Professional Documents
Culture Documents
Workshop on
Distribution & Smart Grid
Relay Testing
INTRODUCTION
Workshop on Distribution Relay Testing & Smart Grid
Introduction - Distribution & Smart Grid
TRANSMISSION
High Voltage grid ( > 110 kV ) composed by
• Large power plants, where the electrical
energy is produced and fed into the network
• Substations, where the energy is routed
according to the requirements
DISTRIBUTION
Medium and Low voltage grid composed by
• Medium size power plants
• Substations
• Consumers (Industries, cities, ecc…)
Workshop on Distribution Relay Testing & Smart Grid
Introduction - Distribution & Smart Grid
Yes, the solution is the SMART GRID, but what is it? It is the evolution of the
todays network!
PROTECTION RELAYS
They continuosly monitor the status of the grid by measuring electrical quantities as
• Voltage
• Current
• Frequency
• Phase shift
According to the grid design, specific protection relays must be installed and
properly setted
Workshop on Distribution Relay Testing & Smart Grid
Introduction - Distribution & Smart Grid
PRINCIPLE SCHEME
GRID AREA 1
Line 1
Not protected
Busbar
zone
Relay tasks:
Disconnector
Analog
Measures
• discriminate a fault from a
ENERGY FLOW
GRID AREA 2
Workshop on Distribution Relay Testing & Smart Grid
Introduction - Distribution & Smart Grid
Maintenance Knowledge
VOLTAGE PROTECTION
UNDERVOLTAGE (27)
OVERVOLTAGE (59)
Workshop on Distribution Relay Testing & Smart Grid
Voltage protection 27 / 59 - Distribution & Smart Grid
DEFINITIONS
VC
Phase to Ground voltage V U CA
Phase to Phase voltage U 120°
U BC 120°
VA
120°
The picture represents a symmetrical
(or balanced) three phase voltage
system U AB
U 3 V (Eq. 1)
VB
Workshop on Distribution Relay Testing & Smart Grid
Voltage protection 27 / 59 - Distribution & Smart Grid
NOTE: for simplicity in the following pages will no longer used the vector notation
Workshop on Distribution Relay Testing & Smart Grid
Voltage protection 27 / 59 - Distribution & Smart Grid
RELAY
LA
VA
27
Wye VB
VA V B VC connected
VTs
VC 59
Workshop on Distribution Relay Testing & Smart Grid
Voltage protection 27 / 59 - Distribution & Smart Grid
RELAY
LA
UAB
27
Delta UBC
VA V B VC connected
VTs
UCA 59
Workshop on Distribution Relay Testing & Smart Grid
Voltage protection 27 / 59 - Distribution & Smart Grid
DRTS 66 description
DI
VA
UAB
VB
VC
UBC
UCA
CB STATUS
CB STATUS
OPEN CMD
OPEN CMD
27 59 27 59
RELAY PARAMETERS
V (or U) pickup
Voltage threshold that defines when the relay must be ready to
release the trip (open) command
Trip Time
Time delay for the releasing of the trip (open) command, starting
from the instant in which the measured voltage reaches the pickup
value
V (or U) reset
Voltage value that defines when the relay must reset the Trip Time
counter
Drop-out ratio
It is the ratio V (or U) reset / V (or U) pickup
Vmeasured (rms)
V59 pickup
V59 reset
V nominal
V27 reset
V27 pickup
CB open
t [s]
pickup contact t [s]
trip contact
t [s]
T59 trip T27 trip
The measured voltage reaches The measured voltage reaches
V59 pickup but decreases V27 pickup and remains below
