Professional Documents
Culture Documents
JULY 2016
Specifications, Applications,
Service Instructions & Parts
MOTORIZED CONTROL
VALVE
&
CONTROLLERS
3/4”- 2”
20mm thru 50mm
Motor Operated Valve
Model MCV
INTRODUCTION KEY FEATURES
The Hansen Motorized Control Valve is a truly unique
motor operated valve which eliminates the most common
concern of other motor operated valves—valve stem
seal leakage. The Motorized Control Valve has no valve
stem seal because the non-electric rotor is enclosed in a WATER-TIGHT
stainless steel cartridge which contains the fluid pressure. NEMA 6 (IP 67)
The electric stator is outside the stainless steel can, and HOUSING ELECTRONICS PROVIDE
is isolated from the fluid in the valve. STRONG, SLOW OPERATION
WITH MINIMAL POWER
CONSUMPTION
APPLICATIONS
Liquid Make-up to Accumulator
Liquid Injection to Compressors
DX Evaporators
Temperature or Pressure Control DIRECT ACTUATION
Low or High Side Level Control OF V-PORT
Slow Opening and Closing: Suction Stop Valve
No Pressure Drop: Gravity Drain
4-20 mA or Floating Point Control
PRECISE LINEAR
FLOW REGULATION
ADDITIONAL FEATURES
• Relay, current, or voltage input for direct
connection to plant PLC or computer.
• All moving parts are sealed so that
frost will not affect operation.
• Tight closing Teflon seat.
• Canned rotor eliminates valve stem seal leakage.
• Controlled opening and closing minimizes TABLE OF CONTENTS
liquid velocity shock, “water hammer.” Introduction/Specifications .......................................................................... 1-2
• Valve is more compact and light weight Applications . ................................................................................................... 3-5
than other motor operated valves. Capacity Tables .... ......................................................................................... 6-14
Operation & Electrical ...................................................................................... 15
• Same flanges and spacing as Hansen HA4A / Wiring Diagrams ......................................................................................... 16-20
HS4A pressure regulators and solenoid valves. Installation Dimensions ... ......................................................................... 21-24
• Suitable for use with ammonia, R22, R134a, Service & Maintenance ............................................................................... 25
CO2 (up to 800 psi welded) glycol, water, Parts .................................... ................................................................................ 26
brines, and other approved refrigerants. Piping Recommendations ................................................................... 27-28
Valve Controllers ................... ................................................................... 29-36
• Available with optional Power-Backup feature. Troubleshooting ....... .............................................................................................. 37
• Valve position indicator display included. Order Information ....................................................................................................... 38
• Available with weld-in connections.
MATERIAL SPECIFICATIONS The Motorized Control Valve does not require stem shaft
Mechanical: heaters like other open motorized valves.
Maximum Safe Working Pressure: The Motorized Control Valve is slow opening and closing
400 psig (28 bar) flanged, 800 psig (55 bar) welded (about 15 to 27) seconds depending on valve size and speed
Maximum Opening Pressure Differential: settings which minimizes the potential for liquid velocity
400 psig (28 bar) flanged, 800 psi (55bar) all sizes shock or “water hammer” often experienced with quick
Ambient Operating Temperature: opening and closing solenoid valves.
-40˚F to 122˚F (-40˚C to 50˚C)
Refrigerant Operating Temperature: POWER BACKUP FEATURE
-75˚F to 240˚F (-60˚C to 115˚C) The Motorized Control Valve is available with an optional
IP67 Rating (NEMA 6) power backup system that will control the valve to a user
Electrical: defined location upon a loss of the incoming voltage. This
Supply Voltage: 24VAC or 24VDC
system can be used in place of an upstream solenoid to
Input Control Signal Types: 4-20mA, 0-20mA, 0-5VDC,
the valve.
0-10VDC, 1-6VDC, relay closed contact
Output Feedback Signal Types: 0-20mA, 4-20mA
Material Specifications VALVE SIZING
Body: Ductile iron, ASTM V536 Proper valve sizing is impor tant for smooth operation and
Bonnet Plate: Steel, zinc plated with yellow chromate long, trouble-free life of the valve. Therefore, capacity
V-port Seal: Teflon at both the maximum and minimum flow and Pressure
Cartridge Assembly: Stainless Steel Drop should be analyzed. Pressure drop across the valve
Cartridge O-ring: Neoprene dramatically increases the capacity of the valve. A valve with
Powerhead Housing: Aluminum 8 psi pressure drop has twice the capacity of a valve with a
Corrosion Protection: Zinc plating is standard on 2 psi pressure drop. Ideally, valves should operate between
bodies up to 1-1/4” 15% and 85% open for optimum trouble-free control. Refer
to the capacity tables on pages 6–14 or the Hansen sizing
APPLICATIONS program found at www.hantech.com.
The Hansen Motorized Control Valve is ideal for applications
where external leakage is intolerable. The valve is suitable LIQUID MAKE-UP APPLICATIONS
for use with a variety of fluids, including those that are For applications with a large pressure drop across
incompatible with copper, such as ammonia, because the Motorized Control Valve , attention must be paid to
the copper windings of the motor stator are isolated proper outlet line sizing to accommodate flash gas. It is
from the fluid in the valve. Typical uses include slow recommended that dual Motorized Control Valve s in parallel
opening solenoid valve, temperature controlled evaporator be used when the low load (weekend load) is less than 15%
regulator, liquid injection to screw compressors, pressure of the full load capacity properly sized for the application.
control, liquid level control of pump accumulators, high Also, for applications requiring a valve size over 2˝ port size,
side receivers or low side flooded chillers, or as a gravity it is strongly recommended that two liquid make-up valves
drain valve. in parallel be used. This valve arrangement could be two
Motorized Control Valve s or one solenoid valve with hand
The full ported MCV valve series is best suited for computer expansion valve and one Motorized Control Valve to be used
controlled operations using 4-20 mA signals. The MCV as a “tri m” valve under low load conditions.
is ideal for precise temperature and pressure control,
hot gas defrost, and other applications where accurate LIQUID LINE SIZING
process control is required.
Liquid lines should be adequately sized for the capacity of
The MCR valve with expansion plug is for high pressure the valve. Listed below are the recommended capacities for
drop applications such as liquid makeup and liquid liquid lin e s . R 2 2 c a p a c i t i e s b a s e d o n 3 f t / s l i q u i d v e l o c i t y .
injection. The MCR valve series is also suitable for suction For R134a, use 94% of R22 capacity; R404 80%; R507 60%.
line, liquid line and hot gas line where reduced capacities
more closely match the expected operating conditions. TABLE 1
The full ported MCV valve series is best suited for LINE MA XIMUM CAPACITY MA XIMUM CAPACITY
applications requiring open/close operation only. (Floating SIZE AMMONIA R22
Point Control) 1/2˝ 32 Tons 112 kW 8 Tons 27 kW
Refer to pages 3-5 for typical applications. 3/4˝ 58 Tons 208 kW 14 Tons 49 kW
1˝ 97 Tons 340 kW 24 Tons 82 kW
ADVANTAGES 1-1/4˝ 179 Tons 625 kW 42 Tons 147 kW
No pressure drop is required to operate, unlike most 1-1/2˝ 254 Tons 890 kW 58 Tons 202 kW
pressure regulators and solenoid valves which require a 2˝ 496 Tons 1740 kW 110 Tons 384 kW
m i n i m u m 2 p s i p r e s s u r e d r o p to k e e p th e v a l v e f u ll y o p e n . 2-1/2˝ 729 Tons 2550 kW 155 Tons 543 kW
The Motorized Control Valve can be used for applications 3˝ 1160 Tons 4060 kW 241 Tons 845 kW
which require a very low pressure drop (e.g. suction lines), 4˝ 2040 Tons 7140 kW 416 Tons 1457 kW
or no pressure drop (e.g. equalizing or drain lines). 5˝ 3300 Tons 11606 kW 654 Tons 2289 kW
Valves are drop-in replacement for Hansen and other 6˝ 4890 Tons 17198 kW 946 Tons 3309 kW
select solenoid and pressure regulating valves. NH3 capacities are based on IIAR Refrigeration Piping
Handbook tables.
R549a
JULY 2016 2
LIQUID MAKE-UP TO ACCUMULATOR HANSEN
PXVC
LEVEL
CONTROLLER
CUSTOMER-SUPPLIED HANSEN
VARI-LEVEL (WITH MOD420)
OR TECHNI-LEVEL VLT
MCR
MOTORIZED CONTROL VALVE
(INSTEAD OF HAND LOW
EXPANSION VALVE) TEMPERATURE
VESSEL
HIGH-PRESSURE
LIQUID
HANSEN PXVC
PRESSURE CONTROLLER
OR COMPUTER/PLC
1/4" NPT
HANSEN SUPPLIED
PRESSURE TRANSDUCER
HANSEN SUPPLIED
PRESSURE TRANSDUCER
EVAPORATOR
MCV
MOTORIZED CONTROL VALVE
R549a
3 JULY 2016
MCR AND MCV HIGH PRESSURE LIQUID LINE CAPACITIES
HANSEN PXVC
LEVEL CONTROLLER
MCV
MOTORIZED
CONTROL
VALVE
CUSTOMER SUPPLIED HANSEN HANSEN
VARI-LEVEL (WITH MOD420) PXVC
OR TECHNI-LEVEL VLT TEMPERATURE
SHUTDOWN SOLENOID CONTROLLER
INLIEU OF INTEGRAL
POWER-CLOSE MCV
SURGE VESSEL
MCR
MOTORIZED CONTROL VALVE
IN PLACE OF HAND
EXPANSION VALVE
R549a
JULY 2016 4
TYPICAL APPLICATIONS - MCV MOTORIZED CONTROL VALVE-SLOW OPENING AND CLOSING
CONTROLLING
CONTACT, E.G.
