You are on page 1of 42

EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP

PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC


ISSUE No. & DATE: 0 24/04/13 APPROVED BY: JBJ

Precept EN13 Fire Detection/Alarm Panel


& Precept EN13 Repeater

Application Guide

PAGE 1 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13

List of Contents
1. LIST OF FIGURES ............................................... 3 10.8. PULSE NON-ALARM ZONES ...................... 27
2. LIST OF TABLES................................................. 3 10.9. INHIBIT FIRE PROTECTION ON NON-LATCHED
3. INTRODUCTION .................................................. 4 ZONE ...................................................... 27
4. GENERAL DESCRIPTION ..................................... 4 10.10. DELAY ALARM SILENCE AND RESET ......... 27
4.1. CABINET SPECIFICATIONS .......................... 4 10.11. ALARMS ON EVACUATE ONLY................... 27
4.1.1. PANEL & REPEATER ORDER CODES......... 4 10.12. SILENCE BEFORE RESET ......................... 27
4.1.2. SEMI-FLUSH PANEL ORDER CODES & 10.13. SILENT ZONE TEST .................................. 27
DESCRIPTIONS ........................................ 5 10.14. BUZZER DISABLE ..................................... 27
4.1.3. FULLY FLUSH PANEL ORDER CODES AND 10.15. LATCHED FAULTS .................................... 27
DESCRIPTIONS ........................................ 5 10.16. REPEATER CONFIGURATION..................... 27
4.2. PANEL DESCRIPTION.................................. 6 10.17. OUTPUT RELAY CONFIGURATION ............. 27
4.2.1. C1626 2/4 ZONE MOTHERBOARD ............ 7 10.18. EARTH FAULT MONITORING. ..................... 28
4.2.2. C1627 8/16 ZONE MOTHERBOARD .......... 7 11. PANEL REPEATERS ......................................... 28
4.2.3. C1628 16 ZONE DISPLAY BOARD ............ 7 12. CIRCUIT CONNECTION DETAILS ........................ 28
4.2.4. C1631 REPEATER INTERFACE BOARD...... 7 12.1. AUXILIARY SUPPLY .................................. 29
4.3. PANEL ASSEMBLY ...................................... 8 12.2. FIRE ROUTING, FIRE PROTECTION AND
4.4. PANEL RANGE .......................................... 10 FAULT ROUTING OUTPUTS ....................... 29
4.5. REPEATER DESCRIPTION ......................... 10 12.3. USE OF AUXILIARY INPUTS ....................... 30
5. FUNCTIONAL SPECIFICATION ............................ 10 12.4. SOUNDER CIRCUITS ................................ 30
5.1. PANEL INPUT/OUTPUT LIST ...................... 10 13. ELECTRICAL DESIGN OF DETECTION ZONES ..... 31
5.2. FEATURES LIST........................................ 11 13.1. MAXIMUM NUMBER OF DEVICES ON A ZONE
6. PRECEPT EN13 C1627 MOTHERBOARD .............................................................. 31
FEATURES ...................................................... 13 14. C1651 CLOCK/TIMER MODULE ........................ 31
7. POWER SUPPLIES ............................................ 14 14.1. CLOCK MODULE FUNCTIONALITY .............. 31
7.1. BATTERY CHARGER ................................. 14 14.1.1. ALARM COUNTER .................................. 31
7.2. VISUAL INDICATIONS................................. 14 14.1.2. DAY/NIGHT DELAY MODE CONTROL ....... 31
ST
7.3. FAULT OUTPUTS ...................................... 14 14.1.3. 1 FIRE ALARM TIME ............................ 31
7.4. BATTERY DISCONNECT ............................ 14 14.2. CLOCK MODULE EDIT FACILITY ................ 31
8. COMPATIBLE FIELD DEVICES............................ 15 14.2.1. USER CONTROL/EDITING....................... 32
8.1. CABLE ..................................................... 15 14.2.2. ENGINEER’S EDITING AND CONFIGURATION
8.2. FIELD DEVICE PART NUMBERS & ............................................................ 32
DESCRIPTIONS......................................... 15 14.3. C1651 CLOCK MODULE PCB FEATURES.. 32
8.2.1. ZONE DEVICES...................................... 15 15. MECHANICAL, ELECTRICAL & ENVIRONMENTAL
8.2.2. SOUNDERS ........................................... 20 SPECIFICATION ............................................... 35
9. OVERVIEW OF USER FUNCTIONS ...................... 23 16. PRECEPT EN13 INPUT & OUTPUT SPECIFICATION
9.1. USER INDICATIONS................................... 23 ...................................................................... 37
9.2. USER CONTROLS ..................................... 24 17. APPENDIX ....................................................... 39
9.3. SELECTION OF DETECTION ZONES OR 17.1. EN54 OPTIONAL FUNCTIONS WITH
OUTPUTS FOR DISABLEMENT, ENABLEMENT REQUIREMENTS....................................... 39
OR TEST .................................................. 25 17.2. ANCILLARY FUNCTIONS NOT REQUIRED BY
9.4. DISABLEMENT/RE-ENABLEMENT OF EN54 ..................................................... 39
DETECTION ZONES AND OUTPUTS ............ 25 17.3. POWER SUPPLY LOAD CALCULATION ....... 39
9.5. DETECTOR ZONE ONE MAN TEST. ............ 25 17.4. BATTERY STANDBY CAPACITY CALCULATION
9.6. ALARM SOUNDER ONE MAN TEST ............. 25 .............................................................. 40
10. OVERVIEW OF ENGINEERS FUNCTIONS ............. 25 17.5. PANEL CONFIGURATION DESIGN CHART ... 41
10.1. ENGINEER’S CONFIGURATION PROCESS .... 25
10.1.1. ZONE/OUTPUT DELAY CONFIGURATION .. 25
10.1.2. FACTORY DEFAULT CONFIGURATION ...... 26
10.1.3. OTHER CONFIGURABLE FEATURES......... 26
10.2. CONFIGURABLE DETECTION ZONES .......... 26
10.3. DELAY ZONE CONFIGURATION ................... 26
10.4. STANDARD OR INTRINSICALLY SAFE ZONE . 26
10.5. SHORT CIRCUIT FIRE CONFIGURATION ....... 26
10.6. THE DELAY MODE FEATURE ...................... 26
10.6.1. CONFIGURE DELAY ZONES .................... 26
10.6.2. 1-2 STAGE DELAY ................................. 27
10.6.3. SELECTION OF OUTPUTS TO BE DELAYED 27
10.7. SELECTABLE ZONAL OR GENERAL ALARM
SOUNDER OPERATION .............................. 27

PAGE 2 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13

1. List of Figures 2. List of Tables


FIGURE 1 – ENCLOSURE - SURFACE BOXES ................ 4 TABLE 1 – PANEL INPUT & OUTPUT LIST ................... 10
FIGURE 2 – ENCLOSURE - SEMI FLUSH BOXES............. 5 TABLE 2 – RECOMMENDED CABLE ............................ 15
FIGURE 3 – ENCLOSURE - FULLY FLUSH BOXES........... 5 TABLE 3 – LIST OF APPROVED ZONE DEVICES ........... 15
FIGURE 4 – 2/4 ZONE PANEL, MAIN COMPONENTS ..... 6 TABLE 4 – LIST OF APPROVED SOUNDER DEVICES .... 20
FIGURE 5 – 8/16 ZONE PANEL, MAIN COMPONENTS ... 6 TABLE 5 – SOUNDER LOOP CABLE RESISTANCE &
FIGURE 6 – 2/4 ZONE PANEL - GENERAL ASSEMBLY CURRENT ........................................................ 22
(WITH OPTIONAL CLOCK MODULE) ....................... 8 TABLE 6 – MOTHERBOARD DIL SWITCH
FIGURE 7 – 8/16 ZONE PANEL - GENERAL ASSEMBLY CONFIGURATION DESIGN/RECORD .................... 41
(WITH OPTIONAL CLOCK MODULE) ....................... 9 TABLE 7 – ZONE CONFIGURATION DESIGN/RECORD .. 42
FIGURE 8 – C1627 MOTHERBOARD LAYOUT ............ 13 TABLE 8 – OUTPUT DELAY CONFIGURATION
FIGURE 9 – C1627 MOTHERBOARD FIELD DESIGN/RECORD ............................................. 42
TERMINATION .................................................. 28
FIGURE 10 – FIRE ROUTING, FIRE PROTECTION AND
FAULT ROUTING CONNECTIONS. ...................... 29
FIGURE 11 – RESET RELAY CONTACT CONNECTION
DETAILS .......................................................... 30
FIGURE 12 – AUXILIARY I/P CONNECTION DETAIL ..... 30
FIGURE 13 – ALARM CIRCUIT CONFIGURATION ......... 30
FIGURE 14 – ZONE WIRING DETAILS......................... 31
FIGURE 15 – C1651 CLOCK MODULE PCB .............. 32
FIGURE 16 – TYPICAL PANEL CONNECTION DIAGRAM 33
FIGURE 17 – TYPICAL ALARM CIRCUIT CONNECTION
DIAGRAM......................................................... 34

PAGE 3 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13

3. Introduction 4.1. Cabinet Specifications


This document contains information about the Figure 1 – Enclosure - surface boxes
FIRECLASS Precept EN13 control panel necessary
for application design.
The following supporting documentation is also
available:
 FIRECLASS Precept EN13 Sales Literature
 FIRECLASS Precept EN13 User Manual
 FIRECLASS Precept EN13 Installation and
Commissioning Manual.
 FIRECLASS Precept EN13 Log Book.
 Wiring Recommendations

4. General Description A

The FIRECLASS Precept EN13 Panel range is fully


compliant with the mandatory requirements and
selected optional requirements of EN54-2 and 4 as
well as the relevant requirements of BSEN5839-
1:2002. The Zone Circuits & Alarm Circuits are fully
compliant with the requirements of EN54-13 when
used with the specified devices. C B

The FIRECLASS Precept EN13 equipment range:


Top entry 20mm knock outs 26
Panels: 2, 4, 8, & 16 zone versions. A [mm] 370
B [mm] 325
Repeater: 8 & 16 zone versions (2 & 4 zone
C [mm] 126
panels use the 8-zone repeater).
A system is comprised of the following:
4.1.1. Panel & Repeater Order Codes
 One off Precept EN13 2, 4, 8, or 16 zone fire Part Number Description
detection and alarm panel. 508.032.025 2 Zone Panel
 Up to 5 off Repeater Panels. 508.032.026 4 Zone Panel
508.032.027 8 Zone Panel
Each panel and repeater in the range is housed in a 508.032.028 16 Zone Panel
single metal enclosure incorporating a door-
mounted display board fitted with a polyester 508.032.707 8 Zone Repeater c/w Power Supply
overlay providing user controls and indications. 508.032.708 16 Zone Repeater c/w Power Supply
User controls are locked & unlocked via a key-
switch. All indications are implemented using LEDs.
508.032.710 8 Zone Repeater DC Powered
The power supply and standby batteries are
508.032.711 16 Zone Repeater DC Powered
housed within the panel enclosure.
2605070 Clock Module Kit

PAGE 4 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13
4.1.2. Semi-flush Panel Order Codes & 4.1.3. Fully Flush Panel Order Codes and
Descriptions Descriptions
Part Number Description Part No Description
2603011 2/4/8/16 Zone Semi-flush bezel 2603060 2/4/8/16 Zone Painted bezel
(painted to customer's specification)
Figure 2 – Enclosure - semi flush boxes 2603061 2/4/8/16 Zone Stainless Steel bezel
(brushed or polished)
y
2603062 2/4/8/16 Zone Brass bezel
(brushed or polished)

Figure 3 – Enclosure - fully flush boxes


z
y
z

z
z

x A

x A

C B
A [mm] 433
B [mm] 388
C [mm] 100 C B
x [mm] Hole height 380 A [mm] 411
y [mm] Hole width 340 B [mm] 428
z [mm] 30 C [mm] 126
x [mm] Hole height 380
y [mm] Hole width 380
z [mm] 50

PAGE 5 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13

4.2. Panel Description


The panels consist of the modules shown in the internal views depicted in Figure 4 & Figure 5.
Figure 4 – 2/4 Zone Panel, Main Components
Removable Chassis Secondary earth bar Enclosure fixing
for cable screens holes (3 off)
Cable clip for
incoming mains cable

Mains Warning/
Primary Earth label

ZONE CIRCUITS ALARM CIRCUITS AUX D.C. FAULT FIRE FIRE INPUTS OUTPUTS REPEATER RESET
Mains Terminal Block
ZONE OUTPUTS

CHANGE

ACTIVE
ROUTING ROUTING PROTECTION
1 2 3 4 1 2 3 4

CLASS

EVAC.
& Primary Earth Connection

GND
EVAC
1 2 3 4

RST.

BUZ.

N/O
N/C
24V 0V 24V 0V O/+

A
B
+ - + - + - + - + - + - + - + -

DIS.
P C/- C/+ P O/- C/+ P O/-
Mains Fuse

SIL.

