buzzer will give out a ‘beep’.
• Under unit ON state, when power OFF and power ON, the power supply for outdoor unit will be
turned ON after 3 mins.
• Under unit OFF state, when power OFF and power ON, the power supply for outdoor unit will
be turn ON immediately.
• Contents of memory: Mode, Swing, Set Fan Speed, Set Temperature, Timing, etc.
When the unit runs in COOL, DRY or HEAT mode, there is a 3 mins restart delay for the compressor.
Overload Protection
Ttube is the Condenser Coil Temperature (at cooling mode, Ttube = outdoor coil temperature; at heating
mode, Ttube = indoor coil temperature)
When Ttube is too high, the compressor will stop. Under HEAT mode, indoor fan will blow for 60
seconds at low fan speed and then stop. Under other modes, indoor fan will run at set speed.
When compressor discharge temperature is too high, the compressor will stop. When the compressor
discharge temperature resumes normal, and the compressor has stopped for 3 minutes, the unit will
resume to its original status.
42
Communication Malfunction
When correct signal is not detected for 3 minutes, error code ‘E6’ will be displayed on the wired
controller (do not have this function for wireless remote controller) to show the communication
malfunction. The outdoor unit will stop (the same stop procedures as under the condition of the unit
meets set-point temperature). ’
For inverter models, when compressor power module protection is activated, error code ‘H5’ will be
displayed on the wired controller (do not have this function for wireless remote controller) to show the
module protection stage, the compressor will stop running. After the compressor has been stopped
for 3 minutes, it will resume running.
SAVE mode is used to limit the temperature setting range by the property owner for energy saving.
This function is only available for Wired Controller.
For COOL mode, the default temperature setting range is 16oC ∼ 30oC. In SAVE mode, the lowest
set-point limit can be adjusted and fixed to a higher value (e.g. 25oC).
For HEAT mode, the default temperature setting range is 16oC ∼ 30oC. In SAVE mode, the highest
set-point limit can be adjusted and fixed to a lower value (e.g. 26oC).
43
Hazardous Voltage!
D
isconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power cannot be inadvertently energize. Failure to
disconnect power before servicing could result in death or serious injury
Contains Refrigerant!
System contains oil and refrigerant under high pressure. Recover refrigerant to relieve
pressure before opening the system. See unit nameplate for refrigerant type. Do not use
non‐approved refrigerants, refrigerant substitutes, or refrigerant additives.
Failure to follow proper procedures or the use of non‐approved refrigerants, refrigerant
substitutes, or refrigerant additives could result in death or serious injury or equipment
damage.
12MBH – 18MBH Concealed Type Indoor Unit (Disassemble of Indoor Fan Motor)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
servicing
1. Disconnect of motor • Remove electric box cover
cable screws with screw driver
• Remove electric box cover
• Unplug the motor cables
• Remove filter from the air
inlet
2. Remove filter and air
inlet cover board • Use screw driver to remove
the air inlet cover board
3. Disassemble of fan • Remove fan blower casing
blower casing mounting screws
44
4. Remove fan blower • Remove fan blower casing
casing from the cabinet
• Use hexagonal spanner to
5. Disassemble of fan loosen the set screw of the
motor fan blower and remove the
clamp fixing the motor
• Disengage the motor from
motor support
• Disengage the fan sub‐
6. Remove the fan motor assembly from the motor
shaft
• Remove the motor from the
air inlet
12MBH – 18MBH Concealed Type Indoor Unit (Assemble of Indoor Fan Motor)
Step Illustration Handling Instruction
• Reverse the steps as
described in the section
1. Assemble of indoor fan above “12MBH – 18MBH
motor Concealed Type Unit
(Assemble of Indoor Fan
Motor)”
45
24MBH – 60MBH Concealed Type Indoor Unit (Disassemble of Electric Box)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
servicing
1. Disassemble of electric
box cover • Remove electric box cover
mounting screws with screw
driver
• Remove control box
2. Disassemble of control mounting screws as shown in
box the picture with circle and
arrow
24MBH – 60MBH Concealed Type Indoor Unit (Disassemble of Drainage Pump)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
servicing
1. Remove the drain tray
side panel • Remove 8 drain tray side
cover mounting screws with
screw driver
46
• Remove drainage pump
2. Disassemble of mounting screws with screw
drainage pump driver
3. Remove condensate • Remove condensate drainage
drainage pump pump from the unit
24MBH – 60MBH Concealed Type Indoor Unit (Disassemble of Condensate Tray)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
servicing
1. Disassemble of cover
panel • Remove 6 cover panel
mounting screws mounting
screws with screw driver
• Remove 4 condensate tray
mounting screws with screw
2. Disassemble of driver
condensate tray
• Remove the condensate tray
from the unit
47
24MBH – 60MBH Concealed Type Indoor Unit (Disassemble of Fan and Motor)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
1. Disassemble of fan servicing
blower assembly
• Remove fan blower assembly
with screw driver
• Loosen the fastening screws
on the fan
2. Disassemble of motor
• Remove the motor from the
fan blower assembly
24MBH – 60MBH Concealed Type Indoor Unit (Disassemble of Evaporator)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
servicing
• Check and make sure
refrigerant has been
1. Disassemble of recovered and system
evaporator pressure has been relieved
before opening the system
• Remove suction and
discharge pipe mounting
screws
• Remove evaporator
2. Disassemble mounting screws with screw
driver
• Remove evaporator from the
3. Remove evaporator unit
48
24MBH – 60MBH Concealed Type Indoor Unit (Disassemble of External Casing Cabinet)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
servicing
• Check and make sure
1. Remove mounting refrigerant has been
screws recovered and system
pressure has been relieved
before opening the system
• Remove mounting screws
from the left and right panel
2. Disassemble external • Disassemble external casing
casing as shown in the picture
49
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power cannot be inadvertently energize. Failure to
disconnect power before servicing could result in death or serious injury
WARNING
Contains Refrigerant!