FROSTMASTER
EVAPORATOR
MCV
MOTORIZED
CONTROL VALVE
CONTROLLING
CONTACT
MCV
MOTORIZED CONTROL VALVE
Applications shown use Hansen supplied controllers, however, the Hansen MCV valve series can be integrated into
most customer control systems.
R549a
5 JULY 2016
MCR AND MCV SUCTION VAPOR CAPACITIES
1.0 38 116 70 212 100 297 213 638 290 873 646 – – 885 – –
1.4 45 137 83 251 118 351 252 755 343 1,033 764 – – 1,047 – –
.02 3.1 9.5 5.8 18 8.2 24 18 53 23 70 53 105 156 72 158 249
.04 4.4 13 8.2 25 12 35 25 74 33 99 75 149 221 102 223 352
.08 6.2 19 12 35 16 49 35 105 47 140 105 211 313 144 316 498
-20
.15 8.5 26 16 48 22 67 48 144 64 192 144 289 428 197 432 682
.4 13.9 42 26 78 37 109 78 235 104 314 236 471 699 322 706 1,114
.6 17.0 52 32 96 45 134 96 288 128 384 289 577 856 394 865 1,364
.02 2.2 7 3.9 12 5.5 16 11 34 16 47 35 71 105 48 106 168
.04 3.0 9 5.5 17 8 23 16 49 22 67 50 100 149 69 151 238
-40
.08 4.3 13 8 23 11 33 23 69 32 95 71 142 210 97 213 336
.15 5.9 18 11 32 15 45 31 94 43 130 97 194 288 133 292 460
Kv 1.8 5.5 3.3 10 4.7 14 10 30 13.3 40 30 60 89 40 90 142
R549a
JULY 2016 6
MCR AND MCV SUCTION VAPOR CAPACITIES
.25 0.5 1.6 1.0 2.9 1.4 4.2 3.0 8.8 4.0 12 8.7 16 26 12 27 41
.50 0.8 2.3 1.4 4.1 2.0 6.0 4.3 13 5.6 17 12 23 37 17 39 59
1.0 1.1 3.2 1.9 5.8 2.8 8.5 6.1 18 7.9 23 17 33 52 23 55 83
2.0 1.5 4.5 2.7 8.2 4.0 12 8.6 25 11 33 25 46 73 33 78 117
40
5 2.4 7.1 4.3 13 6.4 19 14 40 18 52 39 73 115 52 123 185
10 3.5 10 6.1 18 9.0 27 19 56 25 74 55 104 163 74 173 262
US
15 4.2 12 7.5 22 11 33 23 68 31 90 67 – – 91 – –
20 4.9 14 8.6 26 13 38 27 79 36 104 78 – – 105 – –
.25 0.3 1.0 0.6 1.8 0.9 2.6 1.8 5.3 2.5 7.4 5.5 10 16 7.3 17 26
.50 0.5 1.4 0.9 2.6 1.2 3.7 2.6 7.5 3.6 11 7.7 15 23 10 24 37
1.0 0.7 2.0 1.2 3.7 1.7 5.2 3.6 11 5.1 15 11 21 33 15 34 52
0
2.0 1.0 2.8 1.7 5.2 2.4 7.3 5.1 15 7.1 21 15 29 46 21 48 73
5 1.5 4.4 2.7 8.2 3.9 12 8.1 24 11 33 24 46 73 33 76 115
10 2.2 6.3 3.9 12 5.5 16 11 34 16 47 35 65 103 46 108 163
.25 0.3 0.8 0.5 1.4 0.7 2.0 1.5 4.2 1.9 5.7 4 8 12 6 13 20
.50 0.4 1.1 0.7 2.0 0.9 2.8 2.1 6.0 2.7 8.0 6 11 18 8 19 29
-40
1.0 0.5 1.6 0.9 2.8 1.3 4.0 2.9 8.5 3.9 11 8 16 25 11 27 40
2.0 0.8 2.2 1.3 4.0 1.9 5.6 4.1 12 5.4 16 12 22 35 16 38 57
Cv 2.2 6.4 3.9 11.7 5.5 16.4 12 35 16 47 35 66 104 47 110 166
METRIC
1.0 15 46 28 85 40 119 79 238 115 346 255 – – 350 – –
1.4 18 55 33 101 47 141 94 281 136 409 302 – – 414 – –
.02 1.3 4.0 2.3 7 3.3 10 7 21 10 29 22 43 64 30 65 102
.04 1.9 6 3.2 10 5 14 10 30 14 41 30 61 90 42 92 145
.08 2.6 8 5 14 7 20 14 42 19 58 43 86 128 59 130 204
-20
.15 3.6 11 6 19 9 27 19 58 27 80 59 118 175 81 177 280
.4 5.9 18 10 31 15 44 32 95 43 131 96 193 286 132 290 457
.6 7.2 22 13 38 18 54 39 116 53 160 118 236 350 162 355 560
.02 1.0 3 1.8 5 2.6 8 5 16 7.0 22 16 33 49 22 49 78
.04 1.4 4 2.6 8 4 11 8 23 10 32 23 46 69 32 70 110
-40
.08 1.9 6 4 11 5 15 11 32 15 45 33 65 97 45 99 156
.15 2.6 8 5 15 7 21 15 44 20 61 45 90 133 62 135 213
Kv 1.8 5.5 3.3 10 4.7 14 10 30 13.3 40 30 60 89 40 90 142
R549a
7 JULY 2016
MCR AND MCV SUCTION VAPOR CAPACITIES
.25 0.4 1.3 0.8 2.3 1.1 3.2 2.3 6.7 3.1 9.2 6.9 13 21 9 22 33
.50 0.6 1.8 1.1 3.3 1.5 4.6 3.3 10 4.4 13 10 18 29 13 30 46
1.0 0.9 2.5 1.5 4.6 2.2 6.4 4.6 13 6.3 18 14 26 41 18 43 65
2.0 1.2 3.6 2.2 6.5 3.1 9.1 6.5 19 8.9 26 20 37 58 26 61 92
40
5 2.0 5.7 3.4 10 4.8 14 10 30 14 41 31 58 92 41 96 145
10 2.8 8.0 4.8 15 6.8 20 15 42 20 58 44 82 130 58 136 206
15 3.4 10 5.9 18 8.4 25 18 52 24 71 53 – – 71 – –
US
20 3.9 11 6.9 21 10 29 21 60 28 82 62 – – 82 – –
.25 0.3 0.7 0.4 1.3 0.6 1.9 1.3 3.9 1.8 5.3 4.0 7.6 12 5.4 13 19
.50 0.4 1.1 0.6 1.9 0.9 2.7 1.9 5.5 2.6 7.5 5.7 11 17 7.6 18 27
1.0 0.5 1.5 0.9 2.7 1.3 3.7 2.7 7.8 3.6 11 8.1 15 24 11 25 38
0
2.0 0.7 2.1 1.3 3.8 1.8 5.3 3.8 11 5.1 15 11 22 34 15 36 54
5 1.1 3.3 2.0 6.0 2.8 8.4 6.0 17 8.1 24 18 34 54 24 57 85
10 1.6 4.7 2.8 8.5 4.0 12 8.4 25 11 34 26 48 76 34 80 121
.25 0.1 0.4 0.2 0.7 0.3 0.9 0.7 2.0 0.9 2.7 2.0 3.8 6.0 2.7 6.3 10
.50 0.2 0.5 0.3 1.0 0.4 1.3 1.0 2.9 1.3 3.8 2.9 5.4 8.5 3.8 8.9 14
-40
1.0 0.2 0.7 0.4 1.3 0.6 1.8 1.4 4.0 1.8 5.4 4.0 7.6 12 5.4 13 19
2.0 0.3 1.0 0.6 1.9 0.9 2.6 2.0 5.7 2.6 7.6 5.7 11 17 7.6 18 27
Cv 2.2 6.4 3.9 11.7 5.5 16.4 12 35 16 47 35 66 104 47 110 166
R549a
JULY 2016 8
MCR AND MCV SUCTION VAPOR CAPACITIES
.25 0.5 1.4 0.8 2.5 1.2 3.5 2.5 7.4 3.4 9.9 7.5 14 22 10 23 35
.50 0.7 2.0 1.2 3.6 1.7 5.0 3.6 11 4.8 14 11 20 32 14 33 50
1.0 0.9 2.8 1.7 5.0 2.4 7.1 5.1 15 6.7 20 15 28 45 20 47 71
2.0 1.3 3.9 2.4 7.1 3.4 10 7.2 21 9.5 28 21 40 63 28 66 100
40
5 2.1 6.2 3.7 11 5.3 16 11 33 15 44 34 63 100 45 105 158
10 3.0 8.7 5.3 16 7.5 22 16 47 21 63 47 89 141 63 148 224
US
15 3.7 11 6.5 19 9.2 27 20 58 26 77 58 – – 78 – –
20 4.2 12 7.5 22 11 32 23 66 30 89 67 – – 90 – –
.25 0.3 0.8 0.5 1.4 0.7 2.1 1.5 4.2 2.0 6.0 4.4 8.3 13 5.9 14 21
.50 0.4 1.2 0.7 2.1 1.0 2.9 2.1 6.0 2.9 8.5 6.2 12 19 8.4 20 30
1.0 0.6 1.6 1.0 2.9 1.4 4.1 2.9 8.5 4.1 12 8.8 17 26 12 28 42