P
L N
Replace
+ 1 - + 2 - + 3 - + 4 - ALARM
CIRCUITS
With
Same Removable Chassis
CEL C1717
Type

01-05-12
ISSUE 0
IN

Relay Board

CEL C1631 ISSUE 2


2
3
OUT

RETURN Relay Board Chassis


Relay Board +

Chassis +

C1631 Repeater Interface


(Optional)
J3

Relay Board

+
-
S
+

Mains Transformer
INHIBIT F/P ON NLZ SILENCE BEFORE RESET
1

1
N
O

N
O

DELAY ALARM SIL & RESET 1


ENABLED

2
CONFIG

S
DELAY ON AUTO 2 DELAY/
3

MINUTES
CONFIG NON-LATCH ZONES 4 OUTPUT OK
4

CONFIG I/S ZONES 8

+
5

ZONAL THERM. FAULT

+
CONFIG M/S ZONES
6

ALARMS
CONFIG DELAY ZONES PULSE NON-ALARM
7

ZONES BAT/CHG FAULT

Mains
CONFIG DELAY O/PS SILENT ZONE TEST
FS1
8

2 STAGE DELAY BUZZER DISABLE CHARGER FAULT


+
9

ALARMS ON EVAC ONLY LATCHED FAULTS


+
10

10

- MAINS FAULT
BATTERY FUSE BATT THERM OUTPUT

FIT EARTH MON

Transformer Motherboard
Motherboard Batteries

Batteries

Figure 5 – 8/16 Zone Panel, Main Components


Cable clip for
Removable Chassis Secondary earth bar Enclosure fixing incoming mains cable
for cable screens holes (3 off) Mains Warning/
Primary Earth label

Mains Terminal Block


Mains Fuse & Primary Earth Connection
L

Replace With
Same Type
N Removable Chassis
ZONE CIRCUITS ALARM CIRCUITS AUX D.C. INPUTS OUTPUTS REPEATER
CHANGE

ZONE OUTPUTS
ACTIVE

RESET
CLASS

+ 1- + 2- + 3- + 4- + 5- + 6- + 7- + 8- + 1- + 2- + 3- + 4-
EVAC.
EVAC

RST.

BUZ.

GND

24V 0V
DIS.

N/C
A
B
SIL.

1 2 3 4

+ 1 - + 2 - + 3 - + 4 - ALARM
CIRCUITS
CEL C1717

01-05-12
ISSUE 0

IN

OUT

RETURN

Relay Board
R0
1

CEL C1631 ISSUE 2

R1
2

R2
3

Relay Board
+
+

Relay Board Chassis


+

Motherboard
-

C1631 Repeater Interface


+

INHIBIT F/P ON NLZ SILENCE BEFORE RST


S
1

1
N
O

N
O

DELAY ALARM SIL & RESET 1


2

DELAY ON AUTO 2 DELAY/


3

OUTPUT OK
+

MINUTES
CONFIG NON-LATCH ZONES 4
4

S
CONFIG I/S ZONES 8
5

BAT/CHG FLT

(Optional)
CONFIG M/S ZONES ZONAL ALARMS

Mains
6

CONFIG DELAY ZONES PULSE NON-ALARM ZONES


7

CHARGER FLT
CONFIG DELAY O/PS SILENT ZONE TEST
8

FS1 +
+

2 STAGE DELAY BUZZER DISABLE


9

MAINS FAULT
ALARMS ON EVAC ONLY LATCHED FAULTS
10

10

- + OUTPUT
BATTERY FUSE BATT THERM

Transformer FIT LINK FOR


EARTH MONITOR

Motherboard
Batteries Batteries

PAGE 6 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13
4.2.1. C1626 2/4 Zone Motherboard display board. The power supply components are
located on this PCB. The microcontroller (including
This board is common to the 2 & 4-zone panels. It Firmware and RAM) and all of the site-specific
is also used, in a depopulated form, as the configuration features (DIL switch & EEPROM) are
motherboard for the Repeater panels. accommodated on this board.
It provides terminals for all the field wiring, interface
connectors for the repeater and connections to the 4.2.3. C1628 16 Zone Display Board
display board. The power supply components for
This board provides visible [LED] user indications
the panels and mains powered repeaters are
and user buttons. The display board connects to
located on this PCB. The microcontroller (including
the motherboard via a ribbon cable.
Firmware and RAM) and all of the site-specific
configuration features (DIL switch & EEPROM) are 4.2.4. C1631 Repeater Interface Board
accommodated on this board.
This optional plug-in board provides an RS485
4.2.2. C1627 8/16 Zone Motherboard capability for communication with up to 5 repeaters
and is fitted to the C1627 motherboard via two
This board is common to the 8 and 16-zone panels.
connectors. One C1631 needs to be fitted to the fire
It is also used, in a depopulated form, as the
alarm panel and one to each repeater.
motherboard for the range of repeaters.
It provides terminals for all the field wiring, interface
connectors for the repeater and connections to the

PAGE 7 of 42
ENCLOSURE
BACKBOX
ISSUE No. & DATE: 0

EARTH BAR
4.3. Panel assembly

MAINS CABLE
CLAMP
EQUIPMENT: FIRECLASS

CHASSIS
24/04/13

EARTH POST MAINS


EARTH
STRAP TERMINAL
se
PUBLICATION: FIRECLASS PREC

RATING ins
Fu
ASSEMBLY
Ma N
L
LABEL lace
Rep
With
me
Sape
Ty

DOOR
TIMER
MODULE
EN13 APP

(OPTIONAL)
PRECEPT EN13

F
Co ire A
ntr larm
ol
Eq Sy
uip ste
KM
me m
95 nt
74
4
DISPLAY App
rova
00
86
-C
Ltd
l: PD
Stan -555
da 92
rds: 1
Pr
od
uc
t:
Pa
rt
See exploded general assembly drawings Figure 6 & Figure 7.

PAGE 8 of 42
Se No:
ria
Inpu l N
o:
Fu t:
se
Cou :
ntry
of
orig
n:
Isol
ate
Ope Su
pp
TH ning ly
IS B
BE UN Covefor
EA IT M er e EARTH TRANSFORMER
RTH UST
ED

POST REPEATER
INTERFACE
(OPTIONAL)
RELAY
PLATE RELAY MOTHERBOARD
BOARD
EARTH
STRAP

RIBBON CABLE
ASSEMBLY
Figure 6 – 2/4 Zone Panel - General Assembly (with optional clock module)

EARTH POST
WRITTEN BY: RKP
CHECKED BY: AJC
MAINS TERMINAL
MAINS CABLE ASSEMBLY
CLAMP
se
Fu
ins
Ma L

With N
pe
laceTy
Repme
Sa
ISSUE No. & DATE: 0

EARTH
BAR
EQUIPMENT: FIRECLASS

EARTH
24/04/13

CABLE
EARTH RELAY
POST MOUNTING
PUBLICATION: FIRECLASS PREC

RATING PLATE
LABEL
RELAY
DOOR
BOARD
DISPLAY
EN13 APP
PRECEPT EN13

F
Co ire A
TIMER MODULE ntr larm
ol
Eq Sy
uip ste
KM
me m
95 nt
74
App 4 Ltd
00
(OPTIONAL) rova
l:
86
-C
PD
Stan -555
da 92
rds: 1
Pr
od
uc
t:
Pa
rt

PAGE 9 of 42
Se No:
ria
Inpu l N
o:
Fu t:
se
Cou :
ntry
of
orig
n:
Isol
ate
Ope Su
pp
ly
TH ning
IS B
BE UN Covefor
EARTH
EA IT M er e
RTH UST
ED

POST
REPEATER
INTERFACE
(OPTIONAL)
EARTH
OUTPUT
CABLE
EXPANSION
CHASSIS INTERFACE
(OPTIONAL)

MOTHERBOARD
Figure 7 – 8/16 Zone Panel - General Assembly (with optional clock module)

EARTH
POST
WRITTEN BY: RKP
CHECKED BY: AJC
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13
4.4. Panel range interface board must to be fitted to the repeater
motherboard.
Enclosure Internal
PSU
Panel Dimensions SLA
(230Vac) Enclosure Internal
[H x W x D mm] Battery PSU
Repeater Dimensions SLA
2/4 zone [370 x 325 x 126] 1.5A 24V 3Ah (230Vac)
[H x W x D mm] Battery
8 zone [370 x 325 x 126] 3A 24V 12Ah
2-8 zone [370 x 325 x 126] 1.5A 24V 3Ah
16 zone [370 x 325 x 126] 3A 24V 12Ah
16 zone [370 x 325 x 126] 1.5A 24V 3Ah
4.5. Repeater Description
The repeater consists of the same PCB modules 5. Functional Specification
and enclosures as used in the Precept EN13 fire
alarm panel. The components for the redundant 5.1. Panel Input/Output List
motherboard I/O [zones, alarm circuits etc] are not See Table 1 below.
fitted to the repeater motherboard. The mechanical
arrangement is identical. The C1631 Repeater

Table 1 – Panel Input & Output List


Precept EN13 Panel
Input/Output
2 zone 4 zone 8 zone 16 zone
Detection zones 2 4 8 16
Remote silence alarm I/P [non monitored] 1 1 1 1
Remote reset I/P [non-monitored] 1 1 1 1
Remote evacuate I/P [non-monitored] 1 1 1 1
Class change I/P [non-monitored] 1 1 1 1
Sounder circuits 2 @ 0.5A 4 @ 0.5A 4 @ 1A 4 @ 1A
1 1
Zonal O/Ps [open collector] 2 4 Optional Optional
Disablement active [open collector] 1 1 1 1
Evacuate active [open collector] 1 1 1 1
Buzzer active [open collector] 1 1 1 1
Monitored Fire Routing O/P 1 1 1 1
Monitored Fire Protection O/P 1 1 1 1
Monitored Fault Routing O/P 1 1 1 1
Volt free reset relay 1 1 1 1
Aux DC Supply [fused] 1 @ 0.5A 1 @ 0.5A 1 @ 1A 1 @ 1A
2 2 2 2
Repeater facility Optional Optional Optional Optional
NOTES:
1
- The 8 & 16 zone panels have zonal outputs for zones 1 to 4 only. Additional outputs can be added
via the output expansion boards. An Output Module communication interface board must be fitted in
the panel if output expansion boards are required..
2
- The use of repeaters requires the addition of a Repeater communication interface board.

PAGE 10 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13

5.2. Features List

Switching regulator power High efficiency voltage regulation. Battery charging voltage is
supplies with temperature automatically adjusted between 28.6 and 26.72Vdc over an ambient
o
compensated battery charging temperature range of -10 to +50 C.

Battery disconnect Protects the battery from permanent damage due to over discharge by
automatically disconnecting it when the battery voltage falls to 21Vdc.

Battery Resistance Check Batteries are monitored for high resistance. A fault indication is given if
the resistance exceeds the following values:
1Ω - 2/4-zone panels & repeaters
0.6Ω - 8/16-zone panels

Class change input Operates all sounders for up to 5 seconds.

Configurable detection zones Simple and flexible display-based configuration process allowing
detection zones to be configured for any of the following:
o Latching or non-latching Fire indication.
o Delayed or non-delayed Output operation.
o Normal or Intrinsically-Safe zone monitoring.
o Short Circuit = Fault or Short Circuit = Fire
Factory configuration: Latching, non-delay, standard [non-I.S.],
S/C = Fault.

Active fault monitoring on Reduces zone monitoring current and therefore reduces the required
detection zones. [Non- battery capacity.
Intrinsically Safe applications Maintains zone wiring continuity following the removal of a detector,
only] while still providing a fault indication on the panel.

Selectable Zonal or General Selectable via DIL switches on the motherboard.


alarm Sounder operation with The standard sounders on the 2 and 4 zone panels can be used in
sounders in alert or silent in General or Zonal modes. [These sounders always operate in General
adjacent zones. mode on 8 and 16 zone panels regardless of DIL switch setting].
The output expansion system provides additional sounder circuits for
General or Zonal use on the 8 and 16 zone panels.

Configurable Fire Routing, Fire Configuration Links on the motherboard allow each Output Relay to be
Protection and Fault Routing individually selected to the EN54-2 powered/fault-monitored mode or
output relays non-EN54-compliant volt-free changeover contacts.
Factory configuration:-Fully Monitored (EN54-2 Mode).

Reset Relay A volt-free changeover contact operating for 10 seconds on panel fire
alarm reset.

Auxiliary 24Vdc power supply Protected by an electronic fuse. Operation of the fuse is indicated on the
output display. The fuse is reset by pressing the Reset button on the display.

Open collector outputs o Evacuate active.


o Buzzer Active.
o Disablement Active.
o Zonal fire for each zone up to zone 4 [Zonal output expansion on 8 &
16 zone versions via output boards].

PAGE 11 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13
Remote inputs Remote Evacuate.
Remote Silence Alarms.
Remote Reset.

Earth Fault monitoring Can be disabled via a link on the motherboard.

Zone/Output disablement The following circuits can be independently disabled/enabled:


feature o Each Zone
o Fire Routing
o Fire Protection
o Fault Routing
o All Sounder Circuits

One Man Zone Test Each zone can be independently set to the One Man test condition.
Sounders can be configured to either operate briefly to confirm the panel
has detected the test fire or no sounder operation during the test fire.