System contains oil and refrigerant under high pressure. Recover refrigerant to relieve
pressure before opening the system. See unit nameplate for refrigerant type. Do not use
non‐approved refrigerants, refrigerant substitutes, or refrigerant additives.
Failure to follow proper procedures or the use of non‐approved refrigerants, refrigerant
substitutes, or refrigerant additives could result in death or serious injury or equipment
damage.
Cassette Type Indoor Unit (Disassemble of Air Inlet Filter)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
servicing
1. Disassemble of front
grille panel • Push the left and right clips
and open the front grille
panel
50
• Push the clips by hand
2. Remove the air inlet
• Remove the filter from the
filter
unit
Cassette Type Indoor Unit (Disassemble of Front Panel)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
1. Disassemble mounting servicing
bracket cover plates
• Remove the mounting
bracket cover plates by hand
• Remove the screws and
loosen the fixing clips on four
2. Disassemble of front corners
panel
• Remove the front panel from
the unit
51
Cassette Type Indoor Unit (Disassemble of Electrical Box)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
servicing
1. Disassemble of • Remove the mounting screws
electrical box with screw driver
• Pull upward and remove the
electrical box
Cassette Type Indoor Unit (Disassemble of Condensate Tray)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
servicing
• Disassemble of electrical box,
1. Disassemble of connecting wires as shown in
electrical box and fan the section of “Cassette Type
shroud Indoor Unit (Disassemble of
Electrical Box)”
• Remove the fan shroud from
the unit
• Remove the condensate tray
mounting screws in 4 corner
2. Disassemble of with screw driver
condensate tray
• Remove the condensate tray
from the unit
52
Cassette Type Indoor Unit (Disassemble of Fan Blower)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
servicing
1. Disassemble of fan • Remove the fan blower
blower mounting nut with wrench
• Remove the fan blower from
the unit
Cassette Type Indoor Unit (Disassemble of Fan Motor)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
servicing
1. Disassemble of fan • Remove the fan motor
motor mounting screws
• Remove the fan motor from
the unit
Cassette Type Indoor Unit (Disassemble of Air‐deflecting Plates and Connection Rods)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
servicing
1. Disassemble of air‐
• Remove the air‐deflecting
deflecting mechanism
mechanism cover plate by
cover plate
removing the mounting
screws at 4 corners under the
insulation
53
• Remove the connection rod
2. Disassemble of air‐ assembly from the unit
deflecting pate
• Disassemble the connection
connection rods
rods with screw driver
Cassette Type Indoor Unit (Disassemble of Air‐deflecting Motor)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
servicing
1. Disassemble of air‐ • Remove the air‐deflecting
deflecting motor motor mounting screws with
screw driver
• Remove the air‐deflecting
motor from the unit
54
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power cannot be inadvertently energize. Failure to
disconnect power before servicing could result in death or serious injury
WARNING
Contains Refrigerant!
System contains oil and refrigerant under high pressure. Recover refrigerant to relieve
pressure before opening the system. See unit nameplate for refrigerant type. Do not use
non‐approved refrigerants, refrigerant substitutes, or refrigerant additives.
Failure to follow proper procedures or the use of non‐approved refrigerants, refrigerant
substitutes, or refrigerant additives could result in death or serious injury or equipment
damage.
