Power Boiler Anlog Inputs

Junction Box Existing DCS


Sl. No. Equipment Name Description Tag No. Field
No. ferrule
FT1-01+ AIJB-01 FT1-01+/1 1-XC07-01
1 Feed Water Flow Feed water line flow transmitter
FT1-01- AIJB-01 FT1-01-/2 2-XC07-02
Position Transmitter of Feed flow ZT1-01+ AIJB-01 ZT1-01+/4 4-XC07-06
2 Feed Flow Control Valve
control valve ZT1-01- AIJB-01 ZT1-01-/5 5-XC07-07
Position Transmitter of ZT2-04+ AIJB-01 ZT2-04+/7 7-XC08-06
3 Temp. Control Valve
Temperature control valve ZT2-04- AIJB-01 ZT2-04-/8 8-XC08-07
LT1-01A+ AIJB-01 LT1-01A+/10 10-XC07-12
4 Drum Level Drum Level Transmitter-1
LT1-01A- AIJB-01 LT1-01A-/11 11-XC07-13
LT1-01B+ AIJB-01 LT1-01B+/13 13-XC07-17
5 Drum Level Drum Level Transmitter-2
LT1-01B- AIJB-01 LT1-01B-/14 14-XC07-18
FT2-01+ AIJB-01 FT2-01+/16 16-XC07-39
6 Steam Flow Transmitter Main Steam Line Flow Transmitter
FT2-01- AIJB-01 FT2-01-/17 17-XC07-40
Steam Pressure Main Steam Line Pressure PT2-02+ AIJB-01 PT2-02+/19 19-XC07-28
7
Transmitter Transmitter PT2-02- AIJB-01 PT2-02-/20 20-XC07-29
Main Steam Drum Pressure PT2-01+ AIJB-01 PT2-01+/22 22-XC07-34
8 Drum Pr.Transmitter
Transmitter PT2-01- AIJB-01 PT2-01-/23 23-XC07-35
PT + AIJB-01 PT +/25 25-XC08-12
9 FW.Pr.Transmitter Feed Water pressure transmitter
PT - AIJB-01 PT -/26 26-XC08-13

Analog Input Junction Box (AIJB-02) (First Floor at Top of the PA Fan)

Junction Box Existing DCS


Sl. No. Equipment Name Description Tag No. Field
No. ferrule
Position Transmitter of FD fan ZT3-01+ AIJB-02 ZT3-01+/01 1-XC08-23
1 FD Fan Suction Damper
Suction damper RPC ZT3-01- AIJB-02 ZT3-01-/02 2-XC08-24
FT3-01+ AIJB-02 FT3-01+/04 4-XC08-28
2 Flow Transmitter Air Flow Transmitter
FT3-01- AIJB-02 FT3-01-/05 5-XC08-29
Pressure Transmitter at Air box PT3-02+ AIJB-02 PT3-02+/07 7-XC09-01
3 Pressure Transmitter
Compartment-1 PT3-02- AIJB-02 PT3-02-/08 8-XC09-02
Pressure Transmitter at Air box PT3-03+ AIJB-02 PT3-03+/10 10-XC09-06
4 Pressure Transmitter
Compartment-2 PT3-03- AIJB-02 PT3-03-/11 11-XC09-07
Pressure Transmitter at Air box PT3-04+ AIJB-02 PT3-04+/13 13-XC09-12
5 Pressure Transmitter
Compartment-3 PT3-04- AIJB-02 PT3-04-/14 14-XC09-13
Pressure Transmitter at Air box PT3-05+ AIJB-02 PT3-05+/16 16-XC09-17
6 Pressure Transmitter
Compartment-4 PT3-05- AIJB-02 PT3-05-/17 17-XC09-18
ZT3-02+ AIJB-02 ZT3-02+/19 19-XC08-39
Pressure Transmitter of ID Fan
7 Pressure Transmitter
suction damper RPC-02
Pressure Transmitter of ID Fan
7 Pressure Transmitter
suction damper RPC-02 ZT3-02- AIJB-02 ZT3-02-/20 20-XC08-40
PT3-01+ AIJB-02 PT3-01+/22 22-XC09-28
8 Pressure Transmitter PA Header Pressure Transmitter
PT3-01- AIJB-02 PT3-01-/23 23-XC09-29

Analog Input Junction Box (AIJB-03) (3rd floor at Soot Blower)

Junction Box Existing DCS


Sl. No. Equipment Name Description Tag No. Field
No. ferrule
Position Transmitter of Main steam ZT2-02+ AIJB-03 ZT2-02+/1 1-XC08-01
1 M.S Vent Valve
vent valve ZT2-02- AIJB-03 ZT2-02-/2 2-XC08-02
Main steam line temperature TT2-04+ AIJB-03 TT2-04+/4 4-XC07-23
2 Temp.Transmitter
Transmitter TT2-04- AIJB-03 TT2-04-/5 5-XC07-24
Pressure Transmitter at Soot PT2-04+ AIJB-03 PT2-04+/7 7-C10-39
3 Pressure Transmitter
Blower steam line PT2-04- AIJB-03 PT2-04-/8 8-C10-40
PT3-06+ AIJB-03 PT3-06+/10 10-XC08-34
4 Pressure Transmitter Furnace pressure Transmitter
PT3-06- AIJB-03 PT3-06-/11 11-XC08-35
Flue Gas pressure Transmitter at PT3-07+ AIJB-03 PT3-07+/13 13-XC09-23
5 Pressure Transmitter
ESP outlet PT3-07- AIJB-03 PT3-07-/14 14-XC09-24
ZT2-05+ AIJB-03 ZT2-05+/16 16-XC10-34
6 Position Transmitter of PV2-05
ZT2-05- AIJB-03 ZT2-05-/17 17-XC10-35
Analog Input Junction Box (AIJB-04) (at Deaerator Tank)

Junction Box Existing DCS


Sl. No. Equipment Name Description Tag No. Field
No. ferrule

PT2-03+ AIJB-04 PT2-03+/1 1-XC10-06


1 Pressure Transmitter Deaerator PressureTransmitter
PT2-03- AIJB-04 PT2-03-/2 2-XC07-07
LT0-01+ AIJB-04 LT0-01+/4 4-XC10-17
2 Level Transmitter Deaerator Level Transmitter
LT0-01- AIJB-04 LT0-01-/5 5-XC10-18
Position Transmitter of Deaerator ZT0-01+ AIJB-04 ZT0-01+/7 7-XC10-01
3 Deaerator Control Valve
Level Control valve ZT0-01- AIJB-04 ZT0-01-/8 8-XC10-02
ZT2-03+ AIJB-04 ZT2-03+/10 10-XC10-12
4 Position Transmitter Position Transmitter of PV2-03
ZT2-03- AIJB-04 ZT2-03-/11 11-XC10-13

Analog Output Junction Box (AOJB-01) (First Floor at Feed Flow Control Valve)

