You are on page 1of 4

Control Systems

565

(N.O.) and normally closed (N.C.) refer to the device po- reading” are the higher quality instruments.
sition with no power applied, where a spring-returning The following example illustrates the important dif-
mechanism exists to drive it to one position or another. ference between “% of reading” and “% of span” concepts.
Valves required to have a “fail position” are necessary in Consider a 0-100 psig (span) transmitter that is indicating
many applications to provide an increased measure of 10 psig (reading).
reliability if control power is lost. In the case of comfort Accuracy Spec “+/- 5% of reading,”
heating and cooling, the choice is made by asking, “upon a Acceptable Range 9.5-10.5 psig
loss of power, control signal or air pressure, would I rather have Accuracy Spec “+/- 5% of span,”
full heat, full cool, or don’t care?” In other cases, there are Acceptable Range 5-15 psig
other operational issues like freezing, overheating, over-
humidifying, etc. that should be considered. Without the 22.8.3 Repeatability
spring return feature, the actuator will simply remain at Repeatability is self-defining; it is the ability of an
its last position prior to the power interruption. Spring- instrument or process to faithfully repeat itself, given
return actuators are more costly, and should be used pru- identical conditions. For instrumentation, this is syn-
dently so the added cost is justified. onymous with precision and is the mark of better grade
For large pneumatic cylinder actuators, a measure of instruments. Regarding instrumentation, a general state-
fail-safe control can be provided without the expense of ment is that accuracy can be adjusted, but repeatability is a
a spring system. Using an air-to-open/air-to-close actuator function of the instrument quality and cannot be changed.
(no spring) and a small spring return air solenoid valve, Repeatability is determined, in large part, by the stability
the position of the actuator can be relatively assured on of the output in the face of environmental changes such
power loss, as long as compressed air remains available. as ambient temperature effect, voltage fluctuation, pres-
sure fluctuation, etc. Instruments whose readings are sus-
ceptible to changes in ambient temperature can be very
22.8 INSTRUMENT ACCURACY, problematic if located in areas where the temperature is
REPEATABILITY, AND DRIFT expected to change; however, this specification (and the
cost to mitigate it with higher quality instruments) is of
22.8.1 Introduction much less concern if located in areas of constant tempera-
Like anything else, there are different grades of in- ture. Commercial grade pneumatic instruments are usu-
struments with corresponding costs, so the task of the ally susceptible to drift from ambient temperature chang-
specifier is to separate the needs from the wants, and to es since thermal expansion changes the volume of tubing,
balance the performance with the costs. With an aware- size of orifices, etc. Some lower grade electronic compo-
ness of some of the basic considerations and of instrument nents are also affected by ambient temperature changes.
grades and selection criteria, good decisions are usually
evident. Leaving the instrument selection entirely up to 22.8.4 Drift
the vendor may or may not be the best approach. To the Drift is an undesirable but inevitable quality for any
extent that the “standard offering” instrument portfolio instrument. Long-term drift is attributable to many fac-
has good performance, this can save money; however, a tors, including normal degradation from age. A general
review of the proposed instruments is advised just to be rule of thumb is that the long term drift, from all sources
sure. When reviewing product literature for instrumen- combined, should leave the instrument reading within
tation, like any other equipment, it is often as important
what is not said as what is said on a component specification
sheet. For example, if long term drift is not mentioned, ask
yourself, “Why is that?”

22.8.2 Accuracy
In the jargon of instrument calibration and
specifications, there are two important terms: percent of
reading and percent of span. It is not enough to say “±5%”
when specifying a calibration tolerance or instrument ac-
curacy rating. The tolerance should be stated as either
±xx degF, ±xx psi, etc., ±xx% of reading, or ±xx% of span.
Usually the instruments that are rated in terms of “% of Figure 22-9. Suggested Tolerances For Commercial Instruments.
566 Energy Management Handbook

reason for a period of five (5) years, to reduce


the need for O/M activities and constant mainte-
nance of the device, leaving it to serve instead of
being served by the facility.
Auto-zero Feature: Some devices, such as
stack gas sensors and very-low range differential
pressure transmitters, periodically re-establish
the zero point of their output span by simultane-
ously providing a zero input condition and auto-
matically adjusting the output to a zero value.

