Operator Panels
for i Series Controls
User's Manual
Warning
Warning notices are used in this publication to emphasize that hazardous voltages, currents,
temperatures, or other conditions that could cause personal injury exist in this equipment or
may be associated with its use.
In situations where inattention could cause either personal injury or damage to equipment, a
Warning notice is used.
Caution
Caution notices are used where equipment might be damaged if care is not taken.
Note
Notes merely call attention to information that is especially significant to understanding and
operating the equipment.
This document is based on information available at the time of its publication. While efforts
have been made to be accurate, the information contained herein does not purport to cover all
details or variations in hardware or software, nor to provide for every possible contingency in
connection with installation, operation, or maintenance. Features may be described herein
which are not present in all hardware and software systems. GE Fanuc Automation assumes
no obligation of notice to holders of this document with respect to changes subsequently made.
This manual provides the information required to attach a GE Fanuc Operator Panel to your
machine tool whenever a Series i CNC has been selected as the control unit. It provides
information on mounting and connecting the Operator Panel to the machine tool and interfacing
the I/O to the CNC. It may also be used to guide your selection of a suitable Operator Panel.
It is important to recognize that only the units discussed in this manual are totally compatible with
the Series i CNCs. GE Fanuc does offer additional Operator Panels (see GFK-0720A), but the
units discussed in that manual do not provide an MPG interface for the Series i CNCs. Conversely,
the MPG interface included in the Series i compatible units are not operable with other GE Fanuc
CNCs. Please refer to this manual for Operator Panels compatible with the Series i CNCs, and
refer to GFK-0720A when CNCs other than the Series i are involved.
Note
For Series i CNCs, it may be possible to connect the MPGs to multiple locations
within the machine tool. Select the location on the I/O Link closest to the CNC,
and connect all MPGs to that unit. This will be the only active MPG circuit.
Operator Panels
The following Operator Panels are available. All units communicate with the Series i CNC via the
I/O Link communication bus.
Convenient Control ON / Control OFF pushbuttons, which may be used to cycle 24Vdc
power to the CNC and other elements of the machine tool.
Optional 1 meter signal cable set for alternative mounting of Connection Unit.
Specification Numbers:
N 44A739025GO 1.
GFK-1478
...
111
Preface
“M” version used for machining centers. “T” version used for lathes.
0 CE Mark compliant.
q These units are physically similar to the Series 0 style Operator Panels.
“M” version used for machining centers. “T” version used for lathes.
If you have elected to interface an Operator Panel of your own design to the Series i CNC, you will
probably need to use one of the Connection Units listed below. If you do not use either of the first
two units, you will need to interface the MPG via an approved method. Connection Unit
documentation is available in the appropriate Connection Manual GFZ-63083EN (for Series
21i/2lOi) and GFZ-63003EN (for Series 16i/l8i/16Oi/MX).
Connection Units
The following Connection Units are available for the Series i CNCs. All units communicate with
the Series i CNC via the I/O Link communication bus. (Refer to the appropriate connection
manual for details.) Note that the MPG interface is operational only with Series i CNCs.
0 72156 I/O
0 48/32 I/O
Operator Panels for i Series Controls User’s Manual - December 1997 GFK-1478
Preface
0 48/32 I/O
Related Publications
GFK-1478 Preface
Contents
Renewal Parts.
North American Operator’s Panel [44A739025=GOl)
The North American Operator’s Panel for i Series CNCs has been designed so that end-users may easily re-
label the pushbuttons. Each pushbutton cap can be removed, and a new paper label can be inserted. Each
pushbutton is backlit with an incandescent bulb. LED kits are available.
The dimensions of the North American Operator’s Panel are 520 mm wide by 180 mm high by 90 mm
deep. If the Connection Unit bracket is removed, the depth is 50 mm. Panel devices project up to 25 mm
from the front of the panel.
The North American Operator’s Panel for i Series Controls is designed to be used with the 72/56 I/O
Connection Unit (see Section 3 of this manual). The Connection Unit (A20B-2002-0470) is ordered
separately. A mounting bracket for the Connection Unit is provided on the back of the Operator’s Panel.
The Operator Panel pushbuttons use 44 of the 56 matrixed type inputs. The rotary switches use 12 of the
16 discrete type 24V inputs. The remaining 12 outputs, 12 matrixed inputs, and 4 discrete 24VDC inputs
are available on connector PL2 for customer use. (See Sheet 2 of the connection diagram.)
All supplied panel devices are wired, except for the Emergency Stop pushbutton. For more information on
Emergency Stop wiring and signals, refer to the Hardware Connection Manual and Function Connection
Manual for the specific CNC control to be used.
The Operator’s Panel is to be connected to a 24-Volt DC power supply fused for a maximum of 8 amps. A
power cable set may be ordered (44C742962-601) to connect the system. It provides 1 meter of wire
between the panel and the power supply, 10 inches from the panel to the connection unit (the length
required when a mounting bracket is used), and 1 meter from the connection unit to the i Series Control.
ON and OFF pushbuttons are provided, switching a 24-Volt DC output for CNC and other machine
devices.
Ribbon cables are included to connect the Operator’s Panel to the connection unit when a mounting bracket
is used. If the mounting bracket is not used, a one-meter set of ribbon cables (44C739032-GOl) can be
ordered.
Item Description
I Control ON and OFF Pushbuttons 7 Provided. Panel can switch 24VDC @ 8 Amps to CNC and Operator Panel Connection Unit. 1
Override % Feedrate 0 - HO%, Binary Code.
% Spindle 50 - 120%, Binary Code.
% Traverse Min, 25%, 50%, 100%.
c
IsoIl
::I151
20 .12 0 18.64
FRONT VI EW
TOLERANCES PER ’
289A!xOAB h
259A5OOAC
The following cable part numbers are not automatically supplied with the GE Fanuc North American i Series
Operator Panel (44A739025GOP). Uzg pre-made cables can greatly expedite installation of the operator
panel. The optional Extended Length ribbon cables are required for mounting the Operator Panel
Connection Unit PCB up to I meter from the Operator Panel. 18Omm ribbon cables for standard mounting
of the Operator Panel Connection Unit PCB on the i Series Operator Panel chassis are provided as standard.
The following cables/cable sets can be ordered separately or specified as additional options when ordering an
i Series Operator Panel.
The following connector part numbers are listed for reference use only. Connectors required for
installation should be included with the hardware called out by GE Fanuc ordering instructions. Separate
connectors may be required for custom configurations or as renewal parts.
Note
The following diagram illustrated switched +24VDC to i Series CNC from the GE Fanuc North American i Series
Operator Panel.
GE Fanuc NA
Series i CNC
( Back View )
To CNC
h CPIA
GE Fanuc NA
Series i Operator Panel
( Back View )
Pin 3 - Open
Pin 1 - +24V SW
44C742962-005ROl
Operator Pane1
Operator Panel
Connection Unit
Printed Circuit Board
A20B-2002-0470
OPNDI
44A739613-GO1
24V SW / PLI -4
Power Cable Set for i Series ( Part No. 44C742962-GOlR02 ) includes three cables displayed above. All cables &
connectors in cable set are fully assembled.
