R E L I O N ® 650 SERIES

IEC 61850 Edition 1, 650 series


Version 2.1
Communication protocol manual
Document ID: 1MRK 511 375-UEN
Issued: March 2019
Revision: A
Product version: 2.1

© Copyright 2016 ABB. All rights reserved


Copyright
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third party, nor
used for any unauthorized purpose.

The software and hardware described in this document is furnished under a license and may
be used or disclosed only in accordance with the terms of such license.

This product includes software developed by the OpenSSL Project for use in the OpenSSL
Toolkit. (http://www.openssl.org/) This product includes cryptographic software written/
developed by: Eric Young (eay@cryptsoft.com) and Tim Hudson (tjh@cryptsoft.com).

Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names
mentioned in this document may be trademarks or registered trademarks of their respective
holders.

Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or product
description and are not to be deemed as a statement of guaranteed properties. All persons
responsible for applying the equipment addressed in this manual must satisfy themselves that
each intended application is suitable and acceptable, including that any applicable safety or
other operational requirements are complied with. In particular, any risks in applications where
a system failure and/or product failure would create a risk for harm to property or persons
(including but not limited to personal injuries or death) shall be the sole responsibility of the
person or entity applying the equipment, and those so responsible are hereby requested to
ensure that all measures are taken to exclude or mitigate such risks.

This document has been carefully checked by ABB but deviations cannot be completely ruled
out. In case any errors are detected, the reader is kindly requested to notify the manufacturer.
Other than under explicit contractual commitments, in no event shall ABB be responsible or
liable for any loss or damage resulting from the use of this manual or the application of the
equipment.
Conformity
This product complies with the directive of the Council of the European Communities on the
approximation of the laws of the Member States relating to electromagnetic compatibility
(EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified
voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests
conducted by ABB in accordance with the product standard EN 60255-26 for the EMC directive,
and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive. The
product is designed in accordance with the international standards of the IEC 60255 series.
Table of contents

Table of contents

Section 1 Introduction.........................................................................................................5
1.1 This manual......................................................................................................................................... 5
1.2 Intended audience............................................................................................................................. 5
1.3 Product documentation................................................................................................................... 6
1.3.1 Product documentation set........................................................................................................ 6
1.3.2 Document revision history...........................................................................................................7
1.3.3 Related documents........................................................................................................................7
1.4 Document symbols and conventions.............................................................................................9
1.4.1 Symbols........................................................................................................................................... 9
1.4.2 Document conventions................................................................................................................ 9
1.5 IEC 61850 edition 1 / edition 2 mapping..................................................................................... 10

Section 2 Introduction to IEC 61850................................................................................13


2.1 Overview.............................................................................................................................................13
2.2 Related documentation to IEC 61850.......................................................................................... 14

Section 3 Substation Configuration description Language (SCL).............................. 17


3.1 The substation section................................................................................................................... 18
3.2 The communication section...........................................................................................................18
3.3 The IED section................................................................................................................................. 19
3.4 Tool concept......................................................................................................................................21
3.5 Engineering concept in IEC 61850-6.............................................................................................22

Section 4 Communication profile.................................................................................... 23

Section 5 Supported services...........................................................................................25

Section 6 Data sets and control blocks.......................................................................... 29


6.1 Data sets............................................................................................................................................29
6.2 Report control block (URCB/BRCB)............................................................................................. 30
6.3 GOOSE Control Blocks (GoCB)...................................................................................................... 33

Section 7 Logical node data model..................................................................................35


7.1 Common data objects in each logical node............................................................................... 35
7.2 Logical nodes for control............................................................................................................... 36
7.2.1 Bay control CBAY......................................................................................................................... 36
7.2.1.1 Bay control QCBAY...................................................................................................................36
7.2.2 Switch controller CSWI............................................................................................................... 38
7.2.2.1 Switch controller SCSWI......................................................................................................... 38
7.3 Logical nodes for conversion functions......................................................................................40
7.3.1 Integer to Boolean converter FCVB......................................................................................... 40
7.3.1.1 Integer to Boolean 16 conversion with logic node representation ITBGAPC.............. 40
7.3.2 Boolean to integer converter FCVI........................................................................................... 41

1
Communication protocol manual
Table of contents

7.3.2.1 Boolean to integer conversion with logical node representation, 16 bit BTIGAPC.....41
7.4 Logical nodes for protection functions...................................................................................... 42
7.4.1 Protection trip conditioning PTRC...........................................................................................42
7.4.1.1 Logic for group alarm ALMCALH...........................................................................................42
7.4.1.2 Logic for group indication INDCALH....................................................................................43
7.4.1.3 Tripping logic common 3-phase output SMPPTRC...........................................................44
7.4.1.4 Logic for group warning WRNCALH..................................................................................... 45
7.4.2 Multipurpose analog protection GAPC................................................................................... 46
7.4.2.1 General currrent and voltage protection CVGAPC............................................................ 46
7.5 System logical nodes...................................................................................................................... 54
7.5.1 Generic security application component............................................................................... 54
7.5.1.1 Generic security application component AGSAL............................................................... 54
7.5.2 Physical device information LPHD........................................................................................... 55
7.5.3 Logical node zero LLNO............................................................................................................. 55
7.5.4 Access point diagnostic for redundant Ethernet ports RCHLCCH................................... 56
7.5.5 Access point diagnostic for non-redundant Ethernet port SCHLCCH............................. 57
7.6 Logical nodes for protection related functions........................................................................ 58
7.6.1 Breaker failure RBRF................................................................................................................... 58
7.6.1.1 Breaker failure protection CCRBRF...................................................................................... 58
7.6.2 Disturbance recorder RDRE.......................................................................................................59
7.6.2.1 Disturbance report DRPRDRE................................................................................................ 59
7.7 Logical nodes for generic references.......................................................................................... 60
7.7.1 Generic process I/O GGIO......................................................................................................... 60
7.7.1.1 Logic rotating switch for function selection and LHMI presentation SLGAPC...........60
7.7.1.2 Selector mini switch VSGAPC................................................................................................ 62
7.7.1.3 Generic communication function for Double Point indication DPGAPC.......................63
7.7.1.4 Single point generic control 8 signals SPC8GAPC.............................................................64
7.7.1.5 Event counter with limit supervision L4UFCNT................................................................. 67
7.7.1.6 IEC 61850 generic communication I/O functions SPGGIO.............................................. 68
7.7.1.7 IEC 61850 generic communication I/O functions 16 inputs SP16GGIO........................ 69
7.7.1.8 Generic communication function for Measured Value MVGAPC.....................................71
7.7.1.9 Trip matrix logic TMAGAPC.................................................................................................... 72
7.7.1.10 Elapsed time integrator with limit transgression and overflow supervision
TEIGGIO...................................................................................................................................... 73
7.8 Logical nodes for sensors and monitoring.................................................................................75
7.8.1 Circuit breaker monitoring SSCBR........................................................................................... 75
7.8.1.1 Breaker monitoring SSCBR.....................................................................................................75
7.8.2 Insulation medium supervision (gas) SIMG............................................................................79
7.8.2.1 Gas medium supervision SSIMG............................................................................................79
7.8.3 Insulation medium supervision (liquid) SIML.........................................................................81
7.8.3.1 Liquid medium supervision SSIML........................................................................................81
7.8.4 Through fault monitoring STHR............................................................................................... 82
7.8.4.1 Through fault monitoring PTRSTHR ....................................................................................82
7.9 Logical nodes for switchgear........................................................................................................ 83
7.9.1 Circuit breaker XCBR...................................................................................................................83
7.9.1.1 Circuit breaker SXCBR............................................................................................................. 83

2
Communication protocol manual
Table of contents

7.9.2 Switch XSWI..................................................................................................................................86


7.9.2.1 Circuit switch SXSWI............................................................................................................... 86

Section 8 Flexible product naming.................................................................................. 89


8.1 Introduction...................................................................................................................................... 89
8.1.1 Mapping example........................................................................................................................ 89
8.1.2 Mapping possibilities and requirements............................................................................... 90

Section 9 Glossary............................................................................................................. 93
9.1 Glossary............................................................................................................................................. 93

3
Communication protocol manual
4
1MRK 511 375-UEN A Section 1
Introduction

Section 1 Introduction

1.1 This manual GUID-AB423A30-13C2-46AF-B7FE-A73BB425EB5F v19

The communication protocol manual describes the communication protocols supported by


the IED. The manual concentrates on the vendor-specific implementations.

1.2 Intended audience GUID-C9B8127F-5748-4BEA-9E4F-CC762FE28A3A v10

This manual addresses the communication system engineer or system integrator responsible
for pre-engineering and engineering for communication setup in a substation from an IED
perspective.

The system engineer or system integrator must have a basic knowledge of communication in
protection and control systems and thorough knowledge of the specific communication
protocol.

5
Communication protocol manual
Section 1 1MRK 511 375-UEN A
Introduction

1.3 Product documentation

1.3.1 Product documentation set GUID-3AA69EA6-F1D8-47C6-A8E6-562F29C67172 v15

Deinstalling & disposal


Planning & purchase

Decommissioning
Commissioning

Maintenance
Engineering

Operation
Installing
Engineering manual
Installation manual

Commissioning manual
Operation manual

Application manual

Technical manual

Communication
protocol manual
Cyber security
deployment guideline
IEC07000220-4-en.vsd
IEC07000220 V4 EN-US

Figure 1: The intended use of manuals throughout the product lifecycle


The engineering manual contains instructions on how to engineer the IEDs using the various
tools available within the PCM600 software. The manual provides instructions on how to set
up a PCM600 project and insert IEDs to the project structure. The manual also recommends a
sequence for the engineering of protection and control functions, LHMI functions as well as
communication engineering for IEC 60870-5-103, IEC 61850, DNP3, LON and SPA.

The installation manual contains instructions on how to install the IED. The manual provides
procedures for mechanical and electrical installation. The chapters are organized in the
chronological order in which the IED should be installed.

The commissioning manual contains instructions on how to commission the IED. The manual
can also be used by system engineers and maintenance personnel for assistance during the
testing phase. The manual provides procedures for the checking of external circuitry and
energizing the IED, parameter setting and configuration as well as verifying settings by
secondary injection. The manual describes the process of testing an IED in a station which is
not in service. The chapters are organized in the chronological order in which the IED should be
commissioned. The relevant procedures may be followed also during the service and
maintenance activities.

The operation manual contains instructions on how to operate the IED once it has been
commissioned. The manual provides instructions for the monitoring, controlling and setting of
the IED. The manual also describes how to identify disturbances and how to view calculated
and measured power grid data to determine the cause of a fault.

6
Communication protocol manual
1MRK 511 375-UEN A Section 1
Introduction

The application manual contains application descriptions and setting guidelines sorted per
function. The manual can be used to find out when and for what purpose a typical protection
function can be used. The manual can also provide assistance for calculating settings.

The technical manual contains operation principle descriptions, and lists function blocks, logic
diagrams, input and output signals, setting parameters and technical data, sorted per
function. The manual can be used as a technical reference during the engineering phase,
installation and commissioning phase, and during normal service.

The communication protocol manual describes the communication protocols supported by


the IED. The manual concentrates on the vendor-specific implementations.

The point list manual describes the outlook and properties of the data points specific to the
IED. The manual should be used in conjunction with the corresponding communication
protocol manual.

The cyber security deployment guideline describes the process for handling cyber security
when communicating with the IED. Certification, Authorization with role based access control,
and product engineering for cyber security related events are described and sorted by
function. The guideline can be used as a technical reference during the engineering phase,
installation and commissioning phase, and during normal service.

1.3.2 Document revision history GUID-C8027F8A-D3CB-41C1-B078-F9E59BB73A6C v2.1.1

Document revision/date History


January 2016 First Release
March 2019 Maintenance Release

1.3.3 Related documents GUID-94E8A5CA-BE1B-45AF-81E7-5A41D34EE112 v4

Documents related to REB650 Document numbers


Application manual 1MRK 505 359-UEN
Commissioning manual 1MRK 505 361-UEN
Product guide 1MRK 505 362-BEN
Technical manual 1MRK 505 360-UEN
Type test certificate 1MRK 505 362-TEN

Documents related to REC650 Document numbers


Application manual 1MRK 511 384-UEN
Commissioning manual 1MRK 511 386-UEN
Product guide 1MRK 511 387-BEN
Technical manual 1MRK 511 385-UEN
Type test certificate 1MRK 511 387-TEN

7
Communication protocol manual
Section 1 1MRK 511 375-UEN A
Introduction

Documents related to RED650 Document numbers


Application manual 1MRK 505 363-UEN
Commissioning manual 1MRK 505 365-UEN
Product guide 1MRK 505 366-BEN
Technical manual 1MRK 505 364-UEN
Type test certificate 1MRK 505 366-TEN

Documents related to REL650 Document numbers


Application manual 1MRK 506 364-UEN
Commissioning manual 1MRK 506 366-UEN
Product guide 1MRK 506 367-BEN
Technical manual 1MRK 506 365-UEN
Type test certificate 1MRK 506 367-TEN

Documents related to REQ650 Document numbers


Application manual 1MRK 505 355-UEN
Commissioning manual 1MRK 505 357-UEN
Product guide 1MRK 505 358-BEN
Technical manual 1MRK 505 356-UEN
Type test certificate 1MRK 505 358-TEN

Documents related to RET650 Document numbers


Application manual 1MRK 504 158-UEN
Commissioning manual 1MRK 504 160-UEN
Product guide 1MRK 504 161-BEN
Technical manual 1MRK 504 159-UEN
Type test certificate 1MRK 504 161-TEN

650 series manuals Document numbers


Operation manual 1MRK 500 125-UEN
Engineering manual 1MRK 511 381-UEN
Installation manual 1MRK 514 025-UEN
Communication protocol manual, DNP3 1MRK 511 374-UUS
Communication protocol manual, IEC 60870-5-103 1MRK 511 377-UEN
Communication protocol manual, IEC 61850 Edition 1 1MRK 511 375-UEN
Communication protocol manual, IEC 61850 Edition 2 1MRK 511 376-UEN
Communication protocol manual, LON 1MRK 511 378-UEN
Communication protocol manual, SPA 1MRK 511 379-UEN
Point list manual, DNP3 1MRK 511 380-UUS
Accessories guide IEC: 1MRK 514 012-UEN
ANSI: 1MRK 514 012-UUS
Table continues on next page

8
Communication protocol manual
1MRK 511 375-UEN A Section 1
Introduction

650 series manuals Document numbers


Cyber security deployment guideline 1MRK 511 382-UEN
Connection and Installation components 1MRK 513 003-BEN
Test system, COMBITEST 1MRK 512 001-BEN

1.4 Document symbols and conventions

1.4.1 Symbols GUID-2945B229-DAB0-4F15-8A0E-B9CF0C2C7B15 v12

The electrical warning icon indicates the presence of a hazard which could
result in electrical shock.

The warning icon indicates the presence of a hazard which could result in
personal injury.

The caution hot surface icon indicates important information or warning about
the temperature of product surfaces.

The caution icon indicates important information or warning related to the


concept discussed in the text. It might indicate the presence of a hazard which
could result in corruption of software or damage to equipment or property.

The information icon alerts the reader of important facts and conditions.

The tip icon indicates advice on, for example, how to design your project or
how to use a certain function.

Although warning hazards are related to personal injury, it is necessary to understand that
under certain operational conditions, operation of damaged equipment may result in
degraded process performance leading to personal injury or death. It is important that the
user fully complies with all warning and cautionary notices.

1.4.2 Document conventions GUID-96DFAB1A-98FE-4B26-8E90-F7CEB14B1AB6 v8

• Abbreviations and acronyms in this manual are spelled out in the glossary. The glossary
also contains definitions of important terms.
• Push button navigation in the LHMI menu structure is presented by using the push button
icons.
For example, to navigate between the options, use and .
• HMI menu paths are presented in bold.
For example, select Main menu/Settings.
• LHMI messages are shown in Courier font.

9
Communication protocol manual
Section 1 1MRK 511 375-UEN A
Introduction

For example, to save the changes in non-volatile memory, select Yes and press .
• Parameter names are shown in italics.
For example, the function can be enabled and disabled with the Operation setting.
• Each function block symbol shows the available input/output signal.
• the character ^ in front of an input/output signal name indicates that the signal
name may be customized using the PCM600 software.
• the character * after an input signal name indicates that the signal must be
connected to another function block in the application configuration to achieve a
valid application configuration.
• Dimensions are provided both in inches and millimeters. If it is not specifically mentioned
then the dimension is in millimeters.

1.5 IEC 61850 edition 1 / edition 2 mapping GUID-C5133366-7260-4C47-A975-7DBAB3A33A96 v3

Table 1: IEC 61850 edition 1 / edition 2 mapping


Function block name Edition 1 logical nodes Edition 2 logical nodes
AGSAL AGSAL AGSAL
SECLLN0
ALMCALH ALMCALH ALMCALH
ALTIM - ALTIM
ALTMS - ALTMS
ALTRK - ALTRK
BRCPTOC BRCPTOC BRCPTOC
BTIGAPC B16IFCVI BTIGAPC
CCPDSC CCRPLD CCPDSC
CCRBRF CCRBRF CCRBRF
CCSSPVC CCSRDIF CCSSPVC
CMMXU CMMXU CMMXU
CMSQI CMSQI CMSQI
CVGAPC GF2LLN0 GF2MMXN
GF2MMXN GF2PHAR
GF2PHAR GF2PTOV
GF2PTOV GF2PTUC
GF2PTUC GF2PTUV
GF2PTUV GF2PVOC
GF2PVOC PH1PTRC
PH1PTRC
CVMMXN CVMMXN CVMMXN
DPGAPC DPGGIO DPGAPC
DRPRDRE DRPRDRE DRPRDRE
EF4PTOC EF4LLN0 EF4PTRC
EF4PTRC EF4RDIR
EF4RDIR GEN4PHAR
GEN4PHAR PH1PTOC
PH1PTOC
EFPIOC EFPIOC EFPIOC
ETPMMTR ETPMMTR ETPMMTR
FUFSPVC SDDRFUF FUFSPVC
HZPDIF HZPDIF HZPDIF
Table continues on next page

10
Communication protocol manual
1MRK 511 375-UEN A Section 1
Introduction

Function block name Edition 1 logical nodes Edition 2 logical nodes


INDCALH INDCALH INDCALH
ITBGAPC IB16FCVB ITBGAPC
L4UFCNT L4UFCNT L4UFCNT
LCPTTR LCPTTR LCPTTR
LD0LLN0 LLN0 LLN0
LDLPSCH LDLPDIF LDLPSCH
LFPTTR LFPTTR LFPTTR
LMBRFLO LMBRFLO LMBRFLO
LOVPTUV LOVPTUV LOVPTUV
LPHD LPHD LPHD
LT3CPDIF LT3CPDIF LT3CGAPC
LT3CPDIF
LT3CPHAR
LT3CPTRC
MVGAPC MVGGIO MVGAPC
NS4PTOC EF4LLN0 EF4PTRC
EF4PTRC EF4RDIR
EF4RDIR PH1PTOC
GEN4PHAR
PH1PTOC
OC4PTOC OC4LLN0 GEN4PHAR
GEN4PHAR PH3PTOC
PH3PTOC PH3PTRC
PH3PTRC
OV2PTOV GEN2LLN0 OV2PTOV
OV2PTOV PH1PTRC
PH1PTRC
PCFCNT PCGGIO PCFCNT
PHPIOC PHPIOC PHPIOC
PRPSTATUS RCHLCCH RCHLCCH
SCHLCCH
QCBAY QCBAY BAY/LLN0
QCRSV QCRSV QCRSV
REFPDIF REFPDIF REFPDIF
ROV2PTOV GEN2LLN0 PH1PTRC
PH1PTRC ROV2PTOV
ROV2PTOV
SCILO SCILO SCILO
SCSWI SCSWI SCSWI
SESRSYN RSY1LLN0 AUT1RSYN
AUT1RSYN MAN1RSYN
MAN1RSYN SYNRSYN
SYNRSYN
SINGLELCCH - SCHLCCH
SLGAPC SLGGIO SLGAPC
SMBRREC SMBRREC SMBRREC
SMPPTRC SMPPTRC SMPPTRC
SP16GAPC SP16GGIO SP16GAPC
SPC8GAPC SPC8GGIO SPC8GAPC
Table continues on next page

11
Communication protocol manual
Section 1 1MRK 511 375-UEN A
Introduction

Function block name Edition 1 logical nodes Edition 2 logical nodes


SPGAPC SPGGIO SPGAPC
SSCBR SSCBR SSCBR
SSIMG SSIMG SSIMG
SSIML SSIML SSIML
SXCBR SXCBR SXCBR
SXSWI SXSWI SXSWI
T3WPDIF T3WPDIF T3WGAPC
T3WPDIF
T3WPHAR
T3WPTRC
TEIGAPC TEIGGIO TEIGAPC
TEILGAPC TEILGGIO TEILGAPC
TMAGAPC TMAGGIO TMAGAPC
TRPTTR TRPTTR TRPTTR
UV2PTUV GEN2LLN0 PH1PTRC
PH1PTRC UV2PTUV
UV2PTUV
VMMXU VMMXU VMMXU
VMSQI VMSQI VMSQI
VNMMXU VNMMXU VNMMXU
VSGAPC VSGGIO VSGAPC
WRNCALH WRNCALH WRNCALH
ZCLCPSCH ZCLCPLAL ZCLCPSCH
ZCPSCH ZCPSCH ZCPSCH
ZCRWPSCH ZCRWPSCH ZCRWPSCH
ZCVPSOF ZCVPSOF ZCVPSOF
ZMFPDIS ZMFLLN0 PSFPDIS
PSFPDIS PSFPDIS
ZMFPDIS ZMFPDIS
ZMFPTRC ZMFPTRC
ZMMMXU ZMMMXU

12
Communication protocol manual
1MRK 511 375-UEN A Section 2
Introduction to IEC 61850

Section 2 Introduction to IEC 61850

2.1 Overview GUID-66925336-B6C3-4B22-95F4-A3321B63FABB v7

The general scope of the IEC 61850 protocol standard is designed to support the
communication of all functions being performed in the substation. Its’ main goal is
interoperability; this is the ability for IEDs from one or different manufacturers to exchange
information and use the information for their own functions. Moreover, the standard allows a
free allocation of these functions and accepts any system philosophy, from a distributed
architecture (for example, decentralised substation automation) to a centralised configuration
(for example, RTU based).

