Professional Documents
Culture Documents
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1.3 SUBMITTALS
1.4 COORDINATION
1. To allow maximum possible headroom unless specific mounting heights that reduce
headroom are indicated.
2. To provide for ease of disconnecting the equipment with minimum interference to other
installations.
3. To allow right of way for piping and conduit installed at required slope so connecting
raceways, cables, wireways, cable trays, and busways will be clear of obstructions and of
the working and access space of other equipment.
B. Coordinate installation of required supporting devices and set sleeves in cast-in-place concrete,
masonry walls, and other structural components as they are constructed.
C. Coordinate location of access panels and doors for electrical items that are behind finished
surfaces or otherwise concealed. Access doors and panels are specified in Division 08 Section
"Access Doors and Frames."
D. Coordinate sleeve selection and application with selection and application of firestopping
specified in Division 07 Section "Penetration Firestopping."
B. The owner will pay all charges and/or fees levied by the serving utility companies relative to
this project.
C. Obtain and pay all fees for permits, licensing, and inspections applicable to work of
Division 26.
PART 2 - PRODUCTS
A. Cast-Iron Pipe Sleeves: Cast or fabricated "wall pipe," equivalent to ductile-iron pressure pipe,
with plain ends and integral waterstop, unless otherwise indicated.
a. For sleeve cross-section rectangle perimeter less than 50 inches (1270 mm) and no
side more than 16 inches (400 mm), thickness shall be 0.052 inch (1.3 mm).
b. For sleeve cross-section rectangle perimeter equal to, or more than, 50 inches
(1270 mm) and 1 or more sides equal to, or more than, 16 inches (400 mm),
thickness shall be 0.138 inch (3.5 mm).
B. Factory assembled rectangular steel pathway containing an intumescent insert material that
adjusts automatically to cable addition or subtraction.
C. Sleeve shall have an F Rating equal to or greater than the rating of the wall in which the sleeve
is installed.
F. Provide square wall plate kits for single sleeve applications. Provide multi-gang wall/floor plate
kits for ganged applications.
PART 3 - EXECUTION
B. Measure indicated mounting heights to bottom of unit for suspended items and to center of unit
for wall-mounting items.
C. Headroom Maintenance: If mounting heights or other location criteria are not indicated,
arrange and install components and equipment to provide maximum possible headroom
consistent with these requirements.
A. Electrical penetrations occur when raceways, cables, wireways or busways penetrate concrete
slabs, concrete, masonry and gypsum board walls, or fire-rated floor and wall assemblies.
B. Sleeves are required where cables (not in raceway) penetrate walls or floors. Sleeves are not
required where raceways penetrate walls, except where raceways penetrate exterior
walls/foundations below grade.
C. Concrete Slabs and Walls: Install sleeves during erection of slabs and walls.
D. Use pipe sleeves unless penetration arrangement requires rectangular sleeved opening.
E. Fire-Rated Assemblies: Install sleeves for penetrations of fire-rated floor and wall assemblies
unless openings compatible with firestop system used are fabricated during construction of floor
or wall.
F. Provide insulated bushings on EMT sleeves for cable not in conduit. Bushings shall be plenum
rated where installed in a plenum.
G. Extend sleeves installed in floors 2 inches (50 mm) above finished floor level unless noted
otherwise.
H. Size pipe sleeves to provide 1/4-inch (6.4-mm) annular clear space between sleeve and raceway
or cable, unless indicated otherwise.
I. Seal space outside of sleeves with grout for penetrations of concrete and masonry.
1. Promptly pack grout solidly between sleeve and wall so no voids remain. Tool exposed
surfaces smooth; protect grout while curing.
J. Interior Penetrations of Non-Fire-Rated Walls and Floors: Seal annular space between sleeve
and raceway or cable, using joint sealant appropriate for size, depth, and location of joint.
Comply with requirements in Division 07 Section "Joint Sealants.".
M. Fire Rated Sleeves for cables: Fabricate openings in wall or floor assemblies per
manufacturer’s recommendations.
1. Through Exterior Walls Below Grade: Cast iron pipe or PVC, Schedule 40 or 80.
3.4 FIRESTOPPING
A. Apply firestopping to penetrations of fire-rated floor and wall assemblies for electrical
installations to restore original fire-resistance rating of assembly. Firestopping materials and
installation requirements are specified in Division 07 Section "Penetration Firestopping."
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
1.3 SUBMITTALS
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for
intended use.
PART 2 - PRODUCTS
C. Conductor Insulation: Comply with NEMA WC 70 for Types THHN-THWN and XHHW.
E. Refer to Division 26 Section “Raceway and Boxes for Electrical Systems” for types of raceways
permitted. Cable assemblies, such as Type AC or MC cable, shall not be permitted unless noted
otherwise.
B. Description: Factory-fabricated connectors and splices of size, ampacity rating, material, type,
and class for application and service indicated.
PART 3 - EXECUTION
A. Feeders: Copper. Solid for No. 10 AWG and smaller; stranded for No. 8 AWG and larger.
B. Branch Circuits: Copper. Solid for No. 10 AWG and smaller; stranded for No. 8 AWG and
larger.
C. Other Feeders and Branch Circuits: Type THHN-THWN, single conductors in raceway.
E. Minimum Wire Size (Interior Work): No. 12 AWG, except No. 14 AWG shall be permitted for
signal, pilot control circuits and fixture whips.
A. Conceal cables in finished walls, ceilings, and floors, unless otherwise indicated.
C. Use pulling means, including fish tape, cable, rope, and basket-weave wire/cable grips that will
not damage cables or raceway. Install exposed cables parallel and perpendicular to surfaces of
exposed structural members, and follow surface contours where possible.
D. Support cables according to Division 26 Section "Hangers and Supports for Electrical Systems."
E. Identify and color-code conductors and cables according to Division 26 Section "Identification
for Electrical Systems."
3.4 CONNECTIONS
B. Make splices and taps that are compatible with conductor material and that possess equivalent
or better mechanical strength and insulation ratings than unspliced conductors.
C. Wiring at Outlets: Install conductor at each outlet, with at least 6 inches (150 mm) of slack.
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes methods and materials for grounding systems and equipment.
1.3 SUBMITTALS
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for
intended use.
B. Comply with UL 467 for grounding and bonding materials and equipment.
PART 2 - PRODUCTS
1. Chatsworth
2. Erico.
3. Harger
4. Panduit
B. Products shall be UL listed meet the specification of TIA/EIA 607 and conform to BICSI
recommendations.
C. Copper busbar, 0.25-inch thick minimum, insulated stand-offs, factory predrilled standard size
holes per TIA/EIA 607 standard.
D. Telecommunications Main Grounding Busbars: Height shall be 4-inches. Length shall be 20-
inches minimum unless indicated otherwise on Drawings. Chatsworth 40153 series or equal.
2.2 CONDUCTORS
A. Insulated Conductors: Tinned-copper wire or cable insulated for 600 V unless otherwise
required by applicable Code or authorities having jurisdiction.
2.3 CONNECTORS
A. Listed and labeled by a nationally recognized testing laboratory acceptable to authorities having
jurisdiction for applications in which used, and for specific types, sizes, and combinations of
conductors and other items connected.
B. Bolted Connectors for Conductors and Pipes: Copper or copper alloy, bolted pressure-type,
with at least two bolts.
A. Ground Rods: Copper-clad steel, sectional type; 3/4 inch by 10 feet (19 mm by 3 m) in
diameter.
PART 3 - EXECUTION
3.1 APPLICATIONS
A. Conductors: Install solid conductor for No. 8 AWG and smaller, and stranded conductors for
No. 6 AWG and larger, unless otherwise indicated.
