You are on page 1of 692

Relion® 650 SERIES

Breaker protection REQ650


Version 2.2 IEC
Technical manual
Document ID: 1MRK 505 384-UEN
Issued: May 2019
Revision: C
Product version: 2.2

© Copyright 2017 ABB. All rights reserved


Copyright
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third party, nor
used for any unauthorized purpose.

The software and hardware described in this document is furnished under a license and may
be used or disclosed only in accordance with the terms of such license.

This product includes software developed by the OpenSSL Project for use in the OpenSSL
Toolkit. (http://www.openssl.org/) This product includes cryptographic software written/
developed by: Eric Young (eay@cryptsoft.com) and Tim Hudson (tjh@cryptsoft.com).

Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names
mentioned in this document may be trademarks or registered trademarks of their respective
holders.

Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or product
description and are not to be deemed as a statement of guaranteed properties. All persons
responsible for applying the equipment addressed in this manual must satisfy themselves that
each intended application is suitable and acceptable, including that any applicable safety or
other operational requirements are complied with. In particular, any risks in applications where
a system failure and/or product failure would create a risk for harm to property or persons
(including but not limited to personal injuries or death) shall be the sole responsibility of the
person or entity applying the equipment, and those so responsible are hereby requested to
ensure that all measures are taken to exclude or mitigate such risks.

This document has been carefully checked by ABB but deviations cannot be completely ruled
out. In case any errors are detected, the reader is kindly requested to notify the manufacturer.
Other than under explicit contractual commitments, in no event shall ABB be responsible or
liable for any loss or damage resulting from the use of this manual or the application of the
equipment.
Conformity
This product complies with the directive of the Council of the European Communities on the
approximation of the laws of the Member States relating to electromagnetic compatibility
(EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified
voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests
conducted by ABB in accordance with the product standard EN 60255-26 for the EMC directive,
and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive. The
product is designed in accordance with the international standards of the IEC 60255 series.
Table of contents

Table of contents

Section 1 Introduction.................................................................................................. 25
1.1 This manual..................................................................................................................................25
1.1.1 Presumptions for Technical Data..........................................................................................25
1.2 Intended audience......................................................................................................................25
1.3 Product documentation............................................................................................................26
1.3.1 Product documentation set................................................................................................... 26
1.3.2 Document revision history..................................................................................................... 27
1.3.3 Related documents.................................................................................................................. 27
1.4 Document symbols and conventions..................................................................................... 28
1.4.1 Symbols......................................................................................................................................28
1.4.2 Document conventions........................................................................................................... 29
1.5 IEC 61850 edition 1 / edition 2 mapping................................................................................31

Section 2 Available functions.......................................................................................35


2.1 Back-up protection functions.................................................................................................. 35
2.2 Control and monitoring functions.......................................................................................... 36
2.3 Communication.......................................................................................................................... 39
2.4 Basic IED functions.................................................................................................................... 40

Section 3 Analog inputs................................................................................................43


3.1 Introduction.................................................................................................................................43
3.2 Function block.............................................................................................................................43
3.3 Signals.......................................................................................................................................... 43
3.4 Settings........................................................................................................................................ 45
3.5 Monitored data...........................................................................................................................48
3.6 Operation principle....................................................................................................................49
3.7 Technical data.............................................................................................................................50

Section 4 Binary input and output modules...............................................................51


4.1 Binary input.................................................................................................................................. 51
4.1.1 Binary input debounce filter...................................................................................................51
4.1.2 Oscillation filter.........................................................................................................................51
4.1.3 Settings...................................................................................................................................... 51
4.1.3.1 Setting parameters for binary input modules.............................................................. 51
4.1.3.2 Setting parameters for binary input/output module................................................. 52

Section 5 Local Human-Machine-Interface LHMI ......................................................53


5.1 Local HMI screen behaviour......................................................................................................53
5.1.1 Identification.............................................................................................................................53
5.1.2 Settings...................................................................................................................................... 53
5.2 Local HMI signals........................................................................................................................ 53
5.2.1 Identification.............................................................................................................................53

Breaker protection REQ650 1


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

5.2.2 Function block...........................................................................................................................53


5.2.3 Signals........................................................................................................................................ 53
5.3 Basic part for LED indication module.................................................................................... 54
5.3.1 Identification............................................................................................................................ 54
5.3.2 Function block.......................................................................................................................... 54
5.3.3 Signals........................................................................................................................................ 55
5.3.4 Settings...................................................................................................................................... 55
5.4 LCD part for HMI function keys control module.................................................................. 56
5.4.1 Identification.............................................................................................................................56
5.4.2 Function block.......................................................................................................................... 56
5.4.3 Signals........................................................................................................................................ 56
5.4.4 Settings...................................................................................................................................... 57
5.5 Operation principle.................................................................................................................... 58
5.5.1 Local HMI................................................................................................................................... 58
5.5.1.1 Keypad.................................................................................................................................. 59
5.5.1.2 Display...................................................................................................................................61
5.5.1.3 LEDs.......................................................................................................................................63
5.5.2 LED configuration alternatives............................................................................................. 64
5.5.2.1 Functionality .......................................................................................................................64
5.5.2.2 Status LEDs......................................................................................................................... 64
5.5.2.3 Indication LEDs................................................................................................................... 65
5.5.3 Function keys............................................................................................................................ 72
5.5.3.1 Functionality ....................................................................................................................... 72
5.5.3.2 Operation principle.............................................................................................................72
5.5.3.3 Enabling and Disabling Authority on Function keys....................................................74

Section 6 Current protection....................................................................................... 75


6.1 Instantaneous phase overcurrent protection PHPIOC ...................................................... 75
6.1.1 Identification.............................................................................................................................75
6.1.2 Functionality..............................................................................................................................75
6.1.3 Function block...........................................................................................................................75
6.1.4 Signals........................................................................................................................................ 75
6.1.5 Settings...................................................................................................................................... 76
6.1.6 Monitored data......................................................................................................................... 76
6.1.7 Operation principle.................................................................................................................. 76
6.1.8 Technical data........................................................................................................................... 77
6.2 Directional phase overcurrent protection, four steps OC4PTOC..................................... 77
6.2.1 Identification.............................................................................................................................78
6.2.2 Functionality..............................................................................................................................78
6.2.3 Function block...........................................................................................................................79
6.2.4 Signals........................................................................................................................................ 79
6.2.5 Settings...................................................................................................................................... 81
6.2.6 Monitored data.........................................................................................................................86
6.2.7 Operation principle..................................................................................................................86
6.2.8 Technical data...........................................................................................................................92
6.3 Instantaneous residual overcurrent protection EFPIOC ................................................... 93

2 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

6.3.1 Identification.............................................................................................................................93
6.3.2 Functionality............................................................................................................................. 93
6.3.3 Function block.......................................................................................................................... 93
6.3.4 Signals........................................................................................................................................ 93
6.3.5 Settings......................................................................................................................................94
6.3.6 Monitored data.........................................................................................................................94
6.3.7 Operation principle..................................................................................................................95
6.3.8 Technical data...........................................................................................................................95
6.4 Directional residual overcurrent protection, four steps EF4PTOC ................................. 96
6.4.1 Identification............................................................................................................................ 96
6.4.2 Functionality............................................................................................................................. 96
6.4.3 Function block...........................................................................................................................97
6.4.4 Signals........................................................................................................................................ 97
6.4.5 Settings......................................................................................................................................98
6.4.6 Monitored data.......................................................................................................................104
6.4.7 Operation principle................................................................................................................104
6.4.7.1 Operating quantity within the function.......................................................................104
6.4.7.2 Internal polarizing.............................................................................................................105
6.4.7.3 External polarizing for earth-fault function................................................................ 107
6.4.7.4 Directional detection for earth fault function............................................................ 107
6.4.7.5 Base quantities within the protection..........................................................................107
6.4.7.6 Internal earth-fault protection structure..................................................................... 107
6.4.7.7 Four residual overcurrent steps.................................................................................... 108
6.4.7.8 Directional supervision element with integrated directional
comparison function........................................................................................................109
6.4.7.9 Second harmonic blocking element...............................................................................111
6.4.7.10 Switch on to fault feature................................................................................................113
6.4.8 Technical data......................................................................................................................... 115
6.5 Four step directional negative phase sequence overcurrent protection NS4PTOC .. 116
6.5.1 Identification........................................................................................................................... 116
6.5.2 Functionality............................................................................................................................ 116
6.5.3 Function block......................................................................................................................... 117
6.5.4 Signals....................................................................................................................................... 117
6.5.5 Settings.................................................................................................................................... 118
6.5.6 Monitored data....................................................................................................................... 122
6.5.7 Operation principle................................................................................................................ 122
6.5.7.1 Operating quantity within the function....................................................................... 122
6.5.7.2 Internal polarizing facility of the function................................................................... 123
6.5.7.3 External polarizing for negative sequence function.................................................. 123
6.5.7.4 Internal negative sequence protection structure...................................................... 124
6.5.7.5 Four negative sequence overcurrent stages...............................................................124
6.5.7.6 Directional supervision element with integrated directional comparison
function...............................................................................................................................125
6.5.8 Technical data......................................................................................................................... 127
6.6 Thermal overload protection, one time constant, Celsius/Fahrenheit
LCPTTR/LFPTTR........................................................................................................................128
6.6.1 Identification...........................................................................................................................128

Breaker protection REQ650 3


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

6.6.2 Functionality............................................................................................................................128
6.6.3 Function block.........................................................................................................................129
6.6.4 Signals...................................................................................................................................... 129
6.6.5 Settings.................................................................................................................................... 130
6.6.6 Monitored data........................................................................................................................131
6.6.7 Operation principle................................................................................................................ 132
6.6.8 Technical data......................................................................................................................... 135
6.7 Breaker failure protection CCRBRF....................................................................................... 135
6.7.1 Identification........................................................................................................................... 135
6.7.2 Functionality............................................................................................................................135
6.7.3 Function block.........................................................................................................................136
6.7.4 Signals...................................................................................................................................... 136
6.7.5 Settings.................................................................................................................................... 137
6.7.6 Monitored data....................................................................................................................... 138
6.7.7 Operation principle................................................................................................................ 138
6.7.8 Technical data......................................................................................................................... 141
6.8 Stub protection STBPTOC ..................................................................................................... 142
6.8.1 Identification...........................................................................................................................142
6.8.2 Functionality............................................................................................................................142
6.8.3 Function block.........................................................................................................................142
6.8.4 Signals...................................................................................................................................... 142
6.8.5 Settings.................................................................................................................................... 143
6.8.6 Monitored data....................................................................................................................... 143
6.8.7 Operation principle................................................................................................................ 143
6.8.8 Technical data.........................................................................................................................144
6.9 Broken conductor check BRCPTOC ......................................................................................144
6.9.1 Identification...........................................................................................................................144
6.9.2 Functionality............................................................................................................................145
6.9.3 Function block........................................................................................................................ 145
6.9.4 Signals...................................................................................................................................... 145
6.9.5 Settings.................................................................................................................................... 145
6.9.6 Monitored data.......................................................................................................................146
6.9.7 Operation principle................................................................................................................146
6.9.8 Technical data......................................................................................................................... 147

Section 7 Voltage protection.....................................................................................149


7.1 Two step undervoltage protection UV2PTUV ....................................................................149
7.1.1 Identification...........................................................................................................................149
7.1.2 Functionality........................................................................................................................... 149
7.1.3 Function block........................................................................................................................ 149
7.1.4 Signals...................................................................................................................................... 150
7.1.5 Settings.....................................................................................................................................151
7.1.6 Monitored data....................................................................................................................... 153
7.1.7 Operation principle................................................................................................................ 153
7.1.7.1 Measurement principle.................................................................................................... 153
7.1.7.2 Time delay.......................................................................................................................... 154

4 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

7.1.7.3 Blocking.............................................................................................................................. 159


7.1.7.4 Design................................................................................................................................. 160
7.1.8 Technical data......................................................................................................................... 161
7.2 Two step overvoltage protection OV2PTOV .......................................................................161
7.2.1 Identification........................................................................................................................... 161
7.2.2 Functionality OV2PTOV......................................................................................................... 161
7.2.3 Function block.........................................................................................................................162
7.2.4 Signals...................................................................................................................................... 162
7.2.5 Settings.................................................................................................................................... 163
7.2.6 Monitored data....................................................................................................................... 165
7.2.7 Operation principle................................................................................................................ 165
7.2.7.1 Measurement principle....................................................................................................165
7.2.7.2 Time delay.......................................................................................................................... 166
7.2.7.3 Blocking............................................................................................................................... 171
7.2.7.4 Design.................................................................................................................................. 171
7.2.8 Technical data......................................................................................................................... 172
7.3 Two step residual overvoltage protection ROV2PTOV .................................................... 173
7.3.1 Identification........................................................................................................................... 173
7.3.2 Monitored data....................................................................................................................... 173
7.3.3 Operation principle................................................................................................................ 173
7.3.3.1 Measurement principle.................................................................................................... 174
7.3.3.2 Time delay.......................................................................................................................... 174
7.3.3.3 Blocking...............................................................................................................................179
7.3.3.4 Design..................................................................................................................................179
7.3.4 Technical data.........................................................................................................................180
7.4 Loss of voltage check LOVPTUV ...........................................................................................180
7.4.1 Identification...........................................................................................................................180
7.4.2 Functionality........................................................................................................................... 180
7.4.3 Function block......................................................................................................................... 181
7.4.4 Signals.......................................................................................................................................181
7.4.5 Settings.................................................................................................................................... 181
7.4.6 Operation principle................................................................................................................ 182
7.4.7 Technical data......................................................................................................................... 183

Section 8 Secondary system supervision.................................................................185


8.1 Current circuit supervision CCSSPVC...................................................................................185
8.1.1 Identification...........................................................................................................................185
8.1.2 Functionality............................................................................................................................185
8.1.3 Function block.........................................................................................................................185
8.1.4 Signals...................................................................................................................................... 185
8.1.5 Settings.................................................................................................................................... 186
8.1.6 Operation principle................................................................................................................186
8.1.7 Technical data......................................................................................................................... 187
8.2 Fuse failure supervision FUFSPVC........................................................................................ 188
8.2.1 Identification...........................................................................................................................188
8.2.2 Functionality........................................................................................................................... 188

Breaker protection REQ650 5


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

8.2.3 Function block........................................................................................................................ 188


8.2.4 Signals...................................................................................................................................... 189
8.2.5 Settings....................................................................................................................................190
8.2.6 Monitored data....................................................................................................................... 191
8.2.7 Operation principle................................................................................................................ 191
8.2.7.1 Zero and negative sequence detection........................................................................ 191
8.2.7.2 Delta current and delta voltage detection...................................................................193
8.2.7.3 Dead line detection.......................................................................................................... 195
8.2.7.4 Main logic........................................................................................................................... 196
8.2.8 Technical data.........................................................................................................................199

Section 9 Control......................................................................................................... 201


9.1 Synchrocheck, energizing check, and synchronizing SESRSYN...................................... 201
9.1.1 Identification...........................................................................................................................201
9.1.2 Functionality............................................................................................................................201
9.1.3 Function block........................................................................................................................ 202
9.1.4 Signals...................................................................................................................................... 202
9.1.5 Settings....................................................................................................................................204
9.1.6 Monitored data...................................................................................................................... 206
9.1.7 Operation principle................................................................................................................207
9.1.7.1 Basic functionality............................................................................................................ 207
9.1.7.2 Logic diagrams................................................................................................................. 207
9.1.8 Technical data......................................................................................................................... 216
9.2 Autorecloser for 1 phase, 2 phase and/or 3 phase operation SMBRREC ......................217
9.2.1 Identification...........................................................................................................................218
9.2.2 Functionality............................................................................................................................218
9.2.3 Function block.........................................................................................................................218
9.2.4 Signals...................................................................................................................................... 219
9.2.5 Settings....................................................................................................................................220
9.2.6 Operation principle................................................................................................................ 222
9.2.6.1 Terminology explanation................................................................................................ 222
9.2.6.2 Status descriptions.......................................................................................................... 222
9.2.6.3 Description of the status transition............................................................................. 223
9.2.6.4 Functional sequence description.................................................................................. 224
9.2.6.5 Time sequence diagrams................................................................................................ 235
9.2.7 Technical data.........................................................................................................................238
9.3 Interlocking ...............................................................................................................................238
9.3.1 Logical node for interlocking SCILO ..................................................................................238
9.3.1.1 Identification..................................................................................................................... 238
9.3.1.2 Functionality......................................................................................................................239
9.3.1.3 Function block...................................................................................................................239
9.3.1.4 Signals.................................................................................................................................239
9.3.1.5 Logic diagram................................................................................................................... 239
9.4 Apparatus control.................................................................................................................... 240
9.4.1 Functionality........................................................................................................................... 240
9.4.2 Operation principle................................................................................................................ 241

6 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

9.4.3 Error handling......................................................................................................................... 242


9.4.4 Bay control QCBAY.................................................................................................................245
9.4.4.1 Functionality......................................................................................................................245
9.4.4.2 Function block...................................................................................................................245
9.4.4.3 Signals................................................................................................................................ 245
9.4.4.4 Settings.............................................................................................................................. 246
9.4.4.5 Operation principle.......................................................................................................... 246
9.4.5 Local/Remote switch LOCREM........................................................................................... 248
9.4.5.1 Function block...................................................................................................................248
9.4.5.2 Signals................................................................................................................................ 248
9.4.5.3 Settings.............................................................................................................................. 249
9.4.5.4 Operation principle.......................................................................................................... 250
9.4.6 Switch controller SCSWI....................................................................................................... 250
9.4.6.1 Functionality ..................................................................................................................... 251
9.4.6.2 Function block................................................................................................................... 251
9.4.6.3 Signals................................................................................................................................. 251
9.4.6.4 Settings.............................................................................................................................. 253
9.4.6.5 Operation principle.......................................................................................................... 253
9.4.7 Circuit breaker SXCBR...........................................................................................................258
9.4.7.1 Functionality .....................................................................................................................259
9.4.7.2 Function block...................................................................................................................259
9.4.7.3 Signals.................................................................................................................................259
9.4.7.4 Settings.............................................................................................................................. 260
9.4.7.5 Operation principle.......................................................................................................... 260
9.4.8 Circuit switch SXSWI..............................................................................................................263
9.4.8.1 Functionality .....................................................................................................................264
9.4.8.2 Function block...................................................................................................................264
9.4.8.3 Signals................................................................................................................................ 264
9.4.8.4 Settings.............................................................................................................................. 265
9.4.8.5 Operation principle.......................................................................................................... 265
9.4.9 Proxy for signals from switching device via GOOSE XLNPROXY .................................269
9.4.9.1 Functionality......................................................................................................................269
9.4.9.2 Function block...................................................................................................................269
9.4.9.3 Signals.................................................................................................................................270
9.4.9.4 Settings............................................................................................................................... 271
9.4.9.5 Operation principle...........................................................................................................271
9.4.9.6 Position supervision......................................................................................................... 271
9.4.9.7 Command response evaluation..................................................................................... 271
9.5 Logic rotating switch for function selection and LHMI presentation SLGAPC............273
9.5.1 Identification...........................................................................................................................273
9.5.2 Functionality............................................................................................................................273
9.5.3 Function block........................................................................................................................ 274
9.5.4 Signals...................................................................................................................................... 274
9.5.5 Settings.................................................................................................................................... 275
9.5.6 Monitored data.......................................................................................................................276
9.5.7 Operation principle................................................................................................................276

Breaker protection REQ650 7


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

9.5.7.1 Graphical display...............................................................................................................276


9.6 Selector mini switch VSGAPC................................................................................................. 277
9.6.1 Identification........................................................................................................................... 277
9.6.2 Functionality............................................................................................................................277
9.6.3 Function block........................................................................................................................ 278
9.6.4 Signals...................................................................................................................................... 278
9.6.5 Settings.................................................................................................................................... 278
9.6.6 Operation principle................................................................................................................279
9.7 Generic communication function for Double Point indication DPGAPC.......................279
9.7.1 Identification...........................................................................................................................279
9.7.2 Functionality........................................................................................................................... 280
9.7.3 Function block........................................................................................................................ 280
9.7.4 Signals......................................................................................................................................280
9.7.5 Settings....................................................................................................................................280
9.7.6 Operation principle............................................................................................................... 280
9.8 Single point generic control 8 signals SPC8GAPC............................................................. 281
9.8.1 Identification...........................................................................................................................281
9.8.2 Functionality............................................................................................................................281
9.8.3 Function block.........................................................................................................................281
9.8.4 Signals...................................................................................................................................... 282
9.8.5 Settings.................................................................................................................................... 282
9.8.6 Operation principle................................................................................................................283
9.9 AutomationBits, command function for DNP3.0 AUTOBITS........................................... 283
9.9.1 Identification...........................................................................................................................283
9.9.2 Functionality........................................................................................................................... 283
9.9.3 Function block........................................................................................................................ 284
9.9.4 Signals...................................................................................................................................... 284
9.9.5 Settings....................................................................................................................................285
9.9.6 Operation principle................................................................................................................285
9.10 Single command, 16 signals SINGLECMD............................................................................286
9.10.1 Identification.......................................................................................................................... 286
9.10.2 Functionality........................................................................................................................... 286
9.10.3 Function block........................................................................................................................ 286
9.10.4 Signals...................................................................................................................................... 286
9.10.5 Settings.................................................................................................................................... 287
9.10.6 Operation principle................................................................................................................287

Section 10 Logic............................................................................................................ 289


10.1 Tripping logic SMPPTRC ........................................................................................................ 289
10.1.1 Identification.......................................................................................................................... 289
10.1.2 Functionality........................................................................................................................... 289
10.1.3 Function block........................................................................................................................ 289
10.1.4 Signals......................................................................................................................................290
10.1.5 Settings.................................................................................................................................... 291
10.1.6 Operation principle................................................................................................................ 291
10.1.6.1 Logic diagram................................................................................................................... 294

8 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

10.1.7 Technical data.........................................................................................................................297


10.2 General start matrix block SMAGAPC...................................................................................297
10.2.1 Identification...........................................................................................................................297
10.2.2 Functionality........................................................................................................................... 297
10.2.3 Function block........................................................................................................................ 297
10.2.4 Signals...................................................................................................................................... 298
10.2.5 Settings....................................................................................................................................298
10.2.6 Operation principle................................................................................................................298
10.3 Trip matrix logic TMAGAPC.................................................................................................... 303
10.3.1 Identification.......................................................................................................................... 303
10.3.2 Functionality........................................................................................................................... 303
10.3.3 Function block........................................................................................................................ 303
10.3.4 Signals......................................................................................................................................304
10.3.5 Settings....................................................................................................................................305
10.3.6 Operation principle................................................................................................................305
10.3.7 Technical data........................................................................................................................ 306
10.4 Logic for group alarm ALMCALH.......................................................................................... 306
10.4.1 Identification.......................................................................................................................... 306
10.4.2 Functionality........................................................................................................................... 306
10.4.3 Function block........................................................................................................................ 307
10.4.4 Signals...................................................................................................................................... 307
10.4.5 Settings................................................................................................................................... 308
10.4.6 Operation principle............................................................................................................... 308
10.4.7 Technical data........................................................................................................................ 308
10.5 Logic for group warning WRNCALH..................................................................................... 308
10.5.1 Identification.......................................................................................................................... 308
10.5.2 Functionality........................................................................................................................... 308
10.5.3 Function block........................................................................................................................ 309
10.5.4 Signals......................................................................................................................................309
10.5.5 Settings.................................................................................................................................... 310
10.5.6 Operation principle................................................................................................................ 310
10.5.7 Technical data......................................................................................................................... 310
10.6 Logic for group indication INDCALH.................................................................................... 310
10.6.1 Identification...........................................................................................................................310
10.6.2 Functionality............................................................................................................................310
10.6.3 Function block......................................................................................................................... 311
10.6.4 Signals....................................................................................................................................... 311
10.6.5 Settings.................................................................................................................................... 312
10.6.6 Operation principle................................................................................................................ 312
10.6.7 Technical data......................................................................................................................... 312
10.7 Basic configurable logic blocks..............................................................................................312
10.7.1 AND function block AND....................................................................................................... 313
10.7.1.1 Function block................................................................................................................... 313
10.7.1.2 Signals................................................................................................................................. 313
10.7.1.3 Technical data................................................................................................................... 314
10.7.2 Controllable gate function block GATE..............................................................................314

Breaker protection REQ650 9


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

10.7.2.1 Function block................................................................................................................... 314


10.7.2.2 Signals.................................................................................................................................314
10.7.2.3 Settings...............................................................................................................................314
10.7.2.4 Technical data....................................................................................................................315
10.7.3 Inverter function block INV................................................................................................... 315
10.7.3.1 Function block................................................................................................................... 315
10.7.3.2 Signals................................................................................................................................. 315
10.7.3.3 Technical data....................................................................................................................315
10.7.4 Loop delay function block LLD............................................................................................ 315
10.7.4.1 Function block................................................................................................................... 316
10.7.4.2 Signals................................................................................................................................. 316
10.7.4.3 Technical data....................................................................................................................316
10.7.5 OR function block................................................................................................................... 316
10.7.5.1 Function block................................................................................................................... 316
10.7.5.2 Signals................................................................................................................................. 317
10.7.5.3 Technical data....................................................................................................................317
10.7.6 Pulse timer function block PULSETIMER............................................................................317
10.7.6.1 Function block................................................................................................................... 317
10.7.6.2 Signals................................................................................................................................. 317
10.7.6.3 Settings...............................................................................................................................318
10.7.6.4 Technical data....................................................................................................................318
10.7.7 Reset-set with memory function block RSMEMORY....................................................... 318
10.7.7.1 Function block................................................................................................................... 318
10.7.7.2 Signals................................................................................................................................. 319
10.7.7.3 Settings...............................................................................................................................319
10.7.7.4 Technical data....................................................................................................................319
10.7.8 Set-reset with memory function block SRMEMORY........................................................319
10.7.8.1 Function block...................................................................................................................320
10.7.8.2 Signals................................................................................................................................ 320
10.7.8.3 Settings.............................................................................................................................. 320
10.7.8.4 Technical data................................................................................................................... 320
10.7.9 Settable timer function block TIMERSET.......................................................................... 320
10.7.9.1 Function block................................................................................................................... 321
10.7.9.2 Signals................................................................................................................................. 321
10.7.9.3 Settings...............................................................................................................................321
10.7.9.4 Technical data................................................................................................................... 322
10.7.10 Exclusive OR function block XOR........................................................................................ 322
10.7.10.1 Function block................................................................................................................... 322
10.7.10.2 Signals.................................................................................................................................322
10.7.10.3 Technical data................................................................................................................... 323
10.8 Fixed signals FXDSIGN............................................................................................................ 323
10.8.1 Identification...........................................................................................................................323
10.8.2 Functionality............................................................................................................................323
10.8.3 Function block.........................................................................................................................323
10.8.4 Signals...................................................................................................................................... 323
10.8.5 Settings....................................................................................................................................324

10 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

10.8.6 Operation principle................................................................................................................324


10.9 Boolean 16 to Integer conversion B16I.................................................................................324
10.9.1 Identification...........................................................................................................................324
10.9.2 Functionality........................................................................................................................... 324
10.9.3 Function block........................................................................................................................ 325
10.9.4 Signals...................................................................................................................................... 325
10.9.5 Monitored data.......................................................................................................................326
10.9.6 Settings....................................................................................................................................326
10.9.7 Operation principle................................................................................................................326
10.9.8 Technical data......................................................................................................................... 327
10.10 Boolean to integer conversion with logical node representation, 16 bit BTIGAPC..... 327
10.10.1 Identification...........................................................................................................................327
10.10.2 Functionality............................................................................................................................327
10.10.3 Function block.........................................................................................................................327
10.10.4 Signals...................................................................................................................................... 328
10.10.5 Settings....................................................................................................................................328
10.10.6 Monitored data.......................................................................................................................328
10.10.7 Operation principle................................................................................................................328
10.10.8 Technical data.........................................................................................................................329
10.11 Integer to boolean 16 conversion IB16................................................................................. 329
10.11.1 Identification...........................................................................................................................329
10.11.2 Functionality........................................................................................................................... 330
10.11.3 Function block........................................................................................................................ 330
10.11.4 Signals...................................................................................................................................... 330
10.11.5 Setting parameters................................................................................................................ 331
10.11.6 Operation principle................................................................................................................ 331
10.11.7 Technical data......................................................................................................................... 332
10.12 Integer to Boolean 16 conversion with logic node representation ITBGAPC............... 332
10.12.1 Identification...........................................................................................................................332
10.12.2 Functionality............................................................................................................................332
10.12.3 Function block........................................................................................................................ 333
10.12.4 Signals...................................................................................................................................... 333
10.12.5 Settings....................................................................................................................................334
10.12.6 Operation principle................................................................................................................334
10.12.7 Technical data.........................................................................................................................335
10.13 Elapsed time integrator with limit transgression and overflow supervision
TEIGAPC......................................................................................................................................335
10.13.1 Identification...........................................................................................................................335
10.13.2 Functionality........................................................................................................................... 335
10.13.3 Function block........................................................................................................................ 336
10.13.4 Signals...................................................................................................................................... 336
10.13.5 Settings....................................................................................................................................336
10.13.6 Operation principle................................................................................................................ 337
10.13.6.1 Operation accuracy.......................................................................................................... 338
10.13.6.2 Memory storage................................................................................................................338
10.13.7 Technical data.........................................................................................................................338

Breaker protection REQ650 11


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

10.14 Comparator for integer inputs INTCOMP........................................................................... 338


10.14.1 Identification...........................................................................................................................338
10.14.2 Functionality........................................................................................................................... 339
10.14.3 Function block........................................................................................................................ 339
10.14.4 Signals...................................................................................................................................... 339
10.14.5 Settings....................................................................................................................................339
10.14.6 Monitored data...................................................................................................................... 340
10.14.7 Operation principle............................................................................................................... 340
10.14.8 Technical data......................................................................................................................... 341
10.15 Comparator for real inputs REALCOMP...............................................................................341
10.15.1 Identification...........................................................................................................................341
10.15.2 Functionality............................................................................................................................341
10.15.3 Function block.........................................................................................................................341
10.15.4 Signals...................................................................................................................................... 341
10.15.5 Settings....................................................................................................................................342
10.15.6 Operation principle................................................................................................................342
10.15.7 Technical data........................................................................................................................ 344

Section 11 Monitoring.................................................................................................. 345


11.1 Measurements.......................................................................................................................... 345
11.1.1 Identification.......................................................................................................................... 345
11.1.2 Functionality........................................................................................................................... 345
11.1.3 Function block........................................................................................................................ 346
11.1.4 Signals......................................................................................................................................348
11.1.5 Settings.................................................................................................................................... 351
11.1.6 Monitored data.......................................................................................................................362
11.1.7 Operation principle................................................................................................................364
11.1.7.1 Measurement supervision.............................................................................................. 364
11.1.7.2 Measurements CVMMXN................................................................................................ 369
11.1.7.3 Phase current measurement CMMXU...........................................................................374
11.1.7.4 Phase-phase and phase-neutral voltage measurements VMMXU, VNMMXU.......374
11.1.7.5 Voltage and current sequence measurements VMSQI, CMSQI............................... 374
11.1.8 Technical data.........................................................................................................................374
11.2 Gas medium supervision SSIMG............................................................................................376
11.2.1 Identification...........................................................................................................................376
11.2.2 Functionality........................................................................................................................... 376
11.2.3 Function block........................................................................................................................ 376
11.2.4 Signals...................................................................................................................................... 377
11.2.5 Settings.................................................................................................................................... 377
11.2.6 Monitored data.......................................................................................................................378
11.2.7 Operation principle................................................................................................................378
11.2.8 Technical data.........................................................................................................................379
11.3 Liquid medium supervision SSIML........................................................................................379
11.3.1 Identification...........................................................................................................................379
11.3.2 Functionality........................................................................................................................... 379
11.3.3 Function block........................................................................................................................ 380

12 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

11.3.4 Signals......................................................................................................................................380
11.3.5 Settings.................................................................................................................................... 381
11.3.6 Monitored data....................................................................................................................... 381
11.3.7 Operation principle................................................................................................................ 381
11.3.8 Technical data.........................................................................................................................382
11.4 Breaker monitoring SSCBR.....................................................................................................382
11.4.1 Identification...........................................................................................................................382
11.4.2 Functionality........................................................................................................................... 383
11.4.3 Function block........................................................................................................................ 383
11.4.4 Signals...................................................................................................................................... 383
11.4.5 Settings....................................................................................................................................384
11.4.6 Monitored data.......................................................................................................................385
11.4.7 Operation principle................................................................................................................386
11.4.7.1 Circuit breaker contact travel time...............................................................................388
11.4.7.2 Circuit breaker status......................................................................................................389
11.4.7.3 Remaining life of circuit breaker................................................................................... 389
11.4.7.4 Accumulated energy........................................................................................................ 390
11.4.7.5 Circuit breaker operation cycles.................................................................................... 391
11.4.7.6 Circuit breaker operation monitoring.......................................................................... 392
11.4.7.7 Circuit breaker spring charge monitoring...................................................................393
11.4.7.8 Circuit breaker gas pressure indication.......................................................................393
11.4.8 Technical data........................................................................................................................ 394
11.5 Event function EVENT............................................................................................................. 394
11.5.1 Identification.......................................................................................................................... 394
11.5.2 Functionality........................................................................................................................... 395
11.5.3 Function block........................................................................................................................ 395
11.5.4 Signals...................................................................................................................................... 395
11.5.5 Settings....................................................................................................................................396
11.5.6 Operation principle................................................................................................................398
11.6 Disturbance report DRPRDRE................................................................................................ 399
11.6.1 Identification.......................................................................................................................... 399
11.6.2 Functionality........................................................................................................................... 399
11.6.3 Function block........................................................................................................................400
11.6.4 Signals...................................................................................................................................... 401
11.6.5 Settings....................................................................................................................................402
11.6.6 Monitored data...................................................................................................................... 408
11.6.7 Operation principle................................................................................................................ 411
11.6.8 Technical data......................................................................................................................... 417
11.7 Logical signal status report BINSTATREP............................................................................417
11.7.1 Identification........................................................................................................................... 417
11.7.2 Functionality............................................................................................................................417
11.7.3 Function block........................................................................................................................ 418
11.7.4 Signals...................................................................................................................................... 418
11.7.5 Settings.................................................................................................................................... 419
11.7.6 Operation principle................................................................................................................419
11.8 Measured value expander block RANGE_XP....................................................................... 420

Breaker protection REQ650 13


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

11.8.1 Identification.......................................................................................................................... 420


11.8.2 Functionality........................................................................................................................... 420
11.8.3 Function block........................................................................................................................ 420
11.8.4 Signals......................................................................................................................................420
11.8.5 Operation principle................................................................................................................ 421
11.9 Limit counter L4UFCNT...........................................................................................................421
11.9.1 Identification...........................................................................................................................421
11.9.2 Functionality............................................................................................................................421
11.9.3 Operation principle................................................................................................................ 421
11.9.3.1 Design................................................................................................................................. 421
11.9.3.2 Reporting........................................................................................................................... 423
11.9.4 Function block........................................................................................................................ 423
11.9.5 Signals...................................................................................................................................... 423
11.9.6 Settings....................................................................................................................................424
11.9.7 Monitored data.......................................................................................................................424
11.9.8 Technical data........................................................................................................................ 424
11.10 Running hour-meter TEILGAPC ............................................................................................ 424
11.10.1 Identification.......................................................................................................................... 424
11.10.2 Functionality........................................................................................................................... 425
11.10.3 Function block........................................................................................................................ 425
11.10.4 Signals...................................................................................................................................... 426
11.10.5 Settings....................................................................................................................................426
11.10.6 Operation principle................................................................................................................426
11.10.6.1 Operation accuracy.......................................................................................................... 428
11.10.6.2 Memory storage............................................................................................................... 428
11.10.7 Technical data.........................................................................................................................428

Section 12 Metering...................................................................................................... 429


12.1 Pulse-counter logic PCFCNT.................................................................................................. 429
12.1.1 Identification.......................................................................................................................... 429
12.1.2 Functionality........................................................................................................................... 429
12.1.3 Function block........................................................................................................................ 429
12.1.4 Signals...................................................................................................................................... 429
12.1.5 Settings................................................................................................................................... 430
12.1.6 Monitored data...................................................................................................................... 430
12.1.7 Operation principle............................................................................................................... 430
12.1.8 Technical data.........................................................................................................................432
12.2 Function for energy calculation and demand handling ETPMMTR................................ 432
12.2.1 Identification...........................................................................................................................432
12.2.2 Functionality........................................................................................................................... 433
12.2.3 Function block........................................................................................................................ 433
12.2.4 Signals...................................................................................................................................... 433
12.2.5 Settings....................................................................................................................................434
12.2.6 Monitored data.......................................................................................................................435
12.2.7 Operation principle................................................................................................................436
12.2.8 Technical data........................................................................................................................ 438

14 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

Section 13 Ethernet.......................................................................................................439
13.1 Access point.............................................................................................................................. 439
13.1.1 Introduction............................................................................................................................ 439
13.1.2 Settings....................................................................................................................................439
13.2 Access point diagnostics....................................................................................................... 440
13.2.1 Functionality...........................................................................................................................440
13.2.2 Function block........................................................................................................................440
13.2.3 Signals...................................................................................................................................... 441
13.2.4 Monitored data.......................................................................................................................441
13.3 Redundant communication....................................................................................................441
13.3.1 Identification...........................................................................................................................441
13.3.2 Functionality........................................................................................................................... 442
13.3.3 Operation principle................................................................................................................442
13.4 Merging unit..............................................................................................................................443
13.4.1 Introduction............................................................................................................................ 443
13.4.2 Settings................................................................................................................................... 444
13.4.3 Monitored data...................................................................................................................... 444
13.5 Routes........................................................................................................................................ 449
13.5.1 Introduction............................................................................................................................449
13.5.2 Settings................................................................................................................................... 450
13.5.3 Monitored data...................................................................................................................... 450

Section 14 Station communication............................................................................. 451


14.1 Communication protocols......................................................................................................451
14.2 Communication protocol diagnostics................................................................................. 451
14.3 DNP3 protocol...........................................................................................................................452
14.4 IEC 61850-8-1 communication protocol.............................................................................. 452
14.4.1 Functionality........................................................................................................................... 452
14.4.2 Communication interfaces and protocols........................................................................453
14.4.3 Settings....................................................................................................................................453
14.4.4 Technical data.........................................................................................................................453
14.4.5 Generic communication function for Single Point indication SPGAPC, SP16GAPC. 454
14.4.5.1 Functionality..................................................................................................................... 454
14.4.5.2 Function block.................................................................................................................. 454
14.4.5.3 Signals................................................................................................................................ 454
14.4.5.4 Settings.............................................................................................................................. 455
14.4.5.5 Monitored data................................................................................................................. 455
14.4.5.6 Operation principle.......................................................................................................... 456
14.4.6 Generic communication function for Measured Value MVGAPC..................................456
14.4.6.1 Functionality..................................................................................................................... 456
14.4.6.2 Function block.................................................................................................................. 456
14.4.6.3 Signals.................................................................................................................................457
14.4.6.4 Settings.............................................................................................................................. 457
14.4.6.5 Monitored data................................................................................................................. 458
14.4.6.6 Operation principle.......................................................................................................... 458
14.4.7 GOOSE function block to receive a double point value GOOSEDPRCV...................... 458

Breaker protection REQ650 15


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

14.4.7.1 Identification.....................................................................................................................458
14.4.7.2 Functionality..................................................................................................................... 458
14.4.7.3 Function block.................................................................................................................. 458
14.4.7.4 Signals................................................................................................................................ 459
14.4.7.5 Settings.............................................................................................................................. 459
14.4.7.6 Operation principle ......................................................................................................... 459
14.4.8 GOOSE function block to receive an integer value GOOSEINTRCV............................. 460
14.4.8.1 Identification.................................................................................................................... 460
14.4.8.2 Functionality..................................................................................................................... 460
14.4.8.3 Function block.................................................................................................................. 460
14.4.8.4 Signals.................................................................................................................................461
14.4.8.5 Settings.............................................................................................................................. 461
14.4.8.6 Operation principle ......................................................................................................... 461
14.4.9 GOOSE function block to receive a measurand value GOOSEMVRCV.........................462
14.4.9.1 Identification.....................................................................................................................462
14.4.9.2 Functionality......................................................................................................................462
14.4.9.3 Function block...................................................................................................................462
14.4.9.4 Signals................................................................................................................................ 463
14.4.9.5 Settings.............................................................................................................................. 463
14.4.9.6 Operation principle ......................................................................................................... 463
14.4.10 GOOSE function block to receive a single point value GOOSESPRCV.........................464
14.4.10.1 Identification.....................................................................................................................464
14.4.10.2 Functionality..................................................................................................................... 464
14.4.10.3 Function block.................................................................................................................. 464
14.4.10.4 Signals................................................................................................................................ 465
14.4.10.5 Settings.............................................................................................................................. 465
14.4.10.6 Operation principle ......................................................................................................... 465
14.4.11 Horizontal communication via GOOSE for interlocking GOOSEINTLKRCV............... 466
14.4.11.1 Functionality..................................................................................................................... 466
14.4.11.2 Function block...................................................................................................................467
14.4.11.3 Signals................................................................................................................................ 467
14.4.11.4 Settings.............................................................................................................................. 469
14.4.11.5 Operation principle..........................................................................................................469
14.4.12 GOOSE binary receive GOOSEBINRCV................................................................................471
14.4.12.1 Function block................................................................................................................... 471
14.4.12.2 Signals................................................................................................................................. 471
14.4.12.3 Settings.............................................................................................................................. 473
14.4.12.4 Operation principle.......................................................................................................... 473
14.4.13 GOOSE function block to receive a switching device GOOSEXLNRCV .......................474
14.4.13.1 Identification.....................................................................................................................474
14.4.13.2 Functionality......................................................................................................................474
14.4.13.3 Function block...................................................................................................................474
14.4.13.4 Signals.................................................................................................................................475
14.4.13.5 Settings.............................................................................................................................. 476
14.4.13.6 Operation principle.......................................................................................................... 476
14.5 IEC/UCA 61850-9-2LE communication protocol................................................................477

16 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

14.5.1 Introduction............................................................................................................................ 477


14.5.2 Function block........................................................................................................................ 477
14.5.3 Signals...................................................................................................................................... 477
14.5.3.1 Output signals...................................................................................................................477
14.5.4 Settings....................................................................................................................................478
14.5.5 Monitored data.......................................................................................................................478
14.5.6 Operation principle................................................................................................................483
14.5.6.1 Conditional blocking....................................................................................................... 486
14.5.6.2 IEC 61850 quality expander QUALEXP......................................................................... 490
14.5.7 Technical data.........................................................................................................................491
14.6 LON communication protocol............................................................................................... 491
14.6.1 Functionality........................................................................................................................... 491
14.6.2 Settings....................................................................................................................................492
14.6.3 Operation principle................................................................................................................492
14.6.4 Technical data........................................................................................................................ 508
14.7 SPA communication protocol................................................................................................509
14.7.1 Functionality........................................................................................................................... 509
14.7.2 Design...................................................................................................................................... 509
14.7.3 Settings................................................................................................................................... 509
14.7.4 Operation principle................................................................................................................510
14.7.4.1 Communication ports......................................................................................................514
14.7.5 Technical data......................................................................................................................... 515
14.8 IEC 60870-5-103 communication protocol..........................................................................515
14.8.1 Introduction.............................................................................................................................515
14.8.2 Measurands for IEC 60870-5-103 I103MEAS..................................................................... 516
14.8.2.1 Functionality...................................................................................................................... 516
14.8.2.2 Identification..................................................................................................................... 516
14.8.2.3 Function block................................................................................................................... 516
14.8.2.4 Signals................................................................................................................................. 517
14.8.2.5 Settings...............................................................................................................................517
14.8.3 Measurands user defined signals for IEC 60870-5-103 I103MEASUSR........................518
14.8.3.1 Functionality...................................................................................................................... 518
14.8.3.2 Identification..................................................................................................................... 518
14.8.3.3 Function block................................................................................................................... 518
14.8.3.4 Signals.................................................................................................................................518
14.8.3.5 Settings...............................................................................................................................519
14.8.4 Function status auto-recloser for IEC 60870-5-103 I103AR...........................................519
14.8.4.1 Functionality...................................................................................................................... 519
14.8.4.2 Identification..................................................................................................................... 519
14.8.4.3 Function block................................................................................................................... 519
14.8.4.4 Signals................................................................................................................................ 520
14.8.4.5 Settings.............................................................................................................................. 520
14.8.5 Function status earth-fault for IEC 60870-5-103 I103EF................................................520
14.8.5.1 Functionality......................................................................................................................520
14.8.5.2 Identification.....................................................................................................................520
14.8.5.3 Function block...................................................................................................................520

Breaker protection REQ650 17


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

14.8.5.4 Signals................................................................................................................................. 521


14.8.5.5 Settings...............................................................................................................................521
14.8.6 Function status fault protection for IEC 60870-5-103 I103FLTPROT...........................521
14.8.6.1 Functionality...................................................................................................................... 521
14.8.6.2 Identification..................................................................................................................... 521
14.8.6.3 Function block................................................................................................................... 522
14.8.6.4 Signals.................................................................................................................................522
14.8.6.5 Settings.............................................................................................................................. 523
14.8.7 IED status for IEC 60870-5-103 I103IED.............................................................................523
14.8.7.1 Functionality...................................................................................................................... 523
14.8.7.2 Identification..................................................................................................................... 523
14.8.7.3 Function block...................................................................................................................524
14.8.7.4 Signals................................................................................................................................ 524
14.8.7.5 Settings.............................................................................................................................. 524
14.8.8 Supervison status for IEC 60870-5-103 I103SUPERV...................................................... 524
14.8.8.1 Functionality......................................................................................................................524
14.8.8.2 Identification..................................................................................................................... 524
14.8.8.3 Function block...................................................................................................................525
14.8.8.4 Signals.................................................................................................................................525
14.8.8.5 Settings.............................................................................................................................. 525
14.8.9 Status for user defined signals for IEC 60870-5-103 I103USRDEF...............................525
14.8.9.1 Functionality......................................................................................................................525
14.8.9.2 Identification..................................................................................................................... 526
14.8.9.3 Function block...................................................................................................................526
14.8.9.4 Signals.................................................................................................................................526
14.8.9.5 Settings...............................................................................................................................527
14.8.10 Function commands for IEC 60870-5-103 I103CMD....................................................... 528
14.8.10.1 Functionality......................................................................................................................528
14.8.10.2 Identification..................................................................................................................... 528
14.8.10.3 Function block...................................................................................................................528
14.8.10.4 Signals.................................................................................................................................528
14.8.10.5 Settings.............................................................................................................................. 529
14.8.11 IED commands for IEC 60870-5-103 I103IEDCMD........................................................... 529
14.8.11.1 Functionality......................................................................................................................529
14.8.11.2 Identification..................................................................................................................... 529
14.8.11.3 Function block...................................................................................................................529
14.8.11.4 Signals.................................................................................................................................529
14.8.11.5 Settings.............................................................................................................................. 530
14.8.12 Function commands user defined for IEC 60870-5-103 I103USRCMD........................530
14.8.12.1 Functionality......................................................................................................................530
14.8.12.2 Identification.....................................................................................................................530
14.8.12.3 Function block...................................................................................................................530
14.8.12.4 Signals................................................................................................................................. 531
14.8.12.5 Settings...............................................................................................................................531
14.8.13 Function commands generic for IEC 60870-5-103 I103GENCMD................................. 532
14.8.13.1 Functionality...................................................................................................................... 532

18 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

14.8.13.2 Identification..................................................................................................................... 532


14.8.13.3 Function block................................................................................................................... 532
14.8.13.4 Signals.................................................................................................................................532
14.8.13.5 Settings.............................................................................................................................. 533
14.8.14 IED commands with position and select for IEC 60870-5-103 I103POSCMD.............533
14.8.14.1 Functionality...................................................................................................................... 533
14.8.14.2 Identification..................................................................................................................... 533
14.8.14.3 Function block...................................................................................................................533
14.8.14.4 Signals................................................................................................................................ 534
14.8.14.5 Settings.............................................................................................................................. 534
14.8.15 IED commands with position for IEC 60870-5-103 I103POSCMDV..............................534
14.8.15.1 Functionality......................................................................................................................534
14.8.15.2 Identification.....................................................................................................................534
14.8.15.3 Function block...................................................................................................................535
14.8.15.4 Signals.................................................................................................................................535
14.8.15.5 Settings.............................................................................................................................. 535
14.8.16 Operation principle ...............................................................................................................535
14.8.16.1 General................................................................................................................................535
14.8.16.2 Communication ports..................................................................................................... 544
14.8.17 Technical data........................................................................................................................ 544
14.9 MULTICMDRCV and MULTICMDSND....................................................................................544
14.9.1 Functionality........................................................................................................................... 545
14.9.2 Design...................................................................................................................................... 545
14.9.2.1 General................................................................................................................................545
14.9.3 Function block........................................................................................................................ 545
14.9.4 Signals......................................................................................................................................546
14.9.5 Settings....................................................................................................................................547
14.9.6 Operation principle............................................................................................................... 548
14.10 Activity logging parameters ACTIVLOG.............................................................................. 548
14.10.1 Activity logging ACTIVLOG.................................................................................................. 548
14.10.2 Settings................................................................................................................................... 548

Section 15 Security........................................................................................................ 551


15.1 Authority check ATHCHCK......................................................................................................551
15.1.1 Identification...........................................................................................................................551
15.1.2 Functionality............................................................................................................................551
15.1.3 Operation principle ...............................................................................................................552
15.1.3.1 Authorization with Central Account Management enabled IED............................. 554
15.2 Authority management AUTHMAN.......................................................................................556
15.2.1 Identification.......................................................................................................................... 556
15.2.2 AUTHMAN................................................................................................................................ 556
15.2.3 Settings....................................................................................................................................556
15.3 FTP access with password FTPACCS................................................................................... 556
15.3.1 Identification.......................................................................................................................... 556
15.3.2 FTP access with TLS, FTPACCS........................................................................................... 556
15.3.3 Settings.................................................................................................................................... 557

Breaker protection REQ650 19


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

15.4 Authority status ATHSTAT......................................................................................................557


15.4.1 Identification...........................................................................................................................557
15.4.2 Functionality........................................................................................................................... 557
15.4.3 Function block........................................................................................................................ 557
15.4.4 Signals...................................................................................................................................... 558
15.4.5 Settings....................................................................................................................................558
15.4.6 Operation principle ...............................................................................................................558
15.5 Self supervision with internal event list INTERRSIG..........................................................558
15.5.1 Functionality........................................................................................................................... 558
15.5.2 Function block........................................................................................................................ 558
15.5.3 Signals...................................................................................................................................... 559
15.5.4 Settings....................................................................................................................................559
15.5.5 Operation principle................................................................................................................559
15.5.5.1 Internal signals................................................................................................................. 560
15.5.5.2 Supervision of analog inputs......................................................................................... 562
15.5.6 Technical data.........................................................................................................................562
15.6 ChangeLock function CHNGLCK........................................................................................... 562
15.6.1 Functionality........................................................................................................................... 563
15.6.2 Function block........................................................................................................................ 563
15.6.3 Signals...................................................................................................................................... 563
15.6.4 Operation principle ...............................................................................................................563
15.7 Denial of service DOS.............................................................................................................. 564
15.7.1 Functionality .......................................................................................................................... 564
15.7.2 Operation principle............................................................................................................... 564

Section 16 Basic IED functions.................................................................................... 565


16.1 Time synchronization TIMESYNCHGEN...............................................................................565
16.1.1 Functionality........................................................................................................................... 565
16.1.2 Settings....................................................................................................................................565
16.1.3 Description of SyncLostMode..............................................................................................571
16.1.4 Operation principle ............................................................................................................... 572
16.1.4.1 General concepts.............................................................................................................. 572
16.1.4.2 Real-time clock (RTC) operation.................................................................................... 573
16.1.4.3 Synchronization alternatives..........................................................................................574
16.1.4.4 Process bus IEC/UCA 61850-9-2LE synchronization.................................................574
16.1.4.5 Precision Time Protocol (PTP) .......................................................................................575
16.1.5 Technical data.........................................................................................................................576
16.2 Parameter setting groups...................................................................................................... 576
16.2.1 Functionality........................................................................................................................... 576
16.2.2 Function block........................................................................................................................ 576
16.2.3 Signals...................................................................................................................................... 577
16.2.4 Settings.................................................................................................................................... 577
16.2.5 Operation principle................................................................................................................ 577
16.3 Test mode functionality TESTMODE....................................................................................579
16.3.1 Functionality........................................................................................................................... 579
16.3.2 Function block........................................................................................................................ 579

20 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

16.3.3 Signals...................................................................................................................................... 579


16.3.4 Settings................................................................................................................................... 580
16.3.5 Operation principle .............................................................................................................. 580
16.4 IED identifiers TERMINALID....................................................................................................581
16.4.1 Functionality............................................................................................................................581
16.4.2 Settings ................................................................................................................................... 581
16.5 Product information PRODINF.............................................................................................. 581
16.5.1 Functionality............................................................................................................................581
16.5.2 Settings ...................................................................................................................................582
16.5.3 Factory defined settings...................................................................................................... 582
16.6 Signal matrix for binary inputs SMBI....................................................................................582
16.6.1 Functionality........................................................................................................................... 583
16.6.2 Function block........................................................................................................................ 583
16.6.3 Signals...................................................................................................................................... 583
16.6.4 Operation principle............................................................................................................... 584
16.7 Signal matrix for binary outputs SMBO ..............................................................................584
16.7.1 Functionality........................................................................................................................... 584
16.7.2 Function block........................................................................................................................ 584
16.7.3 Signals......................................................................................................................................584
16.7.4 Operation principle................................................................................................................585
16.8 Signal matrix for analog inputs SMAI...................................................................................585
16.8.1 Functionality........................................................................................................................... 585
16.8.2 Function block........................................................................................................................ 585
16.8.3 Signals......................................................................................................................................586
16.8.4 Settings....................................................................................................................................587
16.8.5 Operation principle ...............................................................................................................589
16.8.5.1 Frequency values.............................................................................................................. 590
16.9 Summation block 3 phase 3PHSUM..................................................................................... 590
16.9.1 Functionality........................................................................................................................... 590
16.9.2 Function block.........................................................................................................................591
16.9.3 Signals...................................................................................................................................... 591
16.9.4 Settings.................................................................................................................................... 591
16.9.5 Operation principle ...............................................................................................................592

Section 17 IED hardware...............................................................................................593


17.1 Overview.....................................................................................................................................593
17.1.1 Variants of case size with local HMI display..................................................................... 593
17.1.2 Case from the front and rear sides.................................................................................... 594
17.2 Hardware modules.................................................................................................................. 594
17.2.1 Overview.................................................................................................................................. 594
17.2.2 Numeric module (NUM)........................................................................................................ 595
17.2.2.1 Introduction.......................................................................................................................595
17.2.2.2 Functionality......................................................................................................................595
17.2.2.3 Technical data................................................................................................................... 596
17.2.3 Power supply module (PSM)................................................................................................ 597
17.2.3.1 Introduction.......................................................................................................................597

Breaker protection REQ650 21


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

17.2.3.2 Design................................................................................................................................. 597


17.2.3.3 Technical data................................................................................................................... 597
17.2.4 Local human-machine interface (Local HMI).................................................................... 597
17.2.5 Transformer input module (TRM)....................................................................................... 597
17.2.5.1 Introduction.......................................................................................................................598
17.2.5.2 Design.................................................................................................................................598
17.2.5.3 Technical data................................................................................................................... 599
17.2.6 Binary input module (BIM)................................................................................................... 599
17.2.6.1 Introduction.......................................................................................................................599
17.2.6.2 Design.................................................................................................................................599
17.2.6.3 Signals................................................................................................................................ 602
17.2.6.4 Settings.............................................................................................................................. 602
17.2.6.5 Monitored data................................................................................................................. 602
17.2.6.6 Technical data...................................................................................................................603
17.2.7 Binary output modules (BOM).............................................................................................603
17.2.7.1 Introduction...................................................................................................................... 603
17.2.7.2 Design.................................................................................................................................603
17.2.7.3 Signals................................................................................................................................ 605
17.2.7.4 Settings.............................................................................................................................. 605
17.2.7.5 Monitored data.................................................................................................................606
17.2.7.6 Technical data...................................................................................................................609
17.2.8 Binary input/output module (IOM).................................................................................... 610
17.2.8.1 Introduction.......................................................................................................................610
17.2.8.2 Design................................................................................................................................. 610
17.2.8.3 Signals................................................................................................................................. 611
17.2.8.4 Settings............................................................................................................................... 611
17.2.8.5 Monitored data..................................................................................................................612
17.2.8.6 Technical data................................................................................................................... 614
17.2.9 Serial and LON communication module (SLM) ............................................................... 616
17.2.9.1 Introduction....................................................................................................................... 616
17.2.9.2 Design................................................................................................................................. 616
17.2.9.3 Technical data....................................................................................................................617
17.2.10 Galvanic RS485 communication module........................................................................... 617
17.2.10.1 Introduction....................................................................................................................... 617
17.2.10.2 Design..................................................................................................................................617
17.2.10.3 Technical data................................................................................................................... 618
17.2.11 IRIG-B time synchronization module IRIG-B......................................................................619
17.2.11.1 Introduction....................................................................................................................... 619
17.2.11.2 Design................................................................................................................................. 619
17.2.11.3 Encoding.............................................................................................................................619
17.2.11.4 TimeZoneAs1344.............................................................................................................. 620
17.2.11.5 Settings.............................................................................................................................. 620
17.2.11.6 Technical data................................................................................................................... 620
17.3 Dimensions................................................................................................................................ 621
17.3.1 Case with protective cover...................................................................................................621
17.3.2 Case without protective cover............................................................................................ 624

22 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
Table of contents

17.3.3 Flush mounting dimensions................................................................................................ 626


17.3.4 Side-by-side flush mounting dimensions......................................................................... 626
17.3.5 Wall mounting dimensions...................................................................................................627
17.4 Mounting alternatives............................................................................................................. 628
17.4.1 Flush mounting...................................................................................................................... 628
17.4.1.1 Overview.............................................................................................................................628
17.4.1.2 Mounting procedure for flush mounting.....................................................................628
17.4.2 Wall mounting.........................................................................................................................629
17.4.2.1 Overview.............................................................................................................................629
17.4.2.2 Mounting procedure for wall mounting.......................................................................629
17.4.2.3 How to reach the rear side of the IED.......................................................................... 629
17.4.3 19” panel rack mounting.......................................................................................................630
17.4.3.1 Overview.............................................................................................................................630
17.4.3.2 Mounting procedure for 19” panel rack mounting.....................................................631
17.4.4 Side-by-side 19” rack mounting...........................................................................................631
17.4.4.1 Overview............................................................................................................................. 631
17.4.4.2 Mounting procedure for side-by-side rack mounting...............................................632
17.4.4.3 IED mounted with a RHGS6 case...................................................................................632
17.4.5 Side-by-side flush mounting................................................................................................633
17.4.5.1 Overview.............................................................................................................................633
17.4.5.2 Mounting procedure for side-by-side flush mounting............................................. 634
17.5 Technical data...........................................................................................................................634
17.5.1 Enclosure................................................................................................................................. 634
17.5.2 Electrical safety...................................................................................................................... 635
17.5.3 Connection system................................................................................................................635
17.5.4 Influencing factors.................................................................................................................636
17.5.5 Type tests according to standard...................................................................................... 637

Section 18 Labels...........................................................................................................639
18.1 Labels on IED.............................................................................................................................639

Section 19 Connection diagrams................................................................................ 641

Section 20 Inverse time characteristics..................................................................... 643


20.1 Application................................................................................................................................ 643
20.2 Principle of operation............................................................................................................. 645
20.2.1 Mode of operation.................................................................................................................645
20.3 Inverse characteristics............................................................................................................650

Section 21 Glossary....................................................................................................... 677

Breaker protection REQ650 23


Technical manual
© Copyright 2017 ABB. All rights reserved
24
1MRK 505 384-UEN C Section 1
Introduction

Section 1 Introduction
1.1 This manual GUID-AB423A30-13C2-46AF-B7FE-A73BB425EB5F v19

The technical manual contains operation principle descriptions, and lists function blocks, logic
diagrams, input and output signals, setting parameters and technical data, sorted per
function. The manual can be used as a technical reference during the engineering phase,
installation and commissioning phase, and during normal service.

1.1.1 Presumptions for Technical Data GUID-1E949E38-E04D-4374-A086-912C25E9F93C v2

The technical data stated in this document are only valid under the following circumstances:

1. Main current transformers with 1 A or 2 A secondary rating are wired to the IED 1 A rated
CT inputs.
2. Main current transformer with 5 A secondary rating are wired to the IED 5 A rated CT
inputs.
3. CT and VT ratios in the IED are set in accordance with the associated main instrument
transformers. Note that for functions which measure an analogue signal which do not
have corresponding primary quantity the 1:1 ratio shall be set for the used analogue inputs
on the IED. Example of such functions are: HZPDIF, ROTIPHIZ and STTIPHIZ.
4. Parameter IBase used by the tested function is set equal to the rated CT primary current.
5. Parameter UBase used by the tested function is set equal to the rated primary phase-to-
phase voltage.
6. Parameter SBase used by the tested function is set equal to:
• √3 × IBase × UBase
7. The rated secondary quantities have the following values:
• Rated secondary phase current Ir is either 1 A or 5 A depending on selected TRM.
• Rated secondary phase-to-phase voltage Ur is within the range from 100 V to 120 V.
• Rated secondary power for three-phase system Sr = √3 × Ur × Ir
8. For operate and reset time testing, the default setting values of the function are used if
not explicitly stated otherwise.
9. During testing, signals with rated frequency have been injected if not explicitly stated
otherwise.

1.2 Intended audience GUID-C9B8127F-5748-4BEA-9E4F-CC762FE28A3A v11

This manual addresses system engineers and installation and commissioning personnel, who
use technical data during engineering, installation and commissioning, and in normal service.

The system engineer must have a thorough knowledge of protection systems, protection
equipment, protection functions and the configured functional logic in the IEDs. The
installation and commissioning personnel must have a basic knowledge in handling electronic
equipment.

Breaker protection REQ650 25


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 1 1MRK 505 384-UEN C
Introduction

1.3 Product documentation

1.3.1 Product documentation set GUID-3AA69EA6-F1D8-47C6-A8E6-562F29C67172 v16

Deinstalling & disposal


Planning & purchase

Decommissioning
Commissioning

Maintenance
Engineering

Operation
Installing
Engineering manual
Installation manual

Commissioning manual
Operation manual

Application manual

Technical manual

Communication
protocol manual
Cyber security
deployment guideline
IEC07000220-4-en.vsd
IEC07000220 V4 EN-US

Figure 1: The intended use of manuals throughout the product lifecycle


The engineering manual contains instructions on how to engineer the IEDs using the various
tools available within the PCM600 software. The manual provides instructions on how to set
up a PCM600 project and insert IEDs to the project structure. The manual also recommends a
sequence for the engineering of protection and control functions, as well as communication
engineering for IEC 61850.

The installation manual contains instructions on how to install the IED. The manual provides
procedures for mechanical and electrical installation. The chapters are organized in the
chronological order in which the IED should be installed.

The commissioning manual contains instructions on how to commission the IED. The manual
can also be used by system engineers and maintenance personnel for assistance during the
testing phase. The manual provides procedures for the checking of external circuitry and
energizing the IED, parameter setting and configuration as well as verifying settings by
secondary injection. The manual describes the process of testing an IED in a station which is
not in service. The chapters are organized in the chronological order in which the IED should be
commissioned. The relevant procedures may be followed also during the service and
maintenance activities.

The operation manual contains instructions on how to operate the IED once it has been
commissioned. The manual provides instructions for the monitoring, controlling and setting of
the IED. The manual also describes how to identify disturbances and how to view calculated
and measured power grid data to determine the cause of a fault.

26 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 1
Introduction

The application manual contains application descriptions and setting guidelines sorted per
function. The manual can be used to find out when and for what purpose a typical protection
function can be used. The manual can also provide assistance for calculating settings.

The technical manual contains operation principle descriptions, and lists function blocks, logic
diagrams, input and output signals, setting parameters and technical data, sorted per
function. The manual can be used as a technical reference during the engineering phase,
installation and commissioning phase, and during normal service.

The communication protocol manual describes the communication protocols supported by


the IED. The manual concentrates on the vendor-specific implementations.

The point list manual describes the outlook and properties of the data points specific to the
IED. The manual should be used in conjunction with the corresponding communication
protocol manual.

The cyber security deployment guideline describes the process for handling cyber security
when communicating with the IED. Certification, Authorization with role based access control,
and product engineering for cyber security related events are described and sorted by
function. The guideline can be used as a technical reference during the engineering phase,
installation and commissioning phase, and during normal service.

1.3.2 Document revision history GUID-BD82A13A-6FA0-4E33-BDBF-23B5A0CF968F v1

Document Date Product revision History


revision
- 2017–05 2.2.0 First release for product version 2.2
A 2017-10 2.2.1 Ethernet ports with RJ45 connector added.
enhancements/updates made to GENPDIF, ZMFPDIS and
ZMFCPDIS.
B 2018-03 2.2.1 Document enhancements and corrections
C 2019-05 2.2.1 PTP enhancements and corrections

1.3.3 Related documents GUID-94E8A5CA-BE1B-45AF-81E7-5A41D34EE112 v7

Documents related to REQ650 Document numbers


Application manual 1MRK 505 383-UEN
Commissioning manual 1MRK 505 385-UEN
Product guide 1MRK 505 386-BEN
Technical manual 1MRK 505 384-UEN
Type test certificate 1MRK 505 386-TEN

650 series manuals Document numbers


Operation manual 1MRK 500 128-UEN
Engineering manual 1MRK 511 420-UEN
Installation manual 1MRK 514 027-UEN
Communication protocol manual, DNP3 1MRK 511 413-UUS
Communication protocol manual, IEC 60870-5-103 1MRK 511 416-UEN
Communication protocol manual, IEC 61850 Edition 1 1MRK 511 414-UEN
Communication protocol manual, IEC 61850 Edition 2 1MRK 511 415-UEN
Table continues on next page

Breaker protection REQ650 27


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 1 1MRK 505 384-UEN C
Introduction

650 series manuals Document numbers


Communication protocol manual, LON 1MRK 511 417-UEN
Communication protocol manual, SPA 1MRK 511 418-UEN
Point list manual, DNP3 1MRK 511 419-UUS
Accessories guide IEC: 1MRK 514 012-UEN
ANSI: 1MRK 514 012-UUS
Cyber security deployment guideline 1MRK 511 421-UEN
Connection and Installation components 1MRK 513 003-BEN
Test system, COMBITEST 1MRK 512 001-BEN
Application guide, Communication set-up 1MRK 505 382-UEN

1.4 Document symbols and conventions

1.4.1 Symbols GUID-2945B229-DAB0-4F15-8A0E-B9CF0C2C7B15 v13

The electrical warning icon indicates the presence of a hazard which could
result in electrical shock.

The warning icon indicates the presence of a hazard which could result in
personal injury.

The caution hot surface icon indicates important information or warning about
the temperature of product surfaces.

Class 1 Laser product. Take adequate measures to protect the eyes and do not
view directly with optical instruments.

The caution icon indicates important information or warning related to the


concept discussed in the text. It might indicate the presence of a hazard which
could result in corruption of software or damage to equipment or property.

The information icon alerts the reader of important facts and conditions.

The tip icon indicates advice on, for example, how to design your project or
how to use a certain function.

Although warning hazards are related to personal injury, it is necessary to understand that
under certain operational conditions, operation of damaged equipment may result in

28 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 1
Introduction

degraded process performance leading to personal injury or death. It is important that the
user fully complies with all warning and cautionary notices.

1.4.2 Document conventions GUID-96DFAB1A-98FE-4B26-8E90-F7CEB14B1AB6 v8

• Abbreviations and acronyms in this manual are spelled out in the glossary. The glossary
also contains definitions of important terms.
• Push button navigation in the LHMI menu structure is presented by using the push button
icons.
For example, to navigate between the options, use and .
• HMI menu paths are presented in bold.
For example, select Main menu/Settings.
• LHMI messages are shown in Courier font.
For example, to save the changes in non-volatile memory, select Yes and press .
• Parameter names are shown in italics.
For example, the function can be enabled and disabled with the Operation setting.
• Each function block symbol shows the available input/output signal.
• the character ^ in front of an input/output signal name indicates that the signal
name may be customized using the PCM600 software.
• the character * after an input signal name indicates that the signal must be
connected to another function block in the application configuration to achieve a
valid application configuration.
• Dimensions are provided both in inches and millimeters. If it is not specifically mentioned
then the dimension is in millimeters.
• Logic diagrams describe the signal logic of the function block and are bordered by dashed
lines.
In a logic diagram, input and output signal paths are shown as lines that touch the outer
border of the diagram. Input signals are always on the left-hand side and output signals
are on the right-hand side.
Input and output signals can be configured using PCM600. They can be connected to the
inputs and outputs of other functions and to binary inputs and outputs. Examples of input
signals are BLKTR, BLOCK, and VTSZ. Examples of output signals are TRIP, START, STL1,
STL2, and STL3.
• Frames with a shaded area on the right-hand side represent setting parameters.
These parameters can only be set via the PST or LHMI. Their values are high (1) only
when the corresponding setting parameter is set to the symbolic value specified
within the frame. Example is the signal Timer tPP=On. Their logical values
correspond automatically to the selected setting value.
• Internal signals are illustrated graphically and end approximately 2 mm from the
frame edge. If an internal signal path cannot be drawn with a continuous line, the
same signal name is used where the signal should continue, see figure 2 and figure 3.
Example of the internal signal is BLK.
• Signal paths that extend beyond the logic diagram and continue in another diagram
will be approximately 2 mm from the frame edge, see figure 3 and figure 4. Examples
are STNDL1N, STNDL2N, STNDL3N, STNDL1L2, STNDL2L3, and STNDL3L1.

Breaker protection REQ650 29


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 1 1MRK 505 384-UEN C
Introduction

STZMPP
OR
STCND

AND STNDL1L2
L1L2

STNDL2L3
L2L3 AND

L3L1 AND STNDL3L1

AND STNDL1N
L1N

AND STNDL2N
L2N

STNDL3N
L3N AND

OR STPE

OR
VTSZ STND
OR AND
BLOCK
BLOCFUNC BLK

99000557-2.vsd
IEC99000557-TIFF V3 EN-US

Figure 2: Logic diagram example with intermediate output signals

IEC00000488-TIFF V1 EN-US

Figure 3: Logic diagram example with intermediate input signals

30 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 1
Introduction

Timer tPP=On
STZMPP AND tPP
AND
t

BLOCFUNC
OR OR
tPE
t
AND
Timer tPE=On AND
STZMPE 15ms
BLKTR AND t
TRIP
BLK OR

STL1 AND TRL1

STL2 AND TRL2

STL3 AND TRL3

IEC09000887-3-en.vsdx

IEC09000887 V3 EN-US

Figure 4: Logic diagram example with a parameter input

Illustrations are used as an example and might show other products than the
one the manual describes. The example that is illustrated is still valid.

1.5 IEC 61850 edition 1 / edition 2 mapping GUID-C5133366-7260-4C47-A975-7DBAB3A33A96 v7

Function block names are used in ACT and PST to identify functions. Respective function block
names of Edition 1 logical nodes and Edition 2 logical nodes are shown in the table below.

Table 1: IEC 61850 edition 1 / edition 2 mapping


Function block name Edition 1 logical nodes Edition 2 logical nodes
AGSAL AGSAL AGSAL
SECLLN0
ALMCALH ALMCALH ALMCALH
ALTIM - ALTIM
ALTMS - ALTMS
ALTRK - ALTRK
BRCPTOC BRCPTOC BRCPTOC
BTIGAPC B16IFCVI BTIGAPC
CCPDSC CCRPLD CCPDSC
CCRBRF CCRBRF CCRBRF
CCSSPVC CCSRDIF CCSSPVC
CMMXU CMMXU CMMXU
Table continues on next page

Breaker protection REQ650 31


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 1 1MRK 505 384-UEN C
Introduction

Function block name Edition 1 logical nodes Edition 2 logical nodes


CMSQI CMSQI CMSQI
CVGAPC GF2LLN0 GF2MMXN
GF2MMXN GF2PHAR
GF2PHAR GF2PTOV
GF2PTOV GF2PTUC
GF2PTUC GF2PTUV
GF2PTUV GF2PVOC
GF2PVOC PH1PTRC
PH1PTRC
CVMMXN CVMMXN CVMMXN
DPGAPC DPGGIO DPGAPC
DRPRDRE DRPRDRE DRPRDRE
EF4PTOC EF4LLN0 EF4PTRC
EF4PTRC EF4RDIR
EF4RDIR GEN4PHAR
GEN4PHAR PH1PTOC
PH1PTOC
EFPIOC EFPIOC EFPIOC
ETPMMTR ETPMMTR ETPMMTR
FUFSPVC SDDRFUF FUFSPVC
HZPDIF HZPDIF HZPDIF
INDCALH INDCALH INDCALH
ITBGAPC IB16FCVB ITBGAPC
L4UFCNT L4UFCNT L4UFCNT
LCPTTR LCPTTR LCPTTR
LD0LLN0 LLN0 LLN0
LDLPSCH LDLPDIF LDLPSCH
LFPTTR LFPTTR LFPTTR
LMBRFLO LMBRFLO LMBRFLO
LOVPTUV LOVPTUV LOVPTUV
LPHD LPHD LPHD
LT3CPDIF LT3CPDIF LT3CGAPC
LT3CPDIF
LT3CPHAR
LT3CPTRC
MVGAPC MVGGIO MVGAPC
NS4PTOC EF4LLN0 EF4PTRC
EF4PTRC EF4RDIR
EF4RDIR PH1PTOC
GEN4PHAR
PH1PTOC
OC4PTOC OC4LLN0 GEN4PHAR
GEN4PHAR PH3PTOC
PH3PTOC PH3PTRC
PH3PTRC
OV2PTOV GEN2LLN0 OV2PTOV
OV2PTOV PH1PTRC
PH1PTRC
PCFCNT PCGGIO PCFCNT
PHPIOC PHPIOC PHPIOC
QCBAY QCBAY BAY/LLN0
Table continues on next page

32 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 1
Introduction

Function block name Edition 1 logical nodes Edition 2 logical nodes


QCRSV QCRSV QCRSV
RCHLCCH RCHLCCH RCHLCCH
REFPDIF REFPDIF REFPDIF
ROV2PTOV GEN2LLN0 PH1PTRC
PH1PTRC ROV2PTOV
ROV2PTOV
SCHLCCH SCHLCCH SCHLCCH
SCILO SCILO SCILO
SCSWI SCSWI SCSWI
SESRSYN RSY1LLN0 AUT1RSYN
AUT1RSYN MAN1RSYN
MAN1RSYN SYNRSYN
SYNRSYN
SLGAPC SLGGIO SLGAPC
SMBRREC SMBRREC SMBRREC
SMPPTRC SMPPTRC SMPPTRC
SP16GAPC SP16GGIO SP16GAPC
SPC8GAPC SPC8GGIO SPC8GAPC
SPGAPC SPGGIO SPGAPC
SSCBR SSCBR SSCBR
SSIMG SSIMG SSIMG
SSIML SSIML SSIML
SXCBR SXCBR SXCBR
SXSWI SXSWI SXSWI
T3WPDIF T3WPDIF T3WGAPC
T3WPDIF
T3WPHAR
T3WPTRC
TEIGAPC TEIGGIO TEIGAPC
TEILGAPC TEILGGIO TEILGAPC
TMAGAPC TMAGGIO TMAGAPC
TRPTTR TRPTTR TRPTTR
UV2PTUV GEN2LLN0 PH1PTRC
PH1PTRC UV2PTUV
UV2PTUV
VMMXU VMMXU VMMXU
VMSQI VMSQI VMSQI
VNMMXU VNMMXU VNMMXU
VSGAPC VSGGIO VSGAPC
WRNCALH WRNCALH WRNCALH
ZCLCPSCH ZCLCPLAL ZCLCPSCH
ZCPSCH ZCPSCH ZCPSCH
Table continues on next page

Breaker protection REQ650 33


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 1 1MRK 505 384-UEN C
Introduction

Function block name Edition 1 logical nodes Edition 2 logical nodes


ZCRWPSCH ZCRWPSCH ZCRWPSCH
ZCVPSOF ZCVPSOF ZCVPSOF
ZMFPDIS ZMFLLN0 PSFPDIS
PSFPDIS PSFPDIS
ZMFPDIS ZMFPDIS
ZMFPTRC ZMFPTRC
ZMMMXU ZMMMXU

34 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 2
Available functions

Section 2 Available functions


GUID-F5776DD1-BD04-4872-BB89-A0412B4B5CC3 v1

The following tables list all the functions available in the IED. Those functions
that are not exposed to the user or do not need to be configured are not
described in this manual.

2.1 Back-up protection functions GUID-A8D0852F-807F-4442-8730-E44808E194F0 v15

IEC 61850 or ANSI Function description Breaker


function name
REQ650 (B11)
Current protection
PHPIOC 50 Instantaneous phase overcurrent protection 1
OC4PTOC 51_671) Directional phase overcurrent protection, four steps 1

EFPIOC 50N Instantaneous residual overcurrent protection 1


EF4PTOC 51N Directional residual overcurrent protection, four steps 1
67N2)
NS4PTOC 46I2 Four step directional negative phase sequence overcurrent protection 1
LCPTTR 26 Thermal overload protection, one time constant, Celsius 1
LFPTTR 26 Thermal overload protection, one time constant, Fahrenheit 1
CCRBRF 50BF Breaker failure protection 1
STBPTOC 50STB Stub protection 1
CCPDSC 52PD Pole discordance protection 1
BRCPTOC 46 Broken conductor check 1

Voltage protection
UV2PTUV 27 Two step undervoltage protection 1
OV2PTOV 59 Two step overvoltage protection 1
ROV2PTOV 59N Two step residual overvoltage protection 1
LOVPTUV 27 Loss of voltage check 1

1) 67 requires voltage
2) 67N requires voltage

Breaker protection REQ650 35


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 2 1MRK 505 384-UEN C
Available functions

2.2 Control and monitoring functions GUID-E3777F16-0B76-4157-A3BF-0B6B978863DE v19

IEC 61850 or ANSI Function description Breaker


function name
REQ650 (B11)
Control
SESRSYN 25 Synchrocheck, energizing check and synchronizing 1
SMBRREC 79 Autorecloser 1
QCBAY Bay control 1
LOCREM Handling of LR-switch positions 1
LOCREMCTRL LHMI control of PSTO 1
SXCBR Circuit breaker 3
SCILO Interlocking 1
SCSWI Switch controller 5
SXSWI Circuit switch 3
XLNPROXY Proxy for signals from switching device via GOOSE 4
SLGAPC Logic rotating switch for function selection and LHMI presentation 15
VSGAPC Selector mini switch 30
DPGAPC Generic communication function for Double Point indication 16
SPC8GAPC Single point generic control function 8 signals 5
AUTOBITS Automation bits, command function for DNP3.0 3
SINGLECMD Single command, 16 signals 4
I103CMD Function commands for IEC 60870-5-103 1
I103GENCMD Function commands generic for IEC 60870-5-103 50
I103POSCMD IED commands with position and select for IEC 60870-5-103 50
I103POSCMDV IED direct commands with position for IEC 60870-5-503 50
I103IEDCMD IED commands for IEC 60870-5-103 1
I103USRCMD Function commands user defined for IEC 60870-5-103 4
Secondary system supervision
CCSSPVC 87 Current circuit supervison 1
FUFSPVC Fuse failure supervision 1
Logic
SMPPTRC 94 Tripping logic 6
SMAGAPC General start matrix block 6
STARTCOMB Start combinator 32
TMAGAPC Trip matrix logic 12
ALMCALH Logic for group alarm 5
WRNCALH Logic for group warning 5
INDCALH Logic for group indication 5
AND, GATE, INV, Basic configurable logic blocks (see Table 2) 40–420
LLD, OR,
PULSETIMER,
RSMEMORY,
SRMEMORY,
TIMERSET, XOR
FXDSIGN Fixed signal function block 1
Table continues on next page

36 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 2
Available functions

IEC 61850 or ANSI Function description Breaker


function name
REQ650 (B11)
B16I Boolean to integer conversion, 16 bit 18
BTIGAPC Boolean to integer conversion with logical node representation, 16 16
bit
IB16 Integer to Boolean 16 conversion 18
ITBGAPC Integer to Boolean 16 conversion with Logic Node representation 16
TEIGAPC Elapsed time integrator with limit transgression and overflow 12
supervision
INTCOMP Comparator for integer inputs 30
REALCOMP Comparator for real inputs 30

Table 2: Total number of instances for basic configurable logic blocks


Basic configurable logic block Total number of instances
AND 280
GATE 40
INV 420
LLD 40
OR 298
PULSETIMER 40
RSMEMORY 40
SRMEMORY 40
TIMERSET 60
XOR 40

IEC 61850 or ANSI Function description Breaker


function name
REQ650 (B11)
Monitoring
CVMMXN Power system measurement 6
CMMXU Current measurement 10
VMMXU Voltage measurement 6
phase-phase
CMSQI Current sequence 6
measurement
VMSQI Voltage sequence 6
measurement
VNMMXU Voltage measurement 6
phase-earth
AISVBAS General service value 1
presentation of analog
inputs
SSIMG 63 Insulation supervision for 21
gas medium
SSIML 71 Insulation supervision for 3
liquid medium
Table continues on next page

Breaker protection REQ650 37


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 2 1MRK 505 384-UEN C
Available functions

IEC 61850 or ANSI Function description Breaker


function name
REQ650 (B11)
SSCBR Circuit breaker condition 3
monitoring
EVENT Event function 20
DRPRDRE, Disturbance report 1
A1RADR-A4RADR,
B1RBDR-
B22RBDR
SPGAPC Generic communication 64
function for single point
indication
SP16GAPC Generic communication 16
function for single point
indication 16 inputs
MVGAPC Generic communication 24
function for measured
values
BINSTATREP Logical signal status report 3
RANGE_XP Measured value expander 66
block
I103MEAS Measurands for IEC 1
60870-5-103
I103MEASUSR Measurands user defined 3
signals for IEC 60870-5-103
I103AR Function status auto- 1
recloser for IEC 60870-5-103
I103EF Function status earth-fault 1
for IEC 60870-5-103
I103FLTPROT Function status fault 1
protection for IEC
60870-5-103
I103IED IED status for IEC 1
60870-5-103
I103SUPERV Supervision status for IEC 1
60870-5-103
I103USRDEF Status for user defined 20
signals for IEC 60870-5-103
L4UFCNT Event counter with limit 30
supervision
TEILGAPC Running hour meter 6
Metering
PCFCNT Pulse-counter logic 16
ETPMMTR Function for energy 6
calculation and demand
handling

38 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 2
Available functions

2.3 Communication GUID-5F144B53-B9A7-4173-80CF-CD4C84579CB5 v17

IEC 61850 or ANSI Function description Breaker


function name
REQ650 (B11)
Station communication
LONSPA, SPA SPA communication protocol 1
ADE LON communciation protocol 1
HORZCOMM Network variables via LON 1
PROTOCOL Operation selection between SPA and IEC 60870-5-103 for SLM 1
RS485PROT Operation selection for RS485 1
RS485GEN RS485 1
DNPGEN DNP3.0 communication general protocol 1
CHSERRS485 DNP3.0 for EIA-485 communication protocol 1
CH1TCP, CH2TCP, DNP3.0 for TCP/IP communication protocol 1
CH3TCP, CH4TCP
CHSEROPT DNP3.0 for TCP/IP and EIA-485 communication protocol 1
MSTSER DNP3.0 serial master 1
MST1TCP, DNP3.0 for TCP/IP communication protocol 1
MST2TCP,
MST3TCP,
MST4TCP
DNPFREC DNP3.0 fault records for TCP/IP and EIA-485 communication 1
protocol
IEC 61850-8-1 IEC 61850 1
GOOSEINTLKRCV Horizontal communication via GOOSE for interlocking 59
GOOSEBINRCV GOOSE binary receive 16
GOOSEDPRCV GOOSE function block to receive a double point value 64
GOOSEINTRCV GOOSE function block to receive an integer value 32
GOOSEMVRCV GOOSE function block to receive a measurand value 60
GOOSESPRCV GOOSE function block to receive a single point value 64
GOOSEXLNRCV GOOSE function block to receive a switching device 9
MULTICMDRCV/ Multiple command and transmit 60/10
MULTICMDSND
OPTICAL103 IEC 60870-5-103 Optical serial communication 1
RS485103 IEC 60870-5-103 serial communication for RS485 1
AGSAL Generic security application component 1
LD0LLN0 IEC 61850 LD0 LLN0 1
SYSLLN0 IEC 61850 SYS LLN0 1
LPHD Physical device information 1
PCMACCS IED configuration protocol 1
SECALARM Component for mapping security events on protocols such as 1
DNP3 and IEC103
FSTACCS Field service tool access 1
Table continues on next page

Breaker protection REQ650 39


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 2 1MRK 505 384-UEN C
Available functions

IEC 61850 or ANSI Function description Breaker


function name
REQ650 (B11)
IEC 61850-9-2 Process bus communication, 4 merging units 1-P31
ACTIVLOG Activity logging 1
ALTRK Service tracking 1
PRP IEC 62439-3 Parallel redundancy protocol 1-P23
HSR IEC 62439-3 High-availability seamless redundancy 1-P24
PTP Precision time protocol 1
FRONTSTATUS Access point diagnostic for front Ethernet port 1
SCHLCCH Access point diagnostic for non-redundant Ethernet port 4
RCHLCCH Access point diagnostic for redundant Ethernet ports 2
DHCP DHCP configuration for front access point 1
QUALEXP IEC 61850 quality expander 32

2.4 Basic IED functions GUID-C8F0E5D2-E305-4184-9627-F6B5864216CA v13

Table 3: Basic IED functions


IEC 61850 or function Description
name
INTERRSIG Self supervision with internal event list
TIMESYNCHGEN Time synchronization module
BININPUT, Time synchronization
SYNCHCAN,
SYNCHGPS,
SYNCHCMPPS,
SYNCHLON,
SYNCHPPH,
SYNCHPPS, SNTP,
SYNCHSPA
TIMEZONE Time synchronization
IRIG-B Time synchronization
SETGRPS Number of setting groups
ACTVGRP Parameter setting groups
TESTMODE Test mode functionality
CHNGLCK Change lock function
SMBI Signal matrix for binary inputs
SMBO Signal matrix for binary outputs
SMAI1 - SMAI12 Signal matrix for analog inputs
3PHSUM Summation block 3 phase
ATHSTAT Authority status
ATHCHCK Authority check
AUTHMAN Authority management
FTPACCS FTP access with password
ALTMS Time master supervision
ALTIM Time management
COMSTATUS Protocol diagnostic

40 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 2
Available functions

Table 4: Local HMI functions


IEC 61850 or function ANSI Description
name
LHMICTRL Local HMI signals
LANGUAGE Local human machine language
SCREEN Local HMI Local human machine screen behavior
FNKEYTY1–FNKEYTY5 Parameter setting function for HMI in PCM600
FNKEYMD1–
FNKEYMD5
LEDGEN General LED indication part for LHMI
OPENCLOSE_LED LHMI LEDs for open and close keys
GRP1_LED1– Basic part for CP HW LED indication module
GRP1_LED15
GRP2_LED1–
GRP2_LED15
GRP3_LED1–
GRP3_LED15

Breaker protection REQ650 41


Technical manual
© Copyright 2017 ABB. All rights reserved
42
1MRK 505 384-UEN C Section 3
Analog inputs

Section 3 Analog inputs SEMOD55010-1 v3

3.1 Introduction SEMOD55003-5 v11

Analog input channels must be configured and set properly in order to get correct
measurement results and correct protection operations. For power measuring, all directional
and differential functions, the directions of the input currents must be defined in order to
reflect the way the current transformers are installed/connected in the field ( primary and
secondary connections ). Measuring and protection algorithms in the IED use primary system
quantities. Setting values are in primary quantities as well and it is important to set the data
about the connected current and voltage transformers properly.

An AISVBAS reference PhaseAngleRef can be defined to facilitate service values reading. This
analog channel's phase angle will always be fixed to zero degrees and remaining analog
channel's phase angle information will be shown in relation to this analog input. During testing
and commissioning of the IED, the reference channel can be changed to facilitate testing and
service values reading.

The IED has the ability to receive analog values from primary equipment, that
are sampled by Merging units (MU) connected to a process bus, via the IEC
61850-9-2 LE protocol.

The availability of VT inputs depends on the ordered transformer input module


(TRM) type.

3.2 Function block SEMOD116577-1 v5

The hardware channels appear in the signal matrix tool (SMT) and in ACT when
a TRM is included in the configuration with the hardware configuration tool. In
the SMT or the ACT, they can be mapped to the desired virtual input (SMAI) of
the IED and used internally in the configuration.

3.3 Signals
PID-3923-OUTPUTSIGNALS v7

Table 5: TRM_7I_5U Output signals


Name Type Description
STATUS BOOLEAN Analogue input module status
CH1(I) STRING Analogue current input 1
CH2(I) STRING Analogue current input 2
CH3(I) STRING Analogue current input 3
CH4(I) STRING Analogue current input 4
CH5(I) STRING Analogue current input 5
Table continues on next page

Breaker protection REQ650 43


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 3 1MRK 505 384-UEN C
Analog inputs

Name Type Description


CH6(I) STRING Analogue current input 6
CH7(I) STRING Analogue current input 7
CH8(U) STRING Analogue voltage input 8
CH9(U) STRING Analogue voltage input 9
CH10(U) STRING Analogue voltage input 10
CH11(U) STRING Analogue voltage input 11
CH12(U) STRING Analogue voltage input 12

PID-3924-OUTPUTSIGNALS v7

Table 6: TRM_9I_3U Output signals


Name Type Description
STATUS BOOLEAN Analogue input module status
CH1(I) STRING Analogue current input 1
CH2(I) STRING Analogue current input 2
CH3(I) STRING Analogue current input 3
CH4(I) STRING Analogue current input 4
CH5(I) STRING Analogue current input 5
CH6(I) STRING Analogue current input 6
CH7(I) STRING Analogue current input 7
CH8(I) STRING Analogue current input 8
CH9(I) STRING Analogue current input 9
CH10(U) STRING Analogue voltage input 10
CH11(U) STRING Analogue voltage input 11
CH12(U) STRING Analogue voltage input 12

PID-6598-OUTPUTSIGNALS v6

Table 7: TRM_10I_2U Output signals


Name Type Description
STATUS BOOLEAN Analogue input module status
CH1(I) STRING Analogue current input 1
CH2(I) STRING Analogue current input 2
CH3(I) STRING Analogue current input 3
CH4(I) STRING Analogue current input 4
CH5(I) STRING Analogue current input 5
CH6(I) STRING Analogue current input 6
CH7(I) STRING Analogue current input 7
CH8(I) STRING Analogue current input 8
CH9(I) STRING Analogue current input 9
CH10(I) STRING Analogue current input 10
CH11(U) STRING Analogue voltage input 11
CH12(U) STRING Analogue voltage input 12

44 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 3
Analog inputs

3.4 Settings
SEMOD129840-4 v2
Dependent on ordered IED type.
PID-4153-SETTINGS v8

Table 8: AISVBAS Non group settings (basic)


Name Values (Range) Unit Step Default Description
PhaseAngleRef TRM40-Ch1 - Ch12 - - TRM40-Ch1 Reference channel
TRM41-Ch1 - Ch12 for phase angle
MU1-L1I - L4I presentation
MU1-L1U - L4U
MU2-L1I - L4I
MU2-L1U - L4U
MU3-L1I - L4I
MU3-L1U - L4U
MU4-L1I - L4I
MU4-L1U - L4U
MU5-L1I - L4I
MU5-L1U - L4U
MU6-L1I - L4I
MU6-L1U - L4U
MU7-L1I - L4I
MU7-L1U - L4U
MU8-L1I - L4I
MU8-L1U - L4U
MU9-L1I - L4I
MU9-L1U - L4U
MU10-L1I - L4I
MU10-L1U - L4U
MU11-L1I - L4I
MU11-L1U - L4U
MU12-L1I - L4I
MU12-L1U - L4U

GUID-72A8BEE0-2430-4C94-A1E0-9B6A0D149FE2 v1

All the visible parameter selections that are visible are not supported by the
650-series IED.

PID-3923-SETTINGS v7

Table 9: TRM_7I_5U Non group settings (basic)


Name Values (Range) Unit Step Default Description
CTStarPoint1 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec1 1 - 10 A 1 1 Rated CT secondary current
CTprim1 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint2 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec2 1 - 10 A 1 1 Rated CT secondary current
CTprim2 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint3 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec3 1 - 10 A 1 1 Rated CT secondary current
CTprim3 1 - 99999 A 1 3000 Rated CT primary current
Table continues on next page

Breaker protection REQ650 45


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 3 1MRK 505 384-UEN C
Analog inputs

Name Values (Range) Unit Step Default Description


CTStarPoint4 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec4 1 - 10 A 1 1 Rated CT secondary current
CTprim4 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint5 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec5 1 - 10 A 1 1 Rated CT secondary current
CTprim5 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint6 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec6 1 - 10 A 1 1 Rated CT secondary current
CTprim6 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint7 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec7 1 - 10 A 1 1 Rated CT secondary current
CTprim7 1 - 99999 A 1 3000 Rated CT primary current
VTsec8 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim8 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec9 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim9 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec10 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim10 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec11 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim11 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec12 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim12 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage

PID-3924-SETTINGS v7

Table 10: TRM_9I_3U Non group settings (basic)


Name Values (Range) Unit Step Default Description
CTStarPoint1 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec1 1 - 10 A 1 1 Rated CT secondary current
CTprim1 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint2 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec2 1 - 10 A 1 1 Rated CT secondary current
CTprim2 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint3 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec3 1 - 10 A 1 1 Rated CT secondary current
CTprim3 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint4 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec4 1 - 10 A 1 1 Rated CT secondary current
Table continues on next page

46 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 3
Analog inputs

Name Values (Range) Unit Step Default Description


CTprim4 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint5 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec5 1 - 10 A 1 1 Rated CT secondary current
CTprim5 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint6 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec6 1 - 10 A 1 1 Rated CT secondary current
CTprim6 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint7 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec7 1 - 10 A 1 1 Rated CT secondary current
CTprim7 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint8 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec8 1 - 10 A 1 1 Rated CT secondary current
CTprim8 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint9 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec9 1 - 10 A 1 1 Rated CT secondary current
CTprim9 1 - 99999 A 1 3000 Rated CT primary current
VTsec10 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim10 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec11 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim11 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec12 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim12 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage

PID-6598-SETTINGS v6

Table 11: TRM_10I_2U Non group settings (basic)


Name Values (Range) Unit Step Default Description
CTStarPoint1 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec1 1 - 10 A 1 1 Rated CT secondary current
CTprim1 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint2 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec2 1 - 10 A 1 1 Rated CT secondary current
CTprim2 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint3 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec3 1 - 10 A 1 1 Rated CT secondary current
CTprim3 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint4 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
Table continues on next page

Breaker protection REQ650 47


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 3 1MRK 505 384-UEN C
Analog inputs

Name Values (Range) Unit Step Default Description


CTsec4 1 - 10 A 1 1 Rated CT secondary current
CTprim4 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint5 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec5 1 - 10 A 1 1 Rated CT secondary current
CTprim5 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint6 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec6 1 - 10 A 1 1 Rated CT secondary current
CTprim6 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint7 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec7 1 - 10 A 1 1 Rated CT secondary current
CTprim7 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint8 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec8 1 - 10 A 1 1 Rated CT secondary current
CTprim8 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint9 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec9 1 - 10 A 1 1 Rated CT secondary current
CTprim9 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint10 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTsec10 1 - 10 A 1 1 Rated CT secondary current
CTprim10 1 - 99999 A 1 3000 Rated CT primary current
VTsec11 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim11 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec12 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim12 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage

3.5 Monitored data


PID-6531-MONITOREDDATA v3

Table 12: AISVBAS Monitored data


Name Type Values (Range) Unit Description
Status INTEGER 0=Ok - Service value status
1=Error
2=AngRefLow
3=Uncorrelated

PID-3923-MONITOREDDATA v6

Table 13: TRM_7I_5U Monitored data


Name Type Values (Range) Unit Description
STATUS BOOLEAN 0=Ok - Analogue input module status
1=Error

48 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 3
Analog inputs

PID-3924-MONITOREDDATA v6

Table 14: TRM_9I_3U Monitored data


Name Type Values (Range) Unit Description
STATUS BOOLEAN 0=Ok - Analogue input module status
1=Error

PID-6598-MONITOREDDATA v6

Table 15: TRM_10I_2U Monitored data


Name Type Values (Range) Unit Description
STATUS BOOLEAN 0=Ok - Analogue input module status
1=Error

3.6 Operation principle SEMOD55028-5 v9

The direction of a measured current depends on the connection of the CT. The main CTs are
typically star connected and can be connected with the star point towards the object or away
from the object. This information must be set in the IED.

Once the CT direction settings is correctly entered the internal IED convention of the
directionality is defined as follows:

• Positive value of current or power means that the quantity has the direction into the
protected object.
• Negative value of current or power means that the quantity has the direction out from the
protected object.

For directional functions the directional conventions are defined as follows (see Figure 5)

• Forward means the direction is into the object.


• Reverse means the direction is out from the object.

Definition of direction Definition of direction


for directional functions for directional functions
Reverse Forward Forward Reverse
Protected Object
Line, transformer, etc
e.g. P, Q, I e.g. P, Q, I
Measured quantity is Measured quantity is
positive when flowing positive when flowing
towards the object towards the object

Set parameter Set parameter


CTStarPoint CTStarPoint
Correct Setting is Correct Setting is
"ToObject" "FromObject"

en05000456.vsd
IEC05000456 V1 EN-US

Figure 5: Internal convention of the directionality in the IED


If the settings of the primary CT is correct, that is CTStarPoint set as FromObject or ToObject
according to the plant condition, then a positive quantity always flows towards the protected
object, and a Forward direction always looks towards the protected object.

Breaker protection REQ650 49


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 3 1MRK 505 384-UEN C
Analog inputs

The settings of the IED is performed in primary values. The ratios of the main CTs and VTs are,
therefore, basic data for the IED. The user has to set the rated secondary and primary currents
and voltages of the CTs and VTs to provide the IED with their rated ratios.

The CT and VT ratio and the name on respective channel is done under IED Configuration/HW
Configuration/ADM in the Parameter Settings Tool or under Main menu/Configuration/
Analog modules in the HMI.

3.7 Technical data SEMOD55412-1 v1

M16988-1 v11

Table 16: TRM - Energizing quantities, rated values and limits for protection transformer
Description Value
Frequency
Rated frequency fr 50/60 Hz

Operating range fr ± 10%

Current inputs
Rated current Ir 1 or 5 A

Operating range (0-100) x Ir

Thermal withstand 100 × Ir for 1 s *)


30 × Ir for 10 s
10 × Ir for 1 min
4 × Ir continuously

Dynamic withstand 250 × Ir one half wave

Burden < 20 mVA at Ir = 1 A


< 150 mVA at Ir = 5 A

*) max. 350 A for 1 s when COMBITEST test switch is included.


Voltage inputs **)
Rated voltage Ur 110 or 220 V

Operating range 0 - 340 V


Thermal withstand 450 V for 10 s
420 V continuously
Burden < 20 mVA at 110 V
< 80 mVA at 220 V
**) all values for individual voltage inputs
Note! All current and voltage data are specified as RMS values at rated frequency

SEMOD53376-2 v6

Table 17: CT and VT circuit connectors


Connector type Rated voltage and current Maximum conductor area
Screw compression type 250 V AC, 20 A 4 mm2 (AWG12)
2 x 2.5 mm2 (2 x AWG14)
Terminal blocks suitable for ring lug 250 V AC, 20 A 4 mm2 (AWG12)
terminals

50 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 4
Binary input and output modules

Section 4 Binary input and output modules


4.1 Binary input

4.1.1 Binary input debounce filter GUID-AE43976C-E966-484C-AF39-89B2B12F56DC v5

The debounce filter eliminates bounces and short disturbances on a binary input.

A time counter is used for filtering. The time counter is increased once in a millisecond when a
binary input is high, or decreased when a binary input is low. A new debounced binary input
signal is forwarded when the time counter reaches the set DebounceTime value and the
debounced input value is high or when the time counter reaches 0 and the debounced input
value is low. The default setting of DebounceTime is 1 ms.

The binary input ON-event gets the time stamp of the first rising edge, after which the counter
does not reach 0 again. The same happens when the signal goes down to 0 again.

4.1.2 Oscillation filter GUID-41B89E6F-50C3-44BF-9171-3CC82EB5CA15 v4

Binary input wiring can be very long in substations and there are electromagnetic fields from
for example nearby breakers. An oscillation filter is used to reduce the disturbance from the
system when a binary input starts oscillating.

An oscillation counter counts the debounced signal state changes during 1 s. If the counter
value is greater than the set value OscBlock, the input signal is blocked. The input signal is
ignored until the oscillation counter value during 1 s is below the set value OscRelease.

4.1.3 Settings
GUID-07348953-4A72-444B-A31A-030ABEA8E0C4 v1

OscBlock must always be set to a value greater than OscRelease. If this is not
done, oscillation detection will not function correctly, and the resulting
behaviour will be undefined.

4.1.3.1 Setting parameters for binary input modules


PID-3473-SETTINGS v2

Table 18: BIM Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - On Operation Off/On
On
DebounceTime 0.001 - 0.020 s 0.001 0.001 Debounce time for binary inputs
OscBlock 1 - 40 Hz 1 40 Oscillation block limit
OscRelease 1 - 30 Hz 1 30 Oscillation release limit

Breaker protection REQ650 51


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 4 1MRK 505 384-UEN C
Binary input and output modules

4.1.3.2 Setting parameters for binary input/output module


PID-4050-SETTINGS v2

Table 19: IOMIN Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - On Binary input/output module in
On operation (On) or not (Off)
DebounceTime 0.001 - 0.020 s 0.001 0.001 Debounce time for binary inputs
OscBlock 1 - 40 Hz 1 40 Oscillation block limit
OscRelease 1 - 30 Hz 1 30 Oscillation release limit

52 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 5
Local Human-Machine-Interface LHMI

Section 5 Local Human-Machine-Interface


LHMI
5.1 Local HMI screen behaviour

5.1.1 Identification
GUID-84392EFF-4D3F-4A67-A6ED-34C6E98574D6 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Local HMI screen behaviour SCREEN - -

5.1.2 Settings

5.2 Local HMI signals

5.2.1 Identification
GUID-03AB7AEE-87D3-4F3C-B6B9-B1EB1B538E38 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Local HMI signals LHMICTRL - -

5.2.2 Function block GUID-A8AC51E9-5BD7-4A80-9576-4816F14DD08D v2

LHMICTRL
CLRLEDS HMI-ON
RED-S
YELLOW-S
YELLOW-F
CLRPULSE
LEDSCLRD

IEC09000320-1-en.vsd
IEC09000320 V1 EN-US

Figure 6: LHMICTRL function block

5.2.3 Signals
PID-3992-INPUTSIGNALS v6

Table 20: LHMICTRL Input signals


Name Type Default Description
CLRLEDS BOOLEAN 0 Input to clear the LCD-HMI LEDs

Breaker protection REQ650 53


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 5 1MRK 505 384-UEN C
Local Human-Machine-Interface LHMI

PID-3992-OUTPUTSIGNALS v6

Table 21: LHMICTRL Output signals


Name Type Description
HMI-ON BOOLEAN Backlight of the LCD display is active
RED-S BOOLEAN Red LED on the LCD-HMI is steady
YELLOW-S BOOLEAN Yellow LED on the LCD-HMI is steady
YELLOW-F BOOLEAN Yellow LED on the LCD-HMI is flashing
CLRPULSE BOOLEAN A pulse is provided when the LEDs on the LCD-HMI are
cleared
LEDSCLRD BOOLEAN Active when the LEDs on the LCD-HMI are not active

5.3 Basic part for LED indication module

5.3.1 Identification
GUID-6E36C0BC-F284-4C88-A4A8-9535D3BE8B14 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Basic part for LED indication module LEDGEN - -
Basic part for LED indication HW GRP1_LED1 - - -
module GRP1_LED15

GRP2_LED1 -
GRP2_LED15

GRP3_LED1 -
GRP3_LED15

5.3.2 Function block GUID-BDB5797F-F27E-4FEE-9FDB-1C9E2F572BB6 v3

LEDGEN
BLOCK NEWIND
RESET ACK

IEC09000321-1-en.vsd
IEC09000321 V1 EN-US

Figure 7: LEDGEN function block

GRP1_LED1
^HM1L01R
^HM1L01Y
^HM1L01G
IEC09000322 V1 EN-US

Figure 8: GRP1_LED1 function block


The GRP1_LED1 function block is an example. The 15 LEDs in each of the three groups have a
similar function block.

54 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 5
Local Human-Machine-Interface LHMI

5.3.3 Signals
PID-4114-INPUTSIGNALS v5

Table 22: LEDGEN Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Input to block the operation of the LEDs
RESET BOOLEAN 0 Input to acknowledge/reset the indication LEDs

PID-4114-OUTPUTSIGNALS v5

Table 23: LEDGEN Output signals


Name Type Description
NEWIND BOOLEAN New indication signal if any LED indication input is set
ACK BOOLEAN A pulse is provided when the LEDs are acknowledged

PID-1697-INPUTSIGNALS v18

Table 24: GRP1_LED1 Input signals


Name Type Default Description
HM1L01R BOOLEAN 0 Red indication of LED1, local HMI alarm group 1
HM1L01Y BOOLEAN 0 Yellow indication of LED1, local HMI alarm group 1
HM1L01G BOOLEAN 0 Green indication of LED1, local HMI alarm group 1

5.3.4 Settings
PID-4114-SETTINGS v6

Table 25: LEDGEN Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - On Operation Off/On
On
tRestart 0.0 - 100.0 s 0.1 0.0 Defines the disturbance length
tMax 0.1 - 100.0 s 0.1 1.0 Maximum time for the definition of a
disturbance

Breaker protection REQ650 55


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 5 1MRK 505 384-UEN C
Local Human-Machine-Interface LHMI

PID-1697-SETTINGS v18

Table 26: GRP1_LED1 Non group settings (basic)


Name Values (Range) Unit Step Default Description
SequenceType Follow-S - - Follow-S Sequence type for LED 1, local HMI
Follow-F alarm group 1
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
LabelOff 0 - 18 - 1 G1L01_OFF Label string shown when LED 1, alarm
group 1 is off
LabelRed 0 - 18 - 1 G1L01_RED Label string shown when LED 1, alarm
group 1 is red
LabelYellow 0 - 18 - 1 G1L01_YELLOW Label string shown when LED 1, alarm
group 1 is yellow
LabelGreen 0 - 18 - 1 G1L01_GREEN Label string shown when LED 1, alarm
group 1 is green

5.4 LCD part for HMI function keys control module GUID-EECAE7FA-7078-472C-A429-F7607DB884EB v2

5.4.1 Identification
GUID-E6611022-5EA3-420D-ADCD-9D1E7604EFEB v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
LCD part for HMI Function Keys FNKEYMD1 - - -
Control module FNKEYMD5

5.4.2 Function block


GUID-A803A728-5CFC-4606-98E4-793E873B99D4 v3

FNKEYMD1
^LEDCTL1 ^FKEYOUT1
IEC09000327 V1 EN-US

Figure 9: FNKEYMD1 function block


Only the function block for the first button is shown above. There is a similar block for every
function key button.

5.4.3 Signals
PID-7243-INPUTSIGNALS v1

Table 27: FNKEYMD1 Input signals


Name Type Default Description
LEDCTL1 BOOLEAN 0 LED control input for function key

PID-7243-OUTPUTSIGNALS v1

Table 28: FNKEYMD1 Output signals


Name Type Description
FKEYOUT1 BOOLEAN Output controlled by function key

56 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 5
Local Human-Machine-Interface LHMI

5.4.4 Settings
PID-7243-SETTINGS v1

Table 29: FNKEYMD1 Non group settings (basic)


Name Values (Range) Unit Step Default Description
Mode Off - - Off Output operation mode
Toggle
Pulsed
PulseTime 0.001 - 60.000 s 0.001 0.200 Pulse time for output controlled by
LCDFn1
LabelOn 0 - 18 - 1 LCD_FN1_ON Label for LED on state
LabelOff 0 - 18 - 1 LCD_FN1_OFF Label for LED off state
ReqAuthority Off - - On User authorization needed for
On function key operation

PID-7236-SETTINGS v1

Table 30: FNKEYTY1 Non group settings (basic)


Name Values (Range) Unit Step Default Description
Type Off - - Off Function key type
Menu shortcut
Control
MenuShortcut - 0 Menu shortcut for function key

GUID-BCE87D54-C836-40EE-8DA7-779B767059AB v2

For setting ReqAuthority, when users are configured through local or central
account management, the default behavior of the function keys are to only
operate if a user is logged in, and the user have the required rights. This
authentication check can be configured to be bypassed per function key by
changing the ReqAuthority from ON to OFF. To be able to change this, the user
changing it have to have the Security advanced right.

MenuShortcut values are product dependent and created dynamically depending on the
product main menu.

Breaker protection REQ650 57


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 5 1MRK 505 384-UEN C
Local Human-Machine-Interface LHMI

5.5 Operation principle

5.5.1 Local HMI AMU0600442 v15

IEC13000239-3-en.vsd
IEC13000239 V3 EN-US

Figure 10: Local human-machine interface


The LHMI of the IED contains the following elements

• Keypad
• Display (LCD)
• LED indicators
• Communication port for PCM600

The LHMI is used for setting, monitoring and controlling.

58 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 5
Local Human-Machine-Interface LHMI

5.5.1.1 Keypad AMU0600428 v19

The LHMI keypad contains push-buttons which are used to navigate in different views or
menus. The push-buttons are also used to acknowledge alarms, reset indications, provide help
and switch between local and remote control mode.

The keypad also contains programmable push-buttons that can be configured either as menu
shortcut or control buttons.

Breaker protection REQ650 59


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 5 1MRK 505 384-UEN C
Local Human-Machine-Interface LHMI

24

1
23
2
18
3

19
4

6 20

21

7 22

8 9 10 11 12 13 14 15 16 17

IEC15000157-2-en.vsd

IEC15000157 V2 EN-US

Figure 11: LHMI keypad with object control, navigation and command push-buttons and
RJ-45 communication port

1...5 Function button


6 Close
7 Open
8 Escape
9 Left
10 Down
11 Up
12 Right
13 Key
14 Enter
15 Remote/Local
16 Uplink LED
17 Not in use
18 Multipage
19 Menu
20 Clear
21 Help

60 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 5
Local Human-Machine-Interface LHMI

22 Communication port
23 Programmable indication LEDs
24 IED status LEDs

5.5.1.2 Display GUID-55739D4F-1DA5-4112-B5C7-217AAF360EA5 v13

The LHMI includes a graphical monochrome liquid crystal display (LCD) with a resolution of 320
x 240 pixels. The character size can vary. The amount of characters and rows fitting the view
depends on the character size and the view that is shown.

The display view is divided into four basic areas.

IEC15000270-1-en.vsdx

IEC15000270 V1 EN-US

Figure 12: Display layout

1 Path
2 Content
3 Status
4 Scroll bar (appears when needed)

Breaker protection REQ650 61


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 5 1MRK 505 384-UEN C
Local Human-Machine-Interface LHMI

• The path shows the current location in the menu structure. If the path is too long to be
shown, it is truncated from the beginning, and the truncation is indicated with three dots.
• The content area shows the menu content.
• The status area shows the current IED time, the user that is currently logged in and the
object identification string which is settable via the LHMI or with PCM600.
• If text, pictures or other items do not fit in the display, a vertical scroll bar appears on the
right. The text in content area is truncated from the beginning if it does not fit in the
display horizontally. Truncation is indicated with three dots.

IEC15000138-1-en.vsdx

IEC15000138 V1 EN-US

Figure 13: Truncated path


The number after : (colon sign) at the end of the function instance, for example, 1 in SMAI1:1,
indicates the number of that function instance.

The function key button panel shows on request what actions are possible with the function
buttons. Each function button has a LED indication that can be used as a feedback signal for
the function button control action. The LED is connected to the required signal with PCM600.

62 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 5
Local Human-Machine-Interface LHMI

IEC13000281-1-en.vsd
GUID-C98D972D-D1D8-4734-B419-161DBC0DC97B V1 EN-US

Figure 14: Function button panel


The indication LED panel shows on request the alarm text labels for the indication LEDs. Three
indication LED pages are available.

IEC13000240-1-en.vsd
GUID-5157100F-E8C0-4FAB-B979-FD4A971475E3 V1 EN-US

Figure 15: Indication LED panel


The function button and indication LED panels are not visible at the same time. Each panel is
shown by pressing one of the function buttons or the Multipage button. Pressing the ESC
button clears the panel from the display. Both panels have a dynamic width that depends on
the label string length.

5.5.1.3 LEDs AMU0600427 v15

The LHMI includes three status LEDs above the display: Ready, Start and Trip.

There are 15 programmable indication LEDs on the front of the LHMI. Each LED can indicate
three states with the colors: green, yellow and red. The texts related to each three-color LED
are divided into three panels.

There are 3 separate panels of LEDs available. The 15 physical three-color LEDs in one LED
group can indicate 45 different signals. Altogether, 135 signals can be indicated since there are
three LED groups. The LEDs are lit according to priority, with red being the highest and green

Breaker protection REQ650 63


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 5 1MRK 505 384-UEN C
Local Human-Machine-Interface LHMI

the lowest priority. For example, if on one panel there is an indication that requires the green
LED to be lit, and on another panel there is an indication that requires the red LED to be lit, the
red LED takes priority and is lit. The LEDs can be configured with PCM600 and the operation
mode can be selected with the LHMI or PCM600.

Information panels for the indication LEDs are shown by pressing the Multipage button.
Pressing that button cycles through the three pages. A lit or un-acknowledged LED is indicated
with a highlight. Such lines can be selected by using the Up/Down arrow buttons. Pressing the
Enter key shows details about the selected LED. Pressing the ESC button exits from
information pop-ups as well as from the LED panel as such.

The Multipage button has a LED. This LED is lit whenever any LED on any panel is lit. If there are
un-acknowledged indication LEDs, then the Multipage LED blinks. To acknowledge LEDs, press
the Clear button to enter the Reset menu (refer to description of this menu for details).

There are two additional LEDs which are next to the control buttons and . These
LEDs can indicate the status of two arbitrary binary signals by configuring the
OPENCLOSE_LED function block. For instance, OPENCLOSE_LED can be connected to a circuit
breaker to indicate the breaker open/close status on the LEDs.

IEC16000076-1-en.vsd
IEC16000076 V1 EN-US

Figure 16: OPENCLOSE_LED connected to SXCBR

5.5.2 LED configuration alternatives

5.5.2.1 Functionality GUID-1A03E0EF-C10F-4797-9D9F-5CCA86CA29EB v5

The function blocks LEDGEN and GRP1_LEDx, GRP2_LEDx and GRP3_LEDx (x=1-15) controls and
supplies information about the status of the indication LEDs. The input and output signals of
the function blocks are configured with PCM600. The input signal for each LED is selected
individually using SMT or ACT. Each LED is controlled by the GRPn_LEDx (n=1-3) function block
that controls the color and the operating mode.

Each indication LED on local HMI can be set individually to operate in 6 different sequences;
two as follow type and four as latch type. Two of the latching sequence types are intended to
be used as a protection indication system, either in collecting or restarting mode, with reset
functionality. The other two are intended to be used as signalling system in collecting mode
with acknowledgment functionality.

5.5.2.2 Status LEDs GUID-4822DF9C-E343-442B-B3F1-3FA8CD8DF234 v4

There are three status LEDs above the LCD in front of the IED: green, yellow and red.

64 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 5
Local Human-Machine-Interface LHMI

The green LED has a fixed function that presents the healthy status of the IED. The yellow and
red LEDs are user configured. The yellow LED can be used to indicate that a disturbance report
is triggered (steady) or that the IED is in test mode (flashing). The red LED can be used to
indicate a trip command.

Here is a typical configuration of the status LEDs:

• Green LED: unlit > no power; blinking > startup or abnormal situation (IED is not in
service); steady > IED is in service
• Yellow LED: unlit > no attention required; blinking > IED is in Testmode (IED is not in
normal service); steady > at least one of the signals configured to turn the yellow LED on
has been active
• Red LED: unlit > no attention required; blinking > user performs a common write from
PCM600; steady > at least one of the signals configured to turn the red LED on has been
active

The yellow and red status LEDs are configured in the disturbance recorder function, DRPRDRE,
by connecting a start or trip signal from the actual function to a BxRBDR binary input function
block using the PCM600, and configuring the setting to Off, Start or Trip for that particular
signal.

5.5.2.3 Indication LEDs

Operating modes GUID-B67F1ED3-900B-4D34-8EEB-A3005999CE50 v4

Collecting mode

• LEDs that are used in the collecting mode of operation are accumulated continuously until
the unit is acknowledged manually. This mode is suitable when the LEDs are used as a
simplified alarm system. When all three inputs (red, yellow and green) are connected to
different sources of events for the same function block, collecting mode shows the
highest priority LED color that was activated since the latest acknowledgment was made.
If a number of different indications were made since the latest acknowledgment, it is not
possible to get a clear view of what triggered the latest event without looking at the
sequence of events list. A condition for getting the sequence of events is that the signals
have been engineered in the disturbance recorder.

Re-starting mode

• In the re-starting mode of operation each new start resets all previous active LEDs and
activates only those which appear during one disturbance. Only LEDs defined for re-
starting mode with the latched sequence type 6 (LatchedReset-S) will initiate a reset and a
restart at a new disturbance. A disturbance is defined to end a settable time after the
reset of the activated input signals or when the maximum time limit has elapsed. In
sequence 6, the restarting or reset mode means that upon occurrence of any new event,
all previous indications will be reset. This facilitates that only the LED indications related
to the latest event is shown.

Acknowledgment/reset GUID-E6727E8F-C28B-4295-AE21-BC5643363805 v3

• From local HMI


• The active LED indications can be acknowledged/reset manually. Manual
acknowledgment and manual reset have the same meaning and is a common signal
for all the operating sequences and LEDs. The function is positive edge triggered,
not level triggered. The acknowledgment/reset is performed via the button and
menus on the LHMI.

Breaker protection REQ650 65


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 5 1MRK 505 384-UEN C
Local Human-Machine-Interface LHMI

• From function input


• The active LED indications can also be acknowledged/reset via an input, CLRLEDS, to
the function block LHMICTRL. This input can for example be configured to a binary
input operated from an external push button or a function button. The function is
positive edge triggered, not level triggered. This means that even if the button is
continuously pressed, the acknowledgment/reset only affects indications active at
the moment when the button is first pressed.

• Automatic reset
• The automatic reset can only be performed for LED indications defined for re-
starting mode with the latched sequence type 6 (LatchedReset-S). When the
automatic reset of the LEDs has been performed, still persisting indications will be
indicated with a steady light.

Operating sequence GUID-DFCA880B-308C-4334-94DF-97C7765E8C13 v5


The sequences can be of type Follow or Latched. For the Follow type, the LED follows the input
signal completely. For the Latched type, each LED latches to the corresponding input signal
until it is reset.

The figures below show the function of available sequences selectable for each LED separately.
The following 6 sequences are available:

• Sequence 1: Follow-S
• Sequence 2: Follow-F
• Sequence 3: LatchedAck-F-S
• Sequence 4: LatchedAck-S-F
• Sequence 5: LatchedColl-S
• Sequence 6: LatchedReset-S

For sequence 1 and 2, which are of the Follow type, the acknowledgment (Ack ) /reset function
is not applicable because the indication shown by the LED follows its input signal. Sequence 3
and 4, which are of the Latched type with acknowledgement, are only working in collecting
(Coll) mode. Sequence 5 is working according to Latched type and collecting mode while
Sequence 6 is working according to Latched type and re-starting (Reset) mode. The letters S
and F in the sequence names have the meaning S = Steady and F = Flash.

At the activation of the input signal to any LED, the indication on the corresponding LED
obtains a color that corresponds to the activated input, and operates according to the
selected sequence diagrams shown below.

In the sequence diagrams the different statuses of the LEDs are shown using the following
symbols:

= No indication = Steady light = Flash

G= Green Y= Yellow R= Red


IEC09000311.vsd
IEC09000311 V1 EN-US

Figure 17: Symbols used in the sequence diagrams

Sequence 1 (Follow-S) SEMOD56072-39 v4


This sequence follows the corresponding input signals all the time with a steady light. It does
not react on acknowledgment or reset. Every LED is independent of the other LEDs in its
operation.

66 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 5
Local Human-Machine-Interface LHMI

Activating
signal

LED

IEC01000228_2_en.vsd
IEC01000228 V2 EN-US

Figure 18: Operating Sequence 1 (Follow-S)


GUID-107FE952-3B4C-4C01-831A-3147E652327C v4
If inputs for two or more colors are active at the same time to the same LED, the priority color
it shows is in accordance with the color described above. An example of the operation when
two colors are activated in parallel to the same LED is shown in figure19.

Activating
signal GREEN

Activating
signal RED

LED G G R G

IEC09000312_1_en.vsd
IEC09000312 V1 EN-US

Figure 19: Operating sequence 1, two colors

Sequence 2 (Follow-F) SEMOD56072-47 v2


This sequence is the same as Sequence 1, Follow-S, but the LEDs are flashing instead of
showing steady light.

Sequence 3 LatchedAck-F-S SEMOD56072-50 v2


This sequence has a latched function and works in collecting mode. Every LED is independent
of the other LEDs in its operation. At the activation of the input signal, the indication starts
flashing. After acknowledgment the indication disappears if the signal is not present any
more. If the signal is still present after acknowledgment it gets a steady light.

Activating
signal

LED

Acknow.
en01000231.vsd
IEC01000231 V1 EN-US

Figure 20: Operating Sequence 3 LatchedAck-F-S


GUID-CC607709-5344-4C88-AA97-6395FD335E55 v5

The sequence described below is valid only if the same function block is used
for all three colour LEDs.

When an acknowledgment is performed, all indications that appear before the indication with
higher priority has been reset, will be acknowledged, independent of if the low priority
indication appeared before or after acknowledgment. In figure 21 it is shown the sequence

Breaker protection REQ650 67


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 5 1MRK 505 384-UEN C
Local Human-Machine-Interface LHMI

when a signal of lower priority becomes activated after acknowledgment has been performed
on a higher priority signal. The low priority signal will be shown as acknowledged when the
high priority signal resets.

Activating
signal GREEN

Activating
signal RED

R R G
LED

Acknow
IEC09000313_1_en.vsd
IEC09000313 V1 EN-US

Figure 21: Operating Sequence 3 (LatchedAck-F-S), 2 colors involved


GUID-A652A49D-F016-472D-8D38-6D3E75DAB1DB v3
If all three signals are activated the order of priority is still maintained. Acknowledgment of
indications with higher priority will acknowledge also low priority indications, which are not
visible according to figure 22.

Activating
signal GREEN

Activating
signal YELLOW
Activating
signal RED

LED G Y R R Y

Acknow.
IEC09000314-1-en.vsd
IEC09000314 V1 EN-US

Figure 22: Operating sequence 3, three colors involved, alternative 1


GUID-071B9EB5-A1D2-49C5-9458-4D21B7E068BE v3
If an indication with higher priority appears after acknowledgment of a lower priority
indication the high priority indication will be shown as not acknowledged according to figure
23.

68 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 5
Local Human-Machine-Interface LHMI

Activating
signal GREEN

Activating
signal YELLOW
Activating
signal RED

LED G G R R Y

Acknow.
IEC09000315-1-en.vsd
IEC09000315 V1 EN-US

Figure 23: Operating sequence 3, three colors involved, alternative 2

Sequence 4 (LatchedAck-S-F) SEMOD56072-64 v1


This sequence has the same functionality as sequence 3, but steady and flashing light have
been alternated.

Sequence 5 LatchedColl-S SEMOD56072-67 v4


This sequence has a latched function and works in collecting mode. At the activation of the
input signal, the indication will light up with a steady light. The difference to sequence 3 and 4
is that indications that are still activated will not be affected by the reset that is, immediately
after the positive edge of the reset has been executed a new reading and storing of active
signals is performed. Every LED is independent of the other LEDs in its operation.

Activating
signal

LED

Reset

IEC01000235_2_en.vsd
IEC01000235 V2 EN-US

Figure 24: Operating Sequence 5 LatchedColl-S


GUID-4D52D221-F54F-4966-95B1-6ED6C536CEC9 v3
That means if an indication with higher priority has reset while an indication with lower
priority still is active at the time of reset, the LED will change color according to figure25.

Breaker protection REQ650 69


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 5 1MRK 505 384-UEN C
Local Human-Machine-Interface LHMI

Activating
signal GREEN

Activating
signal RED

R G
LED

Reset
IEC09000316_1_en.vsd
IEC09000316 V1 EN-US

Figure 25: Operating sequence 5, two colors

Sequence 6 LatchedReset-S SEMOD56072-75 v4


In this mode all activated LEDs, which are set to Sequence 6 (LatchedReset-S), are
automatically reset at a new disturbance when activating any input signal for other LEDs set to
Sequence 6 LatchedReset-S. Also in this case indications that are still activated will not be
affected by manual reset, that is, immediately after the positive edge of that the manual reset
has been executed a new reading and storing of active signals is performed. LEDs set for
sequence 6 are completely independent in its operation of LEDs set for other sequences.

Timing diagram for sequence 6 SEMOD56072-86 v4


Figure 26 shows the timing diagram for two indications within one disturbance.

Disturbance
tRestart

Activating
signal 1

Activating
signal 2

LED 1

LED 2

Automatic
reset

Manual
reset
IEC01000239_2-en.vsd
IEC01000239 V2 EN-US

Figure 26: Operating sequence 6 (LatchedReset-S), two indications within same


disturbance
Figure 27 shows the timing diagram for a new indication after tRestart time has elapsed.

70 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 5
Local Human-Machine-Interface LHMI

Disturbance Disturbance

tRestart tRestart

Activating
signal 1

Activating
signal 2

LED 1

LED 2

Automatic
reset

Manual
reset
IEC01000240_2_en.vsd
IEC01000240 V2 EN-US

Figure 27: Operating sequence 6 (LatchedReset-S), two different disturbances


Figure 28 shows the timing diagram when a new indication appears after the first one has
reset but before tRestart has elapsed.

Disturbance

tRestart

Activating
signal 1

Activating
signal 2

LED 1

LED 2

Automatic
reset

Manual
reset
IEC01000241_2_en.vsd
IEC01000241 V2 EN-US

Figure 28: Operating sequence 6 (LatchedReset-S), two indications within same


disturbance but with reset of activating signal between
Figure 29 shows the timing diagram for manual reset.

Breaker protection REQ650 71


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 5 1MRK 505 384-UEN C
Local Human-Machine-Interface LHMI

Disturbance

tRestart

Activating
signal 1

Activating
signal 2

LED 1

LED 2

Automatic
reset

Manual
reset
IEC01000242_2_en.vsd
IEC01000242 V2 EN-US

Figure 29: Operating sequence 6 (LatchedReset-S), manual reset

5.5.3 Function keys

5.5.3.1 Functionality GUID-BED38E9A-C90D-4B7F-AA20-42821C4F6A1C v3

Local Human-Machine-Interface (LHMI) has five function buttons, directly to the left of the
LCD, that can be configured either as menu shortcut or control buttons. Each button has an
indication LED that can be configured in the application configuration.

When used as a menu shortcut, a function button provides a fast way to navigate between
default nodes in the menu tree. When used as a control, the button can control a binary signal.

5.5.3.2 Operation principle GUID-977C3829-B19B-457E-8A4D-45317226EF22 v3

Each output on the FNKEYMD1 - FNKEYMD5 function blocks can be controlled from the LHMI
function keys. By pressing a function button on the LHMI, the output status of the actual
function block will change. These binary outputs can in turn be used to control other function
blocks, for example, switch control blocks, binary I/O outputs etc.

FNKEYMD1 - FNKEYMD5 function block also has a number of settings and parameters that
control the behavior of the function block. These settings and parameters are normally set
using the PST.

Operating sequence GUID-84CA7C61-4F83-4F86-A07F-BF9EC4E309BF v5


The operation mode is set individually for each output, either OFF, TOGGLE or PULSED.

Setting OFF

This mode always sets the outputs to a low value (0).

72 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 5
Local Human-Machine-Interface LHMI

Input value

Output value

IEC09000330-2-en.vsd

IEC09000330 V2 EN-US

Figure 30: Sequence diagram for setting OFF


Setting TOGGLE

In this mode the output toggles each time the function key has been pressed for more than
500ms. Note that the input attribute is reset each time the function block executes. The
function block execution is marked with a dotted line below.

Input value
500ms 500ms 500ms

Output value

IEC09000331_1_en.vsd

IEC09000331 V2 EN-US

Figure 31: Sequence diagram for setting TOGGLE


Setting PULSED

In this mode the output sets high (1) when the function key has been pressed for more than
500ms and remains high according to set pulse time. After this time the output will go back to
0. The input attribute is reset when the function block detects it being high and there is no
output pulse.

Note that the third positive edge on the input attribute does not cause a pulse, since the edge
was applied during pulse output. A new pulse can only begin when the output is zero; else the
trigger edge is lost.

Input value
500ms 500ms 500ms 500ms

pulse time pulse time pulse time


Output value

IEC09000332_2_en.vsd

IEC09000332 V2 EN-US

Figure 32: Sequence diagram for setting PULSED

Input function GUID-8EA4AE21-7A74-403A-84AE-D5CEF9292A63 v2


All function keys work the same way: When the LHMI is configured so that a certain function
button is of type CONTROL, then the corresponding input on this function block becomes
active, and will light the yellow function button LED when high. This functionality is active even
if the function block operation setting is set to off. It has been implemented this way for

Breaker protection REQ650 73


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 5 1MRK 505 384-UEN C
Local Human-Machine-Interface LHMI

safety reasons; the idea is that the function key LEDs should always reflect the actual status of
any primary equipment monitored by these LEDs.

5.5.3.3 Enabling and Disabling Authority on Function keys GUID-27413370-00F4-477D-886F-30359C788B55 v1

When users are configured through local or central account management, the default behavior
of the function keys are to only operate if a user is logged in, and the user have the required
rights. This authentication check can be configured to be bypassed per function key by
changing the ReqAuthority from ON to OFF. To be able to change this, the user changing it
have to have the Security advanced right.

Authority can be disabled using parameter Authority. Each function key has the parameter
Authority, which can be enabled or disabled using LHMI or PCM 600. User must have Security
Advanced rights to configure the Authority parameter of the function key.

The possible values for the Authority parameter are as below:

• Enabled: Requires authentication


• Disabled: No user authentication

If there is no User Account Management or Central Account Management


configured in the IED then this parameter has no effect and the function key
can be operated without any authentication.

74 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

Section 6 Current protection


6.1 Instantaneous phase overcurrent protection PHPIOC IP14506-1 v6

6.1.1 Identification
M14880-1 v5

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Instantaneous phase overcurrent PHPIOC 50
protection
3I>>

SYMBOL-Z V1 EN-US

6.1.2 Functionality M12910-3 v14

6.1.3 Function block M12602-3 v6

PHPIOC
I3P* TRIP
BLOCK TRL1
ENMULT TRL2
TRL3

IEC04000391-2-en.vsd
IEC04000391 V2 EN-US

Figure 33: PHPIOC function block

6.1.4 Signals IP11433-1 v2

PID-6914-INPUTSIGNALS v3

Table 31: PHPIOC Input signals


Name Type Default Description
I3P GROUP - Three phase current
SIGNAL
BLOCK BOOLEAN 0 Block of function
ENMULT BOOLEAN 0 Enable current start value multiplier

PID-6914-OUTPUTSIGNALS v3

Table 32: PHPIOC Output signals


Name Type Description
TRIP BOOLEAN Trip signal from any phase
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3

Breaker protection REQ650 75


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

6.1.5 Settings IP11434-1 v2

PID-6914-SETTINGS v3

Table 33: PHPIOC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OpMode 2 out of 3 - - 1 out of 3 Select operation mode 2-out of 3 / 1-
1 out of 3 out of 3
IP>> 5 - 2500 %IB 1 200 Operate phase current level in % of
IBase

Table 34: PHPIOC Group settings (advanced)


Name Values (Range) Unit Step Default Description
IP>>Min 5 - 2500 %IB 1 5 Minimum used operate phase current
level in % of IBase, if IP>> is less than
IP>>Min then IP>> is set to IP>>Min
IP>>Max 5 - 2500 %IB 1 2500 Maximum used operate phase current
level in % of IBase, if IP>> is greater
than IP>>Max then IP>> is set to
IP>>Max
StValMult 0.5 - 5.0 - 0.1 1.0 Multiplier for operate current level

Table 35: PHPIOC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

6.1.6 Monitored data


PID-6914-MONITOREDDATA v3

Table 36: PHPIOC Monitored data


Name Type Values (Range) Unit Description
IL1 REAL - A Current in phase L1
IL2 REAL - A Current in phase L2
IL3 REAL - A Current in phase L3

6.1.7 Operation principle M12913-3 v8

The sampled analogue phase currents are pre-processed in a discrete Fourier filter (DFT)
block. The RMS value of each phase current is derived from the fundamental frequency
components, as well as sampled values of each phase current. These phase current values are
fed to the instantaneous phase overcurrent protection 3-phase output function PHPIOC. In a
comparator the RMS values are compared to the set operation current value of the function
(IP>>).

If a phase current is larger than the set operation current a signal from the comparator for this
phase is set to true. This signal will, without delay, activate the output signal TRLn (n=1,2,3) for
this phase and the TRIP signal that is common for all three phases.

76 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

There is an operation mode (OpMode) setting: 1 out of 3 or 2 out of 3. If the parameter is set to
1 out of 3, any phase trip signal will be activated. If the parameter is set to 2 out of 3, at least
two phase signals must be activated for trip.

There is also a possibility to activate a preset change of the set operation current (StValMult)
via a binary input (ENMULT). In some applications the operation value needs to be changed,
for example, due to transformer inrush currents.

The operation current value IP>>, is limited to be between IP>>Max and IP>>Min. The default
values of the limits are the same as the setting limits for IP>>, and the limits can only be used
for reducing the allowed range of IP>>. This feature is used when remote setting of the
operation current value is allowed, making it possible to ensure that the operation value used
is reasonable. If IP>> is set outside IP>>Max and IP>>Min, the closest of the limits to IP>> is
used by the function. If IP>>Max is smaller then IP>>Min, the limits are swapped. The principle
of the limitation is shown in Figure 34.

IP>>Max
MAX hi

u y
IP>>_used
IP>>

MIN lo
IP>>Min
IEC17000016-1-en.vsdx
IEC17000016 V1 EN-US

Figure 34: Logic for limitation of used operation current value

PHPIOC can be blocked using the binary input BLOCK.

6.1.8 Technical data IP11435-1 v1

M12336-1 v13

Table 37: PHPIOC technical data


Function Range or value Accuracy
Operate current (5-2500)% of lBase ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir

Reset ratio > 95% at (50–2500)% of IBase -


Operate time at 0 to 2 x Iset Min. = 15 ms -
Max. = 25 ms
Reset time at 2 x Iset to 0 Min. = 15 ms -
Max. = 25 ms
Critical impulse time 10 ms typically at 0 to 2 x Iset -

Operate time at 0 to 10 x Iset Min. = 5 ms -


Max. = 15 ms
Reset time at 10 x Iset to 0 Min. = 25 ms -
Max. = 40 ms
Critical impulse time 2 ms typically at 0 to 10 x Iset -

Dynamic overreach < 5% at t = 100 ms -

6.2 Directional phase overcurrent protection, four steps


OC4PTOC SEMOD129998-1 v8

Breaker protection REQ650 77


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

6.2.1 Identification
M14885-1 v6

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Directional phase overcurrent OC4PTOC 51_67
protection, four steps

TOC-REVA V2 EN-US

6.2.2 Functionality M12846-3 v17

Directional phase overcurrent protection, four steps (OC4PTOC) has an inverse or definite
time delay for each step.

All IEC and ANSI inverse time characteristics are available together with an optional user
defined time characteristic.

The directional function needs voltage as it is voltage polarized with memory. The function can
be set to be directional or non-directional independently for each of the steps.

A second harmonic blocking level can be set for the function and can be used to block each
step individually.