Junction Box Existing DCS


Sl. No. Equipment Name Name of the Instrument Tag No. Field
No. ferrule
Current to Pneumatic converter of FY1-01+ AOJB-01 FY1-01+/1 1-XD05-01
1 Feed Control Valve
Feed control valve FY1-01- AOJB-01 FY1-01-/2 2-XD05-02
Current to Pneumatic converter of TY2-04+ AOJB-01 TY2-04+/4 4-XD05-03
2 Temp.Control valve
Temp., control valve
Current to Pneumatic converter of
2 Temp.Control valve
Temp., control valve TY2-04- AOJB-01 TY2-04-/5 5-XD05-04
Current to Pneumatic converter of FY3-01+ AOJB-01 FY3-01+/7 7-XD05-07
3 FD Fan Suction Damper
FD Fan suction damper RPC FY3-01- AOJB-01 FY3-01-/8 8-XD05-08
Current to Pneumatic converter of FY3-02+ AOJB-01 FY3-02+/10 10-XD06-01
4 ID SUCTION DAMPER
RPC3-02 FY3-02- AOJB-01 FY3-02-/11 11-XD06-02
Deaerator level control Current to Pneumatic converter of LY0-01+ AOJB-01 LY0-01+/13 13-XD06-05
5
valve LV-0-01 LY0-01- AOJB-01 LY0-01-/14 14-XD06-06
Deaerator Pressure Current to Pneumatic converter of PY2-03+ AOJB-01 PY2-03+/16 16-XD06-07
6
control valve PV2-03 PY2-03- AOJB-01 PY2-03-/17 17-XD06-08
Current to Pneumatic converter of PY2-04+ AOJB-01 PY2-04+/19 19-XD07-03
7 Soot blower control valve
PRV-2-01 PY2-04- AOJB-01 PY2-04-/20 20-XD07-04

Thermocouple Input Junction Box (TCJB-01) (at Ground Floor)

Junction Box Existing DCS


Sl. No. Equipment Name Name of the Instrument Tag No. Field
No. ferrule
Bed Temp. at Compartment -1 TE3-01A+ TCJB-01 TE3-01A+/01 1-XC05-1
1 Thermocouple
(Top) TE3-01A- TCJB-01 TE3-01A-/02 2-XC05-2
Bed Temp. at Compartment -1 TE3-01B+ TCJB-01 TE3-01B+/03 3-XC05-3
2 Thermocouple
(Bottom) TE3-01B- TCJB-01 TE3-01B-/04 4-XC05-4
Bed Temp.at Compartment-2 TE3-02A+ TCJB-01 TE3-02A+/05 5-XC05-5
3 Thermocouple
(Top) TE3-02A- TCJB-01 TE3-02A-/06 6-XC05-6
Bed Temp. at Compartment -2 TE3-02B+ TCJB-01 TE3-02B+/07 7-XC05-7
4 Thermocouple
(Bottom) TE3-02B- TCJB-01 TE3-02B-/08 8-XC05-8
Bed Temp. at Compartment -3 TE3-03A+ TCJB-01 TE3-03A+/09 9-XC05-12
5 Thermocouple
(Top) TE3-03A- TCJB-01 TE3-03A-/10 10-XC05-13
Bed Temp. at Compartment -3 TE3-03B+ TCJB-01 TE3-03B+/11 11-XC05-14
6 Thermocouple
(Bottom) TE3-03B- TCJB-01 TE3-03B-/12 12-XC05-15
Bed Temp. at Compartment -4 TE3-04A+ TCJB-01 TE3-04A+/13 13-XC05-16
7 Thermocouple
(Top) TE3-04A- TCJB-01 TE3-04A-/14 14-XC05-17
Bed Temp. at Compartment -4 TE3-04B+ TCJB-01 TE3-04B+/15 15-XC05-18
8 Thermocouple
(Bottom) TE3-04B- TCJB-01 TE3-04B-/16 16-XC05-19
Steam Temp. at Desuper Heater TE2-02+ TCJB-01 TE2-02+/17 17-XC04-7
9 Thermocouple
Inlet TE2-02- TCJB-01 TE2-02-/18 18-XC04-8
Steam Temp. at Desuper Heater TE2-03+ TCJB-01 TE2-03+/19 19-XC04-12
10 Thermocouple
Outlet TE2-03- TCJB-01 TE2-03-/20 20-XC04-13
TE3-05+ TCJB-01 TE3-05+/21 21-XC06-1
11 Thermocouple Radiant Super Heater Inlet Temp.
TE3-05- TCJB-01 TE3-05-/22 22-XC06-2

Thermocouple Input Junction Box (TCJB-02) (at First Floor at Economizer)

Junction Box Existing DCS


Sl. No. Equipment Name Name of the Instrument Tag No. Field
No. ferrule
Flue Gas Temp. at Economizer TE3-06+ TCJB-02 TE3-06+/01 1-XC06-5
1 Thermocouple
Inlet TE3-06- TCJB-02 TE3-06-/02 2-XC06-6
Flue Gas Temp. at Air Heater TE3-07+ TCJB-02 TE3-07+/03 3-XC06-7
2 Thermocouple
Inlet TE3-07- TCJB-02 TE3-07-/04 4-XC06-8
Flue Gas Temp. at Air Heater TE3-08+ TCJB-02 TE3-08+/05 5-XC06-12
3 Thermocouple
Outlet TE3-08- TCJB-02 TE3-08-/06 6-XC06-13
Feed water Temp. at Economizer TE1-01+ TCJB-02 TE1-01+/07 7-XC04-1
4 Thermocouple
Inlet TE1-01- TCJB-02 TE1-01-/08 8-XC04-2
Feed water Temp. at Economizer TE1-02+ TCJB-02 TE1-02+/09 9-XC04-3
5 Thermocouple
Outlet TE1-02- TCJB-02 TE1-02-/10 10-XC04-4
Steam Temp. at Convection Super TE2-01+ TCJB-02 TE2-01+/11 11-XC04-5
6 Thermocouple
Heater Outlet TE2-01- TCJB-02 TE2-01-/12 12-XC04-6
TE3-09+ TCJB-02 TE3-09+/13 13-XC04-16
7 Thermocouple Air Temp. at Air Heater Outlet
TE3-09- TCJB-02 TE3-09-/14 14-XC04-17
Deaerator Outlet Temp. at Feed TE0-01+ TCJB-02 TE0-01+/15 15-XC06-16
8 Thermocouple
line TE0-01- TCJB-02 TE0-01-/16 16-XC06-17
Solenoid Coil Box for PA Suction & Air Line Dampers (SCB3-01) (at Ground Floor)

Junction Box Existing DCS


Sl. No. Equipment Name Name of the Instrument Tag No. Field
No. ferrule
PD3-01+ SCB3-01 PD3-01+/1 1-XRB31-1
FD Air line comp.-1 Damper
1 Solenoid Coils
opened PD3-01- SCB3-01 PD3-01-/2 2-XRB31-17

FD Air line comp.-1 Damper PD3-01+ SCB3-01 PD3-01+/3 3-XRB31-3


2 Solenoid Coils
closed PD3-01- SCB3-01 PD3-01-/4 4-XRB31-17
FD Air line comp.-2 Damper PD3-02+ SCB3-01 PD3-02+/5 5-XRB31-5
3 Solenoid Coils
opened PD3-02- SCB3-01 PD3-02-/6 6-XRB31-17
FD Air line comp.-2 Damper PD3-02+ SCB3-01 PD3-02+/7 7-XRB31-7
4 Solenoid Coils
closed PD3-02- SCB3-01 PD3-02-/8 8-XRB31-17

FD Air line comp.-3 Damper PD3-03+ SCB3-01 PD3-03+/9 9-XRB31-9


5 Solenoid Coils
opened PD3-03- SCB3-01 PD3-03-/10 10-XRB31-17

FD Air line comp.- 3 Damper PD3-03+ SCB3-01 PD3-03+/11 11-XRB31-11


6 Solenoid Coils
closed
PD3-03- SCB3-01 PD3-03-/12 12-XRB31-17

FD Air line comp.-4 Damper PD3-04+ SCB3-01 PD3-04+/13 13-XRB31-13


7 Solenoid Coils
opened
PD3-04- SCB3-01 PD3-04-/14 14-XRB31-17
FD Air line comp.-4 Damper PD3-04+ SCB3-01 PD3-04+/15 15-XRB31-15
8 Solenoid Coils
closed
PD3-04- SCB3-01 PD3-04-/16 16-XRB31-17
Solenoid Coil Box for PA Suction & Air Line Dampers (SCB3-02) (at Ground Floor)

