DATA

Location
Occupancy Classification Ordinary Hazard Group 1
Length of Coverage 25 m
Width of Coverage 12,5 m
2
Area Coverage for each Sprinkler 12 m
Density (refer to NFPA 13 Figure 7‐2.3.1.2) 6 mm/min
K‐Factor (Refer to Spec from VIKING) 81 lpm/bar

HYDRAULIC CALCULATION
2
Area Coverage for Building 185 m
Quantity of Sprinkler(s) 16 sprinklers
Flow Rate minimum each Sprinkler 69,6 lpm
Minimum Pressure each Sprinkler at remote 0,74 bar Acceptable (Min. pressure > 0,48 bar …. NFPA 13)