Feeder protection
REF601 / REJ601
Product Guide
Feeder Protection and Control / Feeder Protection 1MDB07212-YN
REF601 / REJ601
Product version: 2.1
Contents
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any
errors that may appear in this document.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered
2 ABB
Feeder Protection and Control / Feeder Protection 1MDB07212-YN
REF601 / REJ601
Product version: 2.1 Issued: 2012-08-15
Revision: A
Protection
Control
Condition monitoring
● = Included
ABB 3
Feeder Protection and Control / Feeder Protection 1MDB07212-YN
REF601 / REJ601
Product version: 2.1
50-1 50-1
50-2
50-2
50N
50N
Lockout 86
Lockout 86
REF601/REJ601
REF601/REJ601
Figure 1. Protection function overview of REF601 Figure 2. Protection function overview of REF601
/ REJ601 with earth current-measurement / REJ601 with earth current measurement
by internal calculation by external core-balance current transformer
4 ABB
Feeder Protection and Control / Feeder Protection 1MDB07212-YN
REF601 / REJ601
Product version: 2.1
8. Event log The relay supports a built-in test mode which ena-
To collect sequence-of-events (SoE) information, bles user to test the relay HMI and trip outputs.
the relay incorporates a non-volatile memory with a
capacity of storing 100 events with associated time
stamps with resolution of 1 milli second. Event log 11. Trip-circuit supervision
includes trip circuit supervision status, protection The trip-circuit supervision continuously monitors
operation status, binary I/O status, blocking status the availability and operability of the trip circuit. It
and relay fault code. The event logs are stored provides open-circuit monitoring both when the
sequentially, the most recent being first and so on. circuit breaker is in its closed and in its open posi-
The non-volatile memory retains its data also in tion. It also detects loss of circuit-breaker control
case the relay temporarily loses its auxiliary supply. voltage.
ABB 5
Feeder Protection and Control / Feeder Protection 1MDB07212-YN
REF601 / REJ601
Product version: 2.1
13. Inputs and outputs The relay has six LED indications on LHMI which
The relay is equipped with three 1A or 5A analog are configured for Ready / IRF, Protection start,
current inputs. The relay has an additional earth- Protection trip, Phase fault trip, Earth fault trip and
current input suitable for a 1A or 5A which can be Trip circuit fault.
connected to core-balanced current transformer /
All binary input and output contacts are pre-con-
spit core current transformer.
figured according to default configuration, however
The relay has four number of binary inputs with can be easily reconfigured by using the LHMI menu.
wide auxliliary voltage 24V-240V AC/DC. The binary
inputs can be configured for various functions
like Blocking, Protection reset, Breaker position, 14. Communication
Breaker control and trip circuit supervision. Individu- The relay is available with optional communica-
al input can be configured as either as “Inverted” or tion feature with Modbus RTU protocol on RS-485
“Non Inverted”. bus with two wire connection. This allows relay to
connect to control and monitoring system through
The relay has six output contacts, two power serial communication for remote monitoring.
outputs and four signalling outputs. The output
contacts can be configured for different functions
like routing of Protection start and trip signals, Ex-
ternal trip /open and external close command, trip
circuit supervision status etc. One dedicated output
contact is available for Unit ready / IRF status
indication.
CT BI BO
REJ601 4 4 6
REF601 4 4 6
GUID-89A9F7DF-FB82-4E8D-B449-7C0BB51C1DCA V1 EN
6 ABB
Feeder Protection and Control / Feeder Protection 1MDB07212-YN
REF601 / REJ601
Product version: 2.1
Table 4. Dimensions
Description Value
case 122.0 mm
case 152.0 mm
Depth 151.5 mm
Description Value
Ripple in the DC auxiliary voltage Max 12% of the DC value (at frequency of 100 Hz)
Description Value
• Continuously 4 A 20 A
ABB 7
Feeder Protection and Control / Feeder Protection 1MDB07212-YN
REF601 / REJ601
Product version: 2.1
Description Value
Description Value
Description Value
8 ABB
