PLC SIGNAL

SLNO DESCRIPTION LONG DESCRIPTION INSTU TAG NAME RANGE DI DO AI AO TREND


TAG NAME
1 RAW WTR PMP O/L HDR PRESS PT01 PI01 0 TO 10KG/CM2 1 YES
2 MAIN CWP O/L HDR PRESS PT02 PI02 0 TO 10KG/CM2 1 YES
3 IND FUR CWP O/L HDR PRESS PT03 PI03 0 TO 10KG/CM2 1 YES
4 FUR CWP O/L HDR PRESS PT04 PI04 0 TO 10KG/CM2 1 YES
5 EMG CWP O/L HDR PRESS PT05 PI05 0 TO 10KG/CM2 1 YES
6 FUR CW I/L MANIFOLD PRESS PT06 PI06 0 TO 10KG/CM2 1 YES

7 COOLING WTR TNK LVL LT01 LI01 0 TO 2.5 MTR 1 NO

8 DM WTR TNK LVL LT02 LI02 0 TO 4 MTR 1 YES


9 EMG DM WTR TANK LVL LT03 LI03 0 TO 3.5 MTR 1 YES

10 RAW WTR FLO TO SOFTNER FT01A FI01A 0 TO 120M3/HR 1 YES

11 SOFTNER O/L FLO TO COOLING TWR FT01B FI01B 0 TO 120M3/HR 1 YES

0 TO 1500
12 COOLING WTR FLO TO WCD FT02A FI02A 1
M3/HR

13 COOLING WTR FLO TO WCD FT02B FI02B 0 TO 1300 1


M3/HR

14 COOLING WTR FLO TO CNVRTR BRG FT02C FI02C 0 TO 10M3/HR 1 YES

15 COOLING WTR FLO TO HT EXCHANGER FT03A FI03A 0 TO 80 M3/HR 1 YES

16 COOLING WTR FLO TO HT EXCHANGER FT03B FI03B 0 TO 80 M3/HR 1 YES

17 COOLING WTR FLO TO IND FUR COIL FT04 FI04 0 TO 80 M3/HR 1 YES

18 WTR FLO TO FIRE EXTINGUISHER FT05 FI05 0 TO 100 M3/HR 1


19 RAW WTR CWP O/L HDR TEMP TE01 TI01 0 TO 150 DEG C 1
20 MAIN CWP O/L HDR TEMP TE01 TI01 0 TO 150 DEG C 1 YES
21 IND FUR CWP O/L HDR TEMP TE02 TI02 0 TO 150 DEG C 1 YES
22 FUR CWP O/L HDR TEMP TE03 TI03 0 TO 150 DEG C 1 YES
23 EMG CWP O/L HDR TEMP TE04 TI04 0 TO 150 DEG C 1 YES
24 IND FUR I/L MANIFOLD WTR TEMP TE05 TI05 0 TO 150 DEG C 1 YES
25 FUR SHELL 1 CW O/L TEMP TE06A TI06A 0 TO 150 DEG C 1 YES
26 FUR SHELL 2 CW O/L TEMP TE06B TI06B 0 TO 150 DEG C 1 YES
27 WCD(SEC-1) O/L COOLING WTR TEMP1 TE07 TE07 0 TO 150 DEG C 1 YES
28 WCD(SEC-1) O/L COOLING WTR TEMP2 TE08 TE08 0 TO 150 DEG C 1 YES
27 WCD(SEC-1) O/L COOLING WTR TEMP1 TE09 TI09 0 TO 150 DEG C 1 YES
28 WCD(SEC-1) O/L COOLING WTR TEMP2 TE10 TI10 0 TO 150 DEG C 1 YES
29 WCD(SEC-2) O/L COOLING WTR TEMP1 TE11 TI11 0 TO 150 DEG C 1 YES
30 WCD(SEC-2) O/L COOLING WTR TEMP2 TE12 TI12 0 TO 150 DEG C 1 YES
31 WCD(SEC-3) O/L COOLING WTR TEMP1 TE13 TI13 0 TO 150 DEG C 1 YES
32 WCD(SEC-3) O/L COOLING WTR TEMP2 TE14 TI14 0 TO 150 DEG C 1 YES
33 WCD(SEC-4) O/L COOLING WTR TEMP1 TE15 TI15 0 TO 150 DEG C 1 YES
34 WCD(SEC-4) O/L COOLING WTR TEMP2 TE16 TI16 0 TO 150 DEG C 1 YES
35 WCD(SEC-5) O/L COOLING WTR TEMP1 TE17 TI17 0 TO 150 DEG C 1 YES
36 WCD(SEC-5) O/L COOLING WTR TEMP2 TE18 TI18 0 TO 150 DEG C 1 YES
37 WCD(SEC-6) O/L COOLING WTR TEMP1 TE19 TI19 0 TO 150 DEG C 1 YES
38 WCD(SEC-6) O/L COOLING WTR TEMP2 TE20 TI20 0 TO 150 DEG C 1 YES
39 WCD(SEC-7) O/L COOLING WTR TEMP1 TE21 TI21 0 TO 150 DEG C 1 YES
40 WCD(SEC-7) O/L COOLING WTR TEMP2 TE22 TI22 0 TO 150 DEG C 1 YES
41 WCD(SEC-8) O/L COOLING WTR TEMP1 TE23 TI23 0 TO 150 DEG C 1 YES
42 WCD(SEC-8) O/L COOLING WTR TEMP2 TE24 TI24 0 TO 150 DEG C 1 YES
43 WCD(SEC-9) O/L COOLING WTR TEMP1 TE25 TI25 0 TO 150 DEG C 1 YES
44 WCD(SEC-9) O/L COOLING WTR TEMP2 TE26 TI26 0 TO 150 DEG C 1 YES
45 WCD COM CW O/L TEMP1 TE27 TI27 0 TO 150 DEG C 1 YES
46 WCD COM CW O/L TEMP2 TE28 TI28 0 TO 150 DEG C 1 YES
47 CNVRTR BRG CW O/L TEMP TE29 TI29 0 TO 150 DEG C 1 YES
48 DM SKID-1 HT EX CW O/L TEMP TE30 TI30 0 TO 150 DEG C 1 YES
49 DM SKID-2 HT EX CW O/L TEMP TE31 TI31 0 TO 150 DEG C 1 YES
50 FUR CW HT EX O/L TEMP TE32 TI32 0 TO 150 DEG C 1 YES
51 CONDENSATE DRAIN VLV(CDCV-1) CDCV1 SET POINT CDCV-1 CDCV1SS 0 TO 100% 1
CDCV1 POS F/B CDCV1SO 0 TO 100% 1
52 DM WTR LINE VLV(SOV-3) SOV-3 OPN F/B SOV-3 SOV3OPNFB 1
SOV-3 CLS F/B SOV3CLSFB 1

SOV-3 ON CMD SOV3ON 1

53 COOLING TOWER FAN 1 CTF-1 RUN F/B CTF-1 CTF1FB 1


CTF-1 MTR O/L TRP CTF1TR 1
CTF-1 L/R MODE CTF1LR 1
CTF-1 VIBRATION CTF1VS 1
CTF-1 OIL LVL LOW CTF1OLL 1
CTF-1 ON CMD CTF1ON 1
DURING FINAL
CTF-1 CURRENT O/P CTF1CO COMMISSIONIN 1
G
CTF-1 SPD O/P CTF1SO 0 TO 1500 RPM 1
CTF-1 SET SPEED CTF1SS 0 TO 100% 1
54 COOLING TOWER FAN 2 CTF-2 RUN F/B CTF-2 CTF2FB 1
CTF-2 MTR O/L TRP CTF2TR 1
CTF-2 -1 L/R MODE CTF2LR 1
CTF-2 VIBRATION CTF2VS 1
CTF-2 OIL LVL LOW CTF2OLL 1
CTF-2 ON CMD CTF2ON 1
DURING FINAL
CTF-2 CURRENT O/P CTF2CO COMMISSIONIN 1
G
CTF-2 SPD O/P CTF2SO 0 TO 1500 RPM 1
CTF-2 SET SPD CTF2SS 0 TO 100% 1
55 FUR. COOLING PUMP-1 FUR PMP-1 RUN F/B FCP-1 FCP1FB 1
FUR PMP-1 MTR O/L TRP FCP1TR 1
FUR CW PMP-1 L/R MODE FCP1LR 1
FUR CW PMP-1 ON CMD FCP1ON 1
56 FUR. COOLING PUMP-2 FUR PMP-2 RUN F/B FCP-2 FCP2FB 1
FUR PMP-2 MTR O/L TRP FCP2TR 1
FUR CW PMP-2 L/R MODE FCP2LR 1
FUR CW PMP-2 ON CMD FCP2ON 1
57 FUR. COOLING PUMP-3 FUR PMP-3 RUN F/B FCP-3 FCP3FB 1
FUR PMP-3 MTR O/L TRP FCP3TR 1
FUR CW PMP-3 L/R MODE FCP3LR 1
FUR CW PMP-3 ON CMD FCP3ON 1
58 E/M COOLING WTR PUMP-1 E/M PMP-1 RUN F/B EWP-1 EWP1FB 1
E/M PMP-1 MTR O/L TRP EWP1TR 1
E/M PMP-1 L/R MODE EWP1LR 1
E/M CW PMP-1 ON CMD EWP1ON 1
59 E/MCOOLING WTR PUMP-2 E/MCW PMP-2 RUN F/B EWP-2 EWP2FB 1
E/M CW PMP-2 MTR O/L TRP EWP2TR 1
E/M CW PMP-2 L/R MODE EWP2LR 1
E/M CW PMP-2 ON COMMAND EWP2ON 1
60 COOLING WTR PUMP 1 CW PMP-1 RUN F/B CWP-1 CWP1FB 1
CW PMP-1 MTR O/L TRP CWP1TR 1
CW PMP-1 L/R MODE CWP1LR 1
CW PMP-1 ON CMD CWP1ON 1
DURING FINAL
CW PMP-1 CURRENT O/P CWP1CO COMMISSIONIN 1
G
CW PMP-1 SPD O/P CWP1SO 0 TO 1500 RPM 1
CW PMP-1 SET SPD CWP1SS 0 TO 100% 1
61 COOLING WTR PUMP 2 CW PMP-2 RUN F/B CWP-2 CWP2FB 1
CW PMP-2 MTR O/L TRP CWP2TR 1
CW PMP-2 L/R MODE CWP2LR 1
CW PMP-2 ON CMD CWP2ON 1
DURING FINAL
CW PMP-2 CURRENT O/P CWP2CO COMMISSIONIN 1
G
CW PMP-2 SPD O/P CWP2SO 0 TO 1500 RPM 1
CW PMP-2 SET SPD CWP2SS 0 TO 100% 1
62 COOLING WTR PUMP 3 CW PMP-3 RUN F/B CWP-3 CWP3FB 1
CW PMP-3 MTR O/L TRP CWP3TR 1
CW PMP-3 L/R MODE CWP3LR 1
CW PMP-3 ON CMD CWP3ON 1
DURING FINAL
CW PMP-3 CURRENT O/P CWP3CO COMMISSIONIN 1
G
CW PMP-3 SPD O/P CWP3SO 0 TO 1500 RPM 1
CW PMP-3 SET SPD CWP3SS 0 TO 100% 1
63 INDUCTION COOLING WTR PUMP 1 IND CW PMP-1 RUN F/B ICWP-1 ICWP1FB 1
IND CW PMP-1 MT O/L TRP ICWP1TR 1
IND CW PMP-1 L/R MODE ICWP1LR 1
IND CW PMP-1 ON CMD ICWP1ON 1
64 INDUCTION COOLING WTR PUMP 2 IND CW PMP-2 RUN F/B ICWP-2 ICWP2FB 1
IND CW PMP-2 MTR O/L TRP ICWP2TR 1
IND CW PMP-2 L/R MODE ICWP2LR 1
IND CW PMP-2 ON CMD ICWP2ON 1
66 ID FAN-1 ID-1 RUN F/B ID-1 ID1FB 1
ID-1 MTR O/L TRP ID1TR 1
ID-1 L/R MODE ID1LR 1
ID-1 ON CMD ID1ON 1
DURING FINAL
ID-1 CURRENT O/P ID1CO COMMISSIONIN 1
G
ID-1 SPD O/P ID1SO 0 TO 1500 RPM 1
ID-1 SET SPD ID1SS 0 TO 100% 1
67 ID FAN-1 SUCTION DMPR ID-1 SUC DMPR OPN F/B ID1SD ID1SDOPN 1
ID-1 SUC DMPR CLS F/B ID1SDCLS 1

ID-1 SUC DMPR ON CMD ID1SDON 1

68 ID FAN-1 DISCHRG DMPR ID-1 DIS DMPR OPN F/B ID1DD ID1DDOPN 1
ID-1 DIS DMPR CLS F/B ID1DDCLS 1

ID-1 DIS DMPR ON CMD ID1DDON 1

69 ID FAN-2 ID-2 RUN F/B ID-2 ID2FB 1


ID-2 MTR O/L TRP ID2TR 1
ID-2 L/R MODE ID2LR 1
ID-2 ON CMD ID2ON 1
DURING FINAL
ID-2 CURRENT O/P ID2CO COMMISSIONIN 1
G
ID-2 SPD O/P ID2SO 0 TO 1500 RPM 1
ID-2 SET SPD ID2SS 0 TO 100% 1
70 ID FAN-2 SUCTION DMPR ID-2 SUC DMPR OPN F/B ID2SD ID2SDOPN 1
ID-2 SUC DMPR CLS F/B ID2SDCLS 1

ID-2 SUC DMPR ON CMD ID2SDON 1

71 ID FAN-2 DISCHRG DMPR ID-2 DIS DMPR OPN F/B ID2DD ID2DDOPN 1
ID-2 DIS DMPR CLS F/B ID2DDCLS 1

ID-2 DIS DMPR ON CMD ID2DDON 1

72 HEAT EXCAHNGER CL FAN 1 HXCF-1 RUN F/B HXCF-1 HXCF1FB 1


HXCF-1 MTR O/L TRP HXCF1TR 1
HXCF-1 L/R MODE HXCF1LR 1
HXCF-1 ON CMD HXCF1ON 1
73 HEAT EXCAHNGER CL FAN 2 HXCF-2 RUN F/B HXCF-2 HXCF2FB 1
HXCF-2 MTR O/L TRP HXCF2TR 1
HXCF-2 L/R MODE HXCF2LR 1
HXCF-2 ON CMD HXCF2ON 1
74 HEAT EXCAHNGER CL FAN 3 HXCF-3 RUN F/B HXCF-3 HXCF3FB 1
HXCF-3 MTR O/L TRP HXCF3TR 1
HXCF-3 L/R MODE HXCF3LR 1
HXCF-3 ON CMD HXCF3ON 1
75 HEAT EXCAHNGER CL FAN 4 HXCF-4 RUN F/B HXCF-4 HXCF4FB 1
HXCF-4 MTR O/L TRP HXCF4TR 1
HXCF-4 L/R MODE HXCF4LR 1
HXCF-4 ON CMD HXCF4ON 1
80 AIR COMPRESSOR1 COMP-1 RUN F/B COMP-1 COMP1FB 1
COMP-1 MTR O/L TRP COMP1TR 1
COMP-1 L/R MODE COMP1LR 1
COMP-1 ON CMD COMP1ON 1
83 AIR DILUTION DMPR AIR DIL DMPR OPN F/B ADD-1 ADD1OPNFB 1
AIR DIL DMPR CLS F/B ADD1CLSFB 1
AIR DIL DMPR OPN TRQ ADD1OPNTL 1
AIR DIL DMPR CLS TRQ ADD1CLSTL 1
AIR DIL DMPR L/R MODE ADD1LR 1
AIR DIL DMPR OPN/CLS CMD ADD1CMD 1
AIR DIL DMPR POSITION FB ADD1POS 1
84 DM SKID-1 PUMP DM SKID 1 PMP-1 RUN F/B DMS1P1 DMS1P1FB 1
DM SKID 1 PMP-1 O/L TRP DMS1P1TR 1
DM SKID 1 PMP-1 L/R MODE DMS1P1LR 1
DM SKID 1 PMP-1 ON CMD DMS1P1ON 1
85 DM SKID-2 PUMP DM SKID 2 PMP-1 RUN F/B DMS2P1 DMS2P1FB 1
DM SKID 2 PMP-1 O/L TRP DMS2P1TR 1
DM SKID 2 PMP-1 L/R MODE DMS2P1LR 1
DM SKID2 PMP-1 ON CMD DMS2P1ON 1
85 DM SKID-3 PUMP DM SKID 2 PMP-2 RUN F/B DMS2P2 DMS2P2FB 1
DM SKID 2 PMP-2 O/L TRP DMS2P2TR 1
DM SKID 2 PMP-2 L/R MODE DMS2P2LR 1
DM SKID2 PMP-2 ON CMD DMS2P2ON 1
86 HYD SKID-1 PUMP HYD SKID 1 PMP-1 RUN F/B HYD1P1 HYDP1FB 1
HYD SKID 1 PMP-1 O/L TRP HYDP1TR 1
HYD SKID 1 PMP-1 L/R MODE HYDP1LR 1
HYD SKID 1 PMP-1 ON CMD HYDP1ON 1
87 HYD SKID-2 PUMP HYD SKID 2 PMP-1 RUN F/B HYD2P1 HYDP2FB 1
HYD SKID 2 PMP-1 O/L TRP HYDP2TR 1
HYD SKID 2 PMP-1 L/R MODE HYDP2LR 1
HYD SKID 2 PMP-1 ON CMD HYDP2ON 1
87 HYD SKID-3 PUMP IND FUR HYD PMP-2 RUN F/B HYD2P2 HYDP2FB 1
IND FUR HYD PMP-2 O/L TRP HYDP2TR 1
IND FUR HYD PMP-2 L/R MODE HYDP2LR 1
IND FUR HYD PMP-2 ON CMD HYDP2ON 1

88 GAS MIXING STATION I/L STEAM FLOW GMS I/L STM FLO FT203 FI203 0 TO 1500 KG/HR 1

89 GAS MIXING STATION I/L STEAM PRESS GMS I/L STM PRESS PT205 PI205 0 TO 30KG/CM2 1
90 GAS MIXING STATION I/L STEAM TEMP GMS I/L STM TEMP TE205 TI205 0 TO 400 DEG C 1
91 GAS MIXING STATION I/L OXYGEN FLOW GMS I/L O2 FLO FT400 FI400 1
92 GAS MIXING STATION I/L ARGON FLOW GMS I/L AR FLO FT100 FI100 1

93 INSTRUMENT AIR HEADER PRESSURE INST AIR HDR PRESS PT303A PI303A 0 TO 16 KG/CM2 1

94 SERVICE AIR HEADER PRESSURE SER AIR HDR PRESS PT303B PI303B 0 TO 16 KG/CM2 1

95 DIFFERENTIAL PRESS SW BF CMBR-1 DP SW BF CMBR1 DPS01 DPAH1 1


96 DIFFERENTIAL PRESS SW BF CMBR-2 DP SW BF CMBR2 DPS02 DPAH2 1
97 DIFFERENTIAL PRESS SW BF CMBR-3 DP SW BF CMBR3 DPS03 DPAH3 1
98 DIFFERENTIAL PRESS SW BF CMBR-4 DP SW BF CMBR4 DPS04 DPAH4 1
99 DIFFERENTIAL PRESS SW BF DP SW BF DPS05 DPAH5 1
100 BF BNKR-1 LVL SW LVL SW BF BNKR1 LSH01 LAH1 1
101 BF BNKR-2 LVL SW LVL SW BF BNKR2 LSH02 LAH2 1
102 BF BNKR-3 LVL SW LVL SW BF BNKR3 LSH02 LAH3 1
103 BF BNKR-4 LVL SW LVL SW BF BNKR4 LSH04 LAH4 1
104 HET EX BNKR LVL SW LVL SW HE BNKR LSH05 LAH5 1

