M1 Notification AccBMD UNIT2 O/H-Overhauling 12.04.2020 800115925
M1 Notification AccBMD UNIT2 O/H-Overhauling 26.02.2021 800146777
M1 Notification AccTMD UNIT2 O/H-Overhauling 13.04.2020 800115986
M1 Notification AccTMD UNIT2 O/H-Overhauling 07.09.2021 800167092
M1 Notification AccBMD UNIT2 O/H-Overhauling 31.12.2021 800180217
M1 Notification AccBMD UNIT2 O/H-Overhauling 06.03.2021 800147807
M1 Notification AccBMD UNIT2 O/H-Overhauling 25.11.2021 800175831
M1 Notification AccTMD UNIT2 O/H-Overhauling 18.01.2020 800109809
M1 Notification AccTMD UNIT2 O/H-Overhauling 28.12.2019 800107981
M1 Notification AccTMD UNIT2 O/H-Overhauling 10.11.2021 800174084
M1 Notification AccTMD UNIT2 O/H-Overhauling 13.04.2020 800115998
M0 PTW Issued ELD1 UNIT2 D- Unit Shut down 06.03.2022 800187904
M1 Outstanding NotiELD1 UNIT2 D- Unit Shut down 23.04.2022 800194021
M1 Notification AccBMD UNIT2 D- Unit Shut down 16.04.2022 800193013
M1 Outstanding NotiELD1 UNIT2 D- Unit Shut down 23.04.2022 800194022
M1 Notification AccBMD UNIT2 D- Unit Shut down 22.04.2022 800193847
M1 Notification AccBMD UNIT2 D- Unit Shut down 14.01.2022 800181786
M1 Notification AccBMD UNIT2 D- Unit Shut down 26.04.2022 800194343
M1 Notification AccBMD UNIT2 D- Unit Shut down 19.04.2022 800193372
M1 Notification AccBMD UNIT2 D- Unit Shut down 23.11.2021 800175616
M1 Notification AccBMD UNIT2 D- Unit Shut down 10.04.2022 800192130
M1 Notification AccTMD UNIT2 D- Unit Shut down 06.01.2022 800180853
M1 Notification AccBMD UNIT2 D- Unit Shut down 01.01.2022 800180265
M1 Notification AccTMD UNIT2 D- Unit Shut down 06.01.2022 800180897
M1 Outstanding NotiC&I UNIT2 D- Unit Shut down 19.04.2022 800193329
M1 Notification AccTMD UNIT2 D- Unit Shut down 21.01.2022 800182591
M1 Notification AccTMD UNIT2 D- Unit Shut down 06.01.2022 800180855
M1 Notification AccTMD UNIT2 D- Unit Shut down 02.04.2022 800191142
M1 Notification AccTMD UNIT2 D- Unit Shut down 05.01.2022 800180818
M1 Notification AccBMD UNIT2 D- Unit Shut down 05.03.2022 800187827
M1 Notification AccBMD UNIT2 D- Unit Shut down 26.04.2022 800194351
M1 Notification AccBMD UNIT2 D- Unit Shut down 26.04.2022 800194350
M1 Notification AccBMD UNIT2 D- Unit Shut down 26.04.2022 800194349
M1 Notification AccBMD UNIT2 D- Unit Shut down 26.04.2022 800194344
M1 Notification AccBMD UNIT2 D- Unit Shut down 21.04.2022 800193713
M1 Notification AccBMD UNIT2 D- Unit Shut down 21.04.2022 800193714
M1 Notification AccBMD UNIT2 D- Unit Shut down 21.04.2022 800193716
M1 Notification AccBMD UNIT2 D- Unit Shut down 04.04.2022 800191374
M1 Outstanding NotiTMD UNIT2 D- Unit Shut down 24.04.2022 800194053
M1 Notification AccTMD UNIT2 D- Unit Shut down 09.12.2021 800177670