below V59 reset before T59 trip V27 reset within T59 trip
expires
[s]
T27 trip
T59 trip
The relay must release the trip command so the trip time can be
measured
Workshop on Distribution Relay Testing & Smart Grid
Voltage protection 27 / 59 - Distribution & Smart Grid
REMINDER: the
X X fault condition must
[V] be applied for more
SHOT 2 PREFAULT than the trip time
V27 pickup Vn
Workshop on Distribution Relay Testing & Smart Grid
Voltage protection 27 / 59 - Distribution & Smart Grid
REMARK 1
TRIP NO TRIP
AREA AREA
TRIP NO TRIP
AREA AREA
SHOT
X
[V]
V27 pickup Vn Nominal Higher
Trip Time Trip Time No trip
REMARK 2
The measured trip time will be slightly longer than the relay setting
Fault
t [s]
Relay pickup
t [s]
Trip cmd
released
t [s]
Trip contact
commutation
T1 Nominal T trip T2 T3
t [s]
Measured T trip
T1 = computation time ≈ 1 ms
T2 = trip contact action time ≈ 10 ms
T3 = CB main contacts open ≈ 50 ms
SHOT EXAMPLE
Relay settings:
U nominal = 100 [V] ; U pickup = 60 [V] ; T trip = 0.2 [s]
Voltage tolerance = ±5% ; Time tolerance = ± 3%+10 [ms]
Test settings:
X X
Workshop on Distribution Relay Testing & Smart Grid
Voltage protection 27 / 59 - Distribution & Smart Grid
[V]
[V]
GRADIENT : the
voltage changes ΔV/s
with a defined slope
ΔV/s t [s]
Workshop on Distribution Relay Testing & Smart Grid
Voltage protection 27 / 59 - Distribution & Smart Grid
DELTA RAMP
[s]
NO TRIP TRIP
AREA AREA
Delta ramp parameters
ΔV
T59 trip
ΔV : voltage step
X X X X amplitude
Vn V59 pickup
T max : maximum
[V] [V] duration time of the
V59 pickup applied voltage step
(longer than T trip)
Vn ΔV
t [s] The time counter is
reset at each step
pickup contact t [s] in order to
trip contact measure T trip
t [s]
GRADIENT
[s]
NO TRIP TRIP
AREA AREA Gradient parameters
ΔV/s
Vn
t [s] T measured ≠ T trip
REMARK 1
[V]
V stop
V59 pickup
ΔV/s
Vn
t [s]
Relay trip
t [s]
T59 trip
T measured
T max
REMARK 2
[V]
V stop
V59 pickup
ΔV/s
Vn
t [s]
Relay trip
t [s]
T59 trip
T measured
T max
REMARK 3
[s]
V>>
V>
GRADIENT EXAMPLE
Relay settings:
U nominal = 100 [V] ; U pickup = 140 [V] ; T trip = 0.4 [s]
Test settings:
X X
Workshop on Distribution Relay Testing & Smart Grid
Voltage protection 27 / 59 - Distribution & Smart Grid
T27 trip
T59 trip
Moving toward the no trip area, the pickup and trip contacts are reset
when the voltage reaches the reset values
V59reset
ΔV/s
1
X
V59 pickup
Vn ΔV/s V59 pickup [V]
V59 reset
[V]
V27reset
1
X
ΔV/s
V59 pickup V27 pickup
V59 reset
ΔV/s
Vn
t [s]
pickup
contact
Relay settings:
U nominal = 100 [V] ; U pickup = 140 [V] ; Drop-out ratio = 0.95
Test settings:
V 1 80.91[V ]
V 1 57.7350 Vstart V 1 V 2 V 2 57.735[V ] Vstart V 1 V 2 V 2 80.91[V ]
V 2 80.91[V ]
V 2 57.735240 slope 5[V / s ] slope 2[V / s ]
V 3 80.91[V ]
V 3 57.735120 T max 10[ s ] T max 10[ s ]
T max 0.2[ s ]
X X
Drop-out ratio measured = 76.74 / 80.91 = 0.948
Workshop on Distribution Relay Testing & Smart Grid
FREQUENCY PROTECTION
UNDERFREQUENCY (81U)
OVERFREQUENCY (81O)
RATE OF CHANGE FREQUENCY (81R)
Workshop on Distribution Relay Testing & Smart Grid
