You are on page 1of 32

Series 600 Heat Detectors

UL Listed* Series 600 Heat Detectors


for Two-Wire Bases

Features

Series 600 Heat Detector details:


• Superior performance and reliability
• Attractive new design
• Designed for fast and easy installation
• Unique ‘park’ position for commissioning and service
procedures
• Interfaces seamlessly with a wide range of panels
• Compatible with Tyco® 600 Series for easy upgrade
• Low operating current, up to 32 detectors per zone
• Optional remote alarm indicating LED 601H-F-UL Heat Detector Mounted
• Low profile, discrete and unobtrusive in 5B Base with 6A-5B-UL Adapter
• Designed for EMI compatibility
• UL listed to Standard 521 Series 600 Detector Features
• Base and adaptor are UL listed to Standard 268
Rate-of-Rise. Two negative temperature coefficient
Available models: thermistors, Rsens and Rref are used in a bridge
• 601H-RF-UL; rate-of-rise plus fixed temperature 135° F configuration. One thermistor, Rsens, is exposed to the air
(57° C), spacing distance is 70 ft (21.3 m) while the other, Rref, is thermally lagged inside the
• 601H-F-UL; fixed temperature 135° F, spacing distance detector body.
is 60 ft (18.3 m) If the temperature of the air around the detector rises
• 631H-F-UL; fixed temperature 200° F (93° C), spacing quickly, a temperature difference will be established
distance is 60 ft (18.3 m) between Rsens and Rref. The values of the bridge
components are chosen such that, if a particular rate of
Description change of temperature is sustained for sufficient time, the
comparator will change state and the detector will signal
Heat Detector Categories. Heat detectors fall into two an alarm condition. If the rate of temperature increase is
main categories; those that go into alarm once a certain very slow, then the temperatures of the sensing and
sensor temperature has been reached (fixed) and those reference thermistors will be more nearly equal. Under
that go into alarm if the rate of temperature increase is these conditions the bridge components ensure that the
above a certain level (rate-of-rise). comparator changes state when the predetermined fixed
temperature is reached.
The combination of rate-of-rise and fixed temperature
sensing elements allows fire detection from low The Rate-of-Rise detector has a rate sensitivity and fixed
temperatures, where rate-of-rise sensing would give an (static) temperature setting to suit a particular type of
earlier alarm than a fixed temperature, with the fixed application.
temperature element available for fires where temperature
builds up gradually. Fixed Temperature. The Fixed Temperature detector is
similar to the rate-of-rise detector except that the
Heat Detector Considerations. Heat detection is not reference thermistor is replaced by a fixed resistor. The
as fast as smoke detection in most fires as early stages of detector, therefore, responds more slowly to Rate-of-Rise
a fire tend to burn less hot than the later stages. However, of temperature. The bridge components are chosen instead
hostile environments where aerosols, dust, smoke or even to cause a comparator to change state when the sensing
extremes of temperature are normally present, preclude thermistor reaches a predetermined temperature
the use of smoke detectors as a fire indicator. In these irrespective of the rate of change.
cases a heat detector may provide an acceptable, though
less sensitive alternative. Heat detection is also often used
where the risk of fires or the consequences of fire are * Refer to page 2 for additional listing information. This product was not ULC or CSFM
listed, or approved by FM or MEA (NYC) as of document revision date. Additional listings
considered low, as heat detection is generally less may be applicable; contact your local Simplex product supplier for the latest status. Listings
expensive than smoke detection. and approvals under Simplex Time Recorder Co. are the property of Tyco Safety Products
Westminster.

A0001-0001-4 3/2009
Application Reference Fixed Temperature Guidelines
Detector Locations (see table on page 4). Heat 135° F (57° C) fixed temperature detectors are for normal
detectors are used where property protection is desired temperatures that do not exceed 100° F (38° C).
and where life safety protection is not required or is
200° F (93° C) fixed temperature detectors are for normal
performed by other equipment. Typical heat detector
temperatures that exceed 100°F (38° C) but are less than
applications are satisfied by the use of fixed temperature
150° F (66° C).
detectors.
The addition of rate-of-rise operation provides two forms WARNING:
of heat detection for use where temperature fluctuations In most fires, hazardous levels of smoke and
are controlled and are less than 6° F/min (3.33° C/min). toxic gas can build up before a heat detection
Where temperature may fluctuate more quickly, use fixed device would initiate an alarm. In cases where
temperature detectors. Life Safety is a factor, the use of a smoke
detector is highly recommended.

Product Selection
Model Description Compatibility
601H-RF-UL Heat Detector Fixed 135° F + Rate-of-Rise
601H-F-UL Heat Detector Fixed 135° F Compatible with 5B base; 5” (127 mm) diameter
631H-F-UL Heat Detector Fixed 200° F
Compatible Bases
Model Description Details Listing Reference
2-Wire Base with connections IDC and LED connections are screw
5B for Remote Alarm LED terminals for input/output wiring; 18 to UL listed under Thorn Security LTD
Indicator 14 AWG (1 mm2 to 1.5 mm2)
Detector Accessories
Model Description Details Listing Reference
6A-5B-UL 6” (152 mm) Base Adapter Increases the 5B surface area UL listed under Thorn Security LTD
Robust protective cage for Series 600
CW-5B Detector Protective Cage Not listed
detectors using the 5B base
Commissioning tool, shorts out base
SA600 Line Shorting Adapter contacts to enable cable resistance Listing not applicable, service tool only
checks to be carried out

Detector Status LED Indicators


LED Indication Status
Pulses approximately every 10 seconds Normal
Steady On Alarm

Dimensions and Reference Information

C5-B Detector Cage

2 A0001-0001-4 3/2009
Mounting Information

Specifications Application Reference


The following table provides a reference for the maximum
10.5 to 33 VDC from fire alarm rectangular area covered for detectors rated with the given
Voltage
control panel IDC spacing. For additional information, including consideration
601H-F-UL 100μA @ 24VDC of ceiling height, refer to NFPA 72, the National Fire
Standby Alarm Code.
Current 601H-RF-UL 90μA @ 24VDC
631H-F-UL 95μA @ 24VDC Maximum Rectangular Area for
Single Detector Coverage
Up to 82 mA maximum, exact 60 ft Rated Spacing 70 ft Rated Spacing
Alarm Current current is determined by alarm (18.3 m) (21.3 m)
current limiting of connected IDC
60 ft x 60 ft 70 ft x 70 ft
Storage Temperature -13° F to 176° F (18.3 m x 18.3 m) (21.3 m x 21.3 m)
Range (-25° C to 80° C) 55 ft x 64.6 ft 65 ft x 74.6 ft
Operating Temperature 32° F to 100° F (16.7 m x 19.7 m) (19.8 m x 22.7 m)
Range (0° C to 38° C) 50 ft x 68.5 ft 60 ft x 78.7 ft
Humidity Range Up to 95% non-condensing (15.2 m x 20.8 m) (18.3 m x 24 m)
45 ft x 72 ft 55 ft x 82.3 ft
Color White 019 (13.7 m x 21.9 m) (16.7 m x 25 m)
Dimensions 40 ft x 74.8 ft 50 ft x 85.4 ft
(12.2 m x 22.8 m) (15.2 m x 26 m)
5” Dia. x 2-1/8”” H
In base 35 ft x 77.3 ft 45 ft x 88.1 ft
(127 mm x 55 mm)
(10.6 m x 23.5 m) (13.7 m x 26.8 m)
In base with base 6” Diameter x 2-9/16” H 30 ft x 79.3 ft 40 ft x 90.5 ft
adapter (152 mm x 66 mm) (9.1 m x 24.1 m) (12.2 m x 27.5 m)
25 ft x 81 ft 35 ft x 92.6 ft
(7.6 m x 24.7 m) (10.6 m x 28.2 m)
20 ft x 82.4 ft 30 ft x 94.3 ft
(6.1 m x 25.1 m) (9.1 m x 28.7 m)
15 ft x 83.5 ft 25 ft x 95.7 ft
(4.5 m x 25.4 m) (7.6 m x 29.1 m)
10 ft x 84.2 ft 20 ft x 96.9 ft
(3.05 m x 25.6 m) (6.1 m x 29.5 m)
5 ft x 84.7 ft 15 ft x 97.8 ft
(1.5 m x 25.8) (4.5 m x 29.8 m)
1 ft x 84.85 ft 10 ft x 98.4 ft
(0.3 m x 25.8 m) (3.05 m x 30 m)
5 ft x 98.8 ft
(1.5 m x 30.1 m)
1 ft x 99 ft
(0.3 m x 30.2 m)

3 A0001-0001-4 3/2009
Application of 600 Series Detectors

The table below is for guidelines only, specific situations are likely to require variations on the suggested detector types. Real
situations may require detector combinations to cover all likely risks.

A B C D E

Environment Benign moderately


Very clean Dusty and/or Unregulated
clean regulated Dirty - smoky
and dry humid temperature
temperature

Loading bay/
For Example Offices, light warehouse
Clean room Livestock pen Kitchen,
industrial, hospitals, with diesel
data mill, laundry, engine room,
residential, fork-lifts etc.
processing changing engine test
passenger Heavy
suite room beds
accommodation industrial ferry
Fire Loading Probable Risk (car deck)
Electronic Cable pyrolosis
equipment (toxic fumes)
601P-UL 601P-UL
electrical electrical arcs
1 601PH-UL 601PH-UL 601P-UL
switchgear electric (ignition source)
601I-ULC 601I-ULC
motors cable associated electrical
conduit dangers
Fabrics, clothes
soft furnishings Smouldering (difficult
paper, cardboard to locate - toxic
601PH-UL
2 plastic foams fumes) likelihood of 601P-UL 601P-UL
601P-UL
animal bedding flashover (back-
wood shavings draught)
etc.
Flaming fire (rapid
Flammable liquids
build-up of dense
paints, solvents 601I-ULC 601I-ULC
smoke) high 601H-RF-UL
3 flammable gasses 601PH-UL 601PH-UL 601H-RF-UL
temperature fumes 601I-ULC
unstable 601P-UL 601P-UL
associated explosion
chemicals
dangers
Foodstuffs general
Smoke and flame
organic waste 601PH-UL
initially fairly slow but 601PH-UL 601P-UL 601H-F-UL
4 animal fodder 601P-UL
high temperatures 601H-RF-UL 601H-RF-UL 631H-F-UL
wooden structures 601I-ULC
once established
solid fuels
Type of fire risk may
Plastic, chemicals
vary as can the type 601PH-UL 601PH-UL 601P-UL
machinery 601H-F-UL
5 of fire (may require a 601P-UL 601I-ULC 601I-ULC 601P-UL
building materials 631H-F-UL
mix of detection 601I-ULC 601H-RF-UL 601H-RF-UL
unknown contents
types)

Tyco is a registered trademark of Tyco International Services GmbH and is used under license. Simplex, and the Simplex logo are trademarks of Tyco International Ltd. and its
affiliates and are used under license. NFPA 72 and National Fire Alarm Code are trademarks of the National Fire Protection Association (NFPA).

