You are on page 1of 30

INSTALLATION MANUAL

Split Duct & Floor Air Conditioner

Thank you very much for purchasing our air conditioner,


Before using your air conditioner, please read this manual carefully and keep it for future reference.
CONTENTS PAGE
WARNING
PRECAUTIONS........................................................................................1
Do not throw or slam the remote controller.
ACCESSORIES (INDOOR UNIT).............................................................. 2
INSTALLATING INDOOR UNIT ...............................................................2
Operate the remote controller within the receiving scope of the
INSTALLATING OUTDOOR UNIT............................................................6 indoor unit, and direct the transmitting part of the remote
controller to the receiver of the indoor unit.
HEAT INSULATION OF THE PIPE ............................................................9
INSTALL THE CONNECTIVE PIPE..........................................................10 The remote controller should be over 1m away from the
television or sound box.
INSTALL THE DRAIN PIPE.....................................................................12
ELECTRIC CONNECTION.......................................................................13 Do not place the remote controller at a moist place, near the
heat sources such as stove, or expose it directly in the sunlight.
ELECTRIC WIRE DIAGRAM...................................................................15
Ensure correct positive and negative poles when loading the
TRIAL RUN...........................................................................................18
batteries.

Decide the correct way of conveying the equipment.

Try to transport this equipment with the original package.

If the a ir conditioner needs to be installed on a metal part of the


building, electric insulation must be performed, and the
installation must meet the relevant technical standards of electric
devices.

The appliance must be installed 2.3m above floor.

The appliance shall not be installed in the laundry.


1. PRECAUTIONS Before obtaining access to terminals, all supply circuits
must be disconnected.

The appliance must be positioned so that the plug is


Precautions before reading the installation manual. accessible.
Read this user manual carefully before installing the equipment.
The enclosure of the appliance shall be marked by word, or
by symbols, with the direction of the fluid flow.
The air conditioner must be installed by professional technicians.
If the supply cord is damaged, it must be replaced by the
When installing the indoor unit and its accessory pipes, adhere to
this user’s manual as far as possible. manufacture or its service agent or a similarly qualified
person in order to avoid a hazard.
Inspect and make sure the piping and cabling are correct before
powering on the air conditioner. An all-pole disconnection switch having a contact
separation of at least 3mm in all poles should be
This information may change with the update of this machine, and connected in fixed wiring.
no further notice will be given for such change.

The safety precautions listed here are divided into two categories. In
either case, important safety information is listed which must be read
CAUTION
carefully.

Before installing the unit,it is necessary to check whether the


WARNING ground wire is charged.
Failure to observe a warning may result in death. If it is,the unit shall not be installed before correction.

Before installing the unit,be sure to confirm with the user whether
CAUTION
there are wires,water pipes,air pipes and so on in the wall or
Failure to observe a caution may result in injury or damage ground of the installation site to avoid accidents due to damage.
to the equipment.
Install the unit where enough space of installation and
After completing the installation, make sure that the unit operates maintenance is available.
properly during the start-up operation. Please instruct the customer
Install the unit where the ceiling is horizontal and enough for
on how to operate the unit and keep it maintained.Also, inform
bearing the weight of the indoor unit.
customers that they should store this installation manual along with
the owner's manual for future reference.
Install the unit where the air inlet and outlet are not baffled and
are the least affected by external air.

Install the unit where the supply air flow can be sent to all parts
in the room.

Installation Manual

1
Install the unit where it is easy to lead out the connective pipe Table.2-2
and the drain pipe.
Accessory name Qty. Shape Purpose
Install the unit where no heat is emitted from a heat source
directly. Owner’s manual 1
Installation manual 1 This manual
Installing the equipment in any of the following places may lead
to faults of the equipment (if that is inevitable, consult the Water connective pipe 1 Connect to water drainage pipe
supplier): Remote controller Owner’s Manual Owner’s Manual
1
The site contains mineral oils such as cutting lubricant. Remove controller 1
AAA battery 2
Seaside where the air contains much salt.
Copper nut Connect to refrigerant pipe
1
Hotpring area where corrosive gases exist, e.g., sulfide gas. (96000 unit not attached)

Factories where the supply voltage fluctuates seriously.

Inside a car or cabin.


3. INSTALLATING INDOOR UNIT
Place like kitchen where oil permeates. 3.1 Duct type
Place where strong electromagnetic waves exist. 3.1.1 Installation space
Ensure enough space required for installation and maintenance.
Place where flammable ga ses or materials exist.

Over 500 mm
Place where acid or alkali gases evaporate.

Other special environments.

Over 600 mm
Install the unit where enough space of installation and
maintenance is available. Maintenance space

Install the unit where the air inlet and air outlet are free from
obstacles and strong wind. 600mmX600mm

Inspection orifice

Fig.3-1
Install the unit in a dry and well ventilated place.

Install the unit where the bearing surface is level and can bear
weight of the unit, and is suitable for installing the unit
horizontally without increasing noise or vibration.
≥600mm

Install the unit where the operation noise and the expelling of air
do not affect neighbours.
≥2500mm
Floor
Install the unit where no flammable gas is leaked.
Note: Ensure that the minimum Inspection orifice
Install the unit where it is convenient for pipe connection and drain gradient is over 1/100. Fig.3-2
electric connection.
3.1.2 Install Φ10 Pendant Bolts Or Ground Bolts
1366
2. ACCESSORIES (INDOOR UNIT) 1350
1231

NOTE
If in the wire control mode, the accessories do not include
758
797

704

display panel assembly remote controller or mounting bracket.


Table.2-1

Accessory name Qty. Shape Purpose 600


Pendant bolt hole
4-12 x25
Owner’s manual 1
MTA1-76H(C)QN1、MTA1-96H(C)QN1 (Unit:mm)
Installation manual 1 This manual Fig.3-3
Restriction assembly 1 Connect to system Pendant bolt hole
4-12×72
Water connective pipe 1 Connect to water drainage pipe
Display board subassembly 1 Connect to control signal
Protective sleeve for refrigerant
760

2
840
800

inlet and outlet pipes


Remove controller 1 Air inlet side

AAA battery 2
1180
Copper connective pipe 4 Connect to Refrigerant pipe MTA1-120H(C)QN1 (Unit:mm)
Fig.3-4
Installation Manual

2
3.1.3 Suspending The Indoor Unit

Use a hoisting device to hoist the indoor unit, align it with the
installation screw, adjust the horizontality and then tighten it.