Junction Box Existing DCS


Sl. No. Equipment Name Name of the Instrument Tag No. Field
No. ferrule
PD3-05+ SCB3-02 PD3-05+/1 1-XRB32-1
1 Solenoid Coils PA fan suction damper opened
PD3-05- SCB3-02 PD3-05-/2 2-XRB32-17
PD3-05+ SCB3-02 PD3-05+/3 3-XRB32-3
2 Solenoid Coils PA fan suction damper closed
PD3-05- SCB3-02 PD3-05-/4 4-XRB32-17
PD3-06+ SCB3-02 PD3-06+/5 5-XRB32-5
3 Solenoid Coils PA airline comp-1 damper opened
PD3-06- SCB3-02 PD3-06-/6 6-XRB32-17
PD3-06+ SCB3-02 PD3-06+/7 7-XRB32-7
4 Solenoid Coils PA airline comp-1 damper closed
PD3-06- SCB3-02 PD3-06-/8 8-XRB32-17
PD3-07+ SCB3-02 PD3-07+/9 9-XRB32-9
5 Solenoid Coils PA airline comp-2 damper opened
PD3-07- SCB3-02 PD3-07-/10 10-XRB32-17

PD3-07+ SCB3-02 PD3-07+/11 11-XRB32-11


6 Solenoid Coils PA airline comp- 2 damper closed
PD3-07- SCB3-02 PD3-07-/12 12-XRB32-17

PD3-08+ SCB3-02 PD3-08+/13 13-XRB32-13


7 Solenoid Coils PA airline comp-3 damper opened
PD3-0-8- SCB3-02 PD3-0-8-/14 14-XRB32-17

PD3-08+ SCB3-02 PD3-08+/15 15-XRB32-15


8 Solenoid Coils PA airline comp-3 damper closed
PD3-0-8- SCB3-02 PD3-0-8-/16 16-XRB32-17
PD3-09+ SCB3-02 PD3-09+/17 17-XRB33-1
9 Solenoid Coils PA airline comp-4 damper opened
PD3-09+ SCB3-02 PD3-09+/18 18-XRB33-17
PD3-09+ SCB3-02 PD3-09+/19 19-XRB33-3
10 Solenoid Coils PA airline comp-4 damper closed
PD3-09+ SCB3-02 PD3-09+20 20-XRB33-17
Solenoid Coil Box for PA Suction & Air Line Dampers (SCB3-03) (at Ground Floor)

Junction Box Existing DCS


Sl. No. Equipment Name Name of the Instrument Tag No. Field
No. ferrule

PD3-10+ SCB3-03 PD3-10+/1 1-XRB63-13


1 Solenoid coils Bed Ash comp.-1 Damper opened
PD3-10- SCB3-03 PD3-10-/2 2-XRB63-17

PD3-10+ SCB3-03 PD3-10+/3 3-XRB63-15


2 Solenoid coils Bed Ash comp.-1 Damper closed
PD3-10- SCB3-03 PD3-10-/4 4-XRB63-17
PD3-11+ SCB3-03 PD3-11+/5 5-XRB64-1
3 Solenoid coils Bed Ash comp.-2 Damper opened
PD3-11- SCB3-03 PD3-11-/6 6-XRB64-17
PD3-11+ SCB3-03 PD3-11+/7 7-XRB64-3
4 Solenoid coils Bed Ash comp.-2 Damper closed
PD3-11- SCB3-03 PD3-11-/8 8-XRB64-17
PD3-12+ SCB3-03 PD3-12+/9 9-XRB64-7
5 Solenoid coils Bed Ash comp.-3 Damper opened
PD3-12- SCB3-03 PD3-12-/10 10-XRB64-17
PD3-12+ SCB3-03 PD3-12+/11 11-XRB64-9
6 Solenoid coils Bed Ash comp.-3 Damper closed
PD3-12- SCB3-03 PD3-12-/12 12-XRB64-17

PD3-13+ SCB3-03 PD3-13+/13 13-XRB64-11


7 Solenoid coils Bed Ash comp.-4 Damper opened
PD3-13- SCB3-03 PD3-13-/14 14-XRB64-17

PD3-13+ SCB3-03 PD3-13+/15 15-XRB64-13


8 Solenoid coils Bed Ash comp.-4 Damper closed
PD3-13- SCB3-03 PD3-13-/16 16-XRB64-17

Digital Input junction box (DIJB-01) (at Ground Floor at below FD damper)

Junction Box Existing DCS


Sl. No. Equipment Name Name of the Instrument Tag No. Field
No. ferrule
Junction Box Existing DCS
Sl. No. Equipment Name Name of the Instrument Tag No. Field
No. ferrule
FD air line damper at comp-1 ZSO3-01 DIJB-01 ZSO3-01-/2 C
1 Read Switches
opened ZSO3-01 DIJB-01 ZSO3-01+/1 1-XA03-2
FD air line damper at comp-1 ZSC3-01 DIJB-01 ZSC3-01-/4 C
2 Read Switches
closed ZSC3-01 DIJB-01 ZSC3-01+/3 3-XA03-3
FD air line damper at comp-2 ZSO3-02 DIJB-01 ZSO3-02+/6 C
3 Read Switches
opened ZSO3-02 DIJB-01 ZSO3-02+/5 5-XA03-4
FD air line damper at comp-2 ZSC3-02 DIJB-01 ZSC3-03-/8 C
4 Read Switches
closed ZSO3-02 DIJB-01 ZSO3-02-/7 7-XA03-5
FD air line damper at comp-3 ZSC3-03 DIJB-01 ZSC3-03-/10 C
5 Read Switches
opened ZSC3-03 DIJB-01 ZSC3-03+/9 9-XA03-6
FD air line damper at comp-3 ZSC3-03 DIJB-01 ZSC3-03-/12 C
6 Read Switches
closed ZSC3-03 DIJB-01 ZSC3-03+/11 11-XA03-7
FD air line damper at comp-4 ZSO3-04 DIJB-01 ZSO3-04-/14 C
7 Read Switches
opened ZSO3-04 DIJB-01 ZSO3-04+/13 13-XA03-8
FD air line damper at comp-4 ZSC3-04 DIJB-01 ZSC3-04-/16 C
8 Read Switches
closed ZSC3-04 DIJB-01 ZSC3-04+/15 15-XA03-9
ZSC3-18 DIJB-01 ZSC3-18-/18 C
9 Read Switches FD Fan suction damper closed
ZSC3-18 DIJB-01 ZSC3-18+/17 17-XA03-1
ZSC3-19 DIJB-01 ZSC3-19-/20 C
10 Read Switches ID Fan suction damper closed
ZSC3-19 DIJB-01 ZSC3-19+/19 19-XA03-24
ZSO3-14 DIJB-01 ZSO3-14-/22 C
11 Read Switches Air bleed off valve-1 opened
ZSO3-14 DIJB-01 ZSO3-14+/21 21-XA03-20
ZSO3-15 DIJB-01 ZSO3-15-/24 C
12 Read Switches Air bleed off valve-2 opened
ZSO3-15 DIJB-01 ZSO3-15+/23 23-XA03-21
ZSO3-16 DIJB-01 ZSO3-16-/26 C
13 Read Switches Air bleed off valve-3 opened
ZSO3-16 DIJB-01 ZSO3-16+/25 25-XA03-22
ZSO3-17 DIJB-01 ZSO3-17-/28 C
14 Read Switches Air bleed off valve-4 opened
ZSO3-17 DIJB-01 ZSO3-17+/27 27-XA03-23

Digital Input junction box (DIJB-02) (Ground Floor at PA fan)