Frequency protection 81U / 81O / 81R - Distribution & Smart Grid
Overfrequency condition
LOAD 1
LOAD 2
G LOAD 3
LOAD 4
Nominal Frequency
Vice versa the rotating speed decreases when the generator is overloaded
Nominal Frequency
LOAD 1
LOAD 2
G LOAD 3
LOAD 4
Underfrequency condition
Workshop on Distribution Relay Testing & Smart Grid
Frequency protection 81U / 81O / 81R - Distribution & Smart Grid
When the power demand is close to the maximum power availability, some
areas of the grid must be disconnected to avoid the collapse
LOAD SHEDDING
Workshop on Distribution Relay Testing & Smart Grid
Frequency protection 81U / 81O / 81R - Distribution & Smart Grid
The frequency variation is not sudden, but it changes with a kind of ramp
T81U trip
T81O trip
[s]
- dF81R / dt 0 [dF/dt]
pickup
Workshop on Distribution Relay Testing & Smart Grid
Frequency protection 81U / 81O / 81R - Distribution & Smart Grid
SHOT GRADIENT
[Hz] [Hz]
dF81R dF81R
pickup pickup
Fn dt Fn dt
F81U F81U
pickup dF pickup dF dF81R
pickup
dt dt dt
t [s] t [s]
pickup
t [s] contact t [s]
pickup
trip
contact
t [s] contact t [s]
trip
T measured ≈ 0 [s] 0 [s] < T measured < T81U trip
contact
This is the easiest way to avoid that the two protective functions
interfere with each other
SOLUTION 2 : measure the time difference between the pickup and trip contact
[Hz]
dF dF
81R pickup First test
Fn dt dt
F81U pickup
Gradient with a variation
dF81R slower then dF81R /dt pickup
pickup
dt
t [s]
When the frequency
pickup contact t [s] reaches F81U pickup, 81U
trip contact
t [s] protection trips after its time
≈ 0.3 [s] setting
[Hz]
dF81R
Fn dt
pickup Second test
dF dF
F81U pickup 81R pickup Gradient with a variation
dt dt
faster then dF81R /dt pickup
t [s]
pickup contact
t [s] 81R protection trips
trip contact
t [s]
≈ 0 [s]
Workshop on Distribution Relay Testing & Smart Grid
Frequency protection 81U / 81O / 81R - Distribution & Smart Grid
C [Hz] D [Hz]
Fn Fn
C: measure of T81R trip
F81U pickup
t [s] t [s]
81R pickup contact
D: 81R no trip
t [s] t [s]
81R trip contact
t [s] t [s]
81U pickup contact
C & D verify of
t [s] t [s]
dF81R /dt pickup
81U trip contact
t [s]
≈ 0 [s] ≈ 0.3 [s] t [s]
Workshop on Distribution Relay Testing & Smart Grid
Frequency protection 81U / 81O / 81R - Distribution & Smart Grid
CONCLUSIONS
The operations that must be done to test properly a protection relay are
During the normal operation, in the lines flow the load current
The overcurrent protection must open the circuit breaker with a time
delay that is adequate to the fult current level
NO TRIP NO TRIP
TRIP AREA TRIP AREA
AREA AREA
T trip
[A] [A]
I > pickup I > pickup
When the fault current rises beyond When the fault current rises beyond
the pickup value, the trip time is the pickup value, the trip time is
independent from the current value dependent from the current value
Workshop on Distribution Relay Testing & Smart Grid
Phase overcurrent protection 50 / 51 - Distribution & Smart Grid
The Time Dependent characteristics are classified into IEC and ANSI standard
(and other)
A * TD K1
Ttrip P
B * TD K 2
I
I
pickup
