Professional Documents
Culture Documents
PAGE 1 of 21
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN OUTPUT EXP MOD INST CHECKED BY: AP
ISSUE No. & DATE: 0 02/03/12
List of Contents
PAGE 2 of 21
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN OUTPUT EXP MOD INST CHECKED BY: AP
ISSUE No. & DATE: 0 02/03/12
2k2 0.5W
resistor
and alarm panels are covered in the FIRECLASS Max current sink into O/P: 60mA
Precept EN manuals mentioned below. Max load on 24V [total for both
NOTE: It is important to read this manual fully +24V O/Ps]: 0.5A
before commencing installation.
+24V
+24V
OP1
OP2
OP3
OP4
OP5
OP6
OP7
OP8
The following supporting documentation is also
available:
FIRECLASS Precept EN Output Expansion
System Application Guide
FIRECLASS Precept EN Panel Application C1633 Open collector output module terminals
Guide
FIRECLASS Precept EN User Manual Figure 2 – C1634 Field Wiring Connections
Wiring Recommendations Relay contact rating: 1A at 30Vdc
Do not exceed
2. Overview of Installation and OP1 OP2 OP3 OP4 OP5 OP6 OP7 OP8
Commissioning Lower
N/O
terminal
This section lists the steps that are taken in tier
installing and commissioning a Precept EN output
Middle
POLE
expansion system. terminal
1. Install all field wiring and equipment tier
Refer to the Installation Guidelines in section
6.2 below Upper
N/C
terminal
Refer to the field device installation manuals
tier
2. Install the panel C1634 Volt free relay output module
Refer to the installation instructions in section terminals [3- tier]
6.2 below Figure 3 – C1635 Field Wiring Connections
Do not connect the field equipment at this
stage. Typical Alarm Typical Remote
Circuit Wiring Relay Circuit
3. Commission the panel 3k9 resistor
Wiring
Refer to section 6. end-of-line
Secondary Earth bar 3 x Enclosure Cable Clip for incoming Mains Warning /
for cable screens fixing holes mains cable Primary Earth Label
Mains
Terminal
Block and
primary Earth
Removable
Connection
Chassis
CHANGE
ACTIVE
ZONE CIRCUITS ALARM CIRCUITS AUX INPUTS OUTPUTS REPEATER
RESET
ZONE OUTPUTS
CLASS
EVAC.
EVAC
BUZ.
RST.
SCN
A
B
DIS.
D.C.
N/O
+ 1- + 2- + 3- + 4- + 5- + 6- + 7- + 8-
SIL.
1 2 3 4
1 2 3 4 + - + - + - + -
Removable
24V 0V
TB1 TB2 TB3 TB4 TB5 TB6 TB7 TB8 TB9 TB10 TB12 TB14 TB15 TB16 TB17 TB18 TB19 TB20 TB21
RL1
RL2
RL3
RL4
RL5
RL6
RL7
RL8
+
9
- +
10
- +
11
- + - + - + -
12 13 14
+
15
- +
16
-
FS6
O/+ P C/-
FAULT ROUTING
C/+ P O/-
FIRE ROUTING
C/+ P O/-
FIRE PROTECTION
N/C P
RESET
Chassis
N/O
ZONE CIRCUITS
I/O EXPANSION
J17
J16 J15 J14
J12 J11 J10
J17
J6
J8 J7
N/C
Motherboard
J20
COM
Relay output
C1630 ISSUE 0
SW1 SW1
ZONE EXPANSION
R0
1
F/P 1 R1 J20
2
S/C 0 R2
3
Module
S/C 1
4
LED 0
5
LED 1
6
Mains
LOG
7
+
C88
HS2
+
BUZ1 C78
Transformer
C78
BUZ1
HS1
BR1
U27
C1630
~ ~
Output
C84
TB23
J1
BR1
U13
U1
U28
DISPLAY
R296A
J1 VR1
Expansion
OUTPUT R296B
R297B
VR1
R297B
SW1 SW2
INHIBIT F/P ON NLZ SILENCE BEFORE RESET D52
1
C90
2
DELAY/ I1
MINUTES
CONFIG CONFIG NON-LATCH ZONES 4
Interface
4
L1 L2 OUTPUT
ENABLED
CONFIG I/S ZONES 8 OK
5
C90
D51
CONFIG M/S ZONES ZONAL ALARMS BAT/CHG
6
L3
FAULT
CONFIG DELAY ZONES PULSE NON-ALARM ZONES
7
FAULT
2 STAGE DELAY BUZZER DISABLE
9 10
9 10
Board
L5
ORIGN1 ALARMS ON EVAC ONLY LATCHED FAULTS FAULT
FS1 - +
C1627 ISSUE 1 BATTERY FUSE BATT THERM
Motherboard
Batteries
Batteries
Figure 5 – Precept EN 16L internal view [32 zone enclosure] with two Output boards
Secondary Earth bars 3 x Enclosure Cable Clip for incoming Mains Warning /
for cable screens fixing holes mains cable Primary Earth Label
Mains
Terminal
Block and
primary Earth
Connection
CHANGE
ACTIVE
ZONE OUTPUTS
EVAC.