CONNECTION UNIT
MOUNTING BRACKET y
50
-----
OFF
n -
I \ \
PL; PL4
I I PLl JPl
Pi.53 PL54
BLOCK DIAGRAM
I/O UNIT
&P CNC
-a-
TRAV
OVRD
SW JDlA [
MFO
SW CPlA [ C
0
sG
I TO PUSHBUl-fONS
24VDC POWER SUPPLY
WlTH SAME KCM t
: _- CUSTOMER SUPPUED
I FUSE FOR 8 AMPS.
0 JP#
Pu l
I I
PL4 CJ ***
I PL30
I
i-J
Ht m---v-----
I I
PLl - 24VDC SWITCHED
IID +24VDC LED
I PUSHBUTTON I u A (IF INCANDESCENT,
mACTs NOT USED)
I I
CPDl CPDl JDlB JDlA r-q
LNDlCATOR
I LIGHTS I MO (OUT)
1
I
OPNDl
PL54 0 I a_
pL53
IFClJlT BOARD 1
-ev
1
II 111
CE54
CE53
JA3
~~!, ‘12-”
>>
CIRCUIT TO
ADD LIGHT
**
TO OTHER
RESISTORS
pL2-xx
<< v >>
TO OUlPUT DRMR
PL!sxx
MACHINE
op~!ET:R’s I CONNECTION
UNIT (MATRIX)
hii
44C742964
2 3
L
446742964
WIRINGDETAILSFOR PUSHBUTTONS
DETAILSTO ADDMATRIXDEVICES.
CONTACTS TO BE 5V, LAMPS TO BE 24V
CUNTACTS LAMPS
ADDITIONAL CONTACT 2PL MATRIX LAMP 2PL
SW7 MPG Xn+4,6 53-A23/53-A22 KCMl/KYD6 Yn+0,6 53-Al0 DEVICE ADDRESS CilNNECTIllNS REFERENCE ADDRESS CCJNNECTIUNS
SW8 ~IIIME Xnt4.7 53-A23/53-B22 KCMl/KYD7 Yn+0,7 53-B10
SW45 Xn+8,4 PL2-BOl/B04 KCM5/KYD4 Yn+5,4 PL2-A01
SW46 Xnt8.5 PL2-BOl/B05 KCMVKYDS Yn+5,5 PL2-A08
SW47 Xnt8.6 PL2-BOl/B06 KCMS/KY
D6 Ynt5.6 PL2-A09
SW48 Xnt8.7 PL2-BOl/B07 KCMS/KYD7 Ynt5.7 PL2-A05
SW49 Xn+9,4 PL2-B02/B08 KCM6/KYD4 Yn+63 PL2-A02
SW50 Xn+9,5 PL2-B02/B09 KCM6/KYDSYn+6J PL2-A06
SW51 Xn+9,6 PL2-B02/B10 KCM6/KYD6 Yn+6,2 ?L2-Al0
SW52 Xn+9,7 PL2-B02/Bll KCM6/KYD7Yn+6,3 PL2-All
SW53 Xn+10,4 PL2-B03/B12 KCM7/KYD4Yn+6,4 PL2-Al2
SW54 Xnt10.5 PL2-BO3/B13 KCM‘I/KYDSYn+6,5 PL2-A13 4
f [.cNC.~P-PNL] a44C742964
-4
) C742964C 1.00
I zc
--I 3 4
CONNECTORS
pin 1 mark,
SWfTCHES WITH
INHIBIT BIT
&[ ny,;y;j
JPl
PL4 PL3 PLl PL54 PL53
--_.I
SZEC -lo
44C742964 5 0
PARTNumER -fEwsoNs
VERSON StAnxs t
i
I I II I
ROTARY SWITCHES
WITH INHIBIT BITS ON & OFF CONNECTION
OFF ON
I
FEEDXRATE
O;K$!!C&E
(G) b BIT>}
INHWT PL2-A18 PL53-A05
SPIfiDLE
SPEED
OVERRIDE TO CNC & l/O
SWiTCH
OPNDl PWB
E-STOP
REFER TO CONNECTION
e> MANkkJ$t!t,:N;Top
E-STOP CONNECTION
L
94 lllv
6 44C742964 6 1
0 0 0 0-
t t
6.30 6.69
CUTOUT
M3 QlY. (8) I
4 MM DIA. (8)
OVERALL DIMENSIONS OF
520 MM OPERATOR PANEL
L
Availability of Sample Operator Panel Ladder Logic
To integrate this Operator Panel with the i Series CNC, Programmable Machine Control (PMC) ladder
logic must be developed by the machine tool builder or system integrator. GE Fanuc Automation can
provide examples of operator panel ladder logic to assist in the development effort.
Examples are available to illustrate common ladder interface methodology and help reduce the overall
design effort. GE Fanuc Automation makes no representation that examples will provide full functionality
for every application. It is the responsibility of the machine tool builder to properly develop and test the
machine tool’s ladder interface for the desired application.
For more information, please contact your local GE Fanuc Automation representative.
Renewal Parts
The following parts are contained within the GE Fanuc North American i Series Operator Panel
(44A739025601). The part numbers listed here are for Renewal Parts ordering convenience only. They
do not need to be ordered separately when ordering a new i Series Operator Panel.
44A717186-008
Section 2:
Dispersion I/O Type Operator Panel
MPG needs a DC5V power supply and the voltage must be less than 0.2V dropping.
(the 0.2V dropping includes the resistance in the cable.)
3
LI - = 76.75(m)
0.0394
If the customer will use a some other vender’s MPG ,not FANUC’s MPG, the electrical
condition must be as follows.
HAn. HBn signals form MPG and CNC internal pulse are as follows. A cycle of the HAlHB
pulse T1 must be more than 200 iu set and 4/T1 must be more than 50 p sec.
1 i
I
f i b
!_
T i i
Tl‘-4
J 1
HAn f 1
T1 i t
;
-7-L I iI t
4 I f 1
HBn
4
LL
in the direction of +
in the direction of - I
Normal wheel f I Reverse whee I
L
f!
I Reverse whee I
Cl ick
point
TITLE
Dispersion I/O Type Operator’s Panel
Connection Manual
DRAW. NO. CUST.
A-73167E/OZ
SHEET
EDIT. DATE DES I G. DESCRIPTION FANUC LTD 0121
1
And the receiver circuit is as follows.
m---c -_----m-m---
i r
I 1 I
+sv Fi lter i
I 1 1 I
i 1 I i
;~/{_i;;:-
A- I I circuit I
_L i
ov ’ I ov
’ I 1
1 L ~~~~~------~-~~ -- J
This terminals are used to relay the signal on the operator’s panel. These signals are not output
to CNC with 110 Link. Following example is transit of ON/OFF control signal for power supply.
-.-.-.-.-.-.-.-. Oeerator’sqanel
.-.-. .-.-.-.-.-.-.-.-.-. 1
i Input unit
CN2 PCB CM58 i
ON switch i
; TRI TRI i
- 1 ‘Al5 i
i i
i
OFF switch a TRZ B,S TR2 i
’ 2 . i
I i I i
i
; TR3 3 A,6 TR3 i
1
i
i
i_._._.-.-._.-.-.-.-.-._.-.-.-.-.-.-.-._._._*
TITLE
Dispersion l/O Type Operator’s Panel
Connection Manual
CUST.