One Man Sounder Test Operates the sounders intermittently.

Configurable Delay Mode Flexible system allows:


Facility o Any zone to be configured as a delay zone.
o Single-stage or two-stage delay.
o Selectable 1 to 10 minute delay period [for single-stage and two-
stage delay modes].
o Selection of the outputs to be delayed [Fire Routing and/or Fire
Protection and/or Sounders]- can be any combination.

Clock Module [Optional] Plug in LCD unit providing either:


o Day/night delay control with or without fire event counter.
or
o Time of fire event with or without fire event counter.

Other configuration features o Prevent the Fire Protection output operating from a fire condition
on a “Non-Latch” zone.
o Inhibit the silencing and resetting of the panel for 3 minutes
following the occurrence of a fire alarm.
o Set the sounders to operate only when the panel is in the
Evacuate condition.
o Inhibit the resetting of the fire alarm condition until the alarm
sounders have been silenced.
o Disable the internal panel buzzer.
o Select latching fault mode where all fault conditions latch until
the panel is manually reset.
o Restore factory default configuration of zones and outputs to be
delayed.

Repeater panels Support for up to 5 repeater panels via two-wire RS485 serial
communication.

PAGE 12 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13

6. Precept EN13 C1627 Motherboard Features


Figure 8 illustrates the motherboard features referred to elsewhere in the documentation.
Figure 8 – C1627 Motherboard Layout

Remote Inputs:
Silence Alarms Aux Outputs:
Evacuate DISablement active
Reset Fire EVACuate Active
Routing
Output BUZzer ACTIVE

Fault
Aux DC Supply Routing Fire
24V & 0V Output Protection
Zone Outputs Output
1-4 Alarm Circuits Repeater
[Marked with Active Terminals:
Polarity] A,B, GND

Reset
Zone Relay
Detection Output
Inputs

J6,J7,J8
Fault Routing
Output
configuration J10,J11,J12
links Fire Routing Output
configuration links J14,J15,J16
Fire Protection Output
configuration links

C1631
J1 Repeater
Display Interface
Connector

Secondary
AC from
transformer

Configuration
mode enabled FS1
LED indicator Battery J18
Fuse Power Supply LED Earth Fault
indicators: Monitoring
Configuration Battery OUTPUT OK Link
switches Terminals Battery/Charger Fault
SW1/1 to Configuration Charger Fault
SW1/10 switches Battery
SW2/1 to Thermistor Mains Fault
SW2/10 Terminals

PAGE 13 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13

7. Power Supplies c) Low Battery voltage (<15.7V ±0.4V)


d) Battery and interconnection resistance is
The 1.5A & 3A power supplies provide 27.1V equal to or higher than:
nominal at load currents of up to 1.5A & 3A
respectively and are designed in accordance with  1Ω - 2/4-zone panels & repeaters
the requirements of EN54-4.  0.6Ω - 8/16-zone panels
The power supplies are contained on the 3) A yellow ‘Charger Fault’ LED indicating any of
motherboard, see Figure 8. the following:
a) A mains fault exists (described below)
7.1. Battery Charger
b) The Switching regulator or charger circuitry
Each power supply provides a temperature-
is malfunctioning
compensated charging voltage for sealed-lead-acid
12V batteries connected in series. Charging voltage c) Battery Fuse is blown
o o
range is 26.72V @ 50 C to 28.25V @ -10 C. 4) A yellow ‘Mains Fault’ LED. This indicates that
Battery sizes are: the mains voltage has failed or is less than the
required minimum for correct operation of the
2 off 12V, 3Ah for the 1.5A supply
power supply (80% of the rated voltage).
2 off 12V, 7Ah or 12 Ah for the 3A supply
The health of the batteries, the battery connections 7.3. Fault Outputs
and fuse are checked by a battery monitor circuit All PSU fault conditions are communicated to the
and automatic battery test facility once every 30 panel motherboard, which will raise a fault
seconds. If the Battery is disconnected or the indication on the display and operate the fault
Battery voltage falls below 15.7V or the Battery and routing output.
inter-connection resistance is greater than or equal
to 1Ω, the Batt/Charge fault LED is illuminated and 7.4. Battery Disconnect
the Fault Output is operated. The circuitry also The power supply provides a battery disconnect
protects against reversed connection of the facility that disconnects the batteries when the
batteries. battery terminal voltage falls below 21.2V ±0.53V.
This will occur under the following conditions:
7.2. Visual indications
1) A short circuit across the battery terminals
Visual indications on the power supply are:
2) To prevent deep discharge of the batteries if
1) A green ‘Output- OK’ LED. This simply supplying the panel for an abnormally long
indicates that power is being supplied to the period of time.
load.
The batteries are reconnected when the mains
2) A yellow ‘Batt Charge Fault’ LED indicating voltage is present and the battery voltage is greater
any of the following conditions: than 18.5V ±0.46V.
a) Battery or associated wiring disconnected
b) Battery fuse blown

PAGE 14 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13

8. Compatible Field Devices


For EN54-13 compatibility, the panel must only be used with the approved cable and devices as listed in the
following sections.
8.1. Cable
The recommended cable for EN54-13 compatibility is FP200 GOLD, up to 2.5mm cross sectional area.
The cables shown in the table below can be used with the panel.
Table 2 – Recommended Cable
Maximum
Resistance Capacitance Capacitance Maximum
Sounder
per Km per Km per Km zone cable
CABLE Loop
per Core Core-Core Core-Screen length
length
(Ω) (uF) (uF) (m)
(m)
FP200
18.1 0.08 0.15 333 333
1.0mm csa
FP200
12.1 0.08 0.15 500 500
1.5mm csa
FP200
7.4 0.08 0.15 733 733
2.5mm csa
MICC PYRO
Light Duty 12.1 0.19 0.21 500 500
1.5mm csa
MICC PYRO
Heavy Duty 12.1 0.13 0.17 500 500
1.5mm csa

For the zone circuits the maximum cable run allowed is 500m for 1.5mm csa cable.

For the Sounder circuits, the maximum cable run is 500m in a loop for 1.5mm csa cable.

8.2. Field Device Part Numbers & Descriptions


8.2.1. Zone Devices
The zone devices approved for use with the Precept EN13 panel are shown below.
Table 3 – List of approved Zone Devices

Manufacturer Part no. Description Max per


Zone
Series 65 Rate-of-Rise, MAT 50°C, MSRT 65°C A1R - flashing LED
55000-120 32
and magnetic test – 55µA
Series 65 Rate-of-Rise, MAT 50°C, MSRT 65°C A1R - flashing LED
Apollo 55000-121 32
– 55µA
Series 65 Rate-of-Rise, MAT 50°C, MSRT 65°C A1R - Standard –
55000-122 32
45µA
Series 65 Rate-of-Rise, MAT 65°C, MSRT 85°C BR - flashing LED 32
55000-125
and magnetic test – 55µA
Series 65 Rate-of-Rise, MAT 65°C, MSRT 85°C BR - flashing LED 32
Apollo 55000-126
– 55µA
Series 65 Rate-of-Rise, MAT 65°C, MSRT 85°C BR - Standard –
55000-127 32
45µA

PAGE 15 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13

Manufacturer Part no. Description Max per


Zone
Series 65 Rate-of-Rise, MAT 80°C, MSRT 100°C CR - flashing
55000-130 32
LED and magnetic test – 55µA
Series 65 Rate-of-Rise, MAT 80°C, MSRT 100°C CR - flashing
Apollo 55000-131 32
LED – 55µA
Series 65 Rate-of-Rise, MAT 80°C, MSRT 100°C CR - Standard –
55000-132 32
45µA
Series 65 Static, MAT 80°C, MSRT 100°C CS - flashing LED and 32
55000-135
magnetic test – 55µA
Apollo Series 65 Static, MAT 80°C, MSRT 100°C CS - flashing LED – 32
55000-136
55µA
55000-137 Series 65 Static, MAT 80°C, MSRT 100°C CS - Standard – 45µA 32
Series 65 Ionisation Smoke Detector with flashing LED and
55000-215 32
magnetic test switch – 55µA
Apollo
55000-216 Series 65 Ionisation Smoke Detector +flashing LED – 55µA 32
55000-217 Series 65 Ionisation Smoke Detector – 45µA 32
Series 65 Integrating Ionisation Smoke Detector with flashing LED
55000-218 32
and magnetic test switch – 55µA
Apollo Series 65 Integrating Ionisation Smoke Detector with flashing LED
55000-219 32
– 55µA
55000-220 Series 65 Integrating Ionisation Smoke Detector – 45µA 32
Series 65 Optical Smoke Detector with flashing LED and magnetic
55000-315 32
test switch – 55µA
Apollo
55000-316 Series 65 Optical Smoke Detector +flashing LED – 55µA 32
55000-317 Series 65 Optical Smoke Detector – 45µA 32
Apollo 55100-001 Conventional Indoor Manual Call Point without LED Red 32
Apollo 45681-200 Series 65 Standard Base 32
Apollo 45681-201 Series 65 Diode Base 32

ORB-HT- ORBIS Rate-of-Rise, MAT 50°C A1R - Standard – 100µA


11001-APO 24
ORB-HT- ORBIS Rate-of-Rise, MAT 50°C A1R - with flashing LED – 105µA
Apollo 24
11013-APO
OEX-HT- ORBIS Rate-of-Rise, MAT 50°C A1R - with SensAlert – 100µA
11089-APO 24
ORB-HT- ORBIS Static, MAT 50°C A1S - Standard – 100µA
11166-APO 24
Apollo
ORB-HT- ORBIS Static, MAT 50°C A1S - with flashing LED – 105µA
24
11167-APO
ORB-HT- ORBIS Static, MAT 50°C A2S - Standard – 100µA 24
11002-APO
Apollo
ORB-HT- ORBIS Static, MAT 50°C A2S - with flashing LED – 105µA 24
11014-APO
ORB-HT- ORBIS Rate-of-Rise, MAT 65°C BR - Standard – 100µA 24
11003-APO
Apollo
ORB-HT- ORBIS Rate-of-Rise, MAT 65°C BR - with flashing LED – 105µA 24
11015-APO
ORB-HT- ORBIS Static, MAT 65°C BS - Standard – 100µA 24
11004-APO
Apollo
ORB-HT- ORBIS Static, MAT 65°C BS - with flashing LED – 105µA 24
11016-APO

PAGE 16 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13

Manufacturer Part no. Description Max per


Zone
ORB-HT- ORBIS Rate-of-Rise, MAT 80°C CR - Standard – 100µA 24
11005-APO
Apollo
ORB-HT- ORBIS Rate-of-Rise, MAT 80°C CR - with flashing LED – 105µA 24
11017-APO
ORB-HT- ORBIS Static, MAT 80°C CS - Standard – 100µA
24
11006-APO
Apollo
ORB-HT- ORBIS Static, MAT 80°C CS - with flashing LED – 105µA
24
11018-APO
ORB-OP- ORBIS Optical Smoke Detector – 100µA
12001-APO 24
ORB-OP- ORBIS Optical Smoke Detector with flashing LED – 105µA
Apollo 24
12003-APO
OEX-OP- ORBIS Optical Smoke Detector with SensAlert – 100µA
12016-APO 24
ORB-OH- ORBIS Multisensor Smoke Detector – 100µA
13001-APO 24
Apollo
ORB-OH- ORBIS Multisensor Smoke Detector with flashing LED – 105µA 24
13003-APO
ORB-MB- ORBIS TimeSaver Base 24
00001-APO
Apollo
ORB-DB- ORBIS TimeSaver Diode Base 24
00003-APO

SLR-E3 CDX Range optical detector – 35µA 32


Hochiki CDX Range optical detector (physically slightly different to SLR-E3)
SLR-E3N 32
– 35µA
DCD-AE3 CDX Range ROR & Fixed (60°C) heat detector – 35µA 32
Hochiki
DCD-CE3 CDX Range ROR & Fixed (90°C) heat detector – 35µA 32
Hochiki DFG-60BLKJ CDX Range Waterproof Fixed (60°C) heat detector – 0µA 32
DFJ-AE3 CDX Range Fixed (60°C) heat detector – 35µA 32
Hochiki
DFJ-CE3 CDX Range Fixed (90°C) heat detector – 35µA 32
CDX Range IR Flame detector, Quiescent 70µA, Alarm 40mA,
Hochiki DRD-E 7
Surge 320µA
Hochiki YBN-R/6 CDX Range mounting base 32
Hochiki YBN-R/6SK CDX Range mounting base with Schottky Diode 32
Hochiki YBO-R/6R CDX Range latching relay base 32
Hochiki YBO-R/6RN CDX Range non-latching relay base 32
Hochiki YBO-R/6RS CDX Range latching relay base with Schottky Diode 32
Hochiki CCP-E Conventional Call Point (KAC) 470R 32

Nittan EVC-DP Evolution Dual Optical Detector, Quiescent 50µA, Alarm 50mA 20
Nittan EVC-P Evolution Optical Detector, Quiescent 50µA, Alarm 50mA 20
Evolution Optical Detector – Intrinsically Safe, Quiescent 50uA,
Nittan EVC-PY-IS 20
Alarm 50mA
Evolution Heat Detector (54°C to 70°C), Quiescent 50µA, Alarm
EVC-H-A2S 32
50mA
Nittan
Evolution Heat Detector (84°C to 100°C), Quiescent 50µA, Alarm
EVC-H-CS 32
50mA

