NOTES:

1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS STATED


OTHERWISE.
2. ALL EXTERNAL CONCRETE CHAMBER SURFACES TO HAVE
TANKING MEMBRANE IN ACCORDANCE WITH QCS SECTION 5
CLAUSE 14.3.
3. ALL INTERNAL SURFACES TO BE COATED WITH TWO COATS
EACH 400 MICRON COAL TAR EPOXY OR EQUIVALENT IN
ACCORDANCE WITH SPECIFICATION.
4. POLYTHENE SHEETING TO BE PLACED BETWEEN ALL VALVES
AND CONCRETE SUPPORT PLINTHS.
5. SLOPE FLOOR OF CHAMBER AT 1:100 TO SUMP.
6. ALL GRP LADDERS TO BE IN ACCORDANCE WITH
SPECIFICATIONS.
7. THE CONTRACTOR IS TO CONFIRM, WHERE APPLICABLE, THE
PIPE SCHEDULE OF FITTINGS FOR CHAMBERS PRIOR TO
PLACEMENT OF ORDERS AND CONSTRUCTION.
8. ALL PIPING INSIDE CHAMBERS TO BE DUCTILE IRON IN
ACCORDANCE WITH SPECIFICATION.
L 9. THE CONTRACTOR IS TO PREPARE REINFORCEMENT DRAWINGS
AND BAR BENDING SCHEDULES AND SUBMIT THEM TO THE
ENGINEER FOR APPROVAL.
SC SC 10. ALL FLANGES ARE TO BS 4504 TABLE 16 UNLESS NOTED
OTHERWISE.
11. PIPEWORK DIMENSIONS ARE TO CENTER LINES,
INTERSECTIONS PIPE ENDS OR FLANGE FACES.
12. ALL FLANGES AND COUPLINGS OUTSIDE OF CHAMBERS TO BE
PROTECTED BY HEAT SHRINKABLE SLEEVING IN ACCORDANCE
D.I. HDPE D.I. HDPE WITH SPECIFICATION.
13. LEGEND
COVER LEVEL - CL
FINAL GROUND LEVEL - FGL
INVERT LEVEL - IL
FLOOR LEVEL - FL
NOMINAL DIA. OF PIPE DN

DRAWING REFERENCE

DRAWING HISTORY
REV DATE STATUS CSRC / REF.

A 21/06/2018 IFA
B 04/08/2018 IFA

CLIENT

MAX.400
STATE OF QATAR
L

L
CLIENT PROJECT TEAM

1000 PROGRAM MANAGEMENT CONSULTANT


1000
SC SC

CONTRACTOR

D.I. HDPE D.I. HDPE


CONTRACTOR DESIGN CONSULTANT
300

300
ARCHITECTS. PLANNERS. ENGINEERS. INTERIOR DESIGNERS. GLOBAL BUSINESS CENTRE - 4TH FLOOR
Lungotevere Michelangelo, 9
CORNICHE ROAD - C RING ROAD PO BOX 25422 DOHA - QATAR
E-mail: apgdoha@apgqatar.com.qa Website: www.apg-arch.com TEL. +974.4402 3054 FAX. +97.44436 6673 00192 Roma
TEL +974 44311235 FAX +974 44436762 TEL. +39.06.6878374 FAX. +39.06.6872238 E-MAIL pras@pras.it Tel: +39 06 3609 3820 info@agrotec-spa.net

INDEPENDENT ENGINEERING CONSULTANT

DISCLAIMER
THIS DRAWING IS CONFIDENTIAL AND SHALL ONLY BE USED FOR THE PURPOSE
OF THIS PROJECT. THE SIGNING OF THIS TITLE BLOCK CONFIRMS THE DESIGN
AND DRAFTING OF THIS PROJECT HAVE BEEN PREPARED AND CHECKED IN
ACCORDANCE WITH THE COMPANY QUALITY ASSURANCE SYSTEM.
PROJECT TITLE
NPP/0085 STRATEGIC FOOD SECURITY FACILITIES (SFSF)
DRAWING TITLE
FIREFIGHTING
AIR RELEASE VALVE CHAMBER
STANDARD DETAILS
DWN DESD CHKD REWD REWD APPR DATE

EA ASH HH MS AG SK 04
08
2018

ORIG SIZE A1
CAD REF: SCALE N.T.S

DWG STATUS DETAILED DESIGN

DRAWING NO. SHEET REV


NPP0085-JEC-DD- ME-DWG-00133 01 OF 01 B

You might also like