M1 Outstanding NotiTMD UNIT2 D- Unit Shut down 24.04.2022 800194054
M1 Notification AccTMD UNIT2 D- Unit Shut down 25.01.2022 800183037
M1 Outstanding NotiTMD UNIT2 D- Unit Shut down 24.04.2022 800194052
M1 Notification AccTMD UNIT2 D- Unit Shut down 01.12.2021 800176623
M1 Outstanding NotiTMD UNIT2 D- Unit Shut down 24.04.2022 800194051
M1 Notification AccBMD UNIT2 D- Unit Shut down 17.02.2022 800185922
M5 Outstanding NotiBOP UNIT2 D- Unit Shut down 04.03.2021 870001284
APH-A seals clearance checking required
APH-B seals clearance checking required
All Corner Coal Burner Tip Found Damage
TG BARRING SPEED STOPPED DURING SHUTDOWN
GEN TE SEAL OIL FLOWMETER NOT WORKING
APH-A & B Sector Plate Damage
MSV-02 Passing suspected
GD-1B1 & 1B2 Damper plate damage
HPTF 1-XY VIBRATION ABOVE ALARM LIMIT
U#2 Main turbine BRG. no-2,5 & TG brg no
Axial shift on higher side above 400mw
TURBINE LUB OIL TEMPERATUR RUNNING HIGHE
10238853 LRSB-128 Rotary Motor takin high current
ID Fan-B Motor NDE Brg temp running high
BOTH PA FAN BLADE PITCH GAP CHECKING REQ
Mill-2B Motor Winding temp running high
10C22 DC VOLTAGE LOW (<30KV)
Ring Hdr Drain MOV B-99 & Its MIV Pasing
BP Lwr Hdr Drn S-66 & S-67 valve Passing
APH-2A AIR MOTOR ROTATING
permanent grating reqd below PC- BT
PAD-4B HEAVY LEAKAGE FROM DAMPER
HRHV-106 VALVE PASSING REPITITIVE
PAD-4B air leakage
EXV-147 valve operation approach N/A
LIQUID IN GENERATOR SWITCH TE HIGH
CRHV-101 VALVE PASSING REPITITIVE
CRHV-106 VALVE PASSING REPITITIVE
LPBP-SV-1 INOPERATIVE
JOP Header Pressure found low
hot air leakage near aph 2A GB area
boiler Drum IBD valve B-96 & 97 Passing
SH initial filling valve passing
Bottom Ring Hdr Drain B-99 Passing 26.04.2022
Low Point Drain Master MIV S-78 passing
1A22 FIELD SPARK RATE HIGH
2A22 FIELD SPARK RATE HIGH
1B12 FIELD SPARK RATE HIGH
U-2 ESP Pass-B I/L duct insulation dmage 30.04.2022
CRHV-101 PASSING OBSERVED
SO RING RELIVE FLOW METER EE END NOT WOR
HRHV-106 PASSING OBSERVED
DC JOP PUMP DEVELOPING LESS PRESSURE
MAL-12 PASSING OBSERVED
UNIT-2 MAL-12 VALVE PASSING OVSERVED
MAL-22 PASSING OBSERVED
55mtr door cooling O/L line drain miv
Additional screen required in CT basin
SECTOR PLATE REPLACEMENT REQUIRED S/D JOB - 15 DAYS.
SECTOR PLATE REPLACEMENT REQUIRED S/D JOB - 15 DAYS.
COMPLETE SET BURNER REPLACEMENT REQUIRED. O/H - 20 DAYS.
TG BARRING SPEED DECREASE TO 8RPM DUE TO LUBE OIL TEMP. SUDDENLY DROPED FROM 67 DEG.C TO 50DEG.C
OVERHAULING WORK
VALVE TO BE REPLACED FROM CLASS-800 TO CLASS-1500 AFTER RECEIVING OF MATERIAL ,PR NO-5000001578
VALVE TO BE REPLACED FROM CLASS-800 TO CLASS-1500 AFTER RECEIVING SPARE, PR NO-5000001578
UNDER OBSERVATION
ALL BEARINGS PRESSURE CHECKED FOUND NORMAL.LIFT CAN BE CHECHED AT NORMAL SHAFT TEMPERATURE