DRAW’
No*A - 7 3 1 6 7 E / 0 2
SHEET
EDIT. DATE DESiG. DESCRIPTION FANUC LTD 0131
I
4. DI/DO address
4.1 Keyboard
Xm+4Nn F3 _ F2 Fl Dl Cl 61 Al
Xm+SNn+l F4 02 c2 B2 A2
Xm+6Nn+2 04 D3 c4 c3 B4 B3 A4 A3
Xm+7Nn+3 F6 F5 D5 c5 B5 A5
Xm+8Nn+4 F8 D6 C6 B6 A6
Xm+9Nn+5 08 C8 68 A8 A7
Xm+l ONn+6 F9 D9 c9 B9 A9
Xm+llNn+7 FIO D10 Cl0 BIO Al0
Keyswitches/LED position
, 9
* l!!zlUD l!!IKzlleruu~m
TITLE
Dispersion I/O Type Operator’s Panel
Connection Manual
DRAW. NO. CUST.
A-73167E/02
SHEET
EDIT. DATE DES I G. DESCRIPTION FANUC LTD 014/
I
(In case of fullkey type operator’s panel)
DVDO address of Keyswitches and LED on the keyboard are as follows.
Xm+rllYn Fl Cl Al F6 D6 C6 B6 A6
Xm+SNn+l c2 A2 F7 c7 A7
Xm+6Nn+2 F3 C3 A3 F8 D8 C8 88 A8
Xm+7Nn+3 F5 F9 D9 c9 B9 A9
Xm+8Nn+4 02 C5 A5 FlO DIO Cl0 810 Al0
Xm+9Nn+5 D4 B2 Fll Dll Cl1 Bll All
Xm+l ONn+6 04 Fl2 012 Cl2 812 Al2
Xm+l lNn+7 F13 013 Cl3 B13 Al3
Keyswitches/LED position
B rl rl rzl rzlUUprUU
D PI rzl rl IzxzlUUUU
; PI PI rlrlrl I!zlUUDUU
4
Address - I 2 3 4 5 6 7 8 9 10 11 12 13
TITLE
Dispersion I/O Type Operator’s Panel
Connection Manual
DRAW. NO. CUST.
A-73167E/02
SHEET
EDIT. DATE DESlG. DESCRIPTION FANUC LTD 015/
I
a
5. EN/DO mapping
I/O address map is as follows.
t DI map DO map
Xm Override etc. Yn
Xm+l Yn+l
Xm+2 Normal DI Yn+2
Xm+3 Yn+3 Keyboard
Xm+4 Yn+4 (LED)
Xm+5 Yn+5
Xm+6 Yn+6
Xm+7 Keyboard Yn+7
Xm+8 (Keyswitches)
Xm+9
Xm+lO
Xm+ll
Xm+12 (1st MPG)
Xm+l3 (2nd MPG) MPG
Xm+l4 (3rd MPG)
Xm+l5 Resen/e
TITLE
I Dispersion I10 Type Operator’s Panel
Connection Manual
CUST.
DRAW*
No’A - 7 3 1 6 7 E / 0 2
SHEET
EDIT. DATE DES i G. DESCRIPTION FANUC LTD 016/
I
01 mapping should be assigned 1 group = 16 byte mapping and DO mapping should be assigned
1 group = 8 byte mapping. The reason is as follows.
MPG interface(the counter for MPG) uses Xm+lZ-Xm+14 area and it is fixed. And if MPG
interface will be used, Xm+12-Xm+l4 area must be assigned. therefore, in case of i series and
using MPG interface, DI mapping must be assigned 16 byte mapping. MPG counter area are
directly
processed by CNC software. So you must not use this area by customer ladder.
It is possible to assign any address for this operator’s panel. But in Dl address, each CNC have
some fixed address that is directly processed by CNC software. So, as refer to the following
mentionassign the DI mapping.
lx001
0 I
lx001
1 I
.....................
f - -ii ias& i$-Gipping start from X00&; ---*------:
Keybosrd
i * DECn#l and * DECn#2 singals which are i
(Keyswitches) i address fixed signals can be used any time. I
: And * ESP signal can be placed at +24V 1
.1
! common fixed address. *1
II
i But SKIP signals can not be used.
:1 Don’t map the * ESP signal matrix DI area. !
1X0018 (1st MPG) I II II
. . . . . . . . . ..I....... . . . . . . . ..I....... . . . . ..I........
IX0019 (2nd MPG) 1 MPG
X0020 (3rd MPG) 1
x002 1 Reserve
TITLE
Dispersion l/O Type Operator’s Panel
Connection Manual
I I I I DRAW’
No*A - 7 3 1 6 7 E / 0 2
I
I
CUST.
SHEET
EDIT. DATE DES I G. DESCRIPTION FANUC LTD 0171
6. Outline In case of small type operator’s panel
164 I
.
_33z-
01 +-
r -- - -------_
c J
c
CD
. @
[rnl~l -- I
081
TITLE
Dispersion 110 Type Operator’s Panel
Connection Manual
I DRAW. NO.
A-73167E/‘OZ
EDIT.
I
DATE
I
DES I G.
I
DESCRIPTION
I FANUC LTD I
SHEET
018/
Y
TITLE
Dispersion I/O Type Operator’s Panel
Connection Manual
DRAW. NO. CUST.
A-73167E/02
SHEET
EDIT. DATE DESIG. DESCRIPTION FANUC LTD 019/
I
a
7. Specification
7.1 Environmental Requirement
9
Temperature At operation o”c+80c
around a unit Storing or transporting -20°C --60°C
Temperature Max. l.l”C/min
variance
Humidity Normally 75% or less (Relative humidity)
Short time(Within one month) 95% or less (Relative humidity)
Vibration Operating 0.5G or less
Atmosphere Normal FA atmosphere(Consult us when using the system under
environments with higher degree of dust, coolant, or organic solution.)
7.3 Operator’s
. panel specification
Item Specification Note
Normal DI points 24 points 24V type input
Keyswitches 42 keys : T type Sheetkey type, Matrix Dl
46 keys : M type
LED Color : Red Attached to all keyswitches,Matrix DO
Override rotary switch 5 bit Gray code output
Emergency stop awitch 1 bit
Program protect key 1 bit
MPG interface Max. 3 units i series is only available.
Interface to CNC FANUC 110Link Max. 16 modules or total points max.
connection 102411024 will be available.
TITLE
Dispersion I/O Type Operator’s Panel
Connection Manual
CUST.
DRAW-
No’A - 7 3 1 6 7 E / 0 2
SHEET
EDIT. DATE DESIG. DESCRIPTION FANUC LTD 020/
I
74. Power supply specification 7
Voltage Capacity Note
DC24Vt 10% (from Power connector CPDI, Including all DI consumption
including momentary values) 0.4A
TITLE
Dispersion l/O Type Operator’s Panel
Connection Manual
CUST.