105 CCS STACK PARTICULATE MONITOR CCS STK DUST LVL SPM02 SPI02 0 TO 200 MG/M3 1 YES

106 FLUE GAS HOOD TEMP-1 AT WCD TE501 TI501 0 TO 1200 DEG C 1 YES

107 FLUE GAS TEMP-2 AT WCD TE502 TI502 0 TO 1200 DEG C 1 YES

108 FLUE GAS TEMP-3 AT WCD TE503 TI503 0 TO 1200 DEG C 1 YES

109 FLUE GAS TEMP-4 AT WCD TE504 TI504 0 TO 1200 DEG C 1 YES

110 FLUE GAS TEMP-5 AT WCD TE505 TI505 0 TO 1200 DEG C 1 YES

111 FLUE GAS TEMP-6 AT WCD TE506 TI506 0 TO 1200 DEG C 1 YES

112 FLUE GAS TEMP FD COOLER I/L TE507 TI507 0 TO 1200 DEG C 1 YES

113 FLUE GAS TEMP FD COOLER O/L TE508 TI508 0 TO 400 DEG C 1 YES
114 FLUE GAS TEMP FD COOLER O/L TE509 TI509 0 TO 400 DEG C 1 YES
115 FLUE GAS TEMP FD COOLER O/L TE510 TI510 0 TO 400 DEG C 1 YES
116 FLUE GAS TEMP BF I/L TE511 TI511 0 TO 400 DEG C 1 YES
117 FLUE GAS TEMP BF O/L TE512 TI512 0 TO 400 DEG C 1 YED
COOLING WATER TANK LEVEL1 SW CTLL1 1
COOLING WATER TANK LEVEL2 SW CTLL2 1
EMERGENCY WATER PUMP-1_DP SWITCH EWP1DPH 1
EMERGENCY WATER PUMP-2_DP SWITCH EWP2DPH 1
FURNACE COOLING PUMP-1_DP SWITCH FCP1DPH 1
FURNACE COOLING PUMP-2_DP SWITCH FCP2DPH 1
INDUCTION COOLING PUMP-1_DP SWITCH ICWP1DPH 1
INDUCTION COOLING PUMP-2_DP SWITCH ICWP2DPH 1
138 37 84 9

TOTAL I/OS 144 48 144 12

SPARE I/OS 6 11 60 3
REMARK
ALARM ALARM SET POINT REMARKS DRG NO
PLC SIDE
LO ALRM 3 KG C871-P&ID-001 TB7:1
LO ALRM 3 KG C871-P&ID-001 TB7:3 DONE
LO ALRM 3 KG C871-P&ID-001 TB7:5 DONE
LO ALRM 3 KG C871-P&ID-001 TB7:7 DONE
LO ALRM 3 KG C871-P&ID-001 TB7:9 DONE
LO ALRM 3 KG C871-P&ID-001 TB7:11

LO ALRM WILL BE
LO ALRM 1 MTR C871-P&ID-001 TB7:13
RECEIVED FROM INSTU

LO ALRM 2.5 MTR C871-P&ID-001 TB7:15 DONE


LO ALRM 2 MTR C871-P&ID-001 TB7:17 DONE
FLOW CUMULATIVE
REQ C871-P&ID-001 TB7:19

FLOW CUMULATIVE C871-P&ID-001 TB7:21


REQ
FLOW CUMULATIVE
C871-P&ID-001 TB7:23
REQ DONE
FLOW CUMULATIVE C871-P&ID-001 TB7:25
REQ
FLOW CUMULATIVE
C871-P&ID-001 TB7:27
REQ
FLOW CUMULATIVE C871-P&ID-001 TB7:29
REQ
FLOW CUMULATIVE
C871-P&ID-001 TB7:31
REQ
FLOW CUMULATIVE
REQ C871-P&ID-001 TB7:33

C871-P&ID-001 TB7:35
C871-P&ID-001 TB7:37
C871-P&ID-001 TB7:39 DONE
C871-P&ID-001 TB7:41 DONE
C871-P&ID-001 TB7:43 DONE
C871-P&ID-001 TB7:45 DONE
C871-P&ID-001 TB7:47
C871-P&ID-001 TB7:49
C871-P&ID-001 TB7:51
TB9:43
TB9:45
C871-P&ID-001 TB7:53 DONE
C871-P&ID-001 TB7:55 DONE
C871-P&ID-001 TB7:57 DONE
C871-P&ID-001 TB7:59 DONE
C871-P&ID-001 TB7:61 DONE
C871-P&ID-001 TB7:63 DONE
C871-P&ID-001 TB8:1 DONE
C871-P&ID-001 TB8:3 DONE
C871-P&ID-001 TB8:5 DONE
C871-P&ID-001 TB8:7 DONE
C871-P&ID-001 TB8:9 DONE
C871-P&ID-001 TB8:11 DONE
C871-P&ID-001 TB8:13 DONE
C871-P&ID-001 TB8:15 DONE
C871-P&ID-001 TB8:17 DONE
C871-P&ID-001 TB8:19 DONE
C871-P&ID-001 TB8:21 DONE
C871-P&ID-001 TB8:23 DONE
C871-P&ID-001 TB8:25
C871-P&ID-001 TB8:27
C871-P&ID-001 TB8:29
C871-P&ID-001 TB8:31
C871-P&ID-001 TB8:33
C871-P&ID-001 TB8:35
C861-P&ID-001 TB4:9
C861-P&ID-001 TB8:37 DONE
C871-P&ID-001 TB5:1
C871-P&ID-001 TB5:2
DIGITAL OUTPUT TO BE
POTENTIAL C871-P&ID-001 TB12:1&2
TYPE(230VAC)
C871-P&ID-001 TB5:3 DONE
C871-P&ID-001 TB5:4 DONE
C871-P&ID-001 TB5:5 DONE
C871-P&ID-001 TB5:36 DONE
TB14:1
C871-P&ID-001 TB12:3&4 DONE

C871-P&ID-001 TB8:41
DONE
C871-P&ID-001 TB8:43 DONE
C871-P&ID-001 TB4:11
C871-P&ID-001 TB5:6 DONE
C871-P&ID-001 TB5:7 DONE
C871-P&ID-001 TB5:8 DONE
C871-P&ID-001 TB5:37 DONE
TB14:2
C871-P&ID-001 TB12:5&6 DONE

C871-P&ID-001 TB8:47
DONE
C871-P&ID-001 TB8:49 DONE
C871-P&ID-001 TB4:13
C871-P&ID-001 TB5:9 DONE
C871-P&ID-001 TB5:10 DONE
C871-P&ID-001 TB5:11 DONE
C871-P&ID-001 TB12:7&8
C871-P&ID-001 TB5:12 DONE
C871-P&ID-001 TB5:13 DONE
C871-P&ID-001 TB5:14 DONE
C871-P&ID-001 TB12:9&10

C871-P&ID-001 TB5:15 DONE


C871-P&ID-001 TB5:16 DONE
C871-P&ID-001 TB5:17 DONE
C871-P&ID-001 TB12:11&12 DONE
C871-P&ID-001 TB5:18 DONE
C871-P&ID-001 TB5:19 DONE
C871-P&ID-001 TB5:20 DONE
C871-P&ID-001 TB12:13&14 DONE
C871-P&ID-001 TB5:21 DONE
C871-P&ID-001 TB5:22 DONE
C871-P&ID-001 TB5:23 DONE
C871-P&ID-001 TB12:15&16 DONE

C871-P&ID-001 TB8:51
DONE
C871-P&ID-001 TB8:53 DONE
C871-P&ID-001 TB4:15
C871-P&ID-001 TB5:24 DONE
C871-P&ID-001 TB5:25 DONE
C871-P&ID-001 TB5:26 DONE
C871-P&ID-001 TB12:17&18 DONE
C871-P&ID-001 TB8:55
DONE
C871-P&ID-001 TB8:57 DONE
C871-P&ID-001 TB4:1
C871-P&ID-001 TB5:27 DONE
C871-P&ID-001 TB5:28 DONE
C871-P&ID-001 TB5:29 DONE
C871-P&ID-001 TB12:19&20 DONE

C871-P&ID-001 TB8:59
DONE
C871-P&ID-001 TB8:61 DONE
C871-P&ID-001 TB4:3
C871-P&ID-001 TB5:30 DONE
C871-P&ID-001 TB5:31 DONE
C871-P&ID-001 TB5:32 DONE
C871-P&ID-001 TB12:21&22 DONE
C871-P&ID-001 TB5:33 DONE
C871-P&ID-001 TB5:34 DONE
C871-P&ID-001 TB5:35 DONE
C871-P&ID-001 TB12:23&24 DONE
E100615008 TB5:42 DONE
E100615008 TB5:43 DONE
E100615008 TB5:44 DONE
E100615008 TB5:29&30 DONE

E100615008 TB8:63
DONE
E100615008 TB9:1 DONE
E100615008 TB4:5
E100615008 TB5:45 DONE
E100615008 TB5:46 DONE
DIGITAL OUTPUT TO BE
POTENTIAL E100615008 TB12:31&32 DONE
TYPE(230VAC)
E100615008 TB5:47 DONE
E100615008 TB5:48 DONE
DIGITAL OUTPUT TO BE
POTENTIAL E100615008 TB12:33&34 DONE
TYPE(230VAC)
E100615008 TB5:49 DONE
E100615008 TB5:50 DONE
E100615008 TB5:51 DONE
E100615008 TB12:35&36 DONE

E100615008 TB9:3
DONE
E100615008 TB9:5 DONE
E100615008 TB4:7
E100615008 TB5:52 DONE
E100615008 TB5:53 DONE
DIGITAL OUTPUT TO BE
POTENTIAL E100615008 TB12:37&38 DONE
TYPE(230VAC)
E100615008 TB5:54 DONE
E100615008 TB5:55 DONE
DIGITAL OUTPUT TO BE
POTENTIAL E100615008 TB12:39&40 DONE
TYPE(230VAC)
E100615008 TB5:56 DONE
E100615008 TB5:57 DONE
E100615008 TB5:58 DONE
E100615008 TB12:41&42 DONE
E100615008 TB5:59 DONE
E100615008 TB5:60 DONE
E100615008 TB5:61 DONE
E100615008 TB12:43&44 DONE
E100615008 TB5:62 DONE
E100615008 TB5:63 DONE
E100615008 TB5:64 DONE
E100615008 TB12:45&46 DONE
E100615008 TB6:1
E100615008 TB6:2 DONE
E100615008 TB6:3 DONE
E100615008 TB12:47&48 DONE
HPSL/CCS/PID-003 TB6:16 DONE
HPSL/CCS/PID-003 TB6:17 DONE
HPSL/CCS/PID-003 TB6:18 DONE
HPSL/CCS/PID-003 TB12:57&58 DONE
E100615008 TB6:23
E100615008 TB6:24
E100615008 TB6:25
E100615008 TB6:26
E100615008 TB6:27
E100615008 TB12:63&64
E100615008 TB13:1&2
C871-P&ID-001 TB6:28 DONE
C871-P&ID-001 TB6:29 DONE
C871-P&ID-001 TB6:30 DONE
C871-P&ID-001 TB13:3&4 DONE
C871-P&ID-001 TB6:31 DONE
C871-P&ID-001 TB6:32 DONE
C871-P&ID-001 TB6:33 DONE
C871-P&ID-001 TB13:5&6 DONE
C871-P&ID-001 TB6:59 DONE
C871-P&ID-001 TB6:60 DONE
C871-P&ID-001 TB6:61 DONE
C871-P&ID-001 TB13:17&18 DONE
C871-P&ID-001 TB6:34 DONE
C871-P&ID-001 TB6:35 DONE
C871-P&ID-001 TB6:36 DONE
C871-P&ID-001 TB13:7&8 DONE
C871-P&ID-001 TB6:37 DONE
C871-P&ID-001 TB6:38 DONE
C871-P&ID-001 TB6:39 DONE
C871-P&ID-001 TB13:9&10 DONE
C871-P&ID-001 TB6:53 DONE
C871-P&ID-001 TB6:54 DONE
C871-P&ID-001 TB6:55 DONE
C871-P&ID-001 TB13:13&14 DONE
C861-P&ID-001 TB9:7
DONE
C861-P&ID-001 TB9:9 DONE
C861-P&ID-001 TB9:11 DONE
TB9:13 DONE
TB9:15 DONE
HPSL/CCS/PID-003 TB9:17
DONE
HPSL/CCS/PID-003 TB9:19
DONE
E100615008 TB6:40 DONE
E100615008 TB6:41 DONE
E100615008 TB6:42 DONE
E100615008 TB6:43 DONE
E100615008 TB6:44
E100615008 TB6:45 DONE
E100615008 TB6:46 DONE
E100615008 TB6:47 DONE
E100615008 TB6:48 DONE
E100615008 TB6:49 DONE
E100615008 TB9:21

TB9:23
DONE
E100615008 TB9:25
DONE
E100615008 TB9:27
DONE
E100615008 TB9:29
DONE
E100615008 TB9:47
DONE
TB9:49
DONE
E100615008 TB9:31
DONE
HI ALARM 140 DEG C E100615008 TB9:33 DONE
HI ALARM 140 DEG C E100615008 TB9:35 DONE
HI ALARM 140 DEG C E100615008 TB9:37 DONE
HI ALARM 140 DEG C E100615008 TB9:39 DONE
E100615008 TB9:41 DONE
TB14.3
TB14.4
TB14.10
TB14.11
TB14.12
TB14.13
TB14.14
TB14.15
REMARK

FIELD SIDE
INTERMEDI
INSTU ATE
TAG COM CABLE CABLE CONNECTIO CABLE
SLNO DESCRIPTION NAME DI DO AI AO M CABLE FROM TAG CABLE TYPE LENGTH N CABLE TO CABLE TYPE LENGTH

CABLE
TAG NO OF DESTINATI NO. OF
SOURCE DETAILS RUN JB TAG ON RUN
1 RAW WTR PMP O/L HDR PRESS PT01 1 FIELD AC101 1 1PX1SQMM JBA109 C871-P&ID-001
2 MAIN CWP O/L HDR PRESS PT02 1 FIELD AC102 1 1PX1SQMM 20 JBA101A
3 IND FUR CWP O/L HDR PRESS PT03 1 FIELD AC103 1 1PX1SQMM 20 JBA101A
4 FUR CWP O/L HDR PRESS PT04 1 FIELD AC104 1 1PX1SQMM 20 JBA101B
5 EMG CWP O/L HDR PRESS PT05 1 FIELD AC105 1 1PX1SQMM 20 JBA101B CR 1 14P 80
6 FUR CW I/L MANIFOLD PRESS PT06 1 FIELD AC106 1 1PX1SQMM 20 C871-P&ID-001

7 COOLING WTR TNK LVL LT01 2 FIELD 2 2CX1.5SQMM 30 JBD101 CR 1 14P 80


8 DM WTR TNK LVL LT02 1 FIELD AC107 1 1PX1SQMM 20 JBA101B CR 1 14P 80
9 EMG DM WTR TANK LVL LT03 1 FIELD AC108 1 1PX1SQMM 20 JBA101B CR 1 14P 80

10 RAW WTR FLO TO SOFTNER FT01A 1 FIELD AC109 1 1PX1SQMM 20 JBA109

11 SOFTNER O/L FLO TO COOLING TWR FT01B 1 FIELD AC110 1 1PX1SQMM 20 JBA101B

12 COOLING WTR FLO TO WCD FT02A 1 FIELD AC111 1 1PX1SQMM 20

13 COOLING WTR FLO TO WCD FT02B 1 FIELD AC112 1 1PX1SQMM 20

14 COOLING WTR FLO TO CNVRTR BRG FT02C 1 FIELD AC113 1 1PX1SQMM 20 JBA105A

15 COOLING WTR FLO TO HT EXCHANGER FT03A 1 FIELD AC114 1 1PX1SQMM 20 JBA101A CR 1 14P 80

16 COOLING WTR FLO TO HT EXCHANGER FT03B 1 FIELD AC115 1 1PX1SQMM 20 JBA101A CR 1 14P 80

17 COOLING WTR FLO TO IND FUR COIL FT04 1 FIELD AC116 1 1PX1SQMM 20 JBA101B CR 1 14P 80
18 WTR FLO TO FIRE EXTINGUISHER FT05 1 FIELD AC117 1 1PX1SQMM 20 C871-P&ID-001
19 RAW WTR CWP O/L HDR TEMP TE01 1 FIELD AC118 1 1PX1SQMM 20 JBA109 C871-P&ID-001
20 MAIN CWP O/L HDR TEMP TE02 1 FIELD AC119 1 1PX1SQMM 20 JBA101A CR 1 14P 80
21 IND FUR CWP O/L HDR TEMP TE03 1 FIELD AC120 1 1PX1SQMM 20 JBA101A CR 1 14P 80
22 FUR CWP O/L HDR TEMP TE04 1 FIELD AC121 1 1PX1SQMM 20 JBA101B CR 1 14P 80
23 EMG CWP O/L HDR TEMP TE05 1 FIELD AC122 1 1PX1SQMM 20 JBA101B CR 1 14P 80
24 IND FUR I/L MANIFOLD WTR TEMP TE06 1 FIELD AC123 1 1PX1SQMM 20 JBA101B CR 1 14P 80
25 FUR SHELL 1 CW O/L TEMP TE07 1 FIELD AC124 1 1PX1SQMM 20 C871-P&ID-001
26 FUR SHELL 2 CW O/L TEMP TE08 1 FIELD AC125 1 1PX1SQMM 20 C871-P&ID-001
27 WCD(SEC-1) O/L COOLING WTR TEMP1 TE09 1 FIELD AC126 1 1PX1SQMM 20 JBA105A CR 1 14P 35
28 WCD(SEC-1) O/L COOLING WTR TEMP2 TE10 1 FIELD AC127 1 1PX1SQMM 20 JBA105A CR 1 14P 35
29 WCD(SEC-2) O/L COOLING WTR TEMP1 TE11 1 FIELD AC128 1 1PX1SQMM 20 JBA105A CR 1 14P 35
30 WCD(SEC-2) O/L COOLING WTR TEMP2 TE12 1 FIELD AC129 1 1PX1SQMM 20 JBA105A CR 1 14P 35
31 WCD(SEC-3) O/L COOLING WTR TEMP1 TE13 1 FIELD AC130 1 1PX1SQMM 20 JBA105A CR 1 14P 35
32 WCD(SEC-3) O/L COOLING WTR TEMP2 TE14 1 FIELD AC131 1 1PX1SQMM 20 JBA105A CR 1 14P 35
33 WCD(SEC-4) O/L COOLING WTR TEMP1 TE15 1 FIELD AC132 1 1PX1SQMM 20 JBA105A CR 1 14P 35
34 WCD(SEC-4) O/L COOLING WTR TEMP2 TE16 1 FIELD AC133 1 1PX1SQMM 20 JBA105A CR 1 14P 35
35 WCD(SEC-5) O/L COOLING WTR TEMP1 TE17 1 FIELD AC134 1 1PX1SQMM 20 JBA105A CR 1 14P 35
36 WCD(SEC-5) O/L COOLING WTR TEMP2 TE18 1 FIELD AC135 1 1PX1SQMM 20 JBA105A CR 1 14P 35
37 WCD(SEC-6) O/L COOLING WTR TEMP1 TE19 1 FIELD AC136 1 1PX1SQMM 20 JBA105B CR 1 14P 25
38 WCD(SEC-6) O/L COOLING WTR TEMP2 TE20 1 FIELD AC137 1 1PX1SQMM 20 JBA105B CR 1 14P 25
39 WCD(SEC-7) O/L COOLING WTR TEMP1 TE21 1 FIELD AC138 1 1PX1SQMM 20 JBA105B CR 1 14P 25
40 WCD(SEC-7) O/L COOLING WTR TEMP2 TE22 1 FIELD AC139 1 1PX1SQMM 20 JBA105B CR 1 14P 25
41 WCD(SEC-8) O/L COOLING WTR TEMP1 TE23 1 FIELD AC140 1 1PX1SQMM 20 JBA105B CR 1 14P 25
42 WCD(SEC-8) O/L COOLING WTR TEMP2 TE24 1 FIELD AC141 1 1PX1SQMM 20 JBA105B CR 1 14P 25
43 WCD(SEC-9) O/L COOLING WTR TEMP1 TE25 1 FIELD AC142 1 1PX1SQMM 20 JBA105B CR 1 14P 25
44 WCD(SEC-9) O/L COOLING WTR TEMP2 TE26 1 FIELD AC143 1 1PX1SQMM 20 JBA105B CR 1 14P 25
45 WCD COM CW O/L TEMP1 TE27 1 FIELD AC144 1 1PX1SQMM 20 JBA105A CR 1 14P 35
46 WCD COM CW O/L TEMP2 TE28 1 FIELD AC145 1 1PX1SQMM 20 JBA105B CR 1 14P 25
47 CNVRTR BRG CW O/L TEMP TE29 1 FIELD AC146 1 1PX1SQMM 20 C871-P&ID-001
48 DM SKID-1 HT EX CW O/L TEMP TE30 1 FIELD AC147 1 1PX1SQMM 20 C871-P&ID-001
49 DM SKID-2 HT EX CW O/L TEMP TE31 1 FIELD AC148 1 1PX1SQMM 20 C871-P&ID-001
50 FUR CW HT EX O/L TEMP TE32 1 FIELD AC149 1 1PX1SQMM 20 C871-P&ID-001
51 CONDENSATE DRAIN VLV(CDCV-1) CDCV-1 1 FIELD AC150 1 JBA106 C861-P&ID-001
52 1 FIELD AC151 1 3PX1SQMM 15 JBA106 C861-P&ID-001
53 DM WTR LINE VLV(SOV-3) SOV-3 1 FIELD JBD101 CR 1 14P 80
54 1 FIELD 5CX1.5SQMM 15 JBD101 CR 1 14P 80