PAGE 17 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13

Manufacturer Part no. Description Max per


Zone
Evolution Dual Band IR Flame Detector Quiescent 100µA, Alarm
Nittan EVC-IR 10
50mA
Nittan RP-RS-01 STI RESET MCP, 680R/470R selectable 32
Nittan UB-4 Universal Mounting Base 32
Nittan UB-4-IS Universal Mounting Base-I.S. 20

MCP1A- MCP, no LED, Red, 470R series resistor, Surface mount, Flexible
R470SF- operating element 32
K013-01
MCP2A- MCP, LED, Red, 470R series resistor, Surface mount, Flexible
R470SF- operating element 32
K013-01
KAC
MCP2A- MCP, LED, Red, 470R series resistor, Surface mount, Glass
R470SG- operating element 32
K013-01
MCP2A- MCP, LED, Red, 470R series resistor, Flush mount, Glass
R470FG- operating element 32
K013-01
MCP1A- MCP, no LED, Red, 680R series resistor, Surface mount, Flexible
KAC R680SF- operating element 32
K013-01
MCP1A- MCP, no LED, Red, 680R series resistor, Surface mount, Glass
KAC R680SG- element 32
C029-01

System Sensor 2351E 300 Series Optical smoke detector – 50µA 20


System Sensor 2351TEM 300 Series Optical & Heat detector – 65µA 20
System Sensor 4351E 300 Series Fixed 78°C (BS) Heat detector – 65µA 20
System Sensor 5351E 300 Series A1R & ROR Heat detector – 60µA 20
System Sensor 5351TE 300 Series Fixed 58°C (A2S) Heat detector – 60µA 20
System Sensor B401R Detector base with resistor for Series 300 20
System Sensor B401RSD Detector base with resistor & diode for Series 300 20
System Sensor ECO1002 ECO1000 A1R & Optical detector – 75µA 15
System Sensor ECO1003 ECO1000 Optical detector – 60µA 15
System Sensor ECO1004T ECO1000 78°C (BS) Heat detector – 75µA 15
System Sensor ECO1005 ECO1000 ROR Heat detector – 70µA 15
System Sensor ECO1005T ECO1000 58°C (A2S) Heat detector – 70µA 15
ECO1000 ECO1000 Base with 470R Resistor
System Sensor
BR
ECO1000 ECO1000 Base with 470R Resistor & Schottky Diode
System Sensor 15
BRSD
ECO1000 ECO1000 Base with 1K Resistor
System Sensor
BR1000

TYCO 516.600.001 601P Optical smoke detector – 65µA 32


TYCO 516.600.002 601PH Optical smoke + Heat detector – 65µA 32
TYCO 516.600.003 601H-R ROR Heat detector – 65µA 32
TYCO 516.600.004 601CH CO + A1R ROR heat detector – 87µA 27
TYCO 516.600.005 601I Ionisation detector – 62µA 32
PAGE 18 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13

Manufacturer Part no. Description Max per


Zone
TYCO 516.600.013 601H-F Fixed 60°C heat detector – 61µA 32
601FEx SB Flame detector, Intrinsically Safe, Quiescent 300uA,
TYCO 516.600.066 2
Alarm 45mA
TYCO 516.052.051 MD601Ex Heat detector A1R (ROR) I.S. – 45µA 20
TYCO 516.052.041 MD611Ex Heat detector A1S (Static) I.S. – 45µA 20
MR601TEx High Performance Optical detector I.S. (Heat
TYCO 516.054.011 6
augmented) – 110µA
TYCO 517.050.023 5BEX 5 inch Universal Ex Base 20
TYCO 517.050.017 5B 5 inch Universal Base 32
TYCO 517.050.600 5BD 5 inch base with diode 32
TYCO 577.001.035 601SB Sounder base 32
TYCO 577.001.037 601SBD Sounder base with diode 32
TYCO 568.001.018 MC600 Relay Base 32
TYCO 514.001.142 MCP200 ALERT (120R/470R) call point 32
TYCO 514.001.110 MCP230 ALERT (120R/470R) call point - weatherproof 32
TYCO 540.003.006 Remote LED 32

MTL MTL5561 2-channel Galvanic Isolator 1

Notes:
1. The FIRECLASS Precept EN13 panel is designed to monitor a composite device made up of a 22µF
capacitor & a 3k9 resistor in parallel as the end-of-line device on the zones. This provides the capability
to detect partial open circuit or partial short circuit on the zone.
2. The maximum quantities per zone listed in the above table are for guidance only and assumes that
different types of detectors are not mixed on the zone. The quiescent current drawn by the detectors is
a typical value and can vary for individual detectors. The current may also be affected by temperatures
outside of the range 23°C ± 5°C, thus reducing the maximum values stated. Each zone should be fully
checked for correct fault monitoring during installation & commissioning.
3. The maximum standby current drawn by devices on a zone must not exceed 2.5mA (not including the
EOL device); otherwise the panel may not detect an open circuit fault at power-up.
4. If the zone is configured as an Intrinsically Safe zone then the end-of- line device must be changed to a
suitable 3k9 resistor. In this case the following limitation must be observed:
 The total current drawn by all devices on a zone must not exceed 1mA (not including the I.S.
barrier) otherwise the panel may not detect a partial fault on the zone wiring. The standby current
drawn by each device will be given in the manufacturer’s datasheet for the device. To calculate the
total number of devices that may be connected to a zone, add up the individual standby current
values for each device and make sure that the total current does not exceed 1mA.
 The maximum number of devices (including Manual Call Points) per zone must not exceed 32,
regardless of standby current.

PAGE 19 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13
8.2.2. Sounders
The sounder devices approved for use with the Precept EN13 panel are shown below.
Table 4 – List of approved Sounder Devices
Max per
Manufacturer Part no. Description Circuit
(see notes)
20-100 6 inch 24Vdc Electronic solenoid bell – weatherproof, 18-30Vdc,
30mA@24Vdc
20-101 6 inch 24Vdc Electronic solenoid bell red, 18-30Vdc,
TYCO 9
30mA@24Vdc
20-111 6 inch 24Vdc Electronic solenoid bell white, 18-30Vdc,
30mA@24Vdc
576.501.060 Banshee Excel sounder, red, 9-30Vdc, 110mA max (Hosiden
Besson)
576.501.061 Banshee Excel sounder, white, 9-30Vdc, 110mA max (Hosiden
TYCO 4
Besson)
576.501.062 Banshee Excel sounder, red, 9-30Vdc, 110mA IP66 (Hosiden
Besson)
576.501.063 Banshee Excel Lite, red sounder, red xenon beacon, 9-30Vdc,
TYCO 3
110mA max +40mA flash
576.501.001 YO3 Yodalarm 3” 24Vdc 100dB @ 1Mtr, 67mA@24Vdc
4
TYCO 576.501.002 YO5 Yodalarm 5” 24Vdc 106dB @ 1Mtr, 67mA@24Vdc
576.501.003 YO8 Yodalarm 8” 24Vdc 112dB @ 1Mtr, 67mA@24Vdc 4
576.501.200 SY/R Low Power Red Symphoni Sounder (3 tone), 6mA max 40
TYCO
576.501.201 SY/W Low Power White Symphoni Sounder (3 tone), 6mA max 40
576.501.202 SYHO/R High Output Red Symphoni Sounder (32 tone), 280mA
1
max
TYCO
576.501.203 SYHO/W High Output White Symphoni Sounder (32 tone),
1
280mA max
ROSHRDSR ROSHNI Sounder c/w deep base – red, 16mA@24Vdc 18
TYCO 576.501.220 ROSHNI Sounder c/w shallow base – red, 16mA@24Vdc 18
576.501.221 ROSHNI Sounder c/w shallow base - white, 16mA@24Vdc 18
576.501.224 Flashni Sounder/Strobe - Red, 68mA@24Vdc
TYCO 4
576.501.227 Flashni Sounder/Strobe, deep base - Red, 68mA@24Vdc
TYCO 576.501.030 Squashni electronic sounder/base - White (9-28Vdc) 29
TYCO 576.501.250 Squashni G3/AV Sounder Beacon, 10mA@24Vdc 29
TYCO 576.501.038 Hosiden Besson Wafer sounder, 9-30Vdc, 30mA max 9

PSS-0003 SONOS electronic sounder (PSS-0001 shallow base + PSS-0084


Klaxon Signals 6
Red Head), 45mA
PSC-0047 SONOS Sounder LED Beacon, red shallow base (PSO-0001) red
Klaxon Signals 5
lens & LED (PSC-0045), 50mA
Klaxon Signals PBS-0003 Base Sounder – White, 17-60Vdc 2-7mA (tone-dependent) 40
Klaxon Signals TAA-0007 6 inch motorised bell, 19-28Vdc, 20mA 14

Fulleon FB/024 Electronic bell, 18-30Vdc, 25-35mA 8


Fulleon RO Roshni Sounder, 9-28Vdc, 16mA Typical (1Hz sweep) 18
Fulleon ROLP Roshni Low Profile Sounder, 9-28Vdc, 16mA Typical (1Hz sweep) 18

PAGE 20 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13
Max per
Manufacturer Part no. Description Circuit
(see notes)
ROLP MAXI Roshni Low Profile Sounder high output, 18-28Vdc, 40mA Typical
Fulleon 7
(1Hz sweep)
ROLP Solista Roshni Sounder Beacon (LED), 9-28Vdc, 19mA Typical (1Hz
Fulleon 15
sweep)
ROLP MAXI Roshni Sounder Beacon (LED) high output, 9-28Vdc, 43mA
Fulleon 6
Solista Typical (1Hz sweep)
Flashni 24V Flashni Sounder Beacon (Xenon), 18-28Vdc, 68mA Typical (1Hz
Fulleon 4
sweep)
Fulleon CS 200 Sounder, 9-28Vdc, 13mA Typical (1Hz sweep) 22
Squashni Squashni Platform (Base) Sounder, 9-28Vdc, 18mA Typical (1Hz
Fulleon 16
sweep)
Squashni Squashni Micro Platform (Base) Sounder, 9-30Vdc, 5.5mA low
Fulleon 19
Micro volume, 15mA high volume
SQ G3 Squashni G3 platform sounder, 18-28Vdc, 5mA Typical (1Hz
Fulleon 58
sweep)
SQ G3 AV Squashni G3/AV platform sounder beacon, 18-28Vdc, 9mA
Fulleon 32
Typical (1Hz sweep)
Fulleon Symphoni Symphoni Ultra Low Current Sounder, 9-28Vdc, 5mA Typical 58
Symphoni AV Symphoni Ultra Low Current Sounder beacon, 9-28Vdc, 10mA
Fulleon 29
(max)
Symphoni HO Symphoni Sounder high output, 9-28Vdc, 240mA Typical (1Hz
Fulleon 1
sweep)
Askari Electronic Sounder, 9-28Vdc, 18mA Typical (1Hz sweep)
Fulleon 16
Compact

PAGE 21 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13
Notes:
1. The FIRECLASS Precept EN13 panel is designed to operate sounders on a loop circuit. This provides
the capability to detect partial open circuit or partial short circuit on the circuit and still provide sufficient
current to operate the sounders.
2. The maximum quantity of sounders per sounder loop will depend on the minimum voltage that the
sounders will operate at and the length of the cable between the sounder and the panel. The voltage
available to the sounders will drop as the distance from the panel increases. The voltage available will
also drop as the load on the sounder circuit increases.
The minimum output voltage is 20Vdc (low battery condition).
Table 4 shows the maximum number of devices which can be connected if the cable loop is 6Ω per core
(500m of 1.5mm csa cable).
A shorter cable loop will allow more devices. For 3Ω per core (250m of 1.5mm csa cable) the number of
devices can be increased by 70%.
A longer cable loop will reduce the number of devices. For 9Ω per core (750m of 1.5mm csa cable) the
number of devices needs to be reduced by 30%. For 12Ω per core (1000m of 1.5mm csa cable) the
number of devices needs to be reduced by 50%.
When a variety of sounders are connected to a single sounder circuit, the total current drawn will
determine the quantity of sounders. The table below shows the amount of current available in order to
provide at least 18Vdc to all sounders. The cable length is the complete loop i.e. the cable goes out to
the furthest device and returns to the panel.
Table 5 – Sounder Loop Cable Resistance & Current
Resistance 1.0mm csa 1.5mm csa 2.5mm csa Current Available Current Available
per Core Cable Length Cable Length Cable Length @18Vdc @18Vdc
(Ω) (Loop) (Loop) (Loop) 2/4 Zone Panel 8/16 Zone Panel
(m) (m) (m) (mA) (mA)
1 55 80 135 500 1000
2 110 165 270 500 690
3 165 250 405 500 500
4 220 330 540 400 400
5 275 410 675 330 330
6 330 500 810 290 290
7 385 575 945 250 250
8 440 660 1080 220 220
9 495 750 1215 200 200
10 550 825 1350 180 180
11 605 905 1485 160 160
12 660 1000 1620 150 150

3. Each sounder loop should be fully checked for correct fault monitoring and operation during installation
& commissioning.

