TYPE DIP-806/00
INSTRUCTION AND USER MANUAL
PARMA ® ITALY
NOTICES
Warning:
adhere closely to the following advice
- Always install it below equipment that produces or spreads heat.
- When making connections, always follow the enclosed circuit diagram.
- Make sure that the power drain and consumption of the connected equipment is compatible with the
enclosed technical characteristics.
- All technical interventions must be performed with the engine stationary and with terminal 50 of the start
motor disconnected.
- Never use the battery charger for emergency start-up, this could damage the engine protection control.
- To ensure the safety of both persons and the equipment, disconnect the eletrical plant terminals from the
battery poles before connecting an external battery charger.
NOTE: THE HOLE MADE IN THE ENCLOSURE FOR EQUIPMENT INSTALLATION COULD INFLUENCE THE
DEGREE OF PROTECTION OF BOOTH. MEASURES MUST BE TAKEN TO MAINTAIN THE
ORIGINAL DEGREE OF PROTECTION.
THIS DEVICE IS NOT SUITABLE FOR OPERATING UNDER THE FOLLOWING CONDITIONS:
- where the environmental temperature is outside the limites specified in the enclosed technical sheet.
- where there are high levels of heat radiation due to the sun, furnaces, etc.
- where there is the risk of fires or explosions.
- where the device could receive knocks or strong vibrations.
ELECTROMAGNETIC COMPATIBILITY
This protection control functions correctly only if it is inserted in plants that meet CE marking standards. The
protection control meets the requirements of standard EN50082-2, but malfunctions cannot be excluded in
extreme situations.
The installer has the ask of ascertaining that the disturbance levels are below those set out in the standards.
UNLESS WE MAKE A WRITTEN DECLARATION STATING THE CONTRARY, THIS PANEL IS NOT SUITABLE
FOR USE AS A CRITICAL COMPONENT IN EQUIPMENT OR PLANTS RESPONSIBLE FOR KEEPING
PERSONS OR OTHER LIVING BEINGS ALIVE.
START.
- ENGINE START-UP
ENGINE PROTECTIONS
The overspeed protection is enabled immediately with the key turned to "AUT". All of the other
protections are enabled when the ACTIVE PROTECTIONS indicators lights up (20 seconds after
the key is turned to "AUT" or 20 seconds after the start pulses have finished).
When the protection probes (mounted on the engine) intervene, the engine is stopped. These
interventions are shown by the relevant indicators and can be divided into two groups:
- OVERHEATING THERMOSTAT
- BATTERY CHARGE ALTERNATOR
(alternator belt breakage)
- OVERSPEED
BATTERY CHARGE
ALTERNATOR (terminal W)
MAGNETIC TRANSDUCER
(pick-up)
PERMANENT MAGNET
ALTERNATOR (yellow wire)
GB DIP-806/00 /2 3
FUNCTIONS
ALARM
(FUEL RESERVE )
Enbled with key in "AUT" position. The engine does not stop.
STOP
GENERAL ALARM
Obtained through the external mounting of a visual and/or acoustic indicator wich is connected to
the relevant output.
If the alarm (fuel reserve) or protections intervene, it is activated permanently.
RESET: Turn the start key to zero.
4 GB DIP-806/00 /2
ENGINE PROBES TEST
(WITH PROBES DISCONNECTED)
YELLOW
RED
YELLOW 3W USUALLY RELEVANT
CHARGE ENGINE ALTERNATOR
ALTERNATOR GRGB L C STATIONARY
TERMINAL IS
PERMANENT ENGINE RUNNING NEGATIVE WITH
(BELT MAGNET ~ R ~ + LE WITH REGULAR ENGINE STATIONARY
BREAKAGE) ALTERNATOR BELT
D+ ENGINE RUNNING
WITH BROKEN
B+ BELT
PRE-EXCITATION
ALTERNATOR
3W USUALLY OIL
LOW OIL ENGINE
STATIONARY PRESSURE SWITCH
PRESSURE TERMINAL IS
ENGINE RUNNING NEGATIVE WITH
WITH REGULAR ENGINE STATIONARY
LOW OIL PRESSURE
PRESSURE
ENGINE RUNNING
WITH INSUFFICIENT
PRESSURE
3W
OVERHEATING ENGINE AT THERMOSTAT
NORMAL TERMINAL IS
TEMPERATURE USUALLY NEGATIVE
OVERHEATED WHEN ENGINE IS
THERMOSTAT ENGINE TOO HOT
W 3W
FUEL RESERVE USUALLY FLOAT
SUFFICIENT
FUEL
TERMINAL W IS
NEGATIVE WHEN
INSUFFICIENT FUEL IS LOW
FUEL
FLOAT
- MAGNETIC V~
TRANSDUCER 2 ÷ 20 VAC
YELLOW
RED
YELLOW
- PERMANENT V~
MAGNET GRGB L C
4 ÷ 50 VAC
ALTERNATOR
YELLOW WIRE ~ R ~ + LE
NOTE: WHEN THE TEST HAS BEEN COMPLETED RECONNECT THE PROBES