Tyco Safety Products Westminster • Westminster, MA • 01441-0001 • USA A0001-0001-4 3/2009


www.tycosafetyproducts-usa-wm.com
© 2009 Tyco Safety Products Westminster. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Series 600 Smoke Detectors
UL Listed* Series 600 Optical Smoke Detectors
for Two-Wire Bases

Features

Series 600 Optical Smoke Detector details:


• Superior performance and reliability
• Attractive new design
• Designed for fast and easy installation
• Unique ‘park’ position for commissioning and service
procedures
• Interfaces seamlessly with a wide range of panels
• Compatible with Tyco® 600 Series for easy upgrade
• Low operating current, up to 32 detectors per zone 601P-UL Optical Smoke Detector Mounted
• Optional remote alarm indicating LED in 5B Base with 6A-5B-UL Adapter
• Low profile, discrete and unobtrusive
• Designed for EMI compatibility Series 600 Detector Features
• UL listed to Standard 268
The optical system consists of an infrared emitter and
Models available in two sensitivity settings: receiver arranged such that their optical axes cross in the
• 601P-UL Standard Sensitivity, nominal 2.11 to 3.8%/ft sampling volume. The emitter produces a narrow beam of
obscuration light which is prevented from reaching the receiver by the
baffles. When smoke is present in the sampling volume a
• 601P-UL-L Special Application Sensitivity, nominal
proportion of the light is scattered, some of which reaches
3.0 to 3.8%/ft obscuration
the receiver. For a given type of smoke, the light reaching
Functional chamber enclosure: the photodetector is proportional to the smoke density.
• Concentric baffle design enhances smoke capture by The emitter is a GaAlAs solid state type operating in the
directing air flow to the smoke chamber near infrared at 880 nm, while the sensor is a matched
silicon photodiode. These devices are held in place by the
Description labyrinth mouldings. The design of the labyrinth is such
that the presence of small insects should not cause false
Optical Detection. The optical detector uses a unique alarms.
measuring system. Unlike most other optical scatter
detectors the optical design does not use vertical chevrons Application Reference
to exclude ambient light, but uses concentric baffles. This
Detector Locations (see table on page 4). Locations
approach gives a better signal to noise ratio.
should be determined only after careful consideration of
This type of detector is very effective in detecting very the physical layout and contents of the area to be
low levels of visible smoke particulates (often at levels protected. Refer to NFPA 72, the National Fire Alarm
where they are not visible to the naked eye). Invisible Code. On smooth ceilings, smoke detector spacing of
smoke aerosol products, cannot however, be detected 30 ft (9.1 m) may be used as a guide.
using current optical smoke detectors as these aerosols do
Sensitivity Selection. The 601P-UL standard
not scatter or obscure light. This means that optical
sensitivity detector is recommended for most applications.
detectors favor the type of fire that we have described as
When a special application for reduced sensitivity
slow burning.
detector is required, the 601-P-UL-L should be
Although this is true, some smoldering materials such as considered. Consult your local Simplex product supplier
rubber will produce a predominantly black smoke, which for assistance in determining the proper selection.
has less scattering properties than white smoke and will
be detected later than an equivalent density of white
smoke. * Refer to page 2 for additional listing information. This product was not ULC or CSFM
listed, or approved by FM or MEA (NYC) as of document revision date. Additional listings
may be applicable; contact your local Simplex product supplier for the latest status. Listings
and approvals under Simplex Time Recorder Co. are the property of Tyco Safety Products
Westminster.

A0001-0004-1 3/2009
Product Selection

Nominal
Model Description Compatibility
Sensitivity
601P-UL 2.11 to 3.8%/ft
Optical Smoke Detector Compatible with 5B base; 5” (127 mm) diameter
601P-UL-L 3.0 to 3.8%/ft

Compatible Bases
Model Description Details Listing Reference
2-Wire Base with connections IDC and LED connections are screw
5B for Remote Alarm LED terminals for input/output wiring; 18 to UL listed under Thorn Security LTD
Indicator 14 AWG (1 mm2 to 1.5 mm2)

Detector Accessories
Model Description Details Listing Reference
6A-5B-UL 6” (152 mm) Base Adapter Increases the 5B surface area UL listed under Thorn Security LTD
Robust protective cage for Series 600
CW-5B Detector Protective Cage Not listed
detectors using the 5B base
Commissioning tool, shorts out base
SA600 Line Shorting Adapter contacts to enable cable resistance Listing not applicable, service tool only
checks to be carried out

Detector Status LED Indicators

LED Indication Status


Pulses approximately every 10 seconds Normal
Steady On Alarm

Dimensions and Reference Information

C5-B Detector Cage

2 A0001-0004-1 3/2009
Mounting Information

Specifications

Voltage 10.5 to 33 VDC from fire alarm control panel IDC


62 μA @ 10.5 VDC
Standby Current 65 μA @ 24 VDC
70 μA @ 33 VDC
Up to 68 mA maximum, exact current is determined by alarm current
Alarm Current
limiting of connected IDC
Storage Temperature Range -13° F to 176° F (-25° C to 80° C)
Operating Temperature Range 32° F to 100° F (0° C to 38° C)
Humidity Range Up to 95% non-condensing
Color White 019
Dimensions
In base 5” Dia. x 2-1/8” H (127 mm x 55 mm)
In base with base adapter 6” Dia x 2-9/16” H (152 mm x 66 mm)

3 A0001-0004-1 3/2009
Application of 600 Series Detectors

The table below is for guidelines only, specific situations are likely to require variations on the suggested detector types. Real
situations may require detector combinations to cover all likely risks.

A B C D E

Environment Benign moderately


Very clean Dusty and/or Unregulated
clean regulated Dirty - smoky
and dry humid temperature
temperature

Loading bay/
For Example Offices, light warehouse
Clean room Livestock pen Kitchen,
industrial, hospitals, with diesel
data mill, laundry, engine room,
residential, fork-lifts etc.
processing changing engine test
passenger Heavy
suite room beds
accommodation industrial ferry
Fire Loading Probable Risk (car deck)
Electronic Cable pyrolosis
equipment (toxic fumes)
601P-UL 601P-UL
electrical electrical arcs
1 601PH-UL 601PH-UL 601P-UL
switchgear electric (ignition source)
601I-ULC 601I-ULC
motors cable associated electrical
conduit dangers
Fabrics, clothes
soft furnishings Smouldering (difficult
paper, cardboard to locate - toxic
601PH-UL
2 plastic foams fumes) likelihood of 601P-UL 601P-UL
601P-UL
animal bedding flashover (back-
wood shavings draught)
etc.
Flaming fire (rapid
Flammable liquids
build-up of dense
paints, solvents 601I-ULC 601I-ULC
smoke) high 601H-RF-UL
3 flammable gasses 601PH-UL 601PH-UL 601H-RF-UL
temperature fumes 601I-ULC
unstable 601P-UL 601P-UL
associated explosion
chemicals
dangers
Foodstuffs general
Smoke and flame
organic waste 601PH-UL
initially fairly slow but 601PH-UL 601P-UL 601H-F-UL
4 animal fodder 601P-UL
high temperatures 601H-RF-UL 601H-RF-UL 631H-F-UL
wooden structures 601I-ULC
once established
solid fuels
Type of fire risk may
Plastic, chemicals
vary as can the type 601PH-UL 601PH-UL 601P-UL
machinery 601H-F-UL
5 of fire (may require a 601P-UL 601I-ULC 601I-ULC 601P-UL
building materials 631H-F-UL
mix of detection 601I-ULC 601H-RF-UL 601H-RF-UL
unknown contents
types)

Tyco is a registered trademark of Tyco International Services GmbH and is used under license. Simplex, and the Simplex logo are trademarks of Tyco International Ltd. and its
affiliates and are used under license. NFPA 72 and National Fire Alarm Code are trademarks of the National Fire Protection Association (NFPA).

Tyco Safety Products Westminster • Westminster, MA • 01441-0001 • USA A0001-0004-1 3/2009


www.tycosafetyproducts-usa-wm.com
© 2009 Tyco Safety Products Westminster. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Multi-Application Peripherals
UL, ULC, CSFM Listed; FM Approved; Non-Coded, Non-Addressable Manual Stations;
MEA (NYC) Acceptance* 2099 Series Single and Double Action Operation

Features
Manual fire alarm stations for general purpose
applications: PUSH
 Operation complies with ADA requirements
 Pull lever protrudes when alarmed
 Break-rod is supplied (use is optional)
 Screw terminals for wiring connections
 Tamper resistant reset key lock (keyed same as
Simplex® fire alarm cabinets) Single Action Station Double Action
Operation types include: Station (Push Type)
 Single action FIRE
FIRE ALARM LOCAL ALARM
 Double Action, Breakglass or Push Type
 Institutional Model, key operated only BREAK GLASS
 Optional NO GRIP Single Action Retrofit Kits are
available with a more easily operated pull lever for
applications where anticipated users may find the
standard station lever difficult to activate
 Optional Local Alarm cover
 Optional pre-signal and annunciator contacts
Double Action Local Fire Alarm
Multiple mounting options: Station (Breakglass) Cover Option
 Surface or semi-flush with standard boxes or matching
Simplex boxes FIRE ALARM
 Flush mount adapter kit
UL listed to Standard 38
KEY
Operation OPERATED
ONLY
Activation of the Simplex single action manual stations
requires a firm downward pull to activate the alarm switch.
Completing the action breaks an internal plastic break-rod
(visible below the pull lever, use is optional). The use of a Single Action Station with 4099-9805 NO GRIP
break-rod can be a deterrent to vandalism without interfering Institutional Cover Retrofit kit
with the minimum pull requirements needed for easy
activation. The pull lever latches into the alarm position and Operation (Continued)
remains extended out of the housing to provide a visible Institutional Stations activate by key operation only
indication. allowing access for manual alarms to be initiated by
Double Action Stations (Breakglass) require the authorized personnel. Operation requires key insertion
operator to strike the front mounted hammer to break the and opening of the station cover.
glass and expose the recessed pull lever. The pull lever then Single Action Station NO GRIP Retrofit Kit
operates as a single action station. 4099-9805. For applications such as California Building
Double Action Stations (Push Type) require that a Code, Title 24, which requires “Controls and operating
spring loaded interference plate (marked PUSH) be pushed mechanisms shall be operable with one hand and shall not
back to access the pull lever of the single action station. require tight grasping, pinching or twisting of the wrist”
the model 4099-9805 Retrofit kit provides a more easily
Station reset requires the use of a key to reset the manual operated pull lever compared to standard stations.
station lever and deactivate the alarm switch. (If the break-
* Refer to page 2 for models with MEA acceptance. These products have been
rod is used, it must be replaced.) approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the
California Health and Safety Code. See CSFM Listing 7150-0026:175 (Pull Boxes) and
Station testing is performed by physical activation of the 7150-0026:0224 (NO GRIP Retrofit Kit) for allowable values and/or conditions concerning
pull lever. Electrical testing can be also performed by material presented in this document. Additional listings may be applicable; contact your
local Simplex product supplier for the latest status. Listings and approvals under Simplex
unlocking the station housing to activate the alarm switch. Time Recorder Co. are the property of Tyco Fire Protection Products.