Convertible Type Indoor Unit (Disassemble of Air Inlet Protection Grille)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
1. Disassemble of air inlet servicing
protection grille
• Pull down the clips to unlock
the grilles
55
Convertible Type Indoor Unit (Disassemble of Front Panel)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
servicing
1. Disassemble of left and
right finishing plates • Disassemble left and right
finishing plates with screw
driver
• Remove 8 front panel
mounting screws with screw
2. Disassemble of front driver
panel
• Remove front panel from the
unit
Convertible Type Indoor Unit (Disassemble of Electric Box)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
servicing
1. Disassemble of electric • Remove 2 electric box cover
box cover mounting screws with screw
driver
• Remover electric box cover
from the unit
• Remove of 4 electric box
2. Disassemble of electric mounting screws with screw
box driver
56
Convertible Type Indoor Unit (Disassemble of Discharge Louvers)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
servicing
1. Disassemble of • Remove the discharge louver
discharge louvers plates from the discharge
assembly
• Remove both ends from
louver swing motor
Convertible Type Indoor Unit (Disassemble of Louver Swing Stop)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
servicing
1. Disassemble of louver
swing stop • Remove the louver swing
stop brackets with screw
driver
Convertible Type Indoor Unit (Disassemble of Condensate Tray)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
servicing
1. Disassemble of
condensate tray • Remove 4 condensate tray
mounting screws with screw
driver
Convertible Type Indoor Unit (Disassemble of Discharge Air Vane Assembly)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
1. Disassemble of servicing
discharge air vane
• Remove air vane assembly
mounting screws with screw
57
driver
• Remove air vane assembly
from the unit
Convertible Type Indoor Unit (Disassemble of Evaporator Assembly)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
servicing
• Check and make sure
refrigerant has been
recovered and system
1. Disassemble of pressure has been relieved
evaporator assembly before opening the system
• Remove evaporator
mounting screws with screw
driver
• Remove evaporator assembly
from the unit
Convertible Type Indoor Unit (Disassemble of Fan Blower Assembly)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
servicing
• Press the buckles by hand
and remove the front scroll
1. Disassemble of fan
casing
blower casing
• Remove the mounting screws
with screw driver
• Remove the back scroll casing
from the unit
• Loosen the fan setting screws
with hexagonal spanner
2. Dissemble of fan
blower • Remove the fan blower from
the unit
58
• Remove 4 bearing support
3. Disassemble of bearing bracket mounting screws
support bracket with screw driver
• Remove motor bracket
mounting bolts
4. Disassemble of fan • Remove motor retaining clip
motor
• Remove the motor from the
unit
Convertible Type Indoor Unit (Disassemble of Unit Mounting Brackets)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
servicing
1. Disassemble of unit • Remove the bolts from the
mounting brackets bracket
• Remove the mounting
bracket from the unit
59
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power cannot be inadvertently energize. Failure to
disconnect power before servicing could result in death or serious injury
WARNING
Contains Refrigerant!
System contains oil and refrigerant under high pressure. Recover refrigerant to relieve
pressure before opening the system. See unit nameplate for refrigerant type. Do not use
non‐approved refrigerants, refrigerant substitutes, or refrigerant additives.
Failure to follow proper procedures or the use of non‐approved refrigerants, refrigerant
substitutes, or refrigerant additives could result in death or serious injury or equipment
damage.
12MBH – 36MBH Outdoor Unit (Disassemble of External Casing)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
disassembling external casing
1. Disassemble of top • Remove the top cover fixing
cover screws with screw driver
• Remove the top cover from
the unit
60
• Remove the protection grille
fixing screws with screw
2. Disassemble of driver
protection grille
• Remove protection grill from
the unit
• Remove all front grille fixing
screws with screw driver
3. Disassemble of front
• Remove the front grill from
grille
the from panel (external
casing)
• Remove the front panel fixing
screws with screw driver
4. Disassemble of front
panel • Remove the front panel from
the unit
• Remove all back side panel
fixing screws with screw
5. Disassemble of back driver
side panel
• Remove the back side panel
from the unit
61
12MBH – 36MBH Outdoor Unit (Assemble of External Casing)
Step Illustration Handling Instruction
• Place the back side panel into
correct position
1. Assemble of back side
• Fasten all back side panel
panel
screws with screw driver to
hold the panel
• Place the front panel into
correct position
2. Assemble of front panel • Fasten all front panel screws
with screw driver to hold the
panel
• Place the front grille into
position
3. Assemble of front grille • Fasten all front grille screws
with screw driver to hold the
front grille
62
• Place the protection grille into
position
4. Assemble of protection
• Fasten all protection grille
grille
screws with screw driver to
hold the protection grille
• Place the top cover into
position
5. Assemble of top cover
• Fasten top cover screws with
screw driver
12MBH – 36MBH Outdoor Unit (Disassemble of Compressor)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
servicing
• Check and make sure
refrigerant has been
recovered and system
pressure has been relieved
1. Disconnect compressor before opening the system
power supply wires • Unfasten compressor power
supply wire terminals with
screw driver
• Pull down the compressor
power supply sires
• Mark the wires with
corresponding joint numbers
63
2. Remove compressor • Remove compressor mounting
mounting nuts nuts with wrench
• Disconnect the suction and
discharge pipes with torch
(pay attention of high
temperature and causing fire
3. Disconnect suction and
of surrounding material)
discharge pipes
• Apply 0.5±0.1kgf/cm2 (relative
pressure) nitrogen for
protection during brazing
• Remove the compressor from
4. Removal of compressor the base pan
12MBH – 36MBH Outdoor Unit (Assemble of Compressor)
Step Illustration Handling Instruction
• Place the compressor on the
base pan and align mounting
holes with mounting bolts
• Fasten the mounting nuts with
wrench
