Professional Documents
Culture Documents
Manual
FOR POTABLEWATER
HEATING ONLY
NOT SUITABLEFOR
SPACEHEATING
NOT FOR USE IN
MOBILE HONES
Model No.
153.332318 30 Gal. High Altitude THE ECONOMIZERTM5
153.332362 30 Gal.
153.332418 40 Gal. High Altitude
153.332462 40 Gal.
GAS WATER HEATER
153.332562 50 Gal. • Safety Instructions • Care and Maintenance
• Installation • Troubleshooting
• Operation • Parts List
• Do not touch any electrical switch; do not use any phone in your
budding.
Immediately call your gas supplier from a neighbor's phone.
_iDo not try to light any appliance.
Follow the gas supplier'sinstructions.
If you can not reach your gas supplier, call the fire department.
Caution: -Installation and service must be performed by a qualified installer,
Read and Follow service agency or the gas supplier.
All Safety Rules and
Operating Instructions AWARNING 1
Before First Use of Improper installation, adjustment, alteration, service or maintenance I
This Product. can cause DEATH, SERIOUS BOD!LY INJURY, OR PROPERTY DAM-|
AGE. Refer to this manual for assistance or consult the local SearsJ
Service Center or gas utility for further information.
Save this Manual for Future Reference. READ THE GENERAL SAFETY SECTION BEGINNING ON INSIDE
COVER AND THEN THIS ENTIRE
AWARNING
MANUAL BEFORE INSTALLING 1
OR OPERATING THIS WATER HEATER.
installation must be accomplishedin a way that the pilot The temperature-pressure_rellef _,,,alvemust be installed
flame and main burner flame are elevated from the floor directly into the fitting of the water heater designated
at least 18 inches. While this may reduce the chancesof for the relief valve. Posltlon-the-valv_downward_ and pro-
flammable vapors from a floor spill being ignited, gasoline vide tubing so that any dischargewill exit only within 6
and other flammable substancesshouldnever be stored or inches above,o_-_-t'_n_-_£_-b'_lov_the structural
used in the same room or area containing a gas water floor. Be certain that no contact is made with any live
heater or other open flame or spark producingappliance. electrical part. The discharge opening must not be
NOTE: Flammable vapors may be drawn by air currents blocked or reduced in size under any circumstances.
from other areas oftbe structure to the appliance. Excessivelength, over 30 feet, or use of more than four
elbows can cause restriction and reduce the discharge
capacity of the valve.
No valve or other obstruction is to be placed between
_,WARNING the relief valve and the tank. Do not connect tubing
directly to dischargedrain unlessa 6" air gap is provided.
If this water heater will be used in beauty shops, barber To prevent bodily injury, hazard to life, or property dam-
shops, cleaning establishments, or self-service laundries
age, the relief valve must be allowed to dischargewater
with dry cleaning equipment, it is imperative that the in quantities should circumstances demand. If the dis-
water heater or water heaters be installed so that com- charge pipe is not connected to a drain or other suitable
bustion and ventilation air be taken from outside these
areas. Refer to the "Facts to Consider About the means, the water flow may causeproperty damage.
The DischargePipe:
Location" section of this manual and also the latest edi-
Must not be smaller in size than the outlet pipe size of
tion of the National Fuel Gas Code, ANSI Z223.1, also the valve, or have any reducing couplings or other
referred to as NFPA 54 for specificsprovided concerning restrictions.
air required. Must not be pluggedor blocked.
Must be of material listed for hot water distribution.
Must be installed so as to allow complete drainage of
both the temperature-pressure relief valve, and the
AWARNING ] dischargepipe.
A fire can start if combustible materials suchas clothing, Must terminate at an adequate drain.
cleaningmaterials, or flammalde liquidsare placedagainst Must not have any valve between the relief valve and
or next to the water heater. tank.
Safer-I iPrecautions
AWARNING AWARNING
A gas water heater cannot operate properly without the This water heater must not be installed directly on car-
correct amount of air for combustion. Do not install in a potlng. Carpeting must be protected by a metal or wood
confined area such a closet, unless you provide air as panel beneath the appliance extending beyond the full
shownin the "Facts to Consider About the Location" sec- width and depth of the appliance by at least 3 inches
tion. Never obstruct the flow of vantilation air, If you have (76.2mm) in any direction, or if the appliance is installed
any doubts or questions at all, call your gas company. in an alcoveor closet, the entire floor must be coveredby
Failure to provide the proper amount of combustion air the panel. Failure to heed this warning may result in a
can result in a fire or explosion and can cause DEATH, fire hazard.
SERIOUS BODILY INJURY,OR PROPERTY DAMAGE.
AWARNING
• _,WARNING VENT DAMPERS - Any vent damper, whether it is operat-
HOTTER WATER CAN SCALD: Water heaters are ed thermally or otherwise must be removed if its use
intended to produce hot water. Water heated to a tem- inhibits proper drafting of the water heater.
perature which will satisfy clothes washing,dish washing, Thermally Operated Vent Dampers: Gas-fired water
and other sanitizing needs can scald and permanently heaters having thermal efficiency in excess of 80% may
injure you upon contact. Some people are more likely to producea relatively low flue gastemperature. Such tem-
be permanently injured by hot water than others. These peratures may not be high enoughto properly open ther-
includethe elderly, children,the infirm, or physically/men- mally operated vent dampers. This would causespillageof
tally handicapped.If anyone usinghot water in your home flue gasesand may causecarbon monoxide poisoning.
f'_sinto one of these groups or if there is a local code or Vent dampers must bear evidenceof certification as com-
state law requiring a certain temperature water at the hot plying with the latest edition of American National
water tap, then you must take specialprecautions.In addi- Standard ANSI Z21.68 (ANSI Z21.66 & 67, respectively,
tion to usingthe lowest possibletemperature setting that cover electrically and mechanically actuated vent
satisfies your hot water needs, a means such as a mixing dampers). Before installation of any vent damper, consult
valve, shouldbe used at the hot water taps used by these your local Sears Service Center or the gas utility for fur-
people or at the water heater. Mixing valvesare available ther information.
at plumbing supply or hardware stores. Follow manufac-
turers instructions for installation of the valves. Before
changingthe factory setting on the thermostat, read the
"Temperature Regulation" section in this manual.
_,WARNING
• The appliance and its individualshutoffvalvemust be dis-
connected from the gas supplypiping system during any
AWARNING pressure testing of the gas system at test pressures in
excessof _ pound per squareinch (3.5kPa).
Soot build-up indicates a problem that requires correc- • The appliance must be isolated from the gas supplypip-
tion before furtber use. Turn "OFF" gasto water heater ing system by closingits individual manual shutoff valve
and leave "OFF" until repairs are made, because failure during any pressure testing of the gas s_upply
piping sys-
to correct the cause of the sootingcan result in a fire or tem at test pressures equal or less than ½ pound per
explosion causing DEATH, SERIOUS BODILY INJURY, squareinch (3.5kPa).
OR PROPERTY DAMAGE.