Junction Box Ferruling at the JB


Sl. No. Name of the Instrument Tag No.
No. From Field To DCS
PA airline damper at comp-1 ZSO3-06 DIJB-02 ZSO3-06-/2 C
1
opened ZSO3-06 DIJB-02 ZSO3-06+/1 1-XA03-12
PA airline damper at comp-1 ZSC3-06 DIJB-02 ZSC3-06-/4 C
2
closed ZSC3-06 DIJB-02 ZSC3-06+/3 3-XA03-13
PA airline damper at comp-2 ZSO3-07 DIJB-02 ZSO3-07-/6 C
3
opened ZSO3-07 DIJB-02 ZSO3-07+/5 5-XA03-14
PA airline damper at comp-2 ZSC3-07 DIJB-02 ZSC3-07-/8 C
4
closed ZSC3-07 DIJB-02 ZSC3-07+/7 7-XA03-15
PA airline damper at comp-3 ZSO3-08 DIJB-02 ZSO3-08-/10 C
5
opened ZSO3-08 DIJB-02 ZSO3-08+/9 9-XA03-16
PA airline damper at comp-3 ZSC3-08 DIJB-02 ZSC3-08-/12 C
6
closed ZSC3-08 DIJB-02 ZSC3-08+/11 11-XA03-17
PA airline damper at comp-4 ZSO3-09 DIJB-02 ZSO3-09-/14 C
7
opened ZSO3-09 DIJB-02 ZSO3-09+/13 13-XA03-18
PA airline damper at comp-4 ZSC3-09 DIJB-02 ZSC3-09-/16 C
8
closed ZSC3-09 DIJB-02 ZSC3-09+/15 15-XA03-19
ZSO3-05 DIJB-02 ZSO3-05-/18 C
9 PA Fan suction damper opened
ZSO3-05 DIJB-02 ZSO3-05+/17 17-XA03-10
ZSC3-05 DIJB-02 ZSC3-05-/20 C
10 PA Fan suction damper closed
ZSC3-05 DIJB-02 ZSC3-05+/19 19-XA03-11
Differential pressure switch at soot DPS-201 DIJB-02 DPS-201-/22 C
11
blower steam line DPS-201 DIJB-02 DPS-201+/21 21-XA04-9

Digital Input junction box (DIJB-03) (Ground floor at Feed pumps)

Junction Box Ferruling at the JB


Sl. No. Name of the Instrument Tag No.
No. From Field To DCS
DPSH-01 DIJB-03 DPSH-01-/2 C
Differential pressure switch at feed
1 DPSH-01 DIJB-03 DPSH-01+/1 1-XA04-1
pump-1 stainer
Differential pressure switch at feed DPSH-02 DIJB-03 DPSH-02-/4 C
2
pump-2 stainer DPSH-02 DIJB-03 DPSH-02+/3 3-XA04-2
LSLLO-01 DIJB-03 LSLLO-01-/6 C
3 Deaerator low low level switch
LSLLO-01 DIJB-03 LSLLO-01+/5 5-XA04-4
LSLO-02 DIJB-03 LSLO-02-/8 C
4 Deaerator low level switch
LSLO-02 DIJB-03 LSLO-02+/7 7-XA04-3
Digital Input junction box (DIJB-04) (First Floor at Temp. control Valve)

Junction Box Ferruling at the JB


Sl. No. Name of the Instrument Tag No.
No. From Field To DCS
Motorized main steam vent valve ZSO2-01A DIJB-04 ZSO2-01A-/2 C
1 open limit switch ZSO2-01A DIJB-04 ZSO2-01A+/1 1-XA08-8
Motorized main steam vent valve ZSC2-01A DIJB-04 ZSC2-01A-/4 C
2
close limit switch ZSC2-01A DIJB-04 ZSC2-01A+/3 3-XA08-9
Motorized main steam vent valve TSO2-01A DIJB-04 TSO2-01A-/6 C
3
open torque switch TSO2-01A DIJB-04 TSO2-01A+/5 5-XA08-10
Motorized main steam vent valve TSC2-01A DIJB-04 TSC2-01A-/8 C
4
close torque switch TSC2-01A DIJB-04 TSC2-01A+/7 7-XA08-11
Motorized main steam stop valve ZSO2-02A DIJB-04 ZSO2-02A-/10 C
5
open limit switch ZSO2-02A DIJB-04 ZSO2-02A+/9 9-XA08-18
Motorized main steam stop valve ZSC2-02A DIJB-04 ZSC2-02A-/12 C
6
close limit switch ZSC2-02A DIJB-04 ZSC2-02A+/11 11-XA08-19
Motorized main steam stop valve TSO2-02A DIJB-04 TSO2-02A-/14 C
7
open torque switch TSO2-02A DIJB-04 TSO2-02A+/13 13-XA08-20
Motorized main steam stop valve TSC2-02A DIJB-04 TSC2-02A-/16 C
8
close torque switch TSC2-02A DIJB-04 TSC2-02A+/15 15-XA08-21
Motorized main steam integral ZSO2-02B DIJB-04 ZSO2-02B-/18 C
9
bypass valve open limit switch ZSO2-02B DIJB-04 ZSO2-02B+/17 17-XA08-28
Motorized main steam integral ZSC2-02B DIJB-04 ZSC2-02B-/20 C
10
bypass valve close limit switch ZSC2-02B DIJB-04 ZSC2-02B+/19 19-XA08-29
Motorized main steam integral TSO2-02B DIJB-04 TSO2-02B-/22 C
11
bypass valve open torque switch TSO2-02B DIJB-04 TSO2-02B+/21 21-XA08-30
Motorized main steam integral TSC2-02B DIJB-04 TSC2-02B-/24 C
12
bypass valve close torque switch TSC2-02B DIJB-04 TSC2-02B+/23 23-XA08-31
Digital Input junction box (DIJB-05) (First Floor at CBD MOV)

Junction Box Ferruling at the JB


Sl. No. Name of the Instrument Tag No.
No. From Field To DCS
Motorized intermediate blow down TSO-101 DIJB-05 TSO-101-/2 C
1 valve open torque switch TSO-101 DIJB-05 TSO-101+/1 1-XA10-10
Motorized intermediate blow down TSC-101 DIJB-05 TSC-101-/4 C
2
valve close torque switch TSC-101 DIJB-05 TSC-101+/3 3-XA10-11
Motorized intermediate blow down ZSO-101 DIJB-05 ZSO-101-/6 C
3
valve open limit switch ZSO-101 DIJB-05 ZSO-101+/5 5-XA10-8
Motorized intermediate blow down ZSC-101 DIJB-05 ZSC-101-/8 C
4
valve close limit switch ZSC-101 DIJB-05 ZSC-101+/7 7-XA10-9
ZSO-203 DIJB-05 ZSO-203-/10 C
5 Soot Blower open limit switch
ZSO-203 DIJB-05 ZSO-203+/9 9-XA10-26
ZSC-203 DIJB-05 ZSC-203-12 C
6 Soot Blower close limit switch
ZSC-203 DIJB-05 ZSC-203+11 11-XA10-27

Digital Input junction box (DIJB-06) (Ground floor at below 4th compartment)

Ferruling at the JB
Junction Box
Sl. No. Name of the Instrument Tag No.
No.
From Field To DCS