EVAC
OP1
OP2
OP3
OP4
OP5
OP6
OP7
OP8
OP1
OP2
OP3
OP4
OP5
OP6
OP7
OP8
RST.
BUZ.
SCN
DIS.
A
B
D.C.
+ 1- + 2- + 3- + 4- + 5- + 6- + 7- + 8-
N/O
SIL.
1 2 3 4
1 2 3 4 + - + - + - + - 24V 0V
Removable
TB1 TB2 TB3 TB4 TB5 TB6 TB7 TB8 TB9 TB10 TB12 TB14 TB15 TB16 TB17 TB18 TB19 TB20 TB21 O/C O/C
FS6
+ - + - + - +
- + - + - + - + - O/+ P C/- C/+ P O/- C/+ P O/- N/C P +24V +24V
9 10 11 12 13 14 15 16
Chassis
FAULT ROUTING FIRE ROUTING FIRE PROTECTION RESET
I/O EXPANSION
ZONE CIRCUITS
J17
J16 J15 J14
J12 J11 J10
J17
J6
+ - + -
J8 J7
LOOP
C1630 ISSUE 0
SW1 SW1
INTERFACE R0
CEL C1631 ISSUE 0
F/P 0
1
Output
F/P 1 R1 J20
2
BOARD S/C 0 R2
3
S/C 1
4
LED 0
5
LED 1
6
LOG
7
+
C88
BUZ1 C78
+ HS2
Modules
+
C78
BUZ1
U27
HS1
BR1
~ ~
C84
TB23
J1
C1630
+
BR1
U13
U28
DISPLAY
R296A
J1 VR1
OUTPUT R296B
R297B
VR1
Output
R297B
SW1 SW2
INHIBIT F/P ON NLZ SILENCE BEFORE RESET D52
1
DELAY/ I1
MINUTES
CONFIG CONFIG NON-LATCH ZONES 4
4
L1 L2 OUTPUT
ENABLED
CONFIG I/S ZONES 8 OK
5
C90
D51
CONFIG M/S ZONES ZONAL ALARMS BAT/CHG
6
L3
Expansion
FAULT
CONFIG DELAY ZONES PULSE NON-ALARM ZONES
7
FAULT
2 STAGE DELAY BUZZER DISABLE
9 10
9 10
Interface
Board
Motherboard
with 5A PSU
&
Transformer
underneath
Batteries
PAGE 4 of 21
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN OUTPUT EXP MOD INST CHECKED BY: AP
ISSUE No. & DATE: 0 02/03/12
Figure 6 – Precept EN Exp 5 internal view
Secondary Earth bars 3 x Enclosure Cable Clip for incoming Mains Warning /
for cable screens fixing holes mains cable Primary Earth Label
Mains
Terminal
Block and
primary Earth
Connection
Removable
Chassis
Space for up
to 5 Output
Boards
PSU &
transformer
mounted
under the
output boards
Batteries
PAGE 5 of 21
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN OUTPUT EXP MOD INST CHECKED BY: AP
ISSUE No. & DATE: 0 02/03/12
PAGE 7 of 21
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN OUTPUT EXP MOD INST CHECKED BY: AP
ISSUE No. & DATE: 0 02/03/12
6.2.3 Interconnections between Fire Alarm Panel and Output Modules
The standard output expansion panel combinations are listed below [see Table 2] along with their respective
requirements for interconnection for the 3 types of O/P modules.