AWARNING
AWARNING Chemical vapor corrosion of the flue and vent system
BEFORE LIGHTING [PROPANE (L.R) GAS WATER may occur if air for combustion contains certain chemical
HEATERS]: Propane (L.P.) gas is heavier than air, Should vapors. Spray can propellants,cleaningsolvents,refrigera-
there be a leak in the system, the gas will settle near the tor and air conditioner refrigerants, swimming pool
ground. Basements, crawl spaces, skirted areas under chemicals, calcium and sodium chloride, waxes, bleach,
mobile homes (even when ventilated), closets and areas and processchemicals are typical compounds which are
below ground level will serve as pockets for the accumula- potentially corrosive.
tion of this gas. Before attempting to light or relight the
water heater'spilot or turning on a nearby electrical light
switch, be absolutely sure there is no accumulated gas in
the area. Search for odor of gas by snifEngat ground level
in the vicinity of the appliance. If odor is detected, follow
steps indicated at "For Your Safety" on the cover page of Obstructed or deteriorated vent systems may present
this manual then leave the premises. i serioushealth risk or A, WARNING
asphyxiation.
AWARNING 1
Do not use this appl_of it has been under _
water. Immediately call a Sears Service Technician to
inspectthe applianceand to replace the gas control or any I
part of the burner system which hasbeen under water.
AWARNIHG
HYDROGEN GAS: Hydrogen gascan be producedin a hot
water system that has not been used for a long period of
time (generally two weeks or more). Hydrogen gas is
extremely flammable and explosive.To prevent the possi-
bility of injury under these conditions,we recommend the
hot water faucet be opened for several minutes at the
kitchen sink before any electrical appliances which are
connectedto the hot water systemare used (suchas a dis-
hwasher or washing machine). If hydrogengas is present,
there will probably be an unusual sound similar to air
escaping through the pipe as the hot water faucet is
i opened. There must be no smoking or open flame near
the faucet at the time it is open.
AWARNING
INSULATING JACKETS: When installing an external
water heater insulation jacket on a gaswater heater:
• DO NOT cover the temperature.pressure relief valve.
• DO NOT put insulation over any part of the top of the
gaswater heater.
• DO NOT put Insulation over the gascontrol valve or
control valvelburner cover, or any accessareas to the
burner.
• DO NOT let insulation around the gas water heater to
get within 8 inches of the floor (air must get to the
burner).
• DO NOT cover or remove operating instructions, and
safety related warning labelsand materials affixed to the
water heater.
Failure to heed this will result in the possibilityof a fire or
explosion.
Table of Contents
Safety Precautions .....................................................................................................
2_
Table of Contents ............................................................................................................
.-.
................................
5
Customer Re.s_onsibilities .......................................................................................
i..6
Product Specincations .............................................................................................
i..6
Materials and Basic Tools Needed .........................................................................
7
Materials Needed ...................................................................................................................................................................... 7
Basic Tools ................................................................................................................................................................................ 7
c__:_v_,verat,n_
AI.
Instructions.......................................................................................
v_,,I
17-19
Lighting ............................................................................................................................................................................. 17-18
Temperature Regulation .......................................................................................................................................................... 19
5
Customer Responsibilities
Thank You for purchasinga Sears water heater. • This manual contains instructions for the installation, opera-
tion, and maintenance of the gas-fired water heater. It also
Properly installed and maintained, it should give you years of
contains warnings through out the manual that you must read
trouble free service. If you should.decide that you want the new
and be aware of. All warnings and all instructions are essential
water heater professionally installed by Sears call the local Sears
Service Center or any Sears store. They will arrange _r prompt, to the proper operation of the water heater and your safety.
quality installation by Sears authorized contractors. _ - - Since we cannot put evea'ything on the first few pages, READ
THE ENTIRE MANUAL BEFORE ATTEMPTING TO
Abbreviations Found In This Instruction Manual
INSTALL OR OPERATE THE WATER
A.G.A. - American Gas Association
• The installation must conform with the instructions in this
A.N.S.1. -American National Standards Institute
manual; gas company rules; and Local Codes, or in the
absence of Local Codes, with the latest edition of the National
AWARNING Fuel Gas code, ANSI Z223.1, also referred to as NFPA 54.
This gas-fired water heater is design certified by the This publication is available from your local government or
American Gas Association Laboratories under American public library or gas company or by writing NFPA,
National Standards for Gas Water Heaters. The installa- Batterymarch Park, Quincy, MA 02269.
tion must conform with this manual, Local Codes and with • If after reading this manualyou have any questions or do not
the latest edition of the National Fuel Gas Code, ANSI understand any portion of the instructions, call the Sears
Z223.1. Service Center.
This publication is available from your local government or • Carefully plan the place where you are going to put the water
public library, gas company, or by writing NFPA, heater. Correct combustion, vent action, an_l vent pipe instal-
Batterymarch Park, Quincy, MA 02269. lation are very important in preventing death from possible
carbon monoxide poisoning and fires.
Examine the location to ensure the water heater complies with
the "Facts to Consider About the Location" section in this
• Read the "Safety Precautions" section, pages 2 through 4 of
manual.
this manual first and then the entire manual carefully. If you
don't follow the safety rules, the water heater will nor operate • For California installation this water heater must be braced,
properly. It could cause DEATH, SERIOUS BODILY anchored, or strapped to avoid falling or moving during an
INJURY AND/OR PROPERTY DAMAGE. earthquake. See instructions for correct installation proce-
dures. Instructions may be obtained from your local dealer
who esaler, public utilities or California Office of the State
Architect, 400 P Street, Sacramento, CA 95814.
Product Specifications
DIMENSIONS IN INCHES
MODEL TANK TYPE RECOVERYRATE MINIMUM
NUMBER CAPACITY OF B.T.U. GALS.PER HOUR HEIGHTTO
VENT
IN GALLONS GAS RATE @90°FRISE PIPE DIAMETER JACKETTOP
153.332318 30 NATURAL 30,000 31.0 3" 16" 56"
153.332362 30 NATURAL 30,000 31.0 3" 16" 56"
153.332418 40 NATURAL 32,000 33.0 3" 18" 56¼"
I53.332462 40 NATURAL 32,000 33.0 3" 18" 56½"
153.332562 50 NATURAL 32,000 33.0 3" 20" 56½"
Materials and Basic Tools Needed
Materials Needed
To simplify the installation Sews has available the installation
parts shown below. You may or may not need all of these materi-
als, depending on your type of installation. !
FLEXIBLE WATER
EXPANSION TANKS HEATER GAS CON-
FOR THERMAL NECTOR WITH
EXPANSION CONDI- FITTINGS
TIONS AVAILABLE IN
2 GALLON AND 5
GALLON CAPACITY
THROUGH LOCAL
SEARS STORE OR
SERVICE CENTERS
WATER HEATER INSTAL- DRAIN PANS
LATION KIT WITH FLEXI- AVAILABLE IN 20" DIAMETER FOR
BLE CONNECTORS FOR WATER HEATERS HAVING A DIAME-
3/4" OR I/2" THREADED TER 18" OR LESS AND AVAILABLE IN
WATER HEATER HEAT
OR COPPER PLUMBING VENT PIPE 28" DIAMETER FOR WATER HEATERS
TRAPS HELP REDUCE HEAT
HAVING A DIAMETER 26" OR LESS
LOSS DUE TO THERMAL
SYPHONING
HACKSAW
PHILLIPS SCREWDRIVER
PROPANE
TORCH
TIN SNIPS
ROLL OF LEAD FREE
SOFT SOLDER
QCheck a_,ain to make sure the gas supply b. If you have galvanized pipe to the water
is "OFF to the water heater. Then dis- heater, loosen the two galvanized pipes
with a pipe wrench at the union in each
connect the gas supply connection from
line. Also disconnect the piping remain-
the gas control valve.
ing to the water heater. These pieces
should be saved since they may be-need-
ed when reconnecting the new water
heater. Disconnect the temperature-pres-
Attach a hose to the water hearer drain sure relief valve drain line. When the
valve and put the other end in a floor water heater is drained, disconnect the
drain or outdoors. Open the water heater hose from the drain valve. Close the
drain valve. Open a nearby hot water drain valve. The water heater is now
faucet which will relieve pressure in the completely disconnected and ready to be
water heater and speed draining. removed.