DRAW-
“’ A - 7 3 1 6 7 E / 0 2
SHEET
EDIT. DATE DES I G. DESCRIPTION FANUC LTD 0211
I
8. Others
The keyboard of this operator’s panel is a matrix composition. When three or more keys are pushed,
the bypass current cause unrelated key to be available. This malfunction can be prevented with ladder
When three keyinputs or more is input, all the keyinput since the third is made invalid.
However, when the number of all keyinput becomes two or less because keyinput was lost, all
keyinputs are made effective.
TITLE
Dispersion 110 Type Operator’s Panel
Connection Manual
1
SHEET
EDIT. DATE DES I G. DESCRIPTION
FANUC LTD 0221
[l] The number of datalines where the keyinput exists is examined.
Logical add Rl of the data of all addresses is calculated. The number of bits which are “I” in the 8bits
(1) When the data of RI is corresponding to OOh, there is no bit which is “1” in the data of Rl.
(2) when the data of Rl is corresponding to the data in undermentioned datatablel., the number
of bits which are “I” in the data of RI is one. Similarly, when the data of Rl is corresponding to
G
the data in datatablez., the number of bits which are “1” in the data of Rl is two.
Ex. State (b) or (c) : RI = (00000100) - There is one dataline where input exists.
Ex. State (d) or (e) : Rl = (00010100) - There are two datalines where input exists.
(3) If the data of Rl is not corresponding to OOhand the both datatables, the number of bits which
are “I” in the data of RI is three or more.
Ex. State (f) : RI = (00110100) - There are three datalines where input exists.
[2] Judgment 1
(1) If there is no dataline where the keyinput exists.
- Any key switch is not pushed. : Ex. State (a)
(2) When the keyinput exists in two datalines or less.
- To [3]
(3) When the keyinput exists in three data lines or more.
- There are three keyinputs or more. It is invalid keyinput. : Ex. State (f)
TITLE
1 Dispersion l/O Type Operator’s Panel
Connection Manual
CUST.
OR*‘.No’ A - 7 3 1 6 7 E / 0 2
SHEET
EDIT. DATE DES I G. DESCRIPTION FANUC LTD 0231
I
.
[3] When the keyinput exists in two datalines or less, it is examined whether two or more keyinput
exists on the same dataline.
The data of all addresses is subtracted from logical add Rl and subtraction result R2 is obtained.
There are no two or more keyinput on the same dataline if it is R2=00h.
Ex. When there is one dataline where input exists.
State (b) : R2 = FCh
State (c) : R2 = F8h
When there are two datalines where input exists.
State (d) : R2 = OOh
State (e) : R2 = FCh
[4] Judgment 2
(I) In case of R2 =OOh - There are two or less datalines where input exists, and there are no
two or more keyinputs on the same dataline. In this case, the
numbers of all keyinputs are one or two. It is effective keyinput.
: Ex. State (d)
(2) In case of R2#00h - There are two or less datalines where input exists, and two or
more keyinputs exists on the same dataline. To [5].
[5] Judgment 3
When there is one dataline where input exists - To [6].
When there are two datalines where input exists - There are three keyinputs or more.
It is invalid keyinput. : Ex. State (e)
[6] Subtraction result R2 is added to logical add RI. If this addition result is OOh,the number of all
keyinputs is two. Ex. State (b) : RI + R2 = 04h + FCh = OOh
State (c) : Rl + R2 = 04h + F8h = FCh
[7]Judgment 4
In case of RI + R2 = OOh - There is one dataline where input exists, and there are two keyinputs
on this dataline.That is, because the numbers of all input are two keys,
it is effective input. : Ex. State (b)
In case of Rl+R2 # OOh - There are three keyinputs or more on the same dataline.
It is invalid keyinput. : Ex. State (c)
[8] Only when the keyinput becomes effective because of judgment l-4, all DI data (Xm+4-Xm+l l) is
used by the ladder program.
TITLE
Dispersion I/O Type Operator’s Panel
Connection Manual
DRAW. NO. CUST.
A--73167E/02
SHEET
EDIT. DATE DESK DESCRIPTION FANUC LTD 024/24
I
’ LOS-SiZO6ELVPP
pued Joqerado saps ? ueqmu~
YWN anuej 39 W$ W!M an JO4
Apgeredas parapro aq qsnur pued s!yl
paxaldglnlu
n ale s)ndul
gun uo!)~auuo~ pued ro$erado JOJgO/366k CL-~ ‘ON fki!MeJa l
:su!equo3 uo!gaas s!yl
I/O Module for Operator’s Panel
Connection Manual
-Item-
2. Each connections
2.1 I/O-Link Connection _ -
2.2 Power supply connection
2.3 DVDO Connector pin assignment
2.4 DI(Normaf input signal) Connection
2.5 Di(Matix input signal) Connection
2.6 DO(Output signal) Connection
2.7 Manual PukeGenerator Connection
3. Module outline
4. Specification
4.1 Environment requirement
4.2 Order specification
4.3 Module specification
4.4 Power supply specification I
4.5 Dl(lnput signal definition)
4.6 DO(Output signal definition)
5. Other notices
5.1 DO signal action when system alarm is happened
5.2 DVDO mapping
5.3 DO action when the DO Power (DOCOM) ON/OFF
5.4 Parallel connection of 00 signals
5.5 Alarm detection of DO signa!s
I
i
03 1 96.11.1 Jinnai Page 016 is modified. w TITLE
L A 1/O Module for Operator’s Panel
02 96.10.15 Jinnai Page 003 i s modif ied. Connection Manual
3
DRAX50.
01 96.8. 3 Jinnai PN& A-71 f 996/03 CW-
1 , I
I/‘0 UNIT
I---@JDlI3
l/O LINK
JDlA
CE53
JA3
CE54
Note) i series CNC is only possible to use the MPG interface on this l/O module.
If i series CNC uses some I/O unit having MPG interface (ex Dispersion type ii0 module for
panel) and this I/O module, the MPG interface nearest the CNC is only available
on the I/O-Link connection.
1 Diur-H0.A-71 199E/02
EDIT.
I DAlE DESK.
I
DESCRlPTlcN
I FANUC LTD IsHfET 002,’
.
2. Each connections
2.1 I/O-Link Connection
Refer to each CNC connectjon Manual, afl I/O-Link connection methods are in common.
But it is not possible to use the below cbnnectors which will be used for the main board
of the i Series.
Not avaimbie connectors for the I/O Modufe for Operator’s Panel
Specification JMaker
Connector Housing Fi-200CV7 IHROSE
Connector Housing and Fl30-ZOS-CV7 fllROSE
IConnector I -1
CPDl (INI
24V power
CPDl (OUT)
24V power
Note) Both connectors CPDl (IN) and CPDl(OUT) are same speMcation. And tfrere is not
indication of (IN) and (OUT) on the PCB.
Note) Power supply for the 110 module must not turn off at operation. If +24V is turned off at
operation, CNC happen to get system alarm(CommunicatM alamr between CNC and l/O
module). +24V for I/O module must be supplied before or same time CNC power on.
And +24V for I/O module must be turned off after or same- CNC power off.