• (Note: do not turn compressor
upside down at any time)
1. Assemble of
compressor onto the
base pan
64
• Apply 0.5±0.1kgf/cm2 (relative
pressure) nitrogen for
protection during brazing
• Connect piping with brazing
(pay attention of high
temperature and causing fire of
surrounding material)
2. Connect suction and
discharge pipes with
compressor
• Align compressor supply power
wire with correct order
• Fasten the terminal screws with
screw driver
3. Connect compressor
power supply wires
• Conduct evacuation of the
system with vacuum pump
through refrigerant injection
mouth
4. Evacuation
• Charge refrigerant into the
system through refrigerant
injection mouth
• Charging amount of refrigerant
should refer to nameplate of
the system
5. Refill of refrigerant
65
12MBH – 36MBH Outdoor Unit (Disassemble of 4‐way Valve)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
servicing
• Check and make sure
1. Disassemble of refrigerant has been recovered
solenoid and system pressure has been
relieved before opening the
system
• Disassemble solenoid from the
valve with wrench
2. Removal of
• Remove the solenoid from the
electromagnetic
valve
solenoid
• Disconnect the piping from the
4‐way valve with a torch (pay
attention of high temperature
3. Disassemble of 4‐way and causing fire of surrounding
valve material)
• Record the orientation and
position of the 4‐way valve
66
4. Remove the 4‐way • Remove the 4‐way valve from
valve the system
12MBH – 36MBH Outdoor Unit (Assemble of 4‐way Valve)
Step Illustration Handling Instruction
• Place the 4‐way valve with
correct orientation and
position
• Apply 0.5±0.1kgf/cm2 (relative
pressure) nitrogen for
protection during brazing
1. Assemble the 4‐way
• Wrap the valve with wet cloth
valve into the system
to protect the valve from high
temperature during brazing
• Connect the pipes by brazing
(pay attention of high
temperature and causing fire
of surrounding material)
2. Assemble the • Assemble the electromagnetic
electromagnetic solenoid onto the valve with
solenoid on the valve wrench
67
• Conduct evacuation of the
system with vacuum pump
through refrigerant injection
mouth
3. Evacuation of the • Charge refrigerant into the
system and charging system through refrigerant
refrigerant injection mouth
• Charging amount of refrigerant
should refer to nameplate of
the system
12MBH – 36MBH Outdoor Unit (Disassemble of Capillary)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
servicing
• Check and make sure
refrigerant has been
recovered and system
pressure has been relieved
before opening the system
1. Disassemble of
capillary • Disconnect the pipes that
connect to the capillary (pay
attention of high temperature
and causing fire of surrounding
material)
• Apply 0.5±0.1kgf/cm2 (relative
pressure) nitrogen for
protection during brazing
12MBH – 36MBH Outdoor Unit (Assemble of Capillary)
Step Illustration Handling Instruction
• Place the capillary onto the
system with correct
orientation and location
• Connect the pipes by brazing
(pay attention of high
1. Assemble of capillary temperature and causing fire
of surrounding material)
• Apply 0.5±0.1kgf/cm2 (relative
pressure) nitrogen for
protection during brazing
• Conduct evacuation of the
68
system with vacuum pump
through refrigerant injection
mouth
• Charge refrigerant into the
system through refrigerant
injection mouth
• Charging amount of refrigerant
should refer to nameplate of
the system
12MBH – 36MBH Outdoor Unit (Disassemble of Vapour Liquid Separator)
Step Illustration Handling Instruction
• Check and make sure
refrigerant has been
recovered and system
1. Remove vapour liquid pressure has been relieved
separator mounting before opening the system
screw
• Unfasten two vapour liquid
separator mounting screws
with screw driver
• Disconnect the pipes from the
vapor liquid separator with a
torch (pay attention of high
temperature and causing fire
of surrounding material)
2. Disassemble of vapour
liquid separator • Apply 0.5±0.1kgf/cm2 (relative
pressure) nitrogen for
protection during brazing
• Remove the vapour liquid
separator from the system
69
12MBH – 36MBH Outdoor Unit (Assemble of Vapour Liquid Separator)
Step Illustration Handling Instruction
• Check and make sure
refrigerant has been
recovered and system
pressure has been relieved
before opening the system
• Place the vapour liquid
separator into the system
with correct orientation and
location
• Connect the pipes by brazing
(pay attention of high
temperature and causing fire
of surrounding material)
• Apply 0.5±0.1kgf/cm2 (relative
1. Assemble of vapour
pressure) nitrogen for
liquid separator
protection during brazing
• Fasten two mounting screws
with screw driver
• Conduct evacuation of the
system with vacuum pump
through refrigerant injection
mouth
• Charge refrigerant into the
system through refrigerant
injection mouth
• Charging amount of
refrigerant should refer to
nameplate of the system
12MBH – 36MBH Outdoor Unit (Disassemble of Axial Fan and Motor)
Step Illustration Handling Instruction
• Refer to 12MBH – 36MBH
1. Disassemble of Outdoor Unit (Disassemble of
external casing External Casing)
70
• Check and make sure power
supply is cut off before
disassembling motor
2. Disassemble of axial • Unfasten the fan mounting nut
fan with wrench
• Remove the axial fan for the
motor shaft
• Open the control parts cover
• Disconnect the motor power
cable from the control box
3. Disassemble of fan
• Unfasten fan motor mounting
motor
screw
• Remove the fan motor from
the mounting bracket
12MBH – 36MBH Outdoor Unit (Assemble of Axial Fan and Motor)
Step Illustration Handling Instruction
• Place the fan motor onto the
mounting bracket with correct
orientation
• Fasten the motor mounting
screws
1. Assemble of fan motor
• Connect the motor power
wires into the control box
• Close the control box cover
and fasten the control box
mounting screws
71
• Place the axial fan onto the
motor shaft
2. Assemble of axial fan
• Fasten the axial fan mounting
nut with wrench
• Refer to 12MBH – 36MBH
3. Assemble of external Outdoor Unit (Assemble of
casing External Casing)
12MBH – 36MBH Outdoor Unit (Disassemble of Control Box)
Step Illustration Handling Instruction
• Make sure to disconnect all
power supply of the unit
before servicing
• Disassemble external casing as
according to 12MBH – 36MBH
Outdoor Unit (Disassemble of
1. Disassemble of control
External Casing)
box cover
• Remove control box cover
mounting screws with screw
driver
• Remove the cover from the
control box
72
• Tag and record the location of
the connecting wires for those
2. Disconnect the
critical components (e.g.