Bed Ash airline damper comp-1 ZSO3-10 DIJB-06 ZSO3-10-/2 C


1
open limit switch ZSO3-10 DIJB-06 ZSO3-10+/1 1-XA10-18
Bed Ash airline damper comp-1 ZSC3-10 DIJB-06 ZSC3-10-/4 C
2
close limit switch ZSC3-10 DIJB-06 ZSC3-10+/3 3-XA10-19
Bed Ash airline damper comp-2 ZSO3-11 DIJB-06 ZSO3-11-/6 C
3
open limit switch ZSO3-11 DIJB-06 ZSO3-11+/5 5-XA10-20
Bed Ash airline damper comp-2 ZSC3-11 DIJB-06 ZSC3-11-/8 C
4
close limit switch ZSC3-11 DIJB-06 ZSC3-11+/7 7-XA10-21
Bed Ash airline damper comp-3 ZSO3-12 DIJB-06 ZSO3-12-/10 C
5
open limit switch
Bed Ash airline damper comp-3
5
open limit switch ZSO3-12 DIJB-06 ZSO3-12+/9 9-XA10-22
Bed Ash airline damper comp-3 ZSC3-12 DIJB-06 ZSC3-12-/12 C
6
close limit switch ZSC3-12 DIJB-06 ZSC3-12+/11 11-XA10-23
Bed Ash airline damper comp-4 ZSO3-13 DIJB-06 ZSO3-13-/14 C
7
open limit switch ZSO3-13 DIJB-06 ZSO3-13+/13 13-XA10-24
Bed Ash airline damper comp-4 ZSC3-13 DIJB-06 ZSC3-13-/16 C
8
close limit switch ZSC3-13 DIJB-06 ZSC3-13+/15 15-XA10-25
Instrument Air Header Pressure PSL-701 DIJB-06 PSL-701-/18 C
9
Switch PSL-701 DIJB-06 PSL-701+/17 17-XA04-7

Digital Output junction box (DOJB-01) (Ground Floor opposite of DOJB-03 (Gas)

Junction Box Ferruling at the JB


Sl. No. Name of the Instrument Tag No.
No. From Field To DCS
2-XRB-33-17
Air bleed of valve-1 open SOV3-14- DOJB-01 SOV3-14-/2
1 (C)
command SOV3-14+ DOJB-01 SOV3-14+/1 1-XRB-33-5
Air bleed of valve-2 open SOV3-15- DOJB-01 SOV3-15-/4 4-XRB-33-17
2
command SOV3-15+ DOJB-01 SOV3-15+/3 3-XRB-33-7
Air bleed of valve-3 open SOV3-16- DOJB-01 SOV3-16-/6 6-XRB-33-17
3
command SOV3-16+ DOJB-01 SOV3-16+/5 5-XRB-33-9
Air bleed of valve-4 open SOV3-17- DOJB-01 SOV3-17-/8 8-XRB-33-17
4
command
SOV3-17+ DOJB-01 SOV3-17+/7 7-XRB-33-11
Digital Output junction box (DOJB-03) (Ground Floor at TCJB-01)

Junction Box Ferruling at the JB


Sl. No. Name of the Instrument Tag No.
No. From Field To DCS
Gas Butterfly valve-01 open BFV-01 DOJB-03 BFV-01/2 2-N5-2(C)
1
command BFV-01 DOJB-03 BFV-01/1 1-XRB63-11
Gas Butterfly valve-02 open BFV-02 DOJB-03 BFV-02/4 4-N5-2(C)
2
command BFV-02 DOJB-03 BFV-02/3 3-XRB63-5
Gas Butterfly valve-03 open BFV-03 DOJB-03 BFV-03/6 6-N5-2(C)
3
command BFV-03 DOJB-03 BFV-03/5 5-XRB62-7
Gas Butterfly valve-04 open BFV-04 DOJB-03 BFV-03/8 8-N5-2(C)
4
command BFV-04 DOJB-03 BFV-03/7 7-XRB61-9
TB No. at
New DCS ferrule TB Address Module Name Channel No
DCS
XC07-01
0
XC07-02
XC07-06
XC07-07
XC08-06
XC08-07
XC07-12
XC07-13
XC07-17
XC07-18
XC07-39
XC07-40
XC07-28
XC07-29
XC07-34
XC07-35
XC08-12
XC08-13

TB No. at
New DCS ferrule TB Address Module Name Channel No
DCS
XC08-23
XC08-24
XC08-28
XC08-29
XC09-01
XC09-02
XC09-06
XC09-07
XC09-12
XC09-13
XC09-17
XC09-18
XC08-39
XC08-40
XC09-28
XC09-29

TB No. at
New DCS ferrule TB Address Module Name Channel No
DCS
XC08-01
XC08-02
XC07-23
XC07-24
XC10-39
XC10-40
XC08-34
XC08-35
XC09-23
XC09-24
XC10-34
XC10-35
TB No. at
New DCS ferrule TB Address Module Name Channel No
DCS

XC10-06
XC07-07
XC10-17
XC10-18
XC10-01
XC10-02
XC10-12
XC10-13

TB No. at
New DCS ferrule TB Address Module Name Channel No
DCS
XD05-01
XD05-02
XD05-03
XD05-04
XD05-07
XD05-08
XD06-01
XD06-02
XD06-05
XD06-06
XD06-07
XD06-08
XD07-03
XD07-04

TB No. at
New DCS ferrule TB Address Module Name Channel No
DCS
XC05-1
XC05-2
XC05-3
XC05-4
XC05-5
XC05-6
XC05-7
XC05-8
XC05-12
XC05-13
XC05-14
XC05-15
XC05-16
XC05-17
XC05-18
XC05-19
XC04-7
XC04-8
XC04-12
XC04-13
XC06-1
XC06-2

TB No. at
New DCS ferrule TB Address Module Name Channel No
DCS
XC06-5
XC06-6
XC06-7
XC06-8
XC06-12
XC06-13
XC04-1
XC04-2
XC04-3
XC04-4
XC04-5
XC04-6
XC04-16
XC04-17
XC06-16
XC06-17
TB No. at
New DCS ferrule TB Address Module Name Channel No
DCS
XRB31-1

C
XRB31-3
C
XRB31-5
C
XRB31-7
C
XRB31-9
C

XRB31-11

XRB31-31

XRB31-15
C
TB No. at
New DCS ferrule TB Address Module Name Channel No
DCS
XRB32-1
XRB32-C
XRB32-3
XRB32-C
XRB32-5
XRB32-C
XRB32-7
XRB32-C
XRB32-9
XRB32-C

XRB32-11

XRB32-C

XRB32-13

XRB32-C

XRB32-15

XRB32-C
XRB32-17
XRB32-C
XRB32-19
XRB32-C
TB No. at
New DCS ferrule TB Address Module Name Channel No
DCS

XRB63-13

XRB63-C

XRB63-15

XRB63-C
XRB64-1
XRB64-C
XRB64-3
XRB64-C
XRB64-7
XRB64-C
XRB64-9
XRB64-C

XRB64-11

XRB64-C

XRB64-13

XRB64-C

TB No. at
New DCS ferrule TB Address Module Name Channel No
DCS
TB No. at
New DCS ferrule TB Address Module Name Channel No
DCS

A03-2

A03-3
A03-4

A03-5

A03-6

A03-7

A03-8

A03-9

XA03-1

XA03-24

XA03-20

XA03-21

XA03-22

XA03-23

TB No. at
DCS
A03-12

A03-13

A03-14
A03-15

A03-16

A03-17

A03-18

A03-19

A03-10

A03-11

A04-9

TB No. at
DCS

A04-1
A04-2

A04-4

A04-3
TB No. at
DCS

A08-8
A08-9

A08-10

A08-11

A08-18

A08-19

A08-20

A08-21

A08-28

A08-29

A08-30

A08-31
TB No. at
DCS

A10-10
A10-11

A10-8

A10-9

A10-26

A10-27

TB No. at
DCS

A10-18

A10-19

A10-20

A10-21

A10-22
A10-23

A10-24

A10-25

A04-7

TB No. at
DCS
RB-33-5

RB-33-7

RB-33-9

RB-33-11
TB No. at
DCS
RB-63

RB-63

RB-62

RB-61
Ferruling at DCS Cable size Gland
Lugs
from JB to size and
From JB To DCS Qty.
DCS Qty.
AIJB-01/XC07-01

