Professional Documents
Culture Documents
056-032 xx60 With No Bus Breaker
056-032 xx60 With No Bus Breaker
• DESCRIPTION
The Mains Controllers (DSE8760 / DSE8660) were designed to operate with both a mains AND a bus load switching
device. This document details how to achieve the functionality of a system where the generator bus load switch device
is NOT fitted.
When the generator controller (DSE8710 / DSE8610) closes its breaker onto the generator common bus with the
mains breaker is closed, the generator is directly connected to the mains as there is no common bus breaker to isolate
the common bus from the mains. Until the DSEXX60 controller closes a common bus breaker, it will not control the
power of the generator(s). As there is no bus breaker for the DSEXX60 to control, it will need to be simulated
externally. This will then enable the DSEXX60 to control the power of the generator(s). However, we first need to
instruct the DSEXX10 generator controller what to do when it first closes its breaker to the mains, before simulating
the closure of the common bus breaker.
• DSEXX60 CONFIGURATION
• DSEXX60 WIRING
One side of a normally closed contact from the external slave relay connected to the DSEXX60 for ‘Open Bus
Output’ must be connected to battery negative. This is used to switch the input configured to ‘Bus Closed Auxiliary’.
This will simulate the closing of the bus breaker.
• DSEXX10 WIRING
An auxiliary of the mains load switch is required to feed a battery negative signal into the configured ‘Mains Parallel
Mode’ input of all of the generator controllers (DSEXX10).
An auxiliary from the output ‘Mains Failed To Open’ from the DSEXX60 controller is required to feed a battery
negative signal into the user configured ‘Mains Failed To Open’ input of all of the generator controllers (DSEXX10) to
stop them closing onto the common bus when the mains breaker has failed to open.