You are on page 1of 56

GE

Industrial Solutions

3.3kV-27kV
Embedded Pole
Vacuum Circuit Breaker
Leading the future of electrification
3.3kV-27kV
Embedded Pole
Vacuum Circuit Breaker
Leading the future of electrification
About GE
GE (NYSE: GE) works on things that matter. The best people and the best technologies taking on
the toughest challenges. Finding solutions in energy, health and home, transportation and
finance. Building, powering, moving and curing the world. Not just imagining. Doing. GE works.
For more information, visit the company's website at www.ge.com.

Industrial Solutions
Industrial Solutions, a GE heritage business, is leading the future of electrification with
advanced technologies that protect and control the distribution of electricity throughout a
facility's infrastructure. We provide customers, across various industries, with end-to-end
product and service solutions that ensure the reliability and protection of the electrical
infrastructure; from the substation, to a facility's critical equipment, and all the power
technologies in between.

Find more information on www.geindustrial.com

Honour
2013 2010 World's Most Innovative Companies
2013 World’s Most Admired Companies

2012 World’s Most Respected Companies

2012 Best Global Brand

2010 World’s Most Respected Companies


More Than 90 Years

90 of Interrupter
Experience
GE pioneered experimental vacuum
interrupters in the 1920s. Refined it and
introduced the world's first 15kV Vacuum
circuit breaker in the 1960s, To date, this
interrupter design has been the world
leader in vacuum technology and has
accumulated over 55 years of reliable field
service.

Universal

A Applications
SecoVac is designed, assembled and tested
to meet or exceed applicable IEC, GB and
DL standards. It is suitable for applications
in all major industries including T&D, Oil
& Gas, Automotive, Processing plants,
World Class Quality Iron and Steel mills, Mining, Commercial
buildings, etc.
Manufactured, assembled and tested It provides protection for all types of
all in the same sophisticated facility, applications: coble, overhead lines, motors,
SecoVac is the product of state of the art capacitors, transformers, busbar sections,
manufacturing processes assured by ISO etc.
9001:2008 and ISO 14001 certification.
Precision tooled parts, computer aided
design and advanced production
techniques, as well as the protection of
the 'E Coat' (cathodic electrocoating) paint
process have resulted in a standard of
excellence unmatched in the industry.

Environment
Conscious
eco Selecting low environmental impact
technologies has become increasingly
important to engineers tasked with
choosing equipment for an application.
With commitment to environment
protection, the solid insulation of epoxy
resin is used for SecoVac series MV
embedded pole vacuum circuit breaker
instead of SF6 gas.
Contents
General Introduction
GE
GE Industrial Solutions
Description
Brief Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 02
Vacuum Interrupter (VI) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 04
Application Condition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 05
Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 06
Advanced Technology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 08
Standards and Quality Control . . . . . . . . . . . . . . . . . . . . . . . . 08
Environmental Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Selection Guide
Product Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Front panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Primary disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Breaker mechanism . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Interlock system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Undercart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Circuit Breaker Characteristics . . . . . . . . . . . . . . . . . . . . . 14
Main circuit resistance of SecoVac . . . . . . . . . . . . . . . . . . 14
Coil Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Motor Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Generator Circuit Breaker and Generator Switchgear . . 15
Generator Faults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
SecoVac VB2+G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
IEC/IEEE 62271-37-013 Combined Standard . . . . . . . . 19
SubSea applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Extreme vibration testing . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Fuse Contactor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Overall dimension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
SecoVac VB2 Plus L-frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Measurement, Protection and Control
Multilin 650 Family . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Multilin 3 Series. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Operation
Internal Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Working Principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Vacuum interrupter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Working principle of operating mechanism . . . . . . . . . . . . 42
Motor spring charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Closing operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Anti-Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Tripping operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Reclosing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Interlocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Preparation Work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Ordering Check List
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

3.3kV-27kV Embedded Pole


Vacuum Circuit Breaker
Introduction
SecoVac series 3.3kV-27kV vacuum circuit breaker designed by
Description

GE is a three-phase AC indoor breaker which can be applied in


controlling and protecting electrical equipment in industrial and
mineral enterprises, power plants and substations.
The product conforms to the IEC62271-100 standard. It is
especially suitable for conditions which require frequent operation.
The breaker can be installed in the switchgear both in fixed type
and withdrawable type. It is the optimum choice for the control
and protection of MV power distribution systems.

02
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Reliability, safety and performance in a compact package


SecoVac 3.3kV-27kV Vacuum Circuit Breakers Provide:

Description
Leading vacuum and Built to highest quality standards Reliability and safety
insulation technology

GE has developed environmentally SecoVac circuit breakers are designed SecoVac circuit breakers have a number
friendly vacuum circuit breakers which and fully third-party KEMA type tested to of inbuilt safety capabilities which can be
are capable of reliably switching high the latest IEC 62271-100 and IEC 62271- incorporated into the switchgear design.
stress fault currents. Increased dielectric 1 standards. All SecoVac circuit breakers Due to its innovative operating
strength of the SecoVac circuit breaker meet or exceed the electrical and mechanism the SecoVac breaker has
is achieved through encapsulation of mechanical endurance requirements of industry leading reliability that is rated at
the vacuum interrupter in epoxy resin E2 and M2 in accordance with IEC 62271- 10,000 operations.
material. SecoVac circuit breaker family 100.
utilizes this solid insulation technology
that has been catering to a wide scope of
applications for years.

Adaptability and versatility


SecoVac circuit breakers can be used in a
Storage conditions wide scope of applications such as the

In order to retain all of the functional protection of transformers, capacitor

units qualities when stored for prolonged banks, motors. The breaker can be used

periods, we recommend that the in a wide range of environments to suit all


Environmentally-friendly design regions of the globe.
equipment is stored in its original
GE’s vacuum and solid insulation packaging in dry conditions sheltered
technology is free of SF6 gas that from the sun and rain at a temperature
contributes significantly to the greenhouse of between -15°C and 40°C. For storage:
effect and associated climate change. -30°C.

03
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Vacuum Interrupter (VI)

Maintenance free

GE vacuum interrupters are hermetically


sealed and offer extensive vacuum
integrity. Dedicated to proven reliability,
safety and performance, GE vacuum
interrupting technology offers highest
quality products which are sealed for life.
Description

Structural durability

At the heart of the 3.3kV-27kV IEC circuit SecoVac circuit breaker is an embedded
breaker portfolio is GE’s proven vacuum pole type, which is extremely durable.
interruption technology and ninety years of
It can protect the vacuum interrupter
expertise in this field.
from mechanical and climatic influence
such as humidity, moisture and dust.
The vacuum interrupter is where current making and The interrupter is immune to shock and
breaking occurs. Copper chromium contacts provide vibration.
superior performance characteristics. The vacuum in the
arc chamber protects the copper chromium contacts from
adverse effects such as contamination and corrosion. High performance

SecoVac circuit breakers provide you with:


●● High dielectric strength

●● High creepage distance

●● High mechanical strength

●● Low moisture absorption

●● Optimum thermal conductivity

Compact size

Combined with GE's embedded pole


technology, SecoVac circuit breaker has a
very compact design. It offers high current
and interruption ratings in a small, cost
effective package.

04
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Application Condition

High performance Special application condition

●● The ambient air temperature does not If the actual application conditions differ
exceed 40°C and its average value, from the normal application conditions,
measured over a period of 24 hours, circuit breaker and associated devices
does not exceed 35°C. The minimum and auxiliary equipment shall be designed
ambient air temperature is –15°C and manufactured to comply with any
(storage and transportation is allowed special application conditions. For special

Environment
at -30°C) application conditions please consult with
●● For applications above 1,000m please GE in advance, normally the following

Description
refer to chapter 4.2.2 of IEC 60071-2 special service conditions maybe
(see following table for reference) encountered:
●● The conditions of humidity are as ●● The installation location is more than
follows: 1,000m above sea level
- The average value of the relative ●● The ambient temperature is between
humidity, measured over a period of -15°C and 40°C, for other conditions
24 hours, does not exceed 95% please contact GE sales for further
- The average value of water vapor detail
pressure, measured over a period of ●● The circuit breaker current and
24 hours, does not exceed 2.2kPa dielectric ratings must be lowered for
- The average value of the relative high altitude and elevated temperature
humidity, measured over a period of applications
one month, does not exceed 90% ●● Marine and SubSea conditions. Refer to
- The average value of water vapor specific chapter in the catalogue.
pressure, measured over a period of
one month, does not exceed 1.8kPa
●● Seismic intensity to UBC zone 4 or GB
intensity 9
●● No adverse operating environment
such as dust, humidity, vermin, polluted
ambient and high altitude operating site

Altitude Derating MV
m K (m=1) V K (m=0.9) In
1,000 1 1 1 1
1,500 1.062 0.94 1.056 0.95
2,000 1.132 0.88 0.12 0.89
2,500 1.2 0.83 1.18 0.85
3,000 1.28 0.78 1.246 0.80
3,500 1.36 0.74 1.32 0.76
4,000 1.44 0.69 1.39 0.72
IEC 60071-2, 4.2.2 the altitude correction factor can be calculated using the following equation,
which modified to reflect that no correction is required up to 1000m.

Where Kа=e m(H-1000)/8150

H Is the altitude, in metres


m Is taken as a fixed value in each case for simplification as follows
m = 1 for power frequency, lightning impulse and phase-to-phase switching impulse voltages
m = 0.9 for longitudinal switching impulse voltages

05
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Applications

Utilities and power plants


Power generation stations
Transformer stations
Switching stations
Main and auxiliary switchgear

Industry
Description

Oil and Gas


Mining
Pulp and Paper
Cement
Textiles
Chemicals
Automotive
Petrochemical
Data Center
Metallurgy

Transport
Airports
Ports
Railways
Underground transport

Services
Supermarkets
Shopping malls
Hospitals
Large infrastructures and civil works

Marine & SubSea


Drilling and Exploration
Merchant
Cruise
FPSO
Naval
Subsea trees

06
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Applications Description

07
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Advanced Technology Standard and Quality Control


High adaptability

●● Compare to traditional design,

enhanced reliability
●● Less resistance

●● Less mechanical parts

●● Various applications for different

climates
Description

Quality Type test

SecoVac circuit breakers provide you with: ●● Dielectric test

●● IEC standard, 3rd party KEMA ●● Temperature rise test

certification ●● Short circuit withstand current test

●● Advanced manufactoring process ●● Mechanical operation test

ensured quality ●● ES-Mechanical operation test

●● Advanced testing equipment ●● Capacitive current switching test

Mechanical structure ●● Integrated routine test

●● Single modular design

●● Integrate closing/opening module

●● Compact size, less than 86 parts

●● Enhanced reliability

●● Low maintenance

Standard

3.3kV-27kV Embedded Pole Vacuum ●● Alternating current disconnector and

Breaker complies with the standards and earth switches


specifications and has been type tested ●● IEC 62271-1:2007 the common

in accordance with the following IEC specification for high voltages


publications: switchgear and control gear standards
●● IEC 62271-100:2008 high-voltage ●● IEC 60529:2001 degrees of protection

alternating current circuit breaks as provided by enclosures (IP code)


●● IEC 62271-200:2003 AC metal enclosed

switchgear and control gear for rated


voltages above 1kV and up to 52kV

08
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

The state-of-the-art processing and advanced quality control


The high quality of the embedded pole is achieved by using the latest APG (Auto Pressure

Quality Control
Gelation) technology and advanced vacuum mixing and degassing technology. The
Vogel clamping machine is an essential piece of equipment to ensure the mechanical
and insulating strength of the embedded pole of 3.3kV-27kV series MV embedded pole
vacuum circuit breaker.
As well as the processing facilities, the testing facilities are also very important to the
quality control of the breaker. In the manufacturing process of SecoVac, from incoming
material quality control to the final inspection and testing, every step is strictly calibrated
and tested.
Every embedded pole goes through the following inspection and testing before it is

Description
allowed into the breaker assembly line:
●● X-ray inspection

●● Power frequency withstand voltage test

●● Partial discharge measurement

●● Thermal cycling test

Before delivery, the following tests and inspections will be done for 3.3kV-27kV
embedded pole vacuum circuit breakers in factory by means of advanced testing
equipment:
●● Dynamic characteristics measurement (Closing/opening speed, contact bounce, wipe

etc.)
●● Power frequency withstand voltage testing

●● Inspection of interlocking system between breaker and withdrawable unit

●● Secondary wiring inspection

●● Circuit resistance measurement

09
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Environmental Protection
Selecting low environmental impact technologies has become
increasingly important when choosing equipment for an
application. With commitment to environment protection, the
solid insulation of epoxy resin is used for 3.3kV-27kV series MV
embedded pole vacuum circuit breaker instead of SF6 gas.