The standard separates the functionality represented by the data model and the related
communication services from the communication implementation (stack).

The data model of the standard is an object-oriented one, grouping the data into the smallest
possible sets referring to the smallest possible functions to be implemented independently.
These smallest possible data groups or functions are named logical nodes. The logical nodes
and all data and attributes contained are named according to a standardised semantic, which
is mandatory.

This manual describes how the IEC 61850 standard is applied in the IEDs. References and brief
descriptions of the standard are also included. It is assumed that the reader has basic
knowledge of the IEC 61850 standard.

The following parts of the IEC 61850 standard are of importance as they relate to this manual:

• Station Configuration description Language (SCL) is described in IEC 61850-6. The SCL is
an XML based definition of how to describe the parts of a substation. This part of the
standard also includes the roles of different tools as well as the engineering concepts.
• Communication profile (IEC 61850 stack) is described in IEC 61850-8-1. This part of the
standard includes a number of possible communication profiles, and how the services
defined in IEC 61850-7-2 are mapped to the communication profile.
• Communication services are described in IEC 61850-7-2. This part deals mainly with the
communication facilities from client and server point of view. It includes the different
possibilities of communication functionality.
• Logical node data model. This is described in IEC 61850-7-3 and IEC 61850-7-4.
• Conformance tests and the basis for conformance documents are handled in IEC
61850-10.

Detailed information regarding the IEC 61850 implementation of the IED is described inside
the conformance documents.

• MICS, Modeling Information Conformance Statement, contains the declaration of the


used logical node types.
• PICS, Protocol Information Conformance Statement, contains the details and what is
supported regarding protocol facilities.
• PIXIT, Protocol Extra Information, contains additional information on how the IEC 61850 is
implemented and used.
• TICS, Tissue Information Conformance Statement, contains the supported Tissues, which
are handled in the Tissues process as defined by UCA, Utility Communication Architecture
forum. The Tissues handling is found in http://www.tissue.iec61850.com.

13
Communication protocol manual
Section 2 1MRK 511 375-UEN A
Introduction to IEC 61850

The conformance documents are unique for each product release and refer to each other. The
identities included in the related documents refer to a specific version of the IED series.

The communication profile in IEC 61850 uses the MMS standard, which uses Ethernet and
TCP/IP to handle the information transport within the substation.

The data modelling uses the concept of logical nodes to identify the published information for
communication. The standard defines a set of logical nodes, each representing a
communication view of a process function with a number of data objects. For example, a
transformer differential - or line differential protection, because the standard defines only a
differential protection. Therefore, it is possible to adapt the logical node, which is defined in
the standard, as a logical node class. The standard defines methods to describe the actually
used logical node as a logical node type which is then based upon the logical node class. This
allows all partners to interpret the logical node type information because the description is
completely given in the standard. The type description of all logical nodes is part of the Data
Type Template (DTT) section in the SCL description file of a station or the IED.

Besides the information about the configuration of the communication facilities, this manual
contains the full description of all logical nodes available in the IEDs. The information about
the logical nodes and their data objects may be used to identify which signals are available for
the functions as described in the technical manual. The link to the technical manual is done in
the logical node tables by listing the signal name as given in the function block, or as seen in
PCM600 or the LHMI.

2.2 Related documentation to IEC 61850 GUID-906D4C7F-29FD-4922-8A8B-8A3A3E2B811E v5

Use the latest revision of the documents listed, unless stated otherwise.

Document ID Title
IEC 61850-5 Communication networks and systems in
First edition 2003-07 substations -
Ref. number: IEC 61850-5:2003(E) Part 5:
Communication requirements for functions and
devices models
IEC 61850-6 Communication networks and systems in
First edition 2004-03 substations -
Ref. number: IEC 61850-6: 2004(E) Part 6:
Configuration description language for
communication in electrical substations related to
IEDs
IEC 61850-7-1 Communication networks and systems in
First edition 2003-07 substations -
Ref. number: IEC 61850-7-1: 2003(E) Part 7-1:
Basic communication structure for substations and
feeder equipment -
Principles and models
IEC 61850-7-2 Communication networks and systems in
First edition 2003-05 substations -
Ref. number: IEC 61850-7-2: 2003(E) Part 7-2:
Basic communication structure for substations and
feeder equipment -
Abstract communication service interface (ACSI)
IEC 61850-7-3 Communication networks and systems in
First edition 2003-05 substations -
Ref. number: IEC 61850-7-3: 2003(E) Part 7-3:
Basic communication structure for substations and
feeder equipment -
Common data classes
Table continues on next page

14
Communication protocol manual
1MRK 511 375-UEN A Section 2
Introduction to IEC 61850

IEC 61850-7-4 Communication networks and systems in


First edition 2003-05 substations -
Ref. number: IEC 61850-7-4: 2003(E) Part 7-4:
Basic communication structure for substations and
feeder equipment -
Compatible logical node classes and data classes
IEC 61850-8-1 Communication networks and systems in
First edition 2004-05 substations -
Ref. number: IEC 61850-8-1: 2004(E) Part 8-1:
Specific Communication Service Mapping (SCSM) -
Mappings to MMS (ISO 9506-1 and ISO 9506-2) and to
ISO/IEC 8802-3
IEC 61850-10 Communication networks and systems in
First edition 2005-05 substations -
Ref. number: IEC 61850-10: 2005(E) Part 10:
Conformance testing
IEC 61850 MICS IED series version 2.1 Ed1 - MICS:
1MRG021087 Modelling implementation conformance statement
IEC 61850 PICS IED series version 2.1 Ed1 - PICS:
1MRG021055 Protocol implementation conformance statement
IEC 61850 PIXIT IED series version 2.1 Ed1 - PIXIT:
1MRG021064 Protocol implementation extra information
IEC 61850 TICS IED series version 2.1 Ed1 - TICS:
1MRG021063 Tissue implementation conformance statement

15
Communication protocol manual
16
1MRK 511 375-UEN A Section 3
Substation Configuration description Language (SCL)

Section 3 Substation Configuration


description Language (SCL)

SEMOD129808-4 v8
Four different types of SCL files - SCD, CID, IID, and ICD, can be exported from PCM 600.

The SCL language is based on XML. However, detailed knowledge of the XML contents is not
needed.

The SCL XML file (ICD/SCD/CID/IID) contains five sections, which are specified in IEC 61850–6
clause 9.

• Header
• Substation section describes the functional structure and its relation to primary devices.
• Communication section describes the connection between the IED access points to the
respective subnetwork. and includes also the properties (addresses) of the access points.
• IED section contains a description of the supported communication services, the access
point(s) and the IEDs logical devices, logical nodes and their attributes.
• Data type template section contains a declaration of all types used in the SCL file, logical
nodes type, DO types, attributes and enums.

The system structure is defined by the organization of the plant structure in PCM600. The
signal engineering and the signal routing are IET600 tasks, signal engineering regarding DS,
rcb,gcb, GOOSE subscribers can be done also in PCM600. The IED needs to be configured with
PCM600 before the system is configured with IET600.

The SCL engineering must be done in an SCL engineering tool. The data sets and the control
blocks are logically defined as part of the logical nodes (see IEC 61850–7–2 clause 9). The IED
also needs a correctly configured communication section for GOOSE engineering, which can
be done in IET600 or PCM600.

The data type templates section provides the correct content description of each logical node
type to all tools and users (clients) of the information. Each IED and vendor may have their own
logical node type definitions included in the data type template section together with all other
logical node types based on the standard.

17
Communication protocol manual
Section 3 1MRK 511 375-UEN A
Substation Configuration description Language (SCL)

Substation
VoltageLevel

Station
Bay
LNode
IED LD LN
IED LD LN

Communucation

Commun
Subnetwork
Connected AP
IED Name AccessPoint Address GSE
IED Name AccessPoint Address GSE

IED
Services AccessPoint
Server
Authentication
LDevice
LN0 LN
DataSet DOI
DAI
Report Control

GOOSE Control

Inputs

DOI

IED
SettingControl

DataTypeTemplates
LNodeType
DO
DOType

DOType
DA SDO
DAType

DAType
BDA
EnumType

EnumType

IEC08000178.vsd
IEC08000178 V1 EN-US

Figure 2: IEC 61850: Principle structure of the SCL XML file


The arrows show the link between the different sections given when an IED is integrated in the
substation structure and/or in the communication structure. All needed logical nodes of an
IED are linked to the substation section by the SCL tool.

A reference to GOOSE Control Blocks (GoCB) is included in the communication section when
GoCB is configured.

3.1 The substation section SEMOD129763-4 v4

The substation description in IEC 61850-6 clause 9 describes the arrangement of the primary
equipment. In addition, it also includes a list of the applied logical nodes and the relation of
those logical nodes to the primary equipment.

3.2 The communication section SEMOD129771-4 v3

The organization of the physical IEDs to the communication network is independent of the
substation structure. The IEC 61850 standard defines the communication network with no
relation to an existing media or protocol. The mapping to an existing media and protocol is
specified in IEC 61850–8–1.

18
Communication protocol manual
1MRK 511 375-UEN A Section 3
Substation Configuration description Language (SCL)

The IEC 61850 standard describes in part 7–2 the ACSI in a media and protocol independent
form. Part 8–1 specifies the mapping of this ACSI to the existing MMS.

The communication section describes how information is routed between the IEDs and
contains the following parts:

• Subnetworks
• IEDs connected to different subnetworks
• Access points per IED to subnetworks
• Address
• IP address of LAN network (is exceptionally part of the address elements)
• Link to GoCB message in transmission direction (extended during signal engineering and
routing)

IED IED
(client) (client)
- Access Point (AP) - Access Point (AP)
- Address - Address
- GSE; GoCBs - GSE; GoCBs
Communication Communication

Subnetwork AP

AP

Communication Communication Communication


- Access Point (AP) - Access Point (AP) - Access Point (AP)
- Address - Address - Address
- GSE; GoCBs - GSE; GoCBs - GSE; GoCBs

IED IED IED


(server) (server) (server)

en06000101.vsd
IEC06000101 V1 EN-US

Figure 3: IEC 61850–6: Communication network


Additional information about the server is part of the IED.

3.3 The IED section SEMOD129775-4 v6

The IED section describes the complete IED as it is needed for IEC 61850 communication and
signal engineering. The data type template part of an IED may be seen as part of the IED, even
when separated in its own section. The IED's ICD files include the description of the logical
nodes, their data type templates and the used or supported services. The structure of the IED
section follows the definitions made in the IEC 61850 standard.

Two basic IED types are used in system configuration.

• Station level IEDs


are located on the station level and are identified as client IEDs when they read or write
information from or to the bay IEDs. This functionality is represented by logical nodes of
group “Information (I)”. These are the logical nodes (LN) = ITCI, IHMI and ITMI. Client IEDs
are the receiver of information in monitoring direction and sender of commands (control).
These logical nodes have no data objects. They are only used to link the report control
blocks (BRCBs) from the server IEDs. They have to read their information about the signals

19
Communication protocol manual
Section 3 1MRK 511 375-UEN A
Substation Configuration description Language (SCL)

and the signal configuration from the bay IEDs. This is possible by checking all control
blocks for a link to it as a client.
• Bay level IEDs
are located on the bay level and are identified as server IEDs when they read or write
information vertically. When GOOSE messages are received, the bay level IED also has the
client role.

Subnetwork

AP

Server IED

SB1.LD0
Logical
Node
LLN0

LPHD Data
SXCBR1 Mod

SCSWI1 Beh

SXSWI1 Health
Data
SCSWI2 NamePlt Attribute
SXSWI2 Pos ctlVal

SCSWI3 Loc stVal

SXSWI3 OpCnt q

SCSWI4 BlkOpn t

SXSWI4 BlkCls Origin

SCSWI5 CBOpCap ctlModel

CVMMXU1 Control

en06000104.vsd
IEC06000104 V2 EN-US

Figure 4: Organization of LDs, LNs, DOs and DAs in an IED

• A server represents the communication interface to the subnetwork (Ethernet).


• One or more logical device(s) (LD) are connected to a server.
• A set of logical nodes belong to a LD.
• The LN LLN0 is a special logical node per LD and contains for example the data sets, the
various control blocks, inputs (from GOOSE messages). In the IED series, the data sets
and the control blocks shall be located to LD0.
• The LN LPHD is a special logical node per LD and contains data objects that describe the
status of the physical device (the IED)
• Each logical node represents a function and contains a number of data objects (DO)
• Each DO includes a number of data attributes (DA)

The data objects represent information signals that may be routed to station level IEDs or to
other bay IEDs that are communicating via GOOSE. The signal engineering task is to select the
requested signals (DOs) and link them to the client IEDs as receiver. When using a dataset for
MMS, the requested signals are DOs but when creating a dataset for GOOSE messaging, DAs
are used.

20
Communication protocol manual
1MRK 511 375-UEN A Section 3
Substation Configuration description Language (SCL)

The number of data objects and data attributes per DO is defined by the used LN type in the
IED. The content of logical node types and DO types are defined in the DTT. This also means
that the definitions in the DTT section have to be unique within an SCD file.

3.4 Tool concept GUID-93477EC1-9BB4-4CCE-8603-0D910BDD661B v6

The IEC 61850-6 defines a number of roles for tools. In the Relion® series, PCM600 is defined as
the IED tool, and IET600 is defined as the system engineering tool.

The sections in SCL contain properties that are to be configured by these tools. There is no
relation between one section and one specific tool. The task of the IED tool is to configure all
properties for the IED, while the system tool has the task to define the place of the IED in the
system and its communication dependencies. For example, the plant structure in PCM600
results in the subsystem section in SCL regarding the subsystem structure down to the IED
level. The PCM600 also configures the IED section as a result of the IED configuration. In
PCM600, the configuration properties for SCL are handled automatically as a result of the
configuration, except for the receiving of GOOSE information that has a dependency with the
system tool.

IEC 61850 engineering with PCM600, PCM600 IEC 61850 Configuration tool and IET600

PCM600:

• When an IED is instantiated, its place in the plant structure creates the corresponding
structure in the substation section in SCL. The communication facilities is also created in
the communication section.
• The functionality of the IED is configured by using ACT in PCM600. For each function, the
corresponding logical device and logical node(s) is created in the IED section together
with its type definition in data type template section
• The above forms the IED capabilities from a communication perspective and will then be
included in the file exported from PCM600 as SCD, ICD, IID and CID file

PCM600: IEC 61850 Configuration tool

• Included in PCM600 is the new IEC 61850 Configuration tool which allows the user to
define data sets and control blocks for both Client Server and GOOSE communication.
• The IEC 61850 Configuration tool gives the user the possibility to make the IEC 61850
engineering without export / import step.

It does NOT however allow the User to define the substation part.

IET600:

• Open a SCD file or import/merge a SCD, ICD or CID file for the particular IED(s).
• For each IED, the user defines the datasets, the control blocks for reporting (this means
unbufffered/buffered reporting and GOOSE) and the properties for each report control
block.

21
Communication protocol manual
Section 3 1MRK 511 375-UEN A
Substation Configuration description Language (SCL)

Data sets (DS) are generated automatically in PCM600. Report control


blocks (RCBs) are not generated automatically in PCM600.

• If client definitions (like client. ICD) are required in the system configuration, they are
merged into IET600 and connected to the unbuffered/buffered report control blocks.
• Logical nodes, which are not related to the conducting equipment, must be included in the
bay level in the substation section.
• The resulting SCD file is exported from IET600.

PCM600:

Define the inputs for the client in IET600 and cross-reference the signals in SMT. Import the
SCD file to PCM600 to receive GOOSE data. For each IED that shall receive GOOSE information,
the received data is connected to the applications using SMT in PCM600.To be able to import
scd-file to PCM600 61850 engineering in PCM must be set to disabled.

If input signals are not defined for clients in IET600, they will not be visible in
SMT. Inputs (GOOSE clients) can also be defined in PCM600.

3.5 Engineering concept in IEC 61850-6 GUID-FFE87459-FBC1-4D85-A6B3-7BD6F576ECE4 v3

• Top-down approach means that the system engineering tool has ICD files available for
each IED to be included in the system configuration. The ICD files may be of the template
type and represent a pre-configured IED.
• Bottom-up approach means that the configurations are produced by the IED tool, and
that are exported as CID files (or SCD file) to be imported into the system tools.

Client A Client B System


tool

IED A IED B IED Z IED



tool

IEC09000151-2-en.vsd

IEC09000151 V2 EN-US

Figure 5: Relation between system and IED tools


Regardless of the engineering approach, the idea is that the IED tool provides the CID or ICD
file for each IED. These ICD/CID files are then imported into the system tool and merged into a
SCD file, representing the complete substation or a part of the substation, like one for each
voltage level.

22
Communication protocol manual
1MRK 511 375-UEN A Section 4
Communication profile

Section 4 Communication profile

GUID-25495333-A2B7-44A7-908D-68EC06694AD5 v6
The IEC 61850 standard is conceptually written to be independent of an existing
communication media and message transmission concept. Out of this, a specific
communication profile is decided and has been commonly used. The profile contains:

• Ethernet as the media


• TCP/IP
• ISO session and presentation layer
• MMS (Manufacturing Message Specification (ISO 9506-1 and ISO 9506-2)

The IEC 61850 standard describes its requested services in ACSI, which is contained in part 7-2
of the standard. The mapping to the MMS for all aspects of services and Ethernet usage is
specified in part 8-1 of IEC 61850.

Each device manufacturer, which is a partner of an IEC 61850 based communication network,
has to take these two specifications and adapt their respective product to the requirements
and definitions given in the standard. To make this profile visible to all other partners, so they
can check what they can expect and what they have to support, the PICS document is defined.
The PICS contains in a table based form the possibility of a product or product family.

IED (client)
(61850 services; part 7-2)

- Access Point (AP) / Address


- GSE
Communication
(MMS services; part 8-1)

AP
Subnetwork

Communication Communication
(MMS services; part 8-1) (MMS services; part 8-1)

- Access Point (AP) / Address - Access Point (AP) / Address


- GSE - GSE

IED (server) IED (server)


(61850 services; part 7-2) (61850 services part; 7-2)

IEC08000179.vsd
IEC08000179 V1 EN-US

Figure 6: IEC 61850 Protocol: related standards for communication

23
Communication protocol manual
Section 4 1MRK 511 375-UEN A
Communication profile

Generic
Object Generic
Sampled Core Substation
Oriented
Values Time ACSI Status
Substation
(Multicast) Sync Services Event
Event

TimeSync
SV GOOSE (SNTP) MMS Protocol Suite GSSE

TCP/IP ISO CO GSSE


UDP/IP
T-Profile T-Profile T-Profile

ISO/IEC 8802-2 LLC

ISO/IEC 8802-3 Ethertype


ISO/IEC 8802-3

IEC09000153-1-en.vsd
IEC09000153 V1 EN-US

Figure 7: Overview of functionality and profiles according to IEC 61850-8-1


Out of this content, the implementation supports:

• Sampled values according to 9-2LE


• GOOSE
• TimeSync using SNTP
• The peer-to-peer/vertical communication using MMS protocol suite with the T-profile
TCP/IP

For each of the above, the resulting underlying protocols as stated in Figure 7.

See the PICS and PIXIT for more information.

24
Communication protocol manual
1MRK 511 375-UEN A Section 5
Supported services

Section 5 Supported services

GUID-E08C91D7-A59B-478B-B39A-26E786591E2A v7
IEC 61850-7-2 describes the services in the standard. IEC 61850-8-1 describes how the services
are applied in the communication. The conformance documents contain the description of the
supported services in the IED.

Services that are not mentioned in this chapter or in the conformance document are not
supported by the IED.

Data set
Define data sets by the SCD description.

Create data sets under LD0/LLN0.

For more information on data sets, see the PIXIT-related documents.

Substitution
Substitution is supported for the respective DATA, according to IEC 61850-7-4, that have the
substitution attributes defined.

Setting group control block


There is only one setting group control block, which is located in LD0/LLN0 (Logical Device0/
Logical Node 0).

Change or edit of setting values as well as reading of setting values is neither supported nor
visible in IEC 61850 edition 1.

The Setting range is expressed in the minVal and maxVal data attributes (DAs) in each setting
data object (DO). When writing settings a check will be done to compare the new value with
the minVal and maxVal attributes, when applicable (this depends on the data type and if the
minVal and maxVal are mapped). So if the minVal and maxVal is not mapped, all values in the
range of the data type will be accepted. If the written value is outside the range, Object-Value-
Invalid will be returned to the client.

Note that the actual number of used setting groups is defined by the
parameter MaxNoSetGRP in the function SETGRPS, which is configured in PST
in PCM600. But six setting groups is the maximum and it cannot be exceeded.