AWARNIHG ACAUTION ]
The water passingout of the drain valve may be extremely Mineral buildup or sediment may have accumulatedin the I
hot. To avoid being scalded,make sure all connectionsare old water heater. This causesthe water heater to be much
tight and that the water flow is directed away from any heavier than normal and this residue, ,f spilled out, could [
person. causestaining. - - [
Installation Instructions (cont'd)
Facts to Consider About the
Location
You should carefully choose an indoor location for the new • The location selection must provide adequate clearances for ser-
water heater, because the placement is a very important consid- vicing and proper operation of the water heater.
eration _or the safety of the occupants in the building and for
the most economical use of the appliance. This water heater is
not for use in mobile homes or outdoor installation. AWARNING
This water heater must not be installed directly on carpeting.
Whether replacing an old water heater or putting the water
Carpeting must be protected by a metal or wood panel
heater in a new location, the following critical points must be
observed. beneath the appliance extending beyond the full width and
depth of the appliance by at least 3 inches (76.2mm) in any
di_ or if the appliance is installed in an alcove or closet,
• The location selected should be indoors as close as practical
the entire floor must be covered by,he panel. Failure to heed
to the gas vent or chimney to which the water heater vent is
this warning may result in a fire haza_l_.
going to be connected, and as centralized with the water
_iping system as possible. The water heater, as all water
eaters, will eventually leak. Do not install without
adequate drainage provisions where water flow will cause AWARNING
damage. Minimum clearances between the water heater and com-
bustible or non-combustible construction are I" at the sides
A CAUTION and rear, 4" at the front, and 6" from the vent pipe. Clearance
WATER HEATERS EVENTUALLY LEAK: Installation of the from the top of the jacket is 18" on most models. Note that a
water heater must be accomplished in such a manner that if lesser dimension may be allowed on some modelg Refer to the
label on the water heater adjacent to the gas control valve for
the tank or any connections should leak, tile flow of water will
all dearance_
not cause damage to the structure. When such locations can-
not be avoided, a suitable drain pan should be installed under
the water heater. Drain pans are available at your local Sears
12"MAX.
store. Such a drain pan must be not greater than 1½ inches
deep, have a minimum length and width of at least 2 inches
greater than the water heater dimensions and must be piped f
VENTILATION
to an adequate drain. The pan must not restrict combustion air
TO VjMI"
AIR
OPENINGSO
flow. Under no circumstances is the manufacturer or Sears to
be held liable for any water damage in connection with this OF CLOSET TOP VIEW I • MiN.
WITHOUT DOOR OF CLOSET
water heater. 2"•HAX. WITH DOOR
FRONT VIE-VV
OF DOOR
AWARNING
AIR DUCT
INSTALLATIONS IN AREAS WHERE FLAMMABLE LIQUIDS Figure I I
IVAPORS) ARE LIKELY TO BE PRESENT OR STORED
rGARAGES, STORAGE, AND UTILITY AREAS, ETC):
_lammable liquids (such as gasoline, solvents, propane (LP) or AWARNING
butane, etc.), all of which emit flammable vapors, may be
A gas water heater cannot operate properly without the cor-
improperly stored or used in such area_ The gas water heater
rect amount of air for combustion. Do not install in a confined
pilot light or main burner can ignite such vaporg The resulting
area such a closet, unlessyon provide air as shownin the "Facts
flashbackand fire can cause death or serious burns to anyone in
to Consider About the Location" section. Never obstruct the
the area, as well as property damage.
flow of ventilation air. If you have any doubts or questionsat all,
If installation in such areas is your only option, then the installa-
callyour gascompany. Failure to provide the proper amount of
tion must be accomplished in a way that the pilot flame and
main burner flame are elevated from the floor at least 18inche_ combustion air can result in a fire or explosion and can cause
DEATH, SERIOUS BODILY INJUR_, OR PROPERTY DAMAGE.
While this may reduce the chances of flammable vaporsfrom a
floor spill being ignited,gasolineand other flammable substances
shouldnever be stored or used in the same room or area con-
taining a gaswater heater or other open flame or sparkproduc- AWARNING
ing applianc_
NOTE: Flammable vapors may be drawn by air currents from If this water heater will be usedin beautyshops,barber shops,
other areas of the structure to the appliance. cleaningestablishments,or self-servicelaundrieswith dry
cleaningequipment,it is imperativethat the water heater or
water heatersbe installedsothat combustionand ventilation
AWARNING air be taken from outsidethese area_ Refer to the "Facts to
Propellantsof aerosolspraysand volatile compounds,(clean- ConsiderAbout the Location"sectionof this manualand also
ers,chlorinebasedchemicals,refrigerants, etc.) in additionto the latestedition of the NationalFuelGasCode, ANSI Z223.1,
beinghighlyflammablein many cases,will alsochangeto cor- also referred to as NFPA 54 for specificsprovidedconcerning
rosive hydrochloricacid when exposedto the combustion air required.
productsof the water heater The resultscan be hazardous
and alsocauseproductfailure.
9
Installation Instructions (cont'd)
Combustion Air and Ventilation
for Appliances Located in
Unconfined Spaces
Unconfined Space is a space whose volume is not less than 50 1. When direcdy communicating with the outdoors, each open-
cubic feet per 1,000 Btu per hour of the aggregate input rating ing shall have a minimum free area of I square inch per 4,000
of all appliances installed in that space. Rooms communicating BTU per hour of total input rating of all equipment in the
directly with the space in which the appliances are installed, enclosure. (See Figure 3.)
through openings not furnished with doors, are considered a
part of the unconfined space 2. When communicating with the outdoors through vertical
In unconfined spaces in buildings, infiltration may be adequate ducts, each opening shall have a minimum free area of 1
to provide air for combustion, ventilation and dilution of flue s,q[uareinch per 4,000 BTU per hour of total input rating of
gases. However, in buildings of tight construction (for example, all equipment in the enclosure. (See Figure 4.)
weather stripping, heavily insulated, caulked, vapor barrier, etc.),
additional air may need to be provided using the methods
described in Combustion Air and Ventilation for Appliances
Located in Confined Spaces, b.
Figure 5 ]
&WARNING
3/4" THREADED-_
Toxic chemicals su_reatment of boilers NIPPLE NIPPLE
or non-potable water heating appliances shall never
be ntroduced nto a potable water heating system.
• Look at the top cover of the water heater. The water outlet is
marked hot. Put two or three turns of teflon tape around the
threaded end of the threaded-to-sweat coupling and around FLOOR DRAIN
both ends of the _" threaded nipple. Using flexible connec-
tors, connect the hot water pipe to the hot water oudet on
the water heater.