Table 2 – Fire Panel/Output Module Interconnection Installation Work
PAGE 8 of 21
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN OUTPUT EXP MOD INST CHECKED BY: AP
ISSUE No. & DATE: 0 02/03/12
Internal Connections Schematic
FIRECLASS
Expansion Panel Internal
Precept EN Panel Main Panel Expansion Panel
Cable
Data out
connector on the
last
Data C1633/C1635 Connector J2 on O/P module 1
Ribbon [right-hand-most] [left hand most module].
module.
J6 on C1633 and
C1635.
16-zone Expanded Exp 4 [or Exp5]
“Power out” Figure 12
with 2 O/P modules no power supply.
connector on the
“Power in” connector on the
last
first C1633/C1635 module
Aux DC C1633/C1635
[from the left hand side of the
power [right-hand-most]
expansion panel].
cable module
J4 on the C1633/J3 on the
J3 on the
C1635.
C1633/J5 on the
C1635.
Data out
connector on the
Data Connector J2 on O/P module 1
O/P module.
Ribbon [left hand most module]
J6 on C1633 and
C1635
Factory fitted.
From:
Exp 4 [or Exp5] C1652 power supply board
8-zone with 1 O/P
with power 28V, 0V and fault signals from Figure 16
module
supply. J1.
Aux DC
To:
power
“Power in” connector on the
cable
first C1633/C1635 module
[from the left hand side of the
expansion panel].
J4 on the C1633/J3 on the
C1635.
Data out
connector on the
last
Data C1633/C1635 Connector J2 on O/P module 1
Ribbon [right-hand-most] [left hand most module].
module
J6 on C1633 and
C1635.
Factory fitted.
Exp 4 [or Exp5]
16-zone Expanded From:
with power Figure 16
with 2 O/P modules C1652 power supply board
supply.
28V, 0V and fault signals from
Aux DC J1.
power To:
cable “Power in” connector on the
first C1633/C1635 module
[from the left hand side of the
expansion panel].
J4 on the C1633/J3 on the
C1635.
PAGE 9 of 21
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN OUTPUT EXP MOD INST CHECKED BY: AP
ISSUE No. & DATE: 0 02/03/12
6.2.4 Installation of the C1630 Output before the interface board can be fitted]. The
Expansion Interface board should be held in place by the 12mm high
Warning: Observe anti-static precautions plastic spacer provided.
1. Ensure that the panel is powered down and the 3. Connect the output expansion ribbon cable to
main and standby supplies are disconnected. header J17 located on the centre right hand
edge of the C1627 motherboard as shown in
2. On the fire alarm panel, remove the jumper link Figure 7.
at J21 on the C1627 motherboard and fit a
C1630 output expansion interface to connectors
J4 and J5 (see Figure 7). [J21 must be removed
Figure 7 – C1627 Motherboard PCB Layout (with optional Repeater Interface board)
Link J21
PAGE 10 of 21
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN OUTPUT EXP MOD INST CHECKED BY: AP
ISSUE No. & DATE: 0 02/03/12
24Vdc Output
OP1
OP2
OP3
OP4
OP5
OP6
OP7
OP8
Outputs 1 to 8
J2 Comms In/Out J2
OPEN COLLECTOR
OUTPUT BOARD
J6
J6 Comms In/Out
CEL C1633
05-05-2005
ISSUE 2
J4 – 24Vdc Power
In from panel or
Aux PSU, with J5 – Fit link to
optional PSU fault enable Auxiliary
monitoring inputs Power Supply Fault
J4
monitoring
0V +24
J3 – 24Vdc output J5
POWER
to other modules FAULT
ENABLE
AD0
AD1
2
SW2
ZONAL
PROC
ON
PS
PAGE 11 of 21
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN OUTPUT EXP MOD INST CHECKED BY: AP
ISSUE No. & DATE: 0 02/03/12
Table 5 – Setting C1634 Board Address Table 7 – Setting C1634 Function
05-05-2005
Relay Outputs:
ISSUE 2
POLE – common
N/C – normally closed
N/C
J2
J2 Comms In/Out
1 2 3 4 56 7 8
8 WAY RELAY BOARD
J3 Comms In/Out J3
AD0
AD1
2
SW2
ZN1
4 5
only)
COMS
PROC
ON
PS
PAGE 12 of 21
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN OUTPUT EXP MOD INST CHECKED BY: AP
ISSUE No. & DATE: 0 02/03/12
7.1.2 C1635 8-way alarm/monitored Table 9 – Setting C1635 Type, General/Zonal
output module configuration. Response and Zone range
Panel O/P 1-8
Table 8 – Setting C1635 Board Address SW1/6 SW1 SW1 SW1
Mode Board zone
[FP] Zonal ZN0 ZN1
SW2/6 range
SW1 Function
All O/Ps
AD0 AD1 Board Address Off SNDR Off N/A N/A N/A operate on
Off Off 1 any fire
On Off 2 Off SNDR On On Off Off Z1-8
Off On 3
On On 4 Off SNDR On On On Off Z9-16
Off SNDR On On Off On Z17- 24
C1635 Connectors:
Off SNDR On
Z25 -32 On On On
J1 – Programming header.