B D E
Ttrip M * A M * M* M*
I I
2
I
3
C C C
I I I
pickup pickup pickup
Workshop on Distribution Relay Testing & Smart Grid
Phase overcurrent protection 50 / 51 - Distribution & Smart Grid
The IEC and ANSI standards define a list of particular characteristic curves
with predefined values of the coefficients in the generic formulas
Examples are
0.14
Ttrip TD[ s ] * 0.02
I
IEC Class A Normal Inverse
I
pickup
13.5
IEC Class B Very Inverse Ttrip TD[ s ] *
I
I
pickup
Workshop on Distribution Relay Testing & Smart Grid
Phase overcurrent protection 50 / 51 - Distribution & Smart Grid
Different curves allow to adjust the trip time in order to match the best
coordination with other protections in the grid
TD = 1.1[s]
Time [s]
Current [A]
Workshop on Distribution Relay Testing & Smart Grid
Phase overcurrent protection 50 / 51 - Distribution & Smart Grid
* I pickup
Time [s]
TD = 1.1[s]
NOTE: it’s possible to
find relays that use the
trip time at 10 times
the pickup current as
time multiplier
TD = 0.1[s]
Current [A]
Workshop on Distribution Relay Testing & Smart Grid
Phase overcurrent protection 50 / 51 - Distribution & Smart Grid
Time Dependendent
curves are used to protect
against overload
conditions
Time Independendent
curves are used to protect
against fault conditions
Workshop on Distribution Relay Testing & Smart Grid
Phase overcurrent protection 50 / 51 - Distribution & Smart Grid
Y Δ
ISOLATED
Y Y If Z = 0 [Ω]
the neutral is called
EARTHED
Z SOLID EARTHED
Workshop on Distribution Relay Testing & Smart Grid
Phase overcurrent protection 50 / 51 - Distribution & Smart Grid
Y Y
When one of the conductors touches the ground, the fault current cannot
flow through the ground, so the loop is closed by the equivalent
capacitance of the other cables not involved in the fault
CTs
LC
LB 50
Y Δ LA 51
X IA IB IC
The fault current IA is divided into the healty phases, where flows in the
opposite direction
IB IC I A I B 180
Amplitude IA Phase shift I B I C
2 2
Workshop on Distribution Relay Testing & Smart Grid
Phase overcurrent protection 50 / 51 - Distribution & Smart Grid
RELAY CONNECTIONS
LC P1 P2 RELAY
S1 S2
LB P1 P2
DI CB STATUS
S1 S2
LA P1 P2
OPEN CMD
S1 S2
IA
Wye 50
connected IB
CTs
IC 51
Workshop on Distribution Relay Testing & Smart Grid
Phase overcurrent protection 50 / 51 - Distribution & Smart Grid
DI
IA
IB
IC
CB STATUS
OPEN CMD
50 51
Workshop on Distribution Relay Testing & Smart Grid
Phase overcurrent protection 50 / 51 - Distribution & Smart Grid
Add characteristic
curve
Select the
characteristic
curve type
and set the
other
parameters
Workshop on Distribution Relay Testing & Smart Grid
Phase overcurrent protection 50 / 51 - Distribution & Smart Grid
CT ratio
and then set the tolerances for the automatic Pass/Fail result assessment
Workshop on Distribution Relay Testing & Smart Grid
Phase overcurrent protection 50 / 51 - Distribution & Smart Grid
seconds
cycles
NO TRIP
TRIP AREA
AREA
Relay
Y Δ GRID
Relay
LC
LB
67
LA Amplitude
IB IC
IA
Y Δ IA IB IC 2 2
LC
LB Phase shift
67
LA
RF
X IA IB IC
I A I B 180
I B I C