CE53 CES4
1
II A I 8 i
I 02 I N. C. 1 +24V 1
i 03 I -xlaco.o I xwo.1 I ! 03 i htd.0 i ml?+l_f i
--i-
IO41 xmo.2 I xh4.3 f I 04 i Xml.2 i xfwl.3 f
IO5 I xJw.4 I xllPo.5 I
tO6i xmto.6 i X&.7 1
I 07 T YrPo.0-1 Yn4.1 1 i 07 : Yn+3.0 i Yn+3.1 i
t 08 i Yn+3.2 I Yrw3.3 I
I09 i ~d.4 I ~~4.5 i i 09 I Yn+3.4 1 Yn+3_5 I
I10 1 Y&.6 t Yn4.7 ! i 10 i Yw3.6 i ym3.1 1
11 1 Yn+l.O 1 Yr?+l.l 1 Ywt.0 Yfw4.0
12 1 Yn+l.2 I Ywl.3 I YIw4.2 Ywa.3
rirm.4 I Y~+I.S i i 13 i Yn+4.4 1 Ywa.5 I
I 14T_ Yn+l.i I Yrwl.7 I I 14 I Yn+4.6 I Yw4.7 I
15 I Yn+Z.O 1 Yfw2.1 i ’ 15 : Yn+5.0 1 Yn+5.I 1
16! Yw2.2 1 Y&.3 , 16 I Yn+5.2 1 Yrw5.3 j
117 f Yn+2.4 1 Yn+2.5
78 1 Yw2.6 1 Yw2.7
191 KYDO Km
201 KYD2 KYD3 I
211 KYD4 1 KYDS
221 KYD6 Km ;
23 ( KCYI Km !
24 I KCU3 1 KCM4 i
t251 DOCOM I OocoY I
I I
1
I
I
I
I
*wo”A-71199E,‘02 IcusT.
1
Pin No.
; CE53(802)
+24V
-i- + CE54(802)
d CE53(B05)
I
XmO.6 1 -I A CE53(A06)
,Rd 4
f+vd
& CE53@06)
~~7----“;RV] i 7 ,
CE54(A03)
CE54@03)
CE54tAO41
CoMl 1 b CE54(A02)
1
J
ir CE53WIlL @If),
CE54(hOI>.!BOl)
--r---T
t t -I--
t l m--A-71 199E/02 / as’.
I
Note) Xm+l .O-Xm+l.7 have a commcn . line which is possible to select the source/sink tvpe.
4
If COMl(CEWA02pin) is connected to +24V, the DI signal logic is negative.
But in this connection, if the 01 signal wires happen to drop the ground levef, the status of
the Df signal is same as the 01 signal is ‘ON”. From the safety viewpoint, COMl
(CE54AOZpin) shouid be connected OV.
Note From the safety viewpoint, Emergency Stop signal must be assigned on the address
Xm+O.O-Xrw0.7. As refer to the 5.2 DVDO mapping, ass@n the Emergency stop 01.
Note Xm+O.O-Xm+0.7 common line are fixed. So, if these 01 pins in this address open, the status
of these one stay ‘0”. And in case of Xm+l .O-Xm+? .7wbch have a selectable common
line,
if tie COW (CESbAO2pin) is connected to OV and these 01 pins open, the status of these
one stay ‘0”. And if tie COMl(CE54-A02pin) is connedeb to +24V and these DI pins open,
the status of these one stay T. And if the COMl(CE54402pin) is not connected to OV or
+24V and these 01 pins open, the status of these one don’t care.
~w-RA-71199E/02_ ~JS
I
EDITa 1 DATE 1 DESK. DESCRlPff
ON FANUC LTD iwT 006 ’
I
I -0 _x-. -:.:-* ‘Jr ,‘a.: - 1..
*KCWl
*KM2
*KCM3
*KCM4
*KCfdS
IrcKCMG
HcM7
,CE53(820)
I I i
i
i
i
I
i I:
,CE53(A21)
J 1 iI
,CE53(B21) 1 i
/ \ I
j
,CE53W2) ]
i
I
> CE53(B22) Ib
Note)Insert diode for preventing short cut current in all part oftheswitchesas refer to the below
figure. Ifthe customer circuit does not have these diodes, you can not input more thantwo
closedswMes. Ifyou input 3 or more closed switches, DI data may not be correct.
I I I Imu’ m-A-7119QE/02
SHEET
1 afsT*
056 points
I-Pin No.
CE53M25,825)
OOCOM
7 $E54(A25. 824.
-Address f I 1
i 1
I
I
I ! I 1 +24V OV : j
24V Power
I I
I I
’I I ! j
I
1
j $
I
1
1
Yrko
.0
,
CE53(A07)LT
: Relay *
’
I
/ iDV; j I
i
I
Yn+o. 1 mi-+ &53(807)
I
i YmO.2
j or+ &CE53 (A081
i
Yti.3 ,~p--f p53(~08)
I
j
I I
Yn+o. 4
I I
f
i
,,
i
I
i
I
CE53(All) 1
!
CE53(Bll)
i!
I 7+ rCE53 (AOl,BOl)
I 1CE54(AOl,BOl)
(AO7)
(807) j
(A081
@08) I
I
(A091 i
(BO9)
(A101
Yrw3.7 ACE54 (BlO)
I
n+ ~CE53(AOl,BOl)
1CE54(A01,507)
7Pin No.
CE53M25.825)
4 /
Address : '
I
S
I
I Bit
I
I
1 i
1 1-a-f
I,
Yn+4.1 [ t CE54 (Bll)
DV/ t 3
II r--Bit I
i
I
i i i
’ 1
I
I L
v
!
I
Yn+6.1 f---- CE54(819)
m/J 7
Yn+6.2 [F-+ CE54(A20)
I
I
I Y~6.5 1 CE54@21)
:I Ytw6.6 _I CE54w2l
\
!
I
i A
i r
77//
v
m
I CE53(AOl.B01)
.CE54(AOl.
BOl)
rr&&j
Wiring
Terminal ManuaI Pulse Generator
r ------- 7 f .. am.
It i t
HA1 ! ?RD A
Hm :’ ;7”H -L%:,
$ !+$g 1 +%I
I
ot’
I - 1
*J3 dR0 t\ I
i#32h;8 if;; 11 ;
+!w
1
9v i’l ;3 8K I
&s :OBK A I
3 WH / \ 1
m3i6 s L
1
,
+5v ;z I
OVb : 1 6K I
I
T-Shield -’
GND
Cable Jifing I
I i
Note) Cakuiate the MPG cable max. length as refer to the foibwing calculation.
MPG needs a DC5V power supply and the voltage must be less than 0.2V dropping.
(the 0.2V dropping Mudes the resistance in the cable.)
3
L s - = 76.75(m)
0.0394
HAn. HBn signak form MPG and CNC internal pulse are as f&lows. A cycle of the WA-tB
pulse T, must be more than 200 p set and 4/T, must be more than 50 p sec.
in the direction of +
in the direction of -
Reverse whee I
Reverse wheel
Cl ick
point
I t
IOK Q
R
A
-L I
1 circuit
_L
I
i
ov I
I uv I
i
1
I
‘W I/O Module for Operator’s Panel
Connection Manual
SHEET
EDIT. DATE DESK DEScRlPTlON FANUC LTD ow
3. Module outline
4&
lf3
SHEET
UESCftlPTlOlU
I FANUC LTD I 015!
