Date Kruger M & E Industries Corp.

Company B3 Welborne Industrial Park, Bancal,


Attention Carmona Cavite, Philippines 4116
Project - LAROSSA
Reference SEF-R-02 Tel: +639175519265 Fax: +63 8622891
Email: mktg@krugerph.net

Fan Selection
Fan Type BSB
Unit BSB355/UIM (I)
Fan Quantity 1
Operating Conditions Ducted
Required Volume 730 l/s
Required Static Pressure 200 Pa
Air Volume 730 l/s
Static Pressure 200 Pa
Velocity Pressure 24.9 Pa
Total Pressure 225 Pa
Outlet Velocity 6.54 m/s
Fan Total Efficiency 63.1 %
Fan Static Efficiency 56.1 %
Fan Speed 1307 rpm
Air Temperature 30 °C
Altitude 1m
Fan Absorbed Power 0.260 kW
Motor Selection
Recommended Motor D71 4p (0.370 kW)
Motor Speed 1750 rpm
Service Factor 5%
Operating Limits
Max. Absorbed Power 3.00 kW
Max. Fan Speed 2800 rpm
Temperature (Min-Max) -20° to 180°C

Hz 63 125 250 500 1k 2k 4k 8k Overall


Lwi(Lin) 69 69 77 71 66 62 55 47 79 dB
Lwo(Lin) 73 73 81 74 69 65 58 50 83 dB
Lwi(A) 43 53 68 67 66 63 56 46 73 dB(A)
Lpi(A) 26 36 52 51 50 47 39 29 56 dB(A)
Sound Pressure Level "Lpi" 3m from the inlet side, Room Conditions

0DL A B C D E F G H J
30 654 578 383 452 247 368 260 548 287
K L M N P Q R S t t1
327 765 60 303 30 300 6 508 8 7
UxS V v1 v2 w X Y z
13x18 355 395 435 40 275 480 33

You might also like