J2 – Comms to panel motherboard. All O/Ps
On FP N/A Off N/A N/A operate on
J3 – Power in [from panel motherboard or aux PSU]
any fire
+ Aux PSU fault I/P. On FP N/A On Off Off Z1-8
J5 – Power out. On FP N/A On On Off Z9-16
C1635 Link Configuration: On FP N/A On Off On Z17- 24
J4 – Fit link to enable Aux PSU fault monitoring. On FP N/A On On On Z25 -32
Notes: SNDR = Sounders, FP = Fire Protection
When panel SW 2/6 is on:
If panel SW2-7 is off, non-alarm zones are
silent.
If panel SW2-7 is on, non-alarm zones pulse
[See FIRECLASS Precept EN panel manuals]
Outputs 1 to 8
(Top row = 1 to 4,
Bottom row = 5 to 8)
J6
J6 Comms In/Out
J3 – 24Vdc Power In
from panel or Aux PSU,
J4 – Fit link to
with optional PSU fault
enable Auxiliary
monitoring inputs
Power Supply Fault
monitoring
0V +24
J5 – 24Vdc output to J3 J4
POWER
other modules FAULT
ENABLE
Communication
SW1 – Configuration Switch. Fault LED
0V +24
AD0
AD1
ZN1 – Zone range bit 1
2
ZN0
3
SW2
ZONAL
FP – Fire Protection FP Power Supply ON LED
6
PROC FAULT
RESET
Outputs
1
2
3
4
5
6
7
8
COMS
PROC
ON
PS
FLT
FLT
OUTPUT FAULTS
Fault LEDs for each output CEL C1635 ISSUE 2 05-05-2005 Processor Fault LED
PAGE 13 of 21
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN OUTPUT EXP MOD INST CHECKED BY: AP
ISSUE No. & DATE: 0 02/03/12
7.1.3 C1630 Output Interface 2. Use the Alarm Test facility [see FIRECLASS
Configuration Precept EN User Manual] or press Evacuate to
operate the sounders. Check that all sounders
Table 10 – Setting Quantity and Type of O/P connected to the alarm circuit operate.
Modules on the C1630 3. Deselect the Alarms Test condition or if
DIL Switch Number “Evacuate” was used, press silence alarms to
Type of board stop the sounders operating.
setting of boards
F/P0 F/P1 C1634 or C1635 4. Repeat steps 1 to 3 for the second and any
Off Off 0 configured to FP [Fire subsequent sounder circuits.
On Off 1 protection Output]. See
Off On 2 C1635 configuration 7.2.2 Powered/fault monitored Fire
On On 4 details. Protection outputs
S/C0 S/C1
C1635 configured as [C1635 modules configured as Fire Protection
Off Off 0
sounder module. See O/Ps]
On Off 1
C1635 configuration 1. Ensure any fire protection equipment to be
Off On 2
details. controlled via the Fire Protection output is locked
On On 4
LED0 LED1 off/safe before attempting any connection,
Off Off 0 testing or commissioning.
C1633 open collector
On Off 1 2. Remove the resistor from the C1635 output
output module
Off On 2 circuit terminal and connect the field wiring to
On On 4 the terminals, observing correct polarity. Check
VDR that any fault indications clear after a few
Not used on Precept seconds.
Off - -
EN
On - - 3. Initiate a fire condition on a zone to operate the
[Note: Select switch to left hand side for OFF and output. Check that the fire signal operates the
right-hand side for ON] remote interface relay adjacent the fire
protection equipment.