Workshop on Distribution Relay Testing & Smart Grid
Directional phase overcurrent protection 67 - Distribution & Smart Grid
The voltage of the faulty phase is reduced as much as the fault resistance is small,
while the voltage of the two healthy phases increases and the phase to phase
voltages remain constant
VCn VC VCn 3 VCn
U CA U CA U CA
U BC V An U BC VA VAn U BC VA 0
U AB U AB U AB
VBn VB VBn 3 VBn
RF RF 10[] RF 0[]
The phase to phase voltage of the two healthy lines is used as reference
quantity for the directional discrimination
Workshop on Distribution Relay Testing & Smart Grid
Directional phase overcurrent protection 67 - Distribution & Smart Grid
LC
IB
LB Amplitude
67
IA
LA
I A IB
Y Δ
LC Phase shift
LB
67 I A I B 180
LA
Workshop on Distribution Relay Testing & Smart Grid
Directional phase overcurrent protection 67 - Distribution & Smart Grid
The directional element computes the phase shift between the phase
current and the phase to phase voltage of the other two phases
C C
C
U CA IB
IA
A A A
U BC U AB
B B B
Ic
When the current in any phase rises over the pickup value, the
corresponding element is activated
Workshop on Distribution Relay Testing & Smart Grid
Directional phase overcurrent protection 67 - Distribution & Smart Grid
The trip sector is defined by an angle range where the phase shift of the
controlled quantities must lie to make the relay trip
A Y Δ
LC
U BC LB
LA
B
FORWARD
Workshop on Distribution Relay Testing & Smart Grid
Directional phase overcurrent protection 67 - Distribution & Smart Grid
MTA
Lagging
IA limit
I pickup
Leading
U BC U BC
Fault angle Leading
limit
limit
ANGLE REFERENCE VOLTAGE
I pickup
Counterclockwise Lagging
positive angle IA limit
convention
Clockwise
positive angle
convention
MTA
Workshop on Distribution Relay Testing & Smart Grid
Directional phase overcurrent protection 67 - Distribution & Smart Grid
Phase sequence
ABC ACB
VC VB
U CA U AB
U BC VA U BC VA
U AB 30 U AB 330
U AB U BC 270 U CA U BC 90
VB U CA 150 VC U CA 210
Can be easily noted that a mistake in the wiring leads to a mistake in the
directional discrimination
Workshop on Distribution Relay Testing & Smart Grid
Directional phase overcurrent protection 67 - Distribution & Smart Grid
RELAY CONNECTIONS (CTs starpoint toward line)
RELAY
LC P1 P2
S1 S2 DI CB STATUS
LB P1 P2
S1 S2
LA P1 P2 OPEN CMD
S1 S2
VA
Wye VB
connected
CTs VC
Wye 67
connected
VTs IA
IB
IC
Workshop on Distribution Relay Testing & Smart Grid
Directional phase overcurrent protection 67 - Distribution & Smart Grid
LC P1 P2
S1 S2 DI CB STATUS
LB P1 P2
S1 S2
LA P1 P2 OPEN CMD
S1 S2
VA
Wye VB
connected
CTs VC
Wye 67
connected
VTs IA
IB
IC
Workshop on Distribution Relay Testing & Smart Grid
Directional phase overcurrent protection 67 - Distribution & Smart Grid
From the relay point of view, the current is “positive” if it flows inside the
terminal marked with a dot
LC LC
LB Wye connected LB Wye connected
CTs CTs
LA (toward line) LA (toward busbar)
IA IB IC IA IB IC
RELAY RELAY
LC LC
LB Wye connected LB Wye connected
CTs CTs
LA (toward busbar) LA (toward busbar)
OPPOSITE ! CORRECT !