55 1 FIELD 2CX1.5SQMM 15 JBD101 CR 1 14P 80


56 COOLING TOWER FAN 1 CTF-1 1 DRV PNL MAIN PLC C871-P&ID-001
57 1 DRV PNL MAIN PLC C871-P&ID-001
58 1 DRV PNL 5CX1.5SQMM 10 MAIN PLC C871-P&ID-001
59 1 FIELD 2CX1.5SQMM 20 JBD101 MAIN PLC 1 14P 80
60 1 DRV PNL 2CX1.5SQMM 10 MAIN PLC C871-P&ID-001
61 1 DRV PNL MAIN PLC C871-P&ID-001
62 1 DRV PNL MAIN PLC C871-P&ID-001
63 1 DRV PNL AC152 1 3PX1SQMM 10 MAIN PLC C871-P&ID-001
64 COOLING TOWER FAN 2 CTF-2 1 DRV PNL MAIN PLC C871-P&ID-001
65 1 DRV PNL MAIN PLC C871-P&ID-001
66 1 DRV PNL 5CX1.5SQMM 10 MAIN PLC C871-P&ID-001
67 1 FIELD 2CX1.5SQMM 30 JBD101 MAIN PLC 1 14P 80
68 1 DRV PNL 2CX1.5SQMM 10 MAIN PLC C871-P&ID-001
69 1 DRV PNL MAIN PLC C871-P&ID-001
70 1 DRV PNL MAIN PLC C871-P&ID-001
71 1 DRV PNL AC153 1 3PX1SQMM 10 MAIN PLC C871-P&ID-001
72 FUR. COOLING PUMP-1 FCP-1 1 MCC PNL MAIN PLC C871-P&ID-001
73 1 MCC PNL MAIN PLC C871-P&ID-001
74 1 MCC PNL 5CX1.5SQMM 20 MAIN PLC C871-P&ID-001
75 1 MCC PNL 2CX1.5SQMM 20 MAIN PLC C871-P&ID-001
76 FUR. COOLING PUMP-2 FCP-2 1 MCC PNL MAIN PLC C871-P&ID-001
77 1 MCC PNL MAIN PLC C871-P&ID-001
78 1 MCC PNL 5CX1.5SQMM 20 MAIN PLC C871-P&ID-001
79 1 MCC PNL 2CX1.5SQMM 20 MAIN PLC C871-P&ID-001
80 EMG COOLING WTR PUMP-1 EWP-1 1 MCC PNL MAIN PLC C871-P&ID-001
81 1 MCC PNL MAIN PLC C871-P&ID-001
82 1 MCC PNL 5CX1.5SQMM 20 MAIN PLC C871-P&ID-001
83 1 MCC PNL 2CX1.5SQMM 20 MAIN PLC C871-P&ID-001
84 EMG COOLING WTR PUMP-2 EWP-2 1 MCC PNL MAIN PLC C871-P&ID-001
85 1 MCC PNL MAIN PLC C871-P&ID-001
86 1 MCC PNL 5CX1.5SQMM 20 MAIN PLC C871-P&ID-001
87 1 MCC PNL 2CX1.5SQMM 20 MAIN PLC C871-P&ID-001
88 COOLING WTR PUMP 1 CWP-1 1 DRV PNL MAIN PLC C871-P&ID-001
89 1 DRV PNL MAIN PLC C871-P&ID-001
90 1 DRV PNL 5CX1.5SQMM 10 MAIN PLC C871-P&ID-001
91 1 DRV PNL 2CX1.5SQMM 10 MAIN PLC C871-P&ID-001
92 1 DRV PNL MAIN PLC C871-P&ID-001
93 1 DRV PNL MAIN PLC C871-P&ID-001
94 1 DRV PNL AC154 1 3PX1SQMM 10 MAIN PLC C871-P&ID-001
95 COOLING WTR PUMP 2 CWP-2 1 DRV PNL MAIN PLC C871-P&ID-001
96 1 DRV PNL MAIN PLC C871-P&ID-001
97 1 DRV PNL 5CX1.5SQMM 10 MAIN PLC C871-P&ID-001
98 1 DRV PNL 2CX1.5SQMM 10 MAIN PLC C871-P&ID-001
99 1 DRV PNL MAIN PLC C871-P&ID-001
100 1 DRV PNL MAIN PLC C871-P&ID-001
101 1 DRV PNL AC155 1 3PX1SQMM 10 MAIN PLC C871-P&ID-001
102 COOLING WTR PUMP 3 CWP-3 1 DRV PNL MAIN PLC C871-P&ID-001
103 1 DRV PNL MAIN PLC C871-P&ID-001
104 1 DRV PNL 1 5CX1.5SQMM 10 MAIN PLC C871-P&ID-001
105 1 DRV PNL 1 2CX1.5SQMM 10 MAIN PLC C871-P&ID-001
106 1 DRV PNL MAIN PLC C871-P&ID-001
107 1 DRV PNL MAIN PLC C871-P&ID-001
108 1 DRV PNL AC156 1 3PX1SQMM 10 MAIN PLC C871-P&ID-001
109 INDUCTION COOLING WTR PUMP 1 ICWP-1 1 MCC PNL MAIN PLC C871-P&ID-001
110 1 MCC PNL MAIN PLC C871-P&ID-001
111 1 MCC PNL 1 5CX1.5SQMM 20 MAIN PLC C871-P&ID-001
112 1 MCC PNL 1 2CX1.5SQMM 20 MAIN PLC C871-P&ID-001
113 INDUCTION COOLING WTR PUMP 2 ICWP-2 1 MCC PNL MAIN PLC C871-P&ID-001
114 1 MCC PNL MAIN PLC C871-P&ID-001
115 1 MCC PNL 5CX1.5SQMM 20 MAIN PLC C871-P&ID-001
116 1 MCC PNL 2CX1.5SQMM 20 MAIN PLC C871-P&ID-001
117 RAW WTR PUMP 1 RWP-1 1 MCC PNL C871-P&ID-001
118 1 MCC PNL C871-P&ID-001
119 1 MCC PNL 5CX1.5SQMM 20 C871-P&ID-001
120 1 MCC PNL 2CX1.5SQMM 20 C871-P&ID-001
121 RAW WTR PUMP 2 RWP-2 1 MCC PNL C871-P&ID-001
122 1 MCC PNL C871-P&ID-001
123 1 MCC PNL 5CX1.5SQMM 20 C871-P&ID-001
124 1 MCC PNL 2CX1.5SQMM 20 C871-P&ID-001
125 ID FAN-1 ID-1 1 DRV PNL MAIN PLC
126 1 DRV PNL MAIN PLC
127 1 DRV PNL 5CX1.5SQMM 10 MAIN PLC
128 1 DRV PNL 2CX1.5SQMM 10 MAIN PLC
129 1 DRV PNL MAIN PLC
130 1 DRV PNL MAIN PLC
131 1 DRV PNL 3PX1SQMM 10 MAIN PLC
132 ID FAN-1 SUCTION DMPR ID1SD 1 FIELD JBD102 CR 1 14P 75
133 1 FIELD 5CX1.5SQMM 10 JBD102 CR 1 14P 75

134 1 FIELD 2CX1.5SQMM 10 JBD102 CR 1 14P 75


135 ID FAN-1 DISCHRG DMPR ID1DD 1 FIELD JBD102 CR 1 14P 75
136 1 FIELD 5CX1.5SQMM 10 JBD102 CR 1 14P 75

137 1 FIELD 2CX1.5SQMM 10 JBD102 CR 1 14P 75


138 ID FAN-2 ID-2 1 DRV PNL MAIN PLC
139 1 DRV PNL MAIN PLC
140 1 DRV PNL 5CX1.5SQMM 10 MAIN PLC
141 1 DRV PNL 2CX1.5SQMM 10 MAIN PLC
142 1 DRV PNL MAIN PLC
143 1 DRV PNL MAIN PLC
144 1 DRV PNL 3PX1SQMM 10 MAIN PLC
145 ID FAN-2 SUCTION DMPR ID2SD 1 FIELD JBD102 CR 1 14P 75
146 1 FIELD 5CX1.5SQMM 10 JBD102 CR 1 14P 75

147 1 FIELD 2CX1.5SQMM 10 JBD102 CR 1 14P 75


148 ID FAN-2 DISCHRG DMPR ID2DD 1 FIELD JBD102 CR 1 14P 75
149 1 FIELD 5CX1.5SQMM 10 JBD102 CR 1 14P 75

150 1 FIELD 2CX1.5SQMM 10 JBD102 CR 1 14P 75


151 HEAT EXCAHNGER CL FAN 1 HXCF-1 1 MCC PNL MAIN PLC
152 1 MCC PNL MAIN PLC
153 1 MCC PNL 5CX1.5SQMM 20 MAIN PLC
154 1 MCC PNL 2CX1.5SQMM 20 MAIN PLC
155 HEAT EXCAHNGER CL FAN 2 HXCF-2 1 MCC PNL MAIN PLC
156 1 MCC PNL MAIN PLC
157 1 MCC PNL 5CX1.5SQMM 20 MAIN PLC
158 1 MCC PNL 2CX1.5SQMM 20 MAIN PLC
159 HEAT EXCAHNGER CL FAN 3 HXCF-3 1 MCC PNL MAIN PLC
160 1 MCC PNL MAIN PLC
161 1 MCC PNL 5CX1.5SQMM 20 MAIN PLC
162 1 MCC PNL 2CX1.5SQMM 20 MAIN PLC
163 HEAT EXCAHNGER CL FAN 4 HXCF-4 1 MCC PNL MAIN PLC
164 1 MCC PNL MAIN PLC
165 1 MCC PNL 5CX1.5SQMM 20 MAIN PLC
166 1 MCC PNL 2CX1.5SQMM 20 MAIN PLC
167 WTR SOFTNER PUMP SOFP-1 1 MCC PNL MAIN PLC
168 1 MCC PNL MAIN PLC
169 1 MCC PNL 5CX1.5SQMM 20 MAIN PLC
170 1 MCC PNL 2CX1.5SQMM 20 MAIN PLC
171 MATERIAL FEED VIBROFEEDER VF-1 1 MCC PNL MAIN PLC
172 1 MCC PNL MAIN PLC
173 1 MCC PNL 5CX1.5SQMM 20 MAIN PLC
174 1 MCC PNL 2CX1.5SQMM 20 MAIN PLC
175 HI RISE CONVEYOR BELT HRC-1 1 MCC PNL MAIN PLC
176 1 MCC PNL MAIN PLC
177 1 MCC PNL 5CX1.5SQMM 20 MAIN PLC
178 1 MCC PNL 2CX1.5SQMM 20 MAIN PLC
179 SHUTTLE CONVEYOR BELT STC-1 1 MCC PNL MAIN PLC
180 1 MCC PNL MAIN PLC
181 1 MCC PNL 5CX1.5SQMM 20 MAIN PLC
182 1 MCC PNL 2CX1.5SQMM 20 MAIN PLC
183 AIR COMPRESSOR MTR COMP-1 1 COMP PNL MAIN PLC
184 1 COMP PNL MAIN PLC
185 1 COMP PNL 5CX1.5SQMM 20 MAIN PLC
186 1 COMP PNL 2CX1.5SQMM 20 MAIN PLC
187 COMP LINE VLV SOV-1 1 COMP PNL JBD110 MAIN PLC
188 1 COMP PNL 5CX1.5SQMM 20 JBD110 MAIN PLC

189 1 COMP PNL 2CX1.5SQMM 20 JBD110


190 COMP BYPASS VLV SOV-2 1 COMP PNL JBD110
191 1 COMP PNL 5CX1.5SQMM 20 JBD110

192 1 COMP PNL 2CX1.5SQMM 20 JBD110


193 AIR DILUTION DMPR ADD-1 1 FIELD JBD103A CR 1 14P 65
194 1 FIELD JBD103A CR 1 14P 65
195 1 FIELD JBD103A CR 1 14P 65
196 1 FIELD JBD103A CR 1 14P 65
197 1 FIELD 7CX1.5SQMM 15 JBD103A CR 1 14P 65
198 1 FIELD 2CX1.5SQMM 15 JBD103A CR 1 14P 65
199 1 FIELD 2CX1.5SQMM 15 JBD103A CR 1 14P 65
200 PWR CABLE FOR AIR DILUTION DMPR MCC PNL 1 3CX2.5SQMM MOTOR OF ADD-1
201 DM SKID-1 PUMP-1 IPCW1P1 1 MCC PNL MAIN PLC C871-P&ID-001
202 1 MCC PNL MAIN PLC C871-P&ID-001
203 1 MCC PNL 5CX1.5SQMM 20 MAIN PLC C871-P&ID-001
204 1 MCC PNL 2CX1.5SQMM 20 MAIN PLC C871-P&ID-001
205 DM SKID-1 PUMP-2 IPCW1P2 1 MCC PNL MAIN PLC
206 1 MCC PNL MAIN PLC
207 1 MCC PNL 5CX1.5SQMM 20 MAIN PLC
208 1 MCC PNL 2CX1.5SQMM 20 MAIN PLC
209 DM SKID-2 PUMP-1 IPCW2P1 1 MCC PNL MAIN PLC C871-P&ID-001
210 1 MCC PNL MAIN PLC C871-P&ID-001
211 1 MCC PNL 5CX1.5SQMM 20 MAIN PLC C871-P&ID-001
212 1 MCC PNL 2CX1.5SQMM 20 MAIN PLC C871-P&ID-001
213 DM SKID-2 PUMP-2 IPCW2P2 1 MCC PNL MAIN PLC
214 1 MCC PNL MAIN PLC
215 1 MCC PNL 5CX1.5SQMM 20 MAIN PLC
216 1 MCC PNL 2CX1.5SQMM 20 MAIN PLC
217 HYD SKID-1 PUMP-1 HYD1P1 1 MCC PNL MAIN PLC C871-P&ID-001
218 1 MCC PNL MAIN PLC C871-P&ID-001
219 1 MCC PNL 5CX1.5SQMM 20 MAIN PLC C871-P&ID-001
220 1 MCC PNL 2CX1.5SQMM 20 MAIN PLC C871-P&ID-001
221 HYD SKID-1 PUMP-2 HYD1P2 1 MCC PNL MAIN PLC
222 1 MCC PNL MAIN PLC
223 1 MCC PNL 5CX1.5SQMM 20 MAIN PLC
224 1 MCC PNL 2CX1.5SQMM 20 MAIN PLC
225 HYD SKID-2 PUMP-1 HYD2P1 1 MCC PNL MAIN PLC C871-P&ID-001
226 1 MCC PNL MAIN PLC C871-P&ID-001
227 1 MCC PNL 5CX1.5SQMM 20 MAIN PLC C871-P&ID-001
228 1 MCC PNL 2CX1.5SQMM 20 MAIN PLC C871-P&ID-001
229 HYD SKID-2 PUMP-2 HYD2P2 1 MCC PNL MAIN PLC
230 1 MCC PNL MAIN PLC
231 1 MCC PNL 5CX1.5SQMM 20 MAIN PLC
232 1 MCC PNL 2CX1.5SQMM 20 MAIN PLC
233 O2 DETECTOR 1 FIELD 1PX1SQMM 10 JBA106 CR 1 14P 40
234 GAS MIXING STATION I/L STEAM FLOW FT203 1 FIELD 1PX1SQMM 10 JBA106 CR 1 14P 40
235 GAS MIXING STATION I/L STEAM PRESS PT205 1 FIELD 1PX1SQMM 10 JBA106 CR 1 14P 40
236 GAS MIXING STATION I/L STEAM TEMP TE205 1 FIELD 1PX1SQMM 10 JBA106 CR 1 14P 40
237 GAS MIXING STATION I/L OXYGEN FLOW FT400 1 FIELD 1PX1SQMM 10 JBA106 CR 1 14P 40
238 GAS MIXING STATION I/L ARGON FLOW FT100 1 FIELD 1PX1SQMM 10 JBA106 CR 1 14P 40
239 INSTRUMENT AIR HEADER PRESSURE PT303A 1 FIELD 1PX1SQMM 5 JBA107 CR 1 14P 20
240 SERVICE AIR HEADER PRESSURE PT303B 1 FIELD 1PX1SQMM 5 JBA107 CR 1 14P 20
241 DIFFERENTIAL PRESS SW BF CMBR-1 DPS01 1 FIELD 1PX1SQMM 10 JBD103A CR 1 14P 65
242 DIFFERENTIAL PRESS SW BF CMBR-2 DPS02 1 FIELD 1PX1SQMM 10 JBD103A CR 1 14P 65
243 DIFFERENTIAL PRESS SW BF CMBR-3 DPS03 1 FIELD 1PX1SQMM 10 JBD103A CR 1 14P 65
244 DIFFERENTIAL PRESS SW BF CMBR-4 DPS04 1 FIELD 1PX1SQMM 10 JBD103A CR 1 14P 65
245 DIFFERENTIAL PRESS SW BF DPS05 1 FIELD 1PX1SQMM 10 JBD103A CR 1 14P 65
246 BF BNKR-1 LVL SW LSH01 1 FIELD 1PX1SQMM 10 JBD103A CR 1 14P 65
247 BF BNKR-2 LVL SW LSH02 1 FIELD 1PX1SQMM 10 JBD103A CR 1 14P 65
248 BF BNKR-3 LVL SW LSH02 1 FIELD 1PX1SQMM 10 JBD103A CR 1 14P 65
249 BF BNKR-4 LVL SW LSH04 1 FIELD 1PX1SQMM 10 JBD103A CR 1 14P 65
250 HET EX BNKR LVL SW LSH05 1 FIELD 1PX1SQMM 10 JBD103A CR 1 14P 65
251 CCS STACK PARTICULATE MONITOR SPM02 1 FIELD 1PX1SQMM 25 JBA102 CR 1 14P 75
252 FLUE GAS TEMP-1 AT WCD TE501 1 FIELD 1PX1SQMM 15 JBA105A CR 1 14P 30
253 FLUE GAS TEMP-2 AT WCD TE502 1 FIELD 1PX1SQMM 15 JBA105A CR 1 14P 30
254 FLUE GAS TEMP-3 AT WCD TE503 1 FIELD 1PX1SQMM 15 JBA105B CR 1 14P 25
255 FLUE GAS TEMP-4 AT WCD TE504 1 FIELD 1PX1SQMM 15 JBA105B CR 1 14P 25
256 FLUE GAS TEMP FD COOLER I/L TE505 1 FIELD 1PX1SQMM 12 JBA105C
257 FLUE GAS TEMP FD COOLER O/L TE506 1 FIELD 1PX1SQMM 12 JBA103 CR 1 14P 65
258 FLUE GAS TEMP FD COOLER O/L TE507 1 FIELD 1PX1SQMM 12 JBA103 CR 1 14P 65
259 FLUE GAS TEMP FD COOLER O/L TE508 1 FIELD 1PX1SQMM 12 JBA103 CR 1 14P 65
260 FLUE GAS TEMP BF I/L TE509 1 FIELD 1PX1SQMM 10 JBA102 CR 1 14P 75
261 FLUE GAS TEMP BF O/L TE510 1 FIELD 1PX1SQMM 10 JBA102 CR 1 14P 75
262
263 CARBON % FROM C744 RS232
264 MOLTEN MTL SMPL TEMP 1 FIELD 1PX1SQMM 35 CNVRTR PLC
265 METAL LOAD FRM WEIGH BRDG 1 FIELD 1PX1SQMM 100 CNVRTR PLC
266 LADLE CAR-1 LIMIT SW 1 FIELD CNVRTR PLC
267 LADLE CAR-2 LIMIT SW 1 FIELD 5CX1.5SQMM 100 CNVRTR PLC
268 I/P TO CONVERTER PLC
269 I/P TO BATCHING PLC
270 I/P TO CONVERTER MCC PNL
271 I/P TO CONVERTER GAS MIXING PLC PANEL
272 I/P FROM TRANSFORMER BRKERS
273 I/P FROM INDUCTION FURNACE PANEL
274 I/P FROM PRDS SYSTEM TO DCS
275 I/P FROM DUST MONITORS TO CPP
276
277
278 POWER SUPPLY CONNECTION