Setting parameter values via IEC 61850 Edition 2


Some parameters values can be set over IEC 61850 Edition 2 communication, provided that the
parameter Enable61850Setting has been set to Enabled in Main menu/Configuration/
Communication/Station communication/IEC61850–8–1/IEC61850–8–1:1/EnableSettings by
PCM600 or in the LHMI.

25
Communication protocol manual
Section 5 1MRK 511 375-UEN A
Supported services

IEC15000002-2-en.vsd

IEC15000002 V2 EN-US

Figure 8: Enabling parameter setting via IEC 61850

Setting parameter values over the communication link doesn't require any
authorization if Enable61850Setting has been set to Enabled.

Write to parameters with functional constraint (FC) = SP

• Issue: write to parameter

Writes to parameters where (FC) = SP should not be done while there is an


ongoing setting group edit session.

Write to parameters with functional constraint FC = SE

• Issue: write to SelectEditSG(n). (n) is the setting group


• Issue: write to one or several parameters
• Issue: write to ConfirmEditSG (CnfEdit=TRUE)

If a second SelectEditSG(n) is issued where n differs from the actual, any


setting changes are discarded and a new edit session is started.

Cancellation of an ongoing edit session. there are two ways to cancel an ongoing edit
session:

• Issue: write to ConfirmEditSG (CnfEdit=FALSE)

or

• Issue: write to SelectEditSG(0)

26
Communication protocol manual
1MRK 511 375-UEN A Section 5
Supported services

Reading values where FC = SP

• Issue: read from parameter

Report control block


For properties about report control blocks, see PIXIT.

UnBuffered reporting as well as Buffered reporting is supported.

Generic object oriented substation event (GOOSE)


The structured GOOSE is supported. This means that the data sets can be defined with FCDA
as well as explicit attributes.

The supported data types to be published and received over GOOSE are binary values, double
point values, integer values and measured values, together with their quality. One signal is
available inside the application to validate the reception of a GOOSE message. Invalid means
that the correct GOOSE message is not received prior 2*TAL(Time Allowed to Live).

GOOSE with TAL= 0 ms is treated as GOOSE with TAL = 100 ms and accepted.

Note that the data sets that are used or referred to by GOOSE control blocks
can only include a data attribute once. In other words, there may not be the
same data attribute in more than one data set.

When publishing a measured value, the user must take care of which measured value data
attributes are added to a data set. If the measured value is event-handled (like in the case of
MMXU functions), then one can add that value directly to the data set. If the value is not event-
handled, (like in the case of Synchrocheck function), it is recommended to connect the value
desired to be published to a MVGAPC function block (in ACT) and then use the measured value
given by the MVGAPC.

Example of functions that have event-handled measured values (can be added directly to the
data set).

• CVMMXN - Measurements
• CMMXU - Phase current measurement
• VMMXU - Phase-phase voltage measurement
• CMSQI - Current sequence component measurement
• VMSQI - Voltage sequence measurement
• VNMMXU - Phase-neutral voltage measurement
• MVGAPC - IEC 61850 generic communication I/ O functions

Generic function blocks are provided to make available to the 61850 bus signals that are not
defined inside any of the available function blocks. Example of such functions include:

• SPGAPC - IEC 61850 generic communication I/ O functions


• DPGAPC - IEC 61850 generic communication I/ O functions
• MVGAPC - IEC 61850 generic communication I/ O functions

Control
Of the different control sequences, the ‘direct-with-normal-security’ and ‘SBO-with-enhanced’
security are supported (defined by the ctlModel parameter, IEC 61850-7-2).

27
Communication protocol manual
Section 5 1MRK 511 375-UEN A
Supported services

Check bits; interlock check and synchrocheck check, are only valid for LN types based upon
CSWI class.

Verification of Originator Category is supported, see also PIXIT.

28
Communication protocol manual
1MRK 511 375-UEN A Section 6
Data sets and control blocks

Section 6 Data sets and control blocks

6.1 Data sets SEMOD129786-5 v7

IEC 61850 has defined data sets and report control blocks to transmit signals for monitoring
purposes. Data sets are also used for GOOSE messages in horizontal communication among
IEDs. The project defines the data objects or single data attributes that should be collected in
a data set. Figure 9 shows a data set where all position information of the apparatuses of a
bay are put into one data set.

PCM600 will generate default data sets, based on the current ACT configuration. The default
data sets can be modified or removed in the engineering tools. No RCBs are created
automatically by PCM600. However, the configured IEDs are delivered with RCBs for all default
the data sets.

LD0

DATA-SET
LLN0 LD0/LLN0.AppPos

LPHD LD0/SXCBR1.Pos FC=ST

SXCBR1 Pos LD0/SXSWI1.Pos FC=ST

SCSWI1 LD0/SXSWI2.Pos FC=ST


LD0/SXSWI3.Pos FC=ST
SXSWI1 Pos
LD0/SXSWI4.Pos FC=ST
SCSWI2

SXSWI2 Pos

SCSWI3

SXSWI3 Pos stVal

SCSWI4 q

SXSWI4 Pos t

SCSWI5 Origin

CVMMXU1
en06000106.vsd
IEC06000106 V2 EN-US

Figure 9: IEC 61850–7–2: Example of a data set for MMS


General rules for data set configuration:

• All data objects or their data attributes can be selected for a data set.
• Only those data attributes of a data object can/will be selected which have the same
function constraint (FC).
• Data objects with different FC can be selected for a data set. For example, DOs with FC =
ST and DOs with FC=MX can be member in one data set.
• A single data attribute can be selected when it is specified with a trigger option. For
example, the data attribute stVal of the data object Pos can be selected as a member of a
data set, because it is specified with the trigger option data change detected (dchg).

29
Communication protocol manual
Section 6 1MRK 511 375-UEN A
Data sets and control blocks

The description of the data sets with name and the list of data object members (FCDAs is
included in the SCL file in the IED section in the Logical device subsection. As specified in IEC
61850–7–2 clause 9, the data sets are part of a logical node. They are most likely included in the
LLN0.

6.2 Report control block (URCB/BRCB) SEMOD129786-17 v5

To be able to transmit the signals configured in a DataSet, a report control block must be
configured to handle and specify how the events are transmitted to the clients. There are two
types of report control blocks; unbuffered and buffered. The buffered report control block
stores the events during a communication interrupt, while the unbuffered is sent upon data
change and not stored during interruption.

The content of a BRCB is listed in IEC 61850-7-2 in clause 14. The BRCB contains many
attributes which are of interest to handle and secure the communication between the client
and the server and may be set once as default in a project. Others are of application interest in
the way events are handled in a project.

• Buffer time (valid only for BRCB)


• This parameter describes how long the report should wait for other expected events
before it sends the report to the client. When it is known, that additional events are
generated as a follow up, it is useful to wait, for example, 500 ms for additional
events stored in the report. This feature reduces the number of telegrams
transmitted in case of a burst of changes. Parameter IEC61850BufTimEnable
enables/disables the buffer time. For more information, refer section IEC 61850-8-1
communication protocol in Technical manual.
• Trigger options
• The data attributes know three different trigger options (dchg, qchg, dupd). Within
the BRCB, the two other can be defined (integrity and general interrogation). The
attribute Trigger option is a multiple choice and allows to mask the supported
trigger options in this BRCB.
• Integrity period
• When integrity is selected in the trigger option attribute, it is needed to define an
integrity period to force the transmission of all data listed in the DataSet. This is
done by the attribute Integrity period. This feature can be used as a background
cycle to ensure that the process image in all partners is the same.
• General interrogation
• A general interrogation is only done on request from a client. Not all Data-sets may
contain information which is needed for a general update of the client. For example
data with T(ransient) = TRUE are not part of a GI. When the BRCB attribute general
interrogation is set to TRUE a GI request from the client will be handled. The report
handler will transmit all data defined in the Data-set with their actual values. The IEC
61850 standard defines that all buffered events shall be transmitted first before the
GI is started. A running GI shall be stopped and a new GI shall be started, when a new
GI request is received while a GI is running.
• Purge buffer (valid only for BRCB)
• This BRCB attribute can be used by a client to clean the event buffer from old events.
The events are discarded on request of the client. This feature can be used to delete
old events not transmitted to the client due to stopped communication. After the
link is reestablished the client can decide to clean the buffer or to receive the history.

30
Communication protocol manual
1MRK 511 375-UEN A Section 6
Data sets and control blocks

Trigger Options
IEC 61850 has defined in total five different TrgOp. Three of them belonging to data attributes
and marked per data attribute in the column TrgOp of the CDC tables in part 7–3. The other
two belonging to the configuration of control blocks.

• dchg = data-change
• Whenever a process value has changed its value either binary or a measurement a
transmission is done.
• qchg = quality change
• Looking to the possibilities of the quality data attribute type (q) any changes in the
quality description will be transmitted.
• dupd = data value update
• This trigger option give the possibility to define that a transmission should be done
on a condition which can be controlled by the application.
• integrity
• This trigger forces the transmission of all process values defined in the data set
when a timer value (the integrity period) expires.
• general interrogation
• This trigger is forced by the clients (= station level IED; NCC gateway, station
HMI, ...). Normally a GI is asked for, when the client and the server start or restart a
session. When the client is able to receive the actual values and when the logical
device has scanned all process values at least once, an image of the actual process
signal status can be transmitted to the client.

Note that the possible trigger options for each attribute are included
and defined in the datatype template section in SCL.

Link BRCB to a client LN


The BRCB has to know to whom the events shall be transmitted. This is the signal routing
engineering step. The IEC standard 61850–6 describes that this is given by including the LN of
the client IED in the ReportBlockEnabled option.

The selected client IED with the corresponding LN, for example, ITCI is included in the SCL
structure of the Report Control description of the IED section.

The description of the BRCB with selected DataSet, configured parameters and selected IEDs
is included in the SCL file in the IED section in the LN0 structure for the LD where this LN0
belongs to.

31
Communication protocol manual
Section 6 1MRK 511 375-UEN A
Data sets and control blocks

IED IED IED


HSI NCC GW 1 NCC GW m

Client 1 IHSI1 Client 2 ITCI1 Client m ITCI2

Subnetwork

Server 1 LLN0
DATA-SET
LD0/LLN0.AppPos
IED 1 LD0/SXCBR1.Pos FC=ST
LD0/SXSWI1.Pos FC=ST
LD0/SXSWI2.Pos FC=ST
LD0/SXSWI3.Pos FC=ST
LD0/SXSWI4.Pos FC=ST

en06000107.vsd
IEC06000107 V2 EN-US

Figure 10: Link BRCB to a client LN

32
Communication protocol manual
1MRK 511 375-UEN A Section 6
Data sets and control blocks

6.3 GOOSE Control Blocks (GoCB) SEMOD129786-83 v6

Receive
Receive

Receive
Receive

Receive

Receive
Send

Send

Send
Data-set Data-set Data-set

LN LN LN
LN LN
LN
LN LN LN
LN
LN LN LN LN LN

Subnetwork

Comm. Comm.
GSE GSE

Server Server

LD0 LD0

GoCB
GoCB
GoCB Input
Input
Input GoCB
GoCB
GoCB Input
Input
Input

DataSet
DataSet
DataSet DataSet
DataSet
DataSet
LN0 LN0

en06000109.vsd
IEC06000109 V2 EN-US

Figure 11: IEC 61850: Principle operation of GOOSE messages


The Generic Object Oriented Substation Event (GOOSE) class model is used to distribute input
and output data values between IEDs on bay level (in horizontal direction) through the use of
multicast services. GOOSE messages enable fast transmission from a publisher to one or
several subscribers (receivers).

The GOOSE service model of IEC 61850-7-2 provides the possibility for fast and reliable
system-wide distribution of input and output data values. This implementation uses a specific
scheme of re-transmission to achieve the appropriate level of reliability. When a GOOSE server
generates a SendGOOSEMessage request, the current data set values are encoded in a GOOSE
message and transmitted on the multicast association. The event that causes the server to
invoke a SendGOOSE service is a local application issue as defined in IEC 61850-7-2. Each
update may generate a message in order to minimize throughput time.

Additional reliability is achieved by re-transmitting the same data (with gradually increasing
SqNum and retransmission time).

33
Communication protocol manual
Section 6 1MRK 511 375-UEN A
Data sets and control blocks

T0 retransmission in stable conditions (no event for a long time)


(T0) retransmission in stable conditions may be shortened by an event
T1 shortest retransmission time after the event
T2, T3 retransmission times until achieving the stable conditions time

Time of transmission

T0 (T0) T1 T1 T2 T3 T0

event
IEC09000152-1-en.vsd
IEC09000152 V1 EN-US

Figure 12: Transmission time for events


Each message in the retransmission sequence carries a timeAllowedToLive parameter that
informs the receiver of the maximum time to wait for the next re-transmission. If a new
message is not received within that time interval, the receiver assumes that the association is
lost. The specific intervals used by any GOOSE publisher are a local issue. The
timeAllowedtoLive parameter informs subscribers of how long to wait. The detection time of
lost GOOSE is 2* timeAllowedToLive in the subscriber. This allows one lost GOOSE message
and to cope with possible transmission delays in the network.

The GOOSE message concept is used for all application functions where two or more IEDs are
involved. Typical example is the station-wide interlocking procedure or breaker failure
protection.

Figure 11 shows the GOOSE concept for three IEDs which interchange GOOSE messages
between each other.

To send GOOSE messages a GoCB must be defined and a data set is needed that contains the
data objects of single data attributes to be sent.

A GOOSE message is forced to be transmitted when a trigger change is detected for a data
attribute. All members of the data set are copied in the send buffer with their actual value and
the message is sent. The subscribers, who knows the address of this GOOSE message,
receives the telegram. The GOOSE message includes a sequence number to verify that all
messages are received.

34
Communication protocol manual
1MRK 511 375-UEN A Section 7
Logical node data model

Section 7 Logical node data model

GUID-EFBB8957-ABA9-4B25-B1CC-630B892A3FC7 v3
The data model used by IEC 61850 is based on logical nodes containing a set of data objects.
The data model is defined in the standards.

• IEC 61850-7-4 Compatible logical node classes and data classes


• IEC 61850-7-3 Common data classes

The standard describes only classes of logical nodes and data objects on one side and
common data classes for the data object attributes. Also here it is given has the elements in
these classes are defined as:

• Mandatory (M)
• Optional (O)
• Conditional optional (Cxxx)
• In addition, the IEC 61850 states rules for adding vendor-specific definitions to the
standard, in order to cope with extra functionality.

The possible description of the data model according to the standard allows to adapt a logical
node of a LN class to that what the product is supporting or using for this LN. This definition
of what parts of a class is used in the actual product and possible addition is called a type,
according to IEC 61850-6. There are LN types based upon LN classes. The LN type attributes
are called Data Objects (or DATA) and are in of DO types, base upon respective CDC class. This
allows all partners in the IEC 61850 project who need this LN to understand the LN in all details
for the communication part.

The IEC 61850 standard does not describe the functionality and way of operation. Each
supplier has to describe this separately. ABB has described their function blocks that
represent a logical node and all other function blocks in the technical manuals. This chapter in
the communication protocol manual has two purposes:

• Describe the Logical Node types and their data object attribute types.
• Make the link to the description of the function block.

7.1 Common data objects in each logical node GUID-8400E43A-6199-4539-BB74-CAC865C85508 v3

The IEC 61850 standard describes in part 7-5, a Common Logical Node. The data objects
contained in that LN are both mandatory and optional. The mandatory data objects have to be
included in each LN. This clause describes the general handling of the data objects in the IEDs.

The mandatory data objects as defined in IEC 61850-7-4 as part of the Common Logical Node
are Mode, Behavior, Health and NamePlate.

Mode

The operation modes ON (enabled) and BLOCKED are supported remotely by a command or
locally from the LHMI of the IED.

If the setting “RemoteModControl” is set to “Off” (default), all remote writes to


Mod will be rejected.

Behaviour

35
Communication protocol manual
Section 7 1MRK 511 375-UEN A
Logical node data model

The operational mode as given by the Mode control is shown in the data object Beh according
to priority rules described for Beh in clause 6 of IEC 61850-7-4.

The Beh shows the actual state of the function depending on the hierarchy described in clause
6 of IEC 61850-7-4.

It is possible that the behavior is influenced also by other sources independent from the Mod,
for example Insertion of the test handle, loss of SV, IED configuration tool (PCM600), or LHMI.

In case the setting “operation” of a function is set to Off from the LHMI or PCM600, the Beh
will be set to Off independent of the value of the Mod.

The state Off can be set from the LHMI or the PCM600 for the functions having the setting
“operation”.

The TEST and the TEST/BLOCKED mode can be operated locally from the LHMI.

Health

Health will reflect the current status of the IED HW and configuration. Possible values are: OK,
Warning, and Alarm.

Health indicates OK, Warning, or Alarm, depending on the IED status.

NamePlt

The name of the logical node and its relation to namespace definition are shown in the data
object NamePlt as specified for the SCL structure.

7.2 Logical nodes for control

7.2.1 Bay control CBAY

7.2.1.1 Bay control QCBAY GUID-2BD411B4-2371-4B97-8D8D-DB632B15BC85 v1

PID-4086-LOGICALNODEDATA v3

LN type LN prefix LN class Function block name


QCBAY (revision 1) Q CBAY QCBAY

Table 2: QCBAY Logical node data


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter for 61850
Oper.origin.orCat CO - Mod Cmd Mode parameter for 61850
Oper.origin.orIdent CO - Mod Cmd Mode parameter for 61850
Oper.ctlNum CO - Mod Cmd Mode parameter for 61850
Oper.T CO - Mod Cmd Mode parameter for 61850
Oper.Test CO - Mod Cmd Mode parameter for 61850
Oper.Check CO - Mod Cmd Mode parameter for 61850
stVal ST - - Mon Mode status value parameter
for 61850

Table continues on next page

36
Communication protocol manual
1MRK 511 375-UEN A Section 7
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
Mod a_dINC q ST - - Mon Quality: Mode status value
parameter for 61850

t ST - - Mon Timestamp: Mode status value


parameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
LocSwPos v1_dINS stVal ST - - Mon Position of the Local/Remote
switch
q ST - - Mon Quality: Position of the Local/
Remote switch
t ST - - Mon Timestamp: Position of the
Local/Remote switch
SrcOpPrm v1_dINS stVal ST - PSTO Mon Value for the operator place
allocation
q ST - PSTO Mon Quality: Value for the operator
place allocation
t ST - PSTO Mon Timestamp: Value for the
operator place allocation
BlkCmd v1_dSPC Oper.ctlVal CO - - Cmd Special block command value
used for blockCommand
Oper.origin.orCat CO - - Cmd Special block command value
used for blockCommand
Oper.origin.orIdent CO - - Cmd Special block command value
used for blockCommand
Oper.ctlNum CO - - Cmd Special block command value
used for blockCommand
Oper.T CO - - Cmd Special block command value
used for blockCommand
Oper.Test CO - - Cmd Special block command value
used for blockCommand
Oper.Check CO - - Cmd Special block command value
used for blockCommand
stVal ST - CMD_BLKD Mon Function is blocked for
commands
q ST - CMD_BLKD Mon Quality: Function is blocked for
commands
t ST - CMD_BLKD Mon Timestamp: Function is
blocked for commands
BlkUpd v1_dSPC Oper.ctlVal CO - - Cmd Special block command value
used for blockUpdate
Oper.origin.orCat CO - - Cmd Special block command value
used for blockUpdate
Oper.origin.orIdent CO - - Cmd Special block command value
used for blockUpdate
Oper.ctlNum CO - - Cmd Special block command value
used for blockUpdate
Oper.T CO - - Cmd Special block command value
used for blockUpdate

Table continues on next page

37
Communication protocol manual
Section 7 1MRK 511 375-UEN A
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
BlkUpd v1_dSPC Oper.Test CO - - Cmd Special block command value
used for blockUpdate

Oper.Check CO - - Cmd Special block command value


used for blockUpdate
stVal ST - UPD_BLKD Mon Update of position is blocked
q ST - UPD_BLKD Mon Quality: Update of position is
blocked
t ST - UPD_BLKD Mon Timestamp: Update of position
is blocked
BlkMeas v1_dSPS stVal ST - - Mon Update of measurand is
blocked
q ST - - Mon Quality: Update of measurand
is blocked
t ST - - Mon Timestamp: Update of
measurand is blocked
Loc v1_dSPS stVal ST - LOC Mon Local operation allowed
q ST - LOC Mon Quality: Local operation
allowed
t ST - LOC Mon Timestamp: Local operation
allowed
Rem v1_dSPS stVal ST - REM Mon Remote operation allowed
q ST - REM Mon Quality: Remote operation
allowed
t ST - REM Mon Timestamp: Remote operation
allowed

7.2.2 Switch controller CSWI

7.2.2.1 Switch controller SCSWI GUID-4F40A4BA-6781-41BF-8389-D8EFD791D005 v1

PID-3955-LOGICALNODEDATA v1

LN type LN prefix LN class Function block name


SCSWI (revision 1) S CSWI SCSWI

Table 3: SCSWI Logical node data


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Pos a_dDPC Cancel.ctlVal CO - - Cmd Command parameter for
IEC61850
Cancel.origin.orCat CO - - Cmd Command parameter for
IEC61850
Oper.ctlVal CO - - Cmd Command parameter for
IEC61850
Oper.origin.orCat CO - - Cmd Command parameter for
IEC61850
SBOw.ctlVal CO - - Cmd Command parameter for
IEC61850

Table continues on next page

38
Communication protocol manual
1MRK 511 375-UEN A Section 7
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
Pos a_dDPC SBOw.origin.orCat CO - - Cmd Command parameter for
IEC61850

