Professional Documents
Culture Documents
Fire
Fire
for
Prepared By:
12/16/2021
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr ALAMARAI MADHINAN DEPO-1
Hell Page 2
General Data
Project Title: ALAMARAI MADHINAN DEPO-1 Project File Name: ALAMARAI MADHNAH DEPO-1..fiw
Designed By: Date: 12/16/2021
Code Reference: Approving Agency:
Client Name: Phone:
Address: City, State Zip Code:
Company Name: Representative:
Company Address: City And State:
Phone:
Building Name: Building Owner:
Contact at Building: Phone at Building:
Address Of Building: City, State Zip Code:
Project Data
Description Of Hazard: COMMODITY CLASS
Sprinkler System Type: Wet
IV
Design Area Of Water Application: 1176 ft² Maximum Area Per Sprinkler: 196 ft²
Default Sprinkler K-Factor: 25.20 K Default Pipe Material: SCHED 40 WET STEEL
Inside Hose Stream Allowance: 100.00 gpm Outside Hose Stream Allowance: 150.00 gpm
In Rack Sprinkler Allowance: 0.00 gpm
Sprinkler Specifications
Make: Model: CMSA
Size: Temperature Rating: 0 F
2E18T2
6 7 SCHED 40 WET STEEL 6.000 0 335.00 574.00 909.00 120
G
Sprinkler Summary
Sprinkler System Type: Wet
Specified Area Of Application: 1176.00 ft²
Minimum Desired Density: 0.700 gpm/ft²
Application Average Density: 0.749 gpm/ft²
Application Average Area Per Sprinkler: 196.00 ft²
Sprinkler Flow: 880.67 gpm
Average Sprinkler Flow: 146.78 gpm
200
180
160
140
Pressure psi
120
111
100
80
60
40
20
0
2 4 6 8 10 12 14 16 18 20
Flowrate(x100) gpm