BS Loads
BS Loads
Mean Height (h) = 6.00 m Low Rise Building Sec. 6.20 ASCE 7-98
(Eave height may be used if θ<=10°) Sec. 6.5.6.2.2 ASCE 7-98
Roof Slope = 0.50 :10 2.86 Degrees
Length of the building (L) = 25.00 m Horizontal dimension measured parallel to the wind
Width of the building (B) = 50.00 m Horizontal dimension measured normal to the wind
Basic Wind Speed (V) = 130 km/hr 3-Sec. gust wind speed at Sec. 6.20 ASCE 7-98
Structure Type = Main Wind Force Resisting System Table 6-6 ASCE 7-98
Ao = Total area of opening in a wall that receives positive external pressure (m2)
Enclosed Building
Velocity Pressure Exp. Coeff. (Kz) = 0.62 For Main Wind Force - Table 6-5 ASCE 7-98
- Resisting system (MWFRS)
Velocity Pressure Exp. Coeff. (Kz) = 0.62 For Components and Clad Table 6-5 ASCE 7-98
Gust effect factor (G) = 0.85 For Rigid Structures Sec. 6.5.8
Design Wind Pressure (p) = qh [ (Gcpf) - (Gcpi) ] kN/m2 Eqn. 1.4.2 MBMA 2002
TRANSVERSE DIRECTION
-0.55 -0.31
-0.39 -0.15
-0.38 -0.24
-0.22 -0.08
-0.48
-0.48
-0.48
-0.48
End Walls
Note:- The Values are Wind Loads in kN/m2
TRANSVERSE DIRECTION
-0.38
-0.22 -0.24
-0.08
0.28
0.38 -0.48
-0.55 -0.48
-0.39
0.19
0.35 -0.31
-0.15
-0.48 -0.21
-0.48 -0.11
-0.27
Err:523
Roofs
Figure 1.4.5(a) Walls
End Zone
-0.38 -0.24
-0.22 -0.08
-0.31
-0.55 0.28 -0.15
-0.39 0.38 -0.48
-0.48
0.19
0.35
-0.21
-0.11
-0.48
-0.48 -0.27
Err:523
Figure 1.4.5(b)
Note:- The Values are Wind Loads in kN/m2
LONGITUDINAL DIRECTION
-0.28 -0.28
-0.12 -0.12
-0.50 -0.50
-0.75*
-0.75* -0.75*
0.75*
1.3 N
where,
N - Number of Frames
for following limits
1) 0.1 <= ϕ <= 0.3
2) 1/6 <= h/B <= 6
3) S/B <= 0.5
See MBMA 2002 page 1-30 for more details
LONGITUDINAL DIRECTION
-0.24
-0.08
-0.28
-0.12
-0.38 -0.21
-0.22 -0.05
-0.27
-0.11
-0.31
-0.15
0.27
0.43 -0.28
-0.12
0.19
0.35 -0.55
-0.39
Figure 1.4.5(c)
Roofs
Walls
End Zone
-0.55
-0.39 -0.31 -0.24
-0.15 -0.08
-0.38 -0.21
-0.22 -0.05
-0.27
-0.11
-0.28
-0.12
-0.28
-0.12
0.27
0.43 0.19
0.35
Figure 1.4.5(b)
Note:- The Values are Wind Loads in kN/m2
-0.48
-0.48 0.48
0.48 -0.48 -0.48
0.48 -0.48 0.48
0.48 -0.48
0.48
SYM -0.56
0.48
-0.52
0.48
-0.56
0.48
-0.70
-0.52
0.48
-1.22
-0.56
0.48
-0.52
-0.56 0.48
0.48
-0.52
0.48
-0.56
0.48 -0.56
0.48
-0.52
0.48
-0.56
0.48 -0.56
0.48
-0.56 -0.56
0.48 -0.56 0.48
0.48
Mean Height (h) = 18.00 m Low Rise Building Sec. 6.20 ASCE 7-05
(Eave height may be used if Θ<=10°)
Roof Slope = 1.00 :10 5.71 Degrees
Length of the building (L) = 100.00 m Horizontal dimension measured parallel to the wind
Width of the building (B) = 50.00 m Horizontal dimension measured normal to the wind
Basic Wind Speed (V) = 160 km/hr 3-Sec. gust wind speed at 10 m Sec. 6.20 ASCE 7-05
Aoi = The sum of the areas of opening in the building envelope (Walls & Roof) not including A o (m2)
Agi = The sum of the gross surface areas of the building envelope (Walls & Roof) not including Ag (m2)
Enclosed Building
Velocity Pressure Exp. Coeff. (Kz) = 1.13 For Main Wind Force - Table 6-3
- Resisting system (MWFRS)
Velocity Pressure Exp. Coeff. (Kz) = 1.13 For Components and Claddings Table 6-3
Gust effect factor (G) = 0.85 For Rigid Structures Sec. 6.5.8
Windward Roof =
Leeward Roof =
Flexible Buildings
Parapets
Design Wind Pressure (p) = kN/m2 qp Gcpn
Open Buildings
-0.89 -0.35
0.79
A1 Enclosed 1
Building
B1 Partially Enclosed 2
Type
C Open 3
A4 End Zone 8
Zone
B4 Interior Zone 9
-0.25
Date 26-Nov-07
Gravity Loads Dsn. By ZAS
Chk. By SKK
BS 6399 Part 1; 1996 Rev. No. 0
A) Dead Loads
Unit weights are given in BS 648 or can be actual weights of the materials used.