SBOw.origin.orIdent CO - - Cmd Command parameter for


IEC61850
Oper.origin.orIdent CO - - Cmd Command parameter for
IEC61850
Cancel.origin.orIdent CO - - Cmd Command parameter for
IEC61850
Cancel.ctlNum CO - - Cmd Command parameter for
IEC61850
Oper.ctlNum CO - - Cmd Command parameter for
IEC61850
SBOw.ctlNum CO - - Cmd Command parameter for
IEC61850
SBOw.T CO - - Cmd Command parameter for
IEC61850
Cancel.T CO - - Cmd Command parameter for
IEC61850
Oper.T CO - - Cmd Command parameter for
IEC61850
Oper.Test CO - - Cmd Command parameter for
IEC61850
Cancel.Test CO - - Cmd Command parameter for
IEC61850
SBOw.Test CO - - Cmd Command parameter for
IEC61850
Oper.Check CO - - Cmd Command parameter for
IEC61850
SBOw.Check CO - - Cmd Command parameter for
IEC61850
stVal ST - POSITION Mon Position indication
q ST - POSITION Mon Quality: Position indication
t ST - POSITION Mon Timestamp: Position indication
stSeld ST - SELECTED Mon Select conditions are fulfilled
subEna SV - - - Substitute enable
subVal SV - - - Substituted double position
value
ctlModel CF - CtlModel - Specifies control model type
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter for 61850
Oper.origin.orCat CO - Mod Cmd Mode parameter for 61850
Oper.origin.orIdent CO - Mod Cmd Mode parameter for 61850
Oper.ctlNum CO - Mod Cmd Mode parameter for 61850
Oper.T CO - Mod Cmd Mode parameter for 61850
Oper.Test CO - Mod Cmd Mode parameter for 61850
Oper.Check CO - Mod Cmd Mode parameter for 61850
stVal ST - - Mon Mode status value parameter
for 61850

Table continues on next page

39
Communication protocol manual
Section 7 1MRK 511 375-UEN A
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
Mod a_dINC q ST - - Mon Quality: Mode status value
parameter for 61850

t ST - - Mon Timestamp: Mode status value


parameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
OpCls b_dACT general ST T EXE_CL Mon Execute command for close
direction
q ST T EXE_CL Mon Quality: Execute command for
close direction
t ST T EXE_CL Mon Timestamp: Execute command
for close direction
OpOpn b_dACT general ST T EXE_OP Mon Execute command for open
direction
q ST T EXE_OP Mon Quality: Execute command for
open direction
t ST T EXE_OP Mon Timestamp: Execute command
for open direction
BlkCmd v1_dSPC Oper.ctlVal CO - - Cmd Special block command value
Oper.origin.orCat CO - - Cmd Special block command value
Oper.origin.orIdent CO - - Cmd Special block command value
Oper.ctlNum CO - - Cmd Special block command value
Oper.T CO - - Cmd Special block command value
Oper.Test CO - - Cmd Special block command value
Oper.Check CO - - Cmd Special block command value
stVal ST - CMD_BLK Mon Commands are blocked
q ST - CMD_BLK Mon Quality: Commands are blocked
t ST - CMD_BLK Mon Timestamp: Commands are
blocked

7.3 Logical nodes for conversion functions

7.3.1 Integer to Boolean converter FCVB

7.3.1.1 Integer to Boolean 16 conversion with logic node representation ITBGAPC SEMOD158419-1 v3

PID-3627-LOGICALNODEDATA v3

LN type LN prefix LN class Function block name


IB16FCVB (revision 0) IB16 FCVB ITBGAPC

40
Communication protocol manual
1MRK 511 375-UEN A Section 7
Logical node data model

Table 4: ITBGAPC Logical node data


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter
Oper.origin.orCat CO - Mod Cmd Mode parameter
Oper.origin.orIdent CO - Mod Cmd Mode parameter
Oper.ctlNum CO - Mod Cmd Mode parameter
Oper.T CO - Mod Cmd Mode parameter
Oper.Test CO - Mod Cmd Mode parameter
Oper.Check CO - Mod Cmd Mode parameter
stVal ST - - Mon Mode status parameter for
61850
q ST - - Mon Quality: Mode status parameter
for 61850
t ST - - Mon Timestamp: Mode status
parameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
ISCSO b_dINC Oper.ctlVal CO - - Cmd Command parameter for
IEC61850
Oper.origin.orCat CO - - Cmd Command parameter for
IEC61850
Oper.origin.orIdent CO - - Cmd Command parameter for
IEC61850
Oper.ctlNum CO - - Cmd Command parameter for
IEC61850
Oper.T CO - - Cmd Command parameter for
IEC61850
Oper.Test CO - - Cmd Command parameter for
IEC61850
Oper.Check CO - - Cmd Command parameter for
IEC61850
stVal ST - - Mon Integer to be converted to bit
pattern OUT1 to OUT16
q ST - - Mon Quality: Integer to be converted
to bit pattern OUT1 to OUT16
t ST - - Mon Timestamp: Integer to be
converted to bit pattern OUT1
to OUT16
ctlModel CF - - - Used by CH

7.3.2 Boolean to integer converter FCVI

7.3.2.1 Boolean to integer conversion with logical node representation, 16 bit


BTIGAPC SEMOD175753-1 v4

41
Communication protocol manual
Section 7 1MRK 511 375-UEN A
Logical node data model

PID-6944-LOGICALNODEDATA v2

LN type LN prefix LN class Function block name


B16IFCVI (revision 0) B16I FCVI BTIGAPC

Table 5: BTIGAPC Logical node data


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter
Oper.origin.orCat CO - Mod Cmd Mode parameter
Oper.origin.orIdent CO - Mod Cmd Mode parameter
Oper.ctlNum CO - Mod Cmd Mode parameter
Oper.T CO - Mod Cmd Mode parameter
Oper.Test CO - Mod Cmd Mode parameter
Oper.Check CO - Mod Cmd Mode parameter
stVal ST - - Mon Mode status parameter for
61850
q ST - - Mon Quality: Mode status parameter
for 61850
t ST - - Mon Timestamp: Mode status
parameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter
q ST - Beh Mon Quality: Behaviour parameter
t ST - Beh Mon Timestamp: Behaviour
parameter
OutInt b_dINS stVal ST - OUT Mon Output value
q ST - OUT Mon Quality: Output value
t ST - OUT Mon Timestamp: Output value

7.4 Logical nodes for protection functions

7.4.1 Protection trip conditioning PTRC

7.4.1.1 Logic for group alarm ALMCALH


PID-6510-LOGICALNODEDATA v1

LN type LN prefix LN class Function block name


ALMCALH (revision 1) ALM CALH ALMCALH

Table 6: ALMCALH Logical node data


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter
Oper.origin.orCat CO - Mod Cmd Mode parameter
Oper.origin.orIdent CO - Mod Cmd Mode parameter

Table continues on next page

42
Communication protocol manual
1MRK 511 375-UEN A Section 7
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
Mod a_dINC Oper.ctlNum CO - Mod Cmd Mode parameter

Oper.T CO - Mod Cmd Mode parameter


Oper.Test CO - Mod Cmd Mode parameter
Oper.Check CO - Mod Cmd Mode parameter
stVal ST - - Mon Mode status parameter for
61850
q ST - - Mon Quality: Mode status parameter
for 61850
t ST - - Mon Timestamp: Mode status
parameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter
q ST - Beh Mon Quality: Behaviour parameter
t ST - Beh Mon Timestamp: Behaviour
parameter
GrAlm a_dSPS stVal ST - ALARM Mon OR function betweeen inputs 1
to 16
q ST - ALARM Mon Quality: OR function betweeen
inputs 1 to 16
t ST - ALARM Mon Timestamp: OR function
betweeen inputs 1 to 16

7.4.1.2 Logic for group indication INDCALH


PID-6511-LOGICALNODEDATA v1

LN type LN prefix LN class Function block name


INDCALH (revision 1) IND CALH INDCALH

Table 7: INDCALH Logical node data


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter
Oper.origin.orCat CO - Mod Cmd Mode parameter
Oper.origin.orIdent CO - Mod Cmd Mode parameter
Oper.ctlNum CO - Mod Cmd Mode parameter
Oper.T CO - Mod Cmd Mode parameter
Oper.Test CO - Mod Cmd Mode parameter
Oper.Check CO - Mod Cmd Mode parameter
stVal ST - - Mon Mode status parameter for
61850
q ST - - Mon Quality: Mode status parameter
for 61850
t ST - - Mon Timestamp: Mode status
parameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter
q ST - Beh Mon Quality: Behaviour parameter

Table continues on next page

43
Communication protocol manual
Section 7 1MRK 511 375-UEN A
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
Beh a_dINS t ST - Beh Mon Timestamp: Behaviour
parameter

GrAlm a_dSPS stVal ST - IND Mon OR function betweeen inputs 1


to 16
q ST - IND Mon Quality: OR function betweeen
inputs 1 to 16
t ST - IND Mon Timestamp: OR function
betweeen inputs 1 to 16

7.4.1.3 Tripping logic common 3-phase output SMPPTRC GUID-B56D86A1-47D9-4B45-A90B-B622C3AE5D2D v2

PID-6907-LOGICALNODEDATA v2

LN type LN prefix LN class Function block name


SMPPTRC (revision 3) SMP PTRC SMPPTRC

Table 8: SMPPTRC Logical node data


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Str a_dACD general ST - START Mon Common start signal
dirGeneral ST - - Mon Common direction signal
phsA ST - STL1 Mon Start signal from phase L1
dirPhsA ST - - Mon Direction signal from phase L1
phsB ST - STL2 Mon Start signal from phase L2
dirPhsB ST - - Mon Direction signal from phase L2
phsC ST - STL3 Mon Start signal from phase L3
dirPhsC ST - - Mon Direction signal from phase L3
q ST - START Mon Quality: Common start signal
t ST - START Mon Timestamp: Common start
signal
Op a_dACT general ST - TRIP Mon General trip output signal
phsA ST - TRL1 Mon Trip signal from phase L1
phsB ST - TRL2 Mon Trip signal from phase L2
phsC ST - TRL3 Mon Trip signal from phase L3
q ST - TRIP Mon Quality: General trip output
signal
t ST - TRIP Mon Timestamp: General trip output
signal
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter
Oper.origin.orCat CO - Mod Cmd Mode parameter
Oper.origin.orIdent CO - Mod Cmd Mode parameter
Oper.ctlNum CO - Mod Cmd Mode parameter
Oper.T CO - Mod Cmd Mode parameter
Oper.Test CO - Mod Cmd Mode parameter

Table continues on next page

44
Communication protocol manual
1MRK 511 375-UEN A Section 7
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
Mod a_dINC Oper.Check CO - Mod Cmd Mode parameter

stVal ST - - Mon Mode status parameter for


61850
q ST - - Mon Quality: Mode status parameter
for 61850
t ST - - Mon Timestamp: Mode status
parameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
LORs v1_dSPC Oper.ctlVal CO - - Cmd Command parameter for
IEC61850
Oper.origin.orCat CO - - Cmd Command parameter for
IEC61850
Oper.origin.orIdent CO - - Cmd Command parameter for
IEC61850
Oper.ctlNum CO - - Cmd Command parameter for
IEC61850
Oper.T CO - - Cmd Command parameter for
IEC61850
Oper.Test CO - - Cmd Command parameter for
IEC61850
Oper.Check CO - - Cmd Command parameter for
IEC61850
SPTr v1_dSPS stVal ST - TR1P Mon Tripping single-pole
q ST - TR1P Mon Quality: Tripping single-pole
t ST - TR1P Mon Timestamp: Tripping single-
pole
TwoPTr v1_dSPS stVal ST - TR2P Mon Tripping two-pole
q ST - TR2P Mon Quality: Tripping two-pole
t ST - TR2P Mon Timestamp: Tripping two-pole
TPTr v1_dSPS stVal ST - TR3P Mon Tripping three-pole
q ST - TR3P Mon Quality: Tripping three-pole
t ST - TR3P Mon Timestamp: Tripping three-
pole
ClsLO v1_dSPS stVal ST - CLLKOUT Mon Circuit breaker lockout output
(set until reset)
q ST - CLLKOUT Mon Quality: Circuit breaker lockout
output (set until reset)
t ST - CLLKOUT Mon Timestamp: Circuit breaker
lockout output (set until reset)

7.4.1.4 Logic for group warning WRNCALH


PID-6512-LOGICALNODEDATA v1

LN type LN prefix LN class Function block name


WRNCALH (revision 1) WRN CALH WRNCALH

45
Communication protocol manual
Section 7 1MRK 511 375-UEN A
Logical node data model

Table 9: WRNCALH Logical node data


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter
Oper.origin.orCat CO - Mod Cmd Mode parameter
Oper.origin.orIdent CO - Mod Cmd Mode parameter
Oper.ctlNum CO - Mod Cmd Mode parameter
Oper.T CO - Mod Cmd Mode parameter
Oper.Test CO - Mod Cmd Mode parameter
Oper.Check CO - Mod Cmd Mode parameter
stVal ST - - Mon Mode status parameter for
61850
q ST - - Mon Quality: Mode status parameter
for 61850
t ST - - Mon Timestamp: Mode status
parameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter
q ST - Beh Mon Quality: Behaviour parameter
t ST - Beh Mon Timestamp: Behaviour
parameter
GrAlm a_dSPS stVal ST - WARNING Mon OR function betweeen inputs 1
to 16
q ST - WARNING Mon Quality: OR function betweeen
inputs 1 to 16
t ST - WARNING Mon Timestamp: OR function
betweeen inputs 1 to 16

7.4.2 Multipurpose analog protection GAPC

7.4.2.1 General currrent and voltage protection CVGAPC


PID-3857-LOGICALNODEDATA v1

LN type LN prefix LN class Function block name


GF2LLN0 instance 1 (revision 0) - LLN0 CVGAPC
GF2MMXN instance 1 (revision 3) GF2 MMXN CVGAPC
GF2PHAR instance 1 (revision 2) GF2 PHAR CVGAPC
GF2PTOV instance 1 (revision 2) GF2 PTOV CVGAPC
GF2PTOV instance 2 (revision 2) GF2 PTOV CVGAPC
GF2PTUC instance 1 (revision 2) GF2 PTUC CVGAPC
GF2PTUC instance 2 (revision 2) GF2 PTUC CVGAPC
GF2PTUV instance 1 (revision 2) GF2 PTUV CVGAPC
GF2PTUV instance 2 (revision 2) GF2 PTUV CVGAPC
GF2PVOC instance 1 (revision 2) GF2 PVOC CVGAPC
GF2PVOC instance 2 (revision 2) GF2 PVOC CVGAPC
PH1PTRC instance 1 (revision 3) PH1 PTRC CVGAPC

46
Communication protocol manual
1MRK 511 375-UEN A Section 7
Logical node data model

Table 10: CVGAPC Logical node data (instance 1)


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Mod aINC Oper.ctlVal CO - Mod Cmd Mode parameter
Oper.origin.orCat CO - Mod Cmd Mode parameter
Oper.origin.orIdent CO - Mod Cmd Mode parameter
Oper.ctlNum CO - Mod Cmd Mode parameter
Oper.T CO - Mod Cmd Mode parameter
Oper.Test CO - Mod Cmd Mode parameter
Oper.Check CO - Mod Cmd Mode parameter
stVal ST - - Mon Mode status parameter for
61850
q ST - - Mon Quality: Mode status parameter
for 61850
t ST - - Mon Timestamp: Mode status
parameter for 61850
Beh aINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
IvdCrv v1SPS stVal ST - - Mon Error signal from overcurrent
functions
q ST - - Mon Quality: Error signal from
overcurrent functions
t ST - - Mon Timestamp: Error signal from
overcurrent functions
UnVBehMem v1SPS stVal ST - UDIRLOW Mon Low voltage for directional
polarization
q ST - UDIRLOW Mon Quality: Low voltage for
directional polarization
t ST - UDIRLOW Mon Timestamp: Low voltage for
directional polarization

Table 11: CVGAPC Logical node data (instance 1)


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Beh aINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
Amp bMV mag.f MX - CURRENT Mon Measured current value
q MX - CURRENT Mon Quality: Measured current value
t MX - CURRENT Mon Timestamp: Measured current
value
Vol bMV mag.f MX - VOLTAGE Mon Measured voltage value
q MX - VOLTAGE Mon Quality: Measured voltage value

Table continues on next page

47
Communication protocol manual
Section 7 1MRK 511 375-UEN A
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
Vol bMV t MX - VOLTAGE Mon Timestamp: Measured voltage
value

Mod cINC stVal ST - - Mon Mode status parameter for


61850
q ST - - Mon Quality: Mode status parameter
for 61850
t ST - - Mon Timestamp: Mode status
parameter for 61850
AmpPwrFact v2MV mag.f MX - ICOSFI Mon Measured current multiplied
with cos (Phi)
q MX - ICOSFI Mon Quality: Measured current
multiplied with cos (Phi)
t MX - ICOSFI Mon Timestamp: Measured current
multiplied with cos (Phi)
VolAmpAng v2MV mag.f MX - UIANGLE Mon Angle between voltage and
current
q MX - UIANGLE Mon Quality: Angle between voltage
and current
t MX - UIANGLE Mon Timestamp: Angle between
voltage and current

Table 12: CVGAPC Logical node data (instance 1)


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
Str b_dACD general ST - BLK2ND Mon Block from second harmonic
detection
q ST - BLK2ND Mon Quality: Block from second
harmonic detection
t ST - BLK2ND Mon Timestamp: Block from second
harmonic detection
Mod c_dINC stVal ST - - Mon Mode status parameter for
61850
q ST - - Mon Quality: Mode status parameter
for 61850
t ST - - Mon Timestamp: Mode status
parameter for 61850

48
Communication protocol manual
1MRK 511 375-UEN A Section 7
Logical node data model

Table 13: CVGAPC Logical node data (instance 1)


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
Str b_dACD general ST - STOV1 Mon Start signal from overvoltage
function OV1
q ST - STOV1 Mon Quality: Start signal from
overvoltage function OV1
t ST - STOV1 Mon Timestamp: Start signal from
overvoltage function OV1
Op b_dACT general ST T TROV1 Mon Trip signal from overvoltage
function OV1
q ST T TROV1 Mon Quality: Trip signal from
overvoltage function OV1
t ST T TROV1 Mon Timestamp: Trip signal from
overvoltage function OV1
Mod c_dINC stVal ST - - Mon Mode status parameter for
61850
q ST - - Mon Quality: Mode status parameter
for 61850
t ST - - Mon Timestamp: Mode status
parameter for 61850

Table 14: CVGAPC Logical node data (instance 2)


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
Str b_dACD general ST - STOV2 Mon Start signal from overvoltage
function OV2
q ST - STOV2 Mon Quality: Start signal from
overvoltage function OV2
t ST - STOV2 Mon Timestamp: Start signal from
overvoltage function OV2
Op b_dACT general ST T TROV2 Mon Trip signal from overvoltage
function OV2
q ST T TROV2 Mon Quality: Trip signal from
overvoltage function OV2
t ST T TROV2 Mon Timestamp: Trip signal from
overvoltage function OV2
Mod c_dINC stVal ST - - Mon Mode status parameter for
61850
q ST - - Mon Quality: Mode status parameter
for 61850
t ST - - Mon Timestamp: Mode status
parameter for 61850

49
Communication protocol manual
Section 7 1MRK 511 375-UEN A
Logical node data model

Table 15: CVGAPC Logical node data (instance 2)


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
Str b_dACD general ST - STUC2 Mon Start signal from undercurrent
function UC2
q ST - STUC2 Mon Quality: Start signal from
undercurrent function UC2
t ST - STUC2 Mon Timestamp: Start signal from
undercurrent function UC2
Op b_dACT general ST T TRUC2 Mon Trip signal from undercurrent
function UC2
q ST T TRUC2 Mon Quality: Trip signal from
undercurrent function UC2
t ST T TRUC2 Mon Timestamp: Trip signal from
undercurrent function UC2
Mod c_dINC stVal ST - - Mon Mode status parameter for
61850
q ST - - Mon Quality: Mode status parameter
for 61850
t ST - - Mon Timestamp: Mode status
parameter for 61850

Table 16: CVGAPC Logical node data (instance 1)


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
Str b_dACD general ST - STUC1 Mon Start signal from undercurrent
function UC1
q ST - STUC1 Mon Quality: Start signal from
undercurrent function UC1
t ST - STUC1 Mon Timestamp: Start signal from
undercurrent function UC1
Op b_dACT general ST T TRUC1 Mon Trip signal from undercurrent
function UC1
q ST T TRUC1 Mon Quality: Trip signal from
undercurrent function UC1
t ST T TRUC1 Mon Timestamp: Trip signal from
undercurrent function UC1
Mod c_dINC stVal ST - - Mon Mode status parameter for
61850
q ST - - Mon Quality: Mode status parameter
for 61850
t ST - - Mon Timestamp: Mode status
parameter for 61850

50
Communication protocol manual
1MRK 511 375-UEN A Section 7
Logical node data model

Table 17: CVGAPC Logical node data (instance 1)


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
Str b_dACD general ST - STUV1 Mon Start signal from undervoltage
function UV1
q ST - STUV1 Mon Quality: Start signal from
undervoltage function UV1
t ST - STUV1 Mon Timestamp: Start signal from
undervoltage function UV1
Op b_dACT general ST T TRUV1 Mon Trip signal from undervoltage
function UV1
q ST T TRUV1 Mon Quality: Trip signal from
undervoltage function UV1
t ST T TRUV1 Mon Timestamp: Trip signal from
undervoltage function UV1
Mod c_dINC stVal ST - - Mon Mode status parameter for
61850
q ST - - Mon Quality: Mode status parameter
for 61850
t ST - - Mon Timestamp: Mode status
parameter for 61850