0
2.0 0.8 2.3 1.4 4.1 1.9 5.8 4.1 12 5.8 17 12 23 37 17 39 59
5 1.3 3.6 2.2 6.5 3.1 9.2 6.5 19 9.2 27 20 37 59 26 62 93
10 1.8 5.1 3.1 9.2 4.3 13 9.2 27 13 38 28 53 83 37 87 132
.25 0.1 0.4 0.3 0.8 0.4 1.1 0.8 2.3 1.1 3.1 2.4 4.5 7.1 3.1 7.3 11
.50 0.2 0.6 0.4 1.1 0.5 1.6 1.1 3.3 1.5 4.5 3.4 6.3 10 4.4 10 16
-40
1.0 0.3 0.8 0.5 1.6 0.7 2.2 1.6 4.7 2.1 6.3 4.8 9.0 14 6.2 15 22
2.0 0.4 1.2 0.7 2.2 1.0 3.1 2.3 6.6 3.0 8.9 6.7 13 20 9 21 31
Cv 2.2 6.4 3.9 11.7 5.5 16.4 12 35 16 47 35 66 104 47 110 166
METRIC
1.0 13 39 24 72 34 101 72 217 98 294 218 – – 299 – –
1.4 15 46 28 86 40 119 86 257 116 348 258 – – 354 – –
.02 1.0 3.1 1.8 5.5 2.6 7.7 5.6 17 7.6 23 17 34 50 23 51 81
.04 1.4 4.3 2.6 7.7 3.6 11 7.9 24 11 33 24 48 71 33 72 114
.08 2.0 6.1 3.6 11 5.1 15 11 34 15 46 34 68 101 47 102 161
-20
.15 2.7 8.4 5.0 15 7.1 21 15 46 21 63 47 93 138 64 140 221
.4 4.5 14 8.1 24 12 34 25 75 34 103 76 152 225 104 229 361
.6 5.5 17 10 30 14 42 31 92 42 126 93 186 276 128 280 442
.02 0.6 1.8 1.0 3.2 1.5 4.4 3.2 9.5 4.4 13 9.6 19 28 13 29 45.6
.04 0.8 2.5 1.5 4.5 2.1 6.2 4.5 13 6.2 19 14 27 40 19 41 64.5
-40
.08 1.1 3.5 2 6.4 2.9 8.8 6.3 19 8.7 26 19 38 57 26 58 91.3
.15 1.6 4.8 3 8.7 4.0 12 8.7 26 12 36 26 53 78 36 79 125
Kv 1.8 5.5 3.3 10 4.7 14 10 30 13.3 40 30 60 89 40 90 142
R549a
9 JULY 2016
MCR AND MCV SUCTION VAPOR CAPACITIES
.25 0.5 1.4 0.9 2.6 1.2 3.5 2.7 7.8 3.5 10 7.7 15 23 10 24 37
.50 0.7 2.0 1.2 3.7 1.7 5.0 3.8 11 4.9 15 11 21 33 15 34 52
1.0 1.0 2.8 1.7 5.2 2.4 7.1 5.3 16 7.0 21 15 29 46 21 49 74
2.0 1.4 4.0 2.4 7.3 3.4 10 7.5 22 9.9 29 22 41 65 29 69 104
40
5 2.2 6.3 3.8 12 5.3 16 12 35 16 46 35 65 103 47 109 164
10 3.1 8.9 5.4 16 7.5 22 17 49 22 65 49 92 145 66 154 233
15 3.8 11 6.7 20 9.2 27 21 60 27 79 60 _ – 81 – –
US
20 4.3 13 7.7 23 11 32 24 70 31 92 69 – – 93 – –
.25 0.3 0.8 0.5 1.6 0.7 2.2 1.6 4.6 2.2 6.4 4.6 8.8 14 6.2 15 22
.50 0.4 1.2 0.7 2.2 1.0 3.1 2.2 6.5 3.1 9.0 6.6 12 20 9 21 31
1.0 0.6 1.7 1.0 3.1 1.4 4.3 3.2 9.2 4.3 13 9.3 18 28 12 29 44
0
2.0 0.8 2.4 1.5 4.4 2.0 6.1 4.5 13 6.1 18 13 25 39 18 41 62
5 1.3 3.8 2.3 7.0 3.2 9.6 7.0 21 9.7 28 21 39 62 28 65 98
10 1.8 5.4 3.3 9.8 4.6 14 10 29 14 40 29 55 87 39 92 139
.25 0.2 0.5 0.3 0.8 0.4 1.2 0.9 2.5 1.1 3.4 2.5 4.7 7.4 3.3 7.7 12
.50 0.2 0.7 0.4 1.2 0.6 1.7 1.2 3.6 1.6 4.8 3.5 6.7 11 4.7 11 17
-40
1.0 0.3 0.9 0.6 1.7 0.8 2.3 1.7 5.0 2.3 6.7 5.0 9.4 15 6.6 15 23
2.0 0.4 1.3 0.8 2.4 1.1 3.3 2.4 7.1 3.2 9.5 7.1 13 21 9 22 33
Cv 2.2 6.4 3.9 11.7 5.5 16.4 12 35 16 47 35 66 104 47 110 166
R549a
JULY 2016 10
MCR AND MCV LIQUID MAKE-UP AND DIRECT EXPANSION CAPACITIES
1-1/2˝ MCRB 2-1/2˝ 3˝ 6.0 726 422 149 100 113 76 105 84 104 81
1-1/2˝ MCR 4˝ 4˝ 12 1,453 844 297 200 226 151 211 168 207 163
US
2˝ MCR 4˝ 4˝ 16 1,937 1,125 396 267 301 202 281 224 277 217
20 MCR 40 40 1.8 936 545 190 130 144 98 137 109 134 106
25 MCR 50 50 3.3 1660 964 341 229 257 172 239 193 236 186
32 MCR 65 65 4.7 2342 1361 478 324 366 243 341 271 334 260
40 MCRB 65 75 5.0 2553 1484 524 352 397 267 369 295 366 285
40 MCR 100 100 10.0 5110 2968 1045 703 795 531 742 591 728 573
METRIC
50 MCR 100 100 13.3 6812 3957 1393 939 1059 710 988 788 974 763
Ammonia line size capacities are based on IIAR Refrigeration Piping Handbook tables. Halocarbon line size capaciites
are based on a nominal 3 ft/sec liquid velocity.
For applications with a large pressure drop across the Motorized Control Valve, attention must be paid to proper outlet
line sizing to accommodate flash gas.
Ammonia, R-22 and R134a capacities are based on +86°F (+30°C) saturated liquid and +20°F(-10°C) evaporating
temperature, and intermediate to low capacity based on +20°F (-10°C) saturation temperature and -20°F (-30°C) evaporating
temperature. Capacities are with ±20% from -40°F (-40°C) to -0°F (-18°C). R404 and R507 capacities based on +95° F
(+35°C) condensing temperature.
R549a
11 JULY 2016
OPERATION
1.0 34 98 60 180 85 254 185 539 246 723 539 1,016 1,601 724 1,693 2,555
2.0 48 139 85 255 120 359 261 762 348 1,023 762 1,437 2,264 1,023 2,395 3,614
Cv 2.2 6.4 3.9 11.7 5.5 16.4 12 35 16 47 35 66 104 47 110 166
0.10 139 425 255 773 363 1,082 773 2,318 1,053 3,168 2,344 5,156 6,953 3,212 7,051 11,125
0.20 197 601 361 1,093 514 1,530 1,093 3,278 1,490 4,480 3,314 7,292 9,833 4,543 9,972 15,733
kv 1.8 5.5 3.3 10 4.7 14 10 30 13.3 40 30 66 89 40 90 142
1.0 7.0 21 12 37 18 53 39 113 52 151 113 213 336 152 355 535
2.0 10 29 18 53 25 75 55 160 73 214 160 301 475 214 502 757
Cv 2.2 6.4 3.9 11.7 5.5 16.4 12 35 16 47 35 66 104 47 110 166
0.10 30 91 54 164 77 230 164 493 218 657 493 1,080 1,460 673 1,480 2,330
0.20 42 128 77 232 109 325 232 697 309 929 697 1,540 2,070 952 2,090 3300
kv 1.8 5.5 3.3 10 4.7 14 10 30 13.3 40 30 66 89 40 90 142
Ammonia, R-22, and R-134a capacities based on +86°F(30°C) saturated liquid, and +20°F (-10°C) evaporator, and no
flashing through the valve. R-404 and R-507 based on 95°F(35°C) saturated liquid temperatures.