78 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

6.2.3 Function block M12609-3 v8

OC4PTOC
I3P* TRIP
U3P* TR1
BLOCK TR2
BLKTR TR3
BLKST1 TR4
BLKST2 TRL1
BLKST3 TRL2
BLKST4 TRL3
ENMULT1 TR1L1
ENMULT2 TR1L2
ENMULT3 TR1L3
ENMULT4 TR2L1
TR2L2
TR2L3
TR3L1
TR3L2
TR3L3
TR4L1
TR4L2
TR4L3
START
ST1
ST2
ST3
ST4
STL1
STL2
STL3
ST1L1
ST1L2
ST1L3
ST2L1
ST2L2
ST2L3
ST3L1
ST3L2
ST3L3
ST4L1
ST4L2
ST4L3
ST2NDHRM
DIRL1
DIRL2
DIRL3
STDI RCND
IEC06000187-4-en.vsdx
IEC06000187 V4 EN-US

Figure 35: OC4PTOC function block

6.2.4 Signals
PID-6973-INPUTSIGNALS v3

Table 38: OC4PTOC Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block of trip
BLKST1 BOOLEAN 0 Block of Step1
BLKST2 BOOLEAN 0 Block of Step2
BLKST3 BOOLEAN 0 Block of Step3
BLKST4 BOOLEAN 0 Block of Step4
Table continues on next page

Breaker protection REQ650 79


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

Name Type Default Description


ENMULT1 BOOLEAN 0 When activated, the current multiplier is in use for step1
ENMULT2 BOOLEAN 0 When activated, the current multiplier is in use for step2
ENMULT3 BOOLEAN 0 When activated, the current multiplier is in use for step3
ENMULT4 BOOLEAN 0 When activated, the current multiplier is in use for step4

PID-6973-OUTPUTSIGNALS v3

Table 39: OC4PTOC Output signals


Name Type Description
TRIP BOOLEAN Trip
TR1 BOOLEAN Common trip signal from step1
TR2 BOOLEAN Common trip signal from step2
TR3 BOOLEAN Common trip signal from step3
TR4 BOOLEAN Common trip signal from step4
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
TR1L1 BOOLEAN Trip signal from step1 phase L1
TR1L2 BOOLEAN Trip signal from step1 phase L2
TR1L3 BOOLEAN Trip signal from step1 phase L3
TR2L1 BOOLEAN Trip signal from step2 phase L1
TR2L2 BOOLEAN Trip signal from step2 phase L2
TR2L3 BOOLEAN Trip signal from step2 phase L3
TR3L1 BOOLEAN Trip signal from step3 phase L1
TR3L2 BOOLEAN Trip signal from step3 phase L2
TR3L3 BOOLEAN Trip signal from step3 phase L3
TR4L1 BOOLEAN Trip signal from step4 phase L1
TR4L2 BOOLEAN Trip signal from step4 phase L2
TR4L3 BOOLEAN Trip signal from step4 phase L3
START BOOLEAN General start signal
ST1 BOOLEAN Common start signal from step1
ST2 BOOLEAN Common start signal from step2
ST3 BOOLEAN Common start signal from step3
ST4 BOOLEAN Common start signal from step4
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
ST1L1 BOOLEAN Start signal from step1 phase L1
ST1L2 BOOLEAN Start signal from step1 phase L2
ST1L3 BOOLEAN Start signal from step1 phase L3
ST2L1 BOOLEAN Start signal from step2 phase L1
ST2L2 BOOLEAN Start signal from step2 phase L2
ST2L3 BOOLEAN Start signal from step2 phase L3
Table continues on next page

80 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

Name Type Description


ST3L1 BOOLEAN Start signal from step3 phase L1
ST3L2 BOOLEAN Start signal from step3 phase L2
ST3L3 BOOLEAN Start signal from step3 phase L3
ST4L1 BOOLEAN Start signal from step4 phase L1
ST4L2 BOOLEAN Start signal from step4 phase L2
ST4L3 BOOLEAN Start signal from step4 phase L3
ST2NDHRM BOOLEAN Second harmonic detected
DIRL1 INTEGER Direction for phase1
DIRL2 INTEGER Direction for phase2
DIRL3 INTEGER Direction for phase3
STDIRCND INTEGER Binary coded start and directional information

6.2.5 Settings
PID-6973-SETTINGS v3

Table 40: OC4PTOC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
AngleRCA 40 - 65 Deg 1 55 Relay characteristic angle (RCA)
AngleROA 40 - 89 Deg 1 80 Relay operation angle (ROA)
StartPhSel 1 out of 3 - - 1 out of 3 Number of phases required for op (1
2 out of 3 of 3, 2 of 3, 3 of 3)
3 out of 3
DirMode1 Off - - Non-directional Directional mode of step 1 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Characterist1 ANSI Ext. inv. - - ANSI Def. Time Selection of time delay curve type for
ANSI Very inv. step 1
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
I1> 5 - 2500 %IB 1 1000 Operating phase current level for step
1 in % of IBase
t1 0.000 - 60.000 s 0.001 0.000 Def time delay or add time delay for
inverse char of step 1
k1 0.05 - 999.00 - 0.01 0.05 Time multiplier for the inverse time
delay for step 1
Table continues on next page

Breaker protection REQ650 81


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

Name Values (Range) Unit Step Default Description


IMin1 1 - 10000 %IB 1 100 Minimum operate current for step1 in
% of IBase
t1Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse
curves for step 1
I1Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for current operate level for
step 1
DirMode2 Off - - Non-directional Directional mode of step 2 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Characterist2 ANSI Ext. inv. - - ANSI Def. Time Selection of time delay curve type for
ANSI Very inv. step 2
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
I2> 5 - 2500 %IB 1 500 Operating phase current level for step
2 in % of IBase
t2 0.000 - 60.000 s 0.001 0.400 Def time delay or add time delay for
inverse char of step 2
k2 0.05 - 999.00 - 0.01 0.05 Time multiplier for the inverse time
delay for step 2
IMin2 1 - 10000 %IB 1 50 Minimum operate current for step2 in
% of IBase
t2Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse
curves for step 2
I2Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for current operate level for
step 2
DirMode3 Off - - Non-directional Directional mode of step 3 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Table continues on next page

82 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

Name Values (Range) Unit Step Default Description


Characterist3 ANSI Ext. inv. - - ANSI Def. Time Selection of time delay curve type for
ANSI Very inv. step 3
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
I3> 5 - 2500 %IB 1 250 Operating phase current level for step
3 in % of IBase
t3 0.000 - 60.000 s 0.001 0.800 Def time delay or add time delay for
inverse char of step 3
k3 0.05 - 999.00 - 0.01 0.05 Time multiplier for the inverse time
delay for step 3
IMin3 1 - 10000 %IB 1 33 Minimum operate current for step3 in
% of IBase
t3Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse
curves for step 3
I3Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for current operate level for
step 3
DirMode4 Off - - Non-directional Directional mode of step 4 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Characterist4 ANSI Ext. inv. - - ANSI Def. Time Selection of time delay curve type for
ANSI Very inv. step 4
ANSI Norm. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
I4> 5 - 2500 %IB 1 175 Operating phase current level for step
4 in % of IBase
t4 0.000 - 60.000 s 0.001 2.000 Def time delay or add time delay for
inverse char of step 4
k4 0.05 - 999.00 - 0.01 0.05 Time multiplier for the inverse time
delay for step 4
Table continues on next page

Breaker protection REQ650 83


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

Name Values (Range) Unit Step Default Description


IMin4 1 - 10000 %IB 1 17 Minimum operate current for step4 in
% of IBase
t4Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse
curves for step 4
I4Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for current operate level for
step 4

Table 41: OC4PTOC Group settings (advanced)


Name Values (Range) Unit Step Default Description
IMinOpPhSel 1 - 100 %IB 1 7 Minimum current for phase selection
in % of IBase
2ndHarmStab 5 - 100 % 1 20 Operate level of 2nd harmonic curr in
% of fundamental curr
I1>Min 5 - 2500 %IB 1 5 Minimum used operating phase
current level for step 1 in % of IBase, if
I1> is less than I1>Min then I1> is set to
I1>Min
I1>Max 5 - 2500 %IB 1 2500 Maximum used operating phase
current level for step 1 in % of IBase, if
I1> is greater than I1>Max then I1> is
set to I1>Max
ResetTypeCrv1 Instantaneous - - Instantaneous Selection of reset curve type for step 1
IEC Reset
ANSI reset
tReset1 0.000 - 60.000 s 0.001 0.020 Constant reset time for step 1
tPCrv1 0.005 - 3.000 - 0.001 1.000 Parameter P for customer
programmable curve for step 1
tACrv1 0.005 - 200.000 - 0.001 13.500 Parameter A for customer
programmable curve for step 1
tBCrv1 0.00 - 20.00 - 0.01 0.00 Parameter B for customer
programmable curve for step 1
tCCrv1 0.1 - 10.0 - 0.1 1.0 Parameter C for customer
programmable curve for step 1
tPRCrv1 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer
programmable curve for step 1
tTRCrv1 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer
programmable curve for step 1
tCRCrv1 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer
programmable curve for step 1
HarmBlock1 Off - - Off Enable block of step 1 from harmonic
On restrain
I2>Min 5 - 2500 %IB 1 5 Minimum used operating phase
current level for step 2 in % of IBase, if
I2> is less than I2>Min then I2> is set
to I2>Min
I2>Max 5 - 2500 %IB 1 2500 Maximum used operating phase
current level for step 2 in % of IBase, if
I2> is greater than I2>Max then I2> is
set to I2>Max
ResetTypeCrv2 Instantaneous - - Instantaneous Selection of reset curve type for step 2
IEC Reset
ANSI reset
tReset2 0.000 - 60.000 s 0.001 0.020 Constant reset time for step 2
Table continues on next page

84 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

Name Values (Range) Unit Step Default Description


tPCrv2 0.005 - 3.000 - 0.001 1.000 Parameter P for customer
programmable curve for step 2
tACrv2 0.005 - 200.000 - 0.001 13.500 Parameter A for customer
programmable curve for step 2
tBCrv2 0.00 - 20.00 - 0.01 0.00 Parameter B for customer
programmable curve for step 2
tCCrv2 0.1 - 10.0 - 0.1 1.0 Parameter C for customer
programmable curve for step 2
tPRCrv2 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer
programmable curve for step 2
tTRCrv2 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer
programmable curve for step 2
tCRCrv2 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer
programmable curve for step 2
HarmBlock2 Off - - Off Enable block of step 2 from harmonic
On restrain
I3>Min 5 - 2500 %IB 1 5 Minimum used operating phase
current level for step 3 in % of IBase, if
I3> is less than I3>Min then I3> is set
to I3>Min
I3>Max 5 - 2500 %IB 1 2500 Maximum used operating phase
current level for step 3 in % of IBase, if
I3> is greater than I3>Max then I3> is
set to I3>Max
ResetTypeCrv3 Instantaneous - - Instantaneous Selection of reset curve type for step 3
IEC Reset
ANSI reset
tReset3 0.000 - 60.000 s 0.001 0.020 Constant reset time for step 3
tPCrv3 0.005 - 3.000 - 0.001 1.000 Parameter P for customer
programmable curve for step 3
tACrv3 0.005 - 200.000 - 0.001 13.500 Parameter A for customer
programmable curve for step 3
tBCrv3 0.00 - 20.00 - 0.01 0.00 Parameter B for customer
programmable curve for step 3
tCCrv3 0.1 - 10.0 - 0.1 1.0 Parameter C for customer
programmable curve for step 3
tPRCrv3 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer
programmable curve for step 3
tTRCrv3 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer
programmable curve for step 3
tCRCrv3 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer
programmable curve for step 3
HarmBlock3 Off - - Off Enable block of step 3 from harmonic
On restrain
I4>Min 5 - 2500 %IB 1 5 Minimum used operating phase
current level for step 4 in % of IBase, if
I4> is less than I4>Min then I4> is set
to I4>Min
I4>Max 5 - 2500 %IB 1 2500 Maximum used operating phase
current level for step 4 in % of IBase, if
I4> is greater than I4>Max then I4> is
set to I4>Max
ResetTypeCrv4 Instantaneous - - Instantaneous Selection of reset curve type for step
IEC Reset 4
ANSI reset
Table continues on next page

Breaker protection REQ650 85


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

Name Values (Range) Unit Step Default Description


tReset4 0.000 - 60.000 s 0.001 0.020 Constant reset time for step 4
tPCrv4 0.005 - 3.000 - 0.001 1.000 Parameter P for customer
programmable curve for step 4
tACrv4 0.005 - 200.000 - 0.001 13.500 Parameter A for customer
programmable curve for step 4
tBCrv4 0.00 - 20.00 - 0.01 0.00 Parameter B for customer
programmable curve for step 4
tCCrv4 0.1 - 10.0 - 0.1 1.0 Parameter C for customer
programmable curve for step 4
tPRCrv4 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer
programmable curve for step 4
tTRCrv4 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer
programmable curve for step 4
tCRCrv4 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer
programmable curve for step 4
HarmBlock4 Off - - Off Enable block of step 4 from harmonic
On restrain

Table 42: OC4PTOC Non group settings (basic)


Name Values (Range) Unit Step Default Description
MeasType DFT - - DFT Selection between DFT and RMS
RMS measurement
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

6.2.6 Monitored data


PID-6973-MONITOREDDATA v3

Table 43: OC4PTOC Monitored data


Name Type Values (Range) Unit Description
DIRL1 INTEGER 1=Forward - Direction for phase1
2=Reverse
0=No direction
DIRL2 INTEGER 1=Forward - Direction for phase2
2=Reverse
0=No direction
DIRL3 INTEGER 1=Forward - Direction for phase3
2=Reverse
0=No direction
IL1 REAL - A Current in phase L1
IL2 REAL - A Current in phase L2
IL3 REAL - A Current in phase L3

6.2.7 Operation principle M12883-3 v10

Directional phase overcurrent protection, four steps OC4PTOC is divided into four different
sub-functions. For each step x , where x is step 1, 2, 3 and 4, an operation mode is set by
DirModex: Off/Non-directional/Forward/Reverse.

86 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

The protection design can be divided into four parts:

• The direction element


• The harmonic restraint blocking function
• The four step overcurrent function
• The mode selection

If VT inputs are not available or not connected, setting parameter DirModex


shall be left to default value, Non-directional.

4 step overcurrent
Direction dirPh1Flt element faultState
faultState
Element One element for each
dirPh2Flt step
I3P dirPh3Flt START

U3P

TRIP

Harmonic harmRestrBlock
Restraint
Element

enableDir
Mode Selection
enableStep1-4
DirectionalMode1-4

IEC05000740-3-en.vsdx

IEC05000740 V3 EN-US

Figure 36: Functional overview of OC4PTOC


M12883-16 v11
A common setting for all steps, StartPhSel, is used to specify the number of phase currents to
be high to enable operation. These settings can be chosen: 1 out of 3, 2 out of 3 or 3 out of 3.

Using a parameter setting MeasType within the general settings for the function OC4PTOC, it
is possible to select the type of the measurement used for all overcurrent stages. Either
discrete Fourier filter (DFT) or true RMS filter (RMS) can be selected.

If the DFT option is selected, only the RMS value of the fundamental frequency component of
each phase current is derived. The influence of the DC current component and higher harmonic
current components are almost completely suppressed. If the RMS option is selected, then the
true RMS value is used. The true RMS value includes the contribution from the current DC
component as well as from the higher current harmonic in addition to the fundamental
frequency component.

In a comparator, the DFT or RMS values are compared to the set operation current value of the
function (I1>, I2>, I3> or I4>) for each phase current. If a phase current is larger than the set
operation current, outputs START, STx, STL1, STL2 and STL3 are activated without delay.
Output signals STL1, STL2 and STL3 are common for all steps. This means that the lowest set
step will initiate the activation. The START signal is common for all three phases and all steps.
It shall be noted that the selection of measured value (DFT or RMS) do not influence the
operation of directional part of OC4PTOC.

Breaker protection REQ650 87


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

Service values for individually measured phase currents are available on the local HMI for
OC4PTOC function, which simplifies testing, commissioning and in service operational
checking of the function.

A harmonic restrain of the function can be chosen. A set 2nd harmonic current in relation to
the fundamental current is used.

The function can be directional.The direction of a fault is given as the current angle in relation
to the voltage angle. The fault current and fault voltage for the directional function are
dependent on the fault type. The selection of the measured value (DFT or RMS) does not
influence the operation of the directional part of OC4PTOC. To enable directional
measurement at close-in faults, causing a low measured voltage, the polarization voltage is a
combination of the apparent voltage (85%) and a memory voltage (15%). The following
combinations are used.

Phase-phase short circuit:

U refL1L 2 = U L1 - U L 2 I dirL1L 2 = I L1 - I L 2
EQUATION1449 V1 EN-US (Equation 1)

U refL 2 L 3 = U L 2 - U L 3 I dirL 2 L 3 = I L 2 - I L 3
EQUATION1450 V1 EN-US (Equation 2)

U refL 3 L1 = U L 3 - U L1 I dirL 3 L1 = I L 3 - I L1
EQUATION1451 V1 EN-US (Equation 3)

Phase-earth short circuit:

U refL1 = U L1 I dirL1 = I L1
EQUATION1452 V1 EN-US (Equation 4)

U refL 2 = U L 2 I dirL 2 = I L 2
EQUATION1453 V1 EN-US (Equation 5)

U refL 3 = U L 3 I dirL 3 = I L 3
EQUATION1454 V1 EN-US (Equation 6)

The polarizing voltage is available as long as the positive-sequence voltage exceeds 5% of the
set base voltage UBase. So the directional element can be used for all unsymmetrical faults
including close-in faults.

For close-in three-phase faults, the U1L1M memory voltage, based on the same positive
sequence voltage, ensures correct directional discrimination.

The memory voltage is used for 100 ms or until the positive sequence voltage is restored.

After 100 ms, the following occurs:

• If the current is still above the set value of the minimum operating current (7% of the set
terminal rated current IBase), the condition seals in.

88 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

• If the fault has caused tripping, the trip endures.


• If the fault was detected in the reverse direction, the measuring element in the
reverse direction remains in operation.
• If the current decreases below the minimum operating value, the memory resets until the
positive sequence voltage exceeds 10% of its rated value.

The directional setting is given as a characteristic angle AngleRCA for the function and an
angle window ROADir.

Reverse

Uref

RCA
ROA

ROA Forward

Idir

en05000745.vsd
IEC05000745 V1 EN-US

Figure 37: Directional characteristic of the phase overcurrent protection


The default value of AngleRCA is –55°. The parameter AngleROA gives the angular distance
from AngleRCA to define the directional borders.

A minimum current for the directional phase start current signal can be set. IMinOpPhSel is the
start level for the directional evaluation of IL1, IL2 and IL3. The directional signals release the
overcurrent measurement in the respective phases if their current amplitudes are higher than
the start level (IMinOpPhSel) and the direction of the current is according to the set direction
of the step.

If no blocking signals are active, the start signal will start the timer of the steps. The time
characteristic for each step can be chosen as definite time delay or an inverse time delay
characteristic. A wide range of standardized inverse time delay characteristics is available. It is
also possible to create a tailor made time characteristic.

The possibilities for inverse time characteristics are described in section "Inverse
characteristics".

Breaker protection REQ650 89


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

Characteristx=DefTime
|IOP| AND
tx TRx
a OR
a>b
Ix> b

AND
STx

txmin
BLKSTx AND
BLOCK
Inverse

Characteristx=Inverse

DirModex=Off OR STAGEx_DIR_Int
DirModex=Non-directional
DirModex=Forward
AND OR
FORWARD_Int
DirModex=Reverse

AND
REVERSE_Int

IEC12000008.vsd
IEC12000008.vsd

IEC12000008 V2 EN-US

Figure 38: Simplified logic diagram for OC4PTOC

I3P
DFWDLx

U3P DFWDLxx

DREVLx
Directional
Element
AngleRCA DREVLxx FORWARD_int

Directional
AngleROA Release REVERSE_int
Block

STLx

Greater
IMinOpPhSel Comparator
x‐ means three phases 1,2 and 3
xx – means phase to phase 12,23,31

IEC15000266-2-en.vsdx
IEC15000266 V2 EN-US

Figure 39: OC4 directional release block diagram


Different types of reset time can be selected as described in section "Inverse characteristics".

There is a possibility to activate a preset change (IxMult x= 1, 2, 3 or 4) of the set operation


current via a binary input ENMULTx (enable multiplier). In some applications the operation
value needs to be changed, for example due to changed network switching state.

90 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

The operation current value Ix>, is limited to be between Ix>Max and Ix>Min. The default values
of the limits are the same as the setting limits for Ix>, and the limits can only be used for
reducing the allowed range of Ix>. This feature is used when remote setting of the operation
current value is allowed, making it possible to ensure that the operation value used is
reasonable. If Ix> is set outside Ix>Max and Ix>Min, the closest of the limits to Ix> is used by
the function. If Ix>Max is smaller then Ix>Min, the limits are swapped. The principle of the
limitation is shown in Figure 40.

Ix>Max
MAX hi

u y
Ix>_used
Ix>

MIN lo
Ix>Min

IEC17000018-1-en.vsdx
IEC17000018 V1 EN-US

Figure 40: Logic for limitation of used operation current value

The STDIRCND output provides an integer signal that depends on the start and directional
evaluation and is derived from a binary coded signal as described in Table 44.

Table 44: Code description for STDIRCND output signal


STDIRCND Description
bit 0 (1) General start
bit 1 (2) Direction detected in forward
bit 2 (4) Direction detected in reverse
bit 3 (8) Start in phase L1
bit 4 (16) Forward direction detected in phase L1
bit 5 (32) Reverse direction detected in phase L1
bit 6 (64) Start in phase L2
bit 7 (128) Forward direction detected in phase L2
bit 8 (256) Reverse direction detected in phase L2
bit 9 (512) Start in phase L3
bit 10 (1024) Forward direction detected in phase L3
bit 11 (2048) Reverse direction detected in phase L3

All four steps in OC4PTOC can be blocked from the binary input BLOCK. The binary input
BLKSTx (x=1, 2, 3 or 4) blocks the operation of the respective step.

The start signals from the function can be blocked by the binary input BLKST.The trip signals
from the function can be blocked by the binary input BLKTR.
GUID-E3980B2D-EEDA-4BF1-A07D-E7B721130554 v6
A harmonic restrain of the directional phase overcurrent protection function OC4PTOC can be
chosen. If the ratio of the 2nd harmonic component in relation to the fundamental frequency
component in a phase current exceeds the preset level defined by the parameter 2ndHarmStab
setting, any of the four overcurrent stages can be selectively blocked by the parameter
HarmBlockx setting. When the 2nd harmonic restraint feature is active, the OC4PTOC function
output signal ST2NDHRM will be set to the logical value one.

Breaker protection REQ650 91


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

BLOCK

a
a>b
0.07*IBase b

a
a>b
b
Extract second AND
IOP
harmonic current a
a>b
component b

2ndH_BLOCK_Int
Extract
fundamental
current component
X
2ndHarmStab

IEC13000014-2-en.vsd
IEC13000014 V2 EN-US

Figure 41: Second harmonic blocking

When DirModex is set to Forward/Reverse and Ix> is set at its minimum value,
that is, 5.0% of IBase, the operation from the respective overcurrent step takes
place at 20.0% of IBase. This is done to avoid unintentional maloperations
during unbalanced loading conditions that might appear in power systems and
the unbalanced loading condition might lead to a neutral current in the range
of 10.0% to 15.0% of IBase.

6.2.8 Technical data


M12342-1 v21

Table 45: OC4PTOC technical data


Function Range or value Accuracy
Operate current, step 1-4 (5-2500)% of lBase ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir

Reset ratio > 95% at (50–2500)% of -


lBase
Minimum operate current, step 1-4 (1-10000)% of lBase ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir

Relay characteristic angle (RCA) (40.0–65.0) degrees ±2.0 degrees


Relay operating angle (ROA) (40.0–89.0) degrees ±2.0 degrees
Second harmonic blocking (5–100)% of fundamental ±2.0% of Ir

Independent time delay at 0 to 2 x Iset, step (0.000-60.000) s ±0.2% or ±35 ms whichever is


1-4 greater

Minimum operate time for inverse curves , (0.000-60.000) s ±0.2% or ±35 ms whichever is
step 1-4 greater
Inverse time characteristics, see table 580, 16 curve types See table 580, table 581 and
table 581 and table 582 table 582
Operate time, start non-directional at 0 to Min. = 15 ms -
2 x Iset
Max. = 30 ms
Reset time, start non-directional at 2 x Iset Min. = 15 ms -
to 0
Max. = 30 ms
Operate time, start non-directional at 0 to Min. = 5 ms -
10 x Iset Max. = 20 ms

Table continues on next page

92 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

Function Range or value Accuracy


Reset time, start non-directional at 10 x Iset Min. = 20 ms -
to 0 Max. = 35 ms

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -


Operate frequency, directional overcurrent 38-83 Hz -
Operate frequency, non-directional 10-90 Hz -
overcurrent

6.3 Instantaneous residual overcurrent protection EFPIOC IP14508-1 v3

6.3.1 Identification
M14887-1 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Instantaneous residual overcurrent EFPIOC 50N
protection
IN>>

IEF V1 EN-US

6.3.2 Functionality M12701-3 v16

The Instantaneous residual overcurrent protection (EFPIOC) has a low transient overreach and
short tripping times to allow the use for instantaneous earth-fault protection, with the reach
limited to less than the typical eighty percent of the line at minimum source impedance.
EFPIOC is configured to measure the residual current from the three-phase current inputs and
can be configured to measure the current from a separate current input.

6.3.3 Function block M12614-3 v6

EFPIOC
I3P* TRIP
BLOCK
BLKAR
ENMULT

IEC06000269-3-en.vsdx
IEC06000269 V3 EN-US

Figure 42: EFPIOC function block

6.3.4 Signals IP11448-1 v2

Breaker protection REQ650 93


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

PID-6915-INPUTSIGNALS v4

Table 46: EFPIOC Input signals


Name Type Default Description
I3P GROUP - Three phase currents
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKAR BOOLEAN 0 Block input for auto reclose
ENMULT BOOLEAN 0 Enable current multiplier

PID-6915-OUTPUTSIGNALS v4

Table 47: EFPIOC Output signals


Name Type Description
TRIP BOOLEAN Trip signal

6.3.5 Settings IP11449-1 v2

PID-6915-SETTINGS v4

Table 48: EFPIOC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
IN>> 5 - 2500 %IB 1 200 Operate residual current level in % of
IBase

Table 49: EFPIOC Group settings (advanced)


Name Values (Range) Unit Step Default Description
IN>>Min 5 - 2500 %IB 1 5 Minimum used operate residual
current level in % of IBase, if IN>> is
less than IN>>Min then IN>> is set to
IN>>Min
IN>>Max 5 - 2500 %IB 1 2500 Maximum used operate residual
current level in % of IBase, if IN>> is
greater than IN>>Max then IN>> is set
to IN>>Max
StValMult 0.5 - 5.0 - 0.1 1.0 Multiplier for operate current level

Table 50: EFPIOC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

6.3.6 Monitored data


PID-6915-MONITOREDDATA v4

Table 51: EFPIOC Monitored data


Name Type Values (Range) Unit Description
IN REAL - A Residual current

94 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

6.3.7 Operation principle M12704-3 v8

The sampled analog residual currents are pre-processed in a discrete Fourier filter (DFT) block.
From the fundamental frequency components of the residual current, as well as from the
sample values the equivalent RMS value is derived. This current value is fed to the
Instantaneous residual overcurrent protection (EFPIOC). In a comparator the RMS value is
compared to the set operation current value of the function (IN>>).

If the residual current is larger than the set operation current a signal from the comparator is
set to true. This signal will, without delay, activate the output signal TRIP.

There is also a possibility to activate a preset change of the set operation current via a binary
input (enable multiplier ENMULT). In some applications the operation value needs to be
changed, for example, due to transformer inrush currents.

The operation current value IN>>, is limited to be between IN>>Max and IN>>Min. The default
values of the limits are the same as the setting limits for IN>>, and the limits can only be used
for reducing the allowed range of IN>>. This feature is used when remote setting of the
operation current value is allowed, making it possible to ensure that the operation value used
is reasonable. If IN>> is set outside IN>>Max and IN>>Min, the closest of the limits to IN>> is
used by the function. If IN>>Max is smaller then IN>>Min, the limits are swapped. The principle
of the limitation is shown in Figure 43.

IN>>Max
MAX hi

u y
IN>>_used
IN>>

MIN lo
IN>>Min

IEC17000015-1-en.vsdx
IEC17000015 V1 EN-US

Figure 43: Logic for limitation of used operation current value

EFPIOC function can be blocked from the binary input BLOCK. The trip signals from the
function can be blocked from the binary input BLKAR, that can be activated during single pole
trip and autoreclosing sequences.

6.3.8 Technical data IP11450-1 v1

M12340-2 v9

Table 52: EFPIOC technical data


Function Range or value Accuracy
Operate current (5-2500)% of lBase ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir

Reset ratio > 95% at (50–2500)% of lBase -


Operate time at 0 to 2 x Iset Min. = 15 ms -
Max. = 25 ms
Reset time at 2 x Iset to 0 Min. = 15 ms -
Max. = 25 ms
Critical impulse time 10 ms typically at 0 to 2 x Iset -

Operate time at 0 to 10 x Min. = 5 ms -


Iset Max. = 15 ms

Table continues on next page

Breaker protection REQ650 95


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

Function Range or value Accuracy


Reset time at 10 x Iset to 0 Min. = 25 ms -
Max. = 35 ms
Critical impulse time 2 ms typically at 0 to 10 x Iset -

Dynamic overreach < 5% at t = 100 ms -

6.4 Directional residual overcurrent protection, four steps


EF4PTOC IP14509-1 v8

6.4.1 Identification
M14881-1 v6

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Directional residual overcurrent EF4PTOC 51N_67N
4(IN>)
protection, four steps
4
alt
4
TEF-REVA V2 EN-US

6.4.2 Functionality M13667-3 v19

EF4PTOC has an inverse or definite time delay independent for each step.

All IEC and ANSI time-delayed characteristics are available together with an optional user-
defined characteristic.

EF4PTOC can be set to be directional or non-directional independently for each step.

IDir, UPol and IPol can be independently selected to be either zero sequence or negative
sequence.

A second harmonic blocking can be set individually for each step.

The residual current can be calculated by summing the three-phase currents or taking the
input from the neutral CT.

96 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

6.4.3 Function block M12619-3 v8

EF4PTOC
I3P* TRIP
U3P* TRIN1
I3PPOL* TRIN2
I3PDIR* TRIN3
BLOCK TRIN4
BLKTR TRSOTF
BLKST1 START
BLKST2 STIN1
BLKST3 STIN2
BLKST4 STIN3
ENMULT1 STIN4
ENMULT2 STSOTF
ENMULT3 STFW
ENMULT4 STRV
CBPOS 2NDHARMD
CLOSECB
OPENCB
IEC06000424-5-en.vsdx
IEC06000424 V5 EN-US

Figure 44: EF4PTOC function block

6.4.4 Signals IP11453-1 v2

PID-6967-INPUTSIGNALS v3

Table 53: EF4PTOC Input signals


Name Type Default Description
I3P GROUP - Group connection for operate current
SIGNAL
U3P GROUP - Group connection for polarizing voltage
SIGNAL
I3PPOL GROUP - Group connection for polarizing current
SIGNAL
I3PDIR GROUP - Group connection for directional current
SIGNAL
BLOCK BOOLEAN 0 General block
BLKTR BOOLEAN 0 Block of trip
BLKST1 BOOLEAN 0 Block of step 1 (Start and trip)
BLKST2 BOOLEAN 0 Block of step 2 (Start and trip)
BLKST3 BOOLEAN 0 Block of step 3 (Start and trip)
BLKST4 BOOLEAN 0 Block of step 4 (Start and trip)
ENMULT1 BOOLEAN 0 When activated, the current multiplier is in use for step1
ENMULT2 BOOLEAN 0 When activated, the current multiplier is in use for step2
ENMULT3 BOOLEAN 0 When activated, the current multiplier is in use for step3
ENMULT4 BOOLEAN 0 When activated, the current multiplier is in use for step4
CBPOS BOOLEAN 0 Breaker position
CLOSECB BOOLEAN 0 Breaker close command
OPENCB BOOLEAN 0 Breaker open command

Breaker protection REQ650 97


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

PID-6967-OUTPUTSIGNALS v3

Table 54: EF4PTOC Output signals


Name Type Description
TRIP BOOLEAN General trip signal
TRIN1 BOOLEAN Trip signal from step 1
TRIN2 BOOLEAN Trip signal from step 2
TRIN3 BOOLEAN Trip signal from step 3
TRIN4 BOOLEAN Trip signal from step 4
TRSOTF BOOLEAN Trip signal from earth fault switch onto fault function
START BOOLEAN General start signal
STIN1 BOOLEAN Start signal step 1
STIN2 BOOLEAN Start signal step 2
STIN3 BOOLEAN Start signal step 3
STIN4 BOOLEAN Start signal step 4
STSOTF BOOLEAN Start signal from earth fault switch onto fault function
STFW BOOLEAN Start signal forward direction
STRV BOOLEAN Start signal reverse direction
2NDHARMD BOOLEAN 2nd harmonic block signal

6.4.5 Settings IP11454-1 v2

PID-6967-SETTINGS v3

Table 55: EF4PTOC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
EnDir Disable - - Enable Enabling the Directional calculation
Enable
AngleRCA -180 - 180 Deg 1 65 Relay Characteristic Angle (RCA)
polMethod Voltage - - Voltage Type of polarization
Current
Dual
UPolMin 1 - 100 %UB 1 1 Minimum voltage level for polarization
in % of UBase
IPolMin 2 - 100 %IB 1 5 Minimum current level for polarization
in % of IBase
RNPol 0.50 - 1000.00 Ohm 0.01 5.00 Real part of source impedance used
for current polarisation
XNPol 0.50 - 3000.00 Ohm 0.01 40.00 Imaginary part of source imp. used for
current polarisation
IN>Dir 1 - 100 %IB 1 10 Residual current level in % of IBase for
Direction release
2ndHarmStab 5 - 100 % 1 20 Operate level of 2nd harmonic curr in
% of fundamental curr
BlkParTransf Off - - Off Enable blocking at energizing of
On parallel transformers
Table continues on next page

98 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

Name Values (Range) Unit Step Default Description


UseStartValue IN1> - - IN4> Current level blk at parallel transf
IN2> (step1, 2, 3 or 4)
IN3>
IN4>
SOTF Off - - Off SOTF operation mode (Off/SOTF/
SOTF Undertime/SOTF&Undertime)
UnderTime
SOTF&UnderTime
ActivationSOTF Open - - Open Select signal to activate SOTF: CB-
Closed Open/ -Closed/ -Close cmd
CloseCommand
StepForSOTF Step 2 - - Step 2 Select start from step 2 or 3 to start
Step 3 SOTF
HarmBlkSOTF Off - - Off Enable harmonic restrain function in
On SOTF
tSOTF 0.000 - 60.000 s 0.001 0.200 Time delay for SOTF
t4U 0.000 - 60.000 s 0.001 1.000 Switch-onto-fault active time
ActUnderTime CB position - - CB position Select signal to activate under time
CB command (CB Pos / CB Command)
tUnderTime 0.000 - 60.000 s 0.001 0.300 Time delay for under time
DirMode1 Off - - Non-directional Directional mode of step 1 (Off, Non-
Non-directional dir, Forward, Reverse)
Forward
Reverse
Characterist1 ANSI Ext. inv. - - ANSI Def. Time Time delay characteristic for step 1
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
IN1> 1 - 2500 %IB 1 100 Residual current operate level for step
1 in % of IBase
t1 0.000 - 60.000 s 0.001 0.000 Def time delay or add time delay for
inverse char of step 1
k1 0.05 - 999.00 - 0.01 0.05 Time multiplier for the step 1 selected
time characteristic
IMin1 1.00 - 10000.00 %IB 1.00 100.00 Minimum operate residual current for
step 1 in % of IBase
t1Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse
time characteristic step 1
IN1Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for the residual current
setting value for step 1
HarmBlock1 Off - - On Enable block of step 1 from harmonic
On restrain
Table continues on next page

Breaker protection REQ650 99


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

Name Values (Range) Unit Step Default Description


DirMode2 Off - - Non-directional Directional mode of step 2 (Off, Non-
Non-directional dir, Forward, Reverse)
Forward
Reverse
Characterist2 ANSI Ext. inv. - - ANSI Def. Time Time delay characteristic for step 2
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
IN2> 1 - 2500 %IB 1 50 Residual current operate level for step
2 in % of IBase
t2 0.000 - 60.000 s 0.001 0.400 Def time delay or add time delay for
inverse char of step 2
k2 0.05 - 999.00 - 0.01 0.05 Time multiplier for the step 2 selected
time characteristic
IMin2 1.00 - 10000.00 %IB 1.00 50 Minimum operate residual current for
step 2 in % of IBase
t2Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse
time characteristic step 2
IN2Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for the residual current
setting value for step 2
HarmBlock2 Off - - On Enable block of step 2 from harmonic
On restrain
DirMode3 Off - - Non-directional Directional mode of step 3 (Off, Non-
Non-directional dir, Forward, Reverse)
Forward
Reverse
Characterist3 ANSI Ext. inv. - - ANSI Def. Time Time delay characteristic for step 3
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
IN3> 1 - 2500 %IB 1 33 Residual current operate level for step
3 in % of IBase
Table continues on next page

100 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

Name Values (Range) Unit Step Default Description


t3 0.000 - 60.000 s 0.001 0.800 Def time delay or add time delay for
inverse char of step 3
k3 0.05 - 999.00 - 0.01 0.05 Time multiplier for the step 3 selected
time characteristic
IMin3 1.00 - 10000.00 %IB 1.00 33 Minimum operate residual current for
step 3 in % of IBase
t3Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse
time characteristic step 3
IN3Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for the residual current
setting value for step 3
HarmBlock3 Off - - On Enable block of step 3 from harmonic
On restrain
DirMode4 Off - - Non-directional Directional mode of step 4 (Off, Non-
Non-directional dir, Forward, Reverse)
Forward
Reverse
Characterist4 ANSI Ext. inv. - - ANSI Def. Time Time delay characteristic for step 4
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
IN4> 1 - 2500 %IB 1 17 Residual current operate level for step
4 in % of IBase
t4 0.000 - 60.000 s 0.001 1.200 Def time delay or add time delay for
inverse char of step 4
k4 0.05 - 999.00 - 0.01 0.05 Time multiplier for the step 4 selected
time characteristic
IMin4 1.00 - 10000.00 %IB 1.00 17 Minimum operate residual current for
step 4 in % of IBase
t4Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse
time characteristic step 4
IN4Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for the residual current
setting value for step 4
HarmBlock4 Off - - On Enable block of step 4 from harmonic
On restrain

Breaker protection REQ650 101


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

Table 56: EF4PTOC Group settings (advanced)


Name Values (Range) Unit Step Default Description
IN1>Min 1 - 2500 %IB 1 1 Minimum used operate residual
current level for step 1 in % of IBase, if
IN1> is less than IN1>Min then IN1> is
set to IN1>Min
IN1>Max 1 - 2500 %IB 1 2500 Maximum used operate residual
current level for step 1 in % of IBase, if
IN1> is greater than IN1>Max then IN1>
is set to IN1>Max
ResetTypeCrv1 Instantaneous - - Instantaneous Reset curve type for step1
IEC Reset (Instantaneous / IEC / ANSI)
ANSI reset
tReset1 0.000 - 60.000 s 0.001 0.020 Reset time delay for step 1
tPCrv1 0.005 - 3.000 - 0.001 1.000 Param P for customized inverse trip
time curve for step 1
tACrv1 0.005 - 200.000 - 0.001 13.500 Param A for customized inverse trip
time curve for step 1
tBCrv1 0.00 - 20.00 - 0.01 0.00 Param B for customized inverse trip
time curve for step 1
tCCrv1 0.1 - 10.0 - 0.1 1.0 Param C for customized inverse trip
time curve for step 1
tPRCrv1 0.005 - 3.000 - 0.001 0.500 Param PR for customized inverse reset
time curve for step 1
tTRCrv1 0.005 - 100.000 - 0.001 13.500 Param TR for customized inverse reset
time curve for step 1
tCRCrv1 0.1 - 10.0 - 0.1 1.0 Param CR for customized inverse
reset time curve for step 1
IN2>Min 1 - 2500 %IB 1 1 Minimum used operate residual
current level for step 2 in % of IBase, if
IN2> is less than IN2>Min then IN2> is
set to IN2>Min
IN2>Max 1 - 2500 %IB 1 2500 Maximum used operate residual
current level for step 2 in % of IBase, if
IN2> is greater than IN2>Max then
IN2> is set to IN2>Max
ResetTypeCrv2 Instantaneous - - Instantaneous Reset curve type for step2
IEC Reset (Instantaneous / IEC / ANSI)
ANSI reset
tReset2 0.000 - 60.000 s 0.001 0.020 Reset time delay for step 2
tPCrv2 0.005 - 3.000 - 0.001 1.000 Param P for customized inverse trip
time curve for step 2
tACrv2 0.005 - 200.000 - 0.001 13.500 Param A for customized inverse trip
time curve for step 2
tBCrv2 0.00 - 20.00 - 0.01 0.00 Param B for customized inverse trip
time curve for step 2
tCCrv2 0.1 - 10.0 - 0.1 1.0 Param C for customized inverse trip
time curve for step 2
tPRCrv2 0.005 - 3.000 - 0.001 0.500 Param PR for customized inverse reset
time curve for step 2
tTRCrv2 0.005 - 100.000 - 0.001 13.500 Param TR for customized inverse reset
time curve for step 2
tCRCrv2 0.1 - 10.0 - 0.1 1.0 Param CR for customized inverse
reset time curve for step 2
Table continues on next page

102 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

Name Values (Range) Unit Step Default Description


IN3>Min 1 - 2500 %IB 1 1 Minimum used operate residual
current level for step 3 in % of IBase, if
IN3> is less than IN3>Min then IN3> is
set to IN3>Min
IN3>Max 1 - 2500 %IB 1 2500 Maximum used operate residual
current level for step 3 in % of IBase, if
IN3> is greater than IN3>Max then
IN3> is set to IN3>Max
ResetTypeCrv3 Instantaneous - - Instantaneous Reset curve type for step3
IEC Reset (Instantaneous / IEC / ANSI)
ANSI reset
tReset3 0.000 - 60.000 s 0.001 0.020 Reset time delay for step 3
tPCrv3 0.005 - 3.000 - 0.001 1.000 Param P for customized inverse trip
time curve for step 3
tACrv3 0.005 - 200.000 - 0.001 13.500 Param A for customized inverse trip
time curve for step 3
tBCrv3 0.00 - 20.00 - 0.01 0.00 Param B for customized inverse trip
time curve for step 3
tCCrv3 0.1 - 10.0 - 0.1 1.0 Param C for customized inverse trip
time curve for step 3
tPRCrv3 0.005 - 3.000 - 0.001 0.500 Param PR for customized inverse reset
time curve for step 3
tTRCrv3 0.005 - 100.000 - 0.001 13.500 Param TR for customized inverse reset
time curve for step 3
tCRCrv3 0.1 - 10.0 - 0.1 1.0 Param CR for customized inverse
reset time curve for step 3
IN4>Min 1 - 2500 %IB 1 1 Minimum used operate residual
current level for step 4 in % of IBase, if
IN4> is less than IN4>Min then IN4> is
set to IN4>Min
IN4>Max 1 - 2500 %IB 1 2500 Maximum used operate residual
current level for step 4 in % of IBase, if
IN4> is greater than IN4>Max then
IN4> is set to IN4>Max
ResetTypeCrv4 Instantaneous - - Instantaneous Reset curve type for step4
IEC Reset (Instantaneous / IEC / ANSI)
ANSI reset
tReset4 0.000 - 60.000 s 0.001 0.020 Reset time delay for step 4
tPCrv4 0.005 - 3.000 - 0.001 1.000 Param P for customized inverse trip
time curve for step 4
tACrv4 0.005 - 200.000 - 0.001 13.500 Param A for customized inverse trip
time curve for step 4
tBCrv4 0.00 - 20.00 - 0.01 0.00 Param B for customized inverse trip
time curve for step 4
tCCrv4 0.1 - 10.0 - 0.1 1.0 Param C for customized inverse trip
time curve for step 4
tPRCrv4 0.005 - 3.000 - 0.001 0.500 Param PR for customized inverse reset
time curve for step 4
tTRCrv4 0.005 - 100.000 - 0.001 13.500 Param TR for customized inverse reset
time curve for step 4
tCRCrv4 0.1 - 10.0 - 0.1 1.0 Param CR for customized inverse
reset time curve for step 4

Breaker protection REQ650 103


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

Table 57: EF4PTOC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
SeqTypeIDir Zero seq - - Zero seq Choice of measurand for directional
Neg seq current
SeqTypeIPol Zero seq - - Zero seq Choice of measurand for polarizing
Neg seq current
SeqTypeUPol Zero seq - - Zero seq Choice of measurand for polarizing
Neg seq voltage

6.4.6 Monitored data


PID-6967-MONITOREDDATA v3

Table 58: EF4PTOC Monitored data


Name Type Values (Range) Unit Description
IOp REAL - A Operating current level
UPol REAL - kV Polarizing voltage level
IPol REAL - A Polarizing current level
UPOLIANG REAL - deg Polarizing angle between voltage and
current
IPOLIANG REAL - deg Polarizing current angle

6.4.7 Operation principle IP12992-1 v2

M13941-51 v7
This function has the following four analog inputs on its function block in the configuration
tool:

1. I3P, input used for the operating quantity. Supplies the zero-sequence magnitude
measuring functionality.
2. U3P, input used for the voltage polarizing quantity. Supplies either the zero or the
negative sequence voltage to the directional functionality
3. I3PPOL, input used for the current polarizing quantity. Provides polarizing current to the
directional functionality. This current is normally taken from the grounding of a power
transformer.
4. I3PDIR, input used for directional detection. Supplies either the zero or the negative
sequence current to the directional functionality.

These inputs are connected from the corresponding pre-processing function blocks in the
configuration tool in PCM600.

6.4.7.1 Operating quantity within the function M13941-58 v9

The function always uses residual current (3I0) for its operating quantity. The residual current
can be:

1. directly measured (when a dedicated CT input of the IED is connected in PCM600 to the
fourth analog input of the pre-processing block connected to EF4PTOC function input
I3P). This dedicated IED CT input can be, for example, connected to:

104 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

• parallel connection of current instrument transformers in all three phases (Holm-


Green connection).
• one single core balance current instrument transformer (cable CT).
• one single current instrument transformer located between power system star point
and earth (current transformer located in the star point of a star connected
transformer winding).
• one single current instrument transformer located between two parts of a protected
object (current transformer located between two star points of double star shunt
capacitor bank).
2. calculated from three-phase current input within the IED (when the fourth analog input of
the pre-processing block, connected to EF4PTOC function Analog Input I3P, is not
connected to a dedicated CT input of the IED in PCM600). In such a case, the pre-
processing block will calculate 3I0 from the first three inputs into the pre-processing block
by using the following formula (will take 3I0 from SMAI AI3P and will be connected to
I3PDIR and I3P inputs.

If the zero sequence current is selected,

Iop = 3I0 = IL1 + IL2 + IL3


EQUATION1874 V2 EN-US (Equation 7)

where:
IL1, IL2 and IL3 are fundamental frequency phasors of three individual phase currents.

The residual current is pre-processed by a discrete Fourier filter. Thus the phasor of the
fundamental frequency component of the residual current is derived. The phasor magnitude is
used within the EF4PTOC protection to compare it with the set operation current value of the
four steps (IN1>, IN2>, IN3> or IN4>).

If the residual current is larger than the set operation current and the step is used in non-
directional mode a signal from the comparator for this step is set to true. This signal will,
without delay, activate the output signal STINx (x=step 1-4) for this step and a common START
signal.

6.4.7.2 Internal polarizing M13941-82 v11

A polarizing quantity is used within the protection in order to determine the direction to the
earth fault (forward/reverse).

The function can be set to use voltage polarizing, current polarizing or dual polarizing.

Voltage polarizing
When voltage polarizing is selected, the protection will use the residual voltage -3U0 as the
polarizing quantity U3P.

This voltage can be:

1. directly measured (when a dedicated VT input of the IED is connected in PCM600 to the
fourth analog input of the pre-processing block connected to EF4PTOC function input
U3P). This dedicated IED VT input shall be then connected to the open delta winding of a
three-phase main VT.
2. calculated from three-phase voltage input within the IED (when the fourth analog input of
the pre-processing block, connected to EF4PTOC analog function input U3P, is NOT
connected to a dedicated VT input of the IED in PCM600). In such a case, the pre-

Breaker protection REQ650 105


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

processing block will calculate -3U0 from the first three inputs into the pre-processing
block by using the following formula:

UPol = -3U 0 = -(UL1 + UL2 + UL3)


EQUATION1875 V2 EN-US (Equation 9)

where:
UL1, UL2 and UL3 are fundamental frequency phasors of three individual phase voltages.

In order to use this, all three phase-to-earth voltages must be connected to three
IED VT inputs.

The residual voltage is pre-processed by a discrete fourier filter. Thus, the phasor of the
fundamental frequency component of the residual voltage is derived.

This phasor is used together with the phasor of the operating directional current, in order to
determine the direction to the earth fault (Forward/Reverse). In order to enable voltage
polarizing the magnitude of polarizing voltage shall be bigger than a minimum level defined by
setting parameter UPolMin.

It shall be noted that residual voltage (-3U0) or negative sequence voltage (-3U2) is used to
determine the location of the earth fault. This ensures the required inversion of the polarizing
voltage within the earth-fault function.

Current polarizing
When current polarizing is selected, the function will use an external residual current (3I0) as
the polarizing quantity IPol. This current can be:

1. directly measured (when a dedicated CT input of the IED is connected in PCM600 to the
fourth analog input of the pre-processing block, connected to EF4PTOC function input
I3PPOL). This dedicated IED CT input is then typically connected to one single current
transformer located between power system star point and earth (current transformer
located in the star point of a star connected transformer winding).
• For some special line protection applications, this dedicated IED CT input can be
connected to a parallel connection of current transformers in all three phases (Holm-
Green connection).
2. calculated from three phase current input within the IED (when the fourth analog input
into the pre-processing block, connected to EF4PTOC function analog input I3PPOL, is
NOT connected to a dedicated CT input of the IED in PCM600). In such case, the pre-
processing block will calculate 3I0 from the first three inputs into the pre-processing block
by using the following formula:

IPol = 3I0 = IL1 + IL2 + IL3


EQUATION2018 V2 EN-US (Equation 11)

where:
IL1, IL2 and IL3 are fundamental frequency phasors of three individual phase currents.

The residual current is pre-processed by a discrete fourier filter. Thus the phasor of the
fundamental frequency component of the polarizing current is derived. This phasor is then

106 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

multiplied with the pre-set equivalent zero-sequence source impedance in order to calculate
the equivalent polarizing voltage UIPol in accordance with the following formula:

UIPol = Z 0s × IPol = (RNPol + j × XNPol) × IPol


EQUATION1877 V2 EN-US (Equation 12)

which will be then used, together with the phasor of the operating current, in order to
determine the direction to the earth fault (forward/reverse).

In order to enable current polarizing, the magnitude of the polarizing current shall be bigger
than a minimum level defined by setting parameter IPolMin.

Dual polarizing
When dual polarizing is selected, the function will use the vectorial sum of the voltage based
and current based polarizing in accordance with the following formula:

UTotPol=UPol  UIPol=UPol  Z 0s  IPol  UPol   RNPol  jXNPol   Ipol


IECEQUATION2408 V2 EN-US (Equation 13)

UPol and IPol can be either zero sequence component or negative sequence component
depending upon the user selection.

Then the phasor of the total polarizing voltage UTotPol will be used, together with the phasor
of the operating current, to determine the direction of the earth fault (forward/reverse).

6.4.7.3 External polarizing for earth-fault function M13941-144 v6

The individual steps within the protection can be set as non-directional. When this setting is
selected, it is possible via the function binary input BLKSTx to provide external directional
control (that is, torque control) by, for example, using one of the following functions if
available in the IED:

1. Distance protection directional function.


2. Negative sequence polarized general current and voltage multi purpose protection
function.

6.4.7.4 Directional detection for earth fault function GUID-FC382DD3-E2C8-455E-8CD5-1DE1793DD178 v6

Zero sequence components will be used for detecting directionality for the earth fault
function. In some cases, zero sequence quantities might detect directionality incorrectly. In
such a scenario, negative sequence quantities will be used. The user can select either zero
sequence components or negative sequence components for detecting directionality with the
parameter SeqTypeIPol. I3PDIR input is always connected to the same source as I3P input.

6.4.7.5 Base quantities within the protection M13941-152 v6

The base quantities are entered as global settings for all functions in the IED. Base current
(IBase) shall be entered as rated phase current of the protected object in primary amperes.
Base voltage (UBase) shall be entered as rated phase-to-phase voltage of the protected object
in primary kV.

6.4.7.6 Internal earth-fault protection structure M13941-157 v5

The protection is internally divided into the following parts:

Breaker protection REQ650 107


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

1. Four residual overcurrent steps.


2. Directional supervision element for residual overcurrent steps with integrated directional
comparison step for communication based earth-fault protection schemes (permissive or
blocking).
3. Second harmonic blocking element with additional feature for sealed-in blocking during
switching of parallel transformers.
4. Switch on to fault feature with integrated Under-Time logic for detection of breaker
problems during breaker opening or closing sequence.

6.4.7.7 Four residual overcurrent steps M13941-166 v8

Each overcurrent step uses operating quantity Iop (residual current) as the measuring
quantity. Each of the four residual overcurrent steps has the following built-in facilities:

• Directional mode can be set to Off/Non-directional/Forward/Reverse. By this parameter


setting the directional mode of the step is selected.
• Residual current start value.
• Type of operating characteristic (inverse or definite time). By this parameter setting it is
possible to select inverse or definite time delay for the earth-fault protection. Most of the
standard IEC and ANSI inverse characteristics are available. For the complete list of
available inverse curves, please refer to section "Inverse characteristics".
• Type of reset characteristic (Instantaneous / IEC Reset / ANSI Reset). By this parameter
setting it is possible to select the reset characteristic of the step. For the complete list of
available reset curves, please refer to section "Inverse characteristics".
• Time delay related settings. By these parameter settings the properties like definite time
delay, minimum operating time for inverse curves, reset time delay and parameters to
define user programmable inverse curve are defined.
• Supervision by second harmonic blocking feature (On/Off). By this parameter setting it is
possible to prevent operation of the step if the second harmonic content in the residual
current exceeds the preset level.
• Multiplier for scaling of the set residual current pickup value by external binary signal. By
this parameter setting it is possible to increase residual current pickup value when
function binary input ENMULTx has logical value 1.
• The operation current value INx>, is limited to be between INx>Max and INx>Min. The
default values of the limits are the same as the setting limits for INx>, and the limits can
only be used for reducing the allowed range of INx>. This feature is used when remote
setting of the operation current value is allowed, making it possible to ensure that the
operation value used is reasonable. If INx> is set outside INx>Max and INx>Min, the closest
of the limits to INx> is used by the function. If INx>Max is smaller then INx>Min, the limits
are swapped. The principle of the limitation is shown in Figure 45.

INx>Max
MAX hi

u y
INx>_used
INx>

MIN lo
INx>Min
IEC17000017-1-en.vsdx
IEC17000017 V1 EN-US

Figure 45: Logic for limitation of used operation current value

Simplified logic diagram for one residual overcurrent step is shown in Figure 46.

108 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

BLKTR
EMULTX

IMinx Characteristx=DefTime
X T b
a>b
F a
tx TRINx
AND AND
|IOP|
a OR t
a>b
b

STINx
INxMult AND
X T
INx> F
AND Inverse
BLKSTx
AND
BLOCK Characteristx=Inverse

txmin
2ndHarm_BLOCK_Int
OR t
HarmRestrainx=Off

DirModex=Off OR STEPx_DIR_Int
DirModex=Non-directional
DirModex=Forward
AND OR
FORWARD_Int
DirModex=Reverse

AND
REVERSE_Int

IEC10000008.vsd

IEC10000008 V5 EN-US

Figure 46: Simplified logic diagram for residual overcurrent step x, where x = step 1, 2, 3 or 4
The protection can be completely blocked from the binary input BLOCK. Output signals for
respective step, and STINx and TRINx, can be blocked from the binary input BLKSTx. The trip
signals from the function can be blocked from the binary input BLKTR.

6.4.7.8 Directional supervision element with integrated directional comparison


function M13941-179 v11

At least one of the four residual overcurrent steps shall be set as directional in
order to enable execution of the directional supervision element and the
integrated directional comparison function.

The protection has an integrated directional feature. As the operating quantity current Iop is
always used, the polarizing method is determined by the parameter setting polMethod. The
polarizing quantity will be selected by the function in one of the following three ways:

1. When polMethod = Voltage, UPol will be used as polarizing quantity.


2. When polMethod = Current, IPol will be used as polarizing quantity.
3. When polMethod = Dual, UPol + IPol · ZNPol will be used as polarizing quantity.

The operating and polarizing quantity are then used inside the directional element, as shown
in Figure 47, in order to determine the direction of the earth fault.

Breaker protection REQ650 109


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

Operating area

STRV
0.6 * IN>DIR
Characteristic for reverse
release of measuring steps
-RCA -85 deg
Characteristic
for STRV 40% of
IN>DIR RCA +85 deg

RCA
65° Upol = -3U 0

-RCA +85 deg

RCA -85 deg


Characteristic for forward
release of measuring steps
IN>DIR

STFW

I op = 3I0

Operating area
Characteristic
for STFW IEC11000243-1-en.ai
IEC11000243 V1 EN-US

Figure 47: Operating characteristic for earth-fault directional element using the zero
sequence components
The relevant setting parameters for the directional supervision element are:

• The directional element will be internally enabled to operate as soon as Iop is bigger than
40% of IN>Dir and the directional condition is fulfilled in the set direction.
• The relay characteristic angle AngleRCA, which defines the position of forward and reverse
areas in the operating characteristic.

The directional comparison will set the output binary signals:

1. STFW=1 when operating quantity magnitude Iop x cos(φ - AngleRCA) is bigger than
setting parameter IN>Dir and directional supervision element detects fault in forward
direction.
2. STRV=1 when operating quantity magnitude Iop x cos(φ - AngleRCA) is bigger than 60% of
setting parameter IN>Dir and directional supervision element detects fault in reverse
direction.

These signals shall be used for communication based earth-fault teleprotection


communication schemes (permissive or blocking).

Simplified logic diagram for directional supervision element with integrated directional
comparison step is shown in Figure 48:

110 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

| IopDir |
a
a>b STRV
b AND
REVERSE_Int
0.6
X
a
a>b STFW
IN>Dir b AND
FORWARD_Int

X
0.4

FWD
AND FORWARD_Int
AngleRCA
polMethod=Voltage
OR

Characteristic
UPolMin

Directional
polMethod=Dual UPol IPolMin
T
I3PDIR
polMethod=Current 0.0 F
OR
UTotPol
IPol AND REVERSE_Int
T RVS
0.0 F

UIPol STAGE1_DIR_Int
RNPol Complex X T STAGE2_DIR_Int
XNPol Number 0.0 F STAGE3_DIR_Int OR
STAGE4_DIR_Int
BLOCK AND

IEC07000067-6-en.vsdx

IEC07000067 V6 EN-US

Figure 48: Simplified logic diagram for directional supervision element with integrated directional
comparison step

6.4.7.9 Second harmonic blocking element M13941-200 v8

A harmonic restrain can be chosen for each step by a parameter setting HarmBlockx. If the
ratio of the 2nd harmonic component in relation to the fundamental frequency component in
the residual current exceeds the preset level (defined by parameter 2ndHarmStab), output
signal 2NDHARMD is set to logical value one and the harmonic restraining feature to the
function block will be applicable.

Blocking from the 2nd harmonic element activates if all of three criteria are satisfied:

1. The fundamental frequency component of the current > 1% of IBase


2. The second harmonic component > 1% of IBase
3. The ratio of the 2nd harmonic component in relation to the fundamental frequency
component in the residual current exceeds the preset level defined by the parameter
2ndHarmStab setting

In addition to the basic functionality explained above, the 2nd harmonic blocking can be set in
such way to seal-in until residual current disappears. This feature might be required to
stabilize EF4PTOC during switching of parallel transformers in the station. In case of parallel
transformers there is a risk of sympathetic inrush current. If one of the transformers is in
operation, and the parallel transformer is switched in, the asymmetric inrush current of the
switched-in transformer will cause partial saturation of the transformer already in service. This
is called transferred saturation. The 2nd harmonic of the inrush currents of the two

Breaker protection REQ650 111


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

transformers is in phase opposition. The summation of the two currents thus gives a small 2nd
harmonic current. The residual fundamental current is however significant. The inrush current
of the transformer in service before the parallel transformer energizing, is a little delayed
compared to the first transformer. Therefore, we have high 2nd harmonic current component
initially. After a short period this current is however small and the normal 2nd harmonic
blocking resets. If the BlkParTransf function is activated, the 2nd harmonic restrain signal is
latched as long as the residual current measured by the relay is larger than a selected step
current level by using setting UseStartValue.

This feature has been called Block for Parallel Transformers. This 2nd harmonic seal-in feature
is activated when all of the following three conditions are simultaneously fulfilled:

1. Feature is enabled by entering setting parameter BlkParTransf = On.


2. Basic 2nd harmonic restraint feature has been active for at least 70ms.
3. Residual current magnitude is higher than the set start value for one of the four residual
overcurrent stages. By a parameter setting UseStartValue it is possible to select which
one of the four start values that will be used (IN1> or IN2> or IN3> or IN4>).

Once Block for Parallel Transformers is activated, the basic 2nd harmonic blocking signal is
sealed-in until the residual current magnitude falls below a value defined by parameter setting
UseStartValue (see condition 3 above).

Simplified logic diagram for 2nd harmonic blocking feature is shown in Figure 49.

112 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

BLOCK

a
a>b
0.07*IBase b

a
a>b
b
Extract second AND
IOP
harmonic current a
a>b
component b

Extract
fundamental
current component
X
2ndHarmStab

q-1

t=70ms OR
t AND OR 2ndH_BLOCK_Int

BlkParTransf=On

a
a>b
b
UseStartValue
IN1>
IN2>
IN3>
IN4>

q-1 = unit delay


IEC13000015-4-en.vsdx

IEC13000015 V4 EN-US

Figure 49: Simplified logic diagram for 2nd harmonic blocking feature and Block for Parallel
Transformers feature

6.4.7.10 Switch on to fault feature M13941-211 v5

Integrated in the four step residual overcurrent protection are the switch on to fault logic
(SOTF) and the under-time logic. The setting parameter SOTF is set to activate SOTF, the
under-time logic or both. When the circuit breaker is closing there is a risk to close it onto a
permanent fault, for example during an autoreclosing sequence. The SOTF logic will enable
fast fault clearance during such situations. The time during which SOTF and under-time logics
will be active after activation is defined by the setting parameter t4U.

The SOTF logic uses the start signal from step 2 or step 3 for its operation, selected by setting
parameter StepForSOTF. The setting parameter ActivationSOTF can be set for activation of CB
position open change, CB position closed change or CB close command. In case of a residual
current start from step 2 or 3 (dependent on setting) the function will give a trip after a set
delay tSOTF. This delay is normally set to a short time (default 200 ms).

The under-time logic acts as a circuit breaker pole-discordance protection, but it is only active
immediately after breaker switching. The under-time logic can only be used in solidly or low
impedance grounded systems.

The under-time logic always uses the start signal from the step 4. The under-time logic will
normally be set to operate for a lower current level than the SOTF function. The under-time

Breaker protection REQ650 113


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

logic can also be blocked by the 2nd harmonic restraint feature. This enables high sensitivity
even if power transformer inrush currents can occur at breaker closing. This logic is typically
used to detect asymmetry of CB poles immediately after switching of the circuit breaker. The
under-time logic is activated either from change in circuit breaker position or from circuit
breaker close and open command pulses. This selection is done by setting parameter
ActUnderTime. In case of a start from step 4 this logic will give a trip after a set delay
tUnderTime. This delay is normally set to a relatively short time (default 300 ms).

SOTF

200 ms
Open
t
t4U
200 ms
Closed
t ActivationSOTF

tSOTF
Close command AND
AND t
STIN2

StepForSOTF
STIN3

SOTF
BLOCK
OFF
SOTF
UNDERTIME TRIP
UnderTime

tUnderTime
SOTF or
2nd Harmonic AND
HarmResSOFT t UnderTime

OR

Open
Close OR

t4U

Close command ActUnderTime


AND

STIN4

IEC06000643-6-en.vsdx

IEC06000643 V6 EN-US

Figure 50: Simplified logic diagram for SOTF and under-time features
M13941-3 v6
Simplified logic diagram for the complete EF4PTOC function is shown in Figure 51:

114 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

signal to communication scheme


Directional Check
Element

4 step over current


INPol Direction
operatingCurrent element
Element
3U0 One element for each
earthFaultDirection step
3I0
angleValid
I3PDIR
DirMode
enableDir

harmRestrBlock
3I0 Harmonic
Restraint 1
Element TRIP


start step 2, 3 and 4

Blocking at parallel
transformers
SwitchOnToFault
TRSOTF

CB
DirMode pos
or cmd
enableDir
Mode
Selection enableStep1-4

DirectionalMode1-4

IEC06000376-4-en.vsdx
IEC06000376 V4 EN-US

Figure 51: Functional overview of EF4PTOC

6.4.8 Technical data IP11455-1 v1

M15223-1 v18

Table 59: EF4PTOC technical data


Function Range or value Accuracy
Operate current, step 1-4 (1-2500)% of IBase ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir

Reset ratio > 95% at (10-2500)% of -


IBase
Relay characteristic angle (-180 to 180) degrees ±2.0 degrees
(RCA)
Operate current for directional release (1–100)% of IBase For RCA ±60 degrees:
±2.5% of Ir at I ≤ Ir
±2.5% of I at I > Ir

Independent time delay at 0 to 2 x Iset, (0.000-60.000) s ±0.2% or ±35 ms whichever is


step 1-4 greater

Minimum operate time for inverse curves, (0.000 - 60.000) s ±0.2% or ±35 ms whichever is
step 1-4 greater
Inverse time characteristics, see Table 16 curve types See Table 580, Table 581 and
580, Table 581 and Table 582 Table 582
Second harmonic blocking (5–100)% of fundamental ±2.0% of Ir

Minimum polarizing voltage (1–100)% of UBase ±0.5% of Ur

Minimum polarizing current (2-100)% of IBase ±1.0% of Ir

Real part of source Z used for current (0.50-1000.00) W/phase -


polarization
Table continues on next page

Breaker protection REQ650 115


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

Function Range or value Accuracy


Imaginary part of source Z used for (0.50–3000.00) W/phase -
current polarization
*Operate time, start non-directional at 0 Min. = 15 ms -
to 2 x Iset Max. = 30 ms

*Reset time, start non-directional at 2 x Min. = 15 ms -


Iset to 0 Max. = 30 ms

*Operate time, start non-directional at 0 Min. = 5 ms -


to 10 x Iset Max. = 20 ms

*Reset time, start non-directional at 10 x Min. = 20 ms -


Iset to 0 Max. = 35 ms

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -


*Note: Operate time and reset time are only valid if harmonic blocking is turned off for a step.

6.5 Four step directional negative phase sequence


overcurrent protection NS4PTOC GUID-E8CF8AA2-AF54-4FD1-A379-3E55DCA2FA3A v1

6.5.1 Identification
GUID-E1720ADA-7F80-4F2C-82A1-EF2C9EF6A4B4 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Four step negative sequence NS4PTOC 46I2
overcurrent protection I2
4
alt
4
IEC10000053 V1 EN-US

6.5.2 Functionality GUID-485E9D36-0032-4559-9204-101539A32F47 v6

Four step directional negative phase sequence overcurrent protection (NS4PTOC) has an
inverse or definite time delay independent for each step separately.

All IEC and ANSI time delayed characteristics are available together with an optional user
defined characteristic.

The directional function is voltage polarized.

NS4PTOC can be set directional or non-directional independently for each of the steps.

116 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

6.5.3 Function block GUID-8EDB8B12-0D86-4F6B-A1FB-F5D0C72AA545 v2

NS4PTOC
I3P* TRIP
I3PDIR* TR1
U3P* TR2
BLOCK TR3
BLKTR TR4
BLKST1 START
BLKST2 ST1
BLKST3 ST2
BLKST4 ST3
ENMULT1 ST4
ENMULT2 STFW
ENMULT3 STRV
ENMULT4

IEC10000054-2-en.vsd
IEC10000054 V2 EN-US

Figure 52: NS4PTOC function block

6.5.4 Signals
PID-4151-INPUTSIGNALS v4

Table 60: NS4PTOC Input signals


Name Type Default Description
I3P GROUP - Group connection for operate current
SIGNAL
I3PDIR GROUP - Group connection for directional current
SIGNAL
U3P GROUP - Group connection for polarizing voltage
SIGNAL
BLOCK BOOLEAN 0 General block
BLKTR BOOLEAN 0 Block of trip
BLKST1 BOOLEAN 0 Block of step 1 (Start and trip)
BLKST2 BOOLEAN 0 Block of step 2 (Start and trip)
BLKST3 BOOLEAN 0 Block of step 3 (Start and trip)
BLKST4 BOOLEAN 0 Block of step 4 (Start and trip)
ENMULT1 BOOLEAN 0 When activated, the current multiplier is in use for step1
ENMULT2 BOOLEAN 0 When activated, the current multiplier is in use for step2
ENMULT3 BOOLEAN 0 When activated, the current multiplier is in use for step3
ENMULT4 BOOLEAN 0 When activated, the current multiplier is in use for step4

PID-4151-OUTPUTSIGNALS v4

Table 61: NS4PTOC Output signals


Name Type Description
TRIP BOOLEAN General trip signal
TR1 BOOLEAN Trip signal from step 1
TR2 BOOLEAN Trip signal from step 2
TR3 BOOLEAN Trip signal from step 3
TR4 BOOLEAN Trip signal from step 4
START BOOLEAN General start signal
ST1 BOOLEAN Start signal step 1
Table continues on next page

Breaker protection REQ650 117


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

Name Type Description


ST2 BOOLEAN Start signal step 2
ST3 BOOLEAN Start signal step 3
ST4 BOOLEAN Start signal step 4
STFW BOOLEAN Forward directional start signal
STRV BOOLEAN Reverse directional start signal

6.5.5 Settings
PID-4151-SETTINGS v4

Table 62: NS4PTOC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
EnDir Disable - - Enable Enabling the Directional calculation
Enable
AngleRCA -180 - 180 Deg 1 65 Relay characteristic angle (RCA)
UPolMin 1 - 100 %UB 1 5 Minimum voltage level for polarization
in % of UBase
I2>Dir 1 - 100 %IB 1 10 Residual current level in % of IBase for
Direction release
DirMode1 Off - - Non-directional Directional mode of step 1 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Characterist1 ANSI Ext. inv. - - ANSI Def. Time Time delay characteristic for step 1
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
I2-1> 1 - 2500 %IB 1 100 Negative sequence current op level for
step 1 in % of IBase
t1 0.000 - 60.000 s 0.001 0.000 Time delay of step 1 when definite
time char. is selected
k1 0.05 - 999.00 - 0.01 0.05 Time multiplier for the step 1 selected
time characteristic
IMin1 1.00 - 10000.00 %IB 1.00 100.00 Minimum current for step 1
t1Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse
time characteristic step 1
I1Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for scaling the current
setting value for step 1
Table continues on next page

118 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

Name Values (Range) Unit Step Default Description


DirMode2 Off - - Non-directional Directional mode of step 2 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Characterist2 ANSI Ext. inv. - - ANSI Def. Time Time delay characteristic for step 2
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
I2-2> 1 - 2500 %IB 1 50 Negative sequence current op level for
step 2 in % of IBase
t2 0.000 - 60.000 s 0.001 0.400 Time delay of step 2 when definite
time char. is selected
k2 0.05 - 999.00 - 0.01 0.05 Time multiplier for the step 2 selected
time characteristic
IMin2 1.00 - 10000.00 %IB 1.00 50 Minimum current for step 2
t2Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse
time characteristic step 2
I2Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for scaling the current
setting value for step 2
DirMode3 Off - - Non-directional Directional mode of step 3 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Characterist3 ANSI Ext. inv. - - ANSI Def. Time Time delay characteristic for step 3
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
I2-3> 1 - 2500 %IB 1 33 Negative sequence current op level for
step 3 in % of IBase
t3 0.000 - 60.000 s 0.001 0.800 Time delay of step 3 when definite
time char. is selected
Table continues on next page

Breaker protection REQ650 119


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

Name Values (Range) Unit Step Default Description


k3 0.05 - 999.00 - 0.01 0.05 Time multiplier for the step 3 selected
time characteristic
IMin3 1.00 - 10000.00 %IB 1.00 33 Minimum current for step 3
t3Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse
time characteristic step 3
I3Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for scaling the current
setting value for step 3
DirMode4 Off - - Non-directional Directional mode of step 4 (off, nodir,
Non-directional forward, reverse)
Forward
Reverse
Characterist4 ANSI Ext. inv. - - ANSI Def. Time Time delay characteristic for step 4
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
I2-4> 1 - 2500 %IB 1 17 Negative sequence current op level for
step 4 in % of IBase
t4 0.000 - 60.000 s 0.001 1.200 Time delay of step 4 when definite
time char. is selected
k4 0.05 - 999.00 - 0.01 0.05 Time multiplier for the step 4 selected
time characteristic
IMin4 1.00 - 10000.00 %IB 1.00 17 Minimum current for step 4
t4Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse
time characteristic step 4
I4Mult 1.0 - 10.0 - 0.1 2.0 Multiplier for scaling the current
setting value for step 4

Table 63: NS4PTOC Group settings (advanced)


Name Values (Range) Unit Step Default Description
ResetTypeCrv1 Instantaneous - - Instantaneous Reset curve type for step1
IEC Reset (Instantaneous / IEC / ANSI)
ANSI reset
tReset1 0.000 - 60.000 s 0.001 0.020 Reset time delay for step 1
tPCrv1 0.005 - 3.000 - 0.001 1.000 Param P for customized inverse trip
time curve for step 1
tACrv1 0.005 - 200.000 - 0.001 13.500 Param A for customized inverse trip
time curve for step 1
tBCrv1 0.00 - 20.00 - 0.01 0.00 Param B for customized inverse trip
time curve for step 1
Table continues on next page

120 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

Name Values (Range) Unit Step Default Description


tCCrv1 0.1 - 10.0 - 0.1 1.0 Param C for customized inverse trip
time curve for step 1
tPRCrv1 0.005 - 3.000 - 0.001 0.500 Param PR for customized inverse reset
time curve for step 1
tTRCrv1 0.005 - 100.000 - 0.001 13.500 Param TR for customized inverse reset
time curve for step
tCRCrv1 0.1 - 10.0 - 0.1 1.0 Param CR for customized inverse
reset time curve for step 1
ResetTypeCrv2 Instantaneous - - Instantaneous Reset curve type for step2
IEC Reset (Instantaneous / IEC / ANSI)
ANSI reset
tReset2 0.000 - 60.000 s 0.001 0.020 Reset time delay for step 2
tPCrv2 0.005 - 3.000 - 0.001 1.000 Param P for customized inverse trip
time curve for step 2
tACrv2 0.005 - 200.000 - 0.001 13.500 Param A for customized inverse trip
time curve for step 2
tBCrv2 0.00 - 20.00 - 0.01 0.00 Param B for customized inverse trip
time curve for step 2
tCCrv2 0.1 - 10.0 - 0.1 1.0 Param C for customized inverse trip
time curve for step 2
tPRCrv2 0.005 - 3.000 - 0.001 0.500 Param PR for customized inverse reset
time curve for step 2
tTRCrv2 0.005 - 100.000 - 0.001 13.500 Param TR for customized inverse reset
time curve for step 2
tCRCrv2 0.1 - 10.0 - 0.1 1.0 Param C for customized inverse reset
time curve for step 2
ResetTypeCrv3 Instantaneous - - Instantaneous Reset curve type for step3
IEC Reset (Instantaneous / IEC / ANSI)
ANSI reset
tReset3 0.000 - 60.000 s 0.001 0.020 Reset time delay for step 3
tPCrv3 0.005 - 3.000 - 0.001 1.000 Param P for customized inverse trip
time curve for step 3
tACrv3 0.005 - 200.000 - 0.001 13.500 Param A for customized inverse trip
time curve for step 3
tBCrv3 0.00 - 20.00 - 0.01 0.00 Param B for customized inverse trip
time curve for step 3
tCCrv3 0.1 - 10.0 - 0.1 1.0 Param C for customized inverse trip
time curve for step 3
tPRCrv3 0.005 - 3.000 - 0.001 0.500 Param PR for customized inverse reset
time curve for step 3
tTRCrv3 0.005 - 100.000 - 0.001 13.500 Param TR for customized inverse reset
time curve for step 3
tCRCrv3 0.1 - 10.0 - 0.1 1.0 Param CR for customized inverse
reset time curve for step 3
ResetTypeCrv4 Instantaneous - - Instantaneous Reset curve type for step4
IEC Reset (Instantaneous / IEC / ANSI)
ANSI reset
tReset4 0.000 - 60.000 s 0.001 0.020 Reset time delay for step 4
tPCrv4 0.005 - 3.000 - 0.001 1.000 Param P for customized inverse trip
time curve for step 4
tACrv4 0.005 - 200.000 - 0.001 13.500 Param A for customized inverse trip
time curve for step 4
Table continues on next page

Breaker protection REQ650 121


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

Name Values (Range) Unit Step Default Description


tBCrv4 0.00 - 20.00 - 0.01 0.00 Param B for customized inverse trip
time curve for step 4
tCCrv4 0.1 - 10.0 - 0.1 1.0 Param C for customized inverse trip
time curve for step 4
tPRCrv4 0.005 - 3.000 - 0.001 0.500 Param PR for customized inverse reset
time curve for step 4
tTRCrv4 0.005 - 100.000 - 0.001 13.500 Param TR for customized inverse reset
time curve for step 4
tCRCrv4 0.1 - 10.0 - 0.1 1.0 Param CR for customized inverse
reset time curve for step 4

Table 64: NS4PTOC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

6.5.6 Monitored data


PID-4151-MONITOREDDATA v4

Table 65: NS4PTOC Monitored data


Name Type Values (Range) Unit Description
IOp REAL - A Operating current level
UPol REAL - kV Polarizing voltage level
UPOLIANG REAL - deg Polarizing angle between voltage and
current

6.5.7 Operation principle GUID-8923EC0B-A5BA-431B-9699-EB67E2637560 v3

Four step negative sequence overcurrent protection NS4PTOC function has the following
three “Analog Inputs” on its function block in the configuration tool:

1. I3P, input used for “Operating Quantity”.


2. U3P, input used for “Polarizing Quantity”.
3. I3PDIR, input used for "Directional finding"

These inputs are connected from the corresponding pre-processing function blocks in the
Configuration Tool within PCM600.

6.5.7.1 Operating quantity within the function GUID-8F0A5BDE-AC98-4188-9085-42A8DF00C476 v3

Four step negative sequence overcurrent protection NS4PTOC function always uses negative
sequence current (I2) for its operating quantity. The negative sequence current is calculated
from three-phase current input within the IED. The pre-processing block calculates I2 from the
first three inputs into the pre-processing block by using the following formula:

1
I2 =
3
(
× IL1 + a × IL 2 + a × IL 3
2
)
EQUATION2266 V2 EN-US (Equation 14)

122 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

where:
IL1, IL2 and IL3 are fundamental frequency phasors of three individual phase currents.
a is so called operator which gives a phase shift of 120 deg, that is, a = 1∠120
deg

a2 similarly gives a phase shift of 240 deg, that is, a2 = 1∠240 deg

The phasor magnitude is used within the NS4PTOC protection to compare it with the set
operation current value of the four steps (I1>, I2>, I3> or I4>). If the negative sequence current
is larger than the set operation current and the step is used in non-directional mode a signal
from the comparator for this step is set to true. This signal, without delay, activates the
output signal STx (x=1 - 4) for this step and a common START signal.

6.5.7.2 Internal polarizing facility of the function GUID-B00FE98B-F269-4F1B-AC03-68250798851B v3

A polarizing quantity is used within the protection to determine the direction to the fault
(Forward/Reverse).

Four step negative sequence overcurrent protection NS4PTOC function uses the voltage
polarizing method.

NS4PTOC uses the negative sequence voltage -U2 as polarizing quantity U3P. This voltage is
calculated from three phase voltage input within the IED. The pre-processing block calculates -
U2 from the first three inputs into the pre-processing block by using the following formula:

1
UPol = -U 2 = - × (UL1 + a 2 × UL 2 + a × UL3 )
3
EQUATION2267 V2 EN-US

where:
UL1, UL2 and UL3 are fundamental frequency phasors of three individual phase voltages.

To use this all three phase-to-earth voltages must be connected to three IED VT
inputs.

This phasor is used together with the phasor of the operating current, in order to determine
the direction to the fault (Forward/Reverse).To enable voltage polarizing the magnitude of
polarizing voltage must be bigger than a minimum level defined by setting UpolMin.

Note that –U2 is used to determine the location of the fault. This ensures the required
inversion of the polarizing voltage within the function.

6.5.7.3 External polarizing for negative sequence function GUID-21930E81-1B40-4BA4-B1D8-3B365327AEF6 v1

The individual steps within the protection can be set as non-directional. When this setting is
selected it is then possible via function binary input BLKSTx (where x indicates the relevant
step within the protection) to provide external directional control (that is, torque control) by
for example using one of the following functions if available in the IED:

Breaker protection REQ650 123


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

• Distance protection directional function


• Negative sequence polarized general current and voltage multi purpose protection
function

6.5.7.4 Internal negative sequence protection structure GUID-A6B9B3F1-A1FE-4653-A8AF-61FCCF19CE95 v1

The protection is internally divided into the following parts:

• Four negative sequence overcurrent steps


• Directional supervision element for negative sequence overcurrent steps with integrated
directional comparison step for communication based negative sequence protection
schemes (permissive or blocking)

Each part is described separately in the following sections.

6.5.7.5 Four negative sequence overcurrent stages GUID-D8ACB136-2BA6-4ADA-A096-5C38BD12DB72 v2

Each overcurrent stage uses Operating Quantity I2 (negative sequence current) as measuring
quantity. Every of the four overcurrent stage has the following built-in facilities:

• Operating mode (Off/ Non-directional /Forward / Reverse). By this parameter setting the
operating mode of the stage is selected. Note that the directional decision (Forward/
Reverse) is not made within the overcurrent stage itself. The direction of the fault is
determined in common “Directional Supervision Element” described in the next
paragraph.
• Negative sequence current pickup value.
• Type of operating characteristic (Inverse or Definite Time). By this parameter setting it is
possible to select Inverse or definite time delay for negative sequence overcurrent
function. Most of the standard IEC and ANSI inverse characteristics are available. For the
complete list of available inverse curves, refer to Chapter "Inverse characteristics"
• Type of reset characteristic (Instantaneous / IEC Reset /ANSI reset).By this parameter
setting it is possible to select the reset characteristic of the stage. For the complete list of
available reset curves, refer to Chapter "Inverse characteristics"
• Time delay related settings. By these parameter settings the properties like definite time
delay, minimum operating time for inverse curves, reset time delay and parameters to
define user programmable inverse curve are defined.
• Multiplier for scaling of the set negative sequence current pickup value by external binary
signal. By this parameter setting it is possible to increase negative sequence current
pickup value when function binary input ENMULTx has logical value 1.

Simplified logic diagram for one negative sequence overcurrent stage is shown in the
following figure:

124 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

BLKTR

Characteristx=DefTime AND
TRx
|IOP| AND
tx
a OR
a>b
ENMULTx b

STx
IxMult AND
X T
Ix> F
txmin
BLKSTx AND
BLOCK
Inverse

Characteristx=Inverse

DirModex=Off OR STAGEx_DIR_Int
DirModex=Non-directional
DirModex=Forward
AND OR
FORWARD_Int
DirModex=Reverse

AND
REVERSE_Int

IEC09000683.vsd
IEC09000683 V3 EN-US

Figure 53: Simplified logic diagram for negative sequence overcurrent stage x , where x=1, 2, 3 or 4
NS4PTOC can be completely blocked from the binary input BLOCK. The start signals from
NS4PTOC for each stage can be blocked from the binary input BLKSTx. The trip signals from
NS4PTOC can be blocked from the binary input BLKTR.

6.5.7.6 Directional supervision element with integrated directional comparison


function GUID-F54E21F7-7C99-41D6-BEC6-2D6EC6D2B2A3 v3

At least one of the four negative sequence overcurrent steps must be set as
directional in order to enable execution of the directional supervision element
and the integrated directional comparison function.

The operating and polarizing quantity are then used inside the directional element, as shown
in figure 54, to determine the direction of the fault.

Breaker protection REQ650 125


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

Reverse
Area

AngleRCA Upol=-U2

Forward
Area
Iop = I2

IEC10000031-1-en.vsd
IEC10000031 V1 EN-US

Figure 54: Operating characteristic for fault directional element

Two relevant setting parameters for directional supervision element are:

• Directional element is internally enable to operate as soon as Iop is bigger than 40% of
I>Dir and the directional condition is fulfilled in set direction.
• Relay characteristic angle AngleRCA which defines the position of forward and reverse
areas in the operating characteristic.

Directional comparison step, built-in within directional supervision element, set NS4PTOC
output binary signals:

1. STFW=1 when tip of I2 phasor (operating quantity magnitude) is in forward area, see fig
54 (Operating quantity magnitude is bigger than setting I>Dir)
2. STRV=1 when tip of I2 phasor (operating quantity magnitude) is in the reverse area, see fig
54. (Operating quantity magnitude is bigger than 60% of setting I>Dir)

These signals must be used for communication based fault teleprotection communication
schemes (permissive or blocking).

Simplified logic diagram for directional supervision element with integrated directional
comparison step is shown in figure 55:

126 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

|Iop|
a a>
STRV
b b REVERSE_Int
AND
0.6
X
a a>
STFW
I>Dir b b FORWARD_Int
AND

X
0.4

FWD
AND FORWARD_Int
AngleRCA

C h a r a c e ri s ti c
D i r e c ti o n a l
UPolMin

IPolMin

t
Iop

UPol
AND REVERSE_Int
RVS

STAGE1_DIR_Int
STAGE2_DIR_Int
STAGE3_DIR_Int OR
STAGE4_DIR_Int
BLOCK AND

IEC07000067-4.vsd

IEC07000067-4 V2 EN-US

Figure 55: Simplified logic diagram for directional supervision element with integrated directional
comparison step

6.5.8 Technical data GUID-10E9194D-3AE9-4D0F-867E-473E6F4BF443 v1

GUID-E83AD807-8FE0-4244-A50E-86B9AF92469E v6

Table 66: NS4PTOC technical data


Function Range or value Accuracy
Operate current, step 1 - 4 (1-2500)% of lBase ±1.0% of Ir at I £ Ir
±1.0% of I at I > Ir

Reset ratio > 95% at (10-2500)% of -


IBase
Independent time delay at 0 to 2 x Iset, (0.000-60.000) s ±0.2% or ±35 ms whichever is
step 1 - 4 greater

Minimum operate time for inverse (0.000 - 60.000) s ±0.2% or ±35 ms whichever is
curves, step 1 - 4 greater
Inverse time characteristics, see table 16 curve types See table 580, table 581 and table
580, table 581 and table 582 582
Minimum operate current, step 1 - 4 (1.00 - 10000.00)% of IBase ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir

Relay characteristic angle (RCA) (-180 to 180) degrees ±2.0 degrees


Table continues on next page

Breaker protection REQ650 127


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

Function Range or value Accuracy


Operate current for directional release (1–100)% of IBase For RCA ±60 degrees:
±2.5% of Ir at I ≤ Ir
±2.5% of I at I > Ir

Minimum polarizing voltage (1–100)% of UBase ±0.5% of Ur

Operate time, start non-directional at Min. = 15 ms -


0 to 2 x Iset Max. = 30 ms

Reset time, start non-directional at 2 x Min. = 15 ms -


Iset to 0 Max. = 30 ms

Operate time, start non-directional at Min. = 5 ms -


0 to 10 x Iset Max. = 20 ms

Reset time, start non-directional at 10 Min. = 20 ms -


x Iset to 0 Max. = 35 ms

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -


Transient overreach <10% at τ = 100 ms -

6.6 Thermal overload protection, one time constant,


Celsius/Fahrenheit LCPTTR/LFPTTR IP14512-1 v7

6.6.1 Identification
M17106-1 v7

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Thermal overload protection, one LCPTTR 26
time constant, Celsius

Thermal overload protection, one LFPTTR 26


time constant, Fahrenheit

6.6.2 Functionality M12020-4 v14

The increasing utilization of the power system closer to the thermal limits has generated a
need of a thermal overload protection for power lines.

A thermal overload will often not be detected by other protection functions and the
introduction of the thermal overload protection can allow the protected circuit to operate
closer to the thermal limits.

The three-phase current measuring protection has an I2t characteristic with settable time
constant and a thermal memory. The temperature is displayed in either Celsius or Fahrenheit,
depending on whether the function used is Thermal overload protection (LCPTTR) (Celsius) or
(LFPTTR) (Fahrenheit).

128 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

An alarm level gives early warning to allow operators to take action well before the line is
tripped.

Estimated time to trip before operation, and estimated time to reclose after operation are
presented.

6.6.3 Function block M12627-3 v8

LCPTTR
I3P* TRIP
BLOCK START
BLKTR ALARM
ENMULT LOCKOUT
AMBTEMP
SENSFLT
RESET

IEC13000199-1-en.vsd
IEC13000199 V1 EN-US
LFPTTR
I3P* TRIP
BLOCK START
BLKTR ALARM
ENMULT LOCKOUT
AMBTEMP
SENSFLT
RESET

IEC13000301-1-en.vsd
IEC13000301 V1 EN-US

Figure 56: LCPTTR/LFPTTR function bloc

6.6.4 Signals
PID-3908-INPUTSIGNALS v7

Table 67: LCPTTR Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block of trip
ENMULT BOOLEAN 0 Current multiplyer used when THOL is for two or more lines
AMBTEMP REAL 0 Ambient temperature from external temperature sensor
SENSFLT BOOLEAN 0 Validity status of ambient temperature sensor
RESET BOOLEAN 0 Reset of internal thermal load counter

PID-3909-INPUTSIGNALS v9

Table 68: LFPTTR Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block of trip
ENMULT BOOLEAN 0 Current multiplyer used when THOL is for two or more lines
AMBTEMP REAL 0 Ambient temperature from external temperature sensor
SENSFLT BOOLEAN 0 Validity status of ambient temperature sensor
RESET BOOLEAN 0 Reset of internal thermal load counter

Breaker protection REQ650 129


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

PID-3908-OUTPUTSIGNALS v7

Table 69: LCPTTR Output signals


Name Type Description
TRIP BOOLEAN Trip
START BOOLEAN Start Signal
ALARM BOOLEAN Alarm signal
LOCKOUT BOOLEAN Lockout signal

PID-3909-OUTPUTSIGNALS v8

Table 70: LFPTTR Output signals


Name Type Description
TRIP BOOLEAN Trip
START BOOLEAN Start Signal
ALARM BOOLEAN Alarm signal
LOCKOUT BOOLEAN Lockout signal

6.6.5 Settings
PID-3908-SETTINGS v7

Table 71: LCPTTR Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
TRef 0 - 300 Deg C 1 90 End temperature rise above ambient
of the line when loaded with IRef
IRef 0 - 400 %IB 1 100 The load current (in % of IBase)
leading to TRef temperature
IMult 1-5 - 1 1 Current multiplier when function is
used for two or more lines
Tau 1 - 1000 Min 1 45 Time constant of the line in minutes.
AlarmTemp 0 - 200 Deg C 1 80 Temperature level for start (alarm)
TripTemp 0 - 300 Deg C 1 90 Temperature level for trip
ReclTemp 0 - 300 Deg C 1 75 Temperature for reset of lockout after
trip
tPulse 0.05 - 0.30 s 0.01 0.10 Operate pulse length. Minimum one
execution cycle
AmbiSens Off - - Off External temperature sensor available
On
DefaultAmbTemp -50 - 100 Deg C 1 20 Ambient temperature used when
AmbiSens is set to Off.
DefaultTemp -50 - 300 Deg C 1 50 Temperature raise above ambient
temperature at startup

Table 72: LCPTTR Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

130 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

PID-3909-SETTINGS v8

Table 73: LFPTTR Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
TRef 0 - 600 Deg F 1 160 End temperature rise above ambient
of the line when loaded with IRef
IRef 0 - 400 %IB 1 100 The load current (in % of IBase)
leading to TRef temperature
IMult 1-5 - 1 1 Current multiplier when function is
used for two or more lines
Tau 1 - 1000 Min 1 45 Time constant of the line in minutes.
AlarmTemp 0 - 400 Deg F 1 175 Temperature level for start (alarm)
TripTemp 0 - 600 Deg F 1 195 Temperature level for trip
ReclTemp 0 - 600 Deg F 1 170 Temperature for reset of lockout after
trip
tPulse 0.05 - 0.30 s 0.01 0.10 Operate pulse length. Minimum one
execution cycle
AmbiSens Off - - Off External temperature sensor available
On
DefaultAmbTemp -50 - 250 Deg F 1 60 Ambient temperature used when
AmbiSens is set to Off.
DefaultTemp -50 - 600 Deg F 1 100 Temperature raise above ambient
temperature at startup

Table 74: LFPTTR Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

6.6.6 Monitored data


PID-3908-MONITOREDDATA v7

Table 75: LCPTTR Monitored data


Name Type Values (Range) Unit Description
TTRIP INTEGER - - Estimated time to trip (in min)
TENRECL REAL - - Estimated time to reset of lockout (in
min)
TEMP REAL - deg Calculated temperature of the device
TEMPAMB REAL - deg Ambient temperature used in the
calculations
TERMLOAD REAL - - Temperature relative to operate
temperature

Breaker protection REQ650 131


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

PID-3909-MONITOREDDATA v7

Table 76: LFPTTR Monitored data


Name Type Values (Range) Unit Description
TTRIP INTEGER - - Estimated time to trip (in min)
TENRECL REAL - - Estimated time to reset of lockout (in
min)
TEMP REAL - Temperatur Calculated temperature of the device
e
Fahrenheit
TEMPAMB REAL - Temperatur Ambient temperature used in the
e calculations
Fahrenheit
TERMLOAD REAL - - Temperature relative to operate
temperature

6.6.7 Operation principle M12018-3 v11

The sampled analog phase currents are pre-processed and for each phase current the RMS
value is derived. These phase current values are fed to the thermal overload protection, one
time constant LCPTTR/LFPTTR function. The temperature is displayed either in Celsius or
Fahrenheit, depending on whether LCPTTR/LFPTTR function is selected.

From the largest of the three-phase currents a final temperature is calculated according to the
expression:

2
æ I ö
Q final =ç ÷÷ × Tref
ç I ref
è ø
EQUATION1167 V1 EN-US (Equation 15)

where:
I is the largest phase current,
Iref is a given reference current and

Tref is steady state temperature rise corresponding to Iref

The ambient temperature is added to the calculated final temperature. If this temperature is
larger than the set operate temperature level, TripTemp, a START output signal is activated.

The actual temperature at the actual execution cycle is calculated as:

132 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

æ Dt
ö
Qn = Qn -1 + ( Q final - Q n-1 ) × ç1 - e t ÷
-

è ø
EQUATION1168 V1 EN-US (Equation 16)

where:
Qn is the calculated present temperature,

Qn-1 is the calculated temperature at the previous time step,

Qfinal is the calculated final temperature with the actual current,

Dt is the time step between calculation of the actual temperature and


t is the set thermal time constant for the protected device (line or cable)

The actual temperature of the protected component (line or cable) is calculated by adding the
ambient temperature to the calculated temperature, as shown above. The ambient
temperature can be taken from a separate sensor or can be given a constant value. The
calculated component temperature is available as a real figure signal, TEMP.

When the component temperature reaches the set alarm level AlarmTemp the output signal
ALARM is set. When the component temperature reaches the set trip level TripTemp the
output signal TRIP is set.

There is also a calculation of the present time to operate with the present current. This
calculation is only performed if the final temperature is calculated to be above the operation
temperature:

æQ - Qoperate ö
toperate = -t × ln ç final
ç Q final - Q n ÷÷
è ø
EQUATION1169 V1 EN-US (Equation 17)

The calculated time to trip is available as a real figure signal, TTRIP.

After a trip, caused by the thermal overload protection, there can be a lockout to reconnect the
tripped circuit. The output lockout signal LOCKOUT is activated when the device temperature
is above the set lockout release temperature setting ReclTemp.

The time to lockout release is calculated by the following cooling time calculation. The thermal
content of the function can be reset with input RESET.

æQ - Qlockout _ release ö
tlockout _ release = -t × ln ç final ÷÷
ç Q - Q
è final n ø
EQUATION1170 V1 EN-US (Equation 18)

In the above equation, the final temperature is equal to the set or measured ambient
temperature. The calculated time to reset of lockout is available as a real figure signal,
TENRECL. This signal is enabled when the LOCKOUT output is activated.

In some applications the measured current can involve a number of parallel lines. This is often
used where one bay connects several parallel cables. By setting the parameter IMult to the
number of parallel lines (cables) the actual current on one line is used in the protection

Breaker protection REQ650 133


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

algorithm by dividing the measured current by the total number of cables. To activate this
option the input ENMULT must be activated.

The protection has a reset input: RESET. By activating this input the calculated temperature is
reset to its default initial value. This is useful during testing when secondary injected current
has given a calculated “false” temperature level.

START
Final Temp > Trip Temp

TEMP
Calculation of actual
temperature

AMBTEMP ALARM
Actual Temp > Alarm Temp

I3P

Calculation of final
temperature
ENMULT
TRIP

Actual Temp > Trip Temp


SENSFLT

LOCKOUT
Lockout logic

Actual Temp < Recl Temp


BLOCK

TTRIP
Calculation of time to trip
BLKTR

TENRECL
Calculation of time to reset
of lockout

IEC09000637-2-en.vsd
IEC09000637 V2 EN-US

Figure 57: Functional overview of LCPTTR/LFPTTR

134 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

6.6.8 Technical data


M12352-1 v15

Table 77: LCPTTR/LFPTTR technical data


Function Range or value Accuracy
Reference current (2-400)% of IBase ±1.0% of Ir

Reference temperature (0-300)°C, (0 - 600)°F ±1.0°C, ±2.0°F


Operate time: Time constant t = (1–1000) IEC 60255-149, ±5.0% or ±200
minutes ms whichever is greater
 
 I , Ip
2 2 
t < σ ln  
 2 TTrip , TAmb 2 
I , T √ I ref

 ref 
EQUATION13000039 V3 EN-US (Equation 19)

TTrip= set operate temperature


TAmb = ambient temperature
Tref = temperature rise above ambient at Iref
Iref = reference load current
I = actual measured current
Ip = load current before overload occurs

Alarm temperature (0-200)°C, (0-400)°F ±2.0°C, ±4.0°F


Operate temperature (0-300)°C, (0-600)°F ±2.0°C, ±4.0°F
Reset level temperature (0-300)°C, (0-600)°F ±2.0°C, ±4.0°F

6.7 Breaker failure protection CCRBRF IP14514-1 v6

6.7.1 Identification
M14878-1 v5

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Breaker failure protection, 3-phase CCRBRF 50BF
activation and output
3I>BF

SYMBOL-U V1 EN-US

6.7.2 Functionality M11550-6 v18

Breaker failure protection (CCRBRF) ensures a fast backup tripping of the surrounding
breakers in case the own breaker fails to open. CCRBRF measurement criterion can be current
based, CB position based or an adaptive combination of these two conditions.

A current based check with extremely short reset time is used as check criterion to achieve
high security against inadvertent operation.

CB position check criteria can be used where the fault current through the breaker is small.

CCRBRF provides three different options to select how t1 and t2 timers are run:

Breaker protection REQ650 135


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

1. By external start signals which is internally latched


2. Follow external start signal only
3. Follow external start signal and the selected FunctionMode

CCRBRF can be single- or three- phase initiated to allow its use with single phase tripping
applications. For the three-phase application of the CCRBRF the current criteria can be set to
operate only if “2 elements operates out of three phases and neutral” for example; two phases
or one phase plus the residual current start. This gives a higher security to the backup trip
command.

The CCRBRF function can be programmed to give a single- or three- phase retrip to its own
breaker to avoid unnecessary tripping of surrounding breakers at an incorrect initiation due to
mistakes during testing.

6.7.3 Function block M11944-3 v8

CCRBRF
I3P* TRBU
BLOCK TRBU2
START TRRET
STL1 TRRETL1
STL2 TRRETL2
STL3 TRRETL3
CBCLDL1 CBALARM
CBCLDL2 STALARM
CBCLDL3
CBFLT

IEC18001006-1-en.vsd
IEC18001006 V1 EN-US

Figure 58: CCRBRF function block

6.7.4 Signals
PID-7233-INPUTSIGNALS v1

Table 78: CCRBRF Input signals


Name Type Default Description
I3P GROUP - Three phase group signal for current inputs
SIGNAL
BLOCK BOOLEAN 0 Block of function
START BOOLEAN 0 Three phase start for breaker failure protection function
STL1 BOOLEAN 0 Start signal for phase L1
STL2 BOOLEAN 0 Start signal for phase L2
STL3 BOOLEAN 0 Start signal for phase L3
CBCLDL1 BOOLEAN 0 Circuit breaker closed in phase L1
CBCLDL2 BOOLEAN 0 Circuit breaker closed in phase L2
CBCLDL3 BOOLEAN 0 Circuit breaker closed in phase L3
CBFLT BOOLEAN 0 CB faulty, unable to trip. Backup trip instantaneously

136 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

PID-7233-OUTPUTSIGNALS v1

Table 79: CCRBRF Output signals


Name Type Description
TRBU BOOLEAN Backup trip by breaker failure protection function
TRBU2 BOOLEAN Second backup trip by breaker failure protection function
TRRET BOOLEAN Retrip by breaker failure protection function
TRRETL1 BOOLEAN Retrip by breaker failure protection function phase L1
TRRETL2 BOOLEAN Retrip by breaker failure protection function phase L2
TRRETL3 BOOLEAN Retrip by breaker failure protection function phase L3
CBALARM BOOLEAN Alarm for faulty circuit breaker
STALARM BOOLEAN External start signal timed out, when by setting StartMode
the external start signal is followed (i.e. when is NOT Latched)

6.7.5 Settings
PID-7233-SETTINGS v1

Table 80: CCRBRF Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

Table 81: CCRBRF Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
FunctionMode Current - - Current Selection of measurement principle:
CB Pos Current / CB Position / Current or CB
Current or CB Pos Position
StartMode LatchedStart - - LatchedStart Select how t1 and t2 timers are run: By
FollowStart external start signals which is
FollowStart&Mod internally latched / Follow the external
e start signal only / Follow external
start signal and selected
FunctionMode
tStartTimeout 0.5 - 600.0 s 0.1 1.0 Time delay after which the external
start signal will be ignored, when by
setting StartMode the external start
signal is followed (i.e. when is NOT
Latched)
BuTripMode 2 out of 4 - - 1 out of 3 Select backup trip mode when t2
1 out of 3 timer expires and current
1 out of 4 measurement is used: 2 elements
operate out of three phases and
neutral / 1 element operates out of
three phases / 1 element operates out
of three phases and neutral
RetripMode Off - - Off Select retrip mode when t1 timer
UseFunctionMode expires: Off / use FunctionMode to
Always check / always without any check
IPh> 5 - 200 %IB 1 10 Operate phase current level in % of
IBase
Table continues on next page

Breaker protection REQ650 137


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

Name Values (Range) Unit Step Default Description


IN> 2 - 200 %IB 1 10 Operate residual current level in % of
IBase
t1 0.000 - 60.000 s 0.001 0.000 Time delay of retrip
t2 0.000 - 60.000 s 0.001 0.150 Time delay of backup trip
t2MPh 0.000 - 60.000 s 0.001 0.150 Time delay of backup trip at multi-
phase start. It can be used to speed
up backup trip command for multi-
phase faults on OHLs
tPulse 0.010 - 60.000 s 0.001 0.200 Minimum trip pulse duration

Table 82: CCRBRF Group settings (advanced)


Name Values (Range) Unit Step Default Description
I>BlkCBPos 5 - 200 %IB 1 20 I> in % of IBase to block operation
based on CB Position when
FunctionMode=Current or CB Pos
t3 0.000 - 60.000 s 0.001 0.030 Additional time delay which is added
to t2. It can be used as a second
backup trip
tCBAlarm 0.000 - 60.000 s 0.001 5.000 Time delay for alarm when faulty
circuit breaker indicated

6.7.6 Monitored data


PID-7233-MONITOREDDATA v1

Table 83: CCRBRF Monitored data


Name Type Values (Range) Unit Description
IL1 REAL - A Measured current in phase L1
IL2 REAL - A Measured current in phase L2
IL3 REAL - A Measured current in phase L3
IN REAL - A Measured residual current

6.7.7 Operation principle M16914-3 v11

Breaker failure protection CCRBRF is initiated from the protection trip command, either from
protection functions within the IED or from external protection devices.

To this function the three-phase current input and/or change to: the breaker normally open
auxiliary contact (i.e. "52a" or "closed") shall be connected. On OHL feeders where single pole
auto-reclosing is used, auxiliary contact from each CB pole shall be connected separately

Phase selective start signals enable single pole retrip functionality. This means that a second
attempt to open the same breaker can be done phase-selective. The retrip attempt is made
after a set time delay t1. For transmission lines, single pole trip and auto-reclosing is often
used. The retrip function can be phase selective if it is initiated from the phase selective line
protection.

The retrip function can be done with or without current check. With this current check, the
retrip is only performed if thecurrent through the circuit breaker is larger than the operate
current level.

138 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

The retrip function can be performed with or without CB position check according to table 84.

Table 84: Dependencies between parameters RetripMode and FunctionMode


RetripMode FunctionMode Description
Retrip Off N/A the retrip function is not activated
CB Pos Check Current retrip is done if phase current is
larger than the operate level after
retrip time has elapsed
Contact retrip is done when auxiliary
contact position indicates that
breaker is still closed after retrip
time has elapsed
Current&Contact both methods according to above
are used but taken into account
also I>BlkCont
No CBPos Check Current retrip is done without check of
current level
Contact retrip is done without check of
auxiliary contact position
Current&Contact retrip is done without check of
current level or auxiliary contact
position

The start signal can be an internal or external protection trip signal. This signal will start the
backup trip timer. The function detects the successful breaker opening, either by detection of
low current through RMS evaluation and a special adapted current algorithm or by open
contact indication. The special algorithm enables a very fast detection of successful breaker
opening, that is, fast resetting of the current measurement. If the current and/or contact
detection has not detected breaker opening before the backup timer has run its time a backup
trip is initiated.

Further the following possibilities are available:


• The minimum length of the retrip pulse, the backup trip pulse and the second backup trip
pulse are settable. This pulse duration is defined by a parameter setting tPulse. The retrip
pulse, the backup trip pulse and the second backup trip pulse will however sustain as long
as there is an indication of closed breaker.
• If the current detection is used it is possible to use three different options: 1 out of 3
where it is sufficient to detect failure to open (high current) in one pole, 1 out of 4 where it
is sufficient to detect failure to open (high current) in one pole or high residual current
and 2 out of 4 where at least two currents (phase current and/or residual current) shall be
high for breaker failure detection.
• The current detection level for the residual current can be set different from the setting of
phase current detection.
• It is possible to have different backup time delays for single-phase faults and for multi-
phase faults.
• It is possible to have this option activated for small load currents only.
• It is possible to have instantaneous backup trip function if a signal is high if the circuit
breaker is incapable to clear faults, for example, at low gas pressure.

Breaker protection REQ650 139


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

30 ms
START
STL1 OR BFP Started L1
150 ms
AND S
SR Q t
R
BLOCK
OR Time out L1
Reset L1 AND
Retrip Time Out L1
Backup Time Out L1

IEC09000976-3-en-us.vsd
IEC09000976 V3 EN-US

Figure 59: Simplified logic scheme of the CCRBRF starting logic

IP>
a
a>b
b

FunctionMode Current
OR AND Reset L1
OR

1 Contact Time out L1


Current and Contact OR
AND
Current High L1
IL1
BFP Started L1 AND CB Closed L1
OR

a AND AND
a>b OR AND
I>BlkCont b

CBCLDL1 Contact Closed L1


AND

IEC09000977-2-en.vsd

IEC09000977 V2 EN-US

Figure 60: Simplified logic scheme of the CCRBRF , CB position evaluation

t1 TRRETL3
BFP Started L1 From other
t Retrip Time Out L1
phases TRRETL2 OR
TRRET

tPulse
RetripMode No CBPos Check AND
OR TRRETL1
OR

1 30ms
OR

CB Pos Check
AND
CB Closed L1
CBFLT

IEC09000978-4-en.vsd
IEC09000978 V4 EN-US

Figure 61: Simplified logic scheme of the retrip logic function

140 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

BUTripMode
1 out of 3
2 out of 4
OR
1 1 out of 4 AND

Current high L1

BFP Started L1
AND
IN
a
a>b
IN> b

Contact Closed L1
OR

OR
Current High L2
From other AND Backup Time Out L1
Current High L3
phases
Current High L1
CBFLT
AND

t2
30ms Backup Trip L1
BFP Started L1 t AND
OR
t2MPh

AND t

AND
OR OR
tPulse
From other Backup Trip L2 OR TRBU
OR
phases Backup Trip L3
BFP Started L2 AND
From other
phases BFP Started L3 OR tPulse
t3
OR
TRBU2
S Q
SR
t
AND R

IEC09000979-5-en-us.vsd
IEC09000979 V5 EN-US

Figure 62: Simplified logic scheme of the backup trip logic function

6.7.8 Technical data IP10269-1 v1

M12353-1 v15

Table 85: CCRBRF technical data


Function Range or value Accuracy
Operate phase current (5-200)% of lBase ±1.0% of Ir at I £ Ir
±1.0% of I at I > Ir

Reset ratio, phase current > 95% -


Operate residual current (2-200)% of lBase ±1.0% of Ir at I £ Ir
±1.0% of I at I > Ir

Reset ratio, residual current > 95% -


Phase current level for blocking of contact (5-200)% of lBase ±1.0% of Ir at I £ Ir
function ±1.0% of I at I > Ir

Reset ratio > 95% -


Operate time for current detection 10 ms typically -
Reset time for current detection 10 ms maximum * -
Time delay for retrip at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±15 ms whichever is
greater
Time delay for backup trip at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±15 ms whichever is
greater
Time delay for backup trip at multi-phase start (0.000-60.000) s ±0.2% or ±20 ms whichever is
at 0 to 2 x Iset greater

Additional time delay for a second backup trip (0.000-60.000) s ±0.2% or ±20 ms whichever is
at 0 to 2 x Iset greater

Table continues on next page

Breaker protection REQ650 141


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

Function Range or value Accuracy


Time delay for alarm for faulty circuit breaker (0.000-60.000) s ±0.2% or ±15 ms whichever is
greater
Minimum trip pulse duration (0.010-60.000) s ±0.2% or ±5 ms whichever is
greater
* Valid for product version 2.2.3 or later

6.8 Stub protection STBPTOC IP14515-1 v3

6.8.1 Identification
M17108-1 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Stub protection STBPTOC 50STB

3I>STUB

SYMBOL-T V1 EN-US

6.8.2 Functionality M12902-3 v10

When a power line is taken out of service for maintenance and the line disconnector is opened
in multi-breaker arrangements the voltage transformers will mostly be outside on the
disconnected part. The primary line distance protection will thus not be able to operate and
must be blocked.

The stub protection (STBPTOC) covers the zone between the current transformers and the
open disconnector. The three-phase instantaneous overcurrent function is released from a
normally open, NO (b) auxiliary contact on the line disconnector.

6.8.3 Function block M12524-3 v5

STBPTOC
I3P* TRIP
BLOCK START
BLKTR
RELEASE

IEC05000678-2-en.vsd
IEC05000678 V2 EN-US

Figure 63: STBPTOC function block

6.8.4 Signals
PID-6931-INPUTSIGNALS v1

Table 86: STBPTOC Input signals


Name Type Default Description
I3P GROUP - Three phase currents
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block of trip
RELEASE BOOLEAN 0 Release of stub protection

142 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

PID-6931-OUTPUTSIGNALS v1

Table 87: STBPTOC Output signals


Name Type Description
TRIP BOOLEAN General trip
START BOOLEAN General start

6.8.5 Settings
PID-6931-SETTINGS v1

Table 88: STBPTOC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
ReleaseMode Release - - Release Release of stub protection
Continuous
I> 5 - 2500 %IB 1 200 Operate current level in % of IBase

Table 89: STBPTOC Group settings (advanced)


Name Values (Range) Unit Step Default Description
tDelay 0.000 - 60.000 s 0.001 0.000 Time delay

Table 90: STBPTOC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

6.8.6 Monitored data


PID-3462-MONITOREDDATA v5

Table 91: STBPTOC Monitored data


Name Type Values (Range) Unit Description
IL1 REAL - A Current in phase L1
IL2 REAL - A Current in phase L2
IL3 REAL - A Current in phase L3

6.8.7 Operation principle M12905-3 v5

The sampled analog phase currents are pre-processed in a discrete Fourier filter (DFT) block.
From the fundamental frequency components of each phase current the RMS value of each
phase current is derived. These phase current values are fed to a comparator in the stub
protection function STBPTOC. In a comparator the RMS values are compared to the set
operating current value of the function I>.

If a phase current is larger than the set operating current the signal from the comparator for
this phase is activated. This signal will, in combination with the release signal from line
disconnection (RELEASE input), activate the timer for the TRIP signal. If the fault current

Breaker protection REQ650 143


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

remains during the timer delay t, the TRIP output signal is activated. The function can be
blocked by activation of the BLOCK input.

STUB PROTECTION FUNCTION

BLOCK

TRIP
STIL1 AND

STIL2 OR

STIL3

RELEASE

en05000731.vsd
IEC05000731 V1 EN-US

Figure 64: Simplified logic diagram for Stub protection

6.8.8 Technical data


M12350-1 v12

Table 92: STBPTOC technical data


Function Range or value Accuracy
Operating current (5-2500)% of IBase ±1.0% of Ir at I ≤ Ir
±1.0% of I at I > Ir

Reset ratio > 95% at (50-2500)% of IBase -


Independent time delay at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±30 ms whichever is
greater
Operate time, start at 0 to 2 x Iset Min. = 10 ms -
Max. = 20 ms
Reset time, start at 2 x Iset to 0 Min. = 10 ms -
Max. = 20 ms
Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -

6.9 Broken conductor check BRCPTOC SEMOD171761-1 v3

6.9.1 Identification
SEMOD172362-2 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Broken conductor check BRCPTOC - 46

144 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

6.9.2 Functionality SEMOD171805-5 v6

Conventional protection functions cannot detect the broken conductor condition. Broken
conductor check BRCPTOC function, consisting of continuous phase selective current
unsymmetrical check on the line where the IED is connected, gives an alarm or trip at detecting
broken conductors.

6.9.3 Function block SEMOD171906-11 v4

BRCPTOC
I3P* TRIP
BLOCK START
BLKTR

IEC07000034-2-en.vsd
IEC07000034 V2 EN-US

Figure 65: BRCPTOC function block

6.9.4 Signals
PID-3479-INPUTSIGNALS v6

Table 93: BRCPTOC Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block of trip

PID-3479-OUTPUTSIGNALS v7

Table 94: BRCPTOC Output signals


Name Type Description
TRIP BOOLEAN Operate signal of the protection logic
START BOOLEAN Start signal of the protection logic

6.9.5 Settings
PID-3479-SETTINGS v7

Table 95: BRCPTOC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
Iub> 50 - 90 %IM 1 50 Highest and lowest phase currents
difference in % of highest phase
current
IP> 5 - 100 %IB 1 20 Minimum phase current for operation
of Iub> in % of IBase
tOper 0.000 - 60.000 s 0.001 5.000 Operate time delay

Breaker protection REQ650 145


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 6 1MRK 505 384-UEN C
Current protection

Table 96: BRCPTOC Group settings (advanced)


Name Values (Range) Unit Step Default Description
tReset 0.010 - 60.000 s 0.001 0.100 Time delay in reset

Table 97: BRCPTOC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

6.9.6 Monitored data


PID-3479-MONITOREDDATA v6

Table 98: BRCPTOC Monitored data


Name Type Values (Range) Unit Description
IUNBAL REAL - - Measured unbalance of phase
currents

6.9.7 Operation principle SEMOD171791-5 v5

Broken conductor check (BRCPTOC) detects a broken conductor condition by detecting the
asymmetry between currents in the three phases. The current-measuring elements
continuously measure the three-phase currents.

The current asymmetry signal output START is set on if:

• The difference in currents between the phase with the lowest current and the phase with
the highest current is greater than set percentage Iub> of the highest phase current
• The highest phase current is greater than the minimum setting value IP>.
• The lowest phase current is below 50% of the minimum setting value IP>

The third condition is included to avoid problems in systems involving parallel lines. If a
conductor breaks in one phase on one line, the parallel line will experience an increase in
current in the same phase. This might result in the first two conditions being satisfied. If the
unsymmetrical detection lasts for a period longer than the set time tOper the TRIP output is
activated.

The simplified logic diagram of the broken conductor check function is shown in figure 66

BRCPTOC is disabled (blocked) if:

• The IED is in TEST status and the function has been blocked from the local HMI test menu
(BlockBRC=Yes).
• The input signal BLOCK is high.

The BLOCK input can be connected to a binary input of the IED in order to receive a block
command from external devices, or can be software connected to other internal functions of
the IED itself to receive a block command from internal functions.

The output trip signal TRIP is a three-phase trip. It can be used to command a trip to the circuit
breaker or for alarm purpose only.

146 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 6
Current protection

TEST

TEST-ACTIVE
and
Block BRCPTOC=Yes
START

Function Enable
BLOCK or
tOper
TRIP
and t
Unsymmetrical
Current Detection
STI

IL1<50%IP>

IL2<50%IP> or

IL3<50%IP>

IEC09000158-3-en.vsd
IEC09000158 V3 EN-US

Figure 66: Simplified logic diagram for Broken conductor check BRCPTOC

6.9.8 Technical data SEMOD171939-1 v1

SEMOD175200-2 v7

Table 99: BRCPTOC technical data


Function Range or value Accuracy
Minimum phase current for operation (5–100)% of IBase ±1.0% of Ir

Unbalance current operation (50–90)% of maximum current ±1.0% of Ir

Independent operate time delay (0.000-60.000) s ±0.2% or ±45 ms whichever is


greater
Independent reset time delay (0.010-60.000) s ±0.2% or ±30 ms whichever is
greater
Start time at current change from Ir to Min. = 25 ms -
0 Max. = 35 ms

Reset time at current change from 0 to Min. = 5 ms -


Ir Max. = 20 ms

Breaker protection REQ650 147


Technical manual
© Copyright 2017 ABB. All rights reserved
148
1MRK 505 384-UEN C Section 7
Voltage protection

Section 7 Voltage protection


7.1 Two step undervoltage protection UV2PTUV IP14544-1 v3

7.1.1 Identification
M16876-1 v7

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Two step undervoltage protection UV2PTUV 27

3U<

V2 EN-US
SYMBOL-R-2U-GREATER-THAN

7.1.2 Functionality M13789-3 v12

Undervoltages can occur in the power system during faults or abnormal conditions. The two-
step undervoltage protection function (UV2PTUV) can be used to open circuit breakers to
prepare for system restoration at power outages or as a long-time delayed back-up to the
primary protection.

UV2PTUV has two voltage steps, each with inverse or definite time delay.

It has a high reset ratio to allow settings close to the system service voltage.

7.1.3 Function block M13794-3 v6

UV2PTUV
U3P* TRIP
BLOCK TR1
BLKTR1 TR1L1
BLKST1 TR1L2
BLKTR2 TR1L3
BLKST2 TR2
TR2L1
TR2L2
TR2L3
START
ST1
ST1L1
ST1L2
ST1L3
ST2
ST2L1
ST2L2
ST2L3

IEC06000276-2-en.vsd
IEC06000276 V2 EN-US

Figure 67: UV2PTUV function block

Breaker protection REQ650 149


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 7 1MRK 505 384-UEN C
Voltage protection

7.1.4 Signals
PID-3586-INPUTSIGNALS v7

Table 100: UV2PTUV Input signals


Name Type Default Description
U3P GROUP - Three phase voltages
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR1 BOOLEAN 0 Block of operate signal, step 1
BLKST1 BOOLEAN 0 Block of step 1
BLKTR2 BOOLEAN 0 Block of operate signal, step 2
BLKST2 BOOLEAN 0 Block of step 2

PID-3586-OUTPUTSIGNALS v7

Table 101: UV2PTUV Output signals


Name Type Description
TRIP BOOLEAN Trip
TR1 BOOLEAN Common trip signal from step1
TR1L1 BOOLEAN Trip signal from step1 phase L1
TR1L2 BOOLEAN Trip signal from step1 phase L2
TR1L3 BOOLEAN Trip signal from step1 phase L3
TR2 BOOLEAN Common trip signal from step2
TR2L1 BOOLEAN Trip signal from step2 phase L1
TR2L2 BOOLEAN Trip signal from step2 phase L2
TR2L3 BOOLEAN Trip signal from step2 phase L3
START BOOLEAN General start signal
ST1 BOOLEAN Common start signal from step1
ST1L1 BOOLEAN Start signal from step1 phase L1
ST1L2 BOOLEAN Start signal from step1 phase L2
ST1L3 BOOLEAN Start signal from step1 phase L3
ST2 BOOLEAN Common start signal from step2
ST2L1 BOOLEAN Start signal from step2 phase L1
ST2L2 BOOLEAN Start signal from step2 phase L2
ST2L3 BOOLEAN Start signal from step2 phase L3

150 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 7
Voltage protection

7.1.5 Settings
PID-3586-SETTINGS v7

Table 102: UV2PTUV Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OperationStep1 Off - - On Enable execution of step 1
On
Characterist1 Definite time - - Definite time Selection of time delay curve type for
Inverse curve A step 1
Inverse curve B
Prog. inv. curve
OpMode1 1 out of 3 - - 1 out of 3 Number of phases required for op (1
2 out of 3 of 3, 2 of 3, 3 of 3) from step 1
3 out of 3
U1< 1.0 - 100.0 %UB 0.1 70.0 Voltage setting/start val (DT & IDMT)
in % of UBase, step 1
t1 0.00 - 6000.00 s 0.01 5.00 Definitive time delay of step 1
t1Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse
curves for step 1
k1 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time
delay for step 1
IntBlkSel1 Off - - Off Internal (low level) blocking mode,
Block of trip step 1
Block all
IntBlkStVal1 1 - 50 %UB 1 20 Voltage setting for internal blocking in
% of UBase, step 1
tBlkUV1 0.000 - 60.000 s 0.001 0.000 Time delay of internal (low level)
blocking for step 1
HystAbs1 0.0 - 50.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase,
step 1
OperationStep2 Off - - On Enable execution of step 2
On
Characterist2 Definite time - - Definite time Selection of time delay curve type for
Inverse curve A step 2
Inverse curve B
Prog. inv. curve
OpMode2 1 out of 3 - - 1 out of 3 Number of phases required for op (1
2 out of 3 of 3, 2 of 3, 3 of 3) from step 2
3 out of 3
U2< 1.0 - 100.0 %UB 0.1 50.0 Voltage setting/start val (DT & IDMT)
in % of UBase, step 2
t2 0.000 - 60.000 s 0.001 5.000 Definitive time delay of step 2
t2Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse
curves for step 2
k2 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time
delay for step 2
IntBlkSel2 Off - - Off Internal (low level) blocking mode,
Block of trip step 2
Block all
Table continues on next page

Breaker protection REQ650 151


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 7 1MRK 505 384-UEN C
Voltage protection

Name Values (Range) Unit Step Default Description


IntBlkStVal2 1 - 50 %UB 1 20 Voltage setting for internal blocking in
% of UBase, step 2
tBlkUV2 0.000 - 60.000 s 0.001 0.000 Time delay of internal (low level)
blocking for step 2
HystAbs2 0.0 - 50.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase,
step 2

Table 103: UV2PTUV Group settings (advanced)


Name Values (Range) Unit Step Default Description
tReset1 0.000 - 60.000 s 0.001 0.025 Reset time delay used in IEC Definite
Time curve step 1
ResetTypeCrv1 Instantaneous - - Instantaneous Selection of used IDMT reset curve
Frozen timer type for step 1
Linearly
decreased
tIReset1 0.000 - 60.000 s 0.001 0.025 Time delay in IDMT reset (s), step 1
ACrv1 0.005 - 200.000 - 0.001 1.000 Parameter A for customer
programmable curve for step 1
BCrv1 0.50 - 100.00 - 0.01 1.00 Parameter B for customer
programmable curve for step 1
CCrv1 0.0 - 1.0 - 0.1 0.0 Parameter C for customer
programmable curve for step 1
DCrv1 0.000 - 60.000 - 0.001 0.000 Parameter D for customer
programmable curve for step 1
PCrv1 0.000 - 3.000 - 0.001 1.000 Parameter P for customer
programmable curve for step 1
CrvSat1 0 - 100 % 1 0 Tuning param for prog. under voltage
IDMT curve, step 1
tReset2 0.000 - 60.000 s 0.001 0.025 Reset time delay used in IEC Definite
Time curve step 2
ResetTypeCrv2 Instantaneous - - Instantaneous Selection of used IDMT reset curve
Frozen timer type for step 2
Linearly
decreased
tIReset2 0.000 - 60.000 s 0.001 0.025 Time delay in IDMT reset (s), step 2
ACrv2 0.005 - 200.000 - 0.001 1.000 Parameter A for customer
programmable curve for step 2
BCrv2 0.50 - 100.00 - 0.01 1.00 Parameter B for customer
programmable curve for step 2
CCrv2 0.0 - 1.0 - 0.1 0.0 Parameter C for customer
programmable curve for step 2
DCrv2 0.000 - 60.000 - 0.001 0.000 Parameter D for customer
programmable curve for step 2
PCrv2 0.000 - 3.000 - 0.001 1.000 Parameter P for customer
programmable curve for step 2
CrvSat2 0 - 100 % 1 0 Tuning param for prog. under voltage
IDMT curve, step 2

152 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 7
Voltage protection

Table 104: UV2PTUV Non group settings (basic)


Name Values (Range) Unit Step Default Description
ConnType PhN DFT - - PhN DFT Group selector for connection type
PhPh RMS
PhN RMS
PhPh DFT
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

7.1.6 Monitored data


PID-3586-MONITOREDDATA v6

Table 105: UV2PTUV Monitored data


Name Type Values (Range) Unit Description
UL1 REAL - kV Voltage in phase L1
UL2 REAL - kV Voltage in phase L2
UL3 REAL - kV Voltage in phase L3

7.1.7 Operation principle M15326-3 v9

Two-step undervoltage protection (UV2PTUV) is used to detect low power system voltage. If
one, two or three phase voltages decrease below the set value, a corresponding START signal
is generated. The parameters OpMode1 and OpMode2 influence the requirements to activate
the START outputs: the measured voltages 1 out of 3, 2 out of 3, or 3 out of 3 have to be lower
than the corresponding set point to issue the corresponding START signal.

UV2PTUV has two voltage-measuring steps with separate time delays. If the voltage remains
below the set value for the chosen time delay, the corresponding trip signal is issued. To avoid
an unwanted trip due to the disconnection of the related high-voltage equipment, a voltage-
controlled blocking of the function is available: if the voltage is lower than the set blocking
level, the function is blocked and no START or TRIP signal is generated. The time delay
characteristic is individually chosen for each step and can be either definite time delay or
inverse time delay.

To avoid oscillations of the output START signal, a hysteresis has been included.

7.1.7.1 Measurement principle M15326-6 v7

Depending on the value of the ConnType parameter, UV2PTUV can be set to measure phase-
to-earth fundamental value, phase-to-phase fundamental value, phase-to-earth true RMS value
or phase-to-phase true RMS value, and compares it against the set values, U1< and U2<. The
voltage-related settings are made in percentage of the base voltage which is set in kV phase-
to-phase voltage. This means operation for phase-to-earth voltage under:

UBase(kV )
U (%) ·
3
EQUATION1429 V3 EN-US (Equation 20)

and operation for phase-to-phase voltage under:

Breaker protection REQ650 153


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 7 1MRK 505 384-UEN C
Voltage protection

U < (%) × UBase(kV)


EQUATION1990 V1 EN-US (Equation 21)

When the phase-to-earth voltage measurement is selected, the function


automatically introduces division of the base value by the square root of three.

7.1.7.2 Time delay M15326-10 v12

The time delay for the two steps can be either definite time delay (DT) or inverse time delay
(IDMT). For the inverse time delay three different modes are available:

• inverse curve A
• inverse curve B
• customer programmable inverse curve

The type A curve is described as:

k
t=
æ Un < -U ö
ç ÷
è Un < ø
EQUATION1431 V2 EN-US (Equation 22)

where:
Un< Set value for step 1 and step 2
U Measured voltage

The type B curve is described as:

k × 480
t= 2.0
+ 0.055
æ Un < - U ö
ç 32 × - 0.5 ÷
è Un < ø
EQUATION1432 V2 EN-US (Equation 23)

The customer programmable curve can be created as:

é ù
ê ú
ê k×A ú
t=ê pú
+D
ê æ Un < - U ö ú
êçB × -C÷ ú
ëè Un < ø û
EQUATION1433 V2 EN-US (Equation 24)

When the denominator in the expression is equal to zero the time delay will be infinity. There
will be an undesired discontinuity. Therefore a tuning parameter CrvSatn is set to compensate
for this phenomenon. In the voltage interval Un< down to Un< · (1.0 – CrvSatn/100) the used

154 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 7
Voltage protection

voltage will be: Un< · (1.0 – CrvSatn/100). If the programmable curve is used this parameter
must be calculated so that:

CrvSatn
B× -C > 0
100
EQUATION1435 V1 EN-US (Equation 25)

The lowest voltage is always used for the inverse time delay integration. The details of the
different inverse time characteristics are shown in section "Inverse characteristics".

Voltage

UL1
UL2
UL3

IDMT Voltage

Time

IEC12000186-1-en.vsd

IEC12000186 V1 EN-US

Figure 68: Voltage used for the inverse time characteristic integration
Trip signal issuing requires that the undervoltage condition continues for at least the user set
time delay. This time delay is set by the parameter t1 and t2 for definite time mode (DT) and by
some special voltage level dependent time curves for the inverse time mode (IDMT). If the start
condition, with respect to the measured voltage, ceases during the delay time, and is not
fulfilled again within a user-defined reset time (tReset1 and tReset2 for the definite time and
tIReset1 and tIReset2 pickup for the inverse time) the corresponding start output is reset.
After leaving the hysteresis area, the start condition must be fulfilled again and it is not
sufficient for the signal to only return back to the hysteresis area. For the undervoltage
function the IDMT reset time is constant and does not depend on the voltage fluctuations
during the drop-off period. However, there are three ways to reset the timer: the timer is reset
instantaneously, the timer value is frozen during the reset time, or the timer value is linearly
decreased during the reset time. See figure 69 and figure 70.

Breaker protection REQ650 155


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 7 1MRK 505 384-UEN C
Voltage protection

tIReset1
Voltage Measured
START Voltage
HystAbs1
TRIP

U1<

Time

START

TRIP

Time
Integrator Frozen Timer

Time
Linearly
Instantaneous
decreased IEC05000010-5-en.vsdx

IEC05000010 V5 EN-US

Figure 69: Voltage profile not causing a reset of the START signal for step 1, and inverse time delay at
different reset types

156 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 7
Voltage protection

tIReset1
Voltage
START
START
HystAbs1 Measured Voltage
TRIP

U1<

Time

START t

TRIP

Time
Integrator Frozen Timer

Time
Instantaneous Linearly decreased
IEC05000011-en-4.vsdx

IEC05000011 V4 EN-US

Figure 70: Voltage profile causing a reset of the START signal for step 1, and inverse time delay at
different reset types
Definite timer delay

When definite time delay is selected the function will operate as shown in figure 71. Detailed
information about individual stage reset/operation behavior is shown in figure 72 and figure
73 respectively. Note that by setting tResetn = 0.0s, instantaneous reset of the definite time
delayed stage is ensured.

Breaker protection REQ650 157


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 7 1MRK 505 384-UEN C
Voltage protection

ST1

U t1
a tReset1
TR1
t
a<b t
U1< R
b
AND

IEC09000785-3-en.vsd
IEC09000785 V3 EN-US

Figure 71: Logic diagram for step 1, DT operation

U1<

ST1

TR1

tReset1

t1

IEC10000039-3-en.vsd
IEC10000039 V3 EN-US

Figure 72: Example for Definite Time Delay stage1 reset

U1<

ST1

TR1

tReset1

t1

IEC10000040-3-en.vsd
IEC10000040 V3 EN-US

Figure 73: Example for Definite Time Delay stage1 operation

158 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 7
Voltage protection

7.1.7.3 Blocking M15326-20 v8

It is possible to block Two step undervoltage protection UV2PTUV partially or completely, by


binary input signals or by parameter settings, where:

BLOCK: blocks all outputs


BLKTR1: blocks all trip outputs of step 1
BLKST1: blocks all start and trip outputs related to step 1
BLKTR2: blocks all trip outputs of step 2
BLKST2: blocks all start and trip outputs related to step 2

If the measured voltage level decreases below the setting of IntBlkStVal1, either the trip output
of step 1, or both the trip and the START outputs of step 1, are blocked. The characteristic of
the blocking is set by the IntBlkSel1 parameter. This internal blocking can also be set to Off
resulting in no voltage based blocking. Corresponding settings and functionality are valid also
for step 2.

In case of disconnection of the high voltage component the measured voltage will get very
low. The event will START both the under voltage function and the blocking function, as seen in
figure 74. The delay of the blocking function must be set less than the time delay of under
voltage function.

U Disconnection

Normal voltage

U1<

U2<

tBlkUV1 <
t1,t1Min
IntBlkStVal1
tBlkUV2 <
t2,t2Min
IntBlkStVal2

Time

Block step 1

Block step 2
en05000466.vsd
IEC05000466 V1 EN-US

Figure 74: Blocking function

Breaker protection REQ650 159


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 7 1MRK 505 384-UEN C
Voltage protection

7.1.7.4 Design M15326-35 v9

The voltage measuring elements continuously measure the three phase-to-neutral voltages or
the three phase-to-phase voltages. Recursive fourier filters or true RMS filters of input voltage
signals are used. The voltages are individually compared to the set value, and the lowest
voltage is used for the inverse time characteristic integration. A special logic is included to
achieve the 1 out of 3, 2 out of 3 and 3 out of 3 criteria to fulfill the START condition. The design
of Two step undervoltage protection UV2PTUV is schematically shown in Figure 75.

UL1 Comparator ST1L1


UL1 < U1< Voltage Phase Phase 1
Selector
OpMode1 ST1L2
UL2 Comparator Phase 2
1 out of 3
UL2 < U1< 2 out of 3 ST1L3
3 out of 3 Phase 3 Start t1
UL3 Comparator t1Reset
UL3 < U1< IntBlkStVal1 &
OR ST1
Trip
Output
START Logic TR1L1

Step 1 TR1L2
Time integrator TRIP
MinVoltSelector tIReset1
ResetTypeCrv1 TR1L3

TR1
OR

Comparator ST2L1
UL1 < U2< Voltage Phase Phase 1
Selector
OpMode2 ST2L2
Comparator Phase 2
UL2 < U2< 1 out of 3
2 out of 3 Start t2 ST2L3
3 out of 3 Phase 3 t2Reset
Comparator IntBlkStVal2 &
UL3 < U2< Trip ST2
Output OR
Logic
START TR2L1

Step 2
TR2L2
Time integrator TRIP
MinVoltSelector tIReset2
ResetTypeCrv2 TR2L3

TR2
OR
START
OR

TRIP
OR

IEC05000834-2-en.vsd
IEC05000834 V2 EN-US

Figure 75: Schematic design of Two step undervoltage protection UV2PTUV

160 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 7
Voltage protection

7.1.8 Technical data IP13001-1 v1

M13290-1 v15

Table 106: UV2PTUV technical data


Function Range or value Accuracy
Operate voltage, low and high step (1.0–100.0)% of UBase ±0.5% of Ur

Absolute hysteresis (0.0–50.0)% of UBase ±0.5% of Ur

Internal blocking level, step 1 and step (1–50)% of UBase ±0.5% of Ur


2
Inverse time characteristics for step 1 - See table 589
and step 2, see table 589
Definite time delay, step 1 at 1.2 x Uset (0.00-6000.00) s ±0.2% or ±40ms whichever is
to 0 greater

Definite time delay, step 2 at 1.2 x Uset (0.000-60.000) s ±0.2% or ±40ms whichever is
to 0 greater

Minimum operate time, inverse (0.000–60.000) s ±0.5% or ±40ms whichever is


characteristics greater
Operate time, start at 2 x Uset to 0 Min. = 15 ms -
Max. = 30 ms
Reset time, start at 0 to 2 x Uset Min. = 15 ms -
Max. = 30 ms
Operate time, start at 1.2 x Uset to 0 Min. = 5 ms -
Max. = 25 ms
Reset time, start at 0 to 1.2 x Uset Min. = 15 ms -
Max. = 35 ms
Critical impulse time 5 ms typically at 1.2 x Uset to -
0
Impulse margin time 15 ms typically -

7.2 Two step overvoltage protection OV2PTOV IP14545-1 v3

7.2.1 Identification
M17002-1 v8

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Two step overvoltage protection OV2PTOV 59

3U>

SYMBOL-C-2U-SMALLER-THAN V2 EN-US

7.2.2 Functionality OV2PTOV M13798-3 v16

Overvoltages may occur in the power system during abnormal conditions such as sudden
power loss, tap changer regulating failures, and open line ends on long lines.

OV2PTOV has two voltage steps, each of them with inverse or definite time delayed.

OV2PTOV has a high reset ratio to allow settings close to system service voltage.

Breaker protection REQ650 161


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 7 1MRK 505 384-UEN C
Voltage protection

7.2.3 Function block M13803-3 v6

OV2PTOV
U3P* TRIP
BLOCK TR1
BLKTR1 TR1L1
BLKST1 TR1L2
BLKTR2 TR1L3
BLKST2 TR2
TR2L1
TR2L2
TR2L3
START
ST1
ST1L1
ST1L2
ST1L3
ST2
ST2L1
ST2L2
ST2L3

IEC06000277-2-en.vsd
IEC06000277 V2 EN-US

Figure 76: OV2PTOV function block

7.2.4 Signals
PID-3535-INPUTSIGNALS v7

Table 107: OV2PTOV Input signals


Name Type Default Description
U3P GROUP - Group signal for three phase voltage input
SIGNAL
BLOCK BOOLEAN 0 Block of function
BLKTR1 BOOLEAN 0 Block of operate signal, step 1
BLKST1 BOOLEAN 0 Block of step 1
BLKTR2 BOOLEAN 0 Block of operate signal, step 2
BLKST2 BOOLEAN 0 Block of step 2

PID-3535-OUTPUTSIGNALS v7

Table 108: OV2PTOV Output signals


Name Type Description
TRIP BOOLEAN Trip
TR1 BOOLEAN Common trip signal from step1
TR1L1 BOOLEAN Trip signal from step1 phase L1
TR1L2 BOOLEAN Trip signal from step1 phase L2
TR1L3 BOOLEAN Trip signal from step1 phase L3
TR2 BOOLEAN Common trip signal from step2
TR2L1 BOOLEAN Trip signal from step2 phase L1
TR2L2 BOOLEAN Trip signal from step2 phase L2
TR2L3 BOOLEAN Trip signal from step2 phase L3
START BOOLEAN General start signal
ST1 BOOLEAN Common start signal from step1
ST1L1 BOOLEAN Start signal from step1 phase L1
Table continues on next page

162 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 7
Voltage protection

Name Type Description


ST1L2 BOOLEAN Start signal from step1 phase L2
ST1L3 BOOLEAN Start signal from step1 phase L3
ST2 BOOLEAN Common start signal from step2
ST2L1 BOOLEAN Start signal from step2 phase L1
ST2L2 BOOLEAN Start signal from step2 phase L2
ST2L3 BOOLEAN Start signal from step2 phase L3

7.2.5 Settings
PID-3535-SETTINGS v7

Table 109: OV2PTOV Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OperationStep1 Off - - On Enable execution of step 1
On
Characterist1 Definite time - - Definite time Selection of time delay curve type for
Inverse curve A step 1
Inverse curve B
Inverse curve C
Prog. inv. curve
OpMode1 1 out of 3 - - 1 out of 3 Number of phases required for op (1
2 out of 3 of 3, 2 of 3, 3 of 3) from step 1
3 out of 3
U1> 1.0 - 200.0 %UB 0.1 120.0 Voltage setting/start val (DT & IDMT)
in % of UBase, step 1
t1 0.00 - 6000.00 s 0.01 5.00 Definitive time delay of step 1
t1Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse
curves for step 1
k1 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time
delay for step 1
HystAbs1 0.0 - 50.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase,
step 1
OperationStep2 Off - - On Enable execution of step 2
On
Characterist2 Definite time - - Definite time Selection of time delay curve type for
Inverse curve A step 2
Inverse curve B
Inverse curve C
Prog. inv. curve
OpMode2 1 out of 3 - - 1 out of 3 Number of phases required for op (1
2 out of 3 of 3, 2 of 3, 3 of 3) from step 2
3 out of 3
U2> 1.0 - 200.0 %UB 0.1 150.0 Voltage setting/start val (DT & IDMT)
in % of UBase, step 2
t2 0.000 - 60.000 s 0.001 5.000 Definitive time delay of step 2
t2Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse
curves for step 2
k2 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time
delay for step 2
HystAbs2 0.0 - 50.0 %UB 0.1 0.5 Absolute hysteresis in % of UBase,
step 2

Breaker protection REQ650 163


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 7 1MRK 505 384-UEN C
Voltage protection

Table 110: OV2PTOV Group settings (advanced)


Name Values (Range) Unit Step Default Description
tReset1 0.000 - 60.000 s 0.001 0.025 Reset time delay used in IEC Definite
Time curve step 1
ResetTypeCrv1 Instantaneous - - Instantaneous Selection of used IDMT reset curve
Frozen timer type for step 1
Linearly
decreased
tIReset1 0.000 - 60.000 s 0.001 0.025 Time delay in IDMT reset (s), step 1
ACrv1 0.005 - 200.000 - 0.001 1.000 Parameter A for customer
programmable curve for step 1
BCrv1 0.50 - 100.00 - 0.01 1.00 Parameter B for customer
programmable curve for step 1
CCrv1 0.0 - 1.0 - 0.1 0.0 Parameter C for customer
programmable curve for step 1
DCrv1 0.000 - 60.000 - 0.001 0.000 Parameter D for customer
programmable curve for step 1
PCrv1 0.000 - 3.000 - 0.001 1.000 Parameter P for customer
programmable curve for step 1
CrvSat1 0 - 100 % 1 0 Tuning param for prog. over voltage
IDMT curve, step 1
tReset2 0.000 - 60.000 s 0.001 0.025 Reset time delay used in IEC Definite
Time curve step 2
ResetTypeCrv2 Instantaneous - - Instantaneous Selection of used IDMT reset curve
Frozen timer type for step 2
Linearly
decreased
tIReset2 0.000 - 60.000 s 0.001 0.025 Time delay in IDMT reset (s), step 2
ACrv2 0.005 - 200.000 - 0.001 1.000 Parameter A for customer
programmable curve for step 2
BCrv2 0.50 - 100.00 - 0.01 1.00 Parameter B for customer
programmable curve for step 2
CCrv2 0.0 - 1.0 - 0.1 0.0 Parameter C for customer
programmable curve for step 2
DCrv2 0.000 - 60.000 - 0.001 0.000 Parameter D for customer
programmable curve for step 2
PCrv2 0.000 - 3.000 - 0.001 1.000 Parameter P for customer
programmable curve for step 2
CrvSat2 0 - 100 % 1 0 Tuning param for prog. over voltage
IDMT curve, step 2

Table 111: OV2PTOV Non group settings (basic)


Name Values (Range) Unit Step Default Description
ConnType PhN DFT - - PhN DFT Group selector for connection type
PhPh DFT
PhN RMS
PhPh RMS
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

164 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 7
Voltage protection

7.2.6 Monitored data


PID-3535-MONITOREDDATA v6

Table 112: OV2PTOV Monitored data


Name Type Values (Range) Unit Description
UL1 REAL - kV Voltage in phase L1
UL2 REAL - kV Voltage in phase L2
UL3 REAL - kV Voltage in phase L3

7.2.7 Operation principle M15330-3 v11

Two step overvoltage protection OV2PTOV is used to detect high power system voltage.
OV2PTOV has two steps with separate time delays. If one-, two- or three-phase voltages
increase above the set value, a corresponding START signal is issued. OV2PTOV can be set to
START/TRIP, based on 1 out of 3, 2 out of 3 or 3 out of 3 of the measured voltages, being above
the set point. If the voltage remains above the set value for a time period corresponding to the
chosen time delay, the corresponding trip signal is issued.