Manufactured, assembled and tested all in the same sophisticated


facility, SecoVac is the product of state-of-the-art manufacturing
processes assured by ISO 9001:2000 and ISO 14001 certification.
Using precision tools, computer-aided design and advanced
Description

production techniques.

10
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Selection Guide
Product Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Front panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Primary disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Breaker mechanism . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Interlock system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Undercart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Circuit Breaker Characteristics . . . . . . . . . . . . . . . . . . . . . . . . 14
Main circuit resistance of SecoVac. . . . . . . . . . . . . . . . . . . . . 14
Coil Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Motor Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Generator Circuit Breaker and Generator Switchgear . . . . . 15

Selection Guide
Generator Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
SecoVac VB2+G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
IEC/IEEE 62271-37-013 Combined Standard . . . . . . . . . . . 19
SubSea applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Extreme vibration testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Overall dimension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
SecoVac VB2 Plus L-frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

11
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Selection Guide

Product Structure

SecoVac 3.3kV-27kV Breaker Features

Front panel Breaker mechanism

Front panel fits into a collar frame in the All the mechanical parts of the mechanism
equipment when the breaker is in the are integrated into individual opening
service position. It provides a metal barrier and closing modules. The modules are
between the breaker compartment and universal to SecoVac embedded pole
the secondary device compartment. vacuum circuit breaker series, regardless
Clearly marked and easy-to-read of rating. The module design assures no
Selection Guide

operating controls and indicators include mechanical adjustment is required after


trip button, close button, open/close replacement. This offers the user shorter
indicator, charge/discharge indicator, lead-times and reduces operational and
operations counter and provision for maintenance costs.
manually charging the breaker. Primary disconnect

The primary disconnect cycloid (tulip)


contact set is rugged and easy-to-inspect.
Designed for optimum contact area,
it is manufactured from silver-plated
copper and tested for continuous and
short-circuit current ratings. The tulip
cluster design expands easily, providing
better finger contact area than flat type
contact designs, and delivering proper
contact integrity throughout the life of the
equipment.

12
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Interlock system Undercart


For personnel safety, SecoVac 3.3kV-27kV Secogear and SecoBloc offers manual
is designed with a number of mechanical operation undercart system which can
and electrical interlocks. For example, be operated for racking in and out. The
breaker contacts must be open before undercart has an interlock with earthing
the breaker can be moved from test to switch, which prevents misoperation. And
service position. A positive mechanical it also allows earthing function of circuit
stop is provided when the breaker breaker by means of metallic structure.
reaches the service or test/disconnect
positions. Mechanical rejection interlocks
are provided to permit only the insertion
of properly rated breakers into specific
compartments.
These and other necessary interlocks
provide a comprehensive safety system.
Furthermore, springs automatically
discharge when the breaker is withdrawn
from the service position and breakers
cannot be inserted in the closed position. Typical layout for vacuum circuit breaker

1 Tripping button
1

Selection Guide
2 Status indicator for charging 3
2
4
3 Closing button
5

4 Counter 6

5 Indicator for open or close

6 Charging handle
Figure 1. Front facial of the circuit breaker

Upper contact arm 2


1
3
2 Embedded poles

4
3 Lower contact arm

4 Tulip cluster

Figure 2. Primary circuit

13
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Circuit Breaker Characteristics


Rated Voltage kV 7.2 12 15 17.5 24 27
Rated power frequency withstand (1min) kV 20 28 36 38 50 65
Rated lightning frequency impulse withstand voltage
kVp 60 75 95 95 125 125
(1.2/50μs)
Rated Frequency Hz 50/60 50/60
Rated Current A 630/1250/1600/2000/2500/3150/4000* 1250, 2500
Rated short-circuit breaking current kA 25/31.5/40/50 31.5
Percentage of DC component   Up to 50% 52%
Rated short-circuit closing current kAp 65/82/104/130 82
Rated short time withstand current kA 25/31.5/40/50 31.5
Rated peak value withstand current kAp 65/82/104/130 82
Rated duration time for short-circuit s 3 3
Opening Time ms 20~50 20~50
Closing Time ms 30~70 30~70
Rated auxiliary control voltage V 24/36/48/60/110/220 V DC 110/220 V AC
Mechanical life operations Quantity 15,000 (M2) 10,000 (M2)
Electrical Endurance class   E2 E2
Single capacitor bank Switching current A 400 400
Rating for Earthing Switch short time withstand current 31.5/40/50 1s 31.5kA 1s

* Force cooling
** 3 phase back to back capacitor bank switching current 630A only for 17.5kV 3150A 40kA breaker

Main circuit resistance of SecoVac


Item Unit Value
Rated Current A 1250~1600 2000~4000
Resistance μΩ ≤ 45 ≤ 25

Coil Characteristics
Selection Guide

Type Name (GE) Rated Voltage (DC.V) Resistance Value (Ω) Rated Current (A) Inrush Current (A) Maximum Power (W)
P-C1X 110 (DC/AC) 51 2.2 12.9 237.3
P-C2X 220 (DC/AC) 198 1.1 6.7 244.4
P-C3X 24 1.8 13.3 80 320
P-C3L 24 1.3 18.5 110.8 443.1
P-C4X 30 1.6 18.8 112.5 562.5
P-C5X 36 3.1 11.5 69.2 415.4
P-C6X 48 3.1 15.5 92.9 743.2
P-C7X 60 10.8 5.6 33.4 334
P-C8X 125 (DC/AC) 45 2.8 16.7 347.2
P-C9X 230-240 (DC/AC) 320 0.7-0.8 4.3-4.5 165.9-180
P-C10X 250 (DC/AC) 216 1.2 6.9 289.4

Motor Characteristics
Rated voltage (V) Normal operation voltage range Charging time at rated voltage (s) Input Power (W)
DC 24 85%-110% <15s 150
DC 30 85%-110% <15s 150
DC 48 85%-110% <15s 150
DC 60 85%-110% <15s 150
DC 110 85%-110% <15s 150
DC 125 85%-110% <15s 150
DC 220 85%-110% <15s 150
DC 230-240 85%-110% <15s 150
AC 110 85%-110% <15s 150
AC 125 85%-110% <15s 150
AC 220 85%-110% <15s 150
AC 230-240 85%-110% <15s 150

14
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Generator Circuit Breaker and Generator Switchgear

Generator Faults Step-up


Generator Transformer High Voltage
Generator Circuit Breaker Circuit Breaker
The fault conditions in the proximity of a
a b
generator source are more demanding
than those in normal distribution circuits.
These special fault characteristics require
Fault at “a” Fault at “b”
specifically designed and tested circuit
breakers.
Generator-source short-circuit current As vacuum interrupters rely on a current
The critical points to be considered are: If there is a short circuit (point “b”, figure zero to break the current, the delay it
1) the current is fed by the generator on results in longer arcing time with extreme
Generator Circuit Configuration the transformer side. The fault currents, thermal stress on the interrupter.
As a result of the circuit configuration, two while relatively smaller in magnitude, are
key unique fault current conditions are subject to a phenomenon called Delayed The generator circuit breakers are tested
encountered by generator circuit breakers Current Zero. This unique characteristic according to IEC/IEEE 62271-37-013 to
(figure 1) is a result of the very high X/R ratio of the withstand the high electrical, thermal and
circuit and the operating conditions of the mechanical stress during the interruption
generator, which can combine to produce of fault currents with a DC component of
System-source short-circuit current
a DC component of the fault current up to 130 %. Normally this short circuit
The short circuit fed by the transformer
exceeding 100%. The asymmetrical fault current will be 50% of system source
(point “a”, figure 1) on the generator side

Selection Guide
current peak becomes so high and its short circuit current with very high DC
leads to high thermal and mechanical
decay becomes so slow, that the current component.
stresses on the vacuum interrupters
zero can be delayed for several cycles.
because the full energy of the power
system feeds the fault. To clear these
faults, Generator Circuit Breakers
are capable to interrupt not only the
symmetrical fault but also the higher
asymmetrical fault currents with a DC
component of up to 75%. This will be the
maximum short circuit current the breaker
needs to interrupt with peak making and
withstand capacity of 2.74 times the RMS
current

15
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Unique Voltage Conditions


Generator circuits are typically designed
for high efficiency in order to minimize
the power loss of the system. Therefore,
the generator circuit breaker may be
located very close to both the generator
and transformer, connected by short
conductors with a large cross-section,
resulting in a very low resistance and low
stray capacitance. These characteristics
combine to produce very high natural
circuit frequencies resulting in extreme
Transient Recovery Voltages (TRV) with
high Rates of Rise of Recovery Voltage
(RRRV).

Transient Recovery Voltages (TRV) Very fast Rate of Rise of Recovery Voltage Out of phase switching
The circuit produces the peak value of (RRRV) The out-of-phase voltage conditions can
TRV, which is nearly double the line-to- An important factor is how fast the TRV occur during normal start-up when the
line system voltage, across the contacts rises across the recovering gap after generator and power system voltages
within microseconds following the current current zero. This is measured by the RRRV, are not in sync. Initially, the generator is
zero. The Vacuum Interrupter must re- which is proportional to the peak value off and the generator circuit breaker is in
Selection Guide

establish dielectric strength across the of the transient voltage in kV, divided by the open position with the power system
open contacts gap in order to withstand the time it takes the voltage to reach that operating. The voltage across the open
this fast rising TRV. If the interrupter is peak value in microseconds. circuit breaker contacts is equal to the
able to withstand that voltage, then the normal power system voltage. When
interruption is successful. Values for standard Medium Voltage additional or emergency power is desired,
distribution circuits are in the range of 0.4 the generator is started and begins to
to 1 kV /microsecond, while RRRV values produce voltage. As the generator comes
for generator circuits are about 3.5 kV / up to speed, the generator output voltage
microsecond. and frequency slowly increase. This causes
the voltage across the open contacts of
These characteristics where tested for the the circuit breaker to vary.
for the first time at the KEMA laboratories
in Netherlands using a Direct on Line IEC/IEEE 62271-37-013 requires that the
connection with GE’s SecoVac VB2+G generator circuit breaker can switch off
Generator Vacuum Circuit Breaker. under out-of-phase conditions (out-of-
phase angle 90°) while the voltages across
the open contacts can be as high as twice
the rated line-to ground voltage of the
system.