CORE
CABLE CABLE CABLE TERMINAL TAG
279 EQUIPMENT PS TYPE ACDB DETAILS TYPE LENGTH CODE DETAILS DETAILS
280 MCB ITP OTP
281 CARBON ANALYSER & PHYSICAL BALANCE 230VAC 2P 32A 3CX2.5SQMM(CU)
282 DUST MONITOR 230VAC 2P 2A 3CX1.5SQMM(CU)
283 ETHERNET SWITCH 230VAC 2P 6A 3CX1.5SQMM(CU)
284 BATCHING SYSTEM PANEL 415VAC 4CX10SQMM
285 BATCHING SYSTEM PANEL 230VAC 2P 6A 3CX1.5SQMM(CU)
286 CONVERTER PLC PANEL 230VAC 2P 6A 3CX1.5SQMM(CU)
287 INTEGRATED PLC PANEL 230VAC 2P 10A 3CX2.5SQMM(CU)
288 CONTROL DESK 230VAC 2P 16A 3CX2.5SQMM(CU)
289 INDUCTION FURNACE PLC PANEL 230VAC 2P 6A 3CX1.5SQMM(CU)
290 BAG FILTER CONTROL PANEL 415VAC
291 BAG FILTER CONTROL PANEL 230VAC 2P 2A 3CX1.5SQMM(CU)
292 LADLE WEIGH BRIDGE 230VAC 2P 2A 3CX1.5SQMM(CU)
293 MOLTEN METAL SAMPLE TEMP SYSTEM 230VAC 2P 2A 3CX1.5SQMM(CU)
294 GAS MIXING PLC PANEL 230VAC 2P 6A 3CX1.5SQMM(CU)
295 SPARE 230VAC 2P 2A
296 SPARE 230VAC 2P 6A
297 SPARE 230VAC 2P 16A
298
299 EARTHING DETAILS
300 INDUCTION FURNACE
301 PLC SYSTEM
302 NEAR WEIGH BRIDGE
303
304
305
306
307
308
309
310
311
312 BATCHING SYSTEM CABLE SCHEDULE
313
314 SUPPLY TO VIBROFEEDER-1 BATCHING PNL 3CX2.5SQMM FIELD
315 SUPPLY TO VIBROFEEDER-2 BATCHING PNL 3CX2.5SQMM FIELD
316 SUPPLY TO VIBROFEEDER-3 BATCHING PNL 3CX2.5SQMM FIELD
317 SUPPLY TO VIBROFEEDER-4 BATCHING PNL 3CX2.5SQMM FIELD
318 SUPPLY TO VIBROFEEDER-5 BATCHING PNL 3CX2.5SQMM FIELD
319 SUPPLY TO VIBROFEEDER-6 BATCHING PNL 3CX2.5SQMM FIELD
320 SUPPLY TO VIBROFEEDER-7 BATCHING PNL 3CX2.5SQMM FIELD
321 SUPPLY TO VIBROFEEDER-8 BATCHING PNL 3CX2.5SQMM FIELD
322 SUPPLY TO VIBROFEEDER-9 BATCHING PNL 3CX2.5SQMM FIELD
323 SUPPLY TO VIBROFEEDER-10 BATCHING PNL 3CX2.5SQMM FIELD
324 SUPPLY TO DIS VF-1 BATCHING PNL 3CX2.5SQMM FIELD
325 SUPPLY TO DIS VF-2 BATCHING PNL 3CX2.5SQMM FIELD
326 SUPPLY TO DIS VF-3 BATCHING PNL 3CX2.5SQMM FIELD
327 SUPPLY TO BC-1 BATCHING PNL 3CX2.5SQMM FIELD
328 SUPPLY TO BC-2 BATCHING PNL 3CX2.5SQMM FIELD
329 SUPPLY TO BVF OF BUNKER-1 BATCHING PNL 3CX2.5SQMM FIELD
330 SUPPLY TO BVF OF BUNKER-2 BATCHING PNL 3CX2.5SQMM FIELD
331 SUPPLY TO BVF OF BUNKER-3 BATCHING PNL 3CX2.5SQMM FIELD
332 SUPPLY TO BVF OF BUNKER-4 BATCHING PNL 3CX2.5SQMM FIELD
333 SUPPLY TO BVF OF BUNKER-5 BATCHING PNL 3CX2.5SQMM FIELD
334 SUPPLY TO BVF OF BUNKER-6 BATCHING PNL 3CX2.5SQMM FIELD
335 SUPPLY TO BVF OF BUNKER-7 BATCHING PNL 3CX2.5SQMM FIELD
336 SUPPLY TO BVF OF BUNKER-8 BATCHING PNL 3CX2.5SQMM FIELD
337 SUPPLY TO BVF OF BUNKER-9 BATCHING PNL 3CX2.5SQMM FIELD
338 SUPPLY TO BVF OF BUNKER-10 BATCHING PNL 3CX2.5SQMM FIELD
339 SUPPLY TO BVF OF WF BUNKER-1 BATCHING PNL 3CX2.5SQMM FIELD
340 SUPPLY TO BVF OF WF BUNKER-2 BATCHING PNL 3CX2.5SQMM FIELD
341 SUPPLY TO BVF OF WF BUNKER-3 BATCHING PNL 3CX2.5SQMM FIELD
342 LOAD CELL EXCITATION WF-1 BATCHING PNL 3CX2.5SQMM FIELD
343 LOAD CELL EXCITATION WF-2 BATCHING PNL 3CX2.5SQMM FIELD
344 LOAD CELL EXCITATION WF-3 BATCHING PNL 3CX2.5SQMM FIELD
345
346
347
348
349 INDUCTION FURNACE CABLE SCHEDULE
350 HPSU-1 DIGITAL INPUT TO PLC IND FUR PLC PNL 1 HPSU-1
351 HPSU-1 DIGITAL OUTPUT TO PLC IND FUR PLC PNL 1 HPSU-1
352 HPSU-1 TO PLC (24VDC) IND FUR PLC PNL 1 HPSU-1
353 HPSU-1 ANALOG INPUT FRM PLC IND FUR PLC PNL 7 HPSU-1
354 HPSU-1 ANALOG O/P FRM PLC IND FUR PLC PNL 2 HPSU-1
355 HPSU-2 DIGITAL INPUT TO PLC IND FUR PLC PNL 1 HPSU-2
356 HPSU-2 DIGITAL OUTPUT TO PLC IND FUR PLC PNL 1 HPSU-2
357 HPSU-2 TO PLC (24VDC) IND FUR PLC PNL 1 HPSU-2
358 HPSU-2 ANALOG INPUT FRM PLC IND FUR PLC PNL 7 HPSU-2
359 HPSU-2 ANALOG O/P FRM PLC IND FUR PLC PNL 2 HPSU-2
360 DM1 JB TO DATA MANAGER BOX IND FUR PLC PNL 1 DM1 JB
361 DM2 JB TO DATA MANAGER BOX IND FUR PLC PNL 1 DM2 JB
362 HYD-1 JB TO DATA MANAGER BOX IND FUR PLC PNL 2 HYD-1 JB
363 HYD-2 JB TO DATA MANAGER BOX IND FUR PLC PNL 2 HYD-2 JB
364 CAPRACK-1 TO CRUCIBLE -1 MANIFOLD IND FUR PLC PNL 1 CRU-1 MF
365 PLC PNL TO CRUCIBLE -1 MANIFOLD IND FUR PLC PNL 1 CRU-1 MF
366 PLC PNL TO HPSU-1 CAPRACK(DI) IND FUR PLC PNL 1
367 PLC PNL TO HPSU-1 CAPRACK(DI) IND FUR PLC PNL 2
368 CAPRACK-1 TO CRUCIBLE -2 MANIFOLD IND FUR PLC PNL 1
369 PLC PNL TO CRUCIBLE -2 MANIFOLD IND FUR PLC PNL
370 PLC PNL TO HPSU-2 CAPRACK(DI) IND FUR PLC PNL
371 PLC PNL TO HPSU-2 CAPRACK(DI) IND FUR PLC PNL
372 PLC PNL TO HPSU-1 CAPRACK(DO) IND FUR PLC PNL
373 PLC PNL TO HPSU-1 CAPRACK(DO) IND FUR PLC PNL
374 PLC PNL TO HPSU-2 CAPRACK(DO) IND FUR PLC PNL
375 PLC PNL TO HPSU-2 CAPRACK(DO) IND FUR PLC PNL
376 PLC PNL TO HPSU-1 DM INSTRUMENT(JB-1)(AI) IND FUR PLC PNL
377 PLC PNL TO HPSU-1DM INSTRUMENT(JB-1)(AI) IND FUR PLC PNL
378 PLC PNL TO HPSU-2DM INSTRUMENT(JB-2)(AI) IND FUR PLC PNL
379 PLC PNL TO HPSU-2 DM INSTRUMENT(JB-2)(AI) IND FUR PLC PNL
380 PLC PNL TO HPSU-1 HYD INSTRUMENT(JB-3)(AI) IND FUR PLC PNL
381 PLC PNL TO HPSU-2 HYD INSTRUMENT(JB-4)(AI) IND FUR PLC PNL
382
383
384
385
386 CNVRTR PLC PNL CABLE SCHEDULE
387 CNVRTR PLC PNL TO MAIN PUIPIT CNVRTR PLC PANEL 35
388 CNVRTR PLC PNL TO TAPPING PUIPIT CNVRTR PLC PANEL 35
389 CNVRTR PLC PNL TO LADLE/SLAGPOT CAR CNVRTR PLC PANEL 100
390 OFF GAS HOOD TEMP(COOLING WATER LINE CNVRTR PLC PANEL 1PX1SQMM 15 JBA105A CLU PLC 1 14P 30
391 OFF GAS HOOD TEMP(COOLING WATER LINE CNVRTR PLC PANEL 1PX1SQMM 15 JBA105A CLU PLC 1 14P 30
392 TT003 COOLING LINE CNVRTR PLC PANEL 1PX1SQMM 15 JBA105A CLU PLC 1 14P 30
393 TT004 RETURN LINE CNVRTR PLC PANEL 1PX1SQMM 15 JBA105A CLU PLC 1 14P 30
394 PT003 COOLING LINE CNVRTR PLC PANEL 1PX1SQMM 15 JBA105A CLU PLC 1 14P 30
395 PT004 RETURN LINE CNVRTR PLC PANEL 1PX1SQMM 15 JBA105A CLU PLC 1 14P 30
396 HYDRAULIC MOTOR PR A CNVRTR PLC PANEL 1PX1SQMM 25 JBA106 CLU PLC
397 HYDRAULIC MOTOR PR B CNVRTR PLC PANEL 1PX1SQMM 25 JBA106 CLU PLC 1 14P 40
398 LADLE TRASFER CAR LIMIT SWITCH CNVRTR PLC PANEL
399 FEEDABLE HOPPER INDICATION CNVRTR PLC PANEL
400 PREHEATER PARKED CNVRTR PLC PANEL
401 PREHEATER CONVERTOR CNVRTR PLC PANEL
402 CONVERTOR BRAKE OIL SWITCH CNVRTR PLC PANEL
403 CONVERTOR CALIPER LIMIT SWITCH CNVRTR PLC PANEL
404 OFF GAS COOLING SV003-BG1 CNVRTR PLC PANEL
405 OFF GAS COOLING SV003-BG2
406 OFF GAS COOLING FS001
407 CONVERTOR TILT ALARM
408 CONVERTOR ANGLE
409 FEEDABLE MATERIAL CONTROL PANEL
410 ENABLE MAUN TILT
411 VIBRATION DAMPING
412 TILTING DRIVER SPIDER
413 220444-0555 MCC
414 CONVERTOR BRAKE APPLY/RELEASE BRAKE
415 CONVERTOR BRAKE START IN REMOTE
416
417 FES SYSTEM CABLE SCHEDULE
418 MBFC TIMER PNL FES TIMR PNL 1 16CX1.5SQMM JBD103D BF-1 SV'S
419 PSV JB-1 12 2CX1.5SQMM
420 MBFC TIMER PNL FES TIMR PNL 1 16CX1.5SQMM JBD103E BF-2 SV'S
421 PSV JB-2 12 2CX1.5SQMM
422 MBFC TIMER PNL FES TIMR PNL 1 16CX1.5SQMM JBD103F BF-3 SV'S
423 PSV JB-3 12 2CX1.5SQMM
424 MBFC TIMER PNL FES TIMR PNL 1 16CX1.5SQMM JBD103G BF-4 SV'S
425 PSV JB-4 12 2CX1.5SQMM
426 FES I/P TO PLC PNL 10 MAIN PLC PNL 1 12CX1.5SQMM BAG FILTR TIMR PNL
427 MBFC TIMER PNL JBD103A PRESS SW
428 FES TIMR PNL 1 5CX1.5SQMM JBD103A DP SW
429 MBFC TIMER PNL FES TIMR PNL 1 10CX1.5SQMM JBD103B SV I/L DMPR(1 TO 4) 4 3CX1.5SQMM
430 MBFC TIMER PNL FES TIMR PNL 1 10CX1.5SQMM JBD103C
O/P,C/L DMPR LIMIT SW4 3CX1.5SQMM

1P*1SQMM 1750 MTR


2C*1.5SQMM700 MTR
3P*1SQMM 100 MTR
5C*1.5SQMM700 MTR
14P 450 MTR

16C*1.5SQMM 800 M
2C*1.5 500 M
5C*1.5 1150 M
9C*1.5 250 M
1P*1 1300 M
3P*1 100 M
7P*1 300 M
14P*1 1250 M
JUNCTION BOX DETAILS
SL NO POSITION JB TYPE QTY JB TAG JB SIZE TOTAL TERMINAL POINT REMARKS
1 COOLING TOWER ANALOG JB 1 JBA101A 500MMX300MMX200MM
ANALOG JB 1 JBA101B 500MMX300MMX200MM
DIGITAL JB 1 JBD101 300MMX200MMX200MM

2 ID FAN & CHIMNEY ANALOG JB 1 JBA102 500MMX300MMX200MM


DIGITAL JB 1 JBD102 500MMX300MMX200MM

3 BAG FILTR & FD COOLER ANALOG JB 1 JBA103 500MMX300MMX200MM


DIGITAL JB JBD103A SUPPLIED BY THERMAX
JBD103B SUPPLIED BY THERMAX
JBD103C SUPPLIED BY THERMAX
BAG FLTR-1TOP JBD103D SUPPLIED BY THERMAX
BAG FLTR-2TOP JBD103E SUPPLIED BY THERMAX
BAG FLTR-3TOP JBD103F SUPPLIED BY THERMAX
BAG FLTR-4TOP JBD103G SUPPLIED BY THERMAX

8 BATCHING SYSTEM ANALOG JB 1 JBA104 500MMX300MMX200MM


DIGITAL JB 1 JBD104 500MMX300MMX200MM

4 WATER COOLED DUCT ANALOG JB 1 JBA105A 500MMX300MMX200MM


ANALOG JB 1 JBA105B 500MMX300MMX200MM
ANALOG JB 1 JBA105C 500MMX300MMX200MM

5 GAS MIXING STATION ANALOG JB 1 JBA106 300MMX300MMX200MM

6 COMPRESSOR UNIT ANALOG JB 1 JBA107 300MMX200MMX200MM

7 PRDS SYSTEM ANALOG JB 1 JBA108 300MMX200MMX200MM

8 RAW WTR TANK ANALOG JB 1 JBA109 300MMX200MMX200MM

9 INDUCTION FURNACE ANALOG JB 1 JBA110A


ANALOG JB 1 JBA110B
DIGITAL JB JBD110

10 SPARE JB ANALOG JB 2 500MMX300MMX200MM


DIGITAL JB 2 300MMX200MMX200MM
21
INSTU
TAG
SLNO DESCRIPTION NAME DI DO AI AO CABLE FROM

CABLE
TAG NO OF
COOLING TOWER SOURCE DETAILS RUN
2 MAIN CWP O/L HDR PRESS PT02 2 FIELD AC102 1
3 IND FUR CWP O/L HDR PRESS PT03 1 FIELD AC103 1
4 FUR CWP O/L HDR PRESS PT04 1 FIELD AC104 1
5 EMG CWP O/L HDR PRESS PT05 1 FIELD AC105 1
6 FUR CW I/L MANIFOLD PRESS PT06 1 FIELD AC106 1

7 COOLING WTR TNK LVL LT01 2 FIELD 2


8 DM WTR TNK LVL LT02 1 FIELD AC107 1
9 EMG DM WTR TANK LVL LT03 1 FIELD AC108 1

11 SOFTNER O/L FLO TO COOLING TWR FT01B 1 FIELD AC110 1

12 COOLING WTR FLO TO WCD(500NB) FT02A 1 FIELD AC111 1

13 COOLING WTR FLO TO WCD(450NB) FT02B 1 FIELD AC112 1

14 COOLING WTR FLO TO CNVRTR BRG FT02C 1 FIELD AC113 1

17 COOLING WTR FLO TO IND FUR COIL FT04 1 FIELD AC116 1


DIFFERENTIAL PRESS SWITCH(6 PUMPS) 6
20 MAIN CWP O/L HDR TEMP TE02 1 FIELD AC119 1
21 IND FUR CWP O/L HDR TEMP TE03 1 FIELD AC120 1
22 FUR CWP O/L HDR TEMP TE04 1 FIELD AC121 1
23 EMG CWP O/L HDR TEMP TE05 1 FIELD AC122 1
24 IND FUR I/L MANIFOLD WTR TEMP TE06 1 FIELD AC123 1
25 FUR SHELL 1 CW O/L TEMP TE07 1 FIELD AC124 1
26 FUR SHELL 2 CW O/L TEMP TE08 1 FIELD AC125 1
27 WCD(SEC-1) O/L COOLING WTR TEMP1 TE09 1 FIELD AC126 1
28 WCD(SEC-1) O/L COOLING WTR TEMP2 TE10 1 FIELD AC127 1
29 WCD(SEC-2) O/L COOLING WTR TEMP1 TE11 1 FIELD AC128 1
30 WCD(SEC-2) O/L COOLING WTR TEMP2 TE12 1 FIELD AC129 1
31 WCD(SEC-3) O/L COOLING WTR TEMP1 TE13 1 FIELD AC130 1
32 WCD(SEC-3) O/L COOLING WTR TEMP2 TE14 1 FIELD AC131 1
33 WCD(SEC-4) O/L COOLING WTR TEMP1 TE15 1 FIELD AC132 1
34 WCD(SEC-4) O/L COOLING WTR TEMP2 TE16 1 FIELD AC133 1
35 WCD(SEC-5) O/L COOLING WTR TEMP1 TE17 1 FIELD AC134 1
36 WCD(SEC-5) O/L COOLING WTR TEMP2 TE18 1 FIELD AC135 1
37 WCD(SEC-6) O/L COOLING WTR TEMP1 TE19 1 FIELD AC136 1
38 WCD(SEC-6) O/L COOLING WTR TEMP2 TE20 1 FIELD AC137 1
45 WCD COM CW O/L TEMP1(450NB) TE27 1 FIELD AC144 1
46 WCD COM CW O/L TEMP2(500NB) TE28 1 FIELD AC145 1
47 CNVRTR BRG CW O/L TEMP TE29 1 FIELD AC146 1
48 DM SKID-1 HT EX CW O/L TEMP TE30 1 FIELD AC147 1
49 DM SKID-2 HT EX CW O/L TEMP TE31 1 FIELD AC148 1
50 FUR CW HT EX O/L TEMP TE32 1 FIELD AC149 1
51 CONDENSATE DRAIN VLV(CDCV-1) CDCV-1 1 FIELD AC150 1
52 1 FIELD AC151 1
53 DM WTR LINE VLV(SOV-3) SOV-3 1 FIELD
1
54 1 FIELD 1