PAGE 22 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13

9. Overview of User Functions


This section gives an overview of the functions available to the end user.
9.1. User Indications
General Indicator Section
Description Colour Operating Condition
Power Supply On Green Illuminates Steady for Mains or Standby power On.
Flashes on any new fire alarm condition, changing to a steady
Fire Red
indication on operation of Silence Alarms.
Fire Routing Active Red Illuminates Steady when the Fire Routing Output is active.
General Fault Yellow Flashes for any fault condition.
Power Supply Fault Yellow Flashes for mains or standby power supply/charge fault
Illuminates Steady to indicate Microcontroller or Memory Failure.
System Fault Yellow
Flashes to indicate Engineer’s Configuration Mode active.
Earth Fault Yellow Flashes for any positive or negative power supply earth fault.
Fuse Fault Yellow Flashes for any auxiliary supply fuse failure
Repeater Fault Yellow Flashes for any Repeater fault or repeater communication fault,
Sounder Fault/Disabled Yellow Flashes for any sounder fault. Steady for sounders disabled.
Sounder Test Yellow Illuminates Steady while sounder walk test is active.
Fire Protection Flashes for a fault on the Fire Protection Output. Steady when Fire
Yellow
Fault/Disabled Protection Output is disabled.
Fire Routing Flashes for a fault on the Fire Routing Output. Steady when Fire
Yellow
Fault/Disabled Routing Output is disabled.
Fault Routing Flashes for a fault on the Fault Routing Output. Steady when Fault
Yellow
Fault/Disabled Routing Output is disabled.

POWER SUPPLY ON
1
FIRE EVACUATE TEST DISPLAY
2
FIRE ROUTING ACTIVE
3
SILENCE/
GENERAL FAULT RESOUND ENABLE 4
ALARMS
POWER SUPPLY FAULT 5

SYSTEM FAULT 6
RESET DISABLE
7
EARTH FAULT
8
FUSE FAILED
SILENCE 9
BUZZER TEST
REPEATER FAULT 10
SOUNDER FAULT/DISABLED 11
DELAY
SOUNDER TEST ON/OFF/ 12
OVERRRIDE
13
FIRE PROTECTION FAULT/DISABLED SELECT
14
FIRE ROUTING FAULT/DISABLED SELECT
ON/OFF 15
FAULT ROUTING FAULT/DISABLED 16

FIRE FAULT DISABLEMENT AND TEST


1. THE RED ZONE INDICATOR 1. DETERMINE THE CAUSE 1. PRESS SELECT ON/OFF.
O I WILL PULSE SHOWING THE OF THE FAULT. THE LED WILL ILLUMINATE.

04:45:34 LOCATION OF THE FIRE.


2. CARRY OUT THE
REQUIRED FIRE DRILL.
2. PRESS SILENCE BUZZER.
3. CALL YOUR SERVICE
ENGINEER.
2. SELECT THE ZONE OR
OUTPUT USING ↑ AND ↓. THE
FAULT LED WILL PULSE.

D/N ON 3. TO SILENCE ALARMS


PRESS SILENCE ALARMS.
4. TO RESET FROM THE FIRE
SYSTEM FAULT
THE PANEL IS INOPERATIVE.
ARRANGE FOR
3. PRESS DISABLE OR TEST.
4. TO RE-ENABLE, SELECT
THE ZONE OR OUTPUT AND
CONDITION PRESS RESET. ALTERNATIVE FIRE PRESS ENABLE.
DETECTIN MEASURES.

Access Controls Keyswitch: Clock Module [Optional]: User Instructions


O – Controls Locked Showing time and Day/Night ON
I – Controls Unlocked Back light flashes for Clock Module fault.
Zone Location Indications
Description Colour Operating Condition
Flashes when zone is in a fire condition, turning to steady on
Red
Detection Zone operation of Silence Alarms.
Location Flashes when zone is in a fault condition. Illuminates steady when
Yellow
zone is disabled or in test.

PAGE 23 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13
9.2. User Controls

POWER SUPPLY ON
1
FIRE EVACUATE TEST DISPLAY
2
FIRE ROUTING ACTIVE
3
SILENCE/
GENERAL FAULT RESOUND ENABLE 4
ALARMS
POWER SUPPLY FAULT 5

SYSTEM FAULT 6
RESET DISABLE
7
EARTH FAULT
8
FUSE FAILED
SILENCE 9
BUZZER TEST
REPEATER FAULT 10
SOUNDER FAULT/DISABLED 11
DELAY
SOUNDER TEST ON/OFF/ 12
OVERRRIDE
13
FIRE PROTECTION FAULT/DISABLED SELECT
14
FIRE ROUTING FAULT/DISABLED SELECT
ON/OFF 15
FAULT ROUTING FAULT/DISABLED 16

FIRE FAULT DISABLEMENT AND TEST


1. THE RED ZONE INDICATOR 1. DETERMINE THE CAUSE 1. PRESS SELECT ON/OFF.
O I WILL PULSE SHOWING THE OF THE FAULT. THE LED WILL ILLUMINATE.

04:45:34 LOCATION OF THE FIRE.


2. CARRY OUT THE
REQUIRED FIRE DRILL.
2. PRESS SILENCE BUZZER.
3. CALL YOUR SERVICE
ENGINEER.
2. SELECT THE ZONE OR
OUTPUT USING ↑ AND ↓. THE
FAULT LED WILL PULSE.

D/N ON 3. TO SILENCE ALARMS


PRESS SILENCE ALARMS.
4. TO RESET FROM THE FIRE
SYSTEM FAULT
THE PANEL IS INOPERATIVE.
ARRANGE FOR
3. PRESS DISABLE OR TEST.
4. TO RE-ENABLE, SELECT
THE ZONE OR OUTPUT AND
CONDITION PRESS RESET. ALTERNATIVE FIRE PRESS ENABLE.
DETECTIN MEASURES.

Access Controls Keyswitch:


O – Controls Locked
I – Controls Unlocked

Switch Functionality Button Availability


Operates all sounders continuously and lights the RED LED next to the
Evacuate When controls are unlocked
button until the Silence/Resound Alarms button is operated
When the sounders are operated, 1st press stops sounders. If a zone
Silence is in fire, the General Fire LED and the Zonal fire LED will change from
When controls are unlocked
Resound Alarms flashing to steady. 2nd press restarts the silenced sounders if a zone is
in fire.
When controls are unlocked and [if
Clears the panel display, resets the zones, outputs and operates the
Reset silence before reset is configured]
reset relay.
sounders are silenced.
1] Press to stop the buzzer sounding in fire or fault conditions. Always available.
Silence Buzzer 2] In 2-Stage Delay Mode, with stage 1 delay running, press to start When the panel is in the fire
stage 2 delay otherwise all delayed outputs operate when Stage 1 condition and the delay is running.
timer times out.
1] Press once to Enable the delay mode, lighting the adjacent delay on 1] When controls are unlocked and
Delay LED. Press again to disable the delay mode and turn off the LED delay period is not zero.
On/Off/Override 2] Overrides the delay when delay is running. All delayed outputs will 2] When the delay is running.
operate immediately.
Enables the USER SELECT feature [ Select ↑, Select ↓] for selection of
Select On/Off zones or outputs for disablement/re-enablement & Day/Night On/Off When controls are unlocked
selection and setting current time on Clock Module if fitted.
Press to illuminate all LEDs on the display and operate the buzzer. All
Test Display indications remain active for approx 5 seconds. Also displays alarm Always available
count on Clock Module if fitted.
When controls are unlocked, the
Press to clear the disablement or test condition on a zone or output Select switch has been operated
Enable
selected via the User Select feature. and a zone or output has been
selected.
Disable Press to disable a zone or output selected via the User Select feature. As above.
Press to initiate the One Man Test on sounders or zones as selected
Test As above.
via the User Select feature.
Used to scroll the cursor indication through the zone and output fault
When controls are unlocked and
LEDs on the display to select a zone or output for disablement,
Select ↑ Select ↓ the Select switch has been
enablement or test. [LED illuminated when Select Mode is active]. Also
operated.
scrolls through Clock Module menu when fitted.

PAGE 24 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13

9.3. Selection of Detection Zones or o A fire condition on a zone in Test Mode will not
operate any of the fire outputs other than any
Outputs for Disablement, sounders configured to respond to the zone
Enablement or Test fire.
The panel provides a simple and straightforward o The panel will respond normally to a fire
means for selecting the sounder outputs and/or condition on any zone not selected to the Test
zones which are to be disabled, re-enabled or set to Mode.
the test mode. The Fire Routing output, Fire o Sounders can be configured not to respond to
Protection output and Fault Routing output can also a detector test or to operate for 5 seconds and
be individually disabled and enabled. then automatically silence.
The zone or output is selected using the Cursor o A Zone Test Fire condition will operate the
Select feature. This allows the User to move a sounders in accordance with the panel
flashing cursor indication up or down through the configuration - i.e. either:
yellow fault LEDs associated with the available
zones and outputs until the required zone or output  Zonally - only the sounder group
is highlighted. The yellow LED for the selected associated with the actual detection zone
zone/output flashes in “Cursor” mode, which is being tested, or
easily distinguishable from all other indications.  Generally - all sounder groups operate.
With the cursor flashing on the required o After each test the panel and the device being
zone/output, pressing the Disable button disables tested is automatically reset allowing the next
the zone/output. Pressing the Enable button re- device to be tested without needing to return to
enables the zone/output. Pressing the Test button the panel to silence and reset.
initiates the test condition. [Note: Fire Routing
o If a fire condition occurs on any zone other
output, Fire Protection output and Fault Routing
than a zone in test mode, the panel responds
outputs cannot be placed in test condition].
fully to the fire condition as per its normal fire
9.4. Disablement/Re-enablement of response and configuration.
Detection Zones and Outputs 9.6. Alarm Sounder One man Test
Any or all of the zones can be disabled. The One Man Sounder Test operates all sounders
The panel will not enter the fire alarm condition if a intermittently until the Test mode is manually
fire detection device operates on a disabled zone. cleared. This allows the Engineer to walk the
Similarly, the panel will not enter the fault condition installation and confirm the operation of all
if a fault occurs on a disabled zone. The fire panel sounders. The sounder on/off cycle is 2 seconds on
will respond normally to fire device operations and and 15 seconds off to allow operation to be
wiring faults on all enabled zones. confirmed without being too intrusive for other
The following outputs can also be individually occupants.
disabled & enabled: A genuine fire alarm condition overrides the test
o All Sounder circuits. mode and operates the sounders normally.
o The Fire Routing output. 10. Overview of Engineers
o The Fire Protection output.
Functions
o The Fault Routing output.
A disabled output is prevented from operating This section provides an overview of the functions
under any circumstances. available to the engineer.