Refer to page 2 for Liquid Line Sizing. Liquid line based on IIAR Piping Handbook Line Size Capacities.
R549a
JULY 2016 12
MCR AND MCV HIGH PRESSURE LIQUID LINE CAPACITIES
1.0 7.0 19 12 35 16 49 36 104 47 139 104 196 309 140 327 493
2.0 9.0 27 16 49 23 69 50 147 67 197 147 277 437 197 462 697
Cv 2.2 6.4 3.9 11.7 5.5 16.4 12 35 16 47 35 66 104 47 110 166
0.10 27 83 50 152 71 213 152 456 202 607 456 1,000 1,350 623 1,370 2,160
0.20 39 118 71 215 101 301 215 645 286 859 644 1,418 1,912 881 1,934 3,051
kv 1.8 5.5 3.3 10 4.7 14 10 30 13.3 40 30 66 89 40 90 142
0.10 19 57 34 103 48 144 103 310 141 423 313 688 928 431 942 1,490
0.20 26 80 48 146 68 204 146 438 199 598 443 974 1,320 610 1,340 2,110
kv 1.8 5.5 3.3 10 4.7 14 10 30 13.3 40 30 66 89 40 90 142
0.10 19 57 34 104 49 145 104 311 142 426 313 688 928 429 941 1,490
0.20 27 81 49 147 69 205 147 440 200 602 443 974 1,310 607 1,330 2,100
kv 1.8 5.5 3.3 10 4.7 14 10 30 13.3 40 30 66 89 40 90 142
Ammonia, R-22, and R-134a capacities based on +86°F(30°C) saturated liquid, and +20°F (-10°C) evaporator, and no
flashing through the valve. R-404 and R-507 based on 95°F(35°C) saturated liquid temperatures.
Refer to page 2 for Liquid Line Sizing. Liquid line based on IIAR Piping Handbook Line Size Capacities.
R549a
13 JULY 2016
MCR AND MCV HOT GAS SOLENOID DEFROST CAPACITIES
EVAPORATOR SIZE IN TONS (kW)
R549a
JULY 2016 14
The valve is driven by a motor and electronics that are CABLE CONNECTIONS
placed inside of an IP67 watertight rated housing. Upon
receiving an input signal, the motor shaft rotates and There are 2 distinct connection points that reside on the
transfers the force via a magnetic coupling to a threaded MCV powerhead. Both are M12 male connectors. The
stem. This cartridge stem directly drives the valve V-port power input consists of a 5 pin keyed connector and the
to open or closed based on the incoming signal. control signal consists of an 8 pin keyed connector.
The MCV comes standard with 6.5ft (2m) long cables with
M12 female heads. The power input cable consists of a
The actuator can run on incoming voltage of either 24VAC
5 pin head and 22AWG wires. The control signal consists
or 24VDC. This is provided via two wires on the 5 pin
of an 8 pin head and 24AWG wires. The standard cables
connector. Upon power-up the valve will run through a
come with flying leads. When an SMV to MCV conversion
self-calibration process. The actuator can be configured
kit is purchased for a modulating valve, the cable dongle
into 1 of 2 operational modes: modulating or slow/open
will come equipped a connection that will plug into to
close based on the wiring of the 8 pin connector along
existing wiring.
with the menu selection. There are 2 additional wires on
the 8 pin connector that provide 0/4-20mA feedback of
the valve V-port position. The feedback does not have
to be connected to operate the valve.
CABLE CONNECTIONS
GREEN RED
There are
8 PIN2SIGNAL
distinct connection points that reside on5 PIN
thePOWER
MCV powerhead. Both are M12 m
To operate in the modulating mode, a milliamp or voltage power input consists of a 5 pin keyed connector and the control signal consists of an 8 pin
input control signal must always be maintained to keep The MCV comes standard with 6.5ft (2m) long cables with M12 female heads. The power i
pin head and 22AWG wires. The control signal consists of an 8 pin head and 24AWG wires.
the V-port in position. A loss of signal or a signal out with flying leads. When an SMV to MCV conversion kit is purchased for a modulating valve
of range will drive the valve closed and display an error come equipped a connection that will plug into to existing wiring.
code. When the signal is present, the V-port will move
and stay at that location until the input signal changes.
If loss of input power occurs, the valve remains in its
current position, unless the valve is equipped with Power
Backup system.
The Motorized Control Valve can be wired to an optional power backup system that will c
defined location upon a loss of the incoming voltage. These locations of fully open, fully
position can all be programmed through the user interface display. TheR549a
Uninterruptable P
15 JULY
of a voltage monitoring system as well as an integrated battery. The 2016 UPS when c
optional
appropriately sized DC power supply can run up to 3 Motorized Control Valves. If the inco
below 19 volts and the power backup system is active, the system will switch over to use
R549a
JULY 2016
CURRENT INPUT MODULATING SIGNAL WIRING DIAGRAM
LINE VOLTAGE
+ +
COMPUTER
1 GRAY: (-)24VDC/24VAC (POWER) OR
CONTROLLER
2 BLACK: (+)24VDC/24VAC (POWER)
16
VALVE INSTALLATIONS, USE WIRE SIZE AS SHOWN
IN TABLE 1: 24 VAC/DC POWER WIRING.
DO NOT RUN MOTOR VALVE WIRING
WITH OR NEAR POWER WIRING OR VFD (VARIABLE
FREQUENCY DRIVES).
LINE VOLTAGE
+ +
COMPUTER
GRAY: (-)24VDC/24VAC (POWER) OR
1
CONTROLLER
2 BLACK: (+)24VDC/24VAC (POWER)
17
22 AND 24 GAUGE WIRES. FOR GREATER DISTANCE
BETWEEN VALVE AND CONTROLLER, OR MULTIPLE
VALVE INSTALLATIONS, USE WIRE SIZE AS SHOWN
IN TABLE 1: 24 VAC/DC POWER WIRING.
DO NOT RUN MOTOR VALVE WIRING
WITH OR NEAR POWER WIRING OR VFD (VARIABLE
FREQUENCY DRIVES).
JULY 2016
R549a
R549a
JULY 2016
SLOW OPEN/CLOSE RELAY INPUT SIGNAL WIRING DIAGRAM
CUSTOMER SUPPLIED POWER SUPPLIES AND CONTROLLER
(Slow Open/Close Control with Position Feedback)
TYPICAL APPLICATIONS
LINE VOLTAGE
IDEAL FOR REPLACEMENT OF:
1. BOTH HOT GAS SOLENOID VALVE
AND SOFT GAS SOLENOID VALVE
WITH A SINGLE HANSEN MOTOR VALVE.
18
IN TABLE 1: 24 VAC/DC POWER WIRING.
DO NOT RUN MOTOR VALVE WIRING.
WITH OR NEAR POWER WIRING OR VFD (VARIABLE
FREQUENCY DRIVES).
voltage power wiring or VFD Controls (Variable Frequency Drives). Do not earth or ground 24 VAC wiring.
use wire size as shown in Table 1: 24VAC/DC Power Wiring. Do not run Motorized Control Valve wiring with or near high
The valve is supplied with 6.5 feet of cable with 22 and 24 gauge wires. For greater distance between valve and controller
POWER BACKUP SYSTEM The optional UPS when combined with an appropriately
5 Gray sized
(+) DC powerInput
0/4-20mA supply can run up to 3 Motorized Control
Signal
The Motorized Control Valve can be wired to an optional Valves. If the incoming line voltage drops below 19 volts
6 the Pink
power backup system that will control valve to a user and(+) 0-5/10VDC & Relay Input
the power backup system is active, the system will
defined location upon a loss of the incoming voltage. Signal
switch over to use the battery power. This UPS mode is
These locations of fully open, fully7 closed,
Blue or another Not Usedby a slow flashing green LED as seen on the
indicated
open position can all be programmed through the user diagram below. The RED illuminate when there is an issue
8
interface display. The Uninterruptable Red
Power Supply Not Used
or the battery needs to be replaced. Once the incoming
(UPS) consists of a voltage monitoring
Add in system
(Voltageas well as Current
Modulating, Modulating,
voltage Slow/Openthe
level is restored, Close) wiring
valve diagrams afterreturn
will automatically this section.
an integrated battery. to normal control mode.
The Motorized Control Valve can be wired to an optional power backup system that will control the valve to a
defined location upon a loss of the incoming voltage. These locations of fully open, fully closed, or another o
position can all be programmed through the user interface display. The Uninterruptable Power Supply (UPS) c
of a voltage monitoring system as well as an integrated battery. The optional UPS when combined with an
appropriately sized DC power supply can run up to 3 Motorized Control Valves. If the incoming line voltage dr
below 19 volts and the power backup system is active, the system will switch over to use the battery power.
UPS mode is indicated by a slow flashing green LED as seen on the diagram below. The RED illuminate when t
an issue or the battery needs to be replaced. Once the incoming voltage level is restored, the valve will
automatically return to normal control mode.
