Professional Documents
Culture Documents
Altivar 58 TRX AC Drives: Line Reactors-208/230 V Rated Three Phase
Altivar 58 TRX AC Drives: Line Reactors-208/230 V Rated Three Phase
Selection
NOTE: Line reactors 50–60 80 KLCUL80A2 56 19.13 486 15.50 394 15.50 394
and filters are intended 75 110 KLCUL110A2 60 19.13 486 15.50 394 15.50 394
for separate mounting 100 130 KLCUL130A2 66 19.13 486 15.50 394 15.50 394
and wiring by the user. 125 160 KLCUL160A2 80 19.13 486 15.50 394 15.50 394
Ratings are based on 150 200 KLCUL200A3 102 22.13 562 20.50 521 24.37 619
NEC (NFPA 70) 430- 200 250 KLCUL250A3 110 22.13 562 20.50 521 24.37 619
150 current ratings. If 250 300 KLCUL300A3 115 22.13 562 20.50 521 24.37 619
the drive has a higher 300 360 KLCUL360A3 125 22.13 562 20.50 521 24.37 619
FLA rating, use the “A” 350 420 KLCUL420A3 145 22.13 562 20.50 521 24.37 619
rating to select the 400 480 KLCUL480A3 150 22.13 562 20.50 521 24.37 619
appropriate filter. 450–500 600 KLCUL600A3 167 22.13 562 20.50 521 24.37 619
133
09/2003 © 2000–2003 Schneider Electric All Rights Reserved
Class 8839 58M Enclosed AC Drives
Motor Protecting Output Filters
Low pass filters can be used on the output of the • Use of a non–inverter duty rated motor(s)
Class 8839 58M Enclosed AC Drive to decease • Existing general purpose motors subject to
the stress of resonant frequencies on the attached retrofit to an AC drive
motor. While low pass filters are not necessary for
most installations, they do provide substantial The motor protecting output filters combine
benefits in installations involving long motor leads, inductance, capacitance, and resistance to form a
such as: low pass filter. This filter will lower the dV/dt levels
• 460 V or higher rated AC drives to prevent exciting the natural resonant wire
• 1–25 hp rated units, if cable lead lengths are in frequency of the motor cables. Motors compliant
excess of 75 feet to NEMA MG–1 Part 31 guidelines do not require
the use of motor protecting output filters.
• 30–400 hp rated units, if cable lead lengths are
in excess of 300 feet
Motor Protecting Output Filters: 4. Output filters are enclosed in Type 1 general
purpose enclosures.
1. Output filters are manufactured by
Trans-Coil, Inc. 5. Output filters are intended for separate
mounting and wiring by user.
2. Output filters are designed for cable lead
lengths ranging from 50 to 1000 feet.
3. Output filters include 1.5% nominal reactance
at 480 V.
161