Around 50 Nos. of Pin type lugs of 1sq.mm size


Single Cable of 10 Pairs, 1sq.mm and 54mtrs-
Length from the JB to DCS Here 8 Pairs are
AIJB-01/XC07-02
AIJB-01/XC07-06

2 Nos. of 1" Glands are required


AIJB-01/XC07-07

used and 2 Pairs kept as spare


AIJB-01/XC08-06
AIJB-01/XC08-07
AIJB-01/XC07-12

are required
AIJB-01/XC07-13
AIJB-01/XC07-17
AIJB-01/XC07-18
AIJB-01/XC07-39
AIJB-01/XC07-40
AIJB-01/XC07-28
AIJB-01/XC07-29
AIJB-01/XC07-34
AIJB-01/XC07-35
AIJB-01/XC08-12
AIJB-01/XC08-13

Ferruling at DCS Cable size Gland


Lugs
from JB to size and
From JB To DCS Qty.
DCS Qty.
AIJB-02/XC08-23
54mtrs- Length from the JB to DCS Here 8

Around 50 Nos. of Pin type lugs of 1sq.mm

AIJB-02/XC08-24
Pairs are used and 2 Pairs kept as spare
Single Cable of 10 Pairs, 1sq.mm and

AIJB-02/XC08-28
2 Nos. of 1" Glands are required

AIJB-02/XC08-29
AIJB-02/XC09-01
AIJB-02/XC09-02
size are required

AIJB-02/XC09-06
AIJB-02/XC09-07
AIJB-02/XC09-12
AIJB-02/XC09-13
AIJB-02/XC09-17
AIJB-02/XC09-18
AIJB-02/XC08-39
siz
2 Nos. of 1
Pairs are used
Single Cable

Around 50 Nos.
54mtrs- Length
AIJB-02/XC08-40
AIJB-02/XC09-28
AIJB-02/XC09-29

Ferruling at DCS Cable size Gland


Lugs
from JB to size and
From JB To DCS Qty.
DCS Qty.
AIJB-03/XC08-01
Pairs are used and 2 Pairs kept
1sq.mm and 54mtrs- Length
from the JB to DCS Here 8

Around 40 Nos. of Pin type


AIJB-03/XC08-02
Single Cable of 10 Pairs,

lugs of 1sq.mm size are


2 Nos. of 1" Glands are

AIJB-03/XC07-23
AIJB-03/XC07-24
AIJB-03/XC10-39
as spare

required
required

AIJB-03/XC10-40
AIJB-03/XC08-34
AIJB-03/XC08-35
AIJB-03/XC09-23
AIJB-03/XC09-24
AIJB-03/XC10-34
AIJB-03/XC10-35
Ferruling at DCS Cable size Gland
Lugs
from JB to size and
Qty.
From JB To DCS DCS Qty.
AIJB-04/XC10-06

54mtrs- Length from

2 Nos. of 1" Glands


Pairs, 1sq.mm and
Single Cable of 10

Around 30 Nos. of
used and 2 Pairs

1sq.mm size are


Here 8 Pairs are
AIJB-04/XC07-07

Pin type lugs of


kept as spare
the JB to DCS

are required
AIJB-04/XC10-17

required
AIJB-04/XC10-18
AIJB-04/XC10-01
AIJB-04/XC10-02
AIJB-04/XC10-12
AIJB-04/XC10-13

Ferruling at DCS Cable size Gland


Lugs
from JB to size and
From JB To DCS Qty.
DCS Qty.
AOJB-01/XD05-01
Pin type lugs of
from the JB to
are used and 2
Pairs, 1sq.mm

AOJB-01/XD05-02
s are required

AOJB-01/XD05-03
e required
s spare
Around 45 Nos. of Pin type lugs of
and 54mtrs- Length from the JB to
DCS Here 8 Pairs are used and 2
Single Cable of 10 Pairs, 1sq.mm

2 Nos. of 1" Glands are required

1sq.mm size are required


AOJB-01/XD05-04

Pairs kept as spare


AOJB-01/XD05-07
AOJB-01/XD05-08
AOJB-01/XD06-01
AOJB-01/XD06-02
AOJB-01/XD06-05
AOJB-01/XD06-06
AOJB-01/XD06-07
AOJB-01/XD06-08
AOJB-01/XD07-03
AOJB-01/XD07-04

Ferruling at DCS Cable size Gland


Lugs
from JB to size and
From JB To DCS Qty.
DCS Qty.
TCJB-01/XC05-1
TCJB-01/XC05-2
und 45 Nos. of Pin type lugs of 1.32 sq.mm size are
pair X 1.32 sq.mm KX(A) Armoured SCR T/C Cable

TCJB-01/XC05-3
TCJB-01/XC05-4
TCJB-01/XC05-5
2 Nos. of 1-1/4" Glands are required

TCJB-01/XC05-6
TCJB-01/XC05-7
TCJB-01/XC05-8
TCJB-01/XC05-12
required

TCJB-01/XC05-13
TCJB-01/XC05-14
TCJB-01/XC05-15
TCJB-01/XC05-16
TCJB-01/XC05-17
TCJB-01/XC05-18
TCJB-01/XC05-19
2 Nos. of

Around 45 Nos. of
16pair X 1.32 sq.
TCJB-01/XC04-7
TCJB-01/XC04-8
TCJB-01/XC04-12
TCJB-01/XC04-13
TCJB-01/XC06-1
TCJB-01/XC06-2

Ferruling at DCS Cable size Gland


Lugs
from JB to size and
From JB To DCS Qty.
DCS Qty.
TCJB-02/XC06-5
16pair X 1.32 sq.mm KX(A) Armoured SCR

Around 35 Nos. of Pin type lugs of 1.32


TCJB-02/XC06-6

2 Nos. of 1-1/4" Glands are required


TCJB-02/XC06-7
TCJB-02/XC06-8

sq.mm size are required


TCJB-02/XC06-12
TCJB-02/XC06-13
TCJB-02/XC04-1
T/C Cable

TCJB-02/XC04-2
TCJB-02/XC04-3
TCJB-02/XC04-4
TCJB-02/XC04-5
TCJB-02/XC04-6
TCJB-02/XC04-16
TCJB-02/XC04-17
TCJB-02/XC06-16
TCJB-02/XC06-17
Ferruling at DCS Cable size Gland
Lugs
from JB to size and
From JB To DCS Qty.
DCS Qty.
SCB3-01/XRB31-1

Around 35 Nos. of Pin type lugs of 1.5 sq.mm size are


SCB3-01/XRB31-17 N2-1
SCB3-01/XRB31-3

24 C X 1.5 Sq.mm Armoured Copper Cable


SCB3-01/XRB31-17

2 Nos. of 1-1/4" Glands are required


SCB3-01/XRB31-5
SCB3-01/XRB31-17
SCB3-01/XRB31-7
SCB3-01/XRB31-17

required
SCB3-01/XRB31-9
SCB3-01/XRB31-17

SCB3-01/XRB31-11

SCB3-01/XRB31-17

SCB3-01/XRB31-13

SCB3-01/XRB31-17

SCB3-01/XRB31-15
SCB3-01/XRB31-17
Ferruling at DCS Cable size Gland
Lugs
from JB to size and
From JB To DCS Qty.
DCS Qty.
SCB3-02/XRB32-1
SCB3-02/XRB32-17 N2-1
SCB3-02/XRB32-3
SCB3-02/XRB32-17

Around 42 Nos. of Pin type lugs of 1.5 sq.mm size are required
SCB3-02/XRB32-5
SCB3-02/XRB32-17
24 C X 1.5 Sq.mm Armoured Copper Cable

