1.0 INTRODUCTION ........................................................................................... 4
1.0 INTRODUCTION
WZR is preparing for the development of the Kurdamir field located approximately 60
kilometres south south-west of the city of Sulaymaniyah, in the southeast part of the Kurdistan
Region of Iraq, as shown in Figure 1.
The Infrastructure & Drilling Facilities will be supported by accommodation Camps and Oil
Police Force Camps in the vicinity of well locations.
2.0 SCOPE
This specification establishes the minimum requirement for staff and labor cabins to
accommodate the workforce required by WZR (Company) activities as explained above. It
covers design, construction & supply of cabins.
Where the provider (hereinafter referred to as Supplier or Contractor), proposes use of
existing cabin facilities, these shall be subject to formal review and approval by WZR
(Company). Modifications to bring standards of existing cabin facilities in accordance with the
present specifications shall be the Supplier’s responsibility.
This Specification should be read in conjunction with all referenced standards and documents.
Recreational facilities
IT server room
Driver rest room
Canine rest room
Weigh bridge office
Guard tower
Guard box
Access control/personnel offices
Relative Humidity:
Relative Humidity (max): 92%
Relative Humidity (min): 18%
Wind:
Prevailing Wind Direction: SW & NE
Mean Wind Velocity: 1.0 to 3.3 m/s
Maximum Possible Gusts: Up to 15 m/s
Maximum wind speed: 11.2 m/s
Seismic:
Seismic Zone: High Seismic Hazard Zone, ZONE IV, Liable to MSK Intensity VIII (Damaging)
EN STANDARDS
EN 14509 Self-supporting double skin metal faced insulating panels. Factory made products.
Specifications
EN-13501-1 Fire classification of construction products and building elements - Part 1:
Classification using data from reaction to fire tests
EN 13501-2 Fire classification of construction products and building elements Classification
using data from fire resistance tests, excluding ventilation services
ELECTRICAL
IEC 60044-1 Instruments transformers – current transformers
IEC 60044-2 Instruments transformers – voltage transformers
IEC 60051 Analogue electrical measuring instruments and their accessories
IEC 60079-10 Classification of areas - Explosive gas atmospheres
IEC 60112 Evaluation and qualification of electrical insulating materials and systems
IEC 60269-1 IEC 60269-2-1 Low voltage fuses
IEC 61439-1:2009 IEC 61439-2:2009 Low voltage switchgear and control gear assemblies
IEC 60529 IEC 60664-1 Degrees of protection
IEC 60688 IEC 60947-1 Electrical measuring transducers for converting AC and DC electrical
quantities to analogue or digital signals
IEC 60947-2 IEC 60947-3 Low voltage switchgear and control gear assemblies
SAFETY
FOOD SAFETY
HACCP Regulation
EC legislation for hygiene of foodstuffs
Regulation (EC) No. 852/2004 & 853/2004
FURNITURE
ISO 3055 Kitchen equipment — Coordinating sizes
ISO 4211 Furniture — Tests for surfaces — Part 4: Assessment of resistance to impact
ISO 7170 Furniture — Storage units — Determination of strength and durability.
ISO 7171 Furniture — Storage units — Determination of stability.
ISO 7172 Furniture — Tables — Determination of stability.
ISO 7173, Furniture — Chairs and stools — Determination of strength and durability.
ISO 7174-1, Furniture — Chairs — Determination of stability — Part 1: Upright chairs and
stools.
ISO 7174-2, Furniture — Chairs — Determination of stability — Part 2: Chairs with tilting or
reclining mechanism.
ISO 8019, Furniture — Tables — Determination of strength and durability.
ISO 19833 Furniture — Beds — Test methods for the determination of stability, strength and
durability
ISO 21015 Office furniture — Office work chairs — Test methods for the determination of
stability, strength and durability
Supplier shall be solely responsible for ensuring that the facilities provided meet the
minimum standards and requirements set by all applicable national and local codes and
other governing authorities and obtain all necessary inspections, permits, occupancy licenses
in order that the facility may be occupied as per the agreed schedule.
Supplier shall provide a copy of their HSSE management system detailing the relevant HSSE
requirements for the construction of the cabins and the management thereof in terms of
HSSE for WZR approval.
Cabins shall be of single-story type and uniform in color.
All furniture shall be sturdy & of good quality. Samples of furniture to be provided shall be
inspected by WZR & approved.
All cabins are a non-smoking premises.
The following requirements shall apply:
1. All cabins shall be of good quality and suitable for a minimum of 20 years of use.
3. Each cabin shall be supplied with integral FF&E (Furniture, Fittings and Equipment)
including toilet/bathroom facilities.
4. All sandwich panels shall be fire tested & rated. Cabin floors, walls and ceilings testing
and rating shall be performed in accordance with standards EN 13501-1 and EN
13501-2, and shall have a fire rating (reaction to fire) class of B-s2d0 as a minimum.
5. Structures and cabin materials shall not be made of wood or materials, which are likely
to be detrimentally affected by humidity or termites.
6. All cabins will be elevated from the ground at a height of 30 cm and supported by a
concrete sleepers/blocks (by others).
7. Any opening in cabin walls, roof, floor or doors shall be properly sealed.
8. Cabin tag number shall be engraved on a stainless-steel tag plate, installed on the main
entrance door of each cabin, with letters in black color (RAL9005), and tags as per
Appendix1. All tags (with a full description of each building item) shall be submitted to
WZR approval prior commencing the work. Once the tag list is approved, WZR will
provide all sequential numbers.
9. WALLS
All walls shall be fixed on the steel structure of the existing base structure.
11. ROOFING
First layer shall be min. 100 mm Sandwich panel as described above; the second
layer shall be plastic Laminate panel.
Roof shall be designed to avoid rainwater or snow accumulation. Fixed rain
gutters/pipes shall be provided at cabin corners (or where required).
Roof Imposed loads=0.75 kN/m2 (#15.7 psf).
12. HVAC
HVAC split units shall maintain a maximum of 24oC summer and a minimum of 21oC
winter.
All HVAC units shall be fitted with a heat pump as they are used as heaters during
winter period.
External HVAC units shall be skid mounted or racks, interior units to be bolted in a
hanging position.
The most environment-friendly refrigerant (such R-290 or R-600A) shall be used in
all HVAC units.
Maximum noise level in an accommodation unit, measured as an eight (8) hour time
weighted average while the air conditioning unit is running, shall not exceed forty
(40) dB(A).
14. DOORS
All doors shall be manufactured from PVC.
External doors shall have a steel frame, a minimum of three hinges, well insulated,
fitted with closure spring and furnished with a handle lock with 3 keys.
15. WINDOWS
Windows shall be manufactured from PVC. Windows to be fitted with internal
shutters constructed from PVC (or internal blackout curtains). Anti-insect covers
(screens) shall be provided for all windows.
Windows glass to be double glass with 4 mm thickness. All glasses must be purposed
for use on windows.
Rain shade is required for all windows.
Hot water boiler shall be installed in the bathroom and equipped with check valve,
& overheating protection.
Two or Three-Runner Heavy Duty Container Skid with end rails, cross runners and
Third Party certified lifting trunnions at each side. Minimum required NDT on lifting
points: 100% DPT.
8.0 APPENDIX
Appendix-1: Building tagging & tag plate