55 1 FIELD 1
59 COOLING TOWER FAN 1 1 FIELD 1
67 COOLING TOWER FAN 2 1 FIELD 1
183 AIR COMPRESSOR MTR COMP-1 1 COMP PNL 1
184 1 COMP PNL
185 1 COMP PNL
186 1 COMP PNL 1
187 COMP LINE VLV SOV-1 1 COMP PNL 1
188 1 COMP PNL 1

189 1 COMP PNL 1


190 COMP BYPASS VLV SOV-2 1 COMP PNL 1
191 1 COMP PNL 1

192 1 COMP PNL 1


193 AIR DILUTION DMPR ADD-1 1 FIELD 1
194 1 FIELD 1
195 1 FIELD 1
196 1 FIELD 1
197 1 FIELD 1
198 1 FIELD 1
199 1 FIELD 1
200 PWR CABLE FOR AIR DILUTION DMPR MCC PNL 1
233 O2 DETECTOR 1 FIELD 1
234 GAS MIXING STATION I/L STEAM FLOW FT203 1 FIELD 1
235 GAS MIXING STATION I/L STEAM PRESS PT205 1 FIELD 1
236 GAS MIXING STATION I/L STEAM TEMP TE205 1 FIELD 1
237 GAS MIXING STATION I/L OXYGEN FLOW FT400 1 FIELD 1
238 GAS MIXING STATION I/L ARGON FLOW FT100 1 FIELD 1
239 INSTRUMENT AIR HEADER PRESSURE PT303A 1 FIELD 1
240 SERVICE AIR HEADER PRESSURE PT303B 1 FIELD 1
241 DIFFERENTIAL PRESS SW BF CMBR-1 DPS01 1 FIELD 1
242 DIFFERENTIAL PRESS SW BF CMBR-2 DPS02 1 FIELD 1
243 DIFFERENTIAL PRESS SW BF CMBR-3 DPS03 1 FIELD 1
244 DIFFERENTIAL PRESS SW BF CMBR-4 DPS04 1 FIELD 1
245 DIFFERENTIAL PRESS SW BF DPS05 1 FIELD 1
246 BF BNKR-1 LVL SW LSH01 1 FIELD 1
247 BF BNKR-2 LVL SW LSH02 1 FIELD 1
248 BF BNKR-3 LVL SW LSH02 1 FIELD 1
249 BF BNKR-4 LVL SW LSH04 1 FIELD 1
250 HET EX BNKR LVL SW LSH05 1 FIELD 1
252 FLUE GAS TEMP AT WCD HEADER TE501 1 FIELD 1
252 FLUE GAS TEMP-1 AT WCD TE501 1 FIELD 1
253 FLUE GAS TEMP-2 AT WCD TE502 1 FIELD 1
254 FLUE GAS TEMP-3 AT WCD TE503 1 FIELD 1
255 FLUE GAS TEMP-4 AT WCD TE504 1 FIELD 1
FLUE GAS TEMP-5 AT WCD 1 FIELD 1
256 FLUE GAS TEMP FD COOLER I/L TE505 1 FIELD 1
265 METAL LOAD FRM WEIGH BRDG 1 FIELD 1
FLOW SWITCH FIELD 1
PRE HEATER PARKING FIELD 1
PRE HEATER CONVERTER FIELD 1
COOLING WATER PRESS FIELD 1
RETURN WATER PRESS FIELD 1
266 LADLE CAR-1 LIMIT SW 1 FIELD 1
267 LADLE CAR-2 LIMIT SW 1 FIELD 1

16C*1.5SQMM 800 M
2C*1.5 500 M
5C*1.5 1150 M
9C*1.5 250 M
1P*1 1300 M
3P*1 100 M
7P*1 300 M
14P*1 1250 M
INTERMEDI
ATE
CABLE CONNECTIO
CABLE TYPE LENGTH N

JB TAG TOTAL LENGTH REMARKS


1PX1SQMM 15 JBA101A 15
1PX1SQMM 15 JBA101A 15
1PX1SQMM 15 JBA101B 15
1PX1SQMM 15 JBA101B 15
1PX1SQMM 15 15

2CX1.5SQMM 20 JBD101 40
1PX1SQMM 15 JBA101B 15
1PX1SQMM 30 JBA101B 30

1PX1SQMM 15 JBA101B 15

1PX1SQMM 2 2

1PX1SQMM 25 25 11

1PX1SQMM 10 JBA105A 10

1PX1SQMM 10 JBA101B 10
2CX1.5SQMM 15 90
1PX1SQMM 15 JBA101A 15
1PX1SQMM 15 JBA101A 15
1PX1SQMM 15 JBA101B 15
1PX1SQMM 15 JBA101B 15
1PX1SQMM 10 JBA101B 10
1PX1SQMM 10 10
1PX1SQMM 10 10
1PX1SQMM 13 JBA105A 13 UHT PLC
1PX1SQMM 13 JBA105A 13 UHT PLC
1PX1SQMM 13 JBA105A 13
1PX1SQMM 13 JBA105A 13
1PX1SQMM 13 JBA105A 13
1PX1SQMM 13 JBA105A 13
1PX1SQMM 13 JBA105A 13
1PX1SQMM 13 JBA105A 13
1PX1SQMM 13 JBA105A 13
1PX1SQMM 13 JBA105A 13
1PX1SQMM 13 JBA105B 13
1PX1SQMM 13 JBA105B 13
1PX1SQMM 15 JBA105A 15
1PX1SQMM 15 JBA105B 15
1PX1SQMM 10 10
1PX1SQMM 20 20
1PX1SQMM 20 20
1PX1SQMM 25 25
JBA106
3PX1SQMM 5 JBA106 5
JBD101
5CX1.5SQMM 15 15
5CX1.5SQMM 15 JBD101 15

2CX1.5SQMM 15 JBD101 15
2CX1.5SQMM 20 JBD101 20
2CX1.5SQMM 30 JBD101 30
20
0
5CX1.5SQMM 20 0
2CX1.5SQMM 20 20
JBD110 20
5CX1.5SQMM 20 JBD110 0

2CX1.5SQMM 20 JBD110 20
JBD110 20
5CX1.5SQMM 20 JBD110 0

2CX1.5SQMM 20 JBD110 20
JBD103A 15
JBD103A 0
JBD103A 0
JBD103A 0
7CX1.5SQMM 15 JBD103A 0
2CX1.5SQMM 15 JBD103A 15
2CX1.5SQMM 15 JBD103A 15
3CX2.5SQMM 0
1PX1SQMM 12 JBA106 12
1PX1SQMM 2 JBA106 2
1PX1SQMM 2 JBA106 2
1PX1SQMM 4 JBA106 4
1PX1SQMM 5 JBA106 5
1PX1SQMM 5 JBA106 5
1PX1SQMM 5 JBA107 5
1PX1SQMM 5 JBA107 5
2CX1.5SQMM 2 JBD103A 2
2CX1.5SQMM 2 JBD103A 2
2CX1.5SQMM 7 JBD103A 7
2CX1.5SQMM 7 JBD103A 7
2CX1.5SQMM 10 JBD103A 10
2CX1.5SQMM 5 JBD103A 5
2CX1.5SQMM 5 JBD103A 5
2CX1.5SQMM 5 JBD103A 5
2CX1.5SQMM 5 JBD103A 5
2CX1.5SQMM 10 JBD103A 10
1PX1SQMM 25 JBA105A 25
1PX1SQMM 20 JBA105A 20
1PX1SQMM 20 JBA105A 20
1PX1SQMM 15 JBA105B 15
1PX1SQMM 20 JBA105B 20
1PX1SQMM 25 JBA105B 25
1PX1SQMM 50 JBA105C 50
1PX1SQMM 100 100
2CX1.5SQMM 15 15 UHT PLC
30 UHT PLC
5CX1.5SQMM 30 0 UHT PLC
1PX1SQMM 10 10 UHT PLC
1PX1SQMM 10 10 UHT PLC
100 UHT PLC
5CX1.5SQMM 100 0 UHT PLC

1P*1SQMM 900 MTR


2C*1.5SQMM350 MTR
3P*1SQMM 10 MTR
5C*1.5SQMM250 MTR
0 0
INSTU TAG
SLNO DESCRIPTION LONG DESCRIPTION
NAME

1 MAIN CWP O/L HDR PRESS PT02

2 IND FUR CWP O/L HDR PRESS PT03

4 FUR CWP O/L HDR PRESS PT04

5 EMG CWP O/L HDR PRESS PT05

6 FUR CW I/L MANIFOLD PRESS PT06

7 COOLING WTR TNK LVL LT01

8 DM WTR TNK LVL LT02

9 EMG DM WTR TANK LVL LT03

10 RAW WTR FLO TO SOFTNER FT01A

11 SOFTNER O/L FLO TO COOLING TWR FT01B

12 COOLING WTR FLO TO WCD FT02A

13 COOLING WTR FLO TO WCD FT02B

17 COOLING WTR FLO TO IND FUR COIL FT04

19 RAW WTR CWP O/L HDR TEMP TE01


20 MAIN CWP O/L HDR TEMP TE01

21 IND FUR CWP O/L HDR TEMP TE02

22 FUR CWP O/L HDR TEMP TE03

23 EMG CWP O/L HDR TEMP TE04

24 IND FUR I/L MANIFOLD WTR TEMP TE05

25 FUR SHELL 1 CW O/L TEMP TE06A

26 FUR SHELL 2 CW O/L TEMP TE06B

27 WCD(SEC-1) O/L COOLING WTR TEMP1 TE07

28 WCD(SEC-1) O/L COOLING WTR TEMP2 TE08

27 WCD(SEC-1) O/L COOLING WTR TEMP1 TE09

28 WCD(SEC-1) O/L COOLING WTR TEMP2 TE10

29 WCD(SEC-2) O/L COOLING WTR TEMP1 TE11

30 WCD(SEC-2) O/L COOLING WTR TEMP2 TE12

31 WCD(SEC-3) O/L COOLING WTR TEMP1 TE13

32 WCD(SEC-3) O/L COOLING WTR TEMP2 TE14


33 WCD(SEC-4) O/L COOLING WTR TEMP1 TE15

34 WCD(SEC-4) O/L COOLING WTR TEMP2 TE16

35 WCD(SEC-5) O/L COOLING WTR TEMP1 TE17

36 WCD(SEC-5) O/L COOLING WTR TEMP2 TE18

37 WCD(SEC-6) O/L COOLING WTR TEMP1 TE19

38 WCD(SEC-6) O/L COOLING WTR TEMP2 TE20

39 WCD(SEC-7) O/L COOLING WTR TEMP1 TE21

40 WCD(SEC-7) O/L COOLING WTR TEMP2 TE22

41 WCD(SEC-8) O/L COOLING WTR TEMP1 TE23

42 WCD(SEC-8) O/L COOLING WTR TEMP2 TE24

43 WCD(SEC-9) O/L COOLING WTR TEMP1 TE25

44 WCD(SEC-9) O/L COOLING WTR TEMP2 TE26

45 WCD COM CW O/L TEMP1 TE27

46 WCD COM CW O/L TEMP2 TE28

47 CNVRTR BRG CW O/L TEMP TE29


48 DM SKID-1 HT EX CW O/L TEMP TE30

49 DM SKID-2 HT EX CW O/L TEMP TE31

50 FUR CW HT EX O/L TEMP TE32

52 DM WTR LINE VLV(SOV-3) SOV-3 OPN F/B SOV-3


SOV-3 CLS F/B

SOV-3 ON CMD

53 COOLING TOWER FAN 1 CTF-1 RUN F/B CTF-1


CTF-1 MTR O/L TRP
CTF-1 L/R MODE
CTF-1 VIBRATION
CTF-1 OIL LVL LOW
CTF-1 ON CMD

CTF-1 CURRENT O/P

CTF-1 SPD O/P


CTF-1 SET SPEED
54 COOLING TOWER FAN 2 CTF-2 RUN F/B CTF-2
CTF-2 MTR O/L TRP
CTF-2 -1 L/R MODE
CTF-2 VIBRATION
CTF-2 OIL LVL LOW
CTF-2 ON CMD

CTF-2 CURRENT O/P

CTF-2 SPD O/P


CTF-2 SET SPD
55 FUR. COOLING PUMP-1 FUR PMP-1 RUN F/B FCP-1
FUR PMP-1 MTR O/L TRP
FUR CW PMP-1 L/R MODE
FUR CW PMP-1 ON CMD
56 FUR. COOLING PUMP-2 FUR PMP-2 RUN F/B FCP-2
FUR PMP-2 MTR O/L TRP
FUR CW PMP-2 L/R MODE
FUR CW PMP-2 ON CMD
57 E/M COOLING WTR PUMP-1 E/M PMP-1 RUN F/B EWP-1
E/M PMP-1 MTR O/L TRP
E/M PMP-1 L/R MODE
E/M CW PMP-1 ON CMD
58 E/MCOOLING WTR PUMP-2 E/MCW PMP-2 RUN F/B EWP-2
E/M CW PMP-2 MTR O/L TRP
E/M CW PMP-2 L/R MODE
E/M CW PMP-2 ON COMMAND
59 COOLING WTR PUMP 1 CW PMP-1 RUN F/B CWP-1
CW PMP-1 MTR O/L TRP
CW PMP-1 L/R MODE
CW PMP-1 ON CMD
CW PMP-1 CURRENT O/P
CW PMP-1 SPD O/P
CW PMP-1 SET SPD
60 COOLING WTR PUMP 2 CW PMP-2 RUN F/B CWP-2
CW PMP-2 MTR O/L TRP
CW PMP-2 L/R MODE
CW PMP-2 ON CMD

CW PMP-2 CURRENT O/P

CW PMP-2 SPD O/P


CW PMP-2 SET SPD
61 COOLING WTR PUMP 3 CW PMP-3 RUN F/B CWP-3
CW PMP-3 MTR O/L TRP
CW PMP-3 L/R MODE
CW PMP-3 ON CMD

CW PMP-3 CURRENT O/P

CW PMP-3 SPD O/P


CW PMP-3 SET SPD
62 INDUCTION COOLING WTR PUMP 1 IND CW PMP-1 RUN F/B ICWP-1
IND CW PMP-1 MT O/L TRP
IND CW PMP-1 L/R MODE
IND CW PMP-1 ON CMD
63 INDUCTION COOLING WTR PUMP 2 IND CW PMP-2 RUN F/B ICWP-2
IND CW PMP-2 MTR O/L TRP
IND CW PMP-2 L/R MODE
IND CW PMP-2 ON CMD
64 RAW WTR PUMP 1 RW PMP-1 RUN F/B RWP-1
RW PMP-1 MTR O/L TRP
RW PMP-1 L/R MODE
RW PMP-1 ON CMD
65 RAW WTR PUMP 2 RW PMP-2 RUN F/B RWP-2
RW PMP-2 MTR O/L TRP
RW PMP-2 L/R MODE
RW PMP-2 ON CMD
66 ID FAN-1 ID-1 RUN F/B ID-1
ID-1 MTR O/L TRP
ID-1 L/R MODE
ID-1 ON CMD

ID-1 CURRENT O/P

ID-1 SPD O/P


ID-1 SET SPD
67 ID FAN-1 SUCTION DMPR ID-1 SUC DMPR OPN F/B ID1SD
ID-1 SUC DMPR CLS F/B

ID-1 SUC DMPR ON CMD

68 ID FAN-1 DISCHRG DMPR ID-1 DIS DMPR OPN F/B ID1DD


ID-1 DIS DMPR CLS F/B

ID-1 DIS DMPR ON CMD

69 ID FAN-2 ID-2 RUN F/B ID-2


ID-2 MTR O/L TRP
ID-2 L/R MODE
ID-2 ON CMD

ID-2 CURRENT O/P

ID-2 SPD O/P


ID-2 SET SPD
70 ID FAN-2 SUCTION DMPR ID-2 SUC DMPR OPN F/B ID2SD
ID-2 SUC DMPR CLS F/B

ID-2 SUC DMPR ON CMD

71 ID FAN-2 DISCHRG DMPR ID-2 DIS DMPR OPN F/B ID2DD


ID-2 DIS DMPR CLS F/B

ID-2 DIS DMPR ON CMD

72 HEAT EXCAHNGER CL FAN 1 HXCF-1 RUN F/B HXCF-1


HXCF-1 MTR O/L TRP
HXCF-1 L/R MODE
HXCF-1 ON CMD
73 HEAT EXCAHNGER CL FAN 2 HXCF-2 RUN F/B HXCF-2
HXCF-2 MTR O/L TRP
HXCF-2 L/R MODE
HXCF-2 ON CMD
74 HEAT EXCAHNGER CL FAN 3 HXCF-3 RUN F/B HXCF-3
HXCF-3 MTR O/L TRP
HXCF-3 L/R MODE
HXCF-3 ON CMD
75 HEAT EXCAHNGER CL FAN 4 HXCF-4 RUN F/B HXCF-4
HXCF-4 MTR O/L TRP
HXCF-4 L/R MODE
HXCF-4 ON CMD
76 WTR SOFTNER PUMP SOFP-1 RUN F/B SOFP-1
SOFP-1 MTR O/L TRP
SOFP-1 L/R MODE
SOFP-1 ON CMD
80 AIR COMPRESSOR1 MTR COMP-1 RUN F/B COMP-1
COMP-1 MTR O/L TRP
COMP-1 L/R MODE
COMP-1 ON CMD
80 AIR COMPRESSOR2 MTR COMP-1 RUN F/B COMP-1
COMP-1 MTR O/L TRP
COMP-1 L/R MODE
COMP-1 ON CMD
83 AIR DILUTION DMPR AIR DIL DMPR OPN F/B ADD-1
AIR DIL DMPR CLS F/B
AIR DIL DMPR OPN TRQ
AIR DIL DMPR CLS TRQ
AIR DIL DMPR L/R MODE
AIR DIL DMPR OPN/CLS CMD
AIR DIL DMPR POSITION FB
84 DM SKID-1 PUMP DM SKID 1 PMP-1 RUN F/B DMS1P1
DM SKID 1 PMP-1 O/L TRP
DM SKID 1 PMP-1 L/R MODE
DM SKID 1 PMP-1 ON CMD
84 DM SKID-2 PUMP DM SKID 1 PMP-2 RUN F/B DMS1P2
DM SKID1 PMP-2 O/L TRP
DM SKID 1 PMP-2 L/R MODE
DM SKID 1 PMP-2 ON CMD
85 DM SKID-3 PUMP DM SKID 2 PMP-1 RUN F/B DMS2P1
DM SKID 2 PMP-1 O/L TRP
DM SKID 2 PMP-1 L/R MODE
DM SKID2 PMP-1 ON CMD
86 HYD SKID-1 PUMP HYD SKID 1 PMP-1 RUN F/B HYD1P1
HYD SKID 1 PMP-1 O/L TRP
HYD SKID 1 PMP-1 L/R MODE
HYD SKID 1 PMP-1 ON CMD
86 HYD SKID-2 PUMP HYD SKID 1 PMP-2 RUN F/B HYD1P2
HYD SKID 1 PMP-2 O/L TRP
HYD SKID 1 PMP-2 L/R MODE
HYD SKID 1 PMP-2 ON CMD
87 HYD SKID-3 PUMP HYD SKID 2 PMP-1 RUN F/B HYD2P1
HYD SKID 2 PMP-1 O/L TRP
HYD SKID 2 PMP-1 L/R MODE
HYD SKID 2 PMP-1 ON CMD
88 GAS MIXING STATION I/L STEAM FLOW GMS I/L STM FLO FT203
89 GAS MIXING STATION I/L STEAM PRESS GMS I/L STM PRESS PT205