S2099-0007-18 12/2014
Operation (Continued) Application Reference (Continued)
Pre-Signal Option activates when the lever is pulled. The following summarizes the basic requirements.
General alarm initiation requires a key to activate a 1. Stations shall be located in the normal path of exit
keyswitch located behind the pull lever. and distributed in the protected area such that they
Station Reset requires the use of a key to reset the are unobstructed and readily accessible.
manual station lever and deactivate the alarm switch. 2. Mounting shall be with the operable part not less than
If the break-rod is used, it must be replaced. 42 in (1.07 m) and not more than 48 in (1.22 m)
Testing requires physical activation of the pull lever above floor level.
(except for institutional stations). 3. At least one station shall be provided on each floor.
Application Reference Additional stations shall be provided to obtain a
travel distance not more than 200 ft (61 m) to the
Refer to NFPA 72, the National Fire Alarm and Signaling nearest station from any point in the building.
Code, and all applicable local codes for complete
requirements for manual stations. 4. When manual station coverage appears limited in any
way, additional stations should be installed.
Product Selection
Single Action Models (General Alarm)
Annunciator Annunciator Local Alarm Institutional Mounting
Model MEA Pre-Signal
Contacts, N.O. Contacts, N.C. Cover Cover Notes
2099-9754 1
2099-9101
2099-9102 2
2099-9107
2099-9755 1
2099-9762 1
Double Action Models (General Alarm)
Annunciator Annunciator Mounting
Model MEA Break-Glass Push Pre-Signal
Contacts N.O. Contacts N.C. Notes
2099-9103 1
2099-9104
2099-9105 2
2099-9108
2099-9756 1
2099-9757
2099-9758 2
2099-9759
Accessories
Model Description
4099-9805 Retrofit Kit for field conversion of a single action station to a NO GRIP station; (reference Instructions 579-1007)
2099-9803 Replacement breakglass (standard, English)
2099-9804 Replacement break-rod
2099-9819 Flush adapter kit, black (refer to page 4)
2099-9820 Flush adapter kit, beige (refer to page 4)
2099-9822 Replacement retaining clip for breakglass
2099-9828 Institutional cover kit
2975-9178 Red, surface mount box, sheet metal, 5-3/16” H x 4” W x 2-3/16” D (127 mm x 102 mm x 56 mm)
2975-9022 Red, cast aluminum surface mount box, 5” H x 3-7/8” W x 2-3/16” D (127 mm x 98 mm x 56 mm)
Notes:
1. These models can be semi-flush mounted using a standard single gang 2-1/2” (64 mm) deep switch box. DO NOT RECESS BOX,
mount box flush or with 1/16” (2 mm) maximum protrusion. These models can also be surface mounted on a Wiremold box model
number V5744S, 4-5/8” H x 2-7/8” W x 2-1/4” D (117 mm x 73 mm x 57 mm).
2. For surface mount, these models require 2975-9178 or 2099-9022 boxes. For semi-flush mount, these models require a 4”
(102 mm) square box with a single gang cover plate (see diagram on page 3).

Additional Manual Station Reference


Non-Addressable Manual Stations Data Sheet Addressable Manual Stations Data Sheet
Releasing Stations S2099-0010 Standard Addressable S4099-0005
Stations for hazardous locations (Ring-Pull) S2099-0008 Addressable for Releasing S4099-0006
Metal housing and explosion-proof/weather-proof stations (T-Handle) S2099-0009 Wire Guard (addr./non-addr.) S2099-0004
2 S2099-0007-18 12/2014
Surface Mounting Reference

2975-9178 Box 2975-9022 Cast Box


Knockouts located
5-3/16" H x 4" W x 2-3/16" D 5" H x 3-7/8" W x 2-3/16" D
top and bottom
(132 mm x 102 mm x 56 mm) (127 mm x 98 mm x 56 mm)
(ordered separately) (ordered separately)

Simplex 2975-9178 box


(shown for reference)

Side View
FIR
FIRE ALARM
E Station cover
hinges open for
installation access

PULL DOWN
Access for 3/4" threaded
5" conduit located top and bottom
(127 mm)

1" (25.4 mm)

3-3/4" (95 mm)

Semi-Flush Mounting Reference

Single Gang Box Mount 4" Square Box Mount


Single gang box, 2-1/2" deep 4" (102 mm) square box, 2-1/8" (54 mm) minimum
(64 mm), RACO #500 or equal depth, RACO #231 or equal (supplied by others)
(supplied by others)

Mount flush or with


1/16" (2 mm)
maximum extension
4" Square box
DO NOT RECESS
with cover plate

Station
FIRE ALARM side view

Single gang cover plate, 3/4"


(19 mm) extension, RACO #773
or equal (supplied by others)
PULL DOWN
Single gang
box outline
Wall surface

Semi-Flush Mount Side View

3 S2099-0007-18 12/2014
Flush Mount Reference

Flush mount adapter kit


2099-9819, Black
2099-9820, Beige

Box must be recessed into wall


1" to 1-1/8" (25.4 mm to 29 mm)

8"
(203 mm)
Hole cutout must be a
minimum of 6" H by 5" W
6" (152 mm by 127 mm)
(152
mm)

4-11/16" (119 mm)


square box, 2-1/8"
(54 mm) minimum
Wall depth (by others)
4-3/4" (121 mm) surface

6-3/4" (171 mm)

Front View Side View

Specifications

Wire Connections Screw terminal for in/out wiring, for 18 to 14 AWG wire
UL Listed Temperature Range 32° to 120° F (0° to 49° C) intended for indoor operation
Humidity Range Up to 93% RH at 100° F (38° F)
Housing Color Red with white raised lettering
Material Housing and pull lever are high impact polycarbonate
Pull Lever Color White with red raised lettering
Housing Dimensions 5” H x 3-3/4” W x 1” D (127 mm x 95 mm x 25 mm)

TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm
and Signaling Code are trademarks of the National Fire Protection Association (NFPA).

Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S2099-0007-18 12/2014


www.simplex-fire.com
© 2014 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
4100ES Fire Control Panels
UL, ULC, CSFM Listed; FM, NYC 4100ES with IDNAC Addressable Fire Detection and Control Basic Panel Modules and
Fire Dept Approved* Accessories

Features during alarm, even during battery operation, allowing strobes to


operate at higher voltage with lower current and ensuring a consistent
current draw and voltage drop margin under both primary power and
secondary battery standby
• Efficiencies include lower strobe currents, wiring distances up to 2 to
3 times farther than with conventional notification, support for more
appliances per IDNAC SLC, and the ability to use smaller gauge wiring –
all providing installation and maintenance savings with high assurance
that appliances that operate during normal system testing will also
operate during worst case alarm conditions
• IDNAC SLCs are compatible with both TrueAlert ES and TrueAlert
addressable notification appliances, and remote 4009 IDNAC
Repeaters to extend power and wiring distance even farther

Optional modules and connections


• Fire Alarm Network Interfaces, city connections, and up to five (5)
RS-232 ports for printers and terminals
• Building Network Interface Card (BNIC) for Ethernet connectivity
options (see data sheet S4100-0061 )
• Side mounted DACT assembly requiring minimal panel space; DACT is
compatible with IP Communicators
• Emergency communications systems (ECS) equipment; 8 channel
digital audio or 2 channel analog audio
• Additional IDNet 2 communications SLCs, IDNet 2+2 Modules with
quad short circuit isolating output loops; additional power supplies,
alarm relays, and auxiliary relays
• LED/switch modules and panel mount printers; VESDA Air Aspiration
Systems interface, ASHRAE BACnet Interface, TCP/IP Bridges
• Battery brackets for seismic area protection
• 4100ES compatible legacy interface modules, including control of
Figure 1: 4100ES cabinets are available with conventional (non-addressable) NACS
one, two or three bays (2 bay cabinet shown)
• 8-point zone/relay module, each point is selectable as an IDC input or
Compatible with Simplex ES Net or 4120 Fire Alarm Networks relay output. Class A IDCs require 2 points (one out and one return).
Relays rated for 2 A @ 30 VDC (resistive). Configurable as normally
Master Controller (top) bay standard equipment
open or closed.
• 32-Bit Master Controller with color-coded operator interface and
raised switches for high confidence feedback 4100ES Listings reference:
• Dual configuration program CPU, convenient service port access, and • UL 864, Fire Detection and Control (UOJZ), and Smoke Control Service
capacity for up to 2500 addressable points (UUKL), Releasing Device Service (SYZV)
• CPU assembly includes 2 GB dedicated compact flash memory for on- • UL 1076. Proprietary Alarm Units - Burglar (APOU)
site system programming and information storage • UL 2017, Process Management Equipment (QVAX), Emergency Alarm
• An Enhanced Power Supply (EPS) and battery charger (9 A output) System Control Units (FSZI)
with on-board: IDNAC SLCs (signaling line circuit) for addressable • UL 1730, Smoke Detector Monitor (UULH)
appliance control, an IDNet 2 Module for addressable device control; • UL 2572, Mass Notification Systems (PGWM)
and programmable function auxiliary output
• CAN/ULC S527, Control Units for Fire Alarm Systems (UOJZ7), Releasing
• Also available with InfoAlarm Command Center expanded content user Device Service (SYZV7)
interface (see data sheet S4100-0045 )
• ULC/ORD-C1076 Proprietary Burglar Alarm Units and Systems (APOU7)
Standard addressable device interfaces include: • ULC/ORD-C100 Smoke Control System Equipment (UUKL7)
• 250 point addressable device IDNet 2 SLC that supports TrueAlarm
analog sensors and IDNet communications monitoring and control Software Feature Summary
devices with an electrically isolated output channel allowing use with
either shielded or unshielded, twisted or untwisted single pair wiring; CPU provides dual configuration programs
and providing dual short circuit isolating output loops • Two programs allow for optimal system protection and commissioning
• MINIPLEX Transponder and remote LCD and LED annunciator support efficiency with one active program and one reserve; downtime is
via RUI+ (isolated or un-isolated) communications port (see Standard reduced because the system stays running during download
CPU Bay Module Details)
PC based programmer features
Standard power supplies (EPS) provide enhanced power delivery • Convenient front panel accessed Ethernet port for quick and easy
IDNAC SLCs to addressable notification appliances download of site-specific programming
• With IDNAC SLCs, a constant 29 VDC source voltage is maintained • Modifications can be uploaded as well as downloaded for greater

This product has been listed by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7165-0026:0251 for allowable values
and/or conditions concerning material presented in this document. NYC Fire Dept COA #6151. At the time of publication only UL and ULC listings are applicable to ES Net network products. Additional
listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.