R549a
19 JULY 2016
MOTORIZED CONTROL VALVE POWER BACKUP WIRING DIAGRAM
The valve is supplied with 6.5 feet of cable with 22 and 24 gauge wires. For greater distance between valve and controller
use wire size as shown in Table 1: 24VAC/DC Power Wiring. Do not run Motorized Control Valve wiring with or near high
voltage power wiring or VFD Controls (Variable Frequency Drives). Do not earth or ground 24 VAC wiring.
1. REMOVE THE FUSE FROM FUSE STORAGE POSITION. INSTALL IT ON THE FUSE HOLDER.
CHANGE TO 1)
THE UPS CAN SUPPLY POWER FOR UP TO (3) MCV'S.
THE FULLY CHARGED STATUS IS INDICATED BY THE LED BEING SOLID GREEN.
INSTRUCTIONS OF USING UNINTERRUPTIBLE POWER SUPPLY (UPS)
H.08
2. THE BATTERY STARTS TO CHARGE WHEN POWER IS ON.
R549a
JULY 2016 20
INSTALLATION
3/4" THRU DIMENSIONS,
1-1/4" MOTORIZED INCHES
CONTROL VALVE (MM)
INSTALLATION DRAWING
3/4" THRU 1-1/4" MOTORIZED CONTROL VALVE INSTALLATION DRAWING
3/4” THRU 1-1/4” MOTORIZED CONTROL VALVE INSTALLATION DRAWING
4.74" [120 mm] = = 7.28" 7.28" 7.28" 4.25" (108 mm) 4.25"
=
4.74" [120 mm] (185 mm) 7.28" (108 mm) =
MAX WIDTH OF VALVE TYP (185 mm) (185 mm) MAX WIDTH OF VALVE TYP
MAX WIDTH OF VALVE TYP (185 mm) MAX WIDTH OF VALVE TYP
10.75" 10.45"
(273 mm)10.75" (265 mm) 10.45"
(273 mm) (265 mm)
9.88"
9.88" (251 mm) 8.94"
(251 mm) 8.94" (227 mm)
(227 mm)
10.89" 10.44"
10.89" 10.44"
(277 mm) (265 mm)
(277 mm) (265 mm)
12.39" FPT, SW WELD-IN-LINE
12.39" FPT, SW (315 mm) WELD-IN-LINE
(315 mm)
13.39" WN, ODS
13.39" WN, ODS (340 mm)
(340 mm)
R549a
21 JULY 2016
MANUAL CONTROL TOOL (MCT)
INSTALLATION OVERVIEW Use of the Manual Control Tool (MCT) requires the removal
Protect the interior of valve from dirt and moisture during of the powerhead. Remove the cables to the powerhead to
storage and installation. Valve should be installed so prevent the powerhead from spinning. Remove powerhead
that the arrow on the valve body is in direction of normal by loosening the set screws at the base. Do not remove
refrigerant flow. the bonnet. Remove the powerhead and place the MCT
over the cartridge. Manually operate the valve open or
P l e a s e n o te : V a l v e w i ll n o t b a c k f l o w i f i n c l o s e d p o s i ti o n . closed by turning the MCT. Rotate clockwise to open
Do not install check valves upstream of the Motorized and counterclockwise to close. Refer to Table 2: Number
Control Valve without hydrostatic pressure relief . Do not of Turns to Actuate Valve for number of turns to fully
close the hand valve on inlet or outlet without making actuate valve.
sure valve is in the open position. System should be free
from dirt, weld slag and rust particles. A 60 mesh, close- Before re-installing rotate the MCT counterclockwise until
coupled strainer is available for installation at inlet of valve the Vport is closed. To re-install the powerhead, follow
for 3/4˝, 1˝ and 1-1/4˝. Do not close-couple strainers to the installation instructions below.
1-1/2 ˝ through 2 ˝ Motorized Control Valves.
1/4˝ NPT Gauge/Purge port connections are provided on TABLE 2: NUMBER OF TURNS TO ACTUATE VALVE
the inlet and outlet of the 3/4˝ thru 2˝ valves. NOMINAL SIZE
NUMBER
OFTURNS
Pipe sizing, valve placement, rating, anchoring, and similar INCH (MM)
prudent precautions should be taken to ensure “liquid
hammer” will not occur when valves open or close. 3/4”-1-1/4” (20-32) 7
YES NO
R549a
JULY 2016 22
INSTALLATION INSTRUCTIONS 7. Install new cartridge gasket to counter bore on top
NEW COMPLETE VALVE face of valve.
NOTE: Do not power on actuator until it is mounted to 8. Ensure V-port is installed into new rotor cartridge.
the valve and the set screws are properly torqued. To install V-port into cartridge fully supporting the
V-port and cartridge while carefully aligning the
1. Remove valve, actuator, and remaining contents from threaded shaft of cartridge with the low friction nut
box. of V-port. Carefully thread together 6-8 turns, and
2. F o r f l a n g e d v a l v e s , a l i g n v a l v e w i t h a r r o w align the anti-rotation slot on the V-port with the
pointing in direction of flow and mount per install anti-rotation pin of the cartridge. Fully thread the
protocol. For weld in line valves, it is recommended V-port into the cartridge, screwing the V-port fully
to remove the cartridge/V-port assembly during into the cartridge by turning the rotor clockwise.
welding by loosening bolts and removing 9. Install new rotor cartridge/V-port assembly into valve.
b o n n e t . R e p l a c e c a r t r i d g e / V- p o r t a s s e m b l y
with new gasket af ter completion and 10. Install new bonnet over cartridge assembly and
torque bolts to 35 ft-lbs. torque bolts to 35 ft-lbs.
5. Grease exterior of car tridge above the O -ring 13. Grease exterior of cartridge above the O-ring with
with supplied low temp, high load, low RPM supplied low temp, high load, low RPM grease such
grease such as Mobilith SHC PM 460 or similar. as Mobilith SHC PM 460 or similar.
6. C h e c k t h e b a s e o f t h e a c t u a t o r t o e n s u r e 14. Check the base of the actuator to ensure that the set
that the set screws are not protruding past the screws are not protruding past the ID of the threaded
ID of the threaded ring. If necessary back the set ring. If necessary back the set screws out to prevent
screws out to prevent interference during installation. interference during installation.
8. Rot ate ac tuator to or ient in desir e d position 16. Rotate actuator to orient in desired position and
and torque the 3 set screws at base to 4 in-oz using torque the 3 set screws at base to 4 in-oz using 3/32”
3/32” hex key. hex key.
9. Wire the flying lead ends of the cable to power and 17. For HMMR/HMMV replacement, connect the black
the desired input signal and feedback loop per wiring 7 pin dongle connector to the existing connection
diagram. already wired in place. The VPIF can be left in place
if desired.
10. Connect the red and green cables to the actuator
11. Upon power-up, the valve will automatically For HMSV replacement, cut off black 7 pin dongle
calibrate. connector wire connectors to power and input/output
per wiring diagram.
12. Program valve size and input signal through the
keypad display. NOTE: For HMSV replacement, it is important to remove
the 24VAC to the pink and yellow relay signal wires.
CONVERSION FROM SMV TO MCV Voltage to this line will cause damage as the input
NOTE: Do not power on actuator until it is mounted to should only be a closed contact switched to ground.
the valve and the set screws are torqued. 18. Connect the red and green cables to the actuator.
1. Isolate and pump down existing valve per PSMs. 19. Upon power-up, the valve will automatically calibrate.
2. Disconnect existing actuator connections. 20. P rogram valve size and input signal through the
3. Remove existing can, actuator from valve by loosening keypad display.
the screws.
4. Remove existing bonnet by loosening the bonnet
bolts.
5. Remove existing can, cartridge and rotor cartridge.
Ensure old gasket is removed from counter bore on
top face of valve.
6. Remove new actuator and remaining contents from
box.
R549a
23 JULY 2016
Menu
USER 3. Use the UP and DOWN arrow buttons to navigate through
he setup menu is usedINTERFACE MENU
to automatically calibrate, AND
adjust the control parameters, and view current
the list below.
ettings. AllINSTRUCTION GUIDE
displays in this menu start with the letter “H.”. The keypad and display are shown below:
4. To display and/or modify a value for that description, press
Up Button the ENTER button.
Red LED 5. Use the UP and DOWN arrow buttons to change the value.
Green LED Enter Button
6. Press the ENTER button to save the value. The display will
Blue LED
Down Button return to the setup menu
7. Repeat steps 3-6 for all desired changes.
The user interface is a located on the front of the valve
o enter andand when
navigate the in normal
menu, followoperation will display the % open
the steps below: 8. Exit the menu at any time by pressing and holding the ENTER
. Pressofandthe
holdvalve
the UPVport.
and DOWNThe arrows
setuponmenu can for
the keypad be3 entered
seconds to button on the keypad for 3 seconds.
. entering, H.01 will
Uponautomatically be shownadjust
calibrate, on the the
display.
control parameters, and
. Use the UPcurrent
view and DOWN arrows to
settings. Allnavigate
displaysthrough the list
in this menubelow.
start with NOTE: Exiting the menu will NOT save the value to the valve .
. To display and/or“H.”.
the letter modify a value
The for that
keypad description,
and display press the ENTER
are shown button.
belo
. Use the UP and DOWN arrows to change the value.