90 GAS MIXING STATION I/L STEAM TEMP GMS I/L STM TEMP TE205

93 INSTRUMENT AIR HEADER PRESSURE INST AIR HDR PRESS PT303A

94 SERVICE AIR HEADER PRESSURE SER AIR HDR PRESS PT303B

95 DIFFERENTIAL PRESS SW BF CMBR-1 DP SW BF CMBR1 DPS01


96 DIFFERENTIAL PRESS SW BF CMBR-2 DP SW BF CMBR2 DPS02
97 DIFFERENTIAL PRESS SW BF CMBR-3 DP SW BF CMBR3 DPS03
98 DIFFERENTIAL PRESS SW BF CMBR-4 DP SW BF CMBR4 DPS04
99 DIFFERENTIAL PRESS SW BF DP SW BF DPS05
100 BF BNKR-1 LVL SW LVL SW BF BNKR1 LSH01
101 BF BNKR-2 LVL SW LVL SW BF BNKR2 LSH02
102 BF BNKR-3 LVL SW LVL SW BF BNKR3 LSH02
103 BF BNKR-4 LVL SW LVL SW BF BNKR4 LSH04
104 HET EX BNKR LVL SW LVL SW HE BNKR LSH05
105 CCS STACK PARTICULATE MONITOR CCS STK DUST LVL SPM02

106 FLUE GAS HOOD TEMP-1 AT WCD TE501

107 FLUE GAS TEMP-2 AT WCD TE502

108 FLUE GAS TEMP-3 AT WCD TE503

109 FLUE GAS TEMP-4 AT WCD TE504


110 FLUE GAS TEMP-5 AT WCD TE505

111 FLUE GAS TEMP-6 AT WCD TE506

112 FLUE GAS TEMP FD COOLER I/L TE507

113 FLUE GAS TEMP-1 FD COOLER O/L TE508

114 FLUE GAS TEMP-2 FD COOLER O/L TE509

116 FLUE GAS TEMP BF I/L TE511

117 FLUE GAS TEMP BF O/L TE512

COOLING WATER TANK LEVEL1 SW CTLL1


COOLING WATER TANK LEVEL2 SW CTLL2
EMERGENCY WATER PUMP-1_DP SWITCH EWP1DPH
EMERGENCY WATER PUMP-2_DP SWITCH EWP2DPH
FURNACE COOLING PUMP-1_DP SWITCH FCP1DPH
FURNACE COOLING PUMP-2_DP SWITCH FCP2DPH
INDUCTION COOLING PUMP-1_DP SWITCH ICWP1DPH
INDUCTION COOLING PUMP-2_DP SWITCH ICWP2DPH
INDUCTION FUR 1 STATUS
INDUCTION FUR 1 TRIP
INDUCTION FUR 2 STATUS
INDUCTION FUR 2 TRIP
INDUCTION FUR 3 STATUS
INDUCTION FUR 3 TRIP
BF CMBR1 I/L DMPR DMPR ON COM
DMPR OPEN FB
DMPR CLS FB
BF CMBR1 O/L DMPR DMPR ON COM
DMPR OPEN FB
DMPR CLS FB
BF CMBR2 I/L DMPR DMPR ON COM
DMPR OPEN FB
DMPR CLS FB
BF CMBR2 O/L DMPR DMPR ON COM
DMPR OPEN FB
DMPR CLS FB
BF CMBR3 I/L DMPR DMPR ON COM
DMPR OPEN FB
DMPR CLS FB
BF CMBR3 O/L DMPR DMPR ON COM
DMPR OPEN FB
DMPR CLS FB
BF CMBR4 I/L DMPR DMPR ON COM
DMPR OPEN FB
DMPR CLS FB
BF CMBR4 O/L DMPR DMPR ON COM
DMPR OPEN FB
DMPR CLS FB
PURGE SOL MATRIX ROW1 DO
PURGE SOL MATRIX ROW2 DO
PURGE SOL MATRIX ROW3 DO
PURGE SOL MATRIX ROW4 DO
PURGE SOL MATRIX COLUMN1 DO
PURGE SOL MATRIX COLUMN2 DO
PURGE SOL MATRIX COLUMN3 DO
PURGE SOL MATRIX COLUMN4 DO
PURGE SOL MATRIX COLUMN5 DO
PURGE SOL MATRIX COLUMN6 DO
PURGE SOL MATRIX COLUMN7 DO
PURGE SOL MATRIX COLUMN8 DO
PURGE SOL MATRIX COLUMN9 DO
PURGE SOL MATRIX COLUMN10 DO
PURGE SOL MATRIX COLUMN11 DO
PLC SIGNAL INSTRUMENTS USED AT
RANGE DI DO AI AO REMARKS
TAG NAME FIELD SIDE

PIEZORESISTIVE
PI02 0 TO 10KG/CM2 1 TRANSMITTER WIKA
MAKE

PIEZORESISTIVE
PI03 0 TO 10KG/CM2 1 TRANSMITTER WIKA
MAKE

PIEZORESISTIVE
PI04 0 TO 10KG/CM2 1 TRANSMITTER WIKA
MAKE

PIEZORESISTIVE
PI05 0 TO 10KG/CM2 1 TRANSMITTER WIKA
MAKE

PIEZORESISTIVE
PI06 0 TO 10KG/CM2 1 TRANSMITTER WIKA
MAKE

LO ALRM WILL BE
LI01 0 TO 2.5 MTR 1
RECEIVED FROM INSTU

ULTRASONIC LEVEL
LI02 0 TO 4 MTR 1 TRANSMITTER MAKE-
ABB, MODEL-
KMICROLP/PVFD/1X

ULTRASONIC LEVEL
LI03 0 TO 3.5 MTR 1 TRANSMITTER MAKE-
ABB, MODEL-
KMICROLP/PVFD/1X
FLOW CUMULATIVE
FI01A 0 TO 120M3/HR 1
REQ

FLOW CUMULATIVE ELECTROMAGNETIC


FI01B 0 TO 120M3/HR 1 FLOWMETER ,ABB MAKE-
REQ
MODEL- FEP321
FLOW CUMULATIVE
FI02A 0 TO 1500 M3/HR 1
REQ ABB MAKE-DPT266 HSH
FLOW CUMULATIVE
FI02B 0 TO 1300 M3/HR 1
REQ ABB MAKE-DPT266 HSH

FLOW CUMULATIVE
FI04 0 TO 80 M3/HR 1 VORTEX FLOWMETER,ABB
REQ
MAKE, MODEL-FSV430

TI01 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS
TI01 0 TO 150 DEG C 1 HEAD MOUNT
TRANSMITTER MASIBUS

TI02 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI03 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI04 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI05 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI06A 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI06B 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TE07 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TE08 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI09 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI10 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI11 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI12 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI13 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI14 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS
TI15 0 TO 150 DEG C 1 HEAD MOUNT
TRANSMITTER MASIBUS

TI16 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI17 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI18 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI19 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI20 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI21 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI22 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI23 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI24 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI25 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI26 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI27 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI28 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI29 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS
TI30 0 TO 150 DEG C 1 HEAD MOUNT
TRANSMITTER MASIBUS

TI31 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI32 0 TO 150 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS
SOV3OPNFB 1
SOV3CLSFB 1
DIGITAL OUTPUT TO BE
SOV3ON 1 POTENTIAL
TYPE(230VAC)
CTF1FB 1
CTF1TR 1
CTF1LR 1
CTF1VS 1
CTF1OLL 1
CTF1ON 1

DURING FINAL
CTF1CO 1
COMMISSIONING

CTF1SO 0 TO 1500 RPM 1


CTF1SS 0 TO 100% 1
CTF2FB 1
CTF2TR 1
CTF2LR 1
CTF2VS 1
CTF2OLL 1
CTF2ON 1
DURING FINAL
CTF2CO COMMISSIONING 1

CTF2SO 0 TO 1500 RPM 1


CTF2SS 0 TO 100% 1
FCP1FB 1
FCP1TR 1
FCP1LR 1
FCP1ON 1
FCP2FB 1
FCP2TR 1
FCP2LR 1
FCP2ON 1
EWP1FB 1
EWP1TR 1
EWP1LR 1
EWP1ON 1
EWP2FB 1
EWP2TR 1
EWP2LR 1
EWP2ON 1
CWP1FB 1
CWP1TR 1
CWP1LR 1
CWP1ON 1
DURING FINAL
CWP1CO COMMISSIONING 1
CWP1SO 0 TO 1500 RPM 1
CWP1SS 0 TO 100% 1
CWP2FB 1
CWP2TR 1
CWP2LR 1
CWP2ON 1

DURING FINAL
CWP2CO 1
COMMISSIONING

CWP2SO 0 TO 1500 RPM 1


CWP2SS 0 TO 100% 1
CWP3FB 1
CWP3TR 1
CWP3LR 1
CWP3ON 1

DURING FINAL
CWP3CO 1
COMMISSIONING

CWP3SO 0 TO 1500 RPM 1


CWP3SS 0 TO 100% 1
ICWP1FB 1
ICWP1TR 1
ICWP1LR 1
ICWP1ON 1
ICWP2FB 1
ICWP2TR 1
ICWP2LR 1
ICWP2ON 1
RWP1FB 1
RWP1TR 1
RWP1LR 1
RWP1ON 1
RWP2FB 1
RWP2TR 1
RWP2LR 1
RWP2ON 1
ID1FB 1
ID1TR 1
ID1LR 1
ID1ON 1

DURING FINAL
ID1CO 1
COMMISSIONING

ID1SO 0 TO 1500 RPM 1


ID1SS 0 TO 100% 1
ID1SDOPN 1
ID1SDCLS 1
DIGITAL OUTPUT TO BE
ID1SDON 1 POTENTIAL
TYPE(230VAC)
ID1DDOPN 1
ID1DDCLS 1
DIGITAL OUTPUT TO BE
ID1DDON 1 POTENTIAL
TYPE(230VAC)
ID2FB 1
ID2TR 1
ID2LR 1
ID2ON 1

DURING FINAL
ID2CO 1
COMMISSIONING

ID2SO 0 TO 1500 RPM 1


ID2SS 0 TO 100% 1
ID2SDOPN 1
ID2SDCLS 1
DIGITAL OUTPUT TO BE
ID2SDON 1 POTENTIAL
TYPE(230VAC)
ID2DDOPN 1
ID2DDCLS 1
DIGITAL OUTPUT TO BE
ID2DDON 1 POTENTIAL
TYPE(230VAC)
HXCF1FB 1
HXCF1TR 1
HXCF1LR 1
HXCF1ON 1
HXCF2FB 1
HXCF2TR 1
HXCF2LR 1
HXCF2ON 1
HXCF3FB 1
HXCF3TR 1
HXCF3LR 1
HXCF3ON 1
HXCF4FB 1
HXCF4TR 1
HXCF4LR 1
HXCF4ON 1
SOFP1FB 1
SOFP1TR 1
SOFP1LR 1
SOFP1ON 1
COMP1FB 1
COMP1TR 1
COMP1LR 1
COMP1ON 1
COMP1FB 1
COMP1TR 1
COMP1LR 1
COMP1ON 1
ADD1OPNFB 1
ADD1CLSFB 1
ADD1OPNTL 1
ADD1CLSTL 1
ADD1LR 1
ADD1CMD 1
ADD1POS 1
DMS1P1FB 1
DMS1P1TR 1
DMS1P1LR 1
DMS1P1ON 1
DMS1P2FB 1
DMS1P2TR 1
DMS1P2LR 1
DMS1P2ON 1
DMS2P1FB 1
DMS2P1TR 1
DMS2P1LR 1
DMS2P1ON 1
HYDP1FB 1
HYDP1TR 1
HYDP1LR 1
HYDP1ON 1
HYDP1FB 1
HYDP1TR 1
HYDP1LR 1
HYDP1ON 1
HYDP2FB 1
HYDP2TR 1
HYDP2LR 1
HYDP2ON 1
FI203 0 TO 1500 KG/HR 1 ABB MAKE-DPT266 HSH
PI205 0 TO 30KG/CM2 1 ABB MAKE-PT266HSH

TI205 0 TO 400 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

PIEZORESISTIVE
PI303A 0 TO 16 KG/CM2 1 TRANSMITTER WIKA
MAKE

PIEZORESISTIVE
PI303B 0 TO 16 KG/CM2 1 TRANSMITTER WIKA
MAKE
DPAH1 1
DPAH2 1
DPAH3 1
DPAH4 1
DPAH5 1
LAH1 1
LAH2 1
LAH3 1
LAH4 1
LAH5 1
SPI02 0 TO 200 MG/M3 1

TI501 0 TO 1200 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI502 0 TO 1200 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI503 0 TO 1200 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI504 0 TO 1200 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS
TI505 0 TO 1200 DEG C 1 HEAD MOUNT
TRANSMITTER MASIBUS

TI506 0 TO 1200 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI507 0 TO 1200 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI508 0 TO 400 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI509 0 TO 400 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI511 0 TO 400 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS

TI512 0 TO 400 DEG C 1 HEAD MOUNT


TRANSMITTER MASIBUS
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

143 56 79 8
SPARES 25 8 17 8
168 64 96 16
I/O DETAILS OF RVR CCS MAIN PLC PANEL
RELAY CARD NO/ FROM
CARD TYPE/ PLC TERMINAL RELAY RELAY
FERRUL SIGNAL PLC PLC NO/ NO/ INSTRUMENT TERMINAL TO EXT.
SL NO E EQUIPMENT DISCRIPTION EQUIP TAG DISCRIPTION TAG NO TYPE ADDRESS LOCATION FERRULE NO NO NO TERMINAL NO

DIGITAL INPUT
1 DI01 DM WTR LINE VLV(SOV-3) SOV-3 SOV-3 OPN F/B SOV3OPNFB 1 1/DI01 IX01,IX02
2 DI02 SOV-3 CLS F/B SOV3CLSFB 1 2/DI02 IX03,IX04
3 DI03 COOLING TOWER FAN 1 CTF-1 CTF-1 RUN F/B CTF1FB 1 3/DI03 IX05,IX06
4 DI04 CTF-1 MTR O/L TRP CTF1TR 1 4/DI04 IX07,IX08
5 DI05 CTF-1 L/R MODE CTF1LR 1 5/DI05 IX09,IX10
6 DI06 CTF-1 VIBRATION CTF1VS 1 6/DI06 IX11,IX12
7 DI07 CTF-1 OIL LVL LOW CTF1OLL 1 7/DI07 IX13,IX14
8 DI08 COOLING TOWER FAN 2 CTF-2 CTF-2 RUN F/B CTF2FB 1 (DI01) 8/DI08 IX15,IX16
5000/1-
9 DI09 CTF-2 MTR O/L TRP CTF2TR 1 CARD1 9/DI09 IX17,IX18
10 DI10 CTF-2 -1 L/R MODE CTF2LR 1 10/DI10 IX19,IX20
11 DI11 CTF-2 VIBRATION CTF2VS 1 11/DI11 IX21,IX22
12 DI12 CTF-2 OIL LVL LOW CTF2OLL 1 12/DI12 IX23,IX24
13 DI13 FUR. COOLING PUMP-1 FCP-1 FUR PMP-1 RUN F/B FCP1FB 1 13/DI13 IX25,IX26
14 DI14 FUR PMP-1 MTR O/L TRP FCP1TR 1 14/DI14 IX27,IX28
15 DI15 FUR CW PMP-1 L/R MODE FCP1LR 1 15/DI15 IX29,IX30
16 DI16 FUR. COOLING PUMP-2 FCP-2 FUR PMP-2 RUN F/B FCP2FB 1 16/DI16 IX31,IX32
17 DI17 FUR PMP-2 MTR O/L TRP FCP2TR 1 1/DI17 IX33,IX34
18 DI18 FUR CW PMP-2 L/R MODE FCP2LR 1 2/DI18 IX35,IX36
19 DI19 FUR. COOLING PUMP-3 FCP-3 FUR PMP-3 RUN F/B FCP3FB 1 3/DI19 IX37,IX38
20 DI20 FUR PMP-3 MTR O/L TRP FCP3TR 1 4/DI20 IX39,IX40
21 DI21 FUR CW PMP-3 L/R MODE FCP3LR 1 5/DI21 IX41,IX42
22 DI22 E/M COOLING WTR PUMP-1 EWP-1 E/M PMP-1 RUN F/B EWP1FB 1 6/DI22 IX43,IX44
23 DI23 E/M PMP-1 MTR O/L TRP EWP1TR 1 7/DI23 IX45,IX46
24 DI24 E/M PMP-1 L/R MODE EWP1LR 1 (DI02) 8/DI24 IX47,IX48
5000/1-
25 DI25 E/MCOOLING WTR PUMP-2 EWP-2 E/MCW PMP-2 RUN F/B EWP2FB 1 CARD2 9/DI25 IX49,IX50
26 DI26 E/M CW PMP-2 MTR O/L TRP EWP2TR 1 10/DI26 IX51,IX52
27 DI27 E/M CW PMP-2 L/R MODE EWP2LR 1 11/DI27 IX53,IX54
28 DI28 COOLING WTR PUMP 1 CWP-1 CW PMP-1 RUN F/B CWP1FB 1 12/DI28 IX55,IX56
29 DI29 CW PMP-1 MTR O/L TRP CWP1TR 1 13/DI29 IX57,IX58
30 DI30 CW PMP-1 L/R MODE CWP1LR 1 14/DI30 IX59,IX60
31 DI31 COOLING WTR PUMP 2 CWP-2 CW PMP-2 RUN F/B CWP2FB 1 15/DI31 IX61,IX62
32 DI32 CW PMP-2 MTR O/L TRP CWP2TR 1 16/DI32 IX63,IX64
33 DI33 CW PMP-2 L/R MODE CWP2LR 1 1/DI33 IX65,IX66
34 DI34 COOLING WTR PUMP 3 CWP-3 CW PMP-3 RUN F/B CWP3FB 1 2/DI34 IX67,IX68
35 DI35 CW PMP-3 MTR O/L TRP CWP3TR 1 3/DI35 IX69,IX70
36 DI36 CW PMP-3 L/R MODE CWP3LR 1 4/DI36 IX71,IX72