The time delay characteristic is individually chosen for the two steps, and can be either
definite time or inverse time delayed.

The voltage related settings are made in percent of the global set base voltage UBase, which is
set in kV, phase-to-phase.

OV2PTOV can be set to measure phase-to-earth fundamental value, phase-to-phase


fundamental value, phase-to-earth RMS value or phase-to-phase RMS value. The choice of
measuring is done by the parameter ConnType.

The setting of the analog inputs are given as primary phase-to-earth or phase-to-phase
voltage. OV2PTOV will operate if the voltage gets higher than the set percentage of the set
base voltage UBase. This means operation for phase-to-earth voltage over:

U > (%) × UBase( kV )


3
EQUATION1434 V1 EN-US (Equation 26)

and operation for phase-to-phase voltage over:

U > (%) × UBase(kV)


EQUATION1993 V1 EN-US (Equation 27)

When phase-to-earth voltage measurement is selected the function


automatically introduces division of the base value by the square root of three.

7.2.7.1 Measurement principle M15330-6 v6

All the three voltages are measured continuously, and compared with the set values, U1> for
Step 1 and U2> for Step 2. The parameters OpMode1 and OpMode2 influence the requirements
to activate the START outputs. Either 1 out of 3, 2 out of 3 or 3 out of 3 measured voltages have
to be higher than the corresponding set point to issue the corresponding START signal.

Breaker protection REQ650 165


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 7 1MRK 505 384-UEN C
Voltage protection

To avoid oscillations of the output START signal, a hysteresis is included.

7.2.7.2 Time delay M15330-10 v11

The time delay for the two steps can be either definite time delay (DT) or inverse time delay
(IDMT). For the inverse time delay four different modes are available:

• inverse curve A
• inverse curve B
• inverse curve C
• customer programmable inverse curve

The type A curve is described as:

k
t=
æ U - Un > ö
ç ÷
è Un > ø
IECEQUATION2422 V1 EN-US (Equation 28)

where:
Un> Set value for step 1 and step 2
U Measured voltage

The type B curve is described as:

k  480
t 2.0
 0.035
 U  Un  
 32   0.5 
 U n  

IECEQUATION2423 V2 EN-US (Equation 29)

The type C curve is described as:

k × 480
t= 3.0
+ 0.035
æ U - Un > ö
ç 32 × - 0.5 ÷
è Un > ø
IECEQUATION2425 V1 EN-US (Equation 30)

The customer programmable curve is defined by the below equation, where A, B, C, D, k and p
are settings:

k×A
t= p
+D
æ U -Un > ö
çB× -C÷
è Un > ø
EQUATION1439 V2 EN-US (Equation 31)

166 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 7
Voltage protection

When the denominator in the expression is equal to zero the time delay will be infinity. There
will be an undesired discontinuity. Therefore, a tuning parameter CrvSatn is set to compensate
for this phenomenon. In the voltage interval Un> up to Un> · (1.0 + CrvSatn/100) the used
voltage will be: Un> · (1.0 + CrvSatn/100). If the programmable curve is used this parameter
must be calculated so that:

CrvSatn
B× -C > 0
100
EQUATION1435 V1 EN-US (Equation 32)

The highest phase (or phase-to-phase) voltage is always used for the inverse time delay
integration, see figure 77. The details of the different inverse time characteristics are shown in
section "Inverse characteristics".

Voltage
IDMT Voltage

UL1
UL2
UL3

Time

IEC05000016-2-en.vsd
IEC05000016 V2 EN-US

Figure 77: Voltage used for the inverse time characteristic integration
Operation of the trip signal requires that the overvoltage condition continues for at least the
user set time delay. This time delay is set by the parameter t1 and t2 for definite time mode
(DT) and by selected voltage level dependent time curves for the inverse time mode (IDMT). If
the START condition, with respect to the measured voltage ceases during the delay time, and
is not fulfilled again within a user defined reset time (tReset1 and tReset2 for the definite time
and tIReset1 and tIReset2 for the inverse time) the corresponding START output is reset, after
that the defined reset time has elapsed. Here it should be noted that after leaving the
hysteresis area, the START condition must be fulfilled again and it is not sufficient for the
signal to only return back to the hysteresis area. The hysteresis value for each step is settable
HystAbsn (where n means either 1 or 2 respectively) to allow a high and accurate reset of the
function. For OV2PTOV the IDMT reset time is constant and does not depend on the voltage
fluctuations during the drop-off period. However, there are three ways to reset the timer:
either the timer is reset instantaneously, or the timer value is frozen during the reset time, or
the timer value is linearly decreased during the reset time.

Breaker protection REQ650 167


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 7 1MRK 505 384-UEN C
Voltage protection

tIReset1
Voltage
START
TRIP

U1>

HystAbs1 Measured
Voltage

Time

START t

TRIP

Time
Integrator Linearly decreased
Frozen Timer
t

Instantaneous Time
IEC09000055‐3‐en.vsdx

IEC09000055 V3 EN-US

Figure 78: Voltage profile not causing a reset of the START signal for step 1, and inverse time delay at
different reset types

168 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 7
Voltage protection

tIReset1
Voltage
START TRIP
START HystAbs1

U1>
Measured
Voltage

Time

START t

TRIP

Time
Integrator Frozen Timer

Time
Linearly
Instantaneous decreased
IEC05000020‐4‐en.vsdx

IEC05000020 V4 EN-US

Figure 79: Voltage profile causing a reset of the START signal for step 1, and inverse time delay at
different reset types
Definite time delay

When definite time delay is selected, the function will operate as shown in figure 80. Detailed
information about individual stage reset/operation behavior is shown in figure 81 and figure
82 respectively. Note that by setting tResetn = 0.0s (where n means either 1 or 2 respectively),
instantaneous reset of the definite time delayed stage is ensured.

Breaker protection REQ650 169


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 7 1MRK 505 384-UEN C
Voltage protection

ST1

U tReset1 t1
a
a>b t t
TR1
U1>
b AND
OFF ON
Delay Delay

IEC10000100-2-en.vsd
IEC10000100 V2 EN-US

Figure 80: Logic diagram for step 1, definite time delay, DT operation

U1>

START

TRIP

tReset1

t1

IEC10000037-2-en.vsd
IEC10000037 V2 EN-US

Figure 81: Example for step 1, Definite Time Delay stage 1 reset

U1>

START

TRIP

tReset1

t1

IEC10000038-2-en.vsd
IEC10000038 V2 EN-US

Figure 82: Example for Definite Time Delay stage 1 operation

170 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 7
Voltage protection

7.2.7.3 Blocking M15330-20 v8

It is possible to block Two step overvoltage protection OV2PTOV partially or completely, by


binary input signals where:

BLOCK: blocks all outputs


BLKTR1: blocks all trip outputs of step 1
BLKST1: blocks all start and trip outputs related to step 1
BLKTR2: blocks all trip outputs of step 2
BLKST2: blocks all start and trip outputs related to step 2

7.2.7.4 Design M15330-34 v8

The voltage measuring elements continuously measure the three phase-to-earth voltages or
the three phase-to-phase voltages. Recursive Fourier filters or true RMS filters of input voltage
signals are used. The phase voltages are individually compared to the set value, and the
highest voltage is used for the inverse time characteristic integration. A special logic is
included to achieve the 1 out of 3, 2 out of 3 or 3 out of 3 criteria to fulfill the START condition.
The design of Two step overvoltage protection (OV2PTOV) is schematically described in
figure 83.

Breaker protection REQ650 171


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 7 1MRK 505 384-UEN C
Voltage protection

UL1 Comparator ST1L1


UL1 > U1> Phase 1
Voltage Phase
Selector ST1L2
UL2 Comparator OpMode1 Phase 2
UL2 > U1> 1 out of 3
Start ST1L3
2 out of 3
3 out of 3 Phase 3 t1
UL3 Comparator t1Reset
UL3 > U1> & ST1
OR
Trip
START Output TR1L1
Logic

Time integrator Step 1 TR1L2


TRIP
MaxVoltSelect tIreset1
ResetTypeCrv1 TR1L3

OR TR1

Comparator ST2L1
UL1 > U2> Phase 1
Voltage Phase
Selector ST2L2
Comparator OpMode2 Phase 2
UL2 > U2> 1 out of 3
Start ST2L3
2 out of 3
Phase 3 t2
3 out of 3
Comparator t2Reset
UL3 > U2> & ST2
OR
Trip
START Output TR2L1
Logic

Time integrator Step 2 TR2L2


MaxVoltSelect tIreset2 TRIP
ResetTypeCrv2 TR2L3

TR2
OR

START
OR

TRIP
OR

IEC05000013-2-en.vsd

IEC05000013-WMF V2 EN-US

Figure 83: Schematic design of Two step overvoltage protection OV2PTOV

7.2.8 Technical data IP13013-1 v1

M13304-1 v14

Table 113: OV2PTOV technical data


Function Range or value Accuracy
Operate voltage, step 1 and 2 (1.0-200.0)% of UBase ±0.5% of Ur at U ≤ Ur
±0.5% of U at U > Ur

Absolute hysteresis (0.0–50.0)% of UBase ±0.5% of Ur at U ≤ Ur


±0.5% of U at U > Ur

Inverse time characteristics for steps 1 - See table 588


and 2, see table 588
Definite time delay, low step (step 1) at (0.00 - 6000.00) s ±0.2% or ±45 ms whichever is
0 to 1.2 x Uset greater

Definite time delay, high step (step 2) at (0.000-60.000) s ±0.2% or ±45 ms whichever is
0 to 1.2 x Uset greater

Table continues on next page

172 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 7
Voltage protection

Function Range or value Accuracy


Minimum operate time, Inverse (0.000-60.000) s ±0.2% or ±45 ms whichever is
characteristics greater
Operate time, start at 0 to 2 x Uset Min. = 15 ms -
Max. = 30 ms
Reset time, start at 2 x Uset to 0 Min. = 15 ms -
Max. = 30 ms
Operate time, start at 0 to 1.2 x Uset Min. = 20 ms -
Max. = 35 ms
Reset time, start at 1.2 x Uset to 0 Min. = 5 ms -
Max. = 25 ms
Critical impulse time 10 ms typically at 0 to 2 x -
Uset

Impulse margin time 15 ms typically -

7.3 Two step residual overvoltage protection ROV2PTOV IP14546-1 v4

7.3.1 Identification
SEMOD54295-2 v6

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Two step residual overvoltage ROV2PTOV 59N
protection
2(U0>)

IEC15000108 V1 EN-US

7.3.2 Monitored data


PID-3531-MONITOREDDATA v4

Table 114: ROV2PTOV Monitored data


Name Type Values (Range) Unit Description
ULevel REAL - kV Magnitude of measured voltage

7.3.3 Operation principle M15331-3 v8

Two step residual overvoltage protection ROV2PTOV is used to detect a high residual voltage.
The residual voltage can be measured directly from a voltage transformer in the neutral of a
power transformer or from a three-phase voltage transformer, where the secondary windings
are connected in an open delta. Another possibility is to measure the three phase-to-earth
voltages, and calculate the corresponding residual voltage internally in the IED. ROV2PTOV has
two steps with separate time delays. If the residual voltage remains above the set value for a
time period corresponding to the chosen time delay, the corresponding TRIP signal is issued.

The time delay characteristic is individually chosen for the two steps and can be either definite
time delay or inverse time delay.

The voltage-related settings are made in percent of the base voltage, which is set in kV, phase-
phase. The set UBase value is divided by sqrt(3) before the set value is calculated.

Breaker protection REQ650 173


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 7 1MRK 505 384-UEN C
Voltage protection

7.3.3.1 Measurement principle M15331-6 v6

The residual voltage is measured continuously, and compared with the set values, U1> and
U2>.

To avoid oscillations of the output START signal, a settable hysteresis has been included.

7.3.3.2 Time delay M15331-10 v11

The time delay for the two steps can be either definite time delay (DT) or inverse time delay
(IDMT). For the inverse time delay four different modes are available:

• inverse curve A
• inverse curve B
• inverse curve C
• customer programmable inverse curve

The type A curve is described as:

k
t=
æ U - Un > ö
ç ÷
è Un > ø
IECEQUATION2422 V1 EN-US (Equation 33)

where:
Un> Set value for step 1 and step 2
U Measured voltage

The type B curve is described as:

k  480
t 2.0
 0.035
 U  Un  
 32   0.5 
 U n  

IECEQUATION2423 V2 EN-US (Equation 34)

The type C curve is described as:

k × 480
t= 3.0
+ 0.035
æ U - Un > ö
ç 32 × - 0.5 ÷
è U> ø
IECEQUATION2421 V1 EN-US (Equation 35)

The customer programmable curve can be created as:

k×A
t= p
+D
æ U -Un > ö
çB× -C÷
è Un > ø
EQUATION1439 V2 EN-US (Equation 36)

174 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 7
Voltage protection

When the denominator in the expression is equal to zero, the time delay will be infinite. There
will be an undesired discontinuity. Therefore a tuning parameter CrvSatn is set to compensate
for this phenomenon. In the voltage interval Un> up to Un> · (1.0 + CrvSatn/100) the used
voltage will be: Un> · (1.0 + CrvSatn/100). If the programmable curve is used this parameter
must be calculated so that:

CrvSatn
B× -C > 0
100
EQUATION1440 V1 EN-US (Equation 37)

The details of the different inverse time characteristics are shown in section "Inverse
characteristics".

TRIP signal issuing requires that the residual overvoltage condition continues for at least the
user set time delay. This time delay is set by the parameter t1 and t2 for definite time mode
(DT) and by some special voltage level dependent time curves for the inverse time mode
(IDMT).

If the START condition, with respect to the measured voltage ceases during the delay time, and
is not fulfilled again within a user defined reset time (tReset1 and tReset2 for the definite time
and tIReset1 and tIReset2 for the inverse time) the corresponding START output is reset, after
the defined reset time has elapsed.

Here it should be noted that after leaving the hysteresis area, the START condition must be
fulfilled again and it is not sufficient for the signal to only return back to the hysteresis area.
Also, notice that for the overvoltage function, IDMT reset time is constant and does not
depend on the voltage fluctuations during the drop-off period.

There are three ways to reset the timer: the timer is reset instantaneously, the timer value is
frozen during the reset time, or the timer value is linearly decreased during the reset time. See
figure 84 and figure 85.

Breaker protection REQ650 175


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 7 1MRK 505 384-UEN C
Voltage protection

tIReset1
Voltage
START
TRIP

U1>

HystAbs1 Measured
Voltage

Time

START t

TRIP

Time
Integrator Linearly decreased
Frozen Timer
t

Instantaneous Time
IEC09000055‐3‐en.vsdx

IEC09000055 V3 EN-US

Figure 84: Voltage profile not causing a reset of the START signal for step 1, and inverse time delay

176 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 7
Voltage protection

tIReset1
Voltage
START TRIP
START HystAbs1

U1>
Measured
Voltage

Time

START t

TRIP

Time
Integrator Frozen Timer

Time
Linearly
Instantaneous decreased
IEC05000020‐4‐en.vsdx

IEC05000020 V4 EN-US

Figure 85: Voltage profile causing a reset of the START signal for step 1, and inverse time delay
Definite time delay

When definite time delay is selected, the function will operate as shown in figure 86. Detailed
information about individual stage reset/operation behavior is shown in figure 87 and figure
88 respectively. Note that by setting tResetn = 0.0s, instantaneous reset of the definite time
delayed stage is ensured.

Breaker protection REQ650 177


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 7 1MRK 505 384-UEN C
Voltage protection

ST1

U tReset1 t1
a
a>b t t
TR1
U1>
b AND
OFF ON
Delay Delay

IEC10000100-2-en.vsd
IEC10000100 V2 EN-US

Figure 86: Logic diagram for step 1, Definite time delay, DT operation

U1<

ST1

TR1

tReset1

t1

IEC10000039-3-en.vsd
IEC10000039 V3 EN-US

Figure 87: Example for Definite Time Delay stage 1 reset

U1<

ST1

TR1

tReset1

t1

IEC10000040-3-en.vsd
IEC10000040 V3 EN-US

Figure 88: Example for Definite Time Delay stage 1 operation

178 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 7
Voltage protection

7.3.3.3 Blocking M15331-18 v7

It is possible to block two step residual overvoltage protection ROV2PTOV partially or


completely by binary input signals where:

BLOCK: blocks all outputs


BLKTR1: blocks all trip outputs of step 1
BLKST1: blocks all start and trip outputs related to step 1
BLKTR2: blocks all trip outputs of step 2
BLKST2: blocks all start and trip inputs related to step 2

7.3.3.4 Design M15331-32 v7

The voltage measuring elements continuously measure the residual voltage. Recursive Fourier
filters filter the input voltage signal for the rated frequency. The residual voltage is compared
to the set value, and is also used for the inverse time characteristic integration. The design of
the function is schematically described in figure 89.

UN Comparator Phase 1 ST1


UN > U1>
Start TR1
START t1
tReset1
&
Trip
Time integrator Output
tIReset1 TRIP
Logic
ResetTypeCrv1
Step 1

ST2
Comparator Phase 1
UN > U2> TR2
Start
t2
START tReset2
& START
Trip OR
Time integrator Output
TRIP Logic
tIReset2
ResetTypeCrv2 TRIP
Step 2 OR

IEC05000748_2_en.vsd
IEC05000748 V2 EN-US

Figure 89: Schematic design of Two step residual overvoltage protection ROV2PTOV

Breaker protection REQ650 179


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 7 1MRK 505 384-UEN C
Voltage protection

7.3.4 Technical data


M13317-2 v14

Table 115: ROV2PTOV technical data


Function Range or value Accuracy
Operate voltage, step 1 - step 2 (1.0-200.0)% of UBase ± 0.5% of Ur at U ≤ Ur
± 0.5% of U at U > Ur

Absolute hysteresis (0.0–50.0)% of UBase ± 0.5% of Ur at U ≤ Ur


± 0.5% of U at U > Ur

Inverse time characteristics for low - See table 590


and high step, see table 590
Definite time delay low step (step 1) at (0.00–6000.00) s ± 0.2% or ± 45 ms whichever is
0 to 1.2 x Uset greater

Definite time delay high step (step 2) (0.000–60.000) s ± 0.2% or ± 45 ms whichever is


at 0 to 1.2 x Uset greater

Minimum operate time (0.000-60.000) s ± 0.2% or ± 45 ms whichever is


greater
Operate time, start at 0 to 2 x Uset Min. = 15 ms -
Max. = 30 ms
Reset time, start at 2 x Uset to 0 Min. = 15 ms -
Max. = 30 ms
Operate time, start at 0 to 1.2 x Uset Min. = 20 ms -
Max. = 35 ms
Reset time, start at 1.2 x Uset to 0 Min. = 5 ms -
Max. = 25 ms
Critical impulse time 10 ms typically at 0 to 2 x Uset -

Impulse margin time 15 ms typically -

7.4 Loss of voltage check LOVPTUV SEMOD171453-1 v3

7.4.1 Identification
SEMOD171954-2 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Loss of voltage check LOVPTUV - 27

7.4.2 Functionality SEMOD171457-5 v8

Loss of voltage check (LOVPTUV ) is suitable for use in networks with an automatic system
restoration function. LOVPTUV issues a three-pole trip command to the circuit breaker, if all
three phase voltages fall below the set value for a time longer than the set time and the circuit
breaker remains closed.

The operation of LOVPTUV is supervised by the fuse failure supervision FUFSPVC.

180 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 7
Voltage protection

7.4.3 Function block SEMOD171785-4 v4

LOVPTUV
U3P* TRIP
BLOCK START
CBOPEN
VTSU

IEC07000039-2-en.vsd
IEC07000039 V2 EN-US

Figure 90: LOVPTUV function block

7.4.4 Signals
PID-3519-INPUTSIGNALS v6

Table 116: LOVPTUV Input signals


Name Type Default Description
U3P GROUP - Voltage connection
SIGNAL
BLOCK BOOLEAN 0 Block the all outputs
CBOPEN BOOLEAN 0 Circuit breaker open
VTSU BOOLEAN 0 Block from voltage circuit supervision

PID-3519-OUTPUTSIGNALS v6

Table 117: LOVPTUV Output signals


Name Type Description
TRIP BOOLEAN Trip signal
START BOOLEAN Start signal

7.4.5 Settings
PID-3519-SETTINGS v6

Table 118: LOVPTUV Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
UPE 1 - 100 %UB 1 70 Operate voltage in % of base voltage
UBase
tTrip 0.000 - 60.000 s 0.001 7.000 Operate time delay

Table 119: LOVPTUV Group settings (advanced)


Name Values (Range) Unit Step Default Description
tPulse 0.050 - 60.000 s 0.001 0.150 Duration of TRIP pulse
tBlock 0.000 - 60.000 s 0.001 5.000 Time delay to block when all 3ph
voltages are not low
tRestore 0.000 - 60.000 s 0.001 3.000 Time delay for enable the function
after restoration

Breaker protection REQ650 181


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 7 1MRK 505 384-UEN C
Voltage protection

Table 120: LOVPTUV Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

7.4.6 Operation principle SEMOD171765-4 v6

The operation of Loss of voltage check LOVPTUV is based on line voltage measurement.
LOVPTUV is provided with a logic, which automatically recognizes if the line was restored for
at least tRestore before starting the tTrip timer. All three phases are required to be low before
the output TRIP is activated. The START output signal indicates start.

Additionally, LOVPTUV is automatically blocked if only one or two phase voltages have been
detected low for more than tBlock.

LOVPTUV operates again only if the line has been restored to full voltage for at least tRestore.
Operation of the function is also inhibited by fuse failure and open circuit breaker information
signals, by their connection to dedicated inputs of the function block.

Due to undervoltage conditions being continuous the trip pulse is limited to a length set by
setting tPulse.

The operation of LOVPTUV is supervised by the fuse-failure function (BLKU input) and the
information about the open position (CBOPEN) of the associated circuit breaker.

The BLOCK input can be connected to a binary input of the IED in order to receive a block
command from external devices or can be software connected to other internal functions of
the IED itself in order to receive a block command from internal functions. LOVPTUV is also
blocked when the IED is in TEST status and the function has been blocked from the HMI test
menu. (Blocked=Yes).

182 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 7
Voltage protection

TEST

TEST-ACTIVE
&
Blocked = Yes

START
BLOCK >1
Function Enable tTrip tPulse TRIP
STUL1N & t

STUL2N &
only 1 or 2 phases are low for
Latched at least 10 s (not three)
STUL3N Enable
&

tBlock
>1 t

CBOPEN Reset Enable


>1
&
VTSU
tRestore
>1 Set Enable
t
>1
Line restored for
at least 3 s

IEC07000089_2_en.vsd

IEC07000089 V2 EN-US

Figure 91: Simplified diagram of Loss of voltage check LOVPTUV

7.4.7 Technical data


SEMOD175210-2 v6

Table 121: LOVPTUV technical data


Function Range or value Accuracy
Operate voltage (1–100)% of UBase ±0.5% of Ur

Pulse timer when (0.050–60.000) s ±0.2% or ±15 ms whichever is greater


disconnecting all three phases
Time delay for enabling the (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
functions after restoration
Operate time delay when (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
disconnecting all three phases
Time delay to block when all (0.000–60.000) s ±0.2% or ±35 ms whichever is greater
three phase voltages are not
low

Breaker protection REQ650 183


Technical manual
© Copyright 2017 ABB. All rights reserved
184
1MRK 505 384-UEN C Section 8
Secondary system supervision

Section 8 Secondary system supervision


8.1 Current circuit supervision CCSSPVC IP14555-1 v5

8.1.1 Identification
M14870-1 v5

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Current circuit supervision CCSSPVC - 87

8.1.2 Functionality M12444-3 v10

Open or short circuited current transformer cores can cause unwanted operation of many
protection functions such as differential, earth-fault current and negative-sequence current
functions.

Current circuit supervision (CCSSPVC) compares the residual current from a three phase set of
current transformer cores with the neutral point current on a separate input taken from
another set of cores on the current transformer.

A detection of a difference indicates a fault in the circuit and is used as alarm or to block
protection functions expected to give inadvertent tripping.

8.1.3 Function block M12436-3 v9

CCSSPVC
I3P* FAIL
IREF* ALARM
BLOCK
IEC13000304-1-en.vsd
IEC13000304 V1 EN-US

Figure 92: CCSSPVC function block

Signal ISIREF must be connected in the configuration.

8.1.4 Signals
PID-6806-INPUTSIGNALS v2

Table 122: CCSSPVC Input signals


Name Type Default Description
I3P GROUP - Group signal for three phase current input
SIGNAL
IREF GROUP - Residual reference current input
SIGNAL
BLOCK BOOLEAN 0 Block of function

Breaker protection REQ650 185


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 505 384-UEN C
Secondary system supervision

PID-6806-OUTPUTSIGNALS v2

Table 123: CCSSPVC Output signals


Name Type Description
FAIL BOOLEAN Detection of current circuit failure
ALARM BOOLEAN Alarm for current circuit failure

8.1.5 Settings
PID-6806-SETTINGS v2

Table 124: CCSSPVC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
IMinOp 10 - 200 %IB 1 20 Minimum operate current differential
level in % of IBase

Table 125: CCSSPVC Group settings (advanced)


Name Values (Range) Unit Step Default Description
Ip>Block 20 - 500 %IB 1 150 Block of the function at high phase
current, in % of IBase

Table 126: CCSSPVC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

8.1.6 Operation principle M12396-5 v10

Current circuit supervision CCSSPVC compares the absolute value of the vectorial sum of the
three phase currents |ΣIphase| and the absolute value of the residual current |Iref| from
another current transformer set, see figure 93.

The FAIL output will be set to high when the following criteria are fulfilled:

• The numerical value of the difference |ΣIphase| – |Iref| is higher than 80% of the numerical
value of the sum |ΣIphase| + |Iref|.
• The numerical value of the current |ΣIphase| – |Iref| is equal to or higher than the set
operate value IMinOp.
• No phase current has exceeded Ip>Block during the last 10 ms.
• CCSSPVC is enabled by setting Operation = On.

The FAIL output remains activated 100 ms after the AND-gate resets when being activated for
more than 20 ms. If the FAIL lasts for more than 150 ms an ALARM will be issued. In this case
the FAIL and ALARM will remain activated 1 s after the AND-gate resets. This prevents
unwanted resetting of the blocking function when phase current supervision element(s)
operate, for example, during a fault.

186 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 8
Secondary system supervision

IL1 IL1 I>1.054 * IMinOp


IL2 IL2 +
IL3 IL3  -
+ +
I ref Iref + x -
0,8
I>IP>Block
10 ms AND
OR FAIL
OR t

40 ms 100 ms

170 ms 3000 ms ALARM


OPERATION
BLOCK

IEC05000463-3-en.vsd
IEC05000463 V3 EN-US

Figure 93: Simplified logic diagram for Current circuit supervision CCSSPVC
The operate characteristic is percentage restrained, which is shown in Figure 94.

| åI phase | - | I ref |

Slope = 1

Operation
Slope = 0.8
area
I MinOp

| åI phase | + | I ref |
99000068.vsd
IEC99000068 V1 EN-US

Figure 94: Operate characteristics

Due to the formulas for the axis compared, |SIphase | - |I ref | and |S I phase | + |
I ref | respectively, the slope can not be above 1.

8.1.7 Technical data


M12358-1 v10

Table 127: CCSSPVCtechnical data


Function Range or value Accuracy
Operate current (10-200)% of IBase ±10.0% of Ir at I ≤ Ir
±10.0% of I at I > Ir

Reset ratio, Operate current >90%


Block current (20-500)% of IBase ±5.0% of Ir at I ≤ Ir
±5.0% of I at I > Ir

Reset ratio, Block current >90% at (50-500)% of IBase

Breaker protection REQ650 187


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 505 384-UEN C
Secondary system supervision

8.2 Fuse failure supervision FUFSPVC IP14556-1 v3

8.2.1 Identification
M14869-1 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Fuse failure supervision FUFSPVC - -

8.2.2 Functionality SEMOD113820-4 v12

The aim of the fuse failure supervision function (FUFSPVC) is to block voltage measuring
functions at failures in the secondary circuits between the voltage transformer and the IED in
order to avoid inadvertent operations that otherwise might occur.

The fuse failure supervision function basically has three different detection methods, negative
sequence and zero sequence based detection and an additional delta voltage and delta current
detection.

The negative sequence detection algorithm is recommended for IEDs used in isolated or high-
impedance earthed networks. It is based on the negative-sequence quantities.

The zero sequence detection is recommended for IEDs used in directly or low impedance
earthed networks. It is based on the zero sequence measuring quantities.

The selection of different operation modes is possible by a setting parameter in order to take
into account the particular earthing of the network.

A criterion based on delta current and delta voltage measurements can be added to the fuse
failure supervision function in order to detect a three phase fuse failure, which in practice is
more associated with voltage transformer switching during station operations.

8.2.3 Function block M13678-3 v9

FUFSPVC
I3P* BLKZ
U3P* BLKU
BLOCK 3PH
CBCLOSED DLD1PH
MCBOP DLD3PH
DISCPOS STDI
BLKTRIP STDIL1
STDIL2
STDIL3
STDU
STDUL1
STDUL2
STDUL3

IEC14000065-1-en.vsd
IEC14000065 V1 EN-US

Figure 95: FUFSPVC function block

188 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 8
Secondary system supervision

8.2.4 Signals
PID-3492-INPUTSIGNALS v9

Table 128: FUFSPVC Input signals


Name Type Default Description
I3P GROUP - Current connection
SIGNAL
U3P GROUP - Voltage connection
SIGNAL
BLOCK BOOLEAN 0 Block of function
CBCLOSED BOOLEAN 0 Active when circuit breaker is closed
MCBOP BOOLEAN 0 Active when external MCB opens protected voltage circuit
DISCPOS BOOLEAN 0 Active when line disconnector is open
BLKTRIP BOOLEAN 0 Blocks operation of function when active

PID-3492-OUTPUTSIGNALS v9

Table 129: FUFSPVC Output signals


Name Type Description
BLKZ BOOLEAN Start of current and voltage controlled function
BLKU BOOLEAN General start of function
3PH BOOLEAN Three-phase start of function
DLD1PH BOOLEAN Dead line condition in at least one phase
DLD3PH BOOLEAN Dead line condition in all three phases
STDI BOOLEAN Common start signal of sudden change in current
STDIL1 BOOLEAN Start signal of sudden change in current, phase L1
STDIL2 BOOLEAN Start signal of sudden change in current, phase L2
STDIL3 BOOLEAN Start signal of sudden change in current, phase L3
STDU BOOLEAN Common start signal of sudden change in voltage
STDUL1 BOOLEAN Start signal of sudden change in voltage, phase L1
STDUL2 BOOLEAN Start signal of sudden change in voltage, phase L2
STDUL3 BOOLEAN Start signal of sudden change in voltage, phase L3

Breaker protection REQ650 189


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 505 384-UEN C
Secondary system supervision

8.2.5 Settings
PID-3492-SETTINGS v9

Table 130: FUFSPVC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OpMode Off - - UZsIZs Operating mode selection
UNsINs
UZsIZs
UZsIZs OR
UNsINs
UZsIZs AND
UNsINs
OptimZsNs
3U0> 1 - 100 %UB 1 30 Operate level of residual overvoltage
element in % of UBase
3I0< 1 - 100 %IB 1 10 Operate level of residual undercurrent
element in % of IBase
3U2> 1 - 100 %UB 1 30 Operate level of neg seq overvoltage
element in % of UBase
3I2< 1 - 100 %IB 1 10 Operate level of neg seq undercurrent
element in % of IBase
OpDUDI Off - - Off Operation of change based function
On Off/On
DU> 1 - 100 %UB 1 60 Operate level of change in phase
voltage in % of UBase
DI< 1 - 100 %IB 1 15 Operate level of change in phase
current in % of IBase
UPh> 1 - 100 %UB 1 70 Operate level of phase voltage in % of
UBase
IPh> 1 - 100 %IB 1 10 Operate level of phase current in % of
IBase
SealIn Off - - On Seal in functionality Off/On
On
USealln< 1 - 100 %UB 1 70 Operate level of seal-in phase voltage
in % of UBase
IDLD< 1 - 100 %IB 1 5 Operate level for open phase current
detection in % of IBase
UDLD< 1 - 100 %UB 1 60 Operate level for open phase voltage
detection in % of UBase

Table 131: FUFSPVC Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups

190 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 8
Secondary system supervision

8.2.6 Monitored data


PID-3492-MONITOREDDATA v8

Table 132: FUFSPVC Monitored data


Name Type Values (Range) Unit Description
3I0 REAL - A Magnitude of zero sequence current
3I2 REAL - A Magnitude of negative sequence
current
3U0 REAL - kV Magnitude of zero sequence voltage
3U2 REAL - kV Magnitude of negative sequence
voltage

8.2.7 Operation principle

8.2.7.1 Zero and negative sequence detection M13677-3 v5

The zero and negative sequence function continuously measures the currents and voltages in
all three phases and calculates, see figure 96:

• the zero-sequence voltage 3U0


• the zero-sequence current 3I0
• the negative sequence current 3I2
• the negative sequence voltage 3U2

The measured signals are compared with their respective set values 3U0> and 3I0<, 3U2> and
3I2<.

The function enable the internal signal FuseFailDetZeroSeq if the measured zero-sequence
voltage is higher than the set value 3U0> and the measured zero-sequence current is below the
set value 3I0<.

The function enable the internal signal FuseFailDetNegSeq if the measured negative sequence
voltage is higher than the set value 3U2> and the measured negative sequence current is below
the set value 3I2<.

A drop out delay of 100 ms for the measured zero-sequence and negative sequence current will
prevent a false fuse failure detection at un-equal breaker opening at the two line ends.

Breaker protection REQ650 191


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 505 384-UEN C
Secondary system supervision

Sequence Detection
3I0< CurrZeroSeq
IL1
Zero 3I0
sequence
filter 100 ms CurrNegSeq
a
IL2 a>b t
b
Negative 3I2
sequence
IL3 filter FuseFailDetZeroSeq
AND
100 ms
a
a>b t
3I2< b
FuseFailDetNegSeq
AND
3U0>
VoltZeroSeq
UL1
Zero
sequence a 3U0
a>b
b
filter
UL2 VoltNegSeq

Negative
sequence a 3U2
a>b
UL3 filter b

3U2>

IEC10000036-2-en.vsd
IEC10000036 V2 EN-US

Figure 96: Simplified logic diagram for sequence detection part


The calculated values 3U0, 3I0, 3I2 and 3U2 are available as service values on local HMI and
monitoring tool in PCM600.

Input and output signals M13677-19 v6


The output signals 3PH, BLKU and BLKZ as well as the signals DLD1PH and DLD3PH from dead
line detections are blocked if any of the following conditions occur:

• The input BLOCK is activated


• The input BLKTRIP is activated and the internal signal FuseFailStarted is not present
• The operation mode selector OpMode is set to Off
• The IED is in TEST status (TEST-ACTIVE is high) and the function has been blocked from
the HMI (BlockFUSE=Yes)

The input BLOCK signal is a general purpose blocking signal of the fuse failure supervision
function. It can be connected to a binary input of the IED in order to receive a block command
from external devices or can be software connected to other internal functions of the IED itself
in order to receive a block command from internal functions. Through OR gate it can be
connected to both binary inputs and internal function outputs.

The input BLKTRIP is intended to be connected to the trip output from any of the protection
functions included in the IED. When activated for more than 20 ms, the operation of the fuse
failure is blocked; a fixed drop-out timer prolongs the block for 100 ms. The aim is to increase
the security against unwanted operations during the opening of the breaker, which might
cause unbalance conditions for which the fuse failure might operate.

The output signal BLKZ will also be blocked if the internal dead line detection is activated. The
dead line detection signal has a 200 ms drop-out time delay.

The input signal MCBOP is supposed to be connected via a terminal binary input to the N.C.
auxiliary contact of the miniature circuit breaker protecting the VT secondary circuit. The
MCBOP signal sets the output signals BLKU and BLKZ in order to block all the voltage related
functions when the MCB is open independent of the setting of OpMode selector. The
additional drop-out timer of 150 ms prolongs the presence of MCBOP signal to prevent the
unwanted operation of voltage dependent function due to non simultaneous closing of the
main contacts of the miniature circuit breaker.

192 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 8
Secondary system supervision

The input signal DISCPOS is supposed to be connected via a terminal binary input to the N.C.
auxiliary contact of the line disconnector. The DISCPOS signal sets the output signal BLKU in
order to block the voltage related functions when the line disconnector is open. The
impedance protection function is not affected by the position of the line disconnector since
there will be no line currents that can cause malfunction of the distance protection. If
DISCPOS=0 it signifies that the line is connected to the system and when the DISCPOS=1 it
signifies that the line is disconnected from the system and the block signal BLKU is generated.

The output BLKU can be used for blocking the voltage related measuring functions
(undervoltage protection, energizing check and so on) except for the impedance protection.

The function output BLKZ shall be used for blocking the impedance protection function.

8.2.7.2 Delta current and delta voltage detection M13685-3 v7

A simplified diagram for the functionality is found in figure 97. The calculation of the changes
of currents and voltages is based on a sample analysis algorithm. The calculated delta
quantities are compared with their respective set values DI< and DU>. The algorithm detects a
fuse failure if a sufficient change in voltage without a sufficient change in current is detected
in each phase separately. The following quantities are calculated in all three phases:

• The change in voltage DU


• The change in current DI

The internal FuseFailDetDUDI signal is activated if the following conditions are fulfilled:

• The magnitude of the phase-ground voltage has been above UPh> for more than 1.5 cycles
(i.e. 30 ms in a 50 Hz system)
• The magnitudes of DU in three phases are higher than the corresponding setting DU>
• The magnitudes of DI in three phases are below the setting DI<

In addition to the above conditions, at least one of the following conditions shall be fulfilled in
order to activate the internal FuseFailDetDUDI signal:

• The magnitude of the phase currents in three phases are higher than the setting IPh>
• The circuit breaker is closed (CBCLOSED = True)

The first criterion means that detection of failure in three phases together with high current
for the three phases will set the output. The measured phase current is used to reduce the risk
of false fuse failure detection. If the current on the protected line is low, a voltage drop in the
system (not caused by fuse failure) may be followed by current change lower than the setting
DI<, and therefore a false fuse failure might occur.

The second criterion requires that the delta condition shall be fulfilled at the same time as
circuit breaker is closed. If CBCLOSED input is connected to FALSE , then only the first criterion
can enable the delta function.If the DUDI detections of three phases set the internal signal
FuseFailDetDUDI at the level high, then the signal FuseFailDetDUDI will remain high as long as
the voltages of three phases are lower then the setting Uph>.

In addition to fuse failure detection, two internal signals DeltaU and DeltaI are also generated
by the delta current and delta voltage DUDI detection algorithm. The internal signals DelatU
and DeltaI are activated when a sudden change of voltage, or respectively current, is detected.
The detection of the sudden change is based on a sample analysis algorithm. In particular
DelatU is activated if at least three consecutive voltage samples are higher then the setting
DU>. In a similar way DelatI is activated if at least three consecutive current samples are higher
then the setting DI<. When DeltaU or DeltaI are active, the output signals STDUL1, STDUL2,
STDUL3 and respectively STDIL1, STDIL2, STDIL3, based on a sudden change of voltage or
current detection, are activated with a 20 ms time off delay. The common start output signals

Breaker protection REQ650 193


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 505 384-UEN C
Secondary system supervision

STDU or STDI are activated with a 60 ms time off delay, if any sudden change of voltage or
current is detected.

The delta function (except the sudden change of voltage and current detection)
is deactivated by setting the parameter OpDUDI to Off.

DUDI Detection
DUDI detection Phase 1
DeltaIL1
IL1
IL2
IL3 DI detection based on sample analysis OR

DI<

UL1

DU detection based on sample analysis


AND
DU>
1.5 cycle 20 ms DeltaUL1
a
a>b t t
UPh> b

IL1 DeltaIL2
IL2 DUDI detection Phase 2
DeltaUL2
IL3
UL2 Same logic as for phase 1

IL1 DeltaIL3
DUDI detection Phase 3
IL2
DeltaUL3
IL3
UL3 Same logic as for phase 1

UL1
a
a<b
b

IL1
a
a>b
IPh> b AND

OR AND
CBCLOSED AND OR

UL2
a
a<b
b

IL2
a
a>b
b AND

OR AND
AND OR

UL3
a
a<b
b

IL3
a
a>b
b AND

OR AND
AND OR FuseFailDetDUDI
AND

IEC12000166-3-en.vsd

IEC12000166 V3 EN-US

Figure 97: Simplified logic diagram for the DU/DI detection part

194 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 8
Secondary system supervision

intBlock
STDI
AND

20 ms
DeltaIL1 STDIL1
t AND
OR
20 ms
DeltaIL2
t STDIL2
AND
20 ms
DeltaIL3
t
STDIL3
AND

STDU
AND

20 ms
DeltaUL1 STDUL1
t AND
OR
20 ms
DeltaUL2
t STDUL2
AND
20 ms
DeltaUL3
t
STDUL3
AND

IEC12000165-1-en.vsd
IEC12000165 V1 EN-US

Figure 98: Internal signals DeltaU or DeltaI and the corresponding output signals

8.2.7.3 Dead line detection M13679-44 v4

A simplified diagram for the functionality is found in figure 99. A dead phase condition is
indicated if both the voltage and the current in one phase is below their respective setting
values UDLD< and IDLD<. If at least one phase is considered to be dead the output DLD1PH
and the internal signal DeadLineDet1Ph is activated. If all three phases are considered to be
dead the output DLD3PH is activated

Breaker protection REQ650 195


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 505 384-UEN C
Secondary system supervision

Dead Line Detection


IL1
a
a<b AllCurrLow
b
AND
IL2
a
a<b
b

IL3
a
a<b
b

IDLD<
DeadLineDet1Ph
UL1
a AND
a<b
b OR DLD1PH
AND
UL2
a AND
a<b
b
AND DLD3PH
UL3 AND
a AND
a<b
b

UDLD<

intBlock

IEC10000035-1-en.vsd
IEC10000035 V2 EN-US

Figure 99: Simplified logic diagram for Dead Line detection part

8.2.7.4 Main logic GUID-D474A49E-D3A8-438C-B7E4-E527FEC2F335 v6

A simplified diagram for the functionality is found in figure 100. The fuse failure supervision
function (FUFSPVC) can be switched on or off by the setting parameter Operation to On or
Off.

For increased flexibility and adaptation to system requirements an operation mode selector,
OpMode, has been introduced to make it possible to select different operating modes for the
negative and zero sequence based algorithms. The different operation modes are:

• Off. The negative and zero sequence function is switched off.


• UNsINs. Negative sequence is selected.
• UZsIZs. Zero sequence is selected.
• UZsIZs OR UNsINs. Both negative and zero sequence are activated and work in parallel
(OR-condition for operation).
• UZsIZs AND UNsINs. Both negative and zero sequence are activated and work in series
(AND-condition for operation).
• OptimZsNs. Optimum of negative and zero sequence current (the function that has the
highest magnitude of measured negative and zero sequence current will be activated).

The delta function can be activated by setting the parameter OpDUDI to On. When selected it
operates in parallel with the sequence based algorithms.

As soon as any fuse failure situation is detected, signals FuseFailDetZeroSeq,


FuseFailDetNegSeq or FuseFailDetDUDI, and the specific functionality is released, the function
will activate the output signal BLKU. The output signal BLKZ will be activated as well if the
internal dead phase detection, DeadLineDet1Ph, is not activated at the same time. The output
BLKU can be used for blocking voltage related measuring functions (under voltage protection,
energizing check, and so on). The output BLKZ shall be used to block the impedance
protection functions.

If the fuse failure situation is present for more than 5 seconds and the setting parameter
SealIn is set to On it will be sealed in as long as at least one phase voltages is below the set

196 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 8
Secondary system supervision

value USealIn<. This will keep the BLKU and BLKZ signals activated as long as any phase
voltage is below the set value USealIn<. If all three phase voltages drop below the set value
USealIn< and the setting parameter SealIn is set to On the output signal 3PH will also be
activated. The signals 3PH, BLKU and BLKZ will now be active as long as any phase voltage is
below the set value USealIn<.

If SealIn is set to On the fuse failure condition lasting more then 5 seconds is stored in the non-
volatile memory in the IED. At start-up of the IED (due to auxiliary power interruption or re-
start due to configuration change) it uses the stored value in its non-volatile memory and re-
establishes the conditions that were present before the shut down. All phase voltages must be
restored above USealIn< before fuse failure is de-activated and resets the signals BLKU, BLKZ
and 3PH.

The output signal BLKU will also be active if all phase voltages have been above the setting
USealIn< for more than 60 seconds, the zero or negative sequence voltage has been above the
set value 3U0> and 3U2> for more than 5 seconds, all phase currents are below the setting
IDLD< (criteria for open phase detection) and the circuit breaker is closed (input CBCLOSED is
activated).

If a MCB is used then the input signal MCBOP is to be connected via a binary input to the N.C.
auxiliary contact of the miniature circuit breaker protecting the VT secondary circuit. The
MCBOP signal sets the output signals BLKU and BLKZ in order to block all the voltage related
functions when the MCB is open independent of the setting of OpMode or OpDUDI. An
additional drop-out timer of 150 ms prolongs the presence of MCBOP signal to prevent the
unwanted operation of voltage dependent function due to non simultaneous closing of the
main contacts of the miniature circuit breaker.

The input signal DISCPOS is supposed to be connected via a terminal binary input to the N.C.
auxiliary contact of the line disconnector. The DISCPOS signal sets the output signal BLKU in
order to block the voltage related functions when the line disconnector is open. The
impedance protection function does not have to be affected since there will be no line currents
that can cause malfunction of the distance protection.

Breaker protection REQ650 197


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 8 1MRK 505 384-UEN C
Secondary system supervision

Fuse failure detection


Main logic
TEST

TEST ACTIVE
AND
BlocFuse = Yes

BLOCK intBlock
OR
BLKTRIP 20 ms 100 ms
AND t t
FusefailStarted

All UL < USealIn<


OR
AND
3PH
AND
SealIn = On AND

AND
Any UL < UsealIn<

FuseFailDetDUDI
AND 5s
OpDUDI = On
OR t
FuseFailDetZeroSeq
AND

AND

FuseFailDetNegSeq
AND

UNsINs OR
UZsIZs OR
UZsIZs OR UNsINs
OpMode
UZsIZs AND UNsINs
OptimZsNs
OR
CurrZeroSeq
a AND
CurrNegSeq a>b
b

AND

DeadLineDet1Ph 200 ms
AND BLKZ
t OR AND
150 ms
MCBOP t

AND BLKU
60 s
t OR OR
All UL > UsealIn<
AND

VoltZeroSeq 5s
VoltNegSeq OR t

AllCurrLow
CBCLOSED

DISCPOS IEC10000033-2-en.vsd

IEC10000033 V2 EN-US

Figure 100: Simplified logic diagram for fuse failure supervision function, Main logic

198 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 8
Secondary system supervision

8.2.8 Technical data


M16069-1 v12

Table 133: FUFSPVCtechnical data


Function Range or value Accuracy
Operate voltage, zero sequence (1-100)% of UBase ±0.5% of Ur

Operate current, zero sequence (1–100)% of IBase ±0.5% of Ir

Operate voltage, negative sequence (1-100)% of UBase ±0.5% of Ur

Operate current, negative sequence (1–100)% of IBase ±0.5% of Ir

Operate voltage change level (1-100)% of UBase ±10.0% of Ur

Operate current change level (1–100)% of IBase ±10.0% of Ir

Operate phase voltage (1-100)% of UBase ±0.5% of Ur

Operate phase current (1–100)% of IBase ±0.5% of Ir

Operate phase dead line voltage (1-100)% of UBase ±0.5% of Ur

Operate phase dead line current (1–100)% of IBase ±0.5% of Ir

Operate time, start, 1 ph, at 1 x Ur to 0 Min. = 10 ms -


Max. = 25 ms
Reset time, start, 1 ph, at 0 to 1 x Ur Min. = 15 ms -
Max. = 30 ms

Breaker protection REQ650 199


Technical manual
© Copyright 2017 ABB. All rights reserved
200
1MRK 505 384-UEN C Section 9
Control

Section 9 Control
9.1 Synchrocheck, energizing check, and synchronizing
SESRSYN IP14558-1 v4

9.1.1 Identification
M14889-1 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Synchrocheck, energizing check, and SESRSYN 25
synchronizing
sc/vc

SYMBOL-M V1 EN-US

9.1.2 Functionality M12480-3 v16

The Synchronizing function allows closing of asynchronous networks at the correct moment
including the breaker closing time, which improves the network stability.

Synchrocheck, energizing check, and synchronizing (SESRSYN) function checks that the
voltages on both sides of the circuit breaker are in synchronism, or with at least one side dead
to ensure that closing can be done safely.

SESRSYN function includes a built-in voltage selection scheme for double bus and 1½ breaker
or ring busbar arrangements.

Manual closing as well as automatic reclosing can be checked by the function and can have
different settings.

For systems, which can run asynchronously, a synchronizing feature is also provided. The main
purpose of the synchronizing feature is to provide controlled closing of circuit breakers when
two asynchronous systems are in phase and can be connected. The synchronizing feature
evaluates voltage difference, phase angle difference, slip frequency and frequency rate of
change before issuing a controlled closing of the circuit breaker. Breaker closing time is a
setting.

Breaker protection REQ650 201


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

9.1.3 Function block M12431-3 v7

SESRSYN
U3PBB1* SYNOK
U3PBB2* AUTOSYOK
U3PLN1* AUTOENOK
U3PLN2* MANSYOK
BLOCK MANENOK
BLKSYNCH TSTSYNOK
BLKSC TSTAUTSY
BLKENERG TSTMANSY
B1QOPEN TSTENOK
B1QCLD USELFAIL
B2QOPEN B1SEL
B2QCLD B2SEL
LN1QOPEN LN1SEL
LN1QCLD LN2SEL
LN2QOPEN SYNPROGR
LN2QCLD SYNFAIL
UB1OK UOKSYN
UB1FF UDIFFSYN
UB2OK FRDIFSYN
UB2FF FRDIFFOK
ULN1OK FRDERIVA
ULN1FF UOKSC
ULN2OK UDIFFSC
ULN2FF FRDIFFA
STARTSYN PHDIFFA
TSTSYNCH FRDIFFM
TSTSC PHDIFFM
TSTENERG INADVCLS
AENMODE UDIFFME
MENMODE FRDIFFME
PHDIFFME
UBUS
ULINE
MODEAEN
MODEMEN

IEC10000046-1-en.vsd
IEC10000046 V1 EN-US

Figure 101: SESRSYN function block

9.1.4 Signals
PID-6724-INPUTSIGNALS v1

Table 134: SESRSYN Input signals


Name Type Default Description
U3PBB1 GROUP - Group signal for phase to earth voltage input L1, busbar 1
SIGNAL
U3PBB2 GROUP - Group signal for phase to earth voltage input L1, busbar 2
SIGNAL
U3PLN1 GROUP - Group signal for phase to earth voltage input L1, line 1
SIGNAL
U3PLN2 GROUP - Group signal for phase to earth voltage input L1, line 2
SIGNAL
BLOCK BOOLEAN 0 General block
BLKSYNCH BOOLEAN 0 Block synchronizing
BLKSC BOOLEAN 0 Block synchro check
BLKENERG BOOLEAN 0 Block energizing check
B1QOPEN BOOLEAN 0 Open status for CB or disconnector connected to bus1
B1QCLD BOOLEAN 0 Close status for CB or disconnector connected to bus1
B2QOPEN BOOLEAN 0 Open status for CB or disconnector connected to bus2
B2QCLD BOOLEAN 0 Close status for CB or disconnector connected to bus2
Table continues on next page

202 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

Name Type Default Description


LN1QOPEN BOOLEAN 0 Open status for CB or disconnector connected to line1
LN1QCLD BOOLEAN 0 Close status for CB or disconnector connected to line1
LN2QOPEN BOOLEAN 0 Open status for CB or disconnector connected to line2
LN2QCLD BOOLEAN 0 Close status for CB or disconnector connected to line2
UB1OK BOOLEAN 0 Bus1 voltage transformer OK
UB1FF BOOLEAN 0 Bus1 voltage transformer fuse failure
UB2OK BOOLEAN 0 Bus2 voltage transformer OK
UB2FF BOOLEAN 0 Bus2 voltage transformer fuse failure
ULN1OK BOOLEAN 0 Line1 voltage transformer OK
ULN1FF BOOLEAN 0 Line1 voltage transformer fuse failure
ULN2OK BOOLEAN 0 Line2 voltage transformer OK
ULN2FF BOOLEAN 0 Line2 voltage transformer fuse failure
STARTSYN BOOLEAN 0 Start synchronizing
TSTSYNCH BOOLEAN 0 Set synchronizing in test mode
TSTSC BOOLEAN 0 Set synchro check in test mode
TSTENERG BOOLEAN 0 Set energizing check in test mode
AENMODE INTEGER 0 Input for setting of automatic energizing mode
MENMODE INTEGER 0 Input for setting of manual energizing mode

PID-6724-OUTPUTSIGNALS v1

Table 135: SESRSYN Output signals


Name Type Description
SYNOK BOOLEAN Synchronizing OK output
AUTOSYOK BOOLEAN Auto synchro check OK
AUTOENOK BOOLEAN Automatic energizing check OK
MANSYOK BOOLEAN Manual synchro check OK
MANENOK BOOLEAN Manual energizing check OK
TSTSYNOK BOOLEAN Synchronizing OK test output
TSTAUTSY BOOLEAN Auto synchro check OK test output
TSTMANSY BOOLEAN Manual synchro check OK test output
TSTENOK BOOLEAN Energizing check OK test output
USELFAIL BOOLEAN Selected voltage transformer fuse failed
B1SEL BOOLEAN Bus1 selected
B2SEL BOOLEAN Bus2 selected
LN1SEL BOOLEAN Line1 selected
LN2SEL BOOLEAN Line2 selected
SYNPROGR BOOLEAN Synchronizing in progress
SYNFAIL BOOLEAN Synchronizing failed
UOKSYN BOOLEAN Voltage amplitudes for synchronizing above set limits
UDIFFSYN BOOLEAN Voltage difference out of limit for synchronizing
FRDIFSYN BOOLEAN Frequency difference out of limit for synchronizing
FRDIFFOK BOOLEAN Frequency difference in band for synchronizing
Table continues on next page

Breaker protection REQ650 203


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

Name Type Description


FRDERIVA BOOLEAN Frequency derivative out of limit for synchronizing
UOKSC BOOLEAN Voltage amplitudes above set limits
UDIFFSC BOOLEAN Voltage difference out of limit
FRDIFFA BOOLEAN Frequency difference out of limit for Auto operation
PHDIFFA BOOLEAN Phase angle difference out of limit for Auto operation
FRDIFFM BOOLEAN Frequency difference out of limit for Manual operation
PHDIFFM BOOLEAN Phase angle difference out of limit for Manual Operation
INADVCLS BOOLEAN Inadvertent circuit breaker closing
UDIFFME REAL Calculated difference of voltage in p.u of set voltage base
value
FRDIFFME REAL Calculated difference of frequency
PHDIFFME REAL Calculated difference of phase angle
UBUS REAL Bus voltage
ULINE REAL Line voltage
MODEAEN INTEGER Selected mode for automatic energizing
MODEMEN INTEGER Selected mode for manual energizing

9.1.5 Settings
PID-6724-SETTINGS v2

Table 136: SESRSYN Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
OperationSynch Off - - Off Operation for synchronizing function
On Off/On
UHighBusSynch 50.0 - 120.0 %UBB 1.0 80.0 Voltage high limit bus for
synchronizing in % of UBaseBus
UHighLineSynch 50.0 - 120.0 %UBL 1.0 80.0 Voltage high limit line for
synchronizing in % of UBaseLine
UDiffSynch 0.02 - 0.50 pu 0.01 0.10 Voltage difference limit for
synchronizing in p.u of set voltage
base value
FreqDiffMin 0.003 - 0.250 Hz 0.001 0.010 Minimum frequency difference limit
for synchronizing
FreqDiffMax 0.050 - 1.000 Hz 0.001 0.200 Maximum frequency difference limit
for synchronizing
CloseAngleMax 15.0 - 30.0 Deg 1.0 15.0 Maximum closing angle between bus
and line for synchronizing
FreqRateChange 0.000 - 0.500 Hz/s 0.001 0.300 Maximum allowed frequency rate of
change
tBreaker 0.000 - 1.000 s 0.001 0.080 Closing time of the breaker
tClosePulse 0.050 - 60.000 s 0.001 0.200 Breaker closing pulse duration
tMaxSynch 0.00 - 6000.00 s 0.01 600.00 Resets synch if no close has been
made before set time
tMinSynch 0.000 - 60.000 s 0.001 2.000 Minimum time to accept
synchronizing conditions
Table continues on next page

204 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

Name Values (Range) Unit Step Default Description


OperationSC Off - - On Operation for synchronism check
On function Off/On
UHighBusSC 50.0 - 120.0 %UBB 1.0 80.0 Voltage high limit bus for
synchrocheck in % of UBaseBus
UHighLineSC 50.0 - 120.0 %UBL 1.0 80.0 Voltage high limit line for
synchrocheck in % of UBaseLine
UDiffSC 0.02 - 0.50 pu 0.01 0.15 Voltage difference limit for
synchrocheck in p.u of set voltage
base value
FreqDiffA 0.003 - 1.000 Hz 0.001 0.010 Frequency difference limit between
bus and line Auto
FreqDiffM 0.003 - 1.000 Hz 0.001 0.010 Frequency difference limit between
bus and line Manual
PhaseDiffA 5.0 - 90.0 Deg 1.0 25.0 Phase angle difference limit between
bus and line Auto
PhaseDiffM 5.0 - 90.0 Deg 1.0 25.0 Phase angle difference limit between
bus and line Manual
tSCA 0.000 - 60.000 s 0.001 0.100 Time delay output for synchrocheck
Auto
tSCM 0.000 - 60.000 s 0.001 0.100 Time delay output for synchrocheck
Manual
AutoEnerg Off - - DLLB Automatic energizing check mode
DLLB
DBLL
Both
ManEnerg Off - - Both Manual energizing check mode
DLLB
DBLL
Both
ManEnergDBDL Off - - Off Manual dead bus, dead line energizing
On
UHighBusEnerg 50.0 - 120.0 %UBB 1.0 80.0 Voltage high limit bus for energizing
check in % of UBaseBus
UHighLineEnerg 50.0 - 120.0 %UBL 1.0 80.0 Voltage high limit line for energizing
check in % of UBaseLine
ULowBusEnerg 10.0 - 80.0 %UBB 1.0 40.0 Voltage low limit bus for energizing
check in % of UBaseBus
ULowLineEnerg 10.0 - 80.0 %UBL 1.0 40.0 Voltage low limit line for energizing
check in % of UBaseLine
UMaxEnerg 50.0 - 180.0 %UB 1.0 115.0 Maximum voltage for energizing in %
of UBase, Line and/or Bus
tAutoEnerg 0.000 - 60.000 s 0.001 0.100 Time delay for automatic energizing
check
tManEnerg 0.000 - 60.000 s 0.001 0.100 Time delay for manual energizing
check

Breaker protection REQ650 205


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

Table 137: SESRSYN Non group settings (basic)


Name Values (Range) Unit Step Default Description
SelPhaseBus1 Phase L1 - - Phase L1 Select phase for busbar1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
GblBaseSelBus 1 - 12 - 1 1 Selection of one of the Global Base
Value groups, Bus
GblBaseSelLine 1 - 12 - 1 1 Selection of one of the Global Base
Value groups, Line
SelPhaseBus2 Phase L1 - - Phase L1 Select phase for busbar2
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
SelPhaseLine1 Phase L1 - - Phase L1 Select phase for line1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
SelPhaseLine2 Phase L1 - - Phase L1 Select phase for line2
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
CBConfig No voltage sel. - - No voltage sel. Select CB configuration
Double bus
1 1/2 bus CB
1 1/2 bus alt. CB
Tie CB

Table 138: SESRSYN Non group settings (advanced)


Name Values (Range) Unit Step Default Description
PhaseShift -180 - 180 Deg 1 0 Additional phase angle for selected
line voltage

9.1.6 Monitored data


PID-6724-MONITOREDDATA v1

Table 139: SESRSYN Monitored data


Name Type Values (Range) Unit Description
UDIFFME REAL - - Calculated difference of voltage in p.u
of set voltage base value
FRDIFFME REAL - Hz Calculated difference of frequency
PHDIFFME REAL - deg Calculated difference of phase angle
UBUS REAL - kV Bus voltage
ULINE REAL - kV Line voltage

206 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

9.1.7 Operation principle

9.1.7.1 Basic functionality M14832-3 v8

The synchrocheck feature measures the conditions across the circuit breaker and compares
them to set limits. The output for closing operation is given when all measured quantities are
simultaneously within their set limits.

The energizing check feature measures the bus and line voltages and compares them to both
high and low threshold detectors. The output is given only when the actual measured
quantities match the set conditions.

The synchronizing feature measures the conditions across the circuit breaker, and also
determines the angle change occurring during the closing delay of the circuit breaker, from the
measured slip frequency. The output is given only when all measured conditions are
simultaneously within their set limits. The closing of the output is timed to give closure at the
optimal time including the time needed for the circuit breaker and the closing circuit
operation.

The voltage difference, frequency difference and phase angle difference values are measured
in the IED centrally and are available for the SESRSYN function for evaluation. By setting the
phases used for SESRSYN, with the settings SelPhaseBus1, SelPhaseBus2, SelPhaseLine1 and
SelPhaseLine2, a compensation is made automatically for the voltage amplitude difference
and the phase angle difference caused if different setting values are selected for both sides of
the breaker. If needed, an additional phase angle adjustment can be done for selected line
voltage with the PhaseShift setting.

For double bus single circuit breaker and 1½ circuit breaker arrangements, the SESRSYN
function blocks have the capability to make the necessary voltage selection. For double bus
single circuit breaker arrangements, selection of the correct voltage is made using auxiliary
contacts of the bus disconnectors. For 1½ circuit breaker arrangements, correct voltage
selection is made using auxiliary contacts of the bus disconnectors as well as the circuit
breakers.

The internal logic for each function block as well as, the input and outputs, and the setting
parameters with default setting and setting ranges is described in this document. For
application related information, please refer to the application manual.

9.1.7.2 Logic diagrams IP14739-1 v1

M14833-3 v5
The logic diagrams that follow illustrate the main principles of the SESRSYN function
components such as Synchrocheck, Synchronizing, Energizing check and Voltage selection,
and are intended to simplify the understanding of the function.

Synchrocheck M14834-3 v15


When the function is set to OperationSC = On, the measuring will start.

The function will compare the bus and line voltage values with the set values for UHighBusSC
and UHighLineSC.

If both sides are higher than the set values, the measured values are compared with the set
values for acceptable frequency, phase angle and voltage difference: FreqDiffA, FreqDiffM,
PhaseDiffA, PhaseDiffM and UDiffSC. If additional phase angle adjustment is done with the
PhaseShift setting, the adjustment factor is deducted from the line voltage before the
comparison of the phase angle values.

The frequency on both sides of the circuit breaker is also measured. The frequencies must not
deviate from the rated frequency more than ±5Hz. The frequency difference between the bus
frequency and the line frequency is measured and may not exceed the set value FreqDiff.

Breaker protection REQ650 207


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

Two sets of settings for frequency difference and phase angle difference are available and
used for the manual closing and autoreclose functions respectively, as required.

The inputs BLOCK and BLKSC are available for total block of the complete SESRSYN function
and selective block of the Synchrocheck function respectively. Input TSTSC will allow testing of
the function where the fulfilled conditions are connected to a separate test output.

The outputs MANSYOK and AUTOSYOK are activated when the actual measured conditions
match the set conditions for the respective output. The output signal can be delayed
independently for MANSYOK and AUTOSYOK conditions.

A number of outputs are available as information about fulfilled checking conditions. UOKSC
shows that the voltages are high, UDIFFSC, FRDIFFA, FRDIFFM, PHDIFFA, PHDIFFM shows
when the voltage difference, frequency difference and phase angle difference are out of limits.

Output INADVCLS, inadvertent circuit breaker closing, indicates that the circuit breaker has
been closed at wrong phase angle by mistake. The output is activated, if the voltage
conditions are fulfilled at the same time the phase angle difference between bus and line is
suddenly changed from being larger than 60 degrees to smaller than 5 degrees.

Note! Similar logic for Manual Synchrocheck.

OperationSC = On
AND TSTAUTSY
AND

invalidSelection AND
OR AUTOSYOK
AND
0-60 s
AND t
tSCA

UDiffSC 50 ms
AND t
UHighBusSC
UOKSC
AND
UHighLineSC
UDIFFSC
1

1
FRDIFFA
FreqDiffA

1
PHDIFFA
PhaseDiffA

UDIFFME
voltageDifferenceValue
FRDIFFME
frequencyDifferenceValue
PHDIFFME
phaseAngleDifferenceValue

32 ms 100 ms
AND t INADVCLS
PhDiff > 60° AND

PhDiff < 5°

IEC07000114-6-en.vsdx

IEC07000114 V6 EN-US

Figure 102: Simplified logic diagram for the auto synchrocheck function

Synchronizing SEMOD171603-4 v12


When the function is set to OperationSynch = On the measuring will be performed.

208 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

The function will compare the values for the bus and line voltage with the set values for
UHighBusSynch and UHighLineSynch, which is a supervision that the voltages are both live.
Also the voltage difference is checked to be smaller than the set value for UDiffSynch, which is
a p.u value of set voltage base values. If both sides are higher than the set values and the
voltage difference between bus and line is acceptable, the measured values are compared with
the set values for acceptable frequency FreqDiffMax and FreqDiffMin, rate of change of
frequency FreqRateChange and phase angle CloseAngleMax.

The measured frequencies between the settings for the maximum and minimum frequency will
initiate the measuring and the evaluation of the angle change to allow operation to be sent at
the right moment including the set tBreaker time. The calculation of the operation pulse sent
in advance is using the measured SlipFrequency and the set tBreaker time. To prevent
incorrect closing pulses, a maximum closing angle between bus and line is set with
CloseAngleMax. Table 140 below shows the maximum settable value for tBreaker when
CloseAngleMax is set to 15 or 30 degrees, at different allowed slip frequencies for
synchronizing. To minimize the moment stress when synchronizing near a power station, a
narrower limit for CloseAngleMax needs to be used.

Table 140: Dependencies between tBreaker and SlipFrequency with different CloseAngleMax values
tBreaker [s] (max settable value) tBreaker [s] (max settable value) SlipFrequency [Hz]
with CloseAngleMax = 15 degrees with CloseAngleMax = 30 degrees (BusFrequency - LineFrequency)
[default value] [max value]
0.040 0.080 1.000
0.050 0.100 0.800
0.080 0.160 0.500
0.200 0.400 0.200
0.400 0.810 0.100
1.000 0.080
0.800 0.050
1.000 0.040

At operation the SYNOK output will be activated with a pulse tClosePulse and the function
resets. The function will also reset if the synchronizing conditions are not fulfilled within the
set tMaxSynch time. This prevents that the function is, by mistake, maintained in operation for
a long time, waiting for conditions to be fulfilled.

The inputs BLOCK and BLKSYNCH are available for total block of the complete SESRSYN
function and block of the Synchronizing function respectively. TSTSYNCH will allow testing of
the function where the fulfilled conditions are connected to a separate output.

Breaker protection REQ650 209


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

OperationSynch=On

TSTSYNCH

STARTSYN

invalidSelection
SYNPROGR
AND
BLOCK AND
S
BLKSYNCH OR
R

UDiffSynch
50 ms SYNOK
AND
UHighBusSynch AND t

UHighLineSynch OR

FreqDiffMax TSTSYNOK
AND
FreqDiffMin

tClosePulse
FreqRateChange
AND

fBus&fLine ± 5Hz
tMaxSynch
CloseAngleMax AND
SYNFAIL

PhaseDiff=Close pulse in advance

FreqDiff
Close pulse
in advance
tBreaker

=IEC06000636=5=en=Original.vsd
IEC06000636 V5 EN-US

Figure 103: Simplified logic diagram for the synchronizing function

Energizing check M14835-3 v12


Voltage values are measured in the IED and are available for evaluation by the Energizing check
function.

The function measures voltages on the busbar and the line to verify whether they are live or
dead. This is done by comparing with the set values UHighBusEnerg and ULowBusEnerg for
bus energizing and UHighLineEnerg and ULowLineEnerg for line energizing.

The frequency on both sides of the circuit breaker is also measured. The frequencies must not
deviate from the rated frequency more than +/-5Hz.

The Energizing direction can be selected individually for the Manual and the Automatic
functions respectively. When the conditions are met the outputs AUTOENOK and MANENOK
respectively will be activated if the fuse supervision conditions are fulfilled. The output signal
can be delayed independently for MANENOK and AUTOENOK conditions. The Energizing
direction can also be selected by an integer input AENMODE respective MENMODE, which for
example, can be connected to a Binary to Integer function block (B16I). Integers supplied shall
be 1=Off, 2=DLLB, 3=DBLL and 4= Both. Not connected input will mean that the setting is done
from Parameter Setting tool. The active position can be read on outputs MODEAEN resp
MODEMEN. The modes are 0=OFF, 1=DLLB, 2=DBLL and 3=Both.

The inputs BLOCK and BLKENERG are available for total block of the complete SESRSYN
function respective block of the Energizing check function. TSTENERG will allow testing of the
function where the fulfilled conditions are connected to a separate test output.

210 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

manEnergOpenBays
MANENOK
OR

TSTENERG

BLKENERG
OR
BLOCK

selectedFuseOK

UHighBusEnerg
DLLB tManEnerg
AND
OR t
AND
OR
ULowLineEnerg AND

ManEnerg BOTH

ULowBusEnerg
DBLL
AND

UHighLineEnerg

TSTENOK
ManEnergDBDL AND AND

UMaxEnerg
fBus and fLine ±5 Hz

IEC14000031-1-en.vsd
IEC14000031 V1 EN-US

Figure 104: Manual energizing

TSTENERG

BLKENERG
OR
BLOCK

selectedFuseOK

UHighBusEnerg
DLLB 50ms tAutoEnerg
AND
OR t t
AND OR
AUTOENOK
ULowLineEnerg AND
BOTH
AutoEnerg
ULowBusEnerg
DBLL
AND

UHighLineEnerg

TSTENOK
UMaxEnerg AND

fBus and fLine ±5 Hz

IEC14000030-2-en.vsdx
IEC14000030 V2 EN-US

Figure 105: Automatic energizing

Breaker protection REQ650 211


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

BLKENERG
BLOCK OR manEnergOpenBays
AND

ManEnerg

1½ bus CB
CBConfig AND

B1QOPEN
LN1QOPEN AND
OR
B1QCLD
B2QOPEN
AND

LN2QOPEN

1½ bus alt. CB AND OR


AND
OR

B2QCLD
AND

Tie CB
AND
AND
OR

AND

IEC14000032-1-en.vsd
IEC14000032 V1 EN-US

Figure 106: Open bays

Fuse failure supervision M14837-3 v11


External fuse failure signals or signals from a tripped fuse switch/MCB are connected to binary
inputs that are configured to the inputs of SESRSYN function in the IED. Alternatively, the
internal signals from fuse failure supervision can be used when available. There are two
alternative connection possibilities. Inputs labelled OK must be connected if the available
contact indicates that the voltage circuit is healthy. Inputs labelled FF must be connected if
the available contact indicates that the voltage circuit is faulty.

The UB1OK/UB2OK and UB1FF/UB2FF inputs are related to the busbar voltage and the
ULN1OK/ULN2OK and ULN1FF/ULN2FF inputs are related to the line voltage. Configure them
to the binary input or function outputs that indicate the status of the external fuse failure of
the busbar and line voltages. In the event of a fuse failure, the energizing check function is
blocked. The synchronizing and the synchrocheck function requires full voltage on both sides,
thus no blocking at fuse failure is needed.

Voltage selection M14836-3 v9


The voltage selection module including supervision of included voltage transformers for the
different arrangements is a basic part of the SESRSYN function and determines the voltages
fed to the Synchronizing, Synchrocheck and Energizing check functions. This includes the
selection of the appropriate Line and Bus voltages and MCB supervision.

The voltage selection type to be used is set with the parameter CBConfig.

If No voltage sel. is set the voltages used will be U-Line1 and U-Bus1. This setting is also used in
the case when external voltage selection is provided. Fuse failure supervision for the used
inputs must also be connected.

The voltage selection function, selected voltages, and fuse conditions are used for the
Synchronizing, Synchrocheck and Energizing check inputs.

212 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

For the disconnector positions it is advisable to use (NO) a and (NC) b type contacts to supply
Disconnector Open and Closed positions but, it is also possible to use an inverter for one of
the positions.

If breaker or disconnector positions not are available for deciding if energizing is allowed, it is
considered to be allowed to manually energize. This is only allowed for manual energizing in
1½ breaker and Tie breaker arrangements. Manual energization of a completely open diameter
in 1 1/2 CB switchgear is allowed by internal logic.

Voltage selection for a single circuit breaker with double busbars M14838-3 v9
The setting CBConfig selected for Double Bus activates the voltage selection for single CB and
double busbars. This function uses the binary input from the disconnectors auxiliary contacts
B1QOPEN-B1QCLD for Bus 1, and B2QOPEN-B2QCLD for Bus 2 to select between bus 1 and bus
2 voltages. If the disconnector connected to bus 1 is closed and the disconnector connected to
bus 2 is opened the bus 1 voltage is used. All other combinations use the bus 2 voltage. The
outputs B1SEL and B2SEL respectively indicate the selected Bus voltage.

The function checks the fuse-failure signals for bus 1, bus 2 and line voltage transformers.
Inputs UB1OK-UB1FF supervise the MCB for Bus 1 and UB2OK-UB2FF supervises the MCB for
Bus 2. ULN1OK and ULN1FF supervises the MCB for the Line voltage transformer. The inputs
fail (FF) or healthy (OK) can alternatively be used dependent on the available signal. If a VT
failure is detected in the selected voltage source an output signal USELFAIL is set. This output
signal is true if the selected bus or line voltages have a VT failure. This output as well as the
function can be blocked with the input signal BLOCK. The function logic diagram is shown in
figure 107.

B1QOPEN
B1SEL
B1QCLD AND

B2QOPEN B2SEL
AND
1
B2QCLD
invalidSelection
AND

bus1Voltage busVoltage

bus2Voltage

UB1OK AND
UB1FF OR
OR selectedFuseOK
AND
UB2OK AND
UB2FF OR USELFAIL
AND

ULN1OK
ULN1FF OR

BLOCK

en05000779-2.vsd
IEC05000779 V2 EN-US

Figure 107: Logic diagram for the voltage selection function of a single circuit breaker with double
busbars

Breaker protection REQ650 213


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

Voltage selection for a 1 1/2 circuit breaker arrangement M14839-3 v8


Note that with 1½ breaker schemes three Synchrocheck functions must be used for the
complete diameter. Below, the scheme for one Bus breaker and the Tie breaker is described.

With the setting parameter CBConfig the selection of actual CB location in the 1 1/2 circuit
breaker switchgear is done. The settings are: 1 1/2 Bus CB, 1 1/2 alt. Bus CB or Tie CB.

This voltage selection function uses the binary inputs from the disconnectors and circuit
breakers auxiliary contacts to select the right voltage for the SESRSYN function. For the bus
circuit breaker one side of the circuit breaker is connected to the busbar and the other side is
connected either to line 1, line 2 or the other busbar depending on the best selection of voltage
circuit.

Inputs LN1QOPEN-LN1QCLD, B1QOPEN-B1QCLD, B2QOPEN-B2QCLD, LN2QOPEN-LN2QCLD are


inputs for the position of the Line disconnectors respectively the Bus and Tie breakers. The
outputs LN1SEL, LN2SEL and B2SEL will give indication of the selected Line voltage as a
reference to the fixed Bus 1 voltage, which indicates B1SEL.

The fuse supervision is connected to ULN1OK-ULN1FF, ULN2OK-ULN2FF and with alternative


Healthy or Failing fuse signals depending on what is available from each fuse (MCB).

The tie circuit breaker is connected either to bus 1 or line 1 voltage on one side and the other
side is connected either to bus 2 or line 2 voltage. Four different output combinations are
possible, bus to bus, bus to line, line to bus and line to line.

• The line 1 voltage is selected if the line 1 disconnector is closed.


• The bus 1 voltage is selected if the line 1 disconnector is open and the bus 1 circuit breaker
is closed.
• The line 2 voltage is selected if the line 2 disconnector is closed.
• The bus 2 voltage is selected if the line 2 disconnector is open and the bus 2 circuit breaker
is closed.

The function also checks the fuse-failure signals for bus 1, bus 2, line 1 and line 2. If a VT failure
is detected in the selected voltage an output signal USELFAIL is set. This output signal is true
if the selected bus or line voltages have a MCB trip. This output as well as the function can be
blocked with the input signal BLOCK. The function block diagram for the voltage selection of a
bus circuit breaker is shown in figure 108 and for the tie circuit breaker in figure 109.

214 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

LN1QOPEN
AND
LN1SEL
LN1QCLD

B1QOPEN
LN2SEL
B1QCLD AND AND
B2SEL
OR
LN2QOPEN
AND invalidSelection
LN2QCLD AND
AND
B2QOPEN
B2QCLD AND

line1Voltage lineVoltage

line2Voltage

bus2Voltage

UB1OK
UB1FF OR

OR selectedFuseOK
UB2OK AND
AND
UB2FF OR

USELFAIL
ULN1OK AND
AND
ULN1FF OR

ULN2OK
AND
ULN2FF OR

BLOCK

en05000780-2.vsd
IEC05000780 V2 EN-US

Figure 108: Simplified logic diagram for the voltage selection function for a bus circuit breaker in a 1 1/2
breaker arrangement

Breaker protection REQ650 215


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

LN1QOPEN
AND
LN1SEL
LN1QCLD
B1SEL
1

B1QOPEN AND
AND
B1QCLD AND

line1Voltage busVoltage

bus1Voltage
LN2QOPEN
LN2SEL
LN2QCLD AND
B2SEL
1
invalidSelection
OR
B2QOPEN AND
AND
B2QCLD AND

line2Voltage lineVoltage

bus2Voltage

UB1OK AND
UB1FF OR

OR selectedFuseOK
UB2OK AND
AND
UB2FF OR

USELFAIL
ULN1OK AND
AND
ULN1FF OR

ULN2OK
AND
ULN2FF OR

BLOCK

en05000781-2.vsd
IEC05000781 V2 EN-US

Figure 109: Simplified logic diagram for the voltage selection function for the tie circuit breaker in 1 1/2
breaker arrangement.

9.1.8 Technical data


M12359-1 v15

Table 141: SESRSYN technical data


Function Range or value Accuracy
Phase shift, jline - jbus (-180 to 180) degrees -

Voltage high limit for synchronizing and (50.0-120.0)% of UBase ±0.5% of Ur at U ≤ Ur


synchrocheck ±0.5% of U at U > Ur

Reset ratio, synchrocheck > 95% -


Frequency difference limit between bus (0.003-1.000) Hz ±2.5 mHz
and line for synchrocheck
Table continues on next page

216 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

Function Range or value Accuracy


Phase angle difference limit between bus (5.0-90.0) degrees ±2.0 degrees
and line for synchrocheck
Voltage difference limit between bus and (0.02-0.5) p.u ±0.5% of Ur
line for synchronizing and synchrocheck
Time delay output for synchrocheck when (0.000-60.000) s ±0.2% or ±35 ms whichever is
angle difference between bus and line greater
jumps from “PhaseDiff” + 2 degrees to
“PhaseDiff” - 2 degrees
Frequency difference minimum limit for (0.003-0.250) Hz ±2.5 mHz
synchronizing
Frequency difference maximum limit for (0.050-1.000) Hz ±2.5 mHz
synchronizing
Maximum allowed frequency rate of (0.000-0.500) Hz/s ±10.0 mHz/s
change
Maximum closing angle between bus and (15-30) degrees ±2.0 degrees
line for synchronizing
Breaker closing pulse duration (0.050-1.000) s ±0.2% or ±15 ms whichever is
greater
tMaxSynch, which resets synchronizing (0.000-6000.00) s ±0.2% or ±35 ms whichever is
function if no close has been made before greater
set time
Minimum time to accept synchronizing (0.000-60.000) s ±0.2% or ±35 ms whichever is
conditions greater
Voltage high limit for energizing check (50.0-120.0)% of UBase ±0.5% of Ur at U ≤ Ur
±0.5% of U at U > Ur

Reset ratio, voltage high limit > 95% -


Voltage low limit for energizing check (10.0-80.0)% of UBase ±0.5% of Ur

Reset ratio, voltage low limit < 105% -


Maximum voltage for energizing (50.0-180.0)% of UBase ±0.5% of Ur at U ≤ Ur
±0.5% of U at U > Ur

Time delay for energizing check when (0.000-60.000) s ±0.2% or ±100 ms whichever is
voltage jumps from 0 to 90% of Urated greater
Operate time for synchrocheck function Min. = 15 ms –
when angle difference between bus and Max. = 30 ms
line jumps from “PhaseDiff” + 2 degrees to
“PhaseDiff” - 2 degrees
Operate time for energizing function Min. = 70 ms –
when voltage jumps from 0 to 90% of Max. = 90 ms
Urated

9.2 Autorecloser for 1 phase, 2 phase and/or 3 phase


operation SMBRREC IP14559-1 v6

Breaker protection REQ650 217


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

9.2.1 Identification
M14890-1 v7

Function Description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Autorecloser for 1 phase, 2 phase and/or 3 SMBRREC 79
phase
5(0 -->1)
IEC15000204 V1 EN-US

9.2.2 Functionality M12390-3 v17

The auto recloser (SMBRREC) function provides:

• high-speed and/or delayed auto reclosing


• single and/or three phase auto reclosing
• support for single or multi-breaker applications.

The auto recloser can be used for delayed busbar restoration.

Up to five reclosing shots can be performed. The first shot can be single-, two-, and /or three-
phase depending on the type of the fault and the selected auto reclosing mode.

Several auto reclosing functions can be provided for multi-breaker arrangements. A priority
circuit allows one circuit breaker to reclose first and the second will only close if the fault
proved to be transient.

Each auto reclosing function can be configured to co-operate with the synchrocheck function.

9.2.3 Function block M12633-3 v6

SMBRREC
ON BLOCKED
OFF SETON
BLKON READY
BLKOFF ACTIVE
RESET SUCCL
INHIBIT UNSUCCL
START INPROGR
STARTHS 1PT1
TRSOTF 2PT1
SKIPHS 3PT1
ZONESTEP 3PT2
TR2P 3PT3
TR3P 3PT4
THOLHOLD 3PT5
CBREADY PERMIT1P
CBCLOSED PREP3P
PLCLOST CLOSECB
SYNC WFMASTER
WAIT COUNT1P
RSTCOUNT COUNT2P
MODEINT COUNT3P1
COUNT3P2
COUNT3P3
COUNT3P4
COUNT3P5
COUNTAR
MODE
ABORTED
SYNCFAIL
INHIBOUT
IEC06000189-3-en.vsd
IEC06000189 V3 EN-US

Figure 110: SMBRREC function block

218 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

9.2.4 Signals
PID-6796-INPUTSIGNALS v2

Table 142: SMBRREC Input signals


Name Type Default Description
ON BOOLEAN 0 Switch AR On (at ExternalCtrl = On)
OFF BOOLEAN 0 Switch AR Off (at ExternalCtrl = On)
BLKON BOOLEAN 0 Set AR in blocked state
BLKOFF BOOLEAN 0 Release AR from blocked state
RESET BOOLEAN 0 Reset AR to initial conditions
INHIBIT BOOLEAN 0 Interrupt and inhibit reclosing sequence
START BOOLEAN 0 Start reclosing sequence
STARTHS BOOLEAN 0 Start high-speed reclosing without synchrocheck
TRSOTF BOOLEAN 0 Continue to shots 2-5 at a trip from switch-on-to-fault
SKIPHS BOOLEAN 0 Skip high speed shot and continue with delayed shots
ZONESTEP BOOLEAN 0 Coordinate local AR with down stream devices
TR2P BOOLEAN 0 Two phase trip occurred
TR3P BOOLEAN 0 Three phase trip occurred
THOLHOLD BOOLEAN 0 Hold AR in wait state
CBREADY BOOLEAN 0 Circuit breaker is ready
CBCLOSED BOOLEAN 0 Circuit breaker status
PLCLOST BOOLEAN 0 Power line carrier or other form of permissive signal is lost
SYNC BOOLEAN 0 Synchrocheck conditions are fulfilled
WAIT BOOLEAN 0 Wait for master
RSTCOUNT BOOLEAN 0 Reset counters
MODEINT INTEGER 0 Integer input used to set reclosing mode (alternative to
setting)

PID-6796-OUTPUTSIGNALS v2

Table 143: SMBRREC Output signals


Name Type Description
BLOCKED BOOLEAN AR is blocked
SETON BOOLEAN AR is operative
READY BOOLEAN AR is ready for a new sequence
ACTIVE BOOLEAN Reclosing sequence in progress
SUCCL BOOLEAN Reclosing is successful
UNSUCCL BOOLEAN Reclosing is unsuccessful
INPROGR BOOLEAN Reclosing in progress, inactive during reclaim time
1PT1 BOOLEAN Single-phase reclosing is in progress for shot 1
2PT1 BOOLEAN Two-phase reclosing is in progress for shot 1
3PT1 BOOLEAN Three-phase reclosing is in progress for shot 1
3PT2 BOOLEAN Three-phase reclosing is in progress for shot 2
3PT3 BOOLEAN Three-phase reclosing is in progress for shot 3
3PT4 BOOLEAN Three-phase reclosing is in progress for shot 4
Table continues on next page

Breaker protection REQ650 219


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

Name Type Description


3PT5 BOOLEAN Three-phase reclosing is in progress for shot 5
PERMIT1P BOOLEAN Single-phase trip is permitted
PREP3P BOOLEAN Three-phase trip is prepared
CLOSECB BOOLEAN Close command for circuit breaker
WFMASTER BOOLEAN Wait signal to slave issued by master for sequential reclosing
COUNT1P INTEGER Number of single-phase reclosing shots
COUNT2P INTEGER Number of two-phase reclosing shots
COUNT3P1 INTEGER Number of three-phase shot 1 reclosings
COUNT3P2 INTEGER Number of three-phase shot 2 reclosings
COUNT3P3 INTEGER Number of three-phase shot 3 reclosings
COUNT3P4 INTEGER Number of three-phase shot 4 reclosings
COUNT3P5 INTEGER Number of three-phase shot 5 reclosings
COUNTAR INTEGER Number of total reclosing shots
MODE INTEGER Integer output for reclosing mode
ABORTED BOOLEAN General abort
SYNCFAIL BOOLEAN AR sequence is aborted by synchrocheck conditions not
fulfilled
INHIBOUT BOOLEAN AR sequence is aborted via INHIBIT input

9.2.5 Settings
PID-6796-SETTINGS v2

Table 144: SMBRREC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
ExternalCtrl Off - - Off To be set On if AR is to be used with
On external control
ARMode 3 phase - - 1/2/3ph AR mode selection
1/2/3ph
1/2ph
1ph+1*2ph
1/2ph+1*3ph
1ph+1*2/3ph
t1 1Ph 0.000 - 120.000 s 0.001 1.000 Dead time for shot 1, single-phase
reclosing
t1 3Ph 0.000 - 120.000 s 0.001 6.000 Dead time for shot 1, delayed three-
phase reclosing with synchrocheck
conditions
t1 3PhHS 0.000 - 120.000 s 0.001 0.400 Dead time for shot 1, high speed
three-phase reclosing
tReclaim 0.00 - 6000.00 s 0.01 60.00 Reclaim time
tSync 0.00 - 6000.00 s 0.01 30.00 Maximum wait time for fulfilled
synchrocheck conditions
tLongStartInh 0.000 - 60.000 s 0.001 0.200 Maximum allowed start pulse duration
tPulse 0.000 - 60.000 s 0.001 0.200 Circuit breaker closing pulse duration
Table continues on next page

220 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

Name Values (Range) Unit Step Default Description


tCBClosedMin 0.00 - 6000.00 s 0.01 5.00 Minimum time that circuit breaker
must be closed before new sequence
is allowed
tUnsucCl 0.00 - 6000.00 s 0.01 30.00 Maximun wait time for circuit breaker
closing before indicating unsuccessful
Priority None - - None Priority selection between adjacent
Low terminals
High
tWaitForMaster 0.00 - 6000.00 s 0.01 60.00 Maximum wait time for release from
master
LongStartInhib Off - - On To be set ON if AR is to be used with
On maximum allowed start pulse
duration check

Table 145: SMBRREC Group settings (advanced)


Name Values (Range) Unit Step Default Description
NoOfShots 1 - - 1 Max number of reclosing shots
2
3
4
5
StartByCBOpen Off - - Off To be set ON if AR is to be started by
On circuit breaker open position
CBReadyType CO - - CO Circuit breaker ready signal type
OCO
t1 2Ph 0.000 - 120.000 s 0.001 1.000 Dead time for shot 1, two-phase
reclosing
t2 3Ph 0.00 - 6000.00 s 0.01 30.00 Dead time for shot 2, three-phase
reclosing
t3 3Ph 0.00 - 6000.00 s 0.01 30.00 Dead time for shot 3, three-phase
reclosing
t4 3Ph 0.00 - 6000.00 s 0.01 30.00 Dead time for shot 4, three-phase
reclosing
t5 3Ph 0.00 - 6000.00 s 0.01 30.00 Dead time for shot 5, three-phase
reclosing
Extended t1 Off - - Off Extend dead time at loss of
On permissive channel
tExtended t1 0.000 - 60.000 s 0.001 0.500 Extend three-phase dead time
duration
tInhibit 0.000 - 60.000 s 0.001 5.000 Reset time for reclosing inhibit
CutPulse Off - - Off Shorten circuit breaker closing pulse
On at a new start
Follow CB Off - - Off Advance to next shot if circuit breaker
On has been closed during dead time
AutoContinue Off - - Off Continue with next reclosing shot if
On circuit breaker did not close
tAutoContWait 0.000 - 60.000 s 0.001 2.000 Wait time after close command before
proceeding to next shot
UnsucClByCBChk NoCBCheck - - NoCBCheck Unsuccessful closing signal obtained
CB check by checking circuit breaker position
BlockByUnsucCl Off - - Off Block AR at unsuccessful reclosing
On
Table continues on next page

Breaker protection REQ650 221


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

Name Values (Range) Unit Step Default Description


ZoneSeqCoord Off - - Off Coordination of down stream devices
On to local protection unit’s AR
tSuccessful 0.000 - 60.000 s 0.001 1.000 Delay time before indicating
successful reclosing
tSlaveDeadTime 0.100 - 60.000 s 0.001 0.400 Wait time for the slave to close when
WAIT input has reset

9.2.6 Operation principle

9.2.6.1 Terminology explanation GUID-EA0760DF-8F0B-4146-8A42-3F20E75E1053 v1

Before describing the auto reclosing function it is first necessary to define the following
terminology:

• a shot is an attempt from the function to close a circuit breaker


• multi-shot is where more than one shot is attempted
• dead time is the time between a start of the function and the attempt to close the circuit
breaker
• reclaim time is the time from the circuit breaker closing command till the reset of the
function, should the auto reclosing attempt be successful and no new start is received
• high-speed shot is generally used for an application where the dead time is less than 1
second and synchrocheck is not required
• delayed auto reclosing is generally regarded as an application where the dead time is
greater than 1 second and where typically synchrocheck is required
• sequence is the auto reclosing cycle beginning with start and ending with successful,
unsuccessful or aborted reclosing as a result
• status is the state which the auto reclosing function have reached in the sequence

9.2.6.2 Status descriptions GUID-AFC069D6-ADA5-4D97-9699-8C9F058458EB v1

The auto reclosing function can be in one of the following five statuses:

“Inactive” GUID-BF80C969-FCBE-4CAB-BF71-9590A2DB433C v1
The auto recloser is in “inactive” status when the following conditions are fulfilled:

• the auto recloser is set to On and


• either the circuit breaker is not closed
• or the circuit breaker is not ready

The function will not react on any start from protection trips while in “inactive” status and
no automatic reclosing is possible.

“Ready” GUID-04F154EC-E236-40A4-A3E0-7624A2F6B132 v1
The function is in “ready” status when the following conditions are fulfilled:

• the circuit breaker is ready


• the circuit breaker must have been closed for more that the set time in setting:
tCBClosedMin
• the function is not in “blocked” status
• the function is not in “in progress” status

Only in “ready” status a start of the auto reclosing sequence is possible.

222 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

“In progress” GUID-24F8890F-A8FA-4A6F-B9E8-08BDB17B9A0D v1


The function is in “in progress” status when the following condition is fulfilled:

• the auto reclosing sequence is started

Start can be initiated by either protection trip command or circuit breaker position change.
The second starting alternative is only possible when enabled by a setting.

In “in progress” status the dead time starts and the status ceases when the dead time expires.
Then circuit breaker close command is given and the function changes its state into the
"reclaim time" status.

“Reclaim time” GUID-D838C380-C74B-498C-82D6-3364E2F6BA22 v1


The auto recloser is in “reclaim time” status while the following conditions are fulfilled:

• the reclaim time has not yet expired


• the status is not interrupted by either a new start signal or a block signal

A new start signal during “reclaim time” status forces the function to proceed to next shot and
change state into “in progress” status, as long as the last shot is not reached.

“Blocked” GUID-9C38B1BE-3772-49AE-B4B3-391CE15D5CD2 v1
The function is in “blocked” status when an external blocking signal exists. No auto reclosing is
possible in “blocked” status. Only an external signal for cancellation of the blocking can cancel
this status.

9.2.6.3 Description of the status transition GUID-C12DF571-AC0D-4A04-9B9E-D53E15A24331 v1

From Table 146 below it is possible to see which status transitions are possible. When the auto
recloser is for instance in “inactive” status only two transition are possible:

• transition to “ready” status when the circuit breaker is ready and closed
• transition to “blocked” status by external blocking

The empty cells in the table indicate that no such transition is possible.

Breaker protection REQ650 223


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

Table 146: Status transition matrix


To → inactive ready in progress reclaim time blocked
From ↓ (dead time)
inactive activate activate BLKON
CBCLOSED and
CBREADY
ready deactivate activate START activate BLKON
CBCLOSED or or activate
CBREADY or STARTHS
activate INHIBIT
or RESET
in progress activate INHIBIT when activate BLKON
(dead time) or RESET CBCLOSED
issued
reclaim time activate RESET activate START activate BLKON
or INHIBIT and the last
shot has not
been reached
yet
blocked deactivate activate
CBCLOSED or BLKOFF and
CBREADY and CBCLOSED and
activate CBREADY
BLKOFF

9.2.6.4 Functional sequence description GUID-C73A160D-330B-4627-B8F0-A31C9B3F7417 v1

To comprehend this chapter better it is essential to first read chapters “Status


descriptions“ and “Description of the status transition” carefully.

The logic for most of the explained inputs, outputs, settings and internal signals, described in
this chapter, is shown in Figure 116. Other figures mentioned are in some way connected or
cooperate with Figure 116.

Before going into details in the following chapters, the short functional/feature summary is
given below.

The auto reclosing function is multi-shot capable and suitable for both high-speed and
delayed auto reclosing. The function can be set to perform a single-shot, two-shot, three-shot,
four-shot or five-shot reclosing sequence. Dead times for all shots can be set independently.

An auto recloser sequence can be initiated by:

• protection operation
• circuit breaker operation (when enabled by setting StartByCBOpen=On)

At the end of the dead time, provided that other conditions are fulfilled, a circuit breaker close
command signal is given. The other conditions to be fulfilled are:

• input signal SYNC is true, which typically indicates that power systems on the two sides of
the circuit breaker are in synchronism
• and that input signal CBREADY is true, typically indicating that circuit breaker springs are
charged.

If a circuit breaker close command is given successfully at the end of the dead time, a reclaim
time starts. If the circuit breaker does not trip again within reclaim time, the auto recloser
indicates a successful reclosing and resets into "ready" status. If the protection trips again
during the reclaim time, the sequence advances to the next shot. If all reclosing attempts have

224 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

been made and the circuit breaker does not remain closed, the auto recloser indicates an
unsuccessful reclosing. Each time a breaker close command is given, a shot counter is
incremented by one.

Operation Off and On GUID-D868C9CF-CDB1-48AA-8B31-60C447FBD1D3 v1


The auto recloser can be switched Off or On with a setting or by external control inputs. With
the setting Operation = On, the auto recloser is activated and with the setting Operation = Off
it is deactivated. With the settings Operation = On and ExternalCtrl = On, the activation and
deactivation is made by signal pulses to the ON and OFF inputs, for example, from a control
system or by a control switch.

If the input conditions CBCLOSED and CBREADY, from the circuit breaker, are not fulfilled
while switching the auto recloser on, the auto recloser changes into “inactive” status and the
output SETON is activated (high). The auto recloser is not ready for auto reclosing. If, however,
the circuit breaker is closed and ready when switching the auto recloser on, the output READY
is activated and the function is prepared to start the auto reclosing cycle. The circuit breaker
must have been closed for at least the set value for setting tCBClosedMin before a start is
accepted. The logic for Off or On operation is shown in Figure 111.

Operation
AND OR S SETON
ExternalCtrl

R
ON AND

OR
OFF AND

StartByCBOpen
START AND

STARTHS AND
100ms OR
AND OR initiate
100ms
AND
TRSOTF
startThermal AND
CBReady
120ms
CBREADY OR S
t AND start
AND
AND
tCBClosedMin R
CBCLOSED
t

cbClosed AND
count0 AND READY
inhibit
OR
INHIBIT

IEC16000153-1-en.vsdx
IEC16000153 V1 EN-US

Figure 111: Simplified logic for Operation Off/On and starting

Mode selection GUID-25A24DC8-80C8-4C42-A084-D25712049F06 v1


The auto reclosing mode is selected with the setting ARMode. As an alternative to the setting,
the mode can be selected by connecting an integer, for example from function block B16I, to
the MODEINT input. The six possible modes are described in Table 147 below with their
corresponding MODEINT integer value.

Breaker protection REQ650 225


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

When a valid integer is connected to the input MODEINT the selected setting ARMode will be
invalid and the MODEINT input value will be used instead. The selected mode is reported as an
integer on the MODE output.

Please note that tripping mode of the IED is defined in Trip Logic function block SMPPTRC. For
example for two-phase faults either 2ph or 3ph tripping and consequent auto reclosing can be
selected

Table 147: Type of reclosing shots at different settings of “ARMode” or integer inputs to "MODEINT"
MODEINT (Integer) ARMode Type of fault 1st shot 2nd - 5th shot
1ph 3ph 3ph
1 3ph 2ph 3ph 3ph
3ph 3ph 3ph
1ph 1ph 3ph
2 1/2/3ph 2ph 2ph 3ph
3ph 3ph 3ph
1ph 1ph 3ph
3 1/2ph 2ph 2ph 3ph
3ph - -
1ph 1ph 3ph
4 1ph+1x2ph 2ph 2ph -
3ph - -
1ph 1ph 3ph
5 1/2ph+1x3ph 2ph 2ph 3ph
3ph 3ph –
1ph 1ph 3ph
6 1ph+1x2/3ph 2ph 2ph -
3ph 3ph -

Auto reclosing shots GUID-817797BE-FAFC-4BC7-B288-F19416459DCE v1


A maximum of five auto reclosing shots can be selected with the setting NoOfShots. Every
shot has its own dead time setting.

The first shot differs from the other shots by the possibility to extend its dead time and to
utilize up to four different time settings for it.

For the first shot, there are separate settings for single-, two- and three-phase dead times, t1
1Ph, t1 2Ph and t1 3Ph. If only the START input signal is applied, and an auto-reclosing program
with single-phase reclosing is selected, the auto reclosing dead time t1 1Ph will be used. If one
of the TR2P or TR3P inputs is activated in in parallel with the START input, the auto reclosing
dead time for either two-phase or three-phase auto reclosing is used.

There is also a separate time setting facility for three-phase high-speed auto reclosing, t1
3PhHS. This high-speed auto reclosing is activated by the STARTHS input and is used when
auto reclosing is done without the requirement of synchrocheck conditions to be fulfilled. The
high-speed dead time shall be set shorter than normal first shot three-phase dead time. Note
that if high-speed three-phase shot is not successful the auto reclosing sequence will continue
with shot two.

A time extension delay, tExtended t1, can be added to the dead time delay for the first shot. It
is intended to come into use if the communication channel for permissive line protection is
lost. In a case like this there can be a significant time difference in fault clearance at the two

226 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

line ends, where a longer auto reclosing dead time can be useful. This time extension is
controlled by the setting Extended t1 and the PLCLOST input. The logic for control of extended
dead time is shown in Figure112 and Figure 116. Time extension delay is not possible to add to
the three-phase high-speed auto reclosing dead time, t1 3PhHS.

Extended t1

AND extendTime
PLCLOST
OR
initiate AND
AND
start

IEC16000155-1-en.vsdx
IEC16000155 V1 EN-US

Figure 112: Control of extended dead time


Shots 2 to 5 are all three-phase shots and have only one corresponding time setting each, t2
3Ph, t3 3Ph, t4 3Ph and t5 3Ph.

Starting auto reclosing GUID-7794EA6E-7D73-46BD-A623-65DED8E45D05 v1


When a start is applied to the auto function, it status will change from “ready” status to “in
progress” status. When the dead time has expired, the close command is issued and the
reclaim time is started and the “in progress” status will change to “reclaim time” status.

The usual way to start a reclosing sequence, is to start it when a selective line protection
tripping has occurred, by applying a signal to the START input. If the auto reclosing mode with
only three-phase reclosing is selected, activation of the START input will start the three-phase
dead timer. When alternatively the START input signal is applied, and an auto reclosing mode
with single-phase reclosing is selected, the auto reclosing dead time for single-phase is used.
However if one of the TR2P or TR3P inputs is activated in connection with the START input, the
auto reclosing dead time for two-phase or three-phase auto reclosing is used. The STARTHS
input (start high-speed reclosing) can also be used to start a separate, high-speed three-phase
dead time in which case the synchrocheck condition will be bypassed.

To start a new auto reclosing cycle, a number of conditions of input signals need to be fulfilled.
The inputs are:

• CBREADY: circuit breaker is ready for a reclosing cycle, for example, charged operating
gear.
• CBCLOSED: to ensure that the circuit breaker was closed when the line fault occurred and
start was applied. The CBCLOSED condition must be present for more that the settable
time tCBClosedMin.
• no BLKON or INHIBIT signal is present.

When the start has been accepted, the internal signals “start” and “initiate” are set. The
internal signal “start” is latched and the internal signal “initiate” follows the length of the
signal on the START input. The latched signal “start” can be interrupted by a signal to the
INHIBIT input.

The simplified logic is shown in Figure 111.

The auto recloser is normally started by selective tripping. It is either a zone 1 or


communication aided trip, or a general trip. If the general trip is used the auto recloser must
be blocked, via the INHIBIT input, from all back-up tripping. The breaker failure function must
always be connected to inhibit the auto recloser. START makes a first shot with synchrocheck
conditions to be fulfilled, STARTHS makes its first shot without any fulfilled synchrocheck
conditions. The TRSOTF “trip by switch onto fault” input starts shots 2 to 5. It may be
connected to the “switch onto fault” output of line protection if multi-shot auto reclosing is
used.

Breaker protection REQ650 227


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

In normal circumstances, the auto recloser is started with a protection trip command which
resets quickly due to fault clearing. In case the start signal lasts for a too long time, the user
can set a maximum start pulse duration tLongStartInh. This start pulse duration time is
controlled by setting LongStartInhib. When the start pulse duration signal is longer than the
set maximum start pulse duration, the auto reclosing sequence will be interrupted in the same
way as if the INHIBIT input was set to true. The logic for the control of long start pulse
duration is shown in Figure 113.

LongStartInhib

start
AND
tLongStartInh
initiate
t
longStartInhibit
OR

Extended t1 AND

t13PhExtTimeout

IEC16000154-1-en.vsdx
IEC16000154 V1 EN-US

Figure 113: Control of long start pulse duration


If the user wants to start the auto recloser from circuit breaker open position instead of the
protection trip signals, this starting mode is selected by enabling a setting StartByCBOpen.
Typically, a circuit breaker auxiliary contact of type normally open (NO) shall be connected to
the CBCLOSED and START inputs. Then the circuit breaker status change from closed to open
will generate an auto reclosing start pulse of limited length (100ms) subject to the usual auto
recloser checks. The auto reclosing sequence continues then as usual. Signals from manual
tripping and other functions, which shall prevent auto reclosing, need to be connected to the
INHIBIT input. The logic for start from circuit breaker open position is shown in Figure 111.

The function can also be set to proceed to the next reclosing shot (if selected) even if the
external start signal is not received but the breaker is still not closed. The user can set a
required time delay for the auto recloser to proceed without a new start with setting
tAutoContWait. Also the synchrocheck conditions not fulfilled will also make the auto recloser
to proceed to next shot. This automatic proceeding of shots is controlled by setting
AutoContinue and is shown in figure 114.

tAutoContWait
t
AND
commandCloseCB
AND S
R
OR
AND
OR
cbClosed AND autoInitiate
synchroCheckOK

AutoContinue

IEC16000156-1-en.vsdx
IEC16000156 V1 EN-US

Figure 114: Automatic proceeding of shots

Blocking, resetting and inhibiting auto reclosing GUID-82719FE0-02E4-48FB-9685-2146480F3653 v1


The BLKON input is used to block the auto recloser for example, when certain special service
conditions arise. The auto recloser can also be blocked by an unsuccessful reclosing attempt.

228 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

This is controlled by the setting BlockByUnsucCl. When the auto recloser is blocked it
immediately resets to its initial conditions and the ACTIVE output is unactivated. The
BLOCKED output indicates that the auto recloser is blocked. To unblock the auto recloser the
BLKOFF input must be activated.

The RESET input is used to reset the auto recloser to its initial conditions. When initial starting
conditions are fulfilled again, after a reset, the auto recloser is ready for a new reclosing
sequence.

If the INHIBIT input is activated it is reported on the INHIBOUT output. To ensure reliable
interruption and temporary blocking of the auto recloser a reset time delay tInhibit is used.
The auto recloser will be blocked the time set in tInhibit after the deactivation of the INHIBIT
input. The following internal inhibit signals are also affected by the setting tInhibit:

• inhibitWaitForMaster: after expiration of the tWaitForMaster time for the WAIT input to
reset, the reclosing cycle of the slave is inhibited.
• longStartInhibit: if start pulse duration is longer than the tLongStartInh time, the
reclosing cycle is inhibited.

The ABORTED output indicates that the auto recloser is inhibited while it was in one of
following internal states:

• inProgress: auto recloser is started and dead time is in progress.


• reclaimTimeStarted: the circuit breaker closing command has started the reclaim timer.
• wait: an auto recloser, acting as slave, is waiting for a release from the master to proceed
with its own reclosing sequence.

The SYNCFAIL output indicates that the auto recloser is inhibited because the synchrocheck or
energizing check condition has not been fulfilled within the set time interval, tSync. The
ABORTED output will also be activated.

The behavior of the functionality described above is described in Table 148 and Table 149
below.

Table 148: BLKON, BLKOFF, RESET, INHIBIT and SYNC behavior when the function is in "ready" status

Output → READY ACTIVE BLOCKED INHIBOUT ABORTED SYNCFAIL


Input ↓
None of below True False False False False False
inputs
activated
BLKON pulse False False True False False False
BLKOFF pulse True False False False False False
RESET pulse False False False False False False
INHIBIT pulse False False False True False False
SYNC True False False False False False

Table 149: BLKON, BLKOFF, RESET, INHIBIT and SYNC behavior when the function is in "in progress" status

Output → READY ACTIVE BLOCKED INHIBOUT ABORTED SYNCFAIL


Input ↓
None of below False True False False False False
inputs
activated
BLKON pulse False False True False False False
Table continues on next page

Breaker protection REQ650 229


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

BLKOFF pulse True False False False False False


RESET pulse False False False False False False
INHIBIT pulse False False False True True False
No SYNC False False False False True True

Auto reclosing sequence GUID-78AAE7CD-702E-407B-94D2-6A70BAFC8E70 v1


When the function has started and the dead time has elapsed during the auto reclosing
sequence, certain conditions must be fulfilled before the circuit breaker closing command is
issued. In three-phase reclosing, a synchrocheck and/or energizing check can be used. It is
possible to use a synchrocheck function in the same physical device or an external one. The
synchrocheck release signal shall be connected to the auto reclosing SYNC input. If reclosing
without synchrocheck is preferred the SYNC input can be set to TRUE (set high) permanently.
The synchrocheck release signal is not checked for single-phase or two-phase auto reclosing.
When a three-phase high-speed reclosing started by STARTHS input, synchronization is not
checked either, and the state of the SYNC input is disregarded. The SYNC input shall be true
within a set time interval, tSync. If it is not, the auto reclosing is interrupted and the SYNCFAIL
and ABORTED outputs are activated.

By choosing CBReadyType = CO (circuit breaker ready for a Close-Open sequence) the


readiness of the circuit breaker is also checked before issuing the circuit breaker closing
command. If the circuit breaker has a readiness contact of type CBReadyType = OCO (circuit
breaker ready for an Open-Close-Open sequence) this condition may not be fulfilled during the
dead time and at the moment of auto reclosure. The Open-Close-Open condition was however
checked at the start of the auto reclosing cycle and it is then likely that the circuit breaker is
prepared for a Close-Open sequence.

The reclaim timer, tReclaim, is started each time a circuit breaker closing command is given. If
no start occurs within this time, the auto recloser will reset. A new start received in “reclaim
time” status will move the auto recloser to “in progress” status and next shot as long as the
final shot is not reached. The auto recloser will reset and enter “inactive” status if a new start
is given during the final reclaim time. This will also happen if the circuit breaker has not been
closed within set time interval tUnsucCl after each circuit breaker close command. The latter
case is controlled by setting UnsucClByCBChk. The auto reclosing sequence is considered
unsuccessful for both above cases and the UNSUCCL output is activated.

If the circuit breaker closing command is given and the circuit breaker is closed within the set
time interval tUnsucCl, the SUCCL output is activated after the set time interval tSuccessful.
The logic for successful and unsuccessful reclosing indication is shown in Figure 115.

230 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

initiate
reclaimTimeStarted AND

OR
AND UNSUCCL
OR tUnsucCl S
AND t unsuccessful
cbClosed
AND
UnsucClByCBChk
count0
OR R

tUnsucCl tSuccessful
AND SUCCL
commandCloseCB t AND S t

R
OR

IEC16000157-1-en.vsdx
IEC16000157 V1 EN-US

Figure 115: Successful/Unsuccessful


Figure 116 shows the logic for most parts of an auto reclosing sequence. Figure 116 should be
read together with the other logic diagrams to get the whole picture.

Breaker protection REQ650 231


Technical manual
© Copyright 2017 ABB. All rights reserved
ZoneSeqCoord

232
ZONESTEP AND
Control

MODEINT MODE
Section 9

start ARMode
initiate inProgress

IEC16000158 V1 EN-US
TR2P and INPROGR
TR3P NoOfShots 1PT1
startThermal OR 2PT1
selection 3PT1
Dead time
reclaimTimeStarted 3PT2
tExtended t1 tExtended t1 is 3PT3
extendTime added to t1 1Ph inhibitThermalStart 3PT4
t
or t1 2ph or t1 3Ph 3PT5
SKIPHS Skips high-speed shot (t1 3PhHS) and PREP3P
continues with delayed shot (t1 3Ph) AND tReclaim PERMIT1P
AND t 1
t1 1Ph OR
t1 2Ph OR
Dead t1 3PhHS AND
t13PhExtTimeout
time inhibit
t1 3PH OR OR
settings t2 3PH synchroCheckOK
t3 3PH OR BlockByUnsucCl
t4 3PH AND
t5 3PH unsuccessful AND ACTIVE
1
t OR OR
AND S

Figure 116: Auto reclosing sequence


tSlaveDeadTime AND
slaveDeadTime sets every dead timer R
t BLOCKED

sequence. The outputs are:


to tSlaveDeadTime

tSync
SYNC AND t SYNCFAIL
inProgress AND
reclaimTimeStarted OR
CBReadyType wait AND ABORTED
CB OR
AND
readiness
AND inhibitWaitForMaster tInhibit
CBReady check t
OR
longStartInhibit count0
OR Counter COUNT1P
inhibitThermalStart COUNT2P
CutPulse inProgress COUNT3P1
AND Set COUNT3P2
OR COUNT3P3
OR COUNT3P4
AND
AND COUNT3P5
Reset COUNTAR

© Copyright 2017 ABB. All rights reserved


tPulse
Follow CB CLOSECB
OR
AND AND
cbClosed
50ms commandCloseCB

RSTCOUNT
RESET

BLKON
BLKOFF
INHIBIT INHIBOUT

IEC16000158-1-en.vsdx

A number of outputs from the function keeps track of the actual state in the auto reclosing

Technical manual
Breaker protection REQ650
1MRK 505 384-UEN C
1MRK 505 384-UEN C Section 9
Control

• INPROGR: any dead time is in progress


• 1PT1, 2PT1, 3PT1, 3PT2, 3PT3, 3PT4 and 3PT5: dead time is in progress for respective shot
and fault type
• ACTIVE: during dead time + reclaim time
• COUNTAR: total number of auto reclosing shots
• COUNT1P, COUNT2P, COUNT3P1, COUNT3P2, COUNT3P3, COUNT3P4 and COUNT3P5:
number of circuit breaker close commands made for respective shot
• STATUS: reports, only through the IEC 61850 protocol, the actual status of the function.

The possible statuses are described in Table 150 below. Their mapping to output signals and
their corresponding IEC 61850 integer value is also given in the table. Mapping from
IEC 61850 Ed2 standard is also shown for the AutoRecSt data object.

Table 150: Auto reclosing status reported by IEC 61850 in priority order
Data object AutoRecSt Description for mapped Mapped output signals / Description in IEC61850
value signals Comments Ed2
1 Ready READY Ready
2 In Progress INPROGR In Progress
3 Successful SUCCL Successful
4 Waiting for trip
5 Trip issued by protection
6 Fault disappeared
7 Wait to complete CLOSECB Wait to complete
8 Circuit breaker closed
9 Cycle unsuccessful UNSUCCL
10
-1 Aborted by synchrocheck SYNCFAIL
fail
11 Aborted ABORTED Aborted
-2 Set On, Not Ready SETON = 1, READY = 0,
ACTIVE = 0, SUCCL = 0,
UNSUCC = 0, INPROG = 0
-3 Set Off, Not Ready SETON = 0
-99 Others Means that auto recloser
is in transitional state,
that should not be visible
in steady state situation

There are several counters within the function. One for each shot and type of fault and one
overall counter for total number of circuit breaker closing commands. All counters can be reset
to zero using either the HMI command or the RSTCOUNT input or by an IEC 61850 command.

The circuit breaker closing command, CLOSECB output is a pulse with settable duration by
setting tPulse. For circuit breakers without anti-pumping function, close pulse cutting can be
used. This is controlled by the setting CutPulse. In case of a new auto recloser start pulse, the
breaker closing command pulse is cut (interrupted). The minimum duration of the closing
pulse is always 50ms.

The prepare three-phase trip, PREP3P output is usually connected to the trip function
SMPPTRC to force the coming trip to be three-phase. If the auto recloser cannot make a single-
phase or two-phase reclosing, the start from the trip function should be three-phase.

Breaker protection REQ650 233


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

The permit single-phase trip, PERMIT1P output is the inverse of the PREP3P output. It can be
connected to a binary output relay for connection to external protection or trip relays. In case
of a total loss of auxiliary power, the output relay drops and does not allow single-phase trip.

The setting Follow CB can be used to prevent close command to be issued when dead time has
expired and circuit breaker is already closed (e.g. by manual close command). If a new start is
received after the dead time expiration the auto recloser will advance to next shot.

If input SKIPHS is activated, and simultaneously STARTHS input is initiated then actually
normal three-phase shot one with dead time "t1 3Ph" will be started.

The ZONESTEP input is used when coordination between local auto reclosers and down
stream auto reclosers is needed. If function is in "ready" status and this input is activated the
auto recloser increases its actual shot number by one and enters directly the “reclaim time”
status for shot one. If a start is received during the reclaim time, the function will proceed with
the next shot (e.g. starting dead time for shot two). Every new pulse on the ZONESTEP input
will further increase the shot number. Note that ZONESTEP input will have such effect only if
local start signal was not activated, as shown in Figure 116. The setting NoOfShots limits of
course the maximum number of available shots. This functionality is controlled by the setting
ZoneSeqCoord.

By activating the THOLHOLD input the auto recloser is set on hold. It can be connected to a
thermal overload protection trip signal which resets only when the thermal content has fallen
to an acceptable level, for example, 70%. As long as the signal is high, indicating that the line is
hot, the auto reclosing is halted. When the signal resets, a reclosing cycle will continue. This
may cause a considerable delay between start of the auto recloser and the breaker closing
command. An external logic limiting this time and activating the INHIBIT input can be used.
The THOLHOLD input can also be used to set the auto recloser on hold, for longer or shorter
time periods, for other purposes if for some reason the auto recloser needs to be halted. The
logic for thermal protection hold is shown in Figure 117.

start inhibitThermalStart
THOLHOLD AND AND S

q-1 20ms
startThermal
AND

inhibit OR

IEC16000159-1-en.vsdx
IEC16000159 V1 EN-US

Figure 117: Thermal protection hold


The auto recloser is set as master or slave in multi-breaker arrangements with sequential
reclosing with the setting Priority. The auto recloser for the first circuit breaker, e.g. near the
busbar, is set as master (when Priority=High) and the auto recloser for the second circuit
breaker is set as slave (when Priority=Low). While the master is in progress, it issues the
WFMASTER output. After an unsuccessful reclosing the WFMASTER output is also maintained
by the UNSUCCL output.

When activating the WAIT input, in the auto recloser set as slave, every dead timer is changed
to the value of setting tSlaveDeadTime and holds back the auto reclosing operation. When the
WAIT input is reset at the time of a successful reclosing of the first circuit breaker, the slave is
released to continue the reclosing sequence after the set tSlaveDeadTime. The reason for
shortening the time, for the normal dead timers with the value of tSlaveDeadTime, is to give
the slave permission to react almost immediately when the WAIT input resets. The mimimum
settable time for tSlaveDeadTime is 0.1sec because both master and slave should not send the
breaker closing command at the same time. The slave should take the duration of the breaker
closing time of the master into consideration before sending the breaker closing command. A
setting tWaitForMaster sets a maximum wait time for the WAIT input to reset. If the wait time

234 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

expires, the reclosing cycle of the slave is inhibited. The maximum wait time, tWaitForMaster
for the second circuit breaker is set longer than the auto reclosing dead time plus a margin for
synchrocheck conditions to be fulfilled for the first circuit breaker. Typical setting is 2sec. In
single circuit breaker applications, the setting Priority is set to None. The logic for master-
slave is shown in Figure 118.

Master:
High (Master)
Priority
WFMASTER
inProgress AND

unsuccessful OR

Slave:
Low (Slave)
Priority
inhibitWaitForMaster
AND
start tWaitForMaster
AND t
WAIT
wait

AND slaveDeadTime
AND S
inhibit
commandCloseCB R
OR
reclaimTimeStarted

IEC16000160-1-en.vsdx
IEC16000160 V1 EN-US

Figure 118: Master-Slave


If reclosing of the first circuit breaker is unsuccessful, the UNSUCCL output connected to the
INHIBIT input of the slave unit interrupts the reclosing sequence of the latter. The signals can
be cross-connected to allow simple changing of the priority by just setting the High and the
Low priorities without changing the configuration. The CBCLOSED inputs from each circuit
breaker are important in multi-breaker arrangements to ensure that the circuit breaker was
closed at the beginning of the sequence. If the High priority breaker was not closed its auto
reclosing sequence will not start and the low priority breaker will just continue its auto
reclosing sequence in accordance with its normal settings.

9.2.6.5 Time sequence diagrams M12458-10 v5

Some examples of the timing of internal and external signals at typical transient and
permanent faults are shown below in Figure 119 to 122.

Breaker protection REQ650 235


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

Fault
CBCLOSED
Closed Open Closed
CBREADY

START
SYNC
tReclaim
READY

INPROGR

1PT1

ACTIVE

CLOSECB t1 1Ph tPulse

PREP3P

SUCCL

Time

IEC04000196-4-en.vsd

IEC04000196 V4 EN-US

Figure 119: Transient single-phase fault, single-phase reclosing

Fault
CBCLOSED Open
Closed Open C C
CBREADY

START

TR3P
SYNC

READY

INPROGR

3PT1 t1 3Ph

3PT2 t2 3Ph

ACTIVE tReclaim

CLOSECB tPulse tPulse

PREP3P

UNSUCCL
Time

IEC04000197-3-en.vsd

IEC04000197 V3 EN-US

Figure 120: Permanent fault, three-phase trip, two-shot reclosing

236 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

Fault
CBCLOSED
CBREADY

START

TR3P

SYNC

READY

INPROGR

1PT1

3PT1

3PT2
CLOSECB t1 1Ph

PREP3P

UNSUCCL tReclaim
IEC04000198-3-en.vsd
IEC04000198 V3 EN-US

Figure 121: Permanent single-phase fault, single-phase trip, single-shot reclosing,


ARMode=1/2/3ph

Fault
CBCLOSED
CBREADY

START

TR3P

SYNC

READY

INPROGR

1PT1

3PT1

3PT2
t2 3Ph
CLOSECB t1 1Ph

PREP3P

UNSUCCL tReclaim

IEC04000199-3-en.vsd
IEC04000199 V3 EN-US

Figure 122: Permanent single-phase fault, single-phase trip, two-shot reclosing,


ARMode=1ph + 1*2ph

Breaker protection REQ650 237


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

9.2.7 Technical data


M12379-1 v13

Table 151: SMBRREC technical data


Function Range or value Accuracy
Dead time:
shot 1 “t1 1Ph” (0.000-120.000) s ±0.2% or ±35 ms
shot 1 “t1 2Ph” whichever is greater
shot 1 “t1 3Ph “
shot 1 “t1 3PhHS”
Dead time: (0.00-6000.00) s ±0.2% or ±35 ms
shot 2 “t2 3Ph” whichever is greater
shot 3 “t3 3Ph”
shot 4 “t4 3Ph”
shot 5 “t5 3Ph”
Extend three-phase dead time duration “tExtended t1” (0.000-60.000) s ±0.2% or ±35 ms
whichever is greater
Minimum time that circuit breaker must be closed before (0.00-6000.00) s ±0.2% or ±35 ms
new sequence is allowed “tCBClosedMin” whichever is greater
Wait time for the slave to close when WAIT input has (0.100-60.000) s ±0.2% or ±35 ms
reset “tSlaveDeadTime” whichever is greater
Maximum allowed start pulse duration “tLongStartInh” (0.000-60.000) s ±0.2% or ±15 ms
whichever is greater
Circuit breaker closing pulse duration “tPulse” (0.000-60.000) s ±0.2% or ±15 ms
whichever is greater
Reclaim time ”tReclaim” (0.00-6000.00) s ±0.2% or ±15 ms
whichever is greater
Maximum wait time for release from master (0.00-6000.00) s ±0.2% or ±15 ms
“tWaitForMaster” whichever is greater
Reset time for reclosing inhibit “tInhibit” (0.000-60.000) s ±0.2% or ±45 ms
whichever is greater
Wait time after close command before proceeding to (0.000-60.000) s ±0.2% or ±45 ms
next shot “tAutoContWait” whichever is greater
Maximum wait time for fulfilled synchrocheck conditions (0.00-6000.00) s ±0.2% or ±45 ms
“tSync” whichever is greater
Delay time before indicating successful reclosing (0.000-60.000) s ±0.2% or ±50 ms
“tSuccessful” whichever is greater
Maximum wait time for circuit breaker closing before (0.00-6000.00) s ±0.2% or ±45 ms
indicating unsuccessful “tUnsucCl” whichever is greater

9.3 Interlocking IP15572-1 v2

9.3.1 Logical node for interlocking SCILO IP14138-1 v2

9.3.1.1 Identification
GUID-3EC5D7F1-FDA0-4F0E-9391-08D357689E0C v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Logical node for interlocking SCILO - 3

238 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

9.3.1.2 Functionality M15048-3 v6

The Logical node for interlocking SCILO function is used to enable a switching operation if the
interlocking conditions permit. SCILO function itself does not provide any interlocking
functionality. The interlocking conditions are generated in separate function blocks containing
the interlocking logic.

9.3.1.3 Function block M15049-3 v6

SCILO
POSOPEN EN_OPEN
POSCLOSE EN_CLOSE
OPEN_EN
CLOSE_EN

IEC05000359-2-en.vsd
IEC05000359 V2 EN-US

Figure 123: SCILO function block

9.3.1.4 Signals
PID-3487-INPUTSIGNALS v7

Table 152: SCILO Input signals


Name Type Default Description
POSOPEN BOOLEAN 0 Open position of switch device
POSCLOSE BOOLEAN 0 Closed position of switch device
OPEN_EN BOOLEAN 0 Open operation from interlocking logic is enabled
CLOSE_EN BOOLEAN 0 Close operation from interlocking logic is enabled

PID-3487-OUTPUTSIGNALS v7

Table 153: SCILO Output signals


Name Type Description
EN_OPEN BOOLEAN Open operation at closed or interm. or bad pos. is enabled
EN_CLOSE BOOLEAN Close operation at open or interm. or bad pos. is enabled

9.3.1.5 Logic diagram M15086-3 v6

The function contains logic to enable the open and close commands respectively if the
interlocking conditions are fulfilled. That means also, if the switch has a defined end position
for example, open, then the appropriate enable signal (in this case EN_OPEN) is false. The
enable signals EN_OPEN and EN_CLOSE can be true at the same time only in the intermediate
and bad position state and if they are enabled by the interlocking function. The position inputs
come from the logical nodes Circuit breaker/Circuit switch (SXCBR/SXSWI) and the enable
signals come from the interlocking logic. The outputs are connected to the logical node Switch
controller (SCSWI). One instance per switching device is needed.

Breaker protection REQ650 239


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

POSOPEN SCILO
POSCLOSE =1 1
EN_OPEN
&
>1
&

OPEN_EN
CLOSE_EN & EN_CLOSE
>1
&
en04000525.vsd

IEC04000525 V1 EN-US

Figure 124: SCILO function logic diagram

9.4 Apparatus control IP14560-1 v3

9.4.1 Functionality M13444-3 v15

The apparatus control functions are used for control and supervision of circuit breakers,
disconnectors and earthing switches within a bay. Permission to operate is given after
evaluation of conditions from other functions such as interlocking, synchrocheck, operator
place selection and external or internal blockings.

The complete apparatus control function is not included in this product, and
the information below is included for understanding of the principle for the use
of QCBAY, LOCREM, LOCREMCTRL, SCILO, SCSWI, SXSWI, SXCBR, XLNPROXY.

The apparatus control function APC10 for up to 10 apparatuses is used for control and
supervision of circuit breakers, disconnectors and earthing switches within a bay. Permission
to operate is given after evaluation of conditions from other functions such as interlocking,
synchrocheck, operator place selection and external or internal blockings.

Apparatus control features:

• Select-Execute principle to give high reliability


• Selection function to prevent simultaneous operation
• Selection and supervision of operator place
• Command supervision
• Block/deblock of operation
• Block/deblock of updating of position indications
• Substitution of position and quality indications
• Overriding of interlocking functions
• Overriding of synchrocheck
• Operation counter
• Suppression of mid position

Two types of command models can be used:

• Direct with normal security


• SBO (Select-Before-Operate) with enhanced security

In normal security, the command is processed and the resulting position is not supervised.
However with enhanced security, the command is processed and the resulting position is
supervised.

240 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

Normal security means that only the command is evaluated and the resulting position is not
supervised. Enhanced security means that the command is evaluated with an additional
supervision of the status value of the control object. The command sequence with enhanced
security is always terminated by a CommandTermination service primitive and an AddCause
telling if the command was successful or if something went wrong.

Control operation can be performed from the local HMI with authority control if so defined.

The switch controller SCSWI initializes and supervises all functions to properly select and
operate switching primary apparatuses. Each of the 10 switch controllers SCSWI may handle
and operate on one three-phase apparatus.

Each of the 3 circuit breaker controllers SXCBR provides the actual position status and pass
the commands to the primary circuit breaker and supervises the switching operation and
positions.

Each of the 9 circuit switch controllers SXSWI provides the actual position status and pass the
commands to the primary disconnectors and earthing switches and supervises the switching
operation and positions.

9.4.2 Operation principle M13423-4 v9

A bay can handle, for example a power line, a transformer, a reactor, or a capacitor bank. The
different primary apparatuses within the bay can be controlled via the apparatus control
functions directly by the operator or indirectly by automatic sequences.

Because a primary apparatus can be allocated to many functions within a Substation


Automation system, the object-oriented approach with a function block that handles the
interaction and status of each process object ensures consistency in the process information
used by higher-level control functions.

Primary apparatuses such as breakers and disconnectors are controlled and supervised by one
function block (SCSWI) each. Because the number and type of signals used for the control of a
breaker or a disconnector are almost the same, the same function block type is used to handle
these two types of apparatuses.

The SCSWI function block is connected either to an SXCBR function block (for circuit breakers)
or to an SXSWI function block (for disconnectors and earthing switches). The physical process
in the switchyard is connected to these two function blocks via binary inputs and outputs.

Four types of function blocks are available to cover most of the control and supervision within
the bay. These function blocks are interconnected to form a control function reflecting the
switchyard configuration. The total number used depends on the switchyard configuration.
These types are:

• Bay control QCBAY


• Switch controller SCSWI
• Circuit breaker SXCBR
• Circuit switch SXSWI

The functions Local Remote (LOCREM) and Local Remote Control (LOCREMCTRL), to handle
the local/remote switch, also belong to the apparatus control function.

The principles of operation, function blocks, input and output signals and setting parameters
for all these functions are described below.

Breaker protection REQ650 241


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

9.4.3 Error handling GUID-6C31D291-74E8-46A3-8FC2-D3959C2458A5 v7

Depending on the error that occurs during the command sequence the error signal will be set
with a value. Table 154 describes the cause values given on local HMI. The translation to
AddCause values specified in IEC 61850-8-1 is shown in Table 155. For IEC 61850-8-1 edition 2
only addcauses defined in the standard are used, for edition 1 also a number of vendor specific
causes are used. The values are available in the command response to commands from IE
C61850-8-1 clients. An output L_CAUSE on the function block for Switch controller (SCSWI),
Circuit breaker (SXCBR) and Circuit switch (SXSWI) indicates the value of the cause during the
latest command if the function specific command evaluation has been started. The causes
that are not always reflected on the output L_CAUSE, with description of the typical reason are
listed in table 156.

Table 154: Values for "cause" signal


Cause Name Description Supported
number
0 None Control action successfully executed X
1 Not-supported Given for Cancel request with Direct Control in Ready state X
2 Blocked-by-switching- Not successful since one of the downstream Loc switches X
hierarchy like in CSWI has the value TRUE
3 Select-failed Cancelled due to an unsuccessful selection (select service) X
4 Invalid-position Control action is aborted due to invalid switch position (Pos X
in XCBR or XSWI)
5 Position-reached Switch is already in the intended position (Pos in XCBR or X
XSWI)
6 Parameter-change-in- Control action is blocked due to running parameter change X
execution
7 Step-limit Control action is blocked, because tap changer has reached X
the limit (EndPosR or EndPosL in YLTC)
8 Blocked-by-Mode Control action is blocked, because the LN (CSWI or XCBR/ X
XSWI) is in a mode (Mod) which doesn’t allow any switching
9 Blocked-by-process Control action is blocked due to some external event at X
process level that prevents a successful operation, for
example blocking indication (EEHealth in XCBR or XSWI)
10 Blocked-by- Control action is blocked due to interlocking of switching X
interlocking devices (in CILO attribute EnaOpn.stVal=”FALSE” or
EnaCls.stVal=”FALSE”
11 Blocked-by- Control action with synchrocheck is aborted due to exceed X
synchrocheck of time limit and missing synchronism condition
12 Command-already-in- Control, select or cancel service is rejected, because control X
execution action is already running
13 Blocked-by-health Control action is blocked due to some internal event that X
prevents a successful operation (Health)
14 1-of-n-control Control action is blocked because another control action in X
a domain (for example, substation) is already running (in
any XCBR or XSWI of that domain, the DPC.stSeld=”TRUE”)
15 Abortion-by-cancel Control action is aborted due to cancel service X
16 Time-limit-over Control action is terminated due to exceed of some time X
limit
17 Abortion-by-trip Control action is aborted due to a trip (PTRC with X
ACT.general=”TRUE”)
18 Object-not-selected Control action is rejected, because control object was not X
selected
Table continues on next page

242 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

Cause Name Description Supported


number
19 Object-already- Select action is not executed because the addressed object X
selected is already selected
20 No-access-authority Control action is blocked due to lack of access authority X
21 Ended-with- Control action executed but the end position has overshoot
overshoot
22 Abortion-due-to- Control action is aborted due to deviation between the
deviation command value and the measured value
23 Abortion-by- Control action is aborted due to the loss of connection with
communication-loss the client that issued the control
24 Blocked-by-command Control action is blocked due to the data attribute X
CmdBlk.stVal is TRUE
26 Inconsistent- The parameters between successive control services are X
parameters not consistent, for example the ctlNum of Select and
Operate service are different
27 Locked-by-other- Another client has already reserved the object X
client
-22 Wrong-Ctl-model Command from client uses wrong control model X
-23 Blocked-by-command Blocked by command X
-24 Blocked-for-open- Blocked for Open command X
cmd
-25 Blocked-for-close- Blocked for Close Command X
cmd
-30 Long-operation-time Operation time too long X
-31 Switch-not-start- Switch did not start moving X
moving
-32 Persistent- Switch stopped in intermediate state X
intermediate-state
-33 Switch-returned-to- Switch returned to the initial position X
init-pos
-34 Switch-in-bad-state Switch is in a bad position state X
-35 Not-expected-final- Switch did not reach the expected final position X
position

Table 155: Translation of cause values for IEC 61850 edition 2 and edition 1
Internal Cause AddCause in IEC 61850-8-1 Name
Number
Ed 2 Ed 1
0 25 0 None
1 1 1 Not-supported
2 2 2 Blocked-by-switching-hierarchy
3 3 3 Select-failed
4 4 4 Invalid-position
5 5 5 Position-reached
6 6 6 Parameter-change-in-execution
7 7 7 Step-limit
8 8 8 Blocked-by-Mode
9 9 9 Blocked-by-process
Table continues on next page

Breaker protection REQ650 243


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

Internal Cause AddCause in IEC 61850-8-1 Name


Number
Ed 2 Ed 1
10 10 10 Blocked-by-interlocking
11 11 11 Blocked-by-synchrocheck
12 12 12 Command-already-in-execution
13 13 13 Blocked-by-health
14 14 14 1-of-n-control
15 15 1 Abortion-by-cancel
16 16 16 Time-limit-over
17 17 17 Abortion-by-trip
18 18 18 Object-not-selected
19 19 3 Object-already-selected
20 20 3 No-access-authority
24 24 -23 Blocked-by-command
26 26 6 Inconsistent-parameters
27 27 12 Locked-by-other-client
-22 0 -22 Wrong-Ctl-model
-23 24 -23 Blocked-by-command
-24 9 -24 Blocked-for-open-cmd
-25 9 -25 Blocked-for-close-cmd
-30 16 -30 Long-operation-time
-31 16 -31 Switch-not-start-moving
-32 4 -32 Persistent-intermediate-state
-33 22 -33 Switch-returned-to-init-pos
-34 4 -34 Switch-in-bad-state
-35 22 -35 Not-expected-final-position

Table 156: Cause values not reflected on the output L_CAUSE


Cause number Cause description Conditions
3 Select-failed Canceled due to an unsuccessful selection
(select service)
8 Blocked-by-Mode Control action is blocked because the LN
(CSWI) is in a mode (Mod) which doesn’t allow
any switching or does not match the mode of
the command.
12 Command-already-in-execution Control, select or cancel service is rejected
because control action is already running.
13 Blocked-by-health Control action is blocked due to some internal
event that prevents a successful operation
(Health).
16 Time-limit-over Control action is terminated due to exceed of
some time limit.
18 Object-not-selected Control action is rejected because control
object was not selected.
19 Object-already-selected Select action is not executed because the
addressed object is already selected.
Table continues on next page

244 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

Cause number Cause description Conditions


20 No-access-authority Control action is blocked due to lack of access
authority.
26 Inconsistent-parameters The parameters between successive control
services are not consistent, for example the
ctlNum of Select and Operate service are
different.
27 Locked-by-other-client Another client has already reserved the object.