9.5. Detector Zone One man Test. 10.1. Engineer’s configuration process
When selected to the One Man Test condition, Most of the Engineer’s configuration facilities are
devices connected to the zone can be operated for controlled by DIL switches located on the
test purposes without operating the Fire Routing or motherboard accessed by opening the panel door,
Fire Protection outputs. The zone[s] to be set to the each configuration feature having its own dedicated
One Man Test condition are selected using the DIL switch.
Cursor Select feature described in 9.3 above. With 10.1.1. Zone/Output Delay Configuration
the cursor flashing on the required zone, pressing
the Test button initiates the zone test. Pressing the Having selected the DIL switch for configuring the
Enable button or pressing the Test button again delay zones or the DIL switch for configuring
clears the test condition and restores normal delayed outputs, the actual selection of the
operation to the zone. zones/output is carried out on the panel display
using the yellow zone [or output] fault/disabled
The features of the One Man Zone Test condition
LEDs via the Cursor Select feature. This allows the
are:
Engineer to scroll a cursor indication up or down
through the yellow LEDs associated with the
PAGE 25 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13
available zones or outputs until the required zone or connected panels cannot be reset from an alarm
output is selected. The yellow LED for the selected condition.
zone/output flashes in “Cursor” mode, which is A fire detector operation on a zone configured to
easily distinguishable from all other indications. the non-latch fire mode initiates the fire alarm
With the cursor flashing on the required condition on the panel, operates the fire alarm
zone/output, pressing the Enable button applies the sounders, the Fire Routing output and zone outputs
configuration to the selected zone. Pressing the as normal. The Fire protection output can be
Disable button clears the configuration, restoring configured to operate or not to operate via DIL
factory setting. switch 1/1. On clearing of the fire input signal on a
When configuring zones, the cursor can only be non-latch zone the panel will clear the alarm
scrolled though zone LEDs. When configuring indication if no other alarms are present.
outputs the cursor is restricted to Fire Routing, Fire
Protection and Sounder LEDs. 10.3. Delay zone configuration
When a zone configuration or the delay outputs This facility is used along with the other delay
configuration feature is initiated, all standing fire configuration features listed below [see 10.5 below]
alarms are reset, all fault/disablement/test to tailor the Panel Delay operation to the needs of
indications are inhibited and the current the protected premises. Each zone can be
configuration is indicated on the fault/disabled LEDs independently configured to Delay Mode. Delay
on the display for the appropriate zones or outputs. zones would normally be used to monitor automatic
The panel is not able to respond to any fire or fault fire detectors. A fire condition on a delay zone will
alarm. indicate the fire alarm audibly and visibly on the
panel, operate any non-delayed outputs and start
10.1.2. Factory Default Configuration the time delay function.
The factory default configuration for the zones 10.4. Standard or Intrinsically Safe zone
and delayed outputs can be restored by selecting
When configured to the Standard Mode the fire
the configuration DIL switches for each of the zone
and fault trip thresholds for the zone being
and output delay configuration features to ON then
configured are set within the panel software to the
pressing the Disable switch on the display and
normal values and are compatible with the
finally setting the configuration switches back to the
detection devices shown in section 8. This is the
OFF position.
factory set condition.
10.1.3. Other Configurable Features When configured to the Intrinsically Safe Mode
All other configurable features involve either setting the fire and fault trip thresholds for the zone being
the appropriate DIL switch to ON or OFF or configured are adjusted within the panel software to
removal/replacement of jumpers on the allow use with I.S barriers. The fault monitoring is
motherboard. configured to the passive mode suitable for use
with end of line resistors only.
10.2. Configurable Detection Zones Note: Removal of a detector will be reported as
Display-based Select/Cursor configuration process a fault but will not allow the detection of a fire
allowing each detection zone to be individually condition on any device connected between the
configured to one of the following types: removed device and the end of line terminator.
o Latching or non-latching fire zone. Warning: Use of capacitors on Intrinsically Safe
o Delay or non-delay zone. circuits is dangerous and is not allowed.
o Standard or Intrinsically Safe zone. 10.5. Short circuit fire configuration
o Short circuit gives fire indication. Factory default configuration:- short circuit on the
Factory default: All zones as latching fire, non- zone wiring raises a fault warning.
delay, standard [non- intrinsically safe and non When configured to the short circuit fire mode, a
short circuit fire mode]. short circuit across the zone wiring initiates the fire
Note: The DIL switch labelled “Configure M.S. alarm condition.
Zones” is used on the Precept EN13 panel to
configure the zones to short circuit fire mode. 10.6. The Delay mode feature
Latching fire configuration- This is the normal This comprises three configurable elements to
operating configuration and is used when fire allow the panel to be configured to delay the
detectors and manual call points are connected to operation of three types of outputs in response to a
the zone wiring. fire alarm condition triggered by a zone configured
as a delay zone.
Non-latching fire configuration - Provided to
allow users to link panels together via the Fire 10.6.1. Configure Delay Zones
Protection relay and non-latching zone without
Zones can be configured as delay or non-delay.
causing a system latch-up state, where the
Fire detectors would normally be connected to
PAGE 26 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13
delay zones and manual call points to non-delay o Zonal sounders operate continuously - all other
zones. [See 10.3 above]. sounders operate in pulsed mode until
silenced.
10.6.2. 1-2 Stage Delay
The delay can be set up as either a Single or 2-
10.9. Inhibit Fire Protection on Non-
stage delay. Latched Zone
 Single stage: 1-10 minutes selectable duration Selects Fire Protection relay to operate or not to
in 1-minute steps. operate for a fire condition on any zone configured
to non-latched mode. This feature has been
 2-stage: Delay 1 = 1-minute fixed delay. Delay provided to allow two panels to be linked so that a
2 = 0-9 minutes [duration selectable as fire condition on one panel triggers a fire on a zone
described above]. on the other panel and vice versa without latching
Operation of the Buzzer Silence button before up. The zones used to monitor the signal from the
delay 1 ends will immediately start delay 2, other panel should be configured to non-latching
otherwise all delayed outputs will operate after and the Fire Protection relay should be used to
delay 1 ends. transmit the fire signal.
10.6.3. Selection of outputs to be delayed 10.10. Delay Alarm Silence and Reset
o The Delay Mode can be applied independently Prevents alarms being silenced and panel reset for
to each or all three of the outputs listed below: a period of 3 minutes after a fire alarm condition
 Fire Alarm Routing Output. occurs.
 Fire alarm sounders. 10.11. Alarms on Evacuate Only
 Fire Protection Output[s]. Selects sounders to operate only when the panel is
No other outputs can be delayed. The factory in the evacuate condition.
default:- No outputs delayed. 10.12. Silence Before Reset
o Operation of a fire detector or manual call point
Selects type of reset mode:
on any “non-delay” zone overrides the delay
and immediately operates all delayed outputs. o Reset available when panel is in the [un
silenced] fire or fault condition, or
o The panel display includes a Delay
On/Off/Override button allowing the User to o Fire Condition Reset is available only when
enable/disable the delay mode or, if the delay panel is in the Alarm Silenced condition. Fault
is running, to override it, immediately operating reset is available when panel is in the fault
the delayed outputs. condition.

10.7. Selectable Zonal or General Alarm 10.13. Silent Zone Test


Sounder operation Select sounder response in One Man [Detector]
Test Mode:
Selects the sounders to:
o Normal sounder response [continuous or
o General Alarm Mode [all sounders operate for
pulsed in line with panel configuration), or
any fire condition] or
o Silent [no sounder operation].
o Zonal Alarm [in conjunction with the Pulse
Non-Alarm Zones switch] 10.14. Buzzer Disable
The standard sounder circuits on the 2 and 4 Enable/disable the internal panel fire/fault buzzer.
zone panels can be used in General or Zonal
modes. On the 8 and 16 zone panels, these 10.15. Latched Faults
sounder outputs always operate in the General When enabled, all fault conditions latch until the
mode regardless of the setting on the Reset switch is operated.
general/zonal alarms configuration switch. The
A latched zone fault will be cleared if a fire condition
output expansion system provides additional
occurs on the same zone.
sounder circuits for General or Zonal use on
the 8 and 16 zone panels. 10.16. Repeater Configuration
10.8. Pulse Non-Alarm Zones The panel can be configured to communicate with
up to 5 remote indication panels via DIL switch
Selects the type of zonal sounder alarm response
selection on Repeater Interface Board.
to a fire when the Zone Alarms feature described
above is selected. The two selectable options are: 10.17. Output Relay Configuration
o Zonal sounders for zone in the fire condition The Fire Routing, Fire Protection and Fault routing
operate continuously until silenced. All others output relays are individually link-configurable on
are silent. the motherboard, providing one of the following
options for each output:
PAGE 27 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13
o Volt-free change over relay output suitable for from the main panel. The repeater uses the same
switching a maximum of 1A at voltages up to motherboard as the fire alarm panel although some
30Vdc. of the components are depopulated. Up to 5
o Fault-monitored 28Vdc powered output repeaters can be connected to a single panel using
suitable for operating remote relays complying an RS485 serial connection. A C1631 repeater
with the following requirements: interface module needs to be fitted to connector
J13/J9 located centrally towards the right-hand
Field relay spec: Coil resistance - 2.6kΩ to
edge of C1627 motherboard on the fire alarm panel
4.5kΩ. Operating Voltage 24Vdc Nominal [min
and also on the repeater motherboard.
18V, max 30V], fitted with a suppression diode.
Note: The disable/enable/test facilities and the
10.18. Earth Fault monitoring. configuration functions are not available at
For installations where earth fault monitoring is repeaters.
unsuitable, it can be disabled by removal of link J18
in the bottom right hand corner of the C1627 12. Circuit Connection Details
motherboard. See Figure 9 for panel field connections.
11. Panel Repeaters
Precept EN repeaters duplicate the panel
indications and user controls at a location remote

Figure 9 – C1627 Motherboard Field Termination


Inputs: Outputs:
SIL = Silence alarms DIS = Disablement active
EVAC = Evacuate EVAC = Evacuation active
RST = Reset BUZ Active = Buzzer active
Panel Grey fill indicates I/O available on selected panel
2
4
8
16
Inputs Outputs Repeater
Class change

Aux

Reset N/C
Buz Active
Zone O/Ps Zone Circuits Alarm Circuits
DC
EVAC

1 2 3 4 5 6 7 8 1 2 3 4
EVAC

GND
RST

DIS
24V

SIL
0V

1 2 3 4 + - + - + - + - + - + - + - + - + - + - + - + - A B
Lower
terminal tier

Upper
terminal tier
+ - + - + - + - + - + - + - + -
O/+

C/+

C/+
24 V
0V

P
C/-

P
O/-

P
O/-

N/O
P

9 10 11 12 13 14 15 16
Zone Circuits Aux Fault Fire Fire Reset
Panel DC Routing Routing Protection
O/- = Normally Open or -ve
2
O/+ = Normally Open or +ve
4 P = Pole
C/+ = Normally Closed or +ve
8 C/- = Normally Closed or -ve
16
Grey fill indicates I/O available on selected panel

PAGE 28 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13
12.1. Auxiliary Supply circuit and therefore the total load across both sets
of terminals must not exceed the rated value.
An auxiliary DC supply is available to power
external field equipment from the panel. This is Note: If equipment draws current from the
nominally rated at 27.1Vdc but varies due to auxiliary supply during the mains failed
temperature changes and also during mains failed condition, this must be included in the battery
conditions. See section 15 below for details of capacity calculations.
maximum load.
12.2. Fire Routing, Fire Protection and
The output is fused using an electronic device and Fault Routing Outputs
fuse activation will be indicated as Fuse Failed on
the panel display. The fuse can be reset after These outputs are factory-set to the fault monitored,
removal of the fault by operating the Reset button powered mode of operation but can be configured
on the display. at site to volt-free relay outputs [See 10.17 above].
Connection details for both types of configuration
The auxiliary supply terminals are labelled Aux DC
are provided in Figure 10.
0V and 24V. Although two sets of terminals are
provided, they are both protected by the same fuse

Figure 10 – Fire Routing, Fire Protection and Fault Routing Connections.

Panel Wiring Field Wiring


Monitored/Powered Output conditions:
O/-

For Fire Routing & Fire Protection O/Ps: P


Quiescent: 5Vdc
Active [fire]: 24Vdc [nominal]
C/+ Field relay specification:
Coil resistance - 2.6kΩ to 4.5kΩ
Voltage 24Vdc Nominal
C/- [min 18Vdc, max 30Vdc]
Fitted with suppression diode as
For Fault Routing O/P: shown.
P
Quiescent: 24Vdc [nominal]
Active [fault]: 5Vdc
O/+

Volt-Free Changeover Relay O/-


Output conditions:
For Fire Routing & P Connect to normally open or normally
Fire Protection O/Ps: closed contact as required.
Shown in quiescent Applied voltage must not exceed 30Vdc.
[de-energised] condition. C/+

C/-

For Fault O/P: P Connect to normally open or normally


Shown in healthy [energised]
condition. closed contact as required.
O/+
Applied voltage must not exceed 30Vdc.

Note: Terminals are dual marked for monitored/powered and volt-free configurations.
For volt-free: O = Open, C = Closed, P = Pole
For monitored/powered: + = Positive, - = Negative

Warning: The volt-free auxiliary relay contacts must not be used to directly switch any voltage that
exceeds 30Vdc.

PAGE 29 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13
Figure 11 – Reset Relay Contact Connection Figure 13 – Alarm Circuit Configuration
details
Panel Wiring Field Wiring Alarm Out +
N/O
Polarising
diode
Volt-Free Changeover [1N4002]
Relay Configuration
Output conditions:
Suppression
For Reset Relay P
Shown in quiescent diode
[de-energised] condition. [1N4002]

Bell Electronic
N/C
sounder
Alarm Out -
Warning: The volt-free auxiliary relay contacts
must not be used to directly switch any voltage
that exceeds 30Vdc.
Alarm Return +
12.3. Use of Auxiliary Inputs Polarising
diode
Auxiliary inputs are provided to allow remote [1N4002]
operation of the following functions:
 Class Change. Suppression
diode
 Remote Evacuate.
[1N4002]
 Remote Silence.
 Remote Reset. Bell Electronic
sounder
To activate an input, 0Vdc should be connected
across the input circuit via a normally open contact Alarm Return -
arranged to close. [See Figure 12]
Figure 12 – Auxiliary I/P Connection Detail The voltage drop on each alarm circuit should be
calculated to ensure that the minimum voltage at
Panel Wiring Field Wiring the end of each circuit exceeds the minimum
required by each sounding device.
Sil, Evac, Reset The voltage at the end of the circuit is given by:
or Class External normally open
switch or relay contact, VAmin = VOmin- (IA x 2 x L x RC)
Change
closing to activate I/P VAmin = Minimum Alarm Voltage
VOmin = Minimum Output Voltage**
Aux DC
IA = Alarm Current in Amps
0V
L = Alarm Circuit Loop Length in metres
RC = Cable resistance (Ohms per metre)
Note: To prevent unauthorised operation of the
system, any manually operated auxiliary input ** Min O/P voltages:
must be operated by a key-switch. The key to Precept EN13 8 and 16 = 19.2V
the switch should be held with the panel’s Precept EN13 2/4 = 19.2V
access control key. The resistance per metre is as follows:
2
12.4. Sounder Circuits 1.5mm - 0.015 per metre per core
2
Precept EN13 2-zone panels have 2 sounder 2.5mm - 0.009 per metre per core
circuits rated at 0.5 Amps. 4-zone panels have 4,
each rated at 0.5 Amps. The 8 &, 16 zone panels
have 4 sounder circuits each rated at 1A. The
circuits are reverse-polarity monitored for open and
short circuit faults. To allow monitoring, all devices
must be polarised. To prevent damage to the
control panel, bells must also have a suppression
diode fitted as shown in Figure 13. Each circuit
must be wired in a loop.