S4100-0100 Rev. 20 1/2019


4100ES with IDNAC Addressable Fire Detection and Control Basic Panel Modules and Accessories

service flexibility; AND, firmware enhancements are made via software


downloads to the on-board flash memory
• "Install Mode" allows grouping of multiple troubles for uninstalled
modules and devices into a single trouble condition (typical with future
phased expansion); with future equipment and devices grouped into
a single trouble, operators can more clearly identify events from the
commissioned and occupied areas
• Module level ground fault searching assists installation and service by
locating and isolating modules with grounded wiring
• "Recurring Trouble Filtering" allows the panel to recognize, process,
and log recurring intermittent troubles (such as external wiring ground
faults), but only sends a single outbound system trouble to avoid
nuisance communications
• WALKTEST silent or audible system test performs an automatic self-
resetting test cycle
• Support for TrueAlarm individual analog sensing and IDNAC
addressable notification with front panel information and selection
access

Introduction
4100ES series fire detection and control panels provide extensive
installation, operator, and service features with point and module
capacities suitable for a wide range of system applications. An on-
board Ethernet port provides fast external system communications
to expedite installation and service activity. Dedicated compact flash
memory archiving provides secure on-site system information storage of
electronic job configuration files.

Modular design
Figure 2: 4100ES Module Placement
A wide variety of functional modules are available to meet specific
Reference in 3-Bay Cabinet
system requirements. Selections allow panels to be configured for either
stand-alone or networked fire control operation.
Mechanical Description
ES panel compatibility with ES Net • Boxes can be close-nippled; each box provides convenient stud
markers for drywall thickness and nail-hole knockouts for quicker
Simplex ES Network (ES Net) is a next generation IP based fire network mounting
that uses industry standard network technology and infrastructure and
• Smooth box surfaces are provided for locally cutting conduit entrance
allows for simplified network upgrades, easy terminal connectivity and IP
holes exactly where required
file transfer between nodes; and advanced network diagnostics.
• Cabinet assembly design has been seismic tested and is certified to
ES fire alarm control panels can be upgraded to operate on an ES IBC and CBC standards as well as to ASCE 7 categories A through F,
network by adding an ES Net NIC to the panel. requires 4100-7912 option for additional legacy card stabilizer brackets
To upgrade an existing 4120 network to ES Net, all of the 4120 NIC cards and battery brackets as detailed on data sheet S2081-0019
on the network loop must be replaced with ES Net NICs. • The latching front panel assembly easily lifts off for internal access
Note: ES NICs and 4120 NICs cannot be mixed on the same network • Modules are power-limited (except as noted, such as relay modules)
loop. • The NEMA 1/IP30 box is ordered separately and available for early
installation
For more detailed information on ES Net, consult datasheet S4100-0076 ,
• Doors are available with tempered glass inserts or solid; boxes and
and talk to your local Simplex product supplier.
doors are available in platinum or red
• Boxes and door/retainer assemblies are ordered separately per system
Module Bay Description requirements; refer to data sheet S4100-0037
The Master Controller Bay (top) includes a standard multi-featured
enhanced power supply (EPS) with IDNet 2 Module, the master
controller board, two vertical expansion blocks, and operator interface
equipment.
The Expansion Bays include a Power Distribution Interface (PDI)
for connection of single or multiple block modules, and/or slot style
(motherboard/daughter card) modules.
The Battery Compartment (bottom) accepts two batteries, up to 50
Ah, to be mounted within the cabinet without interfering with module
space.

Page 2 S4100-0100 Rev. 20 1/2019


4100ES with IDNAC Addressable Fire Detection and Control Basic Panel Modules and Accessories

Operator Interface Detail Reference Table 1: TrueAlarm Addressable Sensor Reference


The following illustration identifies the primary functions of the operator
interface.

Figure 5: TrueAlarm Photo/


Figure 4: TrueAlarm
Heat Sensor in CO Base
Photo Sensor with Base

Programmable sensitivity
Programmable sensitivity of each sensor can be selected at the control
panel for different levels of smoke obscuration (shown directly in
percent) or for specific heat detection levels. To evaluate whether the
sensitivity should be revised, the peak value is stored in memory and can
be easily read (or downloaded as a report) and compared to the alarm
threshold directly in percent.
Figure 3: Operator interface
CO sensor bases
CO sensor bases combine an electrolytic CO sensing module with a
IDNet Addressable Device and IDNAC Addressable TrueAlarm analog sensor to provide a single multiple sensing assembly
Notification Appliance Control using one system address. The CO sensor can be enabled/disabled,
The 4100ES EPS power supply with IDNet 2 Module provides used in LED/Switch modes and custom control, and can be made public
addressable initiating device and IDNAC addressable notification for communication across a fire alarm Network. (refer to data sheet
appliance Signaling Line Circuits (SLCs) that supervise wiring connections S4098-0052 for details)
and the individual device/appliance communications status on their
SLC. With these 2-wire SLCs, initiation, monitoring, and control devices TrueAlarm heat sensors
such as manual fire alarm stations, TrueAlarm sensors, control relays, TrueAlarm heat sensors can be selected for fixed temperature detection,
and sprinkler waterflow switches; and notification appliances such with or without rate-of-rise detection. Utility temperature sensing is also
as strobes and horns can communicate their identity and status and available, typically to provide freeze warnings or alert to HVAC system
receive fire alarm system control. Additional interface modules include problems. Readings can selected as either Fahrenheit or Celsius.
circuit isolators, conventional IDC zone adapters, and interface to other
TrueSense Early Fire Detection
system circuits such as fans, dampers, and elevator controls.
Multi-sensor 4098-9754 provides photoelectric and heat sensor data
using a single 4100ES IDNet address. The panel evaluates smoke
IDNet Addressable Device Operation activity, heat activity, and their combination, to provide TrueSense
Each addressable device on an IDNet communication channel is early detection. For more details on this operation, refer to data sheet
continuously interrogated for status condition such as: normal, off- S4098-0024 .
normal, alarm, supervisory, or trouble. Both Class B and Class A
operation is available. Sophisticated poll and response communication
techniques ensure supervision integrity and allow for "T-tapping" of
Diagnostics and Default Device Type
the circuits for Class B operation. Devices with LEDs pulse the LED Sensor Status
to indicate receipt of a communications poll and can be turned on TrueAlarm operation allows the control panel to automatically indicate
steady from the panel. With addressable devices, the location and when a sensor is almost dirty, dirty, and excessively dirty. The NFPA 72
status of the connected device is monitored and logged, and displayed requirement for a test of the sensitivity range of the sensors is fulfilled
on the operator interface LCD and on remote system annunciators by the ability of TrueAlarm operation to maintain the sensitivity level of
with each device having its own 40 character custom label for precise each sensor. CO Sensors track their 10 year active life status providing
identification. indicators to assist with service planning. Indicators occur at: 1 year, 6
months, and end of life.
TrueAlarm Addressable Sensor Operation
Modular TrueAlarm sensors
Addressable initiating device communications include operation of
TrueAlarm smoke and temperature sensors. Smoke sensors transmit Modular TrueAlarm sensors use the same base and different sensor
an output value based on their smoke chamber condition and the CPU types (smoke or heat sensor) and can be easily interchanged to
maintains a current value, peak value, and an average value for each meet specific location requirements. This allows intentional sensor
sensor. Status is determined by comparing the current sensor value to substitution during building construction when conditions are
its average value. Tracking this average value as a continuously shifting temporarily dusty. Instead of covering smoke sensors (causing them to
reference point filters out environmental factors that cause shifts in be disabled), heat sensors may be installed without reprogramming the
sensitivity. control panel. The control panel will indicate an incorrect sensor type,
but the heat sensor will operate at a default sensitivity to provide heat
detection for building protection at that location.

IDNet Addressable Device Wiring Reference


IDNet Addressable Channel Capacity
The CPU bay standard power supply (EPS) provides an IDNet 2
Module providing a signaling line circuit (SLC) that supports up to 250
addressable monitor and control points intermixed on the same pair

Page 3 S4100-0100 Rev. 20 1/2019


4100ES with IDNAC Addressable Fire Detection and Control Basic Panel Modules and Accessories

of wires. IDNet 2 and IDNet 2+2 Module SLCs are isolated from other Virtual NACs Provide Control Convenience
system reference voltages to reduce common mode noise interaction For control convenience, IDNAC notification appliances can be grouped
with adjacent system wiring. Additional 250 address IDNet 2 or IDNet into Virtual NACS (VNACs) for group control, grouping that can be made
2+2 Modules are available. across SLCs, not defined by their wiring connection.
Table 2: IDNet 2 and IDNet 2+2 SLC Wiring Specifications Panel Control Convenience
Specification Rating Applicable operation settings for each appliance can be programmed
4000 ft (1219 m); 50 without having to replace appliances or remove them from the wall or
Maximum Distance 1 - 125
ohms ceiling. An appliance's VNAC notification zone can be easily changed
from Control Panel per
2500 feet (762 m); 35 through programming without having to add additional circuits, conduit,
Device Load 126 - 250
ohms and wiring. Audible and visible appliances for non-Fire Emergency
Up to 12,500 ft (3.8 Communications notification can be programmed to operate separately
Total Wire Length Allowed With “T” Taps for km); on the same pair of wires as the fire alarm notification appliances. The
Class B Wiring result is lower installation, retrofit, and overall life-cycle cost of ownership
0.60 µF compared with traditional conventional notification systems.
Maximum Capacitance Between IDNet 2
1 µF Installation, Retrofit, and Life-Cycle Cost Benefits
Channels
With each addressable appliance capable of being controlled separately
0.8 mA supv., 1 mA
on the same two-wire IDNAC SLC, installation time and expense for
alarm;
Loading per device both retrofit and new construction can be significantly reduced. When
2 mA per activated Class B wiring is used, wiring can be "T-tapped" allowing more savings
device LED in distance, wire, conduit (size and utilization), and overall installation
Shielded or unshielded, efficiency.
Wire Type and Connections twisted or untwisted Location Information, Diagnostics and Troubleshooting
wire*
Each addressable notification appliance has its own 40 character
Terminals for 18 to custom label to identify the location of the appliance and to aid in
Connections 12 AWG (0.82 mm2 to troubleshooting fault conditions. In conventional notification systems,
3.31 mm2) conventional appliances are not capable of communicating with the
IDNet 2 and IDNet 2+2 Module Compatibility: IDNet control panel. Fault reporting on a conventional system is limited to the
communicating devices and TrueAlarm sensors including QuickConnect circuit wiring and the entire area (zone) covered by appliances on the
and QuickConnect2 sensors notification appliance circuit (NAC) making it much more difficult and
Note: * Some applications may require shielded wiring. Review your costly to locate and correct the source of a problem. Using the TrueAlert
system with your local Simplex product supplier. magnet test allows each appliance to individually identify its candela
setting and address and to briefly operate if desired, and using the
IDNAC SLC Control of TrueAlert and TrueAlert ES TrueAlert ES Appliance Self-Test feature provides detailed performance
Addressable Notification verification per appliance.
Addressable notification appliance communications include operation of
TrueAlert and TrueAlert ES Visible only (V/O, strobe), Audible only (A/O, TrueAlert ES Appliance Self-Test Operation
horn), Audible/Visible (A/V, horn/strobe), and strobes of Speaker/Visible
(S/V) notification appliances. (S/V appliances require separate speaker On-Board Test Sensors
wiring.) IDNAC SLC addressable communications allow each horn and TrueAlert ES appliances are equipped with on-board sensors to detect
strobe to be individually controlled using a single two-wire circuit, strobe and/or horn output allowing efficient and unobtrusive Self-
confirms the wiring connections to the individual notification appliance's Testing. When Automatic Self-Test is initiated from the control panel,
electronic circuit, and confirms communications between each appliance each appliance within the selected VNAC group will briefly operate and
and the fire alarm control panel. Addressable communications increases then report its Self-Test status to the control panel, all within several
supervision integrity versus conventional notification systems by seconds. Silent Self-Test can be selected to test only visible appliance if
providing supervision beyond the circuit wiring to each individual desired. The control panel is in a trouble condition during testing and in
appliance and by constantly verifying the ability of each appliance to the event of an alarm, Self-Test is automatically terminated. Additionally,
communicate with the control panel. Automatic Self-Test can be scheduled to occur at a convenient time on a
regular basis (Requires version 2.03.01 or higher software).
Individual Appliance Status and Settings
The fire alarm control panel monitors and records each addressable Automatic Self-Test
notification appliance status, type of appliance, and its configured Automatic Self-Test results are communicated to the control panel with
appliance settings. A fault in any individual appliance automatically a time and date stamp and are stored in memory. Results are viewable
reports a trouble condition to the control panel. at the front panel display and printed reports can be generated from the
panel service port.