9.4.4 Bay control QCBAY IP15597-1 v2

9.4.4.1 Functionality M13447-3 v8

The Bay control (QCBAY) function is used together with Local remote and local remote control
functions to handle the selection of the operator place per bay. QCBAY also provides blocking
functions that can be distributed to different apparatuses within the bay.

9.4.4.2 Function block M13469-3 v4

QCBAY
LR_OFF PSTO
LR_LOC UPD_BLKD
LR_REM CMD_BLKD
LR_VALID LOC
BL_UPD STA
BL_CMD REM
IEC10000048-3-en.vsdx
IEC10000048 V3 EN-US

Figure 125: QCBAY function block

9.4.4.3 Signals
PID-4086-INPUTSIGNALS v8

Table 157: QCBAY Input signals


Name Type Default Description
LR_OFF BOOLEAN 0 External Local/Remote switch is in Off position
LR_LOC BOOLEAN 0 External Local/Remote switch is in Local position
LR_REM BOOLEAN 0 External Local/Remote switch is in Remote position
LR_VALID BOOLEAN 0 Data representing the L/R switch position is valid
BL_UPD BOOLEAN 0 Steady signal to block the position updates
BL_CMD BOOLEAN 0 Steady signal to block the command

PID-4086-OUTPUTSIGNALS v8

Table 158: QCBAY Output signals


Name Type Description
PSTO INTEGER Value for the operator place allocation
UPD_BLKD BOOLEAN Update of position is blocked
CMD_BLKD BOOLEAN Function is blocked for commands
Table continues on next page

Breaker protection REQ650 245


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

Name Type Description


LOC BOOLEAN Local operation allowed
STA BOOLEAN Station operation allowed
REM BOOLEAN Remote operation allowed

9.4.4.4 Settings
PID-4086-SETTINGS v8

Table 159: QCBAY Non group settings (basic)


Name Values (Range) Unit Step Default Description
AllPSTOValid Priority - - Priority Override Priority of originators,
No priority commands from both local, station
and remote are allowed
RemoteIncStation No - - No Both Station and Remote control are
Yes allowed but not Local when local
remote switch is in remote

9.4.4.5 Operation principle


M13446-4 v8
The function sends information about the Permitted Source To Operate (PSTO) and blocking
conditions to other functions within the bay for example, switch control functions and voltage
control functions. The functionality of the Bay control (QCBAY) function is mainly described by
the LLN0 node in the IEC 61850-8-1 edition 2 standard, applied to one bay. In IEC 61850 edition
1 the functionality is not described by the LLN0 node or any other node, therefore the Bay
control function is represented as a vendor specific node in edition 1.

Local panel switch M13446-7 v8


The local panel switch is a switch that defines the operator place selection. The switch
connected to this function can have three positions (remote/local/off). The positions are here
defined so that remote means that operation is allowed from station and/or remote level and
local means that operation is allowed from the IED level. The local/remote switch is also on the
control/protection IED itself, which means that the position of the switch and its validity
information are connected internally, not via I/O boards. When the switch is mounted
separately from the IED the signals are connected to the function via I/O boards.

When the local panel switch (or LHMI selection, depending on the set source to select this) is in
Off position, all commands from remote and local level will be ignored. If the position for the
local/remote switch is not valid the PSTO output will always be set to faulty state (3), which
means no possibility to operate.

To adapt the signals from the local HMI or from an external local/remote switch, the function
blocks LOCREM and LOCREMCTRL are needed and connected to QCBAY.

Permitted Source To Operate (PSTO) M13446-16 v10


The actual state of the operator place is presented by the value of the Permitted Source To
Operate, PSTO signal. The PSTO value is evaluated from the local/remote switch position
according to Table 160. In addition, there are two settings and one command that affect the
value of the PSTO signal.

If the setting AllPSTOValid is set to No Priority and the LR-switch position is in Local or Remote
state, the PSTO output is set to 5 (all), that is, it is permitted to operate from local, station and
remote level without any priority. When the external panel switch is in Off position, the PSTO
output shows the actual state of the switch that is, 0. In this case, it is not possible to control
anything. The LocSta command value is forced to FALSE if AllPSTOValid is set to No priority.

246 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

If the setting RemoteIncStation is set to Yes and the LR-switch position is in Remote state, the
PSTO output is set to 2 (Station or Remote), that is, it is permitted to operate from both
station and remote level without any priority.

If the LR-switch position is in Remote state, and AllPSTOValid is set to Priority and
RemoteIncStation is set to No, the switching between station and remote level control is done
through the command LocSta. The command is accessible only through the IEC 61850 Edition
2 protocol.

Table 160: PSTO values for different Local panel switch positions
Local panel AllPSTOValid RemoteInc LocSta.CtlV PSTO LED Possible
switch (setting) Station al value indications on locations that
positions (setting) (command) LHMI shall be able
to operate
0 = Off - - - 0 Remote and Not possible
Local Off to operate
1 = Local Priority - - 1 Remote Off, Local Panel
Local On
1 = Local No priority - - 5 Remote and Local,
Local On Station or
Remote level
without any
priority
2 = Remote Priority No TRUE 6 Remote On, Station level
Local Off
2 = Remote Priority No FALSE 7 Remote On, Remote level
Local Off
2 = Remote Priority Yes - 2 Remote On, Station or
Local Off Remote level
2 = Remote No priority - - 5 Remote and Local,
Local On Station or
Remote level
without any
priority
3 = Faulty - - - 3 Remote and Not possible
Local to operate
Flashing

Blockings M13446-50 v6
The blocking states for position indications and commands are intended to provide the
possibility for the user to make common blockings for the functions configured within a
complete bay.

The blocking facilities provided by the bay control function are the following:

• Blocking of position indications, BL_UPD. This input will block all inputs related to
apparatus positions for all configured functions within the bay.
• Blocking of commands, BL_CMD. This input will block all commands for all configured
functions within the bay.

The switching of the Local/Remote switch requires at least system operator level. The
password will be requested at an attempt to operate if authority levels have been defined in
the IED, otherwise the default authority level can handle the control without LogOn. The users
and passwords are defined with the IED Users tool in PCM600.

Breaker protection REQ650 247


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

9.4.5 Local/Remote switch LOCREM IP16319-1 v3

M17086-3 v11
The signals from the local HMI or from an external local/remote switch are connected via the
function blocks local remote (LOCREM) and local remote control (LOCREMCTRL) to the Bay
control (QCBAY) function block. The parameter ControlMode in function block LOCREM is set
to choose if the switch signals are coming from the local HMI or from an external hardware
switch connected via binary inputs.

9.4.5.1 Function block M17088-3 v4

LOCREM
CTRLOFF OFF
LOCCTRL LOCAL
REMCTRL REMOTE
LHMICTRL VALID
IEC05000360-3-en.vsdx
IEC05000360 V3 EN-US

Figure 126: LOCREM function block

LOCREMCTRL
^PSTO1 HMICTR1
^PSTO2 HMICTR2
^PSTO3 HMICTR3
^PSTO4 HMICTR4
^PSTO5 HMICTR5
^PSTO6 HMICTR6
^PSTO7 HMICTR7
^PSTO8 HMICTR8
^PSTO9 HMICTR9
^PSTO10 HMICTR10
^PSTO11 HMICTR11
^PSTO12 HMICTR12
IEC05000361-3-en.vsdx
IEC05000361 V3 EN-US

Figure 127: LOCREMCTRL function block

9.4.5.2 Signals
PID-3944-INPUTSIGNALS v7

Table 161: LOCREM Input signals


Name Type Default Description
CTRLOFF BOOLEAN 0 Disable control
LOCCTRL BOOLEAN 0 Local in control
REMCTRL BOOLEAN 0 Remote in control
LHMICTRL INTEGER 0 LHMI control

PID-3944-OUTPUTSIGNALS v7

Table 162: LOCREM Output signals


Name Type Description
OFF BOOLEAN Control is disabled
LOCAL BOOLEAN Local control is activated
REMOTE BOOLEAN Remote control is activated
VALID BOOLEAN Outputs are valid

248 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

PID-3943-INPUTSIGNALS v6

Table 163: LOCREMCTRL Input signals


Name Type Default Description
PSTO1 INTEGER 0 PSTO input channel 1
PSTO2 INTEGER 0 PSTO input channel 2
PSTO3 INTEGER 0 PSTO input channel 3
PSTO4 INTEGER 0 PSTO input channel 4
PSTO5 INTEGER 0 PSTO input channel 5
PSTO6 INTEGER 0 PSTO input channel 6
PSTO7 INTEGER 0 PSTO input channel 7
PSTO8 INTEGER 0 PSTO input channel 8
PSTO9 INTEGER 0 PSTO input channel 9
PSTO10 INTEGER 0 PSTO input channel 10
PSTO11 INTEGER 0 PSTO input channel 11
PSTO12 INTEGER 0 PSTO input channel 12

PID-3943-OUTPUTSIGNALS v6

Table 164: LOCREMCTRL Output signals


Name Type Description
HMICTR1 INTEGER Bitmask output 1 to local remote LHMI input
HMICTR2 INTEGER Bitmask output 2 to local remote LHMI input
HMICTR3 INTEGER Bitmask output 3 to local remote LHMI input
HMICTR4 INTEGER Bitmask output 4 to local remote LHMI input
HMICTR5 INTEGER Bitmask output 5 to local remote LHMI input
HMICTR6 INTEGER Bitmask output 6 to local remote LHMI input
HMICTR7 INTEGER Bitmask output 7 to local remote LHMI input
HMICTR8 INTEGER Bitmask output 8 to local remote LHMI input
HMICTR9 INTEGER Bitmask output 9 to local remote LHMI input
HMICTR10 INTEGER Bitmask output 10 to local remote LHMI input
HMICTR11 INTEGER Bitmask output 11 to local remote LHMI input
HMICTR12 INTEGER Bitmask output 12 to local remote LHMI input

9.4.5.3 Settings
PID-3944-SETTINGS v7

Table 165: LOCREM Non group settings (basic)


Name Values (Range) Unit Step Default Description
ControlMode Internal LR-switch - - Internal LR- Control mode for internal/external LR-
External LR- switch switch
switch

PID-3943-SETTINGS v2

Breaker protection REQ650 249


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

9.4.5.4 Operation principle M17087-3 v9

The function block Local remote (LOCREM) handles the signals coming from the local/remote
switch. The connections are seen in Figure 128, where the inputs on function block LOCREM
are connected to binary inputs if an external switch is used. When the local HMI is used, the
inputs are not used. The switching between external and local HMI source is done through the
parameter ControlMode. The outputs from the LOCREM function block control the output
PSTO (Permitted Source To Operate) on Bay control (QCBAY).

LOCREM QCBAY
CTRLOFF OFF LR_ OFF PSTO
LOCCTRL LOCAL LR_ LOC UPD_ BLKD
REMCTRL REMOTE LR_ REM CMD_ BLKD
LHMICTRL VALID LR_ VALID LOC
BL_ UPD STA
BL_ CMD REM

LOCREM QCBAY
CTRLOFF OFF LR_ OFF PSTO
LOCCTRL LOCAL LR_ LOC UPD_ BLKD
REMCTRL REMOTE LR_ REM CMD_ BLKD
LHMICTRL VALID LR_ VALID LOC
BL_ UPD STA
BL_ CMD REM

LOCREMCTRL
PSTO1 HMICTR1
PSTO2 HMICTR2
PSTO3 HMICTR3
PSTO4 HMICTR4
PSTO5 HMICTR5
PSTO6 HMICTR6
PSTO7 HMICTR7
PSTO8 HMICTR8
PSTO9 HMICTR9
PSTO 10 HMICTR 10
PSTO 11 HMICTR 11
PSTO 12 HMICTR 12

IEC10000052-1-en.vsd
IEC10000052 V2 EN-US

Figure 128: Configuration for the local/remote handling for a local HMI with two bays and
two screen pages
If the IED contains control functions for several bays, the local/remote position can be
different for the included bays. When the local HMI is used the position of the local/remote
switch can be different depending on which single line diagram screen page that is presented
on the local HMI. The function block Local remote control (LOCREMCTRL) controls the
presentation of the LEDs for the local/remote position to applicable bay and screen page.

The switching of the local/remote switch requires at least system operator level. The
password will be requested at an attempt to operate if authority levels have been defined in
the IED. Otherwise the default authority level, SuperUser, can handle the control without
LogOn. The users and passwords are defined with the IED Users tool in PCM600.

9.4.6 Switch controller SCSWI IP15603-1 v2

250 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

9.4.6.1 Functionality M13486-3 v10

The Switch controller (SCSWI) initializes and supervises all functions to properly select and
operate switching primary apparatuses.

9.4.6.2 Function block M13482-3 v5

SCSWI
BLOCK EXE_OP
PSTO EXE_CL
L_SEL SEL_OP
L_OPEN SEL_CL
L_CLOSE SELECTED
AU_OPEN RES_RQ
AU_CLOSE START_SY
BL_CMD CANC_SY
RES_GRT POSITION
RES_EXT OPENP OS
SY_INPRO CLOSEPOS
SYNC_OK POLEDISC
EN_OPEN CMD_BLK
EN_CLOSE L_CAUSE
XPOSL1* POS_INTR
XPOSL2* XEXINF
XPOSL3*
IEC05000337-6-en.vsdx
IEC05000337 V6 EN-US

Figure 129: SCSWI function block

9.4.6.3 Signals
PID-6798-INPUTSIGNALS v4

Table 166: SCSWI Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
PSTO INTEGER 2 Operator place selection
L_SEL BOOLEAN 0 Select signal from local panel
L_OPEN BOOLEAN 0 Open signal from local panel
L_CLOSE BOOLEAN 0 Close signal from local panel
AU_OPEN BOOLEAN 0 Open signal from local automation function
AU_CLOSE BOOLEAN 0 Close signal from local automation function
BL_CMD BOOLEAN 0 Steady signal for block of the command
RES_GRT BOOLEAN 0 Positive acknowledge that all reservations are made
RES_EXT BOOLEAN 0 Reservation is made externally
SY_INPRO BOOLEAN 0 Synchronizing function in progress
SYNC_OK BOOLEAN 0 Closing is permitted at set to true by the synchrocheck
EN_OPEN BOOLEAN 0 Enables open operation
EN_CLOSE BOOLEAN 0 Enables close operation
XPOSL1 GROUP - Group signal from XCBR/XSWI per phase
SIGNAL
XPOSL2 GROUP - Group signal from XCBR/XSWI per phase
SIGNAL
XPOSL3 GROUP - Group signal from XCBR/XSWI per phase
SIGNAL

Breaker protection REQ650 251


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

PID-6798-OUTPUTSIGNALS v4

Table 167: SCSWI Output signals


Name Type Description
EXE_OP BOOLEAN Execute command for open direction
EXE_CL BOOLEAN Execute command for close direction
SEL_OP BOOLEAN Selected for open command
SEL_CL BOOLEAN Selected for close command
SELECTED BOOLEAN Select conditions are fulfilled
RES_RQ BOOLEAN Request signal to the reservation function
START_SY BOOLEAN Starts the external synchronizing function
CANC_SY BOOLEAN Cancels the external synchronizing function, started through
START_SY
POSITION INTEGER Position indication
OPENPOS BOOLEAN Open position indication
CLOSEPOS BOOLEAN Closed position indication
POLEDISC BOOLEAN The positions for poles L1-L3 are not equal after a set time
CMD_BLK BOOLEAN Commands are blocked
L_CAUSE INTEGER Latest value of the error indication during command
POS_INTR BOOLEAN Stopped in intermediate position
XEXINF GROUP SIGNAL Execution information to XCBR, XSWI & XLNPROXY

GUID-7DABB496-EABE-48A4-8078-7ED5D6D4FE14 v2

AU_OPEN and AU_CLOSE are used to issue automated commands as e.g. for
load shedding for opening respectively closing to the SCSWI function. They
work without regard to how the operator place selector, PSTO, is set. In order
to have effect on the outputs EXE_OP and EXE_CL, the corresponding enable
input, EN_OPEN respectively EN_CLOSE must be set, and that no interlocking is
active.

L_SEL, L_OPEN and L_CLOSE are used for local command sequence connected
to binary inputs. In order to have effect, the operator place selector, PSTO,
must be set to local or to remote with no priority. If the control model used is
Select before operate, Also the corresponding enable input must be set, and no
interlocking is active. The L_SEL input must be set before L_OPEN or L_CLOSE
is operated, if the control model is Select before operate.

If one multi-phase XCBR/XSWI or two single-phase XCBR/XSWI are used for a


two- or three-phase system, two or more of the inputs XPOSL1, XPOSL2 and
XPOSL3 are connected to the same source.

252 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

9.4.6.4 Settings
PID-6798-SETTINGS v4

Table 168: SCSWI Non group settings (basic)


Name Values (Range) Unit Step Default Description
CtlModel Dir Norm - - SBO Enh Specifies control model type
SBO Enh
PosDependent Always permitted - - Always Permission to operate depending on
Not perm at permitted the position
00/11
tSelect 0.00 - 600.00 s 0.01 30.00 Maximum time between select and
execute signals
tResResponse 0.000 - 60.000 s 0.001 5.000 Allowed time from reservation request
to reservation granted
tSynchrocheck 0.00 - 600.00 s 0.01 10.00 Allowed time for synchrocheck to fulfil
close conditions
tSynchronizing 0.00 - 600.00 s 0.01 0.00 Supervision time to get the signal
synchronizing in progress
tExecutionFB 0.00 - 600.00 s 0.01 30.00 Maximum time from command
execution to termination
tPoleDiscord 0.000 - 60.000 s 0.001 2.000 Allowed time to have discrepancy
between the poles
SuppressMidPos Off - - On Mid-position is suppressed during
On time tIntermediate; tIntermediate is
set on each connected XCBR/XSWI
function individually
InterlockChk Sel & Op phase - - Sel & Op phase Selection if interlock check should be
Op phase done in select phase

9.4.6.5 Operation principle


M13484-4 v4
The Switch controller (SCSWI) is provided with verification checks for the select - execute
sequence, that is, checks the conditions prior each step of the operation are fulfilled. The
involved functions for these condition verifications are interlocking, reservation, blockings and
synchrocheck.

Control handling M13484-6 v7


.
Two types of control models can be used. The two control models are "direct with normal
security" and "SBO (Select-Before-Operate) with enhanced security". The parameter CtlModel
defines which one of the two control models is used. The control model "direct with normal
security" does not require a select whereas, the "SBO with enhanced security" command model
requires a select before execution. The command sequence for a command with control mode
SBO with enhanced security is shown in figure 130, with control mode direct with normal
security is shown in figure 131.

Breaker protection REQ650 253


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

Reservation SXCBR /
Client SCSWI
logic SXSWI
select

SEL_CL = TRUE

RES_RQ = TRUE
tReservation
Response

tSelect
RES_GRT = TRUE
SELECTED = TRUE
selectAck/AddCause = 0

requestedPosition = 10

opRcvd = TRUE
EXE_CL

opOK = TRUE, tOpOk


operateAck/AddCause = 0
operateAck/AddCause = 0
tExecutionFB

POSITION = 00, timeStamp


POSITION = 00, timeStamp
POSITION = 10, timeStamp
cmdTermination/AddCause = 0

POSITION = 10, timeStamp


cmdTermination/AddCause = 0
SELECTED = FALSE
SEL_CL = FALSE

RES_RQ = FALSE

RES_GRT = FALSE

IEC15000416-2-EN.vsdx

IEC15000416 V2 EN-US

Figure 130: Example of command sequence for a successful close command when the
control model SBO with enhanced security is used

Reservation SwitchCtrl Switch


client
core core core

requestedPosition = 10

opRcvd = TRUE

RES_RQ
tReservation
Response

RES_GRT = TRUE
EXE_CL

opOK = TRUE, tOpOk

operateAck/AddCause = 0 operateAck/AddCause = 0

POSITION = 00, timeStamp POSITION = 00, timeStamp

POSITION = 10, timeStamp


cmdTermination/
POSITION = 10, timeStamp AddCause = 0

RES_RQ = FALSE

RES_GRT = FALSE

IEC15000417-1-en.vsdx

IEC15000417 V1 EN-US

Figure 131: Example of command sequence for a successful close command when the
control model direct with normal security is used
Normal security means that only the command is evaluated and the resulting position is not
supervised. Enhanced security means that the command sequence is supervised in three
steps, the selection, command evaluation and the supervision of position. Each step ends up
with a pulsed signal to indicate that the respective step in the command sequence is finished.
If an error occurs in one of the steps in the command sequence, the sequence is terminated.
The last error (L_CAUSE) can be read from the function block and used for example at
commissioning.

254 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

There is no relation between the command direction and the actual position.
For example, if the switch is in closed position it is possible to execute a close
command.

Before an execution command, an evaluation of the position is done. If the parameter


PosDependent is true and the position is in intermediate state or in bad state no execution
command is sent. If the parameter is false the execution command is sent independent of the
position value.

Evaluation of position M13484-14 v5


The position output from the switches (SXCBR or SXSWI) is connected to the switch controller
SCSWI. The XPOSL1, XPOSL2 and XPOSL3 input signals receive the position, time stamps and
quality attributes of the position which is used for further evaluation.

In the case when there are two or more one-phase switches connected to the switch control
function, the switch control will "merge" the position of the switches to the resulting multi-
phase position. In the case when the position differ between the one-phase switches,
following principles will be applied:

All switches in open position: switch control position = open


All switches in closed position: switch control position = closed
At least one switch in open position and the switch control position = intermediate
other(s) in closed position:
Any switch in intermediate position: switch control position = intermediate
Any switch in bad state: switch control position = bad state

The time stamp of the output multi-phase position from switch control will have the time
stamp of the last changed phase when it reaches the end position. When it goes to
intermediate position or bad state, it will get the time stamp of the first changed phase.

In addition, there is also the possibility that one of the one-phase switches will change
position at any time due to a trip. Such situation is here called pole discordance and is
supervised by this function. In case of a pole discordance situation, that is, the positions of the
one-phase switches are not equal for a time longer than the setting tPoleDiscord, an error
signal POLEDISC will be set.

In the supervision phase, the switch controller function evaluates the "cause" values from the
switch modules circuit breaker (SXCBR)/circuit switch (SXSWI). At error the "cause" value with
highest priority is shown.

Blocking principles M13484-37 v5


The blocking signals are normally coming from the bay control function (QCBAY) and via the
IEC 61850 communication from the operator place.

The different blocking possibilities are:

• Block/deblock of command. It is used to block command for operation of position.


• Blocking of function, BLOCK. If the BLOCK signal is set, it means that the function is
active, but no outputs are generated, no reporting, control commands are rejected and
functional and configuration data is visible.

The different block conditions will only affect the operation of this function,
that is, no blocking signals will be "forwarded" to other functions. The above
blocking outputs are stored in a non-volatile memory.

Breaker protection REQ650 255


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

Dependence on operator place GUID-AB327F15-AF44-4ACC-8FA5-2A52AE4AE090 v4


For the commands from a communication protocol, such as IEC 61850-8-1, and through the
inputs L_SEL, L_OPEN and L_CLOSE, the operator place is evaluated, and only the commands
from enabled operator places are accepted, see Table 160. Commands through the inputs
L_SEL, L_OPEN and L_CLOSE are always from the local operator place. For commands through
the inputs AU_OPEN and AU_CLOSE, the operator place is not evaluated. If the operator place is
set to Off, the commands through the inputs AU_OPEN and AU_CLOSE are not accepted.

Interaction with synchrocheck and synchronizing functions M13484-47 v5


The Switch controller (SCSWI) works in conjunction with the synchrocheck and the
synchronizing function (SESRSYN). It is assumed that the synchrocheck function is
continuously in operation and gives the result to SCSWI. The result from the synchrocheck
function is evaluated during the close execution. If the operator performs an override of the
synchrocheck, the evaluation of the synchrocheck state is omitted. When there is a positive
confirmation from the synchrocheck function, SCSWI will send the close signal EXE_CL to the
switch function Circuit breaker (SXCBR).

When there is no positive confirmation from the synchrocheck function, SCSWI will send a
start signal START_SY to the synchronizing function, which will send the closing command to
SXCBR when the synchronizing conditions are fulfilled, see Figure 132. If no synchronizing
function is included, the timer for supervision of the "synchronizing in progress signal" is set
to 0, which means no start of the synchronizing function. SCSWI will then set the attribute
"blocked-by-synchrocheck" in the "cause" signal. See also the time diagram in Figure 136.

SCSWI SXCBR
EXE_CL
OR CLOSE

SYNC_OK
START_SY
CANC_SY
SY_INPRO
SESRSYN

CLOSECB
Synchro Synchronizing
check function

IEC09000209-2-en.vsd
IEC09000209 V2 EN-US

Figure 132: Example of interaction between SCSWI, SESRSYN (synchrocheck and


synchronizing function) and SXCBR function

Time diagrams M13484-51 v7


The Switch controller (SCSWI) function has timers for evaluating different time supervision
conditions. These timers are explained here.

The timer tSelect is used for supervising the time between the select and the execute
command signal, that is, the time the operator has to perform the command execution after
the selection of the object to operate.

256 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

select
execute command
tSelect
timer t1 t1>tSelect, then long-
operation-time in 'cause'
is set

en05000092.vsd
IEC05000092 V1 EN-US

Figure 133: tSelect

The Long-operation-time cause is only given on the output L_CAUSE. It is not


sent on protocols since the selection has already received a positive response,
and no operation has been issued. If an operation is issued after the time out,
the negative response is Object-not-selected.

The parameter tResResponse is used to set the maximum allowed time to make the
reservation, that is, the time between reservation request and the feedback reservation
granted from all bays involved in the reservation function.

select

reservation request RES_RQ

reservation granted RES_GRT


t1>tResResponse, then 1-
tResResponse
of-n-control in 'cause' is
timer t1
set
IEC05000093-2-en.vsd
IEC05000093 V2 EN-US

Figure 134: tResResponse


The timer tExecutionFB supervises the time between the execute command and the command
termination, see Figure 135.

Breaker protection REQ650 257


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

execute command

position L1 open

close

position L2 open

close

position L3 open

close

cmd termination L1

cmd termination L2

cmd termination L3

cmd termination *

position open

close

t1>tExecutionFB, then
tExecutionFB timer long-operation-time in
t1 'cause' is set

* The cmd termination will be delayed one execution sample . APCtExecutionFB=IEC0


5000094=2=en=Original
.vsd
IEC05000094 V2 EN-US

Figure 135: tExecutionFB


The parameter tSynchrocheck is used to define the maximum allowed time between the
execute command and the input SYNC_OK to become true. If SYNC_OK=true at the time the
execute command signal is received, the timer "tSynchrocheck" will not start. The start signal
for the synchronizing is obtained if the synchrocheck conditions are not fulfilled.

The parameter tSynchronizing is used to define the maximum allowed time between the start
signal for synchronizing and the confirmation that synchronizing is in progress.

execute command

SYNC_OK

tSynchrocheck
t1
START_SY

SY_INPRO

tSynchronizing t2>tSynchronizing, then


t2 blocked-by-synchrocheck in
'cause' is set

en05000095.vsd
IEC05000095 V1 EN-US

Figure 136: tSynchroCheck and tSynchronizing

9.4.7 Circuit breaker SXCBR IP15614-1 v3

258 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

9.4.7.1 Functionality M13489-3 v6

The purpose of Circuit breaker (SXCBR) is to provide the actual status of positions and to
perform the control operations, that is, pass all the commands to primary apparatuses in the
form of circuit breakers via binary output boards and to supervise the switching operation and
position.

9.4.7.2 Function block M13500-3 v5

SXCBR
BLOCK XPOS
LR_SWI EXE_OP
OPEN EXE_CL
CLOSE SUBSTED
BL_OPEN OP_BLKD
BL_CLOSE CL_BLKD
BL_UPD UPD_BLKD
POSOP EN POSITION
POSCLOSE OPENP OS
CBOPCAP CLOSEPOS
TR_OPEN TR_POS
TR_CLOSE CNT_VAL
RS_CNT L_CAUSE
EEH_WARN EEHEALTH
EEH_ALM CBOPCAP
XIN
IEC05000338-6-en.vsdx
IEC05000338 V6 EN-US

Figure 137: SXCBR function block

9.4.7.3 Signals
PID-6799-INPUTSIGNALS v3

Table 169: SXCBR Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
LR_SWI BOOLEAN 0 Local/Remote switch indication from switchyard
OPEN BOOLEAN 0 Pulsed signal used to immediately open the switch
CLOSE BOOLEAN 0 Pulsed signal used to immediately close the switch
BL_OPEN BOOLEAN 0 Signal to block the open command
BL_CLOSE BOOLEAN 0 Signal to block the close command
BL_UPD BOOLEAN 0 Steady signal for block of the position updating
POSOPEN BOOLEAN 0 Signal for open position of apparatus from I/O
POSCLOSE BOOLEAN 0 Signal for close position of apparatus from I/O
CBOPCAP INTEGER 3 Breaker operating capability 1 = None, 2 = O, 3 = CO, 4 = OCO,
5 = COCO, 6+ = More
TR_OPEN BOOLEAN 0 Signal for open position of truck from I/O
TR_CLOSE BOOLEAN 0 Signal for close position of truck from I/O
RS_CNT BOOLEAN 0 Resets the operation counter
EEH_WARN BOOLEAN 0 Warning from external equipment
EEH_ALM BOOLEAN 0 Alarm from external equipment
XIN GROUP - Execution information from CSWI
SIGNAL

Breaker protection REQ650 259


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

PID-6799-OUTPUTSIGNALS v3

Table 170: SXCBR Output signals


Name Type Description
XPOS GROUP SIGNAL Group connection to CSWI for XCBR and XSWI
EXE_OP BOOLEAN Executes the command for open direction
EXE_CL BOOLEAN Executes the command for close direction
SUBSTED BOOLEAN Indication that the position is substituted
OP_BLKD BOOLEAN Indication that the function is blocked for open commands
CL_BLKD BOOLEAN Indication that the function is blocked for close commands
UPD_BLKD BOOLEAN Update of position indication is blocked
POSITION INTEGER Apparatus position indication
OPENPOS BOOLEAN Apparatus open position
CLOSEPOS BOOLEAN Apparatus closed position
TR_POS INTEGER Truck position indication
CNT_VAL INTEGER Operation counter value
L_CAUSE INTEGER Latest value of the error indication during command
EEHEALTH INTEGER External equipment health. 1=No warning or alarm,
2=Warning, 3=Alarm
CBOPCAP INTEGER Breaker operating capability 1 = None, 2 = O, 3 = CO, 4 = OCO,
5 = COCO, 6+ = More

9.4.7.4 Settings
PID-6799-SETTINGS v3

Table 171: SXCBR Non group settings (basic)


Name Values (Range) Unit Step Default Description
tStartMove 0.000 - 60.000 s 0.001 0.100 Supervision time for the apparatus to
move after a command
tIntermediate 0.000 - 60.000 s 0.001 0.150 Allowed time for intermediate
position
AdaptivePulse Not adaptive - - Not adaptive Output resets when a new correct end
Adaptive position is reached
tOpenPulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for open
command
tClosePulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for close
command
InitialCount 0 - 20000 - 1 0 Initial number of operations (Initial
count value)

9.4.7.5 Operation principle


M13487-4 v8
The circuit breaker function (SXCBR) is used by other functions such as, for example, switch
controller, protection functions, autorecloser function or an IEC 61850 client residing in
another IED or the operator place. This switch function executes commands, evaluates block
conditions and evaluates different time supervision conditions. Only if all conditions indicate a
switch operation to be allowed, the function performs the execution command. In case of
erroneous conditions, the function indicates an appropriate "cause" value, see Table 154.

260 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

SXCBR has an operation counter for closing and opening commands. The counter value can be
read remotely from the operator place. The value is reset from local HMI, a binary input or
remotely from the operator place by configuring a signal from the Single Point Generic Control
8 signals (SPC8GAPC) for example. The health of the external equipment, the switch, can be
monitored according to IEC 61850-8-1. The operation counter functionality and the external
equipment health supervision are independent sub-functions of the circuit breaker function.

Local/Remote switch M13487-7 v4


One binary input signal LR_SWI is included in SXCBR to indicate the local/remote switch
position from switchyard provided via the I/O board. If this signal is set to TRUE it means that
change of position is allowed only from switchyard level. If the signal is set to FALSE it means
that command from IED or higher level is permitted. When the signal is set to TRUE all
commands (for change of position) are rejected, even trip commands from protection
functions are rejected. The functionality of the local/remote switch is described in Figure 138.

Local= Operation at
UE switch yard level
TR

From I/O switchLR


FAL
SE
Remote= Operation at
IED or higher level

en05000096.vsd
IEC05000096 V1 EN-US

Figure 138: Local/Remote switch

Blocking principles M13487-12 v6


SXCBR includes several blocking principles. The basic principle for all blocking signals is that
they will affect commands from all other clients for example, switch controller, protection
functions and autoreclosure.

The blocking possibilities are:

• Block/deblock for open command. It is used to block operation for the open command.
• Block/deblock for close command. It is used to block operation for the close command.
• Update block/deblock of positions. It is used to block the updating of position values.
Other signals related to the position will be reset.
• Blocking of function, BLOCK. If BLOCK signal is set, it means that the function is active,
but no outputs are generated, no reporting, control commands are rejected and
functional and configuration data is visible.

The above blocking outputs are stored in a non-volatile memory.

Substitution M13487-22 v5
The substitution part in SXCBR is used for manual set of the position and quality of the switch.
The typical use of substitution is that an operator enters a manual value because that the real
process value is erroneous for some reason. SXCBR will then use the manually entered value
instead of the value for positions determined by the process.

It is always possible to make a substitution, independently of the position


indication and the status information of the I/O board. When substitution is
enabled, the other signals related to the position follow the substituted
position. The substituted values are stored in a non-volatile memory. If the
function is blocked or blocked for update when the substitution is released, the
position value is kept the same as the last substitution value, but the quality is
changed to "questionable, old data", indicating that the value is old and not
reliable.

Breaker protection REQ650 261


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

When the position of the SXCBR is substituted, its IEC 61850-8-1 data object is
marked as “substituted", in addition to the substituted quality, but the position
quality of the connected SCSWI is not dependent on the substitution indication
in the quality, so it does not show that it is derived from a substituted value.

Time diagrams M13487-28 v5


There are two timers for supervising of the execute phase, tStartMove and tIntermediate.
tStartMove supervises that the primary device starts moving after the execute output pulse is
sent. tIntermediate defines the maximum allowed time for intermediate position. Figure 139
explains these two timers during the execute phase.

EXE_CL AdaptivePulse = TRUE


Close pulse duration

OPENPOS

CLOSEPOS

if t1 > tStartMove then


tStartMove timer "switch-not-start-moving"
t1 attribute in 'cause' is set
tStartMove

if t2 > tIntermediate then


tIntermediate timer "persisting-intermediate-state"
t2 attribute in 'cause' is set
tIntermediate

en05000097.vsd

IEC05000097 V1 EN-US

Figure 139: The timers tStartMove and tIntermediate


The timers tOpenPulse and tClosePulse are the length of the execute output pulses to be sent
to the primary equipment. Note that the output pulses for open and close command can have
different pulse lengths. The pulses can also be set to be adaptive with the configuration
parameter AdaptivePulse. Figure 140 shows the principle of the execute output pulse. The
AdaptivePulse parameter will have effect on both execute output pulses.

OPENPOS

CLOSEPOS

AdaptivePulse=FALSE
EXE_CL
tClosePulse

AdaptivePulse=TRUE
EXE_CL
tClosePulse
en05000098.vsd
IEC05000098 V1 EN-US

Figure 140: Execute output pulse

262 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

If the pulse is set to be adaptive, it is not possible for the pulse to exceed tOpenPulse or
tClosePulse.

The execute output pulses are reset when:

• the new expected final position is reached and the configuration parameter AdaptivePulse
is set to true
• the timer tOpenPulse or tClosePulse has elapsed
• an error occurs due to the switch does not start moving, that is, tStartMove has elapsed.

If the breaker reaches the final position before the execution pulse time has
elapsed, and AdaptivePulse is not true, the function waits for the end of the
execution pulse before telling the activating function that the command is
completed.

There is one exception to the first item above: if the primary device is in open position and an
open command is executed or if the primary device is in closed position and a close command
is executed. In these cases, with the additional condition that the configuration parameter
AdaptivePulse is true, the execute output pulse is always activated and resets when
tStartMove has elapsed. If the configuration parameter AdaptivePulse is set to false, the
execution output remains active until the pulse duration timer has elapsed.

If the start position indicates bad state (OPENPOS=1 and CLOSEPOS =1) when
a command is executed, the execute output pulse resets only when timer
tOpenPulse or tClosePulse has elapsed.

An example of when a primary device is open and an open command is executed is shown in
Figure 141 .

OPENPOS

CLOSEPOS

EXE_OP AdaptivePulse=FALSE

tOpenPulse

EXE_OP AdaptivePulse=TRUE

tOpenPulse

tStartMove timer

en05000099.vsd
IEC05000099 V1 EN-US

Figure 141: Open command with open position indication

9.4.8 Circuit switch SXSWI IP15620-1 v2

Breaker protection REQ650 263


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

9.4.8.1 Functionality M16492-3 v6

The purpose of Circuit switch (SXSWI) function is to provide the actual status of positions and
to perform the control operations, that is, pass all the commands to primary apparatuses in
the form of disconnectors or earthing switches via binary output boards and to supervise the
switching operation and position.

9.4.8.2 Function block M13504-3 v5

SXSWI
BLOCK XPOS
LR_SWI EXE_OP
OPEN EXE_CL
CLOSE SUBSTED
BL_OPEN OP_BLKD
BL_CLOSE CL_BLKD
BL_UPD UPD_BLKD
POSOP EN POSITION
POSCLOSE OPENP OS
SWOPCAP CLOSEPOS
RS_CNT CNT_VAL
EEH_WARN L_CAUSE
EEH_ALM EEHEALTH
XIN SWOPCAP

IEC05000339-5-en.vsdx
IEC05000339 V5 EN-US

Figure 142: SXSWI function block

9.4.8.3 Signals
PID-6800-INPUTSIGNALS v4

Table 172: SXSWI Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
LR_SWI BOOLEAN 0 Local/Remote switch indication from switchyard
OPEN BOOLEAN 0 Pulsed signal used to immediately open the switch
CLOSE BOOLEAN 0 Pulsed signal used to immediately close the switch
BL_OPEN BOOLEAN 0 Signal to block the open command
BL_CLOSE BOOLEAN 0 Signal to block the close command
BL_UPD BOOLEAN 0 Steady signal for block of the position updating
POSOPEN BOOLEAN 0 Signal for open position of apparatus from I/O
POSCLOSE BOOLEAN 0 Signal for close position of apparatus from I/O
SWOPCAP INTEGER 4 Switch operating capability 1 = None, 2 = O, 3 = C, 4 = O and C
RS_CNT BOOLEAN 0 Resets the operation counter
EEH_WARN BOOLEAN 0 Warning from external equipment
EEH_ALM BOOLEAN 0 Alarm from external equipment
XIN GROUP - Execution information from CSWI
SIGNAL

264 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

PID-6800-OUTPUTSIGNALS v4

Table 173: SXSWI Output signals


Name Type Description
XPOS GROUP SIGNAL Group connection to CSWI for XCBR and XSWI
EXE_OP BOOLEAN Executes the command for open direction
EXE_CL BOOLEAN Executes the command for close direction
SUBSTED BOOLEAN Indication that the position is substituted
OP_BLKD BOOLEAN Indication that the function is blocked for open commands
CL_BLKD BOOLEAN Indication that the function is blocked for close commands
UPD_BLKD BOOLEAN Update of position indication is blocked
POSITION INTEGER Apparatus position indication
OPENPOS BOOLEAN Apparatus open position
CLOSEPOS BOOLEAN Apparatus closed position
CNT_VAL INTEGER Operation counter value
L_CAUSE INTEGER Latest value of the error indication during command
EEHEALTH INTEGER External equipment health. 1=No warning or alarm,
2=Warning, 3=Alarm
SWOPCAP INTEGER Switch operating capability 1 = None, 2 = O, 3 = C, 4 = O and C

9.4.8.4 Settings
PID-6800-SETTINGS v4

Table 174: SXSWI Non group settings (basic)


Name Values (Range) Unit Step Default Description
tStartMove 0.000 - 60.000 s 0.001 3.000 Supervision time for the apparatus to
move after a command
tIntermediate 0.000 - 60.000 s 0.001 15.000 Allowed time for intermediate
position
AdaptivePulse Not adaptive - - Not adaptive Output resets when a new correct end
Adaptive position is reached
tOpenPulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for open
command
tClosePulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for close
command
SwitchType Load Break - - Disconnector 1=LoadBreak,2=Disconnector,3=Earth
Disconnector Sw,4=HighSpeedEarthSw
Earthing Switch
HS Earthing
Switch
InitialCount 0 - 20000 - 1 0 Initial number of operations (Initial
count value)

9.4.8.5 Operation principle


M16494-3 v8
The users of the Circuit switch (SXSWI) are other functions such as for example, switch
controller, protection functions, autorecloser function, or a 61850 client residing in another IED
or the operator place. SXSWI executes commands, evaluates block conditions and evaluates
different time supervision conditions. Only if all conditions indicate a switch operation to be

Breaker protection REQ650 265


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

allowed, SXSWI performs the execution command. In case of erroneous conditions, the
function indicates an appropriate "cause" value, see Table 154.

SXSWI has an operation counter for closing and opening commands. The counter value can be
read remotely from the operator place. The value is reset from a binary input or remotely from
the operator place by configuring a signal from the Single Point Generic Control 8 signals
(SPC8GAPC), for example.

Also, the health of the external equipment, the switch, can be monitored according to IEC
61850-8-1.

Local/Remote switch M16494-6 v4


One binary input signal LR_SWI is included in SXSWI to indicate the local/remote switch
position from switchyard provided via the I/O board. If this signal is set to TRUE it means that
change of position is allowed only from switchyard level. If the signal is set to FALSE it means
that command from IED or higher level is permitted. When the signal is set to TRUE all
commands (for change of position) from internal IED clients are rejected, even trip commands
from protection functions are rejected. The functionality of the local/remote switch is
described in Figure 143.

Local= Operation at
UE switch yard level
TR

From I/O switchLR


FAL
SE
Remote= Operation at
IED or higher level

en05000096.vsd
IEC05000096 V1 EN-US

Figure 143: Local/Remote switch

Blocking principles M16494-11 v6


SXSWI includes several blocking principles. The basic principle for all blocking signals is that
they will affect commands from all other clients for example, switch controller, protection
functions and autorecloser.

The blocking possibilities are:

• Block/deblock for open command. It is used to block operation for open command.
• Block/deblock for close command. It is used to block operation for close command.
• Update block/deblock of positions. It is used to block the updating of position values.
Other signals related to the position will be reset.
• Blocking of function, BLOCK. If BLOCK signal is set, it means that the function is active,
but no outputs are generated, no reporting, control commands are rejected and
functional and configuration data is visible.

The above blocking outputs are stored in a non-volatile memory.

Substitution M16494-21 v7
The substitution part in SXSWI is used for manual set of the position and quality of the switch.
The typical use of substitution is that an operator enters a manual value because the real
process value is erroneous of some reason. SXSWI will then use the manually entered value
instead of the value for positions determined by the process.

266 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

It is always possible to make a substitution, independently of the position


indication and the status information of the I/O board. When substitution is
enabled, the other signals related to the position follow the substituted
position. The substituted values are stored in a non-volatile memory. If the
function is blocked or blocked for update when the substitution is released, the
position value is kept the same as the last substitution value, but the quality is
changed to "questionable, old data", indicating that the value is old and not
reliable.

When the position of the SXSWI is substituted, its IEC 61850-8-1 data object is
marked as “substituted", in addition to the substituted quality, but the position
quality of the connected SCSWI is not dependent on the substitution indication
in the quality, so it does not show that it is derived from a substituted value.

Time diagrams M16494-26 v6


There are two timers for supervising of the execute phase, tStartMove and tIntermediate.
tStartMove supervises that the primary device starts moving after the execute output pulse is
sent. tIntermediate defines the maximum allowed time for intermediate position. Figure 144
explains these two timers during the execute phase.

EXE_CL AdaptivePulse = TRUE


Close pulse duration

OPENPOS

CLOSEPOS

if t1 > tStartMove then


tStartMove timer "switch-not-start-moving"
t1 attribute in 'cause' is set
tStartMove

if t2 > tIntermediate then


tIntermediate timer "persisting-intermediate-state"
t2 attribute in 'cause' is set
tIntermediate

en05000097.vsd

IEC05000097 V1 EN-US

Figure 144: The timers tStartMove and tIntermediate


The timers tOpenPulse and tClosePulse are the length of the execute output pulses to be sent
to the primary equipment. Note that the output pulses for open and close command can have
different pulse lengths. The pulses can also be set to be adaptive with the configuration
parameter AdaptivePulse. Figure 145 shows the principle of the execute output pulse. The
AdaptivePulse parameter will have effect on both execute output pulses.

Breaker protection REQ650 267


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

OPENPOS

CLOSEPOS

AdaptivePulse=FALSE
EXE_CL
tClosePulse

AdaptivePulse=TRUE
EXE_CL
tClosePulse
en05000098.vsd
IEC05000098 V1 EN-US

Figure 145: Execute output pulse


If the pulse is set to be adaptive, it is not possible for the pulse to exceed tOpenPulse or
tClosePulse.

The execute output pulses are reset when:

• the new expected final position is reached and the configuration parameter AdaptivePulse
is set to true
• the timer tOpenPulse or tClosePulse has elapsed
• an error occurs due to the switch does not start moving, that is, tStartMove has elapsed.

If the controlled primary device reaches the final position before the execution
pulse time has elapsed, and AdaptivePulse is not true, the function waits for
the end of the execution pulse before telling the activating function that the
command is completed.

There is one exception from the first item above. If the primary device is in open position and
an open command is executed or if the primary device is in close position and a close
command is executed. In these cases, with the additional condition that the configuration
parameter AdaptivePulse is true, the execute output pulse is always activated and resets when
tStartMove has elapsed. If the configuration parameter AdaptivePulse is set to false the
execution output remains active until the pulse duration timer has elapsed.

If the start position indicates bad state (OPENPOS=1 and CLOSEPOS =1) when
a command is executed the execute output pulse resets only when timer
tOpenPulse or tClosePulse has elapsed.

An example when a primary device is open and an open command is executed is shown in
Figure 146.

268 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

OPENPOS

CLOSEPOS

EXE_OP AdaptivePulse=FALSE

tOpenPulse

EXE_OP AdaptivePulse=TRUE

tOpenPulse

tStartMove timer

en05000099.vsd
IEC05000099 V1 EN-US

Figure 146: Open command with open position indication

9.4.9 Proxy for signals from switching device via GOOSE XLNPROXY

9.4.9.1 Functionality GUID-11F9CA1C-8E20-489B-822B-34DACC59553A v1

The proxy for signals from switching device via GOOSE (XLNPROXY) gives an internal
representation of the position status and control response for a switch modelled in a breaker
IED. This representation is identical to that of an SXCBR or SXSWI function.

9.4.9.2 Function block GUID-408513CD-A87E-45E8-8E44-24E153947F02 v1

XLNPROXY
BEH* XPOS
BEH_VALID* SELECTED
LOC* OP_BLKD
LOC_VALID* CL_BLKD
BLKOPN* OPENPOS
BLKOPN_V* CLOSEPOS
BLKCLS* CNT_VAL
BLKCLS_V* L_CAUSE
POSVAL* EEHEALTH
POSVAL_V* OPCAP
OPCNT*
OP_CNT_V*
BLK
BLK_VAL
STSELD
STSELD_V
OPRCVD
OPRCVD_V
OPOK
OPOK_VAL
EEHEALTH
EEH_VAL
OPCAP
OPCAP_V
COMMVALID
XIN

IEC16000043-1-en.vsdx
IEC16000043 V1 EN-US

Figure 147: XLNPROXY function block

Breaker protection REQ650 269


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

9.4.9.3 Signals
PID-6712-INPUTSIGNALS v3

Table 175: XLNPROXY Input signals


Name Type Default Description
BEH INTEGER -1 Behaviour
BEH_VLD BOOLEAN 0 Valid data on BEH input
LOC BOOLEAN 0 Local control behaviour
LOC_VLD BOOLEAN 0 Valid data on LOC input
BLKOPN BOOLEAN 0 Block opening
BLKOPN_VLD BOOLEAN 0 Valid data on BLKOPN input
BLKCLS BOOLEAN 0 Block closing
BLKCLS_VLD BOOLEAN 0 Valid data on BLKCLS input
POSVAL INTEGER 0 Switch position, Pos.stVal
POSVAL_VLD BOOLEAN 0 Valid data on POSVAL input
OPCNT INTEGER -1 Operation counter
OPCNT_VLD BOOLEAN 0 Valid data on OPCNT input
BLK BOOLEAN 0 Dynamic blocking of function described by the LN
BLK_VLD BOOLEAN 0 Valid data on BLK input
STSELD BOOLEAN 0 The controllable data is in the status "selected”
STSELD_VLD BOOLEAN 0 Valid data on STSELD input
OPRCVD BOOLEAN 0 Operate command for a controllable data object received
OPRCVD_VLD BOOLEAN 0 Valid data on OPRCVD input
OPOK BOOLEAN 0 Operate command for a controllable data object accepted
OPOK_VLD BOOLEAN 0 Valid data on OPOK input
EEHEALTH INTEGER -1 External equipment health
EEHEALTH_VLD BOOLEAN 0 Valid data on EEHEALTH input
OPCAP INTEGER -1 Operating capability
OPCAP_VLD BOOLEAN 0 Valid data on OPCAP input
COMMVALID BOOLEAN 0 Communication valid
XIN GROUP - Execution information from CSWI
SIGNAL

PID-6712-OUTPUTSIGNALS v3

Table 176: XLNPROXY Output signals


Name Type Description
XPOS GROUP SIGNAL Group connection to CSWI
SELECTED BOOLEAN Select conditions are fulfilled
OP_BLKD BOOLEAN Indication that the function is blocked for open commands
CL_BLKD BOOLEAN Indication that the function is blocked for close commands
OPENPOS BOOLEAN Apparatus open position
CLOSEPOS BOOLEAN Apparatus closed position
CNT_VAL INTEGER Operation counter value
Table continues on next page

270 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

Name Type Description


L_CAUSE INTEGER Latest value of the error indication during command
EEHEALTH INTEGER External equipment health. 1=No warning or alarm,
2=Warning, 3=Alarm
OPCAP INTEGER Switch / breaker operating capability

9.4.9.4 Settings
PID-6712-SETTINGS v3

Table 177: XLNPROXY Non group settings (basic)


Name Values (Range) Unit Step Default Description
SwitchType Circuit Breaker - - Circuit Breaker 0 = CB, 1 = Load Break, 2 =
Load Break Disconnector, 3 = Earthing Switch, 4 =
Disconnector High Speed Earthing Switch
Earthing Switch
HS Earth Switch
tStartMove 0.000 - 60.000 s 0.001 0.100 Supervision time for the apparatus to
move after a command
tIntermediate 0.000 - 60.000 s 0.001 0.150 Allowed time for intermediate
position

GUID-A4CCC681-D4D8-4534-905D-1D8AD40E923B v1

The default values of the inputs BEH, OPCNT, EEHEALTH and OPCAP are set to
-1 to denote that they are not connected.

9.4.9.5 Operation principle GUID-D2679E0E-ABB5-46F0-AD9C-F6E8E8099534 v1

The proxy for signals from switching device via GOOSE (XLNPROXY) is intended to be used
when the switch (XCBR/XSWI) is modelled and controlled in a breaker IED or similar unit on the
process bus. XLNPROXY packages the signals from the GOOSE receive function, normally
GOOSEXLNRCV, into the same format as used from SXCBR and SXSWI to SCSWI. It makes a
similar evaluation of the command response as SXCBR and SXSWI when a command is issued
from the connected SCSWI.

9.4.9.6 Position supervision GUID-95C72346-A577-4F0A-8584-8E1593B9B947 v1

XLNPROXY has two outputs for position indication: OPENPOS and CLOSEPOS. Position is a
double point indication and the OPENPOS and CLOSEPOS are binary outputs intended to be
used for condition logics to protection and control functions

Normally, the position outputs, OPENPOS and CLOSEPOS, follow the value of the input
POSVAL. However, if the POSVAL_V input is FALSE, the communication is lost (COMMVALID =
FALSE), or the quality of the position received is bad, the OPENPOS and CLOSEPOS are both
set to FALSE.

9.4.9.7 Command response evaluation GUID-A2CDC1AE-A6F5-478B-B6E5-3442C54212D8 v1

The command evaluation is triggered through the group input XIN that is connected to the
SCSWI function controlling the switch.

Breaker protection REQ650 271


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

If an operation is initiated by the SCSWI, the XLNPROXY function checks if the switch is
blocked for the operation direction and that the position moves to the desired position within
the two time limits tStartMove and tIntermediate. The default values for tStartMove and
tIntermediate are for a breaker. The typical values for a disconnector are:

• tStartMove = 3s
• tIntermediate = 15s

In most cases, tStartMove and tIntermediate can be set to the same values as
in the source XCBR or XSWI function. However, if the time limits are set very
close to the actual movement times of the apparatus, compensation may be
needed for the communication delays and differences in cycle time of the
XLNPROXY function and the source function. The compensation should be in
the range of 0 - 5ms.

When the switch has started moving, it issues a response to the SCSWI function that the
operation has started. If it does not start moving within tStartMove, the command is deemed
as failed, and a cause is raised on the L_CAUSE output and sent to the SCSWI. The different
causes it can identify are listed in order of priority in table 1. The detection of the different
ways of blocking is done while waiting for movement of the switch, but the cause is not given
until the tStartMove has elapsed.

Table 178: Possible cause values from XLNPROXY


Cause No Cause Description Conditions
8 Blocked-by-Mode The BEH input is 5.
2 Blocked-by-switching- The LOC input indicates that only local commands
hierarchy are allowed for the breaker IED function.
-24 Blocked-for-open-cmd The BLKOPN is active indicating that the switch is
blocked for open commands.
-25 Blocked-for-close-cmd The BLKCLS is active indicating that the switch is
blocked for close commands.
9 Blocked-by-process If the Blk input is connected and active indicating
that the switch is dynamically blocked. Or if the
OPCAP input is connected, it indicates that the
operation capability of the switch is not enough to
perform the command.
5 Position-reached Switch is already in the intended position.
-31 Switch-not-start-moving Switch did not start moving within tStartMove.
-32 Persistent-intermediate-state The switch stopped in intermediate state for longer
than tIntermediate.
-33 Switch-returned-to-init-pos Switch returned to the initial position.
-34 Switch-in-bad-state Switch is in a bad position.
-35 Not-expected-final-position Switch did not reach the expected final position.

The L_CAUSE output keeps its output value until a new command sequence has been started.

If the quality of the position or the communication becomes bad, the command evaluation
replaces the uncertain position value with intermediate position. Thus, as long as the quality is
bad, all commands will result in the cause Persistant-intermediate-state, -32.

If the switch in the merging unit has the behaviour set to Test or Test blocked, when the
IED has the behaviour On or Blocked, all data from the switch is regarded as invalid. Thus, any
command will fail with the cause PersistantiIntermediate-state, -32, and if selection is used for

272 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

the switch, all attempts to select the connected SCSWI will fail with the cause Select-failed, 3,
from the SCSWI.

It is possible to speed up the command response for when the command has been started by
the switch in the breaker IED by connecting the inputs OPOK and OPOK_VAL. Then the
blocking check is only done until OPOK is activated and confirmation of that the command has
been started is given to the SCSWI function.

If the inputs STSELD and STSELD_V are connected, the switch in the breaker IED is assumed to
use selection. Then the SCSWI will wait for a selected indication, STSELD input of XLNPROXY,
before accepting selection, this information is transferred to the SCSWI function from the
XLNPROXY through the group connection XPOS. If STSELD is not activated within tSelect of
the SCSWI function, the selection is deemed failed and it gives a negative selection
acknowledgement to the command issuer with the cause Select-failed. Further, if the
communication is lost, or the data received is deemed invalid, the selection will also fail with
cause Select-failed from the SCSWI.

9.5 Logic rotating switch for function selection and LHMI


presentation SLGAPC SEMOD114936-1 v5

9.5.1 Identification
SEMOD167845-2 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Logic rotating switch for function SLGAPC - -
selection and LHMI presentation

9.5.2 Functionality SEMOD114908-4 v11

The logic rotating switch for function selection and LHMI presentation (SLGAPC) (or the
selector switch function block) is used to get an enhanced selector switch functionality
compared to the one provided by a hardware selector switch. Hardware selector switches are
used extensively by utilities, in order to have different functions operating on pre-set values.
Hardware switches are however sources for maintenance issues, lower system reliability and
an extended purchase portfolio. The selector switch function eliminates all these problems.

Breaker protection REQ650 273


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

9.5.3 Function block SEMOD114954-4 v6

SLGAPC
BLOCK ^P01
PSTO ^P02
UP ^P03
DOWN ^P04
^P05
^P06
^P07
^P08
^P09
^P10
^P11
^P12
^P13
^P14
^P15
^P16
^P17
^P18
^P19
^P20
^P21
^P22
^P23
^P24
^P25
^P26
^P27
^P28
^P29
^P30
^P31
^P32
SWPOSN

IEC14000005-1-en.vsd
IEC14000005 V1 EN-US

Figure 148: SLGAPC function block

9.5.4 Signals
PID-6641-INPUTSIGNALS v3

Table 179: SLGAPC Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
PSTO INTEGER 0 Operator place selection
UP BOOLEAN 0 Binary "UP" command
DOWN BOOLEAN 0 Binary "DOWN" command

PID-6641-OUTPUTSIGNALS v3

Table 180: SLGAPC Output signals


Name Type Description
P01 BOOLEAN Selector switch position 1
P02 BOOLEAN Selector switch position 2
P03 BOOLEAN Selector switch position 3
P04 BOOLEAN Selector switch position 4
P05 BOOLEAN Selector switch position 5
P06 BOOLEAN Selector switch position 6
P07 BOOLEAN Selector switch position 7
Table continues on next page

274 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

Name Type Description


P08 BOOLEAN Selector switch position 8
P09 BOOLEAN Selector switch position 9
P10 BOOLEAN Selector switch position 10
P11 BOOLEAN Selector switch position 11
P12 BOOLEAN Selector switch position 12
P13 BOOLEAN Selector switch position 13
P14 BOOLEAN Selector switch position 14
P15 BOOLEAN Selector switch position 15
P16 BOOLEAN Selector switch position 16
P17 BOOLEAN Selector switch position 17
P18 BOOLEAN Selector switch position 18
P19 BOOLEAN Selector switch position 19
P20 BOOLEAN Selector switch position 20
P21 BOOLEAN Selector switch position 21
P22 BOOLEAN Selector switch position 22
P23 BOOLEAN Selector switch position 23
P24 BOOLEAN Selector switch position 24
P25 BOOLEAN Selector switch position 25
P26 BOOLEAN Selector switch position 26
P27 BOOLEAN Selector switch position 27
P28 BOOLEAN Selector switch position 28
P29 BOOLEAN Selector switch position 29
P30 BOOLEAN Selector switch position 30
P31 BOOLEAN Selector switch position 31
P32 BOOLEAN Selector switch position 32
SWPOSN INTEGER Switch position (integer)

9.5.5 Settings
PID-6641-SETTINGS v3

Table 181: SLGAPC Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
NrPos 2 - 32 - 1 32 Number of positions in the switch
OutType Pulsed - - Steady Output type, steady or pulse
Steady
tPulse 0.000 - 60.000 s 0.001 0.200 Operate pulse duration, in [s]
tDelay 0.000 - s 0.010 0.000 Time delay on the output, in [s]
60000.000
StopAtExtremes Disabled - - Disabled Stop when min or max position is
Enabled reached

Breaker protection REQ650 275


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

9.5.6 Monitored data


PID-6641-MONITOREDDATA v3

Table 182: SLGAPC Monitored data


Name Type Values (Range) Unit Description
SWPOSN INTEGER - - Switch position (integer)

9.5.7 Operation principle


SEMOD114931-4 v8
The logic rotating switch for function selection and LHMI presentation (SLGAPC) function has
two operating inputs – UP and DOWN. When a signal is received on the UP input, the function
will activate the output next to the present activated output, in ascending order (for example
if the present activated output is P03 and one activates the UP input then the output P04 will
be activated). When a signal is received on the DOWN input, the function will activate the
output next to the present activated output, in descending order (for example if the present
activated output is P03 and one activates the DOWN input then the output P02 will be
activated). Depending on the output settings the output signals can be steady or pulsed. In
case of steady signals, the output will be active till the time it receives next operation of UP/
DOWN inputs. Also, depending on the settings one can have a time delay between activation of
the UP or DOWN input signals and the output activation.

Besides the inputs visible in the application configuration in the Application Configuration
Tool, there are other possibilities that will allow an user to set the desired position directly
(without activating the intermediate positions), either locally or remotely, using a “select
before execute” dialog. One can block the function operation, by activating the BLOCK input.
In this case, the present position will be kept and further operation will be blocked. The
operator place (local or remote) is specified through the PSTO input. If any operation is
allowed the signal INTONE from the Fixed signal function block can be connected. SLGAPC
function block has also an integer value output, that generates the actual position number.
The positions and the block names are fully settable by the user. These names will appear in
the menu, so the user can see the position names instead of a number.

9.5.7.1 Graphical display SEMOD114931-35 v4

There are two possibilities for SLGAPC

• if it is used just for the monitoring, the switches will be listed with their actual position
names, as defined by the user (max. 13 characters).
• if it is used for control, the switches will be listed with their actual positions, but only the
first three letters of the name will be used.

In both cases, the switch full name will be shown, but the user has to redefine it when building
the Graphical Display Editor, under the "Caption". If used for the control, the following
sequence of commands will ensure:

276 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

From the graphical display:

Control
Control Sing le Line Diagram
Measurements Comma nds
Events
Disturb ance r eco rds
Settings
Diagno stics
Test
Chang e to the "Switche s" pag e Reset
of the SLD by left-righ t arrows. Authori zation
Sele ct switch by up-down Lan guage
arro ws

../Control/SLD/Switch
O I ../Control/SLD/Switch

SMBRREC control SMBRREC control


WFM Sele ct switch. Pre ss the
WFM
I or O key. A dialo g b ox
Pilo t se tup app ears.
Pilo t se tup
OFF OFF

Damage control
P: Disc N: Disc Fe
DAL
The pos will not b e mod ified
(outputs will not b e activa ted) unt il OK Cancel
you press the Enter button for O.K.

../Control/SLD/Switch

SMBRREC control
WFM

Pilo t se tup
OFF

Damage control
DFW

IEC06000421-3-en.vsdx
IEC06000421 V3 EN-US

Figure 149: Example 2 on handling the switch from the local HMI.
From the single line diagram on local HMI.

9.6 Selector mini switch VSGAPC SEMOD158754-1 v3

9.6.1 Identification
SEMOD167850-2 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Selector mini switch VSGAPC - 43

9.6.2 Functionality SEMOD158756-5 v10

The Selector mini switch (VSGAPC) function block is a multipurpose function used for a variety
of applications, as a general purpose switch.

Breaker protection REQ650 277


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

VSGAPC can be controlled from the menu, from a symbol on the single line diagram (SLD) on
the local HMI or from Binary inputs.

9.6.3 Function block SEMOD158768-4 v3

VSGAPC
BLOCK BLOCKED
PSTO POSITION
IPOS1 POS1
IPOS2 POS2
CMDPOS12
CMDPOS21

IEC14000066-1-en.vsd
IEC14000066 V1 EN-US

Figure 150: VSGAPC function block

9.6.4 Signals
PID-6504-INPUTSIGNALS v6

Table 183: VSGAPC Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
PSTO INTEGER 0 Operator place selection
IPOS1 BOOLEAN 0 Position 1 indicating input
IPOS2 BOOLEAN 0 Position 2 indicating input

PID-6504-OUTPUTSIGNALS v6

Table 184: VSGAPC Output signals


Name Type Description
BLOCKED BOOLEAN The function is active but the functionality is blocked
POSITION INTEGER Position indication, integer
POS1 BOOLEAN Position 1 indication, logical signal
POS2 BOOLEAN Position 2 indication, logical signal
CMDPOS12 BOOLEAN Execute command from position 1 to position 2
CMDPOS21 BOOLEAN Execute command from position 2 to position 1

9.6.5 Settings
PID-6504-SETTINGS v6

Table 185: VSGAPC Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
CtlModel Dir Norm - - Dir Norm Specifies the type for control model
SBO Enh according to IEC 61850
Mode Steady - - Pulsed Operation mode
Pulsed
tSelect 0.000 - 60.000 s 0.001 30.000 Max time between select and execute
signals
tPulse 0.000 - 60.000 s 0.001 0.200 Command pulse lenght

278 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

9.6.6 Operation principle SEMOD158762-4 v7

Selector mini switch (VSGAPC) function can be used for double purpose, in the same way as
switch controller (SCSWI) functions are used:

• for indication on the single line diagram (SLD). Position is received through the IPOS1 and
IPOS2 inputs and distributed in the configuration through the POS1 and POS2 outputs, or
to IEC 61850 through reporting, or GOOSE.
• for commands that are received via the local HMI or IEC 61850 and distributed in the
configuration through outputs CMDPOS12 and CMDPOS21.
The output CMDPOS12 is set when the function receives a CLOSE command from the local
HMI when the SLD is displayed and the object is chosen.
The output CMDPOS21 is set when the function receives an OPEN command from the local
HMI when the SLD is displayed and the object is chosen.

It is important for indication in the SLD that a symbol is associated with a


controllable object, otherwise the symbol won't be displayed on the screen. A
symbol is created and configured in GDE tool in PCM600.

The PSTO input is connected to the Local remote switch to have a selection of operators place,
operation from local HMI (Local) or through IEC 61850 (Remote). An INTONE connection from
Fixed signal function block (FXDSIGN) will allow operation from local HMI.

As it can be seen, both indications and commands are done in double-bit representation,
where a combination of signals on both inputs/outputs generate the desired result.

The following table shows the relationship between IPOS1/IPOS2 inputs and the name of the
string that is shown on the SLD. The value of the strings are set in PST.

IPOS1 IPOS2 Name of displayed string Default string value


0 0 PosUndefined P00
1 0 Position1 P01
0 1 Position2 P10
1 1 PosBadState P11

9.7 Generic communication function for Double Point


indication DPGAPC SEMOD55384-1 v4

9.7.1 Identification
GUID-E16EA78F-6DF9-4B37-A92D-5C09827E2297 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Generic communication function for DPGAPC - -
Double Point indication

Breaker protection REQ650 279


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

9.7.2 Functionality SEMOD55850-5 v7

Generic communication function for Double Point indication (DPGAPC) function block is used
to send double point position indications to other systems, equipment or functions in the
substation through IEC 61850-8-1 or other communication protocols. It is especially intended
to be used in the interlocking station-wide logics.

9.7.3 Function block SEMOD54710-4 v5

IEC13000081 V1 EN-US

Figure 151: DPGAPC function block

9.7.4 Signals SEMOD55883-1 v2

PID-4139-INPUTSIGNALS v12

Table 186: DPGAPC Input signals


Name Type Default Description
OPEN BOOLEAN 0 Open indication
CLOSE BOOLEAN 0 Close indication
VALID BOOLEAN 0 Valid indication

PID-4139-OUTPUTSIGNALS v11

Table 187: DPGAPC Output signals


Name Type Description
POSITION INTEGER Double point indication

9.7.5 Settings ABBD8E283863 v4

The function does not have any parameters available in the local HMI or PCM600.

9.7.6 Operation principle SEMOD55861-5 v7

When receiving the input signals, DPGAPC sends the signals over IEC 61850-8-1 to the systems,
equipment or functions that requests and thus subscribes on these signals. To be able to get
the signals into other systems, equipment or functions, one must use other tools, described in
the Engineering manual, and define which function block in which systems, equipment or
functions should receive this information.

More specifically, DPGAPC function reports a combined double point position indication
output POSITION, by evaluating the value and the timestamp attributes of the inputs OPEN
and CLOSE, together with the logical input signal VALID.

When the input signal VALID is active, the values of the OPEN and CLOSE inputs determine the
two-bit integer value of the output POSITION. The timestamp of the output POSITION will have
the latest updated timestamp of the inputs OPEN and CLOSE.

280 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

When the input signal VALID is inactive, DPGAPC function forces the position to intermediated
state.

When the value of the input signal VALID changes, the timestamp of the output POSITION will
be updated as the time when DPGAPC function detects the change.

Refer to Table 188 for the description of the input-output relationship in terms of the value
and the quality attributes.

Table 188: Description of the input-output relationship


POSITION
VALID OPEN CLOSE
Value Description
0 - - 0 Intermediate
1 0 0 0 Intermediate
1 1 0 1 Open
1 0 1 2 Closed
1 1 1 3 Bad State

9.8 Single point generic control 8 signals SPC8GAPC SEMOD176448-1 v3

9.8.1 Identification
SEMOD176456-2 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Single point generic control 8 signals SPC8GAPC - -

9.8.2 Functionality SEMOD176462-4 v11

The Single point generic control 8 signals (SPC8GAPC) function block is a collection of 8 single
point commands that can be used for direct commands for example reset of LEDs or putting
IED in "ChangeLock" state from remote. In this way, simple commands can be sent directly to
the IED outputs, without confirmation. Confirmation (status) of the result of the commands is
supposed to be achieved by other means, such as binary inputs and SPGAPC function blocks.
The commands can be pulsed or steady with a settable pulse time.

9.8.3 Function block SEMOD176479-4 v5

SPC8GAPC
BLOCK ^OUT1
PSTO ^OUT2
^OUT3
^OUT4
^OUT5
^OUT6
^OUT7
^OUT8

IEC07000143-3-en.vsd
IEC07000143 V3 EN-US

Figure 152: SPC8GAPC function block

Breaker protection REQ650 281


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

9.8.4 Signals
PID-3575-INPUTSIGNALS v8

Table 189: SPC8GAPC Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Blocks the function operation
PSTO INTEGER 1 Operator place selection

PID-3575-OUTPUTSIGNALS v8

Table 190: SPC8GAPC Output signals


Name Type Description
OUT1 BOOLEAN Command output 1
OUT2 BOOLEAN Command output 2
OUT3 BOOLEAN Command output 3
OUT4 BOOLEAN Command output 4
OUT5 BOOLEAN Command output 5
OUT6 BOOLEAN Command output 6
OUT7 BOOLEAN Command output 7
OUT8 BOOLEAN Command output 8

9.8.5 Settings
PID-3575-SETTINGS v8

Table 191: SPC8GAPC Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
PulseMode1 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 1
tPulse1 0.01 - 6000.00 s 0.01 0.10 Pulse time output 1
PulseMode2 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 2
tPulse2 0.01 - 6000.00 s 0.01 0.10 Pulse time output 2
PulseMode3 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 3
tPulse3 0.01 - 6000.00 s 0.01 0.10 Pulse time output 3
PulseMode4 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 4
tPulse4 0.01 - 6000.00 s 0.01 0.10 Pulse time output 4
PulseMode5 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 5
tPulse5 0.01 - 6000.00 s 0.01 0.10 Pulse time output 5
PulseMode6 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 6
tPulse6 0.01 - 6000.00 s 0.01 0.10 Pulse time output 6
PulseMode7 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 7
Table continues on next page

282 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

Name Values (Range) Unit Step Default Description


tPulse7 0.01 - 6000.00 s 0.01 0.10 Pulse time output 7
PulseMode8 Pulsed - - Pulsed Setting for pulsed/latched mode for
Latched output 8
tPulse8 0.01 - 6000.00 s 0.01 0.10 Pulse time output 8

9.8.6 Operation principle SEMOD176471-4 v7

The PSTO input selects the operator place (LOCAL, REMOTE or ALL). One of the eight outputs
is activated based on the command sent from the operator place selected. The settings
Latchedx and tPulsex (where x is the respective output) will determine if the signal will be
pulsed (and how long the pulse is) or latched (steady). BLOCK will block the operation of the
function – in case a command is sent, no output will be activated.

PSTO is the universal operator place selector for all control functions. Although,
PSTO can be configured to use LOCAL or ALL operator places, only REMOTE
operator place is used in SPC8GAPC function.

9.9 AutomationBits, command function for DNP3.0


AUTOBITS SEMOD158589-1 v3

9.9.1 Identification
GUID-C3BB63F5-F0E7-4B00-AF0F-917ECF87B016 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
AutomationBits, command function
AUTOBITS - -
for DNP3

9.9.2 Functionality SEMOD158591-5 v8

Automation bits function for DNP3 (AUTOBITS) is used within PCM600 to get into the
configuration of the commands coming through the DNP3 protocol. The AUTOBITS function
plays the same role as functions GOOSEBINRCV (for IEC 61850) and MULTICMDRCV (for LON).

Breaker protection REQ650 283


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

9.9.3 Function block SEMOD158603-4 v3

AUTOBITS
BLOCK ^CMDBIT1
PSTO ^CMDBIT2
^CMDBIT3
^CMDBIT4
^CMDBIT5
^CMDBIT6
^CMDBIT7
^CMDBIT8
^CMDBIT9
^CMDBIT10
^CMDBIT11
^CMDBIT12
^CMDBIT13
^CMDBIT14
^CMDBIT15
^CMDBIT16
^CMDBIT17
^CMDBIT18
^CMDBIT19
^CMDBIT20
^CMDBIT21
^CMDBIT22
^CMDBIT23
^CMDBIT24
^CMDBIT25
^CMDBIT26
^CMDBIT27
^CMDBIT28
^CMDBIT29
^CMDBIT30
^CMDBIT31
^CMDBIT32

IEC09000925-1-en.vsd
IEC09000925 V1 EN-US

Figure 153: AUTOBITS function block

9.9.4 Signals
PID-3776-INPUTSIGNALS v6

Table 192: AUTOBITS Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
PSTO INTEGER 0 Operator place selection

PID-3776-OUTPUTSIGNALS v6

Table 193: AUTOBITS Output signals


Name Type Description
CMDBIT1 BOOLEAN Command out bit 1
CMDBIT2 BOOLEAN Command out bit 2
CMDBIT3 BOOLEAN Command out bit 3
CMDBIT4 BOOLEAN Command out bit 4
CMDBIT5 BOOLEAN Command out bit 5
CMDBIT6 BOOLEAN Command out bit 6
CMDBIT7 BOOLEAN Command out bit 7
CMDBIT8 BOOLEAN Command out bit 8
CMDBIT9 BOOLEAN Command out bit 9
CMDBIT10 BOOLEAN Command out bit 10
Table continues on next page

284 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

Name Type Description


CMDBIT11 BOOLEAN Command out bit 11
CMDBIT12 BOOLEAN Command out bit 12
CMDBIT13 BOOLEAN Command out bit 13
CMDBIT14 BOOLEAN Command out bit 14
CMDBIT15 BOOLEAN Command out bit 15
CMDBIT16 BOOLEAN Command out bit 16
CMDBIT17 BOOLEAN Command out bit 17
CMDBIT18 BOOLEAN Command out bit 18
CMDBIT19 BOOLEAN Command out bit 19
CMDBIT20 BOOLEAN Command out bit 20
CMDBIT21 BOOLEAN Command out bit 21
CMDBIT22 BOOLEAN Command out bit 22
CMDBIT23 BOOLEAN Command out bit 23
CMDBIT24 BOOLEAN Command out bit 24
CMDBIT25 BOOLEAN Command out bit 25
CMDBIT26 BOOLEAN Command out bit 26
CMDBIT27 BOOLEAN Command out bit 27
CMDBIT28 BOOLEAN Command out bit 28
CMDBIT29 BOOLEAN Command out bit 29
CMDBIT30 BOOLEAN Command out bit 30
CMDBIT31 BOOLEAN Command out bit 31
CMDBIT32 BOOLEAN Command out bit 32

9.9.5 Settings
PID-3776-SETTINGS v6

Table 194: AUTOBITS Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On

9.9.6 Operation principle SEMOD158597-4 v5

AutomationBits function (AUTOBITS) has 32 individual outputs which each can be mapped as a
Binary Output point in DNP3. The output is operated by a "Object 12" in DNP3. This object
contains parameters for control-code, count, on-time and off-time. To operate an AUTOBITS
output point, send a control-code of latch-On, latch-Off, pulse-On, pulse-Off, Trip or Close. The
remaining parameters will be regarded were appropriate. ex: pulse-On, on-time=100, off-
time=300, count=5 would give 5 positive 100 ms pulses, 300 ms apart.

There is a BLOCK input signal, which will disable the operation of the function, in the same way
the setting Operation: On/Off does. That means that, upon activation of the BLOCK input, all
32 CMDBITxx outputs will be set to 0. The BLOCK acts like an overriding, the function still
receives data from the DNP3 master. Upon deactivation of BLOCK, all the 32 CMDBITxx
outputs will be set by the DNP3 master again, momentarily. For AUTOBITS , the PSTO input

Breaker protection REQ650 285


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 9 1MRK 505 384-UEN C
Control

determines the operator place. The command can be written to the block while in “Remote”. If
PSTO is in “Local” then no change is applied to the outputs.

9.10 Single command, 16 signals SINGLECMD SEMOD119849-1 v2

9.10.1 Identification
GUID-2217CCC2-5581-407F-A4BC-266CD6808984 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Single command, 16 signals SINGLECMD - -

9.10.2 Functionality M12446-6 v5

The IEDs can receive commands either from a substation automation system or from the local
HMI. The command function block has outputs that can be used, for example, to control high
voltage apparatuses or for other user defined functionality.

9.10.3 Function block SEMOD116040-4 v2

SINGLECMD
BLOCK ^OUT1
^OUT2
^OUT3
^OUT4
^OUT5
^OUT6
^OUT7
^OUT8
^OUT9
^OUT10
^OUT11
^OUT12
^OUT13
^OUT14
^OUT15
^OUT16

IEC05000698-2-en.vsd
IEC05000698 V3 EN-US

Figure 154: SINGLECMD function block

9.10.4 Signals
PID-6189-INPUTSIGNALS v7

Table 195: SINGLECMD Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block single command function

286 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 9
Control

PID-6189-OUTPUTSIGNALS v7

Table 196: SINGLECMD Output signals


Name Type Description
OUT1 BOOLEAN Single command output 1
OUT2 BOOLEAN Single command output 2
OUT3 BOOLEAN Single command output 3
OUT4 BOOLEAN Single command output 4
OUT5 BOOLEAN Single command output 5
OUT6 BOOLEAN Single command output 6
OUT7 BOOLEAN Single command output 7
OUT8 BOOLEAN Single command output 8
OUT9 BOOLEAN Single command output 9
OUT10 BOOLEAN Single command output 10
OUT11 BOOLEAN Single command output 11
OUT12 BOOLEAN Single command output 12
OUT13 BOOLEAN Single command output 13
OUT14 BOOLEAN Single command output 14
OUT15 BOOLEAN Single command output 15
OUT16 BOOLEAN Single command output 16

9.10.5 Settings
PID-6189-SETTINGS v7

Table 197: SINGLECMD Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
Steady
Pulsed

9.10.6 Operation principle M12447-3 v3

Single command, 16 signals (SINGLECMD) function has 16 binary output signals. The outputs
can be individually controlled from a substation automation system or from the local HMI.
Each output signal can be given a name with a maximum of 13 characters in PCM600.

The output signals can be of the types Off, Steady, or Pulse. This configuration setting is done
via the local HMI or PCM600 and is common for the whole function block. The length of the
output pulses are 100 ms. In steady mode, SINGLECMD function has a memory to remember
the output values at power interruption of the IED. Also a BLOCK input is available used to
block the updating of the outputs.

The output signals, OUT1 to OUT16, are available for configuration to built-in functions or via
the configuration logic circuits to the binary outputs of the IED.

Breaker protection REQ650 287


Technical manual
© Copyright 2017 ABB. All rights reserved
288
1MRK 505 384-UEN C Section 10
Logic

Section 10 Logic
10.1 Tripping logic SMPPTRC IP14576-1 v4

10.1.1 Identification
SEMOD56226-2 v7

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Tripping logic SMPPTRC 94

1 -> 0
IEC15000314 V1 EN-US

10.1.2 Functionality M12275-3 v14

A function block for protection tripping and general start indication is always provided as a
basic function for each circuit breaker. It provides a settable pulse prolongation time to ensure
a trip pulse of sufficient length, as well as all functionality necessary for correct co-operation
with autoreclosing functions.

The trip function block includes a settable latch function for the trip signal and circuit breaker
lockout.

The trip function can collect start and directional signals from different application functions.
The aggregated start and directional signals are mapped to the IEC 61850 logical node data
model.

10.1.3 Function block M12638-3 v7

SMPPTRC
BLOCK TRIP
BLKLKOUT TRL1
TRIN TRL2
TRINL1 TRL3
TRINL2 TR1P
TRINL3 TR2P
PSL1 TR3P
PSL2 CLLKOU T
PSL3 START
1PTRZ STL1
1PTREF STL2
P3PTR STL3
SETLKOUT STN
RSTLKOUT FW
STDI R REV
IEC05000707-4-en.vsdx
IEC05000707 V4 EN-US

Figure 155: SMPPTRC function block

Breaker protection REQ650 289


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 505 384-UEN C
Logic

10.1.4 Signals
GUID-2918ECA6-4D98-493F-A33C-2D33DE64AE3B v1

Table 198: SMPPTRC Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
BLKLKOUT BOOLEAN 0 Blocks circuit breaker lockout output (CLLKOUT)
TRIN BOOLEAN 0 Trip all phases
TRINL1 BOOLEAN 0 Trip phase L1
TRINL2 BOOLEAN 0 Trip phase L2
TRINL3 BOOLEAN 0 Trip phase L3
PSL1 BOOLEAN 0 Functional input for phase selection in phase L1
PSL2 BOOLEAN 0 Functional input for phase selection in phase L2
PSL3 BOOLEAN 0 Functional input for phase selection in phase L3
1PTRZ BOOLEAN 0 Input for phase selective carrier aided trip
1PTREF BOOLEAN 0 Input for phase selective earth fault trip
P3PTR BOOLEAN 0 Prepare all tripping to be three-phase
SETLKOUT BOOLEAN 0 Input for setting the circuit breaker lockout function
RSTLKOUT BOOLEAN 0 Input for resetting the circuit breaker lockout function
STDIR INTEGER 0 General start direction input

GUID-D6B3DFE3-F7DF-4602-B57E-764DC9EB0D4A v1

Table 199: SMPPTRC Output signals


Name Type Description
TRIP BOOLEAN General trip output signal
TRL1 BOOLEAN Trip signal from phase L1
TRL2 BOOLEAN Trip signal from phase L2
TRL3 BOOLEAN Trip signal from phase L3
TR1P BOOLEAN Trip single-pole
TR2P BOOLEAN Trip two-pole
TR3P BOOLEAN Trip three-pole
CLLKOUT BOOLEAN Circuit breaker lockout output (set until reset)
START BOOLEAN General start signal
STL1 BOOLEAN Start signal from phase L1
STL2 BOOLEAN Start signal from phase L2
STL3 BOOLEAN Start signal from phase L3
STN BOOLEAN Start signal from neutral
FW BOOLEAN General forward signal
REV BOOLEAN General reverse signal

290 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 10
Logic

10.1.5 Settings
GUID-6D6424B9-B676-4D9B-949A-33C74BDC5711 v1

Table 200: SMPPTRC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
Program 3 phase - - 1ph/3ph Three ph; single or three ph; single,
1ph/3ph two or three ph trip
1ph/2ph/3ph
tTripMin 0.000 - 60.000 s 0.001 0.150 Minimum duration of trip output
signal
tWaitForPHS 0.020 - 0.500 s 0.001 0.050 Secure 3-pole trip when phase
selection failed

Table 201: SMPPTRC Group settings (advanced)


Name Values (Range) Unit Step Default Description
TripLockout Off - - Off Latch TRIP output when SETLKOUT
On input is activated
AutoLock Off - - Off Activate CLLKOUT output when TRIP
On output is activated
tEvolvingFault 0.000 - 60.000 s 0.001 2.000 Secure 3-pole tripping at evolving
faults

10.1.6 Operation principle M12255-3 v12

The duration of the trip output signal is settable (tTripMin). The pulse length should be long
enough to secure the opening of the circuit breaker.

There is a single input (TRIN) through which all trip output signals from the protection
functions within the IED or from external protection functions via one or more of the IEDs'
binary inputs are routed. It has a single three-phase trip output (TRIP) to connect to one or
more of the IEDs' binary outputs, as well as to other functions within the IED requiring this
signal.

Breaker protection REQ650 291


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 505 384-UEN C
Logic

Simplified logic where setting


Program = 3 phase
BLKLKOUT

Final Tripping Circuits


3 phase BLKLKOUT TRIP
TRIP
BLOCK TRL1
BLOCK TRIPALL TRIPALL TRL1
TRIN TRL2
TRIN TRIPL1 TRL2
TRINL1 TRL3
TRINL1 TRIPL2 TRL3
TRINL2
TRINL2 TRIPL3 TR1P
TRINL3
TRINL3 SETLKOUT TR2P
1PTRZ TR3P
1PTRZ RSTLKOUT TR3P
1PTREF CLLKOUT
1PTREF CLLKOUT

SETLKOUT
RSTLKOUT

Simplified logic where setting


Program = 1ph/3ph
BLKLKOUT
Final Tripping Circuits
BLOCK
TRIP
BLKLKOUT TRIP
1ph/3ph TRL1
TRIPALL TRL1
Phase Segregated TRL2
BLOCK TRIPL1 TRIPL1 TRL2
TRIN TRL3
TRIN L1TRIP L1TRIP TRIPL2 TRIPL2 TRL3
TRINL1 TR1P
TRINL1 L2TRIP L2TRIP TRIPL3 TRIPL3 TR1P
TRINL2
TRINL2 L3TRIP L3TRIP SETLKOUT TR2P
TRINL3 TR3P
TRINL3 P3PTR RSTLKOUT TR3P
PSL1 CLLKOUT
PSL1 CLLKOUT
PSL2
PSL2
PSL3
PSL3
1PTRZ
1PTRZ
1PTREF
1PTREF

P3PTR
SETLKOUT
RSTLKOUT

Simplified logic where setting


Program = 1ph/2ph/3ph
BLKLKOUT
Final Tripping Circuits
BLOCK
TRIP
BLKLKOUT TRIP
1ph/2ph/3ph TRL1
TRIPALL TRL1
Phase Segregated BLOCK TRIPL1 TRL2
TRIPL1 TRL2
TRIN TRL3
TRIN L1TRIP L1TRIP TRIPL2 TRIPL2 TRL3
TRINL1 TR1P
TRINL1 L2TRIP L2TRIP TRIPL3 TRIPL3 TR1P
TRINL2 TR2P
TRINL2 L3TRIP L3TRIP SETLKOUT TR2P
TRINL3 P3PTR TR3P
TRINL3 RSTLKOUT TR3P
PSL1 CLLKOUT
PSL1 CLLKOUT
PSL2
PSL2
PSL3
PSL3
1PTRZ
1PTRZ
1PTREF
1PTREF

P3PTR
SETLKOUT
RSTLKOUT

IEC10000266=2=en=Original.vsdx

IEC10000266 V2 EN-US

Figure 156: Simplified logic diagrams with different program modes


SMPPTRC function has separate inputs (TRINL1, TRINL2, TRINL3) which are used for single-
phase and two-phase tripping from the functions which offer phase segregated trip outputs.

The inputs 1PTRZ and 1PTREF enable single- phase and two-phase tripping for those functions
which do not have their own phase selection capability (i.e. which have just a single trip
output). An example of such a protection function is the residual overcurrent protection. The
SMPPTRC function has two inputs for these functions, one for impedance tripping (1PTRZ
used for carrier-aided tripping commands from the scheme communication logic), and one for
earth fault tripping (1PTREF used for tripping from a residual overcurrent protection). External
phase selection for these two trip signals shall be provided via inputs PSL1, PSL2 and PSL3.

292 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 10
Logic

A timer tWaitForPHS, secures a three-phase trip command for these two trip signals in the
absence of the external phase selection signals.

The SMPPTRC function has three trip outputs TRL1, TRL2, TRL3 (besides the three-phase trip
output TRIP), one per phase, to connect to one or more of the IEDs’ binary outputs, as well as
to other functions within the IED requiring these signals. These three output signals shall be
used as trip signals for individual circuit breaker poles. These signals are important for
cooperation with the autorecloser SMBRREC function.

The SMPPTRC function is equipped with logic which secures correct operation for evolving
faults as well as for reclosing on to persistent faults. A binary input P3PTR is provided which
will force all tripping to be three-phase. This input is required in order to cooperate with the
SMBRREC function.

In multi-breaker arrangements, one SMPPTRC function block is used for each circuit breaker.

The lockout function


A tripped circuit breaker can be locked out and prevented from closing by the output close
lockout (CLLKOUT). The reset lockout (RSTLKOUT) is the input for deactivating and resetting
the output close lockout CLLKOUT.

CLLKOUT can be set by an external trip signal from another protection function via the input
SETLKOUT or internally via a three-phase trip with the setting AutoLock = On. If CLLKOUT is
set by an external trip signal from another protection function and setting TripLockout = On,
all trip outputs are set true.

The BLKLKOUT input blocks the circuit breaker lockout output CLLKOUT.

Directional data
Merged directional data from application functions can be provided to the trip function
(SMPPTRC) via the start matrix function (SMAGAPC) connected to the STDIR input.

The directional input signal STDIR is a coded integer signal which may contain up to 14
individual Boolean signals; see Figure 161:

STDIRX=[b0, b1, b2, b3, b4, b5, b6, b7, b8, b9, b10, b11, b12, b13, b14]
b0= START (start)
b1= FW (forward)
b2= REV (reverse)
b3= STL1 (start L1)
b4= FWL1 (forward L1)
b5= REVL1 (reverse L1)
b6= STL2 (start L2)
b7= FWL2 (forward L2)
b8= REVL2 (reverse L2)
b9= STL3 (start L3)
b10= FWL3 (forward L3)
b11= REVL3 (reverse L3)
b12= STN (start N)
b13= FWN (forward N)
b14= REVN (reverse N)

Breaker protection REQ650 293


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 505 384-UEN C
Logic

The indications for general start START and phase-wise starts STL1, STL2 and STL3, and
neutral STN and general directional forward FW and reverse REV are all available as outputs on
the trip function.

All start and directional outputs are mapped to the IEC 61850 logical node data model of the
trip function. The time stamping is updated each time an operate or start signal is changed:

• The common DIR output (general) is mapped as:

dirGeneral
0 unknown
1 forward
2 backward (reverse)
3 both
• The phase wise directional outputs (DIRL1, DIRL2, DIRL3 and DIRN) are mapped as:

dirPhsA, dirPhsB, dirPhsC, dirNeut


0 unknown
1 forward
2 backward (reverse)

10.1.6.1 Logic diagram M12258-7 v6

tTripMin
BLOCK TRIPALL
OR
AND t

TRINL1
TRINL2
TRINL3
TRIN OR
1PTREF
1PTRZ

IEC05000517=4=en=Original..vsdx
IEC05000517 V4 EN-US

Figure 157: Three-phase front logic — simplified logic diagram

294 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 10
Logic

TRIN
TRINL1
L1TRIP
OR
PSL1
AND

TRINL2
L2TRIP
OR
PSL2
AND

TRINL3
L3TRIP
OR
PSL3
AND

-LOOP

OR OR
OR

AND
AND

OR
tWaitForPHS
-LOOP t

OR

1PTREF AND
AND

1PTRZ OR

IEC10000056=4=en=Original.vsdx

IEC10000056 V4 EN-US

Figure 158: Phase segregated front logic

tTripMin
BLOCK
OR TRIPL1
L1TRIP AND t OR

tEvolvingFault

t TRIP
AND

L2TRIP
L3TRIP
OR
P3PTR

IEC17000065-2-en.vsdx

IEC17000065 V2 EN-US

Figure 159: Simplified additional logic per phase, Program = 1ph/3ph or 1ph/2ph/3ph

Breaker protection REQ650 295


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 505 384-UEN C
Logic

BLKLKOUT

TRIPL1
TRL1
OR

TRIPL2
TRL2
OR

TRIPL3
TRL3
OR

TRIP
TRIPALL OR
OR
-LOOP

OR
AND
TR3P
AND

10 ms To ensure that the


AND fault is single phase TR1P
t

OR 5 ms To ensure that the


fault is two phase TR2P
t

AND

AND

AND OR
OR

-LOOP
AND

-LOOP
AND
AutoLock
CLKLKOUT
OR AND
SETLKOUT OR AND
3ms
RSTLKOUT t

AND
TripLockout

-LOOP

IEC17000066=1=en=Original.vsdx

IEC17000066 V1 EN-US

Figure 160: Final tripping circuits

Directional logic
IntToBits
STDIR START START
in b0
FW STL1
b1
REV STL2
b2
STL1 STL3
b3
FWL1 STN
b4
REVL1
b5
STL2
b6
FWL2 FW
b7
REVL2 BitsToInt
b8 dirGeneral (61850 Standard)
STL3
b9 0 = unknown
FWL3 b0 out
b10 DIR 1 = forward
REVL3 b1 2 = backward (reverse)
b11
STN 3 = both
b12
FWN REV
b13
REVN
b14
b15

BitsToInt dirPhsA (61850 Standard)


0 = unknown
AND b0 out DIRL1
b0 = START 1 = forward
b1 2 = backward (reverse)
b1 = FW
b2 = REV
b3 = STL1 XOR
b4 = FWL1
b5 = REVL1
b6 = STL2 AND
b7 = FWL2
b8 = REVL2
b9 = STL3 BitsToInt dirPhsB (61850 Standard)
b10 = FWL3
0 = unknown
b11 = REVL3 AND b0 out DIRL2
1 = forward
b12 = STN b1 2 = backward (reverse)
b13 = FWN
b14 = REVN
b15 = N/A XOR

AND

BitsToInt dirPhsC (61850 Standard)


0 = unknown
AND b0 out DIRL3
1 = forward
b1 2 = backward (reverse)

XOR

AND

BitsToInt dirNeut (61850 Standard)


0 = unknown
AND b0 out DIRN
1 = forward
b1 2 = backward (reverse)

XOR

AND

IEC16000179-2-en.vsdx

IEC16000179 V2 EN-US

Figure 161: The directional logic

296 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 10
Logic

10.1.7 Technical data


M12380-1 v14

Table 202: SMPPTRC technical data


Function Range or value Accuracy
Trip action 3-ph, 1/3-ph, 1/2/3-ph -
Minimum trip pulse length (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
3-pole trip delay (0.020-0.500) s ±0.2% or ±15 ms whichever is greater
Evolving fault delay (0.000-60.000) s ±0.2% or ±15 ms whichever is greater

10.2 General start matrix block SMAGAPC

10.2.1 Identification GUID-C6D3DE50-03D2-4F27-82FF-623E81D019F4 v1

Function Description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Generat start matrix block SMAGAPC - -

10.2.2 Functionality GUID-BA516165-96DE-4CD9-979B-29457C7653C0 v3

The Start Matrix (SMAGAPC) merges start and directional output signals from different
application functions and creates a common start and directional output signal (STDIR) to be
connected to the Trip function, see Figure 162.

The purpose of this functionality is to provide general start and directional information for the
IEC 61850 trip logic data model SMPPTRC.

10.2.3 Function block GUID-99B1DF71-F7C4-4954-8688-BC709C3C2A16 v1

SMAGAPC
BLOCK STDIR
STDIR1
STDIR2
STDIR3
STDIR4
STDIR5
STDIR6
STDIR7
STDIR8
STDIR9
STDIR10
STDIR11
STDIR12
STDIR13
STDIR14
STDIR15
STDIR16

IEC16000165-1-en.vsdx
IEC16000165 V1 EN-US

Figure 162: SMAGAPC function block

Breaker protection REQ650 297


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 505 384-UEN C
Logic

10.2.4 Signals
PID-6906-INPUTSIGNALS v2

Table 203: SMAGAPC Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
STDIR1 INTEGER 0 Start direction input 1
STDIR2 INTEGER 0 Start direction input 2
STDIR3 INTEGER 0 Start direction input 3
STDIR4 INTEGER 0 Start direction input 4
STDIR5 INTEGER 0 Start direction input 5
STDIR6 INTEGER 0 Start direction input 6
STDIR7 INTEGER 0 Start direction input 7
STDIR8 INTEGER 0 Start direction input 8
STDIR9 INTEGER 0 Start direction input 9
STDIR10 INTEGER 0 Start direction input 10
STDIR11 INTEGER 0 Start direction input 11
STDIR12 INTEGER 0 Start direction input 12
STDIR13 INTEGER 0 Start direction input 13
STDIR14 INTEGER 0 Start direction input 14
STDIR15 INTEGER 0 Start direction input 15
STDIR16 INTEGER 0 Start direction input 16

PID-6906-OUTPUTSIGNALS v2

Table 204: SMAGAPC Output signals


Name Type Description
STDIR INTEGER Common start direction output

10.2.5 Settings
PID-6906-SETTINGS v2

Table 205: SMAGAPC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On

10.2.6 Operation principle GUID-02403756-5715-4D6B-9308-540D72979BD0 v3

Start matrix
The Start Matrix function requires that a protection function delivers the directional output
signals in a fixed order to Start Matrix.

A directional input signal STDIRX of the Start Matrix is of type word. Each input contains 14
individual Boolean signals, which are positioned as, see Figure 164.

298 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 10
Logic

STDIRX=[b0, b1, b2, b3, b4, b5, b6, b7, b8, b9, b10, b11, b12, b13, b14]
b0= START (start)
b1= FW (forward)
b2= REV (reverse)
b3= STL1 (startL1)
b4= FWL1 (forwardL1)
b5= REVL1 (reverseL1)
b6= STL2 (startL2)
b7= FWL2 (forwardL2)
b8= REVL2 (reverseL2)
b9= STL3 (startL3)
b10= FWL3 (forwardL3)
b11= REVL3 (reverseL3)
b12= STN (startN)
b13= FWN (forwardN)
b14= REVN (reverseN)

The StartMatrix function contains two function: the START criteria and the DIRECTION criteria,
see Figure 163.

The START criteria is to ensure that a forward and reverse signal shall come together with a
start signal to pass through the block. This is done individually for each protection function
connected to the StartMatrix via the STDIRX inputs, see Figure 164.

All STDIROUT signals are then connected via an OR gate, see Figure 163.

The DIRECTION criteria allow either forward or reverse (phase-wise forward FWLx or forward
neutral FWN or phase-wise reverse REVLx or reverse neutral REVN) to pass through to the
general STDIR output. If both forward and reverse are active phase-wise (e.g. REVLx=FWLx =
True) or at neutral (e.g. FWN = REVN = True) at the same time, none will be shown, see Figure
165.

Breaker protection REQ650 299


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 505 384-UEN C
Logic

SMAGAPC
(StartMatrix)

START Criteria
STDIR1
STDIRX STDIROUT

START Criteria
STDIR2
STDIRX STDIROUT

START Criteria
STDIR3
STDIRX STDIROUT
DIRECTION Criteria
STDIR
≥1 STDIRIN STDIR
START Criteria
STDIR4
STDIRX STDIROUT

START Criteria
STDIR5
STDIRX STDIROUT

START Criteria
STDIR6
STDIRX STDIROUT

START Criteria
STDIR7
STDIRX STDIROUT

START Criteria
STDIR8
STDIRX STDIROUT

START Criteria
STDIR9
STDIRX STDIROUT

START Criteria
STDIR10
STDIRX STDIROUT

START Criteria
STDIR11
STDIRX STDIROUT

START Criteria
STDIR12
STDIRX STDIROUT

START Criteria
STDIR13
STDIRX STDIROUT

START Criteria
STDIR14
STDIRX STDIROUT

START Criteria
STDIR15
STDIRX STDIROUT

START Criteria
STDIR16
STDIRX STDIROUT

IEC16000161-2-en.vsdx

IEC16000161 V2 EN-US

Figure 163: The StartMatrix function

300 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 10
Logic

START Criteria

START (in)
STL1 (in)
STL2 (in) ≥1 START (out)
STL3 (in)
IntToBits STN (in) BitsToint
STDIRX STDIROUT
in b0 START (in) STL1 (out) START (out) b0 out
b1 FW (in) STL2 (out) FW (out) b1
b2 REV (in) STL3 (out) REV (out) b2
b3 STL1 (in) STN (out) STL1 (out) b3
b4 FWL1 (in) FWL1 (out) b4
b5 REVL1 (in) REVL1 (out) b5
&
b6 STL2 (in) FW (in) STL2 (out) b6
b7 FWL2 (in) FWL2 (out) b7
≥1 FW (out)
b8 REVL2 (in) REVL2 (out) b8
b9 STL3 (in) STL3 (out) b9
b10 FWL3 (in) FWL3 (out) b10
b11 REVL3 (in) & REVL3 (out) b11
REV (in)
b12 STN (in) STN (out) b12
b13 FWN (in) ≥1 REV (out) FWN (out) b13
b14 REVN (in) REVN (out) b14
b15 N/A FALSE b15

& FWL1 (out)


FWL1 (in)

& REVL1 (out)


REVL1 (in)

& FWL2 (out)


FWL2 (in)

& REVL2 (out)


REVL2 (in)

& FWL3 (out)


FWL3 (in)

& REVL3 (out)


REVL3 (in)

& FWN (out)


FWN (in)

& REVN (out)


REVN (in)

IEC16000162-2-en.vsdx

IEC16000162 V2 EN-US

Figure 164: The START Criteria function

DIRECTION Criteria

START (in) START (out)


IntToBits STL1 (in) STL1 (out) BitsToint
STDIRIN STL2 (in) STL2 (out) STDIR
in b0 START (in) START (out) b0 out
STL3 (in) STL3 (out)
b1 FW (in) FW (out) b1
STN (in) STN (out)
b2 REV (in) REV (out) b2
b3 STL1 (in) STL1 (out) b3
FW (in)
b4 FWL1 (in) FWL1 (out) b4
b5 REVL1 (in) REVL1 (out) b5
≥1 FW (out)
b6 STL2 (in) STL2 (out) b6
b7 FWL2 (in) FWL2 (out) b7
b8 REVL2 (in) REVL2 (out) b8
b9 STL3 (in) STL3 (out) b9
REV (in)
b10 FWL3 (in) FWL3 (out) b10
b11 REVL3 (in) REVL3 (out) b11
≥1 REV (out)
b12 STN (in) STN (out) b12
b13 FWN (in) FWN (out) b13
b14 REVN (in) REVN (out) b14
b15 N/A FALSE b15
& FWL1 (out)

FWL1 (in)
=1
REVL1 (in)

& REVL1 (out)

& FWL2 (out)

FWL2 (in)
=1
REVL2 (in)

& REVL2 (out)

& FWL3 (out)

FWL3 (in)
=1
REVL3 (in)

& REVL3 (out)

& FWN (out)

FWN (in)
=1
REVN (in)

& REVN (out)

IEC16000163-2-en.vsdx

IEC16000163 V2 EN-US

Figure 165: The DIRECTION Criteria function

STARTCOMB
To make it possible to provide the directional information from a protection function, a
STARTCOMB block is used in between the application function and the Start Matrix function.

The STARTCOMB function has one block input and 14 Boolean inputs that convert the 14
Boolean inputs into a WORD output STDIR, see Figure 166.

Breaker protection REQ650 301


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 505 384-UEN C
Logic

STDIRX=[b0, b1, b2, b3, b4, b5, b6, b7, b8, b9, b10, b11, b12, b13, b14]
b0= START (start)
b1= FW (forward)
b2= REV (reverse)
b3= STL1 (startL1)
b4= FWL1 (forwardL1)
b5= REVL1 (reverseL1)
b6= STL2 (startL2)
b7= FWL2 (forwardL2)
b8= REVL2 (reverseL2)
b9= STL3 (startL3)
b10= FWL3 (forwardL3)
b11= REVL3 (reverseL3)
b12= STN (startN)
b13= FWN (forwardN)
b14= REVN (reverseN)

STARTCOMB
BLOCK STDI R
START
FW
REV
STL1
FWL1
REVL1
STL2
FWL2
REVL2
STL3
FWL3
REVL3
STN
FWN
REVN
IEC16000166-2-en.vsdx
IEC16000166 V2 EN-US

Figure 166: STARTCOMB

Protection functions
Some protection functions are provided with start and directional outputs, for example:

• Protection 1: General START, FW and REV


• Protection 2: Phase-wise STLx, FWLx and REVLx (where x = 1, 2 and 3)
• Protection 3: STN, FWN and REVN
• Protection 4: STDIR

Connection example
In Figure 167 below is an example how to connect start and directional signals from protection
functions via STARTCOMB and SMAGAPC to SMPPTRC.

Figure 167: Connection example of protection functions using STARTCOMB, SMAGAPC to


SMPPTRC

302 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 10
Logic

10.3 Trip matrix logic TMAGAPC IP15121-1 v4

10.3.1 Identification
SEMOD167882-2 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Trip matrix logic TMAGAPC - -

10.3.2 Functionality M15321-3 v13

The trip matrix logic (TMAGAPC) function is used to route trip signals and other logical output
signals to different output contacts on the IED.

The trip matrix logic function has 3 output signals and these outputs can be connected to
physical tripping outputs according to the specific application needs for settable pulse or
steady output.

10.3.3 Function block SEMOD54400-4 v6

TMAGAPC
BLOCK OUTPUT1
BLK1 OUTPUT2
BLK2 OUTPUT3
BLK3
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16
INPUT17
INPUT18
INPUT19
INPUT20
INPUT21
INPUT22
INPUT23
INPUT24
INPUT25
INPUT26
INPUT27
INPUT28
INPUT29
INPUT30
INPUT31
INPUT32

IEC13000197-1-en.vsd
IEC13000197 V1 EN-US

Figure 168: TMAGAPC function block

Breaker protection REQ650 303


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 505 384-UEN C
Logic

10.3.4 Signals
PID-6513-INPUTSIGNALS v4

Table 206: TMAGAPC Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
BLK1 BOOLEAN 0 Block of output 1
BLK2 BOOLEAN 0 Block of output 2
BLK3 BOOLEAN 0 Block of output 3
INPUT1 BOOLEAN 0 Binary input 1
INPUT2 BOOLEAN 0 Binary input 2
INPUT3 BOOLEAN 0 Binary input 3
INPUT4 BOOLEAN 0 Binary input 4
INPUT5 BOOLEAN 0 Binary input 5
INPUT6 BOOLEAN 0 Binary input 6
INPUT7 BOOLEAN 0 Binary input 7
INPUT8 BOOLEAN 0 Binary input 8
INPUT9 BOOLEAN 0 Binary input 9
INPUT10 BOOLEAN 0 Binary input 10
INPUT11 BOOLEAN 0 Binary input 11
INPUT12 BOOLEAN 0 Binary input 12
INPUT13 BOOLEAN 0 Binary input 13
INPUT14 BOOLEAN 0 Binary input 14
INPUT15 BOOLEAN 0 Binary input 15
INPUT16 BOOLEAN 0 Binary input 16
INPUT17 BOOLEAN 0 Binary input 17
INPUT18 BOOLEAN 0 Binary input 18
INPUT19 BOOLEAN 0 Binary input 19
INPUT20 BOOLEAN 0 Binary input 20
INPUT21 BOOLEAN 0 Binary input 21
INPUT22 BOOLEAN 0 Binary input 22
INPUT23 BOOLEAN 0 Binary input 23
INPUT24 BOOLEAN 0 Binary input 24
INPUT25 BOOLEAN 0 Binary input 25
INPUT26 BOOLEAN 0 Binary input 26
INPUT27 BOOLEAN 0 Binary input 27
INPUT28 BOOLEAN 0 Binary input 28
INPUT29 BOOLEAN 0 Binary input 29
INPUT30 BOOLEAN 0 Binary input 30
INPUT31 BOOLEAN 0 Binary input 31
INPUT32 BOOLEAN 0 Binary input 32

304 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 10
Logic

PID-6513-OUTPUTSIGNALS v4

Table 207: TMAGAPC Output signals


Name Type Description
OUTPUT1 BOOLEAN OR function betweeen inputs 1 to 16
OUTPUT2 BOOLEAN OR function between inputs 17 to 32
OUTPUT3 BOOLEAN OR function between inputs 1 to 32

10.3.5 Settings
PID-6513-SETTINGS v4

Table 208: TMAGAPC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
PulseTime 0.050 - 60.000 s 0.001 0.150 Output pulse time
OnDelay 0.000 - 60.000 s 0.001 0.000 Output on delay time
OffDelay 0.000 - 60.000 s 0.001 0.000 Output off delay time
ModeOutput1 Steady - - Steady Mode for output ,1 steady or pulsed
Pulsed
ModeOutput2 Steady - - Steady Mode for output 2, steady or pulsed
Pulsed
ModeOutput3 Steady - - Steady Mode for output 3, steady or pulsed
Pulsed

10.3.6 Operation principle SEMOD52537-5 v8

The trip matrix logic (TMAGAPC) block is provided with 32 input signals and 3 output signals.
The function block incorporates internal logic OR gates in order to provide grouping of
connected input signals to the three output signals from the function block.

Internal built-in OR logic is made in accordance with the following three rules:

1. when any one of first 16 inputs signals (INPUT1 to INPUT16) has logical value 1 the first
output signal (OUTPUT1) will get logical value 1.
2. when any one of second 16 inputs signals (INPUT17 to INPUT32) has logical value 1 the
second output signal (OUTPUT2) will get logical value 1.
3. when any one of all 32 input signals (INPUT1 to INPUT32) has logical value 1 the third
output signal (OUTPUT3) will get logical value 1.

By use of the settings ModeOutput1, ModeOutput2, ModeOutput3, PulseTime, OnDelay and


OffDelay the behavior of each output can be customized. The OnDelay is always active and will
delay the input to output transition by the set time. The ModeOutput for respective output
decides whether the output shall be steady with an drop-off delay as set by OffDelay or if it
shall give a pulse with duration set by PulseTime. Note that for pulsed operation and that the
inputs are connected in an OR-function, a new pulse will only be given on the output if all
related inputs are reset and then one is activated again. For steady operation the OffDelay will
start when all related inputs have reset. Detailed logical diagram is shown in figure 169

Breaker protection REQ650 305


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 505 384-UEN C
Logic

PulseTime

t
&
ModeOutput1=Pulsed
INPUT 1
OUTPUT 1
Ondelay Offdelay
&
³1
³1 t t
INPUT 16

PulseTime

t
&
ModeOutput2=Pulsed

INPUT 17
OUTPUT 2
Ondelay Offdelay
&
³1
³1 t t
INPUT 32

PulseTime
t
&

ModeOutput3=Pulsed

OUTPUT 3
Ondelay Offdelay
&
³1
³1 t t

IEC09000612-3-en.vsd
IEC09000612 V3 EN-US

Figure 169: Trip matrix internal logic


Output signals from TMAGAPC are typically connected to other logic blocks or directly to
output contacts in the IED. When used for direct tripping of the circuit breaker(s) the pulse
time shall be set to at least 0.150 seconds in order to obtain satisfactory minimum duration of
the trip pulse to the circuit breaker trip coils.

10.3.7 Technical data


GUID-3AB1EE95-51BF-4CC4-99BD-F4ECDAACB75A v3

Table 209: Number of TMAGAPC instances


Function Quantity with cycle time
3 ms 8 ms 100 ms
TMAGAPC 6 6 -

10.4 Logic for group alarm ALMCALH GUID-64EA392C-950F-486C-8D96-6E7736B592BF v1

10.4.1 Identification GUID-64EA392C-950F-486C-8D96-6E7736B592BF v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Logic for group alarm ALMCALH - -

10.4.2 Functionality GUID-16E60E27-F7A8-416D-8648-8174AAC49BB5 v4

The group alarm logic function (ALMCALH) is used to route several alarm signals to a common
indication, LED and/or contact, in the IED.

306 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 10
Logic

10.4.3 Function block GUID-EA192656-71DD-4D44-A1D5-96B1B4937971 v1

ALMCALH
BLOCK ALARM
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16

IEC13000181-1-en.vsd
IEC13000181 V1 EN-US

10.4.4 Signals
PID-6510-INPUTSIGNALS v5

Table 210: ALMCALH Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
INPUT1 BOOLEAN 0 Binary input 1
INPUT2 BOOLEAN 0 Binary input 2
INPUT3 BOOLEAN 0 Binary input 3
INPUT4 BOOLEAN 0 Binary input 4
INPUT5 BOOLEAN 0 Binary input 5
INPUT6 BOOLEAN 0 Binary input 6
INPUT7 BOOLEAN 0 Binary input 7
INPUT8 BOOLEAN 0 Binary input 8
INPUT9 BOOLEAN 0 Binary input 9
INPUT10 BOOLEAN 0 Binary input 10
INPUT11 BOOLEAN 0 Binary input 11
INPUT12 BOOLEAN 0 Binary input 12
INPUT13 BOOLEAN 0 Binary input 13
INPUT14 BOOLEAN 0 Binary input 14
INPUT15 BOOLEAN 0 Binary input 15
INPUT16 BOOLEAN 0 Binary input 16

PID-6510-OUTPUTSIGNALS v5

Table 211: ALMCALH Output signals


Name Type Description
ALARM BOOLEAN OR function betweeen inputs 1 to 16

Breaker protection REQ650 307


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 505 384-UEN C
Logic

10.4.5 Settings
PID-6510-SETTINGS v5

Table 212: ALMCALH Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On

10.4.6 Operation principle GUID-0405BB7B-7EF7-4546-92CD-F703AA0DD9F4 v2

The logic for group alarm ALMCALH block is provided with 16 input signals and one ALARM
output signal. The function block incorporates internal logic OR gate in order to provide
grouping of connected input signals to the output ALARM signal from the function block.

When any one of 16 input signals (INPUT1 to INPUT16) has logical value 1, the ALARM output
signal will get logical value 1.

The function has a drop-off delay of 200 ms when all inputs are reset to provide a steady
signal.

Input 1
200 ms
ALARM
³1 t
Input 16

IEC13000191-1-en.vsd
IEC13000191 V1 EN-US

Figure 170: Group alarm logic

10.4.7 Technical data


GUID-A05AF26F-DC98-4E62-B96B-E75D19F20767 v2

Table 213: Number of ALMCALH instances


Function Quantity with cycle time
3 ms 8 ms 100 ms
ALMCALH - - 5

10.5 Logic for group warning WRNCALH

10.5.1 Identification GUID-3EBD3D5B-F506-4557-88D7-DFC0BD21C690 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Logic for group warning WRNCALH - -

10.5.2 Functionality GUID-F7D9A012-3AD4-4D86-BE97-DF2A99BE5383 v4

The group warning logic function (WRNCALH) is used to route several warning signals to a
common indication, LED and/or contact, in the IED.

308 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 10
Logic

10.5.3 Function block GUID-C909E4FB-3F7A-47F7-8988-36B159E2C7B2 v1

WRNCALH
BLOCK WARNING
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16

IEC13000182-1-en.vsd
IEC13000182 V1 EN-US

10.5.4 Signals
PID-4127-INPUTSIGNALS v3

Table 214: WRNCALH Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
INPUT1 BOOLEAN 0 Binary input 1
INPUT2 BOOLEAN 0 Binary input 2
INPUT3 BOOLEAN 0 Binary input 3
INPUT4 BOOLEAN 0 Binary input 4
INPUT5 BOOLEAN 0 Binary input 5
INPUT6 BOOLEAN 0 Binary input 6
INPUT7 BOOLEAN 0 Binary input 7
INPUT8 BOOLEAN 0 Binary input 8
INPUT9 BOOLEAN 0 Binary input 9
INPUT10 BOOLEAN 0 Binary input 10
INPUT11 BOOLEAN 0 Binary input 11
INPUT12 BOOLEAN 0 Binary input 12
INPUT13 BOOLEAN 0 Binary input 13
INPUT14 BOOLEAN 0 Binary input 14
INPUT15 BOOLEAN 0 Binary input 15
INPUT16 BOOLEAN 0 Binary input 16

PID-4127-OUTPUTSIGNALS v3

Table 215: WRNCALH Output signals


Name Type Description
WARNING BOOLEAN OR function betweeen inputs 1 to 16

Breaker protection REQ650 309


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 505 384-UEN C
Logic

10.5.5 Settings
PID-4127-SETTINGS v3

Table 216: WRNCALH Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On

10.5.6 Operation principle GUID-71C65C20-7B6C-499F-BFCD-E418AA55F7EC v2

The logic for group warning WRNCALH block is provided with 16 input signals and 1 WARNING
output signal. The function block incorporates internal logic OR gate in order to provide
grouping of connected input signals to the output WARNING signal from the function block.

When any one of 16 input signals (INPUT1 to INPUT16) has logical value 1, the WARNING output
signal will get logical value 1.

The function has a drop-off delay of 200 ms when all inputs are reset to provide a steady
signal.

INPUT1
200 ms
WARNING
³1 t
INPUT16

IEC13000192-1-en.vsd
IEC13000192 V1 EN-US

10.5.7 Technical data


GUID-70B7357D-F467-4CF5-9F73-641A82D334F5 v2

Table 217: Number of WRNCALH instances


Function Quantity with cycle time
3 ms 8 ms 100 ms
WRNCALH - - 5

10.6 Logic for group indication INDCALH

10.6.1 Identification GUID-3B5D4371-420D-4249-B6A4-5A168920D635 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Logic for group indication INDCALH - -

10.6.2 Functionality GUID-D8D1A4EE-A87F-46C6-8529-277FC1ADA9B0 v4

The group indication logic function (INDCALH) is used to route several indication signals to a
common indication, LED and/or contact, in the IED.

310 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 10
Logic

10.6.3 Function block GUID-9D89E183-449A-4016-AB83-E57C8DDBA843 v1

INDCALH
BLOCK IND
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16

IEC13000183-1-en.vsd
IEC13000183 V1 EN-US

10.6.4 Signals
PID-4128-INPUTSIGNALS v4

Table 218: INDCALH Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
INPUT1 BOOLEAN 0 Binary input 1
INPUT2 BOOLEAN 0 Binary input 2
INPUT3 BOOLEAN 0 Binary input 3
INPUT4 BOOLEAN 0 Binary input 4
INPUT5 BOOLEAN 0 Binary input 5
INPUT6 BOOLEAN 0 Binary input 6
INPUT7 BOOLEAN 0 Binary input 7
INPUT8 BOOLEAN 0 Binary input 8
INPUT9 BOOLEAN 0 Binary input 9
INPUT10 BOOLEAN 0 Binary input 10
INPUT11 BOOLEAN 0 Binary input 11
INPUT12 BOOLEAN 0 Binary input 12
INPUT13 BOOLEAN 0 Binary input 13
INPUT14 BOOLEAN 0 Binary input 14
INPUT15 BOOLEAN 0 Binary input 15
INPUT16 BOOLEAN 0 Binary input 16

PID-4128-OUTPUTSIGNALS v4

Table 219: INDCALH Output signals


Name Type Description
IND BOOLEAN OR function betweeen inputs 1 to 16

Breaker protection REQ650 311


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 505 384-UEN C
Logic

10.6.5 Settings
PID-4128-SETTINGS v4

Table 220: INDCALH Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On

10.6.6 Operation principle GUID-72B1B4E8-BC6C-4AF7-8B41-058241B944F8 v2

The logic for group indication INDCALH block is provided with 16 input signals and 1 IND
output signal. The function block incorporates internal logic OR gate in order to provide
grouping of connected input signals to the output IND signal from the function block.

When any one of 16 input signals (INPUT1 to INPUT16) has logical value 1, the IND output signal
will get logical value 1.

The function has a drop-off delay of 200 ms when all inputs are reset to provide a steady
signal.

INPUT1
200 ms
IND
³1 t
INPUT16

IEC13000193-1-en.vsd
IEC13000193 V1 EN-US

10.6.7 Technical data


GUID-EAA43288-01A5-49CF-BF5B-9ABF6DC27D85 v2

Table 221: Number of INDCALH instances


Function Quantity with cycle time
3 ms 8 ms 100 ms
INDCALH - 5 -

10.7 Basic configurable logic blocks M11396-4 v18

The basic configurable logic blocks do not propagate the time stamp and quality of signals.
The list below shows a summary of the function blocks and their features.

These logic blocks are also available as part of an extension logic package.

• AND function block. The AND function is used to form general combinatory expressions
with boolean variables. The AND function block has up to four inputs and two outputs.
One of the outputs is inverted.

• GATE function block is used for whether or not a signal should be able to pass from the
input to the output.

• INVERTER function block that inverts the input signal to the output.

312 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 10
Logic

• LLD function block. Loop delay used to delay the output signal one execution cycle.

• OR function block. The OR function is used to form general combinatory expressions with
boolean variables. The OR function block has up to six inputs and two outputs. One of the
outputs is inverted.

• PULSETIMER function block can be used, for example, for pulse extensions or limiting of
operation of outputs, settable pulse time.

• RSMEMORY function block is a flip-flop that can reset or set an output from two inputs
respectively. Each block has two outputs where one is inverted. The memory setting
controls if, after a power interruption, the flip-flop resets or returns to the state it had
before the power interruption. RESET input has priority.

• SRMEMORY function block is a flip-flop that can set or reset an output from two inputs
respectively. Each block has two outputs where one is inverted. The memory setting
controls if, after a power interruption, the flip-flop resets or returns to the state it had
before the power interruption. The SET input has priority.

• TIMERSET function has pick-up and drop-out delayed outputs related to the input signal.
The timer has a settable time delay.

• XOR is used to generate combinatory expressions with boolean variables. XOR has two
inputs and two outputs. One of the outputs is inverted. The output signal OUT is 1 if the
input signals are different and 0 if they are the same.

10.7.1 AND function block AND IP11013-1 v2

M11453-3 v4
The AND function is used to form general combinatory expressions with boolean variables. The
AND function block has up to four inputs and two outputs. One of the outputs is inverted.

10.7.1.1 Function block


M11452-3 v2

AND
INPUT1 OUT
INPUT2 NOUT
INPUT3
INPUT4

IEC14000071-1-en.vsd
IEC14000071 V1 EN-US

Figure 171: AND function block

10.7.1.2 Signals
PID-3437-INPUTSIGNALS v7

Table 222: AND Input signals


Name Type Default Description
INPUT1 BOOLEAN 1 Input signal 1
INPUT2 BOOLEAN 1 Input signal 2
INPUT3 BOOLEAN 1 Input signal 3
INPUT4 BOOLEAN 1 Input signal 4

Breaker protection REQ650 313


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 505 384-UEN C
Logic

PID-3437-OUTPUTSIGNALS v7

Table 223: AND Output signals


Name Type Description
OUT BOOLEAN Output signal
NOUT BOOLEAN Inverted output signal

10.7.1.3 Technical data


GUID-D1179280-1D99-4A66-91AC-B7343DBA9F23 v3

Table 224: Number of AND instances


Logic block Quantity with cycle time
3 ms 8 ms 100 ms
AND 60 60 160

10.7.2 Controllable gate function block GATE IP11021-1 v2

M11489-3 v2
The Controllable gate function block (GATE) is used for controlling if a signal should be able to
pass from the input to the output or not depending on a setting.

10.7.2.1 Function block


M11490-3 v2

GATE
INPUT OUT

IEC04000410-2-en.vsd
IEC04000410 V2 EN-US

Figure 172: GATE function block

10.7.2.2 Signals
PID-3801-INPUTSIGNALS v6

Table 225: GATE Input signals


Name Type Default Description
INPUT BOOLEAN 0 Input to gate

PID-3801-OUTPUTSIGNALS v5

Table 226: GATE Output signals


Name Type Description
OUT BOOLEAN Output from gate

10.7.2.3 Settings
PID-3801-SETTINGS v6

Table 227: GATE Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On

314 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 10
Logic

10.7.2.4 Technical data


GUID-45DF373F-DC39-4E1B-B45B-6B454E8E0E50 v3

Table 228: Number of GATE instances


Logic block Quantity with cycle time
3 ms 8 ms 100 ms
GATE 10 10 20

10.7.3 Inverter function block INV IP11011-1 v2

10.7.3.1 Function block


M11445-3 v1

INV
INPUT OUT

IEC04000404_2_en.vsd
IEC04000404 V2 EN-US

Figure 173: INV function block

10.7.3.2 Signals
PID-3803-INPUTSIGNALS v5

Table 229: INV Input signals


Name Type Default Description
INPUT BOOLEAN 0 Input

PID-3803-OUTPUTSIGNALS v4

Table 230: INV Output signals


Name Type Description
OUT BOOLEAN Output

10.7.3.3 Technical data


GUID-0EC4192A-EF03-47C0-AEC1-09B68B411A98 v3

Table 231: Number of INV instances


Logic block Quantity with cycle time
3 ms 8 ms 100 ms
INV 90 90 240

10.7.4 Loop delay function block LLD GUID-05D959B5-A55B-437C-8E8F-831A4A357E24 v2

GUID-64B24094-010D-4B8F-8B7B-DDD49499AAE5 v3
The Logic loop delay function block (LLD) function is used to delay the output signal one
execution cycle, that is, the cycle time of the function blocks used.

Breaker protection REQ650 315


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 505 384-UEN C
Logic

10.7.4.1 Function block


GUID-EE44CFDF-C8F7-4870-BD1C-98D9CD91FD97 v4

LLD
INPUT OUT

IEC15000144.vsd
IEC15000144 V1 EN-US

Figure 174: LLD function block

10.7.4.2 Signals
PID-3805-INPUTSIGNALS v5

Table 232: LLD Input signals


Name Type Default Description
INPUT BOOLEAN 0 Input signal

PID-3805-OUTPUTSIGNALS v5

Table 233: LLD Output signals


Name Type Description
OUT BOOLEAN Output signal delayed one execution cycle

10.7.4.3 Technical data


GUID-B2E6F510-8766-4381-9618-CE02ED71FFB6 v2

Table 234: Number of LLD instances


Logic block Quantity with cycle time
3 ms 8 ms 100 ms
LLD 10 10 20

10.7.5 OR function block IP11012-1 v3

M11449-3 v2
The OR function is used to form general combinatory expressions with boolean variables. The
OR function block has up to six inputs and two outputs. One of the outputs is inverted.

10.7.5.1 Function block


M11448-3 v1

OR
INPUT1 OUT
INPUT2 NOUT
INPUT3
INPUT4
INPUT5
INPUT6

IEC04000405_2_en.vsd
IEC04000405 V2 EN-US

Figure 175: OR function block

316 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 10
Logic

10.7.5.2 Signals
PID-3806-INPUTSIGNALS v5

Table 235: OR Input signals


Name Type Default Description
INPUT1 BOOLEAN 0 Input 1 to OR gate
INPUT2 BOOLEAN 0 Input 2 to OR gate
INPUT3 BOOLEAN 0 Input 3 to OR gate
INPUT4 BOOLEAN 0 Input 4 to OR gate
INPUT5 BOOLEAN 0 Input 5 to OR gate
INPUT6 BOOLEAN 0 Input 6 to OR gate

PID-3806-OUTPUTSIGNALS v5

Table 236: OR Output signals


Name Type Description
OUT BOOLEAN Output from OR gate
NOUT BOOLEAN Inverted output from OR gate

10.7.5.3 Technical data


GUID-35A795D7-A6BD-4669-A023-43C497DBFB01 v4

Table 237: Number of OR instances


Logic block Quantity with cycle time
3 ms 8 ms 100 ms
OR 78 60 160

10.7.6 Pulse timer function block PULSETIMER IP11016-1 v2

M11466-3 v3
The pulse (PULSETIMER) function can be used, for example, for pulse extensions or limiting the
operation time of outputs. The PULSETIMER has a settable length. When the input is 1, the
output will be 1 for the time set by the time delay parameter t. Then it returns to 0.

10.7.6.1 Function block


M11465-3 v4

PULSETIMER
INPUT OUT

IEC04000407-3-en.vsd
IEC04000407 V3 EN-US

Figure 176: PULSETIMER function block

10.7.6.2 Signals
PID-6985-INPUTSIGNALS v1

Table 238: PULSETIMER Input signals


Name Type Default Description
INPUT BOOLEAN 0 Input to pulse timer

Breaker protection REQ650 317


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 505 384-UEN C
Logic

PID-6985-OUTPUTSIGNALS v1

Table 239: PULSETIMER Output signals


Name Type Description
OUT BOOLEAN Output from pulse timer

10.7.6.3 Settings
PID-6985-SETTINGS v1

Table 240: PULSETIMER Non group settings (basic)


Name Values (Range) Unit Step Default Description
t 0.000 - s 0.001 0.010 Time delay of function
90000.000

10.7.6.4 Technical data


GUID-E05E5FB1-23E7-4816-84F2-1FBFFDFF2B43 v2

Table 241: Number of PULSETIMER instances


Logic block Quantity with cycle time Range or Value Accuracy
3 ms 8 ms 100 ms
PULSETIMER 10 10 20 (0.000–90000.000) s ±0.5% ±10 ms

10.7.7 Reset-set with memory function block RSMEMORY GUID-9C93669F-078B-49EA-85B8-C4BB6A434734 v1

GUID-4C804DEA-3C83-4C20-82C6-BAD03BD48242 v4
The Reset-set with memory function block (RSMEMORY) is a flip-flop with memory that can
reset or set an output from two inputs respectively. Each RSMEMORY function block has two
outputs, where one is inverted. The memory setting controls if, after a power interruption, the
flip-flop resets or returns to the state it had before the power interruption. For a Reset-Set
flip-flop, RESET input has higher priority over SET input.

Table 242: Truth table for RSMEMORY function block


RESET SET OUT NOUT
0 0 Last Inverted last
value value
0 1 1 0
1 0 0 1
1 1 0 1

10.7.7.1 Function block


GUID-50D5A4C0-59BF-44DE-86AC-47640ACD35A7 v3

RSMEMORY
SET OUT
RESET NOUT

IEC09000294-1-en.vsd
IEC09000294 V1 EN-US

Figure 177: RSMEMORY function block

318 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 10
Logic

10.7.7.2 Signals
PID-3811-INPUTSIGNALS v5

Table 243: RSMEMORY Input signals


Name Type Default Description
SET BOOLEAN 0 Input signal to set
RESET BOOLEAN 0 Input signal to reset

PID-3811-OUTPUTSIGNALS v5

Table 244: RSMEMORY Output signals


Name Type Description
OUT BOOLEAN Output signal
NOUT BOOLEAN Inverted output signal

10.7.7.3 Settings
PID-3811-SETTINGS v5

Table 245: RSMEMORY Group settings (basic)


Name Values (Range) Unit Step Default Description
Memory Off - - On Operating mode of the memory
On function

10.7.7.4 Technical data


GUID-BE6FD540-E96E-4F15-B2A2-12FFAE6C51DB v2

Table 246: Number of RSMEMORY instances


Logic block Quantity with cycle time
3 ms 8 ms 100 ms
RSMEMORY 10 10 20

10.7.8 Set-reset with memory function block SRMEMORY IP11020-1 v2

M11485-3 v4
The Set-reset with memory function block (SRMEMORY) is a flip-flop with memory that can set
or reset an output from two inputs respectively. Each SRMEMORY function block has two
outputs, where one is inverted. The memory setting controls if, after a power interruption, the
flip-flop resets or returns to the state it had before the power interruption. The input SET has
priority.

Table 247: Truth table for SRMEMORY function block


SET RESET OUT NOUT
0 0 Last Inverted
value last value
0 1 0 1
1 0 1 0
1 1 1 0

Breaker protection REQ650 319


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 505 384-UEN C
Logic

10.7.8.1 Function block


M11484-3 v2

SRMEMORY
SET OUT
RESET NOUT

IEC04000408_2_en.vsd
IEC04000408 V2 EN-US

Figure 178: SRMEMORY function block

10.7.8.2 Signals
PID-3813-INPUTSIGNALS v5

Table 248: SRMEMORY Input signals


Name Type Default Description
SET BOOLEAN 0 Input signal to set
RESET BOOLEAN 0 Input signal to reset

PID-3813-OUTPUTSIGNALS v5

Table 249: SRMEMORY Output signals


Name Type Description
OUT BOOLEAN Output signal
NOUT BOOLEAN Inverted output signal

10.7.8.3 Settings
PID-3813-SETTINGS v5

Table 250: SRMEMORY Group settings (basic)


Name Values (Range) Unit Step Default Description
Memory Off - - On Operating mode of the memory
On function

10.7.8.4 Technical data


GUID-7A0F4327-CA83-4FB0-AB28-7C5F17AE6354 v2

Table 251: Number of SRMEMORY instances


Logic block Quantity with cycle time
3 ms 8 ms 100 ms
SRMEMORY 10 10 20

10.7.9 Settable timer function block TIMERSET IP11022-1 v2

M11494-3 v3
The Settable timer function block (TIMERSET) timer has two outputs for the delay of the input
signal at drop-out and at pick-up. The timer has a settable time delay. It also has an Operation
setting On and Off that controls the operation of the timer.

320 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 10
Logic

Input
tdelay
On

Off
tdelay

t
IEC08000289-2-en.vsd

IEC08000289 V2 EN-US

Figure 179: TIMERSET status diagram

10.7.9.1 Function block


M11495-3 v3

TIMERSET
INPUT ON
OFF

IEC04000411-2-en.vsd
IEC04000411 V2 EN-US

Figure 180: TIMERSET function block

10.7.9.2 Signals
PID-6976-INPUTSIGNALS v1

Table 252: TIMERSET Input signals


Name Type Default Description
INPUT BOOLEAN 0 Input to timer

PID-6976-OUTPUTSIGNALS v1

Table 253: TIMERSET Output signals


Name Type Description
ON BOOLEAN Output from timer, pick-up delayed
OFF BOOLEAN Output from timer, drop-out delayed

10.7.9.3 Settings
PID-6976-SETTINGS v1

Table 254: TIMERSET Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
t 0.000 - s 0.001 0.000 Delay for settable timer n
90000.000

Breaker protection REQ650 321


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 505 384-UEN C
Logic

10.7.9.4 Technical data


GUID-C6C98FE0-F559-45EE-B853-464516775417 v3

Table 255: Number of TIMERSET instances


Logic block Quantity with cycle time Range or Value Accuracy
3 ms 8 ms 100 ms
TIMERSET 15 15 30 (0.000–90000.000) s ±0.5% ±10 ms

10.7.10 Exclusive OR function block XOR IP11018-1 v2

M11477-3 v4
The exclusive OR function (XOR) is used to generate combinatory expressions with boolean
variables. XOR has two inputs and two outputs. One of the outputs is inverted. The output
signal OUT is 1 if the input signals are different and 0 if they are the same.

Table 256: Truth table for XOR function block


INPUT1 INPUT2 OUT NOUT
0 0 0 1
0 1 1 0
1 0 1 0
1 1 0 1

10.7.10.1 Function block


M11476-3 v1

XOR
INPUT1 OUT
INPUT2 NOUT

IEC04000409-2-en.vsd
IEC04000409 V2 EN-US

Figure 181: XOR function block

10.7.10.2 Signals
PID-3817-INPUTSIGNALS v2

Table 257: XOR Input signals


Name Type Default Description
INPUT1 BOOLEAN 0 Input 1 to XOR gate
INPUT2 BOOLEAN 0 Input 2 to XOR gate

PID-3817-OUTPUTSIGNALS v2

Table 258: XOR Output signals


Name Type Description
OUT BOOLEAN Output from XOR gate
NOUT BOOLEAN Inverted output from XOR gate

322 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 10
Logic

10.7.10.3 Technical data


GUID-0B07F78C-10BD-4070-AFF0-6EE36454AA03 v2

Table 259: Number of XOR instances


Logic block Quantity with cycle time
3 ms 8 ms 100 ms
XOR 10 10 20

10.8 Fixed signals FXDSIGN

10.8.1 Identification
SEMOD167904-2 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Fixed signals FXDSIGN - -

10.8.2 Functionality M15322-3 v15

The Fixed signals function (FXDSIGN) has nine pre-set (fixed) signals that can be used in the
configuration of an IED, either for forcing the unused inputs in other function blocks to a
certain level/value, or for creating certain logic. Boolean, integer, floating point, string types of
signals are available.

One FXDSIGN function block is included in all IEDs.

10.8.3 Function block SEMOD54909-4 v4

FXDSIGN
OFF
ON
INTZERO
INTONE
INTALONE
REALZERO
STRNULL
ZEROSMPL
GRP_OFF

IEC05000445-3-en.vsd
IEC05000445 V3 EN-US

Figure 182: FXDSIGN function block

10.8.4 Signals
PID-6191-OUTPUTSIGNALS v6

Table 260: FXDSIGN Output signals


Name Type Description
OFF BOOLEAN Boolean signal fixed off
ON BOOLEAN Boolean signal fixed on
INTZERO INTEGER Integer signal fixed zero
INTONE INTEGER Integer signal fixed one
Table continues on next page

Breaker protection REQ650 323


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 505 384-UEN C
Logic

Name Type Description


INTALONE INTEGER Integer signal fixed all ones
REALZERO REAL Real signal fixed zero
STRNULL STRING String signal with no characters
ZEROSMPL GROUP SIGNAL Channel id for zero sample
GRP_OFF GROUP SIGNAL Group signal fixed off

10.8.5 Settings
PID-1325-SETTINGS v12
The function does not have any settings available in Local HMI or Protection and Control IED
Manager (PCM600).

10.8.6 Operation principle SEMOD54827-5 v6

There are nine outputs from FXDSIGN function block:

• OFF is a boolean signal, fixed to OFF (boolean 0) value


• ON is a boolean signal, fixed to ON (boolean 1) value
• INTZERO is an integer number, fixed to integer value 0
• INTONE is an integer number, fixed to integer value 1
• INTALONE is an integer value FFFF (hex)
• REALZERO is a floating point real number, fixed to 0.0 value
• STRNULL is a string, fixed to an empty string (null) value
• ZEROSMPL is a channel index, fixed to 0 value
• GRP_OFF is a group signal, fixed to 0 value

10.9 Boolean 16 to Integer conversion B16I SEMOD175715-1 v1

10.9.1 Identification
SEMOD175721-2 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Boolean 16 to integer conversion B16I - -

10.9.2 Functionality SEMOD175725-4 v5

Boolean to integer conversion, 16 bit (B16I) is used to transform a set of 16 boolean (logical)
signals into an integer.

324 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 10
Logic

10.9.3 Function block SEMOD175798-5 v4

B16I
BLOCK OUT
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
IN9
IN10
IN11
IN12
IN13
IN14
IN15
IN16

IEC07000128-2-en.vsd
IEC07000128 V2 EN-US

Figure 183: B16I function block

10.9.4 Signals
PID-3606-INPUTSIGNALS v4

Table 261: B16I Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
IN1 BOOLEAN 0 Input 1
IN2 BOOLEAN 0 Input 2
IN3 BOOLEAN 0 Input 3
IN4 BOOLEAN 0 Input 4
IN5 BOOLEAN 0 Input 5
IN6 BOOLEAN 0 Input 6
IN7 BOOLEAN 0 Input 7
IN8 BOOLEAN 0 Input 8
IN9 BOOLEAN 0 Input 9
IN10 BOOLEAN 0 Input 10
IN11 BOOLEAN 0 Input 11
IN12 BOOLEAN 0 Input 12
IN13 BOOLEAN 0 Input 13
IN14 BOOLEAN 0 Input 14
IN15 BOOLEAN 0 Input 15
IN16 BOOLEAN 0 Input 16

PID-3606-OUTPUTSIGNALS v3

Table 262: B16I Output signals


Name Type Description
OUT INTEGER Output value

Breaker protection REQ650 325


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 505 384-UEN C
Logic

10.9.5 Monitored data


PID-3606-MONITOREDDATA v4

Table 263: B16I Monitored data


Name Type Values (Range) Unit Description
OUT INTEGER - - Output value

10.9.6 Settings ABBD8E283673 v4

The function does not have any parameters available in the local HMI or PCM600.