B. Underground Grounding Conductors: Install bare tinned-copper conductor, No. 2/0 AWG
minimum.
B. Provide grounding as required by the serving utility company. Grounding shall be provided at,
but not limited to, the following locations:
1. Transformer
2. Meter
A. Install insulated equipment grounding conductors with all feeders and branch circuits.
3.5 INSTALLATION
A. Grounding Conductors: Route along shortest and straightest paths possible, unless otherwise
indicated or required by Code. Avoid obstructing access or placing conductors where they may
be subjected to strain, impact, or damage.
B. Ground Rods: Drive rods until tops are 2 inches (50 mm) below finished floor or final grade,
unless otherwise indicated.
1. Interconnect ground rods with grounding electrode conductor below grade and as
otherwise indicated. Make connections without exposing steel or damaging coating, if
any.
C. Bonding Straps and Jumpers: Install in locations accessible for inspection and maintenance,
except where routed through short lengths of conduit.
1. Bonding to Structure: Bond straps directly to basic structure, taking care not to penetrate
any adjacent parts.
2. Bonding to Equipment Mounted on Vibration Isolation Hangers and Supports: Install so
vibration is not transmitted to rigidly mounted equipment.
3. Use exothermic-welded connectors for outdoor locations, but if a disconnect-type
connection is required, use a bolted clamp.
1. Metal Water Service Pipe: Install insulated copper grounding conductors, in conduit,
from building's main service equipment, or grounding bus, to main metal water service
entrances to building. Connect grounding conductors to main metal water service pipes,
using a bolted clamp connector or by bolting a lug-type connector to a pipe flange, using
one of the lug bolts of the flange. Where a dielectric main water fitting is installed,
connect grounding conductor on street side of fitting. Bond metal grounding conductor
conduit or sleeve to conductor at each end.
2. Water Meter Piping: Use braided-type bonding jumpers to electrically bypass water
meters. Connect to pipe with a bolted connector.
3. Bond each aboveground portion of gas piping system downstream from equipment
shutoff valve.
E. Bonding Interior Metal Ducts: Bond metal air ducts to equipment grounding conductors of
associated fans, blowers, electric heaters, and air cleaners. Install tinned bonding jumper to
bond across flexible duct connections to achieve continuity.
F. Ufer Ground (Concrete-Encased Grounding Electrode): Fabricate according to NFPA 70, using
a minimum of 20 feet (6 m) of bare copper conductor not smaller than No. 4 copper size AWG.
1. If concrete foundation is less than 20 feet (6 m) long, coil excess conductor within base
of foundation.
2. Bond grounding conductor to reinforcing steel in at least four locations and to anchor
bolts. Extend grounding conductor below grade and connect to building grounding grid
or to grounding electrode external to concrete.
A. Perform the following tests and inspections and prepare test reports:
1. After installing grounding system but before permanent electrical circuits have been
energized, test for compliance with requirements.
2. Test completed grounding system at each location where a maximum ground-resistance
level is specified, at service disconnect enclosure grounding terminal, and at individual
ground rods. Make tests at ground rods before any conductors are connected.
a. Measure ground resistance not less than two full days after last trace of
precipitation and without soil being moistened by any means other than natural
drainage or seepage and without chemical treatment or other artificial means of
reducing natural ground resistance.
b. Perform tests by fall-of-potential method according to IEEE 81.
3. Prepare dimensioned drawings locating each ground rod and ground rod assembly, and
other grounding electrodes. Identify each by letter in alphabetical order, and key to the
record of tests and observations. Include the number of rods driven and their depth at
each location, and include observations of weather and other phenomena that may affect
test results. Describe measures taken to improve test results.
B. If resistance to ground values at the ground rod exceeds 10 ohms, provide another sectional
ground rod connected to the original ground rod for a total of 20ft rod and drive rod deep into
earth. Repeat tests as described above, record and submit test results. If soil conditions (rock)
do not allow for a deep driven ground rod, provide two additional rods spaced at least one-rod
length from each other and the original rod and locate at least the same distance from other
grounding electrodes, and connect to the service grounding electrode conductor. Repeat tests as
described above, record and submit test results.
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
1.3 DEFINITIONS
1.4 SUBMITTALS
A. Design supports for multiple raceways capable of supporting combined weight of supported
systems and its contents.
1.7 COORDINATION
A. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases. Concrete,
reinforcement, and formwork requirements are specified in Division 03.
B. Coordinate installation of roof curbs, equipment supports, and roof penetrations. These items
are specified in Division 07 Section "Roof Accessories."
PART 2 - PRODUCTS
A. Steel Slotted Support Systems: Comply with MFMA-4, factory-fabricated components for field
assembly.
C. Conduit and Cable Support Devices: Steel Hangers, clamps, and associated fittings, designed
for types and sizes of raceway or cable to be supported.
E. Structural Steel for Fabricated Supports and Restraints: ASTM A 36/A 36M, steel plates,
shapes, and bars; black and galvanized.
F. Support for conduits routed horizontally on roofs: Factory assembled UV-stabilized rubber
base with galvanized steel channel for attachment of conduit(s). Size and type of support as
recommended by manufacturer for the quantity and weight of conduits supported. Provide one
of the following products:
G. Mounting, Anchoring, and Attachment Components: Items for fastening electrical items or
their supports to building surfaces include the following:
1) Hilti Inc.
2) ITW Ramset/Red Head; a division of Illinois Tool Works, Inc.
3) MKT Fastening, LLC.
4) Simpson Strong-Tie Co., Inc.; Masterset Fastening Systems Unit.
3. Concrete Inserts: Steel or malleable-iron, slotted support system units similar to MSS
Type 18; complying with MFMA-4 or MSS SP-58.
4. Clamps for Attachment to Steel Structural Elements: MSS SP-58, type suitable for
attached structural element.
5. Through Bolts: Structural type, hex head, and high strength. Comply with
ASTM A 325.
6. Toggle Bolts: All-steel springhead type.
7. Hanger Rods: Threaded steel.
A. Description: Welded or bolted, structural steel shapes, shop or field fabricated to fit dimensions
of supported equipment.
B. Materials: Comply with requirements in Division 05 Section "Metal Fabrications" for steel
shapes and plates.
PART 3 - EXECUTION
3.1 APPLICATION
A. Comply with NECA 1 and NECA 101 for application of hangers and supports for electrical
equipment and systems except if requirements in this Section are stricter.
B. Maximum Support Spacing and Minimum Hanger Rod Size for Raceway: Space supports for
EMT, IMC, and RMC as required by NFPA 70. Minimum rod size shall be 1/4 inch (6 mm) in
diameter.
C. Multiple Raceways or Cables: Install trapeze-type supports fabricated with steel slotted or
other support system, sized so capacity can be increased by at least 25 percent in future without
exceeding specified design load limits.
1. Secure raceways and cables to these supports with single-bolt conduit clamps using
spring friction action for retention in support channel.
A. Comply with NECA 1 and NECA 101 for installation requirements except as specified in this
Article.
B. Raceway Support Methods: In addition to methods described in NECA 1, EMT, IMC, and
RMC may be supported by openings through structure members, as permitted in NFPA 70.
C. Strength of Support Assemblies: Where not indicated, select sizes of components so strength
will be adequate to carry present and future static loads within specified loading limits.
Minimum static design load used for strength determination shall be weight of supported
components plus 200 lb (90 kg).
D. Mounting and Anchorage of Surface-Mounted Equipment and Components: Anchor and fasten
electrical items and their supports to building structural elements by the following methods
unless otherwise indicated by code:
E. Drill holes for expansion anchors in concrete at locations and to depths that avoid reinforcing
bars.