Table 18: CVGAPC Logical node data (instance 2)


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
Str b_dACD general ST - STUV2 Mon Start signal from undervoltage
function UV2
q ST - STUV2 Mon Quality: Start signal from
undervoltage function UV2
t ST - STUV2 Mon Timestamp: Start signal from
undervoltage function UV2
Op b_dACT general ST T TRUV2 Mon Trip signal from undervoltage
function UV2
q ST T TRUV2 Mon Quality: Trip signal from
undervoltage function UV2
t ST T TRUV2 Mon Timestamp: Trip signal from
undervoltage function UV2
Mod c_dINC stVal ST - - Mon Mode status parameter for
61850
q ST - - Mon Quality: Mode status parameter
for 61850
t ST - - Mon Timestamp: Mode status
parameter for 61850

51
Communication protocol manual
Section 7 1MRK 511 375-UEN A
Logical node data model

Table 19: CVGAPC Logical node data (instance 2)


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
Str b_dACD general ST - STOC2 Mon Start signal from overcurrent
function OC2
dirGeneral ST - DIROC2 Mon Directional mode of OC2
(nondir, forward,reverse)
q ST - STOC2 Mon Quality: Start signal from
overcurrent function OC2
t ST - STOC2 Mon Timestamp: Start signal from
overcurrent function OC2
Op b_dACT general ST T TROC2 Mon Trip signal from overcurrent
function OC2
q ST T TROC2 Mon Quality: Trip signal from
overcurrent function OC2
t ST T TROC2 Mon Timestamp: Trip signal from
overcurrent function OC2
Mod c_dINC stVal ST - - Mon Mode status parameter for
61850
q ST - - Mon Quality: Mode status parameter
for 61850
t ST - - Mon Timestamp: Mode status
parameter for 61850
IvdCrv v1_dSPS stVal ST - - Mon Error signal from overcurrent
function OC2
q ST - - Mon Quality: Error signal from
overcurrent function OC2
t ST - - Mon Timestamp: Error signal from
overcurrent function OC2

Table 20: CVGAPC Logical node data (instance 1)


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
Str b_dACD general ST - STOC1 Mon Start signal from overcurrent
function OC1
dirGeneral ST - DIROC1 Mon Directional mode of OC1
(nondir, forward,reverse)
q ST - STOC1 Mon Quality: Start signal from
overcurrent function OC1
t ST - STOC1 Mon Timestamp: Start signal from
overcurrent function OC1
Table continues on next page

52
Communication protocol manual
1MRK 511 375-UEN A Section 7
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
Op b_dACT general ST T TROC1 Mon Trip signal from overcurrent
function OC1
q ST T TROC1 Mon Quality: Trip signal from
overcurrent function OC1
t ST T TROC1 Mon Timestamp: Trip signal from
overcurrent function OC1
Mod c_dINC stVal ST - - Mon Mode status parameter for
61850
q ST - - Mon Quality: Mode status parameter
for 61850
t ST - - Mon Timestamp: Mode status
parameter for 61850
IvdCrv v1_dSPS stVal ST - - Mon Error signal from overcurrent
function OC1
q ST - - Mon Quality: Error signal from
overcurrent function OC1
t ST - - Mon Timestamp: Error signal from
overcurrent function OC1

Table 21: CVGAPC Logical node data (instance 1)


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
Str b_dACD general ST - START Mon General start signal
q ST - START Mon Quality: General start signal
t ST - START Mon Timestamp: General start
signal
Op b_dACT general ST - TRIP Mon General trip signal
q ST - TRIP Mon Quality: General trip signal
t ST - TRIP Mon Timestamp: General trip signal
Mod c_dINC stVal ST - - Mon Mode status parameter for
61850
q ST - - Mon Quality: Mode status parameter
for 61850
t ST - - Mon Timestamp: Mode status
parameter for 61850

53
Communication protocol manual
Section 7 1MRK 511 375-UEN A
Logical node data model

7.5 System logical nodes

7.5.1 Generic security application component

7.5.1.1 Generic security application component AGSAL


PID-7016-LOGICALNODEDATA v2

LN type LN prefix LN class Function block name


AGSAL instance 1 (revision 2) A GSAL AGSAL
SECLLN0 instance 1 (revision 1) - LLN0 AGSAL

Table 22: AGSAL Logical node data (instance 1)


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
AcsCtlFail a_dSEC cnt ST - - Mon Mapping tag
t ST - - Mon Timestamp: Mapping tag
AuthFail a_dSEC cnt ST - - Mon Mapping tag
t ST - - Mon Timestamp: Mapping tag
Ina a_dSEC cnt ST - - Mon Mapping tag
t ST - - Mon Timestamp: Mapping tag
SvcViol a_dSEC cnt ST - - Mon Mapping tag
t ST - - Mon Timestamp: Mapping tag
Mod c_dINC stVal ST - - Mon Mode status value parameter
for 61850
q ST - - Mon Quality: Mode status value
parameter for 61850
t ST - - Mon Timestamp: Mode status value
parameter for 61850
OpCntRs f_dINC Oper.ctlVal CO - - Cmd Mapping tag
Oper.origin.orCat CO - - Cmd Mapping tag
Oper.origin.orIdent CO - - Cmd Mapping tag
Oper.ctlNum CO - - Cmd Mapping tag
Oper.T CO - - Cmd Mapping tag
Oper.Test CO - - Cmd Mapping tag
Oper.Check CO - - Cmd Mapping tag
stVal ST - - Mon Mapping tag
q ST - - Mon Quality: Mapping tag
t ST - - Mon Timestamp: Mapping tag
NumCntRs o_dINS stVal ST - - Mon Mapping tag
q ST - - Mon Quality: Mapping tag
t ST - - Mon Timestamp: Mapping tag

54
Communication protocol manual
1MRK 511 375-UEN A Section 7
Logical node data model

Table 23: AGSAL Logical node data (instance 1)


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
Mod c_dINC stVal ST - - Mon Mode status value parameter
for 61850
q ST - - Mon Quality: Mode status value
parameter for 61850
t ST - - Mon Timestamp: Mode status value
parameter for 61850

7.5.2 Physical device information LPHD


PID-4023-LOGICALNODEDATA v3

LN type LN prefix LN class Function block name


LPHD (revision 6) - LPHD LPHD

Table 24: LPHD Logical node data


DO name DO type DA name FC T Signal Mon/ Description
Cmd
PhyNam b_dDPL swRev DC - - - Firmware version
serNum DC - - - Serial Number
model DC - - - IEDModel for IEC61850
PhyHealth n_dINS stVal ST - PhyHealth Mon Physical health
q ST - PhyHealth Mon Quality: Physical health
t ST - PhyHealth Mon Timestamp: Physical health

7.5.3 Logical node zero LLNO


PID-5185-LOGICALNODEDATA v1

LN type LN prefix LN class Function block name


LLN0 (revision 2) - LLN0 LD0LLN0

Table 25: LD0LLN0 Logical node data


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter for 61850
Oper.origin.orCat CO - Mod Cmd Mode parameter for 61850
Oper.origin.orIdent CO - Mod Cmd Mode parameter for 61850
Oper.ctlNum CO - Mod Cmd Mode parameter for 61850
Oper.T CO - Mod Cmd Mode parameter for 61850

Table continues on next page

55
Communication protocol manual
Section 7 1MRK 511 375-UEN A
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
Mod a_dINC Oper.Test CO - Mod Cmd Mode parameter for 61850

Oper.Check CO - Mod Cmd Mode parameter for 61850


stVal ST - - Mon Mode status value parameter
for 61850
q ST - - Mon Quality: Mode status value
parameter for 61850
t ST - - Mon Timestamp: Mode status value
parameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
NamPlt ln0_dLPL swRev DC - - - Firmware version
Health n_dINS stVal ST - - Mon Physical health
q ST - - Mon Quality: Physical health
t ST - - Mon Timestamp: Physical health

7.5.4 Access point diagnostic for redundant Ethernet ports


RCHLCCH
PID-6819-LOGICALNODEDATA v2

LN type LN prefix LN class Function block name


RCHLCCH (revision 1) RCH LCCH RCHLCCH

Table 26: RCHLCCH Logical node data


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter for 61850
Oper.origin.orCat CO - Mod Cmd Mode parameter for 61850
Oper.origin.orIdent CO - Mod Cmd Mode parameter for 61850
Oper.ctlNum CO - Mod Cmd Mode parameter for 61850
Oper.T CO - Mod Cmd Mode parameter for 61850
Oper.Test CO - Mod Cmd Mode parameter for 61850
Oper.Check CO - Mod Cmd Mode parameter for 61850
stVal ST - - Mon Mode status value parameter
for 61850
q ST - - Mon Quality: Mode status value
parameter for 61850
t ST - - Mon Timestamp: Mode status value
parameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850

Table continues on next page

56
Communication protocol manual
1MRK 511 375-UEN A Section 7
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
Beh a_dINS t ST - Beh Mon Timestamp: Behaviour
parameter for 61850

ChLiv a_dSPS stVal ST - LinkAUp Mon Channel A link status


q ST - LinkAUp Mon Quality: Channel A link status
t ST - LinkAUp Mon Timestamp: Channel A link
status
RedChLiv a_dSPS stVal ST - LinkBUp Mon Channel B link status
q ST - LinkBUp Mon Quality: Channel B link status
t ST - LinkBUp Mon Timestamp: Channel B link
status
FerCh b_dINS stVal ST - ErrorRateA Mon Channel A redundancy error
rate
q ST - ErrorRateA Mon Quality: Channel A redundancy
error rate
t ST - ErrorRateA Mon Timestamp: Channel A
redundancy error rate
RedFerCh b_dINS stVal ST - ErrorRateB Mon Channel B redundancy error
rate
q ST - ErrorRateB Mon Quality: Channel B redundancy
error rate
t ST - ErrorRateB Mon Timestamp: Channel B
redundancy error rate

7.5.5 Access point diagnostic for non-redundant Ethernet port


SCHLCCH
PID-6818-LOGICALNODEDATA v2

LN type LN prefix LN class Function block name


SCHLCCH (revision 1) SCH LCCH SCHLCCH

Table 27: SCHLCCH Logical node data


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter for 61850
Oper.origin.orCat CO - Mod Cmd Mode parameter for 61850
Oper.origin.orIdent CO - Mod Cmd Mode parameter for 61850
Oper.ctlNum CO - Mod Cmd Mode parameter for 61850
Oper.T CO - Mod Cmd Mode parameter for 61850
Oper.Test CO - Mod Cmd Mode parameter for 61850
Oper.Check CO - Mod Cmd Mode parameter for 61850
stVal ST - - Mon Mode status value parameter
for 61850
q ST - - Mon Quality: Mode status value
parameter for 61850
t ST - - Mon Timestamp: Mode status value
parameter for 61850
Table continues on next page

57
Communication protocol manual
Section 7 1MRK 511 375-UEN A
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
ChLiv a_dSPS stVal ST - LINKUP Mon Access point link status
q ST - LINKUP Mon Quality: Access point link
status
t ST - LINKUP Mon Timestamp: Access point link
status

7.6 Logical nodes for protection related functions

7.6.1 Breaker failure RBRF

7.6.1.1 Breaker failure protection CCRBRF IP14514-1 v6

PID-3562-LOGICALNODEDATA v2

LN type LN prefix LN class Function block name


CCRBRF (revision 0) CC RBRF CCRBRF

Table 28: CCRBRF Logical node data


DO name DO type DA name FC T Signal Mon/ Description
Cmd
OpIn aACT general ST T TRRET Mon Retrip by breaker failure
protection function
phsA ST T TRRETL1 Mon Retrip by breaker failure
protection function phase L1
phsB ST T TRRETL2 Mon Retrip by breaker failure
protection function phase L2
phsC ST T TRRETL3 Mon Retrip by breaker failure
protection function phase L3
q ST T TRRET Mon Quality: Retrip by breaker
failure protection function
t ST T TRRET Mon Timestamp: Retrip by breaker
failure protection function
Mod aINC Oper.ctlVal CO - Mod Cmd Mode parameter
Oper.origin.orCat CO - Mod Cmd Mode parameter
Oper.origin.orIdent CO - Mod Cmd Mode parameter
Oper.ctlNum CO - Mod Cmd Mode parameter
Oper.T CO - Mod Cmd Mode parameter
Oper.Test CO - Mod Cmd Mode parameter
Oper.Check CO - Mod Cmd Mode parameter

Table continues on next page

58
Communication protocol manual
1MRK 511 375-UEN A Section 7
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
Mod aINC stVal ST - - Mon Mode status parameter for
61850

q ST - - Mon Quality: Mode status parameter


for 61850
t ST - - Mon Timestamp: Mode status
parameter for 61850
Beh aINS stVal ST - Beh Mon Behaviour parameter
q ST - Beh Mon Quality: Behaviour parameter
t ST - Beh Mon Timestamp: Behaviour
parameter
OpEx bACT general ST T TRBU Mon Back-up trip by breaker failure
protection function
q ST T TRBU Mon Quality: Back-up trip by breaker
failure protection function
t ST T TRBU Mon Timestamp: Back-up trip by
breaker failure protection
function
OpEx2 v2ACT general ST - TRBU2 Mon Second back-up trip by breaker
failure protection function
q ST - TRBU2 Mon Quality: Second back-up trip by
breaker failure protection
function
t ST - TRBU2 Mon Timestamp: Second back-up
trip by breaker failure
protection function

7.6.2 Disturbance recorder RDRE

7.6.2.1 Disturbance report DRPRDRE GUID-0B12001D-5AD2-451B-8AFE-0920B947F5C1 v1

PID-3949-LOGICALNODEDATA v3

LN type LN prefix LN class Function block name


DRPRDRE (revision 0) DRP RDRE DRPRDRE

Table 29: DRPRDRE Logical node data


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter for 61850
Oper.origin.orCat CO - Mod Cmd Mode parameter for 61850
Oper.origin.orIdent CO - Mod Cmd Mode parameter for 61850
Oper.ctlNum CO - Mod Cmd Mode parameter for 61850
Oper.T CO - Mod Cmd Mode parameter for 61850
Oper.Test CO - Mod Cmd Mode parameter for 61850
Oper.Check CO - Mod Cmd Mode parameter for 61850
stVal ST - ModeSt Mon Mode status parameter for
61850

Table continues on next page

59
Communication protocol manual
Section 7 1MRK 511 375-UEN A
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
Mod a_dINC q ST - ModeSt Mon Quality: Mode status parameter
for 61850

t ST - ModeSt Mon Timestamp: Mode status


parameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
RcdMade a_dSPS stVal ST - RECMADE Mon Disturbance recording made
q ST - RECMADE Mon Quality: Disturbance recording
made
t ST - RECMADE Mon Timestamp: Disturbance
recording made
FltNum b_dINS stVal ST - FaultNumber Mon Disturbance fault number
q ST - FaultNumber Mon Quality: Disturbance fault
number
t ST - FaultNumber Mon Timestamp: Disturbance fault
number

7.7 Logical nodes for generic references

7.7.1 Generic process I/O GGIO

7.7.1.1 Logic rotating switch for function selection and LHMI presentation
SLGAPC SEMOD114936-1 v4

PID-6641-LOGICALNODEDATA v2

LN type LN prefix LN class Function block name


SLGGIO (revision 7) SL GGIO SLGAPC

Table 30: SLGAPC Logical node data


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter
Oper.origin.orCat CO - Mod Cmd Mode parameter
Oper.origin.orIdent CO - Mod Cmd Mode parameter
Oper.ctlNum CO - Mod Cmd Mode parameter
Oper.T CO - Mod Cmd Mode parameter
Oper.Test CO - Mod Cmd Mode parameter
Oper.Check CO - Mod Cmd Mode parameter
stVal ST - - Mon Mode status parameter for
61850

Table continues on next page

60
Communication protocol manual
1MRK 511 375-UEN A Section 7
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
Mod a_dINC q ST - - Mon Quality: Mode status parameter
for 61850

t ST - - Mon Timestamp: Mode status


parameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter
q ST - Beh Mon Quality: Behaviour parameter
t ST - Beh Mon Timestamp: Behaviour
parameter
IntIn b_dINS stVal ST - SWPOSN Mon Switch position (integer)
q ST - SWPOSN Mon Quality: Switch position
(integer)
t ST - SWPOSN Mon Timestamp: Switch position
(integer)
SwPosC1 v5_dISC Oper.ctlVal CO - - Cmd Command parameter for
IEC61850
Oper.origin.orCat CO - - Cmd Command parameter for
IEC61850
valWTr.posVal ST - - Mon Position
Oper.origin.orIdent CO - - Cmd Command parameter for
IEC61850
Oper.ctlNum CO - - Cmd Command parameter for
IEC61850
Oper.T CO - - Cmd Command parameter for
IEC61850
Oper.Test CO - - Cmd Command parameter for
IEC61850
Oper.Check CO - - Cmd Command parameter for
IEC61850
q ST - - Mon Quality: Position
t ST - - Mon Timestamp: Position
ctlModel CF - - - Control model type for jump
cmd
sboTimeout CF - - - Maximum time between select
and execute signals for jump
cmd
sboClass CF - - - Select for many used for jump
cmd
SPCCO v6_dSPC Oper.ctlVal CO - - Cmd Command parameter for
IEC61850
Oper.origin.orCat CO - - Cmd Command parameter for
IEC61850
Oper.origin.orIdent CO - - Cmd Command parameter for
IEC61850
Oper.ctlNum CO - - Cmd Command parameter for
IEC61850
Oper.T CO - - Cmd Command parameter for
IEC61850
Oper.Test CO - - Cmd Command parameter for
IEC61850

Table continues on next page

61
Communication protocol manual
Section 7 1MRK 511 375-UEN A
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
SPCCO v6_dSPC Oper.Check CO - - Cmd Command parameter for
IEC61850

ctlModel CF - - - Control model type for step


cmd
sboTimeout CF - - - Maximum time between select
and execute signals for step
cmd
sboClass CF - - - Select for many used for step
cmd

7.7.1.2 Selector mini switch VSGAPC SEMOD158754-1 v3

PID-3829-LOGICALNODEDATA v3

LN type LN prefix LN class Function block name


VSGGIO (revision 1) VS GGIO VSGAPC

Table 31: VSGAPC Logical node data


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter
Oper.origin.orCat CO - Mod Cmd Mode parameter
Oper.origin.orIdent CO - Mod Cmd Mode parameter
Oper.ctlNum CO - Mod Cmd Mode parameter
Oper.T CO - Mod Cmd Mode parameter
Oper.Test CO - Mod Cmd Mode parameter
Oper.Check CO - Mod Cmd Mode parameter
stVal ST - - Mon Mode status parameter for
61850
q ST - - Mon Quality: Mode status parameter
for 61850
t ST - - Mon Timestamp: Mode status
parameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter
q ST - Beh Mon Quality: Behaviour parameter
t ST - Beh Mon Timestamp: Behaviour
parameter
DPCSO d_dDPC Cancel.ctlVal CO - - Cmd Command parameter for
IEC61850
Cancel.origin.orCat CO - - Cmd Command parameter for
IEC61850
Oper.ctlVal CO - - Cmd Command parameter for
IEC61850
Oper.origin.orCat CO - - Cmd Command parameter for
IEC61850
SBOw.ctlVal CO - - Cmd Command parameter for
IEC61850

Table continues on next page

62
Communication protocol manual
1MRK 511 375-UEN A Section 7
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
DPCSO d_dDPC SBOw.origin.orCat CO - - Cmd Command parameter for
IEC61850
SBOw.origin.orIdent CO - - Cmd Command parameter for
IEC61850
Oper.origin.orIdent CO - - Cmd Command parameter for
IEC61850
Cancel.origin.orIdent CO - - Cmd Command parameter for
IEC61850
Cancel.ctlNum CO - - Cmd Command parameter for
IEC61850
Oper.ctlNum CO - - Cmd Command parameter for
IEC61850
SBOw.ctlNum CO - - Cmd Command parameter for
IEC61850
SBOw.T CO - - Cmd Command parameter for
IEC61850
Cancel.T CO - - Cmd Command parameter for
IEC61850
Oper.T CO - - Cmd Command parameter for
IEC61850
Oper.Test CO - - Cmd Command parameter for
IEC61850
Cancel.Test CO - - Cmd Command parameter for
IEC61850
SBOw.Test CO - - Cmd Command parameter for
IEC61850
Oper.Check CO - - Cmd Command parameter for
IEC61850
SBOw.Check CO - - Cmd Command parameter for
IEC61850
stVal ST - POSITION Mon Position indication, integer
q ST - POSITION Mon Quality: Position indication,
integer
t ST - POSITION Mon Timestamp: Position
indication, integer
stSeld ST - - Mon Select conditions are fulfilled
ctlModel CF - CtlModel - Specifies the type for control
model according to IEC 61850