10.9.7 Operation principle SEMOD175737-4 v5

The Boolean 16 to integer conversion function (B16I) will transfer a combination of up to 16


binary inputs INx, where 1≤x≤16, to an integer. Each INx represents a value according to the
table below from 0 to 32768. This follows the general formula: INx = 2x-1 where 1≤x≤16. The sum
of all the values on the activated INx will be available on the output OUT as a sum of the integer
values of all the inputs INx that are activated. OUT is an integer. When all INx (where 1≤x≤16)
are activated, that is = Boolean 1, it corresponds to that integer 65535 is available on the
output OUT. The B16I function is designed for receiving up to 16 booleans input locally. If the
BLOCK input is activated, it will freeze the output at the last value.

Values of each of the different OUTx from function block B16I for 1≤x≤16.

The sum of the value on each INx corresponds to the integer presented on the output OUT on
the function block B16I

Name of input Type Default Description Value when Value when


activated deactivated
IN1 BOOLEAN 0 Input 1 1 0
IN2 BOOLEAN 0 Input 2 2 0
IN3 BOOLEAN 0 Input 3 4 0
IN4 BOOLEAN 0 Input 4 8 0
IN5 BOOLEAN 0 Input 5 16 0
IN6 BOOLEAN 0 Input 6 32 0
IN7 BOOLEAN 0 Input 7 64 0
IN8 BOOLEAN 0 Input 8 128 0
IN9 BOOLEAN 0 Input 9 256 0
IN10 BOOLEAN 0 Input 10 512 0
IN11 BOOLEAN 0 Input 11 1024 0
IN12 BOOLEAN 0 Input 12 2048 0
IN13 BOOLEAN 0 Input 13 4096 0
IN14 BOOLEAN 0 Input 14 8192 0
IN15 BOOLEAN 0 Input 15 16384 0
IN16 BOOLEAN 0 Input 16 32768 0

The sum of the numbers in column “Value when activated” when all INx (where 1≤x≤16) are
active that is=1; is 65535. 65535 is the highest boolean value that can be converted to an
integer by the B16I function block.

326 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 10
Logic

10.9.8 Technical data


GUID-65A2876A-F779-41C4-ACD7-7662D1E7F1F2 v3

Table 264: Number of B16I instances


Function Quantity with cycle time
3 ms 8 ms 100 ms
B16I 6 4 8

10.10 Boolean to integer conversion with logical node


representation, 16 bit BTIGAPC SEMOD175753-1 v4

10.10.1 Identification
SEMOD175757-2 v5

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Boolean to integer conversion with BTIGAPC - -
logical node representation, 16 bit

10.10.2 Functionality SEMOD175781-4 v8

Boolean to integer conversion with logical node representation, 16 bit (BTIGAPC) is used to
transform a set of 16 boolean (logical) signals into an integer. The block input will freeze the
output at the last value.

10.10.3 Function block SEMOD175801-5 v4

BTIGAPC
BLOCK OUT
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
IN9
IN10
IN11
IN12
IN13
IN14
IN15
IN16

IEC13000303-1-en.vsd
IEC13000303 V1 EN-US

Figure 184: BTIGAPC function block

Breaker protection REQ650 327


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 505 384-UEN C
Logic

10.10.4 Signals
PID-6944-INPUTSIGNALS v2

Table 265: BTIGAPC Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
IN1 BOOLEAN 0 Input 1
IN2 BOOLEAN 0 Input 2
IN3 BOOLEAN 0 Input 3
IN4 BOOLEAN 0 Input 4
IN5 BOOLEAN 0 Input 5
IN6 BOOLEAN 0 Input 6
IN7 BOOLEAN 0 Input 7
IN8 BOOLEAN 0 Input 8
IN9 BOOLEAN 0 Input 9
IN10 BOOLEAN 0 Input 10
IN11 BOOLEAN 0 Input 11
IN12 BOOLEAN 0 Input 12
IN13 BOOLEAN 0 Input 13
IN14 BOOLEAN 0 Input 14
IN15 BOOLEAN 0 Input 15
IN16 BOOLEAN 0 Input 16

PID-6944-OUTPUTSIGNALS v2

Table 266: BTIGAPC Output signals


Name Type Description
OUT INTEGER Output value

10.10.5 Settings ABBD8E283673 v4

The function does not have any parameters available in the local HMI or PCM600.

10.10.6 Monitored data


PID-6944-MONITOREDDATA v2

Table 267: BTIGAPC Monitored data


Name Type Values (Range) Unit Description
OUT INTEGER - - Output value

10.10.7 Operation principle SEMOD158425-4 v6

The Boolean 16 to integer conversion with logic node representation function (BTIGAPC) will
transfer a combination of up to 16 binary inputs INx, where 1≤x≤16, to an integer. Each INx
represents a value according to the table below from 0 to 32768. This follows the general
formula: INx = 2x-1 where 1≤x≤16. The sum of all the values on the activated INx will be available

328 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 10
Logic

on the output OUT as a sum of the integer values of all the inputs INx that are activated. OUT
is an integer. When all INx (where 1≤x≤16) are activated, that is = Boolean 1, it corresponds to
that integer 65535 is available on the output OUT. If the BLOCK input is activated, it will freeze
the logical outputs at the last value.

Values of each of the different OUTx from function block BTIGAPC for 1≤x≤16.

The sum of the value on each INx corresponds to the integer presented on the output OUT on
the function block BTIGAPC.

Name of input Type Default Description Value when Value when


activated deactivated
IN1 BOOLEAN 0 Input 1 1 0
IN2 BOOLEAN 0 Input 2 2 0
IN3 BOOLEAN 0 Input 3 4 0
IN4 BOOLEAN 0 Input 4 8 0
IN5 BOOLEAN 0 Input 5 16 0
IN6 BOOLEAN 0 Input 6 32 0
IN7 BOOLEAN 0 Input 7 64 0
IN8 BOOLEAN 0 Input 8 128 0
IN9 BOOLEAN 0 Input 9 256 0
IN10 BOOLEAN 0 Input 10 512 0
IN11 BOOLEAN 0 Input 11 1024 0
IN12 BOOLEAN 0 Input 12 2048 0
IN13 BOOLEAN 0 Input 13 4096 0
IN14 BOOLEAN 0 Input 14 8192 0
IN15 BOOLEAN 0 Input 15 16384 0
IN16 BOOLEAN 0 Input 16 32768 0

The sum of the numbers in column “Value when activated” when all INx (where 1≤x≤16) are
active that is=1; is 65535. 65535 is the highest boolean value that can be converted to an
integer by the BTIGAPC function block.

10.10.8 Technical data


GUID-3820F464-D296-4CAD-8491-F3F997359D79 v2

Table 268: Number of BTIGAPC instances


Function Quantity with cycle time
3 ms 8 ms 100 ms
BTIGAPC 4 4 8

10.11 Integer to boolean 16 conversion IB16

10.11.1 Identification
SEMOD167941-2 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Integer to boolean 16 conversion IB16 - -

Breaker protection REQ650 329


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 505 384-UEN C
Logic

10.11.2 Functionality SEMOD158373-5 v6

Integer to boolean 16 conversion function (IB16) is used to transform an integer into a set of 16
boolean (logical) signals.

10.11.3 Function block SEMOD158389-4 v4

IB16
BLOCK OUT1
INP OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
OUT9
OUT10
OUT11
OUT12
OUT13
OUT14
OUT15
OUT16

IEC06000501-3-en.vsdx

IEC06000501 V3 EN-US

Figure 185: IB16 function block

10.11.4 Signals
PID-6938-INPUTSIGNALS v1

Table 269: IB16 Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
INP INTEGER 0 Integer Input

PID-6938-OUTPUTSIGNALS v1

Table 270: IB16 Output signals


Name Type Description
OUT1 BOOLEAN Output 1
OUT2 BOOLEAN Output 2
OUT3 BOOLEAN Output 3
OUT4 BOOLEAN Output 4
OUT5 BOOLEAN Output 5
OUT6 BOOLEAN Output 6
OUT7 BOOLEAN Output 7
OUT8 BOOLEAN Output 8
OUT9 BOOLEAN Output 9
OUT10 BOOLEAN Output 10
OUT11 BOOLEAN Output 11
OUT12 BOOLEAN Output 12
Table continues on next page

330 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 10
Logic

Name Type Description


OUT13 BOOLEAN Output 13
OUT14 BOOLEAN Output 14
OUT15 BOOLEAN Output 15
OUT16 BOOLEAN Output 16

10.11.5 Setting parameters ABBD8E242451 v4

The function does not have any parameters available in local HMI or Protection and Control IED
Manager (PCM600)

10.11.6 Operation principle SEMOD158385-4 v4

With integer 15 on the input INP the OUT1 = OUT2 = OUT3= OUT4 =1 and the remaining OUTx =
0 for (5≤x≤16).

OUTx represents a value when activated. The value of each of the OUTx is in accordance with
the table IB16_1. When not activated the OUTx has the value 0.

In the above example when integer 15 is on the input INP the OUT1 has a value =1, OUT2 has a
value =2, OUT3 has a value =4 and OUT4 has a value =8. The sum of these OUTx is equal to 1 + 2
+ 4 + 8 = 15.

This follows the general formulae: The sum of the values of all OUTx = 2x-1 where 1≤x≤16 will be
equal to the integer value on the input INP.

The Integer to Boolean 16 conversion function (IB16) will transfer an integer with a value
between 0 to 65535 connected to the input INP to a combination of activated outputs OUTx
where 1≤x≤16. The sum of the values of all OUTx will then be equal to the integer on input INP.
The values of the different OUTx are according to the table below. When an OUTx is not
activated, its value is 0.

When all OUTx where 1≤x≤16 are activated that is = Boolean 1 it corresponds to that integer
65535 is connected to input INP. The IB16 function is designed for receiving the integer input
locally. If the BLOCK input is activated, it will freeze the logical outputs at the last value.

Values of each of the different OUTx from function block IB16 for 1≤x≤16.

The sum of the value on each INx corresponds to the integer presented on the output OUT on
the function block IB16.

Name of OUTx Type Description Value when Value when


activated deactivated
OUT1 BOOLEAN Output 1 1 0
OUT2 BOOLEAN Output 2 2 0
OUT3 BOOLEAN Output 3 4 0
OUT4 BOOLEAN Output 4 8 0
OUT5 BOOLEAN Output 5 16 0
OUT6 BOOLEAN Output 6 32 0
OUT7 BOOLEAN Output 7 64 0
OUT8 BOOLEAN Output 8 128 0
OUT9 BOOLEAN Output 9 256 0
Table continues on next page

Breaker protection REQ650 331


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 505 384-UEN C
Logic

Name of OUTx Type Description Value when Value when


activated deactivated
OUT10 BOOLEAN Output 10 512 0
OUT11 BOOLEAN Output 11 1024 0
OUT12 BOOLEAN Output 12 2048 0
OUT13 BOOLEAN Output 13 4096 0
OUT14 BOOLEAN Output 14 8192 0
OUT15 BOOLEAN Output 15 16384 0
OUT16 BOOLEAN Output 16 32768 0

The sum of the numbers in column “Value when activated” when all OUTx (where x = 1 to 16)
are active that is=1; is 65535. 65535 is the highest integer that can be converted by the IB16
function block.

10.11.7 Technical data


GUID-B45901F4-B163-4696-8220-7F8CAC84D793 v2

Table 271: Number of IB16 instances


Function Quantity with cycle time
3 ms 8 ms 100 ms
IB16 6 4 8

10.12 Integer to Boolean 16 conversion with logic node


representation ITBGAPC SEMOD158419-1 v3

10.12.1 Identification
SEMOD167944-2 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Integer to boolean 16 conversion ITBGAPC - -
with logic node representation

10.12.2 Functionality SEMOD158421-5 v9

Integer to boolean conversion with logic node representation function (ITBGAPC) is used to
transform an integer which is transmitted over IEC 61850 and received by the function to 16
boolean (logic) output signals.

ITBGAPC function can only receive remote values over IEC 61850 when the R/L (Remote/Local)
push button on the front HMI indicates that the control mode for the operator is in position R
(Remote i.e. the LED adjacent to R is lit), and the corresponding signal is connected to the
input PSTO ITBGAPC function block. The input BLOCK will freeze the output at the last received
value and blocks new integer values to be received and converted to binary coded outputs.

332 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 10
Logic

10.12.3 Function block SEMOD158435-4 v4

ITBGAPC
BLOCK OUT1
PSTO OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
OUT9
OUT10
OUT11
OUT12
OUT13
OUT14
OUT15
OUT16

IEC14000012-1-en.vsd
IEC14000012 V1 EN-US

Figure 186: ITBGAPC function block

10.12.4 Signals
PID-3627-INPUTSIGNALS v7

Table 272: ITBGAPC Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
PSTO INTEGER 1 Operator place selection

PID-3627-OUTPUTSIGNALS v7

Table 273: ITBGAPC Output signals


Name Type Description
OUT1 BOOLEAN Output 1
OUT2 BOOLEAN Output 2
OUT3 BOOLEAN Output 3
OUT4 BOOLEAN Output 4
OUT5 BOOLEAN Output 5
OUT6 BOOLEAN Output 6
OUT7 BOOLEAN Output 7
OUT8 BOOLEAN Output 8
OUT9 BOOLEAN Output 9
OUT10 BOOLEAN Output 10
OUT11 BOOLEAN Output 11
OUT12 BOOLEAN Output 12
OUT13 BOOLEAN Output 13
OUT14 BOOLEAN Output 14
OUT15 BOOLEAN Output 15
OUT16 BOOLEAN Output 16

Breaker protection REQ650 333


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 505 384-UEN C
Logic

10.12.5 Settings
GUID-F573CA16-4821-4203-970A-F7D01AF5E63B v1
This function does not have any setting parameters.

10.12.6 Operation principle SEMOD176587-4 v6

An example is used to explain the principle of operation: With integer 15 sent to and received
by the ITBGAPC function on the IEC 61850 the OUTx changes from 0 to 1 on each of the OUT1;
OUT2 OUT3 and OUT4. All other OUTx (5≤x≤16) remains 0. The boolean interpretation of this is
represented by the assigned values of each of the outputs OUT1 = 1; and OUT2 = 2; and OUT3=
4; and OUT4 = 8. The sum of these OUTx (1≤x≤4) is equal to the integer 15 received via the IEC
61850 network. The remaining OUTx = 0 for (5≤x≤16).

OUTx represents a value when activated. The value of each of the OUTx is in accordance with
the Table 274. When not activated the OUTx has the value 0.

The value of each OUTx for 1≤x≤16 (1≤x≤16) follows the general formulae: OUTx = 2x-1 The sum
of the values of all activated OUTx = 2x-1 where 1≤x≤16 will be equal to the integer value
received over IEC 61850 to the ITBGAPC_1 function block.

The Integer to Boolean 16 conversion with logic node representation function (ITBGAPC) will
transfer an integer with a value between 0 to 65535 communicated via IEC 61850 and
connected to the ITBGAPC function block to a combination of activated outputs OUTx where
1≤x≤16. The values represented by the different OUTx are according to Table 274. When an
OUTx is not activated, its value is 0.

The ITBGAPC function is designed for receiving the integer input from a station computer - for
example, over IEC 61850. If the BLOCK input is activated, it will freeze the logical outputs at the
last value.

Table 274: Outputs and their values when activated


Name of OUTx Type Description Value when Value when
activated deactivated
OUT1 BOOLEAN Output 1 1 0
OUT2 BOOLEAN Output 2 2 0
OUT3 BOOLEAN Output 3 4 0
OUT4 BOOLEAN Output 4 8 0
OUT5 BOOLEAN Output 5 16 0
OUT6 BOOLEAN Output 6 32 0
OUT7 BOOLEAN Output 7 64 0
OUT8 BOOLEAN Output 8 128 0
OUT9 BOOLEAN Output 9 256 0
OUT10 BOOLEAN Output 10 512 0
OUT11 BOOLEAN Output 11 1024 0
OUT12 BOOLEAN Output 12 2048 0
OUT13 BOOLEAN Output 13 4096 0
OUT14 BOOLEAN Output 14 8192 0
OUT15 BOOLEAN Output 15 16384 0
OUT16 BOOLEAN Output 16 32768 0

334 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 10
Logic

The sum of the numbers in column “Value when activated” when all OUTx (1≤x≤16) are active
equals 65535. This is the highest integer that can be converted to boolean by the ITBGAPC
function block.

The operator position input (PSTO) determines the operator place. The integer number that is
communicated to the ITBGAPC can only be written to the block while the PSTO is in position
“Remote”. If PSTO is in position ”Off” or ”Local”, then no changes are applied to the outputs.

10.12.7 Technical data


GUID-A339BBA3-8FD0-429D-BB49-809EAC4D53B0 v2

Table 275: Number of ITBGAPC instances


Function Quantity with cycle time
3 ms 8 ms 100 ms
ITBGAPC 4 4 8

10.13 Elapsed time integrator with limit transgression and


overflow supervision TEIGAPC

10.13.1 Identification GUID-1913E066-37D1-4689-9178-5B3C8B029815 v3

Function Description IEC 61850 IEC 60617 ANSI/IEEE C37.2 device


identificatio identificatio number
n n
Elapsed time integrator TEIGAPC - -

10.13.2 Functionality GUID-390D7433-0C1C-48B4-9A90-71AA148C3C35 v3

Elapsed Time Integrator (TEIGAPC) function is a function that accumulates the elapsed time
when a given binary signal has been high, see also Figure 187.

BLOCK
RESET
IN Time Integration ACCTIME
with Retain

q-1

a
OVERFLOW
AND
a>b
999 999 s b

a
WARNING
AND
a>b
tWarning b

a
ALARM
AND
a>b
tAlarm b

q-1 = unit delay IEC13000290-2-en.vsd

IEC13000290 V2 EN-US

Figure 187: TEIGAPC logics


The main features of TEIGAPC

Breaker protection REQ650 335


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 505 384-UEN C
Logic

• Applicable to long time integration up to 999 999.9 seconds


• Supervision of overflow
• Possibility to define a warning and an alarm with the resolution of 10 milliseconds
• Retain the integration value
• Possibilities for blocking and reset of the total integrated time
• Report of the integrated time

10.13.3 Function block GUID-6D50A060-7751-405B-AEC1-FAE942EBDA64 v2

TEIGAPC
BLOCK WARNING
IN ALARM
RESET OVERFLOW
ACCTIME

IEC14000014-1-en.vsd
IEC14000014 V1 EN-US

Figure 188: TEIGAPC function block

10.13.4 Signals
PID-6836-INPUTSIGNALS v2

Table 276: TEIGAPC Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Freeze the integration and block the other outputs
IN BOOLEAN 0 The input signal that is used to measure the elapsed time,
when its value is high
RESET BOOLEAN 0 Reset the integration time

PID-6836-OUTPUTSIGNALS v2

Table 277: TEIGAPC Output signals


Name Type Description
WARNING BOOLEAN Indicator of the integrated time has reached the warning limit
ALARM BOOLEAN Indicator of the integrated time has reached the alarm limit
OVERFLOW BOOLEAN Indicator of the integrated time has reached the overflow
limit
ACCTIME REAL Integrated elapsed time in seconds

10.13.5 Settings
PID-6836-SETTINGS v2

Table 278: TEIGAPC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
tWarning 1.00 - 999999.00 s 0.01 600.00 Time limit for warning supervision
tAlarm 1.00 - 999999.00 s 0.01 1200.00 Time limit for alarm supervision

336 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 10
Logic

10.13.6 Operation principle GUID-04CC8365-DCDE-4DC7-BEF0-6EF8382305DD v3

The elapsed time integrator (TEIGAPC) provides

• time integration, accumulating the elapsed time when a given binary signal has been high
• blocking and reset of the total integrated time
• supervision of limit transgression and overflow, the overflow limit is fixed to 999999.9
seconds
• retaining of the integrated value

Figure 189 describes the simplified logic of the function where the block “Time
Integration“ covers the logics for the first two items listed above while the block
“Transgression Supervision Plus Retain“ contains the logics for the last two.

Loop Delay

tWarning
OVERFLOW
tAlarm
Transgression Supervision WARNING
Plus Retain
ALARM

BLOCK
RESET ACCTIME
Time Integration
IN

Loop Delay

IEC12000195-4-en.vsd

IEC12000195 V4 EN-US

Figure 189: TEIGAPC Simplified logic


TEIGAPC main functionalities

• integration of the elapsed time when IN has been high


• applicable to long time integration (≤999 999.9 seconds)
• output ACCTIME presents integrated value in seconds
• integrated value is retained in nonvolatile memory
• any retained value with a warning/alarm/overflow is used as initiation value for the
integration following by a restart
• RESET: Reset of the integration value. Consequently all other outputs are also reset
• unconditionally on the input IN value
• reset the value of the nonvolatile memory to zero
• BLOCK: Freeze the integration and block/reset the other outputs
• unconditionally on the signal value
• BLOCK request overrides RESET request
• Monitor and report the conditions of limit transgression
• overflow if output ACCTIME >999999.9 seconds
• alarm if ACCTIME > tAlarm
• warning if ACCTIME > tWarning

Breaker protection REQ650 337


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 505 384-UEN C
Logic

The ACCTIME output represents the integrated time in seconds while tOverflow, tAlarm and
tWarning are the time limit parameters in seconds.

tAlarm and tWarning are user settable limits. They are also independent, that is, there is no
check if tAlarm > tWarning.

tAlarm and tWarning are possible to be defined with a resolution of 10 ms, depending on the
level of the defined values for the parameters.

The limit for the overflow supervision is fixed at 999999.9 seconds. The outputs freeze if an
overflow occurs.

10.13.6.1 Operation accuracy GUID-E0772193-9F6E-43DA-B642-2923565E5D4C v3

The accuracy of TEIGAPC depends on essentially three factors

• function cycle time


• the pulse length
• the number of pulses, that is, the number of rising and falling flank pairs

In principle, a shorter function cycle time, longer integrated time length or more pulses may
lead to reduced accuracy.

10.13.6.2 Memory storage GUID-6FDD6590-30F9-4CC1-AC9D-945544AB8688 v3

The value of the integrated elapsed time is retained in a non-volatile memory.

10.13.7 Technical data


GUID-B258726E-1129-47C9-94F9-BE634A2085FA v4

Table 279: TEIGAPC Technical data


Function Cycle time (ms) Range or value Accuracy
Elapsed time integration 3 0 ~ 999999.9 s ±0.2% or ±20 ms whichever
is greater
8 0 ~ 999999.9 s ±0.2% or ±100 ms
whichever is greater
100 0 ~ 999999.9 s ±0.2% or ±250 ms
whichever is greater

Table 280: Number of TEIGAPC instances


Function Quantity with cycle time
3 ms 8 ms 100 ms
TEIGAPC 4 4 4

10.14 Comparator for integer inputs INTCOMP

10.14.1 Identification GUID-5992B0F2-FC1B-4838-9BAB-2D2542BB264D v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Comparison of integer values INTCOMP Int<=>

338 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 10
Logic

10.14.2 Functionality GUID-A93564FA-0017-4939-A9C1-095DA0FD9832 v1

The function gives the possibility to monitor the level of integer values in the system relative
to each other or to a fixed value. It is a basic arithmetic function that can be used for
monitoring, supervision, interlocking and other logics.

10.14.3 Function block GUID-EB28F45B-B1D0-452F-98B4-F96D7FA34069 v1

INTCOMP
INPUT INEQUAL
REF INHIGH
INLOW

IEC15000052-1-en.vsdx
IEC15000052 V1 EN-US

10.14.4 Signals
PID-6928-INPUTSIGNALS v2

Table 281: INTCOMP Input signals


Name Type Default Description
INPUT INTEGER 0 Input value to be compared with reference value
REF INTEGER 0 Reference value to be compared with input value

PID-6928-OUTPUTSIGNALS v2

Table 282: INTCOMP Output signals


Name Type Description
INEQUAL BOOLEAN Input value is equal to the reference value
INHIGH BOOLEAN Input value is higher than the reference value
INLOW BOOLEAN Input value is lower than the reference value

10.14.5 Settings
PID-6928-SETTINGS v2

Table 283: INTCOMP Group settings (basic)


Name Values (Range) Unit Step Default Description
EnaAbs Signed - - Signed Selection for absolute or signed
Absolute comparison
RefSource Set Value - - Set Value Selection for reference value either
Input REF input or setting
SetValue -2000000000 - - 1 100 Set value for reference
2000000000

Breaker protection REQ650 339


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 505 384-UEN C
Logic

10.14.6 Monitored data


PID-6928-MONITOREDDATA v1

Table 284: INTCOMP Monitored data


Name Type Values (Range) Unit Description
INEQUAL BOOLEAN - - Input value is equal to the reference
value
INHIGH BOOLEAN - - Input value is higher than the
reference value
INLOW BOOLEAN - - Input value is lower than the reference
value

10.14.7 Operation principle GUID-E9C1B863-ACA7-45C0-91F1-A51FE38755FE v2

The comparison can be done in two ways,

• Between 2 inputs, INPUT and REF


• Between INPUT and the value set by the user SetValue.

The selection of reference value for comparison can be done through setting RefSource. If
RefSource is selected as Input REF then the reference value for comparison is taken from
second input signal (REF). If RefSource is selected as Set Value then the reference value for
comparison is taken from setting (SetValue).

The comparison can be done either between absolute values or signed values and it depends
on the setting EnaAbs. If EnaAbs is selected as Absolute then both input and reference value is
converted into absolute values and comparison is done. If EnaAbs is selected as Signed then
the comparison is done without any conversion.

The function has three state outputs high, low and equal to condition. It will check the
following condition and give corresponding outputs.

• If the input is above the reference value then INHIGH is set HIGH
• If the input is below the reference value then INLOW is set HIGH
• If the input is equal to reference value then INEQUAL is set HIGH

EnaAbs
INPUT ABS T a
F
INHIGH
a>b
b

a INEQUAL
a=b
b
RefSource

REF ABS T
T
SetValue
F a INLOW
F a<b
b

IEC15000129-3-en.vsdx
IEC15000129 V4 EN-US

Figure 190: Function logic diagram for INTCOMP

340 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 10
Logic

10.14.8 Technical data GUID-CEA332FF-838D-42B7-AEFC-C1E87809825E v3

Table 285: Number of INTCOMP instances


Function Quantity with cycle time
3 ms 8 ms 100 ms
INTCOMP 10 10 10

10.15 Comparator for real inputs REALCOMP

10.15.1 Identification GUID-0D68E846-5A15-4C2C-91A2-F81A74034E81 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Comparator for real inputs REALCOMP Real<=>

10.15.2 Functionality GUID-E17A88D7-D095-4F36-9CD5-64EBFD2A1DEA v1

The function gives the possibility to monitor the level of real value signals in the system
relative to each other or to a fixed value. It is a basic arithmetic function that can be used for
monitoring, supervision, interlocking and other logics.

10.15.3 Function block GUID-8752DF2A-D131-4461-80C6-C52F9980D228 v1

REALCOMP
INPUT INEQUAL
REF INHIGH
INLOW

IEC15000053-1-en.vsdx
IEC15000053 V1 EN-US

10.15.4 Signals
PID-7248-INPUTSIGNALS v1

Table 286: REALCOMP Input signals


Name Type Default Description
INPUT REAL 0.000 Input value to be compared with reference value
REF REAL 0.000 Reference value to be compared with input value

PID-7248-OUTPUTSIGNALS v1

Table 287: REALCOMP Output signals


Name Type Description
INEQUAL BOOLEAN Input value is equal to the reference value
INHIGH BOOLEAN Input value is higher than the reference value
INLOW BOOLEAN Input value is lower than the reference value

Breaker protection REQ650 341


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 505 384-UEN C
Logic

10.15.5 Settings
PID-7248-SETTINGS v1

Table 288: REALCOMP Group settings (basic)


Name Values (Range) Unit Step Default Description
EnaAbs Signed - - Signed Selection for absolute or signed
Absolute comparison
RefSource Set Value - - Set Value Selection for reference value either
Input REF input or setting
SetValue -999.999 - - 0.001 0.001 Set value for reference
999.999
SetValPrefix milli - - unit Multiplication factor for SetValue
unit
kilo
Mega
Giga
EqualBandHigh 0.10 - 50.00 % 0.01 0.50 Equal band high limit in % of
reference value
EqualBandLow 0.10 - 50.00 % 0.01 0.50 Equal band low limit in % of reference
value

10.15.6 Operation principle GUID-3FA699A8-D076-4E5E-BCB8-C6B7907573D1 v2

The comparison can be done in two ways,

1. Between 2 inputs, INPUT and REF


2. Between INPUT and the SetValue setting

The selection of reference value for comparison can be done through setting RefSource. If
RefSource is selected as Input REF then the reference value for comparison is taken from
second input signal (REF). If RefSource is selected as Set Value then the reference value for
comparison is taken from setting (SetValue).

Generally the inputs to the function are in SI units, but when the comparison is to be done with
respect to set level, then the user can set a value in any unit out of Milli to Giga range in setting
SetValue. The unit can be separately set with setting RefPrefix. Internally the function handles
the reference value for comparator as SetValue*RefPrefix.

Additionally the comparison can be done either between absolute values or signed values and
it depends on the setting EnaAbs. If EnaAbs is selected as Absolute then both input and
reference value is converted into absolute values and then comparison is done. If EnaAbs is
selected as Signed then the comparison is done without absolute conversion.

342 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 10
Logic

EnaAbs
INPUT
ABS T
F
High
Comparator
EqualBandHigh INHIGH

RefSource XOR INEQUAL

REF ABS T
T
F Low
SetValue F comparator
INLOW
SetValPrefix

EqualBandLow

IEC15000130-2-en.vsdx
IEC15000130 V2 EN-US

Figure 191: Logic diagram for REALCOMP


This function has two settings EqualBandHigh and EqualBandLow to provide margins from
reference value for equal to condition. When the INPUT value is within high and low band,
output INEQUAL will get set.

In order to avoid oscillations at boundary conditions of equal band low limit and high limit,
hysteresis has been provided. If the INPUT is above the equal high level margin including
hysteresis, then INHIGH will set. Similarly if the INPUT is below the equal low level margin
including hysteresis, then INLOW will set.

INEQUAL Reset / INHIGH Set INEQUAL Set / INHIGH Reset

EqualBandHigh

Internal
Equal Band REF or SetValue Hysteresis for
equal band

EqualBandLow

INEQUAL Reset / INLOW Set INEQUAL Set / INLOW Reset


IEC15000261-1-en.vsdx

IEC15000261 V1 EN-US

Figure 192: Operation principle of REALCOMP

When EnaAbs is set as absolute comparison and SetValue is set less than 0.2%
of the set unit then INLOW output will never pickups. During the above
mentioned condition, due to marginal value for avoiding oscillations of
function outputs, the INLOW output will never set.

Breaker protection REQ650 343


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 10 1MRK 505 384-UEN C
Logic

10.15.7 Technical data


GUID-62792FCB-B436-4034-9A08-C9FF918FF547 v1
REALCOMP function can compare the values from milli value level to giga value level and the
maximum expectable accuracy level from the function is 10 µ.
GUID-3FDD7677-1D86-42AD-A545-B66081C49B47 v4

Table 289: Number of REALCOMP instances


Function Quantity with cycle time
3 ms 8 ms 100 ms
REALCOMP 10 10 10

344 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

Section 11 Monitoring
11.1 Measurements IP14593-1 v3

11.1.1 Identification
SEMOD56123-2 v8

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Power system measurements CVMMXN -
P, Q, S, I, U, f

SYMBOL-RR V1 EN-US

Phase current measurement CMMXU -

SYMBOL-SS V1 EN-US

Phase-phase voltage measurement VMMXU -

SYMBOL-UU V1 EN-US

Current sequence component CMSQI -


measurement
I1, I2, I0

SYMBOL-VV V1 EN-US

Voltage sequence component VMSQI -


measurement
U1, U2, U0

SYMBOL-TT V1 EN-US

Phase-neutral voltage measurement VNMMXU -

SYMBOL-UU V1 EN-US

11.1.2 Functionality SEMOD54488-4 v12

Measurement functions are used for power system measurement, supervision and reporting
to the local HMI, monitoring tool within PCM600 or to station level for example, via IEC 61850.
The possibility to continuously monitor measured values of active power, reactive power,
currents, voltages, frequency, power factor etc. is vital for efficient production, transmission
and distribution of electrical energy. It provides to the system operator fast and easy overview
of the present status of the power system. Additionally, it can be used during testing and
commissioning of protection and control IEDs in order to verify proper operation and
connection of instrument transformers (CTs and VTs). During normal service by periodic
comparison of the measured value from the IED with other independent meters the proper
operation of the IED analog measurement chain can be verified. Finally, it can be used to verify
proper direction orientation for distance or directional overcurrent protection function.

Breaker protection REQ650 345


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

The available measured values from an IED are depending on the actual
hardware (TRM) and the logic configuration made in PCM600.

All measured values can be supervised with four settable limits that is, low-low limit, low limit,
high limit and high-high limit. A zero clamping reduction is also supported, that is, the
measured value below a settable limit is forced to zero which reduces the impact of noise in
the inputs.

Dead-band supervision can be used to report measured signal value to station level when
change in measured value is above set threshold limit or time integral of all changes since the
last time value updating exceeds the threshold limit. Measure value can also be based on
periodic reporting.

Main menu/Measurement/Monitoring/Service values/CVMMXN

The measurement function, CVMMXN, provides the following power system quantities:

• P, Q and S: three phase active, reactive and apparent power


• PF: power factor
• U: phase-to-phase voltage amplitude
• I: phase current amplitude
• F: power system frequency

,
The measuring functions CMMXU, VMMXU and VNMMXU provide physical quantities:

• I: phase currents (amplitude and angle) (CMMXU)


• U: voltages (phase-to-earth and phase-to-phase voltage, amplitude and angle) (VMMXU,
VNMMXU)

The CVMMXN function calculates three-phase power quantities by using fundamental


frequency phasors (DFT values) of the measured current and voltage signals. The measured
power quantities are available either, as instantaneously calculated quantities or, averaged
values over a period of time (low pass filtered) depending on the selected settings.

It is possible to calibrate the measuring function above to get better then class 0.5
presentation. This is accomplished by angle and amplitude compensation at 5, 30 and 100% of
rated current and at 100% of rated voltage.

The power system quantities provided, depends on the actual hardware, (TRM)
and the logic configuration made in PCM600.

The measuring functions CMSQI and VMSQI provide sequence component quantities:

• I: sequence currents (positive, zero, negative sequence, amplitude and angle)


• U: sequence voltages (positive, zero and negative sequence, amplitude and angle).

11.1.3 Function block SEMOD130334-4 v7

The available function blocks of an IED are depending on the actual hardware (TRM) and the
logic configuration made in PCM600.

346 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

CVMMXN
I3P* S
U3P* S_RANGE
P_INST
P
P_RANGE
Q_INST
Q
Q_RANGE
PF
PF_RANGE
ILAG
ILEAD
U
U_RANGE
I
I_RANGE
F
F_RANGE

IEC10000016-1-en.vsd
IEC10000016 V1 EN-US

Figure 193: CVMMXN function block

CMMXU
I3P* IL1
IL1RANG
IL1ANGL
IL2
IL2RANG
IL2ANGL
IL3
IL3RANG
IL3ANGL

IEC05000699-2-en.vsd
IEC05000699 V2 EN-US

Figure 194: CMMXU function block

VMMXU
U3P* UL12
UL12RANG
UL12ANGL
UL23
UL23RANG
UL23ANGL
UL31
UL31RANG
UL31ANGL

IEC05000701-2-en.vsd
IEC05000701 V2 EN-US

Figure 195: VMMXU function block

CMSQI
I3P* 3I0
3I0RANG
3I0ANGL
I1
I1RANG
I1ANGL
I2
I2RANG
I2ANGL

IEC05000703-2-en.vsd
IEC05000703 V2 EN-US

Figure 196: CMSQI function block

Breaker protection REQ650 347


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

VMSQI
U3P* 3U0
3U0RANG
3U0ANGL
U1
U1RANG
U1ANGL
U2
U2RANG
U2ANGL

IEC05000704-2-en.vsd
IEC05000704 V2 EN-US

Figure 197: VMSQI function block

VNMMXU
U3P* UL1
UL1RANG
UL1ANGL
UL2
UL2RANG
UL2ANGL
UL3
UL3RANG
UL3ANGL

IEC09000850-1-en.vsd
IEC09000850 V1 EN-US

Figure 198: VNMMXU function block

11.1.4 Signals
PID-6713-INPUTSIGNALS v3

Table 290: CVMMXN Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
U3P GROUP - Group signal for voltage input
SIGNAL

PID-6713-OUTPUTSIGNALS v3

Table 291: CVMMXN Output signals


Name Type Description
S REAL Apparent Power magnitude of deadband value
S_RANGE INTEGER Apparent Power range
P_INST REAL Active Power
P REAL Active Power magnitude of deadband value
P_RANGE INTEGER Active Power range
Q_INST REAL Reactive Power
Q REAL Reactive Power magnitude of deadband value
Q_RANGE INTEGER Reactive Power range
PF REAL Power Factor magnitude of deadband value
PF_RANGE INTEGER Power Factor range
ILAG BOOLEAN Current is lagging voltage
ILEAD BOOLEAN Current is leading voltage
U REAL Calculated voltage magnitude of deadband value
U_RANGE INTEGER Calculated voltage range
Table continues on next page

348 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

Name Type Description


I REAL Calculated current magnitude of deadband value
I_RANGE INTEGER Calculated current range
F REAL System frequency magnitude of deadband value
F_RANGE INTEGER System frequency range

PID-6735-INPUTSIGNALS v3

Table 292: CMMXU Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL

PID-6735-OUTPUTSIGNALS v3

Table 293: CMMXU Output signals


Name Type Description
IL1 REAL IL1 Amplitude, magnitude of reported value
IL1RANG INTEGER IL1 Amplitude range
IL1ANGL REAL IL1 Angle, magnitude of reported value
IL2 REAL IL2 Amplitude, magnitude of reported value
IL2RANG INTEGER IL2 Amplitude range
IL2ANGL REAL IL2 Angle, magnitude of reported value
IL3 REAL IL3 Amplitude, magnitude of reported value
IL3RANG INTEGER IL3 Amplitude range
IL3ANGL REAL IL3 Angle, magnitude of reported value

PID-6738-INPUTSIGNALS v2

Table 294: VMMXU Input signals


Name Type Default Description
U3P GROUP - Group signal for voltage input
SIGNAL

PID-6738-OUTPUTSIGNALS v2

Table 295: VMMXU Output signals


Name Type Description
UL12 REAL UL12 Amplitude, magnitude of reported value
UL12RANG INTEGER UL12 Amplitude range
UL12ANGL REAL UL12 Angle, magnitude of reported value
UL23 REAL UL23 Amplitude, magnitude of reported value
UL23RANG INTEGER UL23 Amplitude range
UL23ANGL REAL UL23 Angle, magnitude of reported value
UL31 REAL UL31 Amplitude, magnitude of reported value
UL31RANG INTEGER UL31 Amplitude range
UL31ANGL REAL UL31 Angle, magnitude of reported value

Breaker protection REQ650 349


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

PID-6736-INPUTSIGNALS v3

Table 296: CMSQI Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL

PID-6736-OUTPUTSIGNALS v3

Table 297: CMSQI Output signals


Name Type Description
3I0 REAL 3I0 Amplitude, magnitude of reported value
3I0RANG INTEGER 3I0 Amplitude range
3I0ANGL REAL 3I0 Angle, magnitude of reported value
I1 REAL I1 Amplitude, magnitude of reported value
I1RANG INTEGER I1 Amplitude range
I1ANGL REAL I1 Angle, magnitude of reported value
I2 REAL I2 Amplitude, magnitude of reported value
I2RANG INTEGER I2 Amplitude range
I2ANGL REAL I2 Angle, magnitude of reported value

PID-6739-INPUTSIGNALS v2

Table 298: VMSQI Input signals


Name Type Default Description
U3P GROUP - Group signal for voltage input
SIGNAL

PID-6739-OUTPUTSIGNALS v2

Table 299: VMSQI Output signals


Name Type Description
3U0 REAL 3U0 Amplitude, magnitude of reported value
3U0RANG INTEGER 3U0 Amplitude range
3U0ANGL REAL 3U0 Angle, magnitude of reported value
U1 REAL U1 Amplitude, magnitude of reported value
U1RANG INTEGER U1 Amplitude range
U1ANGL REAL U1 Angle, magnitude of reported value
U2 REAL U2 Amplitude, magnitude of reported value
U2RANG INTEGER U2 Amplitude range
U2ANGL REAL U2 Angle, magnitude of reported value

PID-6737-INPUTSIGNALS v2

Table 300: VNMMXU Input signals


Name Type Default Description
U3P GROUP - Group signal for voltage input
SIGNAL

350 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

PID-6737-OUTPUTSIGNALS v2

Table 301: VNMMXU Output signals


Name Type Description
UL1 REAL UL1 Amplitude, magnitude of reported value
UL1RANG INTEGER UL1 Amplitude range
UL1ANGL REAL UL1 Angle, magnitude of reported value
UL2 REAL UL2 Amplitude, magnitude of reported value
UL2RANG INTEGER UL2 Amplitude range
UL2ANGL REAL UL2 Angle, magnitude of reported value
UL3 REAL UL3 Amplitude, magnitude of reported value
UL3RANG INTEGER UL3 Amplitude range
UL3ANGL REAL UL3 Angle, magnitude of reported value

11.1.5 Settings SEMOD130322-4 v7

The available setting parameters of the measurement function (MMXU, MSQI) are depending
on the actual hardware (TRM) and the logic configuration made in PCM600.

These six functions are not handled as a group, so parameter settings are only available in the
first setting group.

The following terms are used in the Unit and Description columns:

• UBase (UB): Base voltage in primary kV. This voltage is used as reference for voltage
setting. It can be suitable to set this parameter to the rated primary voltage supervised
object.
• IBase (IB): Base current in primary A. This current is used as reference for current setting.
It can be suitable to set this parameter to the rated primary current of the supervised
object.
• SBase (SB): Base setting for power values in MVA.

PID-6713-SETTINGS v3

Table 302: CVMMXN Non group settings (basic)


Name Values (Range) Unit Step Default Description
SLowLim 0.0 - 2000.0 %SB 0.1 80.0 Low limit in % of SBase
SLowLowLim 0.0 - 2000.0 %SB 0.1 60.0 Low Low limit in % of SBase
SMin 0.0 - 2000.0 %SB 0.1 50.0 Minimum value in % of SBase
SMax 0.0 - 2000.0 %SB 0.1 200.0 Maximum value in % of SBase
SRepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
PMin -2000.0 - 2000.0 %SB 0.1 -200.0 Minimum value in % of SBase
PMax -2000.0 - 2000.0 %SB 0.1 200.0 Maximum value in % of SBase
Table continues on next page

Breaker protection REQ650 351


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

Name Values (Range) Unit Step Default Description


PRepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
QMin -2000.0 - 2000.0 %SB 0.1 -200.0 Minimum value in % of SBase
QMax -2000.0 - 2000.0 %SB 0.1 200.0 Maximum value in % of SBase
QRepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
PFMin -1.000 - 1.000 - 0.001 -1.000 Minimum value
PFMax -1.000 - 1.000 - 0.001 1.000 Maximum value
PFRepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
UMin 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
UMax 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
URepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
IMin 0.0 - 500.0 %IB 0.1 5.0 Minimum value in % of IBase
IMax 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase
IRepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
FrMin 0.000 - 100.000 Hz 0.001 0.000 Minimum value
FrMax 0.000 - 100.000 Hz 0.001 70.000 Maximum value
FrRepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
Operation Off - - Off Operation Off / On
On
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
Table continues on next page

352 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

Name Values (Range) Unit Step Default Description


Mode L1, L2, L3 - - L1, L2, L3 Selection of measured current and
Arone voltage
Pos Seq
L1L2
L2L3
L3L1
L1
L2
L3
PowAmpFact 0.000 - 6.000 - 0.001 1.000 Amplitude factor to scale power
calculations
PowAngComp -180.0 - 180.0 Deg 0.1 0.0 Angle compensation for phase shift
between measured I & U
k 0.000 - 1.000 - 0.001 0.000 Low pass filter coefficient for power
measurement, U and I

Table 303: CVMMXN Non group settings (advanced)


Name Values (Range) Unit Step Default Description
SDbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
SZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
SHiHiLim 0.0 - 2000.0 %SB 0.1 150.0 High High limit in % of SBase
SHiLim 0.0 - 2000.0 %SB 0.1 120.0 High limit in % of SBase
SLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
PDbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
PZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
PHiHiLim -2000.0 - 2000.0 %SB 0.1 150.0 High High limit in % of SBase
PHiLim -2000.0 - 2000.0 %SB 0.1 120.0 High limit in % of SBase
PLowLim -2000.0 - 2000.0 %SB 0.1 -120.0 Low limit in % of SBase
PLowLowLim -2000.0 - 2000.0 %SB 0.1 -150.0 Low Low limit in % of SBase
PLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
QDbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
QZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
QHiHiLim -2000.0 - 2000.0 %SB 0.1 150.0 High High limit in % of SBase
QHiLim -2000.0 - 2000.0 %SB 0.1 120.0 High limit in % of SBase
QLowLim -2000.0 - 2000.0 %SB 0.1 -120.0 Low limit in % of SBase
QLowLowLim -2000.0 - 2000.0 %SB 0.1 -150.0 Low Low limit in % of SBase
QLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
PFDbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
PFZeroDb 0 - 100000 m% 100 500 Magnitude zero point clamping in
0,001% of range
Table continues on next page

Breaker protection REQ650 353


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

Name Values (Range) Unit Step Default Description


PFHiHiLim -1.000 - 1.000 - 0.001 1.000 High High limit (physical value)
PFHiLim -1.000 - 1.000 - 0.001 0.800 High limit (physical value)
PFLowLim -1.000 - 1.000 - 0.001 -0.800 Low limit (physical value)
PFLowLowLim -1.000 - 1.000 - 0.001 -1.000 Low Low limit (physical value)
PFLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
UDbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
UZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
UHiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
UHiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
ULowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
ULowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
ULimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
IDbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
IZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
IHiHiLim 0.0 - 500.0 %IB 0.1 150.0 High High limit in % of IBase
IHiLim 0.0 - 500.0 %IB 0.1 120.0 High limit in % of IBase
ILowLim 0.0 - 500.0 %IB 0.1 80.0 Low limit in % of IBase
ILowLowLim 0.0 - 500.0 %IB 0.1 60.0 Low Low limit in % of IBase
ILimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
FrDbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
FrZeroDb 0 - 100000 m% 10 100 Magnitude zero point clamping in
0,001% of range
FrHiHiLim 0.000 - 100.000 Hz 0.001 65.000 High High limit (physical value)
FrHiLim 0.000 - 100.000 Hz 0.001 63.000 High limit (physical value)
FrLowLim 0.000 - 100.000 Hz 0.001 47.000 Low limit (physical value)
FrLowLowLim 0.000 - 100.000 Hz 0.001 45.000 Low Low limit (physical value)
FrLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
UGenZeroDb 1 - 100 %UB 1 5 Zero point clamping in % of UBase
IGenZeroDb 1 - 100 %IB 1 5 Zero point clamping in % of IBase
UAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage
at 5% of Ur
UAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage
at 30% of Ur
UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage
at 100% of Ur
IAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current
at 5% of Ir
IAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current
at 30% of Ir
Table continues on next page

354 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

Name Values (Range) Unit Step Default Description


IAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current
at 100% of Ir
IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 5% of
Ir
IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 30% of
Ir
IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 100%
of Ir

PID-6735-SETTINGS v3

Table 304: CMMXU Non group settings (basic)


Name Values (Range) Unit Step Default Description
IL1DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
Operation Off - - Off Operation Mode On / Off
On
IL1Min 0.0 - 500.0 %IB 0.1 50.0 Minimum value in % of IBase
IL1Max 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
IL1RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
IL1AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
IL2DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
IL2Min 0.0 - 500.0 %IB 0.1 50.0 Minimum value in % of IBase
IL2Max 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase
IL2RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
IL2AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
IL3DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
IL3Min 0.0 - 500.0 %IB 0.1 50.0 Minimum value in % of IBase
IL3Max 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase
IL3RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
IL3AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)

Breaker protection REQ650 355


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

Table 305: CMMXU Non group settings (advanced)


Name Values (Range) Unit Step Default Description
IL1ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
IL1HiHiLim 0.0 - 500.0 %IB 0.1 150.0 High High limit in % of IBase
IL1HiLim 0.0 - 500.0 %IB 0.1 120.0 High limit in % of IBase
IAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current
at 5% of Ir
IAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current
at 30% of Ir
IL1LowLim 0.0 - 500.0 %IB 0.1 80.0 Low limit in % of IBase
IL1LowLowLim 0.0 - 500.0 %IB 0.1 60.0 Low Low limit in % of IBase
IAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current
at 100% of Ir
IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 5% of
Ir
IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 30% of
Ir
IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 100%
of Ir
IL1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
IL2ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
IL2HiHiLim 0.0 - 500.0 %IB 0.1 150.0 High High limit in % of IBase
IL2HiLim 0.0 - 500.0 %IB 0.1 120.0 High limit in % of IBase
IL2LowLim 0.0 - 500.0 %IB 0.1 80.0 Low limit in % of IBase
IL2LowLowLim 0.0 - 500.0 %IB 0.1 60.0 Low Low limit in % of IBase
IL2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
IL3ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
IL3HiHiLim 0.0 - 500.0 %IB 0.1 150.0 High High limit in % of IBase
IL3HiLim 0.0 - 500.0 %IB 0.1 120.0 High limit in % of IBase
IL3LowLim 0.0 - 500.0 %IB 0.1 80.0 Low limit in % of IBase
IL3LowLowLim 0.0 - 500.0 %IB 0.1 60.0 Low Low limit in % of IBase
IL3LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits

PID-6738-SETTINGS v2

Table 306: VMMXU Non group settings (basic)


Name Values (Range) Unit Step Default Description
UL12DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
Operation Off - - Off Operation Mode On / Off
On
UL12ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
UL12Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
Table continues on next page

356 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

Name Values (Range) Unit Step Default Description


UL12Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
UL12RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
UL12AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
UL23DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
UL23ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
UL23Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
UL23Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
UL23RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
UL23AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
UL31DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
UL31ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
UL31Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
UL31Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
UL31RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
UL31AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)

Table 307: VMMXU Non group settings (advanced)


Name Values (Range) Unit Step Default Description
UL12HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
UL12HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
UL12LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
UL12LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage
at 100% of Ur
UL12LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
UL23HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
UL23HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
UL23LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
Table continues on next page

Breaker protection REQ650 357


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

Name Values (Range) Unit Step Default Description


UL23LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
UL23LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
UL31HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
UL31HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
UL31LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
UL31LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
UL31LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits

PID-6736-SETTINGS v3

Table 308: CMSQI Non group settings (basic)


Name Values (Range) Unit Step Default Description
3I0DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
3I0ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
3I0Min 0.0 - 500.0 %IB 0.1 50.0 Minimum value in % of IBase
3I0Max 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase
3I0RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
3I0LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
3I0AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
Operation Off - - Off Operation Mode On / Off
On
I1DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
I1ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
I1Min 0.0 - 500.0 %IB 0.1 50.0 Minimum value in % of IBase
I1Max 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase
I1RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
I1AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
I2DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
I2ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
I2Min 0.0 - 500.0 %IB 0.1 50.0 Minimum value in % of IBase
Table continues on next page

358 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

Name Values (Range) Unit Step Default Description


I2Max 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase
I2RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
I2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
I2AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)

Table 309: CMSQI Non group settings (advanced)


Name Values (Range) Unit Step Default Description
3I0HiHiLim 0.0 - 500.0 %IB 0.1 150.0 High High limit in % of IBase
3I0HiLim 0.0 - 500.0 %IB 0.1 120.0 High limit in % of IBase
3I0LowLim 0.0 - 500.0 %IB 0.1 80.0 Low limit in % of IBase
3I0LowLowLim 0.0 - 500.0 %IB 0.1 60.0 Low Low limit in % of IBase
I1HiHiLim 0.0 - 500.0 %IB 0.1 150.0 High High limit in % of IBase
I1HiLim 0.0 - 500.0 %IB 0.1 120.0 High limit in % of IBase
I1LowLim 0.0 - 500.0 %IB 0.1 80.0 Low limit in % of IBase
I1LowLowLim 0.0 - 500.0 %IB 0.1 60.0 Low Low limit in % of IBase
I1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
I2HiHiLim 0.0 - 500.0 %IB 0.1 150.0 High High limit in % of IBase
I2HiLim 0.0 - 500.0 %IB 0.1 120.0 High limit in % of IBase
I2LowLim 0.0 - 500.0 %IB 0.1 80.0 Low limit in % of IBase
I2LowLowLim 0.0 - 500.0 %IB 0.1 60.0 Low Low limit in % of IBase

PID-6739-SETTINGS v2

Table 310: VMSQI Non group settings (basic)


Name Values (Range) Unit Step Default Description
3U0DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
3U0ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
3U0Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
3U0Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
3U0RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
3U0LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
3U0AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
Table continues on next page

Breaker protection REQ650 359


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

Name Values (Range) Unit Step Default Description


Operation Off - - Off Operation Mode On / Off
On
U1DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
U1ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
U1Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
U1Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
U1RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
U1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
U1AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
U2DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
U2ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
U2Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
U2Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
U2RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
U2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
U2AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
UAmpPreComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to pre-calibrate
voltage at 5% of Ur
UAmpPreComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to pre-calibrate
voltage at 30% of Ur
UAmpPreComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to pre-calibrate
voltage at 100% of Ur

Table 311: VMSQI Non group settings (advanced)


Name Values (Range) Unit Step Default Description
3U0HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
3U0HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
3U0LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
3U0LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
U1HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
U1HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
U1LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
U1LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
Table continues on next page

360 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

Name Values (Range) Unit Step Default Description


U2HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
U2HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
U2LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
U2LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase

PID-6737-SETTINGS v2

Table 312: VNMMXU Non group settings (basic)


Name Values (Range) Unit Step Default Description
UL1DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
Operation Off - - Off Operation Mode On / Off
On
UL1ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
UL1Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
UL1Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
UL1RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
UL1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
UL1AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
UL2DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
UL2ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
UL2Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
UL2Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
UL2RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
UL2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
UL2AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
UL3DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
UL3ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
UL3Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
UL3Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
Table continues on next page

Breaker protection REQ650 361


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

Name Values (Range) Unit Step Default Description


UL3RepTyp Cyclic - - Cyclic Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
UL3LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range,
common for all limits
UL3AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)

Table 313: VNMMXU Non group settings (advanced)


Name Values (Range) Unit Step Default Description
UL1HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
UL1HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
UL1LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
UL1LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage
at 100% of Ur
UL2HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
UL2HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
UL2LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
UL2LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
UL3HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
UL3HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
UL3LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
UL3LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase

11.1.6 Monitored data


PID-6713-MONITOREDDATA v3

Table 314: CVMMXN Monitored data


Name Type Values (Range) Unit Description
S REAL - MVA Apparent Power magnitude of
deadband value
P REAL - MW Active Power magnitude of deadband
value
Q REAL - MVAr Reactive Power magnitude of
deadband value
PF REAL - - Power Factor magnitude of deadband
value
U REAL - kV Calculated voltage magnitude of
deadband value
I REAL - A Calculated current magnitude of
deadband value
F REAL - Hz System frequency magnitude of
deadband value

362 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

PID-6735-MONITOREDDATA v3

Table 315: CMMXU Monitored data


Name Type Values (Range) Unit Description
IL1 REAL - A IL1 Amplitude, magnitude of reported
value
IL1ANGL REAL - deg IL1 Angle, magnitude of reported value
IL2 REAL - A IL2 Amplitude, magnitude of reported
value
IL2ANGL REAL - deg IL2 Angle, magnitude of reported
value
IL3 REAL - A IL3 Amplitude, magnitude of reported
value
IL3ANGL REAL - deg IL3 Angle, magnitude of reported
value

PID-6738-MONITOREDDATA v2

Table 316: VMMXU Monitored data


Name Type Values (Range) Unit Description
UL12 REAL - kV UL12 Amplitude, magnitude of
reported value
UL12ANGL REAL - deg UL12 Angle, magnitude of reported
value
UL23 REAL - kV UL23 Amplitude, magnitude of
reported value
UL23ANGL REAL - deg UL23 Angle, magnitude of reported
value
UL31 REAL - kV UL31 Amplitude, magnitude of
reported value
UL31ANGL REAL - deg UL31 Angle, magnitude of reported
value

PID-6736-MONITOREDDATA v3

Table 317: CMSQI Monitored data


Name Type Values (Range) Unit Description
3I0 REAL - A 3I0 Amplitude, magnitude of reported
value
3I0ANGL REAL - deg 3I0 Angle, magnitude of reported
value
I1 REAL - A I1 Amplitude, magnitude of reported
value
I1ANGL REAL - deg I1 Angle, magnitude of reported value
I2 REAL - A I2 Amplitude, magnitude of reported
value
I2ANGL REAL - deg I2 Angle, magnitude of reported value

Breaker protection REQ650 363


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

PID-6739-MONITOREDDATA v2

Table 318: VMSQI Monitored data


Name Type Values (Range) Unit Description
3U0 REAL - kV 3U0 Amplitude, magnitude of
reported value
3U0ANGL REAL - deg 3U0 Angle, magnitude of reported
value
U1 REAL - kV U1 Amplitude, magnitude of reported
value
U1ANGL REAL - deg U1 Angle, magnitude of reported value
U2 REAL - kV U2 Amplitude, magnitude of reported
value
U2ANGL REAL - deg U2 Angle, magnitude of reported value

PID-6737-MONITOREDDATA v2

Table 319: VNMMXU Monitored data


Name Type Values (Range) Unit Description
UL1 REAL - kV UL1 Amplitude, magnitude of reported
value
UL1ANGL REAL - deg UL1 Angle, magnitude of reported
value
UL2 REAL - kV UL2 Amplitude, magnitude of
reported value
UL2ANGL REAL - deg UL2 Angle, magnitude of reported
value
UL3 REAL - kV UL3 Amplitude, magnitude of
reported value
UL3ANGL REAL - deg UL3 Angle, magnitude of reported
value

11.1.7 Operation principle

11.1.7.1 Measurement supervision SEMOD54417-130 v4

The protection, control, and monitoring IEDs have functionality to measure and further
process information for currents and voltages obtained from the pre-processing blocks. The
number of processed alternate measuring quantities depends on the type of IED and built-in
options.

The information on measured quantities is available for the user at different locations:

• Locally by means of the local HMI


• Remotely using the monitoring tool within PCM600 or over the station bus
• Internally by connecting the analogue output signals to the Disturbance Report function

Phase angle reference SEMOD54417-303 v5


All phase angles are presented in relation to a defined reference channel. The General setting
parameter PhaseAngleRef defines the reference.

364 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

Zero point clamping SEMOD54417-137 v4


Measured value below zero point clamping limit is forced to zero. This allows the noise in the
input signal to be ignored. The zero point clamping limit is a general setting (XZeroDb where X
equals S, P, Q, PF, U, I, F, IL1-3, UL1-3, UL12-31, I1, I2, 3I0, U1, U2 or 3U0). Observe that this
measurement supervision zero point clamping might be overridden by the zero point clamping
used for the measurement values within CVMMXN.

Continuous monitoring of the measured quantity SEMOD54417-140 v5


Users can continuously monitor the measured quantity available in the function block by
means of four defined operating thresholds, see figure 199. The monitoring has two different
modes of operating:

• Overfunction, when the measured quantity exceeds the High limit (XHiLim) or High-high
limit (XHiHiLim) pre-set values
• Underfunction, when the measured quantity decreases under the Low limit (XLowLim) or
Low-low limit (XLowLowLim) pre-set values.

X_RANGE is illustrated in figure 199.

Y = Magnitude of the Measured Quantity

X_RANGE = 3
High-high limit

X_RANGE= 1 Hysteresis
High limit

X_RANGE=0

X_RANGE=0 t

Low limit

X_RANGE=2

Low-low limit
X_RANGE=4

IEC05000657-3-en.vsdx
IEC05000657 V3 EN-US

Figure 199: Presentation of operating limits


Each analogue output has one corresponding supervision level output (X_RANGE). The output
signal is an integer in the interval 0-4 (0: Normal, 1: High limit exceeded, 3: High-high limit
exceeded, 2: below Low limit and 4: below Low-low limit).

The logical value of the functional output signals changes according to figure 199.

The user can set the hysteresis (XLimHyst), which determines the difference between the
operating and reset value at each operating point, in wide range for each measuring channel
separately. The hysteresis is common for all operating values within one channel.

Actual value of the measured quantity SEMOD54417-150 v4


The actual value of the measured quantity is available locally and remotely. The measurement
is continuous for each measured quantity separately, but the reporting of the value to the
higher levels depends on the selected reporting mode. The following basic reporting modes
are available:

• Cyclic reporting (Cyclic)


• Amplitude dead-band supervision (Dead band)
• Integral dead-band supervision (Int deadband)

Breaker protection REQ650 365


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

• Amplitude Deadband and 5s cyclic


• Amplitude Deadband and 30s cyclic
• Amplitude Deadband and 1min cyclic

Cyclic reporting SEMOD54417-158 v3


The cyclic reporting of measured value is performed according to chosen setting (XRepTyp).
The measuring channel reports the value independent of amplitude or integral dead-band
reporting.

In addition to the normal cyclic reporting the IED also report spontaneously when measured
value passes any of the defined threshold limits.

Y
Value Reported Value Reported
Value Reported Value Reported
(1st)

Y3 Value Reported
Y2 Y4

Y1 Y5

t (*) t (*) t (*) t (*)

t
Value 1

Value 2

Value 3

Value 4

Value 5

(*)Set value for t: XDbRepInt IEC05000500-2-en.vsdx

IEC05000500 V2 EN-US

Figure 200: Periodic reporting

Amplitude dead-band supervision SEMOD54417-163 v6


If a measuring value is changed, compared to the last reported value, and the change is larger
than the ±ΔY pre-defined limits that are set by user (XDbRepInt), then the measuring channel
reports the new value to a higher level. This limits the information flow to a minimum
necessary. Figure 201 shows an example with the amplitude dead-band supervision. The
picture is simplified: the process is not continuous but the values are evaluated with a time
interval of one execution cycle from each other.

366 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

Value Reported
Y

Value Reported Value Reported


Value Reported
(1st)
Y3 Y
Y
Y2 Y
Y
Y
Y
Y1

IEC99000529-2-en.vsdx

IEC99000529 V2 EN-US

Figure 201: Amplitude dead-band supervision reporting


After the new value is reported, the ±ΔY limits for dead-band are automatically set around it.
The new value is reported only if the measured quantity changes more than defined by the ±ΔY
set limits.

Integral dead-band reporting SEMOD54417-167 v4


The measured value is reported if the time integral of all changes exceeds the pre-set limit
(XDbRepInt), figure 202, where an example of reporting with integral dead-band supervision is
shown. The picture is simplified: the process is not continuous but the values are evaluated
with a time interval of one execution cycle from each other.

The last value reported, Y1 in figure 202 serves as a basic value for further measurement. A
difference is calculated between the last reported and the newly measured value and is
multiplied by the time increment (discrete integral). The absolute values of these integral
values are added until the pre-set value is exceeded. This occurs with the value Y2 that is
reported and set as a new base for the following measurements (as well as for the values Y3,
Y4 and Y5).

The integral dead-band supervision is particularly suitable for monitoring signals with small
variations that can last for relatively long periods.

Breaker protection REQ650 367


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

Y A1 >=
A >= pre-set value
A2 >=
pre-set value pre-set value
Y3 A3 + A4 + A5 + A6 + A7 >=
pre-set value
Y2 A1 A2
A4 A6
Value Reported Y4 A3 A5 A7
Value
(1st) Value
A Reported Y5
Reported Value
Reported Value
Y1 Reported

t
IEC99000530-2-en.vsdx

IEC99000530 V2 EN-US

Figure 202: Reporting with integral dead-band supervision

Amplitude deadband and xx cyclic (xx: 5 sec, 30 sec, 1 min) GUID-297D6481-EDFA-4A38-BC9D-29538491254D v1


In this mode of operation, the reporting interval will be cyclic like in reporting type cyclic. This
cyclic time has three options: 5sec, 30 sec and 1 min.

Additionally, if a measuring value has changed from the last reported value, and the change is
larger than ±ΔY predefined limits that are set by user (XDbRepInt), then the measuring channel
reports the new value to a higher level immediately irrespective of cyclic trigger. See Figure
203 for example.

368 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

Value

Y1...Y7 : Cyclic reported values, depending upon time Δt.


Y’ and Y” : Deadband reported value, change is greater than setting

Value
Reported

Y5
Y6

Y’ -ΔY

+ΔY
Y1 Y7
Y2 Y4 Y”

Y3

Δt Δt Δt Δt Δt Δt

Time
IEC16000109-1-en.vsdx
IEC16000109 V1 EN-US

Figure 203: Example of value reporting in mode dead band and xx cyclic (xx : 5 sec , 30
sec, 1 min)

11.1.7.2 Measurements CVMMXN SEMOD54417-172 v3

Mode of operation SEMOD54417-174 v7


The measurement function must be connected to three-phase current and three-phase voltage
input in the configuration tool (group signals), but it is capable to measure and calculate
above mentioned quantities in nine different ways depending on the available VT inputs
connected to the IED. The end user can freely select by a parameter setting, which one of the
nine available measuring modes shall be used within the function. Available options are
summarized in the following table:

Breaker protection REQ650 369


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

Set value Formula used for complex, Formula used for voltage Comment
for three-phase power calculation and current magnitude
parameter calculation
“Mode”
1 L1, L2, L3 Used when three phase-to-
* * *
S = U L1 × I L1 + U L 2 × I L 2 + U L 3 × I L 3 U = ( U L1 + U L 2 + U L 3 ) / 3 earth voltages are available
EQUATION1385 V1 EN-US (Equation 38) I = ( I L1 + I L 2 + I L 3 ) / 3

EQUATION1386 V1 EN-US (Equation 39)


2 Arone Used when two phase-to-
S = U L1 L 2 × I L*1 - U L 2 L 3 × I L* 3 U = ( U L1 L 2 + U L 2 L 3 ) / 2 phase voltages are
available
(Equation 40)
EQUATION1387 V1 EN-US
I = ( I L1 + I L 3 ) / 2
EQUATION1388 V1 EN-US (Equation 41)
3 PosSeq Used when only
S = 3 × U PosSeq × I PosSeq
*
U = 3 × U PosSeq symmetrical three phase
power shall be measured
(Equation 42)
EQUATION1389 V1 EN-US
I = I PosSeq
EQUATION1390 V1 EN-US (Equation 43)
4 L1L2 Used when only UL1L2
S = U L1 L 2 × ( I L*1 - I L* 2 ) U = U L1 L 2 phase-to-phase voltage is
available
(Equation 44)
I = ( I L1 + I L 2 ) / 2
EQUATION1391 V1 EN-US

EQUATION1392 V1 EN-US (Equation 45)


5 L2L3 Used when only UL2L3
S = U L 2 L 3 × ( I L* 2 - I L* 3 ) U = U L2 L3 phase-to-phase voltage is
available
(Equation 46)
I = ( I L2 + I L3 ) / 2
EQUATION1393 V1 EN-US

EQUATION1394 V1 EN-US (Equation 47)


6 L3L1 Used when only UL3L1
S = U L 3 L1 × ( I L* 3 - I L*1 ) U = U L 3 L1 phase-to-phase voltage is
available
(Equation 48)
I = ( I L 3 + I L1 ) / 2
EQUATION1395 V1 EN-US

EQUATION1396 V1 EN-US (Equation 49)


7 L1 Used when only UL1 phase-
S = 3 × U L1 × I L*1 U = 3 × U L1 to-earth voltage is
available
(Equation 50)
I = I L1
EQUATION1397 V1 EN-US

EQUATION1398 V1 EN-US (Equation 51)


8 L2 Used when only UL2 phase-
S = 3 × U L 2 × I L* 2 U = 3 × U L2 to-earth voltage is
available
(Equation 52)
I = IL2
EQUATION1399 V1 EN-US

EQUATION1400 V1 EN-US (Equation 53)


9 L3 Used when only UL3 phase-
S = 3 × U L 3 × I L* 3 U = 3 × U L3 to-earth voltage is
available
(Equation 54)
I = I L3
EQUATION1401 V1 EN-US

EQUATION1402 V1 EN-US (Equation 55)


* means complex conjugated value

370 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

It shall be noted that only in the first two operating modes that is, 1 & 2 the measurement
function calculates the three-phase power accurately. In other operating modes that is, from 3
to 9 it calculates the three-phase power under assumption that the power system is fully
symmetrical. Once the complex apparent power is calculated then the P, Q, S, & PF are
calculated in accordance with the following formulas:

P = Re( S )
EQUATION1403 V1 EN-US (Equation 56)

Q = Im( S )
EQUATION1404 V1 EN-US (Equation 57)

S = S = P2 + Q2
EQUATION1405 V1 EN-US (Equation 58)

PF = cosj = P
S
EQUATION1406 V1 EN-US (Equation 59)

Additionally to the power factor value, the two binary output signals from the function are
provided which indicates the angular relationship between the current and voltage phasors.
Binary output signal ILAG is set TRUE when current phasor is lagging behind voltage phasor.
Binary output signal ILEAD is set TRUE when current phasor is leading the voltage phasor.

Each analogue output has a corresponding supervision level output (X_RANGE). The output
signal is an integer in the interval 0-4, see section "Measurement supervision".

Calibration of analog inputs SEMOD54417-293 v5


Measured currents and voltages used in the CVMMXN function can be calibrated to get 0.5
class measuring accuracy. This is achieved by amplitude and angle compensation at 5, 30 and
100% of rated current and voltage. The compensation below 5% and above 100% is constant
and linear in between, see example in figure 204.

Breaker protection REQ650 371


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

IEC05000652 V2 EN-US

Figure 204: Calibration curves


The first current and voltage phase signal, in the group signals will be used as reference. The
amplitude and angle compensation will be used for other related input signals.

Low pass filtering SEMOD54417-233 v4


In order to minimize the influence of the noise signal on the measurement it is possible to
introduce the recursive, low pass filtering of the measured values for P, Q, S, U, I and power
factor. This will make slower measurement response to the step changes in the measured
quantity. Filtering is performed in accordance with the following recursive formula:

X = k × X Old + (1 - k ) × X Calculated
EQUATION1407 V1 EN-US (Equation 60)

where:
X is a new measured value (that is P, Q, S, U, I or PF) to be given out from the function
XOld is the measured value given from the measurement function in previous execution cycle

XCalculated is the new calculated value in the present execution cycle

k is settable parameter by the end user which influence the filter properties

Default value for parameter k is 0.00. With this value the new calculated value is immediately
given out without any filtering (that is, without any additional delay). When k is set to value
bigger than 0, the filtering is enabled. Appropriate value of k shall be determined separately
for every application. Some typical value for k =0.14.

Zero point clamping SEMOD54417-250 v5


In order to avoid erroneous measurements when either current or voltage signal is not
present, it is possible for the end user to set the amplitudeIGenZeroDb level for current and
voltage measurement UGenZeroDb is forced to zero. When either current or voltage

372 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

measurement is forced to zero automatically the measured values for power (P, Q and S) and
power factor are forced to zero as well. Since the measurement supervision functionality,
included in CVMMXN, is using these values the zero clamping will influence the subsequent
supervision (observe the possibility to do zero point clamping within measurement
supervision, see section "Measurement supervision").

Compensation facility SEMOD54417-253 v5


In order to compensate for small amplitude and angular errors in the complete measurement
chain (CT error, VT error, IED input transformer errors and so on.) it is possible to perform on
site calibration of the power measurement. This is achieved by setting the complex constant
which is then internally used within the function to multiply the calculated complex apparent
power S. This constant is set as amplitude (setting parameter PowAmpFact, default value
1.000) and angle (setting parameter PowAngComp, default value 0.0 degrees). Default values
for these two parameters are done in such way that they do not influence internally calculated
value (complex constant has default value 1). In this way calibration, for specific operating
range (for example, around rated power) can be done at site. However, to perform this
calibration it is necessary to have an external power meter with high accuracy class available.

Directionality SEMOD54417-256 v7
If CT earthing parameter is set as described in section "Analog inputs", active and reactive
power will be always measured towards the protected object. This is shown in the following
figure 205.

Busbar

IED

P Q

Protected
Object
IEC09000038-1-en.vsd
IEC09000038-1-EN V1 EN-US

Figure 205: Internal IED directionality convention for P & Q measurements


Practically, it means that active and reactive power will have positive values when they flow
from the busbar towards the protected object and they will have negative values when they
flow from the protected object towards the busbar.

In some application, for example, when power is measured on the secondary side of the power
transformer it might be desirable, from the end client point of view, to have actually opposite
directional convention for active and reactive power measurements. This can be easily
achieved by setting parameter PowAngComp to value of 180.0 degrees. With such setting the

Breaker protection REQ650 373


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

active and reactive power will have positive values when they flow from the protected object
towards the busbar.

Frequency SEMOD54417-261 v2
Frequency is actually not calculated within measurement block. It is simply obtained from the
pre-processing block and then just given out from the measurement block as an output.

11.1.7.3 Phase current measurement CMMXU SEMOD54417-264 v7

The Phase current measurement (CMMXU) function must be connected to three-phase current
input in the configuration tool to be operable. Currents handled in the function can be
calibrated to get better then 0.5 class measuring accuracy for internal use, on the outputs and
IEC 61850. This is achieved by amplitude and angle compensation at 5, 30 and 100% of rated
current. The compensation below 5% and above 100% is constant and linear in between, see
figure 204.

Phase currents (amplitude and angle) are available on the outputs and each amplitude output
has a corresponding supervision level output (ILx_RANG). The supervision output signal is an
integer in the interval 0-4, see section "Measurement supervision".

11.1.7.4 Phase-phase and phase-neutral voltage measurements VMMXU, VNMMXU SEMOD54417-268 v6

The voltage function must be connected to three-phase voltage input in the configuration tool
to be operable. Voltages are handled in the same way as currents when it comes to class 0.5
calibrations, see above.

The voltages (phase-to-earth or phase-to-phase voltage, amplitude and angle) are available on
the outputs and each amplitude output has a corresponding supervision level output
(ULxy_RANG). The supervision output signal is an integer in the interval 0-4, see
section "Measurement supervision".

11.1.7.5 Voltage and current sequence measurements VMSQI, CMSQI SEMOD54417-299 v6

The measurement functions must be connected to three-phase current (CMSQI) or voltage


(VMSQI) input in the configuration tool to be operable. No outputs, other than X_RANG, are
calculated within the measuring blocks and it is not possible to calibrate the signals. Input
signals are obtained from the pre-processing block and transferred to corresponding output.

Positive, negative and three times zero sequence quantities are available on the outputs
(voltage and current, amplitude and angle). Each amplitude output has a corresponding
supervision level output (X_RANGE). The output signal is an integer in the interval 0-4, see
section "Measurement supervision".

11.1.8 Technical data


M12386-1 v16

Table 320: Power system measurement CVMMXN technical data


Function Range or value Accuracy
Frequency (0.95-1.05) x fr ±2.0 mHz

Voltage (10 to 300) V ±0.3% of U at U≤ 50 V


±0.2% of U at U> 50 V
Current (0.1-4.0) x Ir ±0.8% of I at 0.1 x Ir< I < 0.2 x Ir
± 0.5% of I at 0.2 x Ir< I < 0.5 x Ir
±0.2% of I at 0.5 x Ir< I < 4.0 x Ir

Table continues on next page

374 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

Function Range or value Accuracy


Active power, P (10 to 300) V ±0.5% of Sr at S ≤0.5 x Sr
(0.1-4.0) x Ir ±0.5% of S at S > 0.5 x Sr

(100 to 220) V ±0.2% of P


(0.5-2.0) x Ir
cos φ> 0.7
Reactive power, Q (10 to 300) V ±0.5% of Sr at S ≤0.5 x Sr
(0.1-4.0) x Ir ±0.5% of S at S > 0.5 x Sr

(100 to 220) V ±0.2% of Q


(0.5-2.0) x Ir
cos φ< 0.7
Apparent power, S (10 to 300) V ±0.5% of Sr at S ≤0.5 x Sr
(0.1-4.0) x Ir ±0.5% of S at S >0.5 x Sr

(100 to 220) V ±0.2% of S


(0.5-2.0) x Ir

Power factor, cos (φ) (10 to 300) V <0.02


(0.1-4.0) x Ir

(100 to 220) V <0.01


(0.5-2.0) x Ir

GUID-5E04B3F9-E1B7-4974-9C0B-DE9CD4A2408F v6

Table 321: CMMXU technical data


Function Range or value Accuracy
Current at symmetrical load (0.1-4.0) × Ir ±0.3% of Ir at I ≤ 0.5 × Ir
±0.3% of I at I > 0.5 × Ir

Phase angle at symmetrical (0.1-4.0) × Ir ±1.0 degrees at 0.1 × Ir < I ≤ 0.5 × Ir


load ±0.5 degrees at 0.5 × Ir < I ≤ 4.0 × Ir

GUID-374C2AF0-D647-4159-8D3A-71190FE3CFE0 v5

Table 322: VMMXU technical data


Function Range or value Accuracy
Voltage (10 to 300) V ±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
Phase angle (10 to 300) V ±0.5 degrees at U ≤ 50 V
±0.2 degrees at U > 50 V

GUID-9B8A7FA5-9C98-4CBD-A162-7112869CF030 v5

Table 323: CMSQI technical data


Function Range or value Accuracy
Current positive sequence, I1 (0.1–4.0) × Ir ±0.3% of Ir at I ≤ 0.5 × Ir
Three phase settings ±0.3% of I at I > 0.5 × Ir

Current zero sequence, 3I0 (0.1–1.0) × Ir ±0.3% of Ir at I ≤ 0.5 × Ir


Three phase settings ±0.3% of I at I > 0.5 × Ir

Current negative sequence, I2 (0.1–1.0) × Ir ±0.3% of Ir at I ≤ 0.5 × Ir


Three phase settings ±0.3% of I at I > 0.5 × Ir

Phase angle (0.1–4.0) × Ir ±1.0 degrees at 0.1 × Ir < I ≤ 0.5 × Ir


±0.5 degrees at 0.5 × Ir < I ≤ 4.0 × Ir

Breaker protection REQ650 375


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

GUID-47094054-A828-459B-BE6A-D7FA1B317DA7 v6

Table 324: VMSQItechnical data


Function Range or value Accuracy
Voltage positive sequence, U1 (10 to 300) V ±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
Voltage zero sequence, 3U0 (10 to 300) V ±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
Voltage negative sequence, U2 (10 to 300) V ±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
Phase angle (10 to 300) V ±0.5 degrees at U ≤ 50 V
±0.2 degrees at U > 50 V

GUID-ED634B6D-9918-464F-B6A4-51B78129B819 v6

Table 325: VNMMXU technical data


Function Range or value Accuracy
Voltage (5 to 175) V ±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
Phase angle (5 to 175) V ±0.5 degrees at U ≤ 50 V
±0.2 degrees at U > 50 V

11.2 Gas medium supervision SSIMG GUID-358AD8F8-AE06-4AEA-9969-46E5299D5B4B v3

11.2.1 Identification
GUID-AD96C26E-C3E5-4B21-9ED6-12E540954AC3 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Insulation gas monitoring function SSIMG - 63

11.2.2 Functionality GUID-0692CD0D-F33E-4370-AC91-B216CAAAFC28 v6

Insulation supervision for gas medium (SSIMG) is used for monitoring the circuit breaker
condition. Binary information based on the gas pressure in the circuit breaker is used as input
signals to the function. In addition, the function generates alarms based on received
information.

11.2.3 Function block


GUID-94B75A6D-973D-4F1F-8643-F2128AD31CC4 v3

SSIMG
BLOCK LOCKOUT
BLKALM PRESLO
SENPRES TEMPLO
SENTEMP ALARM
SENPRESALM PRESALM
SENPRESLO TEMPALM
SETPLO PRESSURE
SETTLO TEMP
RESETLO
IEC09000129-2-en.vsdx
IEC09000129 V2 EN-US

Figure 206: SSIMG function block

376 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

11.2.4 Signals
GUID-89749F71-CAEB-4A57-A1F0-148CCF68E97E v2

PID-6950-INPUTSIGNALS v6

Table 326: SSIMG Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
BLKALM BOOLEAN 0 Block all the alarms
SENPRES REAL 0.0 Pressure input from CB
SENTEMP REAL 0.0 Temperature of the insulation medium from CB
SENPRESALM BOOLEAN 0 Pressure alarm signal
SENPRESLO BOOLEAN 0 Pressure lockout signal
SETPLO BOOLEAN 0 Set pressure lockout
SETTLO BOOLEAN 0 Set temperature lockout
RESETLO BOOLEAN 0 Reset pressure and temperature lockout

PID-6950-OUTPUTSIGNALS v6

Table 327: SSIMG Output signals


Name Type Description
LOCKOUT BOOLEAN Pressure below lockout level or temperature above lockout
level
PRESLO BOOLEAN Pressure below lockout level
TEMPLO BOOLEAN Temperature above lockout level
ALARM BOOLEAN Pressure below alarm level or temperature above alarm level
PRESALM BOOLEAN Pressure below alarm level
TEMPALM BOOLEAN Temperature above alarm level
PRESSURE REAL Pressure service value
TEMP REAL Temperature of the insulation medium

11.2.5 Settings
PID-6950-SETTINGS v6

Table 328: SSIMG Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
PresAlmLimit 1.00 - 100.00 - 0.01 5.00 Alarm setting for pressure
PresLOLimit 1.00 - 100.00 - 0.01 3.00 Pressure lockout setting
TempAlarmLimit -40.00 - 200.00 - 0.01 30.00 Temperature alarm level setting of the
medium
TempLOLimit -40.00 - 200.00 - 0.01 30.00 Temperature lockout level of the
medium
tPressureAlarm 0.000 - 60.000 s 0.001 0.000 Time delay for pressure alarm
tPressureLO 0.000 - 60.000 s 0.001 0.000 Time delay for pressure lockout
indication
tTempAlarm 0.000 - 60.000 s 0.001 0.000 Time delay for temperature alarm
Table continues on next page

Breaker protection REQ650 377


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

Name Values (Range) Unit Step Default Description


tTempLockOut 0.000 - 60.000 s 0.001 0.000 Time delay for temperture lockout
tResetPresAlm 0.000 - 60.000 s 0.001 0.000 Reset time delay for pressure alarm
tResetPresLO 0.000 - 60.000 s 0.001 0.000 Reset time delay for pressure lockout
tResetTempLO 0.000 - 60.000 s 0.001 0.000 Reset time delay for temperture
lockout
tResetTempAlm 0.000 - 60.000 s 0.001 0.000 Reset time delay for temperture alarm

11.2.6 Monitored data


PID-6950-MONITOREDDATA v5

Table 329: SSIMG Monitored data


Name Type Values (Range) Unit Description
PRESSURE REAL - - Pressure service value
TEMP REAL - deg Temperature of the insulation
medium

11.2.7 Operation principle GUID-359458EA-FFAA-4A44-A8E8-9469CA069C80 v7

Gas medium supervision SSIMG is used to monitor the gas pressure in the circuit breaker.
Binary inputs of gas density SENPRESALM, SENPRESLO, and gas pressure signal SENPRES, are
taken into account to initiate the alarm PRESALM and the lockout PRESLO. When SENPRES is
less than PresAlmLimit or binary signal from CB SENPRESALM is high, the gas pressure alarm
PRESALM will be initiated. Similarly, if pressure input SENPRES is less than PresLOLimit or
binary signal from CB SENPRESLO is high, PRESLO will be initiated.

There may be sudden change in pressure of the gas for a very small time, for which the
function need not to initiate any alarm. To avoid the intermittent alarm, two time delays
tPressureAlarm or tPressureLO have been included. If the pressure goes below the settings for
more than these time delays, the corresponding alarm PRESALM or lockout PRESLO will be
initiated. The SETPLO binary input is used for setting the gas pressure lockout PRESLO. The
PRESLO output retains the last value until it is reset by using the binary input RESETLO. The
binary input BLKALM can be used to block the alarms, and the BLOCK input can block both
alarm and the lockout indications.

Temperature of the medium is available from the input signal of temperature. The signal is
monitored to detect high temperature.

When temperature input SENTEMP is above TempAlarmLimit, temperature alarm TEMPALM


will be initiated. Similarly, if temperature input SENTEMP is above TempLOLimit, temperature
lockout TEMPLO will be initiated.

There may be sudden change in temperature of the medium for a very small time, for which the
function need not to initiate any alarm. To avoid the intermittent alarm, two time delays
tTempAlarm or tTempLockOut have been included. If the temperature goes above the settings
for more than these time delays, the corresponding alarm TEMPALM or lockout TEMPLO will be
initiated. The SETTLO binary input is used for setting the temperature lockout TEMPLO. The
TEMPLO output retains the last value until it is reset by using the binary input RESETLO. The
binary input BLKALM can be used to block the alarms, and the BLOCK input can block both
alarm and the lockout indications.

The output ALARM goes high if the pressure alarm condition or the temperature alarm
condition exists inside the circuit breaker. The output ALARM can be blocked by activating
BLOCK or BLKALM inputs.

378 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

The output LOCKOUT goes high if the pressure lockout condition or the temperature lockout
condition exists inside the circuit breaker and it resets by using the binary input RESETLO. The
output LOCKOUT can be blocked by activating BLOCK input.

11.2.8 Technical data


GUID-F034B396-6600-49EF-B0A5-8ED96766A6A0 v8

Table 330: SSIMG Technical data


Function Range or value Accuracy
Pressure alarm level 1.00-100.00 ±10.0% of set value
Pressure lockout level 1.00-100.00 ±10.0% of set value
Temperature alarm level -40.00-200.00 ±2.5% of set value
Temperature lockout level -40.00-200.00 ±2.5% of set value
Time delay for pressure alarm (0.000-60.000) s ±0.2% or ±250ms whichever is
greater
Reset time delay for pressure (0.000-60.000) s ±0.2% or ±250ms whichever is
alarm greater
Time delay for pressure lockout (0.000-60.000) s ±0.2% or ±250ms whichever is
greater
Time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is
greater
Reset time delay for temperature (0.000-60.000) s ±0.2% or ±250ms whichever is
alarm greater
Time delay for temperature (0.000-60.000) s ±0.2% or ±250ms whichever is
lockout greater

11.3 Liquid medium supervision SSIML GUID-37669E94-4830-4C96-8A67-09600F847F23 v3

11.3.1 Identification
GUID-4CE96EF6-42C6-4F2E-A190-D288ABF766F6 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Insulation liquid monitoring function SSIML - 71

11.3.2 Functionality GUID-3B1A665F-60A5-4343-85F4-AD9C066CBE8D v7

Insulation supervision for liquid medium (SSIML) is used for monitoring the oil insulated device
condition. For example, transformers, shunt reactors, and so on. Binary information based on
the oil level in the oil insulated devices are used as input signals to the function. In addition,
the function generates alarms based on the received information.

Breaker protection REQ650 379


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

11.3.3 Function block GUID-AC82A86C-495D-4CBD-9BF9-3CC760591AA9 v3

SSIML
BLOCK LOCKOUT
BLKALM LVLLO
SENLEVEL TEMPLO
SENTEMP ALARM
SENLVLALM LVLALM
SENLVLLO TEMPALM
SETLLO LEVEL
SETTLO TEMP
RESETLO
IEC09000128-2-en.vsdx
IEC09000128 V2 EN-US

Figure 207: SSIML function block

11.3.4 Signals
GUID-0C378BB3-2104-417F-94B5-16EFC55151FE v2

PID-6951-INPUTSIGNALS v7

Table 331: SSIML Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
BLKALM BOOLEAN 0 Block all the alarms
SENLEVEL REAL 0.0 Level input from CB
SENTEMP REAL 0.0 Temperature of the insulation medium from CB
SENLVLALM BOOLEAN 0 Level alarm signal
SENLVLLO BOOLEAN 0 Level lockout signal
SETLLO BOOLEAN 0 Set level lockout
SETTLO BOOLEAN 0 Set temperature lockout
RESETLO BOOLEAN 0 Reset level and temperature lockout

PID-6951-OUTPUTSIGNALS v7

Table 332: SSIML Output signals


Name Type Description
LOCKOUT BOOLEAN Level below lockout level or temperature above lockout level
LVLLO BOOLEAN Level below lockout level
TEMPLO BOOLEAN Temperature above lockout level
ALARM BOOLEAN Level below alarm level or temperature above alarm level
LVLALM BOOLEAN Level below alarm level
TEMPALM BOOLEAN Temperature above alarm level
LEVEL REAL Level service value
TEMP REAL Temperature of the insulation medium

380 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

11.3.5 Settings
PID-6951-SETTINGS v7

Table 333: SSIML Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
LevelAlmLimit 1.00 - 100.00 - 0.01 5.00 Alarm setting for level
LevelLOLimit 1.00 - 100.00 - 0.01 3.00 Level lockout setting
TempAlarmLimit -40.00 - 200.00 - 0.01 30.00 Temperature alarm level setting of the
medium
TempLOLimit -40.00 - 200.00 - 0.01 30.00 Temperature lockout level of the
medium
tLevelAlarm 0.000 - 60.000 s 0.001 0.000 Time delay for level alarm
tLevelLockOut 0.000 - 60.000 s 0.001 0.000 Time delay for level lockout indication
tTempAlarm 0.000 - 60.000 s 0.001 0.000 Time delay for temperature alarm
tTempLockOut 0.000 - 60.000 s 0.001 0.000 Time delay for temperture lockout
tResetLevelAlm 0.000 - 60.000 s 0.001 0.000 Reset time delay for level alarm
tResetLevelLO 0.000 - 60.000 s 0.001 0.000 Reset time delay for level lockout
tResetTempLO 0.000 - 60.000 s 0.001 0.000 Reset time delay for temperture
lockout
tResetTempAlm 0.000 - 60.000 s 0.001 0.000 Reset time delay for temperture alarm

11.3.6 Monitored data


PID-6951-MONITOREDDATA v5

Table 334: SSIML Monitored data


Name Type Values (Range) Unit Description
LEVEL REAL - - Level service value
TEMP REAL - deg Temperature of the insulation
medium

11.3.7 Operation principle GUID-F4340B59-90D0-4EA7-9FD8-F21D425C884A v8

Liquid medium supervision SSIML is used to monitor the oil level in the oil insulated devices.
Binary inputs of oil level SENLVLALM, SENLVLLO and oil level signal SENLEVEL are taken into
account to initiate the alarm LVLALM and the lockout LVLLO. When SENLEVEL is less than
LevelAlmLimit or binary signal from oil insulated device SENLVLALM is high, the oil level
indication alarm LVLALM will be initiated. Similarly, if oil level input SENLEVEL is less than
LevelLOLimit or binary signal from oil insulated device SENLVLLO is high, the oil level
indication lockout LVLLO will be initiated.

There may be sudden change in oil level for a very small time, for which the function need not
to initiate any alarm. To avoid the intermittent alarm, two time delays tLevelAlarm or
tLevelLockOut have been included. If the oil level goes below the settings for more than these
time delays, the corresponding alarm LVLALM or lockout LVLLO will be initiated. The SETLLO
binary input is used for setting the liquid level lockout LVLLO. The LVLLO output retains the
last value until it is reset by using the binary input RESETLO. The binary input BLKALM can be
used for blocking the alarms, and the BLOCK input can block both alarms and the lockout
indication.

Breaker protection REQ650 381


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

Temperature of the medium is available from the input signal of temperature. The signal is
monitored to detect high temperature.

When temperature input SENTEMP is above TempAlarmLimit, temperature alarm TEMPALM


will be initiated. Similarly, if temperature input SENTEMP is above TempLOLimit, temperature
lockout TEMPLO will be initiated.

There may be sudden change in temperature of the medium for a very small time, for which the
function need not to initiate any alarm. To avoid the intermittent alarm, two time delays
tTempAlarm or tTempLockOuthave been included. If the temperature goes above the settings
for more than these time delays, the corresponding alarm TEMPALM or lockout TEMPLO will be
initiated. The SETTLO binary input is used for setting the temperature lockout TEMPLO. The
TEMPLO output retains the last value until it is reset by using the binary input RESETLO. The
binary input BLKALM can be used for blocking the alarms, and the BLOCK input can block both
alarm and the lockout indications.

The output ALARM goes high if the level alarm condition or the temperature alarm condition
exists in the oil insulated devices. The output ALARM can be blocked by activating BLOCK or
BLKALM inputs.

The output LOCKOUT goes high if the pressure lockout condition or the temperature lockout
condition exists in the oil insulated devices and it resets by using the binary input RESETLO.
The output LOCKOUT can be blocked by activating BLOCK input.

11.3.8 Technical data


GUID-83B0F607-D898-403A-94FD-7FE8D45C73FF v8

Table 335: SSIMLTechnical data


Function Range or value Accuracy
Oil alarm level 1.00-100.00 ±10.0% of set value
Oil lockout level 1.00-100.00 ±10.0% of set value
Temperature alarm level -40.00-200.00 ±2.5% of set value
Temperature lockout level -40.00-200.00 ±2.5% of set value
Time delay for oil alarm (0.000-60.000) s ±0.2% or ±250ms whichever is
greater
Reset time delay for oil alarm (0.000-60.000) s ±0.2% or ±250ms whichever is
greater
Time delay for oil lockout (0.000-60.000) s ±0.2% or ±250ms whichever is
greater
Time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is
greater
Reset time delay for temperature (0.000-60.000) s ±0.2% or ±250ms whichever is
alarm greater
Time delay for temperature (0.000-60.000) s ±0.2% or ±250ms whichever is
lockout greater

11.4 Breaker monitoring SSCBR

11.4.1 Identification GUID-0FC081B2-0BC8-4EB8-9529-B941E51F18EE v7

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Breaker monitoring SSCBR - -

382 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

11.4.2 Functionality GUID-E1FD74C3-B9B6-4E11-AA1B-7E7F822FB4DD v13

11.4.3 Function block GUID-B002ED61-5092-4E9E-AEB6-E4A4310BDAF2 v11

SSCBR
I3P* OPENPOS
BLOCK CLOSEPOS
BLKALM INVDPOS
TRIND TRCMD
POSOPEN TRVTOPAL
POSCLOSE TRVTCLAL
PRESALM OPERALM
PRESLO OPERLO
SPRCHRST CBLIFEAL
SPRCHRD MONALM
RSTCBWR IPOWALPH
RSTTRVT IPOWLOPH
RSTIPOW SPCHALM
RSTSPCHT GPRESALM
GPRESLO

IEC13000231-2-en.vsd
IEC13000231 V2 EN-US

Figure 208: SSCBR function block

11.4.4 Signals
PID-3267-INPUTSIGNALS v10

Table 336: SSCBR Input signals


Name Type Default Description
I3P GROUP - Group signal for current input
SIGNAL
BLOCK BOOLEAN 0 Block all the alarm and lockout indication
BLKALM BOOLEAN 0 Block all the alarms
TRIND BOOLEAN 0 Trip command from trip circuit
POSOPEN BOOLEAN 0 Signal for open position of apparatus from I/O
POSCLOSE BOOLEAN 0 Signal for close position of apparatus from I/O
PRESALM BOOLEAN 0 Pressure alarm indication from CB
PRESLO BOOLEAN 0 Pressure lockout indication from CB
SPRCHRST BOOLEAN 0 CB spring charging started indication signal
SPRCHRD BOOLEAN 0 CB spring charged indication signal
RSTCBWR BOOLEAN 0 Reset of CB remaining life and operation counter
RSTTRVT BOOLEAN 0 Reset of CB closing and opening travel times
RSTIPOW BOOLEAN 0 Reset of accumulated I^CurrExponent
RSTSPCHT BOOLEAN 0 Reset of CB spring charging time

PID-3267-OUTPUTSIGNALS v10

Table 337: SSCBR Output signals


Name Type Description
OPENPOS BOOLEAN CB is in open position
CLOSEPOS BOOLEAN CB is in closed position
INVDPOS BOOLEAN CB is in Invalid Position
Table continues on next page

Breaker protection REQ650 383


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

Name Type Description


TRCMD BOOLEAN Open command issued to CB
TRVTOPAL BOOLEAN CB open travel time exceeded set value
TRVTCLAL BOOLEAN CB close travel time exceeded set value
OPERALM BOOLEAN Number of CB operations exceeds alarm limit
OPERLO BOOLEAN Number of CB operations exceeds lockout limit
CBLIFEAL BOOLEAN Remaining life of CB reduced to Life alarm level
MONALM BOOLEAN CB 'not operated for long time' alarm
IPOWALPH BOOLEAN Accum I^CurrExponent integr over CB open travel time
exceeds alarm limit
IPOWLOPH BOOLEAN Accum I^CurrExponent integr over CB open travel time
exceeds lockout limit
SPCHALM BOOLEAN Spring charging time has crossed the set value
GPRESALM BOOLEAN Pressure below alarm level
GPRESLO BOOLEAN Pressure below lockout level

11.4.5 Settings
PID-3267-SETTINGS v10

Table 338: SSCBR Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
PhSel Phase L1 - - Phase L1 Phase selection
Phase L2
Phase L3
RatedOperCurr 100.00 - 5000.00 A 0.01 1000.00 Rated operating current of the
breaker
OperNoRated 1 - 99999 - 1 10000 Number of operations possible at
rated current
RatedFltCurr 500.00 - 99999.99 A 0.01 5000.00 Rated fault current of the breaker
OperNoFault 1 - 10000 - 1 1000 Number of operations possible at
rated fault current
tTrOpenAlm 0.000 - 0.200 s 0.001 0.040 Alarm level for open travel time
tTrCloseAlm 0.000 - 0.200 s 0.001 0.040 Alarm level for close travel time
OperAlmLevel 0 - 9999 - 1 200 Alarm level for number of operations
OperLOLevel 0 - 9999 - 1 300 Lockout level for number of
operations
AccSelCal Aux Contact - - Trip Signal Accumulated energy calculation
Trip Signal selection
CurrExponent 0.50 - 3.00 - 0.01 2.00 Current exponent value used for
energy calculation
AccStopCurr 5.00 - 100.00 %IB 0.01 10.00 RMS current level below which energy
accumulation stops
AlmAccCurrPwr 0.00 - 20000.00 - 0.01 2500.00 Alarm level for accumulated
I^CurrExponent integrated over CB
open travel time
Table continues on next page

384 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

Name Values (Range) Unit Step Default Description


LOAccCurrPwr 0.00 - 20000.00 - 0.01 2500.00 Lockout level for accumulated
I^CurrExponent integrated over CB
open travel time
SpChAlmTime 0.00 - 60.00 s 0.01 1.00 Alarm level for spring charging time
InitCBRemLife 1 - 99999 - 1 10000 Initial value for remaining life
estimates
InactiveAlDays 0 - 9999 Day 1 2000 Alarm level for inactive days counter

Table 339: SSCBR Non group settings (advanced)


Name Values (Range) Unit Step Default Description
OpenTimeCorr -0.100 - 0.100 s 0.001 0.010 Correction for open travel time
CloseTimeCorr -0.100 - 0.100 s 0.001 0.010 Correction for close travel time
DirCoef -3.00 - -0.50 - 0.01 -1.50 Directional coefficient for CB life
calculation
CBLifeAlmLevel 1 - 99999 - 1 5000 Alarm level for CB remaining life
ContTrCorr -0.010 - 0.010 s 0.001 0.005 Correction for time difference in
auxiliary and main contacts open time
OperTimeDelay 0.000 - 0.200 s 0.001 0.020 Time delay between change of status
of trip output and start of main
contact separation
tDGasPresAlm 0.00 - 60.00 s 0.01 0.10 Time delay for gas pressure alarm
tDGasPresLO 0.00 - 60.00 s 0.01 0.10 Time delay for gas pressure lockout
InitCounterVal 0 - 9999 - 1 0 Initial value for number of operations
InitAccCurrPwr 0.00 - 9999.99 - 0.01 0.00 Initial value for accum I^CurrExponent
integr over CB open travel time value
InitInactDays 0 - 9999 Day 1 0 Initial value for inactive days
InactiveAlHrs 0 - 23 Hour 1 0 Alarm time for inactive days counter in
hours

11.4.6 Monitored data


PID-3267-MONITOREDDATA v7

Table 340: SSCBR Monitored data


Name Type Values (Range) Unit Description
TTRVOP REAL - ms Travel time of the CB during opening
operation
TTRVCL REAL - ms Travel time of the CB during closing
operation
NOOPER INTEGER - - Number of CB operation cycle
CBLIFEPH INTEGER - - CB Remaining life of respective phase
INADAYS INTEGER - - The number of days CB has been
inactive
IPOWPH REAL - - Accumulated I^CurrExponent
integrated over CB open travel time
SPCHT REAL - s The charging time of the CB spring

Breaker protection REQ650 385


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

11.4.7 Operation principle GUID-3902D69C-1858-40DD-AD63-C33C381697BA v12

The breaker monitoring function includes metering and monitoring subfunctions. The
subfunctions can be enabled and disabled with the Operation setting. The corresponding
parameter values are On and Off.

The operation of the subfunctions is described by the module diagram as shown in figure 209.
All the modules in the diagram are explained in subsequent sections.

386 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

I3P-ILRMSPH
POSCLOSE TTRVOP
POSOPEN CB Contact Travel TTRVCL
BLOCK Time TRVTOPAL
BLKALM TRVTCLAL
RSTTRVT

OPENPOS

CB Status CLOSEPOS
INVDPOS

CBLIFEAL
Remaining Life of CB
CBLIFEPH
RSTCBWR

TRCMD

Accumulated IPOWALPH
energy
I3P-IL IPOWLOPH
TRIND
IPOWPH
RSTIPOW

CB Operation OPERALM
Cycles NOOPER

CB Operation MONALM
Monitoring INADAYS

SPCHALM
SPRCHRST CB Spring Charge SPCHT
SPRCHRD Monitoring
RSTSPCHT

CB Gas Pressure GPRESALM


PRESALM Indication GPRESLO
PRESLO
IEC12000624-3-en.vsd
IEC12000624 V3 EN-US

Figure 209: Functional module diagram of breaker monitoring

Breaker protection REQ650 387


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

11.4.7.1 Circuit breaker contact travel time GUID-3AF0EE8D-AA8E-4F83-9916-61B5D0D6B05B v13

The circuit breaker contact travel time sub function calculates the breaker contact travel time
for opening and closing operations. The operation of the breaker contact travel time
measurement is described in figure210.

POSCLOSE TTRVOP
Contact travel
POSOPEN time TTRVCL
calculation
RSTTRVT

TRVTOPAL
Alarm limit
BLOCK check TRVTCLAL
BLKALM
IEC12000615-2-en.vsd
IEC12000615 V2 EN-US

Figure 210: Functional module diagram for circuit breaker contact travel time

Contact travel time calculation


The contact travel time of the breaker is calculated from the time between the state of change
of auxiliary contacts. The opening travel time is measured between the opening of the
POSCLOSE and closing of the POSOPEN auxiliary contacts. Similarly, the closing travel time is
measured between the opening of the POSOPEN and closing of the POSCLOSE auxiliary
contacts. A compensation factor has been added to consider the time difference between
auxiliary contact operation and the actual physical opening of the breaker main contact.

Main Contact
1

0
POSCLOSE

POSOPEN
1

t1 tOpen t2 t3 tClose t4

tTravelOpen = tOpen + t1 + t2 tTravelClose = tClose + t3 + t4


IEC12000616_2_en.vsd

IEC12000616 V2 EN-US

Figure 211: Travel time calculation


There is a time difference t1 between the start of the main contact opening and the opening of
the POSCLOSE auxiliary contact. Similarly, there is a time difference t2 between the time when
the POSOPEN auxiliary contact opens and the main contact is completely open. Therefore, a
correction factor needs to be added to get the actual opening time. This factor is added with
the OpenTimeCorr (t1+t2) setting. The closing time is calculated by adding the value set with
the CloseTimeCorr (t3+t4) setting to the measured closing time.

The last measured opening travel time (TTRVOP) and the closing travel time (TTRVCL) are given
as service values.

The values can be reset using the Clear menu on the LHMI or by activation the input RSTCBWR.

388 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

Alarm limit check


When the measured opening travel time is longer than the value set in the tTrOpenAlm setting,
the TRVTOPAL output is activated. Similarly, when the measured closing travel time is longer
than the value set in the tTrCloseAlm setting, the TRVTCLAL output is activated.

It is also possible to block the TRVTCLAL and TRVTOPAL alarm signals by activating the BLKALM
input.

11.4.7.2 Circuit breaker status GUID-390A1250-B258-4023-9A7D-0D7E19E13A6C v12

The circuit breaker status subfunction monitors the position of the circuit breaker, that is,
whether the breaker is in the open, closed or error position. The operation is described in
figure 212.

Phase current
I3P-ILRMSPH
check

OPENPOS
Contact
POSCLOSE position CLOSEPOS
indicator
POSOPEN INVDPOS

IEC12000613-3-en.vsd
IEC12000613 V3 EN-US

Figure 212: Functional module diagram for monitoring circuit breaker status

Phase current check


The module compares the phase current I3P-ILRMSPH to the AccStopCurr setting. If the
current in the selected phase exceeds the set level, it is reported to the contact position
indicator module as closed circuit breaker.

Contact position indicator


The circuit breaker status is open when the auxiliary input contact POSCLOSE is low, the
POSOPEN input is high and the phase current is less than the setting AccStopCurr value. The
circuit breaker is closed when the POSOPEN input is low and the POSCLOSE input is high. The
breaker is in the error state if both auxiliary contacts have the same value or if the auxiliary
input contact POSCLOSE is low and the POSOPEN input is high but the current is above the
setting AccStopCurr.

The status of the breaker is indicated with the binary outputs OPENPOS, CLOSEPOS and
INVDPOS for open, closed and error position respectively.

11.4.7.3 Remaining life of circuit breaker GUID-C347406A-2B6F-42BD-B70B-51489AB51EAE v13

The Remaining life of circuit breaker subfunction is used to give an indication on the wear and
tear of the circuit breaker. Every time the breaker operates, the life of the circuit breaker
reduces due to wear. The breaker wear depends on the interrupted current. The remaining life
of the breaker is estimated from the circuit breaker trip curve provided by the manufacturer.
The remaining life is decreased by at least one when the circuit breaker is opened. The
operation of the remaining life of circuit breaker subfunction is described in figure 213.

Breaker protection REQ650 389


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

I3P-ILRMSPH
CB remaining CBLIFEPH
POSCLOSE life estimation

RSTCBWR

Alarm limit
BLOCK CBLIFEAL
Check
BLKALM

IEC12000620-3-en.vsd
IEC12000620 V3 EN-US

Figure 213: Functional module diagram for estimating the life of the circuit breaker

Circuit breaker remaining life estimation


If the interrupted current is less than the rated operating current set using the RatedOperCurr
setting, the remaining operations of the breaker are reduced by one operation. If the
interrupted current is more than the rated fault current set using the RatedFltCurr setting, the
remaining operations of the circuit breaker are reduced by the set OperNoRated divided by the
set OperNoFault value. If the tripping current is between these two values, the remaining life
of the circuit breaker is calculated based on the maintenance curve equation given by the
manufacturer. The OperNoRated parameter sets the number of operations the breaker can
perform at the rated current. The OperNoFault parameter sets the number of operations the
breaker can perform at the rated fault current.

Alarm limit check


When the remaining life of a circuit breaker phase drops below the CBLifeAlmLevel setting, the
life alarm CBLIFEAL is activated.

It is possible to deactivate the CBLIFEAL alarm signal by activating the binary input BLKALM.

The old circuit breaker operation counter value can be used by adding the value to the
InitCBRemLife parameter. The value can be reset using the Clear menu from LHMI or by
activating the input RSTCBWR.

11.4.7.4 Accumulated energy GUID-0163FF0F-6E18-4CDC-87AA-578304E0872E v12

The Accumulated energy subfunction calculates the accumulated energy (Iyt) based on current
samples, where the setting CurrExponent (y) ranges from 0.5 to 3.0. The operation is
described in figure 214.

The TRCMD output is enabled when either of the trip indications from the trip coil circuit TRIND
is high or the breaker status is OPENPOS.

I3P-IL
TRCMD
I3P-ILRMSPH Accumulated
POSCLOSE energy
calculation IPOWPH
TRIND

LRSTIPOW

IPOWALPH
Alarm limit
BLOCK Check IPOWLOPH
BLKALM

IEC12000619-3-en.vsd
IEC12000619 V3 EN-US

Figure 214: Functional module diagram for estimating accumulated energy

390 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

Accumulated energy calculation


Accumulated energy can be calculated either with TRIND or POSCLOSE by selecting the
AccSelCal parameter value accordingly.

The calculation is initiated with the POSCLOSE or TRIND input events. It ends when the RMS
current is lower than the AccStopCurr setting.

The ContTrCorr setting is used to determine the accumulated energy in relation to the time
the main contact opens. If the setting is positive, the calculation of energy starts after the
auxiliary contact has opened and the delay equal to the value of the ContTrCorr setting has
passed. When the setting is negative, the calculation starts in advance by the correction time
in relation to when the auxiliary contact opened.

Main Contact Main Contact


close close

open open
POSCLOSE 1 POSCLOSE 1

0 0

Energy Energy
Accumulation Accumulation
starts starts

ContTrCorr ContTrCorr
(Negative) (Positive)
IEC12000618_1_en.vsd
IEC12000618 V1 EN-US

Figure 215: Significance of correction factor setting


Accumulated energy can also be calculated by using the change of state of the trip output.
TRIND is used to get the instance of the trip output and the time delay between the trip
initiation and the opening of the main contact is introduced by the setting OperTimeDelay.

The accumulated energy output IPOWPH is provided as a service value. The value can be reset
by enabling RSTIPOW through LHMI or by activating the input RSTIPOW.

Alarm limit check


The IPOWALPH alarm is activated when the accumulated energy exceeds the set value
AlmAccCurrPwr.

IPOWLOPH is activated when the accumulated energy exceeds the limit of the LOAccCurrPwr
setting.

The IPOWALPH and IPOWLOPH outputs can be blocked by activating the binary input BLKALM.

11.4.7.5 Circuit breaker operation cycles GUID-D3481D26-2E42-455E-8DB2-91538421F3B1 v10

The circuit breaker operation cycles subfunction counts the number of closing-opening
sequences of the breaker. The operation counter value is updated after each closing-opening
sequence. The operation is described in figure216.

Breaker protection REQ650 391


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

POSCLOSE
Operation
POSOPEN NOOPER
counter
RSTCBWR

OPERALM
Alarm limit
BLOCK
Check
OPERLO
BLKALM
IEC12000617 V2 EN-US

Figure 216: Functional module diagram for circuit breaker operation cycles

Operation counter
The operation counter counts the number of operations based on the state of change of the
auxiliary contact inputs POSCLOSE and POSOPEN.

The number of operations NOOPER is given as a service value. The old circuit breaker
operation counter value can be used by adding the value to the InitCounterVal parameter and
can be reset by Clear CB wear in the Clear menu on the LHMI or activating the input RSTCBWR.

Alarm limit check


OPERALM is generated when the number of operations exceeds the set value of the
OperAlmLevel threshold setting.

If the number of operations increases and exceeds the limit value set with the OperLOLevel
setting, the OPERLO output is activated.

The binary outputs OPERALM and OPERALO are deactivated when the BLKALM input is activated.

11.4.7.6 Circuit breaker operation monitoring GUID-6DAE4C6B-BD66-49CD-817D-08E4EBF47DE0 v9

The circuit breaker operation monitoring subfunction indicates the inactive days of the circuit
breaker and gives an alarm when the number of days exceed the set level. The operation of the
circuit breaker operation monitoring is shown in figure 217.

POSCLOSE
Inactive timer INADAYS
POSOPEN

Alarm limit MONALM


BLOCK
Check
BLKALM
IEC12000614 V2 EN-US

Figure 217: Functional module diagram for circuit breaker operation monitoring

Inactive timer
The Inactive timer module calculates the number of days the circuit breaker has remained in
the same open or closed state. The value is calculated by monitoring the states of the POSOPEN
and POSCLOSE auxiliary contacts.

The number of inactive days INADAYS is available as a service value. The initial number of
inactive days is set using the InitInactDays parameter.

392 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

Alarm limit check


MONALM is initiated when the number of inactive days and hours exceed the limit value defined
by the InactiveAlDays and InactivAlHrs setting. The alarm signal MONALM can be blocked by
activating the binary input BLKALM.

11.4.7.7 Circuit breaker spring charge monitoring GUID-F850A940-7890-4C37-8B31-6C7D5B30E582 v12

The circuit breaker spring charge monitoring subfunction calculates the spring charging time.
The operation is described in figure 218.

SPRCHRST
Spring charging
SPRCHRD time SPCHT
measurement
RSTSPCHT

Alarm limit
BLOCK SPCHALM
Check
BLKALM
IEC12000621 V2 EN-US

Figure 218: Functional module diagram for circuit breaker spring charge indication

Spring charging time measurement


Spring charging time calculation will be initiated as soon as the circuit breaker is closed and
charging motor starts (NO contact of the device is connected to SPRCHRST) to store the energy
in the close spring. An indicator provided in the circuit breaker is displayed when the spring is
completely charged. This status is taken through NO contact and then connected to SPRCHRD.

The binary input SPRCHRST indicates the start of circuit breaker spring charging time.
SPRCHRD indicates that the circuit breaker spring is charged. The spring charging time is
calculated from the difference of these two signal timings. Spring charging indication is
described in figure 218.

The last measured spring charging time SPCHT is provided as a service value. The spring
charging time SPCHT can be reset on the LHMI or by activating the input RSTSPCHT.

Alarm limit check


If the time taken by the spring to charge is more than the value set with the SpChAlmTime
setting, the subfunction generates the SPCHALM alarm.

It is possible to block the SPCHALM alarm signal by activating the BLKALM binary input.

11.4.7.8 Circuit breaker gas pressure indication GUID-9D070D52-B499-4D45-9195-60181819184E v10

The circuit breaker gas pressure indication subfunction monitors the gas pressure inside the
arc chamber. The operation is described in figure 219.

Breaker protection REQ650 393


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

PRESALM
tDGasPresAlm
BLOCK AND t GPRESALM

BLKALM

tDGasPresLO
PRESLO AND t GPRESLO
IEC12000622 V3 EN-US

Figure 219: Functional module diagram for circuit breaker gas pressure indication
When the PRESALM binary input is activated, the GPRESALM output is activated after a time
delay set with the tDGasPresAlm setting. The GPRESALM alarm can be blocked by activating the
BLKALM input.

If the pressure drops further to a very low level, the PRESLO binary input goes high, activating
the lockout alarm GPRESLO after a time delay set with the tDGasPresLO setting. The GPRESLO
alarm can be blocked by activating the BLKALM input.

The binary input BLOCK can be used to block the function. The activation of the BLOCK input
deactivates all outputs and resets internal timers. The alarm signals from the function can be
blocked by activating the binary input BLKALM.

11.4.8 Technical data


GUID-B6799420-D726-460E-B02F-C7D4F1937432 v9

Table 341: SSCBR Technical data


Function Range or value Accuracy
Alarm level for open and close (0 – 200) ms ±3 ms
travel time
Alarm level for number of (0 – 9999) -
operations
Independent time delay for spring (0.00 – 60.00) s ±0.2% or ±30 ms whichever is
charging time alarm greater
Independent time delay for gas (0.00 – 60.00) s ±0.2% or ±30 ms whichever is
pressure alarm greater
Independent time delay for gas (0.00 – 60.00) s ±0.2% or ±30 ms whichever is
pressure lockout greater
CB Contact Travel Time, opening ±3 ms
and closing
Remaining Life of CB ±2 operations
Accumulated Energy ±1.0% or ±0.5 whichever is greater

11.5 Event function EVENT SEMOD120002-1 v2

11.5.1 Identification
SEMOD167950-2 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Event function EVENT -
S00946 V1 EN-US

394 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

11.5.2 Functionality M12805-6 v11

When using a Substation Automation system with LON or SPA communication, time-tagged
events can be sent at change or cyclically from the IED to the station level. These events are
created from any available signal in the IED that is connected to the Event function (EVENT).
The EVENT function block is used for LON and SPA communication.

Analog, integer and double indication values are also transferred through the EVENT function.

11.5.3 Function block SEMOD116030-4 v2

EVENT
BLOCK
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
^INPUT10
^INPUT11
^INPUT12
^INPUT13
^INPUT14
^INPUT15
^INPUT16

IEC05000697-2-en.vsd
IEC05000697 V2 EN-US

Figure 220: EVENT function block

11.5.4 Signals IP11335-1 v2

PID-4145-INPUTSIGNALS v6

Table 342: EVENT Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
INPUT1 GROUP 0 Input 1
SIGNAL
INPUT2 GROUP 0 Input 2
SIGNAL
INPUT3 GROUP 0 Input 3
SIGNAL
INPUT4 GROUP 0 Input 4
SIGNAL
INPUT5 GROUP 0 Input 5
SIGNAL
INPUT6 GROUP 0 Input 6
SIGNAL
INPUT7 GROUP 0 Input 7
SIGNAL
INPUT8 GROUP 0 Input 8
SIGNAL
INPUT9 GROUP 0 Input 9
SIGNAL
Table continues on next page

Breaker protection REQ650 395


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

Name Type Default Description


INPUT10 GROUP 0 Input 10
SIGNAL
INPUT11 GROUP 0 Input 11
SIGNAL
INPUT12 GROUP 0 Input 12
SIGNAL
INPUT13 GROUP 0 Input 13
SIGNAL
INPUT14 GROUP 0 Input 14
SIGNAL
INPUT15 GROUP 0 Input 15
SIGNAL
INPUT16 GROUP 0 Input 16
SIGNAL

11.5.5 Settings IP11336-1 v2

PID-4145-SETTINGS v6

Table 343: EVENT Non group settings (basic)


Name Values (Range) Unit Step Default Description
SPAChannelMask Off - - Off SPA channel mask
Channel 1-8
Channel 9-16
Channel 1-16
LONChannelMask Off - - Off LON channel mask
Channel 1-8
Channel 9-16
Channel 1-16
EventMask1 NoEvents - - AutoDetect Reporting criteria for input 1
OnSet
OnReset
OnChange
AutoDetect
EventMask2 NoEvents - - AutoDetect Reporting criteria for input 2
OnSet
OnReset
OnChange
AutoDetect
EventMask3 NoEvents - - AutoDetect Reporting criteria for input 3
OnSet
OnReset
OnChange
AutoDetect
EventMask4 NoEvents - - AutoDetect Reporting criteria for input 4
OnSet
OnReset
OnChange
AutoDetect
EventMask5 NoEvents - - AutoDetect Reporting criteria for input 5
OnSet
OnReset
OnChange
AutoDetect
Table continues on next page

396 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

Name Values (Range) Unit Step Default Description


EventMask6 NoEvents - - AutoDetect Reporting criteria for input 6
OnSet
OnReset
OnChange
AutoDetect
EventMask7 NoEvents - - AutoDetect Reporting criteria for input 7
OnSet
OnReset
OnChange
AutoDetect
EventMask8 NoEvents - - AutoDetect Reporting criteria for input 8
OnSet
OnReset
OnChange
AutoDetect
EventMask9 NoEvents - - AutoDetect Reporting criteria for input 9
OnSet
OnReset
OnChange
AutoDetect
EventMask10 NoEvents - - AutoDetect Reporting criteria for input 10
OnSet
OnReset
OnChange
AutoDetect
EventMask11 NoEvents - - AutoDetect Reporting criteria for input 11
OnSet
OnReset
OnChange
AutoDetect
EventMask12 NoEvents - - AutoDetect Reporting criteria for input 12
OnSet
OnReset
OnChange
AutoDetect
EventMask13 NoEvents - - AutoDetect Reporting criteria for input 13
OnSet
OnReset
OnChange
AutoDetect
EventMask14 NoEvents - - AutoDetect Reporting criteria for input 14
OnSet
OnReset
OnChange
AutoDetect
EventMask15 NoEvents - - AutoDetect Reporting criteria for input 15
OnSet
OnReset
OnChange
AutoDetect
EventMask16 NoEvents - - AutoDetect Reporting criteria for input 16
OnSet
OnReset
OnChange
AutoDetect
MinRepIntVal1 0 - 3600 s 1 2 Minimum reporting interval input 1
MinRepIntVal2 0 - 3600 s 1 2 Minimum reporting interval input 2
MinRepIntVal3 0 - 3600 s 1 2 Minimum reporting interval input 3
MinRepIntVal4 0 - 3600 s 1 2 Minimum reporting interval input 4
Table continues on next page

Breaker protection REQ650 397


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

Name Values (Range) Unit Step Default Description


MinRepIntVal5 0 - 3600 s 1 2 Minimum reporting interval input 5
MinRepIntVal6 0 - 3600 s 1 2 Minimum reporting interval input 6
MinRepIntVal7 0 - 3600 s 1 2 Minimum reporting interval input 7
MinRepIntVal8 0 - 3600 s 1 2 Minimum reporting interval input 8
MinRepIntVal9 0 - 3600 s 1 2 Minimum reporting interval input 9
MinRepIntVal10 0 - 3600 s 1 2 Minimum reporting interval input 10
MinRepIntVal11 0 - 3600 s 1 2 Minimum reporting interval input 11
MinRepIntVal12 0 - 3600 s 1 2 Minimum reporting interval input 12
MinRepIntVal13 0 - 3600 s 1 2 Minimum reporting interval input 13
MinRepIntVal14 0 - 3600 s 1 2 Minimum reporting interval input 14
MinRepIntVal15 0 - 3600 s 1 2 Minimum reporting interval input 15
MinRepIntVal16 0 - 3600 s 1 2 Minimum reporting interval input 16

11.5.6 Operation principle M12807-6 v6

The main purpose of the Event function (EVENT) is to generate events when the state or value
of any of the connected input signals is in a state, or is undergoing a state transition, for which
event generation is enabled.

Each EVENT function has 16 inputs INPUT1 - INPUT16. Each input can be given a name from the
Application Configuration tool. The inputs are normally used to create single events, but are
also intended for double indication events. For double indications, only the first eight inputs,
1–8, must be used. Inputs 9–16 can be used for other types of events in the same EVENT block.

The EVENT function also has an input BLOCK to block the generation of events.

Events that are sent from the IED can originate from both internal logical signals and binary
input channels. The internal signals are time-tagged in the main processing module, while the
binary input channels are time-tagged directly on the input module. Time-tagging of the
events that are originated from internal logical signals have a resolution corresponding to the
execution cycle-time of the source application. Time-tagging of the events that are originated
from binary input signals have a resolution of 1 ms.

The outputs from the EVENT function are formed by the reading of status, events and alarms
by the station level on every single input. The user-defined name for each input is intended to
be used by the station level.

All events according to the event mask are stored in a buffer, which contains up to 1000
events. If new events appear before the oldest event in the buffer is read, the oldest event is
overwritten and an overflow alarm appears.

Events are produced according to set event masks. The event masks are treated commonly for
both the LON and SPA communication. An EventMask can be set individually for each input
channel. These settings are available:

• NoEvents
• OnSet
• OnReset
• OnChange
• AutoDetect

398 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

It is possible to define which part of the EVENT function generates the events. This can be
performed individually for communication types SPAChannelMask and LONChannelMask. For
each communication type these settings are available:

• Off
• Channel 1-8
• Channel 9-16
• Channel 1-16

For LON communication, events are normally sent to station level at change. It is also possible
to set a time for cyclic sending of the events individually for each input channel.

To protect the SA system from signals with a high change rate that can easily saturate the
EVENT function or the communication subsystems behind it, a quota limiter is implemented. If
an input creates events at a rate that completely consume the granted quota then further
events from the channel will be blocked. This block will be removed when the input calms down
and the accumulated quota reach 66% of the maximum burst quota. The maximum burst
quota per input channel is 45 events per second.

11.6 Disturbance report DRPRDRE IP14584-1 v2

11.6.1 Identification
M16055-1 v9

Function description IEC 61850 identification IEC 60617 ANSI/IEEE C37.2


identification device number
Disturbance report DRPRDRE - -
Disturbance report A1RADR - A4RADR - -
Disturbance report B1RBDR - B22RBDR - -

11.6.2 Functionality M12153-3 v14

Complete and reliable information about disturbances in the primary and/or in the secondary
system together with continuous event-logging is accomplished by the disturbance report
functionality.

Disturbance report (DRPRDRE), always included in the IED, acquires sampled data of all
selected analog input and binary signals connected to the function block with a maximum of
40 analog and 352 binary signals.

The Disturbance report functionality is a common name for several functions:

• Event list
• Indications
• Event recorder
• Trip value recorder
• Disturbance recorder
• Settings information

The Disturbance report function is characterized by great flexibility regarding configuration,


starting conditions, recording times, and large storage capacity.

Breaker protection REQ650 399


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

A disturbance is defined as an activation of an input to the AnRADR or BnRBDR function blocks,


which are set to trigger the disturbance recorder. All connected signals from start of pre-fault
time to the end of post-fault time will be included in the recording. Disturbance record will
have visible settings from all function instances that are configured in the application
configuration tool.

Every disturbance report recording is saved in the IED in the standard Comtrade format as a
reader file HDR, a configuration file CFG, and a data file DAT. The same applies to all events,
which are continuously saved in a ring-buffer. The local HMI is used to get information about
the recordings. The disturbance report files can be uploaded to PCM600 for further analysis
using the disturbance handling tool.

11.6.3 Function block IP806-1 v1

M12510-3 v3

DRPRDRE
DRPOFF
RECSTART
RECMADE
CLEARED
MEMUSED

IEC05000406-3-en.vsd
IEC05000406 V3 EN-US

Figure 221: DRPRDRE function block


SEMOD54843-4 v3

A4RADR
^INPUT31
^INPUT32
^INPUT33
^INPUT34
^INPUT35
^INPUT36
^INPUT37
^INPUT38
^INPUT39
^INPUT40

IEC05000431-3-en.vsd
IEC05000431 V3 EN-US

Figure 222: A4RADR function block, derived analog inputs


SEMOD54845-4 v6

B1RBDR
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
^INPUT10
^INPUT11
^INPUT12
^INPUT13
^INPUT14
^INPUT15
^INPUT16

IEC05000432-3-en.vsd
IEC05000432 V3 EN-US

Figure 223: B1RBDR function block, binary inputs, example for B1RBDR - B22RBDR

400 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

11.6.4 Signals
PID-3949-OUTPUTSIGNALS v2

Table 344: DRPRDRE Output signals


Name Type Description
DRPOFF BOOLEAN Disturbance report function turned off
RECSTART BOOLEAN Disturbance recording started
RECMADE BOOLEAN Disturbance recording made
CLEARED BOOLEAN All disturbances in the disturbance report cleared
MEMUSED BOOLEAN More than 80% of memory used

GUID-D025D5D9-A0F3-4A00-891A-63AD5F609A77
PID-4017-INPUTSIGNALS v6
v3

Table 345: A4RADR Input signals


Name Type Default Description
INPUT31 REAL 0 Analog channel 31
INPUT32 REAL 0 Analog channel 32
INPUT33 REAL 0 Analog channel 33
INPUT34 REAL 0 Analog channel 34
INPUT35 REAL 0 Analog channel 35
INPUT36 REAL 0 Analog channel 36
INPUT37 REAL 0 Analog channel 37
INPUT38 REAL 0 Analog channel 38
INPUT39 REAL 0 Analog channel 39
INPUT40 REAL 0 Analog channel 40

PID-3798-INPUTSIGNALS v6

Table 346: B1RBDR Input signals


Name Type Default Description
INPUT1 BOOLEAN 0 Binary channel 1
INPUT2 BOOLEAN 0 Binary channel 2
INPUT3 BOOLEAN 0 Binary channel 3
INPUT4 BOOLEAN 0 Binary channel 4
INPUT5 BOOLEAN 0 Binary channel 5
INPUT6 BOOLEAN 0 Binary channel 6
INPUT7 BOOLEAN 0 Binary channel 7
INPUT8 BOOLEAN 0 Binary channel 8
INPUT9 BOOLEAN 0 Binary channel 9
INPUT10 BOOLEAN 0 Binary channel 10
INPUT11 BOOLEAN 0 Binary channel 11
INPUT12 BOOLEAN 0 Binary channel 12
INPUT13 BOOLEAN 0 Binary channel 13
INPUT14 BOOLEAN 0 Binary channel 14
INPUT15 BOOLEAN 0 Binary channel 15
INPUT16 BOOLEAN 0 Binary channel 16

Breaker protection REQ650 401


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

GUID-D3A8067F-80F8-4174-BD2D-4C43F4B99020 v3
B2RBDR to B22RBDR functions have the same input signal specifications as B1RBDR but with
different numbering:

• B2RBDR: INPUT17 to INPUT32 (binary channels 17 to 32)


• B3RBDR: INPUT33 to INPUT48 (binary channels 33 to 48)
• B4RBDR: INPUT49 to INPUT64 (binary channels 49 to 64)
• B5RBDR: INPUT65 to INPUT80 (binary channels 65 to 80)
• B6RBDR: INPUT81 to INPUT96 (binary channels 81 to 96)
• B7RBDR: INPUT97 to INPUT112 (binary channels 97 to 112)
• B8RBDR: INPUT113 to INPUT128 (binary channels 113 to 128)
• B9RBDR: INPUT129 to INPUT144 (binary channels 129 to 144)
• B10RBDR: INPUT145 to INPUT160 (binary channels 145 to 160)
• B11RBDR: INPUT161 to INPUT176 (binary channels 161 to 176)
• B12RBDR: INPUT177 to INPUT192 (binary channels 177 to 192)
• B13RBDR: INPUT193 to INPUT208 (binary channels 193 to 208)
• B14RBDR: INPUT209 to INPUT224 (binary channels 209 to 224)
• B15RBDR: INPUT225 to INPUT240 (binary channels 225 to 240)
• B16RBDR: INPUT241 to INPUT256 (binary channels 241 to 256)
• B17RBDR: INPUT257 to INPUT272 (binary channels 257 to 272)
• B18RBDR: INPUT273 to INPUT288 (binary channels 273 to 288)
• B19RBDR: INPUT289 to INPUT304 (binary channels 289 to 304)
• B20RBDR: INPUT305 to INPUT320 (binary channels 305 to 320)
• B21RBDR: INPUT321 to INPUT336 (binary channels 321 to 336)
• B22RBDR: INPUT337 to INPUT352 (binary channels 337 to 352)

11.6.5 Settings
PID-7068-SETTINGS v1

Table 347: DRPRDRE Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
PreFaultRecT 0.05 - 9.90 s 0.01 0.10 Pre-fault recording time
PostFaultRecT 0.1 - 10.0 s 0.1 0.5 Post-fault recording time
TimeLimit 0.5 - 10.0 s 0.1 1.0 Fault recording time limit
PostRetrig Off - - Off Post-fault retrig enabled (On) or not
On (Off)
MaxNoStoreRec 10 - 100 - 1 100 Maximum number of stored
disturbances
ZeroAngleRef 1 - 30 Ch 1 1 Trip value recorder, phasor reference
channel
OpModeTest Off - - Off Operation mode during test mode
On
SetInfoInDRep Disable - - Enable Enable Disturbance report settings
Enable functionality

GUID-E05EEC82-CB90-4E73-B9C9-4C16FD95FCBF v1
A2RADR to A4RADR functions have the same Non group settings (basic) as A1RADR but with
different numbering:

• A2RADR: Operation11 to Operation20


• A3RADR: Operation21 to Operation30
• A4RADR: Operation31 to Operation40

402 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

A2RADR to A4RADR functions have the same Non group settings (advanced) as A1RADR but
with different numbering (examples given in brackets):

• A2RADR: 11 to 20 (NomValue11, nominal value for analog channel 11)


• A3RADR: 21 to 30 (NomValue21, nominal value for analog channel 21)
• A4RADR: 31 to 40 (NomValue31, nominal value for analog channel 31)

PID-3798-SETTINGS v6

Table 348: B1RBDR Non group settings (basic)


Name Values (Range) Unit Step Default Description
TrigDR01 Off - - Off Trigger operation On/Off
On
SetLED01 Off - - Off Set LED on HMI for binary channel 1
Start
Trip
Start and Trip
TrigDR02 Off - - Off Trigger operation On/Off
On
SetLED02 Off - - Off Set LED on HMI for binary channel 2
Start
Trip
Start and Trip
TrigDR03 Off - - Off Trigger operation On/Off
On
SetLED03 Off - - Off Set LED on HMI for binary channel 3
Start
Trip
Start and Trip
TrigDR04 Off - - Off Trigger operation On/Off
On
SetLED04 Off - - Off Set LED on HMI for binary channel 4
Start
Trip
Start and Trip
TrigDR05 Off - - Off Trigger operation On/Off
On
SetLED05 Off - - Off Set LED on HMI for binary channel 5
Start
Trip
Start and Trip
TrigDR06 Off - - Off Trigger operation On/Off
On
SetLED06 Off - - Off Set LED on HMI for binary channel 6
Start
Trip
Start and Trip
TrigDR07 Off - - Off Trigger operation On/Off
On
SetLED07 Off - - Off Set LED on HMI for binary channel 7
Start
Trip
Start and Trip
TrigDR08 Off - - Off Trigger operation On/Off
On
SetLED08 Off - - Off Set LED on HMI for binary channel 8
Start
Trip
Start and Trip
Table continues on next page

Breaker protection REQ650 403


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

Name Values (Range) Unit Step Default Description


TrigDR09 Off - - Off Trigger operation On/Off
On
SetLED09 Off - - Off Set LED on HMI for binary channel 9
Start
Trip
Start and Trip
TrigDR10 Off - - Off Trigger operation On/Off
On
SetLED10 Off - - Off Set LED on HMI for binary channel 10
Start
Trip
Start and Trip
TrigDR11 Off - - Off Trigger operation On/Off
On
SetLED11 Off - - Off Set LED on HMI for binary channel 11
Start
Trip
Start and Trip
TrigDR12 Off - - Off Trigger operation On/Off
On
SetLED12 Off - - Off Set LED on HMI for binary channel 12
Start
Trip
Start and Trip
TrigDR13 Off - - Off Trigger operation On/Off
On
SetLED13 Off - - Off Set LED on HMI for binary channel 13
Start
Trip
Start and Trip
TrigDR14 Off - - Off Trigger operation On/Off
On
SetLED14 Off - - Off Set LED on HMI for binary channel 14
Start
Trip
Start and Trip
TrigDR15 Off - - Off Trigger operation On/Off
On
SetLED15 Off - - Off Set LED on HMI for binary channel 15
Start
Trip
Start and Trip
TrigDR16 Off - - Off Trigger operation On/Off
On
SetLED16 Off - - Off Set LED on HMI for binary channel 16
Start
Trip
Start and Trip
FunType1 0 - 255 - 1 0 Function type for binary channel 1 (IEC
-60870-5-103)
InfNo1 0 - 255 - 1 0 Information number for binary
channel 1 (IEC -60870-5-103)
FunType2 0 - 255 - 1 0 Function type for binary channel 2 (IEC
-60870-5-103)
InfNo2 0 - 255 - 1 0 Information number for binary
channel 2 (IEC -60870-5-103)
Table continues on next page

404 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

Name Values (Range) Unit Step Default Description


FunType3 0 - 255 - 1 0 Function type for binary channel 3 (IEC
-60870-5-103)
InfNo3 0 - 255 - 1 0 Information number for binary
channel 3 (IEC -60870-5-103)
FunType4 0 - 255 - 1 0 Function type for binary channel 4
(IEC -60870-5-103)
InfNo4 0 - 255 - 1 0 Information number for binary
channel 4 (IEC -60870-5-103)
FunType5 0 - 255 - 1 0 Function type for binary channel 5 (IEC
-60870-5-103)
InfNo5 0 - 255 - 1 0 Information number for binary
channel 5 (IEC -60870-5-103)
FunType6 0 - 255 - 1 0 Function type for binary channel 6
(IEC -60870-5-103)
InfNo6 0 - 255 - 1 0 Information number for binary
channel 6 (IEC -60870-5-103)
FunType7 0 - 255 - 1 0 Function type for binary channel 7 (IEC
-60870-5-103)
InfNo7 0 - 255 - 1 0 Information number for binary
channel 7 (IEC -60870-5-103)
FunType8 0 - 255 - 1 0 Function type for binary channel 8
(IEC -60870-5-103)
InfNo8 0 - 255 - 1 0 Information number for binary
channel 8 (IEC -60870-5-103)
FunType9 0 - 255 - 1 0 Function type for binary channel 9
(IEC -60870-5-103)
InfNo9 0 - 255 - 1 0 Information number for binary
channel 9 (IEC -60870-5-103)
FunType10 0 - 255 - 1 0 Function type for binary channel 10
(IEC -60870-5-103)
InfNo10 0 - 255 - 1 0 Information number for binary
channel 10 (IEC -60870-5-103)
FunType11 0 - 255 - 1 0 Function type for binary channel 11
(IEC -60870-5-103)
InfNo11 0 - 255 - 1 0 Information number for binary
channel 11 (IEC -60870-5-103)
FunType12 0 - 255 - 1 0 Function type for binary channel 12
(IEC -60870-5-103)
InfNo12 0 - 255 - 1 0 Information number for binary
channel 12 (IEC -60870-5-103)
FunType13 0 - 255 - 1 0 Function type for binary channel 13
(IEC -60870-5-103)
InfNo13 0 - 255 - 1 0 Information number for binary
channel 13 (IEC -60870-5-103)
FunType14 0 - 255 - 1 0 Function type for binary channel 14
(IEC -60870-5-103)
InfNo14 0 - 255 - 1 0 Information number for binary
channel 14 (IEC -60870-5-103)
FunType15 0 - 255 - 1 0 Function type for binary channel 15
(IEC -60870-5-103)
Table continues on next page

Breaker protection REQ650 405


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

Name Values (Range) Unit Step Default Description


InfNo15 0 - 255 - 1 0 Information number for binary
channel 15 (IEC -60870-5-103)
FunType16 0 - 255 - 1 0 Function type for binary channel 16
(IEC -60870-5-103)
InfNo16 0 - 255 - 1 0 Information number for binary
channel 16 (IEC -60870-5-103)

Table 349: B1RBDR Non group settings (advanced)


Name Values (Range) Unit Step Default Description
TrigLevel01 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 1
IndicationMa01 Hide - - Show Indication mask for binary channel 1
Show
TrigLevel02 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 2
IndicationMa02 Hide - - Show Indication mask for binary channel 2
Show
TrigLevel03 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 3
IndicationMa03 Hide - - Show Indication mask for binary channel 3
Show
TrigLevel04 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 4
IndicationMa04 Hide - - Show Indication mask for binary channel 4
Show
TrigLevel05 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 5
IndicationMa05 Hide - - Show Indication mask for binary channel 5
Show
TrigLevel06 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 6
IndicationMa06 Hide - - Show Indication mask for binary channel 6
Show
TrigLevel07 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 7
IndicationMa07 Hide - - Show Indication mask for binary channel 7
Show
TrigLevel08 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 8
IndicationMa08 Hide - - Show Indication mask for binary channel 8
Show
TrigLevel09 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 9
IndicationMa09 Hide - - Show Indication mask for binary channel 9
Show
TrigLevel10 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 10
IndicationMa10 Hide - - Show Indication mask for binary channel 10
Show
TrigLevel11 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 11
Table continues on next page

406 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

Name Values (Range) Unit Step Default Description


IndicationMa11 Hide - - Show Indication mask for binary channel 11
Show
TrigLevel12 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 12
IndicationMa12 Hide - - Show Indication mask for binary channel 12
Show
TrigLevel13 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 13
IndicationMa13 Hide - - Show Indication mask for binary channel 13
Show
TrigLevel14 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 14
IndicationMa14 Hide - - Show Indication mask for binary channel 14
Show
TrigLevel15 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 15
IndicationMa15 Hide - - Show Indication mask for binary channel 15
Show
TrigLevel16 Trig on 0 - - Trig on 1 Trigger on positive (1) or negative (0)
Trig on 1 slope for binary input 16
IndicationMa16 Hide - - Show Indication mask for binary channel 16
Show

GUID-8702C5B9-05A3-4E61-8952-C66483FFDFE2 v4
B2RBDR to B22RBDR functions have the same Non group settings (basic) as B1RBDR but with
different numbering (examples given in brackets):

• B2RBDR: 17 to 32 (SetLED17, set LED on HMI for binary channel 17)


• B3RBDR: 33 to 48 (SetLED33, set LED on HMI for binary channel 33)
• B4RBDR: 49 to 64 (SetLED49, set LED on HMI for binary channel 49)
• B5RBDR: 65 to 80 (SetLED65, set LED on HMI for binary channel 65)
• B6RBDR: 81 to 96 (SetLED81, set LED on HMI for binary channel 81)
• B7RBDR: 97 to 112 (SetLED97, set LED on HMI for binary channel 97)
• B8RBDR: 113 to 128 (SetLED113, set LED on HMI for binary channel 113)
• B9RBDR: 129 to 144 (SetLED129, set LED on HMI for binary channel 129)
• B10RBDR: 145 to 160 (SetLED145, set LED on HMI for binary channel 145)
• B11RBDR: 161 to 176 (SetLED161, set LED on HMI for binary channel 161)
• B12RBDR: 177 to 192 (SetLED177, set LED on HMI for binary channel 177)
• B13RBDR: 193 to 208 (SetLED193, set LED on HMI for binary channel 193)
• B14RBDR: 209 to 224 (SetLED209, set LED on HMI for binary channel 209)
• B15RBDR: 225 to 240 (SetLED225, set LED on HMI for binary channel 225)
• B16RBDR: 241 to 256 (SetLED241, set LED on HMI for binary channel 241)
• B17RBDR: 257 to 272 (SetLED257, set LED on HMI for binary channel 257)
• B18RBDR: 273 to 288 (SetLED273, set LED on HMI for binary channel 273)
• B19RBDR: 289 to 304 (SetLED289, set LED on HMI for binary channel 289)
• B20RBDR: 305 to 320 (SetLED305, set LED on HMI for binary channel 305)
• B21RBDR: 321 to 336 (SetLED321, set LED on HMI for binary channel 321)
• B22RBDR: 337 to 352 (SetLED337, set LED on HMI for binary channel 337)

B2RBDR to B22RBDR functions have the same Non group settings (advanced) as B1RBDR but
with different numbering (examples given in brackets):

• B2RBDR: 17 to 32 (IndicationMa17, indication mask for binary channel 17)


• B3RBDR: 33 to 48 (IndicationMa33, indication mask for binary channel 33)
• B4RBDR: 49 to 64 (IndicationMa49, indication mask for binary channel 49)

Breaker protection REQ650 407


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

• B5RBDR: 65 to 80 (IndicationMa65, indication mask for binary channel 65)


• B6RBDR: 81 to 96 (IndicationMa81, indication mask for binary channel 81)
• B7RBDR: 97 to 112 (IndicationMa97, indication mask for binary channel 97)
• B8RBDR: 113 to 128 (IndicationMa113, indication mask for binary channel 113)
• B9RBDR: 129 to 144 (IndicationMa129, indication mask for binary channel 129)
• B10RBDR: 145 to 160 (IndicationMa145, indication mask for binary channel 145)
• B11RBDR: 161 to 176 (IndicationMa161, indication mask for binary channel 161)
• B12RBDR: 177 to 192 (IndicationMa177, indication mask for binary channel 177)
• B13RBDR: 193 to 208 (IndicationMa193, indication mask for binary channel 193)
• B14RBDR: 209 to 224 (IndicationMa209, indication mask for binary channel 209)
• B15RBDR: 225 to 240 (IndicationMa225, indication mask for binary channel 225)
• B16RBDR: 241 to 256 (IndicationMa241, indication mask for binary channel 241)
• B17RBDR: 257 to 272 (IndicationMa257, indication mask for binary channel 257)
• B18RBDR: 273 to 288 (IndicationMa273, indication mask for binary channel 273)
• B19RBDR: 289 to 304 (IndicationMa289, indication mask for binary channel 289)
• B20RBDR: 305 to 320 (IndicationMa305, indication mask for binary channel 305)
• B21RBDR: 321 to 336 (IndicationMa321, indication mask for binary channel 321)
• B22RBDR: 337 to 352 (IndicationMa337, indication mask for binary channel 337)

11.6.6 Monitored data


PID-3949-MONITOREDDATA v2

Table 350: DRPRDRE Monitored data


Name Type Values (Range) Unit Description
MemoryUsed INTEGER - % Memory usage (0-100%)
UnTrigStatCh1 BOOLEAN - - Under level trig for analog channel 1
activated
OvTrigStatCh1 BOOLEAN - - Over level trig for analog channel 1
activated
UnTrigStatCh2 BOOLEAN - - Under level trig for analog channel 2
activated
OvTrigStatCh2 BOOLEAN - - Over level trig for analog channel 2
activated
UnTrigStatCh3 BOOLEAN - - Under level trig for analog channel 3
activated
OvTrigStatCh3 BOOLEAN - - Over level trig for analog channel 3
activated
UnTrigStatCh4 BOOLEAN - - Under level trig for analog channel 4
activated
OvTrigStatCh4 BOOLEAN - - Over level trig for analog channel 4
activated
UnTrigStatCh5 BOOLEAN - - Under level trig for analog channel 5
activated
OvTrigStatCh5 BOOLEAN - - Over level trig for analog channel 5
activated
UnTrigStatCh6 BOOLEAN - - Under level trig for analog channel 6
activated
OvTrigStatCh6 BOOLEAN - - Over level trig for analog channel 6
activated
UnTrigStatCh7 BOOLEAN - - Under level trig for analog channel 7
activated
OvTrigStatCh7 BOOLEAN - - Over level trig for analog channel 7
activated
Table continues on next page

408 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

Name Type Values (Range) Unit Description


UnTrigStatCh8 BOOLEAN - - Under level trig for analog channel 8
activated
OvTrigStatCh8 BOOLEAN - - Over level trig for analog channel 8
activated
UnTrigStatCh9 BOOLEAN - - Under level trig for analog channel 9
activated
OvTrigStatCh9 BOOLEAN - - Over level trig for analog channel 9
activated
UnTrigStatCh10 BOOLEAN - - Under level trig for analog channel 10
activated
OvTrigStatCh10 BOOLEAN - - Over level trig for analog channel 10
activated
UnTrigStatCh11 BOOLEAN - - Under level trig for analog channel 11
activated
OvTrigStatCh11 BOOLEAN - - Over level trig for analog channel 11
activated
UnTrigStatCh12 BOOLEAN - - Under level trig for analog channel 12
activated
OvTrigStatCh12 BOOLEAN - - Over level trig for analog channel 12
activated
UnTrigStatCh13 BOOLEAN - - Under level trig for analog channel 13
activated
OvTrigStatCh13 BOOLEAN - - Over level trig for analog channel 13
activated
UnTrigStatCh14 BOOLEAN - - Under level trig for analog channel 14
activated
OvTrigStatCh14 BOOLEAN - - Over level trig for analog channel 14
activated
UnTrigStatCh15 BOOLEAN - - Under level trig for analog channel 15
activated
OvTrigStatCh15 BOOLEAN - - Over level trig for analog channel 15
activated
UnTrigStatCh16 BOOLEAN - - Under level trig for analog channel 16
activated
OvTrigStatCh16 BOOLEAN - - Over level trig for analog channel 16
activated
UnTrigStatCh17 BOOLEAN - - Under level trig for analog channel 17
activated
OvTrigStatCh17 BOOLEAN - - Over level trig for analog channel 17
activated
UnTrigStatCh18 BOOLEAN - - Under level trig for analog channel 18
activated
OvTrigStatCh18 BOOLEAN - - Over level trig for analog channel 18
activated
UnTrigStatCh19 BOOLEAN - - Under level trig for analog channel 19
activated
OvTrigStatCh19 BOOLEAN - - Over level trig for analog channel 19
activated
UnTrigStatCh20 BOOLEAN - - Under level trig for analog channel 20
activated
OvTrigStatCh20 BOOLEAN - - Over level trig for analog channel 20
activated
Table continues on next page

Breaker protection REQ650 409


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

Name Type Values (Range) Unit Description


UnTrigStatCh21 BOOLEAN - - Under level trig for analog channel 21
activated
OvTrigStatCh21 BOOLEAN - - Over level trig for analog channel 21
activated
UnTrigStatCh22 BOOLEAN - - Under level trig for analog channel 22
activated
OvTrigStatCh22 BOOLEAN - - Over level trig for analog channel 22
activated
UnTrigStatCh23 BOOLEAN - - Under level trig for analog channel 23
activated
OvTrigStatCh23 BOOLEAN - - Over level trig for analog channel 23
activated
UnTrigStatCh24 BOOLEAN - - Under level trig for analog channel 24
activated
OvTrigStatCh24 BOOLEAN - - Over level trig for analog channel 24
activated
UnTrigStatCh25 BOOLEAN - - Under level trig for analog channel 25
activated
OvTrigStatCh25 BOOLEAN - - Over level trig for analog channel 25
activated
UnTrigStatCh26 BOOLEAN - - Under level trig for analog channel 26
activated
OvTrigStatCh26 BOOLEAN - - Over level trig for analog channel 26
activated
UnTrigStatCh27 BOOLEAN - - Under level trig for analog channel 27
activated
OvTrigStatCh27 BOOLEAN - - Over level trig for analog channel 27
activated
UnTrigStatCh28 BOOLEAN - - Under level trig for analog channel 28
activated
OvTrigStatCh28 BOOLEAN - - Over level trig for analog channel 28
activated
UnTrigStatCh29 BOOLEAN - - Under level trig for analog channel 29
activated
OvTrigStatCh29 BOOLEAN - - Over level trig for analog channel 29
activated
UnTrigStatCh30 BOOLEAN - - Under level trig for analog channel 30
activated
OvTrigStatCh30 BOOLEAN - - Over level trig for analog channel 30
activated
UnTrigStatCh31 BOOLEAN - - Under level trig for analog channel 31
activated
OvTrigStatCh31 BOOLEAN - - Over level trig for analog channel 31
activated
UnTrigStatCh32 BOOLEAN - - Under level trig for analog channel 32
activated
OvTrigStatCh32 BOOLEAN - - Over level trig for analog channel 32
activated
UnTrigStatCh33 BOOLEAN - - Under level trig for analog channel 33
activated
OvTrigStatCh33 BOOLEAN - - Over level trig for analog channel 33
activated
Table continues on next page

410 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

Name Type Values (Range) Unit Description


UnTrigStatCh34 BOOLEAN - - Under level trig for analog channel 34
activated
OvTrigStatCh34 BOOLEAN - - Over level trig for analog channel 34
activated
UnTrigStatCh35 BOOLEAN - - Under level trig for analog channel 35
activated
OvTrigStatCh35 BOOLEAN - - Over level trig for analog channel 35
activated
UnTrigStatCh36 BOOLEAN - - Under level trig for analog channel 36
activated
OvTrigStatCh36 BOOLEAN - - Over level trig for analog channel 36
activated
UnTrigStatCh37 BOOLEAN - - Under level trig for analog channel 37
activated
OvTrigStatCh37 BOOLEAN - - Over level trig for analog channel 37
activated
UnTrigStatCh38 BOOLEAN - - Under level trig for analog channel 38
activated
OvTrigStatCh38 BOOLEAN - - Over level trig for analog channel 38
activated
UnTrigStatCh39 BOOLEAN - - Under level trig for analog channel 39
activated
OvTrigStatCh39 BOOLEAN - - Over level trig for analog channel 39
activated
UnTrigStatCh40 BOOLEAN - - Under level trig for analog channel 40
activated
OvTrigStatCh40 BOOLEAN - - Over level trig for analog channel 40
activated
FaultNumber INTEGER - - Disturbance fault number

11.6.7 Operation principle


M12155-6 v13
Disturbance report DRPRDRE is a common name for several functions to supply the operator,
analysis engineer, and so on, with sufficient information about events in the system.