SCB3-02/XRB32-7
2 Nos. of 1-1/4" Glands are required
SCB3-02/XRB32-17
SCB3-02/XRB32-9
SCB3-02/XRB32-17

SCB3-02/XRB32-11

SCB3-02/XRB32-17

SCB3-02/XRB32-13

SCB3-02/XRB32-17

SCB3-02/XRB32-15

SCB3-02/XRB32-17
SCB3-02/XRB33-1
SCB3-02/XRB33-17
SCB3-02/XRB33-3
SCB3-02/XRB33-17
Ferruling at DCS Cable size Gland
Lugs
from JB to size and
From JB To DCS Qty.
DCS Qty.
SCB3-03/XRB63-13

Around 35 Nos. of Pin type lugs of 1.5 sq.mm size are required
SCB3-03/XRB63-17 N5-1

SCB3-03/XRB63-15

24 C X 1.5 Sq.mm Armoured Copper Cable


SCB3-03/XRB63-17

2 Nos. of 1-1/4" Glands are required


SCB3-03/XRB64-1
SCB3-03/XRB64-17
SCB3-03/XRB64-3
SCB3-03/XRB64-17
SCB3-03/XRB64-7
SCB3-03/XRB64-17
SCB3-03/XRB64-9
SCB3-03/XRB64-17

SCB3-03/XRB64-11

SCB3-03/XRB64-17

SCB3-03/XRB64-13

SCB3-03/XRB64-17

Ferruling at DCS Cable size Gland


Lugs
from JB to size and
Qty.
Lugs
from JB to size and
From JB To DCS Qty.
DCS Qty.

DIJB-01/XA03-2

Around 60 Nos. of Pin type lugs of 1.5 sq.mm size are required
DIJB-01/XA03-3
DIJB-01/XA03-4

DIJB-01/XA03-5

37 C X 1.5 Sq.mm Armoured Copper Cable

2 Nos. of 1-1/2"Glands are required


DIJB-01/XA03-6

DIJB-01/XA03-7

DIJB-01/XA03-8

DIJB-01/XA03-9

DIJB-01/XA03-1

DIJB-01/XA03-24

DIJB-01/XA03-20

DIJB-01/XA03-21

DIJB-01/XA03-22

DIJB-01/XA03-23

Ferruling at DCS Cable size Gland


Lugs
from JB to size and
From JB To DCS Qty.
DCS Qty.
DIJB-02/XA03-12
of 1.5 sq.mm size are

DIJB-02/XA03-13
d Copper Cable

DIJB-02/XA03-14
are required
From JB

DIJB-03/XA04-3
DIJB-03/XA04-4
DIJB-03/XA04-2
DIJB-03/XA04-1
DIJB-02/XA04-9
DIJB-02/XA03-11
DIJB-02/XA03-10
DIJB-02/XA03-19
DIJB-02/XA03-18
DIJB-02/XA03-17
DIJB-02/XA03-16
DIJB-02/XA03-15

Ferruling at DCS
To DCS
16 C X 1.5 Sq.mm
Armoured Copper 37 C X 1.5 Sq.mm Armoured Copper Cabl

DCS
Cable

2 Nos. of 1-
1/4"Glands are 2 Nos. of 1-1/2"Glands are required

Qty.
Cable size Gland
required

from JB to size and


Around 20 Nos. of
Pin type lugs of 1.5 Around 45 Nos. of Pin type lugs of 1.5 sq.mm s

Qty.
Lugs
sq.mm size are required
required
Ferruling at DCS Cable size Gland
Lugs
from JB to size and
From JB To DCS Qty.
DCS Qty.

DIJB-04/XA08-8
DIJB-04/XA08-9
Around 60 Nos. of Pin type lugs of 1.5 sq.mm size are
DIJB-04/XA08-10
37 C X 1.5 Sq.mm Armoured Copper Cable

2 Nos. of 1-1/2"Glands are required

DIJB-04/XA08-11

DIJB-04/XA08-18

DIJB-04/XA08-19
required

DIJB-04/XA08-20

DIJB-04/XA08-21

DIJB-04/XA08-28

DIJB-04/XA08-29

DIJB-04/XA08-30

DIJB-04/XA08-31
Ferruling at DCS Cable size Gland
Lugs
from JB to size and
From JB To DCS Qty.
DCS Qty.

DIJB-05/XA10-10

16 C X 1.5 Sq.mm Armoured

Around 25 Nos. of Pin type


2 Nos. of 1-1/4"Glands are

lugs of 1.5 sq.mm size are


DIJB-05/XA10-11

Copper Cable
DIJB-05/XA10-8

required

required
DIJB-05/XA10-9

DIJB-05/XA10-26

DIJB-05/XA10-27

Ferruling at DCS
Cable size Gland
Lugs
from JB to size and
Qty.
From JB To DCS DCS Qty.

DIJB-06/XA10-18
s. of Pin type lugs of 1.5 sq.mm
.mm Armoured Copper Cable

DIJB-06/XA10-19
1-1/2"Glands are required

DIJB-06/XA10-20
size are required

DIJB-06/XA10-21

DIJB-06/XA10-22
From JB
DIJB-06/XA04-7
DIJB-06/XA10-25
DIJB-06/XA10-24
DIJB-06/XA10-23

DOJB-01/XRB-33-9
DOJB-01/XRB-33-7
DOJB-01/XRB-33-5

DOJB-01/XRB-33-11
Ferruling at DCS
To DCS
1P X 1 Sq.mm
Armoured Copper 37 C X 1.5 Sq.mm Armoured

DCS
Cable

2 Nos. of 1"Glands are


2 Nos. of 1-1/2"Glands ar

Qty.
required Cable size Gland
from JB to size and
Around 20 Nos. of Pin
Around 40 Nos. of Pin type lu
type lugs of 1.5 sq.mm
Qty.
Lugs

size are require


size are required
Ferruling at DCS Cable size Gland
Lugs
from JB to size and
From JB To DCS Qty.
DCS Qty.
DOJB-03/XRB63-11

DOJB-03/XRB63-5

DOJB-03/XRB62-7

DOJB-03/XRB61-9
Power Boiler Anlog Inputs
Junction Box Existing DCS
Sl. No. Equipment Name Description Tag No. Field
No. ferrule

FT1-01+ AIJB-01 FT1-01+/1 1-XC07-01


1 Feed Water Flow Feed water line flow transmitter
FT1-01- AIJB-01 FT1-01-/2 2-XC07-02
Position Transmitter of Feed flow ZT1-01+ AIJB-01 ZT1-01+/4 4-XC07-06
2 Feed Flow Control Valve
control valve ZT1-01- AIJB-01 ZT1-01-/5 5-XC07-07
Position Transmitter of ZT2-04+ AIJB-01 ZT2-04+/7 7-XC08-06
3 AttemTemp. Control Valve
Temperature control valve ZT2-04- AIJB-01 ZT2-04-/8 8-XC08-07
LT1-01A+ AIJB-01 LT1-01A+/10 10-XC07-12
4 Drum Level Drum Level Transmitter-1
LT1-01A- AIJB-01 LT1-01A-/11 11-XC07-13
LT1-01B+ AIJB-01 LT1-01B+/13 13-XC07-17
5 Drum Level Drum Level Transmitter-2
LT1-01B- AIJB-01 LT1-01B-/14 14-XC07-18
FT2-01+ AIJB-01 FT2-01+/16 16-XC07-39
6 Steam Flow Transmitter Main Steam Line Flow Transmitter
FT2-01- AIJB-01 FT2-01-/17 17-XC07-40
Steam Pressure Main Steam Line Pressure PT2-02+ AIJB-01 PT2-02+/19 19-XC07-28
7
Transmitter Transmitter PT2-02- AIJB-01 PT2-02-/20 20-XC07-29
Main Steam Drum Pressure PT2-01+ AIJB-01 PT2-01+/22 22-XC07-34
8 Drum Pr.Transmitter
Transmitter PT2-01- AIJB-01 PT2-01-/23 23-XC07-35
PT + AIJB-01 PT +/25 25-XC08-12
9 FW.Pr.Transmitter Feed Water pressure transmitter
PT - AIJB-01 PT -/26 26-XC08-13

