LT MCC FOR ST#2 ECO DEASHING MOTOR
1.LT MCC panel shall be suitable for floor mounting, free standing, draw-
out type, Compartmentalized, single front, powder coated with gray colour
and suitable for 50 KA short circuit level dust proof and vermin proof with
IP 54 protection as per IS 2147. The MCC specified herein otherwise stated
shall conform to the relevant and latest revisions of Indian standards and
Indian Electricity rules. (CODES AND STANDARDS IEC: 60947, IS: 13947, IEC:
60439, IS: 8623, IEC: 61850)
2.1000A LT SWITCHGEAR with Incoming breaker & draw out type module as per
details given below:
a) Incomer, 1000A rated ACB 1 No.
b) 90 KW draw out outgoing motor Feeder 3 Nos.
c) 250A draw out SFU (E type module) 2 Nos.
d) 63A draw out SFU (E type module) 2 Nos.
e) Metering module 1 No.
f) Control supply module with control
Transformer output Voltage-110V AC
& accessories 1 No
Note:
a)Control supply for indications and motor start/stop Shall be 110 v AC.
b)Breaker control supply shall be 220v DC (220v DC supply will be provided
by NTPC)
3. TYPE
Circuit Breakers -Shall be air break, three pole, spring charged, and
horizontal draw out type, suitable for local/remote electrical operation.
4. SYSTEM PARAMETERS
5. OPERATIONAL REQUIREMENTS
5.1 Breakers
a)1000A , Triple pole, drawout type ACB with 50kA breaking capacity
with microprocessor based LSIG protection, under voltage coil, spring
charging motor, closing, tripping coil. The breaker should operate on
220VDC control supply. Provision for breaker remote operation should
be available with 24v DCS Command.
b)Incomers shall be provided with remote /local, close/trip
arrangement, Breaker On/Off/Trip Indication, Ammeter and Volt meter
with Selector Switches.
c)Breaker shall have built in interlocks for equipment and personnel
safety.
d)Mechanical tripping shall be through red 'Trip' push button outside
the panels for breakers.
e)Provision of mechanical closing of breaker only in 'Test' and
'Withdrawn' position shall be made. It shall be possible to close the
door with breaker in test position. Breaker should be fitted with
Automatic Safety shutter. Breaker should not be allowed to rack-
in/rack-out in closed condition. Safety lock to be provided in
breaker isolated position to prevent accidental rack-in.
f)Clear status indication for each circuit shall be provided through
lamps, switch positions or other mechanical means.
g)Supervision relays shall be provided for trip coil monitoring.
h)Minimum protection such as Short circuit ,earth fault & Over
current shall be provided
6.Wiring
For control wiring 1.5sqmm PVC insulated copper flexible wire of
1100V to be used. For CT Wiring 2.5sqmm PVC insulated copper flexible
wire of 1100V to be used. For power wiring copper flexible wire of
size upto 125A to be used. Above 125A aluminium bus bar with 0.8
current density to be used.
b)All frames and load bearing members shall be fabricated using mild
steel structural sections or pressed and shaped cold rolled sheet
steel of thickness 3mm.
vi)All draw out modules shall have distinct service, test and
isolated positions with provision of external pad locking
facility in each position. Power contacts shall get
disconnected in both test and isolated positions whereas the
control contacts shall get disconnected in isolated position
only.
f)Busbar system will be 3 phase 4 wire (Neutral 50% size of the phase
busbar).The Power Bus Bar will be Electrolytic Grade PVC Sleeved
Aluminum Bus bar supported with FRP / DMC supports of suitable cross
section (@0.8 Amps/Sq. Mm)shall be considered.
Busbar clearance Phase to Phase and Phase to earth will be as per IS
standards.
7. TYPE TESTS
a)GENERAL
(i) All equipment to be supplied shall be of type tested design. The
Contractor shall submit all the type test report listed in these
specifications for NTPC approval .The type test reports should be carried
out within last five years from the date of bid opening. These reports
should be for the tests conducted on the equipment similar to those
proposed to be supplied under this contract and the test(s) should have
been conducted at an independent laboratory.
(ii) In case the Contractor is not able to submit report of the type
test(s) conducted within last five years from the date of bid opening, or
in case the type test report(s) are not found to be meeting the
specification requirements, the Contractor shall conduct all such tests
under this contract at no additional cost either at third party lab or in
presence of client/owner's representative and submit the reports for
approval.
(iii) The type test reports once approved for any projects shall be
treated as reference. For subsequent projects of NTPC, an endorsement sheet
will be furnished by the manufacturer confirming similarity and "No design
Change". Minor changes if any shall be highlighted on the endorsement
sheet.
b)LT SWITCHGEAR
The following type test certificates on each type & rating of L.T.
Switchgear and MCC panel shall be submitted.
8. Vendor shall submit the following documents along with offer for
technical scrutiny:
a)Approved and signed copy of attached NTPC Reference Quality Plan no-
14080R1 OR their detail Manufacturing Quality Plan in-line with our RQP-
14080R1 for NTPC review and approval.
b)Technical data sheet & dimensional drawing of complete switchgear.
9. Successful Vendor shall submit the following documents for NTPC review
and approval.
a) All data sheets
b) GA drawing
c) Schematic drawings
d) Type test reports
e) Quality plan for NTPC review and approval.