11
Installation Instructions (cont'd)
Temperature-Pressure Relief Valve
_,WARNING A, WARNING
At the time of manufacture this water heater was provided The temperature-preasure relief valve must be manually
with a combination temperatom-pressures relief vane certified opereted at least once a year. CauCdon shouldbe teken to
by a nationally recognized testing laboratory that maintains ensurethat (I) no one isin front of or aroundthe outlet of
periodic inspection of production of listed equipment or mate- the temperature-pressure relief valvedischargeline, and (2)
rials, as meeting the requirements for Relief Valves and the water manually dischargedwill not causeany bodily
Automatic Gas Shutoff Devices for Hot Water SupplySystems, injury or property damage because the water may be
and the latest edition of ANSI Z21.22 and the code require- extremely hot.
ments of ASMF. If replaced, the valve must meet the require- If after manuallyoperating the valve, it fails to completely
ments of local codes, but not lessthan a combination tempera- resetand continuesto releasewater, immediatelyclosethe
turn and pressure relief valve certified as meeting the require- cold water inlet to the water heater, follow the draining
ments for Relief Valvesand Automatic Gas Shutoff Devicesfor
instructions,and replace the temperature-pressure relief
Hot Water Supply Systems, ANSI Z21.22 by a nationally recog- valvewith a new one.
nized testing laboratory that maintains periodic inspection of
bmduction of listed equipment or materials,
The valve must be marked with a maximum set pressure not
to exceed the marked hydrostatic working pressure of the
water heater (150 Ibsdsq.in.) and a discharge capacity not less
than the water heater input rate as shown on the model rating
HOT COLD
plate. (Electric heaters - watts divided by 1000 x 3415 equal
VALVE
BTU/Hr. rate.)
Your local jurisdictional authority, while mandating the use of a
temperature-pressure relief valve complying with ANSI Z21.22
and ASME, may require a valve model different from the one
furnished with the water heater
Compliance with such local requirements must he satisfiedby RELIEF VALVE
the installer or end user of the water heater with a locally pre-
scribed temperature-pressure relief valve installed in the desig-
nated opening in the water heater in place of the factory fur-
nishedvalve.
For safe operation of the water heater, the relief valve must not
be removed from it's designatedopening or plugged. PIPE
The temperature.pressure relief valve must be installeddirectly (Do not cap or plug)
into the fitting of the water heater designatedfor the relief valve.
Positionthe valve downward and provide tubing so that any dis-
charge will exit only within 6 inches above, or at any distance
below the structural floor. Be certain that no contact is made
with any live electrical part. The dischargeopening must not be
blocked or reduced in size under any circumstances. Excessive
length, over 30 feet, or use of more than four elbows can cause
restriction and reduce the dischargecapacit7 of the valve.
No valve or other obstruction is to he placed between the relief
valve and the tank. Do not connect tubing directly to discharge FLOOR DRAIN
drain unlessa 6" air gap is provided.To prevent bedily injury, haz-
ard to life, or property damage, the relief valve must be allowed
to dischargewater in quantities shouldcircumstancesdemand. If RELIEFVALVEOPENING
the discharge pipe is not connected to a drain or other suitable At the time of manufacture,this water heaterwasprovidedwitha combinationtern-
means, the water flow may causeproperty damage. perature-pressurereliefvalvelistedascomplyin_withthestandard for reliefvalvesand
automaticgasshut-offdevicesfor hot water supplysystems, ANSI Z2L22. For safe
The Discharge Pipe: operationofthe waterheater,the relief valvemu_ not beremovedfromitsdesignated
Must not he smaller in size than the outlet pipe size of the pointofinstalla_onor plugged.
valve, or have any reducing couplings or other restrictions. Yourlocaljurisdictionalauthority,whilemandatin_the use of a temperature-pressure
Must not be plugged or blocked. reliefvalvecomplyingwithANSIZ21.22andASME.mayrequirei valvemodeldifferent
from the onefurnished vdththewaterheater.
• Must be of material listed for hot water distribution. Compliance withsuchlocalrequirements mustbe satisfied
bythe installer or enduser
• Must be installed so as to allow complete drainage of both of the water heaterwitha IocaJly prescribed
temperature-pressure relief_ installed
the temperature-pressure relief valve, and the discharge inthe designated
opening in the waterheater
pipe. Seemanual heading="Temperature.Pressure ReliefValves"
for installa_on andmainte-
nanceof_ief valve,discharge line,andothersafetyprecautions.
• Must terminate at an adequate drain.
• Must not have any valve between the relief valve and tank.
12
Installation Instructions (cont'd)
Filling the Water Heater
.,CA ON I For proper venting in certain installations, a larger diameter vent
pipe may be necessary. Due to great variances in installations,
Never usethiswater beater unlessit mcomplntely filled with [ balforeseeable by the manufacturer of the water heater, you must
waer. To prts_ ddmageto the t_k, the tenk must betilled I consult your gas company to aid you in determining the proper
with water. Water must flow from the hot water faucet"I venting for your water heater from the vent tables in the latest edi-
beforeturning "ON" gasto the _ heater. ] tion of the National Fuel Gas Code ANSI Z223.1, also referred to
as NFPA 54.
To fill the water heater with water: Check the venting system for signs of obstruction or deterioration
• Close the water heater drain valve by turning the handle to and replace if needed.
the right (clockwise). The drain valve is on the lower front of
the water heater. The combustion and ventilation air flow must not be obstructed.
• Open the cold water supply valve to the water heater.
NOTE: The cold water supply valve must be left open
when the water heater is in use.
AWARNING [
• To insure complete filling of the tank, allow air to exit by
Obstructedor deterioratedventsystemsmaypresenta serious
opening the nearest hot water faucet. Allow water to run
until a constant flow is obtained. This will let air out of the risk or asph_tion.
water heater and the piping.
• Check all new water piping for leaks.Repairas needed.
• Place the draft hood legs in the receiving holes on the top of
the water heater. The legs will snap in the holes to give a tight
fit.
Venting Place the vent pipe over the draft hood. With the vent pipe
in position, drill a small hole through both the vent pipe and
AWARNING draft hood. Secure them together with a sheet metal screw.
VENT DAMPERS- Any vent dampe_ whether it is operated
thermallyor otherwisemust be removedif itsuseinhibitsprop-
er draftingoftbe water beaten
DRAFT HOOD _ ]rENTalI #
Thermally Operated Vent Damper_ Gas-firedwater heaters SCR_V%_'__ DRAFT HOOD
13
Installation Instructions (cont'd)
Venting (cont'd) Gas Piping
All vent gases must be completely vented to the outdoors of the AWARNING
structure (dwelling). Install only the draft hood provided with
the new water heater and no other drafthood. Make sure the gas supplied is the same type listed on the
Vent pipes must be secured at each joint with sheet metal screws. model rating plate. The inlet gas pressure must not exceed
14 inches water column _A pound per square inch (3.5kPa).
The minimum inlet gas pressure listed on the model rating
plate is for the purpose of input adjustment.