16
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

SecoVac VB2+G Benefits

Performance requirements for Generator The SecoVac VB2+G generator circuit


Circuit Breakers are specified in the IEC/ breaker is based upon the same design
IEEE 62271-37-013 standard. This is a principles as our distribution type
combined standard intended to replace SecoVacVB2+ breaker this results in
the IEEE C37.013 and fill the gap of the IEC Applications advantages for electrical designers,
which has never had a generator breaker operating personnel and maintenance
A properly protected generator unit
standard previously. staff .
increases its levels of reliability, availability
and safety, and by extension the same
The new SecoVac VB2+G 15kV have The SecoVac VB2+G is designed to
for the complete electrical system where
passed all the Type Tests as per the new be fitted into GE’s SecoGear range of
is being operated. Even the smaller
IEC/IEEE combined standard, becoming medium voltage type tested IEC panels.
generator units can produce high DC
the first Generator Circuit Breaker of the The SecoGear range can accommodate
component or Transient Overvoltage
SecoVac family. generator, distribution circuit breakers
levels requiring special breakers intended
and fuse contactors within the same
to protect such fault conditions.
The standard SecoVac VB2+ breaker and standard panel design offering industry
the SecoVac VB2+G generator circuit leading safety, reliability and performance
With this new addition to the SecoVac
breaker can be used in all SecoGear features to meet the requirements for
family, SecoGear is perfectly set to
IEC switchgear panels. With the same all Medium Voltage Distribution in Power
protect Generators. Applications up to
functionality and footprint of conventional Plant applications.
60MVA, 31.5kA, 15kV can be operated
IEC Switchgear while getting all the
with SecoVac VB2+G. These power output
benefits from a fully proven Generator In addition to being able to be supplied

Selection Guide
ranges are commonly used on:
Circuit Breaker. as part of a complete switchgear lineup,
●● Distributed Power Generation
SecoVac VB2+G can be supplied as part of
-Diesel/Gas Engines
SecoVac VB2+G can also be installed in GEs SecoBloc OEM modules. SecoBloc is
-Small Frame Gas Turbines
SecoBloc modules, producing the perfect designed specifically to allow OEM panel
-Aero Derivative Turbines
combination for OEM manufacturers builders to incorporate a type tested
●● Marine Diesel-Electric Generators
building generator switchboards. circuit breaker and cable compartment
●● Oil and Gas Start-up/Back-up
into their customer built switchboard
Generator units
arrangement. VB2+G modules are
●● Mining Power Plants
available in various configurations to suit
●● Small Hydro
specific generator applications.
●● Small Steam Turbines

17
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Technical Data

Rated short-circuit breaking current: kA 31.5 40 50

Rated Voltage: kV 15 15 15

Rated Current: A 2500/3150/4000* 2500/3150/4000*/5000* 2500/3150/4000*

Rated Frequency: Hz 50/60 50/60 50/60

Rated power Freq withstand voltage (1 min): kV 38 38 38

Rated lightening impulse withstand voltage: kVp 95 95 95

Operation sequence: CO – 30min - CO CO – 30min - CO CO – 30min - CO

Generator Circuit Class: G2 G2 G2

'a' – System 'b' – Generator 'a' – System 'b' – Generator 'a' – System 'b' – Generator
Location of fault
supplied fault supplied fault supplied fault supplied fault supplied fault supplied fault

Rated short-circuit breaking current: kA 31.5 15.8 40 25 50 25

Rated short-circuit making current: Ipeak kAp 86.3 34.1 110 54 137 54

Interrupting Time ms 50 50 50

Minimum Opening Time ms 24.3 24.3 24.3

Degree of Asymmetry % 75 130 75 130 75 130

Asymmetry interrupting capability kAp 46 34.1 58.4 36.5 73 36.5

Close and Latch Capability kAp 86.3 110 110


Selection Guide

Rated short time withstand current: kA 31.5 N/A 40 N/A 50 N/A

Rated duration time for short-circuit s 3 N/A 3 N/A 3 N/A

Rate of Rise of Recovery Voltage (RRRV) kV/μs 3.5 3.5 3.5 3.5 3.5 3.5

Peak Recovery Voltage kV 27 27 27 27 27 27

Out-of-Phase Current Switching

Duty Voltage kV 21.2 N/A 21.2 N/A 21.2 N/A

Breaking Current kA 15.8 N/A 20 N/A 25 N/A

Max. Making Current (V~0) kAp 31.5 N/A 40 N/A 40 N/A

Rate of Rise of Recovery Voltage (RRRV) kV/μs 3.3 N/A 3.3 N/A 3.3 N/A

Peak Recovery Voltage kV 39 N/A 39 N/A 39 N/A

Mechanical life operations: Number 10000 10000 10000

Center distance between phase mm 275 275 275

* Is VCB with force cooling.

18
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

IEC/IEEE 62271-37-013 Combined


Standard

Up until the development of a common


IEC / IEEE standard for generator circuit
breakers there was no IEC standard to
cover the special needs of circuit breakers
Improvements to IEEE C37.013
being used in generator application.
The new IEC/IEEE dual standard has
Commonly users were referring to the IEEE
several improvements compared to the
standard for generator application.
previous IEEE standard.
●● It has included the definition of several
History
concepts in Clause 3.1, helping both
The IEC proposed to have a standard
IEEE and IEC users of this document to
covering the generator circuit breakers in
have same understanding of terms as
November 2008, and started activities to
they are used in this document readily
develop it after approval of the proposal in
available
April 2009.
●● Included explanations of why certain
Firstly the Standard was named IEC
requirements are needed in generator
62271-112, and later on moved to IEC
circuit-breaker applications that may
62271-37-013 and target of the project
not be needed for standard distribution
broaden to jointly revise IEEE Std C37.013
circuit-breakers page 13
with IEEE under the IEC/IEEE Dual Logo
●● The clauses covering generator-source
-Joint Development Agreement- Liaison
fault current requirements have been

Selection Guide
with IEEE Switchgear Committee.
greatly expanded in section 8.103.5.3
to explain how to treat the extremely
The document is pending to be officially
high degrees of asymmetry that may
released in the first months of 2015 with
occur under certain conditions
the official title: IEC/IEEE 62271-37-013
●● Expanded the application section,
Ed. 1.0 High-voltage switchgear and
clause 8, in order to make the selection
Controlgear - Part 37-013: Alternating
of a generator circuit-breaker easier for
current generator circuit-breakers
users, will enable the user to be sure
he has chosen the right circuit-breaker
to protect their particular generator
circuit

19
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

SubSea applications

SecoVac VB2 Plus 27kV has successfully ●● High Temperature test

passed strict tests for SubSea applications, IEC 62271-100 Clause 6.101.3, +70ºC
proving its robustness, and versatility for for 48 hrs.
operation under severe conditions. The high temperature test is to be
performed immediately after low
Extreme Temperature Testing temperature test.
●● Storage The breaker is held in the closed
ISO 13628-6: 2006, Clause 5.4.2.4. position at +70ºC for 24h. Then the
The breaker is held inside an breaker is operated with CLOSE /
environmental chamber in open OPEN operations carried out 5 times at
condition for 16 hours at -30ºC, +70ºC, at rated control supply voltage.
then the temperature is returned to
ambient temperature and the breaker
is operated with CLOSE / OPEN
Extreme vibration testing
operations carried out 5 times at
Vibration tests were conducted in 3 steps.
minimum control voltage, rated control
●● Class 2M1 IEC 60721-3-2 and IEC
voltage and maximum and control
60721-4-2 (ref Sheet2)
voltage
●● Real life conditions for a North Sea

Project
●● Real life conditions for a North Sea

Project with Safety factor 2x


Selection Guide

Below table represents the acceleration


factors.

Frequency Acceleration amplitude (g)


(Hz) IEC North Sea Conditions 2x North Sea
2 0.1 0.02 0.04
4 0.4 0.8 1.6
11 1.0 0.8 1.6
100 1.0 0.04 0.08
●● Low temperature test

IEC 62271-100 Clause 6.101.3 -18ºC for


48 hrs.
The breaker is held in the closed IEC

position at -18ºC for 24h. Then the


breaker is operated with CLOSE / OPEN
Acceleration (g)

2x North Sea conditions


operations carried out 5 times at -18ºC,
North Sea conditions
at rated control supply voltage.

Frequency (Hz)

20
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Fuse Contactor
Embedded Pole Design
SecoVAC fuse contactor applies the
embedded-pole design in the main
Fuse Selection
circuitry. The vacuum interrupter (VI) and
The fuse contactor unit uses fuse to make
the main conductor are fully casted by
and break the short circuit current and the
epoxy resin using APG process. So the
vacuum contactor to make and break the
surface of the VI is not affected by the
overcurrent or the normal load current.
environment condition, and the external
Therefore, it’s critical to choose a right
insulation is free from dust, humidity, due, voltage shall be equal or a little bigger
fuse to take over a reliable protection.
animal and filth. Therefore, the embedded than the rated system voltage
For the fuse selection, please refer to
pole of SecoVAC FC is free of maintenance ●● Fuse rated current: the continuous
IEC 60282-1 High-voltage fuses – Part 1:
in the whole life cycle operation. Likewise, carry current without exceeding the
Current-limiting fuses. The customer can
the fuse base uses the same APG process temperature rise
also refer to the following selection rules.
of epoxy resin casting, improving the ●● Fuse dimension: in line with the referred
Just in case, you’re welcomed to contact
insulation performance of the fuses and IEC/DIN standard and the following
us or the fuse manufacturer.
the holders. chart
The fuse manufacturer shall supply the
●● Time-current characteristic of the
sufficient fuse data for the fuse selection,
fuse: the curves shall show the relation
including but not limiting to,
Mechanical Life ●● Fuse classes: for the fuse contactor
between the virtual pre-arcing time
Different from the VCB, the vacuum and the prospective current; the time
application, the back-up current-
contactor uses electromagnetic range for back-up fuses from 0.01s to
limiting fuse is recommended.
mechanism and low chopping current ●● Applied fuse standard: IEC 60282-1 /
600s, a dotted line shall be plotted from
VI, so it has much longer mechanical life minimum breaking current to 600s if

Selection Guide
VDE 0670 Part 4 High-voltage fuses
which can reach one million operation the minimum breaking corresponds to
part 1: current limiting fuses and
cycles, capable of frequent switching on/ a time less than 600s.
DIN 43625 High-voltage fuses, rated
off. ●● Cut-off characteristic: the smaller of the
voltages 3.6 up to 36kV
●● Fuse rated voltage: the rated fuse
maximum cut-off current, the better of
the fuse

Technical data
Rated Voltage kV 7.2 12
Power frequency Hz 50/60 50/60
Power frequency withstand voltage (1 min) kV 20 28
Lightning impulse withstand voltage (peak) kV 60 75
Rated contactor current A 400 400
Max rated fuse current A 315 160
Breaking capacity by contactor A 3200 3200
Making capacity by contactor A 4000 4000
Power factor of circuit cos 0.35 0.35
Short time withstand current by main circuitry (1s) A 6000 6000
Peak withstand current kA 15.6 15.6
Take-over current A 3200 3200
Breaking capacity by fuse kA 50 50
Rated duties   Class 30 Class 30
Utilization category   AC-4 AC-4
Mechanical life cycle 300000 300000
Electrical life (AC3) cycle 250000 250000
Open distance between VI contacts mm 6.5±0.5 6.5±0.5
Over travel by VI contacts mm 2.5±0.5 2.5±0.5
Allowable wearing thickness of VI contacts mm 3 3
Main circuitry resistance without fuses ohm <150 <150
Rated supply voltage of operating devices, and of auxiliary circuits VDC VAC 110~130 220~250 110~130 220~250
Dimension (H*W*D) with undercarriage mm 637*531*631 637*531*631
Estimated Weight including fuses kg 100 100

21
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Fuse Contactor
Overall Dimension

488
A 201.5
ጀᅪǖᇑࡋ༹ದࢇ้ᆌԍኤ‫ةৢۯ‬
GDZ-58
ཀྵౚࢇ؅٫ྺ15ċ25mm
ْܾ֭ཀྵ Caution: Please ensure 15ċ25mm engagement
Ui 250V Ith2 10A of moving and fixed contact.
ॿ໋෧ᇸ‫ۉ‬ഘࠣ‫ݻ‬ᆶ၌ࠅິ
Tel:0512-57750777

ৢ‫ة‬ཀྵ ‫ةۯ‬ཀྵ
Fixed contact Moving contact

15ċ25mm

205±1
637

ླ၃:
൩ჹ߭ፏ๰๑ᆩࡀ‫ײ‬ ऺຕഗ
ࢅኟඓ‫֡ڦ‬ፕࡀ‫ݔ‬ƽ Counter
DANGER:
Follow all approved safety 300000
procedures and operation guideƽ

260±1
I/O ࢇ‫ݴ‬ኸ๖ ఀಈ
৆थ‫ݴ‬ቄ indicator
Emergency trip

78
ELECTRICAL HAZARD

76
A 436±1 32
502
531 599±1

A-A
150±1 150±1
Selection Guide

Note:
1.Use screw locking lacquer to coat only the first four threads in the place of thread joint,tighten bolts.
2.All rotating surface, sliding surface should be coated lithium base grease.

