Function description
06.04.2011 48-020-212EN02
1/15
(1)
Function description
FK 3-12 spring operating mechanisms
For circuit breakers
Contents Page
Introduction 3
Functional units 3
Operating states 6
Closing operation 10
Operating operation 14
06.04.2011 48-020-212EN02
2/15
(2)
Function description
FK 3-12 spring operating mechanisms
For circuit breakers
Introduction
Fonctional units
70.26
70.19
70.24
70.52
70.42
70.18
70.31
70.12
70.44
70.17
70.43
70.15
71.09
70.14
71.35
70.16
70.13
70.11
06.04.2011 48-020-212EN02
3/15
(3)
Function description
FK 3-12 spring operating mechanisms
For circuit breakers
Energy store • Closing spring 70.25 stores energy to close the circuit breaker and to
charge trip spring 70.20. Surplus energy ensures that the circuit breaker
can be safely closed in all situations.
• Trip spring 70.20 furnishes the energy necessary to trip the circuit
breaker. The trip spring may be in the operating mechanism or in the
circuit breaker, depending on the circuit breaker design.
Energy store
• Motor 70.01 and gearing 79.04 serve to charge closing spring 70.25
Charging mechanism
Closing unit • On closing, the energy of closing spring 70.25 is transmitted to cam
disk 70.10 via closing chain 70.26, crank lever 71.43 and closing shaft
70.09. The cam disc drives main shaft 70.12 via roller lever 70.11. The
circuit breaker is closed and trip spring 70.20 charged via drive lever
70.18 and the linkage
• Cam disc 70.10 controls the travel/time characteristic of the main con-
tact during closing.
Tripping unit • If trip spring 70.20 is mounted in the operating mechanism, its energy is
transmitted to the circuit breaker via trip chain 70.19, main shaft 70.12
and drive lever 70.18.
• The motion is retarde by trip dashpot 70.17 at the end of the tripping
process.
Latches • When closing spring 70.25 is charged, closing latch 70.05 supports it
through crank lever 71.43 and support pin 71.44.
• When trip spring 70.20 is charged, trip latch 70.16 supports it by the
lever arm of roller lever 70.11 and main shaft 70.12.
06.04.2011 48-020-212EN02
4/15
(4)
Function description
FK 3-12 spring operating mechanisms
For circuit breakers
Auxiliaire switch • Auxiliary switch 70.21 Coupled to main shaft 70.12 serves as a refer-
ence for the main contact for control, signaling and interlock functions
• When the circuit breaker is closed, one contact of auxiliary switch 70.21
interrupts the closing coil circuit and thus prevents further electrical ex-
citation.
• When the circuit breaker is in the tripped position, one contact of auxil-
iary switch 70.21 breaks the operating release coil circuit and thus pre-
vents further electrical excitation.
Motor limit switch • Motor limit switch 70.24 closes and interrupts the motor circuit. It also
performs interlock functions.
• While closing spring 70.25 is being charged, one contact of motor limit
switch 70.24 interupts the closing coil circuit and thus prevents
premature electrical closing operation.
Mechanical closing • When the circuit breaker is closed, a lever coupled to main shaft 70.12
interlock disables closing latch 70.05 and prevents any further release of the
closing system.
Indicators • Circuit breaker position indicator 70.52 displays the position of the main
contact (I or O).
• Spring position indicator 70.31 displays the state (charged or dis-
charged) of closing spring 70.25.
Auxiliairy devices • Mechanical manual releases 70.07, 70.13 permit switching operations
and tools during field service.
• Hand crank 70.53 permits manual charging of closing spring 70.25.
06.04.2011 48-020-212EN02
5/15
(5)
Function description
FK 3-12 spring operating mechanisms
For circuit breakers
Operating states
Note • The two illustrations below show the possible operating states and
sequences of an operating mechanism. These are characterised
mains by the position of the circuit breaker to which the mechanism is
attached, and by the position of the closing spring. The position of the
spring is always linked to the position of the circuit breaker. The
positions of the auxiliary switch and motor limit switch are important
secondary characteristics.
• An operating mechanism remains in a steady operating state until its
position is changed by an external control command. It can then pass
through well-defined transient (unsteady) operating states.
CHARGING
and
CHARGING
06.04.2011 48-020-212EN02
6/15
(6)
Function description
FK 3-12 spring operating mechanisms
For circuit breakers
Y1 Y2
M
S2 S2
Y1 Closing coil
Note • The following functions will now be described : charging the energy
store, closing, recharging and opening. The operating mechanism and
the circuit breaker pass through the operating states in the order
1→2→3→4→2
06.04.2011 48-020-212EN02
7/15
(7)
Function description
FK 3-12 spring operating mechanisms
For circuit breakers
70.26
70.24
70.42
70.31
71.44
71.29
71.43
71.35
A
06.04.2011 48-020-212EN02
8/15
(8)
Function description
FK 3-12 spring operating mechanisms
For circuit breakers
06.04.2011 48-020-212EN02
9/15
(9)
Function description
FK 3-12 spring operating mechanisms
For circuit breakers
Closing operation
70.19
70.52
70.26
70.18
70.24
70.31
70.09 70.12
B
71.43
70.29
70.16
06.04.2011 48-020-212EN02
10/15
(10)
Function description
FK 3-12 spring operating mechanisms
For circuit breakers
• Cam disc 70.10 turns roller lever 70.11, which follows it, in the CLOSE
direction. The circuit breaker is closed via main shaft 70.12, operating
lever 70.18 and an attached linkage. At the end of the closing move-
ment, after a 60° rotation, specially designed cam disc 70.10 brings
main shaft 70.12 to a safe, low-impact stop against trip latch 70.16 via
a lever arm of roller lever 70.11. At the same time, cam disc 70.10 has
moved away from roller lever 70.11 and the circuit breaker can be trip-
ped.
• In the course of the closing movement, trip spring 70.20 is charged via
trip chain 70.19.
• The return-stop of pair of winding lever 71.32 keeps the fast gearing
stages from tracking the motion during the closing operation.
• After closing shaft 70.09 has turned through approx. 180°, crank journal
70.29 passes through bottom dead point B. The Kinetic energy still
possessed by crank wheel 70.30 is returned to closing spring 70.25
(recovered) via chain 70.26. By virtue of this principle, the closing
movement is brought to a gentle, impact-free stop.
06.04.2011 48-020-212EN02
11/15
(11)
Function description
FK 3-12 spring operating mechanisms
For circuit breakers
70.25 70.22
70.24
06.04.2011 48-020-212EN02
12/15
(12)
Function description
FK 3-12 spring operating mechanisms
For circuit breakers
• When motor limit switch 70.24 is actuated by motor limit switch actuat-
ing cam 70.22 at the end of the closing movement, the motor circuit is
made and closing spring 70.25 is automatically recharged.
• If no breaking operation has taken place during the charging process,
the circuit breaker is in steady operating state 4 at the end of the charg-
ing process. This is the normal operating state of all circuit breakers in
the electric power grid.
Y1 Y2
M
S2 S2
06.04.2011 48-020-212EN02
13/15
(13)
Function description
FK 3-12 spring operating mechanisms
For circuit breakers
Opening operation
70.21 70.20
70.52
70.12
70.17
70.15
70.16
70.13
70.05
Y1 Y2
M
S2 S2
06.04.2011 48-020-212EN02
14/15
(14)
Function description
FK 3-12 spring operating mechanisms
For circuit breakers
06.04.2011 48-020-212EN02
15/15
(15)