__ -- "_ TO
CHIMNEY
MIN. ¼ INCH
RISE PERLINEAR AWARNING , I
FOOT If the gascontrolvalveissubjectedto pressuresexceeding ½I
t poundper square inch(3.gkPa),the damageto the gascon-
VENT PIPE INSTALLATION trol valvecouldresultin a fire or explosionfrom leaking
AWARNING Standard Models are for installation up to 3,300 feet above sea
level.
Chemical vapor corrosion of the flue and vent system may
High Altitude Models are for installation from 3,300 to 5,500
occur if air for combustion contains certain chemical vapors. feet above sea level.
Spray can propellants, cleaning solvents, refrigerator and air
conditioner refrigerants, swimming pool chemicals, calcium Ifa standard model is installed above 3,300 feet or a high altitude
and sodium chloride, waxes, Beach, and processchemicals are model is installed above 5,500 feet, the input rating must be
typical compounds which are potentially corrosive. reduced at the rate of 4 percent for each 1,000 feet above sea level.
Contact your local Sears Service Center or gas utility for further
information.
14
Installation Instructions (cont'd)
tem by dosingitsindividualmanualshutoffvalveduringany
GROUND
pressuretestingof the gassupply pipingsystemat test pres-
suresequalor lessthan ½poundper squareinch(3.5k1_
GAS
CONTROL
VALVE
SEDIMENT TRAP
GAS PIPING WITH ALL BLACK IRON
A sediment trap shall be installed as close to the inlet of the PIPE TO GAS CONTROL
water heater as practical at the time of water heater installation.
The sediment trap shall be either a tee fitting with a capped nip-
ple in the bottom outlet or other device recognized as an effec-
tive sediment trap. Ifa tee fitting is used, it snail be installed in
conformance with one of the methods of installation shown GROUND JOINT BLACK PiPE
below. UNION(Optional)
Connecting the gas piping to the gas control valve of the water GAS
CONTROL
heater can be accomplished by either of the two methods shown. VALVE
,AWARNING
CAP
Contaminants in the gaslinesmay causeimproper operation
of the gascontrol valvethat may result in fire or explosion.
Beforeattachingthe gaslinebe sere that all gaspipe isclean
on the inside.To trap any dirt or foreignmaterial in the gas
supply line, a drip leg (sometimes called a sediment trap)
must be incorporated in the piping. The drip leg must be
readilyaccessible.Installin accordancewith the "Gas Piping"
section. Refer to the latest edition of the National Fuel Gas
Code,ANSI Z223.1,alsoreferredto as NFPA 54.
15
Installation Instructions (cont'd)
Installation Checklist
BEFORE LIGHTING.THE PILOT:
: • Are the cold and hot water lines connected to the water DRAFT HOOD
heater correctly? See "Water Piping" instructions in the
GAS SUPPLY
"Installation Instructions" section. PRESSURE
+ RELIEF VALVE
DRIP
• Do you have adequate ventilation so that the water heater
(Sediment trap)
will operate properly? See "Combustion Air and Ventilation"
in the "Installation Instructions" section. PIPE CAP ----i_ '
• Is the vent pipe properly sloped and does the vent terminate
outdoors? See "Venting" instructions in the "Installation
Instructions sectmn.
• Do you need to call your gas company to check the gas pipe
and its hookup?
16
Operating Instructions
Lighting
_,WARNING
BEFORE LIGHTING [PROPANE (L.P.) GAS WATER
HEATERS]:Propane(I.R) gasis heavierthan air.Shouldthere
be a leak in the system,the gaswill settle near the ground.
Basements,crawl spaces,skirted areas under mobile homes
(eve.
wi . vendL '), .. -ound lo/e[win
serve as pockets for the accumulation of this gas. DeTore
attemp_ngto lightor mlight the water heater'spilot or turning
on a nearbyelectricallightswitch,be absolutelysurethere isno
accumulatedgasin the area.Searchfor odor ofgasbymiffingat
groundlevelin ffm vicinityof the appliance,.
If odor is detected,
follow stepsindicatedat "For YourSafety' on the coverpageof
this manualthen leavethe premises, i
I Figure 6 ]
AWARNING
AN ODORANT IS ADDED TO THE GAS USED
BY THIS WATER HEATER.
FOR YOUR SAFETY
IF YOU SMELLGAS:
Do not try to lightany appliance.
Do not touchanyelectricalswitch;do not useanyphonein
yourbuilding. Figure 7 ]
Immediatelycallyour gassupplierfrom a neighbor'sphone.
Followthe gassuppliers instructions
If you cannot reach your gassupplier,call the Ere depart-
mont.
AWARNING
DO NOT force the gascontrol Imob. Use onlyyour handto
pushit downto lightthe pilot, or to tom it to "ON", "OFF"
or "PILOT". Never usea tool suchas a lever,wrenchor pli-
ers. Do not hit or d_Jmage the I_nob.A damagedImob may
resultin an explosionand serious injury.If you haveproblem
turningthe Imob,callthe gassupplierimmediately.
Figure 8 1
Be sure to check all your gas pipes for leaks before lighting your
water heater. Use a soapy water solution, not a match or open
flame. Check the factory gasfittings after _ilot is lit and gas con-
trol knob is still in PILOT position,, Then, check the fittings
when the main burner is turned ON . Use a soapy water solu-
tion for this, too. i
INNER DOOR
17
Operating Instructions (cont'd)
Lighting label on the water heater as it appears above the thermostat
A. This appliancehas a pilot whichmust be lightedby • If you cannotreach your gas supplier,call the fire
hand.Whenlightingthe pilot,followtheseinstructions department.
exactly. C. Use onlyyour handto pushin or turn the gascontrol
B. BEFORELIGHTINGsmellall aroundthe appliancearea knob. Neverusetools. If the knobwill not pushIn or
for gas. Be sure to smell next to the floor because turnby hand,don'ttry to repairit, calla qualifiedser-
somegas is heavierthanair and willsettleon thefloor. vice technician.Forceor attemptedrepair may result
WHATTO DOIF YOUSMELLGAS in a fire or explosion.
• Do nottryto lightanyappliance. D. Do not use this applianceit any part has .beenunder
• Do not touch any electric switch; do not use any water.Immediatelycall a qualifiedservice technician
phonein yourbuilding. to inspecttheapplianceand to replaceanypart ofthe
• Immediatelycall yourgas supplierfroma neighbor's controlsystemand any gas controlwhichhas been
phone.Followthegas supplier'sinstructions. underwater.
LIGHTING INSTRUCTIONS
1. STOP!Readthesafetyinformation aboveon thislabel. 9. Push in control knob all the way and hold down.
2. Removeouterdoor. Immediatelylightthe pilot with a match.Continueto
3. Set the thermostat to lowest setting by turning the hold control knob in for aboutone (1) minuteafter
watertemperaturedial clockwise,(F_'_) to its lowest the pilot is lit. Releaseknoband it will pop backup.
temperaturesetting(witharrowon dial)as shown.DO Pilotshouldremainlit. If it goes out, repeat steps3
through8.
• If knobdoes not popup whenreleased,stopand
immediatelycall your service technicianor gas
NOT FORCE. supplier.