A. Comply with installation requirements in Division 05 Section "Metal Fabrications" for site-
fabricated metal supports.
B. Cut, fit, and place miscellaneous metal supports accurately in location, alignment, and elevation
to support and anchor electrical materials and equipment.
3.4 PAINTING
A. Touchup: Clean field welds and abraded areas of shop paint. Paint exposed areas immediately
after erecting hangers and supports. Use same materials as used for shop painting. Comply
with SSPC-PA 1 requirements for touching up field-painted surfaces.
1. Apply paint by brush or spray to provide minimum dry film thickness of 2.0 mils (0.05
mm).
B. Touchup: Comply with requirements in Division 09 Painting Sections for cleaning and touchup
painting of field welds, bolted connections, and abraded areas of shop paint on miscellaneous
metal.
C. Galvanized Surfaces: Clean welds, bolted connections, and abraded areas and apply
galvanizing-repair paint to comply with ASTM A 780.
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes raceways, fittings, boxes, enclosures, and cabinets for electrical wiring.
1.3 DEFINITIONS
1.4 SUBMITTALS
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for
intended use.
PART 2 - PRODUCTS
H. Fittings for Conduit (Including all Types and Flexible and Liquidtight), EMT, and Cable:
NEMA FB 1; listed for type and size raceway with which used, and for application and
environment in which installed.
1. CANTEX Inc.
C. Fittings for RNC: NEMA TC 3; match to conduit or tubing type and material.
B. Description: Sheet metal sized and shaped as indicated, NEMA 250, Type 1 unless otherwise
indicated.
C. Fittings and Accessories: Include couplings, offsets, elbows, expansion joints, adapters, hold-
down straps, end caps, and other fittings to match and mate with wireways as required for
complete system.
A. Surface Metal Raceways: Galvanized steel with snap-on covers. Manufacturer's standard
enamel finish in color selected by Architect.
a. Hubbell.
b. Mono-Systems Inc.
c. Wiremold Company (The); Legrand
C. Cast-Metal Outlet and Device Boxes: NEMA FB 1, ferrous alloy, Type FD, with gasketed
cover.
D. Floor Boxes in Wood Floors: Suitable for installation in floating wood floors with brass cover
and screw-in plugs, Lew FFB series or approved equal.
F. Cast-Metal Access, Pull, and Junction Boxes: NEMA FB 1, galvanized, cast iron with gasketed
cover.
G. Hinged-Cover Enclosures: NEMA 250, Type 1, with continuous-hinge cover with flush latch,
unless otherwise indicated.
1. Metal Enclosures: Steel, finished inside and out with manufacturer's standard enamel.
B. Polymer-Concrete Handholes and Boxes with Polymer-Concrete Cover: Molded of sand and
aggregate, bound together with polymer resin, and reinforced with steel or fiberglass or a
combination of the two
C. Fiberglass Handholes and Boxes with Polymer-Concrete Frame and Cover: Sheet-molded,
fiberglass-reinforced, polyester-resin enclosure joined to polymer-concrete top ring or frame..
PART 3 - EXECUTION
a. Handholes and Pull Boxes in Driveway, Parking Lot, and Off-Roadway Locations,
Subject to Occasional, Nondeliberate Loading by Heavy Vehicles: Polymer
concrete SCTE 77, Tier 15 structural load rating.
1. Exposed, Not Subject to Physical Damage: EMT. Includes raceways in the following
locations:
2. Exposed and Subject to Physical Damage: Rigid steel conduit. Includes raceways up to
8 feet above the finished floor in the following locations:
a. Loading dock.
b. Corridors used for traffic of mechanized carts, forklifts, and pallet-handling units.
c. Mechanical rooms.
1. Exposed, Not Subject to Physical Damage: EMT. Includes raceways in the following
locations:
2. Exposed and Subject to Physical Damage: Rigid steel conduit. Includes raceways up to
8 feet above the finished floor in the following locations:
a. Loading dock.
b. Corridors used for traffic of mechanized carts, forklifts, and pallet-handling units.
c. Mechanical rooms.
3. Exposed Finished Space: Surface metal raceway. Limited to the following locations
only:
D. Minimum Raceway Size: 3/4-inch (21-mm) trade size diameter for lighting and branch circuit
homeruns and exterior work; 1/2-inch (16-mm) diameter for other interior work, unless shown
or specified otherwise.
E. Raceway Fittings: Compatible with raceways and suitable for use and location.
1. Rigid and Intermediate Steel Conduit: Use threaded rigid steel conduit fittings, unless
otherwise indicated.
2. PVC Externally Coated, Rigid Steel Conduits: Use only fittings listed for use with that
material. Patch and seal all joints, nicks, and scrapes in PVC coating after installing
conduits and fittings. Use sealant recommended by fitting manufacturer.
3.2 INSTALLATION
A. Comply with NECA 1 for installation requirements applicable to products specified in Part 2
except where requirements on Drawings or in this Article are stricter.
B. Keep raceways at least 6 inches (150 mm) away from parallel runs of flues and steam or hot-
water pipes. Install horizontal raceway runs above water and steam piping.
D. Support raceways as specified in Division 26 Section "Hangers and Supports for Electrical
Systems."
E. Arrange stub-ups so curved portions of bends are not visible above the finished slab.
F. Install no more than the equivalent of three 90-degree bends in any conduit run except for
communications conduits, for which fewer bends are allowed.
G. Conceal conduit and EMT within finished walls, ceilings, and floors, unless otherwise
indicated.
1. Run conduit larger than 1-inch (27-mm) trade size, parallel or at right angles to main
reinforcement. Where at right angles to reinforcement, place conduit close to slab
support.
2. Arrange raceways to cross building expansion joints at right angles with expansion
fittings.
I. Threaded Conduit Joints, Exposed to Wet, Damp, Corrosive, or Outdoor Conditions: Apply
listed compound to threads of raceway and fittings before making up joints. Follow compound
manufacturer's written instructions.
K. Install pull wires in empty raceways. Use polypropylene or monofilament plastic line with not
less than 200-lb (90-kg) tensile strength. Leave at least 12 inches (300 mm) of slack at each end
of pull wire.
L. Raceways for Optical Fiber and Communications Cable: Install raceways, metallic and
nonmetallic, rigid and flexible, as follows:
1. 3/4-Inch (19-mm) Trade Size and Smaller: Install raceways in maximum lengths of 50
feet (15 m).
2. 1-Inch (25-mm) Trade Size and Larger: Install raceways in maximum lengths of 75 feet
(23 m).
3. Install with a maximum of two 90-degree bends or equivalent for each length of raceway
unless Drawings show stricter requirements. Separate lengths with pull or junction boxes
or terminations at distribution frames or cabinets where necessary to comply with these
requirements.
M. Install raceway sealing fittings at suitable, approved, and accessible locations and fill them with
listed sealing compound. For concealed raceways, install each fitting in a flush steel box with a
blank cover plate having a finish similar to that of adjacent plates or surfaces. Install raceway
sealing fittings at the following points:
1. Where conduits pass from warm to cold locations, such as boundaries of refrigerated
spaces.
2. Where otherwise required by NFPA 70.
N. Flexible Conduit Connections: Use maximum of 72 inches (1830 mm) of flexible conduit for
recessed and semirecessed lighting fixtures, equipment subject to vibration, noise transmission,
or movement; and for transformers and motors.
O. Recessed Boxes in Masonry Walls: Saw-cut opening for box in center of cell of masonry block,
and install box flush with surface of wall.
P. Set metal floor boxes level and flush with finished floor surface.
A. Direct-Buried Conduit:
1. Excavate trench bottom to provide firm and uniform support for conduit. Prepare trench
bottom as specified in Division 31 Section "Earth Moving" for pipe less than 6 inches
(150 mm) in nominal diameter.