Individual Self-Test
Individual Self-Test is selected from the control panel when individual
appliances need to be observed to operate. Each appliance in the
selected VNAC group will turn on its LED until individually activated by
applying a magnet. After performing the individual test, the appliance
LED turns off to indicate completion. Results are recorded the same as
during the automatic test.

Figure 6: TrueAlert ES Addressable Appliance Reference

Page 4 S4100-0100 Rev. 20 1/2019


4100ES with IDNAC Addressable Fire Detection and Control Basic Panel Modules and Accessories

IDNAC SLC Hardware Reference 4100-6032, without disconnect switches) can be selected for
conventional dual circuit city connections
EPS Power Supplies
• Alarm Relay Module (4100-6033) provides three Form C relays that are
EPS Power Supplies provide three, 3 A IDNAC SLCs for control and used for Alarm, Trouble, and Supervisory, rated 2 A resistive @ 32 VDC
power to TrueAlert ES and TrueAlert addressable notification appliances.
Both power supplies incorporate an efficient switching design that EPS (Enhanced Power Supply) with IDNet 2 Module Details
provides a regulated output of 29 VDC, even during battery operation. • Rating is 9 A output with "Special Application" appliances
With 29 VDC minimum output at the panel, addressable notification • Outputs are power-limited, except for the battery charger
SLCs can support wiring distances 2 to 3 times farther than available
• Provides system power, battery charging, auxiliary power, earth
with conventional notification, or support more appliances per SLC, or
detection, on-board electrically isolated IDNet 2 Module with 250
work with smaller gauge wiring, or combinations of these benefits, all
point SLC, three on-board 3 A IDNAC SLCs, and provisions for either
resulting in installation and maintenance savings with high assurance
an optional City Connect Module or an optional Alarm/Supv/Tbl Relay
that appliances that operate during normal system testing will operate
Module
during worst case alarm conditions.
• IDNet 2 Module SLC Output provides Class B or Class A
communications for up to 250 addressable devices with dual short
IDNAC SLC Appliance Wiring Reference circuit isolating loop outputs
IDNAC SLC Capacity
Note: The "IDNet 2 Module" replaced the "IDNet 1+ Module" and the
Up to 127 addresses and up to 139 unit loads (appliances are typically term "EPS with IDNet 2 Module" replaces the term "EPS+"
one unit load, devices such as Isolators may require more than one load,
• Note: The “IDNet 2 Module” replaced the “IDNet 1+ Module” and the
refer to individual device data sheet for specific information)
term “EPS with IDNet 2 Module” replaces the term “EPS+”. DCAI (Dual
Table 3: IDNAC SLC Appliance Wiring Reference Class A IDNAC Isolator) Module creates two Class A outputs from
Specification Rating one IDNAC SLC Class B Input; up to two can be connected to one
IDNAC SLC, with up to 6 total per EPS; total Class A output loop current
Recommended wire type UTP, unshielded twisted pair
is limited to the 3 A rating of the IDNAC SLC
Maximum wire length allowed
with "T-Taps" for Class B wiring, 10,000 ft (3048 m) • Battery Charger is dual rate, temperature compensated, and
per SLC charges up to 50 Ah sealed lead-acid batteries mounted in the battery
compartment (33 Ah for single bay cabinets). UL listed for charging up
Maximum wire length per SLC
4000 ft (1219 m) to 110 Ah batteries mounted in an external cabinet (see data sheet
to any appliance
S2081-0012 for details)
Appliance Supervisory Current 1 unit load = 0.8 mA per appliance
2 • Battery and Charger Monitoring includes battery charger status
Terminals for 18 to 12 AWG (0.82 mm and low or depleted battery conditions; status information provided
Wiring connections 2
to 3.31 mm ) to the master controller includes analog values for: battery voltage,
Installation Instructions (see for charger voltage and current, actual system voltage and current, and
579-1015
more information) individual IDNAC SLC currents
• Low Battery Cutout is selectable for each EPS power supply,
Standard CPU Bay Module Details Canadian models are shipped selected, other models are shipped
unselected
Master Controller and Motherboard
• Mounts in Slot 2 of a two slot motherboard and provides one Class B 2 A Programmable Output
or Class A, RUI+ communications channel configurable for isolated or • Select for conventional non-synchronous NAC operation to provide
un-isolated operation supervised reverse polarity for sounder base power, Suppression
• Slot 1 of the motherboard is primarily for an optional network Release Peripheral (SRP) power, or other coded NAC operation
interface card or secondarily for the 4100-6038 dual RS-232 board requirements
communications • Select for Auxiliary (AUX) operation for sounder base power, 4-wire
• RUI+ and RUI communications controls up to 31 remote devices per detector power, or door holder; supervised AUX operation does not
master controller at up to 2500 ft (762 m) for single run, or 10,000 require an end-of-line relay to provide power-limited operation
ft (3048 m) total if wiring is Class B and T tapped; if more distance is 8-Point Zone/Relay Module Details
required, up to four total RUI channels are supported; add up to three
• Select as IDC or Relay; configure up to 8, Class B IDCs, or up to
4100-1291 RUI Expansion Modules (4100-1291 provides unisolated
4, Class A IDCs; or up to 8, Relay outputs rated 2 A resistive @ 30
RUI communications)
VDC (N.O. or N.C.); or combinations of IDCs and Relays; each zone is
• Compatible RUI+ and RUI remote equipment includes: MINIPLEX separately configurable as an IDC or Relay output
transponders, 4603-9101 LCD Annunciators, 4602-9101 Status
• IDC Support: each IDC supports up to 30, two-wire devices. Zone relay
Command Units (SCU), 4602-9102 Remote Command Units (RCU),
modules may be powered directly from the control unit power supply
4602 Series LED Annunciator Panels, 4100 Series 24 I/O and LED/
or through the optional 25 VDC regulator module where required for
Switch modules, (4602 series annunciators require un-isolated
2- wire detector compatibility (refer to 2-Wire Detector Compatibility
communications).
document 579-832 for additional details).
• Up to 4 RUI channels (combination of built-in RUI+ and optional RUI
• IDC EOL resistor values are selectable as: 3.3 kΩ, 2 kΩ, 2.2 kΩ, 3.4
modules) are supported
kΩ, 3.9 kΩ, 4.7 kΩ, 5.1 kΩ, 5.6 kΩ, 6.34/6.8 kΩ, and 3.6 kΩ + 1.1 kΩ; see
• Open slot space on the left of the CPU motherboard is available for instructions for more details
either another dual slot motherboard, or for one or two block modules
(refer to Figure 2)

EPS Mounted Optional Modules (select one)


• City Connect Module (4100-6031, with disconnect switches, or

Page 5 S4100-0100 Rev. 20 1/2019


4100ES with IDNAC Addressable Fire Detection and Control Basic Panel Modules and Accessories

Master Controller Selection Information


Table 4: Master Controller and Expansion Bay Selection
Model Model Type and Listing Description Current
Without IDNet devices:

Supervisory = 425 mA
4100-9311 120 VAC, 50/60 Hz Input UL Alarm = 735 mA

Note: Master Controller current does not


4100ES Master Controller Assembly with LCD subtract from 9 A output rating
display, operator interface and RUI+ isolated Without IDNet devices:
or un-insolated output communications
interface; 9 A EPS (Enhanced Power Supply) Supervisory = 425 mA
120 VAC, 50/60 with battery charger, electrically isolated 250
4100-9312 English ULC
Hz Canadian point IDNet 2 Module, three Class B IDNAC Alarm = 735 mA
SLCs, one 2 A output configurable for Auxiliary
Power or Simple NAC operation and expansion Note: Master Controller current does not
slot for City Circuit or Alarm/Supv/Tbl Relay subtract from 9 A output rating
option. Without IDNet devices:

Supervisory = 425 mA
120 VAC, 50/60
4100-9313 French ULC
Hz Canadian Alarm = 735 mA

Note: Master Controller current does not


subtract from 9 A output rating
4100ES Master Controller Assembly with LCD
display, operator interface and RUI+ isolated
or un-insolated output communications
interface; 9 A EPS (Enhanced Power Supply) Without IDNet devices:
with battery charger, electrically isolated 250
4100-9511 220-240 VAC, 50/60 Hz Input UL Supervisory = 425 mA
point IDNet 2 Module, three Class B IDNAC
SLCs, one 2 A output configurable for Auxiliary
Alarm = 735 mA
Power or Simple NAC operation and expansion
slot for City Circuit or Alarm/Supv/Tbl Relay Note: Master Controller current does not
option subtract from 9 A output rating
4100ES Master Controller Assembly ; same as
4100-9331 120 VAC, 50/60 Hz input UL above models except without LCD Display and
Operator Interface
Without IDNet devices:

4100ES Master Controller Assembly ; same as Supervisory = 425 mA


120 VAC, 50/60 Hz input,
4100-9332 ULC above models except without LCD Display and Alarm = 735 mA
Canadian, English
Operator Interface
Note: Master Controller current does not
subtract from 9 A output rating
4100-2300 Expansion Bay Assembly; order for each required expansion bay
4100-2303 Slot Module Stabilizer Bracket, used when expansion bays have style modules
Table 5: Communication Modules
Model Description Size Supv. Alarm
Network Access Dial-in Service Modem, mounts to 4100-6078 or 4100-6061 Network
4100-6055 N.A. 60 mA 60 mA
Interface Card, requires telephone line connection
4100-1291 Un-isolated Remote Unit Interface Module (RUI); up to 3 maximum per control panel 1 Slot 85 mA 85 mA
4100-6031 Select one per EPS. City Circuit, with disconnect switches N.A. 20 mA 36 mA
4100-6032 Maximum one City City Circuit, w/o disconnect switches N.A. 20 mA 36 mA
Circuit module per Alarm/Supv/Tbl Relay, 3 Form C relays, 2 A @
4100-6033 N.A. 15 mA 37 mA
panel 32 VDC
4100-6046 Dual Port RS-232 standard interface (single block) 3maximum 1Block 60mA 60mA
RS-232
4100-6038 Dual Port RS-232 with 2120 interface (slot module) Modules per 1Slot 132 mA 132 mA
panel
4100-6079 SafeLINC Internet Interface (refer to data sheet S4100-0062 for details) 2 Blocks 145 mA 145 mA
4190-6104 TrueInsight Remote Monitoring Module (refer to data sheet S4100-0063 for details) Side Mt. 62 mA 73 mA
4100-6101 Physical Bridge, Class B, includes 1 modem module and 2 wired modules 1Slot 210 mA 210 mA

Page 6 S4100-0100 Rev. 20 1/2019


4100ES with IDNAC Addressable Fire Detection and Control Basic Panel Modules and Accessories

Table 5: Communication Modules


Model Description Size Supv. Alarm
4100-6102 Physical Bridge, Class X, includes 2 modem and 2 wired modules 2Slots 300 mA 300 mA
4100-6048 VESDA Aspiration System Interface (refer to data sheet S4100-0026 for details) 1Slot 132 mA 132 mA
DACT, Point or Event Reporting; 1 shipped unless 4100-7908 is selected; 2 max. per
4100-6080 SideMt. 30 mA 40 mA
system; includes 2, 2080-9047 cables, 14 ft (4.3 m) long, RJ45 plug and spade lugs

Module Selection Information


Table 6: Additional Enhanced Power Supplies, Expansion Power Supply, and Accessories
Model Voltage Listing Description Size Supv. Alarm
4100-5311 120 VAC UL & ULC Enhanced Power Supply (EPS) with IDNet 2 Module; 9 225 mA 490 mA
A Enhanced Power Supply with battery charger, electrically
isolated 250 point IDNet 2 Module, three Class B IDNAC 4 Blocks add IDNet
SLCs, one 2 A output configurable for Auxiliary Power or device
4100-5313 220-240 VAC UL & ULC Right Side
Simple NAC operation, and expansion slot for City Circuit or currents
Alarm/Supv/Tbl Relay option; 120 VAC model has selectable separately
low battery cutout
4100-5325 120 VAC UL & ULC Expansion EPS; 9 A Expansion EPS, functionally identical 4 Blocks
to the Enhanced Power Supply except without the IDNet 2 125 mA 220 mA
4100-5327 220-240 VAC UL & ULC Right Side
Module
4100-5101 120 VAC UL & ULC Expansion Power Supply (XPS); 9 A output, 3 built-in
Class A/B conventional (non-addressable) 3 A NACs that
2 Blocks 50 mA 50 mA
4100-5102 220-240 VAC UL & ULC can also be selected as 2 A auxiliary power output, 2 A
separate auxiliary power output; without battery charger
Expansion Power Supply (XPS); 9 A output, 3 built-in
Class A/B conventional (non-addressable) 3 A NACs that
120 VAC,
4100-5103 ULC can also be selected as 2 A auxiliary power output, 2 A 2 Blocks 50 mA 50 mA
Canadian
separate auxiliary power output; without battery charger;
Canadian model has low battery cutout
4100-5115 NAC Expansion Module, 3 NACs, Class A/B, mounts on XPS only N.A. 25 mA 25 mA
Dual Class A IDNAC Isolator (DCAI), converts a single Class B IDNAC SLC input to
two Class A or two Class B SLC outputs; provides short circuit isolation between each
Class A or B output circuit; connect up to two DCAI Modules per IDNAC SLC input up
to a maximum of 6 DCAI Modules per EPS; each isolated output SLC used requires one
4100-6103 IDNAC address; the total current remains controlled by the Class B input source SLC 1 Block 8.3 mA 18.5 mA
at 3 A maximum; each isolated loop supports up to 30 device addresses (note: up to
30 additional device addresses may be installed between each 4905-9929 TrueAlert
Addressable Isolator+ Module, not to exceed the maximum address and unit loading
specifications for the IDNAC channel)
1.5 A
4100-5152 12 VDC Power Option, 2 A maximum 1 Block
maximum
included w/
4100-0156 8 VDC Converter, required for multiple Physical Bridge Modules, 3 A maximum 1 Block
loads
3 A maximum
with 2.5A
Voltage Regulator Module, 22.8 to 26.4 VDC (25VDC nominal); isolated and resettable
4100-5130 1 Block load, 4.9A
output; includes earth detection circuit and trouble relay for status monitoring
maximum
with 4 A load
4100-0636 Box Interconnection Harness Kit (non-audio); order one for each close-nippled cabinet
4100-0638 4100 Slot Module Additional 24 VDC Harness; needed when 4100 Slot module requirements exceed 2 A from EPS

Note: for additional non-addressable Power Supplies, refer to data sheet S4100-0031.
Table 7: 8 Zone Initiating Device Circuits
Model Type Supv. Alarm
4100-5005 Class B 75 mA 195 mA
4100-5015 Class A 75 mA 195 mA

Note: Modules are for use with all 4100U systems and 4100ES systems version 3.03.05 or earlier. IDC Modules are 1 slot size.

Page 7 S4100-0100 Rev. 20 1/2019


4100ES with IDNAC Addressable Fire Detection and Control Basic Panel Modules and Accessories

Table 8: 8-Point Zone/Relay Card (requires 4100ES Version 3.04.01 or later)


Model Description Size Supv. Alarm
8 point zone/relay 4x5” flat module. Mounts in any open block in a master
controller or expansion bay. Alarm current shown is for 8 Class B IDCs using 3.3K
4100-5013 end-of-line-resistors with 4 in alarm and 4 in standby. Standby current shown 1 block 83 mA 351 mA
is for all 8 IDCs in standby. Refer to 579-1236 Zone/Relay Module Installation
Instructions for additional information.
25V regulator harness for 8 point zone/relay module. One required for each 8
point zone/relay module to be powered by the 4100-5130 25V regulator module. A
4100-6305 N/A N/A N/A
maximum of (5) 8 point zone/relay modules may be powered from the 4100-5130
per bay.
Table 9: System Option for Seismic Compliance
Model Description
4100-7912 System option for Seismic compliance, provides additional stabilizer brackets required for legacy style cards
Table 10: Addressable Interface Modules
Model Description Supv. Alarm
IDNet 2 Module, 250 point capacity; electrically no devices 50 mA 60 mA
isolated output with two short circuit isolating Class 50 devices 90 mA 150 mA
4100-3109* B or Class A output loops, 1 block; standard on EPS 125 devices 150 mA 225 mA
with IDNet 2 Module; alarm currents for 50 and above
devices includes 20 device LEDs in alarm 250 devices 250 mA 350 mA
IDNet 2+2 Module, 250 point capacity; electrically no devices 50 mA 60 mA
isolated output with four short circuit isolating Class B 50 devices 90 mA 150 mA
or Class A output loops, 1 block; mounts in expansion 125 devices 150 mA 225 mA
4100-3110* bay or available master controller bay module locations
only, not applicable for EPS mounting; alarm currents
for 50 and above devices includes 20 device LEDs in 250 devices 250 mA 350 mA
alarm
IDNet Short Circuit Isolating Loop Output Module; mount up to two on a 4100-3109 module; for use with 4100-3109
4100-3111* modules in expansion bays or available master controller bay module locations only; not applicable for mounting on a
4100-3109 mounted on an EPS; this option is for aftermarket field installation only
Four Loop IDNet Master Controller; for the Master Controller Assemblies listed in Master Controller Selection
Information, this option moves the standard IDNet 2 Module from the Master Controller EPS to an available block space in
4100-3112 the master controller bay and adds 2, 4100-3111 IDNet Loop Output Modules.

Requires selection of Factory Built Option 4100-7905; current requirements remain the same.
Note: *

Loading per IDNet device (no LEDs on) = 0.8 mA supervisory and 1 mA alarm.

Total of initiating SLCs per CPU, including VESDA Interface, is 30.

Each IDNet 2 and IDNet 2+2 Short Circuit Isolating Loop Output can be individually controlled for system diagnostics and can be assigned a public
point for Fire Alarm Network annunciation.
Table 11: Relay Modules; Non power-limited (for mounting in expansion bay only)
Resistive Inductive
Model Description Size Supv. Alarm
Ratings Ratings
4100-3202 4 DPDT w/feedback 10 A @ 250 VAC 10 A @ 250 VAC 2 Slots 15 mA 175 mA
2 A @ 30 VDC/ 1/2 A @ 30
4100-3204 4 DPDT w/feedback 1 Block 15 mA 60 mA
VAC VDC/120 VAC
3 A @ 30 1-1/2 A @ 30
4100-3206 8 SPDT 1 Block 15 mA 190 mA
VDC/120 VAC VDC/120 VAC
Current Calculation Notes:

To determine total supervisory current, add currents of modules in panel to base system value and all external loads powered by panel power
supplies.

To determine total alarm current, add currents of modules in panel to base system alarm current and add all panel SLC and NAC loads and all
external loads powered from panel power supplies.
Table 12: End User Programming Software (requires 4100-8802)
Model Description
4100-8802 Programming Software (select)

Page 8 S4100-0100 Rev. 20 1/2019


4100ES with IDNAC Addressable Fire Detection and Control Basic Panel Modules and Accessories

Table 13: End User Programming Software Selection (select maximum of one each from below)
Model Description
4100-0292 Custom Labels Editing; allows editing of 40 Character Custom Labels for non-system user points
Access Level/Passcode Editing; allows user to re-assign Access Levels and Passcodes for each display function;
4100-0296 Acknowledge, Alarm Silence, System Reset, Point Enable/Disable, WALKTEST Enable/Disable, Clear History Logs, Change
Time & Date, etc.
4100-0295 Port Vectoring Setup and Control; Allows vectoring of events to PC Annunciator, Printers, LCD Annunciators, etc.
WALKTEST Configuration Setup and Control; Allows user to create or edit WALKTEST groups used to test system
initiating devices and signals by a single person, these groups allow an inspector to conduct a one-person WALKTEST in
4100-0298
a specific area of a building (or different buildings), and limit the activation of the building signals to only the intended
area; up to 8 WALKTEST groups are supported
Table 14: Miscellaneous Accessories
Model Description
4100-1279 Single blank 2” display cover; 4100-2302 provides a single plate for a full bay
4100-9835 Termination and Address Label Kit (for module marking); provides additional labels for field installed modules
4100-9856 4100ES Canadian French Appliqué Kit; Simplex, 4100ES, Contrôle Incendie
4100-9868 Special Purpose Appliqué Kit: Simplex, Elevator Recall Control and Supervisory Control Unit, 4100ES
4100-9869 Special Purpose Appliqué Kit: Simplex, Sprinkler Waterflow and Supervisory Station, 4100ES
4100-6029 Smoke Management Application Guide; required for UUKL listing
Tamper Switch, one per cabinet assembly if required; monitors solid door for panels with solid door; monitors the
4100-6034
internal retainer panel for panels with glass door (not the glass door); has a built-in addressable IDNet IAM
Series resistor for WSO, IDCs (N.O. water flow and tamper on same circuit, wires after water flow and before tamper)
2081-9031
470 Ω, 1 W, encapsulated, two 18 AWG leads (0.82 mm2 ), 2-1/2” L x 1-3/8” W x 1” H (64 mm x 35 mm x 25 mm)

Network Interface and Network Media Card Product Selection


4100ES fire alarm control units are compatible with Simplex ES Net network or 4120 network fire alarm products.
• Refer to datasheet S4100-0076 for additional information on compatible ES Net fire alarm products.
• Refer to datasheet S4100-0056 for additional information on compatible 4120 network fire alarm products.