7.7.1.3 Generic communication function for Double Point indication DPGAPC SEMOD55384-1 v4

PID-4139-LOGICALNODEDATA v3

LN type LN prefix LN class Function block name


DPGGIO (revision 0) DP GGIO DPGAPC

63
Communication protocol manual
Section 7 1MRK 511 375-UEN A
Logical node data model

Table 32: DPGAPC Logical node data


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Mod aINC Oper.ctlVal CO - Mod Cmd Mode parameter
Oper.origin.orCat CO - Mod Cmd Mode parameter
Oper.origin.orIdent CO - Mod Cmd Mode parameter
Oper.ctlNum CO - Mod Cmd Mode parameter
Oper.T CO - Mod Cmd Mode parameter
Oper.Test CO - Mod Cmd Mode parameter
Oper.Check CO - Mod Cmd Mode parameter
stVal ST - - Mon Mode status parameter for
61850
q ST - - Mon Quality: Mode status parameter
for 61850
t ST - - Mon Timestamp: Mode status
parameter for 61850
Beh aINS stVal ST - Beh Mon Behaviour parameter
q ST - Beh Mon Quality: Behaviour parameter
t ST - Beh Mon Timestamp: Behaviour
parameter
DPCSO bDPC stVal ST - POSITION Mon Double point indication
q ST - POSITION Mon Quality: Double point indication
t ST - POSITION Mon Timestamp: Double point
indication

7.7.1.4 Single point generic control 8 signals SPC8GAPC SEMOD176448-1 v3

PID-3575-LOGICALNODEDATA v3

LN type LN prefix LN class Function block name


SPC8GGIO (revision 2) SPC8 GGIO SPC8GAPC

Table 33: SPC8GAPC Logical node data


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter for 61850
Oper.origin.orCat CO - Mod Cmd Mode parameter for 61850
Oper.origin.orIdent CO - Mod Cmd Mode parameter for 61850
Oper.ctlNum CO - Mod Cmd Mode parameter for 61850
Oper.T CO - Mod Cmd Mode parameter for 61850
Oper.Test CO - Mod Cmd Mode parameter for 61850
Oper.Check CO - Mod Cmd Mode parameter for 61850
stVal ST - - Mon Mode status parameter for
61850
q ST - - Mon Quality: Mode status parameter
for 61850

Table continues on next page

64
Communication protocol manual
1MRK 511 375-UEN A Section 7
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
Mod a_dINC t ST - - Mon Timestamp: Mode status
parameter for 61850

Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850


q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
SPCSO1 d_dSPC Oper.ctlVal CO - - Cmd Command parameter for
IEC61850
Oper.origin.orCat CO - - Cmd Command parameter for
IEC61850
Oper.origin.orIdent CO - - Cmd Command parameter for
IEC61850
Oper.ctlNum CO - - Cmd Command parameter for
IEC61850
Oper.T CO - - Cmd Command parameter for
IEC61850
Oper.Test CO - - Cmd Command parameter for
IEC61850
Oper.Check CO - - Cmd Command parameter for
IEC61850
SPCSO2 d_dSPC Oper.ctlVal CO - - Cmd Command parameter for
IEC61850
Oper.origin.orCat CO - - Cmd Command parameter for
IEC61850
Oper.origin.orIdent CO - - Cmd Command parameter for
IEC61850
Oper.ctlNum CO - - Cmd Command parameter for
IEC61850
Oper.T CO - - Cmd Command parameter for
IEC61850
Oper.Test CO - - Cmd Command parameter for
IEC61850
Oper.Check CO - - Cmd Command parameter for
IEC61850
SPCSO3 d_dSPC Oper.ctlVal CO - - Cmd Command parameter for
IEC61850
Oper.origin.orCat CO - - Cmd Command parameter for
IEC61850
Oper.origin.orIdent CO - - Cmd Command parameter for
IEC61850
Oper.ctlNum CO - - Cmd Command parameter for
IEC61850
Oper.T CO - - Cmd Command parameter for
IEC61850
Oper.Test CO - - Cmd Command parameter for
IEC61850
Oper.Check CO - - Cmd Command parameter for
IEC61850
SPCSO4 d_dSPC Oper.ctlVal CO - - Cmd Command parameter for
IEC61850

Table continues on next page

65
Communication protocol manual
Section 7 1MRK 511 375-UEN A
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
SPCSO4 d_dSPC Oper.origin.orCat CO - - Cmd Command parameter for
IEC61850

Oper.origin.orIdent CO - - Cmd Command parameter for


IEC61850
Oper.ctlNum CO - - Cmd Command parameter for
IEC61850
Oper.T CO - - Cmd Command parameter for
IEC61850
Oper.Test CO - - Cmd Command parameter for
IEC61850
Oper.Check CO - - Cmd Command parameter for
IEC61850
SPCSO5 d_dSPC Oper.ctlVal CO - - Cmd Command parameter for
IEC61850
Oper.origin.orCat CO - - Cmd Command parameter for
IEC61850
Oper.origin.orIdent CO - - Cmd Command parameter for
IEC61850
Oper.ctlNum CO - - Cmd Command parameter for
IEC61850
Oper.T CO - - Cmd Command parameter for
IEC61850
Oper.Test CO - - Cmd Command parameter for
IEC61850
Oper.Check CO - - Cmd Command parameter for
IEC61850
SPCSO6 d_dSPC Oper.ctlVal CO - - Cmd Command parameter for
IEC61850
Oper.origin.orCat CO - - Cmd Command parameter for
IEC61850
Oper.origin.orIdent CO - - Cmd Command parameter for
IEC61850
Oper.ctlNum CO - - Cmd Command parameter for
IEC61850
Oper.T CO - - Cmd Command parameter for
IEC61850
Oper.Test CO - - Cmd Command parameter for
IEC61850
Oper.Check CO - - Cmd Command parameter for
IEC61850
SPCSO7 d_dSPC Oper.ctlVal CO - - Cmd Command parameter for
IEC61850
Oper.origin.orCat CO - - Cmd Command parameter for
IEC61850
Oper.origin.orIdent CO - - Cmd Command parameter for
IEC61850
Oper.ctlNum CO - - Cmd Command parameter for
IEC61850
Oper.T CO - - Cmd Command parameter for
IEC61850
Oper.Test CO - - Cmd Command parameter for
IEC61850

Table continues on next page

66
Communication protocol manual
1MRK 511 375-UEN A Section 7
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
SPCSO7 d_dSPC Oper.Check CO - - Cmd Command parameter for
IEC61850
SPCSO8 d_dSPC Oper.ctlVal CO - - Cmd Command parameter for
IEC61850
Oper.origin.orCat CO - - Cmd Command parameter for
IEC61850
Oper.origin.orIdent CO - - Cmd Command parameter for
IEC61850
Oper.ctlNum CO - - Cmd Command parameter for
IEC61850
Oper.T CO - - Cmd Command parameter for
IEC61850
Oper.Test CO - - Cmd Command parameter for
IEC61850
Oper.Check CO - - Cmd Command parameter for
IEC61850

7.7.1.5 Event counter with limit supervision L4UFCNT GUID-C7139F45-E03E-440A-85FD-2102B6470688 v1

PID-3553-LOGICALNODEDATA v3

LN type LN prefix LN class Function block name


L4UFCNT (revision 0) L4U FCNT L4UFCNT

Table 34: L4UFCNT Logical node data


DO name DO type DA name FC T Signal Mon/ Description
Cmd
CntRs a_dBCR actVal ST - VALUE Mon Counted value
q ST - VALUE Mon Quality: Counted value
t ST - VALUE Mon Timestamp: Counted value
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter for 61850
Oper.origin.orCat CO - Mod Cmd Mode parameter for 61850
Oper.origin.orIdent CO - Mod Cmd Mode parameter for 61850
Oper.ctlNum CO - Mod Cmd Mode parameter for 61850
Oper.T CO - Mod Cmd Mode parameter for 61850
Oper.Test CO - Mod Cmd Mode parameter for 61850
Oper.Check CO - Mod Cmd Mode parameter for 61850
stVal ST - - Mon Mode status value parameter
for 61850
q ST - - Mon Quality: Mode status value
parameter for 61850
t ST - - Mon Timestamp: Mode status value
parameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850

Table continues on next page

67
Communication protocol manual
Section 7 1MRK 511 375-UEN A
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
Beh a_dINS t ST - Beh Mon Timestamp: Behaviour
parameter for 61850

RsCnt v1_dSPC Oper.ctlVal CO - - Cmd Command parameter for


IEC61850
Oper.origin.orCat CO - - Cmd Command parameter for
IEC61850
Oper.origin.orIdent CO - - Cmd Command parameter for
IEC61850
Oper.ctlNum CO - - Cmd Command parameter for
IEC61850
Oper.T CO - - Cmd Command parameter for
IEC61850
Oper.Test CO - - Cmd Command parameter for
IEC61850
Oper.Check CO - - Cmd Command parameter for
IEC61850
Lim1 v1_dSPS stVal ST - LIMIT1 Mon Counted value is larger than or
equal to CounterLimit1
q ST - LIMIT1 Mon Quality: Counted value is larger
than or equal to CounterLimit1
t ST - LIMIT1 Mon Timestamp: Counted value is
larger than or equal to
CounterLimit1
Lim2 v1_dSPS stVal ST - LIMIT2 Mon Counted value is larger than or
equal to CounterLimit2
q ST - LIMIT2 Mon Quality: Counted value is larger
than or equal to CounterLimit2
t ST - LIMIT2 Mon Timestamp: Counted value is
larger than or equal to
CounterLimit2
Lim3 v1_dSPS stVal ST - LIMIT3 Mon Counted value is larger than or
equal to CounterLimit3
q ST - LIMIT3 Mon Quality: Counted value is larger
than or equal to CounterLimit3
t ST - LIMIT3 Mon Timestamp: Counted value is
larger than or equal to
CounterLimit3
Lim4 v1_dSPS stVal ST - LIMIT4 Mon Counted value is larger than or
equal to CounterLimit4
q ST - LIMIT4 Mon Quality: Counted value is larger
than or equal to CounterLimit4
t ST - LIMIT4 Mon Timestamp: Counted value is
larger than or equal to
CounterLimit4

7.7.1.6 IEC 61850 generic communication I/O functions SPGGIO GUID-900EC450-B37E-4578-ADAA-901CB8CC497D v2

PID-3780-LOGICALNODEDATA v3

LN type LN prefix LN class Function block name


SPGGIO (revision 1) SP GGIO SPGAPC

68
Communication protocol manual
1MRK 511 375-UEN A Section 7
Logical node data model

Table 35: SPGAPC Logical node data


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter
Oper.origin.orCat CO - Mod Cmd Mode parameter
Oper.origin.orIdent CO - Mod Cmd Mode parameter
Oper.ctlNum CO - Mod Cmd Mode parameter
Oper.T CO - Mod Cmd Mode parameter
Oper.Test CO - Mod Cmd Mode parameter
Oper.Check CO - Mod Cmd Mode parameter
stVal ST - - Mon Mode status parameter for
61850
q ST - - Mon Quality: Mode status parameter
for 61850
t ST - - Mon Timestamp: Mode status
parameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
Ind c_dSPS stVal ST - OUT Mon Output status
q ST - OUT Mon Quality: Output status
t ST - OUT Mon Timestamp: Output status

7.7.1.7 IEC 61850 generic communication I/O functions 16 inputs SP16GGIO GUID-E6D85EF8-3DA5-4814-9337-24DB15B76BF5 v2

PID-3781-LOGICALNODEDATA v3

LN type LN prefix LN class Function block name


SP16GGIO (revision 2) SP16 GGIO SP16GAPC

Table 36: SP16GAPC Logical node data


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter
Oper.origin.orCat CO - Mod Cmd Mode parameter
Oper.origin.orIdent CO - Mod Cmd Mode parameter
Oper.ctlNum CO - Mod Cmd Mode parameter
Oper.T CO - Mod Cmd Mode parameter
Oper.Test CO - Mod Cmd Mode parameter
Oper.Check CO - Mod Cmd Mode parameter
stVal ST - - Mon Mode status parameter for
61850
q ST - - Mon Quality: Mode status parameter
for 61850

Table continues on next page

69
Communication protocol manual
Section 7 1MRK 511 375-UEN A
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
Mod a_dINC t ST - - Mon Timestamp: Mode status
parameter for 61850

Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850


q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
Ind c_dSPS stVal ST - OUT1 Mon Output 1 status
q ST - OUT1 Mon Quality: Output 1 status
t ST - OUT1 Mon Timestamp: Output 1 status
Ind2 c_dSPS stVal ST - OUT2 Mon Output 2 status
q ST - OUT2 Mon Quality: Output 2 status
t ST - OUT2 Mon Timestamp: Output 2 status
Ind3 c_dSPS stVal ST - OUT3 Mon Output 3 status
q ST - OUT3 Mon Quality: Output 3 status
t ST - OUT3 Mon Timestamp: Output 3 status
Ind4 c_dSPS stVal ST - OUT4 Mon Output 4 status
q ST - OUT4 Mon Quality: Output 4 status
t ST - OUT4 Mon Timestamp: Output 4 status
Ind5 c_dSPS stVal ST - OUT5 Mon Output 5 status
q ST - OUT5 Mon Quality: Output 5 status
t ST - OUT5 Mon Timestamp: Output 5 status
Ind6 c_dSPS stVal ST - OUT6 Mon Output 6 status
q ST - OUT6 Mon Quality: Output 6 status
t ST - OUT6 Mon Timestamp: Output 6 status
Ind7 c_dSPS stVal ST - OUT7 Mon Output 7 status
q ST - OUT7 Mon Quality: Output 7 status
t ST - OUT7 Mon Timestamp: Output 7 status
Ind8 c_dSPS stVal ST - OUT8 Mon Output 8 status
q ST - OUT8 Mon Quality: Output 8 status
t ST - OUT8 Mon Timestamp: Output 8 status
Ind9 c_dSPS stVal ST - OUT9 Mon Output 9 status
q ST - OUT9 Mon Quality: Output 9 status
t ST - OUT9 Mon Timestamp: Output 9 status
Ind10 c_dSPS stVal ST - OUT10 Mon Output 10 status
q ST - OUT10 Mon Quality: Output 10 status
t ST - OUT10 Mon Timestamp: Output 10 status
Ind11 c_dSPS stVal ST - OUT11 Mon Output 11 status
q ST - OUT11 Mon Quality: Output 11 status
t ST - OUT11 Mon Timestamp: Output 11 status
Ind12 c_dSPS stVal ST - OUT12 Mon Output 12 status
q ST - OUT12 Mon Quality: Output 12 status
t ST - OUT12 Mon Timestamp: Output 12 status
Table continues on next page

70
Communication protocol manual
1MRK 511 375-UEN A Section 7
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
Ind13 c_dSPS stVal ST - OUT13 Mon Output 13 status
q ST - OUT13 Mon Quality: Output 13 status
t ST - OUT13 Mon Timestamp: Output 13 status
Ind14 c_dSPS stVal ST - OUT14 Mon Output 14 status
q ST - OUT14 Mon Quality: Output 14 status
t ST - OUT14 Mon Timestamp: Output 14 status
Ind15 c_dSPS stVal ST - OUT15 Mon Output 15 status
q ST - OUT15 Mon Quality: Output 15 status
t ST - OUT15 Mon Timestamp: Output 15 status
Ind16 c_dSPS stVal ST - OUT16 Mon Output 16 status
q ST - OUT16 Mon Quality: Output 16 status
t ST - OUT16 Mon Timestamp: Output 16 status
GrInd v1_dSPS stVal ST - OUTOR Mon Output status logic OR gate for
input 1 to 16
q ST - OUTOR Mon Quality: Output status logic OR
gate for input 1 to 16
t ST - OUTOR Mon Timestamp: Output status
logic OR gate for input 1 to 16

7.7.1.8 Generic communication function for Measured Value MVGAPC SEMOD55402-1 v3

PID-3779-LOGICALNODEDATA v2

LN type LN prefix LN class Function block name


MVGGIO (revision 1) MV GGIO MVGAPC

Table 37: MVGAPC Logical node data


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter
Oper.origin.orCat CO - Mod Cmd Mode parameter
Oper.origin.orIdent CO - Mod Cmd Mode parameter
Oper.ctlNum CO - Mod Cmd Mode parameter
Oper.T CO - Mod Cmd Mode parameter
Oper.Test CO - Mod Cmd Mode parameter
Oper.Check CO - Mod Cmd Mode parameter
stVal ST - - Mon Mode status parameter for
61850
q ST - - Mon Quality: Mode status parameter
for 61850
t ST - - Mon Timestamp: Mode status
parameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850

Table continues on next page

71
Communication protocol manual
Section 7 1MRK 511 375-UEN A
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
Beh a_dINS q ST - Beh Mon Quality: Behaviour parameter
for 61850

t ST - Beh Mon Timestamp: Behaviour


parameter for 61850
AnIn a_dMV rangeC.hhLim.f CF - MV hhLim - High High limit multiplied with
the base prefix (multiplication
factor)
rangeC.hLim.f CF - MV hLim - High limit multiplied with the
base prefix (multiplication
factor)
rangeC.lLim.f CF - MV lLim - Low limit multiplied with the
base prefix (multiplication
factor)
rangeC.llLim.f CF - MV llLim - Low Low limit multiplied with
the base prefix (multiplication
factor)
rangeC.max.f CF - MV max - Maximum value multiplied with
the base prefix (multiplication
factor)
rangeC.min.f CF - MV min - Minimum value multiplied with
the base prefix (multiplication
factor)
mag.f MX - VALUE Mon Magnitude of deadband value
subMag.f SV - - - Substituted value
range MX - RANGE Mon Range
q MX - VALUE Mon Quality: Magnitude of
deadband value
t MX - VALUE Mon Timestamp: Magnitude of
deadband value
subEna SV - - - Enable substitution
db CF - MV db - Cycl: Report interval (s), Db: In
% of range, Int Db: In %s
zeroDb CF - MV zeroDb - Zero point clamping in 0,001%
of range

7.7.1.9 Trip matrix logic TMAGAPC IP15121-1 v4

PID-4125-LOGICALNODEDATA v2

LN type LN prefix LN class Function block name


TMAGGIO (revision 0) TMA GGIO TMAGAPC

Table 38: TMAGAPC Logical node data


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Mod aINC Oper.ctlVal CO - Mod Cmd Mode parameter
Oper.origin.orCat CO - Mod Cmd Mode parameter
Oper.origin.orIdent CO - Mod Cmd Mode parameter
Oper.ctlNum CO - Mod Cmd Mode parameter

Table continues on next page

72
Communication protocol manual
1MRK 511 375-UEN A Section 7
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
Mod aINC Oper.T CO - Mod Cmd Mode parameter

Oper.Test CO - Mod Cmd Mode parameter


Oper.Check CO - Mod Cmd Mode parameter
stVal ST - - Mon Mode status parameter for
61850
q ST - - Mon Quality: Mode status parameter
for 61850
t ST - - Mon Timestamp: Mode status
parameter for 61850
Beh aINS stVal ST - Beh Mon Behaviour parameter
q ST - Beh Mon Quality: Behaviour parameter
t ST - Beh Mon Timestamp: Behaviour
parameter
Out1 v1SPS stVal ST - OUTPUT1 Mon OR function betweeen inputs 1
to 16
q ST - OUTPUT1 Mon Quality: OR function betweeen
inputs 1 to 16
t ST - OUTPUT1 Mon Timestamp: OR function
betweeen inputs 1 to 16
Out2 v1SPS stVal ST - OUTPUT2 Mon OR function between inputs 17
to 32
q ST - OUTPUT2 Mon Quality: OR function between
inputs 17 to 32
t ST - OUTPUT2 Mon Timestamp: OR function
between inputs 17 to 32
Out3 v1SPS stVal ST - OUTPUT3 Mon OR function between inputs 1
to 32
q ST - OUTPUT3 Mon Quality: OR function between
inputs 1 to 32
t ST - OUTPUT3 Mon Timestamp: OR function
between inputs 1 to 32

7.7.1.10 Elapsed time integrator with limit transgression and overflow


supervision TEIGGIO GUID-9DD4C562-D0D7-4BFB-B9E0-D016675EB772 v1

PID-4047-LOGICALNODEDATA v3

LN type LN prefix LN class Function block name


TEIGGIO (revision 0) TEI GGIO TEIGAPC

Table 39: TEIGAPC Logical node data


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter for 61850
Oper.origin.orCat CO - Mod Cmd Mode parameter for 61850
Oper.origin.orIdent CO - Mod Cmd Mode parameter for 61850
Oper.ctlNum CO - Mod Cmd Mode parameter for 61850

Table continues on next page

73
Communication protocol manual
Section 7 1MRK 511 375-UEN A
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
Mod a_dINC Oper.T CO - Mod Cmd Mode parameter for 61850

Oper.Test CO - Mod Cmd Mode parameter for 61850


Oper.Check CO - Mod Cmd Mode parameter for 61850
stVal ST - - Mon Mode status value parameter
for 61850
q ST - - Mon Quality: Mode status value
parameter for 61850
t ST - - Mon Timestamp: Mode status value
parameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
Alm a_dSPS stVal ST - ALARM Mon Indicator of the integrated time
has reached the alarm limit
q ST - ALARM Mon Quality: Indicator of the
integrated time has reached
the alarm limit
t ST - ALARM Mon Timestamp: Indicator of the
integrated time has reached
the alarm limit
RsAccTms v1_dSPC Oper.ctlVal CO - - Cmd Command parameter for
IEC61850
Oper.origin.orCat CO - - Cmd Command parameter for
IEC61850
Oper.origin.orIdent CO - - Cmd Command parameter for
IEC61850
Oper.ctlNum CO - - Cmd Command parameter for
IEC61850
Oper.T CO - - Cmd Command parameter for
IEC61850
Oper.Test CO - - Cmd Command parameter for
IEC61850
Oper.Check CO - - Cmd Command parameter for
IEC61850
Wrn v1_dSPS stVal ST - WARNING Mon Indicator of the integrated time
has reached the warning limit
q ST - WARNING Mon Quality: Indicator of the
integrated time has reached
the warning limit
t ST - WARNING Mon Timestamp: Indicator of the
integrated time has reached
the warning limit
AccTms v2_dMV mag.f MX - ACCTIME Mon Integrated elapsed time in
seconds
q MX - ACCTIME Mon Quality: Integrated elapsed
time in seconds
t MX - ACCTIME Mon Timestamp: Integrated elapsed
time in seconds