749.5
Unit body Pendant bolt

1895

Not less than 30


MTA1-150H(C)QN1、MTA1-180H(C)QN1MTA1-240H(C)QN1 (Unit:mm)

Fig.3-5

Use Φ10 or bigger screws. The screw material is high-quality


carbon steel (whose surface is zinc plated or undergoes other Fig.3-10
rustproof treatment) or stainless steel. 3.1.4 Design And Connection Of Duct

The treatment of the ceiling varies between buildings. For The duct design must comply with the national heating air
detailed measures, consult with the fitting-out staff. conditioner pipeline design specifications.

Fix the pendant bolts firmly and reliably in light of the specific The duct accessories and materials must be produced by
situation. professional manufacturers.

Installation of the pendant bolt in different environments. In order to prevent air flow shorting, do not keep the air inlet pipe
near the air outlet pipe.
A. Wooden structure
Put rectanglar sticks across the beams, and set pendant bolts. Install a filter at an easy-to-maintain place such as intake pipe.
(Otherwise, the duct will gather on the air heat exchanger and
Wooden span lead to fault and water leak of the air conditioner.)

In order to suppress noise effectively, install noise suppression


Beam and sound insulation devices, especially in the noise-sensitive
spaces such as meeting rooms.
Ceiling

For connection of the flange plane, use non-flammable canvas


Pendant bolt
adapter to prevent transmission of vibration. For its size, see the
Fig.3-6 indoor unit outline diagram. Use M6X20 screws (configured on
site) for connection.
B. New concrete roughcast
Use embedded bolts, embedded pulling plugs, and embedded All pipelines must be connected closely and soundly without
stick harness. leak of air. The pipelines must be adiabatic and free from
condensation.

Key points of duct connection


Steel bar
Canvas adapter Canvas adapter

Embedded bolt
Noise suppression chamber
Pipe pendant embedded bolt
Fig.3-7
Air outlet Noise Air inlet
C. New concrete roughcast suppression chamber Inspection
Air filter
Set it with embedded bushes or embedded bolts. orifice

Fig.3-11
3.1.5 Install the drainpipe
1. Install the indoor unit drainpipe
Install a drain stream trap in the drainpipe to prevent water from
Blade plug-in unit Slide plug-in unit overflowing. (The drainpipeabsorbs the odor. When the outside
static pressure is high (especially the air inlet),it is difficult todrain the
Fig.3-8 water.)
D. Steel beam and girder structure
Set and use supportive angle steel. Drainage should be natural. When constructing, the outside pipe of
outdoor unit should be inclined (1/50~1/100).
Suspended bolt
The bending part of drainpipe should be fewer than 2. Furthermore,
to reduce the depositing dust, avoid bending the pipe as possible as
you can.
Make sure there is no dust or rubbish falling into indoor unit drain
Pendant bolt Supportive elbow and drainpipe.
angle steel
After installation, remove the checking panel, pour some water in the
Fig.3-9 drain elbow to see whether it drains smoothly.

Installation Manual

3
100mm or more
Checking panel Checking panel MTA1-120H(C)QN1
Drain pipe

540 540

394 12-
Φ8

638
668
S heath

217

217
247
217
50mm or more
Sheath
(Checking or ifice)

120
(Checking orifice)
209 364 364 364
1828
General drain pipe
1970
Fig.3-12
Front view (Air supply outlet) Fig.3-15
CAUTION
106 120
Rubbish is easy to accumulate at drain stream trap. Make
sure to install a plug or other things which is easy to clean.

2. Test draining
Open the clapboard of indoor unit, pour the water in to see whether it
drain smoothly and whether there is water leakage.

313
Gas side liquid side
3. Heat insulation 181

24
After confirming that drainage is smoothly and there is no leakage,
wrap the drainpipe with insulation material, or there will be
outlet
condensed water. 749.5
860 45

Side view (Pipes) Fig.3-16


3.1.6 Dimension(Unit:mm)
1655
MTA1-76H(C)QN1、MTA1-96H(C)QN1

1350

10
1231
300 300 60
36

350
117

153

153

65
143
450

306 306

20
315 315 214 315 315

-M
6
1366
Rear view (Air return vent) Fig.3-17
Liquid pipe Gas pipe
100 150

MTA1-150H(C)QN1、MTA1-180H(C)QN1、MTA1-240H(C)QN1
450

345

35
88 540 540
24
40

Outlet
196 112 Fig.3-13
394 12-
Air outlet duct connection screw hole location diagram Φ8
638
668
217

217
247
217

1139
34

120

209 364 364 364


1828
348

1970

Front view (Air supply outlet)


Fig.3-18

Fig.3-14
Return air duct rivet screw hole location diagram

Installation Manual

4
106 120
≥300mm ≥300mm

≥100mm
Rear

≥1170 mm
168

indoor unit
374

Gas side liquid side


181

No obstacle in front of it

outlet
749.5
860 45
Fig.3-23
Side view (Pipes)
Fig.3-19 For anti-fall down, please conduct the follow measures:

1655 See Fig.3-24 to fix the feet on the floor after select a proper
place for installation, since the height of this unit casing is very
high.

10
The right and left sides as weel as rear can be fixed, please
60
350

select the unit fixed measure as per to your actual installing


65 ambient.
143

20

315 315 214 315 315


-M
6

Rear view (Air return vent)


Fig.3-20

3.2 Floor type


Outline of the unit
Foot screw
420
1200
960 216

(Unit:mm)

Fig.3-24
1860

Put down the air intake planel, brfore electric connection, see
Fig.3-25:

Uncover the screw-cap in the air intake planel, and then lossen
the screws.

Take off the air intake panel, ensure which palce secure enough

(Unit:mm)
Fig.3-21

Installation

For ensure the proper installation


Select the enough solid and level site.
Ensure enough space required for installation and maintenance. Screw

Screw cap

>30cm
Air intake panel

Fig.3-25

NOTE
Please beware of the foot screw, which may be hurt for the
pass-by people, make sure enough security of that, prevent
accident occure.
Fig.3-22

Installation Manual

5
4. INSTALLATING OUTDOOR UNIT Air outlet

4.1 Important: Construction Checkpoints


Installation
Check the model and name to avoid mistaken installation.
Air outlet Air inlet
Refrigerant pipe

The refrigerant pipes must have the specified diameter.

Nitrogen of a certain pressure must be filled into the refrigerant


pipe before welding. Fig.4-1

The refrigerant pipe must undergo heat insulation treatment.