• If the pilot will not stay lit after several tries,
depressand turnthe gascontrolknobclockwise
4. Turngas controlknobclockwise_jl to "OFF" posi-
tion. Knob cannot be turned from "PILOT" to "OFF" or_gas) to "OFF"and call yourservicetechnician
unlessknob is depressedslightly.DO NOT FORCE. supplier.(Figure6, page17)
(Figure6, page 17) 10. Replace(or close) innerdoor. Replaceouter door if
5. Wait five (5) minutesto clear out any gas. If you then door does not covergas controlon/offknobor tem-
smell gas, STOP!Follow"B" in the safetyinformation peratureadjustmentknob.(Figure9, page17)
above on this label. If you don't smellgas, go to the 11. At armslenflthaway,turngascontrolknobcounter-
nextstep. clockwise_ to the full "ON" position.Warning
6. Remove(or open) inner door locatedbelowthe gas do not use gas control knob to regulate gas
controlunit. flow. (Figure8, page17)
7. Findpilot-followmetaltubefrom gascontrol.The pilot 12. At arms length away,set the thermostatto desired
is locatedin frontof the burner. setting.The mark( • ) HOTindicativeof approximate
120°F is preferredstarting point. Somelocal laws
PILOT BURNER __THERMOCOUPLE may requirea lowerstartingpoint.If hotterwateris
desired,seeinstructionmanualand "warning" below.
8. If youdon'tsmellgas,turnknobon gascontrolcounter 13.Replacetheouterdoorif not replacedin step10.
clockwise_e(_' to "PILOT" position.(Figure7,page 17)
WARNING
Hotterwater increasesthe risk of scald injury.Before changingtemperaturesettingsee instructionmanual.
18
Operating Instructions (cont'd)
Temperature Regulation
Due to the nature of the typical gas water heater, the water tem- Turn the water temperature dial dockwise _f"_) to decrease
_oerature in certain situations may vary up to 30°F higher or the temperature, or counterclockwise (€"- _"_) to increase the
wer at the point of use such as, bathtubs, showers, sink, etc. temperature.
: AWARNING
HOTTER WATER CAN SCALD: Water heaters are intended to
produce hot water. Water heated to a temperature which will
satisfyclothes washing,dishwashing, and other sanitizing needs
can scald and permanently injure you upon contact. Some peo-
ple are more lilmly to be permanently injured by hot water than PILOT LIGHTING-Set here before attempting to light pilot.
otherg These include the elderly, children,the infirm, or physical-
• HOT- ls a thermostat setting of approximately
b/mentally handicapped.If anyone usinghot water in your home
120°F, which will supply hot water at the
fits into one of these groups or if there isa localcode or state law
most economical temperatures. The
requiring a certain temperature water at the hot water ta_ then
temperature adjustment knob can be
you must take special pmcaution_ In addition to usingthe lowest turned lower than "HOT" if desired.
possibletemperature setting that satisfiesyour hot water needs,
a means such as a mixing valve, shouldbe usedat the hot water
taps used by these people or at the water heater. Mixing valves A-Is a thermostat setting of approximately
130°E
are availableat plumbing supplyor hardware stores.Follow man-
ufacturers instructions for installation of the valves. Before
changing the factory setting on the thermostat, read the B-Is a thermostat setting of approximately
140°E
'_remperature Regulation" section in this manual.
19
Service and Adjustment
Tank (Sediment) Cleaning Burner Inspection
Sediment build-up on the tank bottom may create varying
amounts of noise, and if left in the tank will cause premature • AWARNING
tank failure. In some water areas, you may not be able to drain Donnt usethisapld'_n__ hasbeenunderwater.
all sediment deposits by simply draining the tank. In these cases Immediately call a Sears Service Technician to inspect the
Mag-Erad (part no. 23600) can be used to help remove the sedi- appliance and to replace the gas control or any part of the"
ment deposits. This may be ordered from theSears Service Jburner system which has been under water.
Center. For ordering, refer to the Parts Order List section.
At least once a year a visual inspection should be made of the You should check for sooting which is not normal and will
venting system. You should look for: impair proper coinbustion.
• Obstructions which could cause improper venting. The com-
bustion and ventilation air flow must not be obstructed.
Damage or deterioration which could cause improper vent-
i ing or leakage of combustion products.
Rusted flakes around top ofwarer heater.
AWARNING
Chemical vapor corrosion of the flue and vent system may
occur if air for combustion contains certain chemical vapors.
Spray can propellants, cleaning solvents, refrigerator and air
conditioner refrigerants, swimming pool chemicals, calcium
and sodium chloride, waxes, bleach, and process chemicals are
typical compounds which are potentially corrosive. _,WARNING
Soot build-up indicates a problem that requires correction
before further use. Turn "OFF" gas to water heater and leave
"OFF" until repairs are made, because failure to correct the
_,WARNING cause of the sooting can result in a fire or explosion ceusln2
Obstructed or deteriorated vent systemsmay present a serious DEATH, SERIOUS BODILY INJURY, OR PROPERTY
DAMAGE.
health risk or asphyxiation.
20
Service and Adjustment (cont'd)
Draining Drain Valve Washer
The water heater should be drained if being shut down during Replacement
freezing temperatures. Also periodic draining and cleaning of
sediment from the tank may be necessary. NOTE: For replacesurnt, use a '_" x _" x ¼" thick washer
available at your nearest hardware stot_.. For ordering replace-
Turn the gas control knob to the _OFF _ position. ment washers, refer to the "Parts Order List" section.
CLOSE the cold water inlet valve to the water heater.
• OPEN a nearby hot water faucet and leave open to allow for • Turn "OFF" gas supply to water heater.
draining. • Follow "Draining" instructions.
• Connect a hose to the drain valve and terminate to an • Turning counter clockwise, remove the hex cap below the
screw handle.
adequate drain.
• OPEN the water heater drain valve to allow for tank draining. Remove the washer and put the new one in place.
NOTE: If the water heater is going to be shut down and Screw the handle and cap assembly back into the drain valve
drained for an extended period, the drain valve should be and retighten using a wrench. DO NOT OVER TIGHTEN.
left open with hose connected allowing water to terminate Follow.instructions in the "Filling The Water Heater _
to an adequate drain. section.
• Close thedrain valve. Check for leaks.
• Follow instructions in the "Filling The Water Heater" • Follow the lighting instructions in the "Lighting" section to
Section.
restartthe water heater.
Follow the lighting instructions in the "Lighting" section to
restart the water heater.
Temperature-Pressure Relief
ASSEMBLY
Valve Operation WASHER
Housekeeping
Vacuum around base of water heater for dust, dirt, and lint on a
regular basis.
AWARNING
INSTALLED IN SUITABLE AREA: To insure sumcient venti-
DISCHARGE PIPE
lation and combustion air supply, proper clearances from the
water heater must be maintained. See "Facts to Consider
Failure to install and maintain a new properly listed tempera- About the Location" section. Combustible materials such as
ture-pressure relief valve will release the manufacturer from any clothing, cleaning materials, or flammable liquids, etc. must
claim which might result from excessive temperature or pressure. not be placed against or adjacent to the water heater which
¢_n cause a _re.
AWARNING
If the temperatu_-pressure relief valve on the appliance
weeps or discharges periodically, this may be due to thermal Service
expansion. Your water heater may have a check valve
installed in the water line or a water meter with a check
valve. Consult the Sears Service Center for further informa- Before calling for repair service, read the St_ct Up Conditions
and Operational Conditions found in the Troubleshooting
tion. Do not plug the temperature-prassure relief valve. Guide of this manual.