2. Install backfill as specified in Division 31 Section "Earth Moving."
3. After installing conduit, backfill and compact. Start at tie-in point, and work toward end
of conduit run, leaving conduit at end of run free to move with expansion and contraction
as temperature changes during this process. Firmly hand tamp backfill around conduit to
provide maximum supporting strength. After placing controlled backfill to within 12
inches (300 mm) of finished grade, make final conduit connection at end of run and
complete backfilling with normal compaction as specified in Division 31 Section "Earth
Moving."
4. Install manufactured PVC coated rigid steel conduit elbows for stub-ups at poles and
equipment and at building entrances through the floor, unless noted otherwise.
a. Couple steel conduits to ducts with adapters designed for this purpose, and encase
coupling with 3 inches (75 mm) of concrete.
b. For stub-ups at equipment mounted on outdoor concrete bases, extend steel conduit
horizontally a minimum of 60 inches (1500 mm) from edge of equipment pad or
foundation. Install insulated grounding bushings on terminations at equipment.
5. Where feeder and communications conduits 2-inches in diameter and larger transition
from below concrete floor slab to above slab, RNC may continue up to 36inches
maximum to destination (i.e. panelboard) without converting to the indoor raceway
system specified above.
A. Install handholes and boxes level and plumb and with orientation and depth coordinated with
connecting conduits to minimize bends and deflections required for proper entrances.
B. Unless otherwise indicated, support units on a level bed of crushed stone or gravel, graded from
1/2-inch (12.5-mm) sieve to No. 4 (4.75-mm) sieve and compacted to same density as adjacent
undisturbed earth.
C. Elevation: In paved areas, set so cover surface will be flush with finished grade. Set covers of
other enclosures 1 inch (25 mm) above finished grade.
D. Install handholes and boxes with bottom below the frost line.
3.5 FIRESTOPPING
A. Apply firestopping to electrical penetrations of fire-rated floor and wall assemblies to restore
original fire-resistance rating of assembly. Firestopping materials and installation requirements
are specified in Division 07 Section "Penetration Firestopping."
3.6 PROTECTION
A. Provide final protection and maintain conditions that ensure coatings, finishes, and cabinets are
without damage or deterioration at time of Substantial Completion.
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
1. Time switches.
2. Photoelectric switches.
3. Indoor occupancy sensors.
4. Outdoor motion sensors.
5. Lighting contactors.
6. Emergency shunt relays.
1. Division 26 Section "Wiring Devices" for wall-switch occupancy sensors, and manual
light switches.
1.3 DEFINITIONS
1.4 SUBMITTALS
B. Shop Drawings: Show installation details for occupancy and light-level sensors.
C. Operation and Maintenance Data: For each type of product to include in emergency, operation,
and maintenance manuals.
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for
intended use.
1.6 COORDINATION
A. Coordinate layout and installation of ceiling-mounted devices with other construction that
penetrates ceilings or is supported by them, including light fixtures, HVAC equipment, smoke
detectors, fire-suppression system, and partition assemblies.
PART 2 - PRODUCTS
B. Description: Solid state, with SPST dry contacts rated for 1800-VA tungsten or 1000-VA
inductive, to operate connected relay, contactor coils, or microprocessor input; complying with
UL 773A.
1. Light-Level Monitoring Range: 1.5 to 10 fc (16.14 to 108 lx), with an adjustment for
turn-on and turn-off levels within that range, and a directional lens in front of photocell to
prevent fixed light sources from causing turn-off.
2. Time Delay: 15-second minimum, to prevent false operation.
3. Surge Protection: Metal-oxide varistor, complying with IEEE C62.41.1, IEEE C62.41.2,
and IEEE 62.45 for Category A1 locations.
4. Mounting: Twist lock complying with IEEE C136.10, with base-and-stem mounting or
stem-and-swivel mounting accessories as required to direct sensor to the north sky
exposure.
B. General Description: Wall- or ceiling-mounting, solid-state units with a separate relay unit.
1. Operation: Unless otherwise indicated, turn lights on when covered area is occupied and
off when unoccupied; with a time delay for turning lights off, adjustable over a minimum
range of 1 to 15 minutes.
2. Sensor Output: Contacts rated to operate the connected relay, complying with UL 773A.
Sensor shall be powered from the relay unit.
3. Relay Unit: Dry contacts rated for 20-A ballast load at 120- and 277-V ac, for 13-A
tungsten at 120-V ac, and for 1 hp at 120-V ac. Power supply to sensor shall be 24-V dc,
150-mA, Class 2 power source as defined by NFPA 70.
4. Mounting:
5. Indicator: LED, to show when motion is being detected during testing and normal
operation of the sensor.
6. Bypass Switch: Override the on function in case of sensor failure.
7. Automatic Light-Level Sensor: Adjustable from 2 to 200 fc (21.5 to 2152 lx); keep
lighting off when selected lighting level is present.
1. Detector Sensitivity: Detect a person of average size and weight moving not less than 12
inches (305 mm) in either a horizontal or a vertical manner at an approximate speed of 12
inches/s (305 mm/s).
2. Time delay: 30 seconds to 30 minutes.
3. Detection Coverage (Standard Room): Detect occupancy anywhere within a circular area
of 1000 sq. ft. (93 sq. m) when mounted on a 96-inch- (2440-mm-) high ceiling.
1) Hubbell Omni-US1000
2) Leviton OSC10-U0W
3) Sensor Switch CM-PDT
4) Wattstopper WT-1100
4. Detection Coverage (Large Room): Detect occupancy anywhere within a circular area of
2000 sq. ft. (186 sq. m) when mounted on a 96-inch- (2440-mm-) high ceiling.
1) Hubbell Omni-US2000
2) Leviton OSC20-U0W
3) Sensor Switch CM-PDT-10
4) Wattstopper WT-2200
1) Hubbell Omni-DT1000
2) Levition OSC20-M0W
3) Sensor Switch CM-PDT
4) Wattstopper DT-300
B. Description: Electrically operated and mechanically held, complying with NEMA ICS 2 and
UL 508.
1. Current Rating for Switching: Listing or rating consistent with type of load served,
including tungsten filament, inductive, and high-inrush ballast (ballast with 15 percent or
less total harmonic distortion of normal load current).
2. Fault Current Withstand Rating: Equal to or exceeding the available fault current at the
point of installation.
3. Enclosure: Comply with NEMA 250.
A. Power Wiring to Supply Side of Remote-Control Power Sources: Not smaller than No. 12
AWG. Comply with requirements in Division 26 Section "Low-Voltage Electrical Power
Conductors and Cables."
B. Classes 2 and 3 Control Cable: Multiconductor cable with stranded-copper conductors not
smaller than No. 18 AWG. Comply with requirements in Division 26 Section "Low-Voltage
Electrical Power Conductors and Cables."
C. Class 1 Control Cable: Multiconductor cable with stranded-copper conductors not smaller than
No. 18AWG. Comply with requirements in Division 26 Section "Low-Voltage Electrical
Power Conductors and Cables."
PART 3 - EXECUTION
A. Install and aim sensors in locations to achieve 100 percent coverage of areas indicated. Do not
exceed coverage limits specified in manufacturer's written instructions.
A. Wiring Method: Comply with Division 26 Section "Low-Voltage Electrical Power Conductors
and Cables." Minimum conduit size shall be 1/2 inch (13 mm).
B. Wiring within Enclosures: Comply with NECA 1. Separate power-limited and nonpower-
limited conductors according to conductor manufacturer's written instructions.
C. Size conductors according to lighting control device manufacturer's written instructions, unless
otherwise indicated.