Figure 11 – C1630 output expansion interface 4. Reset the panel and confirm that the remote
board interface relay deactivates.
5. Open-circuit the field wiring and confirm that the
fire alarm panel indicates Fire Protection output
fault.
1
F/P 0
6. Reconnect the cabling and confirm the faults
F/P 1 Configuration Switch
2
clear.
S/C 0 to set quantity & type
3
of modules connected.
Precept EN panel [see Precept EN Operating
LED 0
Instructions]. Initiate a fire condition on a zone to
6
LED 1
operate the output and check that the output
7
VDR
does not operate. Reset the panel and re –
enable the Fire Protection O/Ps after the test.
8. Final testing and commissioning of the loop
through to the fire protection equipment,
including test [simulated] activation of the
equipment, should be carried out at the
appropriate time in conjunction with the engineer
responsible for the fire protection system.
7.2 Commissioning Procedure
9. Repeat steps 1 to 7 for the second and any
After completion of the pre-commissioning wiring subsequent fire protection signal outputs.
check, power-up and configuration, commission the
circuits in line with the following guide.
7.2.3 Volt-free relay Fire Protection
7.2.1 Sounder Circuits outputs
1. Remove the resistor from the first alarm circuit [C1634 modules configured as Fire Protection
terminal and connect the first alarm circuit wiring O/Ps]
to the terminals, observing correct polarity. 1. Ensure any fire protection equipment to be
Check that any alarm fault indications clear after controlled via the Fire Protection output is locked
a few seconds. off/safe before attempting any connection,
testing or commissioning.
PAGE 14 of 21
EQUIPMENT: FIRECLASS PRECEPT EN WRITTEN BY: RKP
PUBLICATION: FIRECLASS PREC EN OUTPUT EXP MOD INST CHECKED BY: AP
ISSUE No. & DATE: 0 02/03/12
2. Connect the field wiring to the appropriate equipment, should be carried out at the
terminals [N/O, P, N/C] appropriate time in conjunction with the engineer
3. Initiate a fire condition on a zone to operate the responsible for the fire protection system.
output. Use a test meter set to continuity or 7. Repeat steps 1 to 6 for the second and any
Ohms to confirm the correct relay contact subsequent volt free relay fire protection signal
condition can be measured at the remote end of outputs.
the installation wiring adjacent the fire protection
equipment to be controlled. 7.2.4 C1633 open collector outputs
4. Reset the fire alarm panel and with the test
1. Connect the field signal wires and the common
meter, confirm that the relay contacts have
return to the appropriate terminals observing the
returned to the deactivated condition.
correct polarity.
5. Disable the Fire Protection Outputs via the
2. The correct operation of equipment connected to
Precept EN panel [see Precept EN Operating
these outputs should be verified in turn by
Instructions]. Initiate a fire condition on a zone to
initiating a fire condition on each of the
operate the output and check that the output
appropriate zones and observing the operation
does not operate. Reset the panel and re –
of the equipment connected to the outputs in the
enable the Fire Protection O/Ps after the test.
field.
6. Final testing and commissioning of the loop
through to the fire protection equipment,
including test [simulated] activation of the
PAGE 15 of 21
Precept EN 8 or 16 fire panel with 1 x C1634 V/F Relay O/P module Precept EN 16L with 2 x C1635 Sounder O/P module
C1634 C1635 C1635
J2 J2 J2
Data ribbon Data ribbon
EQUIPMENT:
J17 J17
PUBLICATION:
C1627 C1627
Motherboard J3 Motherboard J6 Data J6
ISSUE No. & DATE:
J24 J24
J5 J5
Precept EN 16 Panel with internal Output Modules Precept EN Exp 4 [4 way O/P expansion enclosure with 4
modules powered from the Precept en panel
C1633 C1635 C1633 C1635 C1634 C1634
Data
J2 J2 Data J2 Data J2 J2
ribbon J2
ribbon ribbon
J17
Data
Data
PAGE 16 of 21
FIRECLASS PRECEPT EN
Aux DC J4 J3 J4 J3
J24 Aux DC Aux DC
J3 J5 J3 Aux DC J5
modules must be
connected at the end
Standard Panel Expansion Systems. of the sequence
PSU load calculation must be
1] Precept EN 8 with 1 off O/P module. carried out for each application
2] Precept EN 16 with 1 off O/P module.