Installation & maintenance surface
After the refrigerant pipe is installed completely, the indoor unit
cannot be powered on before performing the airtight test and ≥1000 mm
creating a vacuum.

Refrigerant pipe
The refrigerant pipe must undergo the airtight test [with
≥1000 mm ≥500 mm ≥1000 mm
2.94MPa (30kgf/cm2G) nitrogen].
≥1000 mm

Creating a vacuum Top view of the outdoor unit (multiple units installed)
Be sure to use the vacuum pump to create a vacuum of the
connective pipe at both air side and liquid side concurrently.
Fig.4-2
Refrigerant replenishment
NOTE
If the pipe is longer than the reference pipe, the refrigerant
replenishment quantity for each outdoor unit should be In case any obstacles exist above the outdoor unit, such
calculated through the formula obtained according to the actual obstacles must be 2000mm above the outdoor unit.
length of the pipe.
If miscellaneous articles are piled around the outdoor unit, such
Record the refrigerant replenishment quantity, actual length of articles must be 400mm below the top of the outdoor unit.
pipe and the height difference of the indoor & outdoor units onto
the operation confirmation table (on the electric control box) of
the outdoor unit in advance for future reference.
4.3 Convey Outdoor Unit
Electric wiring

Select the power supply capacity and wire size according to the Use 4 steel ropes of Φ6mm or bigger size to hoist the outdoor
design manual. The power wire size of the air conditioner should unit and convey it into the room.
be greater than that of ordinary motors.
In order to prevent scratch and deformity the outdoor unit, apply
In order to prevent misoperation of the air conditioner, do not a guard board to the surface of contact between the steel wire
interleave or entwine the power cable (208 230V 3N~ 60Hz) and the air conditioner.
with the connection wires (low-voltage wires) of the
indoor/outdoor unit. Remove the cushion for use in the transport after finishing the
transport.
Power on the indoor unit after performing the airtight test and
making a vacuum.

Trial run
Perform the trial run only after the outdoor unit has been
powered on for over 12 hours. Steel wire

Guard board
4.2 Installation Space
When installing the unit, leave a space for maintenance shown
in the following figure. Install the power supply at the side of the
outdoor unit. For installation procedure, see the relevant
installation manual.

Ensure enough space for installation and maintenance.(see


Fig.4-1 and Fig.4-2)

Fig.4-3

Installation Manual

6
4.4 Installing The Outdoor Unit

As shown in Fig.4-4, leave an interval of 100mm between the


outdoor units.

≥500 mm ≥500 mm

M12 foundation bolt


4 screws for 1 unit
steel

Fig.4-4
Fig.4-7
The distance of the foundation bolt is shown in Fig.4-5.

NOTE
762
When welding the refrigerant pipe, in order to prevent internal
(Unit:mm) oxidation of the pipe, nitrogen must be filled in. Otherwise, the
oxidized chips may block refrigerating circulatory system.
676

4.6 Size Of Outdoor Unit Pipes And Piping


Methods
Through hole (15×20 rectangular hole)

Fig.4-5
Snow protection facilities must be installed in the snowfall areas. Indoor unit
(See the right figure) (in case the snow protection facilities are
incomplete, faults may occur). In order to prevent influence
caused by snow, set up raised pavilion, and install snow
protection sheds at the air inlet and air outlet.

Fig.4-8

Size of outdoor unit pipes and piping methods


Snow protection
Snow protection Table.4-1
shed at the air inlet shed at the air outlet
Model Gas side Liquid side

MTA1-76H(C)QN1
MFA1-76H(C)RN1 φ19.0 φ9.52
MTA1-150H(C)QN1

MTA1-96H(C)QN1
MFA1-96H(C)RN1 φ22.0 φ9.52
MTA1-180H(C)QN1

MTA1-120H(C)QN1
Snow protection φ25 φ12.7
MTA1-240H(C)QN1
shed at the air inlet

Fig.4-6
Allowed length of refrigerant pipe and height difference
4.5 Refrigerant Pipe
Outdoor unit

The refrigerant pipe adapter is located inside the outdoor unit.


Height difference between indoor
unit and outdoor unit H 30m

So remove the right front board first.(three M5 screw)

When the pipe is connected from the front side, the pipe can be
led out through the right front board.

As shown in Fig.4-7, when brazing the indoor and outdoor


Max. pipe length L 50m
connective lines, pad a sheet metal under the valve avoids the
flame burning the chassis.

Indoor unit
Fig.4-9

Installation Manual

7
4.11 Remove Trash And Moist In The Pipe
Table.4-2
Allowed Trash and foreign matters may come into the pipe in the process
value of installing the refrigerant pipe. Be sure to blow them off with
Max. actual length of pipe (L) nitrogen before connecting the pipe to the outdoor units.
50m
Height difference Outdoor Use high-pressure nitrogen to clean the pipelines. Do not use

Max. height difference


(upper) 25m
between indoor the refrigerant of the outdoor unit for cleaning.
unit and outdoor Outdoor
unit (H) 30m 4.12 Schematic Diagram Of Connection
(lower)
Between Indoor Unit And Outdoor Unit
Signal wire

Floor Type

Indoor unit

Gas-side connective pipe of system


Fig.4-8

4.7 Airtight Test


Liquid-side connective pipe of system
After the pipes between the indoor unit and the outdoor unit are
connected, replenish compressed nitrogen to perform airtight Signal wire Fig.4-10
test.

NOTE
The airtight test is performed by using the compressed nitrogen
[2.94MPa(30kg/cm2G)].

Tighten the spool of the gas valve and liquid valve before
compressing the nitrogen. Signal wire

Compress the nitrogen at the air vent of the gas valve.

The gas valve and liquid valve are closed in the process of
compressing the nitrogen. Gas-side connective pipe of system

Do not use oxygen, flammable gas or toxic gas in the airtight


test.

4.8 Use A Vacuum Pump To Create A Vacuum Liquid-side connective pipe of system

Use a vacuum pump to make a vacuum. Do not use refrigerant Fig.4-11


gas to expel air.

When making the vacuum, start from the air side.