D. Splices, Taps, and Terminations: Make connections only on numbered terminal strips in
junction, pull, and outlet boxes; terminal cabinets; and equipment enclosures.
A. Perform the following field tests and inspections and prepare test reports:
1. After installing time switches and sensors, and after electrical circuitry has been
energized, adjust and test for compliance with requirements.
2. Operational Test: Verify operation of each lighting control device, and adjust time
delays.
B. Lighting control devices that fail tests and inspections are defective work.
3.4 ADJUSTING
A. Prior to final completion, sensors shall be adjusted for proper operation. Proper operation
includes:
3.5 DEMONSTRATION
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
1. Distribution panelboards.
1.3 DEFINITIONS
1.4 SUBMITTALS
A. Product Data: For each type of panelboard, overcurrent protective device, transient voltage
suppression device, accessory, and component indicated. Include dimensions and
manufacturers' technical data on features, performance, electrical characteristics, ratings, and
finishes.
a. Enclosure types and details for types other than NEMA 250, Type 1.
b. Bus configuration, current, and voltage ratings.
c. Short-circuit current rating of panelboards and overcurrent protective devices.
d. Features, characteristics, ratings, and factory settings of individual overcurrent
protective devices.
PANELBOARDS 262416 - 1
RAYTOWN PUBLIC WORKS BUILDING IMPROVEMENTS 10-107
CITY OF RAYTOWN, MISSOURI
C. Panelboard Schedules: For installation in panelboards. Submit final versions after load
balancing.
D. Operation and Maintenance Data: For panelboards and components to include in emergency,
operation, and maintenance manuals.
C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for
intended use.
A. Environmental Limitations: Rate equipment for continuous operation under the following
conditions, unless otherwise indicated:
1.7 COORDINATION
A. Coordinate layout and installation of panelboards and components with other construction that
penetrates walls or is supported by them, including electrical and other types of equipment,
raceways, piping, and encumbrances to workspace clearance requirements.
A. Furnish extra materials described below that match products installed and that are packaged
with protective covering for storage and identified with labels describing contents.
PANELBOARDS 262416 - 2
RAYTOWN PUBLIC WORKS BUILDING IMPROVEMENTS 10-107
CITY OF RAYTOWN, MISSOURI
PART 2 - PRODUCTS
2.1 MANUFACTURERS
1. Front: Secured to box with concealed trim clamps. For surface-mounted fronts, match
box dimensions; for flush-mounted fronts, overlap box.
2. Finish: Manufacturer's standard enamel finish over corrosion-resistant treatment or
primer coat.
3. Directory Card: With transparent protective cover, mounted in metal frame or plastic
pouch, inside panelboard door.
D. Future Devices: Mounting brackets, bus connections, and necessary appurtenances required for
future installation of devices.
A. Fully rated to interrupt symmetrical short-circuit current available at terminals. Series rated
devices are not acceptable.
PANELBOARDS 262416 - 3
RAYTOWN PUBLIC WORKS BUILDING IMPROVEMENTS 10-107
CITY OF RAYTOWN, MISSOURI
1. For Circuit-Breaker Frame Sizes 125 A and Smaller: Bolt-on circuit breakers.
2. For Circuit-Breaker Frame Sizes Larger Than 125 A: Bolt-on circuit breakers; plug-in
circuit breakers where individual positive-locking device requires mechanical release for
removal.
3. Fused switches.
B. Doors: Concealed hinges; secured with flush latch with tumbler lock; keyed alike.
A. Doors: Secured with vault-type latch with tumbler lock; keyed alike.
E. Transient Voltage Suppression Device: IEEE C62.41, factory installed, integrally mounted,
plug-in-style, solid-state, parallel-connected, sine-wave tracking suppression and filtering
modules.
a. Line to neutral.
b. Line to ground.
c. Neutral to ground.
3. EMI/RFI Noise Attenuation Using 50-ohm Insertion Loss Test: 55 dB at 100 kHz.
4. Maximum Category C Combination Wave Clamping Voltage as follows:
PANELBOARDS 262416 - 4
RAYTOWN PUBLIC WORKS BUILDING IMPROVEMENTS 10-107
CITY OF RAYTOWN, MISSOURI
5. Withstand Capabilities: 3000 Category C surges with less than 5 percent change in
clamping voltage.
6. Accessories:
A. Molded-Case Circuit Breaker: UL 489, with interrupting capacity to meet available fault
currents.
B. Molded-Case Circuit-Breaker Features and Accessories: Standard frame sizes, trip ratings, and
number of poles.
1. Lugs: Mechanical style, suitable for number, size, trip ratings, and conductor materials.
2. Application Listing: Appropriate for application; Type SWD for switching fluorescent
lighting loads; Type HACR for heating, air-conditioning, and refrigerating equipment.
3. Ground-Fault Protection: Integrally mounted relay and trip unit with adjustable pickup
and time-delay settings, push-to-test feature, and ground-fault indicator.
4. Shunt Trip: 120-V trip coil energized from separate circuit, set to trip at 55 percent of
rated voltage.
5. Multipole units enclosed in a single housing or factory-assembled to operate as a single
unit.
C. Fused Switch: NEMA KS 1, Type HD; clips to accommodate specified fuses; lockable handle.
PART 3 - EXECUTION
3.1 INSTALLATION
B. Mount top of trim 74 inches (1880 mm) above finished floor, unless otherwise indicated.
C. Mount plumb and rigid without distortion of box. Mount recessed panelboards with fronts
uniformly flush with wall finish.
PANELBOARDS 262416 - 5
RAYTOWN PUBLIC WORKS BUILDING IMPROVEMENTS 10-107
CITY OF RAYTOWN, MISSOURI
F. For panelboards mounted flush in walls, stub four 1-inch (27-GRC) empty conduits from
panelboard into accessible ceiling space or space designated to be ceiling space in the future.
G. Arrange conductors in gutters into groups and bundle and wrap with wire ties after completing
load balancing.
3.2 IDENTIFICATION
B. Create a directory to indicate installed circuit loads after balancing panelboard loads. Obtain
approval before installing. Use a computer or typewriter to create directory; handwritten
directories are not acceptable. Directories shall reflect room numbers as assigned by the Owner,
which may not match room numbers indicated on contract document drawings.
3.3 CONNECTIONS
A. Ground equipment according to Division 26 Section "Grounding and Bonding for Electrical
Systems."
1. Test insulation resistance for each panelboard bus, component, connecting supply, feeder,
and control circuit.
2. Test continuity of each circuit.
B. Perform the following field tests and inspections and prepare test reports:
1. Perform each electrical test and visual and mechanical inspection stated in NETA ATS,
Section 7.5 for switches and Section 7.6 for molded-case circuit breakers. Certify
compliance with test parameters.
2. Correct malfunctioning units on-site, where possible, and retest to demonstrate
compliance; otherwise, replace with new units and retest.
C. Load Balancing: After Substantial Completion, but not more than 60 days after Final
Acceptance, measure load balancing and make circuit changes.
PANELBOARDS 262416 - 6
RAYTOWN PUBLIC WORKS BUILDING IMPROVEMENTS 10-107
CITY OF RAYTOWN, MISSOURI
3.5 CLEANING
PANELBOARDS 262416 - 7
RAYTOWN PUBLIC WORKS BUILDING IMPROVEMENTS 10-107
CITY OF RAYTOWN, MISSOURI
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
1.3 DEFINITIONS
1.4 SUBMITTALS
B. Operation and Maintenance Data: For wiring devices to include in all manufacturers' packing
label warnings and instruction manuals that include labeling conditions.