INDUCTION COOLING WTR PUMP1 ICWP-1 IND CW PMP-1 RUN F/B ICWP1FB 1
37 DI37 5/DI37 IX73,IX74
38 DI38 IND CW PMP-1 MT O/L TRP ICWP1TR 1 6/DI38 IX75,IX76
39 DI39 IND CW PMP-1 L/R MODE ICWP1LR 1 7/DI39 IX77,IX78
(DI03)
INDUCTION COOLING WTR PUMP2 ICWP-2 IND CW PMP-2 RUN F/B ICWP2FB 1 5000/1-
40 DI40 CARD3 8/DI40 IX79,IX80
5000/1-
CARD3
41 DI41 IND CW PMP-2 MTR O/L TRP ICWP2TR 1 9/DI41 IX81,IX82
42 DI42 IND CW PMP-2 L/R MODE ICWP2LR 1 10/DI42 IX83,IX84
43 DI43 ID FAN-1 ID-1 ID-1 RUN F/B ID1FB 1 11/DI43 IX85,IX86
44 DI44 ID-1 MTR O/L TRP ID1TR 1 12/DI44 IX87,IX88
45 DI45 ID-1 L/R MODE ID1LR 1 13/DI45 IX89,IX90
46 DI46 ID FAN-1 SUCTION DMPR ID1SD ID-1 SUC DMPR OPN F/B ID1SDOPN 1 14/DI46 IX91,IX92
47 DI47 ID-1 SUC DMPR CLS F/B ID1SDCLS 1 15/DI47 IX93,IX94
48 DI48 ID FAN-1 DISCHRG DMPR ID1DD ID-1 DIS DMPR OPN F/B ID1DDOPN 1 16/DI48 IX95,IX96
49 DI49 ID-1 DIS DMPR CLS F/B ID1DDCLS 1 1/DI49 IX97,IX98
50 DI50 ID FAN-2 ID-2 ID-2 RUN F/B ID2FB 1 2/DI50 IX99,IX100
51 DI51 ID-2 MTR O/L TRP ID2TR 1 3/DI51 IX101,IX102
52 DI52 ID-2 L/R MODE ID2LR 1 4/DI52 IX103,IX104
53 DI53 ID FAN-2 SUCTION DMPR ID2SD ID-2 SUC DMPR OPN F/B ID2SDOPN 1 5/DI53 IX105,IX106
54 DI54 ID-2 SUC DMPR CLS F/B ID2SDCLS 1 6/DI54 IX107,IX108
55 DI55 ID FAN-2 DISCHRG DMPR ID2DD ID-2 DIS DMPR OPN F/B ID2DDOPN 1 7/DI55 IX109,IX110
56 DI56 ID-2 DIS DMPR CLS F/B ID2DDCLS 1 (DI04) 8/DI56 IX111,IX112
5000/1-
57 DI57 HEAT EXCAHNGER CL FAN 1 HXCF-1 HXCF-1 RUN F/B HXCF1FB 1 CARD4 9/DI57 IX113,IX114
58 DI58 HXCF-1 MTR O/L TRP HXCF1TR 1 10/DI58 IX115,IX116
59 DI59 HXCF-1 L/R MODE HXCF1LR 1 11/DI59 IX117,IX118
60 DI60 HEAT EXCAHNGER CL FAN 2 HXCF-2 HXCF-2 RUN F/B HXCF2FB 1 12/DI60 IX119,IX120
61 DI61 HXCF-2 MTR O/L TRP HXCF2TR 1 13/DI61 IX121,IX122
62 DI62 HXCF-2 L/R MODE HXCF2LR 1 14/DI62 IX123,IX124
63 DI63 HEAT EXCAHNGER CL FAN 3 HXCF-3 HXCF-3 RUN F/B HXCF3FB 1 15/DI63 IX125,IX126
64 DI64 HXCF-3 MTR O/L TRP HXCF3TR 1 16/DI64 IX127,IX128
65 DI65 HXCF-3 L/R MODE HXCF3LR 1 1/DI65 IX129,IX130
66 DI66 HEAT EXCAHNGER CL FAN 4 HXCF-4 HXCF-4 RUN F/B HXCF4FB 1 2/DI66 IX131,IX132
67 DI67 HXCF-4 MTR O/L TRP HXCF4TR 1 3/DI67 IX133,IX134
68 DI68 HXCF-4 L/R MODE HXCF4LR 1 4/DI68 IX135,IX136
69 DI69 SER AIR COMPRESSOR1 COMP-1 COMP-1 RUN F/B COMP1FB 1 5/DI69 IX137,IX138
70 DI70 COMP-1 MTR O/L TRP COMP1TR 1 6/DI70 IX139,IX140
71 DI71 COMP-1 L/R MODE COMP1LR 1 7/DI71 IX141,IX142
72 DI72 SER AIR COMPRESSOR2 COMP-2 COMP-2 RUN F/B COMP2FB 1 (DI05) 8/DI72 IX143,IX144
5000/1-
73 DI73 COMP-2 MTR O/L TRP COMP2TR 1 CARD5 9/DI73 IX145,IX146
74 DI74 COMP-2 L/R MODE COMP2LR 1 10/DI74 IX147,IX148
75 DI75 SER AIR COMPRESSOR3 COMP-3 COMP-3 RUN F/B COMP3FB 1 11/DI75 IX149,IX150
76 DI76 COMP-3 MTR O/L TRP COMP3TR 1 12/DI76 IX151,IX152
77 DI77 COMP-3 L/R MODE COMP3LR 1 13/DI77 IX153,IX154
78 DI78 INST AIR COMPRESSOR1 COMP-4 COMP-4 RUN F/B COMP4FB 1 14/DI78 IX155,IX156
79 DI79 COMP-4 MTR O/L TRP COMP4TR 1 15/DI79 IX157,IX158
80 DI80 COMP-4 L/R MODE COMP4LR 1 16/DI80 IX159,IX160
81 DI81 INST AIR COMPRESSOR2 COMP-5 COMP-5 RUN F/B COMP5FB 1 1/DI81 IX161,IX162
82 DI82 COMP-5 MTR O/L TRP COMP5TR 1 2/DI82 IX163,IX164
83 DI83 COMP-5 L/R MODE COMP5LR 1 3/DI83 IX165,IX166
84 DI84 AIR DILUTION DMPR ADD-1 AIR DIL DMPR OPN F/B ADD1OPNFB 1 4/DI84 IX167,IX168
85 DI85 AIR DIL DMPR CLS F/B ADD1CLSFB 1 5/DI85 IX169,IX170
86 DI86 AIR DIL DMPR OPN TRQ ADD1OPNTL 1 6/DI86 IX171,IX172
87 DI87 AIR DIL DMPR CLS TRQ ADD1CLSTL 1 7/DI87 IX173,IX174
88 DI88 AIR DIL DMPR OPN RUN FB ADD1ORFB 1 (DI06) 8/DI88 IX175,IX176
5000/2-
89 DI89 AIR DIL DMPR CLS RUN FB ADD1CRFB CARD1 9/DI89 IX177,IX178
90 DI90 AIR DIL DMPR L/R MODE ADD1LR 1 10/DI90 IX179,IX180
CARD1

91 DI91 DM SKID-1 PUMP1 DMS1P1 DM SKID 1 PMP-1 RUN F/B DMS1P1FB 1 11/DI91 IX181,IX182
92 DI92 DM SKID 1 PMP-1 O/L TRP DMS1P1TR 1 12/DI92 IX183,IX184
93 DI93 DM SKID 1 PMP-1 L/R MODE DMS1P1LR 1 13/DI93 IX185,IX186
94 DI94 DM SKID-1 PUMP2 DMS1P1 DM SKID 1 PMP-2 RUN F/B DMS1P1FB 1 14/DI94 IX187,IX188
95 DI95 DM SKID 1 PMP-2 O/L TRP DMS1P1TR 1 15/DI95 IX189,IX190
96 DI96 DM SKID 1 PMP-2 L/R MODE DMS1P1LR 1 16/DI96 IX191,IX192
97 DI97 DM SKID-2 PUMP1 DMS2P1 DM SKID 2 PMP-1 RUN F/B DMS2P1FB 1 1/DI97 IX193,IX194
98 DI98 DM SKID 2 PMP-1 O/L TRP DMS2P1TR 1 2/DI98 IX195,IX196
99 DI99 DM SKID 2 PMP-1 L/R MODE DMS2P1LR 1 3/DI99 IX197,IX198
100 DI100 DM SKID-2 PUMP2 DMS2P1 DM SKID 2 PMP-2 RUN F/B DMS2P1FB 1 4/DI100 IX199,IX200
101 DI101 DM SKID 2 PMP-2 O/L TRP DMS2P1TR 1 5/DI101 IX201,IX202
102 DI102 DM SKID 2 PMP-2 L/R MODE DMS2P1LR 1 6/DI102 IX203,IX204
103 DI103 DM SKID-3 PUMP1 DMS2P2 DM SKID 2 PMP-2 RUN F/B DMS2P2FB 1 7/DI103 IX205,IX206
104 DI104 DM SKID 2 PMP-2 O/L TRP DMS2P2TR 1 (DI07) 8/DI104 IX207,IX208
5000/2-
105 DI105 DM SKID 2 PMP-2 L/R MODE DMS2P2LR 1 CARD2 9/DI105 IX209,IX210
106 DI106 DM SKID-3 PUMP2 DMS2P2 DM SKID 3 PMP-2 RUN F/B DMS2P2FB 1 10/DI106 IX211,IX212
107 DI107 DM SKID 3 PMP-2 O/L TRP DMS2P2TR 1 11/DI107 IX213,IX214
108 DI108 DM SKID 3 PMP-2 L/R MODE DMS2P2LR 1 12/DI108 IX215,IX216
109 DI109 HYD SKID-1 PUMP HYD1P1 HYD SKID 1 PMP-1 RUN F/B HYDP1FB 1 13/DI109 IX217,IX218
110 DI110 HYD SKID 1 PMP-1 O/L TRP HYDP1TR 1 14/DI110 IX219,IX220
111 DI111 HYD SKID 1 PMP-1 L/R MODE HYDP1LR 1 15/DI111 IX221,IX222
112 DI112 HYD SKID-2 PUMP HYD2P1 HYD SKID 2 PMP-1 RUN F/B HYDP2FB 1 16/DI112 IX223,IX224
113 DI113 HYD SKID 2 PMP-1 O/L TRP HYDP2TR 1 1/DI113 IX225,IX226
114 DI114 HYD SKID 2 PMP-1 L/R MODE HYDP2LR 1 2/DI114 IX227,IX228
115 DI115 HYD SKID-3 PUMP HYD2P2 IND FUR HYD PMP-2 RUN F/B HYDP2FB 1 3/DI115 IX229,IX230
116 DI116 IND FUR HYD PMP-2 O/L TRP HYDP2TR 1 4/DI116 IX231,IX232
117 DI117 IND FUR HYD PMP-2 L/R MODE HYDP2LR 1 5/DI117 IX233,IX234
DIFFERENTIAL PRESS SW BF CMBR- DPS01
DP SW BF CMBR1 DPAH1 1
118 DI118 1 6/DI118 IX235,IX236
DIFFERENTIAL PRESS SW BF CMBR- DPS02 DP SW BF CMBR2 DPAH2 1
119 DI119 2 7/DI119 IX237,IX238
DIFFERENTIAL PRESS SW BF CMBR- DPS03
DP SW BF CMBR3 DPAH3 1 (DI08)
120 DI120 3 8/DI120 IX239,IX240
5000/2-
DIFFERENTIAL PRESS SW BF CMBR- CARD3
4 DPS04 DP SW BF CMBR4 DPAH4 1
121 DI121 9/DI121 IX241,IX242
DIFFERENTIAL PRESS SW BF CMBR- DPS05
5 DP SW BF CMBR5 DPAH5 1
122 DI122 10/DI122 IX243,IX244
DIFFERENTIAL PRESS SW BF CMBR-
DPS06 DP SW BF CMBR6 DPAH6 1
123 DI123 6 11/DI123 IX245,IX246
124 DI124 DIFFERENTIAL PRESS SW BF DPS07 DP SW BF DPAH7 1 12/DI124 IX247,IX248
125 DI125 BF BNKR-1 LVL SW LSH01 LVL SW BF BNKR1 LAH1 1 13/DI125 IX249,IX250
126 DI126 BF BNKR-2 LVL SW LSH02 LVL SW BF BNKR2 LAH2 1 14/DI126 IX251,IX252
127 DI127 BF BNKR-3 LVL SW LSH02 LVL SW BF BNKR3 LAH3 1 15/DI127 IX253,IX254
128 DI128 BF BNKR-4 LVL SW LSH04 LVL SW BF BNKR4 LAH4 1 16/DI128 IX255,IX256
129 DI129 BF BNKR-5 LVL SW LSH05 LVL SW BF BNKR5 LAH5 1 1/DI129 IX257,IX258
130 DI130 BF BNKR-6 LVL SW LSH06 LVL SW BF BNKR6 LAH6 1 2/DI130 IX259,IX260
131 DI131 HET EX BNKR LVL SW LSH07 LVL SW HE BNKR LAH7 1 3/DI131 IX261,IX262

COOLING WATER TANK LEVEL1 SW CTLL1 COOLING WATER TANK LVL SW1 CTLL1 1
132 DI132 4/DI132 IX263,IX264
COOLING WATER TANK LEVEL2 SW CTLL2 COOLING WATER TANK LVL SW2 CTLL2 1
133 DI133 5/DI133 IX265,IX266

EMERGENCY WATER PUMP DPS EWP1DPH EMG WATER PUMP1 DPSH EWP1_DPSH 1
134 DI134 6/DI134 IX267,IX268
EMERGENCY WATER PUMP-2_DP EWP2DPH EMG WATER PUMP2 DPSH EWP2_DPSH 1
135 DI135 SWITCH 7/DI135 IX269,IX270
FURNACE COOLING PUMP-1_DP (DI09)
SWITCH FCP1DPH FCP WATER PUMP1 DPSH FCP1_DPSH 1
136 DI136 5000/2- 8/DI136 IX271,IX272
CARD4
FURNACE COOLING PUMP-2_DP
SWITCH FCP2DPH FCP WATER PUMP2 DPSH FCP2_DPSH 1
137 DI137 9/DI137 IX273,IX274
FURNACE COOLING PUMP-3_DP FCP2DPH FCP WATER PUMP3 DPSH FCP2_DPSH 1
138 DI138 SWITCH 10/DI138 IX275,IX276
INDUCTION COOLING PUMP-1_DP ICWP1DPH
ICWP WATER PMP1 DPSH ICWP1_DPSH 1
139 DI139 SWITCH 11/DI139 IX277,IX278
INDUCTION COOLING PUMP-2_DP ICWP2DPH ICWP WATER PMP2 DPSH ICWP2_DPSH 1
140 DI140 SWITCH 12/DI140 IX279,IX280
141 DI141 INDUCTION FUR 1 IND FUR1 ON/OFF FB INDF1FB 13/DI141 IX281,IX282
142 DI142 IND FUR1 TRP FB INDF1TR 14/DI142 IX283,IX284
143 DI143 INDUCTION FUR 2 IND FUR2 ON/OFF FB INDF2FB 15/DI143 IX285,IX286
144 DI144 IND FUR2 TRP FB INDF2TR 16/DI144 IX287,IX288
145 DI145 INDUCTION FUR 3 IND FUR3 ON/OFF FB INDF3FB 1/DI145 IX289,IX290
146 DI146 IND FUR3 TRP FB INDF3TR 2/DI146 IX291,IX292
147 DI147 BF CMBR1 I/L DMPR DMPR OPEN FB C1IL_OPN 3/DI147 IX293,IX294
148 DI148 DMPR CLS FB C1IL_CLS 4/DI148 IX295,IX296
149 DI149 BF CMBR1 O/L DMPR DMPR OPEN FB C1OL_OPN 5/DI149 IX297,IX298
150 DI150 DMPR CLS FB C1OL_CLS 6/DI150 IX299,IX300
151 DI151 BF CMBR2 I/L DMPR DMPR OPEN FB C2IL_OPN 7/DI151 IX301,IX302
152 DI152 DMPR CLS FB C2IL_CLS (DI10) 8/DI152 IX303,IX304
5000/2-
153 DI153 BF CMBR2 O/L DMPR DMPR OPEN FB C2OL_OPN CARD5 9/DI153 IX305,IX306
154 DI154 DMPR CLS FB C2OL_CLS 10/DI154 IX307,IX308
155 DI155 BF CMBR3 I/L DMPR DMPR OPEN FB C3IL_OPN 11/DI155 IX309,IX310
156 DI156 DMPR CLS FB C3IL_CLS 12/DI156 IX311,IX312
157 DI157 BF CMBR3 O/L DMPR DMPR OPEN FB C3OL_OPN 13/DI157 IX313,IX314
158 DI158 DMPR CLS FB C3OL_CLS 14/DI158 IX315,IX316
159 DI159 BF CMBR4 I/L DMPR DMPR OPEN FB C4IL_OPN 15/DI159 IX317,IX318
160 DI160 DMPR CLS FB C4IL_CLS 16/DI160 IX319,IX320
161 DI161 BF CMBR4 O/L DMPR DMPR OPEN FB C4OL_OPN 1/DI161 IX321,IX322
162 DI162 DMPR CLS FB C4OL_CLS 2/DI162 IX323,IX324
163 DI163 BF CMBR3 I/L DMPR DMPR OPEN FB C5IL_OPN 3/DI163 IX325,IX326
164 DI164 DMPR CLS FB C5IL_CLS 4/DI164 IX327,IX328
165 DI165 BF CMBR3 O/L DMPR DMPR OPEN FB C5OL_OPN 5/DI165 IX329,IX330
166 DI166 DMPR CLS FB C5OL_CLS 6/DI166 IX331,IX332
167 DI167 BF CMBR4 I/L DMPR DMPR OPEN FB C6IL_OPN 7/DI167 IX333,IX334
168 DI168 DMPR CLS FB C6IL_CLS (DI11) 8/DI168 IX335,IX336
5000/3-
169 DI169 BF CMBR4 O/L DMPR DMPR OPEN FB C6OL_OPN CARD1 9/DI169 IX337,IX338
170 DI170 DMPR CLS FB C6OL_CLS 10/DI170 IX339,IX340
171 DI171 CENTRALISED AC1 CENTRALISED AC1 RUN FB AC1FB 11/DI171 IX341,IX342
172 DI172 CENTRALISED AC2 CENTRALISED AC2 RUN FB AC2FB 12/DI172 IX343,IX344
173 DI173 CENTRALISED AC3 CENTRALISED AC3 RUN FB AC3FB 13/DI173 IX345,IX346
174 DI174 spare 14/DI174 IX347,IX348
175 DI175 spare 15/DI175 IX349,IX350
176 DI176 spare 16/DI176 IX351,IX352
177 DI177 spare 1/DI177 IX353,IX354
178 DI178 spare 2/DI178 IX355,IX356
179 DI179 spare 3/DI179 IX357,IX358
180 DI180 spare 4/DI180 IX359,IX360
181 DI181 spare 5/DI181 IX361,IX362
182 DI182 spare 6/DI182 IX363,IX364
183 DI183 spare 7/DI183 IX365,IX366
184 DI184 spare (DI12) 8/DI184 IX367,IX368
5000/3-
185 DI185 spare CARD2 9/DI185 IX369,IX370
186 DI186 spare 10/DI186 IX371,IX372
187 DI187 spare 11/DI187 IX373,IX374
188 DI188 spare 12/DI188 IX375,IX376
189 DI189 spare 13/DI189 IX377,IX378
190 DI190 spare 14/DI190 IX379,IX380
191 DI191 spare 15/DI191 IX381,IX382
192 DI192 spare 16/DI192 IX383,IX384