4.9 Open All Valves


Signal wire

4.10 Refrigerant Replenishment Quantity


According to the diameter and length of the connective
liquid-side pipe of the outdoor unit and indoor unit, calculate the
refrigerant replenishment quantity. The refrigerant for
replenishment is R410A.
Table.4-3
Quantity of refrigerant
Diameter of liquid-side pipe
replenished for 1 m pipe length
Gas-side connective pipe of system
φ 9.52/12.7 0.06 kg

Liquid-side connective pipe of system

Fig.4-10

Installation Manual

8
4.13 Refrigerant Leak Precautions NOTE
This air conditioner uses refrigerant R410A. The R410A is safe
The indoor unit and outdoor unit are categorized into system A
refrigerant which is harmless and non-flammable. The room for
and system B. When installing and connecting the indoor unit
placing the air conditioner should have a proper space. Even if
and outdoor unit, identify the label carefully, and make sure that
refrigerant leakage occurs, the density threshold will not be
indoor unit corresponds to the outdoor unit exactly. Otherwise, it
crossed. Additional measures may also be taken.
may lead to fault of the air conditioner.
Density threshold: Density of the Freon gas that does not harm
Model of indoor unit.Room name
the human body. Density threshold of R410A: 0.3 [ kg/m3]
Example: The first system indoor unit (A) of the 2nd floor is
recorded as: 2F 1A
Calculate the total quantity of refrigerant to be replenished (A
[kg]). Total refrigerant quantity for 10HP = refrigerant
replenishment quantity upon shipment (11[kg]) + additional
refrigerant replenishment corresponding to the pipe length

Calculate out the indoor volume (B[m3]) (according to the


minimum volume) 5. HEAT INSULATION OF THE PIPE
Calculate out the refrigerant density:
A[kg] 5.1 Heat Insulation Of The Pipe
≤ Density threshold: 0.3 [kg/m3 ]
B[m ]
3 In order to prevent faults caused by condensate of the
refrigerant pipe and drain pipe, perform condensate prevention
Measures against crossing of the refrigerant density threshold and heat insulation properly.

In order to keep the refrigerant density below the threshold


value, please install a mechanic ventilation device. (perform
ventilation often) CAUTION
In case frequent ventilation is impossible, please install the If it is forecast that high humidity/temperature environment
leakage detection alarm device linked with the mechanical (condensate temperature is over 23℃) may exist in the ceiling,
ventilation device. e.g., inside the ceiling with slab, ceiling which is in the same
environment as the outdoor air), it is necessary to apply 10mm
Outdoor unit or thicker adiabatic wool (16~20kg/m2 ) to the refrigerant pipe
and the drain pipe in addition to applying the general heat
insulation materials. Enough heat insulation materials should
also be applied to the refrigerant joint and the pipe joint.

5.2 Heat Insulation Of The Drain Pipe

Be sure to entwine heat insulation materials round the drain pipe


which runs through the room.
Room in which refrigerant is leaked
(All refrigerant is leaked) Carry through heat insulation for the drain pipes thoroughly.

Fig.4-12
5.3 Heat Insulation Of The Refrigerant Pipe
b. Leakage detection alarm device linked
with the mechanical ventilation device
Please use heat-resistant materials as heat insulation materials
of the air-side pipe. (e.g., EPT)
Indoor unit

OA Cover heat insulation materials separately at the liquid side and


the air side. Moreover, perform heat insulation thoroughly for the
air-side pipes of the indoor unit, and prevent water from dripping
outside the unit.

(air-side pipe)

Indoor unit
a. Ventilation orifice part
(The leakage detection alarm device should be installed at the place
vulnerable to retention of the refrigerant)

Fig.5-1
Fig.4-13
After applying the auxiliary heat insulation materials, use
vinylresin tape to seal it lest water leak.
4.14 Completing The Connection System Name
In case multiple systems are set, in order to identify the
connection system of the indoor unit and outdoor unit, it is
necessary to give name to each system, and mark it onto the
nameplate on the electric control box cover of the outdoor unit.

Installation Manual

9
6. INSTALL THE CONNECTIVE PIPE
6.1 Preparation Before Installtion
Check the height difference between the indoor unit and the
outdoor unit, and check the length and number of bends of the
refrigerant pipeline, which must meet the following requirements:
Max. height difference....25m (If the height difference is greater
than 5m, it is best to put the outdoor unit below the indoor unit)
Max. pipeline length.........50m
Max. number of bends....15 Fig.6-1

In the process of installing the connective pipe, do not letmmmm 2. Braze the liquid line to the liquid valve at the outdoor unit. Be sure
the air, dust or foreign substance intrude into the pipeline to wrap the valve body with a wet rag. Allow the nitrogen to continue
system. flowing. Refer to the Tabular Data Sheet for proper liquid line sizing.
3. Carefully remove the rubber plugs from the evaporator liquid and
Install the connective pipe only after fixing the indoor and vapor connections at the indoor coil.
outdoor units. 4. Braze the liquid line to the evaporator liquid connection. Nitrogen
should be flowing through the evaporator coil.
Keep dry when installing the connective pipe. Do not let moist 5. Slide the plastie cap away from the vapor connection at the indoor
intrude into the pipeline system. coil. Braze the vapor line to the evaporator vapor connection. Refer
to the Table 1 for proper vapor line sizing.
6. Protect the vapor valve with a wet rag and braze the vapor line
connection to the outdoor unit. The nitrogen flow should be exiting the
system from the vapor service port connection. After this connection
6.2 PRECAUTIONS DURING BRAZING OF LINES has cooled, remove the nitrogen source from the liquid fitting service
port.
All outdoor unit and evaporator coil connections are 7. Replace the Schrader core in the liquid and vapor valves.
copper-to-copper and should be brazed with a 8. Leak test all refrigerant piping connections including the service
port flare caps to be sure they are leak tight. DO NOT OVER
phosphorous-copper alloy material such as Silfos-5 or
TIGHTEN (between 40 and 60 inch -lbs. maximum).
equivalent. DO NOT use soft solder. The outdoor units 9. Evacuate the vapor line, evaporator and the liquid line, to 500
have reusable service valves on both the liquid and microns or less.
vapor connections. The total system refrigerant charge
is retained within the outdoor unit during shipping and NOTE
installation. The reusable service valves are provided to 1. Tube diameters are for lengths up to 50 equivalent ft and/or 20 ft
vertical differential.
evacuate and charge per this instruction. 2. Do not increase or decrease tubing sizes.
Serious service problems can be avoided by taking
adequate precautions to assure an internally clean and
dry system. NOTE
Line set and indoor coil can be pressurized, to 250 psig with dry
nitrogen and leak tested with a bubble type leak detector. Than
CAUTION release the nitrogen charge. Do not use the system refrigerant in
the outdoor unit to purge or leak test.
Dry nitrogen should always be supplied through the tubing while it
is being brazed, because the temperature required is high enough 10. Replace cap on service ports. Do not remove the flare caps from
to cause oxidation of the copper unless an inert atmosphere is the service ports except when necessary for servicing the system.
provide. The flow of dry nitrogen should continue until the joint has
cooled. Always use a pressure regulator and safety valve to insure
CAUTION
that only low pressure dry nitrogen is introduced into the
tubing.Only a small flow is necessary to displace air and prevent Do not connect manifold gauges unless trouble is suspected.
oxidation. Approximately 3/4 ounce of refrigerant will be lost each time a
standard manifold gauge is connected.