component
motor, compressor, etc)
connecting wires from
the control box • Disconnect the connecting
wires from the control box
• Remove the control box
3. Disassemble of control mounting screws with screw
box drive
4. Remove the control • Hold the control box and
box remove it from the chassis
12MBH – 36MBH Outdoor Unit (Assemble of Control Box)
Step Illustration Handling Instruction
• Place the control box onto the
chassis with correct
orientation and location
1. Assemble of control
box • Fasten the control box
mounting screws with screw
drive
73
2. Connection of • Connect all component
component power connection wires as according
wires to the recorded position
• Place the control box cover
onto the control box
• Fasten the control box cover
mounting screw with screw
3. Assemble of control drive
box cover
• Assemble the external casing
as according to 12MBH –
36MBH Outdoor Unit
(Assemble of External Casing)
74
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power cannot be inadvertently energize. Failure to
disconnect power before servicing could result in death or serious injury
WARNING
Contains Refrigerant!
System contains oil and refrigerant under high pressure. Recover refrigerant to relieve
pressure before opening the system. See unit nameplate for refrigerant type. Do not use
non‐approved refrigerants, refrigerant substitutes, or refrigerant additives.
Failure to follow proper procedures or the use of non‐approved refrigerants, refrigerant
substitutes, or refrigerant additives could result in death or serious injury or equipment
damage.
48MBH – 60MBH Outdoor Unit (Disassemble of External Casing)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
disassembling external casing
1. Disassemble of top • Remove the top cover fixing
cover screws with screw driver
• Remove the top cover from
the unit
75
• Remove the protection grille
fixing screws with screw driver
2. Disassemble of
protection grille • Remove protection grill from
the unit
• Remove side front panel
mounting screws with screw
3. Disassemble of side driver
front panel
• Remove side front panel from
the unit
• Remove all front grille fixing
screws with screw driver
4. Disassemble of front
• Remove the front grill from
grille
the from panel (external
casing)
• Remove the front panel fixing
screws with screw driver
5. Disassemble of front
panel • Remove the front panel from
the unit
76
• Remove all back side panel
fixing screws with screw driver
6. Disassemble of back
side panel • Remove the back side panel
from the unit
48MBH – 60MBH Outdoor Unit (Assemble of External Casing)
Step Illustration Handling Instruction
• Place the back side panel into
correct position
1. Assemble of back side
• Fasten all back side panel
panel
screws with screw driver to
hold the panel
• Place the front panel into
correct position
2. Assemble of front
• Fasten all front panel screws
panel
with screw driver to hold the
panel
77
• Place the front grille into
position
3. Assemble of front
• Fasten all front grille screws
grille
with screw driver to hold the
front grille
• Place the side front panel into
position
4. Assemble of side front
• Fasten all side front panel
panel
screws with screw driver to
hold the panel
• Place the protection grille into
position
5. Assemble of
• Fasten all protection grille
protection grille
screws with screw driver to
hold the protection grille
78
• Place the top cover into
position
6. Assemble of top cover
• Fasten top cover screws with
screw driver
48MBH – 60MBH Outdoor Unit (Disassemble of Compressor)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
servicing
• Check and make sure
refrigerant has been
recovered and system
pressure has been relieved
1. Disconnect before opening the system
compressor power
supply wires • Unfasten compressor power
supply wire terminals with
screw driver
• Pull down the compressor
power supply sires
• Mark the wires with
corresponding joint numbers
2. Remove compressor • Remove compressor mounting
mounting nuts nuts with wrench
79
• Disconnect the suction and
discharge pipes with torch
(pay attention of high
temperature and causing fire
3. Disconnect suction
of surrounding material)
and discharge pipes
• Apply 0.5±0.1kgf/cm2 (relative
pressure) nitrogen for
protection during brazing
4. Removal of • Remove the compressor from
compressor the base pan
48MBH – 60MBH Outdoor Unit (Assemble of Compressor)
Step Illustration Handling Instruction
• Place the compressor on the
base pan and align mounting
holes with mounting bolts
1. Assemble of
compressor onto the • Fasten the mounting nuts with
base pan wrench
• (Note: do not turn compressor
upside down at any time)
80
• Apply 0.5±0.1kgf/cm2 (relative
pressure) nitrogen for
protection during brazing
2. Connect suction and
discharge pipes with • Connect piping with brazing
compressor (pay attention of high
temperature and causing fire
of surrounding material)
• Align compressor power
supply wire with correct order
3. Connect compressor
power supply wires • Fasten the terminal screws
with screw driver
• Conduct evacuation of the
system with vacuum pump
through refrigerant injection
mouth
4. Evacuation and • Charge refrigerant into the
charging refrigerant system through refrigerant
injection mouth
• Charging amount of
refrigerant should refer to
nameplate of the system
81
48MBH – 60MBH Outdoor Unit (Disassemble of 4‐way Valve)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
servicing
• Check and make sure
refrigerant has been