3] Precept EN 16L with 2 off O/P modules.
4] Precept EN 16 with Exp 4 [4 way O/P enclosure with max 4 O/P modules,
with or without optional 5 Amp PSU and batteries]. Note: To reduce the quantity of standard cable looms, any modules that are to be powered from the
fire alarm panel need to be located in the left hand side of the output expansion enclosure.
CHECKED BY: AP
J17
C1627 J6 Data J6 J3 Data J3
Motherboard ribbon ribbon
Aux DC J4 J3
J24
J3 J5
Aux DC
PAGE 17 of 21
FIRECLASS PRECEPT EN
4] Precept EN 16 with Exp 4 [4 way O/P enclosure with max 4 O/P Note: To reduce the quantity of standard cable looms, any modules that are to be
modules, with or without optional 5 Amp PSU and batteries]. powered from the fire alarm panel need to be located in the left hand side of the output
5] Precept EN 32 with Exp 5 [5 way O/P enclosure with max 5 O/P expansion enclosure.
modules, with or without optional 5 Amp PSU and batteries].
Figure 13 – 8/16 zone panel and Exp 4 Output Module Panel with no PSU
CHECKED BY: AP
WRITTEN BY: RKP
EQUIPMENT:
PUBLICATION:
ISSUE No. & DATE:
Precept EN Exp 5 [5 way O/P expansion enclosure with 5 modules c/w 5 Amp PSU ] Note: All C1634
Precept EN 8, 16 or 32 modules must be
0
C1627 Data
J6 J6 J6 Data J6 J6
Motherboard ribbon ribbon
Further expansion
J4 J3 J3 J3 J3 modules
J24 Aux DC or use
J3 Aux DC J5 Aux DC J5 Aux DC J5 Aux DC J5 additional PSU
Aux DC
CFlt
PAGE 18 of 21
FIRECLASS PRECEPT EN
MFlt
C1652 Power lead TB5
0V
28V PSU load calculation must be
Aux DC, Mains Flt & TB1 carried out for each application
C1652
Comm PSU Flt PWR
& Flt 5 Amp
O/Ps PSU
J1
FIRECLASS PREC EN OUTPUT EXP MOD INST
Note: To reduce the quantity of standard cable looms, any modules that are to be powered from the
fire alarm panel need to be located in the left hand side of the output expansion enclosure.
Figure 14 – 8, 16 or 32 zone panel & Exp 5 Output Module Panel with 5 Amp PSU
CHECKED BY: AP
WRITTEN BY: RKP
EQUIPMENT:
PUBLICATION:
ISSUE No. & DATE:
0
J2 J2 J2 J2 J2
ribbon Data ribbon Data ribbon ribbon
C1627 J17
Precept EN J6 J6 J6 J6 J6 Further expansion
Aux DC Data ribbon Data ribbon
Motherboard J24 modules
J4 J3 J3 J3 J3 Aux DC or use
J19 additional PSU
J3 Aux DC J5 Aux DC J5 Aux DC J5 Aux DC J5
Aux DC
J1
PAGE 19 of 21
C1652
FIRECLASS PRECEPT EN
PWR
5 Amp & Flt
O/Ps
PSU
TB1 PSU load calculation must be
28V carried out for each application
0V
TB5
MFlt
CFlt
FIRECLASS PREC EN OUTPUT EXP MOD INST
Figure 15 – 32 zone panel & Exp 5 Output Module Panel with no PSU
CHECKED BY: AP
WRITTEN BY: RKP
EQUIPMENT:
PUBLICATION:
J6
Precept EN ribbon ribbon
Motherboard
Aux DC J4 J3 J4 J3
J24 Aux DC
J3 J5 J3 Aux DC J5
PAGE 20 of 21
FIRECLASS PRECEPT EN
28V
0086
Control Equipment Ltd
Hillcrest Business Park
Cinder Bank
Dudley
West Midlands
DY2 9AP
United Kingdom.
09
0086-CPD-555921
EN54-2
Control and indicating equipment for fire detection and fire alarm systems for
buildings
Provided options:
Outputs to fire alarm devices.
Outputs to Fire Protection Equipment – Output type B
Test condition.
Delays to Outputs
EN54-4
Power supply equipment for fire detection and fire alarm systems for buildings
PAGE 21 of 21