11. Release the refrigerant charge into the system. Open both the
6.3 PRECAUTIONS DURING BRAZING SERVICE VALVE liquid
Precautions should be taken to prevent heat damage to service valve and vapor valves by removing the plunger cap and with an hex
by wrapping a wet rag around it as shown in Fig. 6. wrench back out counter-clockwise until valve stem just touches the
Also, protect all painted surfaces, insulation, during brazing. After chamfered retaining wall.
brazlng cool joint with wet rag. 12. Replace plunger cap finger tight, then tighten an additional 1/12
turn (1/2 hex flat). Cap must be replaced to prevent leaks.
Valve can be opened by removing the plunger cap and fully inserting
a hex wrench into the stem and backing out counter-clockwise until
WARNING
valve stem just touches the chamfered retaining wall.
Never attempt to repair any brazed connections while the system is
under pressure. Personal injury could result.
Connect the refrigerant lines using the following procedure:
1. Remove the cap and Schrader core from both the liquid
See "System Charge" section for checking and recording system
and vapor service valve service ports at the outdoor unit. Connect Iow
charge.
pressure nitrogen to the liquid line service port.

Installation Manual

10
6.4 Expelling Air Use refrigerant tank to expel air (see Fig.6-2 and Fig.6-3 )

From the following table, select a method of expelling air. Screw up the pipe nuts at A, B, C and D completely.

Table.6-2 Loosen and remove the square-head cover and the


maintenance orifice nut of valves A and B.
Length of connective pipe
Procedure of expelling air
(single pass) Connect the filler hose of the refrigerant tank with the
maintenance orifice of valve A.
Less than 5m Use refrigerant in the outdoor unit
Loosen the valve of the refrigerant tank, continue filling
refrigerant for 6 seconds to expel the air, and tighten the nut of
Use vacuum pump or refrigerant valve B quickly.
5~15m
tank.
Loosen the valve of the refrigerant tank again, and fill the
refrigerant for 6 seconds. Detect leak for all adapters at A, B, C
If the air conditioner is relocated, be sure to use a vacuum pump and D. After making sure that no leak exists, screw off the filler
or refrigerant tank to expel air. hose. After all the filled refrigerant is expelled, screw up the
maintenance orifice nut of valve A quickly.
Use the refrigerant in the outdoor unit to expel air(see
Fig.6-2and Fig.6-3) Open the square-head spools of valves A and B completely.

Screw up the pipe nuts at A, B, C and D completely. Tighten the square-head cover of valves A and B.

Loosen and remove the square-head cover of valves A and B, Use a vacuum pump to expel the air (Fig.6-4 ): (For method of
rotate the square-head spool of valve B counterclockwise for 45 using the manifold valve, see the operation manual of manifold
degrees and stay for about 10 seconds, and then close the valve)
spool of valve B tightly.
Loosen and remove the maintenance orifice nut of valve A, and
Detect leak for all adapters at A, B, C and D. After making sure connect the filler hose of the manifold valve to the maintenance
that no leak exists, open the maintenance orifice nut of valve A. orifice of valve A (tighten both valve A and valve B).
After all air is expelled, tighten the maintenance orifice nut of
valve A. Connect the filler hose adapter to the vacuum pump.

Open the spools of valves A and B completely. Open the low pressure (Lo) handle of the manifold valve
completely.
Tighten the square-head cover of valves A and B completely.
Start the vacuum pump to extract air. At the beginning of
extracting air, slightly loosen the maintenance orifice nut of valve
B, check whether any air enters it (the vacuum pump noise
Outdoor unit Air side Intdoor unit changes, and the multimeter indicates from negative to 0). Then
A C tighten this maintenance orifice nut.

D Upon completion of vacuuming, tighten the low pressure (Lo)


handle of the manifold valve completely and stop the vacuum
B
pump. Keep extracting air for over 15 minutes. Check whether
Liquid side the multimeter points at -1.0X10 Pa(-76cmHg).
Stop valve pipe adapter
Loosen and remove the square-head cover of valves A and B.
Fig.6-2 After opening valves A and B completely, tighten the
square-head cover of valves A and B.

Remove the filler hose off the maintenance orifice of valve A, and
then tighten the nut.

Manifold valve
Multimeter manometer

-76cmHg
Fig.6-3
Lo-handle Hi -handle

Filler hose Filler hose


Vacuum pum p

Lo pressure valve

Fig.6-4

Installation Manual

11
Inspection panel Drain pipe Inspection panel
Procedure of using stop valve

over 100m m
Open the spool until it touches the stop block. Do not attempt to
open further.

Use a spanner or a similar tool to tighten the bonnet. The bonnet


tightening torque is shown in aboveTable “Tightening torque”.
Bush

over 50m m
Upon completion of installation, open all valves before trial run. (inspection and sweep orifice) Bush
Each unit has two valves of different sizes located at the outdoor (inspection and sweep orifice)
unit side. Of the two valves, one is gas valve and the other is Main drain pipe
liquid valve. The procedure of opening/closing the valve is
shown in the right figure (Fig.6-5).

Floor Type Fig.7-1


Procedure of opening the valve: Open the square-head cover,
use a spanner to capture the square head and open it
thoroughly. Then tighten the square-head cover. Install the drain pipe of the indoor unit

Procedure of closing the valve: Same as the procedure of There is natural drain, please comfirm that the height of drain
opening the valve, but rotate the spanner clockwise thoroughly. pipe is not higher than water collection tray. (See Fig.7-1)

The number of bends and folds of the drain pipe should not
Valve body
System port exceed 2. Try to avoid bends in order to prevent trash
accumulation.
Maintenance orifice
Trial draining of the drain pipe
Connective pipe port Charge water into water collection tray, after the drain water pipe
is installed, check whether the water can be drained smoothly,
and whether the joints are leakage.

Heat insulation of drain pipe


After making sure that the water drains smoothly and no water is
Fig.6-5
leaked, use adiabatic wool bushes to preserve heat of the drain
pipe. Otherwise, condensate will occur.