. Press the ENTER button to save the value. The display will return to the setup menu. If E.01 or E.02 become active, the valve will drive to zero and
. RepeatTosteps
enter
3-6and navigate
for all the menu, follow the steps below:
desired changes. close until the signal issue has been rectified. Once the input
. Exit the menu at any time by pressing and holding the ENTER button on the keypadsignal for 3 is within the proper limits, the powerhead will return to
1. Press and hold the UP and DOWN arrow buttons on the keypad
seconds. normal operation.
for 3 seconds
2. Upon entering, H.01 will be shown on the display.
Setup Parameters
Display Mode Description Min Max Factory Setting Comments
(Menu #) Value Value
- Normal Operation 0 100 - Valve % Open
H.01 Re-Zero 0 1 0 0 = No Action
Calibration 1 = Force motor to recalibrate zero
Display will show CAL
H.02 Automated/Manual 0 100 0 Mode becomes Manual when entered.
Mode Green LED will illuminate.
Range: 0 - 100% when Enter is pressed
H.03 Valve Size 0 8 0 00 = 3/4”
02 = 1”
03 = 1-1/4”
04 = 1-1/2”
05 = 2”
07 = Future
08 = Future
Valve will automatically calibrate after
selection is made by pressing Enter
H.04 Input Signal Type 0 1 0 0 = 4-20mA
1 = 0-20mA
2 = 0-5Vdc
3 = 0-10Vdc
4 = 1-6Vdc
5 = Relay input
H.05 Output Signal Type 0 2 0 0 = 4-20mA
1 = 0-20mA
H.06 Operation Type 0 3 0 0 = Modulating (Direct)
(input signal increase % open increase)
1 = Modulating (Reverse)
(input signal increase % open decrease)
2 = Open/Close (Direct)
(Closed relay fully closed valve)
3 = Open/Close (Reverse)
(Closed relay fully open valve)
H.07 Speed 25 100 100 Motor speed adjustment
Increments of 25%
H.08 Power Backup 0 1 0 0 = Disabled
Supply Status 1 = Enabled
H.09 Power Backup Fail 0 3 0 Define motor position on power loss
Safe Position upon 0 = close
power loss 1 = open
2 = user defined position @ H. 10
H.10 Fail Safe Position 0 100 0 Number between
when H.09 = 2 0 – 100
Increments of 10
H.11 Alarm Log 0 9 - A0 = Active alarm
A1 A9 = logged alarm. A9 oldest
H. 12 Max. Open Limit 30 100 100 Max. Open must be greater than Min.
Close increments of 10
H. 13 Min. Close Limit 0 40 0 Min. Close Limit must be less than Max.
Open Limit in increments of 10
H. 14 Input Dampening 1 5 -
H. 20 Password protected 0 999 -
H. 21 Measuring interval 1 50 -
H. 34 Factory Reset - Input value of 1 will reset all parameters to
factory defaults
H. 99 Software Version - Displays Software Version
R549a
JULY 2016 24
SERVICE AND MAINTENANCE
MCV MOTORIZED CONTROL VALVE
ACTUATOR
SET SCREWS
O-RING
BONNET
BONNET BOLTS
CARTRIDGE ASSEMBLY
CARTRIDGE GASKET
GUIDE PIN
PUMP OUT
GAUGE PORTS V-PORT
5. Grasp the top of the cartridge and while lifting out 7. Grease exterior of cartridge above the O-ring with
squarely, remove the cartridge assembly, taking supplied low temp, high load, low RPM grease such
care not to bend the shaft. If cartridge removal is as Mobilith SHC PM 460 or similar.
difficult, remove by placing the MCT on the cartridge 8. Check the base of the actuator to ensure that the set
and rotating counterclockwise and the cartridge will screws are not protruding past the ID of the threaded
press out. WARNING: Don’t bend shaft. ring. If necessary back the set screws out to prevent
6. Remove the V-port from the cartridge assembly by interference during installation.
unscrewing the rotor counterclockwise. 9. Install new actuator onto cartridge. Press firmly
down on the top of the actuator to ensure it fully
MCV REASSEMBLY seats. The gap between the base of the powerhead
and bonnet should be less than 1/16”.
1. Install new cartridge gasket to counter bore on top
face of valve. 10. Rotate actuator to orient in desire position and torque
the 3 set screws at base to 8 in-oz using 3/32” hex
2. Ensure V-port is installed into new rotor cartridge.
key.
To install V-port into cartridge fully supporting the
V-port and cartridge while carefully aligning the 11. Connect the red and green cables to the actuator.
threaded shaft of cartridge with the low friction nut
12. Upon power-up, the valve will automatically calibrate.
of V-port. Carefully thread together 6-8 turns, and
align the anti-rotation slot on the V-port with the
anti-rotation pin of the cartridge. Fully thread the
V-port into the cartridge, screwing the V-port fully
R549a
25 JULY 2016
MOTORIZED CONTROL VALVE PARTS LIST
3/4˝(20mm) - 2˝(50mm) MCV & MCR
MOTORIZED CONTROL VALVE
ACTUATOR KIT 1
Before
Dan, you send, Kelly has sent 4 additional picture updates. Please update those. I also have some changes by our internal technical team for the following:
Dan, 2 SEAT V-PORT
Page 4 you
Before – Remove
send, picture
Kelly has are bottom and move Typical ChillerPlease
Application tothose.
the topI of thehave
pagesome changes byKIT
Before
Page 11you send,
– Not sureKelly has sent
if I already
4
4 additional
sentmentioned
additional picture
butpicture
remove
updates.
updates.
lines forPlease
update
update
Port Sizes: those.
3/16” I also
(5mm),also¼”have some
(7mm), changes
3” (80 mm), by
our internal
4” our internal technical
(100mm) technical team
team for
for the
the following:
following:
Page 25
Page 4
4– – Number
– Remove of
Remove picture Turns
picture are to Actuate
are bottom
bottom and Valve
and move – Remove
move Typical 7/32”,
Typical Chiller 9/32”, 3”,
Chiller Application 4”
Application toto the
the top
top of
of the
the page
page
Page
Page
Page 30
Page 11 ––– Not
Simplify
Not sure to chart andmentioned
ifif II already
already keep formatting to looklines
but remove
remove like for
below.
Port Sizes:
Sizes: 3/16”
3/16” (5mm),
(5mm), ¼” ¼” (7mm),
(7mm), 3”3” (80
(80 mm),
mm), 4” 4” (100mm)
(100mm)
Pages11
Page 2542-44
– – sure
Remove
Number of Turns to
mentionedpages.
Troubleshooting
Actuate
but
Valve – Remove
lines for
7/32”,
Port
9/32”, 3”, 4”
Page
Page 25
45 – – Number
Change to of Turns to ActuateatValve
Troubleshooting the top– Remove
of the 7/32”,to9/32”,
screen 3”, 4” Parameters for
Installation
Page
Page 30
30 –
– Simplify chart and keep formatting to look like below.
Page
Pages46 – Simplify
42-44Under
–
to chart Information
Ordering and keep formatting
remove to look
7/32”, like below.
9/32”, 3”, 4” lines.
Pages
Page 4642-44
– – Remove
Remove
Detach Motorized
Troubleshooting
Troubleshooting pages.
pages.
ControlatValve Tools from Optional Controllers Table and for label it as Optional Equipment. Add HUPS under MCT and to the right add Uninterruptable
Page
Page 45 – Change Troubleshooting
Troubleshooting the top of the screen
screen to to Installation
Installation Parameters
Parameters for
Power45
Page 46
– Change
Supply
– Underand DC power
Ordering supplyatremove
Information
theup
for toptoof3the
7/32”,valves.
9/32”, 3”, 4” lines.
Page 46
Page 46
46 – – Under
– Detach Ordering
Under HUPS Information
add 75-1321 remove 7/32”, 9/32”, 3”, 4”
Cable setlines.
2m long Table and label it as Optional Equipment. Add HUPS under MCT and to the right add Uninterruptable
Page Motorized
Motorized ControlandValveto the
Tools right addOptional
from Controllers
Page
Page
Power
46 –
– Detach
46Supply
Underand75-1321
DC addControl
power 75-1329
supply
Valve
andup
for
Tools
to fromadd
the3 right
to valves.