PAGE 30 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13

13. Electrical Design of Detection A jumper and DIL switch are provided on the clock
module PCB to allow one of the following modes of
Zones operation to be set:
To allow the panel to correctly monitor for fault i. Day/Night Delay Time
conditions, the wiring for each zone must be ii. Day/Night Delay Time and Alarm Counter.
installed as a continuous pair with no spurs or tees st
iii. Time of 1 fire alarm.
and be terminated with an end of line device which st
consists of a 22F 35V capacitor and a 3k9 0.25W iv. Time of 1 fire alarm and Alarm Counter.
resistor as shown in Figure 14. For intrinsically safe The module is fitted to the rear of the display PCB,
zones only a 3k9 0.25W resistor is used. Correct inside a break-out window. Two DIL pin headers
polarity must be strictly observed throughout. fitted to the rear of the display PCB provide all
electrical connections. The module has a 2-line 8-
Figure 14 – Zone wiring Details character alphanumeric backlit LCD.
The clock module must be used with the “fully
Panel Field Wiring insertable” display overlay which has a clear
window through which the LCD can be viewed. A
tab on the end of the User Instruction insert
Zone + Out + normally blanks off the window. This tab must be
In + Out + removed before the insert is fitted, to expose the
In + 22uF & 3k9
Clock Module Display.
EOL fitted in
In - last device 14.1. Clock Module Functionality
In - Out -
Out - 14.1.1. Alarm Counter
Zone -
MCP Detector Complying with the requirements of EN54-2 clause
7.13, recording the number of times the panel
enters the fire alarm condition.
13.1. Maximum Number of Devices on a The current count can be displayed (via Test
Lamps) or reset to zero manually when required.
Zone
The maximum number of devices supported by a 14.1.2. Day/Night Delay Mode control
zone depends on the quiescent current drawn by This allows the delay mode to be automatically
each device and the length of cable on the zone. controlled by the clock module. It can be configured
Intrinsically safe zones will support less devices to operate in one of two modes via a DIL switch on
than normal zones. The quiescent current will be the control panel motherboard (DELAY ON AUTO):
listed on the device data sheet provided by the
DIL SW OFF - Automatically turns off the delay
device manufacturers. See section 8 for more
mode once a day at a set time [the delay mode
details.
first being turned on manually].
For non-intrinsically safe zones, the maximum
DIL SW ON - Automatically turns the delay mode
current available is 2.5mA.
on once a day and off once a day at set times.
For intrinsically safe zones, the maximum current
available is 2mA. 14.1.3. 1st Fire Alarm Time
Note: To comply with BSEN 54-2, the maximum This displays the time of the first fire alarm. This
number of devices per zone is limited to 32 condition is latched until the panel is reset and is
and the maximum number of devices not updated by any subsequent fire alarms [i.e. fire
connected to a panel is limited to 512. alarms which occur while the first alarm is still
Intrinsically Safe Zones displayed].
Warning: I.S zone wiring and equipment 14.2. Clock Module Edit Facility
installation must comply with the installation
guidelines provided with the I.S. fire detection The Clock Module has a simple edit feature to
equipment and the I.S. barrier. Any zone on allow:
which I.S. equipment is to be connected must  Set time of day [User accessible].
be configured as an I.S. zone. [See 10.4  Selection of Day/Night delay mode on/off
above]. [User accessible].
14. C1651 Clock/Timer Module  Set daily delay mode on/off times [Engineer
accessible].
The LCD clock/Timer module is an optional feature
for the Precept EN13 range of panels, providing the
Alarm Counter and Day/Night Delay Time features
described elsewhere in this document.
PAGE 31 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13
14.2.1. User Control/Editing Setting the time of day at which the clock module
automatically turns the delay mode on/off is set
When the Clock Module is fitted, the User has using the Clock Module menu system as described
access to select the status of the Day/Night Mode - in the FIRECLASS Precept EN13 Installation and
either ON or OFF and to set the current time. These Commissioning Manual. Access to these extra
edit features are accessed by operating the Access menu pages is protected by a DIL switch on the
key switch, pressing the Select button and using rear of the Clock Module PCB.
the Select ↑ Select ↓ buttons to scroll the cursor
indicator through the selectable LEDs until the A jumper and DIL switch are provided on the clock
Clock Module is selected [Clock Module back light module PCB to allow one of the following modes of
lit]. operation to be set:
i. Day/Night Delay Time
14.2.2. Engineer’s Editing and
ii. Day/Night Delay Time and Alarm Counter.
Configuration
iii. First Fire Alarm Time.
Editing: Manual selection of the Day/Night Mode
iv. First Fire Alarm Time and Alarm counter.
and setting the current time is described in the
FIRECLASS Precept EN13 Installation and 14.3. C1651 Clock Module PCB Features
Commissioning Manual. Figure 15 llustrates the PCB controls on the Clock
Configuration: Module.

Figure 15 – C1651 Clock Module PCB

LK1 – Select
Operating Mode
Connections to Panel
Display Board LK1
J1

J2
J3

S1
WP
1

ON

ZERO
2

DIL Switch S1 – Select


Configuration Mode,
Reset/Disable Alarm
Counter

PAGE 32 of 42
Typical Zone Wiring
22uF capacitor & 3k9 resistor end-of-line
device. Observe polarity

+ - Typical Input Circuit Wiring for


Remote Silence, Evacuate,
+ 1A 2A - Reset & Class Change
Normally open switch contacts Typical Ouput
ISSUE No. & DATE: 0

Manual call point Circuit wiring


with 680R resistor for Disabled,
Evacuate,
+ 1 2 - Buzzer Active
EQUIPMENT: FIRECLASS

2k2 0.5W
24/04/13

Typical zonal resistor


output wiring Detector base with
Schottky Diode
PUBLICATION: FIRECLASS PREC

24Vdc
-
relay
+ Alarm Circuits wired to
Connect to Alarm Relay Board. Repeater Wiring.
EN13 APP

Aux DC 24V See Alarm Relay Board See Repeater


PRECEPT EN13

Wiring Diagram connection diagram

Lower Lower
1 2 3 4 1+ 1- 2+ 2- 3+ 3- 4+ 4- 5+ 5- 6+ 6- 7+ 7- 8+ 8- 1+ 1- 2+ 2- 3+ 3- 4+ 4 - 24V 0V Sil Evac RST Cl/C Dis Evac BAct A B GND N/C

PAGE 33 of 42
terminal terminal
Zone O/Ps Zone Circuits Alarm Circuits Aux DC Inputs Outputs Repeater RST
tier tier
Upper Zone Circuits Aux DC Fault Routing Fire Routing Fire Protection RST Upper
terminal 9+ 9 - 10 + 10 - 11 + 11 - 12 + 12 - 13 + 13 - 14 + 14 - 15 + 15 - 16 + 16 - 24V 0V O/+ P C/- C/+ P O/- C/+ P O/- P N/O terminal
tier tier
Fire Routing, Fault Routing & Fire Protection Outputs Specification: Fire and Fault Routing
When configured as When configured as output wiring shown
Relay fitted locally for the monitored/
Figure 16 – Typical Panel Connection Diagram

monitored/powered outputs: volt-free changeover relays :


to fault routing powered configuration
For Fire Routing For Fire Routing and Fire Protection O/Ps: equipment
& Fire Protection O/Ps: Volt free relay contacts shown in quiescent Relay fitted locally
Quiescent: 5Vdc [de-energised] condition. to fire routing
Active [fire]: 24Vdc nom] equipment
For Fault O/P:
For Fault Routing O/P: Volt free relay contacts shown in healthy Field relay spec:
Quiescent: 24Vdc [nom] [energised] condition. Coil resistance – 2.6k to 4.5k Ohms
Active [fault]: 5Vdc Voltage 24Vdc Nom
Connections: [min 18V, max 30V]
Connections: Connect to normally open or normally closed Fitted with suppression diode as shown.
Observe correct polarity. contact as required.
[+ = Positive, - = Negative] [P= Pole, C= Closed, O = Open]
Applied voltage must not exceed 30Vdc.
WRITTEN BY: RKP
CHECKED BY: AJC
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13
Figure 17 – Typical Alarm Circuit Connection Diagram

Typical Alarm Circuit Wiring

Sounder Circuits are


+ -
wired as a loop
+ -

Each Alarm circuit from the panel motherboard is + -


connected to the IN terminals on the Alarm Relay
Board.
+ -
Each Alarm Circuit is wired out to the sounders
from the OUT terminals and the circuit is looped
back into the RETURN terminals. No EOL resistor
is required because this is already fitted on the
Alarm Relay board on the RETURN side. + -

+ -

Pre-wired cables from + -


Panel motherboard

+ -

1 2 3 4

1 2 3 4 IN 1

1 2 3 4 IN 1
OUT

1 2 3 4 OUT 1
RETURN

C1717 Alarm Circuit RETURN


Relay Board C1717 Alarm Circuit
Terminal Layout Relay Board
Field Connections

PAGE 34 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13

15. Mechanical, Electrical & Environmental Specification


Mechanical Panel Repeater (AC powered)
Specification 2/4 zone 8 zone 16 zone 2, 4, 8 & 16 zone
Size [mm]
Height: 370 370 370 370
Width: 325 325 325 325
Depth: 126 126 126 126
Weight excluding
6.8Kg 7.2Kg 7.2Kg 6.65Kg
batteries:

Mains Input Panel Repeater (AC powered)


Specification 2/4 zone 8 zone 16 zone 2, 4, 8 & 16 zone
Maximum Input
85W 165W 165W 85W
Power:
Protection:
[Warning: Replace T3.15A T3.15A
T1A T1A
only with identical H250V H250V
H250V H250V
type & rating of [3.15A anti- [3.15A anti-
[1A anti-surge] [1A anti-surge]
BEAB or VDE surge] surge]
approved fuse]
Voltage: 230Vac +10%/-15%
Cable 2
Minimum of 1mm copper protected by a 5A fuse.
requirements:

Power Supply Panel Repeater (AC powered)


Output
2/4 zone 8 zone 16 zone 2, 4, 8 & 16 zone
Specification
Maximum Short
Term Current
1.5A 3A 3A 1.5A
Output
(I max b)
Maximum
Continuous Current
0.6A 2A 2A 0.6A
Output
(I max a)
Minimum Output
N/A
Current
(PSU is integrated into the motherboard)
(I min)
Voltage Output,
26.9 - 28.0V (27.3V nominal, temperature dependent)
Mains On
Maximum Current
Output, Mains 1.5A 3A 3A 1.5A
Failed
Voltage Output,
Mains Failed 20.0* - 28.0V 20.0* - 28.0V 20.0* - 28.0V No Auxiliary Output Provided
[* at full load]
Max Ripple
including switching
spikes[full 200mV peak to peak
load/battery
disconnected]
Output Voltage
Factory Set
adjustment
Output protection: Electronic current limiting
Common fault
N/A (PSU is integrated into the motherboard)
output:
Mains failed fault
N/A (PSU is integrated into the motherboard)
output:

PAGE 35 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13
Panel Repeater (AC powered)
Battery Specification
2/4 zone 8 zone 16 zone 2, 4, 8 & 16 zone
Battery charger output:
[Temperature
compensated float
charger]
1.5A 3A 3A 1.5A
28.0V 0.1V@-5C
(21k Thermistor input)

26.9 V0.1V@ +40 C


(2k66 Thermistor input)
Maximum internal
resistance of battery &
charger circuit: 1Ω 0.6Ω 0.6Ω 1Ω
(Ri max)
Battery type:
2 off 2 off 2 off 2 off
POWERSONIC
PS12120 PS12120 PS12120 PS1230
[Warning: Replace only [12V 12Ah] [12V 12Ah] [12V 12Ah] [12V 3.4Ah]
with identical battery]
Battery size (mm):
W
L = 151 L = 151 L = 151 L = 133
W = 98 W = 98 W = 98 W = 67
H = 94 H = 94 H = 94 H = 60
HT H
HT = 100 HT = 100 HT = 100 HT = 66
L

Battery circuit protection:


F2AL250V F5AL250V 20mm F5AL250V 20mm
[Warning: Replace only F2AL250V
20mm fast blow fast blow glass fast blow glass
with identical type & 20mm fast blow glass fuse
glass fuse fuse fuse
rating of fuse]
Mains failed fault battery
55mA 65mA 85mA 40mA
current:
Mains failed alarm battery
90mA 100mA 120mA 75mA
current:

Environmental
All Panels & Repeaters
Specification
Operating temperature: -5ºC to 40ºC
Operating humidity: 5% to 95%

PAGE 36 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13

16. Precept EN13 Input & Output Specification


Panel
Detection zone Inputs
2 zone 4 zone 8 zone 16 zone
Quantity 2 4 8 16
Conventional open and short circuit fault monitored.
Threshold current- Normal configuration:
Short circuit threshold: ≥ 57.85mA.
Evacuate Manual Call Point alarm threshold: ≥ 37.92; <57.85mA.
Detector/Alert Manual Call Point alarm threshold: ≥ 10.78; <37.92mA.
Quiescent: <10.78mA.
Open circuit: N/A (active monitoring via capacitor).
Specification
Threshold current- I.S. configuration [Using MTL5061 galvanic isolator]:
Short circuit threshold: ≥ 27.78mA.
Evacuate Manual Call Point threshold: ≥ 20.92; <27.78mA.
Detector/Alert Manual Call Point alarm threshold: ≥ 8.5; <20.92mA.
Quiescent: ≥ 1.63; <8.5mA.
Open circuit: <1.63mA.
Cable requirements Max resistance of circuit loop: 12 Ohms.