A. Source Limitations: Obtain each type of wiring device and associated wall plate through one
source from a single manufacturer. Insofar as they are available, obtain all wiring devices and
associated wall plates from a single manufacturer and one source.
B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for
intended use.
1.6 COORDINATION
PART 2 - PRODUCTS
2.1 MANUFACTURERS
a. Cooper; GF20.
b. Hubbell GFR5352.
c. Leviton 7899.
d. Pass & Seymour 2094.
C. GFI receptacles may be arranged to protect downstream receptacles if and only if the
downstream receptacle is in the same room as the GFI receptacle. Provide machine printed
labels on such downstream receptacles indicating the receptacle is “GFI PROTECTED”.
A. Description: Match voltage and current ratings and number of conductors to requirements of
equipment being connected.
B. Switches, 120/277 V, 20 A:
a. Cooper; 2221 (single pole), 2222 (two pole), 2223 (three way), 2224 (four way).
b. Hubbell; CS1221 (single pole), CS1222 (two pole), CS1223 (three way), CS1224
(four way).
c. Leviton; 1221-2 (single pole), 1222-2 (two pole), 1223-2 (three way), 1224-2 (four
way).
d. Pass & Seymour; 20AC1 (single pole), 20AC2 (two pole), 20AC3 (three way),
20AC4 (four way).
2. Description: Single pole, with neon-lighted handle, illuminated when switch is "ON."
A. Wall-Switch Sensors:
B. Wet-Location, Weatherproof Cover Plates: NEMA 250, complying with Type 3R weather-
resistant, die-cast aluminum with lockable cover.
1. Size: Selected to fit nominal 3-inch (75-mm) cored holes in the floor and matched to the
floor thickness.
2. Fire Rating: Unit is listed and labeled to match the fire rating of the floor.
3. Receptacle: 5-20R duplex receptacle with spring loaded cover.
4. Two, 1/2-inch openings for future data cable.
5. Brass carpet flange and matching brass duplex flap covers.
6. Hubbell Catalog No. PT7FSDBRS2, or approved equal.
B. Description: Neon bulb emits light through transparent lens, illuminated when 120-volt power
is “ON”. Provide engraved wall plate indicating load served.
2.9 FINISHES
A. Color: Wiring device catalog numbers in Section text do not designate device color.
PART 3 - EXECUTION
3.1 INSTALLATION
1. Take steps to insure that devices and their boxes are protected. Do not place wall finish
materials over device boxes and do not cut holes for boxes with routers that are guided by
riding against outside of the boxes.
2. Keep outlet boxes free of plaster, drywall joint compound, mortar, cement, concrete, dust,
paint, and other material that may contaminate the raceway system, conductors, and
cables.
3. Install device boxes in brick or block walls so that the cover plate does not cross a joint
unless the joint is troweled flush with the face of the wall.
4. Install wiring devices after all wall preparation, including painting, is complete.
C. Conductors:
1. Do not strip insulation from conductors until just before they are spliced or terminated on
devices.
2. Strip insulation evenly around the conductor using tools designed for the purpose. Avoid
scoring or nicking of solid wire or cutting strands from stranded wire.
3. The length of free conductors at outlets for devices shall meet provisions of NFPA 70,
Article 300, without pigtails.
D. Device Installation:
1. Replace all devices that have been in temporary use during construction or that show
signs that they were installed before building finishing operations were complete.
2. Keep each wiring device in its package or otherwise protected until it is time to connect
conductors.
3. Do not remove surface protection, such as plastic film and smudge covers, until the last
possible moment.
4. Connect devices to branch circuits using pigtails that are not less than 6 inches (152 mm)
in length.
5. When there is a choice, use side wiring with binding-head screw terminals. Wrap solid
conductor tightly clockwise, 2/3 to 3/4 of the way around terminal screw.
6. Use a torque screwdriver when a torque is recommended or required by the manufacturer.
7. When conductors larger than No. 12 AWG are installed on 15- or 20-A circuits, splice
No. 12 AWG pigtails for device connections.
8. Tighten unused terminal screws on the device.
9. When mounting into metal boxes, remove the fiber or plastic washers used to hold device
mounting screws in yokes, allowing metal-to-metal contact.
E. Receptacle Orientation:
1. Install ground pin of vertically mounted receptacles up, and on horizontally mounted
receptacles to the right.
F. Device Plates: Do not use oversized or extra-deep plates. Repair wall finishes and remount
outlet boxes when standard device plates do not fit flush or do not cover rough wall opening.
G. Dimmers:
H. Arrangement of Devices: Unless otherwise indicated, mount flush, with long dimension
vertical and with grounding terminal of receptacles on top. Group adjacent switches under
single, multigang wall plates.
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
1. Cartridge fuses rated 600 V and less for use in switches and controllers.
1.3 SUBMITTALS
A. Product Data: Include the following for each fuse type indicated:
B. Operation and Maintenance Data: For fuses to include in emergency, operation, and
maintenance manuals.
B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for
intended use.
A. Where ambient temperature to which fuses are directly exposed is less than 40 deg F (5 deg C)
or more than 100 deg F (38 deg C), apply manufacturer's ambient temperature adjustment
factors to fuse ratings.
FUSES 262813 - 1
RAYTOWN PUBLIC WORKS BUILDING IMPROVEMENTS 10-107
CITY OF RAYTOWN, MISSOURI
1.6 COORDINATION
A. Coordinate fuse ratings with utilization equipment nameplate limitations of maximum fuse size.
A. Furnish extra materials described below that match products installed and that are packaged
with protective covering for storage and identified with labels describing contents.
1. Fuses: Quantity equal to one percent of each fuse type and size, but no fewer than three
of each type and size.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Characteristics: NEMA FU 1, nonrenewable cartridge fuse; class and current rating indicated;
voltage rating consistent with circuit voltage.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine utilization equipment nameplates and installation instructions. Install fuses of sizes
and with characteristics appropriate for each piece of equipment.
B. Evaluate ambient temperatures to determine if fuse rating adjustment factors must be applied to
fuse ratings.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
FUSES 262813 - 2
RAYTOWN PUBLIC WORKS BUILDING IMPROVEMENTS 10-107
CITY OF RAYTOWN, MISSOURI
3.3 INSTALLATION
A. Install fuses in fusible devices. Arrange fuses so rating information is readable without
removing fuse.
3.4 IDENTIFICATION
A. Install labels indicating fuse replacement information on inside door of each fused switch.
FUSES 262813 - 3
RAYTOWN PUBLIC WORKS BUILDING IMPROVEMENTS 10-107
CITY OF RAYTOWN, MISSOURI
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and other Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes the following individually mounted, enclosed switches and circuit
breakers:
1. Fusible switches.
2. Nonfusible switches.
3. Molded-case circuit breakers.
4. Enclosures.
1.3 DEFINITIONS
1.4 SUBMITTALS
A. Product Data: For each type of enclosed switch, circuit breaker, accessory, and component
indicated. Include dimensioned elevations, sections, weights, and manufacturers' technical data
on features, performance, electrical characteristics, ratings, and finishes.
1. Enclosure types and details for types other than NEMA 250, Type 1.
2. Current and voltage ratings.
3. Short-circuit current rating.
4. Features, characteristics, ratings, and factory settings of individual overcurrent protective
devices and auxiliary components.
B. Operation and Maintenance Data: For enclosed switches and circuit breakers to include in
emergency, operation, and maintenance manuals. In addition to items specified in Division 01
Section "Operation and Maintenance Data," include the following:
1. Manufacturer's written instructions for testing and adjusting enclosed switches and circuit
breakers.
2. Time-current curves, including selectable ranges for each type of circuit breaker.
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for
intended use.