Page 9 S4100-0100 Rev. 20 1/2019


4100ES with IDNAC Addressable Fire Detection and Control Basic Panel Modules and Accessories

General Specifications
Table 15: General Specifications
Specification Description
120 VAC Models 4.6 A maximum @ 102 to 132 VAC, 50/60 Hz
2.3 A maximum @ 204 to 264 VAC, 50/60 Hz; separate taps for
Enhanced Power Supplies (EPS) 220-240 VAC Models
220/230/240 VAC
Input Power Battery Input Rating 12 A maximum @ 24 VDC (during battery operation)
120 VAC Models 4 A maximum @ 102 to 132 VAC, 60 Hz
Expansion Power Supplies (XPS) 2 A maximum @ 204 to 264 VAC, 50/60 Hz; separate taps for
220-240 VAC Models
220/230/240 VAC
9 A output for "Special Application" appliances

Note:
Total Power Supply
Output Rating The 9 A output rating of the EPS was determined such that optional
module currents, and external device and appliance currents can be Output switches to
Power Supply Output directly added together, not to exceed 9 A total. battery backup during
Ratings for EPS 3 A, regulated 29 VDC during Alarm, 127 addresses, 139 unit loads; mains AC failure or
IDNAC SLC Ratings
DC-DC converter circuit is >92% efficient over operating range brownout conditions
Output terminals are rated for 18 to 12 AWG with duplicate output
terminals rated for two wires each, allowing up to four (4) Class B
IDNAC SLC Wiring
branch circuit T-taps to be made in the cabinet; additional T-taps
may be made in external wiring junction cabinets or boxes
Auxiliary Power Tap 2 A maximum, 24 VDC nominal (19.5 to 31.1 VDC)
Simplex TrueAlert ES and TrueAlert addressable notification appliances; contact your Simplex
Compatible Special Application Appliances
product representative for compatible appliances
UL listed for battery charging of 6.2 Ah up to 115 Ah (batteries larger than 50 Ah require a
Battery Charger Ratings Battery capacity range
remote battery cabinet); ULC listed for charging up to 50 Ah batteries
for EPS (sealed lead-
Charger characteristics and Temperature compensated, dual rate, recharges depleted batteries within 48 hours per UL
acid batteries)
performance Standard 864; to 70% capacity in 12 hours per ULC Standard S527
Including module currents and auxiliary power outputs; NAC outputs
Power Supply Output Total Power Supply Output are rated 9 A output for "Special Application" non-addressable
Output switches to
Ratings for XPS Rating appliances; 4 A output for "Regulated 24 DC" power (see details
(nominal 28 VDC on below); 6 A output with each NAC selected as auxiliary power output battery backup during
mains AC failure or
AC; 24 VDC on battery Auxiliary Power Tap 2 A maximum
brownout conditions
backup) NACs Programmed for 2 A maximum per NAC; 5 A Rated 19.1 to 31.1 VDC
Auxiliary Power maximum total
Special Application Simplex horns, strobes, and combination horn/strobes and speaker/strobes (contact your Simplex product representative
Appliances for compatible appliances)
Regulated 24 DC
Power for other UL listed appliances; use associated external synchronization modules where required
Appliances
Operating Temperature 32° to 120°F (0° to 49° C)
Environmental
Operating Humidity Up to 93% RH, non-condensing @ 90° F (32° C) maximum

Expansion Bay Module Loading Reference

Figure 7: Expansion Bay Reference

Size Definitions:
• 1 Block = 4" W x 5.65" H (102 mm x 144 mm); (often called 4 x 5 modules)
• 1 Slot = 2" W x 11.3" H (51 mm x 287 mm), typically a motherboard with daughter card

Page 10 S4100-0100 Rev. 20 1/2019


4100ES with IDNAC Addressable Fire Detection and Control Basic Panel Modules and Accessories

Operator Interface
Convenient Status Information
With the locking door closed, the glass window allows viewing of the display, status LEDs, and available operator switches. Features include a two-line
by 40-character, wide viewing angle (super-twist) LCD with status LEDs and switches as shown in Figure 8.
LED indicators describe the general category of activity being displayed with the LCD providing more detail. For the authorized user, unlocking the door
provides access to the control switches and allows further inquiry by scrolling the display for additional detail.

Operator Interface Features


• Convenient and extensive operator information is provided using a logical, menu-driven display
• Multiple automatic and manual diagnostics for maintenance reduction
• Alarm and Trouble History Logs (up to 1000 entries for each, 2000 total events) are available for viewing from the LCD, or capable of being printed to
a connected printer, or downloaded to a service computer
• Convenient PC programmer label editing
• Password access control

Figure 8: Operator interface features

Page 11 S4100-0100 Rev. 20 1/2019


4100ES with IDNAC Addressable Fire Detection and Control Basic Panel Modules and Accessories

Mounting and CPU Bay Module Reference

Figure 9: Mounting and CPU Bay Module Reference (* indicates supplied modules)

Note:

1. Side View dimensions are shown with minimal cabinet and door protrusion from the exterior wall. For 6 inch stud construction with minimum pro-
trusion shown, the door will open 90 degrees. To allow the door to open 180 degrees, the exposed cabinet dimension from the exterior wall must be a
minimum of 3 inches (76 mm) for both 4 inch and 6 inch stud construction.

2. A system ground must be provided for Earth Detection and transient protection devices. This connection shall be made to an approved, dedicated
Earth connection per NFPA 70, Article 250, and NFPA 780.
Table 16: Reference Notes
Note PID
Note 1 4100-6052
Note 2 4100-6101
Note 3 4100-6102
Note 4 4100-6048
Note 5 4100-5005 or 4100-5015
Note 6
4100-6038
Note 7
Note 8 4100-6031
Note 9 4100-6032
Note 10 4100-6033

Page 12 S4100-0100 Rev. 20 1/2019


4100ES with IDNAC Addressable Fire Detection and Control Basic Panel Modules and Accessories

TrueAlert ES Appliance Self-Test Last Test ResultsReport Example

Figure 10: TrueAlert ES Appliance Self-Test Last Test Results Report Example


Results Description
• NORMAL = Works correctly
• NO OUT = No Output, no light or sound was detected
• NOT TST = No result. Either the appliance did not return a result before the test ended or the test was conducted as silent (strobes only) and audible
appliance was not activated
• N/A = Not applicable (no strobe, on audible only, etc.)
• UNSUPP = Appliance not compatible with Self-Test (TrueAlert addressable appliance not TrueAlert ES addressable appliance)

Note: Additional TrueAlert ES Self-Test information is detailed in ES Operating Instructions 579-197 shipped with the panel.

TrueAlert ES Appliance Self-Test All Test ResultsReport Example

Figure 11: TrueAlert ES Appliance Self-Test All Test Results Report Example

TrueAlert ES Appliance Self-Test Individual Appliance Report Example

Figure 12: TrueAlert ES Appliance Self-Test Individual Appliance Report Example

Page 13 S4100-0100 Rev. 20 1/2019


4100ES with IDNAC Addressable Fire Detection and Control Basic Panel Modules and Accessories

Additional Technical and Datasheet Reference


Table 17: Additional Technical Reference
Description Document
ES Installation Instructions 574-848
ES Operating Instructions 579-197
DCAI Module Installation Instructions 579-1029
IDNet 2 and 2+2 Module Installation Instructions 579-1169
EPS Installation Instructions 579-1015
Table 18: Additional 4100ES datasheet reference
Subject Data Sheet
Serial DACT (SDACT) for 4100ES, 4010ES, 4007ES S2080-0009
Battery and Battery Cabinet Reference for 4100ES S2081-0006
110 Ah Batteries and Cabinets for 4100ES S2081-0012
Seismic Battery Brackets Reference S2081-0019
4009 IDNet NAC Extender S4009-0002
4009 IDNAC Repeater S4009-0004
External 110 Ah Battery Charger for 4100ES, 4010ES S4081-0002
Graphic I/O Modules for 4100ES, 4010ES, 4007ES S4100-0005
Interface to VESDA Air Aspiration Detection Systems S4100-0026
4100ES Basic Panels with SPS Power Supplies S4100-0031
4100ES LED/Switch Modules & Printer S4100-0032
Master Clock Interface S4100-0033
4100ES Emergency Voice/Alarm Equipment S4100-0034
MINIPLEX Transponders with SPS Power Supplies S4100-0035
NDU with SPS Power Supplies for 4120 Network S4100-0036
4100ES Enclosures S4100-0037
4100ES Remote Annunciator Panels S4100-0038
4100ES Extinguishing Release Applications S4100-0040
TFX Interface Module S4100-0042
InfoAlarm Command Center with SPS Power Supplies S4100-0045
2120 BMUX Module S4100-0048
Multiple Signal Fiber Optic Modems for 4120 Networks S4100-0049
BACpac Ethernet Module S4100-0051
4120 Network Products and Specifications S4100-0056
Building Network Interface Card (BNIC) S4100-0061
SafeLINC Internet Interface S4100-0062
TrueInsight Remote Gateway S4100-0063
ES Net Network Products and Specifications S4100-0076
NDU with SPS Power Supplies for ES Net S4100-0077
InfoAlarm Command Center with EPS Power Supplies S4100-0101
NDU with EPS Power Supplies for 4120 Network S4100-0102
MINIPLEX Transponders with EPS Power Supplies S4100-0103
NDU with EPS Power Supplies for ES Net S4100-0104
120 VAC Remote Printer S4190-0011
PC Annunciator S4190-0013
TrueSite Workstation S4190-0016
Network System Integrator (NSI) for 4120 Networks S4190-0017
TrueSite Incident Commander S4190-0020
SCU/RCU Annunciators S4602-0001
LCD Annunciator for 4100ES S4603-0001