6.5 Leak Detection


Use soap water or a leak detector to check whether gas leakage
exists at the adapters.

6.6 Heat Insulation


Water
Use heat insulation materials to wrap the part protruding outside collection tray
the flared pipe joint and the refrigerant pipe of the liquid pipe and
the gas pipe, and ensure that no gap exists between them.
220mm

Imperfect heat insulation may lead to condensate drips.

Drain pipe Fig.7-1

7. INSTALL THE DRAIN PIPE


NOTE
Duct Type
Drain pipe trash gains easily at the drainage controller. Be sure
Install the drain pipe of the indoor unit to install a stopper and a structure that cleans up trash easily.

In order to prevent drain overflow, install a drainage controller at


place 1 of the drain pipe. (The drainage controller is designed to Trial draining of the drain pipe
smoothen the drainage when the static pressure outside the unit Open the side panel of the indoor unit, fill water inward, and
is high, especially at the air inlet, in addition to remove stink check whether the water can be drained smoothly. Check water
through the drain pipe.) leak at the joint.

The drain of water is natural. In the construction, the external Heat insulation of drain pipe
pipe of the outdoor unit slants downward at a gradient of After making sure that the water drains smoothly and no water is
1/50~1/100. leaked, use adiabatic wool bushes to preserve heat of the drain
pipe. Otherwise, condensate will occur.
The number of bends and folds of the drain pipe should not
exceed 2. Try to avoid bends in order to prevent trash
accumulation.
In the construction, do not drop trash into the drip tray or drain
pipe of the indoor unit.

Upon completion of installing the drain pipe, remove the


inspection panel. Put water into the drip tray to check whether
the water can be drained levelly and steadily.

Installation Manual

12
8. ELECTRIC CONNECTION Table.8-2
Indoor unit Outdoor unit

Model MTA1-96H(C)QN1 MTA1-180H(C)QN1 MOV-96H(C)N1-X


CAUTION Type Mid. static pressure

Power 208-230V~ 60Hz 208 -230V 3N~ 60Hz


Use special power supply for the air conditioner. Design power
supplies specific to the indoor unit and outdoor unit. The supply Switch capacity of the main
voltage must comply with the nominal voltage. 20/8 20/12 90/70
power suppliy/fuse(A)

The external supply circuit of the air conditioner must have a Indoor unit power cable(mm2)
RVV-300/500 3×2.5 mm2
ground wire, and the power supply ground wire of the indoor unit includes grounded wire
must be connected with the external ground wire firmly. Outdoor unit power cable(mm2)
YCW-450/750 5X16mm2
includes grounded wire
The wiring must be performed by professional technicians RVV-300/500 4×1.0 mm2 (HEAT&COOL)
according to the circuit diagram labels. connective wire of indoor outside unit
RVV-300/500 2×1.0 mm2 (COOL ONLY)
Wire controls connective wire RVVP-300/300 5×0.5 mm2
Distribute the wires according to the relevant electric technical
standards promulgated by the State, and set the Residual Outdoor-outdoorunit COM wire RVVP-300/300 3X0.5mm2(Shield wire)
Current-operated Circuit Breaker (RCCB) properly.
Table.8-3
The power wire and the signal wire shall be laid out neatly and
properly, without mutual interference or contacting the Indoor unit Outdoor unit
connection pipe or valve.
Model MTA1-120H(C)QN1 MTA1-240H(C)QN1 MOV-120H(C)N1-X

No power cable is attached to this equipment. The user can Type Mid. static pressure
select the power cable by reference to the stipulated power
Power 208-230V~ 60Hz 208 -230V 3N~ 60Hz
supply specifications. No joint of wires is allowed.
Switch capacity of the main
40/20 40/20 100/70
Upon completion of wire connection, double check it and then power suppliy/fuse(A)
connect the power supply.
Indoor unit power cable(mm2)
RVV-300/500 3×2.5 mm2
includes grounded wire
An all-pole disconnection device which has at least 3mm
separation distance in all pole and a residual current Outdoor unit power cable(mm2)
YCW-450/750 5X20mm2
device(RCD)with the rating of above 10mA shall be incorporated includes grounded wire
in the fixed wiring according to the national rule. RVV-300/500 4×1.0 mm2 (HEAT&COOL)
connective wire of indoor outside unit
RVV-300/500 2×1.0 mm2 (COOL ONLY)
The appliance shall be installed in accordance with national Wire controls connective wire RVVP-300/300 5×0.5 mm2
wiring regulations.
Outdoor-outdoorunit COM wire RVVP-300/300 3X0.5mm2(Shield wire)

Specifications of power supply


Table.8-1 NOTE
Indoor unit Outdoor unit Please regard the refrigerant pipe system, indoor-outdoor unit
Model MTA1-76H(C)QN1 MTA1-150H(C)QN1
connect to control wire as a integral system.
MOV-76H(C)N1-X
Type Mid. static pressure In case installing the power supply wire and control wire are in
parallel site, please insert these wires in which tubes individually
Power 208-230V~ 60Hz 208 -230V 3N~ 60Hz
and keep adequate spacing between them.
Switch capacity of the main
20/8 20/12 70/50
power suppliy/fuse(A) Please refer to Page 11 for size and quantity of wire
Indoor unit power cable(mm2)
RVV-300/500 3×2.5 mm2
includes grounded wire Table.8-4
Outdoor unit power cable(mm2)
YCW-450/750 5X10mm2 Indoor unit Outdoor unit Outdoor unit
includes grounded wire
RVV-300/500 4×1.0 mm (HEAT&COOL)
2
MFA1-76H(C)RN1
connective wire of indoor outside unit
RVV-300/500 2×1.0 mm2 (COOL ONLY) Capacity(Btu/h) MOV-76H(C)N1-X MOV-96H(C)N1-X
MFA1-96H(C)RN1
Wire controls connective wire RVVP-300/300 5×0.5 mm2
RVVP-300/300 3X0.5mm2(Shield wire) Power 208-230V~ 60Hz 208~230V 3N~ 60Hz
Outdoor-outdoorunit COM wire
Switch capacity of the main
20/10 60/40 70/50
power suppliy/fuse(A)