74
Communication protocol manual
1MRK 511 375-UEN A Section 7
Logical node data model

7.8 Logical nodes for sensors and monitoring

7.8.1 Circuit breaker monitoring SSCBR

7.8.1.1 Breaker monitoring SSCBR GUID-30A59448-3B80-4298-965D-19E28BB0BBD8 v3

PID-3267-LOGICALNODEDATA v4

LN type LN prefix LN class Function block name


SSCBR (revision 3) S SCBR SSCBR

Table 40: SSCBR Logical node data


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter for 61850
Oper.origin.orCat CO - Mod Cmd Mode parameter for 61850
Oper.origin.orIdent CO - Mod Cmd Mode parameter for 61850
Oper.ctlNum CO - Mod Cmd Mode parameter for 61850
Oper.T CO - Mod Cmd Mode parameter for 61850
Oper.Test CO - Mod Cmd Mode parameter for 61850
Oper.Check CO - Mod Cmd Mode parameter for 61850
stVal ST - - Mon Mode status parameter for
61850
q ST - - Mon Quality: Mode status parameter
for 61850
t ST - - Mon Timestamp: Mode status
parameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
InaTmdCnt v1_dINS stVal ST - INADAYS Mon The number of days CB has
been inactive
q ST - INADAYS Mon Quality: The number of days CB
has been inactive
t ST - INADAYS Mon Timestamp: The number of
days CB has been inactive
RmnLif v1_dINS stVal ST - CBLIFEPH Mon CB Remaining life of respective
phase
q ST - CBLIFEPH Mon Quality: CB Remaining life of
respective phase
t ST - CBLIFEPH Mon Timestamp: CB Remaining life
of respective phase
RsAccAPwr v1_dSPC Oper.ctlVal CO - - Cmd Command parameter for
IEC61850
Oper.origin.orCat CO - - Cmd Command parameter for
IEC61850

Table continues on next page

75
Communication protocol manual
Section 7 1MRK 511 375-UEN A
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
RsAccAPwr v1_dSPC Oper.origin.orIdent CO - - Cmd Command parameter for
IEC61850

Oper.ctlNum CO - - Cmd Command parameter for


IEC61850
Oper.T CO - - Cmd Command parameter for
IEC61850
Oper.Test CO - - Cmd Command parameter for
IEC61850
Oper.Check CO - - Cmd Command parameter for
IEC61850
RsCBWear v1_dSPC Oper.ctlVal CO - - Cmd Command parameter for
IEC61850
Oper.origin.orCat CO - - Cmd Command parameter for
IEC61850
Oper.origin.orIdent CO - - Cmd Command parameter for
IEC61850
Oper.ctlNum CO - - Cmd Command parameter for
IEC61850
Oper.T CO - - Cmd Command parameter for
IEC61850
Oper.Test CO - - Cmd Command parameter for
IEC61850
Oper.Check CO - - Cmd Command parameter for
IEC61850
RsTrvTm v1_dSPC Oper.ctlVal CO - - Cmd Command parameter for
IEC61850
Oper.origin.orCat CO - - Cmd Command parameter for
IEC61850
Oper.origin.orIdent CO - - Cmd Command parameter for
IEC61850
Oper.ctlNum CO - - Cmd Command parameter for
IEC61850
Oper.T CO - - Cmd Command parameter for
IEC61850
Oper.Test CO - - Cmd Command parameter for
IEC61850
Oper.Check CO - - Cmd Command parameter for
IEC61850
RsSprChaTm v1_dSPC Oper.ctlVal CO - - Cmd Command parameter for
IEC61850
Oper.origin.orCat CO - - Cmd Command parameter for
IEC61850
Oper.origin.orIdent CO - - Cmd Command parameter for
IEC61850
Oper.ctlNum CO - - Cmd Command parameter for
IEC61850
Oper.T CO - - Cmd Command parameter for
IEC61850
Oper.Test CO - - Cmd Command parameter for
IEC61850
Oper.Check CO - - Cmd Command parameter for
IEC61850
Table continues on next page

76
Communication protocol manual
1MRK 511 375-UEN A Section 7
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
OpnAlm v1_dSPS stVal ST - TRVTOPAL Mon CB open travel time exceeded
set value
q ST - TRVTOPAL Mon Quality: CB open travel time
exceeded set value
t ST - TRVTOPAL Mon Timestamp: CB open travel
time exceeded set value
ClsAlm v1_dSPS stVal ST - TRVTCLAL Mon CB close travel time exceeded
set value
q ST - TRVTCLAL Mon Quality: CB close travel time
exceeded set value
t ST - TRVTCLAL Mon Timestamp: CB close travel
time exceeded set value
OpNumAlm v1_dSPS stVal ST - OPERALM Mon Number of CB operations
exceeds alarm limit
q ST - OPERALM Mon Quality: Number of CB
operations exceeds alarm limit
t ST - OPERALM Mon Timestamp: Number of CB
operations exceeds alarm limit
OpNumLO v1_dSPS stVal ST - OPERLO Mon Number of CB operations
exceeds lockout limit
q ST - OPERLO Mon Quality: Number of CB
operations exceeds lockout
limit
t ST - OPERLO Mon Timestamp: Number of CB
operations exceeds lockout
limit
APwrAlm v1_dSPS stVal ST - IPOWALPH Mon Accum I^CurrExponent integr
over CB open travel time
exceeds alarm limit
q ST - IPOWALPH Mon Quality: Accum I^CurrExponent
integr over CB open travel time
exceeds alarm limit
t ST - IPOWALPH Mon Timestamp: Accum
I^CurrExponent integr over CB
open travel time exceeds alarm
limit
APwrLO v1_dSPS stVal ST - IPOWLOPH Mon Accum I^CurrExponent integr
over CB open travel time
exceeds lockout limit
q ST - IPOWLOPH Mon Quality: Accum I^CurrExponent
integr over CB open travel time
exceeds lockout limit
t ST - IPOWLOPH Mon Timestamp: Accum
I^CurrExponent integr over CB
open travel time exceeds
lockout limit
LonTmAlm v1_dSPS stVal ST - MONALM Mon CB 'not operated for long time'
alarm
q ST - MONALM Mon Quality: CB 'not operated for
long time' alarm
t ST - MONALM Mon Timestamp: CB 'not operated
for long time' alarm
SprChaAlm v1_dSPS stVal ST - SPCHALM Mon Spring charging time has
crossed the set value

Table continues on next page

77
Communication protocol manual
Section 7 1MRK 511 375-UEN A
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
SprChaAlm v1_dSPS q ST - SPCHALM Mon Quality: Spring charging time
has crossed the set value
t ST - SPCHALM Mon Timestamp: Spring charging
time has crossed the set value
PosOpn v1_dSPS stVal ST - OPENPOS Mon CB is in open position
q ST - OPENPOS Mon Quality: CB is in open position
t ST - OPENPOS Mon Timestamp: CB is in open
position
PosIvd v1_dSPS stVal ST - INVDPOS Mon CB is in Invalid Position
q ST - INVDPOS Mon Quality: CB is in Invalid Position
t ST - INVDPOS Mon Timestamp: CB is in Invalid
Position
PosCls v1_dSPS stVal ST - CLOSEPOS Mon CB is in closed position
q ST - CLOSEPOS Mon Quality: CB is in closed position
t ST - CLOSEPOS Mon Timestamp: CB is in closed
position
CBLifAlm v1_dSPS stVal ST - CBLIFEAL Mon Remaining life of CB reduced to
Life alarm level
q ST - CBLIFEAL Mon Quality: Remaining life of CB
reduced to Life alarm level
t ST - CBLIFEAL Mon Timestamp: Remaining life of
CB reduced to Life alarm level
PresLO v1_dSPS stVal ST - GPRESLO Mon Pressure below lockout level
q ST - GPRESLO Mon Quality: Pressure below lockout
level
t ST - GPRESLO Mon Timestamp: Pressure below
lockout level
ColOpn v1_dSPS stVal ST - TRCMD Mon Open command issued to CB
q ST - TRCMD Mon Quality: Open command issued
to CB
t ST - TRCMD Mon Timestamp: Open command
issued to CB
TmmsCls v2_dMV mag.f MX - TTRVCL Mon Travel time of the CB during
closing operation
q MX - TTRVCL Mon Quality: Travel time of the CB
during closing operation
t MX - TTRVCL Mon Timestamp: Travel time of the
CB during closing operation
TmmsOpn v2_dMV mag.f MX - TTRVOP Mon Travel time of the CB during
opening operation
q MX - TTRVOP Mon Quality: Travel time of the CB
during opening operation
t MX - TTRVOP Mon Timestamp: Travel time of the
CB during opening operation
TmsSprCha v2_dMV mag.f MX - SPCHT Mon The charging time of the CB
spring
q MX - SPCHT Mon Quality: The charging time of
the CB spring
t MX - SPCHT Mon Timestamp: The charging time
of the CB spring
Table continues on next page

78
Communication protocol manual
1MRK 511 375-UEN A Section 7
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
AccAPwr v2_dMV mag.f MX - IPOWPH Mon Accumulated I^CurrExponent
integrated over CB open travel
time
q MX - IPOWPH Mon Quality: Accumulated
I^CurrExponent integrated over
CB open travel time
t MX - IPOWPH Mon Timestamp: Accumulated
I^CurrExponent integrated over
CB open travel time
PresAlm v3_dSPS stVal ST - GPRESALM Mon Pressure below alarm level
q ST - GPRESALM Mon Quality: Pressure below alarm
level
t ST - GPRESALM Mon Timestamp: Pressure below
alarm level
OpCnt v5_dINS stVal ST - NOOPER Mon Number of CB operation cycle
q ST - NOOPER Mon Quality: Number of CB
operation cycle
t ST - NOOPER Mon Timestamp: Number of CB
operation cycle

7.8.2 Insulation medium supervision (gas) SIMG

7.8.2.1 Gas medium supervision SSIMG GUID-358AD8F8-AE06-4AEA-9969-46E5299D5B4B v3

PID-3703-LOGICALNODEDATA v3

LN type LN prefix LN class Function block name


SSIMG (revision 0) S SIMG SSIMG

Table 41: SSIMG Logical node data


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter for 61850
Oper.origin.orCat CO - Mod Cmd Mode parameter for 61850
Oper.origin.orIdent CO - Mod Cmd Mode parameter for 61850
Oper.ctlNum CO - Mod Cmd Mode parameter for 61850
Oper.T CO - Mod Cmd Mode parameter for 61850
Oper.Test CO - Mod Cmd Mode parameter for 61850
Oper.Check CO - Mod Cmd Mode parameter for 61850
stVal ST - - Mon Mode status parameter for
61850
q ST - - Mon Quality: Mode status parameter
for 61850
t ST - - Mon Timestamp: Mode status
parameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850

Table continues on next page

79
Communication protocol manual
Section 7 1MRK 511 375-UEN A
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
Beh a_dINS t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
InsAlm a_dSPS stVal ST - PRES_LO Mon Pressure below lockout level
q ST - PRES_LO Mon Quality: Pressure below lockout
level
t ST - PRES_LO Mon Timestamp: Pressure below
lockout level
PresAlm a_dSPS stVal ST - PRES_ALM Mon Pressure below alarm level
q ST - PRES_ALM Mon Quality: Pressure below alarm
level
t ST - PRES_ALM Mon Timestamp: Pressure below
alarm level
TmpAlm a_dSPS stVal ST - TEMP_ALM Mon Temperature above alarm level
q ST - TEMP_ALM Mon Quality: Temperature above
alarm level
t ST - TEMP_ALM Mon Timestamp: Temperature
above alarm level
Pres b_dMV mag.f MX - PRESSURE Mon Pressure service value
q MX - PRESSURE Mon Quality: Pressure service value
t MX - PRESSURE Mon Timestamp: Pressure service
value
Tmp b_dMV mag.f MX - TEMP Mon Temperature of the insulation
medium
q MX - TEMP Mon Quality: Temperature of the
insulation medium
t MX - TEMP Mon Timestamp: Temperature of
the insulation medium
LORs v1_dSPC Oper.ctlVal CO - - Cmd Command parameter for
IEC61850
Oper.origin.orCat CO - - Cmd Command parameter for
IEC61850
Oper.origin.orIdent CO - - Cmd Command parameter for
IEC61850
Oper.ctlNum CO - - Cmd Command parameter for
IEC61850
Oper.T CO - - Cmd Command parameter for
IEC61850
Oper.Test CO - - Cmd Command parameter for
IEC61850
Oper.Check CO - - Cmd Command parameter for
IEC61850
TmpLO v1_dSPS stVal ST - TEMP_LO Mon Temperature above lockout
level
q ST - TEMP_LO Mon Quality: Temperature above
lockout level
t ST - TEMP_LO Mon Timestamp: Temperature
above lockout level

80
Communication protocol manual
1MRK 511 375-UEN A Section 7
Logical node data model

7.8.3 Insulation medium supervision (liquid) SIML

7.8.3.1 Liquid medium supervision SSIML GUID-37669E94-4830-4C96-8A67-09600F847F23 v3

PID-3706-LOGICALNODEDATA v3

LN type LN prefix LN class Function block name


SSIML (revision 0) S SIML SSIML

Table 42: SSIML Logical node data


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter for 61850
Oper.origin.orCat CO - Mod Cmd Mode parameter for 61850
Oper.origin.orIdent CO - Mod Cmd Mode parameter for 61850
Oper.ctlNum CO - Mod Cmd Mode parameter for 61850
Oper.T CO - Mod Cmd Mode parameter for 61850
Oper.Test CO - Mod Cmd Mode parameter for 61850
Oper.Check CO - Mod Cmd Mode parameter for 61850
stVal ST - - Mon Mode status parameter for
61850
q ST - - Mon Quality: Mode status parameter
for 61850
t ST - - Mon Timestamp: Mode status
parameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
InsAlm a_dSPS stVal ST - LVL_LO Mon Level below lockout level
q ST - LVL_LO Mon Quality: Level below lockout
level
t ST - LVL_LO Mon Timestamp: Level below
lockout level
PresAlm a_dSPS stVal ST - LVL_ALM Mon Level below alarm level
q ST - LVL_ALM Mon Quality: Level below alarm level
t ST - LVL_ALM Mon Timestamp: Level below alarm
level
TmpAlm a_dSPS stVal ST - TEMP_ALM Mon Temperature above alarm level
q ST - TEMP_ALM Mon Quality: Temperature above
alarm level
t ST - TEMP_ALM Mon Timestamp: Temperature
above alarm level
Pres b_dMV mag.f MX - LEVEL Mon Level service value
q MX - LEVEL Mon Quality: Level service value
t MX - LEVEL Mon Timestamp: Level service value
Table continues on next page

81
Communication protocol manual
Section 7 1MRK 511 375-UEN A
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
Tmp b_dMV mag.f MX - TEMP Mon Temperature of the insulation
medium
q MX - TEMP Mon Quality: Temperature of the
insulation medium
t MX - TEMP Mon Timestamp: Temperature of
the insulation medium
LORs v1_dSPC Oper.ctlVal CO - - Cmd Command parameter for
IEC61850
Oper.origin.orCat CO - - Cmd Command parameter for
IEC61850
Oper.origin.orIdent CO - - Cmd Command parameter for
IEC61850
Oper.ctlNum CO - - Cmd Command parameter for
IEC61850
Oper.T CO - - Cmd Command parameter for
IEC61850
Oper.Test CO - - Cmd Command parameter for
IEC61850
Oper.Check CO - - Cmd Command parameter for
IEC61850
TmpLo v1_dSPS stVal ST - TEMP_LO Mon Temperature above lockout
level
q ST - TEMP_LO Mon Quality: Temperature above
lockout level
t ST - TEMP_LO Mon Timestamp: Temperature
above lockout level

7.8.4 Through fault monitoring STHR

7.8.4.1 Through fault monitoring PTRSTHR GUID-7AE60CB5-3CD5-4FE2-8D54-664AA78DD2DE v1

PID-7144-LOGICALNODEDATA v1

LN type LN prefix LN class Function block name


PTRSTHR (revision 0) PTR STHR PTRSTHR

Table 43: PTRSTHR Logical node data


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter for 61850
Oper.origin.orCat CO - Mod Cmd Mode parameter for 61850
Oper.origin.orIdent CO - Mod Cmd Mode parameter for 61850
Oper.ctlNum CO - Mod Cmd Mode parameter for 61850
Oper.T CO - Mod Cmd Mode parameter for 61850
Oper.Test CO - Mod Cmd Mode parameter for 61850
Oper.Check CO - Mod Cmd Mode parameter for 61850
stVal ST - - Mon Mode status value parameter
for 61850

Table continues on next page

82
Communication protocol manual
1MRK 511 375-UEN A Section 7
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
Mod a_dINC q ST - - Mon Quality: Mode status value
parameter for 61850
t ST - - Mon Timestamp: Mode status value
parameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
GenAlm a_dSPS stVal ST - ALARM Mon General fault detection alarm
q ST - ALARM Mon Quality: General fault detection
alarm
t ST - ALARM Mon Timestamp: General fault
detection alarm
GenCmAlm a_dSPS stVal ST - CMLI2TALM Mon General cumulative fault (I^2)t
alarm
q ST - CMLI2TALM Mon Quality: General cumulative
fault (I^2)t alarm
t ST - CMLI2TALM Mon Timestamp: General cumulative
fault (I^2)t alarm
GenEvtAlm a_dSPS stVal ST - I2TALM Mon General fault (I^2)t alarm for an
event
q ST - I2TALM Mon Quality: General fault (I^2)t
alarm for an event
t ST - I2TALM Mon Timestamp: General fault (I^2)t
alarm for an event
RpRdy a_dSPS stVal ST - REPMADE Mon Report is ready for file transfer
q ST - REPMADE Mon Quality: Report is ready for file
transfer
t ST - REPMADE Mon Timestamp: Report is ready for
file transfer
FltCnt b_dINS stVal ST - TFCNT Mon Overall number of faults
detected since last reset
q ST - TFCNT Mon Quality: Overall number of
faults detected since last reset
t ST - TFCNT Mon Timestamp: Overall number of
faults detected since last reset

7.9 Logical nodes for switchgear

7.9.1 Circuit breaker XCBR

7.9.1.1 Circuit breaker SXCBR GUID-C865CD66-9B2F-4D40-9BC0-BCA7DE7A3D8E v1

PID-4055-LOGICALNODEDATA v1

LN type LN prefix LN class Function block name


SXCBR (revision 1) S XCBR SXCBR

83
Communication protocol manual
Section 7 1MRK 511 375-UEN A
Logical node data model

Table 44: SXCBR Logical node data


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter for 61850
Oper.origin.orCat CO - Mod Cmd Mode parameter for 61850
Oper.origin.orIdent CO - Mod Cmd Mode parameter for 61850
Oper.ctlNum CO - Mod Cmd Mode parameter for 61850
Oper.T CO - Mod Cmd Mode parameter for 61850
Oper.Test CO - Mod Cmd Mode parameter for 61850
Oper.Check CO - Mod Cmd Mode parameter for 61850
stVal ST - - Mon Mode status parameter for
61850
q ST - - Mon Quality: Mode status parameter
for 61850
t ST - - Mon Timestamp: Mode status
parameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
BlkCls a_dSPC Oper.ctlVal CO - - Cmd Special block command value
Oper.origin.orCat CO - - Cmd Special block command value
Oper.origin.orIdent CO - - Cmd Special block command value
Oper.ctlNum CO - - Cmd Special block command value
Oper.T CO - - Cmd Special block command value
Oper.Test CO - - Cmd Special block command value
Oper.Check CO - - Cmd Special block command value
stVal ST - CL_BLKD Mon Indication that the function is
blocked for close commands
q ST - CL_BLKD Mon Quality: Indication that the
function is blocked for close
commands
t ST - CL_BLKD Mon Timestamp: Indication that the
function is blocked for close
commands
BlkOpn a_dSPC Oper.ctlVal CO - - Cmd Special block command value
Oper.origin.orCat CO - - Cmd Special block command value
Oper.origin.orIdent CO - - Cmd Special block command value
Oper.ctlNum CO - - Cmd Special block command value
Oper.T CO - - Cmd Special block command value
Oper.Test CO - - Cmd Special block command value
Oper.Check CO - - Cmd Special block command value
stVal ST - OP_BLKD Mon Indication that the function is
blocked for open commands
q ST - OP_BLKD Mon Quality: Indication that the
function is blocked for open
commands

