Sensible Heat Factor - Case
Sensible Heat Factor - Case
T1 T2
Sensible Cooling
It is the process of lowering the enthalpy/heat content of
air within the conditioned space due to a decrease in its
DBT. The Humidity of the process remains unchanged.
T2 T1
Humidification
It is the process of increasing the enthalpy (heat content) of the
conditioned space by an addition of moisture (humidity).
The DBT of the space remains unaffected by Humidification.
W2
W1
T
Dehumidification
It is the process of decreasing the enthalpy (heat content) of the
conditioned space by a removal of moisture /lowering of humidity.
The DBT of the space remains unaffected by Humidification.
W1
W2
T
What’s this
W2
W1
T1 T2
What’s this
W1
W2
T2 T1
BPUT
OD Air at 45°C DBT & Humidity Ratio 20 g/kg is processed in a SAC @10 kg/min to
25°C DBT & Humidity Ratio 10 g/kg.
Calculate: a. Cooling capacity of the system = m(h1-h2)
b. Condensate removed per min = m (w1-w2)
c. SHF = SH/(SH+LH)
T2 = 25°C T1 = 45°C