For detailed wiring instructions, length allowances and addressing, refer to the following documents:

S7810M: 65-0249
S7999B: 65-0283
R7999A/B: 65-0238
ML7999A: 65-0239
UDC controls: http://hpsweb.honeywell.com/Cultures/en-US/Products/Instrumentation/controllers/default.htm
Modbus Master:

S7999B
Tip: Tip: Tip:
or
S7810M must be set for All Modbus compatible For the UDC boiler functions, settings
PLC
19.2K baud by devices must be wired and reserved modbus addresses by
removing the black pin/ in DAISY-CHAIN function, refer to page 64 of the
baud rate jumper. fashion to the S7999B S7999B1000 product data, 65-0283.
control. No branching S7999B
Tip: is allowed. NOTE: RS-485 terminals vary be model. System Display
Stand alone S7810M or Modbus Master
S7800A requires a S7999B
separate 13Vdc power System Display
COM1 COM2
UDC2500,
supply Local 3 4 5 8 9
UDC3200, 1 2 C b a
6 7
a b
+12 +12
UDC3500 g D- D+ D+ D-
Modbus Module COM1 COM2
To power
supply
S7810M RS-485 1 2
3 4 5
6 7
8 9
C b a a b
+12 +12
SHLD

RS-485 Modbus g D- D+ D+ D-
D+

D-

To power
1 2 3 6 7 8 supply
4 5
a b C C a b
D+
+13 Reset
D- g g D+ D-

Tip:
All RS-485 compatible devices including the R7999
1 2 3 1 2 3
c b a a b C
4 5 a b C ControLinks Control, S7830 Expanded Annunciator & the
D+
+13 Reset

g - + D- g D+ D- g S7800 Keyboard Display should be wired in DAISY-CHAIN


(RS-485) RS-485 RS-485 fashion to the S7810M Modbus Module.
Keyboard Display
ControLinks S7800A Expanded NOTE:
Control Annunciator If using a S7800A series 5 or greater in this application, it
RM78x0 S7830 CANNOT be used in Modbus mode; it communicates in
R7999A Relay Module
either modbus OR DDL protocol – not both at the same time.
S7999B Local #1 & #2 Set-up:
Config: Single boiler/burner system (Local Mode) S7999B Notes
Tip:
Within a Burner/ S7999B set-up for Modbus on COM2 can scan & recognize
COM 1: Connect to System Modbus network
Boiler Node, the all S7810M, RM78x0 R7999, S7800, S7830 & UDC2500/
Give each S7999B a unique modbus address S7810M and UDC 3200/3500 connected to it.
COM 2: Single boiler system (Local Mode) controls must have
different ModBus
EXCEPTION: In Switchable Mode, Modbus addressing is
May need to do a CPU reset for changes to take effect done manually. No duplicate addresses are allowed. Set
addresses. Within
the display, the S7810M modbus address switches 10'S & 1'S. All UDCs
S7810M Modbus Module UDC has reserved must be assigned to a Burner/Boiler Node modbus address
The S7810M support modbus RTU protocol with 1 start bit, modbus addresses via the UDC modbus address & the UDC function. System
by boiler function.
8 data bits, 1 stop bit, no parity Mode is NOT AVAILABLE on COM 1 when Switchable Mode
For proper communication with a modbus master, the S7810M is selected for COM 2.
must have software revision 5022 (US) or 6022 (Europe) or
greater.
R7999 S7800 S7830 Burner/Boiler
RM78x0 Node #1
The S7810M must be set for 19.2K baud (remove black pin/ UDC2500
baud rate jumper). UDC3200
UDC3500 S7810M Tip:
Each S7810M must have a unique COM1 S7999B S7800 requires a separate
678 123
modbus address. Local COM2 13Vdc power supply
#1
Modbus Master:

S7999B (COM1) RM78x0


R7999 S7800 S7830 Burner/Boiler
Node #2
or UDC2500
PLC UDC3200 UDC Controls
S7810M
S7999B UDC3500 UDCs must be set for 19.2k baud AND
Modbus Master COM1
Local
678 123 Modbus communication. Each UDC
S7999B set-up as a System Modbus master on COM2
#2 must have a unique address within each
COM1 can scan and recognize all S7810M, boiler node.
RM78x0 R7999, S7800 and S7830 connected
Remote control of UDCs are not allowed
to it as well as UDC2500/3200/3500 controls. Tip:
through the modbus master
A PLC or PC system modbus master requires Each S7999B S7810M Notes
must have its own S7810M accepts modbus function codes 3 & 4 for query & response
the S7999B system modbus interface power supply
addresses The S7810M is attached to the RM78x0 control and receives power
Remote reset or setpoint changes are NOT Tip: from it. The RM78x0 control generates the start polling bit for its RS-
S7999B only
allowed from the master through the slave 485 slaves.
accepts ModBus
S7999B display; they are read only. function code 3 The S7810M converts the RS-485 slave protocol from the R7999 to
S7999B Set-up for System Modbus Master: for query & modbus RTU protocol.
- COM 1: Connect to System Modbus network response from
Modbus Master A ControLinks modbus network CANNOT exist without the S7810M.
- COM 1: Program the modbus address
S7999B set-up:
Config: Selective boiler system (Switchable Mode) Tip:
Within a Burner/Boiler
COM 1: Not connected (Disabled) Node, the S7810M
COM 2: Selective boiler system (Switchable Mode) and UDC controls
must have different
Check box for Multiple Modbus Masters (share interface-9600 bps) ModBus addresses.
Within the display, the
UDC has reserved
Port Multiplier modbus addresses by
Miille MARC Multii-Port™ module #366-103-322-HW01 boiler function.
Miille Applied Research Company, Inc.
This is the only device Honeywell has tested for the dual master situation. R7999 S7800 S7830 Burner/Boiler
RM78x0 Node #1
The part number above has special software and a hardware
configuration for use with the S7999B1000. UDC2500
S7810M UDC3200 Tip:
Modbus S7800 requires a separate
678 123 UDC3500
Master 13Vdc power supply

Miille MARC
Multii-port module R7999 S7800 S7830 Burner/Boiler
S7999B #366-103-322-HW01 RM78x0
COM2 Node #2
UDC2500
S7810M UDC3200
Wiring 678 123 UDC3500
Wire Miille MARC to COM 2 of S7999B1000
Tips: Tips:
S7810M Modbus Module The baud rate jumper must REMAIN UDCs must be set for 9600 baud
in S7810Ms for 9600 baud AND Modbus communication
For proper communication, the S7810M must have
software revision 5022 (US) or 6022 (Europe) or greater. Each S7810M must have a unique Each UDC must have a unique
The black pin must remain in the S7810M for 9600 baud address address
rate. Notes
The S7810M is attached to the RM78x0 control and receives power
Each S7810M must have a unique modbus address. from it. The RM78x0 control generates the start polling bit for its RS-
485 slaves.
UDC Controls The S7810M converts the RS-485 slave protocol from the R7999 to
UDCs must be set for 9600 baud AND Modbus modbus RTU protocol.
communication. Each UDC must have a unique
address. A ControLinks modbus network CANNOT exist without the S7810M.
S7999B, S7810M, RM78xx, R7999, S7830, UDC
If communication is not occurring between the devices on the bus, check the following:
Verify proper S7999B setup (1234 Setup, Advanced Setup, User Preferences – Configuration, COM 1,
COM 2)
Perform a CPU reset after setting up the User Preferences for the changes to take effect.
The S7810M must be set for 19.2K baud (remove black pin/baud rate jumper).
S7810Ms on different burner/boiler nodes MUST have different modbus addresses.
When the S7810M is communicating, the amber MODE light on the front blinks rapidly, about once
per second.
Verify the communication polarity has been followed from device to device (Data +, Data -, C). Note
the UDC terminals vary by model. Also note the S7999B, S7810M, S7800, R7999 and S7830
designate Data + as terminal A and Data – as terminal B.
The wiring must be a daisy chain pattern from device to device to display – no branching allowed.
Communication may be interrupted if trying to attach 2 modbus masters to the bus.
Possible incompatible devices. If using an enhanced 7800 SERIES control (VPS, programmable post
purge), only certain series of S7800A and S7810M are compatible due to the longer message strings.
The S7800A1001 or S7800A1142 must be a series 5 or greater with a date code of 0620 or later. The
S7810M1003 must be a series 3 or greater with a date code of 0630 or newer.
The UDC must have the modbus card