Size of power supply cable RVV-300/500 YCW-450/750 YCW-450/750


(mm2) 2×2.5 mm2 4×6.0 mm2 4×10.0 mm2

Size of power ground wire RVV-300/500 YCW-450/750 YCW-450/750


(mm2) 2.5 mm2 6.0 mm2 10.0 mm2

connective wire of RVV-300/500 4×1.0 mm2(HEAT & COOL)


indoor/outdoor unit RVV-300/500 2×1.0 mm2(COOL ONLY)

Installation Manual

13
Power supply wire
The specification of power supply wire as follows: Indoor unit
<Power supply wire of outdoor unit>
In case the power cable is individually provides (no power
Control wire between
supply device is in use) indoor unit and outdoor
RCCB Manual switch

unit
Table.8-5
Min. wire size (mm2) Indoor unit power supply

Outdoor unit (main)


Manual
(Metal pipe & synthetic 208-230V~ 60Hz
Item switch(A)
Power resin pipe wire)
RCCB
supply Size
Capacity (Cvaontinuous Ground Capacity Fuse
(Btu/h) length: ≤30 m) wire RCCB Manual switch Outdoor unit power supply
208 -230V 3N~ 60Hz
208- Control wire between
9(A<20m) 100 mA
230V main unit and auxil unit
MFA1-76H(C)RN1 23(20m<A<50m) 6 60 40 Below
~
0.1 sec
60Hz

Outdoor unit (auxil)


208-
9(A<20m) 100 mA
230V
MFA1-96H(C)RN1 23(20m<A<50m) 10 70 50 Below
~
0.1 sec RCCB Manual switch Outdoor unit power supply
60Hz
208 -230V 3N~ 60Hz

Fig.8-2
NOTE
The wire size in the table and the continuous wire length are
applicable to the circumstance where the potential fall amplitude Set the main and auxil units
is within 2%. MTA1-150H(C)QN1、MTA1-180H(C)QN1、MTA1-240H(C)QN1

Where the continuous wire length exceeds the values in the unit (main) unit (auxil)
table, select the wire size according to the relevant rules.

Power wires ( 3
) ( 3
)
The power wires are as follows: (schematic diagram)
Fig.8-3

NOTE
Indoor unit
Please identify outdoor main unit and auxilary unit. Only main
unit connects with signal wire of indoor unit. Users should adjust
Control wire between
indoor unit and outdoor
RCCB Manual switch the dial on electric control board of outdoor unit as follows,
unit otherwise incorrect adjustment may cause malfunction.

Indoor unit power supply


208-230V~ 60Hz com connection between main and auxil units
Outdoor unit

RCCB Manual switch Outdoor unit power supply Signal wire of indoor unit connects to outdoor main unit only and
208 -230V 3N~ 60Hz the control command to outdoor auxil unit is sent by COM wire
connecting with main unit. Make sure to connect COM wire
correctly, otherwise COM error may occur and auxil unit can not
Fig.8-1 start. See following chart for connection:

main unit auxil unit

P Q E (COMwire terminal) P Q E

(COMwire terminal)

3-core shield wire RVVP-300/300 3х0.5mm²


[Optional]

Fig.8-4

NOTE

COM wire can be arranged with the connection pipe . Please


take some protection measure to prevent the wire from aging.

Installation Manual

14
9. ELECTRIC WIRE DIAGRAM

MTA1-76H(C)QN1、MTA1-96H(C)QN1、MTA1-120H(C)QN1

Indoor Unit
L N 1 2 3 4
Wire controller

A B C D E

Fixed-rate wire
controller (option)

5-cord cable
RVVP-300/500 5X0.5mm2

4-cord cable Power supply:


RVV-300/500 4X1.0mm2 208-230V~ 60Hz
3-cord cable
Signal wire
4
Outdoor unit

3
2
1
Power supply wire

Power supply:
(L1 L2 L3 N)
B C N

208 -230V 3N~ 60Hz


5-cord cable
YCW-450/750 5X10mm2 MTA1-76HQN1
A

YCW-450/750 5X16mm2 MTA1-96HQN1


YCW-450/750 5X20mm2 MTA1-120HQN1

Fig.9-1
This wire diagram is applicable to both cooling and heating model .

Indoor Unit
L N 1 2 3 4
Wire controller

A B C D E

Fixed-rate wire
controller (option)

5-cord cable
RVVP-300/500 5X0.5mm2

2-cord cable Power supply:


RVV-300/500 2X1.0mm2 208-230V~ 60Hz
Signal wire

3-cord cable
4
Outdoor unit

3
2
1
Power supply wire

Power supply:
(L1 L2 L3 N)
B C N

208 ~230V 3N~ 60Hz


5-cord cable
YCW-450/750 5X10mm2 MTA1-76CQN1
A

YCW-450/750 5X16mm2 MTA1-96CQN1


YCW-450/750 5X 20mm2 MTA1-120CQN1

This wire diagram is applicable to cooling only model.


Fig.9-2

Installation Manual

15
MTA1-150H(C)QN1、MTA1-180H(C)QN1、MTA1-240H(C)QN1

Indoor Unit
L N 1 2 3 4
Wire controller

A B C D E

Fixed-rate wire
controller (option)

Power supply: 5-cord cable


RVVP-300/500 5X0.5mm2
208-230V~ 60Hz
4-cord cable 3-cord cable
RVV -300/500 4X1.0mm
2

Power supply: Power supply:


208-230V 3N~ 60Hz 208 -230V 3N~ 60Hz
5-cord cable 5-cord cable
3-core shielded wire YCW-450/750 5X 10mm2
YCW-450/750 5X10mm2 (MTA1-150HQN1)
RVVP-300/300 (MTA1-150HQN1)
3 X0.5mm2 YCW-450/750 5X16mm2 (MTA1-180HQN1)
YCW-450/750 5X 16mm2
YCW-450/750 5X20mm2 (MTA1-240HQN1) (MTA1-180HQN1)
YCW-450/750 5X 20mm2
(MTA1-240HQN1)

( )
E 1 2 3 4 A B C N E 1 2 3 4 A B C N

( )
P Q P Q

(L1 L2 L3 N) (L1 L2 L3 N) 3
3

SW1
COM wire between outdoor Signal wire Power supply wire COM wire between outdoor Signal wire Power supply wire
units(weak current) units(weak current)

0# unit (main) Outdoor unit (main unit) Outdoor unit ( auxil unit) 1# unit (auxil)

This wire diagram is applicable to both cooling and heating model. Fig.9-3

Indoor Unit
L N 1 2 3 4
Wire controller

A B C D E

Fixed-rate wire
controller (option)