22.9 BASIC CONTROL BLOCK DIAGRAMS

22.9.1 Introduction Figure 22-10. Closed-loop Control


Besides control technology and control
mode choices, a basic consideration of control strategy is cause variations in actual time required in different
whether it is open or closed loop. seasons is not considered. For example it may take
(4) hours after a long and cold weekend but only
22.9.2 Closed-loop Control a half-hour after a single night in spring; however,
The controlled system impacts the measured vari- the controller is blind to these facts.
able, and process measurement provides feedback to the • Thermostat in room 1 controls the hot water con-
controller. trol valve serving room 2. In this example, closed-
loop feedback control is changed into open-loop
Examples of Closed Loop Control:
control due to a design or installation error.
• Room thermostat controls a heating water valve to
regulate heat to that room.
• Leaving water temperature sensor for a heat ex-
22.10 KEY ELEMENTS OF SUCCESSFULLY
changer controls the steam inlet valve to that heat
APPLIED AUTOMATIC CONTROLS
exchanger.

22.10.1 Examples of Good and


22.9.3 Open-loop Control
Bad Control Applications
An open-loop control system is characterized as one
Example.
whose output has no impact on the measured variable, so
• BAD. Two thermostats in an exterior room, one
any form of process feedback is impossible.
serving the perimeter heat and the other serving the
Examples of Open Loop Control: VAV cooling box overhead air distribution.
• Automatic reset of hot water temperature
from outside air. A common control strat-
egy, this provides general compensation
based on the common sense notion that
“the colder it gets outside the more heat
we’ll need”; however, it is open-loop since
the outside air temperature is unaffected by
water temperature.
• Starting the building HVAC system one
hour before occupancy. Another common
strategy, this follows the common sense no-
tion that the building will need some time
to warm up (or cool down) after being off
all night or all weekend. It provides gen-
eral compensation for the thermal lag in
the building mass, but it is open-loop, be- Figure 22-11. Open-loop Control
Control Systems 567

Figure 22-12a. Successful Controls Application Checklist (Continued)

• GOOD. One thermostat in a perimeter room se- maintain a constant 55 degree discharge tempera-
quencing the VAV box and perimeter heat, with a ture. Excessive equipment cycling will result, re-
dead band in between to prevent overlap. gardless of controls, with the consequence of poor
control and likely premature equipment failure.
22.10.2 Examples of Good and • GOOD. A two-step controller on a 15-ton HVAC
Bad System Controllability package unit that has two compressors, where
Example. 7.5 tons represents a typical part load day for the
• BAD. A single step controller on a 15-ton HVAC building. Cut-in and cut-out are set wider than the
package unit that has one compressor attempting to temperature change of each stage, to prevent short-
568 Energy Management Handbook

Figure 22-12b. Successful Controls Application Checklist (Concluded)

cycling. Minimum on-off times further safeguard 22.12 CONTROL APPLICATIONS


equipment from short-cycle damage. FOR SAVING ENERGY

22.10.3 Examples of User-friendly Control Note the common themes throughout the following
Design Features list of applications:
In general, try to provide a control design that will • Strive to satisfy most of the people most of the time,
be accepted and will last. Match the system complexity but not all the people all the time (80-20 rule).
to the user’s level of sophistication or their willingness • Try not to run any equipment continuously or off-
to learn. If it’s too complex, they’ll probably just unplug season.
it 6 months after start-up. Training will help to raise skill
• Avoid heating, cooling, and lighting areas that are
levels and avoid oversimplification. Be patient, especially
unoccupied.
for anything complex. Any type of measurement that al-
lows the user to see the savings created by the new con- • Use “just enough” air pressure, water pressure, etc.
trol system will help spark interest and encourage owner- to satisfy the point of use.
ship and buy-in. For the control design to stand the test of • “Just enough” heating and cooling, as determined
time (e.g. to be sustainable), it must be a good fit for the by the point of use.
customer. See Figure 22-13. • Use “just enough” ventilation air for the occupants
and to make up the exhaust needs.
• Eliminate simultaneous heating and cooling wher-
22.11 EXPECTED LIFE OF CONTROL EQUIPMENT ever possible; minimize where unavoidable.
Be realistic about how long things will last. Nothing
lasts forever. For example, a control project based on a 10-
year life will need to include cost of repairs to be realistic.
22.13 BASIC ENERGY-SAVING
Note for the table in Figure 22-14 that life spans shown
CONTROL APPLICATIONS
vary by manufacturer and grade. This information is of-
fered as a prompt for realistic life cycle cost estimating
(See Figures 22-15 and 22-16.)
when controls are applied.

You might also like