4. Specification
41. Environmental Requirement
9
_. Temperature ‘At operation 0°C - 5%58”C
.
@ m St&g or transporting -2O”C-60°C
around a unit
/Temperature I
Max 1.1 “C/min -
.variance 1’
Humidity Normally 75% or tess (Relative humidity)
Short time(VVlthin one month) 95% or less (Relative humidity)
1
Vibration Operating OSG or tess I
Atmosphere Normai FA atmosphere(Consuit us when us@ the system under environments
with higher degree of dust, coolant, or organicsolution.)
I
Other condition (1) Use the I/O module in a cabinets that is &ways completely closed.
0 c +eceF
I
ffnPGinterface
I
/Max. 3 units
available.
Ii series is onlv available.
I
1
TITLE
I t/O Module for Operator’s Panel
I
Connection Manual
1
XAW. IYE CUST.
96. 11. 1 Jinnai Dparts are modified. A-71 1996/03
45. Dl(lnput signal definition)
TITLE
f/O Module for Operator’s Panel
Connection Manual
DI map DO map
1 xm otmal input
Yn I
xm+l Yn+l
XIII+2 YrW2 I
J Reserve
Yn+3 output
xm+3 1
Yn+4 1 signal
Yn+5 I
Yn+6
Yn+7 Reserve
01 mapping should be assigned 1 group, 16 byte mapping and DO mapping should be assigned
1 group, 8 byte mapping. The reason is as folfows.
MPG interfke(the counter for MPG) uses Xm+lZ+m+14 acea and it fixes. And if MPG
interface
will be used, Xm+l2-Xm+14 area must be assigned. And incase of i series and using MPG
intelface, DI mapping must be assigned 16 byte mapping- MPG counter area are directly
processed by CNC saftware. So you must not use the area by customer ladder.
There are DO afarm(over current. over heat) indication area in Xm+lS. (Refer to the
5.5 DO(Output detection of DO signafs) Also this area fixes in Xm+l5. And if tiis area wiil be
USed,
this area must be assigned. So in case of using this area, 01 mapping must be assigned 16 byte
mapping.
Direly
l
processed a ress by CNC(in case of FS18,16)
I 7 1 l6 5 4 I 3 2
8
ESKIP -----MLB---1fL
SKIP#I 1-B-W-- -IYIIT2~1 +W2#1 1 -MT141 4ITlt3
--~~L~~~~~-
x0004 SKIPW SKfPfi#t SKIP4#H SKW3#1 SKIP2#$T
SKlPlfl ESKiP I SKIPSit
-M-w-- i SKIP&l SKJFW LB----
zAE#l c
SK JP6#1 SKI P2fsl
X0005 I I I
X0006
xooo7 I 1 4EC7#2 4lEC6#2 1 4EC5#2 1 4EW2 1 rOEC3$2 *OEC2#t21 +OECI#2
X0008 I *sP I I I 4
xm9 I #EC7#1 40EC6#1 [ 4IEC5#1 4IECISI 4IEWl *EC281 1 +DECl#l
x0010 1 I 1 i
I
x0011
I x0012 I I 7
1 SKlP#B SKlPM2 -MIT2#2 L+W2t2
--~~~~ ~~~~~ - -MiTl~2 +MTt$#Z
~--~----~-Ir--~~~- zAE#2 xAEP2
W-W-W
x0013 SKIP5#2 1 SKIP4#!2 1 SKIQ3s2 SKIP2#2 SKfP8!$2 SKIP7#2 .
SKIP#2 SKIP6#2 SKlPS#2 SKIP4##2 SKI= zAE#2 YAE#2
I)~~--~LI-~----~---~ XAE$2
SKI P2#2 SK t P8$2
SK I P7#2
#I means the signales in 1st path. #2 means the signals in 2nd path. And up column means the
T series signals and down columnmeans the M series signals.
’ TITLE
l/O Module for Operator’s Panel
Connection Manual
SHEET
EDIT. DATE DESK OESCFIIPTION FANUC L-I-D 019;
(5.2 U/DO mapping cmtinueing)
L
x001 0
x001 1
1 Reserve
I
I x0015 I ~.I.-....~~.*......*~~~~...~.~ .---.--.es
1 X0016 I h case of mapping form X0008, SKIPs&&~~&b~~"~ .
I x0017 I &ed, but lDECn#l singaies which are address
1 X0018 I .tied signales can be used any time.
I x0019 I Reserve 1 !And ‘ESP signal can be placed at +24V common fixed :.
$ddress.(Don? map the lESP signal matrix DI area.)
.
, .
IncasetbatDO is W
ON in a sequence OFF
Incasethat DO is ON
OFF in a sequence OFF
Note) In case that DO is ON in a sequence, DO signal output same as DOCOM state like
in a doted line in the figure.
I I I I mu. Ho.
A-71 199E/O2 1 (xLsT-
SHEET
EDIT. I DATE I DEW. I
DESCRlPflON
I FANUC LTD I 020;
5.4 Parallel connection of DO signals
ifDO signals are connected in parallel like a figure
and mntro&led same ON/OFF timing in the
ladder, that DO shall be output max. 4UOmA(twice a normal load). But remind that ieakage
current when driver is OFF is max. 40 fl A(twice a normal leakage current).
I !
I4
I
,I I
I i
t
I I
1 / CB150(01). (33) i
Do+
(, i
- 1 iqj
1
iI
t
,
I
i
I
I l
-ttem-
2. Each connections
2.7 I/O-Link Connection
2.2 Power supply connection
2.3 DVDO Connector pin assignment
2.4 Dl(lnput signal) Connection
2.5 DO(Output signal) Connection
2.6 Manual Pulse Generator Connection
3. Module outline
4. Specification
4.1 Environment requirement
4.2 Order specification
4.3 Module specification
4.4 Power supply specification
4.5 Dl(lnput signal definition)
4.6 DO(Output signal definition)
5. Other notices
5.1 DO signal action when system alarm is happened
5.2 DUD0 mapping
5.3 DO action when the DO Power (DOCOM) ON/OFF
5.4 Parallel connection of DO signals
5.5 Alarm detection of DO signals
T 42
TITLE
48/ypoints I/O Module
Connection Manual
DRAW. NO. CUST.
01 96.12.2 Jinnai A-73233E/Ol
W
SHEET
EDIT. DATE DESI G. DESCR
I PTI DN -FNUUc Lx0 001/20
1. Total Connection diagram
CNC
r
1,/O UNIT
4
-
-
-
-< JM --
MPG r ‘<
\
g
z03 I
MPG
. 3 g
r3
. b i/?”
MPG1 ’ 2
2
+24V Power
+24V Power
Note) i series CNC is only possible to use the MPG interface on this I/O module.
If i series CNC uses some I/O unit having MPG interface (ex. Dispersional type I/O module
for Operator’s panel) and this I10 module, the MPG interface nearest the CNC is only
available
on the I/O-Link connection.
TITLE
1 48/32 points l/O Module
Connection Manual
DRAW. NO. CUST.