Optional
Cable Controllers
set 5m longTable and label it as Optional Equipment. Add HUPS under MCT and to the right add Uninterruptable
Power
Page 46Supply
46 – Under and DC
Remove . before power supply
Compact in for
PSU2up to 3 valves.
line add Cable set 2m long
Page
Page 46 – – Under HUPS
HUPS add add 75-1321
75-1321 and
and toto the
the right
right add Cable set 2m long
Page
Page 46
46 – – Under
Under 75-1321
75-1321 add add 75-1329
75-1329 andand to
to the
the right add Cable
right add Cable setset 5m
5m long
long
Page 46 – Remove . before Compact in PSU2 line 1 2 3 4 Conversion Kits
Page 46 – Remove . before Compact in PSU2 line
Nominal Seat/Vport Assembly
Size Actuator 1 Kit kit
2 3 4 Conversion
1 2 3 4 SMVKits
Conversion Power Close to
Kits
Nominal
Nominal Seat/Vport
Seat/Vport Assembly
Assembly SMV to MCV MCV Power Backup
Valve Size
Size Actuator
Actuator Kit Kit kit
kit Cartridge Conversion Kit Conversion Kit to
SMV
SMV Power Close
Power Close to
Type Inch mm Standard Power Backup P/N Cv Assembly Kit Gasket Kit (excludes
SMV to Vport)
MCV (excludes
MCV Power Vport)
Backup
SMV to MCV
75-1318 MCV Power Backup
Valve 3/4" (20) 75-1154 6.4 Cartridge Conversion Kit Conversion Kit
Valve Cartridge
75-1325Kit Conversion
(Actuator, Kit
Dongle Conversion
75-1318 Kit
+ Vport)
HUPS
Type
Type 1"
Inch
Inch (25)
mm
mm Standard
Standard Power
Power Backup
Backup 75-1155
P/N
P/N 11.7
Cv
Cv Assembly
Assembly Kit Gasket
Gasket Kit
Kit (excludes
(excludes Vport)
Vport) (excludes
(excludes Vport)
(Cartridge, gasket, Cable, Cartridge,
75-1318 (Actuator, Dongle
3/4"
3/4" (20)
(20) 75-1154
75-1154 6.4
6.4 75-1318
oring,75-1325
grease, hex Bonnet,
(Actuator, Bolts,
Dongle Cable, Cartridge,
75-1318 +
1"
1" (25)
(25) 75-1155
75-1155 11.7
11.7 75-1325
key)gasket, (Actuator,
Gasket, Dongle
Oring, 75-1318
Bonnet, + HUPS
HUPS
Bolts, Gasket,
(Cartridge, Cable,
Cable, Cartridge,
Cartridge, (Actuator,
(Actuator, Dongle
Dongle
1-1/4" (30) 75-1156 16.4 (Cartridge,
oring,
gasket,
grease, hex 75-1322 Grease)
Bonnet, Bolts, Oring,
Cable, Grease)
Cartridge,
MCV oring, grease, hex Bonnet, Bolts, Cable, Cartridge,
1-1/2" (40) 75-1157 35 75-1319
Gasket,
key)
key) Gasket, Oring,
(Actuator, Oring,
Dongle
Bonnet,
Bonnet, Bolts,
Bolts,
75-1319
Gasket,
Gasket,
+ HUPS
1-1/4"
1-1/4" (30)
(30) 75-1156
75-1156 16.4
16.4 75-1326 75-1322
75-1322 Grease)
Grease) Oring,
Oring, Grease)
Grease)
MCV
MCV (Cartridge, gasket, Cable, Cartridge, (Actuator, Dongle
1-1/2"
1-1/2" (40) (40) 75-1157
75-1157 35
35 75-1319
75-1319
oring, grease, hex Bonnet,
(Actuator, Bolts,
Dongle Cable, Cartridge,
75-1319 + HUPS
HUPS
75-1326
75-1326
key) (Actuator,
Gasket, Dongle
Oring, 75-1319
Bonnet, +
Bolts, Gasket,
(Actuator with (Cartridge,
(Cartridge, gasket,
gasket, Cable, Cartridge,
Cable, Cartridge, (Actuator,
(Actuator, Dongle
Dongle
2" (50) 75-1166 47 oring, grease, hex 75-1323 Grease)
Bonnet, Bolts, Oring,Cartridge,
Cable, Grease)
(Actuator only) UPS, DC Power oring, grease, hex Bonnet, Bolts, Cable, Cartridge,
3/4" (20) 75-1160 2.2 key) Gasket, Oring, Bonnet,
Supply)
(Actuator
key) 75-1318
Gasket, Oring, Bonnet, Bolts,
Bolts, Gasket,
Gasket,
1"
2"
2" (25)
(50)
(50) (Actuator with
with 75-1161
75-1166
75-1166 3.9
47
47 75-1325 75-1323
75-1323 Grease)
(Actuator, Dongle
Grease) Oring,
75-1318
Oring, Grease)
+ HUPS
Grease)
3/4" (20) (Actuator
(Actuator only)
only) UPS,
UPS, DC
DC Power
Power 75-1160 2.2 (Cartridge, gasket, Cable, Cartridge, (Actuator, Dongle
3/4" (20) Supply) 75-1160 2.2 75-1322 75-1318
75-1318
1" (25) Supply) 75-1161 3.9 oring,75-1325
grease, hex Bonnet, Bolts, Cable, Cartridge,
MCR 1" (25) 75-1161 3.9 75-1325
key)gasket, (Actuator,
(Actuator, Dongle
Dongle 75-1318
75-1318 + HUPS
+ HUPS
(Cartridge, Gasket,
Cable, Oring,
Cartridge, Bonnet, Bolts,
(Actuator, Gasket,
Dongle
(Cartridge, gasket, 75-1322 Cable, Cartridge, (Actuator, Dongle
1-1/4" (30) 75-1154 5.5 oring, grease, hex 75-1322 Grease)
Bonnet, Bolts, Oring,Cartridge,
Cable, Grease)
MCR oring, grease, hex Bonnet, Bolts, Cable, Cartridge,
MCR 1-1/2" (40) 75-1162 12 key) 75-1319
Gasket,
key) Gasket, Oring,
(Actuator, Oring,
Dongle
Bonnet,
Bonnet, Bolts,
Bolts,
75-1319
Gasket,
Gasket,
+ HUPS
2"
1-1/4"
1-1/4" (50)
(30)
(30) 75-1163
75-1154
75-1154 16
5.5
5.5 75-1326 Grease)
Grease) Oring,
Oring, Grease)
Grease)
(Cartridge, gasket, Cable, Cartridge,
75-1319 (Actuator, Dongle
1-1/2"
1-1/2" (40) (40) 75-1162
75-1162 12
12 75-1323 75-1319
oring, grease , hex Bonnet,
(Actuator, Bolts,
Dongle Cable, Cartridge,
75-1319 +
2"
2" (50)
(50) 75-1163
75-1163 16
16 75-1326
75-1326
key) (Actuator,
Gasket, Dongle
Oring, 75-1319
Bonnet, + HUPS
HUPS
Bolts, Gasket,
(Cartridge, gasket,
(Cartridge, gasket, Cable,
Cable, Cartridge,
Cartridge, (Actuator,
(Actuator, Dongle
Dongle
MCRB 1-1/2" (40) 75-1230 6 75-1323
75-1323 Grease) Oring, Grease)
oring,
oring, grease
grease ,, hex
hex Bonnet,
Bonnet, Bolts,
Bolts, Cable,
Cable, Cartridge,
Cartridge,
key) Gasket,
key) Gasket, Oring,
Oring, Bonnet,
Bonnet, Bolts,
Bolts, Gasket,
Gasket,
* CARTRIDGE
MCRB
MCRB ASSEMBLY
1-1/2"
1-1/2" (40)
(40) KIT, CAN KIT AND SEAT/V-PORT KIT INCLUDE
75-1230
75-1230 6
6 GASKET KIT (Column 5) Grease)
Grease) Oring,
Oring, Grease)
Grease)
Please call with any questions.
** ACTUATOR KITS INCLUDE REPLACEMENT GASKET AND SCREWS
Thanks,call with any questions.
Please
Please
Bryant call with any questions.
Thanks,
Thanks,
From: Dan Gatz [mailto:dan@apprizepromo.com]
Bryant
Bryant
Sent: Monday, July 25, 2016 2:05 PM
To: Bryant
From: Dan Crane
Gatz <BCrane@hantech.com>
From: Dan
Subject: Gatz [mailto:dan@apprizepromo.com]
Sorry [mailto:dan@apprizepromo.com]
Sent:
Sent: Monday, July 25,
Monday, July 25, 2016
2016 2:05
2:05 PM
PM
To:
To: Bryant
Bryant Crane
Crane <BCrane@hantech.com>
<BCrane@hantech.com>
Hi Bryant
Subject:
Subject: Sorry
Sorry
IHigot bogged down this afternoon I will have something for you in the morning. Sorry Thought I could have it this afternoon.
Hi Bryant
Bryant
R549a
THANKS
II got bogged 26
JULY bogged down
got 2016 down this
this afternoon
afternoon II will
will have
have something
something for
for you
you in
in the
the morning.
morning. Sorry
Sorry Thought
Thought II could
could have
have it
it this
this afternoon.
afternoon.
Dan
THANKS
THANKS
MOTORIZED CONTROL VALVE RECOMMENDED PIPING
R549a
27 JULY 2016
MOTORIZED CONTROL VALVE RECOMMENDED PIPING
R549a
JULY 2016 28
HANSEN CONTROLLERS
HANSEN PXVC CONTROLLERS operation, and sensor location before attempting to tune
MCV Bulletin Page ~30 (Excerpts from page 1 & 2 of PXVC theBulletin) – HANSEN PXVC
PXVC controller. FieldCONTROLLERS
alteration of the controller
The PXVC TheIntelligent, singlesingle
PXVC Intelligent, loop,loop,
PIDPID
controller
controllerisis aa standalone cabinet mounted electronic
configuration is not recommended. universal controller.