22
275±1
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

e GE Consumer & Industrial Systems


户内高压真空断路器
Vacuum circuit breaker
产 品 型 号
Type designation

Overall Dimension
出 厂 编 号
Serial number
额 定 电 压

280±1
kV
Rated voltage(Ur)
额 定 电 流
A
Rated normal current(Ir)
额 定 频 率 Hz
Rated frequency
额 定 雷 电 冲 击 耐 压 (峰值) kV
Rated lightning impulse withstand voltage(Up)
额 定 短 路 开 断 电 流 kA
Rated short-circuit breaking current(Isc)
额 定 短 时 耐 受 电 流 kA
Rated short time withstand current (4s)
额 定 电 缆 充 电 开 断 电 流 A
Rated cable-charging breaking current
电 机 电 压
V
motor voltage
分 闸 合 闸 装 置 电 压
Rated supply voltage of closing and opening devices
V 注意!
执 行 标 准
Relevant standarder
高压危险!请严格遵守操作规程。
额 定 操 作 顺 序 O-0.3s-CO-180s-CO
Warning!
Rated operating sequence
重 量 kg High voltage dangerous! Always observe
Weight
the instruction manual and follow the rules.
出 厂 日 期
Manufacture date

上 海 通 用 电 气 开 关 有 限 公 司
Shanghai GE Breakers Co.,Ltd.

SecoVac VB2+ 3.3kV-17.5kV/630~1250A up to 31.5kA (Pole distance: 150mm)

Withdrawable type 502


516
488 531
488
201.5
201.5 492±1
456
150±1 150±1

ØD

ØD
275±1

275±1

637

637
e
GE Consumer & Industrial Systems
户内高压真空断路器
Vacuum circuit breaker
产 品 型 号
Type designation
出 厂 编 号
Serial number
额 定 电 压
280±1

kV
Rated voltage(Ur)
额 定 电 流
A
Rated normal current(Ir)
额 定 频 率 Hz
Rated frequency
额 定 雷 电 冲 击 耐 压 (峰值) kV
Rated lightning impulse withstand voltage(Up)
额 定 短 路 开 断 电 流 kA
Rated short-circuit breaking current(Isc)
额 定 短 时 耐 受 电 流 kA
Rated short time withstand current (4s)
额 定 电 缆 充 电 开 断 电 流 A
Rated cable-charging breaking current
电 机 电 压
V

78
motor voltage
分 闸 合 闸 装 置 电 压
Rated supply voltage of closing and opening devices
V 注意!
执 行 标 准
Relevant standarder
高压危险!请严格遵守操作规程。
额 定 操 作 顺 序 O-0.3s-CO-180s-CO
Warning!
Rated operating sequence
High voltage dangerous! Always observe
e
重 量
Weight 户内高压真空断路器 kg
the instruction manual and follow the rules.
出 厂 Vacuum 日 期 circuit breaker
GE Consumer & Industrial Systems
Manufacture date

95.5
产 品 型 号
Type designation 上 海 通 用 电 气 开 关 有 限 公 司
出 厂 编 号 Shanghai GE Breakers Co.,Ltd.
Serial number
额 定 电 压
280±1

kV
Rated voltage(Ur)
额 定 电 流
A
Rated normal current(Ir)
额 定 频 率 Hz
Rated frequency
76

额 定 雷 电 冲 击 耐 压 (峰值) kV
Rated lightning impulse withstand voltage(Up)
额 定 短 路 开 断 电 流 kA
Rated short-circuit breaking current(Isc)
额 定 短 时 耐 受 电 流 kA
Rated short time withstand current (4s)
额 定 电 缆 充 电 开 断 电 流 A
Rated cable-charging breaking current
电 机 电 压
V

78
motor voltage
分 闸 合 闸 装 置 电 压
Rated supply voltage of closing and opening devices
V 注意!
执 行 标 准
Relevant standarder
高压危险!请严格遵守操作规程。
额 定 操 作 顺 序 O-0.3s-CO-180s-CO
Warning!
Rated operating sequence

436±1
重 量 kg High voltage dangerous! Always observe

32
Weight
the instruction manual and follow the rules.
出 厂 日 期
Manufacture date

95.5
上 海 通 用 电 气 开 关 有 限 公 司
Shanghai GE Breakers Co.,Ltd.

599±1
502
76

516
531
436±1 Lifting
32 point
492±1
456 599±1
150±1502 150±1
516
531

492±1
456
150±1 150±1

Fixed type
∅62
Terminal section
150 150

M16 Depth 22mm

Selection Guide
275

451.5

e GE Engery
Industrial Solutions
户内高压真空断路器
Vacuum circuit breaker
产 品 型 号
Type designation
出 厂 编 号
Serial number
额 定 电 压 kV
Rated voltage(Ur)

4-M12
额 定 电 流
237

A
Rated normal current(Ir)
额 定 频 率 Hz
Rated frequency
额 定 雷 电 冲 击 耐 压 (峰值) kV
Rated lightning impulse withstand voltage(Up)
额 定 短 路 开 断 电 流 kA

Engagement for threads L is 15~18 mm


Rated short-circuit breaking current(Isc)
额 定 短 时 耐 受 电 流 kA
Rated short time withstand current (3s)
额 定 电 缆 充 电 开 断 电 流 A
Rated cable-charging breaking current
电 机 电 压
V
motor voltage
分 闸 合 闸 装 置 电 压
V
Rated supply voltage of closing and opening devices
执 行 标 准 注意!
Relevant standarder
高压危险!请严格遵守操作规程。

Nominal length for bolt is based on total thickness


额 定 操 作 顺 序 2V&2V&2
Rated operating sequence 2V&2V&2 Warning!
重 量 kg
Weight High voltage dangerous! Always observe
出 厂 日 期
the instruction manual and follow the rules.
Manufacture date

上 海 通 用 电 气 开 关 有 限 公 司
Shanghai GE Breakers Co.,Ltd.

for busbar and washer plus L

370

450 45 275 118

443 Lifting point

23
638
276.5

SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Overall Dimension

310±1
SecoVac 3.3kV-17.5kV/T1250A/2000A-40kA, 50kA (Phase to phase distance: 210mm)

Withdrawable type

295±1
638 638
276.5 276.5
652
664
681

210±1 210±1

310±1
310±1

698
698
295±1
295±1

86
86

95.5
95.5
76
76

361±1 361±1 39 39
652 652 586±1 586±1
664 664
681 681

210±1 210±1 210±1 210±1 Lifting point

Fixed type

210 210 110


2XM10-Depth 15mm
100
45°
70
78

M18 Depth 25mm


Selection Guide

310

451.5
252

Engagement for threads L is 15~18 mm


Nominal length for bolt is based on total thickness
for busbar and washer plus L
520 33.5
588 275 118

Lifting point

24
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

e GE Consumer & Industrial Systems


户内高压真空断路器
Vacuum circuit breaker
产品型号
Type designation
出厂编号
Serial number
额定电压 kV
Rated voltage(Ur)
额定电流
A
Rated normal current(Ir)
额定频率 Hz
Rated frequency
额 定 雷 电 冲 击 耐 压 (峰值) kV
Rated lightning impulse withstand voltage(Up)
额定短路开断电流 kA
Rated short-circuit breaking current(Isc)
额定短时耐受电流 kA
Rated short time withstand current (4s)
额定电缆充电开断电流 A
Rated cable-charging breaking current
电机电压
V
motor voltage
分闸合闸装置电压
Rated supply voltage of closing and opening devices
V 注意!
执行标准 高压危险!请严格遵守操作规程。

SecoVac 3.3kV-17.5kV/T2500~4000A-40kA, 50kA (Phase to phase distance: 275mm)


Relevant standarder
额定操作顺序 O-0.3s-CO-180s-CO
Warning!
Rated operating sequence
重量 kg High voltage dangerous! Always observe
Weight
the instruction manual and follow the rules.
出厂日期
Manufacture date

上海通用电气开关有限公司
Shanghai GE Breakers Co.,Ltd.

Withdrawable type 852


864
881
838
838
376.5
376.5 836±1
(794)
275±1 275±1

Ø109

Ø109
310 ±1

310 ±1

735

735
e GE Consumer & Industrial Systems
户内高压真空断路器
Vacuum circuit breaker

e 户内高压真空断路器

295 ±1
产品型号
Vacuum circuit breaker Type designation
GE Consumer & Industrial Systems
295 ±1

产品型号 出厂编号
Type designation Serial number
出厂编号 额定电压 kV
Rated voltage(Ur)
Serial number 额定电流
额定电压 A
kV Rated normal current(Ir)
Rated voltage(Ur) 额定频率
额定电流 Hz
A Rated frequency
Rated normal current(Ir) 额 定 雷 电 冲 击 耐 压 (峰值) kV
额定频率 Hz Rated lightning impulse withstand voltage(Up)
Rated frequency 额定短路开断电流 kA
额 定 雷 电 冲 击 耐 压 (峰值) kV Rated short-circuit breaking current(Isc)
Rated lightning impulse withstand voltage(Up) 额定短时耐受电流 kA
额定短路开断电流 kA Rated short time withstand current (4s)
Rated short-circuit breaking current(Isc) 额定电缆充电开断电流 A
额定短时耐受电流 kA Rated cable-charging breaking current
Rated short time withstand current (4s) 电机电压

86
V
额定电缆充电开断电流 motor voltage
Rated cable-charging breaking current
电机电压
A 分闸合闸装置电压
Rated supply voltage of closing and opening devices
V 注意!

86
V
motor voltage 执行标准 高压危险!请严格遵守操作规程。
注意!
分闸合闸装置电压 Relevant standarder
Rated supply voltage of closing and opening devices
V 额定操作顺序 O-0.3s-CO-180s-CO
Warning!
Rated operating sequence
执行标准
Relevant standarder
高压危险!请严格遵守操作规程。重量 kg High voltage dangerous! Always observe
Weight
额定操作顺序 O-0.3s-CO-180s-CO
Warning! 出厂日期
the instruction manual and follow the rules.
Rated operating sequence Manufacture date
重量 kg High voltage dangerous! Always observe
Weight
出厂日期
the instruction manual and follow the rules. 上海通用电气开关有限公司
Shanghai GE Breakers Co.,Ltd.
Manufacture date

上海通用电气开关有限公司
Shanghai GE Breakers Co.,Ltd.