A-73233E/Ol
SHEET
EDIT. DATE DESIG. DESCRIPTION +ANlx- LTD 002/
I
2. Each connections
2.1 I/O-Link Connection
Refer to each CNC connection Manual, all l/O-Link connection methods are in common.
But it is not possible to use the below connectors which willbe used forthe main board
of the i Series.
C P D 1 (IN)
C PD 1 (OUT)
Note) Both connectors CPDl(IN) and CPDq(OUT) are same specification. And there is not
indication of (IN) and (OUT) on the PCB.
Note) Power supply for the I/O module must not turn off at operation. If +24V is turned off at
operation, CNC happen to get system alarrn(Communication alarm between CNC and I/O
module). +24V for l/O module must be supplied before or same time CNC power on.
And +24V for I/O module must be turned off after or same time CNC power off.
TITLE
, 48132 points i/O Module
Connection Manual
DRAW. NO. CUST.
. A--73233E/01
SHEET
EDIT. DATE DESIG. DESCRIPTION -FANlJC LTD 003/
I
I
I
CE56 CE57
, ,I
A B
1
' 01 j ov 1 +24V 4'
i 02 j xm+3.0 j xm+3.1 /
TITLE
48/32 points I/O Module
Connection Manual
DRAW. NO. CUST.
A=73233E/Ol
SHEET
EDIT. DATE DESK DESCRIPTION FMWJC LTD 004/
~. ,. I
,
I ,- Terminal
CE57(AOl)
TITLE
48/32 points I/O Module
Connection Manual
DRAW. NO. CUST.
A-73233E/Ol
SHEET
EDIT. DATE DESIG. DESCRfPTION FANUC LTD 005/
I
.
7//// I
* 1
1 4
TITLE
48/32 points I/O Module
Connection Manual
DRAW. NO. CUST.
A-73233E/Ol
SHEET
EDIT. DATE DEW. DESCRIPTION FANUC .ITD 006/
I
/ Terminal
I
k
i Address i CE56(BOl)
+24V
5
I 1 /Bit 7 p CE57(BOl)
xiL*
0”
Xm+4.1
-_ - I
XJ?l+4.2 Q CE57(A07)
[RV]
Xm4.3 [R,,] o CE57(B07)
Xrw4.5 o CE57(808)
---+Kiq
Xm+4.6 a
v Q CE57(A09)
W]
Xm+4.7 CE57(B09)
TITLE
1 48/32 points I/O Module
Connection Manual
DRAW. NO. CUST.
A-73233E/Ol
Note) Xm+O.O-Xm+0.7 and Xm+50YXm+5.7 have a common line which are possible to select
the source/sink type. If COMO(CE56-A14pin) and COMS(CE57-B14pin) are connected to
+24V, the DI signal logic is negative. But in this connection, if the 01 signal wires happen to
drop the ground level, the status of the DI signal is same as the DI signal is “ON”. From the
safety viewpoint, COMO and COM5 should be connected OV.
Note) From the safety viewpoint, Emergency Stop signal must be assigned on the common fixed
address. As refer to the 5.2 DUD0 mapping, assign the Emergency stop DI.
Note) As for the common fixed line, if these 01 pins in this address open, the status of these one
stay “0”. And as for selectable common line, if the is connected to OV and these 01 pins
open,
the status of these one stay “0”. And if it is connected to +24V and these DI pins open,
the status of these one stay “1”. And if it is not connected to OV or +24V and these DI pins
open, the status of these one don’t care.
TITLE
48143 points I/O Module
Connection Manual
DRAW. NO. MST.
A-73233E/Ol
1
SHEET
EDIT. DATE DES
I G. DESCR
I PT1ON SWUUG CLTD 008/
1
1
I
I
TITLE
48143 points l/O Module
Connection Manual
DRAW. NO. CUST.
A--73233E/Ol
SHEET
EDIT. DATE DESIG. DESCRIPTION FAIWJC LTI) 009/
I
lsRt19i:
I
t
---Terminal
4
II
'CE56(Af4.B24.A25.B25)
DOCOM
1 CE57(A24,824.A25825i
TITLE
48143 points l/O Module
Connection Manual
DRAW. NO. GUST.
A-73233E/Ol
SHEET
EDIT. DATE DESIG. DESCRIPTION Fi&J+WC -lXD OlO/
I
I
Wiring
7RD/ ix 1L
ii'___.__.'
I-
I -r#I
HA1'3 !7#j L.-;___._-i
o HA7
mq
“’ ; i
HE7 3- -1
+sv !_.L..-+?i!?L_ +5V j j. c5v
fJv +.._...+uK___-.!__ I- ! ov 7 . w
1 1 t jPZ
13 ~8 RD A 1
HW4 'HA2 ;{ AA2
i3BK / \ f 'Ho2
'4 RD i 3 ; :+i;
YE.18 ' +5t'
9v /I+ !3BK I 4:
t 7 DV
I
is :aBK b I
l+e is i
‘3m ; l\ t
;;'20 6 RD i
I
I
&16 ;f BK !
1
I
_I-Shield aJ
GND
Cable iWiring 1
I I
TITLE
f 48132 points I/O Module
Connection Manual
DFtAW.NO. CUST.
A-73233E/Ol
SHEET
EDIT. DATE DESK. DESCRIPTIDN FAJUUC LTD Oil/
I
Note) Calculate the MPG cable max. length as refer to the followi ng calcull ation.
MPG needs a DCSV power supply and the voltage must be 11 ess than 0.2V dropping.
(the 02V dropping includes the resistance in the cable.)
3
L5 - = 76.75(m)
0.0394
TITLE
48132 points I/O Module
Connection Manual
I I I I DRAW.NO.A-73233E/Ol 1 CUST-
EDIT.
I DATE ) ii&. 1 DESCRIPTION
I FANUC LTD 012/
If the customer will use a some other vender’s MPG ,not FANUC’s MPG, the electrical
condition must be as follows.
HAn. HBn signals form MPG and CNC internal pulse ark as follows. A cycle of the HNHB
pulse 7, must be more than 200 fl set and 4rT: must be more than 50 fl sec.
i
1
i
t I 1
!
!*
tf
1 I I
f
!
:.
in the direction of +
1 I i I
in the direction of - i
Normal wheel , Reverse whee I
i
Reverse whee I
Cl ick
point
1] ~
- i
I
I
I
I f receiver C
circuit I
OV I I I
I OV
‘t f
I t-~~~~~~-~--~-~~~~- J
TlTLE
1 48132 points I/O Module
Connection Manual
DRAW. NO. CUST.
A-73233E/Ol
SHEET
EDIT. DATE DESK. DESCRIPTION FANUC LTD 013/
I
3. Module outline
A --
UT M 9 . .
X0
co II I
- &
z
t
r A I
,W- 60 -jZl-
01
E 0
OZl Sl
0 ln
: 4
TITLE
1 48/32 points I/O Module
Connection Manual
DRAW. NO. CUST.
A-73233E/Ol
SHEET
EDIT. DATE DEW. DESCRIPTION FANUC W-D 014/
1
4. Specification
4.1 Environmental Requirement
Temperature At operation O”C-58°C
around a unit Storing or transporting -2O”C-60°C
I
Temperature Max. 1.1“Urnin
variance
Humidity Normally 75% or less (Relative humidity)
. Short time(Within one month) 95% or less (Relative humidity)
Vibration Operating 0.5G or less
Atmosphere Normal FA atmosphere(Consult us when using the system under environments
with higher degree of dust, coolant, or organic solution.)