1. Removal of recovered and system
electromagnetic pressure has been relieved
solenoid before opening the system
• Disassemble solenoid from the
valve with wrench
• Remove the solenoid from the
valve
• Disconnect the piping from
the 4‐way valve with a torch
(pay attention of high
2. Disassemble of 4‐way temperature and causing fire
valve of surrounding material)
• Record the orientation and
position of the 4‐way valve
3. Remove the 4‐way • Remove the 4‐way valve from
valve the system
82
48MBH – 60MBH Outdoor Unit (Assemble of 4‐way Valve)
Step Illustration Handling Instruction
• Place the 4‐way valve with
correct orientation and
position
• Apply 0.5±0.1kgf/cm2 (relative
pressure) nitrogen for
protection during brazing
1. Assemble the 4‐way
• Wrap the valve with wet cloth
valve into the system
to protect the valve from high
temperature during brazing
• Connect the pipes by brazing
(pay attention of high
temperature and causing fire
of surrounding material)
2. Assemble the • Assemble the electromagnetic
electromagnetic solenoid onto the valve with
solenoid on the valve wrench
• Conduct evacuation of the
system with vacuum pump
through refrigerant injection
mouth
3. Evacuation of the • Charge refrigerant into the
system and charging system through refrigerant
refrigerant injection mouth
• Charging amount of
refrigerant should refer to
nameplate of the system
83
48MBH – 60MBH Outdoor Unit (Disassemble of Capillary)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
servicing
• Check and make sure
refrigerant has been
recovered and system
pressure has been relieved
before opening the system
1. Disassemble of
capillary • Disconnect the pipes that
connect to the capillary (pay
attention of high temperature
and causing fire of
surrounding material)
• Apply 0.5±0.1kgf/cm2 (relative
pressure) nitrogen for
protection during brazing
48MBH – 60MBH Outdoor Unit (Assemble of Capillary)
Step Illustration Handling Instruction
• Place the capillary onto the
system with correct
orientation and location
• Connect the pipes by brazing
(pay attention of high
temperature and causing fire
of surrounding material)
• Apply 0.5±0.1kgf/cm2 (relative
pressure) nitrogen for
protection during brazing
1. Assemble of capillary
• Conduct evacuation of the
system with vacuum pump
through refrigerant injection
mouth
• Charge refrigerant into the
system through refrigerant
injection mouth
• Charging amount of
refrigerant should refer to
nameplate of the system
84
48MBH – 60MBH Outdoor Unit (Disassemble of Vapour Liquid Separator)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
servicing
• Check and make sure
1. Remove vapour liquid refrigerant has been
separator mounting recovered and system
screw pressure has been relieved
before opening the system
• Unfasten two vapour liquid
separator mounting screws
with screw driver
• Remove vapour liquid
2. Remove retaining clips separator retaining clips
• Disconnect the pipes from the
vapor liquid separator with a
torch (pay attention of high
temperature and causing fire
of surrounding material)
3. Disassemble of vapour
liquid separator • Apply 0.5±0.1kgf/cm2 (relative
pressure) nitrogen for
protection during brazing
• Remove the vapour liquid
separator from the system
85
48MBH – 60MBH Outdoor Unit (Assemble of Vapour Liquid Separator)
Step Illustration Handling Instruction
• Place the vapour liquid
separator into the system with
correct orientation and
location
• Connect the pipes by brazing
1. Assemble of vapour (pay attention of high
liquid separator temperature and causing fire
of surrounding material)
• Apply 0.5±0.1kgf/cm2 (relative
pressure) nitrogen for
protection during brazing
• Install the vapour liquid
separator retaining clips and
fasten the screws
• Conduct evacuation of the
system with vacuum pump
through refrigerant injection
2. Assemble of vapour
mouth
liquid separator
retaining clips • Charge refrigerant into the
system through refrigerant
injection mouth
• Charging amount of
refrigerant should refer to
nameplate of the system
48MBH – 60MBH Outdoor Unit (Disassemble of Axial Fan and Motor)
Step Illustration Handling Instruction
• Refer to 48MBH – 60MBH
1. Disassemble of
Outdoor Unit (Disassemble of
external casing
External Casing)
86
• Check and make sure power
supply is cut off before
servicing
2. Disassemble of axial • Unfasten the fan mounting nut
fan with wrench
• Remove the axial fan for the
motor shaft
• Open the control parts cover
• Disconnect the motor power
cable from the control box
3. Disassemble of fan
• Unfasten fan motor mounting
motor
screw
• Remove the fan motor from
the mounting bracket
48MBH – 60MBH Outdoor Unit (Assemble of Axial Fan and Motor)
Step Illustration Handling Instruction
• Place the fan motor onto the
mounting bracket with correct
orientation
• Fasten the motor mounting
screws
1. Assemble of fan motor
• Connect the motor power
wires into the control box
• Close the control box cover
and fasten the control box
mounting screws
87
• Place the axial fan onto the
motor shaft
2. Assemble of axial fan
• Fasten the axial fan mounting
nut with wrench
• Refer to 48MBH – 60MBH
3. Assemble of external
Outdoor Unit (Assemble of
casing
External Casing)
48MBH – 60MBH Outdoor Unit (Disassemble of Control Box)
Step Illustration Handling Instruction
• Check and make sure power
supply is cut off before
servicing
1. Disconnect the • Tag and record the location of
component the connecting wires for those
connecting wires from critical components (e.g.