If a condition persists or you are uncertain about the operation
AWARNING of the water heater, let a qualified person check it out.
When checking the temperature-pressure relief valve opera-
Contact SEARS Repair Services at 1-800-4-MY-HOME
tlon, make sure that (I) no one is in front of or around the
(1-800-469-4663).
outlet of the temperature-pressure relief valve discharge line,
and (2) that the water manually discharged will not causeany
property damage because the water may be extremely hot.
If after manually operating the valve, it fails to completely
reset and continues to release water, immediately close the
cold water inlet to the water heater, follow the draining
instructions, and replace the temperature-pressure relief
valve with a new one.
21
Troubleshooting Guide
Start Up Conditions
CONDENSATION THERMAL EXPANSION
Whenever the water heater is filled with cold water, a certain Water sup,ply systems may, because of such events as high line
amount of condensation will form while the burner is on: A pressure, l_luent cut-offs, the effects of water hammer among
water heater may appear to be leakingwhen in fact the water is others, have installed devices such as pressure reducing valves,
condensation. This usually happens when: check valves, back flow preventers, etc...to control these types of
• When a new water heater is filled with cold water for the problems. When these devices are not equipped with an internal
first time. by-pass, and no other measures are taken, the devices cause the
• When gas burns and water vapor is produced in water water system to be dosed. As water is heated, it expands (ther-
heaters, particularly high efficiency models where flue tem- mal expansion) and closed systems do not allow for the expan-
peratures are lower. sion of heated water.
• When you use large amounts of hot water in a short time
The water within the water heater tank expands as it is heated and
and the refill water is very cold.
increases the pressure of the water system. If the relieving point of
°
the water heater's temperature-pressure relief valve is reached, the
Moisture from the products of combustion condense on the
valve will relieve the excesspressure. The temperatux_pressure
cooler tank surfaces and form drops of water which may fall relief valve is not intendedfor the _onstant relief of thermal
onto the burn6r or other hot surfaces to produce a "sizzling" or
expansion. This is an unacceptable condition and must be
"frying" noise. corrected.
Excessive condensation can cause pilot outage due to water run- It is recommended that any devices installed which could create
ning down the flue tube onto the main burner and putting out a closed system have a by-pass and/or the system have an expan-
the pilot. sion tank to relieve the pressure built by thermal expansion in
the water system. Expansion tanks are available for ordering
Because of the suddenness and amount of water, condensation through the Sears Service Center. Contact the local plumbing
water may be diagnosed as a "tank leak". After the water in the inspector, water supplier, and/or the Sears Service Center for
tank warms up (about 1-2 hours), the condition should assistance in controlling these situations.
disappear.
Do not assume the water heater is leaking until there has been Thermal Expansion Tank Specifications
enough time for the water in the tank to warm up.
Model Tank Capacity Dimensions in Inches Pipe Fitting
An undersized water heater will cause more condensation. The Number In Gallons Diameter Length On Tank
water heater must be sized properly to meet the family's
demands for hot water including dishwashers, washing machines 153.331020 2 8 inches 12_ inches _" Male
and shower heads.
153.331050 5 11 inches 14_ inches _" Male
Excessive condensation may be noticed during the winter and
early spring months when incoming water temperatures are at
their lowest.
Expansion Tank Sizing Chart
Good venting is essential for a gas fired water heater to operate Inlet*
properly as well as to carry away products of combustion and Water HeaterCapadty (Gallons)
Water
water vapor.
Pressure 30 _ 40 50 66 82
Expansion
SMOKE/ODOR Tank 40psi 2 1 2 2 5 5
Capacity 50psi 2 ! 2 2 5 5
It is not uncommon to experience a small amount of smoke and Needed 60psi 2 2 5 5 5
odor during the initial start-up. This is due to burning offofoil 70psi 2 2 5 5 5
from metal parts, and will disappear in a short while. 2 5 5 5 5
80psi
22
Troubleshooting Guide (cont'd)
Operational Conditions
HOT COLD WAT_ HEATER SMELLY WATER
COLDWATER PRESSURE
bINLETFITTING REDUCING In each glasslined water heater there is installed at least one
VALVEWITH
BY-PASS anode rod (see parts section) for corrosion protection of the
tank. Certain water conditions will cause a reaction between this
rod and the water. The most common complaint associated with
the anode rod is one of a "rotten egg smell". This odor is derived
TANK from hydrogen sulfide gas dissolved in the water. The smell is
the result of four factors which must all be present for the odor
to develop:
PRESSURE
GAUGE a. a concentration of sulfate in the supply water.
WATER b. litde or no dissolved oxygen in the water.
SHUTOFF
c. a sulfate reducing bacteria within the water heater. (This
RECOMMENDED INSTALLATION harmless bacteria is non-toxic to humans.)
(VERTICAL MOUNTING) d. an excess of active hydmgen in the:tank. This is caused by
the corrosion protective action of the anode.
If the smelly water persists after the anode replacement and chlo-
HOT STRAPPING rination treatment, we can only suggest that continuous chlori-
nation and filtering conditioning equipment be considered to
eliminate the water problem.
(2) AWARNING
PRESSURE
GAUGE
HYDROGEN GAS: Hydrogen gas can be produced in a hot
ALTERNATE RECOMMENDED water system that has not been used fo'r a long Perind of tlme
INSTALLATION (generally two weeks or more). Hydrogen gas is extremely
(HORIZONTAL MOUNTING) flammable and explosive. To prevent the possibility of injury
under these conditions, we recommend the hot water faucet
be opened for several minutes at the kitchen sink before any
electrical applianceswhich are connected to the hot water sys-
STRANGE SOUNDS tem are used (such as a dishwasher or washing machine). If
hydrogen gas is present, there will probably be an unusual
Possible noises due to expansion and contraction of some metal sound similar to air escapingthrough the pipe as the hot water
parts during periods of heat-up and cool-down do not represent faucet is opened. There must be no smoking or open flame
harmful or dangerous conditions. near the lancet at the time it isopon.
23
Troubleshooting Guide (cont'd)
Operational Conditions
(cont'd)
HIGH TEMPERATURE SHUT OFF SYSTEM WATER IS TOO HOT
This water heater is equipped with an automatic gas shut offsys- • The temperature adjustment dial may be set too high. See the
tern. The high temperature shut off is built into the gas control "Temperature Adjustment" section.
valve. This system shuts off the gas supply to the water heater NOTE: A period of time is necessary after an adjustment has
burners when high water temperatures are present. It is non- been made for the water temperature to reach the new tem-
resettable. If the high temperature shut off activates, the gas con- perature setting.
trol valve must be replaced. If this were to occur, turn _OFF" the
entire gas supply to the water heater. Contact the Sears Service • If lower temperature settings will not lower die water tempeta-
Center. ture, call the SeaxsService Center.