Analog Input Junction Box (AIJB-02) (First Floor at Top of the PA Fan)

Junction Box Existing DCS


Sl. No. Equipment Name Description Tag No. Field
No. ferrule
Position Transmitter of FD fan ZT3-01+ AIJB-02 ZT3-01+/01 1-XC08-23
1 FD Fan Suction Damper
Suction damper RPC ZT3-01- AIJB-02 ZT3-01-/02 2-XC08-24
FT3-01+ AIJB-02 FT3-01+/04 4-XC08-28
2 Flow Transmitter Air Flow Transmitter
FT3-01- AIJB-02 FT3-01-/05 5-XC08-29
Pressure Transmitter at Air box PT3-02+ AIJB-02 PT3-02+/07 7-XC09-01
3 Pressure Transmitter
Compartment-1 PT3-02- AIJB-02 PT3-02-/08 8-XC09-02
Pressure Transmitter at Air box PT3-03+ AIJB-02 PT3-03+/10 10-XC09-06
4 Pressure Transmitter
Compartment-2 PT3-03- AIJB-02 PT3-03-/11 11-XC09-07
Pressure Transmitter at Air box PT3-04+ AIJB-02 PT3-04+/13 13-XC09-12
5 Pressure Transmitter
Compartment-3 PT3-04- AIJB-02 PT3-04-/14 14-XC09-13
Pressure Transmitter at Air box PT3-05+ AIJB-02 PT3-05+/16 16-XC09-17
6 Pressure Transmitter
Compartment-4 PT3-05- AIJB-02 PT3-05-/17 17-XC09-18
ZT3-02+ AIJB-02 ZT3-02+/19 19-XC08-39
Pressure Transmitter of ID Fan
7 Pressure Transmitter
suction damper RPC-02
Pressure Transmitter of ID Fan
7 Pressure Transmitter
suction damper RPC-02 ZT3-02- AIJB-02 ZT3-02-/20 20-XC08-40
PT3-01+ AIJB-02 PT3-01+/22 22-XC09-28
8 Pressure Transmitter PA Header Pressure Transmitter
PT3-01- AIJB-02 PT3-01-/23 23-XC09-29

Analog Input Junction Box (AIJB-03) (3rd floor at Soot Blower)

Junction Box Existing DCS


Sl. No. Equipment Name Description Tag No. Field
No. ferrule
Position Transmitter of Main steam ZT2-02+ AIJB-03 ZT2-02+/1 1-XC08-01
1 M.S Vent Valve
vent valve ZT2-02- AIJB-03 ZT2-02-/2 2-XC08-02
Main steam line temperature TT2-04+ AIJB-03 TT2-04+/4 4-XC07-23
2 Temp.Transmitter
Transmitter TT2-04- AIJB-03 TT2-04-/5 5-XC07-24
Pressure Transmitter at Soot PT2-04+ AIJB-03 PT2-04+/7 7-C10-39
3 Pressure Transmitter
Blower steam line PT2-04- AIJB-03 PT2-04-/8 8-C10-40
PT3-06+ AIJB-03 PT3-06+/10 10-XC08-34
4 Pressure Transmitter Furnace pressure Transmitter
PT3-06- AIJB-03 PT3-06-/11 11-XC08-35
Flue Gas pressure Transmitter at PT3-07+ AIJB-03 PT3-07+/13 13-XC09-23
5 Pressure Transmitter
ESP outlet PT3-07- AIJB-03 PT3-07-/14 14-XC09-24
ZT2-05+ AIJB-03 ZT2-05+/16 16-XC10-34
6 Position Transmitter Position Transmitter of PV2-05
ZT2-05- AIJB-03 ZT2-05-/17 17-XC10-35
Analog Input Junction Box (AIJB-04) (at Deaerator Tank)

Junction Box Existing DCS


Sl. No. Equipment Name Description Tag No. Field
No. ferrule

PT2-03+ AIJB-04 PT2-03+/1 1-XC10-06


1 Pressure Transmitter Deaerator PressureTransmitter
PT2-03- AIJB-04 PT2-03-/2 2-XC07-07
LT0-01+ AIJB-04 LT0-01+/4 4-XC10-17
2 Level Transmitter Deaerator Level Transmitter
LT0-01- AIJB-04 LT0-01-/5 5-XC10-18
Deaerator Control level Position Transmitter of Deaerator ZT0-01+ AIJB-04 ZT0-01+/7 7-XC10-01
3
Valve Level Control valve ZT0-01- AIJB-04 ZT0-01-/8 8-XC10-02
ZT2-03+ AIJB-04 ZT2-03+/10 10-XC10-12
Deaerator Pressure Position Transmitter of Deaerator
4
Control Valve Pressure Control valve Pv2-03 ZT2-03- AIJB-04 ZT2-03-/11 11-XC10-13
New DCS ferrule TB Address Module Name Channel No

New DCS ferrule TB Address Module Name Channel No


New DCS ferrule TB Address Module Name Channel No
New DCS ferrule TB Address Module Name Channel No
Analog Output Junction Box (AOJB-01) (First Floor at Feed Flow Control Valve)

Junction Box Existing DCS


Sl. No. Equipment Name Description Tag No. Field New DCS ferrule
No. ferrule
Current to Pneumatic converter of FY1-01+ AOJB-01 FY1-01+/1 1-XD05-01
1 Feed Control Valve
Feed control valve FY1-01- AOJB-01 FY1-01-/2 2-XD05-02
Current to Pneumatic converter of TY2-04+ AOJB-01 TY2-04+/4 4-XD05-03
2 Temp.Control valve
Temp., control valve TY2-04- AOJB-01 TY2-04-/5 5-XD05-04
FD Fan Suction Current to Pneumatic converter of FY3-01+ AOJB-01 FY3-01+/7 7-XD05-07
3
Damper FD Fan suction damper RPC FY3-01- AOJB-01 FY3-01-/8 8-XD05-08
ID SUCTION Current to Pneumatic converter of FY3-02+ AOJB-01 FY3-02+/10 10-XD06-01
4
DAMPER RPC3-02 FY3-02- AOJB-01 FY3-02-/11 11-XD06-02
LY0-01+ AOJB-01 LY0-01+/13 13-XD06-05
Deaerator level Current to Pneumatic converter of
5
control valve LV-0-01 LY0-01- AOJB-01 LY0-01-/14 14-XD06-06
PY2-03+ AOJB-01 PY2-03+/16 16-XD06-07
Deaerator Pressure Current to Pneumatic converter of
6
control valve PV2-03 PY2-03- AOJB-01 PY2-03-/17 17-XD06-08
Soot blower control Current to Pneumatic converter of PY2-04+ AOJB-01 PY2-04+/19 19-XD07-03
7
valve PRV-2-01 PY2-04- AOJB-01 PY2-04-/20 20-XD07-04
TB Address Module Name Channel No
Junction Box
Sl. No. Equipment Name Description Tag No.
No.

Blow back valve open


1 Blow Back valve
Blow back valve close
Existing DCS
Field New DCS ferrule TB Address Module Name Channel No
ferrule
2X1-45/BBV OPEN+
2X1-46/BBV OPEN- 22
2X1 D4R1S4
2X1-47/BBV CLOSE+
2X1-48/BBV CLOSE- 23