the control box motor, compressor, etc)
• Disconnect the connecting
wires from the control box
88
• Remove the control box
2. Disassemble of control
mounting screws with screw
box
drive
3. Remove the control • Hold the control box and
box remove it from the chassis
48MBH – 60MBH Outdoor Unit (Assemble of Control Box)
Step Illustration Handling Instruction
• Place the control box onto the
chassis with correct
orientation and location
1. Assemble of control
box • Fasten the control box
mounting screws with screw
drive
89
2. Connection of • Connect all component
component power connection wires as according
wires to the recorded position
90
Trouble Shooting
Figure 1. Air Conditioner Cannot Start Up
91
Figure 2. Poor Cooling or Heating Effect
92
Figure 3. Compressor Doesn’t Run / Indoor Fan Doesn’t Run
93
Figure 4. Water Leakage / Abnormal Sound and Vibration
94
. Figure 5. Compressor Too Hot
95
Error Code Descriptions
Table1. Descriptions of Error Code on Indoor Wired Controller
Error
Possible Problem Related Parts Descriptions
Code
• If water‐full protection does not recover after 2 hours, it is
Water pump
E0 Water Pump believed that water pump is failed. Therefore, the unit will be
Malfunction
switched off and cannot be recovered automatically.
• When high pressure protection is detected for 3 seconds
successively, all the loads (except the 4‐way valve of heating) will
High pressure
High‐pressure be switched off. All the buttons and remote control signals
E1 Protection of
Switch (except ON/OFF function) will be disabled and cannot be
Compressor
recovered automatically. To eliminate the fault, it is required to
switch OFF and ON the machine or recover from power failure.
• If the system has been running for a period of time under cooling
or dry mode, and evaporator temperature is lower than
Indoor Evaporator protective temperature value, indoor anti‐frozen protection will
Indoor Anti‐
E2 Temperature be activated. The compressor and outdoor fan will be stopped.
frozen Protection
Sensor The unit will not run until the compressor has been stopped for 3
minutes, and the evaporator temperature increases higher than
protective temperature value.
• Under system ON or Standby condition, if it is detected within 30
seconds successively that the low‐pressure switch is cut off (if the
compressor is started, the low‐protection detection function will
Low Pressure
Low‐pressure be started 3 minutes after the compressor has started running),
E3 Protection of
Switch the low pressure will be activated. For the first two times of low‐
Compressor
protection protection within 30 minutes, the unit can be
recovered automatically. From the third time, the unit will not be
recovered automatically.
• After the compressor is started, if exhaust temperature is
detected for 130oC or higher within 30 seconds successively, E4
High Discharge will be displayed. All the loads (except the 4‐way valve of heating)
Exhaust High
Temperature will be stopped. If the compressor has been stopped for 3 minutes
E4 Temperature
Protection of and the exhaust temperature is lower than 90oC, the systems will
Protection
Compressor be recovered. If the high exhaust temperature protection has
been activated for three times, the system will not be recovered
automatically.
• After the unit is energized, if it is detected successively within 3
Compressor seconds that the compressor overload switch is cut off, the
Overload or compressor overload protection is activated. In this case, all the
E5 Compressor
Compressor loads will be stopped (except the 4‐way valve of heating) and E5
Driver Error will be displayed. If three compressor overload protections are
detected successively in 30 minutes, the compressor will not
96
recover automatically and the buzzer alarm will be activated. It is
required to press ON/OFF to stop the unit and clear the buzzer
alarm before pressing the ON/OFF again. The unit will be
restarted if the high protection disappears. Otherwise, the error
code “E5” will be displayed.
• On the other hand, “E5” will also be displayed in the event of
compressor drive failure.
• Once energized, if the outdoor unit does not receive any signal
from indoor unit for 30 seconds successively, this is identified as
communication failure. In this case, the compressor and outdoor
fan will be stopped. Under heating mode, the 4‐way valve will be
stopped if the compressor has been stopped for 2 minutes.
• If the indoor unit does not receive and signal from outdoor unit
Communication for 1 minute, this is identified as communication failure. In this
Communication Between Indoor case, the indoor unit will be stopped and the indicator will blink.
E6
Failure and Outdoor Main
Board • If the display board does not receive message from outdoor unit
for 1 minute, this is identified as communication failure. In this
case, the error code will be displayed and the machine will not
function.
• After the communication is resumed to normal, the system will be
recovered automatically and run as according to pervious working
mode.
• Once energized, if “Water Full” is detected successively for 8
seconds, the system will enter into water full protection the
indicator will blink (or display E9).
• Under cooling and dry mode, the outdoor fan and compressor will
Water Full Condensate Level be stopped, while the indoor fan will stopped after 1 minute.
