Professional Documents
Culture Documents
Designing and Maintenance of Control
Designing and Maintenance of Control
➢ We’ve created this guide to provide an overview of the key design considerations
applicable to industrial control panel design, including schematics, relevant
regulatory standards, and design considerations relating to every facet of
effective control panel design for industrial equipment and machinery.
Chapter 5
➢ Most induction motors are started directly on line, but when very large motors
are started that way, they cause a disturbance of voltage on the supply lines
due to large starting current surges.
➢ This is the reduced voltage starting method. Voltage reduction during star-delta
starting is achieved by physically reconfiguring the motor windings as
illustrated in the figure below. During starting the motor windings are
connected in star configuration and this reduces the voltage across each
winding 3. This also reduces the torque by a factor of three.
➢ The Star/Delta starter is manufactured from three contactors, a timer and a
thermal overload. The contactors are smaller than the single contactor used in
a Direct on Line starter as they are controlling winding currents only. The
currents through the winding are 1/root 3 (58%) of the current in the line .
➢ Power wiring
➢ Control wiring
➢ Power wiring – Power wiring refers to the distribution of power. In the case of
VFD flow of power from VFD to the motor. As you know that we are making
the wiring of the 3 phase VFD and motor. Therefore 3 wires carry 3 phases i.e
(R, Y, & B) from the circuit breaker to the input terminal of the VFD and 3 wires
from VFD to the motor. This figure also helps you to understand the power
wiring of a VFD.
➢ Control wiring – control wiring is used for controlling purposes. They are used
to give commands to the control devices or communication between electrical
devices. In control wiring, there is no use of heavy voltage and therefore gauge
of wire is thinner. In control wiring normally standard 24vdc is used.
➢ The first stage of a VFD is the converter, which comprises six diodes, which are
similar to check valves used in plumbing systems. These allow current to flow
in only one direction; the direction shown by the arrow in the diode symbol. For
example, whenever A-phase voltage (voltage is similar to pressure in plumbing
systems) is more positive than B- or C-phase voltages, that diode opens and
allows current to flow.
➢ When B phase becomes more positive than A phase, B-phase diode opens and
A-phase diode closes. The same is true for the three diodes on the negative side
of the bus. Thus, we get six current pulses as each diode opens and closes. This
is called a 6-pulse VFD, which is the standard configuration for current VFDs.
Chapter 6