AWARNING AWARNING
Should overheating occur or the gassupplyFailto shut off, HOTTER WATER CAN SCALD: Water heaters are intended to
turn OFF" the manua gascontro valve to the app lance. produce hot water. Water heated to a temperature which will
satisfyclothes washing,dish washing,and other sanitizing needs
can scald and permanently injure you upon contact. Some peo-
NOT ENOUGH OR NO HOT WATER ple are more likely to be permanently injured by hot water than
others. These includethe elderly,children,the infirm, or physicag
ly/mentally handicapped.If anyone usinghot water in your home
Check the pilot flame. It may have gone out. All models have fits into one of these groups or if there is a localcode or state law
[ Check
an the manual
opening behind gas
the shut
outeroffvalve
door fortoviewing
be sure the
it ispilot.
open. requiring a certain temperature water at the hot water _ then
If the pilot is not lit, follow the "Lighting" instructions in this mu must take specialprecaution_ In addition to usingthe lowest
manual are located above the gas control valve on the water x_sible temperature setting that satlsEesyour hot water needs,
heater to relight thepilot. If the water was extremely hot and is means such as a mixing valve,should be usedat the hot water
now cold, the high limit safety temperature shut off may have taps used by these people or at the water heater. M_ng valves
put out the burner and pilot. If the high temperature shut off are availableat plumbing supply or hardware stor-_ Follow man-
activates, the gas controlvalve must be replaced. Contact the ufacturers instructions for installation of the valves. Before
Sears Service Center. changing the factory setting on the thermostat, read the
The gas control knob must be mined to the _ON" position. "Temperature Regulation" seclJonin this manual.
The temperature adjustment dial may be set too low. See the
"Temperature Regulation" section.
The gas company can check the gas input to see if it is correct.
An underflred water heater will not heat water as quickly. AWARNING
i Look for leaking or open hot water faucets. Make sure all are
Due to the nature of the typical gas water heater, the
dosed.
water temperature in certain situations may be hotter
• The cold water inlet temperature may be colder during the than the thermostat setting.
winter months. It will take longer to heat die water and seem Short, frequent draws of hot water - especially with very
like less hot water.
cold incoming water - can shock the thermostat into brief
• If you cannot find what is wrong, call the Sears Service Center. operation resulting in hotter and hotter layers of water
closer to the top of the tank.
Changes in hot water usage patterns or raising the tem-
perature differential between the cut-on of the thermo-
stat and the cold water temperature will usually eliminate
the problem.
24
Troubleshooting Guide (cont'd)
Leakage Checkpoints
Use this guide to check a "Leaking_ water heater. Many suspect-
ed "Leakers_ are not leaking tanks. Often the source of the water A CAUTION
can be found and corrected. Read this mhnual first. Then before checking the water
heater make sure the gas supply has been turned
If you are not thoroughly familiar with your local gas codes your "OFF", and "neverturn the gas "ON" before the tank is
water heater, and safety practices, contact the S_ I completely full of water.
to check the water heater.
A CAUTION [
Never use this water heater unlessit is completely filled I
with water. To prevent damage to the tank, the tank I
must he filled with water. Water must flow from the hot I
water faucet before turning "ON" gas to the water I
heater.
Water from a
drain valve may be due to the valve opened
slightly.
25
Parts Order List
THE ECONOMIZER TM 5 GAS WATER HEATERS
MODEL NUMBERS:
153.332318 30 G'al. High Altitude
153.332362 30 Gal.
153.332418 40 Gal. High Altitude
153.332462 40 Gal.
153.332562 50 Gal.
16
O.
2
17
14
15
13
/ 10 11
26
Parts Order List (cont'd)
THE ECONOMIZER TM 5 GAS WATER HEATERS
MODEL NUMBERS:
153.332318 30 Gal. High Aldtude
153.332362 30 Gal.
153.332418 40 _al. High Altitude
153.332462 40 Gal.
153.332562 50 Gal.
Model Numbers
KEY 153.332318 ] 153.332362 153.332418 153.332462 153.332562
NO. PART DESCRIPTION PART NUMBERS
1 Temperature-Pressure Rdief Valve 9000071 9000071 9000071 9000071 9000071
2 PrimaryAnode Rod 9000279 9000279 9000279 9000279 9000279
3 Model Rating Plate t 0270118 0270118 0270118 0270118 0270118
4 Drain Valve 9000254 9OO0254 9000254 9000254 9000254
5 Drain Valve Washer (_TAz"
x _Y_"x _" thick)** 9001584 9001584 9001584 9001584 9061584
6 Pilot 9000284 9000284 9000284 9000284 9000284
7 Thermocouple* 42-33900 42-33900 42-33900 42-33900 42-33900
8 Pilot Tubing w/Fittings 9000278 9000278 9000278 9000278 9000278
9 Burner Orifice 0230181 0230182 0230122 0230129 0230129
Drill Size (#43)HA (#40) (#41)HA (#38) (#38)
10 Manifold 9002613 9002613 9002615 9002615 9002617
11 Burner 9002411 9002411 9002411 9002411 9002411
12 Outer Door 9000351 9000351 9000351 9000351 9000351
13 Inner Door 9000281 9000281 9000281 9000281 9000281
14 Gas Control Valve F145-1278 F145-1278 F145-1278 F145-1278 F145-1278
15 Temperature Adjustment Knob F145-1280 F145-1280 F145-1280 F145-1280 F145-1280
16 Dip Tube 9001852 9001852 9001852 9001852 9001852
17 Flue Baffle 9000360 9000360 9000360 9000360 9000360
18 Draft Hood 9000272 9000272 9000272 9000272 9000272
# Manual 0002915360
# Mag-Erad 23600
Now that you have purchased your Gas Water Heater, should a need ever exist for repair parrs or service, simply contact any SEARS Service
Center or call 1-800-4-MY-HOME (1-800-469-4663). Be sure to provide pertinent facts when you call or visit.
All parts listed may be ordered from any SEARS Service Center, most SEARS stores and by calling 1-800-366-PART (1-800-366-7247). If the
parts you need are not stocked locally, your order will be electronically transmitted to a SEARS Repair Parts Distribution Center for handling.
The model number of your Gas Water Heater will be found on the model rating plate located near the gas control valve.
WHEN ORDERING REPAIR PARTS, ALWAYS GIVE THE FOLLOWING INFORMATION:
MODEL NUMBER PART DESCRIPTION
PART NUMBER NAME OF ITEM
27
Warranty
a. Adjustingthermostat
About Your Warranty b. Lightingpilot
THE PRICEOF YOUR WATER HEATER DOES NOT INCLUDE c.Leaksin pipes or fittings
A FREE CHECKUP SERVICE CALL. On Water Heater Installations d. Improperventing
e. Condensation
Arranged BySears,Searswirrants the installation.
ON INSTALLATIONS NOT MADE BY SEARS AUTHORIZED This manual is in non-technical hnguage. It may help you ,avoidthe
CONTRACTORS: cost of a needless service'call.Manyservice calls reallyarent needed.
1.YourSearswarranty appliesto the product only. Such aswhen:
2. Searsdoes not warrant the installation. 1. The gas is turned "OFF".
3. A charge wilt be made on service calls due to poor or incomplete 2. The pilot is out.
installation.These include: 3. A gas orwater leak is due to loose pipe orconnections.
To obtain warranty service, SIMPLY CALL 1-800-4-MY-HOME (1-800-469-4663). This warranty applies only while this product is in use
in the United States.
This warranty gives you specific legal rights and you may also have other rights which vary from state to state.
SEARS, ROEBUCK AND CO., Dept. 817 WA, Hoffman Estates, IL 60179
,_-gs Sears, Roebuck and Co., Hoffman Estates, IL 60179 U.S.A. _0zg_s360-0