C. Product Selection for Restricted Space: Drawings indicate maximum dimensions for enclosed
switches and circuit breakers, including clearances between enclosures, and adjacent surfaces
and other items. Comply with indicated maximum dimensions.
A. Environmental Limitations: Rate equipment for continuous operation under the following
conditions, unless otherwise indicated:
1. Ambient Temperature: Not less than minus 22 deg F (minus 30 deg C) and not
exceeding 104 deg F (40 deg C).
2. Altitude: Not exceeding 6600 feet (2010 m).
1.7 COORDINATION
A. Coordinate layout and installation of switches, circuit breakers, and components with other
construction, including conduit, piping, equipment, and adjacent surfaces. Maintain required
workspace clearances and required clearances for equipment access doors and panels.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. In other Part 2 articles where titles below introduce lists, the following requirements apply to
product selection:
A. Manufacturers:
B. Fusible Switch, 800 A and Smaller: NEMA KS 1, Type HD, with clips or bolt pads to
accommodate specified fuses, lockable handle with capability to accept two padlocks, and
interlocked with cover in closed position.
C. Nonfusible Switch, 800 A and Smaller: NEMA KS 1, Type HD, lockable handle with
capability to accept two padlocks, and interlocked with cover in closed position.
D. Accessories:
1. Equipment Ground Kit: Internally mounted and labeled for copper and aluminum ground
conductors.
A. Manufacturers:
B. Molded-Case Circuit Breaker: NEMA AB 1, with interrupting capacity to meet available fault
currents.
2.4 ENCLOSURES
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine elements and surfaces to receive enclosed switches and circuit breakers for compliance
with installation tolerances and other conditions affecting performance.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 INSTALLATION
A. Comply with applicable portions of NECA 1, NEMA PB 1.1, and NEMA PB 2.1 for installation
of enclosed switches and circuit breakers.
B. Mount individual wall-mounting switches and circuit breakers with tops at uniform height,
unless otherwise indicated. Anchor floor-mounting switches to concrete base.
3.3 IDENTIFICATION
3.5 CLEANING
A. On completion of installation, vacuum dirt and debris from interiors; do not use compressed air
to assist in cleaning.
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
1.3 DEFINITIONS
1.4 SUBMITTALS
A. Product Data: For each type of lighting fixture, arranged in order of fixture designation.
Include data on features, accessories, finishes, and the following:
4. Energy-efficiency data.
5. Lamps: include life, output, CRI and color temperature for each type.
6. Photometric data, in IESNA format, based on laboratory tests of each lighting fixture
type, outfitted with lamps, ballasts, and accessories identical to those indicated for the
lighting fixture as applied in this Project. Upon request, provide electronic photometric
data in IESNA format.
C. Operation and Maintenance Data: For lighting equipment and fixtures to include in emergency,
operation, and maintenance manuals.
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for
intended use.
1.6 COORDINATION
A. Coordinate layout and installation of lighting fixtures and suspension system with other
construction that penetrates ceilings or is supported by them, including HVAC equipment, fire-
suppression system, and partition assemblies.
A. Furnish extra materials described below that match products installed and that are packaged
with protective covering for storage and identified with labels describing contents.
1. Lamps: 10 for every 100 of each type and rating installed. Furnish at least one of each
type.
2. Plastic Diffusers and Lenses: 1 for every 100 of each type and rating installed. Furnish
at least one of each type.
3. Battery and Charger Data: One for each emergency lighting unit.
4. Ballasts: 1 for every 100 of each type and rating installed. Furnish at least one of each
type.
5. Globes and Guards: 1 for every 20 of each type and rating installed. Furnish at least one
of each type.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Fixtures: Refer to the Interior Light Fixture Schedule on drawings for allowable fixture
manufacturers. Fixtures must meet requirements noted on drawings and specified below.
B. Ballasts: Subject to compliance with requirements, provide products by one of the following:
C. Lamps: Subject to compliance with requirements, provide products by one of the following:
1. General Electric.
2. Philips.
3. Osram Sylvania.
4. Venture Lighitng International, Inc.
A. Recessed Fixtures: Comply with NEMA LE 4 for ceiling compatibility for recessed fixtures.
B. Fluorescent Fixtures: Comply with UL 1598. Where LER is specified, test according to
NEMA LE 5 and NEMA LE 5A as applicable.
D. Sheet Metal Components: Steel, unless otherwise indicated. Form and support to prevent
warping and sagging.
E. Doors, Frames, and Other Internal Access: Smooth operating, free of light leakage under
operating conditions, and designed to permit relamping without use of tools. Designed to
prevent doors, frames, lenses, diffusers, and other components from falling accidentally during
relamping and when secured in operating position.
F. Reflecting surfaces shall have minimum reflectance as follows, unless otherwise indicated:
1. Acrylic Lighting Diffusers: 100 percent virgin acrylic plastic. High resistance to
yellowing and other changes due to aging, exposure to heat, and UV radiation.
a. Lens Thickness: At least 0.125 inch (3.175 mm) minimum unless different
thickness is indicated.
b. UV stabilized.
A. Electronic Ballasts: Comply with ANSI C82.11; instant-start type, unless otherwise indicated,
and designed for type and quantity of lamps served. Ballasts shall be designed for full light
output unless dimmer control is indicated.
1. Sound Rating: A.
2. Total Harmonic Distortion Rating: Less than 20 percent.
3. Transient Voltage Protection: IEEE C62.41, Category A or better.
4. Operating Frequency: 20 kHz or higher.
5. Lamp Current Crest Factor: 1.7 or less.
6. BF: between 0.85 and 1.05.
7. Power Factor: 0.95 or higher.
8. Input Power (ANSI Watts): Maximum input power for 32-watt T8 lamps are as follows:
B. Single Ballasts for Multiple Lighting Fixtures: Factory-wired with ballast arrangements and
bundled extension wiring to suit final installation conditions without modification or rewiring in
the field.
A. Description: Electronic programmed rapid-start type, complying with ANSI C 82.11, designed
for type and quantity of lamps indicated. Ballast shall be designed for full light output unless
dimmer or bi-level control is indicated:
10. Interference: Comply with 47 CFR, Chapter 1, Part 18, Subpart C, for limitations on
electromagnetic and radio-frequency interference for nonconsumer equipment.
11. Ballast Case Temperature: 75 deg C, maximum.
A. Internal Type: Self-contained, modular, battery-inverter unit, factory mounted within lighting
fixture body and compatible with ballast. Comply with UL 924.
a. Push Button: Push-to-test type, in unit housing, simulates loss of normal power
and demonstrates unit operability.
b. Indicator Light: LED indicates normal power on. Normal glow indicates trickle
charge; bright glow indicates charging at end of discharge cycle.
A. Description: Comply with UL 924; for sign colors, visibility, luminance, and lettering size,
comply with authorities having jurisdiction.
1. Lamps for AC Operation: LEDs, 70,000 hours minimum rated lamp life.
5. LED Indicator Light: Indicates normal power on. Normal glow indicates trickle charge;
bright glow indicates charging at end of discharge cycle.
6. Wire Guard: Heavy-chrome-plated wire guard protects lamp heads or fixtures. Provide
this option where indicated on drawings.
7. Integral Time-Delay Relay: Holds unit on for fixed interval of 15 minutes when power is
restored after an outage. Provide this option where indicated on drawings.
8. Integral Self-Test: Factory-installed electronic device automatically initiates code-
required test of unit emergency operation at required intervals. Test failure is
annunciated by an integral audible alarm and flashing red LED.
A. Low-Mercury Lamps: Comply with EPA's toxicity characteristic leaching procedure test; shall
yield less than 0.2 mg of mercury per liter when tested according to NEMA LL 1.