© 2019 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without
notice. Additional listings may be applicable, contact your local Simplex® product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co.
Simplex, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code are
registered trademarks of the National Fire Protection Association (NFPA).
S4100-0100 Rev. 20 1/2019
TrueAlert® Notification Appliances
UL, ULC Listed; FM, CSFM, Visible Notification Appliances
and MEA (NYC) Approved* for Free-Run Operation

Features
24 VDC powered xenon flashtube visible
notification appliance (strobe) for wall mounting:
x UL listed to Standard 1971
x Models are available with 15, 75, or 110 candela
x Strobe candela rating is clearly indicated on reflector
x Compatible with ADA requirements (refer to important
installation information on page 2)
x Diode polarized input for connection to reverse polarity,
supervised notification appliance
circuit (NAC)
x In/out wiring is accessible from front of housing
providing easy access for installation, inspection, and
testing
x Regulated circuit design ensures consistent output
x Rugged, high impact, flame retardant thermoplastic
housing available in red or white
x Covers are available separately to convert housing color
TrueAlert notification appliance design provides
flexible, easy, and convenient semi-flush or
surface wall mounting:
x Easily mounts to single gang, double gang, or 4-inch
square outlet box TrueAlert Non-Addressable Strobes are Available in Red
with White Lettering and White with Red Lettering
x In/out wiring terminals for 18 AWG to
12 AWG wire
x Rear of housing does not extend into box Description
Optional adapters and wire guard: TrueAlert non-addressable free-run strobes
x Mounting adapters are available to cover surface provide quick and convenient installation using a flexible
mounted electrical boxes and to adapt to Simplex® mounting design. The strobe housing is a rugged,
2975-9145 boxes one-piece assembly (including lens) that mounts to single
gang, double gang, or 4” square standard electrical box.
x UL listed red wire guard is available for semi-flush or Wiring terminals are accessible from the front of the
surface mounting housing, providing easy access for installation, inspection,
and testing. The cover can be quickly removed (a tool is
required) and when in place, the entire assembly is impact
and vandal resistant. Separate covers are available for
color conversion.
Strobe Selection
Proper selection of visible notification is dependent on
* This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing occupancy, location, local codes, and proper applications
7125-0026:235 for allowable values and/or conditions concerning material presented in of: the National Fire Alarm Code (NFPA 72), ANSI
this document. It is subject to re-examination, revision, and possible cancellation.
Accepted for use – City of New York Department of Buildings – MEA35-93E. Additional A117.1; the appropriate model building code: BOCA,
listings may be applicable; contact your local Simplex product supplier for the latest ICBO, or SBCCI, and the application guidelines of the
status. Listings and approvals under Simplex Time Recorder Co. are the property of
Tyco Safety Products Westminster.
Americans with Disabilities Act (ADA).

S4904-0005-5 9/2004
Product Selection
Free-Run Visible Notification Appliances (Strobes)
Strobe Output Rating
Model Number Housing Color
15 cd 75 cd 110 cd
4904-9168
4904-9169 Red with white “FIRE” lettering
4904-9170
4904-9171
4904-9172 White with red “FIRE” lettering
4904-9173

Adapters
Model Description Dimensions

4905-9937 Surface mount red adapter skirt 5-3/8” H x 5-1/4” W x 1-5/8” D


Use to cover 1-1/2” deep (136 mm x 133 mm x 41 mm)
surface mounted boxes Total depth with strobe =
4905-9940 Surface mount white adapter skirt
4-3/8” (111 mm)
Adapter plate, red, for mounting to Simplex 2975-9145 Box 8-5/16” x 5-3/4” x 0.060” Thick
4905-9931
(typically for retrofit, may be mounted vertical or horizontal) (211 mm x 146 mm x 1.5 mm)
7-7/8" x 5-1/8" x 2-3/4" Deep
2975-9145 Red mounting box, requires Adapter Plate 4905-9931
(200 mm x 130 mm x 70 mm)

Covers and Guard


Model Description Dimensions
4905-9992 Red cover with white “FIRE” lettering 5-1/8” H x 5” W x 1-1/2” D
4905-9993 White cover with red “FIRE” lettering (130 mm x 127 mm x 38 mm)
Wire guard with mounting plate, red, compatible with semi-flush or 6-1/16” H x 6-1/16” W x 3-1/8” D
4905-9961*
surface mounted boxes (154 mm x 154 mm x 79 mm)
* UL listed by Space Age Electronics Inc.

Semi-Flush or Surface Strobe Mounting

Mounting is compatible with


single gang, double gang, and
4" (102 mm) square boxes,
IMPORTANT! WALL MOUNT
1-1/2" (38 mm) deep, by others
INSTALLATION HEIGHT REFERENCE

Bottom of lens
is either even
with, or slightly Electrical
Wiring access hole above bottom box outline
2 of compatible
1
boxes
Wiring terminals

Mounting Holes:
4" square (4) NFPA 72 requires 80" (2.03 m)
Single gang (2) that the entire lens minimum
Double gang (3) be not less than
a
80" and not greater
than 96" above the
finished floor
Transparent housing
and lens assembly

Removable cover
(tool required)

2 S4904-0005-5 9/2004
Specifications

General Specifications
UL Listed Range Regulated 24 VDC; see Note 1 below
Rated Voltage Range
ULC Listed Range 20 VDC to 30 VDC per ULC S526-M87
Housing Dimensions (including lens) 5-1/8” H x 5” W x 2-3/4” D (130 mm x 127 mm x 70 mm)
Temperature Range 32° to 122° F (0° to 50° C)
Humidity Range 10% to 93%, non-condensing at 100° F (38° C)
Terminal blocks for 18 AWG to 12 AWG (0.82 mm2 to 3.31 mm2); two
Connections
wires per terminal for in/out wiring
Strobe Specifications
Flash Rate 1 Hz
Maximum RMS Current Rating per Strobe Output 15 cd 75 cd 110 cd
(see Note 2 below) 76 mA 192 mA 227 mA
Reference Currents 18 VDC 68 mA 171 mA 202 mA
at other voltages 24 VDC 51 mA 128 mA 151 mA

NOTES:
1. “Regulated 24 VDC” refers to the voltage range of 16 to 33 VDC per UL Standard 1971, Signaling Devices for the
Hearing Impaired, changes effective May 1, 2004. This voltage range is the absolute operating range. Operation outside
of this range may cause permanent damage to the appliance. Please note that 16 VDC is the lowest operating voltage
that is allowed at the last appliance on the NAC under worst case conditions.
2. The maximum RMS current listed is the device nameplate rating. Strobe designs are constant wattage and the maximum
RMS current rating occurs at the lowest allowable operating voltage. (RMS is root mean square and refers to the
effective value of a varying current waveform.)

Installation Reference, Adapter Plate, Guard, and Adapter Skirt

Surface Mounting Reference


2975-9145 Box with Optional Adapter Skirt
and Optional Wire Guard
Surface mount conduit and
box shown for reference

4" (102 mm) square


box profile, 1-1/2"
(38 mm) deep

Optional
4905-9961
Wire Guard
Strobe

4905-9931 Adapter Plate


Optional Surface Mount Adapter Skirt,
4905-9961 Optional Wire Guard 1-1/2" deep: 4905-9937, Red;
(shown here for reference only, 4905-9940, White (conduit knockouts
4905-9931 Adapter Plate can be used on other mounting options) are provided on all four sides)

3 S4904-0005-5 9/2004
Tyco, Simplex, the Simplex logo, and TrueAlert are trademarks of Tyco International Services AG or its affiliates in the U.S. and/or other countries. NFPA 72 and National Fire
Alarm Code are registered trademarks of the National Fire Protection Association (NFPA).

Tyco Safety Products Westminster • Westminster, MA • 01441-0001 • USA S4904-0005-5 9/2004


www.tycosafetyproducts-usa-wm.com
© 2004 Tyco Safety Products Westminster. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Fire Alarm Bells

The bell remains the most commonly used alarm for fire Features
evacuation systems. Recognising this, Vimpex continue to
innovate with their all-aluminium range of fire alarm bells. + Low current consumption - only 11mA
+ Quickly and easily installed
Five bells make up the range of 150mm (6 inch) and 200mm (8
+ Excellent sonorous tone up to 100dB(A) at 1m
inch) internal and external units. Being of aluminium construction,
our bells have a very high volume output matched with extremely + Slim profile
low power consumption - just 11mA for the 150mm internal. + Fully suppressed and polarised
+ Simple installation with multi-fixing base plate
The specially designed weatherproof bells have an aluminium back
+ Purpose-made weatherproof range
box giving either single or double threaded entry for maximum
flexibility in installation. This is supplied as a full fixing kit with + 24V bells certified by LPCB to EN54-3:2001
gasket and screws. + 24V bells compliant with Construction
Products Directive
As with the Vimpex sounder range, all bells can be supplied
branded with your company logo.

StroBell
For a combined Bell
0832
and Strobe see the
StroBell. 692a
Datasheet Part No.
DS/STROBELL or visit
vimpex.co.uk/strobell.

VIMPEX Shaping Alarm Technology

1
Specification
Description 6" (150mm) 6" (150mm) 8" (200mm) 6" (150mm) 8" (200mm)
Internal - 12V Internal - 24V Internal - 24V Weatherproof Weatherproof
Model No.: MBF-6EV-12 MBF-6EV-24 MBF-8EV MBA-6 + BBX-4 MBA-8 + BBX-4
Rated Voltage (Vdc): 9.6 - 13.2 20.4 - 27.6 20.4 - 27.6 20.4 - 27.6 20.4 - 27.6
Rated Current @24V (mA): 40 11 17 12 25
Starting Voltage (Vdc): 5.5 19.2 19.2 16.0 16.9
Sound Output dB(A) @1m (max): 100.7 96.5 98.8 100.5 100.1
Temperature Range (oC): -10 to +50
Humidity Range (%): 45 - 85
Weight (g), (*with backbox): 410 410 640 780* 1100*
Gong Colour: Red
Gong Construction: Aluminium

Note: Refer to Sound Output Data sheet (DS/BELLDATA/ISS1) for full data and polar plot

Installation
Internal MBF Range Knock-out for
Type A Base surface wiring 150 or 200
50.5

Mounting
Screw

Gong

BESA Box
or single gang 53 60
installation
box

Hex bolt Note: Care should be taken to Mounting holes are provided to suit either BESA single gang
avoid damage to the striker mechanism installation boxes or for direct wall mounting

Weatherproof MBA Range (IP55)


Type B 64
Gasket 150 or 200
Base
Mounting
Screw
7
Gong

95

BBX-4
Installation box
with 20mm
Striker threaded entry 40 128
(BBX-4 + gasket)
Hex bolt
Mounting holes are located to suit BBX-4
installation box supplied.
Dimensions (mm)

Vimpex Limited
Star Lane, Great Wakering
Essex SS3 0PJ England
Tel: +44 (0) 1702 216999
Fax:+44 (0) 1702 216699
E-mail:sales@vimpex.co.uk
www.vimpex.co.uk
VIMPEX Shaping Alarm Technology

DS/BELL/ISS 12
2 We reserve the right to change or amend any design or specification in line
with our policy of continuing development and improvement.

You might also like