D) Partition Loads
1) For permanent partitions the loads should be included in the dead loads
2) For proposed partitions, the uniformly distributed partion load shall not be less than 1 / 3 of the load per metre
run of the finished partition
3) For floors of offices, the additional uniformly distributed partition load should not be less than 1.0 kN/m 2
E) Ceiling Supports
1) Table 4 below specifies the minimum horizontal imposed loads appropriate to the design of parapets, barriers,
balistrades, and other elements of a structure intended to retain, stop or guide people.
2) The uniform line load, uniform distributed and concentrated load should be considered as 3 separate cases
3) The load should be considered to act a height of 1.1 m above the datum level, irrespective of the actual height of element.
4) For all types of activities, these elements should be designed either for a concentrated load of 1 kN or a UDL of
0.6 kN/m, which ever gives the worst design condition.
5) The horizontal force 'F' (kN) normal to and uniformly distributed over any length of 1.5 m of a barrier for a car park
is required to withstand the impact of a vehicle is given by
F = 0.5 m v2 / ( dc + db ) kN
where,
m = the gross mass of the vehicle in kgs. (may be taken as 1500 kgs for vehicles less than or equal to 2500 kgs.)
if mass is more than 2500 kgs, than use the actual weight.
v = the velocity of the vehicle in ( m/sec ) normal to the barrier ( = 4.5 m/sec )
dc = is the deformation of the vehicle in (mm) ( = 100 mm unless better evidence is available)
db = is the deformation of the barrier in (mm) ( = 0 for a rigid barrier )
a) The force is assumed to act at bumper height or 375 mm above floor level for cars less than 2500 kgs.
b) Barriers for access ramps of car parks shall be designed for half the force (F) at a height of 610 mm.
c) If the travel distance for downward travel is more than 20 m, barriers shall be designed for (2F) at a height of 610 mm
Table 4 Minimum Horizontal Imposed Loads for Parapets, Barriers and balustrades etc.
Horz. UD
Occupancy UDL in Con. Load
Examples of Specific Use Line Load
Type (Kn/m2) in (kN)
in (kN/m)
All areas of single family dwellings including stairs,
0.36 0.50 0.25
landings etc.
A
Other residential areas 0.74 1.00 0.50
Light access stairs, gangways not more than 0.6 m wide 0.22 N/A N/A
Building Length (L) = 75.00 m (Denoted as 'B' for Wind Left & Right)
(Denoted as 'D' for Wind End)
3 Second Gust Wind Speed = 160 kmph 44.44 m/sec, Table A7.6 MBMA 2006
Basic Wind Speed (Vb) = 104.58 kmph 29.05 m/sec ( Mean Hourly Wind Speed )
Site Altitude above mean sea level (Ds) = 1.00 m (Ground Level Height, Not building height)
Probability Factor (Sp) = 1.00 (Use 1.00 for normal design applications)
Average Height of surronding Buildings (Ho) = 6.00 m (Average height of surrounding obstructing-buildings)
Section
Probability Factor (Sb) = 1.00 For all normal design applications, Sp = 1.00 2.2.2.5
D/H= 4.17
0.2 b = 2.40 m
Pressure (kN/m2)
External Internal Net Primary Secondary
Windward Wall = 0.60 -0.30 0.90 0.53 0.71
Leeward Wall = -0.10 -0.30 0.20 0.12 0.16