The functions included in the disturbance report are:

• Event list (EL)


• Indications (IND)
• Event recorder (ER)
• Trip value recorder (TVR)
• Disturbance recorder (DR)
• Settings information

Figure 224 shows the relations between Disturbance Report, included functions and function
blocks. Event list (EL), Event recorder (ER) and Indications (IND) uses information from the
binary input function blocks (BxRBDR).Trip value recorder (TVR) uses analog information from
the analog input function blocks (AxRADR). Disturbance recorder DRPRDRE acquires
information from both AxRADR and BxRBDR.

Figure 224: Disturbance report functions and related function blocks


The whole disturbance report can contain information for a number of recordings, each with
the data coming from all the parts mentioned above. The event list function is working

Breaker protection REQ650 411


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

continuously, independent of disturbance triggering, recording time, and so on. Settings


information function contains all the visible settings, parameter information of components
configured in ACT, runtime status and IEC61850 behavior that is added to the disturbance
record header file. These settings information is recorded in XML format and then grouped for
each function instance in the HDR file. The function, setting names and Enum values are same
as in the HMI and can be translated to the selected HMI language. All setting values are
updated along with the units. If the setting values are related to the global base value, then the
setting value is scaled and updated with corresponding global base unit. All information in the
disturbance report is stored in non-volatile flash memories. This implies that no information is
lost in case of loss of auxiliary power. Each report will get an identification number in the
interval from 0-999.

Up to 100 disturbance reports can be stored. If a new disturbance is to be recorded when the
memory is full, the oldest disturbance report is overwritten by the new one. The total
recording capacity for the disturbance recorder is depending of sampling frequency, number
of analog and binary channels and recording time and settings information (refer Figure 226
for the recording times definition). Figure 225 shows the number of recordings versus the
total recording time tested for a typical configuration. In a 50 Hz system, it is possible to
record 100 disturbance recordings where the average recording time for each disturbance
recording file is 3.4 seconds with 40 analog and 96 binary signals in each recording. The
memory limit does not affect the rest of the disturbance recordings report (Event list (EL),
Event recordings (ER), Indications (IND) and Trip value recordings (TVR)).

Number of recordings
100
3,4 s

80 3,4 s 20 analog
96 binary
40 analog
96 binary
60 6,3 s
6,3 s

6,3 s 50 Hz
40
60 Hz
Total recording time

250 300 350 400 s

en05000488.vsd
IEC05000488 V1 EN-US

Figure 225: Example of number of recordings versus the total recording time

The maximum number of recordings depend on each recordings total


recording time. Long recording time will reduce the number of recordings to
less than 100.

The IED flash disk should NOT be used to store any user files. This might cause
disturbance recordings to be deleted due to lack of disk space.

412 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

Disturbance information M12155-175 v4


Date and time of the disturbance, the indications, events, fault location and the trip values are
available on the local HMI. To acquire a complete disturbance report the user must use a PC
and - either the PCM600 Disturbance handling tool - or a FTP or MMS (over 61850) client. The
PC can be connected to the IED front, rear or remotely via the station bus (Ethernet ports).

Indications (IND) M12155-87 v5


Indications is a list of signals that were activated during the total recording time of the
disturbance (not time-tagged).

Event recorder (ER) M12155-89 v6


The event recorder may contain a list of up to 150 time-tagged events, which have occurred
during the disturbance. The information is available via the local HMI or PCM600.

Event list (EL) M12155-177 v7


The event list may contain a list of totally 1000 time-tagged events. The list information is
continuously updated when selected binary signals change state. The oldest data is
overwritten. The logged signals may be presented via the local HMI or PCM600.

Trip value recorder (TVR) M12155-91 v5


The recorded trip values include phasors of selected analog signals before the fault and during
the fault.

Disturbance recorder (DR) M12155-97 v5


Disturbance recorder records analog and binary signal data before, during and after the fault.

Settings information GUID-892F72ED-CC6C-469B-90CA-73E9E1181187 v2


For each disturbance recording, the setting values of the configured components are read
twice; once during the trigger of disturbance record and again during post processing of the
disturbance record.

During post processing of the disturbance record, the header file is updated with a section
called Settings . Settings has complete setting values of the configured components that are
read during the trigger time. The setting values, runtime status and the behavior of each
component are compared between the trigger and the post processing time. If there are any
differences, then it will be added in the header file under section Changed_settings.

In the HDR file, section tag Settings has an attribute tag called function which includes
parameters that are grouped based on the function instance. The function tag has content
called name which is the function name provided together with the user-defined name in
brackets similar to the HMI. Status content will indicate the runtime status of the function and
beh content will indicate the IEC61850 behavior of the components, if supported. Non runtime
components will not have status and beh tag contents.

Parameters of the function are listed as a child tag Set with contents name, value and unit:

• name — parameter name same as HMI


• value — actual parameter value
• unit — parameter unit

The changed_settings attribute tag is similar to the settings section. It contains functions
which have changes in parameter value or runtime status or IEC61850 behavior when
compared with trigger and post-processing settings values.

Time tagging M12155-194 v1


The IED has a built-in real-time calendar and clock. This function is used for all time tagging
within the disturbance report

Breaker protection REQ650 413


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

Recording times M12155-99 v5


Disturbance report DRPRDRE records information about a disturbance during a settable time
frame. The recording times are valid for the whole disturbance report. Disturbance recorder
(DR), event recorder (ER) and indication function register disturbance data and events during
tRecording, the total recording time.

The total recording time, tRecording, of a recorded disturbance is:

tRecording = PreFaultrecT + tFault + PostFaultrecT or PreFaultrecT + TimeLimit, depending on


which criterion stops the current disturbance recording

Trig point
TimeLimit

PreFaultRecT PostFaultRecT

1 2 3

en05000487.vsd
IEC05000487 V1 EN-US

Figure 226: The recording times definition

PreFaultRecT, 1 Pre-fault or pre-trigger recording time. The time before the fault including the operate time
of the trigger. Use the setting PreFaultRecT to set this time.
tFault, 2 Fault time of the recording. The fault time cannot be set. It continues as long as any valid
trigger condition, binary or analog, persists (unless limited by TimeLimit the limit time).
PostFaultRecT, 3 Post fault recording time. The time the disturbance recording continues after all activated
triggers are reset. Use the setting PostFaultRecT to set this time.
TimeLimit Limit time. The maximum allowed recording time after the disturbance recording was
triggered. The limit time is used to eliminate the consequences of a trigger that does not
reset within a reasonable time interval. It limits the maximum recording time of a recording
and prevents subsequent overwriting of already stored disturbances. Use the setting
TimeLimit to set this time.

Analog signals M12155-160 v9


Up to 40 analog signals can be selected for recording by the Disturbance recorder and
triggering of the Disturbance report function. Out of these 40, 30 are reserved for external
analog signals from analog input modules (TRM) and line data communication module (LDCM)
via preprocessing function blocks (SMAI) and summation block (3PHSUM). The last 10 channels
may be connected to internally calculated analog signals available as function block output
signals (mA input signals, phase differential currents, bias currents and so on).

414 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

SMAI A1RADR
Block AI3P A2RADR
^GRP2L1 AI1 INPUT1 A3RADR
External
analogue ^GRP2L2 AI2 INPUT2
signals ^GRP2L3 AI3 INPUT3
^GRP2N AI4 INPUT4
Type AIN INPUT5
INPUT6
...

A4RADR

INPUT31
INPUT32
INPUT33
Internal analogue signals INPUT34
INPUT35
INPUT36

...

INPUT40

IEC10000029-1-en.vsd
IEC10000029 V1 EN-US

Figure 227: Analog input function blocks


The external input signals will be acquired, filtered and skewed and (after configuration)
available as an input signal on the AxRADR function block via the SMAI function block. The
information is saved at the Disturbance report base sampling rate (1000 or 1200 Hz). Internally
calculated signals are updated according to the cycle time of the specific function. If a function
is running at lower speed than the base sampling rate, Disturbance recorder will use the latest
updated sample until a new updated sample is available.

If the IED is preconfigured the only tool needed for analog configuration of the Disturbance
report is the Signal Matrix Tool (SMT, external signal configuration). In case of modification of
a preconfigured IED or general internal configuration the Application Configuration tool within
PCM600 is used.

The preprocessor function block (SMAI) calculates the residual quantities in cases where only
the three phases are connected (AI4-input not used). SMAI makes the information available as
a group signal output, phase outputs and calculated residual output (AIN-output). In situations
where AI4-input is used as an input signal the corresponding information is available on the
non-calculated output (AI4) on the SMAI function block. Connect the signals to the AxRADR
accordingly.

For each of the analog signals, Operation = On means that it is recorded by the disturbance
recorder. The trigger is independent of the setting of Operation, and triggers even if operation
is set to Off. Both undervoltage and overvoltage can be used as trigger conditions. The same
applies for the current signals.

If Operation = Off, no waveform (samples) will be recorded and reported in graph. However,
Trip value, pre-fault and fault value will be recorded and reported. The input channel can still be
used to trig the disturbance recorder.

If Operation = On, waveform (samples) will also be recorded and reported in graph.

The analog signals are presented only in the disturbance recording, but they affect the entire
disturbance report when being used as triggers.

Breaker protection REQ650 415


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

Binary signals M12155-162 v10


Up to 352 binary signals can be selected to be handled by disturbance report. The signals can
be selected from internal logical and binary input signals. A binary signal is selected to be
recorded when:

• the corresponding function block is included in the configuration


• the signal is connected to the input of the function block

Each of the 352 signals can be selected as a trigger of the disturbance report (Operation = On).
A binary signal can be selected to activate the red LED on the local HMI (SetLED = On).

The selected signals are presented in the event recorder, event list and the disturbance
recording. But they affect the whole disturbance report when they are used as triggers. The
indications are also selected from these 352 signals with local HMI IndicationMask = Show/
Hide.

Trigger signals M12155-164 v3


The trigger conditions affect the entire disturbance report, except the event list, which runs
continuously. As soon as at least one trigger condition is fulfilled, a complete disturbance
report is recorded. On the other hand, if no trigger condition is fulfilled, there is no
disturbance report, no indications, and so on. This implies the importance of choosing the
right signals as trigger conditions.

A trigger can be of type:

• Manual trigger
• Binary-signal trigger
• Analog-signal trigger (over/under function)

Manual trigger M12155-167 v5


A disturbance report can be manually triggered from the local HMI, PCM600 or via station bus
(IEC 61850). When the trigger is activated, the manual trigger signal is generated. This feature
is especially useful for testing. Refer to the operator's manual for procedure.

Binary-signal trigger M12155-169 v4


Any binary signal state (logic one or a logic zero) can be selected to generate a trigger
(Triglevel = Trig on 0/Trig on 1). When a binary signal is selected to generate a trigger from a
logic zero, the selected signal will not be listed in the indications list of the disturbance report.

Analog-signal trigger M12155-171 v6


All analog signals are available for trigger purposes, no matter if they are recorded in the
disturbance recorder or not. The settings are OverTrigOp, UnderTrigOp, OverTrigLe and
UnderTrigLe.

The check of the trigger condition is based on peak-to-peak values. When this is found, the
absolute average value of these two peak values is calculated. If the average value is above the
threshold level for an overvoltage or overcurrent trigger, this trigger is indicated with a greater
than (>) sign with the user-defined name.

If the average value is below the set threshold level for an undervoltage or undercurrent
trigger, this trigger is indicated with a less than (<) sign with its name. The procedure is
separately performed for each channel.

This method of checking the analog start conditions gives a function which is insensitive to DC
offset in the signal. The operate time for this start is typically in the range of one cycle, 20 ms
for a 50 Hz network.

All under/over trig signal information is available on the local HMI and PCM600.

416 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

11.6.8 Technical data


M12760-1 v11

Table 351: DRPRDRE technical data


Function Range or value Accuracy
Pre-fault time (0.05–9.90) s -
Post-fault time (0.1–10.0) s -
Limit time (0.5–10.0) s -
Maximum number of recordings 100, first in - first out -
Time tagging resolution 1 ms See table 509
Maximum number of analog inputs 30 + 10 (external + internally -
derived)
Maximum number of binary inputs 352 -
Maximum number of phasors in the Trip Value 30 -
recorder per recording
Maximum number of indications in a disturbance 352 -
report
Maximum number of events in the Event recording 150 -
per recording
Maximum number of events in the Event list 1000, first in - first out -
Maximum total recording time (3.4 s recording 340 seconds (100 recordings) -
time and maximum number of channels, typical at 50 Hz, 280 seconds (80
value) recordings) at 60 Hz
Sampling rate 1 kHz at 50 Hz -
1.2 kHz at 60 Hz
Recording bandwidth (5-300) Hz -

11.7 Logical signal status report BINSTATREP GUID-E7A2DB38-DD96-4296-B3D5-EB7FBE77CE07 v2

11.7.1 Identification GUID-E0247779-27A2-4E6C-A6DD-D4C31516CA5C v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Logical signal status report BINSTATREP - -

11.7.2 Functionality GUID-A72E490D-01F7-4874-B010-8BDE38391D88 v3

The Logical signal status report (BINSTATREP) function makes it possible for a SPA master to
poll signals from various other functions.

Breaker protection REQ650 417


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

11.7.3 Function block GUID-BA0A5BC3-493B-4FE3-B4A9-14F60A88A22F v2

BINSTATREP
BLOCK OUTPUT1
^INPUT1 OUTPUT2
^INPUT2 OUTPUT3
^INPUT3 OUTPUT4
^INPUT4 OUTPUT5
^INPUT5 OUTPUT6
^INPUT6 OUTPUT7
^INPUT7 OUTPUT8
^INPUT8 OUTPUT9
^INPUT9 OUTPUT10
^INPUT10 OUTPUT11
^INPUT11 OUTPUT12
^INPUT12 OUTPUT13
^INPUT13 OUTPUT14
^INPUT14 OUTPUT15
^INPUT15 OUTPUT16
^INPUT16

IEC09000730-1-en.vsd
IEC09000730 V1 EN-US

Figure 228: BINSTATREP function block

11.7.4 Signals
PID-4144-INPUTSIGNALS v6

Table 352: BINSTATREP Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
INPUT1 BOOLEAN 0 Single status report input 1
INPUT2 BOOLEAN 0 Single status report input 2
INPUT3 BOOLEAN 0 Single status report input 3
INPUT4 BOOLEAN 0 Single status report input 4
INPUT5 BOOLEAN 0 Single status report input 5
INPUT6 BOOLEAN 0 Single status report input 6
INPUT7 BOOLEAN 0 Single status report input 7
INPUT8 BOOLEAN 0 Single status report input 8
INPUT9 BOOLEAN 0 Single status report input 9
INPUT10 BOOLEAN 0 Single status report input 10
INPUT11 BOOLEAN 0 Single status report input 11
INPUT12 BOOLEAN 0 Single status report input 12
INPUT13 BOOLEAN 0 Single status report input 13
INPUT14 BOOLEAN 0 Single status report input 14
INPUT15 BOOLEAN 0 Single status report input 15
INPUT16 BOOLEAN 0 Single status report input 16

418 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

PID-4144-OUTPUTSIGNALS v6

Table 353: BINSTATREP Output signals


Name Type Description
OUTPUT1 BOOLEAN Logical status report output 1
OUTPUT2 BOOLEAN Logical status report output 2
OUTPUT3 BOOLEAN Logical status report output 3
OUTPUT4 BOOLEAN Logical status report output 4
OUTPUT5 BOOLEAN Logical status report output 5
OUTPUT6 BOOLEAN Logical status report output 6
OUTPUT7 BOOLEAN Logical status report output 7
OUTPUT8 BOOLEAN Logical status report output 8
OUTPUT9 BOOLEAN Logical status report output 9
OUTPUT10 BOOLEAN Logical status report output 10
OUTPUT11 BOOLEAN Logical status report output 11
OUTPUT12 BOOLEAN Logical status report output 12
OUTPUT13 BOOLEAN Logical status report output 13
OUTPUT14 BOOLEAN Logical status report output 14
OUTPUT15 BOOLEAN Logical status report output 15
OUTPUT16 BOOLEAN Logical status report output 16

11.7.5 Settings
PID-4144-SETTINGS v6

Table 354: BINSTATREP Non group settings (basic)


Name Values (Range) Unit Step Default Description
t 0.0 - 60.0 s 0.1 10.0 Time delay of function

11.7.6 Operation principle GUID-537921CA-82B9-4A02-BAD1-67E3AC61AE96 v3

The Logical signal status report (BINSTATREP) function has 16 inputs and 16 outputs. The
output status follows the inputs and can be read from the local HMI or via SPA communication.

When an input is set, the respective output is set for a user defined time. If the input signal
remains set for a longer period, the output will remain set until the input signal resets.

INPUTn

OUTPUTn
t t

IEC09000732-1-en.vsd
IEC09000732 V1 EN-US

Figure 229: BINSTATREP logical diagram

Breaker protection REQ650 419


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

11.8 Measured value expander block RANGE_XP SEMOD52451-1 v2

11.8.1 Identification
SEMOD113212-2 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Measured value expander block RANGE_XP - -

11.8.2 Functionality SEMOD52450-4 v8

The current and voltage measurements functions (CVMMXN, CMMXU, VMMXU and VNMMXU),
current and voltage sequence measurement functions (CMSQI and VMSQI) and IEC 61850
generic communication I/O functions (MVGAPC) are provided with measurement supervision
functionality. All measured values can be supervised with four settable limits: low-low limit,
low limit, high limit and high-high limit. The measure value expander block (RANGE_XP) has
been introduced to enable translating the integer output signal from the measuring functions
to 5 binary signals: below low-low limit, below low limit, normal, above high limit or above
high-high limit. The output signals can be used as conditions in the configurable logic or for
alarming purpose.

11.8.3 Function block SEMOD54336-4 v3

RANGE_XP
RANGE* HIGHHIGH
HIGH
NORMAL
LOW
LOWLOW

IEC05000346-2-en.vsd
IEC05000346 V2 EN-US

Figure 230: RANGE_XP function block

11.8.4 Signals SEMOD53803-1 v2

PID-3819-INPUTSIGNALS v5

Table 355: RANGE_XP Input signals


Name Type Default Description
RANGE INTEGER 0 Measured value range

PID-3819-OUTPUTSIGNALS v5

Table 356: RANGE_XP Output signals


Name Type Description
HIGHHIGH BOOLEAN Measured value is above high-high limit
HIGH BOOLEAN Measured value is between high and high-high limit
NORMAL BOOLEAN Measured value is between high and low limit
LOW BOOLEAN Measured value is between low and low-low limit
LOWLOW BOOLEAN Measured value is below low-low limit

420 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

11.8.5 Operation principle SEMOD52462-4 v6

The input signal must be connected to a range output of a measuring function block
(CVMMXN, CMMXU, VMMXU, VNMMXU, CMSQI, VMSQ or MVGAPC). The function block converts
the input integer value to five binary output signals according to table 357.

Table 357: Input integer value converted to binary output signals


Measured supervised below low- between low‐ between low between above high-high limit
value is: low limit low and low and high limit high-high
Output: limit and high limit
LOWLOW High
LOW High
NORMAL High
HIGH High
HIGHHIGH High

11.9 Limit counter L4UFCNT GUID-22E141DB-38B3-462C-B031-73F7466DD135 v1

11.9.1 Identification
GUID-F3FB7B33-B189-4819-A1F0-8AC7762E9B7E v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Limit counter L4UFCNT -

11.9.2 Functionality GUID-13157EAB-1686-4D2E-85DF-EC89768F3572 v6

The Limit counter (L4UFCNT) provides a settable counter with four independent limits where
the number of positive and/or negative flanks on the input signal are counted against the
setting values for limits. The output for each limit is activated when the counted value reaches
that limit.

Overflow indication is included for each up-counter.

11.9.3 Operation principle


GUID-4D58423F-329C-4553-9FAF-E55A368849A5 v2
Limit counter (L4UFCNT) counts the number of positive and/or negative flanks on the binary
input signal depending on the function settings. L4UFCNT also checks if the accumulated
value is equal or greater than any of its four settable limits. The four limit outputs will be
activated relatively on reach of each limit and remain activated until the reset of the function.
Moreover, the content of L4UFCNT is stored in flash memory and will not be lost at an auxiliary
power interruption.

11.9.3.1 Design GUID-B643C994-D0BA-4BE9-BACB-ADEA0197CAE4 v1

Figure 231 illustrates the general logic diagram of the function.

Breaker protection REQ650 421


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

BLOCK

INPUT
Operation
Counter
RESET
VALUE
Overflow
CountType Detection OVERFLOW

OnMaxValue

Limit LIMIT1 … 4
MaxValue Check

CounterLimit1...4

Error ERROR
Detection
InitialValue

IEC12000625_1_en.vsd
IEC12000625 V1 EN-US

Figure 231: Logic diagram


The counter can be initialized to count from a settable non-zero value after reset of the
function. The function has also a maximum counted value check. The three possibilities after
reaching the maximum counted value are:

• Stops counting and activates a steady overflow indication for the next count
• Rolls over to zero and activates a steady overflow indication for the next count
• Rolls over to zero and activates a pulsed overflow indication for the next count

The pulsed overflow output lasts up to the first count after rolling over to zero, as illustrated in
figure 232.

Overflow indication

Actual value ... Max value -1® Max value ® Max value +1 ® Max value +2 ® Max value +3 ...

Counted value ... Max value -1 ® Max value ® 0 ® 1 ® 2 ...

IEC12000626_1_en.vsd
IEC12000626 V1 EN-US

Figure 232: Overflow indication when OnMaxValue is set to rollover pulsed


The Error output is activated as an indicator of setting the counter limits and/or initial value
setting(s) greater than the maximum value. The counter stops counting the input and all the
outputs except the error output remains at zero state. The error condition remains until the
correct settings for counter limits and/or initial value setting(s) are applied.

The function can be blocked through a block input. During the block time, input is not counted
and outputs remain in their previous states. However, the counter can be initialized after reset
of the function. In this case the outputs remain in their initial states until the release of the
block input.

422 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

11.9.3.2 Reporting GUID-7DF874A7-F7DA-48DD-8760-5E4CF05FD870 v2

The content of the counter can be read on the local HMI.

Reset of the counter can be performed from the local HMI or via a binary input.

Reading of content and resetting of the function can also be performed remotely, for example
from a IEC 61850 client. The value can also be presented as a measurement on the local HMI
graphical display.

11.9.4 Function block GUID-C90E7375-F3CC-414A-93FC-9AC4A9156FFC v1

L4UFCNT
BLOCK ERROR
INPUT OVERFLOW
RESET LIMIT1
LIMIT2
LIMIT3
LIMIT4
VALUE

IEC12000029-1-en.vsd
IEC12000029 V1 EN-US

Figure 233: L4UFCNT function block

11.9.5 Signals
PID-6966-INPUTSIGNALS v2

Table 358: L4UFCNT Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
INPUT BOOLEAN 0 Input for counter
RESET BOOLEAN 0 Reset of function

PID-6966-OUTPUTSIGNALS v2

Table 359: L4UFCNT Output signals


Name Type Description
ERROR BOOLEAN Error indication on counter limit and/or initial value settings
OVERFLOW BOOLEAN Overflow indication on count of greater than MaxValue
LIMIT1 BOOLEAN Counted value is larger than or equal to CounterLimit1
LIMIT2 BOOLEAN Counted value is larger than or equal to CounterLimit2
LIMIT3 BOOLEAN Counted value is larger than or equal to CounterLimit3
LIMIT4 BOOLEAN Counted value is larger than or equal to CounterLimit4
VALUE INTEGER Counted value

Breaker protection REQ650 423


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

11.9.6 Settings
PID-6966-SETTINGS v2

Table 360: L4UFCNT Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
CountType Positive edge - - Positive edge Select counting on positive and/or
Negative edge negative flanks
Both edges
CounterLimit1 1 - 65535 - 1 100 Value of the first limit
CounterLimit2 1 - 65535 - 1 200 Value of the second limit
CounterLimit3 1 - 65535 - 1 300 Value of the third limit
CounterLimit4 1 - 65535 - 1 400 Value of the fourth limit
MaxValue 1 - 65535 - 1 500 Maximum count value
OnMaxValue Stop - - Stop Select if counter stops or rolls over
Rollover Steady after reaching maxValue with steady
Rollover Pulsed or pulsed overflow flag
InitialValue 0 - 65535 - 1 0 Initial count value after reset of the
function

11.9.7 Monitored data


PID-6966-MONITOREDDATA v2

Table 361: L4UFCNT Monitored data


Name Type Values (Range) Unit Description
VALUE INTEGER - - Counted value

11.9.8 Technical data


GUID-C43B8654-60FE-4E20-8328-754C238F4AD0 v3

Table 362: L4UFCNT technical data


Function Range or value Accuracy
Counter value 0-65535 -
Max. count up speed 30 pulses/s (50% duty cycle) -

11.10 Running hour-meter TEILGAPC

11.10.1 Identification GUID-3F9EF4FA-74FA-4D1D-88A0-E948B722B64F v1

Function Description IEC 61850 IEC 60617 ANSI/IEEE C37.2 device


identification identification number
Running hour-meter TEILGAPC - -

424 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

11.10.2 Functionality GUID-464FB24F-B367-446C-963A-A14841943B87 v2

The Running hour-meter (TEILGAPC) function is a function that accumulates the elapsed time
when a given binary signal has been high, see also figure 234.

BLOCK
RESET
IN Time Accumulation ACC_HOUR
ADDTIME with Retain
ACC_DAY
tAddToTime

q-1

OVERFLOW
a
&
a>b
99 999.9 h b

WARNING
a
&
a>b
tWarning b

ALARM
a
&
a>b
tAlarm b

q-1 = unit delay IEC15000321-1-en.vsd

IEC15000321 V1 EN-US

Figure 234: TEILGAPC logics


The main features of TEILGAPC are:

• Applicable to very long time accumulation (≤ 99999.9 hours)


• Supervision of limit transgression conditions and rollover/overflow
• Possibility to define a warning and alarm with the resolution of 0.1 hours
• Retain any saved accumulation value at a restart
• Possibilities for blocking and reset
• Possibility for manual addition of accumulated time
• Reporting of the accumulated time

11.10.3 Function block GUID-D0E9688B-C9D9-44B7-BD95-81132CCA5E4F v1

TEILGAPC
BLOCK ALARM
IN WARNING
ADDTIME OVERFLOW
RESET ACC_HOUR
ACC_DAY

IEC15000323.vsdx

IEC15000323 V1 EN-US

Figure 235: TEILGAPC function block

Breaker protection REQ650 425


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

11.10.4 Signals
PID-6998-INPUTSIGNALS v1

Table 363: TEILGAPC Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Freeze the accumulation and block the outputs
IN BOOLEAN 0 The input signal that is used to measure the elapsed time,
when its value is high
ADDTIME BOOLEAN 0 Add time to the accumulation
RESET BOOLEAN 0 Reset accumulated time

PID-6998-OUTPUTSIGNALS v1

Table 364: TEILGAPC Output signals


Name Type Description
ALARM BOOLEAN Indicator that accumulated time has reached alarm limit
WARNING BOOLEAN Indicator that accumulated time has reached warning limit
OVERFLOW BOOLEAN Indicator that accumulated time has reached overflow limit
ACC_HOUR REAL Accumulated time in hours
ACC_DAY REAL Accumulated time in days

11.10.5 Settings
PID-6998-SETTINGS v1

Table 365: TEILGAPC Group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off / On
On
tAlarm 1.0 - 99999.9 Hour 0.1 90000.0 Time limit for alarm supervision
tWarning 1.0 - 99999.9 Hour 0.1 50000.0 Time limit for warning supervision
tAddToTime 0.0 - 99999.9 Hour 0.1 0.0 Time to add to the accumulation

11.10.6 Operation principle GUID-C7F91D4E-5942-4006-B7C8-4F499E7DC49D v3

Figure 236 describes the simplified logic of the function.

426 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 11
Monitoring

Loop Delay

tWarning
OVERFLOW
tAlarm
Transgression Supervision WARNING
Plus Retain
ALARM

BLOCK
RESET ACC_HOUR
Time Accumulation
IN
ADDTIME ACC_DAY

tAddToTime

Loop Delay

IEC15000322.vsd

IEC15000322 V1 EN-US

Figure 236: TEILGAPC Simplified logic


TEILGAPC main functionalities

• IN: Accumulation of the elapsed time when input IN is high


• applicable to very long time accumulation (≤99999.9 hours)
• output ACC_HOUR presents accumulated value in hours and ACC_DAY presents
accumulated value in days
• accumulated value is retained in a non-volatile memory
• any retained value is used as initiation value for the integration following by a restart
• RESET: Reset of the accumulated value. Consequently all other outputs are also reset
• independent of the input IN value
• reset the value of the nonvolatile memory to zero.
Note that the nonvolatile memory will not reset to zero if the input IN is high during
the reset.
• reset can be made by activation of input RESET or from LHMI or with IEC 61850
command
• ADDTIME: Manually add time to the currently accumulated time
• the amount of time to be added is defined by a setting tAddToTime
• time is added through activation of input ADDTIME or from LHMI or with IEC 61850
command
• BLOCK: Freeze the accumulation and block/reset the other outputs
• independent of the input IN value
• BLOCK request overrides RESETrequest
• Monitor and report the conditions of limit transgression
• overflow if output ACC_HOUR > 99 999.9 hours
• alarm if output ACC_HOUR > tAlarm
• warning if output ACC_HOUR > tWarning

The ACC_HOURoutput represents the accumulated time in hours and the ACC_DAY output
represents the accumulated time in days.

tAlarm and tWarning are user settable time limit parameters in hours. They are also
independent of each other, that is, there is no check if tAlarm > tWarning.

Breaker protection REQ650 427


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 11 1MRK 505 384-UEN C
Monitoring

tAddToTime is a user settable time parameter in hours.

tAlarm, tWarning and tAddToTime are possible to be defined with a resolution of 0.1 hours (6
minutes).

The limit for the overflow supervision is fixed at 99999.9 hours. The outputs will reset and the
accumulated time will reset and start from zero if an overflow occurs.

11.10.6.1 Operation accuracy GUID-B6FBEFD7-17C8-41C6-B5D5-32E1205E6752 v1

The accuracy of TEILGAPC depends on essentially two factors

• the pulse length


• the number of pulses, that is, the number of rising and falling flank pairs

In principle, more pulses may lead to reduced accuracy.

11.10.6.2 Memory storage GUID-B49698FF-0AB2-4792-A7CB-5534313B6CA0 v2

The value of the accumulated time is retained in a non-volatile memory,

• at every falling edge of the input IN


• at every even 6 minutes, after a rising edge of the input IN
• after a manual addition of time

Consequently in case of a power failure, there is a risk of losing the difference in time between
actual time and last time stored in the non-volatile memory.

11.10.7 Technical data


GUID-F5E124E3-0B85-41AC-9830-A2362FD289F2 v1

Table 366: TEILGAPC Technical data


Function Range or value Accuracy
Time limit for alarm supervision, (0 - 99999.9) hours ±0.1% of set value
tAlarm
Time limit for warning supervision, (0 - 99999.9) hours ±0.1% of set value
tWarning
Time limit for overflow supervision Fixed to 99999.9 hours ±0.1%

428 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 12
Metering

Section 12 Metering
12.1 Pulse-counter logic PCFCNT IP14600-1 v3

12.1.1 Identification
M14879-1 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Pulse-counter logic PCFCNT -

S00947 V1 EN-US

12.1.2 Functionality M13394-3 v7

Pulse-counter logic (PCFCNT) function counts externally generated binary pulses, for instance
pulses coming from an external energy meter, for calculation of energy consumption values.
The pulses are captured by the binary input module and then read by the PCFCNT function. A
scaled service value is available over the station bus. The special Binary input module with
enhanced pulse counting capabilities must be ordered to achieve this functionality.

12.1.3 Function block M13400-3 v5

PCFCNT
BLOCK INVALID
READ_VAL RESTART
BI_PULSE* BLOCKED
RS_CNT NEW_VAL
SCAL_VAL

IEC14000043-1-en.vsd
IEC09000335 V3 EN-US

Figure 237: PCFCNT function block

12.1.4 Signals
PID-6509-INPUTSIGNALS v4

Table 367: PCFCNT Input signals


Name Type Default Description
BI_PULSE BOOLEAN 0 Connect binary input channel for metering
BLOCK BOOLEAN 0 Block of function
READ_VAL BOOLEAN 0 Initiates an additional pulse counter reading
RS_CNT BOOLEAN 0 Resets pulse counter value

Breaker protection REQ650 429


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 12 1MRK 505 384-UEN C
Metering

PID-6509-OUTPUTSIGNALS v4

Table 368: PCFCNT Output signals


Name Type Description
INVALID BOOLEAN The pulse counter value is invalid
RESTART BOOLEAN The reported value does not comprise a complete integration
cycle
BLOCKED BOOLEAN The pulse counter function is blocked
NEW_VAL BOOLEAN A new pulse counter value is generated
SCAL_VAL REAL Scaled value with time and status information

12.1.5 Settings
PID-6509-SETTINGS v4

Table 369: PCFCNT Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
EventMask NoEvents - - NoEvents Report mask for analog events from
ReportEvents pulse counter
CountCriteria Off - - RisingEdge Pulse counter criteria
RisingEdge
Falling edge
OnChange
Scale 1.000 - - 0.001 1.000 Scaling value for SCAL_VAL output to
90000.000 unit per counted value
Quantity Count - - Count Measured quantity for SCAL_VAL
ActivePower output
ApparentPower
ReactivePower
ActiveEnergy
ApparentEnergy
ReactiveEnergy
tReporting 0 - 3600 s 1 60 Cycle time for reporting of counter
value

12.1.6 Monitored data


PID-6509-MONITOREDDATA v4

Table 370: PCFCNT Monitored data


Name Type Values (Range) Unit Description
SCAL_VAL REAL - - Scaled value with time and status
information

12.1.7 Operation principle IP14087-1 v2

M13397-3 v5
The registration of pulses is done for positive transitions (0->1) on one of the 16 binary input
channels located on the Binary Input Module (BIM). Pulse counter values are sent to the station
HMI with predefined cyclicity without reset.

The reporting time period can be set in the range from 1 second to 60 minutes and is
synchronized with absolute system time. Interrogation of additional pulse counter values can

430 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 12
Metering

be done with a command (intermediate reading) for a single counter. All active counters can
also be read by the LON General Interrogation command (GI) or IEC 61850.

Pulse-counter logic (PCFCNT) function in the IED supports unidirectional incremental counters.
That means only positive values are possible. The counter uses a 32 bit format, that is, the
reported value is a 32-bit, signed integer with a range 0...+2147483647. The counter is reset at
initialization of the IED.

The reported value to station HMI over the station bus contains Identity, Scaled Value (pulse
count x scale), Time, and Pulse Counter Quality. The Pulse Counter Quality consists of:

• Invalid (board hardware error or configuration error)


• Wrapped around
• Blocked
• Adjusted

The transmission of the counter value by SPA can be done as a service value, that is, the value
frozen in the last integration cycle is read by the station HMI from the database. PCFCNT
updates the value in the database when an integration cycle is finished and activates the
NEW_VAL signal in the function block. This signal can be connected to an Event function block,
be time tagged, and transmitted to the station HMI. This time corresponds to the time when
the value was frozen by the function.

The pulse-counter logic function requires a binary input card, BIMp, that is
specially adapted to the pulse-counter logic function.

M13399-3 v9
Figure 238 shows the pulse-counter logic function block with connections of the inputs and
outputs.

SingleCmdFunc PulseCounter EVENT


OUTx BLOCK
INVALID INPUT1
SingleCmdFunc Pulse RESTART INPUT2
OUTx INPUT OUT READ_VAL
Pulse length >1s BLOCKED INPUT3
I/O-module NEW_VAL INPUT4
BI_PULSE
”Reset counter” RS_CNT
NAME
SCAL_VAL IEC EVENT

SMS settings Database


1.Operation = Off/On Pulse counter value:
2.tReporting = 0s...60min 0...2147483647
3.Event Mask = No Events/Report Events
4.Scale = 1-90000
en05000744.vsd
IEC05000744 V1 EN-US

Figure 238: Overview of the pulse-counter logic function


The BLOCK and READ_VAL inputs can be connected to Single Command logics, which are
intended to be controlled either from the station HMI or/and the local HMI. As long as the
BLOCK signal is set, the pulse counter is blocked. The signal connected to READ_VAL performs
one additional reading per positive flank. The signal must be a pulse with a length >1 second.

The BI_PULSE input is connected to the used input of the function block for the Binary Input
Module (BIM).

The RS_CNT input is used for resetting the counter.

Breaker protection REQ650 431


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 12 1MRK 505 384-UEN C
Metering

Each pulse-counter logic function block has four binary output signals that can be connected
to an Event function block for event recording: INVALID, RESTART, BLOCKED and NEW_VAL.
The SCAL_VAL signal can be connected to the IEC Event function block.

The INVALID signal is a steady signal and is set if the Binary Input Module, where the pulse
counter input is located, fails or has wrong configuration.

The RESTART signal is a steady signal and is set when the reported value does not comprise a
complete integration cycle. That is, in the first message after IED start-up, in the first message
after deblocking, and after the counter has wrapped around during last integration cycle.

The BLOCKED signal is a steady signal and is set when the counter is blocked. There are two
reasons why the counter is blocked:

• The BLOCK input is set, or


• The Binary Input Module, where the counter input is situated, is inoperative.

The NEW_VAL signal is a pulse signal. The signal is set if the counter value was updated since
last report.

Note, the pulse is short, one cycle.

The SCAL_VAL signal consists of scaled value (according to parameter Scale), time and status
information.

12.1.8 Technical data IP14092-1 v1

M13404-2 v5

Table 371: PCFCNT technical data


Function Setting range Accuracy
Input frequency See Binary Input Module (BIM) -
Cycle time for report of (1–3600) s -
counter value

12.2 Function for energy calculation and demand handling


ETPMMTR SEMOD153638-1 v2

12.2.1 Identification
SEMOD175537-2 v4

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Function for energy calculation and ETPMMTR W_Varh -
demand handling

432 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 12
Metering

12.2.2 Functionality GUID-6898E29B-DA70-421C-837C-1BBED8C63A7A v3

Power system measurement (CVMMXN) can be used to measure active as well as reactive
power values. Function for energy calculation and demand handling (ETPMMTR) uses
measured active and reactive power as input and calculates the accumulated active and
reactive energy pulses, in forward and reverse direction. Energy values can be read or
generated as pulses. Maximum demand power values are also calculated by the function. This
function includes zero point clamping to remove noise from the input signal. As output of this
function: periodic energy calculations, integration of energy values, calculation of energy
pulses, alarm signals for limit violation of energy values and maximum power demand, can be
found.

The values of active and reactive energies are calculated from the input power values by
integrating them over a selected time tEnergy. The integration of active and reactive energy
values will happen in both forward and reverse directions. These energy values are available as
output signals and also as pulse outputs. Integration of energy values can be controlled by
inputs (STARTACC and STOPACC) and EnaAcc setting and it can be reset to initial values with
RSTACC input.

The maximum demand for active and reactive powers are calculated for the set time interval
tEnergy and these values are updated every minute through output channels. The active and
reactive maximum power demand values are calculated for both forward and reverse direction
and these values can be reset with RSTDMD input.

12.2.3 Function block SEMOD175502-4 v5

ETPMMTR
P* ACCINPRG
Q* EAFPULSE
STARTACC EARPULSE
STOPACC ERFPULSE
RSTACC ERRPULSE
RSTDMD EAFALM
EARALM
ERFALM
ERRALM
EAFACC
EARACC
ERFACC
ERRACC
MAXPAFD
MAXPARD
MAXPRFD
MAXPRRD

IEC14000019-1-en.vsd
IEC14000019 V1 EN-US

Figure 239: ETPMMTR function block

12.2.4 Signals
PID-6872-INPUTSIGNALS v3

Table 372: ETPMMTR Input signals


Name Type Default Description
P REAL 0 Measured active power
Q REAL 0 Measured reactive power
STARTACC BOOLEAN 0 Start to accumulate energy values
STOPACC BOOLEAN 0 Stop to accumulate energy values.
RSTACC BOOLEAN 0 Reset of accumulated enery reading
RSTDMD BOOLEAN 0 Reset of maximum demand reading

Breaker protection REQ650 433


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 12 1MRK 505 384-UEN C
Metering

PID-6872-OUTPUTSIGNALS v3

Table 373: ETPMMTR Output signals


Name Type Description
ACCINPRG BOOLEAN Accumulation of energy values in progress
EAFPULSE BOOLEAN Accumulated forward active energy pulse
EARPULSE BOOLEAN Accumulated reverse active energy pulse
ERFPULSE BOOLEAN Accumulated forward reactive energy pulse
ERRPULSE BOOLEAN Accumulated reverse reactive energy pulse
EAFALM BOOLEAN Alarm for active forward energy exceed limit in set interval
EARALM BOOLEAN Alarm for active reverse energy exceed limit in set interval
ERFALM BOOLEAN Alarm for reactive forward energy exceed limit in set interval
ERRALM BOOLEAN Alarm for reactive reverse energy exceed limit in set interval
EAFACC REAL Accumulated forward active energy value
EARACC REAL Accumulated reverse active energy value
ERFACC REAL Accumulated forward reactive energy value
ERRACC REAL Accumulated reverse reactive energy value
MAXPAFD REAL Maximum forward active power demand value for set interval
MAXPARD REAL Maximum reverse active power demand value for set interval
MAXPRFD REAL Maximum forward reactive power demand value for set
interval
MAXPRRD REAL Maximum reverse reactive power demand value for set
interval

12.2.5 Settings
PID-6872-SETTINGS v3

Table 374: ETPMMTR Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
EnaAcc Off - - Off Activate the accumulation of energy
On values
tEnergy 1 Minute - - 1 Minute Time interval for energy calculation
5 Minutes
10 Minutes
15 Minutes
30 Minutes
60 Minutes
180 Minutes
tEnergyOnPls 0.100 - 60.000 s 0.001 1.000 Energy accumulated pulse ON time in
secs
tEnergyOffPls 0.100 - 60.000 s 0.001 0.500 Energy accumulated pulse OFF time in
secs
EAFAccPlsQty 0.001 - 10000.000 MWh 0.001 100.000 Pulse quantity for active forward
accumulated energy value
EARAccPlsQty 0.001 - 10000.000 MWh 0.001 100.000 Pulse quantity for active reverse
accumulated energy value
ERFAccPlsQty 0.001 - 10000.000 MVArh 0.001 100.000 Pulse quantity for reactive forward
accumulated energy value
ERRAccPlsQty 0.001 - 10000.000 MVArh 0.001 100.000 Pulse quantity for reactive reverse
accumulated energy value

434 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 12
Metering

Table 375: ETPMMTR Non group settings (advanced)


Name Values (Range) Unit Step Default Description
EALim 0.001 - MWh 0.001 1000000.000 Active energy limit
10000000000.00
0
ERLim 0.001 - MVArh 0.001 1000.000 Reactive energy limit
10000000000.00
0
EnZeroClamp Off - - On Enable of zero point clamping
On detection function
LevZeroClampP 0.001 - 10000.000 MW 0.001 10.000 Zero point clamping level at active
Power
LevZeroClampQ 0.001 - 10000.000 MVAr 0.001 10.000 Zero point clamping level at reactive
Power
DirEnergyAct Forward - - Forward Direction of active energy flow
Reverse Forward/Reverse
DirEnergyReac Forward - - Forward Direction of reactive energy flow
Reverse Forward/Reverse
EAFPrestVal 0.000 - MWh 0.001 0.000 Preset Initial value for forward active
100000000.000 energy
EARPrestVal 0.000 - MWh 0.001 0.000 Preset Initial value for reverse active
100000000.000 energy
ERFPresetVal 0.000 - MVArh 0.001 0.000 Preset Initial value for forward
100000000.000 reactive energy
ERRPresetVal 0.000 - MVArh 0.001 0.000 Preset Initial value for reverse reactive
100000000.000 energy

12.2.6 Monitored data


PID-6872-MONITOREDDATA v3

Table 376: ETPMMTR Monitored data


Name Type Values (Range) Unit Description
EAFACC REAL - MWh Accumulated forward active energy
value
EARACC REAL - MWh Accumulated reverse active energy
value
ERFACC REAL - MVArh Accumulated forward reactive energy
value
ERRACC REAL - MVArh Accumulated reverse reactive energy
value
MAXPAFD REAL - MW Maximum forward active power
demand value for set interval
MAXPARD REAL - MW Maximum reverse active power
demand value for set interval
MAXPRFD REAL - MVAr Maximum forward reactive power
demand value for set interval
MAXPRRD REAL - MVAr Maximum reverse reactive power
demand value for set interval

Breaker protection REQ650 435


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 12 1MRK 505 384-UEN C
Metering

12.2.7 Operation principle GUID-4A46757C-EC5D-4BCE-9D09-C8152B062CE1 v3

The instantaneous output values of active and reactive power from the Measurements
function CVMMXN are used and integrated over a selected time tEnergy to measure the
integrated energy. Figure 240 shows the overall functionality of the energy calculation and
demand handling function ETPMMTR.

MAXPAFD
RSTDMD
MAXPARD
MAXPRFD
P
MAXPRRD
Zero Clamping Maximum Power
EAFALM
Detection Demand Calculation
Q EARALM
ERFALM
ERRALM

ACCINPRG
EAFPULSE
EARPULSE
ERFPULSE
Energy Accumulation ERRPULSE
STARTACC
Calculation EAFACC
EARACC
STOPACC
ERFACC
ERRACC
RSTACC

IEC13000185-2-en.vsd
IEC13000185 V2 EN-US

Figure 240: ETPMMTR Functional overview logical diagram


The integration of energy values is enabled by the setting EnaAcc and controlled by the
STARTACC and STOPACC inputs. If the integration is in progress, the output ACCINPRG is high.
Otherwise, it is low. Figure 241 shows the logic of the ACCINPRG output. ACCINPRG is active
when the STARTACC input is active and the EnaAcc setting is enabled. When the RSTACC input
is in the active state, the output ACCINPRG is low even if the integration of energy is enabled.
ACCINPRG is deactivated by activating the STOPACC input.

STOPACC

FALSE
STARTACC T
³1
& F ACCINPRG
EnaAcc &

q-1

RSTACC

q-1 = unit delay IEC13000186-4-en.vsd


IEC13000186 V4 EN-US

Figure 241: ACCINPRG Logic diagram


The accumulated energy values (in MWh and MVArh) are available as service values and also as
pulsed output depending on the ExxAccPlsQty setting, which can be connected to a pulse
counter. Accumulated energy outputs are available for forward as well as reverse direction.
The accumulated energy values can be reset to initial accumulated energy values (ExxPrestVal)
from the local HMI reset menu or with the input signal RSTACC. Figure 242 shows the logic for
integration of energy in active forward direction. Similarly, the integration of energy in active
reverse, reactive forward and reactive reverse is done.

436 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 12
Metering

RSTACC

EAFPrestVal

ACCINPRG

P* (ACTIVE FORWARD)
X
 T
T EAFACC
60.0
F
F

&

q-1

1000 GWh T
-1 F
q 0.0

a
a>b
b
-1
q = unit delay
IEC13000187-5-en.vsdx
IEC13000187 V5 EN-US

Figure 242: Logic for integration of active forward energy


The energy pulses generated by using internally calculated accumulated energy values and
energy per pulse (ExxAccPlsQty) setting. The accumulated energy values are divided by the
energy-per-pulse value to get the number of pulses. The number of pulses can be reset to zero
by activating RSTACC input or by using the local HMI reset menu. The pulse on and off time
duration is set by the settings tEnergyOnPls and tEnergyOffPls. Figure 243 shows the logic for
pulse output generation for the integrated energy in the active forward direction. Similarly, the
pulse generation for integrated energy in the active reverse, reactive forward and reactive
reverse is done.

tEnergyOffPls
EAFACC

a Counter q-1
a>b CU
1000 GWh b CV
Rst
tOff
t
R I q-1

0
÷ X
 R I T
EAFPULSE
a TP
a>b F
b
EAFAccPlsQty ÷ 0
Counter
CU
CV
RSTACC
Rst

q-1

tEnergyOnPls

q-1 = unit delay


IEC13000188-5-en.vsdx
IEC13000188 V5 EN-US

Figure 243: Logic for pulse generation of integrated active forward energy
The maximum demand values for active and reactive power are calculated for the set time
interval tEnergy. The maximum values are updated every minute and stored in a register

Breaker protection REQ650 437


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 12 1MRK 505 384-UEN C
Metering

available over communication and from outputs MAXPAFD, MAXPARD, MAXPRFD and MAXPRRD for
the active and reactive power forward and reverse direction. When the RSTDMD input is active
from the local HMI reset menu, these outputs are reset to zero. The energy alarm is activated
once the periodic energy value crosses the energy limit ExLim. Figure 244 shows the logic of
alarm for active forward energy exceeds limit and Maximum forward active power demand
value. Similarly, the maximum power calculation and energy alarm outputs in the active
reverse, reactive forward and reactive reverse is implemented.

P (ACTIVE FORWARD)
Average Power
X a EAFALM
tEnergy Calculation a>b
b

EALim

RSTMAXD

0.0 T MAXPAFD
MAX F

q-1
q-1 = unit delay
IEC13000189-4-en.vsd
IEC13000189 V4 EN-US

Figure 244: Logic for maximum power demand calculation and energy alarm

12.2.8 Technical data


SEMOD153707-2 v5

Table 377: ETPMMTR technical data


Function Range or value Accuracy
Energy metering kWh Export/Import, kvarh Input from MMXU. No extra error at steady
Export/Import load

438 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 13
Ethernet

Section 13 Ethernet
13.1 Access point

13.1.1 Introduction GUID-6E5D2696-A8EE-43E7-A94B-69C3D0612127 v2

An access point is an Ethernet communication interface for single or redundant station


communication. Each access point is allocated with one physical Ethernet port, two physical
Ethernet ports are allocated if redundant communication is activated for the access point.

Device 1 Device 1

AP1 AP2 AP3 AP1 AP2 AP3


SFP_301 SFP_302 SFP_303 SFP_301 SFP_302 SFP_303

IEC16000092-1-en.vsdx
IEC16000092 V1 EN-US

Figure 245: Access points, non redundant (left) and redundant communication (right)

13.1.2 Settings
MANUALPID-17001 v1

Table 378: AP_1 Non group settings (basic)


Name Values (Range) Unit Step Default Description
Redundancy None - - None Ethernet redundancy mode
PRP-0
PRP-1
HSR
IPAddress 0 - 18 IP 1 192.168.1.10 IP address of the access point
Address
SubnetMask 0 - 18 IP 1 255.255.255.0 Subnet mask of the access point
Address
Description 1 - 18 - 1 Station bus User editable access point description
[1-18 char]
PTP Off - - Off Precision time protocol
On
Slave only
PCM600Access Off - - On PCM600 access
On
FTP Off - - On FTP and FTPS access
On
MMS Off - - On IEC61850-8-1 MMS
On
GOOSE Off - - On IEC61850-8-1 GOOSE
On
SNTPServer Off - - On SNTP server
On
FSTAccess Off - - On Field Service Tool access
On
DefaultGateway 0 - 18 IP 1 0.0.0.0 Default gateway IP address
Address

Breaker protection REQ650 439


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 13 1MRK 505 384-UEN C
Ethernet

MANUALPID-17002 v1

Table 379: AP_FRONT Non group settings (basic)


Name Values (Range) Unit Step Default Description
IPAddress 0 - 18 IP 1 10.1.150.3 IP address of the access point
Address
SubnetMask 0 - 18 IP 1 255.255.255.0 Subnet mask of the access point
Address
Description 1 - 18 - 1 FrontPort User editable access point description
[1-18 char]
PCM600Access Off - - On PCM600 access
On
FTP Off - - On FTP and FTPS access
On
MMS Off - - On IEC61850-8-1 MMS
On
GOOSE Off - - On IEC61850-8-1 GOOSE
On
SNTPServer Off - - On SNTP Server
On
FSTAccess Off - - On Field Service Tool access
On
DefaultGateway 0 - 18 IP 1 0.0.0.0 Default gateway IP address
Address

13.2 Access point diagnostics

13.2.1 Functionality GUID-20F64A6D-AA8C-47D7-AA7D-4810996B2FF2 v2

The access point diagnostics function blocks (RCHLCCH, SCHLCCH and FRONTSTATUS)
supervise communication. SCHLCCH is used for communication over the rear Ethernet ports,
RCHLCCH is used for redundant communications over the rear Ethernet ports and
FRONTSTATUS is used for communication over the front port. All access point function blocks
include output signal for denial of service.

13.2.2 Function block GUID-727BF536-1D60-4060-A674-5D73F252CCB7 v2

SCHLCCH
LINKUP
DOSALARM

IEC16000044-1-en.vsdx
IEC16000044 V1 EN-US

Figure 246: SCHLCCH Function block

RCHLCCH
REDLINKA
REDLINKB
DOSALARM

IEC16000045-1-en.vsdx
IEC16000045 V1 EN-US

Figure 247: RCHLCCH Function block

440 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 13
Ethernet

13.2.3 Signals
PID-6818-OUTPUTSIGNALS v2

Table 380: SCHLCCH Output signals


Name Type Description
LINKUP BOOLEAN Access point link status
DOSALARM BOOLEAN Denial of service alarm

PID-6819-OUTPUTSIGNALS v2

Table 381: RCHLCCH Output signals


Name Type Description
REDLINKA BOOLEAN Channel A redundancy status
REDLINKB BOOLEAN Channel B redundancy status
DOSALARM BOOLEAN Denial of service alarm (A + B)

13.2.4 Monitored data


PID-6818-MONITOREDDATA v2

Table 382: SCHLCCH Monitored data


Name Type Values (Range) Unit Description
GatewayConfig INTEGER 0=Ok - Gateway configuration status
1=Error
-1=Off
2=Invalid

PID-6819-MONITOREDDATA v2

Table 383: RCHLCCH Monitored data


Name Type Values (Range) Unit Description
GatewayConfig INTEGER 0=Ok - Gateway configuration status
1=Error
-1=Off
2=Invalid

13.3 Redundant communication

13.3.1 Identification
GUID-B7AE0374-0336-42B8-90AF-3AE1C79A4116 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
IEC 62439-3 Parallel redundancy PRP - -
protocol
IEC 62439-3 High-availability HSR - -
seamless redundancy
Access point diagnostic for RCHLCCH - -
redundant Ethernet ports

Breaker protection REQ650 441


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 13 1MRK 505 384-UEN C
Ethernet

13.3.2 Functionality GUID-494FACF7-4BE0-4B9F-A18F-47CD1E92C0F9 v1

PRP IEC 62439-3 redundant communication


Redundant communication according to IEC 62439-3 PRP-0 and IEC 62439-3 PRP-1 parallel
redundancy protocol (PRP) is available as an option when ordering IEDs. PRP according to IEC
62439-3 uses two optical Ethernet ports.

IEC 62439-3 High-availabillity Seamless Redundancy (HSR)


Redundant station bus communication according to IEC 62439-3 Edition 1 and IEC 62439-3
Edition 2 High-availability seamless redundancy (HSR) is available as an option when ordering
IEDs. Redundant station bus communication according to 62439-3 uses two optical Ethernet
ports.

13.3.3 Operation principle GUID-73DB23CD-A924-4B89-8AAB-1E79D44DE429 v1

PRP IEC 62439-3 redundant communication


The communication is performed in parallel, that is the same data package is transmitted on
both channels simultaneously. The received package identity from one channel is compared
with data package identity from the other channel, if they are the same, the last package is
discarded.

The RCHLCCH function block supervise the redundant communication on the two channels. If
no data package has been received on one (or both) channels within the last 10 s, the output
LinkAUp and/or LinkBUp is set to 0 which indicates an error.

Device 1 Device 2

AP1 AP1
PhyPortA PhyPortB PhyPortA PhyPortB

Switch A Switch B

PhyPortA PhyPortB PhyPortA PhyPortB


AP1 AP1

Device 3 Device 4

IEC09000758-4-en.vsd
IEC09000758 V4 EN-US

Figure 248: Redundant station bus

442 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 13
Ethernet

IEC 62439-3 High-availabillity Seamless Redundancy (HSR)


HSR applies the principle of parallel operation to a single ring.

For each message sent, the node sends two frames, one through each port. Both the frames
circulate in opposite directions over the ring. Every node forwards the frames it receives from
one port to another to reach the next node. When the originating sender node receives the
frame it sent, the sender node discards the frame to avoid loops

The RCHLCCH function block supervise the redundant communication on the two channels. If
no data package has been received on one (or both) channels within the last 10 s, the output
LinkAUp and/or LinkBUp is set to 0 which indicates an error.

If IEEE1588 (PTP) is used an accuracy of 1 µs can be guaranteed for up to 15 devices in one


HSR-ring.

Device 1 Device 2

AP1 AP1
PhyPortA PhyPortB PhyPortA PhyPortB

PhyPortB PhyPortA PhyPortB PhyPortA


AP1 AP1

Device 3 Device 4

IEC16000038-1-en.vsdx
IEC16000038 V1 EN-US

Figure 249: HSR ring

13.4 Merging unit

13.4.1 Introduction GUID-E630C16F-EDB8-40AE-A8A2-94189982D15F v1

The IEC/UCA 61850-9-2LE process bus communication protocol enables an IED to


communicate with devices providing measured values in digital format, commonly known as
Merging Units (MU). The rear access points are used for the communication.

The merging units (MU) are called so because they can gather analog values from one or more
measuring transformers, sample the data and send the data over process bus to other clients
(or subscribers) in the system. Some merging units are able to get data from classical
measuring transformers, others from non-conventional measuring transducers and yet others
can pick up data from both types.

Breaker protection REQ650 443


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 13 1MRK 505 384-UEN C
Ethernet

13.4.2 Settings
PID-6770-SETTINGS v2

Table 384: MU1 Non group settings (basic)


Name Values (Range) Unit Step Default Description
SampleValueID 0 - 34 - 1 ABB_MU0101 Sample Value ID (SVID) for the
merging unit [0-34 char]
APConnection None - - None Access point connection for the
AP1 merging unit
AP2
AP3
AP4

PID-6850-SETTINGS v3

Table 385: MU1_HW Non group settings (basic)


Name Values (Range) Unit Step Default Description
CTStarPoint1 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTStarPoint2 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTStarPoint3 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTStarPoint4 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite

13.4.3 Monitored data


PID-6850-MONITOREDDATA v3

Table 386: MU1_HW Monitored data


Name Type Values (Range) Unit Description
MUDATA BOOLEAN 0=Ok - Fatal error, data not received,
1=Error transmission errors, time-sync issues
or inconsistent sample rate
SYNCH BOOLEAN 0=Ok - High when IED clock is not within
1=Error configured accuracy or time domain
SMPLLOST BOOLEAN 1=Yes - Fatal error or recovery state after fatal
0=No error. High if any subscribed channel
has bad quality or TEST while IED not
in test mode.
MUSYNCH BOOLEAN 0=Ok - MU not synced or MU clock not synced
1=Error to same clock as IED
TESTMODE BOOLEAN 1=Yes - Quality of one or more subscribed
0=No analogue channels is TEST
SIMMODE BOOLEAN 1=Yes - MU delivers simulated data accepted
0=No by IED
BadReference BOOLEAN 1=Yes - BadReference indication output for I1
0=No
Derived BOOLEAN 1=Yes - Derived indication output for I1
0=No
Failure BOOLEAN 1=Yes - Failure indication output for I1
0=No
Table continues on next page

444 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 13
Ethernet

Name Type Values (Range) Unit Description


Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for I1
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for I1
0=No
OldData BOOLEAN 1=Yes - OldData indication output for I1
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No I1
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for I1
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for I1
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for I1
0=No
Source BOOLEAN 0=Process - Source indication output for I1
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for I1
0=No
Validity INTEGER 0=Good - Validity indication output I1
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for I2
0=No
Derived BOOLEAN 1=Yes - Derived indication output for I2
0=No
Failure BOOLEAN 1=Yes - Failure indication output for I2
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for I2
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for I2
0=No
OldData BOOLEAN 1=Yes - OldData indication output for I2
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No I2
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for I2
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for I2
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for I2
0=No
Source BOOLEAN 0=Process - Source indication output for I2
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for I2
0=No
Validity INTEGER 0=Good - Validity indication output I2
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for I3
0=No
Table continues on next page

Breaker protection REQ650 445


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 13 1MRK 505 384-UEN C
Ethernet

Name Type Values (Range) Unit Description


Derived BOOLEAN 1=Yes - Derived indication output for I3
0=No
Failure BOOLEAN 1=Yes - Failure indication output for I3
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for I3
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for I3
0=No
OldData BOOLEAN 1=Yes - OldData indication output for I3
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No I3
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for I3
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for I3
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for I3
0=No
Source BOOLEAN 0=Process - Source indication output for I3
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for I3
0=No
Validity INTEGER 0=Good - Validity indication output I3
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for I4
0=No
Derived BOOLEAN 1=Yes - Derived indication output for I4
0=No
Failure BOOLEAN 1=Yes - Failure indication output for I4
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for I4
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for I4
0=No
OldData BOOLEAN 1=Yes - OldData indication output for I4
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No I4
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for I4
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for I4
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for I4
0=No
Source BOOLEAN 0=Process - Source indication output for I4
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for I4
0=No
Table continues on next page

446 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 13
Ethernet

Name Type Values (Range) Unit Description


Validity INTEGER 0=Good - Validity indication output I4
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for U1
0=No
Derived BOOLEAN 1=Yes - Derived indication output for U1
0=No
Failure BOOLEAN 1=Yes - Failure indication output for U1
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for U1
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for U1
0=No
OldData BOOLEAN 1=Yes - OldData indication output for U1
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No U1
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for U1
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for U1
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for U1
0=No
Source BOOLEAN 0=Process - Source indication output for U1
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for U1
0=No
Validity INTEGER 0=Good - Validity indication output U1
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for U2
0=No
Derived BOOLEAN 1=Yes - Derived indication output for U2
0=No
Failure BOOLEAN 1=Yes - Failure indication output for U2
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for U2
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for U2
0=No
OldData BOOLEAN 1=Yes - OldData indication output for U2
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No U2
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for U2
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for U2
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for U2
0=No
Table continues on next page

Breaker protection REQ650 447


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 13 1MRK 505 384-UEN C
Ethernet

Name Type Values (Range) Unit Description


Source BOOLEAN 0=Process - Source indication output for U2
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for U2
0=No
Validity INTEGER 0=Good - Validity indication output U2
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for U3
0=No
Derived BOOLEAN 1=Yes - Derived indication output for U3
0=No
Failure BOOLEAN 1=Yes - Failure indication output for U3
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for U3
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for U3
0=No
OldData BOOLEAN 1=Yes - OldData indication output for U3
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No U3
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for U3
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for U3
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for U3
0=No
Source BOOLEAN 0=Process - Source indication output for U3
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for U3
0=No
Validity INTEGER 0=Good - Validity indication output U3
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for
0=No U4
Derived BOOLEAN 1=Yes - Derived indication output for U4
0=No
Failure BOOLEAN 1=Yes - Failure indication output for U4
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for U4
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for U4
0=No
OldData BOOLEAN 1=Yes - OldData indication output for U4
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No U4
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for U4
0=No
Table continues on next page

448 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 13
Ethernet

Name Type Values (Range) Unit Description


OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for U4
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for U4
0=No
Source BOOLEAN 0=Process - Source indication output for U4
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for U4
0=No
Validity INTEGER 0=Good - Validity indication output U4
2=Reserved
1=Invalid
3=Questionable

13.5 Routes

13.5.1 Introduction GUID-95F9C7BA-92F8-489F-AD0A-047410B5E66F v1

A route is a specified path for data to travel between the source device in a subnetwork to the
destination device in a different subnetwork. A route consists of a destination address and the
address of the gateway to be used when sending data to the destination device, see Figure
250.

Default gateway

Gateway

Source Destination
IEC16000095-1-en.vsdx
IEC16000095 V1 EN-US

Figure 250: Route from source to destination through gateway

Breaker protection REQ650 449


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 13 1MRK 505 384-UEN C
Ethernet

13.5.2 Settings
PID-6761-SETTINGS v2

Table 387: ROUTE_1 Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation on/off of the route
On
IPAddress 0 - 18 IP 1 0.0.0.0 IP address of the gateway
Address
DestIPAddress 0 - 18 IP 1 0.0.0.0 Destination IP address
Address
DestSubnetMask 0 - 18 IP 1 255.255.255.255 Destination IP subnet mask
Address
Name 1 - 18 - 1 Route1 User configurable name of the route
[1-18 char]

13.5.3 Monitored data


PID-6761-MONITOREDDATA v2

Table 388: ROUTE_1 Monitored data


Name Type Values (Range) Unit Description
RouteConfig INTEGER 0=Ok - Route configuration status
1=Error
-1=Off

450 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

Section 14 Station communication


14.1 Communication protocols M14815-3 v14

Each IED is provided with several communication interfaces enabling it to connect to one or
many substation level systems or equipment, either on the Substation Automation (SA) bus or
Substation Monitoring (SM) bus.

Available communication protocols are:

• IEC 61850-8-1 communication protocol


• IEC/UCA 61850-9-2LE communication protocol
• LON communication protocol
• SPA communication protocol
• IEC 60870-5-103 communication protocol

Several protocols can be combined in the same IED.

14.2 Communication protocol diagnostics GUID-6BC4671F-6D06-4BBD-B1FF-2F03FF16A856 v1

Status of the protocols can be viewed in the LHMI under Main menu/Diagnostics/IED status/
Protocol diagnostics. The diagnostic values are:

Diagnostic value Description


Off Protocol is turned off
Error An error has occured, refer to event list for more
information
Warning Configuration inconsistency. Unable to locate data
point.
Ready Protocol is ready

Breaker protection REQ650 451


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

IEC15000400-1-en.vsd
IEC15000400 V1 EN-US

Figure 251: Protocol diagnostic screen in LHMI

14.3 DNP3 protocol GUID-54A54716-23BD-4E7C-8245-DE2B4C75E8DC v1

DNP3 (Distributed Network Protocol) is a set of communications protocols used to


communicate data between components in process automation systems. For a detailed
description of the DNP3 protocol, see the DNP3 Communication protocol manual.

14.4 IEC 61850-8-1 communication protocol IP14616-1 v2

14.4.1 Functionality M14787-3 v16

IEC 61850 Ed.1 or Ed.2 can be chosen by a setting in PCM600. The IED is equipped with four
optical Ethernet rear ports for IEC 61850-8-1 station bus communication.The IEC 61850-8-1
communication is also possible from the electrical Ethernet front port. IEC 61850-8-1 protocol
allows intelligent electrical devices (IEDs) from different vendors to exchange information and
simplifies system engineering. IED-to-IED communication using GOOSE and client-server
communication over MMS are supported. Disturbance recording file (COMTRADE) uploading
can be done over MMS or FTP.

The front port is only intended for PCM600 communication, maintenance,


training and test purposes due to risk of interference during normal operation.

452 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

14.4.2 Communication interfaces and protocols GUID-35C845D3-574A-40D1-AEF1-9E0D330E31DE v9

Table 389: Supported station communication interfaces and protocols


Protocol Ethernet Serial
100BASE-FX (ST connector) Glass fiber (ST connector) EIA-485
IEC 61850–8–1 ● - -
DNP3 ● ● ●
IEC 60870-5-103 - ● ●
● = Supported

14.4.3 Settings
PID-6702-SETTINGS v3

Table 390: IEC61850-8-1 Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On
GOOSEPortEd1 AP_FRONT - - AP_1 Selection of GOOSE port (only for
AP_1 IEC61850 Ed1)
AP_2
AP_3
AP_4
AP_5
AP_6
ProtocolEdition Ed 1 - - Ed 1 Protocol Edition
Ed 2
RemModControl Off - - Off Remote Mode Control
Maintenance
All levels
AllowSimulation No - - No Allow simulated GOOSE values or
Yes simulated sampled measurand values
RemSetControlEd2 Disabled - - Disabled Changing settings over 61850 enabled
Enabled (only for IEC61850 Ed2)
ResvTmsEd2 1 - 3600 s 1 60 Reservation time (only for IEC61850
Ed2)

14.4.4 Technical data IP14434-1 v1

M15031-1 v9

Table 391: Communication protocols


Function Value
Protocol IEC 61850-8-1
Communication speed for the IEDs 100BASE-FX
Protocol IEC 60870–5–103
Communication speed for the IEDs 9600 or 19200 Bd
Protocol DNP3.0
Communication speed for the IEDs 300–115200 Bd
Protocol TCP/IP, Ethernet
Table continues on next page

Breaker protection REQ650 453


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

Function Value
Communication speed for the IEDs 100 Mbit/s
Protocol LON
Communication speed for the IEDs 1.25 Mbit/s
Protocol SPA
Communication speed for the IEDs 300–38400 Bd

14.4.5 Generic communication function for Single Point indication


SPGAPC, SP16GAPC SEMOD55999-1 v4

14.4.5.1 Functionality SEMOD55713-5 v8

Generic communication function for Single Point indication (SPGAPC) is used to send one
single logical signal to other systems or equipment in the substation.

14.4.5.2 Function block SEMOD54714-4 v4

SPGAPC
BLOCK
^IN

IEC14000021-1-en.vsd
IEC14000021 V1 EN-US

Figure 252: SPGAPC function block

SP16GAPC
BLOCK
^IN1
^IN2
^IN3
^IN4
^IN5
^IN6
^IN7
^IN8
^IN9
^IN10
^IN11
^IN12
^IN13
^IN14
^IN15
^IN16

IEC14000020-1-en.vsd
IEC14000020 V1 EN-US

Figure 253: SP16GAPC function block

14.4.5.3 Signals SEMOD55830-1 v2

PID-3780-INPUTSIGNALS v6

Table 392: SPGAPC Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
IN BOOLEAN 0 Input status

454 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

PID-3781-INPUTSIGNALS v6

Table 393: SP16GAPC Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
IN1 BOOLEAN 0 Input 1 status
IN2 BOOLEAN 0 Input 2 status
IN3 BOOLEAN 0 Input 3 status
IN4 BOOLEAN 0 Input 4 status
IN5 BOOLEAN 0 Input 5 status
IN6 BOOLEAN 0 Input 6 status
IN7 BOOLEAN 0 Input 7 status
IN8 BOOLEAN 0 Input 8 status
IN9 BOOLEAN 0 Input 9 status
IN10 BOOLEAN 0 Input 10 status
IN11 BOOLEAN 0 Input 11 status
IN12 BOOLEAN 0 Input 12 status
IN13 BOOLEAN 0 Input 13 status
IN14 BOOLEAN 0 Input 14 status
IN15 BOOLEAN 0 Input 15 status
IN16 BOOLEAN 0 Input 16 status

14.4.5.4 Settings ABBD8E283673 v4

The function does not have any parameters available in the local HMI or PCM600.

14.4.5.5 Monitored data


PID-3780-MONITOREDDATA v3

Table 394: SPGAPC Monitored data


Name Type Values (Range) Unit Description
OUT GROUP - - Output status
SIGNAL

PID-3781-MONITOREDDATA v3

Table 395: SP16GAPC Monitored data


Name Type Values (Range) Unit Description
OUT1 GROUP - - Output 1 status
SIGNAL
OUT2 GROUP - - Output 2 status
SIGNAL
OUT3 GROUP - - Output 3 status
SIGNAL
OUT4 GROUP - - Output 4 status
SIGNAL
OUT5 GROUP - - Output 5 status
SIGNAL
Table continues on next page

Breaker protection REQ650 455


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

Name Type Values (Range) Unit Description


OUT6 GROUP - - Output 6 status
SIGNAL
OUT7 GROUP - - Output 7 status
SIGNAL
OUT8 GROUP - - Output 8 status
SIGNAL
OUT9 GROUP - - Output 9 status
SIGNAL
OUT10 GROUP - - Output 10 status
SIGNAL
OUT11 GROUP - - Output 11 status
SIGNAL
OUT12 GROUP - - Output 12 status
SIGNAL
OUT13 GROUP - - Output 13 status
SIGNAL
OUT14 GROUP - - Output 14 status
SIGNAL
OUT15 GROUP - - Output 15 status
SIGNAL
OUT16 GROUP - - Output 16 status
SIGNAL
OUTOR GROUP - - Output status logic OR gate for input
SIGNAL 1 to 16

14.4.5.6 Operation principle SEMOD55725-5 v8

Upon receiving a signal at its input, Generic communication function for Single Point
indication (SPGAPC) function sends the signal over IEC 61850-8-1 to the equipment or system
that requests this signal. Additional configuration is needed with PCM600 or IET600 to get the
IEC 61850-8-1 communication established. For more information, refer to the Engineering
manual.

14.4.6 Generic communication function for Measured Value MVGAPC SEMOD55402-1 v3

14.4.6.1 Functionality SEMOD55872-5 v10

Generic communication function for measured values (MVGAPC) function is used to send the
instantaneous value of an analog signal to other systems or equipment in the substation. It
can also be used inside the same IED, to attach a RANGE aspect to an analog value and to
permit measurement supervision on that value.

14.4.6.2 Function block SEMOD54712-4 v4

MVGAPC
BLOCK ^VALUE
^IN RANGE

IEC14000022-1-en.vsd
IEC14000022 V1 EN-US

Figure 254: MVGAPC function block

456 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

14.4.6.3 Signals SEMOD55948-1 v2

PID-6753-INPUTSIGNALS v1

Table 396: MVGAPC Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
IN REAL 0 Analog input value

PID-6753-OUTPUTSIGNALS v1

Table 397: MVGAPC Output signals


Name Type Description
VALUE REAL Magnitude of deadband value
RANGE INTEGER Range

14.4.6.4 Settings SEMOD55954-1 v2

PID-6753-SETTINGS v1

Table 398: MVGAPC Non group settings (basic)


Name Values (Range) Unit Step Default Description
BasePrefix micro - - unit Base prefix (multiplication factor)
milli
unit
kilo
Mega
Giga
Tera
MV db 1 - 100000 Type 1 10000 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
MV zeroDb 0 - 100000 m% 500 1000 Zero point clamping in 0,001% of
range
MV hhLim -5000.00 - xBase 0.01 900.00 High High limit multiplied with the
5000.00 base prefix (multiplication factor)
MV hLim -5000.00 - xBase 0.01 800.00 High limit multiplied with the base
5000.00 prefix (multiplication factor)
MV lLim -5000.00 - xBase 0.01 -800.00 Low limit multiplied with the base
5000.00 prefix (multiplication factor)
MV llLim -5000.00 - xBase 0.01 -900.00 Low Low limit multiplied with the
5000.00 base prefix (multiplication factor)
MV min -5000.00 - xBase 0.01 -1000.00 Minimum value multiplied with the
5000.00 base prefix (multiplication factor)
MV max -5000.00 - xBase 0.01 1000.00 Maximum value multiplied with the
5000.00 base prefix (multiplication factor)
MV dbType Cyclic - - Deadband Reporting type
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
MV limHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range
(common for all limits)

Breaker protection REQ650 457


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

14.4.6.5 Monitored data


PID-6753-MONITOREDDATA v1

Table 399: MVGAPC Monitored data


Name Type Values (Range) Unit Description
VALUE REAL - - Magnitude of deadband value
RANGE INTEGER 1=High - Range
2=Low
3=High-High
4=Low-Low
0=Normal

14.4.6.6 Operation principle SEMOD55936-5 v7

Upon receiving an analog signal at its input, Generic communication function for Measured
Value (MVGAPC) will give the instantaneous value of the signal and the range, as output values.
Additional configuration is needed with PCM600 or IET600 to get the IEC 61850-8-1
communication established. For more information see the Engineering manual.

14.4.7 GOOSE function block to receive a double point value


GOOSEDPRCV

14.4.7.1 Identification
GUID-8C11DB9A-7844-4E1F-A6BB-D97ECE350FC1 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
GOOSE function block to receive a GOOSEDPRCV - -
double point value

14.4.7.2 Functionality GUID-1D2DBC22-4F04-4809-B34E-8939D442C185 v3

GOOSEDPRCV is used to receive a double point value using IEC 61850 protocol via GOOSE.

14.4.7.3 Function block GUID-ED277880-FB5D-4630-872F-9F343D449FFE v1

GOOSEDPRCV
BLOCK ^DPOUT
^SRCDPOUT DATAVALID
COMMVALID
TEST

IEC10000249-2-en.vsdx
IEC10000249 V2 EN-US

Figure 255: GOOSEDPRCV function block

458 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

14.4.7.4 Signals
GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1

Except for the BLOCK input, the rest of the inputs of this GOOSE function block
are used for GOOSE connections. These connections are visible and possible to
make only if Easy GOOSE engineering is enabled. For instructions on how to
enable Easy GOOSE engineering in PCM600, refer to the Engineering Manual.

PID-6828-INPUTSIGNALS v3

Table 400: GOOSEDPRCV Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
SRCDPOUT INTEGER 0 Source to double point output

PID-6828-OUTPUTSIGNALS v3

Table 401: GOOSEDPRCV Output signals


Name Type Description
DPOUT INTEGER Double point output
DATAVALID BOOLEAN Data valid for double point output
COMMVALID BOOLEAN Communication valid for double point output
TEST BOOLEAN Test output

14.4.7.5 Settings
PID-6828-SETTINGS v3

Table 402: GOOSEDPRCV Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On

14.4.7.6 Operation principle GUID-82A1C8A2-827A-40EF-8E58-F573E29E468E v4

The DATAVALID output will be HIGH if the incoming message is with valid data.

The COMMVALID output will become LOW when the sending IED is under total failure
condition and the GOOSE transmission from the sending IED does not happen.

The TEST output will go HIGH if the sending IED is in test mode.

Data Value Data Valid Comm Valid Test


Incoming data with q=Normal Updated 1 1 0
Incoming data with q=oldData 0 0 1 0
Incoming data with q=Invalid 0 0 1 0
Incoming data with q=test 0 0 1 1
Incoming data with q=test+oldData 0 0 1 1

Receiver in block 0 0 1 0
Table continues on next page

Breaker protection REQ650 459


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

Data Value Data Valid Comm Valid Test


Receiver in block and communication 0 0 0 0
error
Receiver in test mode and incoming Updated 1 1 0
data with q= Normal
Receiver in test mode and incoming Updated 1 1 1
data with q= Test
Communication Error 0 0 0 0

The input of this GOOSE block must be linked either in SMT by means of a cross
or in ACT by means of a GOOSE connection (if easy GOOSE engineering is
enabled) to receive the double point values.

The implementation for IEC 61850 quality data handling is restricted to a


simple level. If quality data validity is GOOD then the DATAVALID output will be
HIGH. If quality data validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE
or OLD DATA then the DATAVALID output will be LOW.

14.4.8 GOOSE function block to receive an integer value


GOOSEINTRCV

14.4.8.1 Identification
GUID-93A1E81B-1DE8-483A-BB3B-DB771EE66DC1 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
GOOSE function block to receive an GOOSEINTRCV - -
integer value

14.4.8.2 Functionality GUID-27B1ED7A-C8E8-499E-89C1-C656FB0337F8 v3

GOOSEINTRCV is used to receive an integer value using IEC 61850 protocol via GOOSE.

14.4.8.3 Function block GUID-56F0C9F7-98F3-4091-B071-53CA5074DC8F v1

GOOSEINTRCV
BLOCK ^INTOUT
^SRCINTOUT DATAVALID
COMMVALID
TEST
IEC10000250-2-en.vsd
IEC10000250 V2 EN-US

Figure 256: GOOSEINTRCV function block

460 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

14.4.8.4 Signals
GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1

Except for the BLOCK input, the rest of the inputs of this GOOSE function block
are used for GOOSE connections. These connections are visible and possible to
make only if Easy GOOSE engineering is enabled. For instructions on how to
enable Easy GOOSE engineering in PCM600, refer to the Engineering Manual.

PID-6829-INPUTSIGNALS v3

Table 403: GOOSEINTRCV Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
SRCINTOUT INTEGER 0 Source to integer output

PID-6829-OUTPUTSIGNALS v3

Table 404: GOOSEINTRCV Output signals


Name Type Description
INTOUT INTEGER Integer output
DATAVALID BOOLEAN Data valid for integer output
COMMVALID BOOLEAN Communication valid for integer output
TEST BOOLEAN Test output

14.4.8.5 Settings
PID-6829-SETTINGS v3

Table 405: GOOSEINTRCV Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On

14.4.8.6 Operation principle GUID-5BBDF772-3B3E-4F7C-ABE9-18CE3C1A2E2D v4

The DATAVALID output will be HIGH if the incoming message is with valid data.

The COMMVALID output will become LOW when the sending IED is under total failure
condition and the GOOSE transmission from the sending IED does not happen.

The TEST output will go HIGH if the sending IED is in test mode.

Data Value Data Valid Comm Valid Test


Incoming data with q=Normal Updated 1 1 0
Incoming data with q=oldData Freeze 0 1 0
Incoming data with q=Invalid Freeze 0 1 0
Incoming data with q=test Freeze 0 1 1
Incoming data with q=test+oldData Freeze 0 1 1

Receiver in block Freeze 0 1 0


Table continues on next page

Breaker protection REQ650 461


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

Data Value Data Valid Comm Valid Test


Receiver in block and communication error Freeze 0 0 0
Receiver in test mode and incoming data Updated 1 1 0
with q= Normal
Receiver in test mode and incoming data Updated 1 1 1
with q= Test
Communication Error Freeze 0 0 0

The input of this GOOSE block must be linked either in SMT by means of a cross
or in ACT by means of a GOOSE connection (if easy GOOSE engineering is
enabled) to receive the integer values.

The implementation for IEC 61850 quality data handling is restricted to a


simple level. If quality data validity is GOOD then the DATAVALID output will be
HIGH. If quality data validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE
or OLD DATA then the DATAVALID output will be LOW.

14.4.9 GOOSE function block to receive a measurand value


GOOSEMVRCV

14.4.9.1 Identification
GUID-B1FFBE08-C823-4A58-9FE0-A9A20DA6BB44 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
GOOSE function block to receive a GOOSEMVRCV - -
measurand value

14.4.9.2 Functionality GUID-759CB016-2B4D-4D98-82E1-592044983D53 v3

GOOSEMVRCV is used to receive measured value using IEC 61850 protocol via GOOSE.

14.4.9.3 Function block GUID-A0B333CC-AEF4-40EA-B152-364648AB78D3 v1

GOOSEMVRCV
BLOCK ^MVOUT
^SRCMVOUT DATAVALID
COMMVALID
TEST
IEC10000251-2-en.vsd
IEC10000251 V2 EN-US

Figure 257: GOOSEMVRCV function block

462 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

14.4.9.4 Signals
GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1

Except for the BLOCK input, the rest of the inputs of this GOOSE function block
are used for GOOSE connections. These connections are visible and possible to
make only if Easy GOOSE engineering is enabled. For instructions on how to
enable Easy GOOSE engineering in PCM600, refer to the Engineering Manual.

PID-6830-INPUTSIGNALS v3

Table 406: GOOSEMVRCV Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
SRCMVOUT REAL 0 Source to measurand value output

PID-6830-OUTPUTSIGNALS v3

Table 407: GOOSEMVRCV Output signals


Name Type Description
MVOUT REAL Measurand value output
DATAVALID BOOLEAN Data valid for measurand value output
COMMVALID BOOLEAN Communication valid for measurand value output
TEST BOOLEAN Test output

14.4.9.5 Settings
PID-6830-SETTINGS v3

Table 408: GOOSEMVRCV Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On

14.4.9.6 Operation principle GUID-7B24A6D3-2E5F-4961-A0A6-86436373809E v5

The DATAVALID output will be HIGH if the incoming message is with valid data.

The COMMVALID output will become LOW when the sending IED is under total failure
condition and the GOOSE transmission from the sending IED does not happen.

The TEST output will go HIGH if the sending IED is in test mode.

Data Value Data Valid Comm Valid Test


Incoming data with q=Normal Updated 1 1 0
Incoming data with q=oldData Freeze 0 1 0
Incoming data with q=Invalid Freeze 0 1 0
Incoming data with q=test Freeze 0 1 1
Incoming data with q=test+oldData Freeze 0 1 1

Receiver in block Freeze 0 1 0


Table continues on next page

Breaker protection REQ650 463


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

Data Value Data Valid Comm Valid Test


Receiver in block and communication error Freeze 0 0 0
Receiver in test mode and incoming data Updated 1 1 0
with q= Normal
Receiver in test mode and incoming data Updated 1 1 1
with q= Test
Communication Error Freeze 0 0 0

The input of this GOOSE block must be linked either in SMT by means of a cross
or in ACT by means of a GOOSE connection (in case easy GOOSE engineering is
enabled) to receive the measured value.

The implementation for IEC 61850 quality data handling is restricted to a


simple level. If quality data validity is GOOD then the DATAVALID output will be
HIGH. If quality data validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE
or OLD DATA then the DATAVALID output will be LOW.

14.4.10 GOOSE function block to receive a single point value


GOOSESPRCV

14.4.10.1 Identification
GUID-F2B30A70-842E-435E-8FAB-B1E58B9C0164 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
GOOSE function block to receive a GOOSESPRCV - -
single point value

14.4.10.2 Functionality GUID-0C99A106-C131-45D3-9B81-6B188E35EB34 v3

GOOSESPRCV is used to receive a single point value using IEC 61850 protocol via GOOSE.

14.4.10.3 Function block GUID-A414F31A-323F-4684-BADA-46F9C5E2B0E8 v1

GOOSESPRCV
BLOCK ^SPOUT
^SRCSPOUT DATAVALID
COMMVALID
TEST
IEC10000248-2-en.vsd
IEC10000248 V2 EN-US

Figure 258: GOOSESPRCV function block

464 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

14.4.10.4 Signals
GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1

Except for the BLOCK input, the rest of the inputs of this GOOSE function block
are used for GOOSE connections. These connections are visible and possible to
make only if Easy GOOSE engineering is enabled. For instructions on how to
enable Easy GOOSE engineering in PCM600, refer to the Engineering Manual.

PID-6832-INPUTSIGNALS v3

Table 409: GOOSESPRCV Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
SRCSPOUT BOOLEAN 0 Source to single point output

PID-6832-OUTPUTSIGNALS v3

Table 410: GOOSESPRCV Output signals


Name Type Description
SPOUT BOOLEAN Single point output
DATAVALID BOOLEAN Data valid for single point output
COMMVALID BOOLEAN Communication valid for single point output
TEST BOOLEAN Test output

14.4.10.5 Settings
PID-6832-SETTINGS v3

Table 411: GOOSESPRCV Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On

14.4.10.6 Operation principle GUID-0E25A3FB-41BD-4EFE-9CA0-1262B9CD14CD v4

The DATAVALID output will be HIGH if the incoming message is with valid data.

The COMMVALID output will become LOW when the sending IED is under total failure
condition and the GOOSE transmission from the sending IED does not happen.

The TEST output will go HIGH if the sending IED is in test mode.

Data Value Data Valid Comm Valid Test


Incoming data with q=Normal Updated 1 1 0
Incoming data with q=oldData 0 0 1 0
Incoming data with q=Invalid 0 0 1 0
Incoming data with q=test 0 0 1 1
Incoming data with q=test+oldData 0 0 1 1

Receiver in block 0 0 1 0
Table continues on next page

Breaker protection REQ650 465


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

Data Value Data Valid Comm Valid Test


Receiver in block and communication 0 0 0 0
error
Receiver in test mode and incoming Updated 1 1 0
data with q= Normal
Receiver in test mode and incoming Updated 1 1 1
data with q= Test
Communication Error 0 0 0 0

The input of this GOOSE block must be linked either in SMT by means of a cross
or in ACT by means of a GOOSE connection (if easy GOOSE engineering is
enabled) to receive the binary single point values.

The implementation for IEC 61850 quality data handling is restricted to a


simple level. If quality data validity is GOOD then the DATAVALID output will be
HIGH. If quality data validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE
or OLD DATA then the DATAVALID output will be LOW.

14.4.11 Horizontal communication via GOOSE for interlocking


GOOSEINTLKRCV SEMOD173197-1 v2

14.4.11.1 Functionality GUID-92ECE152-892C-4214-95DE-B92718689434 v2

GOOSE communication can be used for exchanging information between IEDs via the IEC
61850-8-1 station communication bus. This is typically used for sending apparatus position
indications for interlocking or reservation signals for 1-of-n control. GOOSE can also be used to
exchange any boolean, integer, double point and analog measured values between IEDs.

466 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

14.4.11.2 Function block SEMOD173210-4 v5

GOOSEINTLKRCV
BLOCK ^RESREQ
^SRCRESREQ ^RESGRANT
^SRCRESGR ^APP1_OP
^SRCAPP1 ^APP1_CL
^SRCAPP2 APP1VAL
^SRCAPP3 ^APP2_OP
^SRCAPP4 ^APP2_CL
^SRCAPP5 APP2VAL
^SRCAPP6 ^APP3_OP
^SRCAPP7 ^APP3_CL
^SRCAPP8 APP3VAL
^SRCAPP9 ^APP4_OP
^SRCAPP10 ^APP4_CL
^SRCAPP11 APP4VAL
^SRCAPP12 ^APP5_OP
^SRCAPP13 ^APP5_CL
^SRCAPP14 APP5VAL
^SRCAPP15 ^APP6_OP
^APP6_CL
APP6VAL
^APP7_OP
^APP7_CL
APP7VAL
^APP8_OP
^APP8_CL
APP8VAL
^APP9_OP
^APP9_CL
APP9VAL
^APP10_OP
^APP10_CL
APP10VAL
^APP11_OP
^APP11_CL
APP11VAL
^APP12_OP
^APP12_CL
APP12VAL
^APP13_OP
^APP13_CL
APP13VAL
^APP14_OP
^APP14_CL
APP14VAL
^APP15_OP
^APP15_CL
APP15VAL
COMMVALID
TEST
IEC07000048-4-en.vsd
IEC07000048 V4 EN-US

Figure 259: GOOSEINTLKRCV function block

14.4.11.3 Signals SEMOD173205-1 v2

GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1

Except for the BLOCK input, the rest of the inputs of this GOOSE function block
are used for GOOSE connections. These connections are visible and possible to
make only if Easy GOOSE engineering is enabled. For instructions on how to
enable Easy GOOSE engineering in PCM600, refer to the Engineering Manual.

PID-6831-INPUTSIGNALS v3

Table 412: GOOSEINTLKRCV Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of output signals
SRCRESREQ BOOLEAN 0 Source to reservation request
SRCRESGR BOOLEAN 0 Source to reservation granted
Table continues on next page

Breaker protection REQ650 467


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

Name Type Default Description


SRCAPP1 INTEGER 0 Source to apparatus 1 position
SRCAPP2 INTEGER 0 Source to apparatus 2 position
SRCAPP3 INTEGER 0 Source to apparatus 3 position
SRCAPP4 INTEGER 0 Source to apparatus 4 position
SRCAPP5 INTEGER 0 Source to apparatus 5 position
SRCAPP6 INTEGER 0 Source to apparatus 6 position
SRCAPP7 INTEGER 0 Source to apparatus 7 position
SRCAPP8 INTEGER 0 Source to apparatus 8 position
SRCAPP9 INTEGER 0 Source to apparatus 9 position
SRCAPP10 INTEGER 0 Source to apparatus 10 position
SRCAPP11 INTEGER 0 Source to apparatus 11 position
SRCAPP12 INTEGER 0 Source to apparatus 12 position
SRCAPP13 INTEGER 0 Source to apparatus 13 position
SRCAPP14 INTEGER 0 Source to apparatus 14 position
SRCAPP15 INTEGER 0 Source to apparatus 15 position

PID-6831-OUTPUTSIGNALS v3

Table 413: GOOSEINTLKRCV Output signals


Name Type Description
RESREQ BOOLEAN Reservation request
RESGRANT BOOLEAN Reservation granted
APP1_OP BOOLEAN Apparatus 1 position is open
APP1_CL BOOLEAN Apparatus 1 position is closed
APP1VAL BOOLEAN Apparatus 1 position is valid
APP2_OP BOOLEAN Apparatus 2 position is open
APP2_CL BOOLEAN Apparatus 2 position is closed
APP2VAL BOOLEAN Apparatus 2 position is valid
APP3_OP BOOLEAN Apparatus 3 position is open
APP3_CL BOOLEAN Apparatus 3 position is closed
APP3VAL BOOLEAN Apparatus 3 position is valid
APP4_OP BOOLEAN Apparatus 4 position is open
APP4_CL BOOLEAN Apparatus 4 position is closed
APP4VAL BOOLEAN Apparatus 4 position is valid
APP5_OP BOOLEAN Apparatus 5 position is open
APP5_CL BOOLEAN Apparatus 5 position is closed
APP5VAL BOOLEAN Apparatus 5 position is valid
APP6_OP BOOLEAN Apparatus 6 position is open
APP6_CL BOOLEAN Apparatus 6 position is closed
APP6VAL BOOLEAN Apparatus 6 position is valid
APP7_OP BOOLEAN Apparatus 7 position is open
APP7_CL BOOLEAN Apparatus 7 position is closed
APP7VAL BOOLEAN Apparatus 7 position is valid
Table continues on next page

468 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

Name Type Description


APP8_OP BOOLEAN Apparatus 8 position is open
APP8_CL BOOLEAN Apparatus 8 position is closed
APP8VAL BOOLEAN Apparatus 8 position is valid
APP9_OP BOOLEAN Apparatus 9 position is open
APP9_CL BOOLEAN Apparatus 9 position is closed
APP9VAL BOOLEAN Apparatus 9 position is valid
APP10_OP BOOLEAN Apparatus 10 position is open
APP10_CL BOOLEAN Apparatus 10 position is closed
APP10VAL BOOLEAN Apparatus 10 position is valid
APP11_OP BOOLEAN Apparatus 11 position is open
APP11_CL BOOLEAN Apparatus 11 position is closed
APP11VAL BOOLEAN Apparatus 11 position is valid
APP12_OP BOOLEAN Apparatus 12 position is open
APP12_CL BOOLEAN Apparatus 12 position is closed
APP12VAL BOOLEAN Apparatus 12 position is valid
APP13_OP BOOLEAN Apparatus 13 position is open
APP13_CL BOOLEAN Apparatus 13 position is closed
APP13VAL BOOLEAN Apparatus 13 position is valid
APP14_OP BOOLEAN Apparatus 14 position is open
APP14_CL BOOLEAN Apparatus 14 position is closed
APP14VAL BOOLEAN Apparatus 14 position is valid
APP15_OP BOOLEAN Apparatus 15 position is open
APP15_CL BOOLEAN Apparatus 15 position is closed
APP15VAL BOOLEAN Apparatus 15 position is valid
COMMVALID BOOLEAN Communication Valid
TEST BOOLEAN Test Output

14.4.11.4 Settings SEMOD173168-1 v2

PID-6831-SETTINGS v3

Table 414: GOOSEINTLKRCV Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On

14.4.11.5 Operation principle GUID-7275CFBA-F1FE-496A-A9A1-724139DB2081 v1

The APPxVAL output will be HIGH if the incoming message is with valid data.

The COMMVALID output will become LOW when the sending IED is under total failure
condition and the GOOSE transmission from the sending IED does not happen.

The TEST output will go HIGH if the sending IED is in test mode.

Breaker protection REQ650 469


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

Data Value Data Valid Comm Valid Test


Incoming data with q=Normal Updated 1 1 0
Incoming data with q=oldData 0 0 1 0
Incoming data with q=Invalid 0 0 1 0
Incoming data with q=test 0 0 1 1
Incoming data with q=test+oldData 0 0 1 1

Receiver in block 0 0 1 0
Receiver in block and communication 0 0 0 0
error
Receiver in test mode and incoming Updated 1 1 0
data with q= Normal
Receiver in test mode and incoming Updated 1 1 1
data with q= Test
Communication Error 0 0 0 0

At least one of the inputs of this GOOSE block must be linked either in SMT by
means of a cross or in ACT by means of a GOOSE connection (if easy GOOSE
engineering is enabled) to receive any data. Only those outputs whose source
input is linked/connected will be updated.

The implementation for IEC 61850 quality data handling is restricted to a


simple level. If quality data validity is GOOD then the APPxVAL output will be
HIGH. If quality data validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE
or OLD DATA then the APPxVAL output will be LOW.

470 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

14.4.12 GOOSE binary receive GOOSEBINRCV SEMOD173158-1 v3

14.4.12.1 Function block SEMOD173175-4 v2

GOOSEBINRCV
BLOCK ^OUT1
^SRCOUT1 DVALID1
^SRCOUT2 ^OUT2
^SRCOUT3 DVALID2
^SRCOUT4 ^OUT3
^SRCOUT5 DVALID3
^SRCOUT6 ^OUT4
^SRCOUT7 DVALID4
^SRCOUT8 ^OUT5
^SRCOUT9 DVALID5
^SRCOUT10 ^OUT6
^SRCOUT11 DVALID6
^SRCOUT12 ^OUT7
^SRCOUT13 DVALID7
^SRCOUT14 ^OUT8
^SRCOUT15 DVALID8
^SRCOUT16 ^OUT9
DVALID9
^OUT10
DVALID10
^OUT11
DVALID11
^OUT12
DVALID12
^OUT13
DVALID13
^OUT14
DVALID14
^OUT15
DVALID15
^OUT16
DVALID16
COMMVALID
TEST

IEC07000047-4-en.vsd
IEC07000047 V4 EN-US

Figure 260: GOOSEBINRCV function block

14.4.12.2 Signals SEMOD173166-1 v2

GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1

Except for the BLOCK input, the rest of the inputs of this GOOSE function block
are used for GOOSE connections. These connections are visible and possible to
make only if Easy GOOSE engineering is enabled. For instructions on how to
enable Easy GOOSE engineering in PCM600, refer to the Engineering Manual.

PID-6827-INPUTSIGNALS v3

Table 415: GOOSEBINRCV Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of output signals
SRCOUT1 BOOLEAN 0 Source to binary output 1
SRCOUT2 BOOLEAN 0 Source to binary output 2
SRCOUT3 BOOLEAN 0 Source to binary output 3
SRCOUT4 BOOLEAN 0 Source to binary output 4
SRCOUT5 BOOLEAN 0 Source to binary output 5
SRCOUT6 BOOLEAN 0 Source to binary output 6
SRCOUT7 BOOLEAN 0 Source to binary output 7
Table continues on next page

Breaker protection REQ650 471


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

Name Type Default Description


SRCOUT8 BOOLEAN 0 Source to binary output 8
SRCOUT9 BOOLEAN 0 Source to binary output 9
SRCOUT10 BOOLEAN 0 Source to binary output 10
SRCOUT11 BOOLEAN 0 Source to binary output 11
SRCOUT12 BOOLEAN 0 Source to binary output 12
SRCOUT13 BOOLEAN 0 Source to binary output 13
SRCOUT14 BOOLEAN 0 Source to binary output 14
SRCOUT15 BOOLEAN 0 Source to binary output 15
SRCOUT16 BOOLEAN 0 Source to binary output 16

PID-6827-OUTPUTSIGNALS v3

Table 416: GOOSEBINRCV Output signals


Name Type Description
OUT1 BOOLEAN Binary output 1
DVALID1 BOOLEAN Valid data on binary output 1
OUT2 BOOLEAN Binary output 2
DVALID2 BOOLEAN Valid data on binary output 2
OUT3 BOOLEAN Binary output 3
DVALID3 BOOLEAN Valid data on binary output 3
OUT4 BOOLEAN Binary output 4
DVALID4 BOOLEAN Valid data on binary output 4
OUT5 BOOLEAN Binary output 5
DVALID5 BOOLEAN Valid data on binary output 5
OUT6 BOOLEAN Binary output 6
DVALID6 BOOLEAN Valid data on binary output 6
OUT7 BOOLEAN Binary output 7
DVALID7 BOOLEAN Valid data on binary output 7
OUT8 BOOLEAN Binary output 8
DVALID8 BOOLEAN Valid data on binary output 8
OUT9 BOOLEAN Binary output 9
DVALID9 BOOLEAN Valid data on binary output 9
OUT10 BOOLEAN Binary output 10
DVALID10 BOOLEAN Valid data on binary output 10
OUT11 BOOLEAN Binary output 11
DVALID11 BOOLEAN Valid data on binary output 11
OUT12 BOOLEAN Binary output 12
DVALID12 BOOLEAN Valid data on binary output 12
OUT13 BOOLEAN Binary output 13
DVALID13 BOOLEAN Valid data on binary output 13
OUT14 BOOLEAN Binary output 14
DVALID14 BOOLEAN Valid data on binary output 14
OUT15 BOOLEAN Binary output 15
Table continues on next page

472 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

Name Type Description


DVALID15 BOOLEAN Valid data on binary output 15
OUT16 BOOLEAN Binary output 16
DVALID16 BOOLEAN Valid data on binary output 16
COMMVALID BOOLEAN Communication Valid
TEST BOOLEAN Test Output

14.4.12.3 Settings SEMOD173168-1 v2

PID-6827-SETTINGS v3

Table 417: GOOSEBINRCV Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On

14.4.12.4 Operation principle GUID-950F2501-9183-43C0-A193-7D15124F6CCE v2

The DVALIDx output will be HIGH if the incoming message is with valid data.

The COMMVALID output will become LOW when the sending IED is under total failure
condition and the GOOSE transmission from the sending IED does not happen.

The TEST output will go HIGH if the sending IED is in test mode.

Data Value Data Valid Comm Valid Test


Incoming data with q=Normal Updated 1 1 0
Incoming data with q=oldData 1 0 1 0
Incoming data with q=Invalid 0 0 1 0
Incoming data with q=test 0 0 1 1
Incoming data with q=test+oldData 0 0 1 1

Receiver in block 0 0 1 0
Receiver in block and communication 0 0 0 0
error
Receiver in test mode and incoming Updated 1 1 0
data with q= Normal
Receiver in test mode and incoming Updated 1 1 1
data with q= Test
Communication Error 0 0 0 0

At least one of the inputs of this GOOSE block must be linked either in SMT by
means of a cross or in ACT by means of a GOOSE connection (if easy GOOSE
engineering is enabled) to receive any data. Only those outputs whose source
input is linked/connected will be updated.

Breaker protection REQ650 473


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

The implementation for IEC 61850 quality data handling is restricted to a


simple level. If quality data validity is GOOD then the DVALIDx output will be
HIGH. If quality data validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE
or OLD DATA then the DVALIDx output will be LOW.

14.4.13 GOOSE function block to receive a switching device


GOOSEXLNRCV

14.4.13.1 Identification
GUID-4B23D0CF-F298-4BBC-B833-1B8CC98D1604 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
GOOSE function block to receive a GOOSEXLNRCV - -
switching device

14.4.13.2 Functionality GUID-5AC7DE11-CB95-4565-A8AE-FB23D59FD717 v1

The GOOSE XLN Receive component is used to collect information from another device’s
XCBR/XSWI logical node sent over process bus via GOOSE. The GOOSE XLN Receive
component includes 12 different outputs (and their respective channel valid bits) with defined
names to ease the 61850 mapping of the GOOSE signals in the configuration process.

14.4.13.3 Function block GUID-690FD935-5344-4D6F-AB94-F9FD5FD35B23 v1

GOOSEXLNRCV
BLOCK ^BEH
^SRCBEH BEH_VALID
^SRCLOC ^LOC
^SRCBLKOPN LOC_VALID
^SRCBLKCLS ^BLKOPN
^SRCPOS BLKOPN_VALID
^SRCOPCNT ^BLKCLS
^SRCBLK BLKCLS_VALID
^SRCSTSELD ^POSVAL
^SRCOPRCVD POSVAL_VALID
^SRCOPOK ^OPCNT
^SRCEEHLT OPCNT_VALID
^SRCOPCAP ^BLK
BLK_VALID
^STSELD
STSELD_VALID
^OPRCVD
OPRCVD_VALID
^OPOK
OPOK_VALID
^EEHEALTH
EEHEALTH_VALID
^OPCAP
OPCAP_VALID
COMMVALID
TEST
IEC16000036-1-en.vsdx
IEC16000036 V1 EN-US

Figure 261: GOOSEXLNRCV function block

474 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

14.4.13.4 Signals
GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1

Except for the BLOCK input, the rest of the inputs of this GOOSE function block
are used for GOOSE connections. These connections are visible and possible to
make only if Easy GOOSE engineering is enabled. For instructions on how to
enable Easy GOOSE engineering in PCM600, refer to the Engineering Manual.

PID-6643-INPUTSIGNALS v3

Table 418: GOOSEXLNRCV Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of output signals
SRCBEH INTEGER 0 Source to behaviour output
SRCLOC BOOLEAN 0 Source to local control behaviour output
SRCBLKOPN BOOLEAN 0 Source to block opening
SRCBLKCLS BOOLEAN 0 Source to block closing
SRCPOS INTEGER 0 Source to switch position
SRCOPCNT INTEGER 0 Source to operation counter
SRCBLK BOOLEAN 0 Source to dynamic blocking of function described by the LN
SRCSTSELD BOOLEAN 0 Source to the controllable data is in the status "selected”
SRCOPRCVD BOOLEAN 0 Source to operate command for a controllable data object
received
SRCOPOK BOOLEAN 0 Source to operate command for a controllable data object
accepted
SRCEEHLT INTEGER 0 Source to external equipment health
SRCOPCAP INTEGER 0 Source to operating capability

PID-6643-OUTPUTSIGNALS v3

Table 419: GOOSEXLNRCV Output signals


Name Type Description
BEH INTEGER Behaviour
BEH_VLD BOOLEAN Valid data on Beh output
LOC BOOLEAN Local control behaviour
LOC_VLD BOOLEAN Valid data on Loc output
BLKOPN BOOLEAN Block opening
BLKOPN_VLD BOOLEAN Valid data on BlkOpn output
BLKCLS BOOLEAN Block closing
BLKCLS_VLD BOOLEAN Valid data on BlkCls output
POSVAL INTEGER Switch position
POSVAL_VLD BOOLEAN Valid data on PosVal output
OPCNT INTEGER Operation counter
OPCNT_VLD BOOLEAN Valid data on OpCnt output
BLK BOOLEAN Dynamic blocking of function described by the LN
BLK_VLD BOOLEAN Valid data on Blk output
STSELD BOOLEAN The controllable data is in the status "selected”
Table continues on next page

Breaker protection REQ650 475


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

Name Type Description


STSELD_VLD BOOLEAN Valid data on stSeld output
OPRCVD BOOLEAN Operate command for a controllable data object received
OPRCVD_VLD BOOLEAN Valid data on opRcvd output
OPOK BOOLEAN Operate command for a controllable data object accepted
OPOK_VLD BOOLEAN Valid data on opOk output
EEHEALTH INTEGER External equipment health
EEHEALTH_VLD BOOLEAN Valid data on EEHealth output
OPCAP INTEGER Operating capability
OPCAP_VLD BOOLEAN Valid data on OpCap output
COMMVALID BOOLEAN Communication valid
TEST BOOLEAN Test output

14.4.13.5 Settings
PID-6643-SETTINGS v3

Table 420: GOOSEXLNRCV Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation Off/On
On

14.4.13.6 Operation principle GUID-903B5E3F-DC92-4D0A-B4D5-59DD01F36458 v1

The xxx_VALID outputs will be HIGH if the incoming message is with valid data.

The COMMVALID output will become LOW when the sending IED is under total failure
condition and the GOOSE transmission from the sending IED does not happen.

The TEST output will go HIGH if the sending IED is in test mode.

At least one of the inputs of this GOOSE block must be linked either in SMT by
means of a cross or in ACT by means of a GOOSE connection (if easy GOOSE
engineering is enabled) to receive any data. Only those outputs whose source
input is linked/connected will be updated.

The implementation for IEC 61850 quality data handling is restricted to a


simple level. If quality data validity is GOOD then the xxx_VALID output will be
HIGH. If quality data validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE
or OLD DATA then the xxx_VALID output will be LOW.

476 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

14.5 IEC/UCA 61850-9-2LE communication protocol GUID-6814F62B-8D99-4679-A11E-68048D1AC424 v2

14.5.1 Introduction GUID-FE2AC08A-2E04-4E73-8CA4-905522B1026A v2

The IEC/UCA 61850-9-2LE process bus communication protocol enables an IED to


communicate with devices providing measured values in digital format, commonly known as
Merging Units (MU). The rear access points are used for the communication.

14.5.2 Function block GUID-2581F3AD-7487-4C80-BDF3-9C6EC9F2E43C v3

The function blocks are not represented in the configuration tool. The signals
appear only in the SMT tool when merging units (MU) are included in the
configuration with the Ethernet configuration tool. In the SMT tool they can be
mapped to the desired virtual input (SMAI) of the IED and used internally in the
configuration.

14.5.3 Signals

14.5.3.1 Output signals SEMOD166622-1 v1

GUID-942C81AD-22D9-438F-95FA-1972BA2BE2E5 v1
The output signals are the same for all MUs so only the table for MU1_HW is included in this
manual.
PID-6850-OUTPUTSIGNALS v3

Table 421: MU1_HW Output signals


Name Type Description
I1 STRING Analogue input I1
I2 STRING Analogue input I2
I3 STRING Analogue input I3
I4 STRING Analogue input I4
U1 STRING Analogue input U1
U2 STRING Analogue input U2
U3 STRING Analogue input U3
U4 STRING Analogue input U4
MUDATA BOOLEAN Fatal error, data not received, transmission errors, time-sync
issues or inconsistent sample rate
SYNCH BOOLEAN High when IED clock is not within configured accuracy or time
domain
SMPLLOST BOOLEAN Fatal error or recovery state after fatal error. High if any
subscribed channel has bad quality or TEST while IED not in
test mode.
MUSYNCH BOOLEAN MU not synced or MU clock not synced to same clock as IED
TESTMODE BOOLEAN Quality of one or more subscribed analogue channels is TEST
SIMMODE BOOLEAN MU delivers simulated data accepted by IED
I1QUALITY INTEGER Binary coded quality information for I1
I2QUALITY INTEGER Binary coded quality information for I2
I3QUALITY INTEGER Binary coded quality information for I3
Table continues on next page

Breaker protection REQ650 477


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

Name Type Description


I4QUALITY INTEGER Binary coded quality information for I4
U1QUALITY INTEGER Binary coded quality information for U1
U2QUALITY INTEGER Binary coded quality information for U2
U3QUALITY INTEGER Binary coded quality information for U3
U4QUALITY INTEGER Binary coded quality information for U4

14.5.4 Settings SEMOD166625-1 v2

PID-6850-SETTINGS v3

Table 422: MU1_HW Non group settings (basic)


Name Values (Range) Unit Step Default Description
CTStarPoint1 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTStarPoint2 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTStarPoint3 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite
CTStarPoint4 FromObject - - ToObject ToObject= towards protected object,
ToObject FromObject= the opposite

14.5.5 Monitored data


PID-6850-MONITOREDDATA v3

Table 423: MU1_HW Monitored data


Name Type Values (Range) Unit Description
MUDATA BOOLEAN 0=Ok - Fatal error, data not received,
1=Error transmission errors, time-sync issues
or inconsistent sample rate
SYNCH BOOLEAN 0=Ok - High when IED clock is not within
1=Error configured accuracy or time domain
SMPLLOST BOOLEAN 1=Yes - Fatal error or recovery state after fatal
0=No error. High if any subscribed channel
has bad quality or TEST while IED not
in test mode.
MUSYNCH BOOLEAN 0=Ok - MU not synced or MU clock not synced
1=Error to same clock as IED
TESTMODE BOOLEAN 1=Yes - Quality of one or more subscribed
0=No analogue channels is TEST
SIMMODE BOOLEAN 1=Yes - MU delivers simulated data accepted
0=No by IED
BadReference BOOLEAN 1=Yes - BadReference indication output for I1
0=No
Derived BOOLEAN 1=Yes - Derived indication output for I1
0=No
Failure BOOLEAN 1=Yes - Failure indication output for I1
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for I1
0=No
Table continues on next page

478 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

Name Type Values (Range) Unit Description


Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for I1
0=No
OldData BOOLEAN 1=Yes - OldData indication output for I1
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No I1
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for I1
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for I1
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for I1
0=No
Source BOOLEAN 0=Process - Source indication output for I1
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for I1
0=No
Validity INTEGER 0=Good - Validity indication output I1
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for I2
0=No
Derived BOOLEAN 1=Yes - Derived indication output for I2
0=No
Failure BOOLEAN 1=Yes - Failure indication output for I2
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for I2
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for I2
0=No
OldData BOOLEAN 1=Yes - OldData indication output for I2
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No I2
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for I2
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for I2
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for I2
0=No
Source BOOLEAN 0=Process - Source indication output for I2
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for I2
0=No
Validity INTEGER 0=Good - Validity indication output I2
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for I3
0=No
Derived BOOLEAN 1=Yes - Derived indication output for I3
0=No
Table continues on next page

Breaker protection REQ650 479


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

Name Type Values (Range) Unit Description


Failure BOOLEAN 1=Yes - Failure indication output for I3
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for I3
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for I3
0=No
OldData BOOLEAN 1=Yes - OldData indication output for I3
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No I3
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for I3
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for I3
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for I3
0=No
Source BOOLEAN 0=Process - Source indication output for I3
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for I3
0=No
Validity INTEGER 0=Good - Validity indication output I3
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for I4
0=No
Derived BOOLEAN 1=Yes - Derived indication output for I4
0=No
Failure BOOLEAN 1=Yes - Failure indication output for I4
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for I4
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for I4
0=No
OldData BOOLEAN 1=Yes - OldData indication output for I4
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No I4
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for I4
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for I4
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for I4
0=No
Source BOOLEAN 0=Process - Source indication output for I4
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for I4
0=No
Validity INTEGER 0=Good - Validity indication output I4
2=Reserved
1=Invalid
3=Questionable
Table continues on next page

480 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

Name Type Values (Range) Unit Description


BadReference BOOLEAN 1=Yes - BadReference indication output for U1
0=No
Derived BOOLEAN 1=Yes - Derived indication output for U1
0=No
Failure BOOLEAN 1=Yes - Failure indication output for U1
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for U1
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for U1
0=No
OldData BOOLEAN 1=Yes - OldData indication output for U1
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No U1
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for U1
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for U1
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for U1
0=No
Source BOOLEAN 0=Process - Source indication output for U1
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for U1
0=No
Validity INTEGER 0=Good - Validity indication output U1
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for U2
0=No
Derived BOOLEAN 1=Yes - Derived indication output for U2
0=No
Failure BOOLEAN 1=Yes - Failure indication output for U2
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for U2
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for U2
0=No
OldData BOOLEAN 1=Yes - OldData indication output for U2
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No U2
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for U2
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for U2
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for U2
0=No
Source BOOLEAN 0=Process - Source indication output for U2
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for U2
0=No
Table continues on next page

Breaker protection REQ650 481


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

Name Type Values (Range) Unit Description


Validity INTEGER 0=Good - Validity indication output U2
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for U3
0=No
Derived BOOLEAN 1=Yes - Derived indication output for U3
0=No
Failure BOOLEAN 1=Yes - Failure indication output for U3
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for U3
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for U3
0=No
OldData BOOLEAN 1=Yes - OldData indication output for U3
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No U3
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for U3
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for U3
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for U3
0=No
Source BOOLEAN 0=Process - Source indication output for U3
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for U3
0=No
Validity INTEGER 0=Good - Validity indication output U3
2=Reserved
1=Invalid
3=Questionable
BadReference BOOLEAN 1=Yes - BadReference indication output for
0=No U4
Derived BOOLEAN 1=Yes - Derived indication output for U4
0=No
Failure BOOLEAN 1=Yes - Failure indication output for U4
0=No
Inaccurate BOOLEAN 1=Yes - Inaccurate indication output for U4
0=No
Inconsistent BOOLEAN 1=Yes - Inconsistent indication output for U4
0=No
OldData BOOLEAN 1=Yes - OldData indication output for U4
0=No
OperatorBlocked BOOLEAN 1=Yes - OperatorBlocked indication output for
0=No U4
Oscillatory BOOLEAN 1=Yes - Oscillatory indication output for U4
0=No
OutOfRange BOOLEAN 1=Yes - OutOfRange indication output for U4
0=No
Overflow BOOLEAN 1=Yes - Overflow indication output for U4
0=No
Table continues on next page

482 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

Name Type Values (Range) Unit Description


Source BOOLEAN 0=Process - Source indication output for U4
1=Substituted
Test BOOLEAN 1=Yes - Test indication output for U4
0=No
Validity INTEGER 0=Good - Validity indication output U4
2=Reserved
1=Invalid
3=Questionable

14.5.6 Operation principle GUID-A1D31CDA-1FE2-4BC0-A472-1B35E73CA1F2 v6

The merging units (MUs) are situated close to the primary equipment, like circuit breakers,
isolators, etc. The MUs have the capability to gather measured values from measuring
transformers, non-conventional transducers or both. The gathered data are then transmitted
to subscribers over the process bus, utilizing the IEC/UCA 61850-9-2LE protocol.

The IED communicates with the MUs over the process bus via the rear access points. For the
user, the MU appears in the IED as a normal analogue input module and is engineered in the
very same way.

Breaker protection REQ650 483


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

IED

Application

Station Wide
Preprocessing blocks Preprocessing blocks GPS Clock
SMAI SMAI

MU1 MU2
Splitter
Electrical-to-
Optical Converter

1PPS
TRM module
Access Point
110 V 1A 1A

IEC/UCA 61850-9-2LE

Ethernet Switch

IEC/UCA 61850-9-2LE

IEC/UCA 61850-9-2LE

Merging 1PPS Merging 1PPS


Unit Unit

Combi Combi
CT CT
Sensor Sensor

Conventional VT
IEC080000723enOriginal.vsd

IEC08000072 V3 EN-US

Figure 262: Example of signal path for sampled analogue values from MU and
conventional CT/VT
The function has the following alarm signals:

• MUDATA:
• Ok[0] indicates that the merging unit samples are received from the merging unit
and are accepted.
• ERROR[1] indicates that the merging unit samples are generated by internal
substitution.
• SYNCH:
• OK[0] indicates
• when SyncLostMode = Block, and the time quality of the hardware is within
the set value [SyncAccLevel=1us, 4us or Unspecified]
• when SyncLostMode = BlockOnLostUTC, the time quality of the hardware is
within the set value [SyncAccLevel=1us, 4us or Unspecified] [AND] IED

484 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

receives global common time[UTC] from any of the FineSyncSource like IRIG-
B, PTP or GPS.
• when SyncLostMode = NoBlock
• ERROR[1] indicates
• when SyncLostMode = Block, and the time quality of the hardware is not
within the set value [SyncAccLevel=1us, 4us or Unspecified]
• when SyncLostMode = BlockonLostUTC, the time quality of the hardware is
not within the set value [SyncAccLevel=1us, 4us or Unspecified] [OR] IED
doesn't receive global common time[UTC] from any of the FineSyncSource
like IRIG-B, PTP or GPS.

• SMPLLOST:
• NO[0] indicates that the merging unit samples are received from the merging unit
and are accepted
• YES[1] indicates
• when merging unit data are generated by internal substitution
• when one/more channel's Quality is not good
• when merging unit is in Testmode/detailed quality=Test, IED is not in test
mode

• MUSYNCH:
• OK[0] indicates
• when SyncLostMode = Block/BlockOnLostUTC, the time quality of the
hardware is within the set value [SyncAccLevel=1us, 4us or Unspecified] [AND]
merging unit is time synchronized [smpSynch flag in datastream is not equal
to 0] [AND] the hardware time matches the time in the datastream within 10
ms.
• when SyncLostMode = NoBlock, the merging unit samples are received
• ERROR[1] indicates
• when SyncLostMode = Block/BlockOnLostUTC, the time quality of the
hardware is not within the set value [SyncAccLevel=1us, 4us or Unspecified]
[OR] merging unit is not time synchronized [smpSynch flag in datastream is
equal to 0] [OR] the hardware time is out of 10 ms from the time in the
datastream.
• when SyncLostMode = NoBlock, the merging unit samples are not received

• TESTMODE:
• NO[0] indicates that No merging unit analog channels are in testmode
• YES[1] indicates that one/more subscribed channels are in testmode
• SIMMODE:
• NO[0] indicates that normal data is received and are accepted
• YES[1] indicates that the received datastream is tagged as simulated and are
accepted

Internal substitution can happen during the following conditions:

1. Transient block after receive error (sample loss)


2. Transient block after Simulated/Real Sample value stream transition
3. Transient block after recovery from substitution
4. No data from merging unit
5. Bad data from merging unit
6. Merging unit report lost sync[smpSynch=0] and SyncLostMode = Block/BlockOnLostUTC

Breaker protection REQ650 485


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

7. IED time quality of hardware is not good [not within set value SyncAccLevel] and
SyncLostMode = Block/BlockOnLostUTC
8. Merging unit channel reported with quality other than good
9. Merging unit channel/channels is/are in testmode and the IED is not in testmode

During Internal substitution, the functions connected to that particular merging unit will be
blocked and the merging unit channel's analog values will be forced to 0 with quality as Invalid,
Substituted, Failure.

Timeout

TSYNCERR Indicates that there is some timeout on any configured time source or the time
quality is worse than specified in SynchAccLevel. The timeout is individually specified per time
source (PPS, IRIG-B, SNTP etc.) See section "Time synchronization TIMESYNCHGEN"

14.5.6.1 Conditional blocking GUID-D129543D-82BE-4F8A-9333-4C3470693F98 v1

Introduction GUID-9D9A73FA-505E-4936-BB55-E7D86AB8023B v1
Conditional blocking is a concept in the 670 series which improves resilience against errors in
network communication, time synchronization, and hardware. This is important for digital
substations where analogue data (some or even all) is sourced from the IEC61850 9-2 MUs
(merging units).

Conditional blocking functionality GUID-C12A5162-7F49-4FF0-98AA-BA362BC48070 v1


The overall idea with conditional blocking is to avoid blocking of the parts of an IED which can
safely continue the operation in presence of certain error conditions (listed below).

To make conditional blocking work as intended, there are configuration rules that need to be
followed. If an incorrect configuration is deployed, the IED functionality may be blocked
inadvertently, thereby reducing the availability of protection functions. An incorrect
configuration also increases the sensitivity to single point failures.

With a proper configuration, on the other hand, only functions directly affected by an error will
be blocked, while other functions will continue to operate.

Implementation GUID-D9880430-E6D6-42EE-B315-7E9279BEC913 v1
In Figure 263, two functions are shown, F1 and F2, where F1 takes data only from MU1, while F2
takes data from both MU1 and MU2.

3Ph Group
MU1 SMAI F1

3Ph Group
MU2 SMAI F2
IEC18001012-1-en.vsdx
IEC18001012 V1 EN-US

Figure 263: Implementation schematic


When F1 and F2 start-up, each function analyzes the analogue data which is driving it. This
information is used to determine how the function should be blocked during error conditions
separately.

486 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

Function F1 is independent of MU2, if MU2 is lost, this will not affect F1. It will execute its
algorithms as long as data from MU1 is available. Note that F1 will operate even with poor time
synchronization. This is possible because F1 only depends on data from a single MU.

Function F2 on the other hand, depends on the correct information and time synchronized
data being available from both MU1 and MU2. If any of the MUs fail, or if any of them indicates
the loss of time synchronization, F2 will be blocked.

Examples of error conditions GUID-AFB2C078-59A8-4DFD-AD6C-B458695E4FA5 v1


This section contains examples of error conditions that can trigger function blocking.

• Time synchronization is not available/correctly configured in the IED

• Time synchronization quality is poor

• Analogue MU data indicates bad time quality in the MU

• Analogue MU data indicates data error in the MU

• Analogue MU data is unavailable (for example, if a connection to an IEC 9-2 MU is lost)

• Hardware errors (for example, network switches and fibers, station clock failures etc.)

Depending on how the IED is configured, these kinds of errors will have a bigger or smaller
impact on how much of the IED functionality that is blocked.

Incorrect configuration GUID-7857CC4E-A7DF-4B85-BF4E-9470A02903E5 v1


As an example, consider an instance of OC4PTOC, which has four steps of functionality. In
Figure 264, it is configured with two 3-phase groups, one for current and one for voltage. The
analogue data comes from two different MUs.

IEC18001013-1-en.vsdx
IEC18001013 V1 EN-US

Figure 264: Incorrect configuration

Breaker protection REQ650 487


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

Assume, that the user has configured one step in the OC4PTOC as non-directional, and
another step as directional. Because the analogue data comes from two different MUs, the
user should understand that the data from both MUs must be available and both must indicate
that they are time synchronized, for the directional step to operate.

Due to the way conditional blocking works, if one or both of the MUs indicate poor time
synchronization, then the entire function will be blocked. Unfortunately, in this example, this
will also block the non-directional over-current step, although it would be perfectly capable of
operating without time synchronization.

This shows the incorrect configuration from a conditional blocking perspective.

Correct configuration GUID-AA803422-5774-4BDE-B84E-2FCF465EE4D0 v1


In Figure 265, the configuration is changed so the user have two instances of the function,
where the non-directional over-current instance uses only currents from one MU, while the
directional over-current instance uses current and voltage from both the MUs.

IEC18001014-1-en.vsdx

IEC18001014 V1 EN-US

Figure 265: Correct configuration


If the time synchronization is lost, or if there is an error in the voltage modules of the MU, or if
the voltage MU is lost altogether, the non-directional instance will still be operative.

This is an example of how the user needs to configure the IED to ensure conditional blocking
works as intended.

Another way to avoid conditional blocking is to take currents as well as voltages from the
same MU. Thus, the usage of multiple SMAIs in itself is not a trigger of conditional blocking,
but the usage of multiple MUs can be. This also implies that hardware-wise, one should try to
not divide a 3-phase group of currents and voltages over multiple MUs, when this is possible
(this is really a consideration for the substation hardware setup).

Functions with multiple internal steps GUID-D067CD74-43CD-480E-9A50-4F978A8DF5D8 v1


The following functions have internal steps/functions, which also can be configured
incorrectly similar to the above description.

NS4PTOC, OC4PTOC, EF4PTOC

• Each step can be set differently with respect to directionality

488 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

SDEPSDE

• Directional overcurrent, non-directional residual overcurrent, and residual overvoltage

VRPVOC

• Voltage restrained overcurrent, undervoltage

LDRGFC

• Current variation, undercurrent, residual overcurrent, and undervoltage

CVGAPC

• Each step can be set differently with respect to directionality: Overcurrent1, Overcurrent2,
Undercurrent1, Undercurrent2, Overvoltage1, Overvoltage2, Undervoltage1, Undervoltage2

Time synchronization GUID-5DD58144-76EA-4019-A8EA-354E263810FB v1


A correct configuration also has to consider how the time synchronization is set up.

To begin with, a suitable station clock must be available. ABB recommends that PTP is used as
a time synchronization protocol.

Further, it is recommended that at least two station clocks are connected to the substation
network. This is to avoid the single point of failure. If one clock encounters an error, or loses its
connection to the network, the other clock will seamlessly take over the time synchronization
task, and thus avoid blocking due to lost time synchronization.