Other condition Use the l/O module in a cabinets that is always completely closed.
TITLE
. 48132 points I/O Module
Connection Manual
DRAW. NO. CUST.
A-73233E/Ol
SHEET
EDIT. DATE DESIG. DESCRIPTION FANCIC LTD 015/
1
45. Dl(lnput signal definition)
(Input signal)
[Capacity lDC3OV, 16mA or higher
intercontact leakage current in closed circuit 1mA 3r less(at 26.4V)
Intercontact voltage drop in closed circuit 2V or less(including the voltage drop in the
cables)
Deiay time Delay time of receiver IC : 2ms(MAX)
Need to consider about the serial
communication (I/O-Link)delay between CNC
and l/O module 2ms(MAX)+Scan cycle of
ladder(Scan cycle is different each CNCs).
.
46 DO(Output signal definition)
Maximum load current when driver in ON 200mA (including momentary values)
Saturation voltage when driver is ON lV(MAX) (When 2OOmA loaded) ,
Withstand voltage 24V+20% (including momentary values)
Leakage current when driver is OFF 20 ~1A or less I
Delay time Delay time of driver IC : 50 p s(MAX)
Need to consider about the serial
communication (I/O-Link)deiay between CNC
and l/O module 2ms(MAX)+Scan cycle of
ladder(Scan cycle is different each CNCs). .
Note) One of DOCOM pin must be less than 0.7A.
TITLE
I 48/32 points I/O Module
Connection Manual
CUST.
DRAII-
N”*A-73233E/Ol
SHEET
EDIT. DATE DEW. I
DESCRlPllON
I FmlJC LTD I 016/
I
5. Other notices
5.1 DO signal action when system alarm is happened
Ifa CNC using the l/O module will happen system alarm or comunication alarm between CNC
These situation should be understood.
and the I/O module, allDOS inthe module will turn off.
And also same situation happens when the power off.
DI map DOmap
7
xm Yn
Xm+l input Yn+l output
XIV2 signal Yn+Z signal
Xm+3 ‘ Yn+3 4
Xm+4
Xm+5 I
No use
Xm+8
XIll+Q
Xm+lO
XmcIZ(MPG1 unit)
DI mapping should be assigned 1 group, 16 byte mapping and DO mapping should be assigned
1 group, 8 byte mapping. The reason is as follows.
MPG interface(the counter for MPG) uses Xm+l2-Xm+14 area and it fixes. And if MPG
interface
will be used, Xm+12-Xm+14 area must be assigned. And in case of i series and using MPG
interface, DI mapping must be assigned 16 byte mapping. MPG counter area are directly
processed by CNC solWare. So you must not use the area by customer ladder.
There are DO aiarm(over current, over heat) indication area in Xm+l5. (Refer to the
5.5 DO(Output detection of DO signals) Also this area fixes in Xm+l5. And if this area will be
used,
this area must be assigned. So in case of using this area, Dl mapping must be assigned 16 byte
mapping.
TITLE
48/32 points I/O Module
Connection Manual
DfW. NO. WT.
A-73233E/Ol
SHEET
EDIT. DATE DESK. DESCRIPTION FAIWJC LTD 0171
I
(5.2 Dl/DO mapping continueing)
It is possible to assign any address for the 1/O module. But in Dl address. Each CNC have some
fixedaddress that is directly processed by CNC software.So, as refer to the following mention,
assign the DI mapping.
7 6 5 4 3 1 2 0 I
-MIT2#1 +MITZ#l -MITl#l
SKIP#l L-L~------~-II-----II~-~--CL~~~~~
ESKIP +MIT1#7 ----- L
ZAE#l XAE#l
-----
x0004 SKIPG#l SKlPS#l SKIP4#1 SKIP3#1 SK I P2#1 SKIP8#1 SKIP7#1
SKIWl B---m-
ESKIP SKIPS#l SKIP4#H SKIP3#1 -------------
ZAE#l YAE#l 1 XAE##l
e--e-
SKlPG#l SKIP2#1 SKlP8#1 SKIP7#1
I x0005
X0006
x0007 l(cOEC7#2 *DEC6#2 *OEC5#2 *DEW2 rOEC3#2 *DEC2#2 *OECl#2
X0008 *ESP
x0009 *OEC7#1 4EC6#1 *OECS#l *OEC4#1 *OEC3#1 *OECZ##l *DECl#l
x0010 I 1
x0011
x0012
SKIP#2 -MIT2#2 +MlT2#2 -MITl#Z +Wl#Z
SKlP6#2 -----~-~------~~--c-~~--- ZAE#Z XAE#2
---------a-
X0013 SKlP5#2 SKIP4##2 SKI P3#2 SKIP2#2 SKIP8#2 SKlP7#2 1
SK I P#2 SKIP6#2 SKIPWZ ZAE#Z YAE#2
SKlP4#2 SKIP3#2 L-----------II----- XAE#2
SKlP2#2 SK IP8#2 SK IP7#2
#? means the signales in 1st path. #2 means the signals in 2nd path. And up column means the
T series signals and down column means the M series signals.
TITLE
48/32 points i/O Module
Connection Manual
DRAW. NO. CUST.
A-73233E/Ol
1
SHEET
EDIT. DATE DEW. DESCf?I PTION FANUC LTD 018/
(5.2DVDO mapping continueing)
in case of 16 byte mapping start from X0004 - for DI area
x0004
x0005 Input
X0006 signal
x0007
X0008 4 *ESP fixed signal
x0009 4 *DECn#l fixed signals
x001 0
x001 1
x0012 No use
x001 3 -._-..--.-_._
DOCOM
In case that DO is ON
ON in a sequence
.*.
-.......__.:
In case that DO is ON
OFF in a sequence OFF
Note) in case that DO is ON in a sequence, DO signal output same as DOCOM state like
in a doted line in the figure.
Note) Power supply for i/O module (+24V) must riot turn off at operation. if +24 is turned off
at operation, CNC happen to get system aiarm(Communication alarm between CNC and i/O
module). +24V for I/O module must be supplied before or same time CNC power on.
And +24V for i/O module must be turn off after or same time CNC power off.
TITLE
. 48/32 points I/O Module
Connection Manual
CUST.
DRAW~no~A-73233E/01
SHEET
EDIT. DATE DESK. DESCRIPTION FANUC LTD 019/
I
5.4 Parallel connection of DO signals
If DO signals are connected in parallel like a figure and controlled same ON/OFF timing in the
ladder, that DO shall be output max. 400mA(twice a normal load). But remind that leakage
current when driver is OFF is max. 40 II A(twice a normal leakage current).
1
8
I I
TITLE
48/32 points I/O Module
Connection Manual
NO.
DRAW. CUST.
A-73233E/Ol
SHEET
EDIT. DATE DES
16. DESCR
I PTION -FAN&JC LTD 020/20
1
GE Fanuc Automation North America, Inc., Charlottesville Virginia