Wall Zone A = -1.30 -0.30 -1.00 -0.59 -0.78
Wall Zone B = -0.80 -0.30 -0.50 -0.30 -0.39
Wall Zone C = -0.50 -0.30 -0.20 -0.12 -0.16
Notes:-
1) Use same values for pressure and suction for design of secondaries
2) Wind End
D/H= 12.50
0.2 b = 2.40 m
Pressure (kN/m2)
External Internal Net Primary Secondary
Windward Wall = 0.60 -0.30 0.90 0.60 0.71
Leeward Wall = -0.10 -0.30 0.20 0.13 0.16
Wall Zone A = -1.30 -0.30 -1.00 -0.67 -0.78
Wall Zone B = -0.80 -0.30 -0.50 -0.33 -0.39
Wall Zone C = -0.50 -0.30 -0.20 -0.13 -0.16
B) Roof Pressure for Pitched Roof Duo Slope
Pressures
External Internal Net Primary Secondary
Windward Roof ( C ) = 0.30 -0.30 0.60 0.36 0.47
0.00 -0.30 0.30 0.18 0.24
Leeward Roof ( G ) = 0.00 -0.30 0.30 0.18 0.24
0.00 -0.30 0.30 0.18 0.24
Eave Corners ( A ) = 0.00 -0.30 0.30 0.18 0.24
0.00 -0.30 0.30 0.18 0.24
Eave Interior ( B ) = 0.00 -0.30 0.30 0.18 0.24
0.00 -0.30 0.30 0.18 0.24
Ridge Corner ( E ) = 0.00 -0.30 0.30 0.18 0.24
0.00 -0.30 0.30 0.18 0.24
Ridge Interior ( F ) = 0.00 -0.30 0.30 0.18 0.24
0.00 -0.30 0.30 0.18 0.24
2) Wind End
Pressures
External Internal Net Primary Secondary
Near Roof ( C ) = 0.00 -0.30 0.30 0.18 0.24
0.00 -0.30 0.30 0.18 0.24
Far Roof ( D ) = 0.00 -0.30 0.30 0.18 0.24
0.00 -0.30 0.30 0.18 0.24
Gable Corners ( A ) = 0.00 -0.30 0.30 0.18 0.24
0.00 -0.30 0.30 0.18 0.24
Gable Interior ( B ) = 0.00 -0.30 0.30 0.18 0.24
0.00 -0.30 0.30 0.18 0.24
C) Roof Pressure for Pitched Roof Mono Slope
Pressures
External Internal Net Primary Secondary
Windward Roof ( C ) = -0.60 -0.30 -0.30 -0.18 -0.24
0.00 -0.30 0.30 0.18 0.24
Eave Corners ( A ) = -1.80 -0.30 -1.50 -0.89 -1.18
0.00 -0.30 0.30 0.18 0.24
Eave Interior ( B ) = -1.20 -0.30 -0.90 -0.53 -0.71
0.00 -0.30 0.30 0.18 0.24
2) Wind End
Pressures
External Internal Net Primary Secondary
Windward Roof ( C ) = -0.70 -0.30 -0.40 -0.24 -0.31
0.00 -0.30 0.30 0.18 0.24
Leeward Roof ( D ) = -0.70 -0.30 -0.40 -0.24 -0.31
0.00 -0.30 0.30 0.18 0.24
Gable Corner ( Au ) = -2.20 -0.30 -1.90 -1.12 -1.49
0.00 -0.30 0.30 0.18 0.24
Gable Corner ( AL ) = -2.10 -0.30 -1.80 -1.06 -1.41
0.00 -0.30 0.30 0.18 0.24
Gable Interior ( B ) = -1.10 -0.30 -0.80 -0.47 -0.63
0.00 -0.30 0.30 0.18 0.24
D) Roof Pressure for Flat Roofs
For Sidewall
Corner Zone ( A ) size at roof = 1.2 x 3 m [( bL / 10 ) x ( bL / 4 )]
Edge Strip width at roof = 6.00 m bL / 2
For Endwall
Corner Zone ( A ) size at roof = 1.2 x 3 m [( bw / 10 ) x ( bw / 4 )]
Edge Strip width at roof = 6.00 m bw / 2
Pressures
External Internal Net Primary Secondary
Near Roof ( C ) = -0.70 -0.30 -0.40 -0.24 -0.31
Eave Corner ( A ) = -1.88 -0.30 -1.58 -0.93 -1.24
Edge Strip ( B ) = -1.30 -0.30 -1.00 -0.59 -0.78
Far Roof ( D ) = 0.20 -0.30 0.50 0.30 0.39
-0.20 -0.30 0.10 0.06 0.08
E) Hipped Roof
Pressures
External Internal Net Primary Secondary
Windward Roof ( C ) = 0.00 -0.30 0.30 0.18 0.24
0.00 -0.30 0.30 0.18 0.24
Leeward Roof ( G ) = 0.00 -0.30 0.30 0.18 0.24
0.00 -0.30 0.30 0.18 0.24
Eave Corners ( A ) = 0.00 -0.30 0.30 0.18 0.24
0.00 -0.30 0.30 0.18 0.24
Eave Interior ( B ) = 0.00 -0.30 0.30 0.18 0.24
0.00 -0.30 0.30 0.18 0.24
Hip Edge ( E ) = 0.00 -0.30 0.30 0.18 0.24
