You are on page 1of 2

Note

Curve TMS (s) Ip (A)


EI 0.05 5 NI Normal Invert
VI Very Invert
Table 1 EI Extremly Invert
If/Ip If (A) Trip Time (s)
1.5 7.5 3.200 *Change value only in green

Table 2 t(s) = A x TMS


If/Ip If (A) Trip Time (s) ((If/ Ip)^B)-1
1.5 7.5 3.200
2 10 1.333
3 15 0.500
1.400

Trip Time (s)


4 20 0.267
5 25 0.167 1.200
6 30 0.114
7 35 0.083 1.000
8 40 0.063
9 45 0.050 0.800
10 50 0.040
0.600

0.400
How to use table 0.200
1. Select Curve type
2. Enter TMS (Time multiplier Setting) 0.000
3. Enter Pickup Current .0 .0 .0 .0 .0 .0
4. Table 1 Enter Fault current (If) 10 15 20 25 30 35
5. Table 2 Change "If/Ip" if necessary Fault Current (A)

TMS : Time Multiplier Setting


Ip : Pickup Current
If : Fault Current
A B
0.14 0.02
13.5 1
80 2

alue only in green

A x TMS
((If/ Ip)^B)-1

.0 .0 .0 .0 .0 .0 .0
20 25 30 35 40 45 50
Fault Current (A)