IA IB IC IA IB IC
CT side Line CT side Busbar
DI
VA
VB
VC
IA
IB
IC
CB STATUS
OPEN CMD
67
Workshop on Distribution Relay Testing & Smart Grid
Directional phase overcurrent protection 67 - Distribution & Smart Grid
Add
characteristic
curve
Select the
characteristic
curve type
and then set the tolerances for the automatic Pass/Fail result assessment
Workshop on Distribution Relay Testing & Smart Grid
Directional phase overcurrent protection 67 - Distribution & Smart Grid
Once the setting of all parameters is completed, the testing can start
Angle
tolerances
TRIP AREA
FAULT
NO TRIP ANGLE
AREA
NO TRIP
AREA
TRIP AREA
Each current pickup value has its own directional element, so the trip sectors
can overlap
Must be noted that the overcurrent characteristic curve changes according to the
fault angle
Workshop on Distribution Relay Testing & Smart Grid
The controlled parameter is the Residual current and not the Phase current
Ideally the residual current is different then zero only in case of earth fault
Workshop on Distribution Relay Testing & Smart Grid
Earth fault overcurrent protection 50N / 51N - Distribution & Smart Grid
The 3-phase current (and voltage) system can be expressed by another mathematical
representation called Symmetrical Components
IA 1 1 1 I0 Zero sequence current
1
Phase currents IB 1 2 I1 Positive sequence current
3
IC 1 2 I2 Negative sequence current
2
i
where e 3
represents a phase shift of 120°
When one of the conductors touches the ground, the fault current flows
through the ground toward the earthed point, so the loop is closed by
the earthing impedance connected to the transformer
CTs
LC
LB 50N
Y Y LA 51N
IA
RF
Z IA IA
IA
I0
1 1 1 IA
1 1 1 IA IA 3
1
I1 1 2
1
IB 1 2 0 0 I residual 3 I 0 I A
3 3
I2 1 2 IC 1 2 0 0
Workshop on Distribution Relay Testing & Smart Grid
Earth fault overcurrent protection 50N / 51N - Distribution & Smart Grid
From the formula can be noted that the residual current is three times the
vectorial sum of the three phase currents
1
I residual 3 I 0 3 I A I B I C I A I B I C
3
That’s why the residual current is ideally zero if the three phase currents are
perfectly balanced (only the positive sequence is different then zero and it is
equal to the three phase current system)
The residual current can be measured as follow
Conventional Phase CTs Core balance CT
LC LC
LB 50N LB 50N
LA 51N LA 51N
Y Y Y Y
Both solutions have the task to reduce the fault current to avoid the fault current when the
ground is involved
The Peterson coil has a variable reactance that can be tuned to compensate the equivalent
capacitance of the cables. If the coil reactance perfectly compensates the cable reactance,
the fault current is ideally zero
The use of core balance CT is suitable when the fault current (i.e. the residual
current) is very low and a very sensitive measurement is needed
Workshop on Distribution Relay Testing & Smart Grid
Earth fault overcurrent protection 50N / 51N - Distribution & Smart Grid
Z
Z IA IB IC
I0 1 1 1 IA 1 1 1 2I A 2I A I A I A
1 1 1
I1 1 2 I B 1 2 I A 2 I A I A 2 I A
3 3 3
I2 1 2 IC 1 2 IA 2 I A 2 I A I A
I0 0 The residual current is ideally zero!
2 2
I 1 I A
3 Due to the not perfect symmetry
2 2
I 2 I A
of the circuit a very small
residual current will flow
3
Workshop on Distribution Relay Testing & Smart Grid
Earth fault overcurrent protection 50N / 51N - Distribution & Smart Grid
LC P1 P2 RELAY
S1 S2
LB P1 P2
DI CB STATUS
S1 S2
LA P1 P2
OPEN CMD
S1 S2
IA 50N
Wye
connected IB
CTs
IC 51N
Workshop on Distribution Relay Testing & Smart Grid
Earth fault overcurrent protection 50N / 51N - Distribution & Smart Grid
P1 P2
LC RELAY
LB
DI CB STATUS
LA
OPEN CMD
50N
Neutral
S2 S1
conductor if
present IRES 51N
Cable
sheath
Workshop on Distribution Relay Testing & Smart Grid
Earth fault overcurrent protection 50N / 51N - Distribution & Smart Grid
Add characteristic
curve
Select the
characteristic
curve type
and set the
other
parameters
Workshop on Distribution Relay Testing & Smart Grid
Earth fault overcurrent protection 50N / 51N - Distribution & Smart Grid
Set Generation mode to match the measurement input configuration of the relay.