It is also required that PTP is active on all ports that send or receive sampled data on all
devices, to secure that the system time is common for all devices.

Synchronization via PTP GUID-F7D9C58F-CB87-4D2A-BC64-2B34D41557A4 v1


While synchronizing a station via PTP (IEC61850-9-3), the time propagates from the clock
through the system to each IED.

This means that during a transition, for example, when a clock regains time from the GPS
system after drifting for some time, there can be different times in different parts of a
substation.

Refer the following figure for a simple system:

Breaker protection REQ650 489


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

GMC

MU2

REX 670

MU1 MU3

SAM600 - TS CT VT
IEC18001015-1-en.vsdx

IEC18001015 V1 EN-US

Figure 266: Synchronization via PTP

If the station clock is out of order for some time and then regains good synch from, for
example, the satellite system, the correct time will reach MU2 and the 670 first. Then, it will
propagate to MU1 and MU3 through the boundary clock in the 670. This means, that for a short
duration, MU1 and MU2 will both appear to be synchronized, but they will in practice have
different times. If the protection is not blocked during this condition, user will get a false trip.

To fix this problem, the synch-lost signal from the merging units is prolonged for 16 seconds in
the 670. The synch-lost signal is used for conditional blocking of protections which use data
from the TRM of the IED in combination with a merging unit. The maximum time frame
specified by IEC61850-9-3 to propagate the time and resynchronize is 16 seconds.

The same time frame applies for the internal synchronization of the 670. In the scenario where
PTP is used in combination with 9-2, the synch-lost signal is also prolonged with 16 seconds.
Again, this delay is needed to ensure that the correct time has propagated to all units before
blocked functions are released for operation.

14.5.6.2 IEC 61850 quality expander QUALEXP GUID-9C5DC78E-041B-422B-9668-320E62B847A2 v1

The quality expander component is used to display the detailed quality of an IEC/UCA
61850-9-2LE analog channel. The component expands the channel quality output of a Merging
Unit analog channel received in the IED as per the IEC 61850-7-3 standard. This component can
be used during the ACT monitoring to get the particular channel quality of the Merging Unit.

The expanded quality bits are visible on the outputs as per IEC 61850-7-3 standard. When
written to IED, the configuration will show the expanded form of the respective MU channel
quality information during the online monitoring in the ACT.

490 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

The validity status of the quality as described in IEC 61850-7-3 is expanded to Good, Invalid,
Reserved and Questionable (QUEST) outputs.

The detailed quality as described in IEC 61850-7-3 is expanded to Overflow, Out of Range
(OUTRANGE), Bad reference (BADREF), Oscillatory (OSC), Failure, old data, inconsistent
(INCONS) and inaccurate (INACC) outputs.

The source status of the quality as described in IEC 61850-7-3 is expanded to Process and
Substituted (SUBST) outputs.

The other quality statuses (Test, Operator Blocked (OPBLKD) and Derived) are shown as they
are.

The derived quality is the extension to IEC 61850-7-3. If the derived bit is set to 1, it indicates
that there is no physical sensor within the system to determine the value, but the value is
derived from a combination of values from other physical sensors. Typically, I4 or U4 are
derived if they are calculated as the sum of the three phase quantities.

The configured MU channel quality as described in IEC 61850-7-3 is available on LHMI. This can
be viewed under Main Menu/Diagnostics/Merging units/MUX:XXXX/XX Quality.

IEC16000074-1-en.vsdx
IEC16000074 V1 EN-US

Figure 267: Configured MU channel quality in LHMI

14.5.7 Technical data SEMOD172233-1 v1

SEMOD172236-2 v3

Table 424: IEC/UCA 61850-9-2LE communication protocol


Functions Value
Protocol IEC/UCA 61850-9-2LE
Communication speed for the IEDs 100BASE-FX

14.6 LON communication protocol IP14420-1 v1

14.6.1 Functionality M11924-3 v6

An optical network can be used within the substation automation system. This enables
communication with the IED through the LON bus from the operator’s workplace, from the
control center and also from other terminals.

LON communication protocol is specified in LonTalkProtocol Specification Version 3 from


Echelon Corporation and is designed for communication in control networks. These networks
are characterized by high speed for data transfer, short messages (few bytes), peer-to-peer

Breaker protection REQ650 491


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

communication, multiple communication media, low maintenance, multivendor equipment,


and low support costs. LonTalk supports the needs of applications that cover a range of
requirements. The protocol follows the reference model for open system interconnection (OSI)
designed by the International Standardization Organization (ISO).

In this document the most common addresses for commands and events are available. For
other addresses, refer to section Related documents.

It is assumed that the reader is familiar with LON communication protocol in general.

14.6.2 Settings IP14441-1 v2

PID-593-SETTINGS v11

Table 425: HORZCOMM Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation
On

PID-4147-SETTINGS v7

Table 426: ADE Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation
On
TimerClass Slow - - Slow Timer class
Normal
Fast
TimeDomain Local without DST - - Local with DST Time domain
Local with DST

14.6.3 Operation principle IP14439-1 v2

M15083-3 v3
The speed of the network depends on the medium and transceiver design. With protection and
control devices, fiber optic media is used, which enables the use of the maximum speed of 1.25
Mbits/s. The protocol is a peer-to-peer protocol where all the devices connected to the
network can communicate with each other. The own subnet and node number are identifying
the nodes (max. 255 subnets, 127 nodes per one subnet).

The LON bus links the different parts of the protection and control system. The measured
values, status information, and event information are spontaneously sent to the higher-level
devices. The higher-level devices can read and write memorized values, setting values, and
other parameter data when required. The LON bus also enables the bay level devices to
communicate with each other to deliver, for example, interlocking information among the
terminals without the need of a bus master.

The LonTalk protocol supports two types of application layer objects: network variables and
explicit messages. Network variables are used to deliver short messages, such as measuring
values, status information, and interlocking/blocking signals. Explicit messages are used to
transfer longer pieces of information, such as events and explicit read and write messages to
access device data.

The benefits achieved from using the LON bus in protection and control systems include direct
communication among all terminals in the system and support for multi-master
implementations. The LON bus also has an open concept, so that the terminals can
communicate with external devices using the same standard of network variables.

492 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

Introduction of LON protocol M15083-8 v2


For more information, refer to LON bus, LonWorks Network in Protection and Control, User’s
manual and Technical description.

LON protocol M15083-11 v1

Configuration of LON M15083-13 v3


LON network tool (LNT) is a multi-purpose tool for LonWorks network configuration. All the
functions required for setting up and configuring a LonWorks network, is easily accessible on a
single tool program.

Activate LON Communication M15083-16 v3


Activate LON communication in the Parameter Setting tool under Main Menu/Configuration/
Communication/Station communication/ LON/HORZCOMM:1, where Operation must be set
to ON.

Add LON Device Types LNT M15083-19 v3


A new device is added to LON Network Tool from the Device menu or by installing the device
from the ABB LON Device Types package for LNT 505 using SLDT package version 1p2 r04.

LON net address M15083-22 v3


To establish a LON connection, the IED has to be given a unique net address. The net address
consists of a subnet and node number. This is accomplished with the LON Network Tool by
creating one device for each IED.

Vertical communication M15083-25 v1


Vertical communication describes communication between the monitoring devices and
protection and control IEDs. This communication includes sending of changed process data to
monitoring devices as events and transfer of commands, parameter data and disturbance
recorder files. This communication is implemented using explicit messages.

Events and indications M15083-28 v3


Events are sent to the monitoring devices using explicit messages (message code 44H) with
unacknowledged transport service of the LonTalk protocol. When a signal is changed in the
IED, one message with the value, quality and time is transmitted from terminal.

Binary events M15083-31 v6


Binary events are generated in Event function blocks EVENT:1 to EVENT:20 in the IEDs. The
EVENT function blocks have predefined LON addresses. Table 427 shows the LON addresses to
the first input on the EVENT function blocks. Addresses to the other inputs on the EVENT
function block are consecutive after the first input. For example, input 15 on EVENT:17 function
block has the address 1280 + 14 (15-1) = 1294.

For double indications, only the first eight inputs 1–8 must be used. Inputs 9–16 can be used
for other types of events at the same EVENT block.

Three EVENT function blocks EVENT:1 to EVENT:3 running with a fast loop time (3 ms) are
available as basic in the IEDs.. The remaining EVENT function blocks EVENT:4 to EVENT:9 run
with a loop time of 8 ms and EVENT:10 to EVENT:20 run with a loop time of 100 ms. The EVENT
blocks are used to send binary signals, integers, real time values like analogue data from
measuring functions and mA input modules as well as pulse counter signals.

16 pulse counter value function blocks PCFCNT:1 to PCFCNT:16 are available in the IEDs.

The first LON address in every EVENT function block is found in table 427. The formula for
calculating the LON address is:

LON Address = (EVBlkNr-1)×16 + signalNr +1023

For instance, the first pin at Event block number 2 has the address: (2-1)×16 +1 +1023 = 1040

Breaker protection REQ650 493


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

Table 427: LON adresses for EVENT functions


Function block First LON address in
function block
EVENT:1 1024
EVENT:2 1040
EVENT:3 1056
EVENT:4 1072
EVENT:5 1088
EVENT:6 1104
EVENT:7 1120
EVENT:8 1136
EVENT:9 1152
EVENT:10 1168
EVENT:11 1184
EVENT:12 1200
EVENT:13 1216
EVENT:14 1232
EVENT:15 1248
EVENT:16 1264
EVENT:17 1280
EVENT:18 1296
EVENT:19 1312
EVENT:20 1328

Event masks M15083-78 v4


Event mask for each input can be set individually from Parameter Setting Tool (PST) under:
Settings/IED settings/ Monitoring / Event Function or via parameter setting tool (PST) as
follows:

• No events
• OnSet, at pick-up of the signal
• OnReset, at drop-out of the signal
• OnChange, at both pick-up and drop-out of the signal
• AutoDetect, the EVENT function makes the reporting decision (reporting criteria for
integers has no semantic, prefer to be set by the user)

Single indication M15083-123 v3


Directly connected binary IO signal via binary input function block (SMBI) is always reported on
change, no changed detection is done in the EVENT function block. Other Boolean signals, for
example a start or a trip signal from a protection function is event masked in the EVENT
function block.

Double indications M15083-126 v3


Double indications can only be reported for the first 8 inputs on an EVENT function block.

• 00 generates an intermediate event with the read status 0


• 01 generates an open event with the read status 1
• 10 generates a close event with the read status 2
• 11 generates an undefined event with the read status 3

Analog value M15083-135 v4

494 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

All analog values are reported cyclic. The reporting interval is taken from the connected
function if there is a limit supervised signal. Otherwise it is taken from the EVENT function
block.

Command handling M15083-80 v4


Commands are transferred using transparent SPA-bus messages. The transparent SPA-bus
message is an explicit LON message which contains an ASCII character message following the
coding rules of the SPA-bus protocol. The message is sent using explicit messages with
message code 41H and using acknowledged transport service.

Both the SPA-bus command messages (R or W) and the reply messages (D, A or N) are sent
using the same message code. It is mandatory that one device sends out only one SPA-bus
message at a time to one node and waits for the reply before sending the next message.

For commands from the operator workplace to the IED for apparatus control, that is the
function blocks type SCSWI 1 to 30, SXCBR 1 to 18 and SXSWI 1 to 24, the SPA addresses are
according to table 428.
SEMOD116913-2 v2

Table 428: SPA addresses for commands from the operator workplace to the IED for apparatus control
Name Function SPA Description
block address
BL_CMD SCSWI01 1 I 5115 SPA parameters for block
command
BL_CMD SCSWI02 1 I 5139 SPA parameters for block
command
BL_CMD SCSWI02 1 I 5161 SPA parameters for block
command
BL_CMD SCSWI04 1 I 5186 SPA parameters for block
command
BL_CMD SCSWI05 1 I 5210 SPA parameters for block
command
BL_CMD SCSWI06 1 I 5234 SPA parameters for block
command
BL_CMD SCSWI07 1 I 5258 SPA parameters for block
command
BL_CMD SCSWI08 1 I 5283 SPA parameters for block
command
BL_CMD SCSWI09 1 I 5307 SPA parameters for block
command
BL_CMD SCSWI10 1 I 5331 SPA parameters for block
command
BL_CMD SCSWI11 1 I 5355 SPA parameters for block
command
BL_CMD SCSWI12 1 I 5379 SPA parameters for block
command
BL_CMD SCSWI13 1 I 5403 SPA parameters for block
command
BL_CMD SCSWI14 1 I 5427 SPA parameters for block
command
BL_CMD SCSWI15 1 I 5451 SPA parameters for block
command
BL_CMD SCSWI16 1 I 5475 SPA parameters for block
command
BL_CMD SCSWI17 1 I 5499 SPA parameters for block
command
Table continues on next page

Breaker protection REQ650 495


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

Name Function SPA Description


block address
BL_CMD SCSWI18 1 I 5523 SPA parameters for block
command
BL_CMD SCSWI19 1 I 5545 SPA parameters for block
command
BL_CMD SCSWI20 1 I 5571 SPA parameters for block
command
BL_CMD SCSWI21 1 I 5594 SPA parameters for block
command
BL_CMD SCSWI22 1 I 5619 SPA parameters for block
command
BL_CMD SCSWI23 1 I 5643 SPA parameters for block
command
BL_CMD SCSWI24 1 I 5667 SPA parameters for block
command
BL_CMD SCSWI25 1 I 5691 SPA parameters for block
command
BL_CMD SCSWI26 1 I 5715 SPA parameters for block
command
BL_CMD SCSWI27 1 I 5739 SPA parameters for block
command
BL_CMD SCSWI28 1 I 5763 SPA parameters for block
command
BL_CMD SCSWI29 1 I 5787 SPA parameters for block
command
BL_CMD SCSWI30 1 I 5811 SPA parameters for block
command
BL_CMD SCSWI31 1 I 5835 SPA parameters for block
command
BL_CMD SCSWI32 1 I 5859 SPA parameters for block
command
CANCEL SCSWI01 1 I 5107 SPA parameters for cancel
command
CANCEL SCSWI02 1 I 5131 SPA parameters for cancel
command
CANCEL SCSWI03 1 I 5153 SPA parameters for cancel
command
CANCEL SCSWI04 1 I 5178 SPA parameters for cancel
command
CANCEL SCSWI05 1 I 5202 SPA parameters for cancel
command
CANCEL SCSWI06 1 I 5226 SPA parameters for cancel
command
CANCEL SCSWI07 1 I 5250 SPA parameters for cancel
command
CANCEL SCSWI08 1 I 5275 SPA parameters for cancel
command
CANCEL SCSWI09 1 I 5299 SPA parameters for cancel
command
CANCEL SCSWI10 1 I 5323 SPA parameters for cancel
command
CANCEL SCSWI11 1 I 5347 SPA parameters for cancel
command
Table continues on next page

496 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

Name Function SPA Description


block address
CANCEL SCSWI12 1 I 5371 SPA parameters for cancel
command
CANCEL SCSWI13 1 I 5395 SPA parameters for cancel
command
CANCEL SCSWI14 1 I 5419 SPA parameters for cancel
command
CANCEL SCSWI15 1 I 5443 SPA parameters for cancel
command
CANCEL SCSWI16 1 I 5467 SPA parameters for cancel
command
CANCEL SCSWI17 1 I 5491 SPA parameters for cancel
command
CANCEL SCSWI18 1 I 5515 SPA parameters for cancel
command
CANCEL SCSWI19 1 I 5537 SPA parameters for cancel
command
CANCEL SCSWI20 1 I 5563 SPA parameters for cancel
command
CANCEL SCSWI21 1 I 5586 SPA parameters for cancel
command
CANCEL SCSWI22 1 I 5611 SPA parameters for cancel
command
CANCEL SCSWI23 1 I 5635 SPA parameters for cancel
command
CANCEL SCSWI24 1 I 5659 SPA parameters for cancel
command
CANCEL SCSWI25 1 I 5683 SPA parameters for cancel
command
CANCEL SCSWI26 1 I 5707 SPA parameters for cancel
command
CANCEL SCSWI27 1 I 5731 SPA parameters for cancel
command
CANCEL SCSWI28 1 I 5755 SPA parameters for cancel
command
CANCEL SCSWI29 1 I 5779 SPA parameters for cancel
command
CANCEL SCSWI30 1 I 5803 SPA parameters for cancel
command
CANCEL SCSWI31 1 I 5827 SPA parameters for cancel
command
CANCEL SCSWI32 1 I 5851 SPA parameters for cancel
command
SELECTOpen=00, SCSWI01 1 I 5105 SPA parameters for select
SELECTClose=01, (Open/Close) command
SELOpen+ILO=10, Note: Send select command
SELClose+ILO=11, before operate command
SELOpen+SCO=20,
SELClose+SCO=21,
SELOpen+ILO+SCO=30,
SELClose+ILO+SCO=31
SELECTOpen=00, SCSWI02 1 I 5129 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
Table continues on next page

Breaker protection REQ650 497


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

Name Function SPA Description


block address
SELECTOpen=00, SCSWI03 1 I 5151 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI04 1 I 5176 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI05 1 I 5200 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI06 1 I 5224 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI07 1 I 5248 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI08 1 I 5273 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI09 1 I 5297 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI10 1 I 5321 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI11 1 I 5345 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI12 1 I 5369 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI13 1 I 5393 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI14 1 I 5417 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI15 1 I 5441 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI16 1 I 5465 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI17 1 I 5489 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI18 1 I 5513 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI19 1 I 5535 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI20 1 I 5561 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI21 1 I 5584 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI22 1 I 5609 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI23 1 I 5633 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI24 1 I 5657 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI25 1 I 5681 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI26 1 I 5705 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI27 1 I 5729 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI28 1 I 5753 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
Table continues on next page

498 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

Name Function SPA Description


block address
SELECTOpen=00, SCSWI29 1 I 5777 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI30 1 I 5801 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI31 1 I 5825 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
SELECTOpen=00, SCSWI32 1 I 5849 SPA parameters for select
SELECTClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI01 1 I 5106 SPA parameters for operate
ExcClose=01, (Open/Close) command
ExcOpen+ILO=10, Note: Send select command
ExcClose+ILO=11, before operate command
ExcOpen+SCO=20,
ExcClose+SCO=21,
ExcOpen+ILO+SCO=30,
ExcClose+ILO+SCO=31
ExcOpen=00, SCSWI02 1 I 5130 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI02 1 I 5152 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI04 1 I 5177 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI05 1 I 5201 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI06 1 I 5225 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI07 1 I 5249 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI08 1 I 5274 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI09 1 I 5298 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI10 1 I 5322 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI11 1 I 5346 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI12 1 I 5370 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI13 1 I 5394 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI14 1 I 5418 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI15 1 I 5442 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI16 1 I 5466 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI17 1 I 5490 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI18 1 I 5514 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI19 1 I 5536 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
Table continues on next page

Breaker protection REQ650 499


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

Name Function SPA Description


block address
ExcOpen=00, SCSWI20 1 I 5562 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI21 1 I 5585 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI22 1 I 5610 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI23 1 I 5634 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI24 1 I 5658 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI25 1 I 5682 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI26 1 I 5706 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI27 1 I 5730 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI28 1 I 5754 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI29 1 I 5778 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI30 1 I 5802 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI31 1 I 5826 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
ExcOpen=00, SCSWI32 1 I 5850 SPA parameters for operate
ExcClose=01, so on. (Open/Close) command
Sub Value SXCBR01 2 I 7854 SPA parameter for position to
be substituted
Note: Send the value before
Enable
Sub Value SXCBR02 2 I 7866 SPA parameter for position to
be substituted
Sub Value SXCBR03 2 I 7884 SPA parameter for position to
be substituted
Sub Value SXCBR04 2 I 7904 SPA parameter for position to
be substituted
Sub Value SXCBR05 2 I 7923 SPA parameter for position to
be substituted
Sub Value SXCBR06 2 I 7942 SPA parameter for position to
be substituted
Sub Value SXCBR07 2 I 7961 SPA parameter for position to
be substituted
Sub Value SXCBR08 2 I 7980 SPA parameter for position to
be substituted
Sub Value SXCBR09 3I7 SPA parameter for position to
be substituted
Sub Value SXCBR10 3 I 26 SPA parameter for position to
be substituted
Sub Value SXCBR11 3 I 45 SPA parameter for position to
be substituted
Sub Value SXCBR12 3 I 56 SPA parameter for position to
be substituted
Table continues on next page

500 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

Name Function SPA Description


block address
Sub Value SXCBR13 3 I 74 SPA parameter for position to
be substituted
Sub Value SXCBR14 3 I 94 SPA parameter for position to
be substituted
Sub Value SXCBR15 3 I 120 SPA parameter for position to
be substituted
Sub Value SXCBR16 3 I 133 SPA parameter for position to
be substituted
Sub Value SXCBR17 3 I 158 SPA parameter for position to
be substituted
Sub Value SXCBR18 3 I 179 SPA parameter for position to
be substituted
Sub Value SXSWI01 3 I 196 SPA parameter for position to
be substituted
Sub Value SXSWI02 3 I 216 SPA parameter for position to
be substituted
Sub Value SXSWI03 3 I 235 SPA parameter for position to
be substituted
Sub Value SXSWI04 3 I 254 SPA parameter for position to
be substituted
Sub Value SXSWI05 3 I 272 SPA parameter for position to
be substituted
Sub Value SXSWI06 3 I 292 SPA parameter for position to
be substituted
Sub Value SXSWI07 3 I 310 SPA parameter for position to
be substituted
Sub Value SXSWI08 3 I 330 SPA parameter for position to
be substituted
Sub Value SXSWI09 3 I 348 SPA parameter for position to
be substituted
Sub Value SXSWI10 3 I 359 SPA parameter for position to
be substituted
Sub Value SXSWI11 3 I 378 SPA parameter for position to
be substituted
Sub Value SXSWI12 3 I 397 SPA parameter for position to
be substituted
Sub Value SXSWI13 3 I 416 SPA parameter for position to
be substituted
Sub Value SXSWI14 3 I 435 SPA parameter for position to
be substituted
Sub Value SXSWI15 3 I 454 SPA parameter for position to
be substituted
Sub Value SXSWI16 3 I 473 SPA parameter for position to
be substituted
Sub Value SXSWI17 3 I 492 SPA parameter for position to
be substituted
Sub Value SXSWI18 3 I 511 SPA parameter for position to
be substituted
Sub Value SXSWI19 3 I 530 SPA parameter for position to
be substituted
Sub Value SXSWI20 3 I 549 SPA parameter for position to
be substituted
Table continues on next page

Breaker protection REQ650 501


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

Name Function SPA Description


block address
Sub Value SXSWI21 3 I 568 SPA parameter for position to
be substituted
Sub Value SXSWI22 3 I 587 SPA parameter for position to
be substituted
Sub Value SXSWI23 3 I 606 SPA parameter for position to
be substituted
Sub Value SXSWI24 3 I 625 SPA parameter for position to
be substituted
Sub Value SXSWI25 3 I 644 SPA parameter for position to
be substituted
Sub Value SXSWI26 3 I 663 SPA parameter for position to
be substituted
Sub Value SXSWI27 3 I 682 SPA parameter for position to
be substituted
Sub Value SXSWI28 3 I 701 SPA parameter for position to
be substituted
Sub Enable SXCBR01 2 I 7855 SPA parameter for substitute
enable command
Note: Send the Value before
Enable
Sub Enable SXCBR02 2 I 7865 SPA parameter for substitute
enable command
Sub Enable SXCBR03 2 I 7885 SPA parameter for substitute
enable command
Sub Enable SXCBR04 2 I 7903 SPA parameter for substitute
enable command
Sub Enable SXCBR05 2 I 7924 SPA parameter for substitute
enable command
Sub Enable SXCBR06 2 I 7941 SPA parameter for substitute
enable command
Sub Enable SXCBR07 2 I 7962 SPA parameter for substitute
enable command
Sub Enable SXCBR08 2 I 7979 SPA parameter for substitute
enable command
Sub Enable SXCBR09 3I8 SPA parameter for substitute
enable command
Sub Enable SXCBR10 3 I 25 SPA parameter for substitute
enable command
Sub Enable SXCBR11 3 I 46 SPA parameter for substitute
enable command
Sub Enable SXCBR12 3 I 55 SPA parameter for substitute
enable command
Sub Enable SXCBR13 3 I 75 SPA parameter for substitute
enable command
Sub Enable SXCBR14 3 I 93 SPA parameter for substitute
enable command
Sub Enable SXCBR15 3 I 121 SPA parameter for substitute
enable command
Sub Enable SXCBR16 3 I 132 SPA parameter for substitute
enable command
Sub Enable SXCBR17 3 I 159 SPA parameter for substitute
enable command
Table continues on next page

502 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

Name Function SPA Description


block address
Sub Enable SXCBR18 3 I 178 SPA parameter for substitute
enable command
Sub Enable SXSWI01 3 I 197 SPA parameter for substitute
enable command
Sub Enable SXSWI02 3 I 215 SPA parameter for substitute
enable command
Sub Enable SXSWI03 3 I 234 SPA parameter for substitute
enable command
Sub Enable SXSWI04 3 I 252 SPA parameter for substitute
enable command
Sub Enable SXSWI05 3 I 271 SPA parameter for substitute
enable command
Sub Enable SXSWI06 3 I 290 SPA parameter for substitute
enable command
Sub Enable SXSWI07 3 I 309 SPA parameter for substitute
enable command
Sub Enable SXSWI08 3 I 328 SPA parameter for substitute
enable command
Sub Enable SXSWI09 3 I 347 SPA parameter for substitute
enable command
Sub Enable SXSWI10 3 I 360 SPA parameter for substitute
enable command
Sub Enable SXSWI11 3I 379 SPA parameter for substitute
enable command
Sub Enable SXSWI12 3 I 398 SPA parameter for substitute
enable command
Sub Enable SXSWI13 3 I 417 SPA parameter for substitute
enable command
Sub Enable SXSWI14 3 I 436 SPA parameter for substitute
enable command
Sub Enable SXSWI15 3 I 455 SPA parameter for substitute
enable command
Sub Enable SXSWI16 3 I 474 SPA parameter for substitute
enable command
Sub Enable SXSWI17 3 I 493 SPA parameter for substitute
enable command
Sub Enable SXSWI18 3 I 512 SPA parameter for substitute
enable command
Sub Enable SXSWI19 3 I 531 SPA parameter for substitute
enable command
Sub Enable SXSWI20 3 I 550 SPA parameter for substitute
enable command
Sub Enable SXSWI21 3 I 569 SPA parameter for substitute
enable command
Sub Enable SXSWI22 3 I 588 SPA parameter for substitute
enable command
Sub Enable SXSWI23 3 I 607 SPA parameter for substitute
enable command
Sub Enable SXSWI24 3 I 626 SPA parameter for substitute
enable command
Sub Enable SXSWI25 3 I 645 SPA parameter for substitute
enable command
Table continues on next page

Breaker protection REQ650 503


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

Name Function SPA Description


block address
Sub Enable SXSWI26 3 I 664 SPA parameter for substitute
enable command
Sub Enable SXSWI27 3 I 683 SPA parameter for substitute
enable command
Sub Enable SXSWI28 3 I 702 SPA parameter for substitute
enable command
Update Block SXCBR01 2 I 7853 SPA parameter for update block
command
Update Block SXCBR02 2 I 7864 SPA parameter for update block
command
Update Block SXCBR03 2 I 7883 SPA parameter for update block
command
Update Block SXCBR04 2 I 7905 SPA parameter for update block
command
Update Block SXCBR05 2 I 7922 SPA parameter for update block
command
Update Block SXCBR06 2 I 7943 SPA parameter for update block
command
Update Block SXCBR07 2 I 7960 SPA parameter for update block
command
Update Block SXCBR08 2 I 7981 SPA parameter for update block
command
Update Block SXCBR09 3I6 SPA parameter for update block
command
Update Block SXCBR10 3 I 27 SPA parameter for update block
command
Update Block SXCBR11 3 I 44 SPA parameter for update block
command
Update Block SXCBR12 3 I 57 SPA parameter for update block
command
Update Block SXCBR13 3 I 73 SPA parameter for update block
command
Update Block SXCBR14 3 I 92 SPA parameter for update block
command
Update Block SXCBR15 3 I 122 SPA parameter for update block
command
Update Block SXCBR16 3 I 131 SPA parameter for update block
command
Update Block SXCBR17 3 I 160 SPA parameter for update block
command
Update Block SXCBR18 3 I 177 SPA parameter for update block
command
Update Block SXSWI01 3 I 198 SPA parameter for update block
command
Update Block SXSWI02 3 I 214 SPA parameter for update block
command
Update Block SXSWI03 3 I 236 SPA parameter for update block
command
Update Block SXSWI04 3 I 253 SPA parameter for update block
command
Update Block SXSWI05 3 I 273 SPA parameter for update block
command
Table continues on next page

504 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

Name Function SPA Description


block address
Update Block SXSWI06 3 I 291 SPA parameter for update block
command
Update Block SXSWI07 3 I 311 SPA parameter for update block
command
Update Block SXSWI08 3 I 329 SPA parameter for update block
command
Update Block SXSWI09 3 I 349 SPA parameter for update block
command
Update Block SXSWI10 3 I 358 SPA parameter for update block
command
Update Block SXSWI11 3 I 377 SPA parameter for update block
command
Update Block SXSWI12 3 I 396 SPA parameter for update block
command
Update Block SXSWI13 3 I 415 SPA parameter for update block
command
Update Block SXSWI14 3 I 434 SPA parameter for update block
command
Update Block SXSWI15 3 I 453 SPA parameter for update block
command
Update Block SXSWI16 3 I 472 SPA parameter for update block
command
Update Block SXSWI17 3 I 491 SPA parameter for update block
command
Update Block SXSWI18 3 I 510 SPA parameter for update block
command
Update Block SXSWI19 3 I 529 SPA parameter for update block
command
Update Block SXSWI20 3 I 548 SPA parameter for update block
command
Update Block SXSWI21 3 I 567 SPA parameter for update block
command
Update Block SXSWI22 3 I 586 SPA parameter for update block
command
Update Block SXSWI23 3 I 605 SPA parameter for update block
command
Update Block SXSWI24 3 I 624 SPA parameter for update block
command
Update Block SXSWI25 3 I 643 SPA parameter for update block
command
Update Block SXSWI26 3 I 662 SPA parameter for update block
command
Update Block SXSWI27 3 I 681 SPA parameter for update block
command
Update Block SXSWI28 3 I 700 SPA parameter for update block
command

Horizontal communication M15083-86 v4


Network variables are used for communication between 500 and 650 series IEDs The
supported network variable type is SNVT_state (NV type 83). SNVT_state is used to
communicate the state of a set of 1 to 16 Boolean values.

Breaker protection REQ650 505


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

Multiple command send function block (MULTICMDSND) is used to pack the information to
one value. This value is transmitted to the receiving node and presented for the application by
a multiple command receive function block (MULTICMDRCV). With horizontal communication,
the input BOUND on MULTICMDSND must be set to 1. There are 10 MULTICMDSND and 60
MULTICMDRCV function blocks available. These function blocks are connected using the LON
network tool (LNT). The tool also defines the service and addressing on LON.

This is an overview for configuring the network variables for the IEDs.

Configuration of LON network variables M15083-92 v3


Configure the Network variables according to the specific application using the LON network
tool (LNT). The following is an example of how to configure network variables concerning, for
example, interlocking between two IEDs.

LON

BAY E1 BAY E3 BAY E4


MULTICMDSND: 7 MULTICMDSND: 9 MULTICMDSND: 9

en05000718.vsd
IEC05000718 V2 EN-US

Figure 268: Examples connections between MULTICMDSND and MULTICMDRCV function


blocks in three IEDs
The network variable connections are done from the NV Connection window. From LNT
window select Connections/ NVConnections/ New.

506 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

en05000719.vsd
IEC05000719 V1 EN-US

Figure 269: The network variables window in LNT


There are two ways of downloading NV connections. Either the users can use the drag-and-
drop method where they can select all nodes in the device window, drag them to the Download
area in the bottom of the program window and drop them there; or, they can perform it by
selecting the traditional menu, Configuration/ Download.

en05000720.vsd
IEC05000720 V1 EN-US

Figure 270: The download configuration window in LNT

Breaker protection REQ650 507


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

Communication ports M15083-97 v6


The serial communication module (SLM) is a mezzanine module placed on the first analog
digital conversion module (ADM), and it is used for LON, SPA, IEC 60870-5-103 and DNP
communication.

In the following figure, X311 ports A/B are for SPA, IEC103 or DNP3 and X311 ports C/D are for
LON protocol.

IEC16000079-1-en.vsd
IEC16000079 V1 EN-US

Figure 271: Rear view of 1/2 x 19” casing with 1 TRM slot
There are two types of IO connectors: snap-in connectors for plastic fiber cables and ST/
bayonet connectors for glass fiber cables. The SLM can be equipped with either type of
connector or a combination of both connectors. This is identified by a tag.

Connect the incoming optical fiber to the RX receiver input, and the outgoing optical fiber to
the TX transmitter output. Pay special attention to the instructions concerning handling and
connection of fiber cables.

14.6.4 Technical data IP14442-1 v1

M11927-1 v2

Table 429: LON communication protocol


Function Value
Protocol LON
Communication speed 1.25 Mbit/s

508 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

14.7 SPA communication protocol IP14614-1 v1

14.7.1 Functionality M11897-3 v6

In this section the most common addresses for commands and events are available. For other
addresses, refer to section Related documents.

It is assumed that the reader is familiar with the SPA communication protocol in general.

14.7.2 Design M11877-3 v7

Using the rear SPA port for either local or remote communication with a PC requires the
following equipment:

• Optical fibers
• Opto/electrical converter for the PC
• PC

SPA cannot be accessed via PCM600.

When communicating between the local HMI and a PC, the only hardware required is a front-
connection cable.

SPA can be accessed via LHMI front only when using the Field Service Tool
Access (FSTACCS).

14.7.3 Settings IP14403-1 v2

PID-6195-SETTINGS v5

Table 430: SPA Non group settings (basic)


Name Values (Range) Unit Step Default Description
SlaveAddress 1 - 899 - 1 30 Slave address
BaudRate 300 Bd - - 9600 Bd Baudrate on serial line
1200 Bd
2400 Bd
4800 Bd
9600 Bd
19200 Bd
38400 Bd

PID-6194-SETTINGS v5

Table 431: LONSPA Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - Off Operation
On
SlaveAddress 1 - 899 - 1 30 Slave address

Breaker protection REQ650 509


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

14.7.4 Operation principle IP14401-1 v3

M11880-3 v2
The SPA bus uses an asynchronous serial communications protocol (1 start bit, 7 data bits +
even parity, 1 stop bit) with data transfer rate up to 38400 bit/s. For more information on
recommended baud rate for each type of IED, refer to Technical reference manual. Messages
on the bus consist of ASCII characters.

Introduction of SPA protocol M11880-7 v2


The basic construction of the protocol assumes that the slave has no self-initiated need to talk
to the master but the master is aware of the data contained in the slaves and, consequently,
can request required data. In addition, the master can send data to the slave. Requesting by
the master can be performed either by sequenced polling (for example, for event information)
or only on demand.

The master requests slave information using request messages and sends information to the
slave in write messages. Furthermore, the master can send all slaves in common a broadcast
message containing time or other data. The inactive state of bus transmit and receive lines is a
logical "1".

SPA protocol M11880-10 v5


The tables below specify the SPA addresses for reading data from and writing data to an IED
with the SPA communication protocol implemented.

The SPA addresses for the pulse counter values PCFCNT:1 to PCFCNT:16 are found in table 432.

Table 432: SPA addresses for the PCFCNT function


Function block SPA address CNT_VAL SPA address NEW_VAL
PCFCNT:1 6-O-2788 6-O-2787
PCFCNT:2 6-O-2794 6-O-2793
PCFCNT:3 6-O-2800 6-O-2799
PCFCNT:4 6-O-2806 6-O-2805
PCFCNT:5 6-O-2812 6-O-2811
PCFCNT:6 6-O-2818 6-O-2817
PCFCNT:7 6-O-2824 6-O-2823
PCFCNT:8 6-O-2830 6-O-2829
PCFCNT:9 6-O-2836 6-O-2835
PCFCNT:10 6-O-2842 6-O-2841
PCFCNT:11 6-O-2848 6-O-2847
PCFCNT:12 6-O-2854 6-O-2853
PCFCNT:13 6-O-2860 6-O-2859
PCFCNT:14 6-O-2866 6-O-2865
PCFCNT:15 6-O-2872 6-O-2871
PCFCNT:16 6-O-2878 6-O-2877

I/O modules M11880-16 v4


To read binary inputs, the SPA-addresses for the outputs of the I/O-module function block are
used, that is, the addresses for BI1 – BI16. For SPA addresses, refer to section Related
documents in Product Guide.
M11880-35 v1

510 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

Single command, 16 signals M11880-51 v5


The IEDs can be provided with a function to receive signals either from a substation
automation system or from the local HMI. That receiving function block has 16 outputs that
can be used, for example, to control high voltage apparatuses in switchyards. For local control
functions, the local HMI can also be used.

The single command, 16 signals function consists of four function blocks: SINGLECMD:1 to
SINGLECMD:4 for 16 binary output signals each.

The signals can be individually controlled from the operator station, remote-control gateway,
or from the local HMI on the IED. For Single command, 3 signals function block, SINGLECMD:1
to SINGLECMD:3, the address is for the first output. The other outputs follow consecutively
after the first one. For example, output 7 on the SINGLECMD:2 function block has the 5O533
address.

The SPA addresses for Single command, 16 signals functions SINGLECMD:1 to SINGLECMD:4
are found in table 433.

Table 433: SPA addresses for SINGLECMD function


Function block SPA address CMD Input SPA address CMD output
SINGLECMD1-Cmd1 4-S-4639 5-O-511
SINGLECMD1-Cmd2 4-S-4640 5-O-512
SINGLECMD1-Cmd3 4-S-4641 5-O-513
SINGLECMD1-Cmd4 4-S-4642 5-O-514
SINGLECMD1-Cmd5 4-S-4643 5-O-515
SINGLECMD1-Cmd6 4-S-4644 5-O-516
SINGLECMD1-Cmd7 4-S-4645 5-O-517
SINGLECMD1-Cmd8 4-S-4646 5-O-518
SINGLECMD1-Cmd9 4-S-4647 5-O-519
SINGLECMD1-Cmd10 4-S-4648 5-O-520
SINGLECMD1-Cmd11 4-S-4649 5-O-521
SINGLECMD1-Cmd12 4-S-4650 5-O-522
SINGLECMD1-Cmdt13 4-S-4651 5-O-523
SINGLECMD1-Cmd14 4-S-4652 5-O-524
SINGLECMD1-Cmd15 4-S-4653 5-O-525
SINGLECMD1-Cmd16 4-S-4654 5-O-526
SINGLECMD2-Cmd1 4-S-4672 5-O-527
SINGLECMD2-Cmd2 4-S-4673 5-O-528
SINGLECMD2-Cmdt3 4-S-4674 5-O-529
SINGLECMD2-Cmd4 4-S-4675 5-O-530
SINGLECMD2-Cmd5 4-S-4676 5-O-531
SINGLECMD2-Cmd6 4-S-4677 5-O-532
SINGLECMD2-Cmd7 4-S-4678 5-O-533
SINGLECMD2-Cmd8 4-S-4679 5-O-534
SINGLECMD2-Cmd9 4-S-4680 5-O-535
SINGLECMD2-Cmd10 4-S-4681 5-O-536
SINGLECMD2-Cmd11 4-S-4682 5-O-537
SINGLECMD2-Cmd12 4-S-4683 5-O-538
Table continues on next page

Breaker protection REQ650 511


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

Function block SPA address CMD Input SPA address CMD output
SINGLECMD2-Cmd13 4-S-4684 5-O-539
SINGLECMD2-Cmd14 4-S-4685 5-O-540
SINGLECMD2-Cmd15 4-S-4686 5-O-541
SINGLECMD2-Cmd16 4-S-4687 5-O-542
SINGLECMD3-Cmd1 4-S-4705 5-O-543
SINGLECMD3-Cmd2 4-S-4706 5-O-544
SINGLECMD3-Cmd3 4-S-4707 5-O-545
SINGLECMD3-Cmd4 4-S-4708 5-O-546
SINGLECMD3-Cmd5 4-S-4709 5-O-547
SINGLECMD3-Cmd6 4-S-4710 5-O-548
SINGLECMD3-Cmd7 4-S-4711 5-O-549
SINGLECMD3-Cmd8 4-S-4712 5-O-550
SINGLECMD3-Cmd9 4-S-4713 5-O-551
SINGLECMD3-Cmd10 4-S-4714 5-O-552
SINGLECMD3-Cmd11 4-S-4715 5-O-553
SINGLECMD3-Cmd12 4-S-4716 5-O-554
SINGLECMD3-Cmd13 4-S-4717 5-O-555
SINGLECMD3-Cmd14 4-S-4718 5-O-556
SINGLECMD3-Cmd15 4-S-4719 5-O-557
SINGLECMD3-Cmd16 4-S-4720 5-O-558
SINGLECMD4-Cmd1 4-S-4738 5-O-559
SINGLECMD4-Cmd2 4-S-4739 5-O-560
SINGLECMD4-Cmd3 4-S-4740 5-O-561
SINGLECMD4-Cmd4 4-S-4741 5-O-562
SINGLECMD4-Cmd5 4-S-4742 5-O-563
SINGLECMD4-Cmd6 4-S-4743 5-O-564
SINGLECMD4-Cmd7 4-S-4744 5-O-565
SINGLECMD4-Cmd8 4-S-4745 5-O-566
SINGLECMD4-Cmd9 4-S-4746 5-O-567
SINGLECMD4-Cmd10 4-S-4747 5-O-568
SINGLECMD4-Cmd11 4-S-4748 5-O-569
SINGLECMD4-Cmd12 4-S-4749 5-O-570
SINGLECMD4-Cmd13 4-S-4750 5-O-571
SINGLECMD4-Cmd14 4-S-4751 5-O-572
SINGLECMD4-Cmd15 4-S-4752 5-O-573
SINGLECMD4-Cmd16 4-S-4753 5-O-574

Figure 272 shows an application example of how the user can, in a simplified way, connect the
command function via the configuration logic circuit in a protection IED for control of a circuit
breaker.

A pulse via the binary outputs of the IED normally performs this type of command control. The
SPA addresses to control the outputs OUT1 – OUT16 in SINGLECMD:1 are shown in table 433.

512 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

SINGLECMD PULSETIMER
BLOCK ^OUT1 INPUT OUT To output board, CLOSE
#CD01-CMDOUT1 ^OUT2
#CD01-CMDOUT2 ^OUT3
#CD01-CMDOUT3 ^OUT4
#CD01-CMDOUT4 ^OUT5 AND PULSETIMER
^OUT6 INPUT1 OUT INPUT OUT To output board, OPEN
#CD01-CMDOUT5
^OUT7 INPUT2 NOUT
#CD01-CMDOUT6
#CD01-CMDOUT7 ^OUT8 INPUT3
#CD01-CMDOUT8 ^OUT9 INPUT4
#CD01-CMDOUT9 ^OUT10
#CD01-CMDOUT10 ^OUT11
#CD01-CMDOUT11 ^OUT12
#CD01-CMDOUT12 ^OUT13
#CD01-CMDOUT13 ^OUT14
#CD01-CMDOUT14 ^OUT15
#CD01-CMDOUT15 ^OUT16
#CD01-CMDOUT16

SYNCH OK

IEC05000717-4-en.vsd
IEC05000717 V4 EN-US

Figure 272: Application example showing a simplified logic diagram for control of a
circuit breaker
The MODE input defines if the output signals from SINGLECMD:1 is off, steady or setable pulse
length signals. This is set in Parameter Setting Tool (PST) under: Main Menu/Settings / IED
Settings / Control / Commands / Single Command or via Parameter Setting Tool (PST).

Event function EVENT M11880-82 v6


The Event function (EVENT) sends time-tagged events to the station level (for example,
operator workplace) over the station bus. On the station level, events are presented in an
event list. Events can be created from both internal logical signals and binary input channels.
All the internal signals are time tagged in the main processing module, while the binary input
channels are time tagged directly on each I/O module. Events are produced according to a set
of event masks. These masks are treated commonly for both LON and SPA channels.

Two special signals for event registration purposes are available in the IED: Terminal Restarted
(0E50) and Event buffer overflow (0E51).

The status and event codes for the EVENT function are found in Table 434.

Table 434: Status and event codes

Single indication1) Double indication


Event block Status Set event Reset Intermed Closed Open Undefined
event iate 00 10 01 11
EVENT:1
Input 1 22O1 22E33 22E32 22E0 22E1 22E2 22E3
Input 2 22O2 22E35 22E34 22E4 22E5 22E6 22E7
Input 3 22O3 22E37 22E36 22E8 22E9 22E10 22E11
Input 4 22O4 22E39 22E38 22E12 22E13 22E14 22E15
Input 5 22O5 22E41 22E40 22E16 22E17 22E18 22E19
Input 6 22O6 22E43 22E42 22E20 22E21 22E22 22E23
Input 7 22O7 22E45 22E44 22E24 22E25 22E26 22E27
Input 8 22O8 22E47 22E46 22E28 22E29 22E30 22E31
Input 9 22O9 22E49 22E48 - - - -
Input 10 22O10 22E51 22E50 - - - -
Input 11 22O11 22E53 22E52 - - - -
Input 12 22O12 22E55 22E54 - - - -
Input 13 22O13 22E57 22E56 - - - -
Input 14 22O14 22E59 22E58 - - - -
Input 15 22O15 22E61 22E60 - - - -
Input 16 22O16 22E63 22E62 - - - -

EVENT:2 230.. 23E.. 23E.. 23E.. 23E.. 23E.. 23E..


EVENT:3 240.. 24E.. 24E.. 24E.. 23E.. 24E.. 24E..
- - - - - - - -
- - - - - - - -
- - - - - - - -
EVENT:20 410.. 41E.. 41E.. 41E.. 41E.. 41E.. 41E..

Breaker protection REQ650 513


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

These values are only applicable if the event mask is masked ≠ OFF.

Connection of signals as events M11880-311 v5


Signals coming from different protection and control functions and sent as events to the
station level over the SPA-bus (or LON-bus), are connected to the EVENT function block as
specified in Figure 273.

EVENT
Block BLOCK
ILRANG ^INPUT1
PSTO ^INPUT2
UL12RANG ^INPUT3
UL23RANG ^INPUT4
UL31RANG ^INPUT5
3I0RANG ^INPUT6
3U0RANG ^INPUT7
FALSE ^INPUT8
^INPUT9
^INPUT10
^INPUT11
^INPUT12
^INPUT13
^INPUT14
^INPUT15
^INPUT16

IEC07000065-2-en.vsd
IEC07000065 V2 EN-US

Figure 273: Connection of protection signals for event handling

14.7.4.1 Communication ports M11880-315 v7

The serial communication module (SLM) is a mezzanine module placed on the first analog
digital conversion module (ADM). It is used for LON, SPA, IEC 60870-5-103 and DNP
communication.

In the following figure, X311 ports A/B are for SPA, IEC103 or DNP3 and X311 ports C/D are for
LON protocol.

514 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

IEC16000079-1-en.vsd
IEC16000079 V1 EN-US

Figure 274: Rear view of 1/2 x 19” casing with 1 TRM slot
There are two types of IO connectors: snap-in connector for plastic fiber cables and ST/
bayonet connector for glass fiber cables. The SLM can be equipped with either type or
connector or with a combination of both types of connectors. This is identified with a tag.

Connect the incoming optical fiber to the RX receiver input, and the outgoing optical fiber to
the TX transmitter output. Pay special attention to the instructions concerning handling and
connection of fiber cables.

For setting the transfer rate (baud rate) and slave number, please refer to the Application
manual and Commissioning manual respectively.

14.7.5 Technical data IP14404-1 v1

M11901-1 v2

Table 435: SPA communication protocol


Function Value
Protocol SPA
Communication speed 300, 1200, 2400, 4800, 9600, 19200 or 38400 Bd
Slave number 1 to 899

14.8 IEC 60870-5-103 communication protocol IP14615-1 v2

14.8.1 Introduction M11910-3 v3

IEC 60870-5-103 communication protocol is mainly used when a protection IED communicates
with a third party control or monitoring system. This system must have software that can
interpret the IEC 60870-5-103 communication messages.

Breaker protection REQ650 515


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

14.8.2 Measurands for IEC 60870-5-103 I103MEAS

14.8.2.1 Functionality GUID-557FB587-9127-4D99-B2C6-16445E06F220 v3

103MEAS is a function block that reports all valid measuring types depending on connected
signals.

The set of connected input will control which ASDUs (Application Service Data Units) are
generated.

• 9 Will be generated if at least IL1 is connected. IL2, IL3, UL1, UL2, UL3, P, Q, F are optional
but there can be no holes.
• 3.4 Will be generated if IN and UN are present.
• 3.3 Will be generated if IL2, Ul1L2, P and Q present.
• 3.2 Will be generated if IL2, UL1L2 and P or Q missing.
• 3.1 Will be generated if IL2 present and IL1 missing (otherwise IL2 in 9).

Description for I103MEAS function block:


9 = IL1
3.4 = IN AND UN
3.3 = IL2 AND UL1L2 AND P AND Q
3.2 = IL2 AND UL1L2 AND NOT 3.3
3.1 = IL2 AND NOT (3.2 OR 3.3 OR 9)

14.8.2.2 Identification
GUID-3E1AB624-1B68-4018-B1BA-BC2C811F8F74 v1

Function description Function block IEC 60617 ANSI/IEEE C37.2


name identification device number
Measurands for IEC 60870-5-103 I103MEAS - -

14.8.2.3 Function block GUID-EC5F1C83-0F47-4548-86E3-FFE056571241 v2

I103MEAS
BLOCK
IL1
IL2
IL3
IN
UL1
UL2
UL3
UL1L2
UN
P
Q
F

IEC10000287-1-en.vsd
IEC10000287 V1 EN-US

Figure 275: I103MEAS function block

516 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

14.8.2.4 Signals
PID-6625-INPUTSIGNALS v4

Table 436: I103MEAS Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of service value reporting
IL1 REAL 0.0 Service value for current phase L1
IL2 REAL 0.0 Service value for current phase L2
IL3 REAL 0.0 Service value for current phase L3
IN REAL 0.0 Service value for residual current IN
UL1 REAL 0.0 Service value for voltage phase L1
UL2 REAL 0.0 Service value for voltage phase L2
UL3 REAL 0.0 Service value for voltage phase L3
UL1L2 REAL 0.0 Service value for voltage phase-phase L1-L2
UN REAL 0.0 Service value for residual voltage UN
P REAL 0.0 Service value for active power
Q REAL 0.0 Service value for reactive power
F REAL 0.0 Service value for system frequency

14.8.2.5 Settings
PID-6625-SETTINGS v4

Table 437: I103MEAS Non group settings (basic)


Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 1 Function type (1-255)
MaxIL1 1 - 99999 A 1 3000 Maximum current phase L1
MaxIL2 1 - 99999 A 1 3000 Maximum current phase L2
MaxIL3 1 - 99999 A 1 3000 Maximum current phase L3
MaxIN 1 - 99999 A 1 3000 Maximum residual current IN
MaxUL1 0.05 - 2000.00 kV 0.05 230.00 Maximum voltage for phase L1
MaxUL2 0.05 - 2000.00 kV 0.05 230.00 Maximum voltage for phase L2
MaxUL3 0.05 - 2000.00 kV 0.05 230.00 Maximum voltage for phase L3
MaxUL1-UL2 0.05 - 2000.00 kV 0.05 400.00 Maximum voltage for phase-phase L1-
L2
MaxUN 0.05 - 2000.00 kV 0.05 230.00 Maximum residual voltage UN
MaxP 0.00 - 2000.00 MW 0.05 1200.00 Maximum value for active power
MaxQ 0.00 - 2000.00 MVAr 0.05 1200.00 Maximum value for reactive power
MaxF 15.0 - 66.0 Hz 1.0 51.0 Maximum system frequency

Breaker protection REQ650 517


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

14.8.3 Measurands user defined signals for IEC 60870-5-103


I103MEASUSR

14.8.3.1 Functionality GUID-FC9ED4BD-F11C-4BDA-8CDB-3ACF00931D3A v1

I103MEASUSR is a function block with user defined input measurands in monitor direction.
These function blocks include the FunctionType parameter for each block in the private range,
and the Information number parameter for each block.

14.8.3.2 Identification
GUID-A9E21066-354B-453D-8D9B-E86EE31CF5F9 v1

Function description Function block IEC 60617 ANSI/IEEE C37.2


name identification device number
Measurands user defined signals for I103MEASUSR - -
IEC 60870-5-103

14.8.3.3 Function block GUID-C234101E-F9B9-4DB0-874C-C51BB50588CB v1

I103MEASUSR
BLOCK
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9

IEC10000288-1-en.vsd
IEC10000288 V1 EN-US

Figure 276: I103MEASUSR function block

14.8.3.4 Signals
PID-3791-INPUTSIGNALS v5

Table 438: I103MEASUSR Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of service value reporting
INPUT1 REAL 0.0 Service value for measurement on input 1
INPUT2 REAL 0.0 Service value for measurement on input 2
INPUT3 REAL 0.0 Service value for measurement on input 3
INPUT4 REAL 0.0 Service value for measurement on input 4
INPUT5 REAL 0.0 Service value for measurement on input 5
INPUT6 REAL 0.0 Service value for measurement on input 6
INPUT7 REAL 0.0 Service value for measurement on input 7
INPUT8 REAL 0.0 Service value for measurement on input 8
INPUT9 REAL 0.0 Service value for measurement on input 9

518 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

14.8.3.5 Settings
PID-3791-SETTINGS v5

Table 439: I103MEASUSR Non group settings (basic)


Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 25 Function type (1-255)
InfNo 1 - 255 - 1 1 Information number for measurands
(1-255)
MaxMeasur1 0.05 - - 0.05 1000.00 Maximum value for measurement on
10000000000.00 input 1
MaxMeasur2 0.05 - - 0.05 1000.00 Maximum value for measurement on
10000000000.00 input 2
MaxMeasur3 0.05 - - 0.05 1000.00 Maximum value for measurement on
10000000000.00 input 3
MaxMeasur4 0.05 - - 0.05 1000.00 Maximum value for measurement on
10000000000.00 input 4
MaxMeasur5 0.05 - - 0.05 1000.00 Maximum value for measurement on
10000000000.00 input 5
MaxMeasur6 0.05 - - 0.05 1000.00 Maximum value for measurement on
10000000000.00 input 6
MaxMeasur7 0.05 - - 0.05 1000.00 Maximum value for measurement on
10000000000.00 input 7
MaxMeasur8 0.05 - - 0.05 1000.00 Maximum value for measurement on
10000000000.00 input 8
MaxMeasur9 0.05 - - 0.05 1000.00 Maximum value for measurement on
10000000000.00 input 9

14.8.4 Function status auto-recloser for IEC 60870-5-103 I103AR

14.8.4.1 Functionality GUID-7A132276-35A2-402C-9722-6259D65998F5 v1

I103AR is a function block with defined functions for autorecloser indications in monitor
direction. This block includes the FunctionType parameter, and the information number
parameter is defined for each output signal.

14.8.4.2 Identification
GUID-7B066282-79D7-480B-BEDE-3C04F0FCBF05 v1

Function description Function block IEC 60617 ANSI/IEEE C37.2


name identification device number
Function status auto-recloser for IEC I103AR - -
60870-5-103

14.8.4.3 Function block GUID-FAC5A3DF-73CB-4A39-A213-5C21ACA05756 v1

I103AR
BLOCK
16_ARACT
128_CBON
130_BLKD

IEC10000289-2-en.vsd
IEC10000289 V2 EN-US

Figure 277: I103AR function block

Breaker protection REQ650 519


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

14.8.4.4 Signals
PID-3973-INPUTSIGNALS v5

Table 440: I103AR Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of status reporting
16_ARACT BOOLEAN 0 Information number 16, auto-recloser active
128_CBON BOOLEAN 0 Information number 128, circuit breaker on by auto-recloser
130_BLKD BOOLEAN 0 Information number 130, auto-recloser blocked

14.8.4.5 Settings
PID-3973-SETTINGS v5

Table 441: I103AR Non group settings (basic)


Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 1 Function type (1-255)

14.8.5 Function status earth-fault for IEC 60870-5-103 I103EF GUID-F23B392E-B55D-4BC3-A0A6-B7992D551092 v1

14.8.5.1 Functionality GUID-13F90E95-7C8C-4DCB-A9D8-2489B66DB81A v2

I103EF is a function block with defined functions for earth fault indications in monitor
direction. This block includes the FunctionType parameter, and the information number
parameter is defined for each output signal.

14.8.5.2 Identification
GUID-033731B7-1B71-4CCC-8356-1C03CBCB23FA v1

Function description Function block IEC 60617 ANSI/IEEE C37.2


name identification device number
Function status earth-fault for IEC I103EF - -
60870-5-103

14.8.5.3 Function block GUID-25B47484-2976-4063-BD81-AE02D03B08B0 v1

I103EF
BLOCK
51_EFFW
52_EFREV

IEC10000290-1-en.vsd
IEC10000290 V1 EN-US

Figure 278: I103EF function block

520 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

14.8.5.4 Signals
PID-3974-INPUTSIGNALS v5

Table 442: I103EF Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of status reporting
51_EFFW BOOLEAN 0 Information number 51, earth-fault forward
52_EFREV BOOLEAN 0 Information number 52, earth-fault reverse

14.8.5.5 Settings
PID-3974-SETTINGS v5

Table 443: I103EF Non group settings (basic)


Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 160 Function type (1-255)

14.8.6 Function status fault protection for IEC 60870-5-103


I103FLTPROT

14.8.6.1 Functionality GUID-6D52F442-1592-4BA7-919C-0CD79046CAE5 v1

I103FLTPROT is used for fault indications in monitor direction. Each input on the function
block is specific for a certain fault type and therefore must be connected to a correspondent
signal present in the configuration. For example: 68_TRGEN represents the General Trip of the
device, and therefore must be connected to the general trip signal SMPPTRC_TRIP or
equivalent.

The delay observed in the protocol is the time difference in between the signal that is
triggering the Disturbance Recorder and the respective configured signal to the IEC
60870-5-103 I103FLTPROT.

14.8.6.2 Identification
GUID-55593EC4-7AED-47A0-8311-DB22D013A193 v1

Function description Function block IEC 60617 ANSI/IEEE C37.2


name identification device number
Function status fault protection for I103FLTPROT - -
IEC 60870-5-103

Breaker protection REQ650 521


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

14.8.6.3 Function block GUID-F0ED13B8-6B82-4CA7-8F22-C200C33EBB7E v2

I103FLTPROT
BLOCK
64_STL1
65_STL2
66_STL3
67_STIN
68_TRGEN
69_TRL1
70_TRL2
71_TRL3
72_TRBKUP
73_SCL
74_FW
75_REV
76_TRANS
77_RECEV
78_ZONE1
79_ZONE2
80_ZONE3
81_ZONE4
82_ZONE5
83_ZONE6
84_STGEN
85_BFP
86_MTRL1
87_MTRL2
88_MTRL3
89_MTRN
90_IOC
91_IOC
92_IEF
93_IEF
ARINPROG
FLTLOC
IEC10000291-2-en.vsdx

IEC10000291 V2 EN-US

Figure 279: I103FLTPROT function block

14.8.6.4 Signals
PID-6864-INPUTSIGNALS v1

Table 444: I103FLTPROT Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of status reporting.
64_STL1 BOOLEAN 0 Information number 64, start phase L1
65_STL2 BOOLEAN 0 Information number 65, start phase L2
66_STL3 BOOLEAN 0 Information number 66, start phase L3
67_STIN BOOLEAN 0 Information number 67, start residual current IN
68_TRGEN BOOLEAN 0 Information number 68, trip general
69_TRL1 BOOLEAN 0 Information number 69, trip phase L1
70_TRL2 BOOLEAN 0 Information number 70, trip phase L2
71_TRL3 BOOLEAN 0 Information number 71, trip phase L3
72_TRBKUP BOOLEAN 0 Information number 72, back up trip I>>
73_SCL REAL 0 Information number 73, fault location in ohm
74_FW BOOLEAN 0 Information number 74, forward/line
75_REV BOOLEAN 0 Information number 75, reverse/busbar
76_TRANS BOOLEAN 0 Information number 76, signal transmitted
Table continues on next page

522 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

Name Type Default Description


77_RECEV BOOLEAN 0 Information number 77, signal received
78_ZONE1 BOOLEAN 0 Information number 78, zone 1
79_ZONE2 BOOLEAN 0 Information number 79, zone 2
80_ZONE3 BOOLEAN 0 Information number 80, zone 3
81_ZONE4 BOOLEAN 0 Information number 81, zone 4
82_ZONE5 BOOLEAN 0 Information number 82, zone 5
83_ZONE6 BOOLEAN 0 Information number 83, zone 6
84_STGEN BOOLEAN 0 Information number 84, start general
85_BFP BOOLEAN 0 Information number 85, breaker failure
86_MTRL1 BOOLEAN 0 Information number 86, trip measuring system phase L1
87_MTRL2 BOOLEAN 0 Information number 87, trip measuring system phase L2
88_MTRL3 BOOLEAN 0 Information number 88, trip measuring system phase L3
89_MTRN BOOLEAN 0 Information number 89, trip measuring system neutral N
90_IOC BOOLEAN 0 Information number 90, over current trip, stage low
91_IOC BOOLEAN 0 Information number 91, over current trip, stage high
92_IEF BOOLEAN 0 Information number 92, earth-fault trip, stage low
93_IEF BOOLEAN 0 Information number 93, earth-fault trip, stage high
ARINPROG BOOLEAN 0 Autorecloser in progress (SMBRREC- INPROGR)
FLTLOC BOOLEAN 0 Faultlocator faultlocation valid (LMBRFLO-CALCMADE)

14.8.6.5 Settings
PID-6864-SETTINGS v1

Table 445: I103FLTPROT Non group settings (basic)


Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 128 Function type (1-255)

14.8.7 IED status for IEC 60870-5-103 I103IED

14.8.7.1 Functionality GUID-52AC7D0F-33C5-46FC-983E-5CB4B3517D88 v1

I103IED is a function block with defined IED functions in monitor direction. This block uses
parameter as FunctionType, and information number parameter is defined for each input
signal.

14.8.7.2 Identification
GUID-5EEBE11C-C8E3-4A8A-814F-840E137DB5B5 v1

Function description Function block IEC 60617 ANSI/IEEE C37.2


name identification device number
IED status for IEC 60870-5-103 I103IED - -

Breaker protection REQ650 523


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

14.8.7.3 Function block GUID-421D5C37-27A5-476A-A7D9-40E70AFDFDC8 v1

I103IED
BLOCK
19_LEDRS
21_TESTM
22_SETCH
23_GRP1
24_GRP2
25_GRP3
26_GRP4

IEC10000292-2-en.vsd
IEC10000292 V2 EN-US

Figure 280: I103IED function block

14.8.7.4 Signals
PID-3975-INPUTSIGNALS v5

Table 446: I103IED Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of status reporting
19_LEDRS BOOLEAN 0 Information number 19, reset LEDs
21_TESTM BOOLEAN 0 Information number 21, test mode is active
22_SETCH BOOLEAN 0 Information number 22, setting changed
23_GRP1 BOOLEAN 0 Information number 23, setting group 1 is active
24_GRP2 BOOLEAN 0 Information number 24, setting group 2 is active
25_GRP3 BOOLEAN 0 Information number 25, setting group 3 is active
26_GRP4 BOOLEAN 0 Information number 26, setting group 4 is active

14.8.7.5 Settings
PID-3975-SETTINGS v5

Table 447: I103IED Non group settings (basic)


Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 1 Function type (1-255)

14.8.8 Supervison status for IEC 60870-5-103 I103SUPERV

14.8.8.1 Functionality GUID-E7A28D8D-398E-437C-9B58-AE125BC38058 v1

I103SUPERV is a function block with defined functions for supervision indications in monitor
direction. This block includes the FunctionType parameter, and the information number
parameter is defined for each output signal.

14.8.8.2 Identification
GUID-C8113B08-3586-412C-A750-606159B1E97E v1

Function description Function block IEC 60617 ANSI/IEEE C37.2


name identification device number
Supervison status for IEC I103SUPERV - -
60870-5-103

524 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

14.8.8.3 Function block GUID-69C2C974-2D64-4174-9F9A-15383C09050D v1

I103SUPERV
BLOCK
32_MEASI
33_MEASU
37_IBKUP
38_VTFF
46_GRWA
47_GRAL

IEC10000293-1-en.vsd
IEC10000293 V1 EN-US

Figure 281: I103SUPERV function block

14.8.8.4 Signals
PID-3976-INPUTSIGNALS v5

Table 448: I103SUPERV Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of status reporting
32_MEASI BOOLEAN 0 Information number 32, measurand supervision of I
33_MEASU BOOLEAN 0 Information number 33, measurand supervision of U
37_IBKUP BOOLEAN 0 Information number 37, I high-high back-up protection
38_VTFF BOOLEAN 0 Information number 38, fuse failure VT
46_GRWA BOOLEAN 0 Information number 46, group warning
47_GRAL BOOLEAN 0 Information number 47, group alarm

14.8.8.5 Settings
PID-3976-SETTINGS v5

Table 449: I103SUPERV Non group settings (basic)


Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 1 Function type (1-255)

14.8.9 Status for user defined signals for IEC 60870-5-103


I103USRDEF

14.8.9.1 Functionality GUID-DADC9CE4-2E80-426C-A3B6-A8E8C7AC3CD4 v3

I103USRDEF is a function block with user defined input signals in monitor direction. Each
instance is associated with a Function Type (FUN) and each input signal with an Information
Number (INF). Additionally, all input signals may be defined to use relative time and how to
respond to a GI request.

The user is responsible for assigning a proper FUN value and proper INF values to all
connected inputs. See Settings for details.

Breaker protection REQ650 525


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

14.8.9.2 Identification
GUID-474FDF39-CEFC-4370-9393-13BE62159969 v2

Function description Function block IEC 60617 ANSI/IEEE C37.2


name identification device number
Status for user defined signals for I103USRDEF - -
IEC 60870-5-103

14.8.9.3 Function block GUID-B8312E77-514D-4117-BB31-B9907755580C v1

I103USRDEF
BLOCK
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
RT_START

IEC10000294-3-en.vsdx

IEC10000294 V3 EN-US

Figure 282: I103USRDEF function block

14.8.9.4 Signals
PID-6485-INPUTSIGNALS v5

Table 450: I103USRDEF Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of status reporting
INPUT1 BOOLEAN 0 Binary signal Input 1
INPUT2 BOOLEAN 0 Binary signal input 2
INPUT3 BOOLEAN 0 Binary signal input 3
INPUT4 BOOLEAN 0 Binary signal input 4
INPUT5 BOOLEAN 0 Binary signal input 5
INPUT6 BOOLEAN 0 Binary signal input 6
INPUT7 BOOLEAN 0 Binary signal input 7
INPUT8 BOOLEAN 0 Binary signal input 8
RT_START BOOLEAN 0 Trig to set base of relative time

GUID-9E29DE39-EA74-4D62-A2BA-F8E31A3D8757 v2
RT_START registers the positive transition (0->1) of a pulse and sets the time from which
relative time is derived. Relative time is assigned only to inputs where the corresponding
TypNo parameter is set to Relative. The maximum relative time and unit conform to the IEC
60870-5-103 standard.

526 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

14.8.9.5 Settings
PID-6485-SETTINGS v5

Table 451: I103USRDEF Non group settings (basic)


Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 5 Function type (1-255)
InfNo1 1 - 255 - 1 1 Information number for binary input 1
(1-255)
InfNo2 1 - 255 - 1 2 Information number for binary input 2
(1-255)
InfNo3 1 - 255 - 1 3 Information number for binary input 3
(1-255)
InfNo4 1 - 255 - 1 4 Information number for binary input 4
(1-255)
InfNo5 1 - 255 - 1 5 Information number for binary input 5
(1-255)
InfNo6 1 - 255 - 1 6 Information number for binary input 6
(1-255)
InfNo7 1 - 255 - 1 7 Information number for binary input 7
(1-255)
InfNo8 1 - 255 - 1 8 Information number for binary input 8
(1-255)
TypNo1 Absolute - - Absolute Type identification (TYP)
Relative
TypNo2 Absolute - - Absolute Type identification (TYP)
Relative
TypNo3 Absolute - - Absolute Type identification (TYP)
Relative
TypNo4 Absolute - - Absolute Type identification (TYP)
Relative
TypNo5 Absolute - - Absolute Type identification (TYP)
Relative
TypNo6 Absolute - - Absolute Type identification (TYP)
Relative
TypNo7 Absolute - - Absolute Type identification (TYP)
Relative
TypNo8 Absolute - - Absolute Type identification (TYP)
Relative
GiNo1 Excluded - - Included Response and status change (GI)
Included
GiNo2 Excluded - - Included Response and status change (GI)
Included
GiNo3 Excluded - - Included Response and status change (GI)
Included
GiNo4 Excluded - - Included Response and status change (GI)
Included
GiNo5 Excluded - - Included Response and status change (GI)
Included
Table continues on next page

Breaker protection REQ650 527


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

Name Values (Range) Unit Step Default Description


GiNo6 Excluded - - Included Response and status change (GI)
Included
GiNo7 Excluded - - Included Response and status change (GI)
Included
GiNo8 Excluded - - Included Response and status change (GI)
Included

GUID-86DE9DBA-BE2F-4CC9-B447-1D2D86849EFF v2
The FunctionType parameter associates a particular instance of the function block with a FUN.
Refer to the IEC 60870-5-103 standard for details.

The InfNon parameters are used to associate each individual input signal with a userdefined
INF. Refer to the IEC 60870-5-103 standard for details.

The TypNon parameters determine if messages use absolute or relative time. This adheres to
the TYPE IDENTIFICATION (TYP) message types 1 (time-tagged message) and 2 (time-tagged
message with relative time) of the IEC 60870-5-103 standard.

The GiNon parameters determine whether a message is sent as a part of a GI reply or not.
Refer to the IEC 60870-5-103 standard for details.

14.8.10 Function commands for IEC 60870-5-103 I103CMD

14.8.10.1 Functionality GUID-973929FE-292B-42A5-ACF9-BC95E2B16AE1 v2

I103CMD is a command function block in control direction with pre-defined output signals. The
signals are in steady state, not pulsed, and stored in the IED in case of restart.

14.8.10.2 Identification
GUID-CFD43980-0791-40D1-9136-CF4CCC35549A v1

Function description Function block IEC 60617 ANSI/IEEE C37.2


name identification device number
Function commands for IEC I103CMD - -
60870-5-103

14.8.10.3 Function block GUID-C0680812-C488-4546-AA65-F590955DBF0C v1

I103CMD
BLOCK 16-AR
17-DIFF
18-PROT

IEC10000282-1-en.vsd
IEC10000282 V1 EN-US

Figure 283: I103CMD function block

14.8.10.4 Signals
PID-3969-INPUTSIGNALS v5

Table 452: I103CMD Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of commands

528 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

PID-3969-OUTPUTSIGNALS v5

Table 453: I103CMD Output signals


Name Type Description
16-AR BOOLEAN Information number 16, off/on of autorecloser
17-DIFF BOOLEAN Information number 17, block of differential protection
18-PROT BOOLEAN Information number 18, block of protection

14.8.10.5 Settings
PID-3969-SETTINGS v5

Table 454: I103CMD Non group settings (basic)


Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 1 Function type (1-255)

14.8.11 IED commands for IEC 60870-5-103 I103IEDCMD

14.8.11.1 Functionality GUID-19AD44B2-21D6-4DB0-AD74-1578DA30C100 v5

I103IEDCMD is a command block in control direction with defined IED functions. All outputs
are pulsed and they are NOT stored. Pulse length is fixed to 400ms.

14.8.11.2 Identification
GUID-0D0B2477-1B0C-48F3-B047-CCF9C7A71856 v1

Function description Function block IEC 60617 ANSI/IEEE C37.2


name identification device number
IED commands for IEC 60870-5-103 I103IEDCMD - -

14.8.11.3 Function block GUID-52D27CDA-8805-48FA-99BE-2E05A438B0C7 v1

I103IEDCMD
BLOCK 19-LEDRS
23-GRP1
24-GRP2
25-GRP3
26-GRP4

IEC10000283-1-en.vsd
IEC10000283 V1 EN-US

Figure 284: I103IEDCMD function block

14.8.11.4 Signals
PID-3788-INPUTSIGNALS v5

Table 455: I103IEDCMD Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of commands

Breaker protection REQ650 529


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

PID-3788-OUTPUTSIGNALS v5

Table 456: I103IEDCMD Output signals


Name Type Description
19-LEDRS BOOLEAN Information number 19, reset LEDs
23-GRP1 BOOLEAN Information number 23, activate setting group 1
24-GRP2 BOOLEAN Information number 24, activate setting group 2
25-GRP3 BOOLEAN Information number 25, activate setting group 3
26-GRP4 BOOLEAN Information number 26, activate setting group 4

14.8.11.5 Settings
PID-3788-SETTINGS v5

Table 457: I103IEDCMD Non group settings (basic)


Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 255 Function type (1-255)

14.8.12 Function commands user defined for IEC 60870-5-103


I103USRCMD

14.8.12.1 Functionality GUID-2989EAC8-20BE-46EE-93FE-C70188D0BC89 v1

I103USRCMD is a command block in control direction with user defined output signals. These
function blocks include the FunctionType parameter for each block in the private range, and
the Information number parameter for each output signal.

14.8.12.2 Identification
GUID-9D6D1636-36C6-4C4E-B157-2D827820DDC7 v1

Function description Function block IEC 60617 ANSI/IEEE C37.2


name identification device number
Function commands user defined for I103USRCMD - -
IEC 60870-5-103

14.8.12.3 Function block GUID-5EBEAED5-ABD9-4257-B879-DF7FD9F7805A v1

I103USRCMD
BLOCK ^OUTPUT1
^OUTPUT2
^OUTPUT3
^OUTPUT4
^OUTPUT5
^OUTPUT6
^OUTPUT7
^OUTPUT8

IEC10000284-1-en.vsd
IEC10000284 V1 EN-US

Figure 285: I103USRCMD function block

530 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

14.8.12.4 Signals
PID-3790-INPUTSIGNALS v5

Table 458: I103USRCMD Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of commands

PID-3790-OUTPUTSIGNALS v5

Table 459: I103USRCMD Output signals


Name Type Description
OUTPUT1 BOOLEAN Command output 1
OUTPUT2 BOOLEAN Command output 2
OUTPUT3 BOOLEAN Command output 3
OUTPUT4 BOOLEAN Command output 4
OUTPUT5 BOOLEAN Command output 5
OUTPUT6 BOOLEAN Command output 6
OUTPUT7 BOOLEAN Command output 7
OUTPUT8 BOOLEAN Command output 8

14.8.12.5 Settings
PID-3790-SETTINGS v5

Table 460: I103USRCMD Non group settings (basic)


Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 1 Function type (1-255)
PulseMode Steady - - Pulsed Pulse mode
Pulsed
PulseLength 0.200 - 60.000 s 0.001 0.400 Pulse length
InfNo_1 1 - 255 - 1 1 Information number for output 1
(1-255)
InfNo_2 1 - 255 - 1 2 Information number for output 2
(1-255)
InfNo_3 1 - 255 - 1 3 Information number for output 3
(1-255)
InfNo_4 1 - 255 - 1 4 Information number for output 4
(1-255)
InfNo_5 1 - 255 - 1 5 Information number for output 5
(1-255)
InfNo_6 1 - 255 - 1 6 Information number for output 6
(1-255)
InfNo_7 1 - 255 - 1 7 Information number for output 7
(1-255)
InfNo_8 1 - 255 - 1 8 Information number for output 8
(1-255)

Breaker protection REQ650 531


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

14.8.13 Function commands generic for IEC 60870-5-103 I103GENCMD

14.8.13.1 Functionality GUID-729E9AFD-0468-4BBD-B54A-A6CDCC68A9B2 v3

I103GENCMD is used for transmitting generic commands over IEC 60870-5-103. The function
has two outputs signals CMD_OFF and CMD_ON that can be used to implement double-point
command schemes.

The I103GENCMD component can be configured as either 2 pulsed ON/OFF or 2 steady


ON/OFF outputs. The ON output is pulsed with a command with value 2, while the OFF output
is pulsed with a command value 1. If in steady mode is ON asserted and OFF deasserted with
command 2 and vice versa with command 1. Steady mode is selected by setting
PulseLength=0. The I103GENCMD is retained, and a command in steady mode will be reissued
on restart.

14.8.13.2 Identification
GUID-1933A30C-5214-4116-8CD3-91BD975FACED v1

Function description Function block IEC 60617 ANSI/IEEE C37.2


name identification device number
Function commands generic for IEC I103GENCMD - -
60870-5-103

14.8.13.3 Function block GUID-6EC8453E-0D00-4720-95A6-156C41CA46BB v1

I103GENCMD
BLOCK ^CMD_OFF
^CMD_ON

IEC10000285-1-en.vsd
IEC10000285 V1 EN-US

Figure 286: I103GENCMD function block

14.8.13.4 Signals
PID-3970-INPUTSIGNALS v5

Table 461: I103GENCMD Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of command

PID-3970-OUTPUTSIGNALS v5

Table 462: I103GENCMD Output signals


Name Type Description
CMD_OFF BOOLEAN Command output OFF
CMD_ON BOOLEAN Command output ON

532 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

14.8.13.5 Settings
PID-3970-SETTINGS v5

Table 463: I103GENCMD Non group settings (basic)


Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 1 Function type (1-255)
PulseLength 0.000 - 60.000 s 0.001 0.400 Pulse length
InfNo 1 - 255 - 1 1 Information number for command
output (1-255)

14.8.14 IED commands with position and select for IEC 60870-5-103
I103POSCMD

14.8.14.1 Functionality GUID-1E40B94D-B6A6-42F0-8757-A47B8A3FA3CD v8

I103POSCMD is a transceiver function that monitors activity on its input signals and interprets
any state transition into commands then sent over an established IEC 60870-5-103 link.
Additionally, it listens for general interrogation (GI) requests and replies to those with a GI
response message with the current state of each connected input.

Input POSITION is a double-indication signal, and it is GI enabled. This means that any state
transition, that is to ON, OFF, intermediate and faulty, is reported spontaneously. However,
the intermediate and faulty states may be suppressed by setting the Report Intermediate
Position = Off. See the settings for RS485 and optical serial communication for more
information.

Input SELECT is a single-indication signal, and it is also GI enabled. State transitions to ON and
OFF are reported spontaneously.

When input BLOCK is ON, the function will ignore GI requests and cease all monitoring activity.
Consequently, no transitions will be detected.

The I103POSCMD function is also equipped with three additional commands: Select, Operate
and Cancel. These are hidden in ACT and respond only to the base INF+1, INF+2 and INF+3
respectively. The base INF (Information Number) parameter is an IEC 60870-5-103 identifier
that associates a function in a 103 Master (such as Scada) with its equivalent in the IED.

14.8.14.2 Identification
GUID-ABF81C27-4605-4A15-9CF5-77FF82DE8747 v1

Function description Function block IEC 60617 ANSI/IEEE C37.2


name identification device number
IED commands with position and I103POSCMD - -
select for IEC 60870-5-103

14.8.14.3 Function block GUID-3A31C1F2-1FB5-4DB0-A698-AD3F55738DB1 v1

I103POSCMD
BLOCK
POSITION
SELECT

IEC10000286-1-en.vsd
IEC10000286 V1 EN-US

Figure 287: I103POSCMD function block

Breaker protection REQ650 533


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

14.8.14.4 Signals
PID-6997-INPUTSIGNALS v1

Table 464: I103POSCMD Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of status reporting
POSITION INTEGER 0 Position of controllable object
SELECT BOOLEAN 0 Select of controllable object

14.8.14.5 Settings
PID-6997-SETTINGS v1

Table 465: I103POSCMD Non group settings (basic)


Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 1 Function type
InfNo 160 - 236 - 4 160 Information number for command
output

14.8.15 IED commands with position for IEC 60870-5-103


I103POSCMDV

14.8.15.1 Functionality GUID-CF04D9AC-40BE-46A3-A418-77204D2B0F27 v3

I103POSCMDV is a transceiver function that monitors activity on its input signals and
interprets any state transition into commands sent over an established IEC 60870-5-103 link.
Additionally, it listens for general interrogation (GI) requests, and replies to those with a GI
response message with the current state of each connected input.

Input POSITION is a double-indication signal, and it is GI enabled. This means that any state
transition, that is to ON, OFF, intermediate and faulty, is reported spontaneously. However,
the intermediate and faulty states may be suppressed by setting the Report Intermediate
Position = Off. See the settings for RS485 and optical serial communication for more
information.

When input BLOCK is ON, the function ignores GI requests and ceases all monitoring activity.
Consequently, no transitions will be detected.

14.8.15.2 Identification
GUID-2249B679-03E4-43CC-B690-916246FE6A31 v1

Function description Function block IEC 60617 ANSI/IEEE C37.2


name identification device number
IED direct commands with position I103POSCMDV - -
for IEC 60870-5-103

534 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

14.8.15.3 Function block GUID-031C0F49-BEBD-40FE-A33F-18F1D94BB4B0 v1

I103POSCMDV
BLOCK
POSITION
IEC15000081-2-en.vsdx

IEC15000081 V2 EN-US

Figure 288: I103POSCMDV function block

14.8.15.4 Signals
PID-6578-INPUTSIGNALS v5

Table 466: I103POSCMDV Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of command
POSITION INTEGER 0 Position of controllable object

14.8.15.5 Settings
PID-6578-SETTINGS v6

Table 467: I103POSCMDV Non group settings (basic)


Name Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 1 Function type
InfNo 160 - 209 - 1 160 Information number for command
output

14.8.16 Operation principle IP14407-1 v3

14.8.16.1 General M11874-3 v5

IEC 60870-5-103 is an unbalanced (master-slave) protocol for coded-bit serial communication


exchanging information with a control system, and with a data transfer rate up to 38400 bit/s.
In IEC terminology, a primary station is a master and a secondary station is a slave. The
communication is based on a point-to-point principle. The master must have software that
can interpret IEC 60870-5-103 communication messages.

Introduction to IEC 60870–5–103 protocol M11874-6 v3


IEC 60870-5-103 protocol functionality consists of the following functions:

• Event handling
• Report of analog service values (measurements)
• Fault location
• Command handling

Breaker protection REQ650 535


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

• Autorecloser ON/OFF
• Teleprotection ON/OFF
• Protection ON/OFF
• LED reset
• Characteristics 1 - 4 (Setting groups)
• File transfer (disturbance files)
• Time synchronization

For detailed information about IEC 60870-5-103, refer to the IEC 60870 standard part 5:
Transmission protocols, and to the section 103: Companion standard for the informative
interface of protection equipment.

IEC 60870-5-103 vendor specific implementation M11874-23 v4


The signal and setting tables specify the information types supported by the IEDs with the
communication protocol IEC 60870-5-103 implemented.

The information types are supported when corresponding functions are included in the
protection and control IED.

Be aware of that different cycle times for function blocks must be considered
to ensure correct time stamping.

Commands in control direction M11874-27 v1


Commands in control direction, I103IEDCMD M11874-29 v6
Command block in control direction with defined output signals.

Number of instances: 1

Function type is selected with parameter FunctionType.

Information number is defined for each output signals.

Table 468: I103IEDCMD supported indications


INF Description
19 LED Reset
23 Activate setting group 1
24 Activate setting group 2
25 Activate setting group 3
26 Activate setting group 4

Function commands in control direction, pre-defined I103CMD M11874-53 v6


Function command block in control direction with defined output signals.

Number of instances: 1

Function type is selected with parameter FunctionType.

Information number is defined for each output signals.

536 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

Table 469: Pre-defined I103CMD supported indications


INF Description
16 Auto-recloser on/off
17 Teleprotection on/off
18 Protection on/off

Function commands in control direction, user-defined, I103USRCMD M11874-72 v6


Function command blocks in control direction with user-defined output signals.

Number of instances: 4

Function type for each function block instance in private range is selected with parameter
FunctionType.

Information number must be selected for each output signal. Default values are 1 - 8.

Table 470: I103USRCMD supported indications

INF 1) Description
1 Output signal 01
2 Output signal 02
3 Output signal 03
4 Output signal 04
5 Output signal 05
6 Output signal 06
7 Output signal 07
8 Output signal 08

1) User defined information number

Status M11874-107 v1
Terminal status indications in monitor direction, I103IED M11874-109 v7
Indication block for status in monitor direction with defined IED functions.

Number of instances: 1

Function type is selected with parameter FunctionType.

Information number is defined for each input signals.

Table 471: I103IED supported functions


INF Description
19 LED reset
21 TestMode
22 Local Parameter setting
23 Setting group 1 active
24 Setting group 2 active
25 Setting group 3 active
26 Setting group 4 active

Function status indications in monitor direction, user-defined, I103USRDEF M11874-137 v7

Breaker protection REQ650 537


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

Function indication block in monitor direction with user-defined input signals.

Number of instances: 20

Function type is selected with parameter FunctionType.

Information number is required for each input signal.

Table 472: I103USRDEF Information number default values


INF Description GI TYP COT
11) Input signal 01 x/- 1/2 1,7,(9)

2* Input signal 02 x/- 1/2 1,7,(9)


3* Input signal 03 x/- 1/2 1,7,(9)
4* Input signal 04 x/- 1/2 1,7,(9)
5* Input signal 05 x/- 1/2 1,7,(9)
6* Input signal 06 x/- 1/2 1,7,(9)
7* Input signal 07 x/- 1/2 1,7,(9)
8* Input signal 08 x/- 1/2 1,7,(9)

1) * User defined information number

Supervision indications in monitor direction, I103SUPERV M11874-171 v7


Indication block for supervision in monitor direction with defined functions.

Number of instances: 1

Function type is selected with parameter FunctionType.

Information number is defined for output signals.

Table 473: I103SUPERV supported functions


INF Description TYP GI COT
32 Measurand supervision I 1 Y 1,7,9
33 Measurand supervision U 1 Y 1,7,9
37 I>>back-up operation 1 Y 1,7,9
38 VT fuse failure 1 Y 1,7,9
46 Group warning 1 Y 1,7,9
47 Group alarm 1 Y 1,7,9

Earth fault indications in monitor direction, I103EF M11874-199 v8


Indication block for earth fault in monitor direction with defined functions.

Number of instances: 1

Function type is selected with parameter FunctionType.

Information number is defined for each output signal.

Table 474: I103EF supported indications


INF Description
51 Earth fault forward
52 Earth fault reverse

538 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

Autorecloser indications in monitor direction, I103AR M11874-363 v6


Indication block for autorecloser in monitor direction with defined functions.

Number of instances: 1

Function type is selected with parameter FunctionType.

Information number is defined for each output signal.

Table 475: I103AR supported indications


INF Description
16 Autorecloser active
128 CB on by Autorecloser
130 Autorecloser blocked

Function status fault protection for IEC 60870-5-103, I103FLTPROT GUID-E9DF9410-F570-4F85-9063-C76D1D4A0668 v6


Number of instances: 1

Function type is selected with parameter FunctionType.

Information number is defined for each input signal.

Table 476: I103FLTPROT supported functions


INF Description TYP GI COT
64 Start phase L1 2 Y 1,7,9
65 Start phase L2 2 Y 1,7,9
66 Start phase L3 2 Y 1,7,9
67 Start residual current IN 2 Y 1,7,9
68 Trip general 2 N 1,7
69 Trip phase L1 2 N 1,7
70 Trip phase L2 2 N 1,7
71 Trip phase L3 2 N 1,7
72 Back up trip I>> 2 N 1,7
73 Fault location in ohm 4 N 1,7
74 Forward/line 2 N 1,7
75 Reverse/busbar 2 N 1,7
76 Signal transmitted 2 N 1,7
77 Signal received 2 N 1,7
78 Zone 1 2 N 1,7
79 Zone 2 2 N 1,7
80 Zone 3 2 N 1,7
81 Zone 4 2 N 1,7
82 Zone 5 2 N 1,7
83 Zone 6 2 N 1,7
84 Start general 2 Y 1,7,9
85 Breaker failure 2 N 1,7
86 Trip measuring system phase 2 N 1,7
L1
Table continues on next page

Breaker protection REQ650 539


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

INF Description TYP GI COT


87 Trip measuring system phase 2 N 1,7
L2
88 Trip measuring system phase 2 N 1,7
L3
89 Trip measuring system neutral 2 N 1,7
N
90 Over current trip, stage low 2 N 1,7
91 Over current trip, stage high 2 N 1,7
92 Earth-fault trip, stage low 2 N 1,7
93 Earth-fault trip, stage high 2 N 1,7

Measurands M11874-382 v2
Function blocks in monitor direction for input measurands. Typically connected to monitoring
function, for example to power measurement CVMMXN.

Measurands in public range, I103MEAS M11874-385 v8


Number of instances: 1

The IED reports all valid measuring types depending on connected signals.

Upper limit for measured currents, active/reactive-power is 2.4 times rated value.

Upper limit for measured voltages and frequency is 1.2 times rated value.

The upper limit is the maximum value that can be encoded into the ASDU (Application Service
Data Unit). Any value higher than this value will be tagged as OVERFLOW. The factors 1.2 and
2.4 are taken from the 103 standard and require that a rated value to use as base exists, and
then use 1.2 or 2.4 times <rated> as maxVal. You can use 2.4 times rated as maxVal, but as
there is no way to propagate value to client, the use of a scale factor on <rated> does not
make much difference.

You can configure client:client-scaled-max ::= 1.2 * <rated> or client-scaled-


max ::= 1.0 * <maxVal>

If the client has a hard-coded gain of 1.2 * <rated> then client-scaled-max ::= 1.2 times
<maxVal>/1.2

Resolution is <maxVal> / 4095 and hence the lowest possible maxVal yields the best accuracy.

Table 477: I103MEAS supported indications


INF Description
148 IL1
144, 145, IL2
146, 148
148 IL3
147 IN, Neutral current
148 UL1
148 UL2
148 UL3
145, 146 UL1-UL2
147 UN, Neutral voltage
Table continues on next page

540 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

INF Description
146, 148 P, active power
146, 148 Q, reactive power
148 f, frequency

Measurands in private range, I103MEASUSR M11874-431 v5


Number of instances: 3

Function type parameter for each block in private range.

Information number must be selected for measurands.

Table 478: I103MEASUSR supported indications


INF FUN GI TYP COT Description
*1) *2) No, polled *3) 2,7 Meas1
with CL2
* * No, polled * 2,7 Meas2
with CL2
* * No, polled * 2,7 Meas3
with CL2
* * No, polled * 2,7 Meas4
with CL2
* * No, polled * 2,7 Meas5
with CL2
* * No, polled * 2,7 Meas6
with CL2
* * No, polled * 2,7 Meas7
with CL2
* * No, polled * 2,7 Meas8
with CL2
* * No, polled * 2,7 Meas9
with CL2

1) * User defined information value (PARAM.3)


2) * User defined information value (PARAM.2)
3) 9 = Measurands II, Format = Measurand II (7.3.1.8 in IEC 60870-5-103:1997), semantics per IE is defined by
semantics of connected source.

<Number of information elements> is defined by index of first input not connected.

Example: Input1, Input2, and Input4 are connected, Input3 is not connected.

<Number of information elements> will be 3 (Input3 NOT connected) -1 = 2, that is, only Input1
and Input2 will be transmitted.

Disturbance recordings M11874-467 v7


The following elements are used in the ASDUs (Application Service Data Units) defined in the
standard.

Analog signals, 40-channels: the channel number for each channel has to be specified.
Channels used in the public range are 1 to 8 and with:

• IL1 connected to channel 1 on disturbance function block A1RADR


• IL2 connected to channel 2 on disturbance function block A1RADR
• IL3 connected to channel 3 on disturbance function block A1RADR
• IN connected to channel 4 on disturbance function block A1RADR

Breaker protection REQ650 541


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

• UL1E connected to channel 5 on disturbance function block A1RADR


• UL2E connected to channel 6 on disturbance function block A1RADR
• UL3E connected to channel 7 on disturbance function block A1RADR
• UEN connected to channel 8 on disturbance function block A1RADR

Channel number used for the remaining 32 analog signals are numbers in the private range 64
to 95.

Binary signals, 128-channels: for each channel the user can specify a FUNCTION TYPE and an
INFORMATION NUMBER.
M11874-629 v7
Disturbance upload

All analog and binary signals that are recorded with disturbance recorder can be reported to
the master. The last eight disturbances that are recorded are available for transfer to the
master. A successfully transferred disturbance (acknowledged by the master) will not be
reported to the master again.

When a new disturbance is recorded by the IED a list of available recorded disturbances will be
sent to the master, an updated list of available disturbances can be sent whenever something
has happened to disturbances in this list. For example, when a disturbance is deleted (by other
client, for example, SPA) or when a new disturbance has been recorded or when the master has
uploaded a disturbance.

Deviations from the standard

Information sent in the disturbance upload is specified by the standard; however, some of the
information are adapted to information available in disturbance recorder in the IED series.

This section describes all data that is not exactly as specified in the standard.

ASDU23

In ‘list of recorded disturbances’ (ASDU23) an information element named SOF (status of fault)
exists. This information element consists of 4 bits and indicates whether:

• Bit TP: the protection equipment has tripped during the fault
• Bit TM: the disturbance data are currently being transmitted
• Bit TEST: the disturbance data have been recorded during normal operation or test mode.
• Bit OTEV: the disturbance data recording has been initiated by another event than start

The only information that is easily available is test-mode status. The other information is
always set (hard coded) to:

TP Recorded fault with trip. [1]


TM Disturbance data waiting for transmission [0]
OTEV Disturbance data initiated by other events [1]

Another information element in ASDU23 is the FAN (fault number). According to the standard
this is a number that is incremented when a protection function takes action. FAN is equal to
disturbance number, which is incremented for each disturbance.

ASDU26 / ASDU31

When a disturbance has been selected by the master by sending ASDU24, the protection
equipment answers by sending ASDU26, which contains an information element named NOF
(number of grid faults). This number must indicate fault number in the power system,that is, a

542 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

fault in the power system with several trip and auto-reclosing has the same NOF (while the
FAN must be incremented). NOF is just as FAN, equal to disturbance number.

Interoperability, physical layer M11874-482 v4

Supported
Electrical Interface
EIA RS-485 Yes
number of loads 32
Optical interface
glass fiber Yes
plastic fiber
Transmission speed
9600 bit/s Yes
19200 bit/s Yes
Link Layer
DFC-bit used Yes
Connectors
connector F-SMA No
connector BFOC/2.5 Yes

Interoperability, application layer M11874-524 v3

Supported
Selection of standard ASDUs in monitoring direction
ASDU Yes
1 Time-tagged message Yes
2 Time-tagged message with rel. time Yes
3 Measurands I Yes
4 Time-tagged message with rel. time Yes
5 Identification Yes
6 Time synchronization Yes
8 End of general interrogation Yes
9 Measurands II Yes
10 Generic data No
11 Generic identification No
23 List of recorded disturbances Yes
26 Ready for transm. of disturbance data Yes
27 Ready for transm. of a channel Yes
28 Ready for transm of tags Yes
29 Transmission of tags Yes
30 Transmission fo disturbance data Yes
31 End of transmission Yes
Selection of standard ASDUs in control direction
ASDU Yes
Table continues on next page

Breaker protection REQ650 543


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

Supported
6 Time synchronization Yes
7 General interrogation Yes
10 Generic data No
20 General command Yes
21 Generic command Yes
24 Order for disturbance data transmission Yes
25 Acknowledgement for distance data Yes
transmission
Selection of basic application functions
Test mode No
Blocking of monitoring direction Yes
Disturbance data Yes
Private data Yes
Generic services No

14.8.16.2 Communication ports M11874-626 v4

The serial communication module (SLM) is used for SPA/IEC 60870-5-103/DNP and LON
communication. This module is a mezzanine module, and is placed assembled on the
Numerical module (NUM). The serial communication module can have connectors for two
plastic fiber cables (snap-in) or two glass fiber cables (ST, bayonet) or a combination of plastic
and glass fiber. Three different types are available depending on type of fiber.

The incoming optical fiber is connected to the RX receiver input, and the outgoing optical fiber
to the TX transmitter output. When the fiber optic cables are laid out, pay special attention to
the instructions concerning the handling and connection of the optical fibers. The module is
identified with a number on the label on the module.

14.8.17 Technical data IP14417-1 v1

M11921-1 v4

Table 479: IEC 60870-5-103 communication protocol


Function Value
Protocol IEC 60870-5-103
Communication speed 9600, 19200 Bd

14.9 MULTICMDRCV and MULTICMDSND SEMOD119881-1 v3

GUID-1A6E066C-6399-4D37-8CA5-3074537E48B2 v3

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Multiple command and receive MULTICMDRCV - -
Multiple command and send MULTICMDSND - -

544 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

14.9.1 Functionality M14790-3 v5

The IED provides two function blocks enabling several IEDs to send and receive signals via the
interbay bus. The sending function block, MULTICMDSND, takes 16 binary inputs. LON enables
these to be transmitted to the equivalent receiving function block, MULTICMDRCV, which has
16 binary outputs.

14.9.2 Design SEMOD119958-1 v1

14.9.2.1 General M14792-3 v3

The common behavior for all 16 outputs of the MULTICMDRCV is set to either of two modes:
Steady or Pulse.

• 1 = Steady: This mode simply forwards the received signals to the binary outputs.
• 2 = Pulse: When a received signal transitions from 0 (zero) to 1 (one), a pulse with a
duration of exactly one execution cycle is triggered on the corresponding binary output.
This means that no connected function block may have a cycle time that is higher than the
execution cycle time of the particular MULTICMDRCV instance.

14.9.3 Function block SEMOD119978-1 v1

SEMOD119976-5 v2

MULTICMDRCV
BLOCK ERROR
NEWDATA
OUTPUT1
OUTPUT2
OUTPUT3
OUTPUT4
OUTPUT5
OUTPUT6
OUTPUT7
OUTPUT8
OUTPUT9
OUTPUT10
OUTPUT11
OUTPUT12
OUTPUT13
OUTPUT14
OUTPUT15
OUTPUT16
VALID

IEC06000007-2-en.vsd
IEC06000007 V2 EN-US

Figure 289: MULTICMDRCV function block

Breaker protection REQ650 545


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

SEMOD120009-4 v2

MULTICMDSND
BLOCK ERROR
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16

IEC06000008-2-en.vsd
IEC06000008 V2 EN-US

Figure 290: MULTICMDSND function block

14.9.4 Signals SEMOD119963-1 v2

PID-400-INPUTSIGNALS v10

Table 480: MULTICMDRCV Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function

PID-399-INPUTSIGNALS v10

Table 481: MULTICMDSND Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block of function
INPUT1 BOOLEAN 0 Input 1
INPUT2 BOOLEAN 0 Input 2
INPUT3 BOOLEAN 0 Input 3
INPUT4 BOOLEAN 0 Input 4
INPUT5 BOOLEAN 0 Input 5
INPUT6 BOOLEAN 0 Input 6
INPUT7 BOOLEAN 0 Input 7
INPUT8 BOOLEAN 0 Input 8
INPUT9 BOOLEAN 0 Input 9
INPUT10 BOOLEAN 0 Input 10
INPUT11 BOOLEAN 0 Input 11
INPUT12 BOOLEAN 0 Input 12
INPUT13 BOOLEAN 0 Input 13
INPUT14 BOOLEAN 0 Input 14
INPUT15 BOOLEAN 0 Input 15
INPUT16 BOOLEAN 0 Input 16

546 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

PID-400-OUTPUTSIGNALS v10

Table 482: MULTICMDRCV Output signals


Name Type Description
ERROR BOOLEAN MultiReceive error
NEWDATA BOOLEAN New data is received
OUTPUT1 BOOLEAN Output 1
OUTPUT2 BOOLEAN Output 2
OUTPUT3 BOOLEAN Output 3
OUTPUT4 BOOLEAN Output 4
OUTPUT5 BOOLEAN Output 5
OUTPUT6 BOOLEAN Output 6
OUTPUT7 BOOLEAN Output 7
OUTPUT8 BOOLEAN Output 8
OUTPUT9 BOOLEAN Output 9
OUTPUT10 BOOLEAN Output 10
OUTPUT11 BOOLEAN Output 11
OUTPUT12 BOOLEAN Output 12
OUTPUT13 BOOLEAN Output 13
OUTPUT14 BOOLEAN Output 14
OUTPUT15 BOOLEAN Output 15
OUTPUT16 BOOLEAN Output 16
VALID BOOLEAN Output data is valid

PID-399-OUTPUTSIGNALS v10

Table 483: MULTICMDSND Output signals


Name Type Description
ERROR BOOLEAN MultiSend error

14.9.5 Settings SEMOD119927-1 v2

PID-400-SETTINGS v10

Table 484: MULTICMDRCV Non group settings (basic)


Name Values (Range) Unit Step Default Description
tMaxCycleTime 0.050 - 200.000 s 0.001 11.000 Maximum cycle time between
receptions of input data
tMinCycleTime 0.000 - 200.000 s 0.001 0.000 Minimum cycle time between
receptions of input data
Mode Steady - - Steady Mode for output signals
Pulsed
tPulseTime 0.000 - 60.000 s 0.001 0.200 Pulse length for multi command
outputs

Breaker protection REQ650 547


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 14 1MRK 505 384-UEN C
Station communication

PID-399-SETTINGS v10

Table 485: MULTICMDSND Non group settings (basic)


Name Values (Range) Unit Step Default Description
tMaxCycleTime 0.000 - 200.000 s 0.001 5.000 Maximum time interval between
transmission of output data
tMinCycleTime 0.000 - 200.000 s 0.001 0.000 Minimum time interval between
transmission of output data

14.9.6 Operation principle M14793-3 v3

There are 10 instances of the MULTICMDSND function block. The first two are fast (8 ms cycle
time) while the others are slow (100 ms cycle time). Each instance has 16 binary inputs, to
which 16 independent signals can be connected. Connected signals are sent through
MULTICMDSND to the receiving equivalent, MULTICMDRCV, located on a different IED.

The MULTICMDRCV function block has 16 binary outputs, all controlled through the command
block of one or many MULTICMDSND function blocks. There are 60 instances of the
MULTICMDRCV where the first 12 are fast (8 ms), and the others are slow (100 ms).
Additionally, the MULTICMDRCV has a supervision function, which sets the output connector
"VALID" to 0 (zero) if its block does not receive any data within the time defined by
tMaxCycleTime.

LON connections are established using LON network tool (LNT).

14.10 Activity logging parameters ACTIVLOG

14.10.1 Activity logging ACTIVLOG GUID-BED7C3D6-6BE3-4DAC-84B3-92239E819CC0 v1

ACTIVLOG contains all settings for activity logging.

There can be 6 external log servers to send syslog events to. Each server can be configured
with IP address; IP port number and protocol format. The format can be either syslog (RFC
5424) or Common Event Format (CEF) from ArcSight.

14.10.2 Settings
PID-6908-SETTINGS v2

Table 486: ACTIVLOG Non group settings (basic)


Name Values (Range) Unit Step Default Description
ExtLogSrv1Type Off - - Off External log server 1 type
SYSLOG UDP/IP
SYSLOG TCP/IP
CEF TCP/IP
ExtLogSrv1Port 1 - 65535 - 1 514 External log server 1 port number
ExtLogSrv1IP 0 - 18 IP 1 127.0.0.1 External log server 1 IP-address
Address
ExtLogSrv2Type Off - - Off External log server 2 type
SYSLOG UDP/IP
SYSLOG TCP/IP
CEF TCP/IP
ExtLogSrv2Port 1 - 65535 - 1 514 External log server 2 port number
Table continues on next page

548 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 14
Station communication

Name Values (Range) Unit Step Default Description


ExtLogSrv2IP 0 - 18 IP 1 127.0.0.1 External log server 2 IP-address
Address
ExtLogSrv3Type Off - - Off External log server 3 type
SYSLOG UDP/IP
SYSLOG TCP/IP
CEF TCP/IP
ExtLogSrv3Port 1 - 65535 - 1 514 External log server 3 port number
ExtLogSrv3IP 0 - 18 IP 1 127.0.0.1 External log server 3 IP-address
Address
ExtLogSrv4Type Off - - Off External log server 4 type
SYSLOG UDP/IP
SYSLOG TCP/IP
CEF TCP/IP
ExtLogSrv4Port 1 - 65535 - 1 514 External log server 4 port number
ExtLogSrv4IP 0 - 18 IP 1 127.0.0.1 External log server 4 IP-address
Address
ExtLogSrv5Type Off - - Off External log server 5 type
SYSLOG UDP/IP
SYSLOG TCP/IP
CEF TCP/IP
ExtLogSrv5Port 1 - 65535 - 1 514 External log server 5 port number
ExtLogSrv5IP 0 - 18 IP 1 127.0.0.1 External log server 5 IP-address
Address
ExtLogSrv6Type Off - - Off External log server 6 type
SYSLOG UDP/IP
SYSLOG TCP/IP
CEF TCP/IP
ExtLogSrv6Port 1 - 65535 - 1 514 External log server 6 port number
ExtLogSrv6IP 0 - 18 IP 1 127.0.0.1 External log server 6 IP-address
Address

Breaker protection REQ650 549


Technical manual
© Copyright 2017 ABB. All rights reserved
550
1MRK 505 384-UEN C Section 15
Security

Section 15 Security
15.1 Authority check ATHCHCK

15.1.1 Identification
GUID-FBEF319B-94E6-41FB-BB9F-D870E0425128 v2

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Authority check ATHCHCK - -

15.1.2 Functionality SEMOD117051-23 v7

To safeguard the interests of our customers, both the IED and the tools that are accessing the
IED are protected, by means of authorization handling. The authorization handling of the IED
and the PCM600 is implemented at both access points to the IED:

• local, through the local HMI


• remote, through the communication ports

The IED users can be created, deleted and edited with PCM600 IED user management tool.

IEC12000202-2-en.vsd
IEC12000202 V2 EN-US

Figure 291: PCM600 user management tool

Breaker protection REQ650 551


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 505 384-UEN C
Security

15.1.3 Operation principle GUID-B555EDD0-BAF1-4F0E-9162-BDB3A3468CF2 v9

There are different levels (or types) of users that can access or operate different areas of the
IED and tools functionality. The pre-defined user types are given in Table 487.

Ensure that the user logged on to the IED has the access required when writing
particular data to the IED from PCM600.

The meaning of the legends used in the table:

• R= Read
• W= Write
• - = No access rights

Table 487: Pre-defined user types


Access rights System Protection Design User
Guest Super User SPA Guest Operator Engineer Engineer Administrato
r
Basic setting possibilities R R/W R R/W R/W R/W R
(change setting group, control
settings, limit supervision)
Advanced setting possibilities R R/W R R R/W R/W R
(for example protection
settings)
Basic control possibilities R R/W R/W R/W R/W R/W R
(process control, no bypass)
Advanced control possibilities R R/W R/W R/W R/W R/W R
(process control including
interlock trigg)
Basic command handling (for R R/W R R/W R/W R/W R
example clear LEDs, manual
trigg)
Advanced command handling R R/W R R R/W R/W R/W
(for example clear disturbance
record)
Basic configuration possibilities R R/W R R R R/W R/W
(I/O-configuration in SMT)
Advanced configuration R R/W R R R R/W R/W
possibilities (application
configuration including SMT,
GDE and CMT)
File loading (database loading - R/W - - - R/W R/W
from XML-file)
File dumping (database - R/W - - - R/W R/W
dumping to XML-file)
File transfer (FTP file transfer) - R/W - R/W R/W R/W R/W
File transfer (limited) (FTP file R R/W R R/W R/W R/W R/W
transfer)
File Transfer (SPA File Transfer) - R/W - - - R/W -
Table continues on next page

552 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 15
Security

Access rights System Protection Design User


Guest Super User SPA Guest Operator Engineer Engineer Administrato
r
Database access for normal R R/W R R/W R/W R/W R/W
user
User administration (user R R/W R R R R R/W
management – FTP File
Transfer)
User administration (user - R/W - - - - -
management – SPA File
Transfer)

The IED users can be created, deleted and edited only with the IED User Management within
PCM600. The user can only LogOn or LogOff on the local HMI on the IED, there are no users,
groups or functions that can be defined on local HMI.

If the IED is Central Account Management enabled, users can only be created,
deleted or edited in the Central Account Management server. In that case, only
the user rights can be edited using the PCM600 tool. See Cyber Security
Deployment Guidelines manual.

Only characters A - Z, a - z and 0 - 9 should be used in user names and


passwords.
The maximum of characters in a password is 18.

At least one user must be included in the UserAdministrator group to be able to


write users, created in PCM600, to IED.

SEMOD176296-5 v10
At delivery the default user is the SuperUser. No Log on is required to operate the IED until a
user has been created with the IED User Management..

Once a user is created and downloaded to the IED, that user can perform a Log on, introducing
the password assigned in the tool.

If there is no user created, an attempt to log on will display a message box: “No user defined!”

If one user leaves the IED without logging off, then after the timeout (set in Main menu/
Settings/General Settings/HMI/Screen/Display Timeout) elapses, the IED returns to Guest
state, when only reading is possible. The display time out is set to 10 minutes at delivery.

If there are one or more users created with the IED User Management and downloaded into the
IED, then, when a user intentionally attempts a Log on or when the user attempts to perform
an operation that is password protected, the Log on window will appear.

The cursor is focused on the User identity field, so upon pressing the key, the user can
change the user name, by browsing the list of users, with the “up” and “down” arrows. After
choosing the right user name, the user must press the “E” key again. When it comes to
password, upon pressing the key, the following character will show up: “$”. After all the
letters are introduced (passwords are case sensitive) choose OK and press the key again.

If everything is alright at a voluntary Log on, the local HMI returns to the Authorization screen.
If the Log on is OK, when required to change for example a password protected setting, the

Breaker protection REQ650 553


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 505 384-UEN C
Security

local HMI returns to the actual setting folder. If the Log on has failed, then the Log on window
opens again, until either the user makes it right or presses “Cancel”.

15.1.3.1 Authorization with Central Account Management enabled IED GUID-1A836989-5D89-4F3D-B3A2-3BABCDFFB440 v2

The users, their roles and rights are created, deleted and edited only in the Central Account
Management server (SDM600). However, the user rights can be edited in the IED by using the
PCM600 user tool.

One user can have one or several user roles. By default, the users in Table 488 are created in
the IED, and when creating new users in the SDM600 server, the predefined roles from Table
489 can be used.

At delivery, the IED user has full access as SuperUser when using the LHMI and
as Administrator when using FTP or PCM600 until Central Account
Management is activated.

Table 488: Default users


User name User rights
SuperUser Full rights, only presented in LHMI. LHMI is logged on by default until other users are
defined
Guest Only read rights, only presented in LHMI. LHMI is logged on by default when other users are
defined (same as VIEWER)
Administrator Full rights. Password: Administrator. This user has to be used when reading out
disturbances with third party FTP-client.

Table 489: Predefined user roles according to IEC 62351-8


User roles Role explanation User rights
VIEWER Viewer Can read parameters and browse the menus from LHMI
OPERATOR Operator Can read parameters and browse the menus as well as perform
control actions
ENGINEER Engineer Can create and load configurations and change settings for the IED
and also run commands and manage disturbances
INSTALLER Installer Can load configurations and change settings for the IED
SECADM Security Can change role assignments and security settings. Can deploy
administrator certificates.
SECAUD Security auditor Can view audit logs
RBACMNT RBAC Can change role assignment
management
ADMINISTRATOR Administrator Sum of all rights for SECADM, SECAUD and RBACMNT
rights

This User role is vendor specific and not defined in


IEC 62351–8

Changes in user management settings do not cause an IED reboot.

554 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 15
Security

The PCM600 tool caches the login credentials after successful login for 15
minutes. During that time no more login will be necessary.

The successfully activation of Central Account Management will disable built-in users or
remove all local created users from PCM600.

Management of user credentials and roles is handled on the central Account Management
server e.g. SDM600 The IED employs two strategies to ensure availability of the authentication
system even if there is a problem with the network or authentication server:

• A substation can be equipped with two redundant authentication servers operating in a


hot standby mode.
• If configured by the security administrator, the IED itself maintains a local replica in the
database with selected users. This database is periodically updated with data from the
server and used as fallback if none of the servers are reachable.

Note that not all users in the SDM600 server are part of the replica. There might be users that
are not assigned to any replication group. IED only replicates those users which are part of
replication group configured in the IED.

This replication can be disabled using PCM600 by the security administrator, which means
that the IED will forward login requests to the SDM600 for authorization and in case of
problems with the network users will not be able to log in to the IED.

If user replication has been disabled in a CAM-enabled IED and if


communication with SDM600 is lost, access to that IED will be denied until
communication is re-established.

All communication between the central management and the IEDs is protected using secure
communication. Customers using SDM600 are required to generate and distribute certificates
during the engineering process of the substation. These certificates ensure mutual trust
between IED and for example SDM600, FTP, PCM600 and other system.

Table 490: Authority-related IED functions


Function Description
Authority status This function is an indication function block for user logon activity.
ATHSTAT User denied attempt to logon and user successful logon are reported.
Authority check To safeguard the interests of our customers, both the IED and the tools that are
ATHCHCK accessing the IED are protected, by means of authorization handling. The
authorization handling of the IED and the PCM600 is implemented at both access
points to the IED:

• local, through the local HMI


• remote, through the communication ports

The IED users can be created, deleted and edited only in the CAM server.
Authority This function enables/disables the maintenance menu. It also controls the
management maintenance menu logon time out.
AUTHMAN

For more information on the functions Authority Management (AUTHMAN), Authority Status
(ATHSTAT), and Authority Check (ATHCHCK) functions, refer to chapter “Basic IED functions”
in the Technical Manual.

Breaker protection REQ650 555


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 505 384-UEN C
Security

15.2 Authority management AUTHMAN

15.2.1 Identification
GUID-7925E6A3-301D-44A5-982F-167805EEA473 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Authority management AUTHMAN - -

15.2.2 AUTHMAN GUID-AF7EDB44-42AA-4D49-BFA0-DA6A9B43973E v1

This function enables/disables the maintenance menu. It also controls the maintenance menu
log on time out.

15.2.3 Settings
PID-6837-SETTINGS v2

Table 491: AUTHMAN Non group settings (basic)


Name Values (Range) Unit Step Default Description
MaintMenuEnable Disable - - Enable Maintenance menu enable
Enable
AuthTimeout 600 - 3600 s 600 600 Authority blocking timeout

15.3 FTP access with password FTPACCS

15.3.1 Identification
GUID-C037D0B0-1AA0-4592-9293-92C7EDED3261 v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
FTP access with SSL FTPACCS - -

15.3.2 FTP access with TLS, FTPACCS GUID-9E64EA68-6FA9-4576-B5E9-92E3CC6AA7FD v4

The FTP Client defaults to the best possible security mode when trying to negotiate with TLS.

The automatic negotiation mode acts on configured port number 21 and server features, it
tries to negotiate with explicit TLS via AUTH TLS. If the specified port is any other, it tries to
negotiate in a similar way.

Using FTP without TLS encryption gives the FTP client reduced capabilities. This mode is only
for accessing disturbance recorder data from the IED.

If normal FTP is required to read out disturbance recordings, create a specific


account for this purpose with rights only to do File transfer. The password of
this user will be exposed in clear text on the wire.

556 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 15
Security

The setting of FTP to OFF on an access point does not switch-off FTP as the service is still
used by PCM600 and FST. So to completely switch off the port number 21 access the following
parameters must be set to OFF.

• FTP = OFF
• PCMAccess = OFF
• FSTAccess = OFF

15.3.3 Settings
PID-6703-SETTINGS v3

Table 492: FTPACCS Non group settings (basic)


Name Values (Range) Unit Step Default Description
SSLMode FTP+FTPS - - FTPS Support for AUTH TLS/SSL
FTPS
TCPPortFTP 1 - 65535 - 1 21 TCP port for FTP and FTP with Explicit
SSL
PasvPortStart 0 - 65515 - 1 49200 First TCP data port for PASV
PasvPortEnd 0 - 65535 - 1 49232 Last TCP data port for PASV

15.4 Authority status ATHSTAT

15.4.1 Identification
GUID-79C63688-4D7D-4954-AC3C-B9484D084F6F v1

Function description IEC 61850 IEC 60617 ANSI/IEEE C37.2


identification identification device number
Authority status ATHSTAT - -

15.4.2 Functionality SEMOD158529-5 v6

Authority status ATHSTAT function is an indication function block for user log-on activity.

User denied attempt to log-on and user successful log-on are reported.

15.4.3 Function block SEMOD158547-4 v4

ATHSTAT
USRBLKED
LOGGEDON

IEC06000503-2-en.vsd
IEC06000503 V2 EN-US

Figure 292: ATHSTAT function block

Breaker protection REQ650 557


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 505 384-UEN C
Security

15.4.4 Signals
PID-3773-OUTPUTSIGNALS v6

Table 493: ATHSTAT Output signals


Name Type Description
USRBLKED BOOLEAN At least one user is blocked by invalid password
LOGGEDON BOOLEAN At least one user is logged on

GUID-87CF079A-64C8-46AE-B7E4-A0B2EEAC92E9 v1

The output signal USRBLKED is not valid if the IED is Centralized Account
Management enabled.

15.4.5 Settings GUID-ECE18AA9-15CC-4522-AA31-78C4F0F052E4 v4

The function does not have any parameters available in Local HMI or in Protection and Control
IED Manager (PCM600)

15.4.6 Operation principle SEMOD158543-4 v6

Authority status (ATHSTAT) function informs about two events related to the IED and the user
authorization:

• the fact that at least one user has tried to log on wrongly into the IED and it was blocked
(the output USRBLKED)
• the fact that at least one user is logged on (the output LOGGEDON)

Whenever one of the two events occurs, the corresponding output (USRBLKED or LOGGEDON)
is activated. The output can for example, be connected on Event (EVENT) function block for
LON/SPA.The signals are also available on IEC 61850 station bus.

15.5 Self supervision with internal event list INTERRSIG IP1721-1 v2

15.5.1 Functionality M11399-3 v8

Self supervision with internal event list function listens and reacts to internal system events,
generated by the different built-in self-supervision elements. The internal events are saved in
an internal event list presented on the LHMI and in PCM600 event viewer tool.

15.5.2 Function block M11402-3 v6

558 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 15
Security

INTERRSIG
FAIL
WARNING
TSYN CERR
RTCERR
STUPBLK

IEC09000787-2-en.vsdx

IEC09000787 V2 EN-US

Figure 293: INTERRSIG function block

15.5.3 Signals IP9674-1 v2

PID-4077-OUTPUTSIGNALS v6

Table 494: INTERRSIG Output signals


Name Type Description
FAIL BOOLEAN Internal fail
WARNING BOOLEAN Internal warning
TSYNCERR BOOLEAN Time synchronization error
RTCERR BOOLEAN Real time clock error
STUPBLK BOOLEAN Application startup block

15.5.4 Settings ABBD8E15533 v4

The function does not have any parameters available in the local HMI or PCM600.

15.5.5 Operation principle IP11943-1 v2

M11401-3 v13
The self-supervision operates continuously and includes:

• Normal micro-processor watchdog function.


• Checking of digitized measuring signals.
• Other alarms, for example hardware and time synchronization.

The self-supervision function status can be monitored from the local HMI or from the Event
Viewer in PCM600.

Under the Diagnostics menu in the local HMI, the actual information from the self-supervision
function can be reviewed. The information can be found under Main menu/Diagnostics/
Internal events or Main menu/Diagnostics/IED status/General. The information from the
self-supervision function is also available in the Event Viewer in PCM600.

Breaker protection REQ650 559


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 505 384-UEN C
Security

IEC15000414-2-en.vsdx
IEC15000414 V2 EN-US

Figure 294: IED general status in local HM


The self supervision records internal signal changes in an internal event list. A maximum of 40
internal events are stored in a first-in, first-out manner.

GUID-B481701F-05B4-4B29-83D4-18F13886FEBE V1 EN-US

Figure 295: Self-supervision event list in local HMI


A self-supervision summary can be obtained by means of an output relay with potential free
alarm contact (INTERNAL FAIL) located on the power supply module. This contact is closed
when the IED either does not have auxiliary power, or when one or more error conditions are
present in the IED (for example harware error).

Some output signals are available from the INTERRSIG function block. The signals from this
function block are sent as events via IEC 61850 to the station level of the control system. These
signals can also be connected to binary outputs for signalization via output relays or they can
be used as conditions for other functions if required/desired.

Individual error signals from I/O modules can be obtained from respective module in the
Signal Matrix tool. Error signals from time synchronization can be obtained from the
INTERRSIG function block via two outputs TSYNCERR and RTCERR .

15.5.5.1 Internal signals M11401-173 v11

Self supervision provides several status signals that give information about the internal status
of the IED. For this reason they are also called internal signals. These internal signals , available
on local HMI under Main menu/Diagnostics/IED status/General, can be divided into two
groups.

560 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 15
Security

• Standard signals are always presented in the IED, see table 495.
• Hardware dependent internal signals are collected depending on the hardware
configuration, see table 496.

Table 495: Self-supervision's standard internal signals


Name of signal Description Displayed on Reasons for activation
local HMI as
FAIL Internal Fail Internal fail This signal will be active if one or more of the
status following internal signals are active; LMDERROR,
WATCHDOG, APPERROR, RTEERROR, or any of the HW
dependent signals
WARNING Internal Internal This signal will be active if one or more of the
Warning warning following internal signals are active; RTCERROR,
status IEC61850ERROR
RTCERROR Real Time Real time This signal will be active when there is a hardware
Clock clock error with the real time clock.
status
TIMESYNCHERROR Time Time synch This signal will be active when the source of the time
Synchroniza synchronization is lost, or when the time system has
tion status to make a time reset.
RTEERROR Runtime Runtime This signal will be active if the Runtime Engine failed to
Execution execution do some actions with the application threads. The
Error status actions can be loading of settings or parameters for
components, changing of setting groups, loading or
unloading of application threads.
IEC61850ERROR IEC 61850 IEC61850 This signal will be active if the IEC 61850 stack did not
Error status succeed in some actions like reading IEC 61850
configuration, startup, for example
DNP3 DNP3 error DNP3 This signal will be active when DNP3 detects any
status configuration error during startup.
LMDERROR LON/Mip SLM301 LON network interface, MIP/DPS, is in an
Device Error unrecoverable error state.
status
APPERROR Runtime Runtime App This signal will be active if one or more of the
Application Error application threads are not in the state that Runtime
Error status Engine expects. The states can be CREATED,
INITIALIZED, RUNNING, for example
SETCHGD Settings Settings This signal will generate an Internal Event to the
changed changed Internal Event list if any settings are changed.
SETGRPCHGD Setting Settings This signal will generate an Internal Event to the
groups changed Internal Event list if any setting groups are changed.
changed

Table 496: Self-supervision's hardware dependent internal signals


Card Name of signal Description Displayed on Reasons for activation
local HMI as
PSM PSM-Error Power PSM1 Activated if the module has a hardware error.
Supply
Module
Error status
BIM BIM-Error Binary In BIMn Activated if the module has a hardware error.
Module n = slot number
Error status
BOM BOM-Error Binary Out BOMn Activated if the module has a hardware error.
Module n = slot number
Error status
Table continues on next page

Breaker protection REQ650 561


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 505 384-UEN C
Security

Card Name of signal Description Displayed on Reasons for activation


local HMI as
IOM IOM-Error In/Out IOMn Activated if the module has a hardware error.
Module n = slot number
Error status
NUM NUM-Error Numerical/ NUM30 Activated if the module has a hardware or
CPU Module software error.
Error status
ADM ADM-Error A/D Module ADM32 Activated if the module has a hardware error.
Error status
LDCM LDCM-Error Line LDCM3nn Activated if the module has a hardware error.
Differential n = slot number
Communica
tion Module
Error status
TRM TRM-Error Transformer TRM40
Module
Error status
TRM TRM-Error Transformer TRM41
Module
Error status

When settings are changed in the IED, the protection and control applications restart in order
to take effect of the changes. During restart, internal events get generated and Runtime App
error will be displayed. These events are only indications and will be for short duration during
the restart.

IED will not be operational during applications restart.

15.5.5.2 Supervision of analog inputs M11401-136 v7

The analog signals to the A/D converter is internally distributed into two different converters,
one with low amplification and one with high amplification.

When the signal is within measurable limits on both channels, a direct comparison of the two
A/D converter channels can be performed. If the validation fails, the CPU will be informed and
an alarm will be given for A/D converter failure.

15.5.6 Technical data IP10272-1 v2

M11963-1 v5

Table 497: Self supervision with internal event list


Data Value
Recording manner Continuous, event controlled
List size 40 events, first in-first out

15.6 ChangeLock function CHNGLCK GUID-E8A1C33A-DD65-42B5-BA13-CFAE40C2C9AD v2

562 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 15
Security

15.6.1 Functionality GUID-00784FC0-B39D-462D-854B-AAF62626DD0A v3

Change lock function CHNGLCK is used to block further changes to the IED configuration and
settings once the commissioning is complete. The purpose is to block inadvertent IED
configuration changes beyond a certain point in time.

The change lock function activation is normally connected to a binary input.

15.6.2 Function block GUID-15AA1D42-912E-4085-8166-33FDC327CEB5 v2

CHNGLCK
LOCK* ACTIVE
OVERRIDE
IEC09000946.vsd

IEC09000946 V2 EN-US

Figure 296: CHNGLCK function block

15.6.3 Signals GUID-1B253577-C81B-40E3-B406-1F6586DCE545 v2

PID-3786-INPUTSIGNALS v6

Table 498: CHNGLCK Input signals


Name Type Default Description
LOCK BOOLEAN 0 Activate change lock

PID-3786-OUTPUTSIGNALS v6

Table 499: CHNGLCK Output signals


Name Type Description
ACTIVE BOOLEAN Change lock active
OVERRIDE BOOLEAN Change lock override

15.6.4 Operation principle GUID-74581AA2-6EB4-4CFA-92DA-90FB89F9A62C v4

The Change lock function (CHNGLCK) is configured using ACT.

The function, when activated, will still allow the following changes of the IED state that does
not involve reconfiguring of the IED:

• Monitoring
• Reading events
• Resetting events
• Reading disturbance data
• Clear disturbances
• Reset LEDs
• Reset counters and other runtime component states
• Control operations
• Set system time
• Enter and exit from test mode
• Change of active setting group

Breaker protection REQ650 563


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 15 1MRK 505 384-UEN C
Security

The binary input signal LOCK controlling the function is defined in ACT or SMT:

Binary input Function


1 Activated
0 Deactivated

15.7 Denial of service DOS

15.7.1 Functionality GUID-407250CA-0076-41E1-AD2D-434077AC3F1D v5

The Denial of service functionality limits overload on the IED produced by heavy Ethernet
network traffic. The communication facilities must not be allowed to compromise the primary
functionality of the device. All inbound network traffic will be quota controlled so that too
heavy network loads can be controlled. Heavy network load might for instance be the result of
malfunctioning equipment connected to the network.

15.7.2 Operation principle GUID-94340D4F-4D32-409B-BA1A-BA49A0C3F297 v6

The denial of service protection is designed to protect the IED from overload when exposed to
high amount of Ethernet network traffic. The communication facilities must not be allowed to
compromise the primary functionality of the device. All inbound network traffic is quota
controlled, so that a too heavy network load can be controlled. Heavy network load might for
instance be the result of malfunctioning equipment connected to the network.

The denial of service functionality in SCHLCCH and RCHLCCH measures the IED load from
communication and, if necessary, limits it from jeopardizing the IED's control and protection
functionality. The function has the following outputs:

• RCHLCCH
• LinkAUp and LinkBUp indicates the Ethernet link status for the rear ports channel A
and B
• DOSLINKA and DOSLINKB indicates that DOS functionality is active on channel A and
channel B
• DOSALARM indicates that DOS functionality is active on the access point
• SCHLCCH
• LINKUP indicates the Ethernet link status
• DOSALARM indicates that DOS functionality is active on the access point

The DOS functionality activates when the inbound traffic rate exceeds 3000
packets per second.

564 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 16
Basic IED functions

Section 16 Basic IED functions


16.1 Time synchronization TIMESYNCHGEN IP1750-1 v2

16.1.1 Functionality M11344-3 v11

The time synchronization function is used to select a common source of absolute time for the
synchronization of the IED when it is a part of a protection system. This makes it possible to
compare events and disturbance data between all IEDs within a station automation system
and in between sub-stations. A common source shall be used for IED and merging unit when
IEC/UCA 61850-9-2LE process bus communication is used.

Micro SCADA OPC server should not be used as a time synchronization source.

16.1.2 Settings IP9657-1 v2

SEMOD55141-5 v7
There are two groups of parameter settings related to time:

• System time
• Synchronization

The System time group relates to setting the on/off and start/end of the Daylight Saving Time
(DST) for the local time zone in relation to Coordinated Universal Time (UTC). The
Synchronization group relates to selecting the coarse and fine synchronization sources.

All the settings and parameters related to time are available via Local HMI under Main menu/
Configuration/Time/System time and via PCM600 under IED Configuration/Time.
PID-6251-SETTINGS v1

Table 500: TIMESYNCHGEN Non group settings (basic)


Name Values (Range) Unit Step Default Description
FineSyncSource Off - - Off Fine time synchronization source
GPS
IRIG-B
GPS+IRIG-B
SyncMaster Off - - Off Activate IEDas synchronization master
SNTP-Server
AppSynch NoSynch - - NoSynch Time synchronization mode for
Synch application
SyncAccLevel Class T5 (1us) - - Unspecified Wanted time synchronization accuracy
Class T4 (4us)
Unspecified

Breaker protection REQ650 565


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 505 384-UEN C
Basic IED functions

PID-6638-SETTINGS v3

Table 501: TIMESYNCHGEN Non group settings (basic)


Name Values (Range) Unit Step Default Description
CoarseSyncSrc Off - - Off Coarse time synchronization source
SPA
LON
DNP
IEC103
FineSyncSource Off - - Off Fine time synchronization source
SPA
LON
BIN
GPS
GPS+SPA
GPS+LON
GPS+BIN
SNTP
GPS+SNTP
IRIG-B
GPS+IRIG-B
PPS
SyncMaster Off - - Off Activate IEDas synchronization master
SNTP-Server
TimeAdjustRate Slow - - Fast Adjust rate for time synchronization
Fast
HWSyncSrc Off - - Off Hardware time synchronization
GPS source
IRIG-B
PPS
SyncLostMode NoBlock - - NoBlock Behavior of dependent protection
Block functions when time synchronization
BlockOnLostUTC quality is inadequate
SyncAccLevel Class T5 (1us) - - Unspecified Wanted time synchronization accuracy
Class T4 (4us)
Unspecified
CurrentSyncSource 0 - 16 - 1 - Current synchronization source
PTPGMId 0 - 16 - 1 - PTP Grand Master Id
PTPGMClass 0 - 16 - 1 - PTP Grand Master Class
PTPGMPriority1 0 - 16 - 1 - PTP Grand Master Prio 1
PTPGMPriority2 0 - 16 - 1 - PTP Grand Master Prio 2
PTPGMAccuracy 0 - 16 - 1 - PTP Grand Master Accuracy
PTPParentId 0 - 16 - 1 - PTP Id of closest parent
PTPSteps 0 - 16 - 1 - PTP number of stepsto Grand master
SNTPSource 0 - 16 - 1 - The source of the SNTP time
SNTPMaster 0 - 16 - 1 - The IP-adress of the SNTP master
GPSNumberOfSats -1 - 12 - 1 0 GPS satellites used in calculation of
time
PTPOwnId 0 - 16 - 1 - PTP own clock identity

GUID-CD154442-0F80-4B69-8C43-22445FD7F865 v1

GPS settings are not supported by 650 due to hardware restrictions.

566 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 16
Basic IED functions

PID-6188-SETTINGS v6

Table 502: BININPUT Non group settings (basic)


Name Values (Range) Unit Step Default Description
ModulePosition 3 - 16 - 1 3 Hardware position of IO module for
time synchronization
BinaryInput 1 - 16 - 1 1 Binary input number for time
synchronization
BinDetection PositiveEdge - - PositiveEdge Positive or negative edge detection
NegativeEdge

PID-6608-SETTINGS v4

Table 503: SNTP Non group settings (basic)


Name Values (Range) Unit Step Default Description
ServerIP-Add 0 - 18 IP 1 0.0.0.0 Server IP-address
Address
RedServIP-Add 0 - 18 IP 1 0.0.0.0 Redundant server IP-address
Address
LocalPort 0 - 65535 - 1 49152 Port number in the IED to
communicate with the SNTP server

PID-6212-SETTINGS v5

Table 504: DSTENABLE Non group settings (basic)


Name Values (Range) Unit Step Default Description
DST Enable Off - - On Enables or disables the use of
On Daylight Saving Time

Breaker protection REQ650 567


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 505 384-UEN C
Basic IED functions

PID-3967-SETTINGS v7

Table 505: DSTBEGIN Non group settings (basic)


Name Values (Range) Unit Step Default Description
MonthInYear January - - March Month in year when daylight time
February starts
March
April
May
June
July
August
September
October
November
December
DayInWeek Sunday - - Sunday Day in week when daylight time starts
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
WeekInMonth Last - - Last Week in month when daylight time
First starts
Second
Third
Fourth
UTCTimeOfDay -24:00 - - 1:00 UTC Time of day in hours when
-23:30 daylight time starts
...
-00:30
00:00
00:30
...
48:00

568 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 16
Basic IED functions

PID-3968-SETTINGS v7

Table 506: DSTEND Non group settings (basic)


Name Values (Range) Unit Step Default Description
MonthInYear January - - October Month in year when daylight time
February ends
March
April
May
June
July
August
September
October
November
December
DayInWeek Sunday - - Sunday Day in week when daylight time ends
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
WeekInMonth Last - - Last Week in month when daylight time
First ends
Second
Third
Fourth
UTCTimeOfDay -24:00 - - 1:00 UTC Time of day in hours when
-23:30 daylight time ends
...
-00:30
00:00
00:30
...
48:00

Breaker protection REQ650 569


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 505 384-UEN C
Basic IED functions

PID-4138-SETTINGS v5

Table 507: TIMEZONE Non group settings (basic)


Name Values (Range) Unit Step Default Description
TimeZone -12:00 - - 1:00 Local time from UTC
-11:00
-10:00
-9:30
-9:00
-8:00
-7:00
-6:00
-5:00
-4:30
-4:00
-3:30
-3:00
-2:00
-1:00
0:00
1:00
2:00
3:00
3:30
4:00
4:30
5:00
5:30
5:45
6:00
6:30
7:00
8:00
8:45
9:00
9:30
10:00
10:30
11:00
11:30
12:00
12:45
13:00
14:00

PID-6630-SETTINGS v2

Table 508: PTP Non group settings (advanced)


Name Values (Range) Unit Step Default Description
Domain 0 - 127 - 1 0 0 = Default domain, 1-3 = Alternative
domain, 4-127 = User defined
Priority1 0 - 255 - 1 128 The clock with the lowest priority 1
becomes the reference clock (Grand
Master)
Priority2 0 - 255 - 1 128 If all the relevant values for selecting
the reference clock are the same for
multiple devices, the clock with the
lowest priority 2 is selected as the
reference clock (Grand Master)

570 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 16
Basic IED functions

16.1.3 Description of SyncLostMode GUID-9BD77B8E-37F2-480F-89D6-9CE251403761 v1

If the time synchronization between the different sources of sampled values are lost, then the
protection function blocking behavior is different based on the parameter SyncLostMode.

The parameter can have three different values:

• NoBlock
• Block
• BlockOnLostUTC

NoBlock
The protection functions are not blocked due to the lost time synchronization. This is mainly
used when all sample values are produced in one source.

Block
The block can be used if there are several data sources that can be synchronized to each other.
However, the relation to UTC time is not required.

As soon as the protection detects a change or uncertainty in time from a data source, the
protections are blocked. This is detected by the jump in sample count or when the data
remains unsynchronized.

When a block occurs, the block stays for an extra blocking time after all the sources are
synchronized again, to secure that the time has propagated to the other sources.

Data stream 1
Time shift
Extra blocking time
on-going

Data stream 2
Time shift
Extra blocking time
on-going

Data stream 3
Time shift
Extra blocking time
on-going

Total protection blocking time

IEC19000001-1-en.vsdx
IEC19000001 V1 EN-US

Figure 297: Principle blocking when SyncLostMode is set to block


For more information, refer to section Time synchronization

BlockOnLostUTC
When BlockOnLostUTC is selected, all the data must be synchronized to UTC, to avoid blocking
of the protection functions.

This cannot be used by the process bus sampled values, since IEC 61859-9-2 LE only contains
the information regarding the synchronized or unsynchronized data.

For example, the BlockOnLostUTC can be used for a phasor measurement unit where the data
is compared between different stations.

Breaker protection REQ650 571


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 505 384-UEN C
Basic IED functions

16.1.4 Operation principle IP12360-1 v4

16.1.4.1 General concepts M11346-77 v1

Time definitions M11346-80 v3


The error of a clock is the difference between the actual time of the clock, and the time the
clock is intended to have. Clock accuracy indicates the increase in error, that is, the time
gained or lost by the clock. A disciplined clock knows its own faults and tries to compensate
for them.

Design of the time system (clock synchronization) GUID-E2B9E81C-5733-4521-B27F-BF33E05CCFB0 v10

PTP(IEEE 1588)
External
synchronization Off
sources On
Time tagging and general synchronization
Slave only
Off
Commu- Protection
LON Events
Time nication and control
SPA regulator functions
Min. pulse
(Setting:
SNTP SW time
see
DNP Technical
manual)
IRIG-B
PPS

Synchronization for differential protection


(Echo mode)
Off Time
IRIG-B regulator HW time
(fast or slow)
PPS

A/D Diff. Merging


converter commu- units*
nication

*IEC 61850-9-2
IEC16000002-2-en.vsdx
IEC16000002 V2 EN-US

Figure 298: Design of the time system (clock synchronization)


All time tagging is performed by the software clock. When, for example, a status signal is
changed in the protection system of a function based on the free running hardware clock, the
event is time tagged by the software clock when it reaches the event recorder. The hardware
clock can thus run independently.

The echo mode of the line differential protection function is based on the hardware clock.
Thus, there is no need to synchronize the hardware clock and the software clock.

Synchronization of the hardware clock to the software clock is necessary only when IRIG B 00X
with optical fiber, IEEE 1344 is used for differential protection. The two clock systems are
synchronized by a special clock synchronization unit with two modes, fast and slow. A special
feature, an automatic fast clock time regulator is used. The automatic fast mode makes the
synchronization time as short as possible during start-up. The Fast and Slow settings are also
available on the local HMI.

572 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 16
Basic IED functions

SyncLostMode is not required to set as Block/BlockonLostUTC when differential protection is


based on ECHO mode.

Fast clock synchronization mode


At start-up and after interruptions in the IRIG B time signals, the deviation between the
external time system and the internal differential time system can be substantial. A new start-
up is also required, for example, after maintenance of the auxiliary voltage system.

When the time difference is > 16 μs, the line differential protection function is blocked and the
time regulator for the hardware clock automatically uses a fast mode to synchronize the clock
systems. Time adjustment is made with an exponential function, that is, with big time
adjustment steps in the beginning, and then smaller steps until a time deviation of < 16 μs
between the external time system and the internal differential time system has been reached.
The protection function is then enabled and the synchronization remains in fast mode or
switches to slow mode depending on the setting.

Synchronization principle M11346-83 v4


From a general point of view synchronization can be seen as a hierarchical structure. A
function is synchronized from a higher level and provides synchronization to lower levels.