C. Compact Fluorescent Lamps: 4-Pin, low mercury, CRI 80 (minimum), color temperature
3500 K, average rated life of 10,000 hours at 3 hours operation per start, and suitable for use
with dimming ballasts, unless otherwise indicated.
A. Comply with Division 26 Section "Hangers and Supports for Electrical Systems" for channel-
and angle-iron supports and nonmetallic channel and angle supports.
B. Suspended fluorescent direct/indirect and direct fixtures in finished space: Suspend fixtures
with manufacturer’s standard aircraft cable system unless noted otherwise. Feed fixtures with
manufacturer’s standard SO cable.
C. Suspended industrial troffers in unfinished spaces: Suspend fixtures with chains unless noted
otherwise.
D. Wires: ASTM A 641/A 641M, Class 3, soft temper, zinc-coated steel, 12 gage (2.68 mm).
E. Wires for Humid Spaces: ASTM A 580/A 580M, Composition 302 or 304, annealed stainless
steel, 12 gage (2.68 mm).
F. Rod Hangers: 3/16-inch (5-mm) minimum diameter, cadmium-plated, threaded steel rod.
G. Hook Hangers: Integrated assembly matched to fixture and line voltage and equipped with
threaded attachment, cord, and locking-type plug.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Lighting fixtures: Set level, plumb, and square with ceilings and walls. Install lamps in each
fixture.
B. Support for Lighting Fixtures in or on Grid-Type Suspended Ceilings: Do not use grid as a
support element.
1. Install ceiling support system wires at a minimum of 2 wires connected directly to each
fixture, located not more than 6 inches (150 mm) from opposite fixture corners. Provide
additional supports if required by local code or the local authority having jurisdiction.
2. Support Clips: Fasten to lighting fixtures and to ceiling grid members at or near each
fixture corner with clips that are UL listed for the application.
3. Fixtures of Sizes Less Than Ceiling Grid: Install as indicated on reflected ceiling plans
or center in acoustical panel, and support fixtures independently with at least two 3/4-
inch (20-mm) metal channels spanning and secured to ceiling tees.
1. Pendants and Rods: Where longer than 48 inches (1200 mm), brace to limit swinging.
2. Stem-Mounted, Single-Unit Fixtures: Suspend with twin-stem hangers.
3. Continuous Rows: Use tubing or stem for wiring at one point and tubing or rod for
suspension for each unit length of fixture chassis, including one at each end.
A. Test for Emergency Lighting: Interrupt power supply to demonstrate proper operation. Verify
transfer from normal power to battery and retransfer to normal.
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
1.3 DEFINITIONS
D. Pole: Luminaire support structure, including tower used for large area illumination.
1.4 SUBMITTALS
A. Product Data: For each luminaire, pole, and support component, arranged in order of lighting
unit designation. Include data on features, accessories, finishes, and the following:
C. Operation and Maintenance Data: For luminaries and poles to include in emergency, operation,
and maintenance manuals.
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,
Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for
intended use.
B. Store poles on decay-resistant-treated skids at least 12 inches (300 mm) above grade and
vegetation. Support poles to prevent distortion and arrange to provide free air circulation.
C. Retain factory-applied pole wrappings on metal poles until right before pole installation. For
poles with nonmetallic finishes, handle with web fabric straps.
A. Furnish extra materials described below that match products installed and that are packaged
with protective covering for storage and identified with labels describing contents.
1. Lamps: 10 lamps for every 100 of each type and rating installed. Furnish at least one of
each type.
2. Glass and Plastic Lenses, Covers, and Other Optical Parts: Furnish one of each type.
3. Ballasts: 10 for every 100 of each type and rating installed. Furnish at least one of each
type.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. In other Part 2 articles where titles below introduce lists, the following requirements apply to
product selection:
B. In Exterior Lighting Fixture Schedule where titles below are column or row headings that
introduce lists, the following requirements apply to product selection:
1. Manufacturers: Subject to compliance with requirements, provide products by one of the
manufacturers specified.
2. Basis of Design Product: The design of each item of exterior luminaire and its support is
based on the product named. Subject to compliance with requirements, provide either the
named product or a comparable product by one of the other manufacturers specified.
A. Luminaires shall comply with UL 1598 and be listed and labeled for installation in wet
locations by an NRTL acceptable to authorities having jurisdiction.
B. Comply with IESNA RP-8 for parameters of lateral light distribution patterns indicated for
luminaires.
D. Sheet Metal Components: Corrosion-resistant aluminum, unless otherwise indicated. Form and
support to prevent warping and sagging.
E. Housings: Rigidly formed, weather- and light-tight enclosures that will not warp, sag, or
deform in use. Provide filter/breather for enclosed luminaires.
F. Doors, Frames, and Other Internal Access: Smooth operating, free of light leakage under
operating conditions, and designed to permit relamping without use of tools. Designed to
prevent doors, frames, lenses, diffusers, and other components from falling accidentally during
relamping and when secured in operating position. Doors shall be removable for cleaning or
replacing lenses. Designed to disconnect ballast when door opens.
H. Plastic Parts: High resistance to yellowing and other changes due to aging, exposure to heat,
and UV radiation.
I. Light Shields: Metal baffles, factory installed and field adjustable, arranged to block light
distribution to indicated portion of normally illuminated area or field.
J. Reflecting surfaces shall have minimum reflectance as follows, unless otherwise indicated:
K. Lenses and Refractors Gaskets: Use heat- and aging-resistant resilient gaskets to seal and
cushion lenses and refractors in luminaire doors.
B. Contact Relays: Factory mounted, single throw, designed to fail in the on position, and factory
set to turn light unit on at 1.5 to 3 fc (16 to 32 lx) and off at 4.5 to 10 fc (48 to 108 lx) with 15-
second minimum time delay.
A. Low-Temperature Ballast Capability: Rated by its manufacturer for reliable starting and
operation of indicated lamp(s) at temperatures [0 deg F (minus 18 deg C)] [minus 20 deg F
(minus 29 deg C)] and higher.
B. Ballast Characteristics:
C. Low-Temperature Lamp Capability: Rated for reliable starting and operation with ballast
provided at temperatures [0 deg F (minus 18 deg C)] [minus 20 deg F (minus 29 deg C)] and
higher.
D. Fluorescent Lamps: Low-mercury type. Comply with the EPA's toxicity characteristic leaching
procedure test; shall yield less than 0.2 mg of mercury per liter when tested according to
NEMA LL 1.
A. Comply with ANSI C82.4 and UL 1029 and capable of open-circuit operation without reduction
of average lamp life. Include the following features, unless otherwise indicated:
A. High-Pressure Sodium Lamps: ANSI C78.42, CRI 21 (minimum), color temperature 1900 K,
and average rated life of 24,000 hours, minimum.
B. Metal-Halide Lamps: ANSI C78.1372, with a minimum CRI 65, and color temperature 4000 K.
C. Pulse-Start, Metal-Halide Lamps: Minimum CRI 65, and color temperature 4000 K.
PART 3 - EXECUTION
1. Use fastening methods and materials selected to resist seismic forces defined for the
application and approved by manufacturer.
C. Adjust luminaires that require field adjustment or aiming. Include adjustment of photoelectric
device to prevent false operation of relay by artificial light sources.
3.2 GROUNDING
A. Ground metal poles and support structures according to Division 26 Section "Grounding and
Bonding for Electrical Systems."
A. Inspect each installed fixture for damage. Replace damaged fixtures and components.
B. Illumination Observations: Verify normal operation of lighting units after installing luminaires
and energizing circuits with normal power source.
C. Prepare a written report of tests, inspections, observations, and verifications indicating and
interpreting results. If adjustments are made to lighting system, retest to demonstrate
compliance with standards.