Table continues on next page

84
Communication protocol manual
1MRK 511 375-UEN A Section 7
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
BlkOpn a_dSPC t ST - OP_BLKD Mon Timestamp: Indication that the
function is blocked for open
commands
Loc a_dSPS stVal ST - - Mon Indication that the function is
in local mode (process level)
q ST - - Mon Quality: Indication that the
function is in local mode
(process level)
t ST - - Mon Timestamp: Indication that the
function is in local mode
(process level)
OpCnt b_dINS stVal ST - CNT_VAL Mon Operation counter value
q ST - CNT_VAL Mon Quality: Operation counter
value
t ST - CNT_VAL Mon Timestamp: Operation counter
value
Pos c_dDPC stVal ST - POSITION Mon Apparatus position indication
q ST - POSITION Mon Quality: Apparatus position
indication
t ST - POSITION Mon Timestamp: Apparatus position
indication
subEna SV - - - Substitute enable
subVal SV - - - Substituted double position
value
CBOpCap h_dINS stVal ST - CBOPCAP Mon Breaker operating capability 1 =
None, 2 = O, 3 = CO, 4 = OCO, 5
= COCO, 6+ = More
q ST - CBOPCAP Mon Quality: Breaker operating
capability 1 = None, 2 = O, 3 =
CO, 4 = OCO, 5 = COCO, 6+ =
More
t ST - CBOPCAP Mon Timestamp: Breaker operating
capability 1 = None, 2 = O, 3 =
CO, 4 = OCO, 5 = COCO, 6+ =
More
BlkUpd v1_dSPC Oper.ctlVal CO - - Cmd Special block command value
Oper.origin.orCat CO - - Cmd Special block command value
Oper.origin.orIdent CO - - Cmd Special block command value
Oper.ctlNum CO - - Cmd Special block command value
Oper.T CO - - Cmd Special block command value
Oper.Test CO - - Cmd Special block command value
Oper.Check CO - - Cmd Special block command value
stVal ST - UPD_BLKD Mon Update of position indication is
blocked
q ST - UPD_BLKD Mon Quality: Update of position
indication is blocked
t ST - UPD_BLKD Mon Timestamp: Update of position
indication is blocked

85
Communication protocol manual
Section 7 1MRK 511 375-UEN A
Logical node data model

7.9.2 Switch XSWI

7.9.2.1 Circuit switch SXSWI GUID-A7AEBCA2-89FD-4F6E-A3B8-57E6A16035C9 v1

PID-4056-LOGICALNODEDATA v1

LN type LN prefix LN class Function block name


SXSWI (revision 1) S XSWI SXSWI

Table 45: SXSWI Logical node data


DO name DO type DA name FC T Signal Mon/ Description
Cmd
Mod a_dINC Oper.ctlVal CO - Mod Cmd Mode parameter for 61850
Oper.origin.orCat CO - Mod Cmd Mode parameter for 61850
Oper.origin.orIdent CO - Mod Cmd Mode parameter for 61850
Oper.ctlNum CO - Mod Cmd Mode parameter for 61850
Oper.T CO - Mod Cmd Mode parameter for 61850
Oper.Test CO - Mod Cmd Mode parameter for 61850
Oper.Check CO - Mod Cmd Mode parameter for 61850
stVal ST - - Mon Mode status parameter for
61850
q ST - - Mon Quality: Mode status parameter
for 61850
t ST - - Mon Timestamp: Mode status
parameter for 61850
Beh a_dINS stVal ST - Beh Mon Behaviour parameter for 61850
q ST - Beh Mon Quality: Behaviour parameter
for 61850
t ST - Beh Mon Timestamp: Behaviour
parameter for 61850
BlkCls a_dSPC Oper.ctlVal CO - - Cmd Special block command value
Oper.origin.orCat CO - - Cmd Special block command value
Oper.origin.orIdent CO - - Cmd Special block command value
Oper.ctlNum CO - - Cmd Special block command value
Oper.T CO - - Cmd Special block command value
Oper.Test CO - - Cmd Special block command value
Oper.Check CO - - Cmd Special block command value
stVal ST - CL_BLKD Mon Indication that the function is
blocked for close commands
q ST - CL_BLKD Mon Quality: Indication that the
function is blocked for close
commands
t ST - CL_BLKD Mon Timestamp: Indication that the
function is blocked for close
commands
BlkOpn a_dSPC Oper.ctlVal CO - - Cmd Special block command value
Oper.origin.orCat CO - - Cmd Special block command value
Oper.origin.orIdent CO - - Cmd Special block command value

Table continues on next page

86
Communication protocol manual
1MRK 511 375-UEN A Section 7
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
BlkOpn a_dSPC Oper.ctlNum CO - - Cmd Special block command value

Oper.T CO - - Cmd Special block command value


Oper.Test CO - - Cmd Special block command value
Oper.Check CO - - Cmd Special block command value
stVal ST - OP_BLKD Mon Indication that the function is
blocked for open commands
q ST - OP_BLKD Mon Quality: Indication that the
function is blocked for open
commands
t ST - OP_BLKD Mon Timestamp: Indication that the
function is blocked for open
commands
Loc a_dSPS stVal ST - - Mon Indication that the function is
in local mode (process level)
q ST - - Mon Quality: Indication that the
function is in local mode
(process level)
t ST - - Mon Timestamp: Indication that the
function is in local mode
(process level)
OpCnt b_dINS stVal ST - CNT_VAL Mon Operation counter value
q ST - CNT_VAL Mon Quality: Operation counter
value
t ST - CNT_VAL Mon Timestamp: Operation counter
value
Pos c_dDPC stVal ST - POSITION Mon Apparatus position indication
q ST - POSITION Mon Quality: Apparatus position
indication
t ST - POSITION Mon Timestamp: Apparatus position
indication
subEna SV - - - Substitute enable
subVal SV - - - Substituted double position
value
SwOpCap f_dINS stVal ST - SWOPCAP Mon Switch operating capability 1 =
None, 2 = O, 3 = C, 4 = O and C
q ST - SWOPCAP Mon Quality: Switch operating
capability 1 = None, 2 = O, 3 = C,
4 = O and C
t ST - SWOPCAP Mon Timestamp: Switch operating
capability 1 = None, 2 = O, 3 = C,
4 = O and C
SwTyp g_dINS stVal ST - - Mon 1=LoadBreak,2=Disconnector,3
=EarthSw,4=HighSpeedEarthS
w
q ST - - Mon Quality:
1=LoadBreak,2=Disconnector,3
=EarthSw,4=HighSpeedEarthS
w
t ST - - Mon Timestamp:
1=LoadBreak,2=Disconnector,3
=EarthSw,4=HighSpeedEarthS
w
Table continues on next page

87
Communication protocol manual
Section 7 1MRK 511 375-UEN A
Logical node data model

DO name DO type DA name FC T Signal Mon/ Description


Cmd
BlkUpd v1_dSPC Oper.ctlVal CO - - Cmd Special block command value
Oper.origin.orCat CO - - Cmd Special block command value
Oper.origin.orIdent CO - - Cmd Special block command value
Oper.ctlNum CO - - Cmd Special block command value
Oper.T CO - - Cmd Special block command value
Oper.Test CO - - Cmd Special block command value
Oper.Check CO - - Cmd Special block command value
stVal ST - UPD_BLKD Mon Update of position indication is
blocked
q ST - UPD_BLKD Mon Quality: Update of position
indication is blocked
t ST - UPD_BLKD Mon Timestamp: Update of position
indication is blocked

88
Communication protocol manual
1MRK 511 375-UEN A Section 8
Flexible product naming

Section 8 Flexible product naming

8.1 Introduction GUID-98BC22A7-8EFF-4CD0-829E-FBB5D8FD8024 v2

The Flexible product naming tool in PCM600 allows the customer to use an IED-vendor
independent 61850 model of the IED. This customer model will be exposed in all IEC 61850
communication, but all other aspects of the IED will remain unchanged (for example, names on
the local HMI and names in the tools).

This offers significant flexibility to adapt the IED to the customers system and standard
solution.

Benefits:

• IEDs uses the customer model for communication.


• Customer specific naming convention for communication can be used.
• Other IEDs and station level equipment can be defined from the customer specific
communication model.
• Error tracing of communication can be the same between different installations.

8.1.1 Mapping example GUID-DD7F097C-1D72-4BA2-8684-61B54EF0D00C v1

Non-affected function views IED 61850 model FPN mapping Customer 61850 model

LHMI
view LD LD

PCM
FunctionA APTOC LD L1PTOC
view

... view

FunctionB BPTOC LD L2PTOC

IEC15000502-2-en.vsdx

IEC15000502 V2 EN-US

Figure 13: L1PTOC in the customer model mapped to BPTOC in the IED model and
L2PTOC mapped to APTOC

Mapping shown in Figure 13 results to mapping shown in Figure 14.

89
Communication protocol manual
Section 8 1MRK 511 375-UEN A
Flexible product naming

Non-affected function views Customer 61850 model

LHMI
view LD

PCM LD L1PTOC
FunctionA
view

... view

FunctionB LD L2PTOC

IEC15000503-2-en.vsdx

IEC15000503 V2 EN-US

Figure 14: L1PTOC mapped to FunctionB and L2PTOC mapped to FunctionA

8.1.2 Mapping possibilities and requirements GUID-AA4E0570-D874-4B82-84A5-729644C67626 v1

The mapping between the IED model and the customer model provides a set of possibilities
but also include some requirements.

The mapping is possible at several levels in the structure:

• Logical Node level (LN to LN)


• Data Object level (DO to DO)
• Data Attribute level (DA to DA).

Custom logical device name (LDName) can be used for addressing.

When the mapping is performed there are some requirements that must be fulfilled between
the IED model and the customer model:

• One attribute in the customer model can only be mapped to one attribute in the IED
model.
• However one attribute in the IED model can be mapped to several attributes in the
customer model.
• The functional constraint (FC) of the data attributes must match.
• The basic type of the data attributes must match.
• Trigger options of the data attributes must match.
• The version of the IEC 61850 standard must match.
• Number of data sets must not exceed the maximum number of data sets that the IED
supports.

There are also some consequences that must be thought about when doing the mapping for
example,

90
Communication protocol manual
1MRK 511 375-UEN A Section 8
Flexible product naming

• If two DOs in one LN in the customer model are mapped to DOs in different LNs in the IED
model the DOs in the customer model might be inconsistent with respect to quality in the
case of different operational states of the IED Functions.
• When several LNs in the customer model are mapped to one function in the IED, the Mod
of the function will affect all the customer LNs

Several other use cases like this exist. By understanding the concept of mapping from IED
functions and IED model to customer model, these cases can be foreseen.

91
Communication protocol manual
92
1MRK 511 375-UEN A Section 9
Glossary

Section 9 Glossary

9.1 Glossary M14893-1 v15

AC Alternating current
ACC Actual channel
ACT Application configuration tool within PCM600
A/D converter Analog-to-digital converter
ADBS Amplitude deadband supervision
ADM Analog digital conversion module, with time synchronization
AI Analog input
ANSI American National Standards Institute
AR Autoreclosing
ASCT Auxiliary summation current transformer
ASD Adaptive signal detection
ASDU Application service data unit
AWG American Wire Gauge standard
BBP Busbar protection
BFOC/2,5 Bayonet fiber optic connector
BFP Breaker failure protection
BI Binary input
BIM Binary input module
BOM Binary output module
BOS Binary outputs status
BR External bistable relay
BS British Standards
BSR Binary signal transfer function, receiver blocks
BST Binary signal transfer function, transmit blocks
C37.94 IEEE/ANSI protocol used when sending binary signals between IEDs
CAN Controller Area Network. ISO standard (ISO 11898) for serial
communication
CB Circuit breaker
CBM Combined backplane module
CCITT Consultative Committee for International Telegraph and Telephony. A
United Nations-sponsored standards body within the International
Telecommunications Union.
CCM CAN carrier module
CCVT Capacitive Coupled Voltage Transformer
Class C Protection Current Transformer class as per IEEE/ ANSI

93
Communication protocol manual
Section 9 1MRK 511 375-UEN A
Glossary

CMPPS Combined megapulses per second


CMT Communication Management tool in PCM600
CO cycle Close-open cycle
Codirectional Way of transmitting G.703 over a balanced line. Involves two twisted
pairs making it possible to transmit information in both directions
COM Command
COMTRADE Standard Common Format for Transient Data Exchange format for
Disturbance recorder according to IEEE/ANSI C37.111, 1999 / IEC
60255-24
Contra-directional Way of transmitting G.703 over a balanced line. Involves four twisted
pairs, two of which are used for transmitting data in both directions
and two for transmitting clock signals
COT Cause of transmission
CPU Central processing unit
CR Carrier receive
CRC Cyclic redundancy check
CROB Control relay output block
CS Carrier send
CT Current transformer
CU Communication unit
CVT or CCVT Capacitive voltage transformer
DAR Delayed autoreclosing
DARPA Defense Advanced Research Projects Agency (The US developer of the
TCP/IP protocol etc.)
DBDL Dead bus dead line
DBLL Dead bus live line
DC Direct current
DFC Data flow control
DFT Discrete Fourier transform
DHCP Dynamic Host Configuration Protocol
DIP-switch Small switch mounted on a printed circuit board
DI Digital input
DLLB Dead line live bus
DNP Distributed Network Protocol as per IEEE Std 1815-2012
DR Disturbance recorder
DRAM Dynamic random access memory
DRH Disturbance report handler
DSP Digital signal processor
DTT Direct transfer trip scheme
EHV network Extra high voltage network
EIA Electronic Industries Association
EMC Electromagnetic compatibility

94
Communication protocol manual
1MRK 511 375-UEN A Section 9
Glossary

EMF Electromotive force


EMI Electromagnetic interference
EnFP End fault protection
EPA Enhanced performance architecture
ESD Electrostatic discharge
F-SMA Type of optical fiber connector
FAN Fault number
FCB Flow control bit; Frame count bit
FOX 20 Modular 20 channel telecommunication system for speech, data and
protection signals
FOX 512/515 Access multiplexer
FOX 6Plus Compact time-division multiplexer for the transmission of up to seven
duplex channels of digital data over optical fibers
FTP File Transfer Protocol
FUN Function type
G.703 Electrical and functional description for digital lines used by local
telephone companies. Can be transported over balanced and
unbalanced lines
GCM Communication interface module with carrier of GPS receiver module
GDE Graphical display editor within PCM600
GI General interrogation command
GIS Gas-insulated switchgear
GOOSE Generic object-oriented substation event
GPS Global positioning system
GSAL Generic security application
GSE Generic substation event
HDLC protocol High-level data link control, protocol based on the HDLC standard
HFBR connector type Plastic fiber connector
HMI Human-machine interface
HSAR High speed autoreclosing
HV High-voltage
HVDC High-voltage direct current
IDBS Integrating deadband supervision
IEC International Electrical Committee
IEC 60044-6 IEC Standard, Instrument transformers – Part 6: Requirements for
protective current transformers for transient performance
IEC 60870-5-103 Communication standard for protection equipment. A serial master/
slave protocol for point-to-point communication
IEC 61850 Substation automation communication standard
IEC 61850–8–1 Communication protocol standard
IEEE Institute of Electrical and Electronics Engineers
IEEE 802.12 A network technology standard that provides 100 Mbits/s on twisted-
pair or optical fiber cable

95
Communication protocol manual
Section 9 1MRK 511 375-UEN A
Glossary

IEEE P1386.1 PCI Mezzanine Card (PMC) standard for local bus modules. References
the CMC (IEEE P1386, also known as Common Mezzanine Card)
standard for the mechanics and the PCI specifications from the PCI SIG
(Special Interest Group) for the electrical EMF (Electromotive force).
IEEE 1686 Standard for Substation Intelligent Electronic Devices (IEDs) Cyber
Security Capabilities
IED Intelligent electronic device
I-GIS Intelligent gas-insulated switchgear
IOM Binary input/output module
Instance When several occurrences of the same function are available in the IED,
they are referred to as instances of that function. One instance of a
function is identical to another of the same kind but has a different
number in the IED user interfaces. The word "instance" is sometimes
defined as an item of information that is representative of a type. In
the same way an instance of a function in the IED is representative of a
type of function.
IP 1. Internet protocol. The network layer for the TCP/IP protocol suite
widely used on Ethernet networks. IP is a connectionless, best-effort
packet-switching protocol. It provides packet routing, fragmentation
and reassembly through the data link layer.
2. Ingression protection, according to IEC 60529
IP 20 Ingression protection, according to IEC 60529, level 20
IP 40 Ingression protection, according to IEC 60529, level 40
IP 54 Ingression protection, according to IEC 60529, level 54
IRF Internal failure signal
IRIG-B: InterRange Instrumentation Group Time code format B, standard 200
ITU International Telecommunications Union
LAN Local area network
LIB 520 High-voltage software module
LCD Liquid crystal display
LDCM Line differential communication module
LDD Local detection device
LED Light-emitting diode
LNT LON network tool
LON Local operating network
MCB Miniature circuit breaker
MCM Mezzanine carrier module
MPM Main processing module
MVAL Value of measurement
MVB Multifunction vehicle bus. Standardized serial bus originally developed
for use in trains.
NCC National Control Centre
NOF Number of grid faults
NUM Numerical module
OCO cycle Open-close-open cycle

96
Communication protocol manual
1MRK 511 375-UEN A Section 9
Glossary

OCP Overcurrent protection


OEM Optical Ethernet module
OLTC On-load tap changer
OTEV Disturbance data recording initiated by other event than start/pick-up
OV Overvoltage
Overreach A term used to describe how the relay behaves during a fault condition.
For example, a distance relay is overreaching when the impedance
presented to it is smaller than the apparent impedance to the fault
applied to the balance point, that is, the set reach. The relay “sees” the
fault but perhaps it should not have seen it.
PCI Peripheral component interconnect, a local data bus
PCM Pulse code modulation
PCM600 Protection and control IED manager
PC-MIP Mezzanine card standard
PMC PCI Mezzanine card
POR Permissive overreach
POTT Permissive overreach transfer trip
Process bus Bus or LAN used at the process level, that is, in near proximity to the
measured and/or controlled components
PSM Power supply module
PST Parameter setting tool within PCM600
PT ratio Potential transformer or voltage transformer ratio
PUTT Permissive underreach transfer trip
RASC Synchrocheck relay, COMBIFLEX
RCA Relay characteristic angle
RISC Reduced instruction set computer
RMS value Root mean square value
RS422 A balanced serial interface for the transmission of digital data in point-
to-point connections
RS485 Serial link according to EIA standard RS485
RTC Real-time clock
RTU Remote terminal unit
SA Substation Automation
SBO Select-before-operate
SC Switch or push button to close
SCL Short circuit location
SCS Station control system
SCADA Supervision, control and data acquisition
SCT System configuration tool according to standard IEC 61850
SDU Service data unit
SLM Serial communication module.
SMA connector Subminiature version A, A threaded connector with constant
impedance.

97
Communication protocol manual
Section 9 1MRK 511 375-UEN A
Glossary

SMT Signal matrix tool within PCM600


SMS Station monitoring system
SNTP Simple network time protocol – is used to synchronize computer clocks
on local area networks. This reduces the requirement to have accurate
hardware clocks in every embedded system in a network. Each
embedded node can instead synchronize with a remote clock,
providing the required accuracy.
SOF Status of fault
SPA Strömberg Protection Acquisition (SPA), a serial master/slave protocol
for point-to-point and ring communication.
SRY Switch for CB ready condition
ST Switch or push button to trip
Starpoint Neutral point of transformer or generator
SVC Static VAr compensation
TC Trip coil
TCS Trip circuit supervision
TCP Transmission control protocol. The most common transport layer
protocol used on Ethernet and the Internet.
TCP/IP Transmission control protocol over Internet Protocol. The de facto
standard Ethernet protocols incorporated into 4.2BSD Unix. TCP/IP
was developed by DARPA for Internet working and encompasses both
network layer and transport layer protocols. While TCP and IP specify
two protocols at specific protocol layers, TCP/IP is often used to refer
to the entire US Department of Defense protocol suite based upon
these, including Telnet, FTP, UDP and RDP.
TEF Time delayed earth-fault protection function
TLS Transport Layer Security
TM Transmit (disturbance data)
TNC connector Threaded Neill-Concelman, a threaded constant impedance version of a
BNC connector
TP Trip (recorded fault)
TPZ, TPY, TPX, TPS Current transformer class according to IEC
TRM Transformer Module. This module transforms currents and voltages
taken from the process into levels suitable for further signal
processing.
TYP Type identification
UMT User management tool
Underreach A term used to describe how the relay behaves during a fault condition.
For example, a distance relay is underreaching when the impedance
presented to it is greater than the apparent impedance to the fault
applied to the balance point, that is, the set reach. The relay does not
“see” the fault but perhaps it should have seen it. See also Overreach.
UTC Coordinated Universal Time. A coordinated time scale, maintained by
the Bureau International des Poids et Mesures (BIPM), which forms the
basis of a coordinated dissemination of standard frequencies and time
signals. UTC is derived from International Atomic Time (TAI) by the
addition of a whole number of "leap seconds" to synchronize it with
Universal Time 1 (UT1), thus allowing for the eccentricity of the Earth's
orbit, the rotational axis tilt (23.5 degrees), but still showing the Earth's

98
Communication protocol manual
1MRK 511 375-UEN A Section 9
Glossary

irregular rotation, on which UT1 is based. The Coordinated Universal


Time is expressed using a 24-hour clock, and uses the Gregorian
calendar. It is used for aeroplane and ship navigation, where it is also
sometimes known by the military name, "Zulu time." "Zulu" in the
phonetic alphabet stands for "Z", which stands for longitude zero.
UV Undervoltage
WEI Weak end infeed logic
VT Voltage transformer
3IO Three times zero-sequence current.Often referred to as the residual or
the earth-fault current
3UO Three times the zero sequence voltage. Often referred to as the
residual voltage or the neutral point voltage

99
Communication protocol manual
100
101
ABB AB
Substation Automation Products
SE-721 59 Västerås, Sweden
Phone +46 (0) 21 32 50 00
Scan this QR code to visit our website
www.abb.com/protection-control
1MRK 511 375-UEN