Controller tuning of
standaloneThecabinet
Hansenmounted electronic
PXVC controller canuniversal controller.
be configured for several the
different
P-I-D applications.
is performed The
in controller, with factory
the “parameters” section and
The Hansen PXVCwill
defaults, controller can be configured
give reasonably for several
good control. If control difficulties
are theoccur during startup,
only parameters theituser
is recommended
may need tofirst to
optimize.
different thoroughly check
applications. Thesystem and components
controller, with factoryfor proper installation, operation, and sensor location before attempting
defaults,
will give to tune the PXVC
reasonably good controller.
control. Field alteration
If control of the controller configuration is not recommended. Controller tuning
difficulties
of the
occur during P-I-D isitperformed
startup, in the “parameters”
is recommended section and are the only parameters the user may need to optimize.
first to thoroughly See the PXVC Universal Controller Bulletin found at www.
check system and components for proper installation, hantech.comfor formore
more information.
See the PXVC Universal Controller Bulletin found at www.hantech.com information.
MCV Bulletin Page (Excerpts from pages 1 & 3 of PXVC Bulletin) – HANSEN PXVC CONTROLLERS
R549a
29 JULY 2016
PXVC-PT (PRESSURE TEMPERATURE) Hansen Motorized Control Valve for direct expansion
SUPERHEAT/SUBCOOLING CONTROL evaporators. The 2 inputs, pressure transducer and
PXVC-PT (Pressure Temperature) SUPERHEAT/SUBCOOLING Control
temperature probe, are used to determine the amount
OVERVIEW
OVERVIEW
of Superheat or Subcooling in a controlled refrigeration
The PXVC-PT controller is used in applications where the system temperatures are not less than -20°F (-28.9°C). It
The PXVC-PT controller is used in to
applications where the of thesystem. The PXVC-PT controls the Motorized Control Valve
is factory programmed provide precise control Hansen Motorized Control Valve for direct expansion
system temperatures are not less than -20°F (-28.9°C). It to modulateprobe,
evaporators. The 2 inputs, pressure transducer and temperature the refrigerant
are used toflow necessary
determine to maintain
the amount of a
is factory programmed
Superheat orto provide precise
Subcooling controlrefrigeration
in a controlled of the set for superheated
system. The PXVC-PT gas leaving
controls the the evaporator.
Motorized Control Valve to
modulate the refrigerant flow necessary to maintain a set for superheated gas leaving the evaporator.
PXVC-DX, PXVC-T, PXVC-L, PXVC-P, PXVC-CI
DISPLAY
INDICATOR
1 2 OUTPUT ON %
SUPERHEAT/
SUBCOOLING 20.6 °F
TEMPERATURE 19.2 °F
SETPOINT
1 2 3 4 5 6 (ALARMS)
TEMPERATURE
ACKNOWLEDGED
ALARM (S)
PIN #1
DISPLAY
INDICATOR
1 2 OUTPUT ON %
SYSTEM
PRESSURE 50.8 P
(PSIA) 32.0 °F
SYSTEM
TEMPERATURE (OR) 1 2 3 4 5 6 (ALARMS)
ACTIVE ALARM
ACKNOWLEDGED
ALARM (S)
PIN #11
R549a
JULY 2016 30
TYPICAL WIRING DIAGRAM for PXVC-PT
R549a
31 JULY 2016
PXVC-DX, PXVC-T, PXVC-L, PXVC-P, PXVC-CI CONTROLLERS
PXVC-DX CONTROL OF EVAPORATOR SELECTION OF CONTROL VALVES
The Hansen PXVC-DX Controller is used in applications
PXV Control Valves
where the refrigerant temperature is between -60°F to
150°F (-51.1°C to 65.6°C). It is factory programmed to • Hansen PXV5, PXV15, PXVW60 or MVP13-1PXV
provide precise control of the Hansen PXV pulse-width Motorized Valves
expansion valve for direct expansion evaporators. A • Hansen 4MMR/V, HMXV, HMMVC, HMMRC and
4-20mA input signal from the Hansen HPT superheat HMXVC
sensor or computer output of superheat to the PXVC-
DX controller which pulses the Hansen PXV valve. The Wiring Diagrams
valve opens and closes at a rate equal to the refrigerant • Refer to page 8 for typical wiring diagram. Also,
flow necessary to maintain a set-for superheated gas refer to www.hantech.com website for latest wiring
leaving the evaporator. and support documentation
R549a
JULY 2016 32
PXVC-DX, PXVC-T, PXVC-L, PXVC-P, PXVC-CI
DISPLAY AND KEYPAD OPERATION
PIN #1
PIN #11
PXVC R549a
NOV 2012
8 33 JULY 2016
PXVC-T (TEMPERATURE) OVERVIEW
The Hansen PXVC-T Controller is factory programmed to provide precise control of temperature in applications such
as Liquid Injection of screw compressors. A temperature sensor, included, provides an input to the Hansen PXVC-T
controller which controls the Hansen Motorized Control Valve. The valve modulates the refrigerant flow necessary to
maintain a set for discharge gas temperature.
R549a
JULY 2016 34
PXVC-L (LEVEL) OVERVIEW
The Hansen PXVC-L Controller is factory programmed to provide precise control of liquid level in flooded evaporators,
small liquid recirculators, and other refrigerant level vessels. A 4-20 mA input signal from the Hansen VLT level probe,
Hansen Vari-Level with 4-20 mA, or other liquid level device to the Hansen PXVC-L controller which controls the Hansen
Motorized Control Valve. The valve modulates the refrigerant flow necessary to maintain a set-for liquid level in the vessel.
R549a
35 JULY 2016
PXVC-P (PRESSURE) OVERVIEW
The Hansen PXVC-P Controller is factory programmed to provide precise control of pressure in applications such as
hot gas bypass to suction of a compressor. A pressure sensor, available from Hansen, provides an input to the Hansen
PXVC-P controller which controls the Hansen Motorized Control Valve. The valve modulates the refrigerant flow necessary
to maintain a set for pressure.
R549a
JULY 2016 36
INSTALLATION PARAMETERS FOR THE MOTORIZED CONTROL VALVE
APPLICATION DESCRIPTION
Refrigerant:____________________________
Service Type (Dry or Wet Suction, liquid make-up, hot gas, liquid feed, etc.):_________________________________________
Rated Capacity of Valve (per capacity tables based on Pressure Drop above):________________________________________
R549a
37 JULY 2016
CAUTION OPTIONAL CONTROLLERS
Hansen valves are for refrigeration and other Hansen
approved systems only. These instructions and related CAT NO DESCRIPTION
s afet y p r e c au t io n s m u s t b e r e a d c o m p le te l y a n d
understood before selecting, using, or servicing these MCV/MCR OPTIONAL CONTROLLERS
va lve s . O nl y k now le dg e a b le, tr a ine d r ef r ig e r ation Temperature controller with temperature sensor
PXVC-T
technicians should install, operate, or service these for fully modulating temperature control.
valves. Stated temperature and pressure limits should
not be exceeded. Bonnets should not be removed from Level controller for fully modulating applications.
PXVC-L
these valves unless the system has been evacuated to Level sensor not included.
zero pressure. See also Safety Precautions in current List
Pressure controller with pressure transducer for
Price Bulletin and Safety Precautions Sheet supplied with PXVC-P
fully modulating pressure control.
product. Escaping refrigerant can cause injury, especially
to the eyes and lungs. Direct expansion or super heat controller for fully
PXVC-PT
modulating applications.
WARRANTY
Hansen electrical and electronic parts are guaranteed RDR Remote digital readout displays valve position
against defective materials and workmanship for 90 days
F.O.B. our plant. All other components are guaranteed for
WTE Watertight Enclosure (Nema4 for above controller)
one year F.O.B. our plant. No consequential damages or
field labor is included.
Compact Power Supply
PSU2
(100-240VAC: 24VDC) for above controller
TYPICAL SPECIFICATIONS
Motor operated control valves shall feature direct actuation
of the main valve seat by the motor shaft, a canned
motor to eliminate valve stem seal leakage, a ductile iron
OPTIONAL EQUIPMENT
body, and be suitable for a safe working pressure of 400
psig (28 bar), as manufactured by Hansen Technologies MCT Manual Control Tool
Corporation, or approved equal.
Uninterruptable Power Supply and DC power
HUPS
supply for up to 3 valves
ORDERING INFORMATION
75-1321 Cable set 2m long
FPT only available up to and 1¼˝ port size.
75-1329 Cable set 5m long
FLANGE CONNECTION
NOMINAL STYLES AND SIZES
PORT SIZE
FPT, SW, WN ODS
INCH (MM) STANDARD ALSO STANDARD
3/4˝ (20) 3/4 ˝ 1, 1-1/4 ˝ 7/8 ˝
1˝ (25) 1˝ 3/4 ˝, 1-1/4 ˝ 1-1/8 ˝
1-1/4˝ (32) 1-1/4 ˝ 3/4 ˝, 1 ˝ 1-3/8 ˝
1-1/2˝ (40) 1-1/2 ˝ 2˝ 1-5/8 ˝
2˝ (50) 2˝ 1-1/2 ˝ 2-1/8 ˝
TO ORDER:
Specify valve type (MCV, MCR), nominal port size, flange
connection style and size.
motorized control valves with weld-in connections available
(3/4˝ thru 2˝ ), contact factory.