76
76

95.5
95.5 361±1 39
852 361±1586±1 39
852 864 586±1
864 881
881

836±1 Lifting point


836±1 (794)
(794) 275±1 275±1
275±1 275±1

Fixed type
30

110 27
275 275 Terminal section
100

∅80
4-M10
(20mm in depth)
310

Selection Guide
451.5

e GE Engery
Industrial Solutions
户内高压真空断路器
Vacuum circuit breaker
产 品 型 号
Type designation
出 厂 编 号
Serial number
额 定 电 压 kV
Rated voltage(Ur)
额 定 电 流
A
Rated normal current(Ir)

4-M12
额 定 频 率 Hz

Engagement for threads L is 15~18 mm


Rated frequency
额 定 雷 电 冲 击 耐 压 (峰值) kV
252

Rated lightning impulse withstand voltage(Up)


额 定 短 路 开 断 电 流 kA
Rated short-circuit breaking current(Isc)
额 定 短 时 耐 受 电 流 kA
Rated short time withstand current (3s)
额 定 电 缆 充 电 开 断 电 流 A
Rated cable-charging breaking current
电 机 电 压
V
motor voltage
分 闸 合 闸 装 置 电 压

Nominal length for bolt is based on total thickness


V
Rated supply voltage of closing and opening devices
执 行 标 准
Relevant standarder
2V&2V&2
注意!
额 定 操 作 顺 序
Rated operating sequence 2V&2V&2 高压危险!请严格遵守操作规程。
重 量
Weight
kg Warning!
出 厂 日 期
High voltage dangerous! Always observe
Manufacture date
the instruction manual and follow the rules.
上 海 通 用 电 气 开 关 有 限 公 司
Shanghai GE Breakers Co.,Ltd.

for busbar and washer plus L


720
34.5 275 118
788

Lifting point

25
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Overall Dimension SecoVac VB2+G Generator Circuit Breaker


SecoVac VB2+G 15kV/2500~4000A- 31.5kA 40kA and 50kA (Pole distance: 275mm)

Withdrawable type

838
376.5

Ø109

310±1

735
e GE Consumer & Industrial Systems 户内高压真空断路器
Vacuum circuit breaker
产品型号
Type designation

295±1
出厂编号
Serial number
额定电压 kV
Rated voltage(Ur)
额定电流 A
Rated normal current(Ir)
额定频率 Hz
Rated frequency
额 定 雷 电 冲 击 耐 压 (峰值) kV
Rated lightning impulse withstand voltage(Up)
额定短路开断电流 kA
Rated short-circuit breaking current(Isc)
额定短时耐受电流 kA
Rated short time withstand current (4s)
额定电缆充电开断电流 A
Rated cable-charging breaking current
电机电压 V
motor voltage
分闸合闸装置电压
Rated supply voltage of closing and opening devices
V
注意!

86
执行标准
Relevant standarder 高压危险!请严格遵守操作规程。
额定操作顺序
Rated operating sequence O-0.3s-CO-180s-CO Warning!
重量 kg High voltage dangerous! Always observe
Weight
the instruction manual and follow the rules.
出厂日期
Manufacture date

上海通用电气开关有限公司
Shanghai GE Breakers Co.,Ltd.

76
852 95.5
864 361±1 39
881 586±1
Lifting point

836±1
(794)
275±1 275±1
Selection Guide

Fixed type
Terminal section
30
Engagement for threads L is 15~18 mm 110
Nominal length for bolt is based on total 27
275 275
thickness for busbar and washer plus L 100

L
∅80
4-M10
(20mm in depth)
310

451.5

e GE Engery
Industrial Solutions
户内高压真空断路器
Vacuum circuit breaker
产 品 型 号
Type designation
出 厂 编 号
Serial number
额 定 电 压 kV
Rated voltage(Ur)
额 定 电 流
252

4-M12
Rated normal current(Ir)
额 定 频 率 Hz
Rated frequency
额 定 雷 电 冲 击 耐 压 (峰值) kV
Rated lightning impulse withstand voltage(Up)
额 定 短 路 开 断 电 流 kA
Rated short-circuit breaking current(Isc)
额 定 短 时 耐 受 电 流 kA
Rated short time withstand current (3s)
额 定 电 缆 充 电 开 断 电 流 A
Rated cable-charging breaking current
电 机 电 压
V
motor voltage
分 闸 合 闸 装 置 电 压
V
Rated supply voltage of closing and opening devices
执 行 标 准
Relevant standarder
2V&2V&2
注意!
额 定 操 作 顺 序
Rated operating sequence 2V&2V&2 高压危险!请严格遵守操作规程。
重 量
Weight
kg Warning!
出 厂 日 期
High voltage dangerous! Always observe
Manufacture date
the instruction manual and follow the rules.
上 海 通 用 电 气 开 关 有 限 公 司
Shanghai GE Breakers Co.,Ltd.

720
34.5 275 118
788

Lifting point Lifting point

26
310
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

345

112.5
SecoVac 24kV-27kV/T630~1250A-31.5kA (Phase to phase distance: 210mm)
652

Withdrawable type 680


638
638

10
10
642
210 210

310
310

762
762
345
345

112.5
112.5

652
652 320
320
680 651
680 651

Lifting point
642
642
210 210
210 210
Fixed type

210 210

Terminal section 45,0°

M18
depth 25mm 70
310

Selection Guide
665

302

Engagement for threads L is 15~18 mm


Nominal length for bolt is based on total thickness
for busbar and washer plus L
52,0
520 4-M12 275 118

588

Lifting point

27
ø109
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

310±1
Overall Dimension SecoVac VB2 Circuit Breaker

345±1
e

SecoVac 24kV-27kV/1250~2500A-31.5kA (Phase to phase distance: 275mm)

Withdrawable type 852


881

838
838

ø109
ø109
275±1,5 275±1,5

310±1
310±1

762
762
345±1

e
345±1

64 112,5
112,5

64

74
74
320
852 651±1320
852 651±1
881
881

Lifting point

Fixed type
275±1,5 275±1,5
275±1,5 275±1,5
30
Terminal section
27

275 275 ø82 4-M10


145
100 depth 20mm

15

30
45
Selection Guide

310

5
730
452

Engagement for threads L is 15~18 mm


305

Nominal length for bolt is based on total thickness


4-M12
for busbar and washer plus L

720
25 275 118

788

Lifting point

28
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

SecoVac VB2 Plus L-frame


SecoVac 3.3kV-17.5kV

A
B
690

ØE
A View M
R-∅
7

270
J

G
C±1

L
260

D±1
∅1

453
2

110
255

255
380

16-∅9

H
65

F
50 200 200 216 F+9

I A View
1250A 25X84 1250A spout
59 3150A 42X126

M8 20mm depth
M10 23mm depth

31.5
P±1

3150A Spout
P±1

∅60
M10 25mm depth

Selection Guide
59

M12 35mm depth

725

A B C D E F G H I J L M N R P
650mm 630~1250A
914 794 275 453 49 632 1031 310 934 78 556 75 150 2 150
up to 31.5kA
800mm 1250~2000A 124/1250A
915 781 310 468 90 782 1039 460 977 NA NA NA NA 210
up to 40kA 114/2000A
1000mm 2500~4000A
915 779 310 468 49/90 982 1039 660 969 101 584 0 137.5 5 275
up to 40kA*

* Valid for SecoVac VB2+G Generator Breaker applications

29
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

SecoVac VB2 Plus L-frame


SecoVac 24kV-27kV

C±1

G
12

D±1
K
L

245.5
M

J E E 120 197.5 197.5


H
F

I
25
896

73
m
0m
0X3
M1 2500A Spout
60
P± 1

91
P± 1

mm
45
6X
M1
Selection Guide

A B C D E F G H I J K L M N P
800mm 1250A 1142 896 310 617.5 157.5 792 1121.5 460 1142 26 185 145 40 170 210
1000mm 2500A 1142 896 310 617.5 150 992 1121.5 660 1264 41 150 150 69.5 223 275

30
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Measurement, Protection and

Measurement, Protection and Control


Control
Multilin 650 Family . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Multilin 3 Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

31
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Measurement, Protection and Control


For more information visit our website: http://www.gedigitalenergy.com/multilin/catalog/F650.htm

Multilin 650 Family


Advanced protection,
control and monitoring system

Key benefits
●● Unique built-in control features - Comprehensive protection ●● Cost Effective Access information - Via multiple protocols,

plus programmable logic through standard RS232 & RS485 Ethernet Ports
●● Flexible and cost effective control for complex systems - ●● Optimal integration flexibility via open standard protocols -

Use IEC compatible programmable logic to customize the Modbus RTU, DNP 3.0 Level 2, IEC 60870-5-104, IEC 61850, IEC
Measurement, Protection and Control

functionality of your protection & control system to address 870-5-103


unique, site specific applications ●● Minimize communication down time - Reliable redundant

●● Human machine interface (HMI) - Standard backlit LCD display Ethernet Communication ports with 10/100BaseTX, 100BaseFX
with 4 x 20, optional 16 x 40 (240 x 128 pixels) graphical LCD, with ST connectors and optional double 100BaseFX, with ST
programmable buttons and directional keys for selecting connectors
setting menus and submenus ●● Complete asset monitoring - Full metering including demand

●● Minimize replacement time - Modular with card draw-out & energy


construction ●● Follow technology evolution - Flash memory for product field

●● Reduce troubleshooting time and maintenance costs - IRIG-B upgrade


time synchronization, event reports, waveform capture, data
logger

Applications
●● F650: Management and primary protection of distribution ●● G650: Distributed generation management device

feeders and bus couplers ●● G650: Reliable Distributed Generation interconnection

●● F650: Backup protection of busses, transformers and power protection system


lines ●● W650: Wind turbine protection, control and monitoring

●● G650: Packaged generator mains failure detection ●● W650: Distributed generation grid interconnection device

32
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Features
Protection and control User interface
●● Up to 32 Programmable digital inputs ●● Large graphic (16 x 40) or regular (4 x 20) character display

●● Up to 16 digital outputs ●● Easy-to-use control via Shuttle key

●● Trip Circuit Supervision ●● Front USB port or standard RS232

●● Redundant power supply option ●● Rear wire 10/100BaseTX Ethernet for LAN connection

●● Configurable PLC logic according to IEC 61131-3 ●● Rear wire CAN bus port (OPEN CAN protocol - W650)

●● Fully configurable graphic display HMI interface ●● Optional fibre optic 100BaseFX Ethernet, single or redundant

●● Alarms panel ●● Optional rear RS485 port

●● 1 ready LED and 15 programmable LED indicators


Monitoring and metering ●● EnerVistaTM Integrator providing easy integration of data in the
●● Energy metering ●● Data logger
650 relay into new or existing monitoring and control systems
●● Demand metering ●● Sequence of event

●● Trip circuit monitoring ●● Self diagnostic

●● Oscillography

Overview Metering
The Multilin 650 family has been designed screens. The Multilin 650 provides the following
as a comprehensive protection, control, The metering capability allows 0.5% metering values.
metering and monitoring package. The accuracy for current and 1% from 10V to ●● Current: Ia, Ib, Ic, In, Ig, Isg

microprocessor based architecture 208V for voltage in metering range. ●● Phase-to-phase and phase-to-ground

is a complete solution for different Monitoring functions include a 479 voltage values for bus and line: Van,
applications that complies with the most event recorder, and a programmable Vbn, Vcn, Vab, Vbc, Vca, Vx
relevant international standards. oscillography recorder. ●● Active power (per phase and total) : Wa,

