Professional Documents
Culture Documents
Starting the Boiler without the BRP is an unusual activity, and should
therefore be carried out in exceptional cases only.
6. Light-off the Boiler in the usual manner. When the first ignitor is
prov- en in service, the feedwater flow setpoint will automatically
be con- trolled to 40%. Warm-up the Boiler in the usual manner.
Drain flow will increase above 40% as the Boiler water swells.
7. When the pressure in the reheater reaches approximately 70 psig
4.9 kg/cm2g) with the HP/LP bypass system in operation,
feedwater heat- er no. 7 can be placed into operation to preheat
the feedwater and raise steam production. Care must be taken to
control the steam flow to FWH no. 7 during this period such that
the LP bypass valve does not close too much, disabling both the
cooling flow through the re- heater and LP pressure control. In
addition, monitor the fluid condition entering the evaporator. If sub-
cooling is less than 10°F (6°C), then increase the economizer inlet
flow or decrease the feedwater temper- ature.
10. At approximately 40% TMCR load the Boiler will enter the once-
through mode. When once-through mode is proven, the warm-
keeping system should be put into operation.
3. The HWL-1 will open in auto mode when the level in the SST
reaches the high setpoint. If additional drain capacity is needed,
HWL-2 will open when HWL-1 reaches full open and level
continues to rise.