DIGITAL OUTPUT
193 DQ01 CFR1 ROW 1 1/DQ01 RLY CARD01/RLY01
194 DQ02 CFR2 ROW 2 2/DQ02 RLY CARD01/RLY02
195 DQ03 CFR3 ROW 3 3/DQ03 RLY CARD01/RLY03
196 DQ04 CFR4 ROW 4 4/DQ04 RLY CARD01/RLY04
197 DQ05 CFR5 ROW 5 5/DQ05 RLY CARD01/RLY05
198 DQ06 CFR6 ROW 6 6/DQ06 RLY CARD01/RLY06
199 DQ07 CFC1 COLUMN 01 7/DQ07 RLY CARD02/RLY01 OX01,OX02
200 DQ08 CFC2 COLUMN 02 (DO01) 8/DQ08 RLY CARD02/RLY02 OX03,OX04
CPU5630-
201 DQ09 CFC3 COLUMN 03 CARD1 9/DQ09 RLY CARD02/RLY03 OX05,OX06
202 DQ10 CFC4 COLUMN 04 10/DQ10 RLY CARD02/RLY04 OX07,OX08
203 DQ11 CFC5 COLUMN 05 11/DQ11 RLY CARD02/RLY05 OX09,OX10
204 DQ12 CFC6 COLUMN 06 12/DQ12 RLY CARD02/RLY06 OX11,OX12
205 DQ13 CFC7 COLUMN 07 13/DQ13 RLY CARD02/RLY07 OX13,OX14
206 DQ14 CFC8 COLUMN 08 14/DQ14 RLY CARD02/RLY08 OX15,OX16
207 DQ15 CFC9 COLUMN 09 15/DQ15 RLY CARD03/RLY01 OX17,OX18
208 DQ16 CFC10 COLUMN 10 16/DQ16 RLY CARD03/RLY02 OX19,OX20
209 DQ17 CFC11 COLUMN 11 1/DQ17 RLY CARD03/RLY03 OX21,OX22
210 DQ18 CFC12 COLUMN 12 2/DQ18 RLY CARD03/RLY04 OX23,OX24
211 RLY CARD03/RLY05 OX25,OX26
212 RLY CARD03/RLY06 OX27,OX28
213 RLY CARD03/RLY07 OX29,OX30
214 RLY CARD03/RLY08 OX31,OX32
215 RLY CARD04/RLY01 OX33,OX34
216 RLY CARD04/RLY02 OX35,OX36
217 RLY CARD04/RLY03 OX37,OX38
218 RLY CARD04/RLY04 OX39,OX40
219 RLY CARD04/RLY05 OX41,OX42
220 RLY CARD04/RLY06 OX43,OX44
221 RLY CARD04/RLY07 OX45,OX46
222 RLY CARD04/RLY08 OX47,OX48
223 RLY CARD05/RLY01 OX49,OX50
224 RLY CARD05/RLY02 OX51,OX52
225 RLY CARD05/RLY03 OX53,OX54
226 RLY CARD05/RLY04 OX55,OX56
227 RLY CARD05/RLY05 OX57,OX58
228 RLY CARD05/RLY06 OX59,OX60
229 RLY CARD05/RLY07 OX61,OX62
230 RLY CARD05/RLY08 OX63,OX64
231 RLY CARD06/RLY01 OX65,OX66
232 RLY CARD06/RLY02 OX67,OX68
233 RLY CARD06/RLY03 OX69,OX70
234 RLY CARD06/RLY04 OX71,OX72
235 RLY CARD06/RLY05 OX73,OX74
236 RLY CARD06/RLY06 OX75,OX76
237 RLY CARD06/RLY07 OX77,OX78
238 RLY CARD06/RLY08 OX79,OX80
239 RLY CARD07/RLY01 OX81,OX82
240 RLY CARD07/RLY02 OX83,OX84
241 RLY CARD07/RLY03 OX85,OX86
242 RLY CARD07/RLY04 OX87,OX88
243 RLY CARD07/RLY05 OX89,OX90
244 RLY CARD07/RLY06 OX91,OX92
245 RLY CARD07/RLY07 OX93,OX94
246 (DO02) RLY CARD07/RLY08 OX95,OX96
CPU5630-
247 CARD2 RLY CARD08/RLY01 OX97,OX98
248 RLY CARD08/RLY02 OX99,OX100
249 RLY CARD08/RLY03 OX101,OX102
250 RLY CARD08/RLY04 OX103,OX104
251 RLY CARD08/RLY05 OX105,OX106
252 RLY CARD08/RLY06 OX107,OX108
253 RLY CARD08/RLY07 OX109,OX110
254 RLY CARD08/RLY08 OX111,OX112
255 RLY CARD09/RLY01 OX113,OX114
256 RLY CARD09/RLY02 OX115,OX116
257 RLY CARD09/RLY03 OX117,OX118
258 RLY CARD09/RLY04 OX119,OX120
259 RLY CARD09/RLY05 OX121,OX122
260 RLY CARD09/RLY06 OX123,OX124
261 RLY CARD09/RLY07 OX125,OX126
262 RLY CARD09/RLY08 OX127,OX128
263 RLY CARD10/RLY 01 OX127,OX128
264 RLY CARD10/RLY 02 OX127,OX128
265 RLY CARD10/RLY 03 OX127,OX128
266 RLY CARD10/RLY 04 OX129,OX130
267 RLY CARD10/RLY 05 OX131,OX132
268 RLY CARD10/RLY 06 OX133,OX134
269 RLY CARD10/RLY 07 OX135,OX136
270 RLY CARD10/RLY 08 OX137,OX138
271 DQ19 SPARE SPARE 3/DQ19 RLY CARD11/RLY 01 OX139,OX140
272 DQ20 SOV-3 ON CMD SOV3ON 1 4/DQ20 RLY CARD11/RLY 02 OX141,OX142
273 DQ21 CTF-1 ON CMD CTF1ON 1 5/DQ21 RLY CARD11/RLY 03 OX143,OX144
274 DQ22 CTF-2 ON CMD CTF2ON 1 6/DQ22 RLY CARD11/RLY 04 OX145,OX146
275 DQ23 FUR CW PMP-1 ON CMD FCP1ON 1 7/DQ23 RLY CARD11/RLY 05 OX147,OX148
276 DQ24 FUR CW PMP-2 ON CMD FCP2ON 1 8/DQ24 RLY CARD11/RLY 06 OX149,OX150
277 DQ25 FUR CW PMP-3 ON CMD FCP3ON 1 9/DQ25 RLY CARD12/RLY 01 OX151,OX152
278 DQ26 E/M CW PMP-1 ON CMD EWP1ON 1 10/DQ26 RLY CARD12/RLY 02 OX153,OX154
279 DQ27 E/M CW PMP-2 ON CMD EWP2ON 1 11/DQ27 RLY CARD12/RLY 03 OX155,OX156
280 DQ28 CW PMP-1 ON CMD CWP1ON 1 12/DQ28 RLY CARD12/RLY 04 OX157,OX158
281 DQ29 CW PMP-2 ON CMD CWP2ON 1 13/DQ29 RLY CARD12/RLY 05 OX159,OX160
282 DQ30 CW PMP-3 ON CMD CWP3ON 1 14/DQ30 RLY CARD12/RLY 06 OX161,OX162
283 DQ31 IND CW PMP-1 ON CMD ICWP1ON 1 15/DQ31 RLY CARD12/RLY 07 OX163,OX164
284 DQ32 IND CW PMP-2 ON CMD ICWP2ON 1 16/DQ32 RLY CARD12/RLY 08 OX165,OX166
285 DQ33 ID-1 ON CMD ID1ON 1 1/DQ33 RLY CARD13/RLY 01 OX167,OX168
286 DQ34 ID-1 SUC DMPR ON CMD ID1SDON 1 2/DQ34 RLY CARD13/RLY 02 OX169,OX170
287 DQ35 ID-1 DIS DMPR ON CMD ID1DDON 1 3/DQ35 RLY CARD13/RLY 03 OX171,OX172
288 DQ36 ID-2 ON CMD ID2ON 1 4/DQ36 RLY CARD13/RLY 04 OX173,OX174
289 DQ37 ID-2 SUC DMPR ON CMD ID2SDON 1 5/DQ37 RLY CARD13/RLY 05 OX175,OX176
290 DQ38 ID-2 DIS DMPR ON CMD ID2DDON 1 6/DQ38 RLY CARD13/RLY 06 OX177,OX178
291 DQ39 HXCF-1 ON CMD HXCF1ON 1 7/DQ39 RLY CARD13/RLY 07 OX179,OX180
292 DQ40 HXCF-2 ON CMD HXCF2ON 1 (DO03) 8/DQ40 RLY CARD13/RLY 08 OX181,OX182
CPU5630-
293 DQ41 HXCF-3 ON CMD HXCF3ON 1 CARD3 9/DQ41 RLY CARD14/RLY 01 OX183,OX184
294 DQ42 HXCF-4 ON CMD HXCF4ON 1 10/DQ42 RLY CARD14/RLY 02 OX185,OX186
295 DQ43 COMP-1 ON CMD COMP1ON 1 11/DQ43 RLY CARD14/RLY 03 OX187,OX188
296 DQ44 COMP-2 ON COM COMP2ON 12/DQ44 RLY CARD14/RLY 04 OX189,OX190
297 DQ45 DM SKID 1 PMP-1 ON CMD DMS1P1ON 1 13/DQ45 RLY CARD14/RLY 05 OX191,OX192
298 DQ46 DM SKID 1 PMP-2 ON CMD DMS1P1ON 1 14/DQ46 RLY CARD14/RLY 06 OX193,OX194
299 DQ47 DM SKID2 PMP-1 ON CMD DMS2P1ON 1 15/DQ47 RLY CARD14/RLY 07 OX195,OX196
300 DQ48 DM SKID2 PMP-2 ON CMD DMS2P2ON 1 16/DQ48 RLY CARD14/RLY 08 OX197,OX198
301 DQ49 DM SKID3 PMP-1 ON CMD DMS3P1ON 1 1/DQ49 RLY CARD15/RLY 01 OX199,OX200
302 DQ50 DM SKID 3 PMP-2 ON CMD DMS3P2ON 1 2/DQ50 RLY CARD15/RLY 02 OX201,OX202
303 DQ51 HYD SKID 1 PMP ON CMD HYDS1PON 1 3/DQ51 RLY CARD15/RLY 03 OX203,OX204
304 DQ52 HYD SKID 2 PMP ON CMD HYDS2PON 1 4/DQ52 RLY CARD15/RLY 04 OX205,OX206
305 DQ53 HYD SKID 3 PMP ON CMD HYDS3PON 1 5/DQ53 RLY CARD15/RLY 05 OX207,OX208
306 DQ54 CHAMBER 1 DAMPERS CH1-SUC-ON CH1 SUC DMPR ON COM C1SUC_ON 6/DQ54 RLY CARD15/RLY 06 OX209,OX210
307 DQ55 CH1-DIS-ON CH1 DIS DMPR ON COM C1DIS_ON 7/DQ55 RLY CARD15/RLY 07 OX211,OX212
308 DQ56 CHAMBER 2 DAMPERS CH2-SUC-ON CH2 SUC DMPR ON COM C2SUC_ON (DO04) 8/DQ56 RLY CARD15/RLY 08 OX213,OX214
CPU5630-
309 DQ57 CH2-DIS-ON CH2 DIS DMPR ON COM C2DIS_ON CARD4 9/DQ57 RLY CARD16/RLY01 OX215,OX216
310 DQ58 CHAMBER 3 DAMPERS CH3-SUC-ON CH3 SUC DMPR ON COM C3SUC_ON 10/DQ58 RLY CARD16/RLY02 OX217,OX218
311 DQ59 CH3-DIS-ON CH3 DIS DMPR ON COM C3DIS_ON 11/DQ59 RLY CARD16/RLY03 OX219,OX220
312 DQ60 CHAMBER 4 DAMPERS CH4-SUC-ON CH4 SUC DMPR ON COM C4SUC_ON 12/DQ60 RLY CARD16/RLY04 OX221,OX222
313 DQ61 CH4-DIS-ON CH4 DIS DMPR ON COM C4DIS_ON 13/DQ61 RLY CARD16/RLY05 OX223,OX224
314 DQ62 CHAMBER 5 DAMPERS CH5-SUC-ON CH5 SUC DMPR ON COM C5SUC_ON 14/DQ62 RLY CARD16/RLY06 OX225,OX226
315 DQ63 CH5-DIS-ON CH5 DIS DMPR ON COM C5DIS_ON 15/DQ63 RLY CARD16/RLY07 OX227,OX228
316 DQ64 CHAMBER 6 DAMPERS CH6-SUC-ON CH6 SUC DMPR ON COM C6SUC_ON 16/DQ64 RLY CARD16/RLY08 OX229,OX230
317 DQ65 CH6-DIS-ON CH6 DIS DMPR ON COM C6DIS_ON 1/DQ65 RLY CARD17/RLY01 OX231,OX232
318 DQ66 SERVICE COMPRESSOR SER COMP1 ON COM COMP1_0N 2/DQ66 RLY CARD17/RLY02 OX233,OX234
319 DQ67 SER COMP2 ON COM COMP2_ON 3/DQ67 RLY CARD17/RLY03 OX235,OX236
320 DQ68 SER COMP3 ON COM COMP3_ON 4/DQ68 RLY CARD17/RLY04 OX237,OX238
321 DQ69 INST COMPRESSOR INST COMP1 ON COM COMP4_ON 5/DQ69 RLY CARD17/RLY05 OX239,OX240
322 DQ70 INST COMP2 ON COM COMP5_ON 6/DQ70 RLY CARD17/RLY06 OX241,OX242
323 DQ71 CENTRALISED AC AC1 ON COM AC1ON 7/DQ71 RLY CARD17/RLY07 OX243,OX244
324 DQ72 AC2 ON COM AC2ON (DO05) 8/DQ72 RLY CARD17/RLY08 OX245,OX246
CPU5630-
325 DQ73 AC3 ON COM AC3ON CARD5 9/DQ73 RLY CARD18/RLY01 OX247,OX248
326 DQ74 10/DQ74 RLY CARD18/RLY02 OX249,OX250
327 DQ75 11/DQ75 RLY CARD18/RLY03 OX251,OX252
328 DQ76 12/DQ76 RLY CARD18/RLY04 OX253,OX254
329 DQ77 13/DQ77 RLY CARD18/RLY05 OX255,OX256
330 DQ78 14/DQ78 RLY CARD18/RLY06 OX257,OX258
331 DQ79 15/DQ79 RLY CARD18/RLY07 OX259,OX260
332 DQ80 16/DQ80 RLY CARD18/RLY08 OX261,OX262

ANALOG INPUT
333 AI01 CDCV1 POS F/B CDCV1SO 1 1/AI01 IY01,IY02
334 AI02 CTF-1 CURRENT O/P CTF1CO 1 2/AI02 IY03,IY04
335 AI03 CTF-1 SPD O/P CTF1SO 1 3/AI03 IY05,IY06
336 AI04 CTF-2 CURRENT O/P CTF2CO 1 (AI01) 4/AI04 IY07,IY08
CPU5630-
337 AI05 CTF-2 SPD O/P CTF2SO 1 CARD6 5/AI05 IY09,IY10
338 AI06 CW PMP-1 CURRENT O/P CWP1CO 1 6/AI06 IY11,IY12
339 AI07 CW PMP-1 SPD O/P CWP1SO 1 7/AI07 IY13,IY14
340 AI08 CW PMP-2 CURRENT O/P CWP2CO 1 8/AI08 IY15,IY16
341 AI09 CW PMP-2 SPD O/P CWP2SO 1 1/AI09 IY17,IY18
342 AI10 CW PMP-3 CURRENT O/P CWP3CO 1 2/AI10 IY19,IY20
343 AI11 CW PMP-3 SPD O/P CWP3SO 1 3/AI11 IY21,IY22
344 AI12 ID-1 CURRENT O/P ID1CO 1 (AI02) 4/AI12 IY23,IY24
CPU5000/1-
345 AI13 ID-1 SPD O/P ID1SO 1 CARD6 5/AI13 IY25,IY26
346 AI14 ID-2 CURRENT O/P ID2CO 1 6/AI14 IY27,IY28
347 AI15 ID-2 SPD O/P ID2SO 1 7/AI15 IY29,IY30
348 AI16 AIR DIL DMPR POSITION FB ADD1POS 1 8/AI16 IY31,IY32
349 AI17 DUST MONITOR DM101 1/AI17 IY33,IY34
350 AI18 SOFT WTR FLO FI100 2/AI18 IY35,IY36
351 AI19 DM WTR FLO FI101 3/AI19 IY37,IY38
352 AI20 CWP O/L PRESS PI201 (AI03) 4/AI20 IY39,IY40
CPU5000/2-
353 AI21 CWP O/L FLO 1 FI201A CARD6 5/AI21 IY41,IY42
354 AI22 CWP O/L FLO 2 FI201B 6/AI22 IY43,IY44
355 AI23 FI201C 7/AI23 IY45,IY46
356 AI24 ICWP O/L PRESS PI202 8/AI24 IY47,IY48
357 AI25 ICWP O/L TEMP TI202 1/AI25 IY49,IY50
358 AI26 ICWP O/L FLO FI202 2/AI26 IY51,IY52
359 AI27 DM MAIN TNK LVL LI301 3/AI27 IY53,IY54
360 AI28 DM EMG TNK LVL LI302 (AI04) 4/AI28 IY55,IY56
CPU5000/2-
361 AI29 FCP O/L PRESS PI301 CARD7 5/AI29 IY57,IY58
362 AI30 FCP O/L WTR TEMP TI301 6/AI30 IY59,IY60
363 AI31 IND FUR I/L WTR HDR PRESS PI301A 7/AI31 IY61,IY62
364 AI32 IND FUR I/L WTR HDR FLO FI301A 8/AI32 IY63,IY64
365 AI33 EMG PMP O/L PRESS PI302 1/AI33 IY65,IY66
366 AI34 SERV AIR PRESS PI303A 2/AI34 IY67,IY68
367 AI35 INST AIR PRESS PI303B 3/AI35 IY69,IY70
368 AI36 FLUE GAS TEMP HOOD TI501 (AI05) 4/AI36 IY71,IY72
CPU5000/2-
369 AI37 FLUE GAS TEMP 1 LINE TI502 CARD8 5/AI37 IY73,IY74
370 AI38 FLUE GAS TEMP 2 LINE TI503 6/AI38 IY75,IY76
371 AI39 FLUE GAS TEMP 3 LINE TI504 7/AI39 IY77,IY78
372 AI40 FLUE GAS TEMP HTEX I/L TI505 8/AI40 IY79,IY80
373 AI41 FLUE GAS TEMP1 HTEX O/L TI506A 1/AI41 IY81,IY82
374 AI42 FLUE GAS TEMP2 HTEX O/L TI506B 2/AI42 IY83,IY84
375 AI43 FLUE GAS TEMP BF I/L TI507 3/AI43 IY85,IY86
376 AI44 FLUE GAS TEMP BF O/L TI508 (AI06) 4/AI44 IY87,IY88
CPU5000/3-
377 AI45 FLUE GAS PRESS HOOD PI501 CARD3 5/AI45 IY89,IY90
378 AI46 FLUE GAS PRESS HTEX I/L PI502 6/AI46 IY91,IY92
379 AI47 FLUE GAS PRESS BF I/L PI503 7/AI47 IY93,IY94
380 AI48 FLUE GAS PRESS BF CMBR1 SUC PI504A 8/AI48 IY95,IY96
381 AI49 FLUE GAS PRESS BF CMBR1 DIS PI504B 1/AI49 IY97,IY98
382 AI50 FLUE GAS PRESS BF CMBR2 SUC PI505A 2/AI50 IY99,IY100
383 AI51 FLUE GAS PRESS BF CMBR2 DIS PI505B 3/AI51 IY101,IY102
384 AI52 FLUE GAS PRESS BF CMBR3 SUC PI506A (AI07) 4/AI52 IY103,IY104
CPU5000/3-
385 AI53 FLUE GAS PRESS BF CMBR3 DIS PI506B CARD4 5/AI53 IY105,IY106
386 AI54 FLUE GAS PRESS BF CMBR4 SUC PI507A 6/AI54 IY107,IY108
387 AI55 FLUE GAS PRESS BF CMBR4 DIS PI507B 7/AI55 IY109,IY110
388 AI56 FLUE GAS PRESS BF CMBR5 SUC PI508A 8/AI56 IY111,IY112
389 AI57 FLUE GAS PRESS BF CMBR5 DIS PI508B 1/AI57 IY113,IY114
390 AI58 FLUE GAS PRESS BF CMBR6 SUC PI509A 2/AI58 IY115,IY116
391 AI59 FLUE GAS PRESS BF CMBR6 DIS PI509B 3/AI59 IY117,IY118
392 AI60 FLUE GAS PRESS BF O/L PI510 (AI08) 4/AI60 IY119,IY120
CPU5000/3-
393 AI61 CARD5 5/AI61 IY121,IY122
394 AI62 6/AI62 IY123,IY124
395 AI63 7/AI63 IY125,IY126
396 AI64 8/AI64 IY127,IY128

ANALOG OUTPUT
CONDENSATE DRAIN VLV(CDCV-1) CDCV-1 CDCV1 SET POINT CDCV1SS 1
397 AO01 (AQ01) 1/AQ01 OY01,OY02
398 AO02 CTF1 SET SPEED CTF1SS 1 CPU5630- 2/AQ02 OY03,OY04
399 AO03 CTF2 SET SPEED CTF2SS 1 CARD7 3/AQ03 OY05,OY06
400 AO04 CWP1 SET SPEED CWP1SS 1 4/AQ04 OY07,OY08
401 AO05 CWP2 SET SPEED CWP2SS 1 1/AQ05 OY09,OY10
402 AO06 CWP3 SET SPEED CWP3SS 1 (AQ02) 2/AQ06 OY11,OY12
CPU5630-
403 AO07 ID FAN1 SET SPEED ID1SS 1 CARD8 3/AQ07 OY13,OY14
404 AO08 ID FAN2 SET SPEED ID2SS 1 4/AQ08 OY15,OY16
405 AO09 AIR DILUTION DMPR SET ADD1CMD 1 1/AQ09 OY17,OY18
406 AO10 (AQ03) 2/AQ10 OY19,OY20
CPU5000/1-
407 AO11 CARD7 3/AQ11 OY21,OY22
408 AO12 4/AQ12 OY23,OY24
409 AO13 1/AQ13 OY25,OY26
410 AO14 (AQ04) 2/AQ14 OY27,OY28
CPU5000/1-
411 AO15 CARD8 3/AQ15 OY29,OY30
412 AO16 4/AQ16 OY31,OY32
TERMINAL
FERRULE NO
C1SV1
C1SV2
C1SV3
C1SV4
C1SV5
C1SV6
C1SV7
C1SV8
C1SV9
C1SV10
C1SV11
C1SV12
C2SV1
C2SV2
C2SV3
C2SV4
C2SV5
C2SV6
C2SV7
C2SV8
C2SV9
C2SV10
C2SV11
C2SV12
C3SV1
C3SV2
C3SV3
C3SV4
C3SV5
C3SV6
C3SV7
C3SV8
C3SV9
C3SV10
C3SV11
C3SV12
C4SV1
C4SV2
C4SV3
C4SV4
C4SV5
C4SV6
C4SV7
C4SV8
C4SV9
C4SV10
C4SV11
C4SV12
C5SV1
C5SV2
C5SV3
C5SV4
C5SV5
C5SV6
C5SV7
C5SV8
C5SV9
C5SV10
C5SV11
C5SV12
C6SV1
C6SV2
C6SV3
C6SV4
C6SV5
C6SV6
C6SV7
C6SV8
C6SV9
C6SV10
C6SV11
C6SV12

You might also like