All the elements required for each The Multilin 650’s communications Wb, Wc, W

Measurement, Protection and Control


application have been integrated into a capability and option make the product ●● Reactive power (per phase and total) :

single package for a cost-effective, reliable very unique. These units include VARa, VARb, VARc, VAR
and simple utilization. The low number of a maximum of three independent ●● Power factor (per phase and total)

components, thanks to the use of state- communication ports: COM1, COM2 ●● Frequency

of-the-art but mature technology, deliver and COM3, with many physical choices ●● These signals are available for local

a very high reliability. through the use of two removable plug- display and accessible remotely using
Hardware inputs and outputs have been and-play boards. communications
designed in a modular way that allow The brain of the Multilin 650 units includes
easy migration from simple to more a powerful built-in virtual PLC. This PLC Recording functions
complex applications. can be programmed according to the IEC The recording functions within the Multilin
The control functions include a full- 61131-3 language by functional block 650 include:
scheme virtual PLC with an optional diagrams. ●● Event recorder capable of storing 479

graphical display. The combination of 650 units come with 8 to 32 digital inputs time-tagged events (1 true millisecond
both elements provide total control for and with 8 to 16 outputs depending on accurate tagging)
a bay. This means real-time monitoring options. All digital inputs may be filtered ●● Up to 20 separate oscillography records

of breakers and selector switches, open with a separate debounce time to tailor can be stored in memory. The capacity
and close commands supervised by the customer requirements. of each record will depend on the type of
programmable interlockings and metering oscillo selected (1 Mbyte/Max. No. Osc)

33
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

These records are stored in non volatile Communications


memory. Therefore, there is no need Multilin 650 units incorporate up to TCP/IP and IEC 60870-5-104.
for internal battery monitoring or three ports that operate independently.
maintenance. Redundant ports are available for high
reliability applications:
Trip circuit monitoring Available protocols for rear port 1 and 2
Multilin 650 units offer as an option two are ModBus RTU, IEC 103 and serial DNP
complete supervision circuits for breaker 3.0.
trip and closing coils and circuits. These The third port is located in a removable
supervision inputs monitor both the communications card. This plug-and-
battery voltage level and the continuity of play card can be easily changed in the
the trip and/or closing circuits, applying future as new standards arrive to the
current through those circuits and market, thus providing a migration path
checking that it flows properly. In order to the customer.
to apply this feature it is necessary to The protocol available for the third port
choose I/O board 1 option 2. is DNP 3.0 over TCP/IP, UDP/IP, ModBus

User Interface

●● Graphic 16 x 40 or text 4 x 20 LCD display

●● Fluorescent backlight to improve visibility

●● Multicolor programmable LEDs with label panel

●● Local/Remote/Off pushbutton with LEDs


Measurement, Protection and Control

●● Key control for easy navigation

●● Ergonomic programmable keys

●● Electrically isolated front USB communication port


ANSI Device Numbers & Functions
Device
Number Function
25 Synchrocheck
27/27X Bus/Line Undervoltage

Functional Block Diagram 32


32FP
Sensitive Directional Power
Forward Power
32N Wattmetric zero-sequence directional
46 Negative Sequence Time Overcurrent
47 Negative Sequence Voltage
48 Blocked Rotor
49 Thermal Image - overload protection
1
52 50 BF Breaker Failure
50PH/PL Phase Instantaneous Overcurrent (High/Low)
50N Neutral Instantaneous Overcurrent
79
1 CLOSE TRIP 27X 50G Ground Instantaneous Overcurrent
3
Monitoring 50SG Sensitive Ground Instantaneous Overcurrent
3 59X 50IG Isolated Ground Instantaneous Overcurrent
BROKEN 3
50BF 49 50PH 50PL 46 48 32FP 32 32N CONDUCTOR 51PH/V 51PL/V 67P
R R 50N 51N 67N 51N Neutral Time Overcurrent
1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
25 51G Ground Time Overcurrent
1
51SG Sensitive Ground Time Overcurrent
1 2 2 51PH/V Voltage Restraint Phase Time Overcurrent
50G 51G 67G 51PL/V
3 3 3
1 59/59X Bus/Line Overvoltage
50SG 51SG 50IG 67SG METERING 59NH/NL Neutral Overvoltage - High/Low
3 3 3 3
3V_0 67P Phase Directional Overcurrent
3 67N Neutral Directional Overcurrent
67G Ground Directional Overcurrent
67SG Sensitive Ground Directional Overcurrent
47 27 59 VTFF 81U 81O 81R 79 Autorecloser
3 3 3 1 3 3 3
59NH 81 U/O Under/Over Frequency Broken Conductor
3
Detection
59NL N/A Load Encroachment
F650 Digital Bay Controller 3
81R Frequency Rate of Change
EN F650 BLOCK F.CDR
VTFF VT Fuse Failure Detection

34
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Measurement, Protection and Control


For more information visit our website: http://www.gedigitalenergy.com/multilin/catalog/3Series.htm

Multilin 3 Series
Intuitive industrial and utility
protective relay systems
for feeders, motors and
transformers

Key benefits
●● Easy-to-use and cost effective protection and control for ●● Application flexibility with the use of programmable logic

feeders, motors and transformers elements


●● Effortless draw-out construction eliminates requirements for ●● Large backlit display with 40 characters for easy viewing of

test switches and reduces downtime relay information and settings

Measurement, Protection and Control


●● Environmental monitoring system to alarm on destructive ●● Flexible communications with multiple ports & protocols to

operating conditions to enable preventative maintenance allow seamless integration into new and existing infrastructure
●● Easy-to-use interface and set up in one simple step ●● Easy access to information via multiple communication

●● Accelerated Life Cycle Tested to ensure reliability of relay network options including USB, Serial, Fiber & Copper Ethernet
operation under abnormal conditions ●● Reduced wiring with support for remote I/O

●● Advanced power system diagnostics to increase reliability ●● Reduce setup and configuration time with the Simplified Motor

through fault and disturbance recording capabilities Setup screen


●● Arc Flash mitigation via zone inter-tripping, flex curves and ●● Powerful Security Audit Trail tool to increase security and

multiple setting groups minimize system risks by tracking setting changes

Applications
●● Advanced protection, monitoring & control relays for feeders ●● Distribution utility down stream breaker protection

(Multilin 350), motors (Multilin 339) and transformers (Multilin ●● Medium voltage utility feeders with advanced control features

345) including, cold load pickup, auto reclose and multiple setting
●● Industrial feeders with enhanced breaker monitoring and groups
diagnostics

35
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Features Easy-to-use
Protection & control Drawout construction
(for Multilin 350 Feeder Protection System) The Multilin 3 Series offers a complete
●● Phase, neutral and ground TOC and IOC drawout feature eliminating the need for
●● Undervoltage, overvoltage, frequency rewiring after testing has been concluded.
●● Neutral/ground directional The withdrawable feature also eradicates
●● Negative sequence overcurrent the need to disconnect communication
●● ANSI, IAC, IEC, flex curves cables, e.g. fiber, copper, RJ45, etc and
Overview
●● Cable Thermal Model protection helps retain communication status even
●● Breaker failure The Multilin 3 Series of protection relays after a relay has been withdrawn from its
●● Cold load pick-up are highly functional, economical case.
●● Four-shot auto reclose protection relays for feeders, motors and

●● 8 digital inputs, 7 contact outputs transformers. By providing an economical

●● Two setting groups system for protection, control, monitoring


and metering, and both local and
Metering & monitoring remote user interfaces in one assembly,
●● Event Recorder: 256 events with 1ms
the Multilin 3 Series relays effectively
time stamping eliminate the need for expensive discrete
●● Oscillography with 32 samples per
components.
cycle and digital states The Multilin 3 Series provides detailed
●● IRIG-B clock synchronization
diagnostic information allowing users to
●● Relay & Asset Health Diagnostics
troubleshoot and minimize downtime.
●● Security audit trail
Detailed diagnostics is provided via the
Advanced communications
256 1ms time stamped event recorder
User interface and programming
and the 192 cycle Oscillography report Easy integration into new or existing
●● 4x20 character LCD display
sampled at 32 samples per cycle. infrastructure
Measurement, Protection and Control

●● Control panel with 12 LED indicators


The robust Multilin 3 Series streamlines With several Ethernet and serial port
●● Front USB and rear serial, Ethernet and
user work flow processes and simplifies options, and a variety of communication
Fiber ports
engineering tasks such as configuration, protocols, the Multilin 3 Series provides
●● Multiple protocols - IEC 61850 & 61850
wiring, testing, commissioning, and advanced and flexible communication
GOOSE, ModBus™ RTU, ModBus™
maintenance. This cost-effective relay selections enabling seamless integration
TCP/IP, DNP 3.0, IEC 60870-5-104, IEC
also offers enhanced features such as into new or existing applications.
60870-5-103
diagnostics, preventative maintenance, The Multilin 3 Series supports various

EnerVista™ software device health reports and advance industry standard protocols such as, IEC

●● An industry-leading suite of software security features. 61850 & IEC 61850 GOOSE, Modbus RTU,

tools that simplifies every aspect of Modbus TCP/IP, DNP3.0, IEC 60870-5-104

working with Multilin devices and IEC 60870-5-103.

●● Document and software archiving

toolset to ensure reference material


and device utilities are up-to-date

36
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Enhanced diagnostics EnerVistaTM Launchpad Security


Preventative maintenance EnerVista™ Launchpad is a complete set of Security audit trail
The Multilin 3 Series allows users to track powerful device setup and configuration tools The Multilin 3 Series monitors security
relay exposure to extreme environmental that is included at no extra charge with the SR and reliability of asset protection. The
conditions by monitoring and alarming Relays. Multilin 3 Series protection devices
at high temperatures. This data allows ●● Set up the Multilin 3 Series Relays - and any offer complete traceability of any
user to proactively schedule regular other Multilin device - in minutes. Retrieve relay setting and command changes,
maintenance work and upgrade activities. and view oscillography and event data at allowing the user to quickly identify
All relays utilize EnerVista setup TM
the click of a button changes made to the relay.
software for communication, monitoring ●● Build an instant archive on any of the

and metering. Actual values, setpoints, latest Multilin manuals, service advisories,
status, trending, and waveform capture application notes, specifications or
information may all be viewed via firmware for your SR Relay
the software, and can be used for ●● Automatic document and software version

troubleshooting. updates via the internet and detailed e-mail


notification of new releases

User Interface
●● SETPOINT GROUP 1, 2:
These indicators are continuously on if corresponding group provides settings for protection elements.
TRIP:
Indicator turns on when relay detects a trip condition.
Operates the trip relay to open the breaker.
ALARM:
While relay detects an alarm condition, indicator flashes.
PICKUP:
Indicator lights steady when any protection feature pickup threshold exceeded.

●● DISPLAY:
4 line text for easy viewing of key data.

Measurement, Protection and Control


●● LEDs:
10 LED indicators for quick diagnostics.

●● KEYPAD:
Ten button keypad for access to device interrogation and change of settings.

●● FRONT PORT:
Electrically isolated front USB communication port.