Feeder Protection and Control / Feeder Protection 1MDB07212-YN
REF601 / REJ601
Product version: 2.1
Table 10. Single-pole signal and IRF output relay (XK2 : BO3, BO4, BO5, BO6)
Description Value
Description Value
Front side IP 43
Description Value
Altitude up to 2000 m
ABB 9
Feeder Protection and Control / Feeder Protection 1MDB07212-YN
REF601 / REJ601
Product version: 2.1
10 ABB
Feeder Protection and Control / Feeder Protection 1MDB07212-YN
REF601 / REJ601
Product version: 2.1
• Radiated
30-230 MHz < 40 dB ( μV/m)
230-1000 MHz < 47 dB ( μV/m)
ABB 11
Feeder Protection and Control / Feeder Protection 1MDB07212-YN
REF601 / REJ601
Product version: 2.1
LV directive 2006/95/IEC
Description
GUID-89A9F7DF-FB82-4E8D-B449-7C0BB51C1DCA V1 EN
12 ABB
Feeder Protection and Control / Feeder Protection 1MDB07212-YN
REF601 / REJ601
Product version: 2.1
Table 23. Very High-set phase overcurrent protection, stage I>>> / 50-2
ABB 13
Feeder Protection and Control / Feeder Protection 1MDB07212-YN
REF601 / REJ601
Product version: 2.1
Setting range of pick-up current ‘Io >’ External earth measurement : 0.013...2.0 x In in steps 0.001, infinite
Internal earth measurement : 0.2...2.0 x In in steps 0.001, infinite
Operate time delay (DMT) ‘to >’ 0.04...64 sec in steps of 0.01
Operation time accuracy External earth measurement : ± 5.0% of set value or ± 30 msec
Internal earth measurement : ± 10.0% of set value or ± 30 msec
Setting range of pick-up current ‘Io >>’ External earth measurement : 0.05...12.5 x In in steps 0.001, infinite
Internal earth measurement : 0.5...12.5 x In in steps 0.001, infinite
Operate time delay (DMT) ‘to >>’ 0.04...64 sec in steps of 0.01
Operation time accuracy External earth measurement : ± 5.0% of set value or ± 30 msec
Internal earth measurement : ± 10.0% of set value or ± 30 msec
14 ABB
Feeder Protection and Control / Feeder Protection 1MDB07212-YN
REF601 / REJ601
Product version: 2.1
17. Dimensions and mounting With appropriate mounting accessories the REF601/
The REF601/REJ601 have been equipped with REJ601 can be mounted on the ABB make circuit
in-built press-fit mechanism. Without using an ad- breakers type VD4 /HD4.
ditional mounting accessories, the REF601/REJ601
can be easily flush mounted on the panel.
130 4
REF601
Ready Start Trip
Trip Ip
Trip Io
TCS Fault
151.5
160
Panel thickness
Front Left
3.0 (Max)
12 1.5
151.5
8 9.5
Top
ABB 15
Feeder Protection and Control / Feeder Protection 1MDB07212-YN
REF601 / REJ601
Product version: 2.1
18. Selection and ordering data Use the ordering key information in Fig. 4 to gen-
The relay type and serial number label identifies the erate the order number when ordering complete
protection relay. An order number label is placed on protection relays.
the side of the relay. The order number consists of
a string of codes generated from the hardware and
software modules of the relay The serial number and
order number label is placed on side of relay.
REF601 B E 4 4 6 B A 1 X F
# Description
1 Relay type
Feeder protection with control REF601
Feeder protection w/o control REJ601
2 Standard
IEC B
3,4 Analog input / output
Phase and Earth current input - 1A D4
Phase and Earth current input - 5A E4
5,6 Binary input / output
4 BI + 6 BO 46
REF601 B E 4 4 6 B A 1 X F
# Description
7 Serial communication
with RS485 B
None N
8 Communication protocol
MODBUS RTU A
None N
9 Power supply
24...240V AC / DC 1
10 For future use
GUID-89A9F7DF-FB82-4E8D-B449-7C0BB51C1DCA V1 EN
Undefined X
11 Version
Product version 2.1 F
Digit (#) 1 2 3 4 5 6 7 8 9 10 11
Code
Figure 4. Ordering key for complete relay
16 ABB
Feeder Protection and Control / Feeder Protection 1MDB07212-YN
REF601 / REJ601
Product version: 2.1
ABB 17
Feeder Protection and Control / Feeder Protection 1MDB07212-YN
REF601 / REJ601
Product version: 2.1
REF601 / REJ601
XK8 XK9
1 IL1 1
2 Uaux
2
3 IL2 3
4 4
5 IL3
6
7 Io
8
XK1 XK10
1
2 BI1 1
BO1
3 2
4 BI2
XK4 XK2
1
2 BI3 1
BO6
3 2
4 BI4
3
BO5
4
XK3
1 D+ Communication 5
2 D- on Modbus RTU BO4
3 G Protocol (Optional) 6
(IRF)
SHIELD
7
BO3
8
BO2
9
10
18 ABB
Feeder Protection and Control / Feeder Protection 1MDB07212-YN
REF601 / REJ601
Product version: 2.1
ABB 19
Contact us
www.abb.com/substationautomation
1MDB07212-YN A