Seismic Bracing Calculation

Project Goodyear Indonesia Zone 2 Contractor: PT Foxone Media Pratama


Address: LTD
Ruko Paris Square
Bogor
BSD City
Bogor, West Java 16161
Serpong, Prov. Banten 15321

Calculations based on NFPA 13 2013 using FM approved product load limits

Brace Information Brace Components

PHD Component Fig. Number Adjusted Load


Max. Spacing: 40' Between Braces
Fig. 031 Clamping Pipe 1111.3004 kg
Max. Brace Length: 7'-0" Attachment
Fig. 030 C-Clamp Structural
Bracing Material: Sch. 40 Pipe 1" Attachment
1011.51016 kg
Angle from Vertical: 60° to 74° Fig. 045 Sway Brace Structural
Adapter
Least Rad. of Gyration: 0.421

L/R Value: 200 *Calculations are Based on CONCENTRIC Loading


Max Horizontal Load: 727.561568 kg *Please Note: These calculations are for PHD
components only. Use of any other components voids
these calculations and the listing of the assembly.
Fastener Information
Assembly Detail
Structural Steel Member -
Structure Type:
Not Boltable

Structure Description: H Beam

Fastener Orientation: NFPA Type C

Anchor Type: None Required

Orientation of Brace: Longitudinal

Brace ID on Plans: Warehouse Zone 2 #1 LTD

Braced Pipe: 150 mm mm Sch. 40 Load Information Force Factor (Cp): 0.9
Size Type Total Length Weight Total Weight Wp (Weight +15%)

2" Sch. 40 6.096 m 7.6342810122 kg/m 46.719976 kg 53.523856 kg

6" Sch. 40 12.192 m 47.1599152586 kg/m 575.154656 kg 661.337136 kg

Total Adjusted Load of all pipe within Zone of Influence (Wp * Cp = Fpw): 643.647048 kg