Protection Features ANSI Device Numbers & Functions


Device
BUS Number Function
27P Phase Undervoltage
27X Auxiliary Undervoltage
BUS VT
49 Thermal Model
52 50P Phase Instantaneous Overcurrent
50N Neutral Instantaneous Overcurrent
50G Ground/Sensitive Ground
79 27P 59P 27X 59X 59_2 59N 81U 81O Instantaneous Overcurrent
TRIP CLOSE 1 1 1 1 1 1 1 2 2 50BF Breaker Failure
MONITORING 50_2 Negative Sequence Overcurrent
3 51P Phase Timed Overcurrent
51G Ground Timed Overcurrent
50P 50N 51P 51N 50_2 49 METERING
51N Neutral Timed Overcurrent
2 2 1 1 1 1 59P Phase Overvoltage
59X Auxiliary Overvoltage
CLP 50BF 79 59N Neutral Overvoltage
59_2 Negative Sequence Overvoltage
1 67G Ground Directional Overcurrent
50G 50G/
51G 67N Neutral Directional Overcurrent
51G TRANSIENT RECORDER
EVENT RECORDER 79 Autoreclose
2 1 81U Underfrequency
81O Overfrequency
350 RELAY CLP Cold Load Pickup

Latched Lockout available as a standard feature


LOAD

37
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
Operation

Operation
Internal Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Working Principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Vacuum interrupter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Working principle of operating mechanism . . . . . . . . . . . . . . . 40
Motor spring charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Closing operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Anti-Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Tripping operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Reclosing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Interlocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Preparation Work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

38
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Internal Wiring Diagram


Withdrawable Type

Spring Charge Motor Closing Circuit Breaker Interlock Circuit Opening Circuit Truck Interlock Circuit

26 24 25 10 52 30 6 3 5 7 9 23 27 28 29 8 1

V2 V4 V3

CC
V1 K0
TC V5 A~
(13) C+ B-
(14) S2 Y4 1
D~
ZC
M S4
BC
2

(51) (53) (73) (11) 91 31 41 71 61 63 23 33 83 93


(52) S5
(54) S5
S5 (12) S5 92 32 42 72 62 64 24 34 84 94 S5
(74)
(5) (2)
K0
(3)

43 43
44 S8 44 S9
(21) (13) (21)

(22) S3 (14) S3 (22) S1

36 34 35 20 53 54 31 32 16 13 15 17 19 33 37 38 39 18 40

11 2 4 47 57 55

13 33 23 53

14 S9 S9 S9 54 S9
34 24

13 33 23 53
14 34 24 54
S8 S8 S8 S8

Operation
21 43 13 81
22 S5 44 S5 14 S5 S5
82

21 22 51 50 12 14 48 49 58 56

S9: Limit switch (service position) CC: Closing coil KO: Anti-pumping relay (optional)
S8: Limit switch (test position) TC: Trip coil BC: Electromagnet for locking (optional)
S4: Electromagnet for locking's auxiliary switch M: Spring Charge Motor ZC: Electromagnet for locking truck (optional)
S5: Auxiliary switch V1~V4: Rectifier
S1~S3: Energy storing limit switch

Note:
1. This wiring diagram describes that a breaker is open, racked to test position with spring in discharge state.
2. The polarity in dashed frame should be connected to common DC voltage terminal.

39
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Internal Wiring Diagram


Withdrawable Type (with UVR)

Spring Charge Motor Closing Circuit Breaker Interlock Circuit Opening Circuit Truck Interlock Circuit

24 25 10 52 30 6 3 5 7 9 23 27 28 29 8 1
26

V2 V4 V3

CC
V1 K0
TC V5 A~
(13) C+ B-
(14) S2 Y4 1
D~
ZC
M S4
BC
2

(51) (53) (73) (11) 91 31 41 71 61 63 23 33 83 93


(52) S5
(54) S5
S5 (12) S5 92 32 42 72 62 64 24 34 84 94 S5
(74)
(5) (2)
K0
(3)

43 43
44 S8 44 S9
(21) (13) (21)

(22) S3 (14) S3 (22) S1

36 34 35 20 53 54 31 32 16 13 15 17 19 33 37 38 39 18 40

UVR circuit

43 11 2 4 47 57 55

13 33 23 53

14 S9 S9 S9 54 S9
34 24

MM UM

13 33 23 53
14 34 24 54
S8 S8 S8 S8
Operation

21 43 13 81
22 S5 44 S5 14 S5 S5
82

44 21 22 51 50 12 14 48 49 58 56

S9: Limit switch(service position) CC: Closing coil UM: UVR


S8: Limit switch(test position) TC: Opening coil V1~V5: Rectifier
S4: Electromagnet for locking's A.S. M: Motor K0: Anti-pumping relay(optional)
S1~S3: Energy storing travel switch MM: UVR PCB(optional) ZC: Electromagnet for locking truck(optional)
S5: Auxiliary switch BC: Electromagnet for locking(optional)

Note:
1.This wiring diagram describes that a breaker is open, racked to test position with spring in discharge state
2.The polarity in dashed frame should be connected to common DC voltage terminal

40
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Fixed Type

Spring Charge Motor Closing Circuit Breaker Interlock Circuit Opening Circuit
24 25 10 52 30 6 3 5 7 9 23 27 28 29 8
26

V2 V4 V3

CC
V1 K0
TC
(13)
(14) S2

BC
M S4

(51) (53) (73) (11) 91 31 41 71 61 63 23 33 83 93


(52) S5
(54) S5
S5 (12) S5 92 32 42 72 62 64 24 34 84 94 S5
(74)
(5) (2)
K0
(3)

(21) (13) (21)

(22) S3 (14) S3 (22) S1

36 34 35 20 50 51 31 32 16 13 15 17 19 33 37 38 39 18

11 2 4

Operation
21 43 13 81
22 S5 44 S5 14 S5 S5
82

21 22 12 14

S4: Electromagnet for locking's auxiliary switch CC: Closing coil KO: Anti-pumping relay (optional)
S5: Auxiliary switch TC: Trip coil BC: Over current release coil (optional)
S1~S3: Energy storing travel switch M: Energy storing motor ZC: Electromagnet for locking (optional)
V1~V4: Rectifier C: Control

Note:
1. This wiring diagram describes that a breaker is uncharged and is in an open state.
2. The polarity in dashed frame should be consistent when the operation voltage is DC.

41
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Working Principle
Vacuum interrupter

The vacuum gas pressure inside vacuum interrupter is less than


1.33×10-3Pa. Under normal circuit conditions the interrupter is
closed. Arcing is established within the interrupter by withdrawing
the moving contact from stationary contact. This arc burns in
the metal vapor evaporated from local hot spots on the contact
surfaces. The metal vapor continually leaves the inter-contact
region and recondenses on the contact surfaces and surrounding
metal vapor condensation shield. The latter is usually isolated
from both contacts and serves to protect the glass or ceramic
envelope from vapor deposition. At current zero, vapor production
ceases and the original vacuum condition is rapidly approached.
The dielectric strength of the interrupter also increases, and the
circuit is interrupted. Within the contacts in the open position, the
circuit voltage is withstood internally by the inter-contact gap
and externally by the insulating envelope.

Working Principle of Operating


Operation

Mechanism
Motor spring charging

1
The energy that is necessary for closing the circuit breaker is
provided by the closing spring. The energy storage can be done
by the motor or by the manual charging handle.

Motor spring charging


The energy charging mechanism consists of energy storing
motor, gear wheel, cam, holder and closing spring. When the 6

energy-storing motor (11) is charged, the pinion of output shaft 2


5
(12) that is connected to motor will rotateand drive the gear
wheel. The holder fixed on the gear wheel will make the cam fixed
4
on the shaft move, which then drive the shaft to rotate, so that
draws out the closing spring (17) for storing energy. When the 3

block on the gear wheel is pushed away, the clutch is separated Figure 3.
and the holder (4) will hold the roller on the cam (5) to keep the 1 Embedded pole 4 Holder
mechanism in charged position, thus completing the charging 2 Insulating rod 5 Cam
3 Opening spring 6 Position switch
operation succeeds.

42
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

When energy is charged manually, the operator charges


the spring by operating the energy-charging handle on the
mechanism up and down repeatedly.
When the charging operation is completed, you can hear a 'click',
and the energy charging indicator (13) is switched over, as well as
the status of position switch (6), cutting the secondary charging
circuit supply to motor. The operating mechanism now is ready
for the next operation. (Figure 3)

Closing operation Anti-Pump

When the closing circuit is powered, the closing coil is energized Anti-pumping function is fitted with SecoVac to prevent repeated
and the holder (4) will rotate counter clockwise to break away sequences of opening and closing operations. Once the circuit
from the roller on the cam (5). The cam, under the action of the breaker is in closed position, the closing operation will be
force from closing spring (17), will rotate clockwise, prohibited.
to push the roller on the main shaft, which will move the main
shaft (10) in counter clockwise rotation. The main shaft moves the
Reclosing
connecting rod down through arm, so that the insulating rod (2)
moves upright, pushing the movable contact to the fixed contact
When the circuit breaker is closed, the mechanism can be
at the required speed, and compressing the contact spring and
charged for close, so that the circuit breaker can reclose
making it a necessary contact travel (overtravel) to ensure the
immediately after tripping.
pressure is generated between movable and fixed contacts.
After the closed operation is finished, the closed/opening indicator

Operation
(9) will indicate 'closed'. The power to the closing circuit will be cut
off. If the external power supply is energized, the charging circuit 7
motor will operate and the charging operation will be finished
automatically.
Note: Once the circuit breaker is in closed position, the closing operation
will be prohibited.
17 8
Tripping operation 16 9
10
When the breaker receives an opening command (the opening
15

push button is pressed or the tripping coil (16) is energized), the 11


14
tripping shaft will rotate clockwise. Under the action of opening
spring (3) and contact-compressing spring, main shaft will move 13
clockwise, and the insulating rod (2) will make the movable
12
contact to separate from the fixed contact at a suitable speed.
The buffer will absorb the residual energy and tripping operation Figure 4.
is completed. 7 Closing coil 13 Charging indicator
8 Holder 14 Interlock coil
9 Open/close indicator 15 Over-current release
After the tripping operation is finished, the closing/opening
10 Main shaft 16 Tripping coil
indicator (9) will indicate 'open'. Meanwhile, the counter will record 11 Motor 17 Closing spring
the operation. 12 Output shaft

43
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Interlocks Installation
The follow interlocking facilities are Correct installation is of primary
incorporated to ensure the safe operation importance, the manufacturer’s
of the breaker. when the breaker is closed, instructions must be carefully studied
the withdrawable circuit breaker cannot and followed. It is good practice to use
be racked between the service position gloves for handling the breaker during the
and test position. installation.
●● When the earthing switch is in the

closed position, the withdrawable Please carry out installation and wiring Installation for fixed circuit
circuit breaker cannot be racked into of breaker according to manual. Do not breakers
the service position place any foreign objects in the breaker or
●● When the withdrawable circuit breaker ●● The careful and professional
modify it in anyway.
is in service position, the earthing installation is a fundamental condition

switch cannot be closed for the failure free operation of the


circuit breaker
Check before installation
●● The circuit breaker should be

After the breaker is unpacked, check installed so that there are no external
the poles for any signs of mechanical forces applied to it from busbars or
damage. The product nameplate and mechanical supports
quality certificate shall conform to the ●● The busbar connection should not

order. Check goods according with the cause any deformation to the breaker
packing list. terminals
●● Take note of supplied drawings for bolt
Operation

Clean the insulating parts with a clean sizing and lengths


dry cloth. Make sure the upper and lower ●● Use the standard bolts with strength

contact arms are clean and free of any of class 8.8 and the disc springs to
deformation caused by mishandling tighten the bus bar (Table 1)
during transport or storage.
Check the vacuum pressure in the vacuum
interrupter through power frequency
withstand voltage test. If it fails, please
contact or your local GE office.

Table 1 Tightening torque of bolt


Basic dimensions Tightening torque Tightening torgue
of bolts (mm) without lubricant applied (N•m) with lubricant applied (N•m)
M8 25 10
M10 45 25
M12 85 45
M16 170 80

44
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Commissioning Preparation Work


All commissioning and operation work ●● Check the circuit breaker for any

shall be carried out by persons who have damage or any other dangerous
received professional training and are environmental influence
familiar with operation of the breaker. ●● Wipe down the breaker, especially dirt

Necessary protective and preventive that may have accumulated on the


measures shall be taken during work. surface of the insulator. Especially the
●● Use the product under normal working dirt on the surface of insulation
conditions and within the range ●● The lifting hook of the circuit breaker

of technical data according to the must be removed prior to operation


specifications of IEC 62271-1:2007 ●● Check the primary and secondary

circuits as well as the earthing


●● Implement energy charged, opening

and closing operations. Manually

Considerations ensure the breaker is operating


correctly
Operation for withdrawable circuit breaker
●● Put the circuit breaker into test position

●● Connect the secondary wiring plug and

open and close the breaker several


times to ensure correct operation by
local and remote control

Operation
●● Insert the handle and rotate the racking

handle clockwise about 20 revolutions.