Power supply: 5-cord cable


RVVP-300/500 5X0.5mm2
208-230V~ 60Hz
2-cord cable 3-cord cable
RVV -300/500 2X1.0mm
2

Power supply: Power supply:


208-230V 3N~ 60Hz 208 -230V 3N~ 60Hz
5-cord cable 5-cord cable
3-core shielded wire YCW-450/750 5X 10mm2
RVVP-300/300 YCW-450/750 5X10mm2 (MTA1-150CQN1)
(MTA1-150CQN1)
3 X0.5mm2 YCW-450/750 5X16mm2 (MTA1-180CQN1)
YCW-450/750 5X 16mm2
YCW-450/750 5X20mm2 (MTA1-240CQN1)
(MTA1-180CQN1)
YCW-450/750 5X 20mm2
(MTA1-240CQN1)

B C N B C N
( )
P Q E 1 2 3 4 A P Q E 1 2 3 4 A

( ) (L1 L2 L3 N) (L1 L2 L3 N)
Signal wire Signal wire
3
3

SW1
COM wire between outdoor Power supply wire COM wire between outdoor Power supply wire
units(weak current) units(weak current)

0# unit (main) Outdoor unit (main unit) Outdoor unit ( auxil unit) 1# unit (auxil)

This wire diagram is applicable to cooling only model. Fig.9-4

NOTE
Pay attention to the phase sequence of the power supply. If the phase sequence is reversed, the compressor will not start.
Meanwhile, the fault indicator of the outdoor electric control board will light up. For details, see Outdoor unit wring diagram on the
cover plate of the electric control box .

After shifting the phase sequence, power on the unit until the fault indicator goes out and the compressor starts up normally.

Installation Manual

16
MFA1-76H(C)RN1、MFA1-96H(C)RN1

Indoor unit
Signal wire Power supply wire
1 2 3 4 5 L N

Power supply
Signal wire

208-230V~ 60HZ
4
3

3-cord cable
Outdoor unit

RVV 300/500 3x2.5mm2


1

4-cord cable
2
RVV-300/500 4X1.0mm
Power supply wire

Power supply
(L1 L2 L3 N)

208-230V 3N~ 60HZ


B C N

5-cord cable
YCW-450/750 5x6mm2 MFA1-76H(C)RN1
A

YCW-450/750 5x10mm2 MFA1-96H(C)RN1

This wire diagram is applicable to both cooling and heating model .


Fig.9-1

Indoor unit
Signal wire Power supply wire
1 2 3 4 5 L N

Power supply
Signal wire

208-230V~ 60HZ
4

3-cord cable
3

RVV 300/500 3x2.5mm2


2
1
Outdoor unit

2-cord cable 2
RVV-300/500 2X1.0mm
.0mm
Power supply wire

Power supply
(L1 L2 L3 N)

208-230V 3N~ 60HZ


A B C N

5-cord cable
YCW-450/750 5x6mm2 MFA1-76H(C)RN1
YCW-450/750 5x10mm2 MFA1-96H(C)RN1

This wire diagram is applicable to cooling only model.


Fig.9-2

NOTE
Pay attention to the phase sequence of the power supply. If the phase sequence is reversed, the compressor will not start.
Meanwhile, the tindicator of the outdoor electric control board will light up. For details, see Outdoor unit wring diagram on the cover
plate of the wire controller.

After shifting the phase sequence, power on the unit until the fault indicator goes out and the compressor starts up normally.

Installation Manual

17
10. TRIAL RUN Indoor unit

Please conduct in accordance with “Trial Run Tenor Nameplate” Check whether the switch of the remote controller or wire
on the electric control box. controller is normal.

Check whether the functional keys of the remote controller or


wire controller are normal.
CAUTION
Check whether the indoor temperature conditioning is normal.
Perform the trial run only after the outdoor unit has been
powered on for over 12 hours. Check whether the indicators illuminate normally.

Check that all valves are opened before trial run. Check whether the manual operation buttons are normal.

Check the electric safety before trial run. Check whether the drain function is normal.

Do not perform compulsory operation in any way.(It is very Check whether the connective copper pipes and the drain pipes
dangerous if the protection device is not active) generate condensate due to loose wrapping.

Open the air inlet grille to check whether any penetration or leak
of water occurs, especially at the drain stopper.
Perform trial run only after all installations are finished.
Check whether any vibration or abnormal sound occurs during
Confirm the following issues before trial operation, and the the operation.
box for the confirmed items.
Test whether the unit works normally in the heatig mode.
Check whether the indoor unit and the outdoor are
installed properly. Outdoor unit

Check whether the piping and wiring are correct. Check whether any vibration or abnormal sound occurs during
the operation.
Check whether the refrigerant pipeline system is
inspected for leakage. Check whether the air, noise and condensate generated by the
unit affect the neighbors.
Check whether the drain is smooth.
Check whether any refrigerant is leaked.
Check whether the heat insulation is perfect.

Check whether the ground cables are connected


correctly.

Check whether the pipe length and the refrigerant


amount are recorded.

Check whether the supply voltage is equal to the rated


voltage of the air conditioner.

Check whether any obstacles exist at the air


inlet/outlet of the indoor or outdoor unit.

Open the gas valve and the liquid valve.

Connect the power supply to preheat the air


conditioner.

Install the remote controller holder as required by the user.


The holder must be installed in a location suitable for
transmitting the signals of the remote controller to the indoor
unit.

Trial run
Use the remote controller or wire controller (matched) to let the
air conditioner run in the cooling mode. Inspect the following
items against the operation manual. (If any fault occurs, remove
the fault by reference to the Section headed “Faults of Air
Conditioner and Causes” in the Operation Manual.)

Installation Manual

18
16123100000036 V.D
此页不做菲林

版本A升级为版本B:第一页增加“Before installing the


unit,it is necessary to check whether the ground wire is
charged.If it is,the unit shall not be installed before
correction.”
“Before installing the unit,be sure to confirm with the user
whether there are wires,water pipes,air pipes and so on in the
wall or ground of the installation site to avoid accidents due
to damage. ”
版本B升级为版本C:
1.外机供电相序增加“(L1 L2 L3 N)” 标识;
2.网络拨码增加与新主板一致的拨码标识。

此页不做菲林,说明书更改说明
技术要求
双胶纸80g,黑白印刷,210*297mm

2020.7.23
增加技术要求,内容不变,故不升级版本

2021.1.21
更改材质为双胶纸80g,内容不变,故不升级版本

C-D 20210129
安装空间增加离地高度2.5m要求

You might also like