Synchronization from
a higher level

Function

Optional synchronization of
modules at a lower level

IEC09000342-1-en.vsd
IEC09000342 V1 EN-US

Figure 299: Synchronization principle


A function is said to be synchronized when it periodically receives synchronization messages
from a higher level. As the level decreases, the accuracy of the synchronization decreases as
well. A function can have several potential sources of synchronization, with different maximum
errors. This gives the function the possibility to choose the source with the best quality, and to
adjust its internal clock based on this source. The maximum error of a clock can be defined as:

• The maximum error of the last used synchronization message


• The time since the last used synchronization message
• The rate accuracy of the internal clock in the function.

16.1.4.2 Real-time clock (RTC) operation M11346-57 v4

The IED has a built-in real-time clock (RTC) with a resolution of one millisecond. The clock has a
built-in calendar that handles leap years through 2100.

Real-time clock at power off M11346-60 v3


During power off, the system time in the IED is kept by a capacitor-backed real-time clock that
will provide 5 ppm accuracy for at least two days. This means that if the power is off, the time

Breaker protection REQ650 573


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 505 384-UEN C
Basic IED functions

in the IED may drift with maximum 0.5 second per day for two days, and after this the time will
be lost.

Real-time clock at startup M11346-63 v4

Time synchronization startup procedure M11346-66 v9


The first message that contains the full time (as for instance LON and SNTP) gives an accurate
time to the IED. After the initial setting of the clock, one of the three following conditions
happens with each of the coming synchronization messages configured as FineSynchSource:

• If the synchronization message, which is similar to the other messages, has an offset
compared to the internal time in the IED, the message is used directly for synchronization,
which means, for adjusting the internal clock to obtain zero offset at the next coming time
message.
• If the synchronization message has a large offset compared to the other messages, a
spike-filter in the IED removes this time-message.

Rate accuracy M11346-93 v7


The rate accuracy is the accuracy of the internal clock while the external time signal is lost. In
the IED, the rate accuracy at cold start is 2 ppm but if the IED is synchronized for a while, the
rate accuracy is approximately 0.2 ppm if the surrounding temperature is constant.

Time-out on synchronization sources M11346-96 v3


All synchronization interfaces have a time-out, and a configured interface must receive time
synchronization messages regularly in order not to give an error signal (TSYNCERR) that is
reported from the INTERRSIG function block. The time-out is such that one message can be
lost without getting a TSYNCERR, but if more than one message is lost, a TSYNCERR is given.

16.1.4.3 Synchronization alternatives M11346-3 v7

Three main alternatives of external synchronization sources are available. The synchronization
message is applied:

• via any of the communication ports of the IED as a telegram message including date and
time
• as a minute pulse connected to a binary input
• via IRIG-B or PPS

16.1.4.4 Process bus IEC/UCA 61850-9-2LE synchronization GUID-6E384BDB-5598-4108-99B4-0B4A4E1828B2 v5

When process bus communication (IEC/UCA 61850-9-2LE protocol) is used, it is essential that
the merging units are synchronized with the hardware time of the IED (see Technical manual,
section Design of the time system (clock synchronization) ). To achieve this, PTP, PPS or IRIG-B
can be used depending of the facilities of the merging unit.

If the merging unit supports PTP, use PTP. If PTP is used in the IED and the merging unit
cannot be synchronized from the IED, then use GPS-based clocks to provide PTP synch as well
as sync to the merging unit.

If synchronization of the IED and the merging unit is based on GPS, set the parameter
SyncLostMode to BlockOnLostUTC in order to provide a block of protection functions
whenever the global common time is lost.

If PTP is not used, use the same synchronization method for the HwSyncSrc as the merging
unit provides. For instance, if the merging unit provides PPS as synchronization, use PPS as
HwSyncSrc. If LDCM in GPS-mode is used, that is, the hardware and software clocks are
connected to each other, HwSyncSrc is not used and other means to synchronize the merging

574 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 16
Basic IED functions

unit to the IED is required. For instance, FineSyncSource is set to the same source that the
merging unit uses.

If the IED is used together with a merging unit and no time synchronization is
available, for example, in the laboratory test, the IED will synchronize to the SV
data stream. During the re-synchronization, the protection functions will be
blocked once a second for about 45 ms, and this will continue for up to 10
minutes. To avoid this, configure PTP (IEEE 1588) to On for the access point
where the merging unit is configured.

16.1.4.5 Precision Time Protocol (PTP) GUID-4F2B68B8-CCC8-4173-A644-D1674D3146F8 v3

PTP according to IEEE 1588-2008 and specifically its profile IEC/IEEE 61850-9-3 for power
utility automation is a synchronization method that differs from SNTP, for instance, by
providing much better accuracy and by being not predefined. By not predefined is meant that
it is not mandatory to have a predefined synchronization tree, as the master (Grand Master)
may shift.

Consider instead PTP as a synchronization grouping, i.e. all devices connected to the PTP
group will be synchronized to the same source or, if there is no external source the group will
at least maintain a common time. The group is synchronized by connecting one or more
“Grand Master” clocks to it. The clocks can be part of the devices in the group or be specialized
synchronization devices, as for instance a GPS clock or similar. If several synchronization
devices are connected to the group, the “Best Master Algorithm” in the PTP protocol will
assure that only one is the “Grand Master”. The IED can act as a synchronization device and
supply any synchronization source (like SNTP, SPA) as clock input, that will synchronize the
whole PTP group if there is no better source available in the group. The IED can be connected
to several groups and thereby connect them to each other, by acting as a “Boundary Clock”. If
PTP is “On” on several Access Points, the IED connects the Access Points via a boundary clock.
If PTP is “On” on redundant Access Points, the IED acts as a “Transparent Clock”.

In a network there may be variety of possible masters that are connected together where the
masters by selection, using the priority of PTP (also called the Best Master Algorithm, or BMC)
to determine which of them that is the best master.

Priority order according to PTP

1. Priority 1
setting for each device, default 128, set to a lower number if this device shall be the Grand
Master.
2. GM class
given from the type of device, for instance “6” for a GPS clock, “7” for a GPS clock that has
lost synch during a hold-over time, “187” for a clock that can also be a slave.
3. GM Accuracy
how accurate the time is as a enumerated value
4. Offset Scaled Variance
calculated value that shows the oscillator quality
5. Priority 2
setting for each device, default 128, set to a lower number if this device is preferred to be
the Grand Master, if Priority 1, GM class, GM accuracy and OffsetScaledVariance are the
same for all devices.
6. Identity, that is the MAC-adress of the port.

MAC address of the access points can be seen in LHMI under the settings
of each access point.

Breaker protection REQ650 575


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 505 384-UEN C
Basic IED functions

To setup a PTP network with no obvious Grand Master, you simply connect the IEDs to one
network and configure PTP to be “on” on all IEDs. On one IED, the one from which you want to
set the time in the station, you set the Priority2 to 127, instead of default 128. Now, this IED has
higher priority than the rest of the IEDs and will thereby act as “Grand Master”.

PTP is not set from TIMESYNCGEN:1General, as SNTP is. Instead PTP is set via a parameter of
each Access Point. For more information, refer to section Time synchronization.

16.1.5 Technical data IP9658-1 v1

M12331-1 v9

Table 509: Time synchronization, time tagging


Function Value
Time tagging resolution, events and sampled measurement values 1 ms
Time tagging error with synchronization once/min (minute pulse ± 1.0 ms typically
synchronization), events and sampled measurement values
Time tagging error with SNTP synchronization, sampled measurement values ± 1.0 ms typically

GUID-8AEB81D0-1731-46DF-A206-D2E758823575 v2

Table 510: Time synchronization PTP: IEC/IEEE 61850-9-3

Supported types of clock Boundary Clock (BC), Ordinary Clock (OC), Transparent
Clock (TC)
Accuracy According to standard IEC/IEEE 61850-9-3
Number of nodes According to standard IEC/IEEE 61850-9-3
Ports supported All rear Ethernet ports

16.2 Parameter setting groups IP1745-1 v1

16.2.1 Functionality M12006-6 v7

Use the six different groups of settings to optimize the IED operation for different power
system conditions. Creating and switching between fine-tuned setting sets, either from the
local HMI or configurable binary inputs, results in a highly adaptable IED that can be applied to
a variety of power system scenarios.

16.2.2 Function block IP9661-1 v1

M12010-3 v3

ACTVGRP
ACTGRP1 GRP1
ACTGRP2 GRP2
ACTGRP3 GRP3
ACTGRP4 GRP4
ACTGRP5 GRP5
ACTGRP6 GRP6
SETCHGD
REMSETEN

IEC05000433-3-en.vsd
IEC05000433 V3 EN-US

Figure 300: ActiveGroup function block

576 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 16
Basic IED functions

16.2.3 Signals IP14073-1 v2

PID-6558-INPUTSIGNALS v6

Table 511: ACTVGRP Input signals


Name Type Default Description
ACTGRP1 BOOLEAN 0 Selects setting group 1 as active
ACTGRP2 BOOLEAN 0 Selects setting group 2 as active
ACTGRP3 BOOLEAN 0 Selects setting group 3 as active
ACTGRP4 BOOLEAN 0 Selects setting group 4 as active
ACTGRP5 BOOLEAN 0 Selects setting group 5 as active
ACTGRP6 BOOLEAN 0 Selects setting group 6 as active

PID-6558-OUTPUTSIGNALS v6

Table 512: ACTVGRP Output signals


Name Type Description
GRP1 BOOLEAN Setting group 1 is active
GRP2 BOOLEAN Setting group 2 is active
GRP3 BOOLEAN Setting group 3 is active
GRP4 BOOLEAN Setting group 4 is active
GRP5 BOOLEAN Setting group 5 is active
GRP6 BOOLEAN Setting group 6 is active
SETCHGD BOOLEAN Pulse when setting changed
REMSETEN BOOLEAN Settings over IEC 61850 enabled

16.2.4 Settings IP11026-1 v2

PID-3572-SETTINGS v5

Table 513: SETGRPS Non group settings (basic)


Name Values (Range) Unit Step Default Description
ActiveSetGrp SettingGroup1 - - SettingGroup1 Active setting group
SettingGroup2
SettingGroup3
SettingGroup4
SettingGroup5
SettingGroup6
MaxNoSetGrp 1-6 - 1 1 Max number of setting groups 1-6

16.2.5 Operation principle M12008-6 v3

M12008-8 v11
Parameter setting groups ActiveGroup function has six functional inputs, each corresponding
to one of the setting groups stored in the IED. Activation of any of these inputs changes the
active setting group. Eight functional output signals are available for configuration purposes,
so that information on the active setting group is always available.

A setting group is selected by using the local HMI, from a front connected personal computer,
remotely from the station control or station monitoring system or by activating the
corresponding input to the ActiveGroup function block.

Breaker protection REQ650 577


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 505 384-UEN C
Basic IED functions

Each input of the function block can be configured to connect to any of the binary inputs in the
IED. To do this PCM600 must be used.

The external control signals are used for activating a suitable setting group when adaptive
functionality is necessary. Input signals that should activate setting groups must be either
permanent or a pulse exceeding 400 ms.

More than one input may be activated at the same time. In such cases the lower order setting
group has priority. This means that if for example both group four and group two are set to be
activated, group two will be the one activated.

Every time a setting is changed, the output signal SETCHGD is sending a pulse. Activating or
deactivating test mode is made by changing a parameter, consequently this will also cause a
pulse on the SETCHGD output.

The parameter MaxNoSetGrp defines the maximum number of setting groups in use to switch
between.

The output REMSETEN indicates whether setting changes over IEC 61850 are enabled or not.
Per default, this is not enabled, which results in REMSETEN being at a logical low level. If setting
changes via IEC 61850 are enabled, then REMSETEN will be a logical high. The setting changes
over IEC 61850 is enabled with the setting EnableSettings in the IEC 61850-8-1 configuration
under Main menu/Configuration/Communication/Station communication/IEC
61850-8-1/IEC 61850-8-1. Please refer to documentation for IEC 61850 for further details.

Switching can only be done within that number of groups. The number of setting groups
selected to be used will be filtered so only the setting groups used will be shown on the
Parameter Setting Tool.

ACTIVATE GROUP 6
ACTIVATE GROUP 5
ACTIVATE GROUP 4
ACTIVATE GROUP 3
ACTIVATE GROUP 2
+RL2 ACTIVATE GROUP 1
ACTVGRP
IOx-Bly1
Æ ACTGRP1 GRP1

IOx-Bly2
Æ ACTGRP2 GRP2

IOx-Bly3 ACTGRP3 GRP3


Æ
IOx-Bly4
Æ ACTGRP4 GRP4

IOx-Bly5
Æ ACTGRP5 GRP5

IOx-Bly6
Æ ACTGRP6 GRP6

SETCHGD

REMSETEN

IEC05000119-3-en.vsd
IEC05000119 V3 EN-US

Figure 301: Connection of the function to external circuits


The above example also includes seven output signals, for confirmation of which group that is
active.

578 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 16
Basic IED functions

16.3 Test mode functionality TESTMODE IP1647-1 v3

16.3.1 Functionality M4803-3 v11

When entering IED test mode there is an option to block all functions. Active test mode is
indicated by a flashing yellow Start LED on the LHMI. After that, it is possible to block/unblock
arbitrarily selected functions from the LHMI to perform required tests.

When leaving TESTMODE, all blockings are removed (except for functions that have their block
input active), and the IED resumes normal operation. However, if during TESTMODE operation,
power is removed and later restored, the IED will remain in TESTMODE with the same
protection functions blocked or unblocked as before the power was removed. All testing will
be done with actually set and configured values within the IED. No settings will be changed,
thus mistakes are avoided.

Forcing of binary input and output signals is only possible when the IED is in IED test mode.

16.3.2 Function block SEMOD54888-4 v5

TESTMODE
IED_TEST TEST
IED_TEST
BLOCK
NOEVENT
INPUT
SETTING
IEC61850

IEC14000072-1-en.vsd
IEC09000219 V2 EN-US

Figure 302: TESTMODE function block

16.3.3 Signals IP9680-1 v2

PID-6730-INPUTSIGNALS v1

Table 514: TESTMODE Input signals


Name Type Default Description
IED_TEST BOOLEAN 0 Activate IED test mode

PID-6730-OUTPUTSIGNALS v1

Table 515: TESTMODE Output signals


Name Type Description
TEST BOOLEAN In test via IED TEST or via LD0 Mode
IED_TEST BOOLEAN IED test mode is active
BLOCK BOOLEAN Active when LD0 is blocked or test blocked
NOEVENT BOOLEAN Event disabled during test mode
INPUT BOOLEAN IED TEST input is active
SETTING BOOLEAN IED test mode setting is On
IEC61850 BOOLEAN Active when LD0 Mode is in Blocked, Test or Test blocked

Breaker protection REQ650 579


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 505 384-UEN C
Basic IED functions

16.3.4 Settings IP11343-1 v2

PID-6730-SETTINGS v1

Table 516: TESTMODE Non group settings (basic)


Name Values (Range) Unit Step Default Description
IEDTestMode Off - - Off Activate IED Test mode
On
EventDisable Off - - Off Event disable during test mode
On
BlockAllFunc Off - - On Block all functions when entering IED
On test mode
CmdTestEd1 Off - - Off Require test bit in command at test
On mode (only for IEC61850 Ed1)

16.3.5 Operation principle IP12116-1 v4

M12015-4 v11
Set the IED in test mode by

• configuration, activating the input SIGNAL on the function block TESTMODE.


• setting TestMode to On in the local HMI, under Main menu/TEST/IED test mode.

While the IED is in test mode, the output ACTIVE of the function block TESTMODE is activated.
The outputs of the function block TESTMODE shows the cause of the “Test mode: being in On”
state. If the input from the configuration (OUTPUT signal is activated) or setting from local
HMI (SETTING signal is activated).

While the IED is in test mode, the yellow Start LED will flash and all functions can be blocked
depending on the configuration of the testmode component. Any function can be unblocked
individually regarding functionality and event signalling.
M11828-3 v9
The deblocking operation will reset when exiting the test mode.

The blocking of a function concerns all output signals from the actual function, so no outputs
will be activated.

If the IED is restarted while set to IED TESTMODE by a binary input all functions
will be temporarily unblocked during startup, which might cause unwanted
operations.

The TESTMODE function block might be used to automatically block functions when a test
handle is inserted in a test switch. A contact in the test switch (RTXP24 contact 29-30) can
supply a binary input which in turn is configured to the TESTMODE function block.

Each of the functions includes the blocking from the TESTMODE function block.

The functions can also be blocked from sending events over IEC 61850 station bus to prevent
filling station and SCADA databases with test events, for example during a commissioning or
maintenance test.

580 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 16
Basic IED functions

16.4 IED identifiers TERMINALID IP15060-1 v2

16.4.1 Functionality M15324-3 v6

IED identifiers (TERMINALID) function allows the user to identify the individual IED in the
system, not only in the substation, but in a whole region or a country.

Use only characters A-Z, a-z and 0-9 in station, object and unit names.

16.4.2 Settings GUID-3C49A222-FFE4-492B-A96C-9E9965FA2CB4 v2

PID-6801-SETTINGS v1

Table 517: TERMINALID Non group settings (basic)


Name Values (Range) Unit Step Default Description
StationName 0 - 18 - 1 Station name Station name
StationNumber 0 - 99999 - 1 0 Station number
ObjectName 0 - 18 - 1 Object name Object name
ObjectNumber 0 - 99999 - 1 0 Object number
UnitName 0 - 18 - 1 Unit name Unit name
UnitNumber 0 - 99999 - 1 0 Unit number
IEDMainFunType 0 - 255 - 1 0 IED main function type for
IEC60870-5-103
TechnicalKey 0 - 16 - 1 AA0B0Q0A0 Technical key (part 1)
0 - 16 - 1 Technical key (part 2)
0 - 16 - 1 Technical key (part 3)
0 - 16 - 1 Technical key (part 4)

16.5 Product information PRODINF GUID-F67243CA-2429-4118-BBFF-3D62BF55E080 v2

16.5.1 Functionality GUID-D78786E6-C34A-4E63-9D1E-0582C8F1F7E1 v9

Product information contains unchangeable data that uniquely identifies the IED.

Product information data is visible on the local HMI under Main menu/Diagnostics/IED
status/Product identifiers and under Main menu/Diagnostics/IED Status/Identifiers:

Product information data is visible on the local HMI under Main menu/Diagnostics/IED
status/Product identifiers and under Main menu/Diagnostics/IED Status/Identifiers.

• ProductVer
• ProductDef
• FirmwareVer
• SerialNo
• OrderingNo
• ProductionDate
• IEDProdType

Breaker protection REQ650 581


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 505 384-UEN C
Basic IED functions

Figure 303: IED summary


This information is very helpful when interacting with ABB product support (for example
during repair and maintenance).

16.5.2 Settings GUID-168CD792-8811-43B5-8760-74ED82DE17F7 v5

The function does not have any parameters available in the local HMI or PCM600.

16.5.3 Factory defined settings M11789-39 v11

The factory defined settings are very useful for identifying a specific version and very helpful in
the case of maintenance, repair, interchanging IEDs between different Substation Automation
Systems and upgrading. The factory made settings can not be changed by the customer. They
can only be viewed. The settings are found in the local HMI under Main menu/Diagnostics/IED
status/Product identifiers

The following identifiers are available:

• IEDProdType
• Describes the type of the IED. Example: REL650
• ProductDef
• Describes the release number from the production. Example: 2.1.0
• FirmwareVer
• Describes the firmware version.
• The firmware version can be checked from Main menu/Diagnostics/IED status/
Product identifiers
• Firmware version numbers run independently from the release production numbers.
For every release number there can be one or more firmware versions depending on
the small issues corrected in between releases.
• ProductVer
• Describes the product version. Example: 2.1.0

1 is the Major version of the manufactured product this means, new platform of the product
2 is the Minor version of the manufactured product this means, new functions or new hardware
added to the product
3 is the Major revision of the manufactured product this means, functions or hardware is either
changed or enhanced in the product

• IEDMainFunType
• Main function type code according to IEC 60870-5-103. Example: 128 (meaning line
protection).
• SerialNo
• OrderingNo
• ProductionDate

16.6 Signal matrix for binary inputs SMBI SEMOD55793-1 v2

582 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 16
Basic IED functions

16.6.1 Functionality M15302-3 v5

The Signal matrix for binary inputs (SMBI) function is used within the Application
Configuration Tool (ACT) in direct relation with the Signal Matrix Tool (SMT), see the
application manual to get information about how binary inputs are brought in for one IED
configuration.

16.6.2 Function block M15306-3 v3

SMBI
^VIN1 ^BI1
^VIN2 ^BI2
^VIN3 ^BI3
^VIN4 ^BI4
^VIN5 ^BI5
^VIN6 ^BI6
^VIN7 ^BI7
^VIN8 ^BI8
^VIN9 ^BI9
^VIN10 ^BI10

IEC05000434-2-en.vsd
IEC05000434 V2 EN-US

Figure 304: SMBI function block

16.6.3 Signals SEMOD55814-1 v2

PID-3940-INPUTSIGNALS v5

Table 518: SMBI Input signals


Name Type Default Description
BI1 BOOLEAN 0 SMT Connect input
BI2 BOOLEAN 0 SMT Connect input
BI3 BOOLEAN 0 SMT Connect input
BI4 BOOLEAN 0 SMT Connect input
BI5 BOOLEAN 0 SMT Connect input
BI6 BOOLEAN 0 SMT Connect input
BI7 BOOLEAN 0 SMT Connect input
BI8 BOOLEAN 0 SMT Connect input
BI9 BOOLEAN 0 SMT Connect input
BI10 BOOLEAN 0 SMT Connect input

PID-3940-OUTPUTSIGNALS v5

Table 519: SMBI Output signals


Name Type Description
BI1 BOOLEAN Binary input 1
BI2 BOOLEAN Binary input 2
BI3 BOOLEAN Binary input 3
BI4 BOOLEAN Binary input 4
BI5 BOOLEAN Binary input 5
BI6 BOOLEAN Binary input 6
BI7 BOOLEAN Binary input 7
Table continues on next page

Breaker protection REQ650 583


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 505 384-UEN C
Basic IED functions

Name Type Description


BI8 BOOLEAN Binary input 8
BI9 BOOLEAN Binary input 9
BI10 BOOLEAN Binary input 10

16.6.4 Operation principle M15305-3 v5

The Signal matrix for binary inputs (SMBI) function , see figure 304, receives its inputs from the
real (hardware) binary inputs via the Signal Matrix Tool (SMT) or ACT, and makes them
available to the rest of the configuration via its outputs, BI1 to BI10. The inputs and outputs, as
well as the whole block, can be given a user defined name. These names will be represented in
SMT as information which signals shall be connected between physical IO and SMBI function.
The input/output user defined name will also appear on the respective output/input signal.

16.7 Signal matrix for binary outputs SMBO SEMOD55215-1 v2

16.7.1 Functionality M15311-3 v5

The Signal matrix for binary outputs (SMBO) function is used within the Application
Configuration Tool (ACT) in direct relation with the Signal Matrix Tool (SMT), see the
application manual to get information about how binary inputs are sent from one IED
configuration.

16.7.2 Function block SEMOD54860-4 v3

SMBO
BO1 ^BO1
BO2 ^BO2
BO3 ^BO3
BO4 ^BO4
BO5 ^BO5
BO6 ^BO6
BO7 ^BO7
BO8 ^BO8
BO9 ^BO9
BO10 ^BO10

IEC05000439-2-en.vsd
IEC05000439 V2 EN-US

Figure 305: SMBO function block

16.7.3 Signals SEMOD55887-1 v2

PID-3831-INPUTSIGNALS v5

Table 520: SMBO Input signals


Name Type Default Description
BO1 BOOLEAN 0 Signal name for BO1 in Signal Matrix Tool
BO2 BOOLEAN 0 Signal name for BO2 in Signal Matrix Tool
BO3 BOOLEAN 0 Signal name for BO3 in Signal Matrix Tool
BO4 BOOLEAN 0 Signal name for BO4 in Signal Matrix Tool
BO5 BOOLEAN 0 Signal name for BO5 in Signal Matrix Tool
Table continues on next page

584 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 16
Basic IED functions

Name Type Default Description


BO6 BOOLEAN 0 Signal name for BO6 in Signal Matrix Tool
BO7 BOOLEAN 0 Signal name for BO7 in Signal Matrix Tool
BO8 BOOLEAN 0 Signal name for BO8 in Signal Matrix Tool
BO9 BOOLEAN 0 Signal name for BO9 in Signal Matrix Tool
BO10 BOOLEAN 0 Signal name for BO10 in Signal Matrix Tool

16.7.4 Operation principle SEMOD55864-4 v7

The Signal matrix for binary outputs (SMBO) function , see figure 305, receives logical signal
from the IED configuration, which is transferring to the real (hardware) outputs, via the Signal
Matrix Tool (SMT) or ACT. The inputs in SMBO are BO1 to BO10 and they, as well as the whole
function block, can be tag-named. The name tags will appear in SMT as information which
signals shall be connected between physical IO and the SMBO.

16.8 Signal matrix for analog inputs SMAI SEMOD55751-1 v2

16.8.1 Functionality SEMOD55744-4 v10

Signal matrix for analog inputs (SMAI), also known as the preprocessor function block,
analyses the connected four analog signals (three phases and neutral) and calculates all
relevant information from them like the phasor magnitude, phase angle, frequency, true RMS
value, harmonics, sequence components and so on. This information is then used by the
respective functions connected to this SMAI block in ACT (for example protection,
measurement or monitoring functions).

16.8.2 Function block SEMOD55766-1 v3

SEMOD54868-4 v12

SMAI1
BLOCK SPFCOUT
DFTSPFC G1AI3P
REVROT G1AI1
^GRP1L1 G1AI2
^GRP1L2 G1AI3
^GRP1L3 G1AI4
^GRP1N G1N

IEC14000027-1-en.vsd
IEC14000027 V1 EN-US

Figure 306: SMAI1 function block


Figure 306 is an example of SMAI1:n in each of the four task time groups 1, 2, 3 or 4 where:

• n=1 in task group 1


• n=13 in task group 2
• n=25 in task group 3
• n=37 in task group 4

The number of available task time groups depend on product and configuration. Up to four
task time groups are available in a product. The task time defines the execution repetition rate
for the task time groups. The task times valid for a product are found in PCM600, Application
configuration tool.

Breaker protection REQ650 585


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 505 384-UEN C
Basic IED functions

SEMOD54997-4 v11

SMAI2
BLOCK G2AI3P
REVROT G2AI1
^GRP2L1 G2AI2
^GRP2L2 G2AI3
^GRP2L3 G2AI4
^GRP2N G2N

IEC14000028-1-en.vsd
IEC14000028 V1 EN-US

Figure 307: SMAI2 function block


Figure 307 is an example of SMAI2:n to SMAI12:m in each of the four task time groups 1, 2, 3 or
4 where:

• n=2 and m=12 in task group 1


• n=14 and m=24 in task group 2
• n=26 and m=36 in task group 3
• n=38 and m=48 in task group 4

The number of available task time groups depend on product and configuration. Up to four
task time groups are available in a product. The task time defines the execution repetition rate
for the task time groups. The task times valid for a product are found in PCM600, Application
configuration tool.

16.8.3 Signals SEMOD55773-1 v2

PID-3405-INPUTSIGNALS v6

Table 521: SMAI1 Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block group 1
DFTSPFC REAL 20.0 Number of samples per fundamental cycle used for DFT
calculation
REVROT BOOLEAN 0 Reverse rotation group 1
GRP1L1 STRING - First analog input used for phase L1 or L1-L2 quantity
GRP1L2 STRING - Second analog input used for phase L2 or L2-L3 quantity
GRP1L3 STRING - Third analog input used for phase L3 or L3-L1 quantity
GRP1N STRING - Fourth analog input used for residual or neutral quantity

PID-3405-OUTPUTSIGNALS v5

Table 522: SMAI1 Output signals


Name Type Description
SPFCOUT REAL Number of samples per fundamental cycle from internal DFT
reference function
G1AI3P GROUP SIGNAL Group 1 analog input 3-phase group
G1AI1 GROUP SIGNAL Group 1 analog input 1
G1AI2 GROUP SIGNAL Group 1 analog input 2
G1AI3 GROUP SIGNAL Group 1 analog input 3
G1AI4 GROUP SIGNAL Group 1 analog input 4
G1N GROUP SIGNAL Group parameter for residual sample

586 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 16
Basic IED functions

PID-3406-INPUTSIGNALS v6

Table 523: SMAI2 Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block group 2
REVROT BOOLEAN 0 Reverse rotation group 2
GRP2L1 STRING - First analog input used for phase L1 or L1-L2 quantity
GRP2L2 STRING - Second analog input used for phase L2 or L2-L3 quantity
GRP2L3 STRING - Third analog input used for phase L3 or L3-L1 quantity
GRP2N STRING - Fourth analog input used for residual or neutral quantity

PID-3406-OUTPUTSIGNALS v5

Table 524: SMAI2 Output signals


Name Type Description
G2AI3P GROUP SIGNAL Group 2 analog input 3-phase group
G2AI1 GROUP SIGNAL Group 2 analog input 1
G2AI2 GROUP SIGNAL Group 2 analog input 2
G2AI3 GROUP SIGNAL Group 2 analog input 3
G2AI4 GROUP SIGNAL Group 2 analog input 4
G2N GROUP SIGNAL Group parameter for residual sample

16.8.4 Settings SEMOD55783-1 v2

SEMOD130357-4 v3

Settings DFTRefExtOut and DFTReference shall be set to default value


InternalDFTRef if no VT inputs are available. Internal nominal frequency DFT
reference is then the reference.

Breaker protection REQ650 587


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 505 384-UEN C
Basic IED functions

PID-3405-SETTINGS v5

Table 525: SMAI1 Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
DFTRefExtOut InternalDFTRef - - InternalDFTRef DFT reference for external output
DFTRefGrp1
DFTRefGrp2
DFTRefGrp3
DFTRefGrp4
DFTRefGrp5
DFTRefGrp6
DFTRefGrp7
DFTRefGrp8
DFTRefGrp9
DFTRefGrp10
DFTRefGrp11
DFTRefGrp12
External DFT ref
DFTReference InternalDFTRef - - InternalDFTRef DFT reference
DFTRefGrp1
DFTRefGrp2
DFTRefGrp3
DFTRefGrp4
DFTRefGrp5
DFTRefGrp6
DFTRefGrp7
DFTRefGrp8
DFTRefGrp9
DFTRefGrp10
DFTRefGrp11
DFTRefGrp12
External DFT ref
ConnectionType Ph-N - - Ph-N Input connection type
Ph-Ph
AnalogInputType Voltage - - Voltage Analog input signal type
Current

Table 526: SMAI1 Non group settings (advanced)


Name Values (Range) Unit Step Default Description
Negation Off - - Off Negation
NegateN
Negate3Ph
Negate3Ph+N
MinValFreqMeas 5 - 200 % 1 10 Limit for frequency calculation in % of
UBase

588 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 16
Basic IED functions

PID-3406-SETTINGS v5

Table 527: SMAI2 Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
DFTReference InternalDFTRef - - InternalDFTRef DFT reference
DFTRefGrp1
DFTRefGrp2
DFTRefGrp3
DFTRefGrp4
DFTRefGrp5
DFTRefGrp6
DFTRefGrp7
DFTRefGrp8
DFTRefGrp9
DFTRefGrp10
DFTRefGrp11
DFTRefGrp12
External DFT ref
ConnectionType Ph-N - - Ph-N Input connection type
Ph-Ph
AnalogInputType Voltage - - Voltage Analog input signal type
Current

Table 528: SMAI2 Non group settings (advanced)


Name Values (Range) Unit Step Default Description
Negation Off - - Off Negation
NegateN
Negate3Ph
Negate3Ph+N
MinValFreqMeas 5 - 200 % 1 10 Limit for frequency calculation in % of
UBase

16.8.5 Operation principle SEMOD55746-4 v14

Every Signal matrix for analog inputs function (SMAI) can receive four analog signals (three
phases and one neutral or residual value), either voltage or current, see figure 306 and
figure 307. SMAI outputs give information about every aspect of the 3ph analog signals
acquired (phase angle, RMS value, frequency and frequency derivates etc. – 244 values in total).
The BLOCK input will force all outputs to value zero if BLOCK is TRUE (1). However, when the
disturbance recorder is connected to the single-phase outputs of SMAI, the sample data to the
disturbance recorder will not be blocked. The disturbance recorder bypasses SMAI to the
sample data channels.

System phase rotation and frequency are defined using the PhaseRotation and Frequency
settings in the primary system values PRIMVAL function. Logic 1 in the REVROT input to the
SMAI function means that the phase rotation is changed relative to the set PhaseRotation in
PRIMVAL.

The output signal AI1 to AI4 are single phase outputs which directly represent the four inputs
GRPxL1, GRPxL2, GRPxL3 and GRPxN, x=1-12. GxN (x = 1-12) is always calculated residual sum
from the first three inputs. A3P is grouped, three-phase information containing all relevant
information about four connected inputs. Note that all other functions, with a few exceptions,
use this output in configuration. Note that the SMAI function will always calculate the residual
sum of current/voltage if the input GRPxN is not connected in SMT. Applications with a few
exceptions shall always be connected to AI3P.

Breaker protection REQ650 589


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 505 384-UEN C
Basic IED functions

16.8.5.1 Frequency values GUID-B494B93C-B5AA-4FD6-8080-8611C34C2AD8 v5

The SMAI function includes a functionality based on the level of positive sequence voltage,
MinValFreqMeas, to validate if the frequency measurement is valid or not. If the positive
sequence voltage is lower than MinValFreqMeas, the function freezes the frequency output
value for 500 ms and after that the frequency output is set to the nominal value. A signal is
available for the SMAI function to prevent operation due to non-valid frequency values.
MinValFreqMeas is set as % of UBase/√3

If SMAI setting ConnectionType is Ph-Ph, at least two of the inputs GRPxL1, GRPxL2 and
GRPxL3, where 1≤x≤12, must be connected in order to calculate the positive sequence voltage.
Note that phase to phase inputs shall always be connected as follows: L1-L2 to GRPxL1, L2-L3
to GRPxL2, L3-L1 to GRPxL3. If SMAI setting ConnectionType is Ph-N, all three inputs GRPxL1,
GRPxL2 and GRPxL3 must be connected in order to calculate the positive sequence voltage.

If only one phase-phase voltage is available and SMAI setting ConnectionType is Ph-Ph, the
user is advised to connect two (not three) of the inputs GRPxL1, GRPxL2 and GRPxL3 to the
same voltage input as shown in figure 308 to make SMAI calculate a positive sequence voltage.

SMAI1
BLOCK SPFCOUT SAPTOF
DFTSPFC G1AI3P U3P* TRIP SAPTOF(1)_TRIP
UL1L2 BLOCK START
REVROT G1AI1
PHASEL1 G1AI2 BLKTRIP BLKDMAGN
^GRP1L1 G1AI4 FREQ
TRM_40.CH7(U) PHASEL2
G1N
^GRP1L2
PHASEL3
^GRP1L3
NEUTRAL
^GRP1N

EC10000060-3-en.vsdx
IEC10000060 V3 EN-US

Figure 308: Connection example

The above described scenario does not work if SMAI setting ConnectionType is
Ph-N. If only one phase-earth voltage is available, the same type of connection
can be used but the SMAI ConnectionType setting must still be Ph-Ph and this
has to be accounted for when setting MinValFreqMeas. If SMAI setting
ConnectionType is Ph-N and the same voltage is connected to all three SMAI
inputs, the positive sequence voltage will be zero and the frequency functions
will not work properly.

The outputs from the above configured SMAI block shall only be used for
Overfrequency protection (SAPTOF), Underfrequency protection (SAPTUF) and
Rate-of-change frequency protection (SAPFRC) due to that all other
information except frequency and positive sequence voltage might be wrongly
calculated.

16.9 Summation block 3 phase 3PHSUM SEMOD55968-1 v2

16.9.1 Functionality SEMOD55976-4 v4

Summation block 3 phase function 3PHSUM is used to get the sum of two sets of three-phase
analog signals (of the same type) for those IED functions that might need it.

590 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 16
Basic IED functions

16.9.2 Function block SEMOD54885-4 v4

3PHSUM
BLOCK SPFCOUT
BLKGR1 AI3P
BLKGR2 AI1
REVROT AI2
^G1AI3P* AI3
^G2AI3P* AI4
IEC05000441-4-en.vsdx
IEC05000441 V4 EN-US

Figure 309: 3PHSUM function block

16.9.3 Signals SEMOD55989-1 v2

PID-6428-INPUTSIGNALS v3

Table 529: 3PHSUM Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block
BLKGR1 BOOLEAN 0 Block input for group 1
BLKGR2 BOOLEAN 0 Block input for group 2
REVROT BOOLEAN 0 Reverse rotation
G1AI3P GROUP - Group 1 three phase analog input from first SMAI
SIGNAL
G2AI3P GROUP - Group 2 three phase analog input from second SMAI
SIGNAL

PID-6428-OUTPUTSIGNALS v4

Table 530: 3PHSUM Output signals


Name Type Description
SPFCOUT REAL Number of samples per fundamental cycle from internal DFT
reference function
AI3P GROUP SIGNAL Linear combination of two connected three phase inputs
AI1 GROUP SIGNAL Linear combination of input 1 signals from both SMAI blocks
AI2 GROUP SIGNAL Linear combination of input 2 signals from both SMAI blocks
AI3 GROUP SIGNAL Linear combination of input 3 signals from both SMAI blocks
AI4 GROUP SIGNAL Linear combination of input 4 signals from both SMAI blocks

16.9.4 Settings SEMOD55995-1 v2

SEMOD130361-4 v2

Settings DFTRefExtOut and DFTReference shall be set to default value


InternalDFTRef if no VT inputs are available.

Breaker protection REQ650 591


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 16 1MRK 505 384-UEN C
Basic IED functions

PID-6428-SETTINGS v3

Table 531: 3PHSUM Non group settings (basic)


Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
SummationType Group1+Group2 - - Group1+Group2 Summation type
Group1-Group2
Group2-Group1
-(Group1+Group2)
DFTReference InternalDFTRef - - InternalDFTRef DFT reference
DFTRefGrp1
External DFT ref
DFTRefExtOut InternalDFTRef - - InternalDFTRef DFT reference for external output
DFTRefGrp1
External DFT ref

Table 532: 3PHSUM Non group settings (advanced)


Name Values (Range) Unit Step Default Description
FreqMeasMinVal 5 - 200 % 1 10 Amplitude limit for frequency
calculation in % of UBase

16.9.5 Operation principle SEMOD55749-4 v6

Summation block 3 phase 3PHSUM receives the three-phase signals from Signal matrix for
analog inputs function (SMAI). The BLOCK input will reset all the outputs of the function to 0.

592 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 17
IED hardware

Section 17 IED hardware


17.1 Overview IP14270-1 v1

17.1.1 Variants of case size with local HMI display M15024-3 v6

IEC04000458-2-en.psd
IEC04000458 V2 EN-US

Figure 310: 1/2 19” case with local HMI display.

Breaker protection REQ650 593


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 505 384-UEN C
IED hardware

17.1.2 Case from the front and rear sides IP16286-1 v2

M16105-3 v10

Table 533: Designations for 1/2 x 19” casing with 1 TRM slot

1/2x19"
Front view Rear position Module
p40 p31 p30 p5 p4 p3 p1
P30:1

X11 PSM
P30:2

X31 and X32 etc. to X51 and X52 BIM, BOM or IOM
P30:3

X301, X302, X303, X304 SFP


P30:4

X305 LDCM
P31:1

6U
X306 LDCM
X311: A, B, C, D SLM
P31:2
P30:5

X312 LDCM or IRIG-B


P31:3
P30:6

X313 LDCM, IRIG-B or RS485


X401 TRM
Rear view
X11 X31 X41 X51 X401
X301

X302

X303

X311
A

X304
B

X32 X42 X52 D

X305 X312

X306 X313

IEC17000067 V1 EN-US

17.2 Hardware modules IP14529-1 v1

17.2.1 Overview M11562-3 v11

Table 534: Basic modules


Module Description
Power supply module (PSM) Including a regulated DC/DC converter that supplies auxiliary
voltage to all static circuits.

• An internal fail alarm output is available.

Numerical module (NUM) Module for overall application control. All information is
processed or passed through this module, such as
configuration, settings and communication. The module
provides four SFPs for Ethernet traffic.
Local Human machine interface (LHMI) The module consists of LEDs, an LCD, a push button
keyboard and an ethernet connector used to connect a PC to
the IED.
Transformer input module (TRM) Transformer module that galvanically separates the internal
circuits from the VT and CT circuits. It has 12 analog inputs.
Table continues on next page

594 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 17
IED hardware

Module Description
Analog digital conversion module (ADM) The module converts the VT and CT analog signals from the
TRM to digital signals processed by the NUM. Carrier for
communication boards.
Note: TRM module is not included in SAM600-IO, so ADM
module is only used for internal communication carrier for IO
modules.
Combined backplane module (CBM) The module has two main purposes: to distribute supply
voltages from the PSM to the other modules and to act as a
communication carrier via its two buses, CompactPCI for fast
I/O and communication and CAN for slow I/O.
Universal backplane module (UBM) The module is used to interconnect the TRM and the ADM. It
also connects the NUM with the LHMI

Table 535: Application specific modules


Module Description
Binary input module (BIM) Module with 16 optically isolated binary inputs
Binary output module (BOM) Module with 24 single outputs or 12 double-pole command
outputs including supervision function
Binary I/O module (IOM) Module with 8 optically isolated binary inputs, 10 outputs and
2 fast signalling outputs.
Serial SPA/LON/IEC 60870-5-103 Used for SPA/LON/IEC 60870–5–103 communication
communication modules (SLM)
Optical Ethernet SFP Small form factor pluggable for Ethernet communication
Galvanic RJ45 Ethernet SFP Small form factor pluggable for Ethernet communication
Galvanic RS485 communication module Module used for DNP3 and IEC 60870-5-103 communication
(RS485)
IRIG-B Time synchronization module (IRIG-B) Module with 2 inputs. One is used for handling both pulse-
width modulated signals and amplitude modulated signals
and one is used for optical input type ST for PPS time
synchronization.

17.2.2 Numeric module (NUM) IP14288-1 v2

17.2.2.1 Introduction M12643-3 v4

The numeric processing module (NUM) is a CPU module that handles all protection functions
and logic.

For communication with high speed modules, for example analog input modules and high
speed serial interfaces, NUM is equipped with a Compact PCI bus. NUM is a compact PCI
system card, that is, it controls bus mastering, clock distribution and receives interrupts.

NUM provides up to 4 optical (type LC) or galvanic (type RJ45) Ethernet ports(one basic and
three optional).

17.2.2.2 Functionality M12644-3 v5

The numeric module (NUM) is a high-performance CPU module based on a dual-core


processor. It is 6U high and occupies one slot. Contact with the backplane is achieved via a
compact PCI connector and an euro connector.

Breaker protection REQ650 595


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 505 384-UEN C
IED hardware

The NUM has two PC-MIP expansion slots where mezzanine cards, such as the LDCM, can be
mounted. It also has four SFP cages for Ethernet communication. Up to four SFP transceivers
for optical 100BASE-FX or galvanic RJ45 100BASE-TX communication can be mounted in the
SFP cages.

Only SPF transceivers approved by ABB (1MRK005500) are compatible with the
SFP cages.

Application code and configuration data are stored in flash memory, and non-volatile RAM is
used to store log data.

The NUM is equipped with a real time clock. It uses a capacitor to keep track of the time when
the IED is not energized.

The NUM is passively cooled, which is possible due to its low power dissipation.

17.2.2.3 Technical data SEMOD55319-1 v1

SEMOD55310-2 v13

Table 536: SFP - Optical ethernet port


Quantity Rated value
Number of channels 4 single or 2 redundant can be used for single or redundant
communication using any protocol
Standard IEEE 802.3u 100BASE-FX
Type of fiber 62.5/125 mm multimode fiber
Wave length 1310 nm, Class 1 laser safety
Optical connector Type LC
Communication speed Fast Ethernet 100 Mbit/s

Table 537: SFP - Galvanic RJ45


Quantity Rated value
Number of channels Up to 6 single or 3 redundant or a combination of single and
redundant links for communication using any protocol
Standard IEEE 802.3u 100BASE-TX
Type of cable Cat5e FTP
Connector Type RJ45
Communication Speed Fast Ethernet 100 Mbit/s

GUID-96676D5D-0835-44DA-BC22-058FD18BDF34 v3

Table 538: NUM: Communication ports

NUM 4 Ethernet ports


1 Basic, 3 Optional
Ethernet connection type SFP Optical LC or Galvanic RJ45

596 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 17
IED hardware

17.2.3 Power supply module (PSM) IP15594-1 v1

17.2.3.1 Introduction M11595-3 v6

The power supply module is used to provide the correct internal voltages and full isolation
between the IED and the battery system. An internal fail alarm output is available.

Alternative connectors of Ring lug or Compression type can be ordered.

17.2.3.2 Design IP14278-1 v1

M6377-3 v2
There are two types of the power supply module. They are designed for different DC input
voltage ranges see table 539. The power supply module contains a built-in, self-regulated
DC/DC converter that provides full isolation between the terminal and the external battery
system.

The DC input is protected against inverse polarity within the rated DC voltage range.

Connection diagram M6377-8 v3

IEC08000476 V2 EN-US

Figure 311: PSM Connection diagram.

17.2.3.3 Technical data SEMOD52801-1 v1

M12286-1 v9

Table 539: PSM - Power supply module


Quantity Rated value Nominal range
Auxiliary DC voltage, EL (input) EL = (24-60) V EL ±20%
EL = (90-250) V EL ±20%
Power consumption 32 W typically -
Auxiliary DC power in-rush < 10 A during 0.1 s -
Supply interruption bridging time < 50 ms -

17.2.4 Local human-machine interface (Local HMI) SEMOD56218-5 v4

Refer to section Local HMI for information.

17.2.5 Transformer input module (TRM) IP15581-1 v1

Breaker protection REQ650 597


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 505 384-UEN C
IED hardware

17.2.5.1 Introduction M14875-3 v9

The transformer input module is used to galvanically separate and adapt the secondary
currents and voltages generated by the measuring transformers. The module has twelve
inputs in different combinations of currents and voltage inputs.

Alternative connectors of Ring lug or Compression type can be ordered.

17.2.5.2 Design M14858-3 v8

TRM variants are available depending on the product. The rated values and channel type of the
current inputs are selected at order.

Transformer input module for measuring should not be used with current
transformers intended for protection purposes, due to limitations in overload
characteristics.

The TRM is connected to the ADM and NUM.

For configuration of the input and output signals, refer to section "Signal matrix for analog
inputs SMAI".

1MRK006501-AF-TRM-IEC-6502P1 V1 EN-US

Figure 312: TRM connection diagram

598 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 17
IED hardware

17.2.5.3 Technical data SEMOD55412-1 v1

M16988-1 v11

Table 540: TRM - Energizing quantities, rated values and limits for protection transformer
Description Value
Frequency
Rated frequency fr 50/60 Hz

Operating range fr ± 10%

Current inputs
Rated current Ir 1 or 5 A

Operating range (0-100) x Ir

Thermal withstand 100 × Ir for 1 s *)


30 × Ir for 10 s
10 × Ir for 1 min
4 × Ir continuously

Dynamic withstand 250 × Ir one half wave

Burden < 20 mVA at Ir = 1 A


< 150 mVA at Ir = 5 A

*) max. 350 A for 1 s when COMBITEST test switch is included.


Voltage inputs **)
Rated voltage Ur 110 or 220 V

Operating range 0 - 340 V


Thermal withstand 450 V for 10 s
420 V continuously
Burden < 20 mVA at 110 V
< 80 mVA at 220 V
**) all values for individual voltage inputs
Note! All current and voltage data are specified as RMS values at rated frequency

17.2.6 Binary input module (BIM) IP14535-1 v1

17.2.6.1 Introduction M1769-3 v4

The binary input module has 16 optically isolated inputs and is available in two versions, one
standard and one with enhanced pulse counting capabilities on the inputs to be used with the
pulse counter function. The binary inputs are freely programmable and can be used for the
input of logical signals to any of the functions. They can also be included in the disturbance
recording and event-recording functions. This enables extensive monitoring and evaluation of
operation of the IED and for all associated electrical circuits.

17.2.6.2 Design M11586-3 v6

The Binary input module contains 16 optical isolated binary inputs. The voltage level of the
binary input is selected at order.

For configuration of the input signals, refer to section "Signal matrix for binary inputs SMBI".

Breaker protection REQ650 599


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 505 384-UEN C
IED hardware

A signal discriminator detects and blocks oscillating signals. When blocked, a hysteresis
function may be set to release the input at a chosen frequency, making it possible to use the
input for pulse counting. The blocking frequency may also be set.

Well defined input high and input low voltages ensure normal operation at battery supply earth
faults, see figure 313 The figure shows the typical operating characteristics of the binary
inputs of the four voltage levels.

The standard version of binary inputs gives an improved capability to withstand disturbances
and should generally be used when pulse counting is not required. Inputs are debounced by
software.

I/O events are time stamped locally on each module for minimum time deviance and stored by
the event recorder if present.

[V]

300

176
144
88
72
38
32
19
17

24/30V 48/60V 110/125V 220/250V

xx06000391-2-en.vsd
IEC06000391 V2 EN-US

Figure 313: Voltage dependence for the binary inputs

Operation

Operation uncertain

No operation
IEC99000517-ABC V1 EN-US

This binary input module communicates with the Numerical module (NUM).

The design of all binary inputs enables the burn off of the oxide of the relay contact connected
to the input, despite the low, steady-state power consumption, which is shown in figure "" and
314.

600 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 17
IED hardware

[mA]
50

5.5 [ms]

en07000105-1.vsd
IEC07000105 V2 EN-US

Figure 314: Approximate binary input inrush current for the BIM version with enhanced
pulse counting capabilities.

IEC99000503 V3 EN-US

Figure 315: Connection diagram

Breaker protection REQ650 601


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 505 384-UEN C
IED hardware

17.2.6.3 Signals
PID-6435-OUTPUTSIGNALS v5

Table 541: BIM Output signals


Name Type Description
STATUS BOOLEAN Binary input module status
BI1 BOOLEAN Binary input 1 value
BI2 BOOLEAN Binary input 2 value
BI3 BOOLEAN Binary input 3 value
BI4 BOOLEAN Binary input 4 value
BI5 BOOLEAN Binary input 5 value
BI6 BOOLEAN Binary input 6 value
BI7 BOOLEAN Binary input 7 value
BI8 BOOLEAN Binary input 8 value
BI9 BOOLEAN Binary input 9 value
BI10 BOOLEAN Binary input 10 value
BI11 BOOLEAN Binary input 11 value
BI12 BOOLEAN Binary input 12 value
BI13 BOOLEAN Binary input 13 value
BI14 BOOLEAN Binary input 14 value
BI15 BOOLEAN Binary input 15 value
BI16 BOOLEAN Binary input 16 value
OSCWRN BOOLEAN Oscillation warning

17.2.6.4 Settings
PID-3473-SETTINGS v2

Table 542: BIM Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - On Operation Off/On
On
DebounceTime 0.001 - 0.020 s 0.001 0.001 Debounce time for binary inputs
OscBlock 1 - 40 Hz 1 40 Oscillation block limit
OscRelease 1 - 30 Hz 1 30 Oscillation release limit

17.2.6.5 Monitored data


PID-3473-MONITOREDDATA v2

Table 543: BIM Monitored data


Name Type Values (Range) Unit Description
STATUS BOOLEAN 0=Ok - Binary input module status
1=Error

602 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 17
IED hardware

17.2.6.6 Technical data SEMOD55338-1 v1

M50609-2 v9

Table 544: BIM - Binary input module with enhanced pulse counting capabilities
Quantity Rated value Nominal range
Binary inputs 16 -
DC voltage, RL 24/30 V RL ±20%
48/60 V RL ±20%
110/125 V RL ±20%
220/250 V RL ±20%
Power consumption
24/30 V max. 0.05 W/input -
48/60 V max. 0.1 W/input
110/125 V max. 0.2 W/input
220/250 V max. 0.4 W/input
Counter input frequency 10 pulses/s max -
Balanced counter input frequency 40 pulses/s max -
Oscillating signal discriminator Blocking settable 1–40 Hz
Release settable 1–30 Hz
*Debounce filter Settable 1-20 ms
Binary input operate time 3 ms -
(Debounce filter set to 0 ms)
* Note: For compliance with surge immunity a debounce filter time setting of 5 ms is required.

The stated operate time for functions include the operating time for the binary
inputs and outputs.

17.2.7 Binary output modules (BOM) IP14536-1 v1

17.2.7.1 Introduction M6938-3 v4

The binary output module has 24 independent output relays and is used for trip output or any
signaling purpose.

17.2.7.2 Design M1819-3 v4

The binary output module (BOM) has 24 software supervised output relays. Each pair of relays
have a common power source input to the contacts, see figure 316. This should be considered
when connecting the wiring to the connection terminal on the back of the IED.

The high closing and carrying current capability allows connection directly to breaker trip and
closing coils. If breaking capability is required to manage fail of the breaker auxiliary contacts
normally breaking the trip coil current, a parallel reinforcement is required.

For configuration of the output signals, refer to section "Signal matrix for binary outputs
SMBO".

Breaker protection REQ650 603


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 505 384-UEN C
IED hardware

Output module

xx00000299.vsd

IEC00000299 V1 EN-US

Figure 316: Relay pair example

1 Output connection from relay 1


2 Output signal power source connection
3 Output connection from relay 2

IEC99000505 V4 EN-US

Figure 317: Connection diagram

604 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 17
IED hardware

17.2.7.3 Signals
PID-3439-INPUTSIGNALS v2

Table 545: BOM Input signals


Name Type Default Description
BLOCK BOOLEAN 0 Block binary outputs
BO1 BOOLEAN 0 Binary output 1
BO2 BOOLEAN 0 Binary output 2
BO3 BOOLEAN 0 Binary output 3
BO4 BOOLEAN 0 Binary output 4
BO5 BOOLEAN 0 Binary output 5
BO6 BOOLEAN 0 Binary output 6
BO7 BOOLEAN 0 Binary output 7
BO8 BOOLEAN 0 Binary output 8
BO9 BOOLEAN 0 Binary output 9
BO10 BOOLEAN 0 Binary output 10
BO11 BOOLEAN 0 Binary output 11
BO12 BOOLEAN 0 Binary output 12
BO13 BOOLEAN 0 Binary output 13
BO14 BOOLEAN 0 Binary output 14
BO15 BOOLEAN 0 Binary output 15
BO16 BOOLEAN 0 Binary output 16
BO17 BOOLEAN 0 Binary output 17
BO18 BOOLEAN 0 Binary output 18
BO19 BOOLEAN 0 Binary output 19
BO20 BOOLEAN 0 Binary output 20
BO21 BOOLEAN 0 Binary output 21
BO22 BOOLEAN 0 Binary output 22
BO23 BOOLEAN 0 Binary output 23
BO24 BOOLEAN 0 Binary output 24

PID-3439-OUTPUTSIGNALS v1

Table 546: BOM Output signals


Name Type Description
STATUS BOOLEAN Binary output part of IOM module status

17.2.7.4 Settings
PID-3439-SETTINGS v2

Table 547: BOM Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - On Operation Off/On
On

Breaker protection REQ650 605


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 505 384-UEN C
IED hardware

17.2.7.5 Monitored data


PID-3439-MONITOREDDATA v2

Table 548: BOM Monitored data


Name Type Values (Range) Unit Description
STATUS BOOLEAN 0=Ok - Binary output part of IOM module
1=Error status
BO1VALUE BOOLEAN 1=1 - Binary output 1 value
0=0
BO1FORCE BOOLEAN 0=Normal - Binary output 1 force
1=Forced
BO1 BOOLEAN 0=Normal - Binary output 1 status
1=Forced
2=Blocked
BO2VALUE BOOLEAN 1=1 - Binary output 2 value
0=0
BO2FORCE BOOLEAN 0=Normal - Binary output 2 force
1=Forced
BO2 BOOLEAN 0=Normal - Binary output 2 status
1=Forced
2=Blocked
BO3VALUE BOOLEAN 1=1 - Binary output 3 value
0=0
BO3FORCE BOOLEAN 0=Normal - Binary output 3 force
1=Forced
BO3 BOOLEAN 0=Normal - Binary output 3 status
1=Forced
2=Blocked
BO4VALUE BOOLEAN 1=1 - Binary output 4 value
0=0
BO4FORCE BOOLEAN 0=Normal - Binary output 4 force
1=Forced
BO4 BOOLEAN 0=Normal - Binary output 4 status
1=Forced
2=Blocked
BO5VALUE BOOLEAN 1=1 - Binary output 5 value
0=0
BO5FORCE BOOLEAN 0=Normal - Binary output 5 force
1=Forced
BO5 BOOLEAN 0=Normal - Binary output 5 status
1=Forced
2=Blocked
BO6VALUE BOOLEAN 1=1 - Binary output 6 value
0=0
BO6FORCE BOOLEAN 0=Normal - Binary output 6 force
1=Forced
BO6 BOOLEAN 0=Normal - Binary output 6 status
1=Forced
2=Blocked
BO7VALUE BOOLEAN 1=1 - Binary output 7 value
0=0
BO7FORCE BOOLEAN 0=Normal - Binary output 7 force
1=Forced
Table continues on next page

606 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 17
IED hardware

Name Type Values (Range) Unit Description


BO7 BOOLEAN 0=Normal - Binary output 7 status
1=Forced
2=Blocked
BO8VALUE BOOLEAN 1=1 - Binary output 8 value
0=0
BO8FORCE BOOLEAN 0=Normal - Binary output 8 force
1=Forced
BO8 BOOLEAN 0=Normal - Binary output 8 status
1=Forced
2=Blocked
BO9VALUE BOOLEAN 1=1 - Binary output 9 value
0=0
BO9FORCE BOOLEAN 0=Normal - Binary output 9 force
1=Forced
BO9 BOOLEAN 0=Normal - Binary output 9 status
1=Forced
2=Blocked
BO10VALUE BOOLEAN 1=1 - Binary output 10 value
0=0
BO10FORCE BOOLEAN 0=Normal - Binary output 10 force
1=Forced
BO10 BOOLEAN 0=Normal - Binary output 10 status
1=Forced
2=Blocked
BO11VALUE BOOLEAN 1=1 - nary output 11 value
0=0
BO11FORCE BOOLEAN 0=Normal - Binary output 11 force
1=Forced
BO11 BOOLEAN 0=Normal - Binary output 11 status
1=Forced
2=Blocked
BO12VALUE BOOLEAN 1=1 - Binary output 12 value
0=0
BO12FORCE BOOLEAN 0=Normal - Binary output 12 force
1=Forced
BO12 BOOLEAN 0=Normal - Binary output 12 status
1=Forced
2=Blocked
BO13VALUE BOOLEAN 1=1 - Binary output 13 value
0=0
BO13FORCE BOOLEAN 0=Normal - Binary output 13 force
1=Forced
BO13 BOOLEAN 0=Normal - Binary output 13 status
1=Forced
2=Blocked
BO14VALUE BOOLEAN 1=1 - Binary output 14 value
0=0
BO14FORCE BOOLEAN 0=Normal - Binary output 14 force
1=Forced
BO14 BOOLEAN 0=Normal - Binary output 14 status
1=Forced
2=Blocked
BO15VALUE BOOLEAN 1=1 - Binary output 15 value
0=0
Table continues on next page

Breaker protection REQ650 607


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 505 384-UEN C
IED hardware

Name Type Values (Range) Unit Description


BO15FORCE BOOLEAN 0=Normal - Binary output 15 force
1=Forced
BO15 BOOLEAN 0=Normal - Binary output 15 status
1=Forced
2=Blocked
BO16VALUE BOOLEAN 1=1 - Binary output 16 value
0=0
BO16FORCE BOOLEAN 0=Normal - Binary output 16 force
1=Forced
BO16 BOOLEAN 0=Normal - Binary output 16 status
1=Forced
2=Blocked
BO17VALUE BOOLEAN 1=1 - Binary output 17 value
0=0
B017FORCE BOOLEAN 0=Normal - Binary output 17 force
1=Forced
BO17 BOOLEAN 0=Normal - Binary output 17 status
1=Forced
2=Blocked
BO18VALUE BOOLEAN 1=1 - Binary output 18 value
0=0
BO18FORCE BOOLEAN 0=Normal - Binary output 18 force
1=Forced
BO18 BOOLEAN 0=Normal - Binary output 18 status
1=Forced
2=Blocked
BO19VALUE BOOLEAN 1=1 - Binary output 19 value
0=0
BO19FORCE BOOLEAN 1=Forced - Binary output 19 force
0=Normal
BO19 BOOLEAN 0=Normal - Binary output 19 status
1=Forced
2=Blocked
BO20VALUE BOOLEAN 1=1 - Binary output 20 value
0=0
BO20FORCE BOOLEAN 0=Normal - Binary output 20 force
1=Forced
BO20 BOOLEAN 0=Normal - Binary output 20 status
1=Forced
2=Blocked
BO21VALUE BOOLEAN 1=1 - Binary output 21 value
0=0
BO21FORCE BOOLEAN 0=Normal - Binary output 21 force
1=Forced
BO21 BOOLEAN 0=Normal - Binary output 21 status
1=Forced
2=Blocked
BO22VALUE BOOLEAN 1=1 - Binary output 22 value
0=0
BO22FORCE BOOLEAN 0=Normal - Binary output 22 force
1=Forced
BO22 BOOLEAN 0=Normal - Binary output 22 status
1=Forced
2=Blocked
Table continues on next page

608 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 17
IED hardware

Name Type Values (Range) Unit Description


BO23VALUE BOOLEAN 1=1 - Binary output 23 value
0=0
BO23FORCE BOOLEAN 0=Normal - Binary output 23 force
1=Forced
BO23 BOOLEAN 0=Normal - Binary output 23 status
1=Forced
2=Blocked
BO24VALUE BOOLEAN 1=1 - Binary output 24 value
0=0
BO24FORCE BOOLEAN 0=Normal - nary output 24 force
1=Forced
BO24 BOOLEAN 0=Normal - Binary output 24 status
1=Forced
2=Blocked

17.2.7.6 Technical data SEMOD55355-1 v1

M12441-1 v10

Table 549: BOM - Binary output module contact data (reference standard: IEC 61810-2)
Function or quantity Trip and Signal relays
Binary outputs 24
Max system voltage 250 V AC, DC
Min load voltage 24VDC
Test voltage across open contact, 1 min 1000 V rms
Current carrying capacity
Per relay, continuous 8A
Per relay, 1 s 10 A
Per process connector pin, continuous 12 A
Max operations with load 1000
Max operations with no load 10000
Making capacity at inductive load with L/R > 10 ms
0.2 s 30 A
1.0 s 10 A

Breaking capacity for AC, cos j > 0.4 250 V/8.0 A

Breaking capacity for DC with L/R < 40 ms 48 V/1 A


110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
Operating time < 6 ms

Maximum 72 outputs may be activated simultaneously with influencing factors


within nominal range. After 6 ms an additional 24 outputs may be activated.
The activation time for the 96 outputs must not exceed 200 ms. 48 outputs can
be activated during 1 s. Continued activation is possible with respect to current
consumption but after 5 minutes the temperature rise will adversely affect the
hardware life. Maximum two relays per BOM/IOM should be activated
continuously due to power dissipation.

Breaker protection REQ650 609


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 505 384-UEN C
IED hardware

The stated operate time for functions include the operating time for the binary
inputs and outputs.

17.2.8 Binary input/output module (IOM) IP15582-1 v1

17.2.8.1 Introduction M6939-3 v6

The binary input/output module is used when only a few input and output channels are
needed. The ten standard output channels are used for trip output or any signaling purpose.
The two high speed signal output channels are used for applications where short operating
time is essential. Eight optically isolated binary inputs cater for required binary input
information.

17.2.8.2 Design IP10635-1 v2

M1718-3 v4
The binary input/output module is available in two basic versions, one with unprotected
contacts and one with MOV (Metal Oxide Varistor) protected contacts.

Inputs are designed to allow oxide burn-off from connected contacts, and increase the
disturbance immunity during normal protection operate times. This is achieved with a high
peak inrush current while having a low steady-state current, see figure "". Inputs are
debounced by software.

Well defined input high and input low voltages ensures normal operation at battery supply
earth faults, see figure 313.

The voltage level of the inputs is selected when ordering. Alternative connectors of Ring lug or
Compression type can be ordered.

I/O events are time stamped locally on each module for minimum time deviance and stored by
the event recorder if present.
SEMOD175370-4 v1
The binary input/output module version with MOV protected contacts can for example be
used in applications where breaking high inductive load would cause excessive wear of the
contacts.

The test voltage across open contact is lower for this version of the binary
input/output module.

xx04000069.vsd

IEC04000069 V1 EN-US

Figure 318: IOM with MOV protection, relay example

610 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 17
IED hardware

17.2.8.3 Signals
PID-6434-OUTPUTSIGNALS v4

Table 550: IOMIN Output signals


Name Type Description
STATUS BOOLEAN Binary input part of IOM module status
BI1 BOOLEAN Binary input 1 value
BI2 BOOLEAN Binary input 2 value
BI3 BOOLEAN Binary input 3 value
BI4 BOOLEAN Binary input 4 value
BI5 BOOLEAN Binary input 5 value
BI6 BOOLEAN Binary input 6 value
BI7 BOOLEAN Binary input 7 value
BI8 BOOLEAN Binary input 8 value
OSCWRN BOOLEAN Oscillation warning

PID-4049-INPUTSIGNALS v2

Table 551: IOMOUT Input signals


Name Type Default Description
BLKOUT BOOLEAN 0 Block binary outputs
BO1 BOOLEAN 0 Binary output 1
BO2 BOOLEAN 0 Binary output 2
BO3 BOOLEAN 0 Binary output 3
BO4 BOOLEAN 0 Binary output 4
BO5 BOOLEAN 0 Binary output 5
BO6 BOOLEAN 0 Binary output 6
BO7 BOOLEAN 0 Binary output 7
BO8 BOOLEAN 0 Binary output 8
BO9 BOOLEAN 0 Binary output 9
BO10 BOOLEAN 0 Binary output 10
BO11 BOOLEAN 0 Binary output 11
BO12 BOOLEAN 0 Binary output 12

17.2.8.4 Settings
PID-4050-SETTINGS v2

Table 552: IOMIN Non group settings (basic)


Name Values (Range) Unit Step Default Description
Operation Off - - On Binary input/output module in
On operation (On) or not (Off)
DebounceTime 0.001 - 0.020 s 0.001 0.001 Debounce time for binary inputs
OscBlock 1 - 40 Hz 1 40 Oscillation block limit
OscRelease 1 - 30 Hz 1 30 Oscillation release limit

Breaker protection REQ650 611


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 505 384-UEN C
IED hardware

17.2.8.5 Monitored data


PID-4050-MONITOREDDATA v2

Table 553: IOMIN Monitored data


Name Type Values (Range) Unit Description
STATUS BOOLEAN 0=Ok - Binary input part of IOM module
1=Error status

PID-4049-MONITOREDDATA v2

Table 554: IOMOUT Monitored data


Name Type Values (Range) Unit Description
BO1VALUE BOOLEAN 1=1 - Binary output 1 value
0=0
BO1FORCE BOOLEAN 0=Normal - Binary output 1 force
1=Forced
BO1 BOOLEAN 0=Normal - Binary output 1 status
1=Forced
2=Blocked
BO2VALUE BOOLEAN 1=1 - Binary output 2 value
0=0
BO2FORCE BOOLEAN 0=Normal - Binary output 2 force
1=Forced
BO2 BOOLEAN 0=Normal - Binary output 2 status
1=Forced
2=Blocked
BO3VALUE BOOLEAN 1=1 - Binary output 3 value
0=0
BO3FORCE BOOLEAN 0=Normal - Binary output 3 force
1=Forced
BO3 BOOLEAN 0=Normal - Binary output 3 status
1=Forced
2=Blocked
BO4VALUE BOOLEAN 1=1 - Binary output 4 value
0=0
BO4FORCE BOOLEAN 0=Normal - Binary output 4 force
1=Forced
BO4 BOOLEAN 0=Normal - Binary output 4 status
1=Forced
2=Blocked
BO5VALUE BOOLEAN 1=1 - Binary output 5 value
0=0
BO5FORCE BOOLEAN 0=Normal - Binary output 5 force
1=Forced
BO5 BOOLEAN 0=Normal - Binary output 5 status
1=Forced
2=Blocked
BO6VALUE BOOLEAN 1=1 - Binary output 6 value
0=0
BO6FORCE BOOLEAN 0=Normal - Binary output 6 force
1=Forced
BO6 BOOLEAN 0=Normal - Binary output 6 status
1=Forced
2=Blocked
Table continues on next page

612 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 17
IED hardware

Name Type Values (Range) Unit Description


BO7VALUE BOOLEAN 1=1 - Binary output 7 value
0=0
BO7FORCE BOOLEAN 0=Normal - Binary output 7 force
1=Forced
BO7 BOOLEAN 0=Normal - Binary output 7 status
1=Forced
2=Blocked
BO8VALUE BOOLEAN 1=1 - Binary output 8 value
0=0
BO8FORCE BOOLEAN 0=Normal - Binary output 8 force
1=Forced
BO8 BOOLEAN 0=Normal - Binary output 8 status
1=Forced
2=Blocked
BO9VALUE BOOLEAN 1=1 - Binary output 9 value
0=0
BO9FORCE BOOLEAN 0=Normal - Binary output 9 force
1=Forced
BO9 BOOLEAN 0=Normal - Binary output 9 status
1=Forced
2=Blocked
BO10VALUE BOOLEAN 1=1 - Binary output 10 value
0=0
BO10FORCE BOOLEAN 0=Normal - Binary output 10 force
1=Forced
BO10 BOOLEAN 0=Normal - Binary output 10 status
1=Forced
2=Blocked
BO11VALUE BOOLEAN 1=1 - Binary output 11 value
0=0
BO11FORCE BOOLEAN 0=Normal - Binary output 11 force
1=Forced
BO11 BOOLEAN 0=Normal - Binary output 11 status
1=Forced
2=Blocked
BO12VALUE BOOLEAN 1=1 - Binary output 12 value
0=0
BO12FORCE BOOLEAN 0=Normal - Binary output 12 force
1=Forced
BO12 BOOLEAN 0=Normal - Binary output 12 status
1=Forced
2=Blocked

Breaker protection REQ650 613


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 505 384-UEN C
IED hardware

17.2.8.6 Technical data IP10636-1 v1

M12573-1 v11

Table 555: IOM - Binary input/output module


Quantity Rated value Nominal range
Binary inputs 8 -
DC voltage, RL 24/30 V RL ±20%
48/60 V RL ±20%
110/125 V RL ±20%
220/250 V RL ±20%
Power consumption -
24/30 V, 50 mA max. 0.05 W/input
48/60 V, 50 mA max. 0.1 W/input
110/125 V, 50 mA max. 0.2 W/input
220/250 V, 50 mA max. 0.4 W/input
220/250 V, 110 mA max. 0.5 W/input
Counter input frequency 10 pulses/s max
Oscillating signal discriminator Blocking settable 1-40 Hz
Release settable 1-30 Hz
*Debounce filter Settable 1-20 ms
Binary input operate time 3 ms -
(Debounce filter set to 0 ms)
* Note: For compliance with surge immunity a debounce filter time setting of 5 ms is required.

The stated operate time for functions include the operating time for the binary
inputs and outputs.

M12318-1 v10

Table 556: IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
Function or quantity Trip and signal relays Fast signal relays (parallel
reed relay)
Binary outputs 10 2
Max system voltage 250 V AC, DC 250 V DC
Min load voltage 24VDC —
Test voltage across open contact, 1 min 1000 V rms 800 V DC
Current carrying capacity
Per relay, continuous 8A 8A
Per relay, 1 s 10 A 10 A
Per process connector pin, continuous 12 A 12 A
Making capacity at inductive load with L/R >
10 ms

0.2 s 30 A 0.4 A
1.0 s 10 A 0.4 A
Making capacity at resistive load
220–250 V/0.4 A
0.2 s 30 A 110–125 V/0.4 A
1.0 s 10 A 48–60 V/0.2 A
24–30 V/0.1 A
Breaking capacity for AC, cos φ > 0.4 250 V/8.0 A 250 V/8.0 A
Table continues on next page

614 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 17
IED hardware

Function or quantity Trip and signal relays Fast signal relays (parallel
reed relay)
Breaking capacity for DC with L/R < 40 ms 48 V/1 A 48 V/1 A
110 V/0.4 A 110 V/0.4 A
125 V/0.35 A 125 V/0.35 A
220 V/0.2 A 220 V/0.2 A
250 V/0.15 A 250 V/0.15 A
Maximum capacitive load - 10 nF
Max operations with load 1000
Max operations with no load 10000
Operating time < 6 ms <= 1 ms

The stated operate time for functions include the operating time for the binary
inputs and outputs.

M12584-1 v10

Table 557: IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-2)
Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay)
Binary outputs IOM: 10 IOM: 2
Max system voltage 250 V AC, DC 250 V DC
Min load voltage 24VDC -
Test voltage across open 250 V rms 250 V rms
contact, 1 min
Current carrying capacity
Per relay, continuous 8A 8A
Per relay, 1 s 10 A 10 A
Per process connector pin, 12 A 12 A
continuous
Making capacity at inductive
loadwith L/R > 10 ms
0.2 s 30 A 0.4 A
1.0 s 10 A 0.4 A
Making capacity at resistive
load 220–250 V/0.4 A
30 A 110–125 V/0.4 A
0.2 s 10 A 48–60 V/0.2 A
1.0 s 24–30 V/0.1 A
Breaking capacity for AC, cos 250 V/8.0 A 250 V/8.0 A
j > 0.4
Breaking capacity for DC with 48 V/1 A 48 V/1 A
L/R < 40 ms 110 V/0.4 A 110 V/0.4 A
220 V/0.2 A 220 V/0.2 A
250 V/0.15 A 250 V/0.15 A
Maximum capacitive load - 10 nF
Max operations with load 1000 -
Max operations with no load 10000 -
Operating time < 6 ms <= 1 ms

The stated operate time for functions include the operating time for the binary
inputs and outputs.

Breaker protection REQ650 615


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 505 384-UEN C
IED hardware

17.2.9 Serial and LON communication module (SLM) IP15583-1 v2

17.2.9.1 Introduction M14933-3 v6

The Serial and LON communication module (SLM) is used for SPA, IEC 60870-5-103, DNP3 and
LON communication. SLM has two optical communication ports for plastic/plastic, plastic/
glass or glass/glass fiber cables. One port is used for serial communication (SPA, IEC
60870-5-103 or DNP3 port) and the other port is used for LON communication.

17.2.9.2 Design M17126-3 v6

SLM is a PMC card and it is factory mounted as a mezzanine card on the first Analog digital
conversion module (ADM). Three variants of SLM are available with different combinations of
optical fiber connectors, see figure 319. The plastic fiber connectors are of snap-in type and
the glass fiber connectors are of ST type.

I
EC0500760=1=en=Or
igi
nal
.psd
IEC05000760 V2 EN-US

Figure 319: SLM variants, component side view

1 Receiver, LON
2 Transmitter, LON
3 Receiver, SPA/IEC 60870-5-103/DNP3
4 Transmitter, SPA/IEC 60870-5-103/DNP3
A Snap-in connector for plastic fiber
B ST connector for glass fiber

When the SLM connectors are viewed from the rear side of the IED, contact 4 is
in the topmost position and contact 1 in the lowest position.

616 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 17
IED hardware

17.2.9.3 Technical data SEMOD117454-1 v1

M12589-1 v4

Table 558: SLM – LON port


Quantity Range or value
Optical connector Glass fiber: type ST
Plastic fiber: type HFBR snap-in
Fiber, optical budget Glass fiber: 11 dB (1000m/3000 ft typically *)
Plastic fiber: 7 dB (10m/35ft typically *)
Fiber diameter Glass fiber: 62.5/125 mm
Plastic fiber: 1 mm
*) depending on optical budget calculation

SEMOD117441-2 v5

Table 559: SLM – SPA/IEC 60870-5-103/DNP3 port


Quantity Range or value
Optical connector Glass fiber: type ST
Plastic fiber: type HFBR snap-in
Fiber, optical budget Glass fiber: 11 dB (1000m/3000ft m typically *)
Plastic fiber: 7 dB (25m/80ft m typically *)
Fiber diameter Glass fiber: 62.5/125 mm
Plastic fiber: 1 mm
*) depending on optical budget calculation

17.2.10 Galvanic RS485 communication module SEMOD174899-1 v1

17.2.10.1 Introduction SEMOD158664-5 v3

The Galvanic RS485 communication module (RS485) is used for DNP3.0 and IEC 60870-5-103
communication. The module has one RS485 communication port. The RS485 is a balanced
serial communication that can be used either in 2-wire or 4-wire connections. A 2-wire
connection uses the same signal for RX and TX and is a multidrop communication with no
dedicated Master or slave. This variant requires however a control of the output. The 4-wire
connection has separated signals for RX and TX multidrop communication with a dedicated
Master and the rest are slaves. No special control signal is needed in this case.

17.2.10.2 Design SEMOD158668-1 v1

SEMOD158670-4 v3
RS485 is a PC-MIP card, and it is factory mounted as a mezzanine card on the Analog digital
conversion module (ADM).

RS485 connector pinouts SEMOD158670-10 v1


The arrangement for the pins in the RS485 connector (figure 320) are presented in table 560:

Table 560: The arrangement for the pins

Pin Name 2-wire Name 4-wire Description


1 RS485+ TX+ Receive/transmit high or transmit high
2 RS485– TX– Receive/transmit
Table continues on next page

Breaker protection REQ650 617


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 505 384-UEN C
IED hardware

3 Term T-Term Termination resistor for transmitter (and receiver in 2–wir


case) (connect to TX+)
4 N.A. R-Term Termination resistor for receiver (connect to RX+)
5 N.A. RX– Receive low
6 N.A. RX+ Receive high

Angle
bracket

Screw
1
terminal
X3 2
1
2 RS485
3 PWB
Screw
4
terminal
5
X1
6

Backplane

IEC06000517 V1 EN-US

Figure 320: RS485 connector

• 2-wire: Connect pin 1 to pin 6 and pin 2 to pin 5

• Termination (2-wire): Connect pin 1 to pin 3

• Termination (4-wire): Connect pin 1 to pin 3 and pin 4 to pin 6

Soft ground connector pinouts SEMOD158670-45 v1


A second 2-pole screw connector is used for the connection of IO-ground. It can be used in two
combinations like:

• Unconnected: No ground of the IO-part · .

• Soft grounded: The IO is connected to the GND with an RC net parallel with a MOV

17.2.10.3 Technical data SEMOD158678-1 v1

SEMOD158710-2 v2

Table 561: Galvanic RS485 communication module


Quantity Range or value
Communication speed 2400–19200 bauds
External connectors RS-485 6-pole connector
Soft ground 2-pole connector

618 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 17
IED hardware

17.2.11 IRIG-B time synchronization module IRIG-B SEMOD141102-1 v1

17.2.11.1 Introduction SEMOD141113-4 v9

The IRIG-B time synchronizing module is used for accurate time synchronizing of the IED from
a station clock.

The Pulse Per Second (PPS) input is supported.

Electrical (BNC) and optical connection (ST) for 0XX and 12X IRIG-B support.

17.2.11.2 Design SEMOD141098-4 v5

The IRIG-B module has two inputs. One input is for the IRIG-B that can handle both a pulse-
width modulated signal (also called unmodulated) and an amplitude modulated signal (also
called sine wave modulated). The other is an optical input type ST for optical pulse-width
modulated signal (IRIG-B 00X). The IRIG-B module is mounted as a mezzanine card on the
Analog digital conversion module (ADM).

ST

Y2
A1

IEC06000304=1=en=Original.ai
IEC06000304 V2 EN-US

Figure 321: IRIG-B PC-MIP board with top left ST connector for optical IRIG-B 00X 820 nm
multimode fiber optic signal input and lower left BNC connector for IRIG-B
signal input

17.2.11.3 Encoding GUID-9F0D795F-80D6-46D2-A5CC-F34F701C8E85 v1

This type of encoding consists of the following options:

• IRIG-B. This encoding is based on the legacy of (pre-2004) IRIG-B standard which is
without any time zone information. IRIG-B uses the timecoding available in IRIG-B 00x and
IRIG-B 12x, where x = 0-7. When x is set in the range from 4-7, the year information is
provided along with year and time data.
• 1344. This encoding is based on the current (2004) IRIG-B standard. IED uses the time zone
information from TIMEZONE:1. The setting 1344 refers to the Annex F in IEEE1344, which
adds information regarding quality of the time using the control bits in the IRIG-B
message. This annex also contains the year information with the variable x that ranges
from 4-7 in the 2004 version of IRIG-B.
• 1344TZ. This encoding is based on the current (2004) IRIG-B standard. This time zone
information from IRIG-B overrides the TIMEZONE:1 settings. This setting” uses the
information as 1344, overriding the TIMEZONE setting.

Breaker protection REQ650 619


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 505 384-UEN C
IED hardware

17.2.11.4 TimeZoneAs1344 GUID-39AACFEA-2E3E-4B39-9D7A-E49DA5DE3506 v1

This type of encoding consists of the following options:

• MinusTZ. Encoded IRIG time minus time zone offset equals UTC at all times.
• PlusTZ. Encoded IRIG time plus time zone offset equals UTC at all times.

17.2.11.5 Settings
PID-5187-SETTINGS v5

Table 562: IRIG-B Non group settings (basic)


Name Values (Range) Unit Step Default Description
SynchType BNC - - Opto Type of synchronization
Opto
TimeDomain LocalTime - - LocalTime Time domain
UTC
Encoding IRIG-B - - IRIG-B Type of encoding
1344
1344TZ
TimeZoneAs1344 MinusTZ - - PlusTZ Time zone as in 1344 standard
PlusTZ

17.2.11.6 Technical data SEMOD141132-1 v1

SEMOD141136-2 v10

Table 563: IRIG-B


Quantity Rated value
Number of channels IRIG-B 1
Number of optical channels 1
Electrical connector:
Electrical connector IRIG-B BNC
Pulse-width modulated 5 Vpp
Amplitude modulated
– low level 1-3 Vpp
– high level 3 x low level, max 9 Vpp
Supported formats IRIG-B 00x, IRIG-B 12x
Accuracy +/-10μs for IRIG-B 00x and +/-100μs for IRIG-B 12x
Input impedance 100 k ohm
Optical connector:
Optical connector IRIG-B Type ST
Type of fiber 62.5/125 μm multimode fiber
Supported formats IRIG-B 00x
Accuracy +/- 1μs

620 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 17
IED hardware

17.3 Dimensions IP11490-1 v3

17.3.1 Case with protective cover SEMOD53199-1 v2

M11985-110 v7

IEC08000163‐3‐en.vsdx

IEC08000163 V3 EN-US

Figure 322: Case with protective cover

Breaker protection REQ650 621


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 505 384-UEN C
IED hardware

IEC08000165‐3‐en.vsdx

IEC08000165 V3 EN-US

Figure 323: Case with protective cover and 19” rack mounting kit

622 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 17
IED hardware

IEC05000503-3-en.vsdx

IEC05000503 V3 EN-US

Figure 324: Protective cover case with details


M11985-120 v6

Case size A B C D E F G H I
(mm)
6U, 1/2 x 19” 265.9 223.7 247.5 255.0 205.8 190.5 466.5 232.5 482.6
The G and I dimensions are defined by the 19” rack mounting kit.

Breaker protection REQ650 623


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 505 384-UEN C
IED hardware

17.3.2 Case without protective cover SEMOD53195-1 v2

M2152-3 v8

IEC08000164-4-en.vsdx

IEC08000164 V4 EN-US

Figure 325: Case without protective cover

624 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 17
IED hardware

IEC08000166‐3‐en.vsdx

IEC08000166 V3 EN-US

Figure 326: Case without protective cover with 19” rack mounting kit
M2152-11 v5

Case size
A B C D E F G H I
(mm)
6U, 1/2 x 19” 265.9 223.7 204.1 249.9 205.8 190.5 466.5 189.1 482.6
The G and I dimensions are defined by the 19” rack mounting kit

Breaker protection REQ650 625


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 505 384-UEN C
IED hardware

17.3.3 Flush mounting dimensions M11571-3 v6

A C

E
D
IEC04000465-3-en.vsd
IEC04000465 V3 EN-US

Figure 327: Flush mounting

Cut-out dimensions (mm)


Case size
Tolerance A B C D
+/-1 +/-1
6U, 1/2 x 19" 210.1 254.3 4.0-10.0 13.5
E = 191.1 mm without rear protection cover, 231.8 mm with rear protection cover

17.3.4 Side-by-side flush mounting dimensions M11984-3 v6

IEC06000182-2-en.vsd
IEC06000182 V2 EN-US

Figure 328: A 1/2 x 19” size IED side-by-side with RHGS6

626 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 17
IED hardware

D
B
E

F
C
xx05000505.vsd
IEC05000505 V1 EN-US

Figure 329: Panel-cut out dimensions for side-by-side flush mounting

Case size A B C D E F G
(mm) ±1 ±1 ±1 ±1 ±1 ±1 ±1
Tolerance
6U, 1/2 x 19” 214.0 259.3 240.4 190.5 34.4 13.2 6.4 diam

17.3.5 Wall mounting dimensions M11569-3 v5

IEC04000471-2-en.vsd
IEC04000471 V2 EN-US

Figure 330: Wall mounting

Case size (mm) A B C D E


6U, 1/2 x 19” 292.0 267.1 272.8 390.0 243.0

Breaker protection REQ650 627


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 505 384-UEN C
IED hardware

17.4 Mounting alternatives IP11721-1 v1

17.4.1 Flush mounting IP10303-1 v1

17.4.1.1 Overview M11967-3 v5

The flush mounting kit can be used for the 1/2 x 19” case size.

Only a single case can be mounted in each cut-out on the cubicle panel, for class IP54
protection. The screws from the IED shall be used to fasten the fasteners to the IED.

Flush mounting cannot be used for side-by-side mounted IEDs when IP54 class
must be fulfilled. Only IP20 class can be obtained when mounting two cases
side-by-side in one (1) cut-out.

To obtain IP54 class protection, an additional factory mounted sealing must be


ordered when ordering the IED.

17.4.1.2 Mounting procedure for flush mounting M11942-2 v5

6
3

IEC16000080=1=en.vsd
IEC16000080 V1 EN-US

Figure 331: Flush mounting details.

PosNo Description Quantity Type


1 Sealing strip, used to obtain IP54 - -
class. The sealing strip is factory
mounted between the case and
front plate.
2 Fastener 2 -
Table continues on next page

628 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 17
IED hardware

3 Groove - -
4 Screw 4 M3x8 mm
5 Joining point of sealing strip - -
6 Panel - -

17.4.2 Wall mounting IP10316-1 v1

17.4.2.1 Overview M11973-3 v7

The IED can be mounted on a wall, a panel or in a cubicle.

Use only the screws included in the mounting kit when mounting the plates and
the angles on the IED. Screws with wrong dimension may damage the PCBs
inside the IED.

If fiber cables are bent too much, the signal can be weakened. Wall mounting is
therefore not recommended for any communication modules with fiber
connection.

17.4.2.2 Mounting procedure for wall mounting M11949-2 v3

Figure 332: Wall mounting details.

17.4.2.3 How to reach the rear side of the IED M11941-2 v5

The IED can be equipped with a rear protection cover recommended to be used with this type
of mounting. See figure 333.

To reach the rear side of the IED, a free space of 80 mm is required on the unhinged side.

Breaker protection REQ650 629


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 505 384-UEN C
IED hardware

3
1

80 mm 2

IEC06000135-2-en.vsd
IEC06000135 V3 EN-US

Figure 333: How to reach the connectors on the rear side of the IED.

PosNo Description Type


1 Screw M4x10
2 Screw M5x8
3 Rear protection cover (Ordered separately)

17.4.3 19” panel rack mounting IP10313-1 v1

17.4.3.1 Overview SEMOD127656-5 v4

The IED can be mounted in a standard 19” cubicle rack by using a mounting kit consisting of
two mounting angles and their fastening screws.

The mounting angles are reversible which enables mounting of the IED either to the left or the
right side of the cubicle.

A separately ordered rack mounting kit for side-by-side mounted IEDs or IEDs
together with RHGS cases should be selected so that the total size equals 19”.

Use only the screws included in the mounting kit when mounting the plates and
the angles on the IED. Screws with wrong dimension may damage the PCBs
inside the IED.

630 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 17
IED hardware

17.4.3.2 Mounting procedure for 19” panel rack mounting M11948-2 v7

1a

1b

IEC04000452-3-en.vsd
IEC04000452 V3 EN-US

Figure 334: 19” panel rack mounting details

The required torque for the screws is 3.5 Nm.

PosNo Description Quantity Type


1a, 1b Mounting angles, can be mounted 2 -
either to the left or the right side of
the case
2 Screw 8 M4x6
3 Washer 8 M4x6

17.4.4 Side-by-side 19” rack mounting IP10323-1 v1

17.4.4.1 Overview M11974-3 v3

IED case size 1/2 x 19” and RHGS cases can be mounted side-by-side up to a maximum size of
19”. For side-by-side rack mounting, the side-by-side mounting kit together with the 19” rack
panel mounting kit must be used. The mounting kit has to be ordered separately.

Use only the screws included in the mounting kit when mounting the plates and
the angles on the IED. Screws with wrong dimension may damage the PCBs
inside the IED.

Breaker protection REQ650 631


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 505 384-UEN C
IED hardware

17.4.4.2 Mounting procedure for side-by-side rack mounting M11955-2 v4

3 1
2

4
IEC040004563enOriginal.vsdx
IEC04000456 V3 EN-US

Figure 335: Side-by-side rack mounting details.

The required torque for the screws is 3.5 Nm.

PosNo Description Quantity Type


1 Mounting plate 2 -
2, 3 Screw 16 M4x6
4 Mounting angle 2 -
5 Washer 16 M4x6

17.4.4.3 IED mounted with a RHGS6 case M11953-3 v4

A 1/2 x 19” size IED can be mounted with a RHGS case (6 or 12). The RHGS case can be used for
mounting a test switch of type RTXP 24. It also has enough space for a terminal base of RX 2
type for mounting of, for example, a DC-switch or two auxiliary relays.

632 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 17
IED hardware

1 2 1 2

1 1 1 1

2 2 2 2

3 3 3 3

4 4 4 4

5 5 5 5

6 6 6 6

7 7 7 7

8 8 8 8

IEC06000180-2-en.vsd
IEC06000180 V2 EN-US

Figure 336: IED (1/2 x 19”) mounted with a RHGS6 case containing a test switch module
equipped with only a test switch and a RX2 terminal base

17.4.5 Side-by-side flush mounting IP10329-1 v1

17.4.5.1 Overview M11975-3 v3

If IP54 is required it is not allowed to flush mount side by side mounted cases. If your
application demands side-by-side flush mounting, the side-by-side mounting details kit and
the 19” panel rack mounting kit must be used. The mounting kit has to be ordered separately.
The maximum size of the panel cut out is 19”.

With side-by-side flush mounting installation, only IP class 20 is obtained. To


reach IP class 54, it is required to mount the IEDs separately. For cut out
dimensions of separately mounted IEDs, see section "Flush mounting".

Use only the screws included in the mounting kit when mounting the plates and
the angles on the IED. Screws with wrong dimension may damage the PCBs
inside the IED.

Please contact factory for special add on plates for mounting FT switches on
the side (for 1/2 19" case) or bottom of the relay.

Breaker protection REQ650 633


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 505 384-UEN C
IED hardware

17.4.5.2 Mounting procedure for side-by-side flush mounting M12730-6 v4

1 2

IEC06000181-2-en.vsd
IEC06000181 V2 EN-US

Figure 337: Side-by-side flush mounting details (RHGS6 side-by-side with 1/2 x 19” IED).

The required torque for the screws is 3.5 Nm.

PosNo Description Quantity Type


1 Mounting plate 2 -
2, 3 Screw, washer 16 M4x6
4 Mounting angle 2 -

17.5 Technical data IP16276-1 v1

17.5.1 Enclosure IP16278-1 v1

M11778-1 v7

Table 564: Case


Material Steel sheet
Front plate Stainless steel with cut-out for HMI
Surface treatment Aluzink preplated steel
Finish Light grey (RAL 7035)

M12327-1 v5

Table 565: Water and dust protection level according to IEC 60529

Front IP40 (IP54 with sealing strip)


Sides, top and bottom IP40
Rear side IP20 with screw compression type
IP10 with ring lug terminals

634 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 17
IED hardware

M11777-1 v7

Table 566: Weight


Case size Weight
6U, 1/2 x 19” £ 7.5 kg/16 lb

17.5.2 Electrical safety GUID-2825B541-DD31-4DAF-B5B3-97555F81A1C2 v1

GUID-1CF5B10A-CF8B-407D-8D87-F4B48B43C2B2 v2

Table 567: Electrical safety according to IEC 60255-27

Equipment class I (protective earthed)


Overvoltage category III
Pollution degree 2 (normally only non-conductive pollution occurs except that occasionally a
temporary conductivity caused by condensation is to be expected)

17.5.3 Connection system SEMOD53371-1 v1

SEMOD53376-2 v6

Table 568: CT and VT circuit connectors


Connector type Rated voltage and current Maximum conductor area
Screw compression type 250 V AC, 20 A 4 mm2 (AWG12)
2 x 2.5 mm2 (2 x AWG14)
Terminal blocks suitable for ring lug 250 V AC, 20 A 4 mm2 (AWG12)
terminals

M12583-1 v8

Table 569: Auxiliary power supply connectors


Connector type Rated voltage Maximum conductor area
Screw compression type 250 V AC 2.5 mm2 (AWG14)
2 × 1 mm2 (2 x AWG18)
Terminal blocks suitable for ring lug 300 V AC 3 mm2 (AWG14)
terminals

Table 570: Binary I/O connectors


Connector type Rated voltage Maximum conductor area
Screw compression type 250 V AC 2.5 mm2 (AWG14)
2 × 1 mm2 (2 x AWG18)

Breaker protection REQ650 635


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 505 384-UEN C
IED hardware

17.5.4 Influencing factors SEMOD52785-1 v1

M16705-1 v16

Table 571: Temperature and humidity influence


Parameter Reference value Nominal range Influence
Ambient temperature, +20±5°C -25°C to +55°C 0.02%/°C
operate value
Relative humidity 45-75% 10-90% -
Operative range 0-95%
Storage temperature - -40°C to +70°C -

Table 572: Auxiliary DC supply voltage influence on functionality during operation


Dependence on Reference value Within nominal Influence
range
Ripple, in DC auxiliary voltage max. 2% 15% of EL 0.01%/%
Operative range Full wave
rectified
Auxiliary voltage dependence, ±20% of EL 0.01%/%
operate value
Interrupted auxiliary DC voltage 24-60 V DC ± 20%

100-250 V DC
Interruption
±20%
interval
0–50 ms No restart
0–∞ s Correct behaviour at power
down
Restart time < 300 s

Table 573: Frequency influence (reference standard: IEC 60255–1)


Dependence on Within nominal range Influence
Frequency dependence, operate value fr ±2.5 Hz for 50 Hz ±1.0%/Hz
fr ±3.0 Hz for 60 Hz

Harmonic frequency dependence (20% 2nd, 3rd and 5th harmonic of fr ±2.0%
content)

Table 574: Frequency influence (reference standard: IEC 60255–1)


Dependence on Within nominal range Influence
Frequency dependence, operate value fr ±2.5 Hz for 50 Hz ±1.0%/Hz
fr ±3.0 Hz for 60 Hz

Frequency dependence for broken fr ±2.5 Hz for 50 Hz ±2.0%/Hz


conductor fr ±3.0 Hz for 60 Hz

Harmonic frequency dependence (20% 2nd, 3rd and 5th harmonic of fr ±1.0%
content)
Harmonic frequency dependence for 2nd, 3rd and 5th harmonic of fr ±2.0%
broken conductor (20% content)

636 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 17
IED hardware

17.5.5 Type tests according to standard IP16288-1 v1

M16706-1 v14

Table 575: Electromagnetic compatibility


Test Type test values Reference standards
1 MHz burst disturbance 2.5 kV IEC 60255-26
100 kHz slow damped oscillatory 2.5 kV IEC 61000-4-18, Level 3
wave immunity test
Ring wave immunity test, 100 kHz 2-4 kV IEC 61000-4-12, Level 4
Electrostatic discharge 15 kV air discharge IEC 60255-26
Direct application 8 kV contact discharge
Indirect application 8 kV contact discharge IEC 61000-4-2, Level 4
Electrostatic discharge 15 kV air discharge IEEE/ANSI C37.90.3
Direct application 8 kV contact discharge
Indirect application 8 kV contact discharge
Fast transient disturbance 4 kV IEC 60255-26, Zone A
2 kV, SFP galvanic RJ45
2 kV, MIM mA-inputs IEC 60255-26, Zone B
Surge immunity test 2-4 kV, 1.2/50ms high energy IEC 60255-26, Zone A
1-2 kV, BOM and IRF outputs IEC 60255-26, Zone B

Power frequency immunity test 150-300 V, 50 Hz IEC 60255-26, Zone A


Conducted common mode immunity 30-3 V, 15-150 Hz IEC 61000-4-16, Level 4
test
Power frequency magnetic field test 1000 A/m, 3 s IEC 61000-4-8, Level 5
100 A/m, cont.
Pulse magnetic field immunity test 1000 A/m IEC 61000–4–9, Level 5
Damped oscillatory magnetic field 100 A/m IEC 61000-4-10, Level 5
test
Radiated electromagnetic field 20 V/m IEC 60255-26
disturbance 80-1000 MHz IEEE/ANSI C37.90.2
1.4-2.7 GHz EN 50121-5
10 V/m, 2.7-6.0 GHz
Radiated emission 30-6000 MHz IEC 60255-26
30-8500 MHz IEEE/ANSI C63.4, FCC
Conducted emission 0.15-30 MHz IEC 60255-26

Table 576: Insulation


Test Type test values Reference standard
Dielectric test 2.0 kV AC, 1 min. IEC 60255-27
1.0 kV AC, 1 min.: ANSI C37.90
-SFP galvanic RJ45 IEEE 802.3-2015,
- X.21-LDCM Environment A
Impulse voltage test 5 kV, 1.2/50ms, 0.5 J
1 kV, 1.2/50 ms 0.5 J:
-SFP galvanic RJ45
- X.21-LDCM
Insulation resistance > 100 MW at 500 VDC

Breaker protection REQ650 637


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 17 1MRK 505 384-UEN C
IED hardware

Table 577: Environmental tests


Test Type test value Reference standard
Cold operation test Test Ad for 16 h at -25°C IEC 60068-2-1
Cold storage test Test Ab for 16 h at -40°C IEC 60068-2-1
Dry heat operation test Test Bd for 16 h at +70°C IEC 60068-2-2
Dry heat storage test Test Bb for 16 h at +85°C IEC 60068-2-2
Change of temperature test Test Nb for 5 cycles at -25°C to +70°C IEC 60068-2-14
Damp heat test, steady state Test Ca for 10 days at +40°C and humidity IEC 60068-2-78
93%
Damp heat test, cyclic Test Db for 6 cycles at +25 to +55°C and IEC 60068-2-30
humidity 93 to 95% (1 cycle = 24 hours)

Table 578: CE compliance


Test According to
Electromagnetic compatibility (EMC) EN 60255–26
Low voltage (LVD) EN 60255–27

Table 579: Mechanical tests


Test Type test values Reference standards
Vibration response test Class II: Rack mount IEC 60255-21-1
Class I: Flush and wall mount
Vibration endurance test Class I: Rack, flush and wall mount IEC 60255-21-1
Shock response test Class I: Rack, flush and wall mount IEC 60255-21-2
Shock withstand test Class I: Rack, flush and wall mount IEC 60255-21-2
Bump test Class I: Rack, flush and wall mount IEC 60255-21-2
Seismic test Class II: Rack mount IEC 60255-21-3
Class I: Flush and wall mount

638 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 18
Labels

Section 18 Labels
18.1 Labels on IED SEMOD168249-4 v5

Front view of IED

6
2

10
3
IEC16000081=1=en.vsdx
IEC16000081 V1 EN-US

Figure 338: Example of IED label

1 QR-code containing the complete ordering code


2 Power supply module (PSM)
3 Ordering and serial number
4 Manufacturer
5 Transformer designations
6 Transformer input module, rated currents and voltages
7 Optional, customer specific information
8 Order number, dc supply voltage and rated frequency
9 Product type, description and serial number
10 Product type

Breaker protection REQ650 639


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 18 1MRK 505 384-UEN C
Labels

Rear view of IED

IEC15000573=2=en=Original.wsdx
IEC15000573 V2 EN-US

1 Warning label
2 Caution label
3 Class 1 laser product label It is used when an optical SFP or an MR LDCM is configured in
the product.

IEC06000575 V1 EN-US

640 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 19
Connection diagrams

Section 19 Connection diagrams GUID-CF4EFFA5-3081-4FC7-9A14-ED127C3C0FDE v7

The connection diagrams are delivered in the IED Connectivity package as part of the product
delivery.

The latest versions of the connection diagrams can be downloaded from


http://www.abb.com/protection-control.

Connection diagrams for Configured products

Connection diagram, REQ650 2.2, B11X00 1MRK006507-QA

Connection diagrams for Customized products

Connection diagram, 650 series 2.2 IEC 1MRK006501-AG

Connection diagram, 650 series 2.2 ANSI 1MRK006502-AG

Breaker protection REQ650 641


Technical manual
© Copyright 2017 ABB. All rights reserved
642
1MRK 505 384-UEN C Section 20
Inverse time characteristics

Section 20 Inverse time characteristics


20.1 Application M16686-3 v5

In order to assure time selectivity between different overcurrent protections at different


points in the network different time delays for the different protections are normally used. The
simplest way to do this is to use definite time-lag. In more sophisticated applications current
dependent time characteristics are used. Both alternatives are shown in a simple application
with three overcurrent protections operating in series.

I> I> I>


xx05000129.vsd
IEC05000129 V1 EN-US

Figure 339: Three overcurrent protections operating in series

Stage 3

Time
Stage 2 Stage 2

Stage 1 Stage 1 Stage 1

Fault point
position

en05000130.vsd
IEC05000130 V1 EN-US

Figure 340: Definite time overcurrent characteristics

Time

Fault point
position

en05000131.vsd
IEC05000131 V1 EN-US

Figure 341: Inverse time overcurrent characteristics with inst. function


The inverse time characteristic makes it possible to minimize the fault clearance time and still
assure the selectivity between protections.

Breaker protection REQ650 643


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 20 1MRK 505 384-UEN C
Inverse time characteristics

To assure selectivity between protections there must be a time margin between the operation
time of the protections. This required time margin is dependent of following factors, in a
simple case with two protections in series:

• Difference between pickup time of the protections to be co-ordinated


• Opening time of the breaker closest to the studied fault
• Reset times of the protections
• Margin dependent of the time delay inaccuracy of the protections

Assume we have the following network case.

A1 B1
Feeder

I> I>

Time axis

t=0 t=t1 t=t2 t=t3

en05000132.vsd
IEC05000132 V1 EN-US

Figure 342: Selectivity steps for a fault on feeder B1

where:
t=0 is The fault occurs
t=t1 is Protection B1 trips

t=t2 is Breaker at B1 opens

t=t3 is Protection A1 resets

In the case protection B1 shall operate without any intentional delay (instantaneous). When the
fault occurs the protections start to detect the fault current. After the time t1 the protection B1
send a trip signal to the circuit breaker. The protection A1 starts its delay timer at the same
time, with some deviation in time due to differences between the two protections. There is a
possibility that A1 will start before the trip is sent to the B1 circuit breaker. At the time t2 the
circuit breaker B1 has opened its primary contacts and thus the fault current is interrupted.
The breaker time (t2 - t1) can differ between different faults. The maximum opening time can
be given from manuals and test protocols. Still at t2 the timer of protection A1 is active. At
time t3 the protection A1 is reset, that is the timer is stopped.

In most applications it is required that the times shall reset as fast as possible when the
current fed to the protection drops below the set current level, the reset time shall be
minimized. In some applications it is however beneficial to have some type of delayed reset
time of the overcurrent function. This can be the case in the following applications:

644 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 20
Inverse time characteristics

• If there is a risk of intermittent faults. If the current IED, close to the faults, starts and
resets there is a risk of unselective trip from other protections in the system.
• Delayed resetting could give accelerated fault clearance in case of automatic reclosing to
a permanent fault.
• Overcurrent protection functions are sometimes used as release criterion for other
protection functions. It can often be valuable to have a reset delay to assure the release
function.

20.2 Principle of operation IP15777-1 v2

20.2.1 Mode of operation M16687-3 v8

The function can operate in a definite time-lag mode or in a current definite inverse time
mode. For the inverse time characteristic both ANSI and IEC based standard curves are
available. Also programmable curve types are supported via the component inputs: p, A, B, C
pr, tr, and cr.

Different characteristics for reset delay can also be chosen.

If current in any phase exceeds the set start current value (here internal signal startValue), a
timer, according to the selected operating mode, is started.

In case of definite time-lag mode the timer will run constantly until the time is reached or until
the current drops below the reset value (start value minus the hysteresis) and the reset time
has elapsed.

For definite time delay curve ANSI/IEEE Definite time or IEC Definite time are chosen.

The general expression for inverse time curves is according to equation 61.

æ ö
ç A
÷
t[ s ] = ç + B ÷×k
ç æ i öp ÷
çç ÷ -C ÷
è è in > ø ø
EQUATION1189 V1 EN-US (Equation 61)

where:
p, A, B, C are constants defined for each curve type,
in> is the set start current for step n,
k is set time multiplier for step n and
i is the measured current.

For inverse time characteristics a time will be initiated when the current reaches the set start
level. From the general expression of the characteristic the following can be seen:

Breaker protection REQ650 645


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 20 1MRK 505 384-UEN C
Inverse time characteristics

ææ i öp ö
(top - B × k ) × ç ç ÷ - C ÷ = A×k
è è in > ø ø
EQUATION1190 V1 EN-US (Equation 62)

where:
top is the operating time of the protection

The time elapsed to the moment of trip is reached when the integral fulfils according to
equation 63, in addition to the constant time delay:

t
ææ i öp ö
ò è in > ø ÷ × dt ³ A × k
ç ç ÷ - C
0 è ø
EQUATION1191 V1 EN-US (Equation 63)

For the numerical protection the sum below must fulfil the equation for trip.

æ æ i( j ) ö p
n ö
Dt × å ç ç ÷ - C ÷ ³ A× k
j =1 è è in > ø ø
EQUATION1192 V1 EN-US (Equation 64)

where:
j=1 is the first protection execution cycle when a fault has been detected,
that is, when

i
>1
in >
EQUATION1193 V1 EN-US

Dt is the time interval between two consecutive executions of the


protection algorithm,
n is the number of the execution of the algorithm when the trip time
equation is fulfilled, that is, when a trip is given and
i (j) is the fault current at time j

For inverse time operation, the inverse time characteristic is selectable. Both the IEC and
ANSI/IEEE standardized inverse time characteristics are supported.

For the IEC curves there is also a setting of the minimum time-lag of operation, see figure 343.

646 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 20
Inverse time characteristics

Operate
time

tMin

Current
IMin
IEC05000133-3-en.vsd
IEC05000133 V2 EN-US

Figure 343: Minimum time-lag operation for the IEC curves


In order to fully comply with IEC curves definition setting parameter tMin shall be set to the
value which is equal to the operating time of the selected IEC inverse time curve for measured
current of twenty times the set current start value. Note that the operating time value is
dependent on the selected setting value for time multiplier k.

In addition to the ANSI and IEC standardized characteristics, there are also two additional
inverse curves available; the RI curve and the RD curve.

The RI inverse time curve emulates the characteristic of the electromechanical ASEA relay RI.
The curve is described by equation 65:

æ ö
ç k ÷
t[ s ] = ç
in > ÷
ç 0.339 - 0.235 × ÷
è i ø
EQUATION1194 V1 EN-US (Equation 65)

where:
in> is the set start current for step n
k is set time multiplier for step n
i is the measured current

The RD inverse curve gives a logarithmic delay, as used in the Combiflex protection RXIDG. The
curve enables a high degree of selectivity required for sensitive residual earth-fault current
protection, with ability to detect high-resistive earth faults. The curve is described by
equation 66:

Breaker protection REQ650 647


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 20 1MRK 505 384-UEN C
Inverse time characteristics

æ i ö
t[ s ] = 5.8 - 1.35 × ln ç ÷
è k × in > ø
EQUATION1195 V1 EN-US (Equation 66)

where:
in> is the set start current for step n,
k is set time multiplier for step n and
i is the measured current

If the curve type programmable is chosen, the user can make a tailor made inverse time curve
according to the general equation 67.

æ ö
ç A
÷
t[ s ] = ç + B ÷×k
ç æ i öp ÷
çç ÷ -C ÷
è è in > ø ø
EQUATION1196 V1 EN-US (Equation 67)

Also the reset time of the delayed function can be controlled. There is the possibility to choose
between three different reset time-lags.

• Instantaneous Reset
• IEC Reset
• ANSI Reset.

If instantaneous reset is chosen the timer will be reset directly when the current drops below
the set start current level minus the hysteresis.

If IEC reset is chosen the timer will be reset after a set constant time when the current drops
below the set start current level minus the hysteresis.

If ANSI reset time is chosen the reset time will be dependent of the current after fault
clearance (when the current drops below the start current level minus the hysteresis). The
timer will reset according to equation 68.

æ ö
ç tr ÷
t [s] = ç ÷×k
çæ i ö ÷
2

çç ÷ -1 ÷
è è in > ø ø
EQUATION1197 V2 EN-US (Equation 68)

where:
The set value tr is the reset time in case of zero current after fault clearance.

The possibility of choice of reset characteristics is to some extent dependent of the choice of
time delay characteristic.

648 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 20
Inverse time characteristics

For the definite time delay characteristics the possible reset time settings are instantaneous
and IEC constant time reset.

For ANSI inverse time delay characteristics all three types of reset time characteristics are
available; instantaneous, IEC constant time reset and ANSI current dependent reset time.

For IEC inverse time delay characteristics the possible delay time settings are instantaneous
and IEC set constant time reset).

For the programmable inverse time delay characteristics all three types of reset time
characteristics are available; instantaneous, IEC constant time reset and ANSI current
dependent reset time. If the current dependent type is used settings pr, tr and cr must be
given, see equation 69:

æ ö
ç tr ÷
t [s] = ç ÷×k
çæ i ö ÷
pr

çç ÷ - cr ÷
è è in > ø ø
EQUATION1198 V2 EN-US (Equation 69)

For RI and RD inverse time delay characteristics the possible delay time settings are
instantaneous and IEC constant time reset.
GUID-F7AA2194-4D1C-4475-8853-C7D064912614 v4

When inverse time overcurrent characteristic is selected, the operate time of


the stage will be the sum of the inverse time delay and the set definite time
delay. Thus, if only the inverse time delay is required, it is important to set the
definite time delay for that stage to zero.

Breaker protection REQ650 649


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 20 1MRK 505 384-UEN C
Inverse time characteristics

20.3 Inverse characteristics IP15797-1 v2

M12388-1 v23

Table 580: ANSI Inverse time characteristics


Function Range or value Accuracy
Operating characteristic: 0.05 ≤ k ≤ 999.00 ANSI/IEEE C37.112 ,
1.5 x Iset ≤ I ≤ 20 x Iset ±2.0% or ±40 ms
whichever is greater
æ A ö
t =ç P + B÷×k
è (
ç I -1 ÷
ø )
EQUATION1249-SMALL V3 EN-US

Reset characteristic:

tr
t = ×k
(I 2
-1)
EQUATION1250-SMALL V1 EN-US

I = Imeasured/Iset

ANSI Extremely Inverse A=28.2, B=0.1217, P=2.0 , tr=29.1


ANSI Very inverse A=19.61, B=0.491, P=2.0 , tr=21.6
ANSI Normal Inverse A=0.0086, B=0.0185, P=0.02, tr=0.46
ANSI Moderately Inverse A=0.0515, B=0.1140, P=0.02, tr=4.85
ANSI Long Time Extremely Inverse A=64.07, B=0.250, P=2.0, tr=30
ANSI Long Time Very Inverse A=28.55, B=0.712, P=2.0, tr=13.46
ANSI Long Time Inverse A=0.086, B=0.185, P=0.02, tr=4.6

650 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 20
Inverse time characteristics

Table 581: IEC Inverse time characteristics


Function Range or value Accuracy
Operating characteristic: 0.05 ≤ k ≤ 999.00 IEC 60255-151, ±2.0%
1.5 x Iset ≤ I ≤ 20 x Iset or ±40 ms whichever
æ A ö is greater
t = ç P ÷×k
ç ( I - 1) ÷
è ø
EQUATION1251-SMALL V1 EN-US

I = Imeasured/Iset

IEC Normal Inverse A=0.14, P=0.02


IEC Very inverse A=13.5, P=1.0
IEC Inverse A=0.14, P=0.02
IEC Extremely inverse A=80.0, P=2.0
IEC Short time inverse A=0.05, P=0.04
IEC Long time inverse A=120, P=1.0
Programmable characteristic k = (0.05-999) in steps of 0.01
Operate characteristic: A=(0.005-200.000) in steps of 0.001
B=(0.00-20.00) in steps of 0.01
æ A ö C=(0.1-10.0) in steps of 0.1
t = ç P + B÷ × k P=(0.005-3.000) in steps of 0.001
ç (I - C ) ÷ TR=(0.005-100.000) in steps of 0.001
è ø CR=(0.1-10.0) in steps of 0.1
EQUATION1370-SMALL V1 EN-US
PR=(0.005-3.000) in steps of 0.001
Reset characteristic:

TR
t = ×k
(I PR
- CR )
EQUATION1253-SMALL V1 EN-US

I = Imeasured/Iset

The parameter setting Characteristn = Reserved (where, n = 1 - 4) shall not be


used, since this parameter setting is for future use and not implemented yet.

Table 582: RI and RD type inverse time characteristics


Function Range or value Accuracy
RI type inverse characteristic 0.05 ≤ k ≤ 999.00 IEC 60255-151, ±2.0%
1.5 x Iset ≤ I ≤ 20 x Iset or ±40 ms whichever
1 is greater
t = ×k
0.236
0.339 -
I
EQUATION1137-SMALL V1 EN-US

I = Imeasured/Iset

RD type logarithmic inverse


characteristic

æ I ö
t = 5.8 - ç 1.35 × In ÷
è k ø
EQUATION1138-SMALL V1 EN-US

I = Imeasured/Iset

Breaker protection REQ650 651


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 20 1MRK 505 384-UEN C
Inverse time characteristics

GUID-19F8E187-4ED0-48C3-92F6-0D9EAA2B39BB v4

Table 583: ANSI Inverse time characteristics for Sensitive directional residual overcurrent and power protection
Function Range or value Accuracy
Operating characteristic: 0.05 ≤ k ≤ 2.00 ANSI/IEEE C37.112 ,
1.5 x Iset ≤ I ≤ 20 x Iset ±5.0% or ±160 ms
whichever is greater
æ A ö
t =ç P + B÷×k
ç I -1
è ( ÷
ø )
EQUATION1249-SMALL V3 EN-US

Reset characteristic:

tr
t = ×k
(I 2
-1 )
EQUATION1250-SMALL V1 EN-US

I = Imeasured/Iset

ANSI Extremely Inverse A=28.2, B=0.1217, P=2.0 , tr=29.1


ANSI Very inverse A=19.61, B=0.491, P=2.0 , tr=21.6
ANSI Normal Inverse A=0.0086, B=0.0185, P=0.02, tr=0.46
ANSI Moderately Inverse A=0.0515, B=0.1140, P=0.02, tr=4.85
ANSI Long Time Extremely Inverse A=64.07, B=0.250, P=2.0, tr=30
ANSI Long Time Very Inverse A=28.55, B=0.712, P=2.0, tr=13.46
ANSI Long Time Inverse A=0.086, B=0.185, P=0.02, tr=4.6

Table 584: IEC Inverse time characteristics for Sensitive directional residual overcurrent and power protection
Function Range or value Accuracy
Operating characteristic: 0.05 ≤ k ≤ 2.00 IEC 60255-151, ±5.0%
1.5 x Iset ≤ I ≤ 20 x Iset or ±160 ms whichever
æ A ö is greater
t = ç P ÷×k
ç ( I - 1) ÷
è ø
EQUATION1251-SMALL V1 EN-US

I = Imeasured/Iset

IEC Normal Inverse A=0.14, P=0.02


IEC Very inverse A=13.5, P=1.0
IEC Inverse A=0.14, P=0.02
IEC Extremely inverse A=80.0, P=2.0
IEC Short time inverse A=0.05, P=0.04
IEC Long time inverse A=120, P=1.0
Programmable characteristic k = (0.05-2.00) in steps of 0.01
Operate characteristic: A=(0.005-200.000) in steps of 0.001
B=(0.00-20.00) in steps of 0.01
æ A ö C=(0.1-10.0) in steps of 0.1
t = ç P + B÷ × k P=(0.005-3.000) in steps of 0.001
ç (I - C ) ÷ TR=(0.005-100.000) in steps of 0.001
è ø CR=(0.1-10.0) in steps of 0.1
EQUATION1370-SMALL V1 EN-US
PR=(0.005-3.000) in steps of 0.001
Reset characteristic:

TR
t = ×k
(I PR
- CR )
EQUATION1253-SMALL V1 EN-US

I = Imeasured/Iset

652 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 20
Inverse time characteristics

The parameter setting TimeChar = Reserved shall not be used, since this
parameter setting is for future use and not implemented yet.

Table 585: RI and RD type inverse time characteristics for Sensitive directional residual overcurrent and power
protection
Function Range or value Accuracy
RI type inverse characteristic 0.05 ≤ k ≤ 2.00 IEC 60255-151, ±5.0%
1.5 x Iset ≤ I ≤ 20 x Iset or ±160 ms whichever
1 is greater
t = ×k
0.236
0.339 -
I
EQUATION1137-SMALL V1 EN-US

I = Imeasured/Iset

RD type logarithmic inverse


characteristic

æ I ö
t = 5.8 - ç 1.35 × In ÷
è k ø
EQUATION1138-SMALL V1 EN-US

I = Imeasured/Iset

GUID-2AE8C92E-5DA8-487F-927D-8E553EE29240 v2

Table 586: ANSI Inverse time characteristics for Voltage restrained time overcurrent protection
Function Range or value Accuracy
Operating characteristic: 0.05 ≤ k ≤ 999.00 ANSI/IEEE C37.112 , ±
5.0% or ±40 ms
whichever is greater
æ A ö
t =ç P + B÷×k
è (
ç I -1 ÷
ø )
EQUATION1249-SMALL V3 EN-US

Reset characteristic:

tr
t = ×k
(I 2
-1 )
EQUATION1250-SMALL V1 EN-US

I = Imeasured/Iset

ANSI Extremely Inverse A=28.2, B=0.1217, P=2.0 , tr=29.1


ANSI Very inverse A=19.61, B=0.491, P=2.0 , tr=21.6
ANSI Normal Inverse A=0.0086, B=0.0185, P=0.02, tr=0.46
ANSI Moderately Inverse A=0.0515, B=0.1140, P=0.02, tr=4.85
ANSI Long Time Extremely Inverse A=64.07, B=0.250, P=2.0, tr=30
ANSI Long Time Very Inverse A=28.55, B=0.712, P=2.0, tr=13.46
ANSI Long Time Inverse A=0.086, B=0.185, P=0.02, tr=4.6

Breaker protection REQ650 653


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 20 1MRK 505 384-UEN C
Inverse time characteristics

Table 587: IEC Inverse time characteristics for Voltage restrained time overcurrent protection
Function Range or value Accuracy
Operating characteristic: 0.05 ≤ k ≤ 999.00 IEC 60255-151, ±5.0%
or ±40 ms whichever
æ A ö is greater
t = ç P ÷×k
ç ( I - 1) ÷
è ø
EQUATION1251-SMALL V1 EN-US

I = Imeasured/Iset

IEC Normal Inverse A=0.14, P=0.02


IEC Very inverse A=13.5, P=1.0
IEC Inverse A=0.14, P=0.02
IEC Extremely inverse A=80.0, P=2.0
IEC Short time inverse A=0.05, P=0.04
IEC Long time inverse A=120, P=1.0

SEMOD116978-2 v10

Table 588: Inverse time characteristics for overvoltage protection


Function Range or value Accuracy
Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms
whichever is greater
k
t =
æU -U >ö
ç ÷
è U> ø
EQUATION1436-SMALL V1 EN-US

U> = Uset
U = Umeasured

Type B curve: k = (0.05-1.10) in steps of 0.01

k  480
t 2.0
 0.035
 U  Un  
 32   0.5 
 Un  

IECEQUATION2423 V2 EN-US

Type C curve: k = (0.05-1.10) in steps of 0.01

k × 480
t= 3.0
+ 0.035
æ U - Un > ö
ç 32 × - 0.5 ÷
è U> ø
IECEQUATION2421 V1 EN-US

Programmable curve: k = (0.05-1.10) in steps of 0.01


A = (0.005-200.000) in steps of
k×A 0.001
t = +D B = (0.50-100.00) in steps of 0.01
P
æB × U - U > ö C = (0.0-1.0) in steps of 0.1
ç -C÷
D = (0.000-60.000) in steps of
è U > ø
EQUATION1439-SMALL V1 EN-US
0.001
P = (0.000-3.000) in steps of 0.001

654 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 20
Inverse time characteristics

Table 589: Inverse time characteristics for undervoltage protection


Function Range or value Accuracy
Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms
whichever is greater
k
t =
æ U < -U ö
ç ÷
è U< ø
EQUATION1431-SMALL V1 EN-US

U< = Uset
U = Umeasured

Type B curve: k = (0.05-1.10) in steps of 0.01

k × 480
t = + 0.055
2.0
æ 32 × U < -U - 0.5 ö
ç ÷
è U < ø
EQUATION1432-SMALL V1 EN-US

U< = Uset
U = Umeasured

Programmable curve: k = (0.05-1.10) in steps of 0.01


A = (0.005-200.000) in steps of
é ù 0.001
ê ú B = (0.50-100.00) in steps of 0.01
k×A C = (0.0-1.0) in steps of 0.1
t =ê ú+D
ê æ U < -U P
ú D = (0.000-60.000) in steps of
ö
êçB × -C÷ ú 0.001
ëè U < ø û P = (0.000-3.000) in steps of
EQUATION1433-SMALL V1 EN-US
0.001
U< = Uset
U = Umeasured

Breaker protection REQ650 655


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 20 1MRK 505 384-UEN C
Inverse time characteristics

Table 590: Inverse time characteristics for residual overvoltage protection


Function Range or value Accuracy
Type A curve: k = (0.05-1.10) in steps ±5.0% or ±45 ms whichever is
of 0.01 greater
k
t =
æU -U >ö
ç ÷
è U > ø
EQUATION1436-SMALL V1 EN-US

U> = Uset
U = Umeasured

Type B curve: k = (0.05-1.10) in steps


of 0.01
k ⋅ 480
t = + 0.035
2.0
 32 ⋅ U − U > − 0.5 
 
 U > 
EQUATION1437-SMALL V2 EN-US

Type C curve: k = (0.05-1.10) in steps


of 0.01
k ⋅ 480
t = + 0.035
3.0
 32 ⋅ U − U > − 0.5 
 
 U > 
EQUATION1438-SMALL V2 EN-US

Programmable curve: k = (0.05-1.10) in steps


of 0.01
k×A A = (0.005-200.000) in
t = +D steps of 0.001
P
æB × U - U > ö B = (0.50-100.00) in
ç -C÷ steps of 0.01
è U > ø
EQUATION1439-SMALL V1 EN-US
C = (0.0-1.0) in steps of
0.1
D = (0.000-60.000) in
steps of 0.001
P = (0.000-3.000) in
steps of 0.001

656 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 20
Inverse time characteristics

SEMOD118114-4 v4

A070750 V2 EN-US

Figure 344: ANSI Extremely inverse time characteristics

Breaker protection REQ650 657


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 20 1MRK 505 384-UEN C
Inverse time characteristics

A070751 V2 EN-US

Figure 345: ANSI Very inverse time characteristics

658 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 20
Inverse time characteristics

A070752 V2 EN-US

Figure 346: ANSI Normal inverse time characteristics

Breaker protection REQ650 659


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 20 1MRK 505 384-UEN C
Inverse time characteristics

A070753 V2 EN-US

Figure 347: ANSI Moderately inverse time characteristics

660 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 20
Inverse time characteristics

A070817 V2 EN-US

Figure 348: ANSI Long time extremely inverse time characteristics

Breaker protection REQ650 661


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 20 1MRK 505 384-UEN C
Inverse time characteristics

A070818 V2 EN-US

Figure 349: ANSI Long time very inverse time characteristics

662 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 20
Inverse time characteristics

A070819 V2 EN-US

Figure 350: ANSI Long time inverse time characteristics

Breaker protection REQ650 663


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 20 1MRK 505 384-UEN C
Inverse time characteristics

A070820 V2 EN-US

Figure 351: IEC Normal inverse time characteristics

664 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 20
Inverse time characteristics

A070821 V2 EN-US

Figure 352: IEC Very inverse time characteristics

Breaker protection REQ650 665


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 20 1MRK 505 384-UEN C
Inverse time characteristics

A070822 V2 EN-US

Figure 353: IEC Inverse time characteristics

666 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 20
Inverse time characteristics

A070823 V2 EN-US

Figure 354: IEC Extremely inverse time characteristics

Breaker protection REQ650 667


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 20 1MRK 505 384-UEN C
Inverse time characteristics

A070824 V2 EN-US

Figure 355: IEC Short time inverse time characteristics

668 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 20
Inverse time characteristics

A070825 V2 EN-US

Figure 356: IEC Long time inverse time characteristics

Breaker protection REQ650 669


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 20 1MRK 505 384-UEN C
Inverse time characteristics

A070826 V2 EN-US

Figure 357: RI-type inverse time characteristics

670 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 20
Inverse time characteristics

A070827 V2 EN-US

Figure 358: RD-type inverse time characteristics

Breaker protection REQ650 671


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 20 1MRK 505 384-UEN C
Inverse time characteristics

GUID-ACF4044C-052E-4CBD-8247-C6ABE3796FA6 V1 EN-US

Figure 359: Inverse curve A characteristic of overvoltage protection

672 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 20
Inverse time characteristics

GUID-F5E0E1C2-48C8-4DC7-A84B-174544C09142 V1 EN-US

Figure 360: Inverse curve B characteristic of overvoltage protection

Breaker protection REQ650 673


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 20 1MRK 505 384-UEN C
Inverse time characteristics

GUID-A9898DB7-90A3-47F2-AEF9-45FF148CB679 V1 EN-US

Figure 361: Inverse curve C characteristic of overvoltage protection

674 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 20
Inverse time characteristics

GUID-35F40C3B-B483-40E6-9767-69C1536E3CBC V1 EN-US

Figure 362: Inverse curve A characteristic of undervoltage protection

Breaker protection REQ650 675


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 20 1MRK 505 384-UEN C
Inverse time characteristics

GUID-B55D0F5F-9265-4D9A-A7C0-E274AA3A6BB1 V1 EN-US

Figure 363: Inverse curve B characteristic of undervoltage protection

676 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 21
Glossary

Section 21 Glossary M14893-1 v18

AC Alternating current
ACC Actual channel
ACT Application configuration tool within PCM600
A/D converter Analog-to-digital converter
ADBS Amplitude deadband supervision
ADM Analog digital conversion module, with time synchronization
AI Analog input
ANSI American National Standards Institute
AR Autoreclosing
ASCT Auxiliary summation current transformer
ASD Adaptive signal detection
ASDU Application service data unit
AWG American Wire Gauge standard
BBP Busbar protection
BFOC/2,5 Bayonet fiber optic connector
BFP Breaker failure protection
BI Binary input
BIM Binary input module
BOM Binary output module
BOS Binary outputs status
BR External bistable relay
BS British Standards
BSR Binary signal transfer function, receiver blocks
BST Binary signal transfer function, transmit blocks
C37.94 IEEE/ANSI protocol used when sending binary signals between IEDs
CAN Controller Area Network. ISO standard (ISO 11898) for serial
communication
CB Circuit breaker
CBM Combined backplane module
CCITT Consultative Committee for International Telegraph and Telephony. A
United Nations-sponsored standards body within the International
Telecommunications Union.
CCM CAN carrier module
CCVT Capacitive Coupled Voltage Transformer
Class C Protection Current Transformer class as per IEEE/ ANSI
CMPPS Combined megapulses per second
CMT Communication Management tool in PCM600

Breaker protection REQ650 677


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 21 1MRK 505 384-UEN C
Glossary

CO cycle Close-open cycle


Codirectional Way of transmitting G.703 over a balanced line. Involves two twisted
pairs making it possible to transmit information in both directions
COM Command
COMTRADE Standard Common Format for Transient Data Exchange format for
Disturbance recorder according to IEEE/ANSI C37.111, 1999 / IEC
60255-24
Contra-directional Way of transmitting G.703 over a balanced line. Involves four twisted
pairs, two of which are used for transmitting data in both directions
and two for transmitting clock signals
COT Cause of transmission
CPU Central processing unit
CR Carrier receive
CRC Cyclic redundancy check
CROB Control relay output block
CS Carrier send
CT Current transformer
CU Communication unit
CVT or CCVT Capacitive voltage transformer
DAR Delayed autoreclosing
DARPA Defense Advanced Research Projects Agency (The US developer of the
TCP/IP protocol etc.)
DBDL Dead bus dead line
DBLL Dead bus live line
DC Direct current
DFC Data flow control
DFT Discrete Fourier transform
DHCP Dynamic Host Configuration Protocol
DIP-switch Small switch mounted on a printed circuit board
DI Digital input
DLLB Dead line live bus
DNP Distributed Network Protocol as per IEEE Std 1815-2012
DR Disturbance recorder
DRAM Dynamic random access memory
DRH Disturbance report handler
DSP Digital signal processor
DTT Direct transfer trip scheme
ECT Ethernet configuration tool
EHV network Extra high voltage network
EIA Electronic Industries Association
EMC Electromagnetic compatibility
EMF Electromotive force

678 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 21
Glossary

EMI Electromagnetic interference


EnFP End fault protection
EPA Enhanced performance architecture
ESD Electrostatic discharge
F-SMA Type of optical fiber connector
FAN Fault number
FCB Flow control bit; Frame count bit
FOX 20 Modular 20 channel telecommunication system for speech, data and
protection signals
FOX 512/515 Access multiplexer
FOX 6Plus Compact time-division multiplexer for the transmission of up to seven
duplex channels of digital data over optical fibers
FPN Flexible product naming
FTP File Transfer Protocol
FUN Function type
G.703 Electrical and functional description for digital lines used by local
telephone companies. Can be transported over balanced and
unbalanced lines
GCM Communication interface module with carrier of GPS receiver module
GDE Graphical display editor within PCM600
GI General interrogation command
GIS Gas-insulated switchgear
GOOSE Generic object-oriented substation event
GPS Global positioning system
GSAL Generic security application
GSE Generic substation event
HDLC protocol High-level data link control, protocol based on the HDLC standard
HFBR connector type Plastic fiber connector
HLV circuit Hazardous Live Voltage according to IEC60255-27
HMI Human-machine interface
HSAR High speed autoreclosing
HSR High-availability Seamless Redundancy
HV High-voltage
HVDC High-voltage direct current
IDBS Integrating deadband supervision
IEC International Electrical Committee
IEC 60044-6 IEC Standard, Instrument transformers – Part 6: Requirements for
protective current transformers for transient performance
IEC 60870-5-103 Communication standard for protection equipment. A serial master/
slave protocol for point-to-point communication
IEC 61850 Substation automation communication standard
IEC 61850–8–1 Communication protocol standard

Breaker protection REQ650 679


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 21 1MRK 505 384-UEN C
Glossary

IEEE Institute of Electrical and Electronics Engineers


IEEE 802.12 A network technology standard that provides 100 Mbits/s on twisted-
pair or optical fiber cable
IEEE P1386.1 PCI Mezzanine Card (PMC) standard for local bus modules. References
the CMC (IEEE P1386, also known as Common Mezzanine Card)
standard for the mechanics and the PCI specifications from the PCI SIG
(Special Interest Group) for the electrical EMF (Electromotive force).
IEEE 1686 Standard for Substation Intelligent Electronic Devices (IEDs) Cyber
Security Capabilities
IED Intelligent electronic device
IET600 Integrated engineering tool
I-GIS Intelligent gas-insulated switchgear
IOM Binary input/output module
Instance When several occurrences of the same function are available in the IED,
they are referred to as instances of that function. One instance of a
function is identical to another of the same kind but has a different
number in the IED user interfaces. The word "instance" is sometimes
defined as an item of information that is representative of a type. In
the same way an instance of a function in the IED is representative of a
type of function.
IP 1. Internet protocol. The network layer for the TCP/IP protocol suite
widely used on Ethernet networks. IP is a connectionless, best-effort
packet-switching protocol. It provides packet routing, fragmentation
and reassembly through the data link layer.
2. Ingression protection, according to IEC 60529
IP 20 Ingression protection, according to IEC 60529, level 20
IP 40 Ingression protection, according to IEC 60529, level 40
IP 54 Ingression protection, according to IEC 60529, level 54
IRF Internal failure signal
IRIG-B: InterRange Instrumentation Group Time code format B, standard 200
ITU International Telecommunications Union
LAN Local area network
LIB 520 High-voltage software module
LCD Liquid crystal display
LDCM Line data communication module
LDD Local detection device
LED Light-emitting diode
LNT LON network tool
LON Local operating network
MCB Miniature circuit breaker
MCM Mezzanine carrier module
MPM Main processing module
MVAL Value of measurement
MVB Multifunction vehicle bus. Standardized serial bus originally developed
for use in trains.
NCC National Control Centre

680 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 21
Glossary

NOF Number of grid faults


NUM Numerical module
OCO cycle Open-close-open cycle
OCP Overcurrent protection
OLTC On-load tap changer
OTEV Disturbance data recording initiated by other event than start/pick-up
OV Overvoltage
Overreach A term used to describe how the relay behaves during a fault condition.
For example, a distance relay is overreaching when the impedance
presented to it is smaller than the apparent impedance to the fault
applied to the balance point, that is, the set reach. The relay “sees” the
fault but perhaps it should not have seen it.
PCI Peripheral component interconnect, a local data bus
PCM Pulse code modulation
PCM600 Protection and control IED manager
PC-MIP Mezzanine card standard
PELV circuit Protected Extra-Low Voltage circuit type according to IEC60255-27
PMC PCI Mezzanine card
POR Permissive overreach
POTT Permissive overreach transfer trip
Process bus Bus or LAN used at the process level, that is, in near proximity to the
measured and/or controlled components
PRP Parallel redundancy protocol
PSM Power supply module
PST Parameter setting tool within PCM600
PTP Precision time protocol
PT ratio Potential transformer or voltage transformer ratio
PUTT Permissive underreach transfer trip
RASC Synchrocheck relay, COMBIFLEX
RCA Relay characteristic angle
RISC Reduced instruction set computer
RMS value Root mean square value
RS422 A balanced serial interface for the transmission of digital data in point-
to-point connections
RS485 Serial link according to EIA standard RS485
RTC Real-time clock
RTU Remote terminal unit
SA Substation Automation
SBO Select-before-operate
SC Switch or push button to close
SCL Short circuit location
SCS Station control system

Breaker protection REQ650 681


Technical manual
© Copyright 2017 ABB. All rights reserved
Section 21 1MRK 505 384-UEN C
Glossary

SCADA Supervision, control and data acquisition


SCT System configuration tool according to standard IEC 61850
SDU Service data unit
SELV circuit Safety Extra-Low Voltage circuit type according to IEC60255-27
SFP Small form-factor pluggable (abbreviation)
Optical Ethernet port (explanation)

SLM Serial communication module.


SMA connector Subminiature version A, A threaded connector with constant
impedance.
SMT Signal matrix tool within PCM600
SMS Station monitoring system
SNTP Simple network time protocol – is used to synchronize computer clocks
on local area networks. This reduces the requirement to have accurate
hardware clocks in every embedded system in a network. Each
embedded node can instead synchronize with a remote clock,
providing the required accuracy.
SOF Status of fault
SPA Strömberg Protection Acquisition (SPA), a serial master/slave protocol
for point-to-point and ring communication.
SRY Switch for CB ready condition
ST Switch or push button to trip
Starpoint Neutral point of transformer or generator
SVC Static VAr compensation
TC Trip coil
TCS Trip circuit supervision
TCP Transmission control protocol. The most common transport layer
protocol used on Ethernet and the Internet.
TCP/IP Transmission control protocol over Internet Protocol. The de facto
standard Ethernet protocols incorporated into 4.2BSD Unix. TCP/IP
was developed by DARPA for Internet working and encompasses both
network layer and transport layer protocols. While TCP and IP specify
two protocols at specific protocol layers, TCP/IP is often used to refer
to the entire US Department of Defense protocol suite based upon
these, including Telnet, FTP, UDP and RDP.
TEF Time delayed earth-fault protection function
TLS Transport Layer Security
TM Transmit (disturbance data)
TNC connector Threaded Neill-Concelman, a threaded constant impedance version of a
BNC connector
TP Trip (recorded fault)
TPZ, TPY, TPX, TPS Current transformer class according to IEC
TRM Transformer Module. This module transforms currents and voltages
taken from the process into levels suitable for further signal
processing.
TYP Type identification

682 Breaker protection REQ650


Technical manual
© Copyright 2017 ABB. All rights reserved
1MRK 505 384-UEN C Section 21
Glossary

UMT User management tool


Underreach A term used to describe how the relay behaves during a fault condition.
For example, a distance relay is underreaching when the impedance
presented to it is greater than the apparent impedance to the fault
applied to the balance point, that is, the set reach. The relay does not
“see” the fault but perhaps it should have seen it. See also Overreach.
UTC Coordinated Universal Time. A coordinated time scale, maintained by
the Bureau International des Poids et Mesures (BIPM), which forms the
basis of a coordinated dissemination of standard frequencies and time
signals. UTC is derived from International Atomic Time (TAI) by the
addition of a whole number of "leap seconds" to synchronize it with
Universal Time 1 (UT1), thus allowing for the eccentricity of the Earth's
orbit, the rotational axis tilt (23.5 degrees), but still showing the Earth's
irregular rotation, on which UT1 is based. The Coordinated Universal
Time is expressed using a 24-hour clock, and uses the Gregorian
calendar. It is used for aeroplane and ship navigation, where it is also
sometimes known by the military name, "Zulu time." "Zulu" in the
phonetic alphabet stands for "Z", which stands for longitude zero.
UV Undervoltage
WEI Weak end infeed logic
VT Voltage transformer
3IO Three times zero-sequence current.Often referred to as the residual or
the earth-fault current
3UO Three times the zero sequence voltage. Often referred to as the
residual voltage or the neutral point voltage

Breaker protection REQ650 683


Technical manual
© Copyright 2017 ABB. All rights reserved
684
685
ABB AB
Grid Automation Products
SE-721 59 Västerås, Sweden
Phone +46 (0) 21 32 50 00
Scan this QR code to visit our website
www.abb.com/protection-control
1MRK 505 384-UEN

© Copyright 2017 ABB.


All rights reserved.

You might also like