Upon the 'click', the withdrawable
circuit breaker will be in the service
position (Don't apply excessive force, to
avoid any damage)

45
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Spare parts
For ordering, please contact GE.

S/N Name Reference Cat. No.

1 Moving contact 1250A/31.5kA A-00211

2 Moving contact 1250A/40kA A-00211

3 Moving contact 2000A/40kA A-00225

4 Moving contact 3150A/40kA A-00230

5 Moving contact 4000A*/40kA A-00230

6 Close Coil AC/DC110V P-C1X

7 Close Coil AC/DC220V P-C2X

8 Close Coil DC24V P-C3X

9 Close Coil DC30V P-C4X

10 Close Coil DC36V P-C5X

11 Close Coil DC48V P-C6X

12 Close Coil DC60V P-C7X

13 Close Coil AC/DC125V P-C8X

14 Close Coil AC/DC230-240V P-C9X

15 Open Coil AC/DC110V P-C1X

16 Open Coil AC/DC220V P-C2X

17 Open Coil DC24V P-C3X


Operation

18 Open Coil DC30V P-C4X

19 Open Coil DC36V P-C5X

20 Open Coil DC48V P-C6X

21 Open Coil DC60V P-C7X

22 Open Coil AC/DC125V P-C8X

23 Open Coil AC/DC230-240V P-C9X

24 Charge Motor AC/DC110V P-MOTOR1

25 Charge Motor AC/DC220V P-MOTOR2

26 Charge Motor DC24V P-MOTOR3

27 Charge Motor DC30V P-MOTOR4

28 Charge Motor DC36V P-MOTOR5

29 Charge Motor DC48V P-MOTOR6

30 Charge Motor DC60V P-MOTOR7

31 Charge Motor AC/DC125V P-MOTOR8

32 Charge Motor AC/DC230-240V P-MOTOR9

33 Rack in/out handle Y-002

34 Secondary Sockets Assembly A-00700

35 Opening/closing module for VCB type SecoVac 17,5 kV P-M1

36 Closing Circuit Blocking Magnet AC/DC110V P-L1

*4000A is VCB with force cooling


46
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

S/N Name Reference Cat. No.

37 Closing Circuit Blocking Magnet AC/DC220V P-L2

38 Closing Circuit Blocking Magnet DC24V P-L3

39 Closing Circuit Blocking Magnet DC30V P-L4

40 Closing Circuit Blocking Magnet DC36V P-L5

41 Closing Circuit Blocking Magnet DC48V P-L6

42 Closing Circuit Blocking Magnet DC60V P-L7

43 Closing Circuit Blocking Magnet AC/DC125V P-L8

44 Closing Circuit Blocking Magnet AC/DC230-240V P-L9

45 Truck Blocking Magnet AC/DC110V C-90020

46 Truck Blocking Magnet AC/DC220V C-90016

47 Truck Blocking Magnet DC24V P-W3

48 Truck Blocking Magnet DC30V P-W4

49 Truck Blocking Magnet DC36V P-W5

50 Truck Blocking Magnet DC48V P-W6

51 Truck Blocking Magnet DC60V P-W7

52 Truck Blocking Magnet AC/DC125V P-W8

53 Truck Blocking Magnet AC/DC230-240V P-W9

Operation
54 Racking Motor AC/DC220V P-MOTORD1

55 UVR AC/DC110V P-UVCOIL1

56 UVR AC/DC220V P-UVCOIL2

57 UVR DC24V P-UVCOIL3

58 UVR DC30V P-UVCOIL4

59 UVR DC48V P-UVCOIL5

60 UVR DC60V P-UVCOIL6

61 UVR AC/DC125V P-UVCOIL1

62 UVR AC/DC230-240V P-UVCOIL2

63 Auxiliary Switch F10-18 (9NO/9NC) Breaker open/close GDF5AA00

64 Auxiliary Switch GDF-5 - 5NO/5NC Breaker service/test position GDFSAC00

65 Micro position switch LXW1811821

66 Control wiring board P-AP910X

67 Cluster 1250-50KA A-00220

68 Cluster 3150-50KA A-00230

47
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker
Check List

Ordering Check List


. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

48
SecoVac 3.3kV-27kV Embedded Pole Vacuum Circuit Breaker

Ordering Check List


1&2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Phase Distance & Voltage

Door Interlock & Padlock


SecoVac VB2+ Breaker

Motorized Rack In/out


Breaking Current (kA)

Secondary Wiring
Second Open Coil
Charging Motor

Truck Interlock
Close Interlock

Under Voltage
Rated Current
Device Type

Anti Pump
Close Coil
Open Coil
Structure

Description
SV SecoVac VB2+ Breaker
I IEC SecoVac VB2+
G IEC/IEEE SecoVac VB2+G
W Withdrawable
F Fixed
0 17.5kV, Pole Distance 150mm
1 17.5kV, Pole Distance 210mm
2 17.5kV, Pole Distance 275mm
5 27kV, Pole Distance 210mm
6 27kV, Pole Distance 275mm
8 40.5kV, Pole Distance 275mm
D 15kV Type G IEC/IEEE Pole Distance 210mm
E 15kV Type G IEC/IEEE Pole Distance 275mm
0 630A
1 1250A
2 1600A
3 2000A
4 2500A
5 3150A
6 4000A
0 25kA
1 31.5kA
2 40kA
3 50kA
X 0 0 0 0 0 0 None
1 1 1 1 1 1 1 AC/DC110V
2 2 2 2 2 2 2 2 AC/DC220V
3 3 3 3 3 3 3 DC24V
4 4 4 4 4 4 4 DC30V
5 5 5 5 5 5 DC36V
6 6 6 6 6 6 6 DC48V
7 7 7 7 7 7 7 DC60V
8 8 8 8 8 8 8 AC/DC125V
9 9 9 9 9 9 9 AC/DC230-240V
Z Provided
1 Door Interlock
2 Padlock
3 Door Interlock + Padlock
1 Through terminal block above SecoVac frame
Check List

2 Through secondary plug with socket


3 Through secondary socket above SecoVac frame with plug

49
Greater China
Shanghai Taiwan
4F, Building 2, CTP, No.1 Hua Tuo Rd. Zhang Jiang Hi-Tech 6F, No. 8, Min Sheng E. Rd., Sec. 3, Taipei 10480
Park, Shanghai, China 201203 T : +886 2 2183 7000
T : +86 21 3877 7888 F : +886 2 2516 6829
F : +86 21 3877 7600

South East Asia


Malaysia Philippines & Guam Indonesia
Level 6, 1 Sentral, Jalan Rakyat, 8F Net Cube Building, 30th Street, Corner 3rd Avenue, BRI II Tower, 27th floor, Jl. Jend. Sudirman No. 44-46
Kuala Lumpur 50470 Crescent West Park, Global City Taguig 1634 Jakarta 10210
T : +603 2273 9788 T : +63 2 877 7000 T: +62 21 573 0430
F : +603 2273 3481 F : +63 2 846 0629 F: +62 21 574 7089

Thailand & Myanmar Vietnam, Cambodia & Laos Singapore


7th floor, Capital Tower, All Seasons Place, 87/1 Wireless Floors 6 & 7 - The Crescent CR3, 111 Ton Dat Tien Street, Level 9, The Metropolis Tower 2
Road, Lumpini, Pathumwan, Bangkok 10330 Tan Phu Ward, District 7, Ho Chi Minh City 710000 11 North Buona Vista Drive, Singapore 138589
T : +66 2 648 0199 T : + 84 8 54137000 T : +65 6220 7022
F : +66 2 648 0100 F : + 84 8 54137040

India
India
Plot No. 42/1 & 45/14, Electronic City-Phase II
Bangalore-560100
T: (080) 41434000
F: (080) 41434199

Australia & New Zealand


572 Swan Street, Building 2, Richmond, VIC 3121
T: 1800 733 632

North Asia
Japan Korea
11F, Akasaka Park Bldg.,5-2-20, Akasaka, Minato-ku 22, Daewangpangyo-ro 712 beon-gil, Bundang-gu,
Tokyo 107-6111 Seongnam-si, Gyeonggi-do, 463-400, Korea
T : +81 3 3588 5288 T: +82-31-620-6000
F : +81 3 3585 3010 F: +82-31-620-7070

Europe & Middle East


Spain & Portugal Italy Russia
Miño 122, naves E - F Centro Direzionale Colleoni 27/8, Electrozavodskaya street, Moscow, 107023
08223 - Terrassa - Barcelona Via Paracelso 16, Palazzo Andromeda B1 T: +7 495 937 11 11
T: +34 93 736 57 00 I-20864 Agrate Brianza (MB)
T: +39 039 637 3701 South Africa
Belgium Unit 4, 130 Gazelle Avenue, Corporate Park Midrand 1685
Nieuwevaart 51, B-9000 Gent Netherlands P.O. Box 76672 Wendywood 2144
T: +32 (0)9 265 21 11 Parallelweg 10, Nl-7482 CA Haaksbergen T: +27 11 238 3000
T: +31 (0)53 573 03 03
Finland
United Kingdom
Kuortaneenkatu 2, FI-00510 Helsinki
Germany 2 The Arena, Downshire Way
T: +358 (0)10 394 3760
Robert-Bosch Str. 2a, 50354 Hürth-Efferen Bracknell, Berkshire RG12 1PU
France T: +49 (0) 2233/ 9719-0 T: +44 (0) 800 587 1239
Paris Nord 2, 13, rue de la Perdrix
F-95958 Roissy CDG Cédex United Arab Emirates Turkey
T: +33 (0)800 912 816 Injaz Building, 3rd Floor Windowist Tower Eski Büyükdere Cad. No: 26 Kat: 5
Dubai Internet City, PO Box 11549, Dubai Maslak 34467, Sarıyer, İstanbul
Poland T: +971 4 4546912 T: +90 212 214 76 91
Ul. Odrowaza 15, 03-310 Warszawa F: +90 212 214 77 30
T: +48 22 519 76 00 Hungary
and Vaci ut 81-83. H-1139 Budapest
Ul. Leszczyńska 6, Bielsko-Biała 43-300 T: +36 1 447 6050
T: +48 33 828 62 33

Latin America
Latin America Headquarters Brazil
790 N.W. 107th Avenue, Suite 200, Miami, Fl 33172 USA Av. María Coelho Aguiar, 215, Bloco C - 6.Andar
T: +1 305 551 5155 Jd.São Luiz, 05804-900, São Paulo
T: +55 11 36141900
Chile
Vespucio Norte, Avenida Presidente Eduardo Frei Mexico
Montalva 6001, Edificio N° 66 Av. Churubusco 3900 Nte, Col. Industrial Benito Juárez
Comuna: Conchalí, Sector el Cortijo, Santiago Monterrey, N.L. 64517
T: (56 2) 928-4700 T: (01-800) 800-1968

North America
USA Canada
41 Woodford Avenue, Plainville CT, USA 06062 2300 Meadowvale Blvd. Mississauga, ON L5N 5P9
and 12305 Kurland Drive, Houston, TX USA 77034 T: 1-800-GE1-STOP
T: +1 800-431-7867

2000 Centre Green Way Suite 200 Cary, NC 27513


T: +1 919-238-6620
GE
Industrial Solutions

You may be interested in other MV Seco-family products


For more information, please visit www.geindustrial.com

For more information, please visit


www.geindustrial.com
Approval number: GE/VB2/CA/2017/01
Printing Code: IN201701B07EN
© Copyright GE Industrial Solutions 2017

You might also like