Ancillary Inputs 2, 4, 8 & 16 zone Panels


Zonal Fire Outputs for
Open collector, 50mA 30Vdc max input
Zones 1-4
Class Change Input Non- fault monitored. 0 Volt I/P to activate. I/P sensitivity: 0-1k Ohm
Remote Evacuate
Non- fault monitored. 0 Volt I/P to activate. I/P sensitivity: 0-1k Ohm
Input
Remote Silence Input Non- fault monitored. 0 Volt I/P to activate. I/P sensitivity: 0-1k Ohm
Remote Reset Input Non- fault monitored. 0 Volt I/P to activate. I/P sensitivity: 0-1k Ohm
Cable requirements Cable loop resistance <= 1k Ohm
Alarm threshold between 10k Ohm to 70 k Ohm [dependant on circuit] between
Earth Fault I/P
chassis and +ve or -ve line

Outputs 2, 4, 8 & 16 zone Panels


Evacuate [active]
Open collector. 50mA 30Vdc max
Output
Buzzer [active] Output Open collector. 50mA 30Vdc max
Disablement [active]
Open collector. 50mA 30Vdc max
Output
Reset Relay 1 x Volt-free change over rated 1 Amp at 30Vdc
Fire Routing Output
Monitored configuration Quiescent: 2Vdc; Active [fire]: 24Vdc nominal
Field relay spec: Coil resistance - 2.6k to 4.5k Ohms. Voltage 24Vdc nominal [min
18V, max 30V], fitted with suppression diode.

Volt-free configuration 1 x Volt-free change over rated 1 Amp at 30Vdc


Fire Protection Output
Monitored configuration Quiescent: 2Vdc; Active [fire]: 24Vdc nominal
Field relay spec: Coil resistance - 2.6k to 4.5k Ohms. Voltage 24Vdc nominal [min
18V, max 30V], fitted with suppression diode.

Volt-free configuration 1 x Volt-free change over rated 1 Amp at 30Vdc


Fault Routing Output
Monitored configuration Quiescent: 24Vdc nominal; Active [fault]: 2Vdc.
Field relay spec: Coil resistance - 2.6k to 4.5k Ohms. Voltage 24Vdc nominal [min
18V, max 30V], fitted with suppression diode.

Volt-free configuration 1 x Volt-free change over rated 1 Amp at 30Vdc


Cable requirements No special requirements.

PAGE 37 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13

Alarm Circuits 2 zone Panel 4 zone Panel 8 zone Panel 16 zone Panel
Quantity: 2 4 4 4
Maximum Current:
0.5A 0.5A 1A 1A
per circuit
Output Voltage (battery
20- 28.6Vdc
operation):
Output Voltage (mains
28.6- 26.5 Vdc
operation):
Fault Monitoring: Reverse polarity for open and short circuit faults
Protection [Self resetting
0.93A 0.93A 0.93A 1.85A
electronic]
Cable requirements: Use with capacitance & resistance within the specified values. Cable resistance
and current load must allow a voltage at all sounders that is above the minimum
operating voltage of the sounders.

Panel
Auxiliary Supply
2 zone 4 zone 8 zone 16 zone
Maximum Current: 0.5A 0.5A 1A 1A
Auxiliary supply
20–28.0Vdc
(battery operation):
Auxiliary supply
28.0- 26.5Vdc
(mains operation):
Protection:
0.5 A 0.5A 1A 1A
[Electronic]
No special requirements. 1A minimum current rating. Minimum voltage at end-of-
Cable requirements:
line must be above sounding device minimum operating voltage.

Repeater Output 2, 4, 8 & 16 zone Panels


Number of repeaters: 1 to 5
Maximum repeater
2000m
cable length:
Communication
RS485 serial data 9600baud
protocol:
Protection: Electronic, current limited
Cable Type: Two pair RS485 shielded cable (see below)

RS485 Cable Specification


Generic Type: RS422/RS485 data cable.
Conductors: Two pairs plus screen.
Alpha cable: 57602, 58412, 57632, 58802, 58902 PLENUM RATED
Belden cable: 82842, 89842, 88777 PLENUM RATED

PAGE 38 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13

17. Appendix  Open collector outputs for evacuate active,


buzzer active, disablement active, zonal fire
17.1. EN54 Optional Functions with O/Ps for each zone up to zone 4.
Requirements  Remote inputs for remote evacuation, reset and
The Precept EN13 panel has the following EN54-2 silence alarms.
optional functions:  One Man Sounder Test [see 5.2 above].
 Clause 7.8 Outputs to fire alarm devices.  Latching fault mode where all fault conditions
 Clause 7.9 Outputs to fire alarm routing latch until the panel is manually reset.
equipment.  Restore default configuration of zones and
 Clause 7.10 Outputs to Fire Protection outputs.
Equipment.
17.3. Power Supply Load Calculation
 Clause 7.11 Delays to outputs.
The power supply load must not exceed a
 Clause 8.9 Output to fault warning routing maximum identified below
equipment. Panel Max Load
 Clause 10 Test condition. Precept EN13 2/4 1.4 Amps
Precept EN13 8 2.9 Amps
17.2. Ancillary Functions Not Required Precept EN13 16 2.9 Amps
By EN54
The Precept EN13 panel offers several auxiliary To determine the maximum power supply load
functions that are not required/allowed by EN54. perform the following steps:
These are: 1. Look-up the mains failed panel load in alarm.
Enter this value as Ipanel.
 Fire Routing, Fire Protection and Fault Routing
3. Calculate the maximum load on the alarm
outputs can be configured to be volt-free
circuits in mA in an alarm condition. Enter this
change over contacts.
value as Ialarms.
 Detection zones can be configured as non- 4. Calculate the load on the auxiliary supply in mA
latching. in an alarm condition. Enter this value as Iaux.
 Detection zones can be configured for 5. Calculate the maximum power supply load
Intrinsically Safe applications. using the formula below:
 Detection zones can be configured to initiate Ipanel ………mA
the fire alarm condition when a short circuit is Ialarms ………mA
connected across zone wiring [used when
replacing a panel on an older “non-short circuit” Iaux ………mA
monitored system].
 Class change input for operating sounders Ipse = (Ipanel + Iaux + Ialarms )/1000 A
briefly to signal class changes in educational =
institutions. =
 Reset relay to interrupt power supplies to (………)/1000 A
external equipment that needs to be reset along = ……… A
with the Precept EN13 panel (e.g. IR Beam
Detectors). Warning:
This current must not exceed the maximum
 Engineer configurable features for:
power output of the power supply (see section
o To require the silencing of the fire alarm 4.4)
condition prior to enabling the fire alarm Note: A battery and loop calculation
condition reset. spreadsheet is available from your panel
o To inhibit the operation of the Fire supplier to assist in site calculations
Protection Output for a fire condition on a
zone configured as non-latching.
o To inhibit the silencing of fire alarm devices
and resetting of the fire alarm condition for
a period of 3 minutes after a fire alarm
condition occurs.
o To prevent fire alarm devices operating for
any fire alarm condition other than the
Evacuate condition.
o To disable the panel buzzer.

PAGE 39 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13
17.4. Battery Standby Capacity 10. Substitute the values in to the formula below.
Calculation Cmin = 1.25 x ((Tfault x Ifault) + 2 x (Talarm x Ialarm))/1000Ah
This section describes how to calculate the = ……))/1000Ah
minimum required standby battery capacity for the = 1.25 x (…… +2 x (……)/1000 Ah
control panel. To determine the battery capacity, 1.25 x (……)/1000Ah
perform the following steps:
= 1.25 x ……/1000Ah
1. Look-up the mains failed fault battery current.
Enter this value as Ipanelfault. = ……/1000Ah
2. Look-up the mains failed alarm battery current. = …… Ah
Enter this value as Ipanelalarm.
3. Calculate the maximum load on the alarm 11. Select the next highest available battery size.
circuits in mA in an alarm condition. Enter this
Notes:
value as Ialarms and enter this figure in the table.
1. The maximum battery capacities which
4. Calculate the load on the auxiliary supply in mA
can be charged according to BFPSA
in an alarm condition. Enter this value as Iauxfault.
recommendations are:
5. Calculate the load on the auxiliary supply in mA
Maximum
in an alarm condition. Enter this value as Panel
Battery Capacity
Iauxalarm.
Precept EN13 2 and 4 12Ah
6. Calculate the total battery load in fault, Ifault.
Precept EN13 8 and 16 24Ah
7. Calculate the total battery load in alarm, Ialarm.
2. Any battery which cannot be contained
8. Enter the required standby time in hours, T fault. in the panel enclosure must be located
9. Enter the required time in alarm in hours, T alarm. in an enclosure adjacent to the panel.
Ipanelfault = ………mA 3. The FIRECLASS Precept EN13 panels
accommodate internally mounted SLA
batteries as listed below:
Iauxfault = ………mA Maximum
Panel
Battery Capacity
Ifault = [Ipanelfault + Iauxfault] ………mA
Precept EN13 2 and 4 12Ah
Precept13 EN 8 12Ah
Tfault = ………Hrs Precept13 EN 16 12Ah

Ipanelalarm = ………mA
Ialarms = ………mA
Iauxalarm = ………mA
Ialarm = [Ipanelalarm + Ialarms + ………mA
Iauxalarm]

Talarm = hrs

PAGE 40 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13

17.5. Panel Configuration Design Chart


Table 6 – Motherboard DIL Switch Configuration Design/Record
Actual
Switch Position Function
Setting
Off Fire Protection relays operate for a fire condition on any zone.
1-1
On Fire Protection relays operate for a fire condition on any latching fire zone.
Off Silence and reset available as normal.
1-2
On Prevents alarms being silenced or reset for 3 minutes after a fire alarm condition occurs
Off Not used
1-3
On Not used
Off Configuration mode disabled.
1-4
On Zones can be configured to non-latch mode via the Engineer’s Select feature. Table 7
Off Configuration mode disabled.
1-5
On Zones can be configured to Intrinsically Safe monitoring mode Table 7
Off Configuration mode disabled
1-6
On Zones can be configured to “short circuit to fire” mode.
Off Configuration mode disabled
1-7
On Zones can be configured to Delay Mode via the Engineer’s Select feature. Table 7
Off Configuration mode disabled.
1-8
On Configure delayed outputs via the Engineer’s Select feature. Table 8
Off Single Stage Delay Mode.
1-9
On Two Stage Delay Mode.
Off Sounders operate on any fire condition including evacuate.
1-10
On Selects sounders to operate only when the panel is in the evacuate condition
Off Reset available when panel is in the [un silenced] fire or fault condition
2-1
On Fire Condition Reset available only when panel is in Alarm Silenced condition.
Off Delay Duration S/W 2/2 S/W 2/3 S/W 2/4 S/W 2/5
2-2 Delay disabled Off Off Off Off
On
1 min On Off Off Off
Off 2 min Off On Off Off
2-3
On 3 min On On Off Off Mark
4 min Off Off On Off actual
Off
2-4 5 min On Off On Off settings
On 6 min Off On On Off on table
Off 7 min On On On Off
8 min Off Off Off On
2-5 On
9 min On Off Off On
10 min Off On Off On
Off General Alarm Sounder Mode
2-6
On Zonal Sounder Mode
Off Sounders for zones in alarm operate continuously until silenced, all other zones are silent.
2-7
On Zonal sounders operate continuously, all other sounders pulse until silenced.
Off Sounders operate in response to zone one-man test.
2-8
On Sounders do not respond to a zone one-man test.
Off Buzzer enabled.
2-9
On Buzzer disabled
Off Non-latched faults
2-10
On Latched faults.

PAGE 41 of 42
EQUIPMENT: FIRECLASS PRECEPT EN13 WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN13 APP CHECKED BY: AJC
ISSUE No. & DATE: 0 24/04/13
Table 7 – Zone Configuration Design/Record
Zone Zone Configuration
Number Non-Latch Intrinsically Safe Short Circuit = Fire Delay
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

Table 8 – Output Delay Configuration Design/Record


Output Configuration
Output
Delay Non-delay
Fire Routing
Fire protection
Alarm Devices

PAGE 42 of 42

You might also like