In case of one current, set the core balanced CT ratio.
Workshop on Distribution Relay Testing & Smart Grid
NOTE: the residual current and voltage are called Polarizing Quantities
Workshop on Distribution Relay Testing & Smart Grid
Directional earth fault overcurrent protection 67N - Distribution & Smart Grid
VA 1 1 1 V0 Zero sequence voltage
1
Phase voltages VB 1 2
V1 Positive sequence voltage
3
VC 1 V2
2
Negative sequence voltage
2
i
where e 3
represents a phase shift of 120°
From the formula can be noted that the residual voltage is three times the
vectorial sum of the three phase voltages
1
Vresidual 3 V0 3 VA VB VC VA VB VC
3
That’s why the residual voltage is ideally zero if the three phase voltages are
perfectly balanced (only the positive sequence is different then zero and it is
equal to the three phase voltage system)
LC LC
LB LB
LA 67N LA 67N
It is the series of three delta connected voltage transformers, in this way it’s possible to
perform the vectorial sum of the three phase voltages
VC
U CA
VC VA
Vres
U BC VA
VB
Vres U AB
VB
Usually the VTs used to make an Open Delta have a special ratio to reduce
the maximum voltage across the terminals
The maximum voltage across the Open Delta VTs terminals occurs in case of single
phase to ground fault in an isolated neutral network:
VA 0 (Fault on Phase A)
Standard ratio
30 VLL primary VLLsecondary
KVT 1
3 3
VLN primary VLN primary
3 VC 3 3 VB 3 Special ratio
KVT KVT
VLL primary VLLsecondary
KVT 2
3 3
VLN primary 3 VLN primary VLN primary
Vres 2 cos(30) 3 2 3 3
KVT 2 KVT KVT
Since KVT2 = 1.73*KVT1 , the same fault produces a 57,7% greater voltage if
standard ratio VTs are used. This fact leads to a cheaper relay voltage input design.
Workshop on Distribution Relay Testing & Smart Grid
Directional earth fault overcurrent protection 67N - Distribution & Smart Grid
The directional element computes the phase shift between the residual current
and residual voltage
NOTE: if the residual quantities are not suitable to protect the feeder, can be
substitute by the negative sequence quantities
VC
VC
I res 3I 2
VA VA
Vres 3V2
VB VB
MTA
Lagging
I res limit
I pickup
Leading
Vres Vres
Fault angle Leading
limit
limit
ANGLE REFERENCE VOLTAGE
I pickup
Counterclockwise Lagging
positive angle I res limit
convention
Clockwise
positive angle
convention
MTA
Workshop on Distribution Relay Testing & Smart Grid
Directional earth fault overcurrent protection 67N - Distribution & Smart Grid
RELAY CONNECTIONS
These are the most common relay connections
Phase VTs
VB VB Vres
VC VC
67N 67N 67N
IB Ires Ires
IC
NOTE: the phase VTs and CTs can be substitute with voltage and current sensor,
they provide a low voltage signal proportional to the primary voltage or current
Workshop on Distribution Relay Testing & Smart Grid
Directional earth fault overcurrent protection 67N - Distribution & Smart Grid
Add
characteristic
curve
Select the
characteristic
curve type
Set Generation mode to match the measurement input configuration of the relay.
In case of one current, set the core balanced CT ratio.
In case of one voltage, set the residual voltage ratio
Workshop on Distribution Relay Testing & Smart Grid
Directional earth fault overcurrent protection 67N - Distribution & Smart Grid
Once the setting of all parameters is completed, the testing can start
Angle
tolerances
TRIP AREA
FAULT
ANGLE
NO TRIP
AREA
NO TRIP
AREA
TRIP AREA
Each current pickup value has its own directional element, so the trip sectors
can overlap
Must be noted that the overcurrent characteristic curve changes according to the
fault angle
Workshop on Distribution Relay Testing & Smart Grid