GB DIP-806/00 /2 5
CIRCUIT
30 85
(USE THE STOP LEVER OR
INTERRUPT THEFUEL FLOW)
87 86
2/7
W
157
h 3W
MAX 3
FUSE 48
30 5A
1 50
15/54 FUSE
5A 4 16
30
50
40 41
1 2 3 5 6 7 8 29 30 31 37 39 40
W
B+
D+ DIP-806/00
28 9 13 14 33
(BELT BREAKAGE)
YELLOW OVERSPEED
ADJUSTMENT
RED
YELLOW
GRGB L C
27
~ R ~ + LE
FOR OVERSPEED CONTROL
26 CONNECT TERMINAL 9
OR TERMINALS 13-14
(NOT BOOTH)
ENGINE FLYWHEEL TEETH
DISTANCE
0.5 mm ±0.2
35
6
GB DIP-806/00 /2
DIAGRAM
DRIVE
STOP SYSTEMS SET UP EXCITATION
The system is arranged to command SOLENOID
the stopping with SOLENOID. for closing
diesel
For ELECTROMAGNET stopping,
connect terminals 39 and 40. STOP
EXCITATION ELECTROMAGNET
for pulling
STOP lever
39 40
WARNING ACCESSORIES
IF THE FOLLOWING AVAILABLE ON REQUEST
FUNCTIONS ARE NOT (1) START KEY
USED: (2/7) ELECTROMAGNET OR SOLENOID
• OVERSPEED (3) OIL PRESSURE SWITCH
BRIDGE BETWEEN (4) THERMOSTAT
TERMINALS 9 - 13 (16) FUEL FLOAT
9 13 14 (35) MAGNETIC TRANSDUCER (TYPE TM30/50, /60, /85)
(48) HOUOR COUNTER
• LOW COOLING (155) RADIATOR LIQUID LEVEL PROBE
LIQUID LEVEL (157) INDICATOR (MAIN ALARM)
CONNECT TERMINAL MOUNTED ON THE ENGINE
33 TO EARTH (26) PERMANENT MAGNET CHARGE ALTERNATOR
33 (27) ALTERNATOR REGULATOR
(28) PRE-EXCITATION CHARGE ALTERNATOR
(40) START MOTOR
(41) BATTERY
155 155
SCREW ROD
ELECTRODES ELECTRODE
7
GB DIP-806/00 /2
DEVICE TEST
(SIMULATION)
FUNCTION PERFORMED INTERVENTION SIMULATION FUNCTIONS INTERVENTION
(WITH ACTIVE PROTECTIONS (STOP, GENERAL ALARM
AND VISUAL
INDICATOR ON) INDICATOR ON)
AFTER 3 SECONDS
FUEL RESERVE DISCONNECT WIRE FROM TERMINAL RELAVANT INDICATOR
W OF FLOAT AND CONNECT TO EARTH LIGHTS UP, BUT ENGINE
DOES NOT STOP
NOTE
WHEN THE SIMULATION HAS BEEN COMPLETED, MAKE SURE THAT ALL CONNECTIONS AND
CALIBRATIONS ARE RETURNED TO THEIR ORIGINAL POSITIONS.
TROUBLE SHOOTING
8 GB DIP-806/00 /2
TROUBLE SHOOTING
ENGINE STOPPAGE - Low cooling liquid level - Check cooling liquid level
FOR ANOMALY indicator is on
ENGINE DOES NOT - Stop system (electromagnet - Check the correct mechanical or electrical
STOP or solenoid) is not functioning functioning of the stop system. If the
problem persists, check the stop servorelay.
GB DIP-806/00 /2 9
TROUBLE SHOOTING
ENGINE STOPPAGE - Low cooling liquid level - Check probe, clean it, if necessary replace
FOR ANOMALY, indicator is on it
ALTHOUGH ALL SEEMS
TO FUNCTION - Belt breakage indicator - Check charge alternator functions correctly
is on after ACTIVE
PROTECTIONS
indicator lights up
Before replacing the protection control, one of our technicians should be telephoned for advice.
When your electrical-technician telephones, he should have the schemes on pages
6-7 available together with the following information:
- Type of equipment installed
- Problem
- Appearance of indicators on dashboard when problem occurred
- Any previous remedial action taken
10 GB DIP-806/00 /2
ACCESSORIES AVAILABLE ON REQUEST
FRONT PIECE 48 × 96
107
FRONT PIECE 48 × 96
(COMPLETE WITH:
FIXING SCREWS,
HORIZONTAL AND
VERTICAL PLATE)
105
type F806 code 26.16.22
EXAMPLE OF MOUNTING
Drill holes into the panel Remove the plate Screw protection control Apply the sticky plate
using the front piece as a from protection control and front piece onto the
template panel
Ø5
GB DIP-806/00 /2 11
DIMENSIONS TECHNICAL DATA
(STOP)
- DEGREE OF PROTECTION
FOR THE ELECTRONICS IP 65
FOR THE TERMINAL BOARD IP 00
- WEIGHT 460 g
CONFORMITY DECLARATION
type: DIP-806/00
used in the ways and for the purposes described in this instruction and user
manual is in conformity with the following directive:
89/336/CEE concerning electromagnetic compatibility
modified by the directive 93/68/CEE
being manufactured and functioning in accordance with the harmonized
standards:
EN 50081-1, EN 50082-2
® Parma, 15/10/1998
S.r.l. President
Via Naviglio Alto, 24/a
43100 PARMA ITALIA
Tel. +39 0521/772021 Fax +39 0521/270218
E-mail: info@elcos.it - HTTP://www.elcos.it
Walter Consigli
12 GB DIP-806/00 /2