E9
Protection Switch
• Under heating mode, the outdoor fan and compressor will be
stopped, the 4‐way valve will maintain its original state, the
indoor unit will be stopped after 1 minute.
• Under fan mode, the indoor unit will be stopped.
• For the indoor air temperature sensor, if “open circuit” or “short
circuit” is detected successively for 3 seconds, the indoor
temperature will set to 24oC forcibly. In this case, the system will
Malfunction of not function. The indicator will blink or display the error code. The
Indoor Ambient
Indoor Return Air system will resume automatically after the failure is eliminated
F0 Temperature
Temperature and corrected.
Sensor
Sensor
• Under fan mode, the error will be displayed with the unit running
normally. The error code will disappear after the fault is
eliminated or corrected.
Malfunction of Evaporator
• For the evaporator temperature sensor, if “open circuit” of “short
F1 Evaporator Temperature
circuit” is detected successively for 5 seconds, the evaporator
Temperature Sensor
97
Sensor temperature sensor malfunction is identified.
• Under cooling and dry mode, the system will be stopped,
• Under heating mode, all the loads (except the 4‐way valve) will be
stopped. The indicator will blink or display the error code “F1”.
After the fault is eliminated, the system will resume automatically
and the clear the error display.
• Under fan mode, the error will be displayed with the indoor unit
running normally. The error code will disappear after the fault is
eliminated or corrected.
• For the outdoor condenser temperature sensor, if “open circuit”
of “short circuit” is detected successively for 5 seconds, the
outdoor condenser temperature sensor malfunction is identified.
• Under cooling and dry mode, the system will be stopped.
Malfunction of Outdoor
Condenser Condenser • Under heating mode, all the loads (except the 4‐way valve) will be
F2 stopped. The indicator will blink or display the error code “F2”.
Temperature Temperature
Sensor Sensor After the fault is eliminated, the system will resume automatically
and the clear the error display.
• Under fan mode, the error will be displayed with the indoor unit
running normally. The error code will disappear after the fault is
eliminated or corrected.
• For the outdoor environment temperature sensor, if “open
circuit” of “short circuit” is detected successively for 5 seconds,
the outdoor environment temperature sensor malfunction is
identified.
Malfunction of • Under cooling and dry mode, the system will be stopped.
Outdoor
Outdoor
Environment • Under heating mode, all the loads (except the 4‐way valve) will be
F3 Environment
Temperature stopped. The indicator will blink or display the error code “F3”.
Temperature
Sensor After the fault is eliminated, the system will resume automatically
Sensor
and the clear the error display.
• Under fan mode, the error will be displayed with the indoor unit
running normally. The error code will disappear after the fault is
eliminated or corrected.
• For the exhaust temperature sensor, if “open circuit” is detected
successively for 5 seconds after the compressor is started, the
indoor coil temperature sensor malfunction is identified. Under
cooling and dry mode, the system will be stopped. Under heating
Malfunction of
Exhaust mode, all the loads (except the 4‐way valve) will be stopped. The
Exhaust
F4 Temperature indicator will blink or display the error code “F4”. The buzzer
Temperature
Sensor alarm will be activated. After the fault is eliminated, the system
Sensor
will resume automatically and the clear the error display.
• For the exhaust temperature sensor, if “short circuit” is detected,
the indoor coil temperature sensor malfunction is identified.
Under cooling and dry mode, the system will be stopped. Under
98
heating mode, all the loads (except the 4‐way valve) will be
stopped. The indicator will blink or display the error code “F4”.
The buzzer alarm will be activated. After the fault is eliminated,
the system will resume automatically and the clear the error
display.
• For the wired controller, if “open circuit” or “short circuit” is
detected successively for 3 seconds, the indoor temperature will
Malfunction of set to 24oC forcibly. In this case, the system will not function. The
Wired Controller indicator will blink or display the error code. The system will
F5 Indoor Wired Controller resume automatically after the failure is eliminated and
Environment corrected.
Sensor • Under fan mode, the error will be displayed with the unit running
normally. The error code will disappear after the fault is
eliminated or corrected.
Keys Locked • This is not a failure. It means the keys on the wired controller are
EE Wired Controller
(not a failure) locked.
Table2. Descriptions of Error Code on Cassette Type Indoor Unit
Error Descriptions
LED Indications No. of Flashes
Descriptions
per 2 seconds
1 time Indoor ambient temperature sensor error
• It goes on as per set
time 2 times Evaporator temperature sensor error
Yellow
3 times Condenser temperature sensor error
(Timing Indication lamp) • It flashes when the
temperature sensor 4 times Outdoor ambient temperature sensor error
error occurs
5 times Discharge air temperature sensor error
• It goes on/off as the 2 times Defrosting
compressor is turned
on/off. 3 times High pressure protection
Green
(Compressor Indication 4 times Low pressure protection
• It flashes when
Lamp)
defrosting or the 5 times Overload protection
compressor error
occurs 6 times Discharge high temperature protection
1 time Communication error
• It goes on/off as the
Red unit is turned on/off. 2 times Water overflow protection
(Running Indication
Lamp) • It flashes when the 3 times Anti‐freezing error
indoor unit error occurs
4 times Anti‐high temperature protection
99
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the
leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad
portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more
information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
MS-SVM13A-EN