0.00 -0.30 0.30 0.18 0.24
Ridge Interior ( F ) = 0.00 -0.30 0.30 0.18 0.24
0.00 -0.30 0.30 0.18 0.24
Hip Edge ( H ) = 0.00 -0.30 0.30 0.18 0.24
0.00 -0.30 0.30 0.18 0.24
Hip Interior ( I ) = 0.00 -0.30 0.30 0.18 0.24
0.00 -0.30 0.30 0.18 0.24
Farside Roof ( J ) = 0.00 -0.30 0.30 0.18 0.24
0.00 -0.30 0.30 0.18 0.24
F) Multi Bay Roofs
If the roof overhang projects less than ( b / 10 ) from the wall then, pressure coefficients are as below,
For roof overhangs, larger than ( b / 10 ) it should be treated as open sided building with internal pressure
2) Secondaries
Upper Surface = -1.80 Pressure coefficient for Zone A of monoslope
Lower Surface = -1.30 Pressure coefficient for Zone A of walls
Total Pressure = -3.10
Pressure = -2.43 kN/m2
a) Walls
For long walls with D > b when wind is parallel to wall, the frictional drag coefficient is assumed to
act over all area of zone C of such walls.
The total frictional drag force has to be added to the total wind pressure in that direction
2) Wind End
D= 75.00 m
b= 12.00 m
Since D > b, Frictional Drag on walls applicable
Length of Zone C = 63.00 m D-b
Area of Drag ( As ) = 378.00 m2 (D-b)xH
Frictional Drag Coefficient ( Cf ) = 0.02 Surfaces with corrogations across the wind direction (Table 6)
Frictional Drag Force ( Pf ) = 4.47 kN qs Cf As Ca Eqn. 7a
b) Roof
For long roofs away from upwind edges, the frictional drag should be assumed to act over zone D
for flat roofs for all wind directions.
And over zone D for monopitch or duopitch roof and zone J for hipped roof only when wind is parallel to ridge.
1) Wind End
Length of zone D = 69.00 m L - bw / 2
Area of Drag ( As ) = 1725.00 m2 ( L - bw / 2 ) x W
Frictional Drag Coefficient ( Cf ) = 0.02 Surfaces with corrogations across the wind direction (Table 6)
Frictional Drag Force ( Pf ) = 20.42 kN qs Cf As Ca Eqn. 7a
Should be divided by 2 for load along each sidewall for bracing design.
For open buildings the external pressure remains the same as for an enclosed building
The internal pressure is as below,
0.85 Table 18
Internal Pressure Coefficients =
0.00
Date 26-Nov-07
Snow Loads Dsn. By ZAS
Chk. By SKK
BS 6399 Part 3; 1988 Rev. No. 0
A) Monoslope
Roof Slope = 0.50 : 10
2h / So = 2.00 -----( 1 )
2b3 / (ls1+ls2) = 3.00 -----( 2 )
E) Parapets
a) Case - 1
Dimension ( ho1 ) = 10 m
Dimension ( b1 ) = 15 m
Dimension ( b2 ) = 30 m
a) Case - 1
Dimension ( ho1 ) = 1 m
Dimension ( b1 ) = 15 m
Dimension ( b2 ) = 15 m
Dimension ( b3 ) = 45 m
Dimension ( ho1 ) = 2 m
Dimension ( b1 ) = 15 m
Dimension ( b2 ) = 15 m
c) Case - 3
Dimension ( ho1 ) = 2 m
Dimension ( b1 ) = 15 m
Dimension ( b2 ) = 15 m
b1 ho1
Dimension ( ho1 ) = 2 m
Dimension ( b1 ) = 15 m
Dimension ( b1 ) = 15 m
Dimension ( b2 ) = 25 m
Dimension ( h ) = 0.38 m tan ( a ) ls1 ls2 / ( ls1 + ls2 )
Length of Drift Snow ( ls1 ) = 7.50 m ls1 = b1 if b1 < 7.5 otherwise 7.5
Length of Drift Snow ( ls2 ) = 7.50 m ls2 = b2 if b2 < 7.5 otherwise 7.5
H) Obstructions on Roof
Length of Drift Snow ( ls1 ) = 1.00 m ls1 = b1 if b1 < 5 ho1 otherwise 5 ho1
I) Door Canopies
Length of Drift Snow ( ls1 ) = 2.00 m ls1 = b1 if b1 < 5 ho1 otherwise 5 ho1