Electrical installations • Through measures for the connection


of exposed metal and extraneous
a lower rated short-circuit MCB is quite
acceptable to use at the switchboard.
require protection conductive parts Hence the MCBs can be of a lower
short-circuit rating as they are protecting
Circuit protection or specifically, cable
to ensure that the protection is another vitally important part downstream of the already protected
to be considered. Essentially the rating of consumer mains. Simple as that, just
installation cabling the circuit breaker has to match or be a because the regional short-circuit rating is
at 10kA for example doesn’t necessarily
system is sound, that lower rating than the size of cable being
used. The idea is that there will never mean you need 10kA MCBs, as the
products connected into be an overload in the cables whether a
short-circuit or continuous overload which
installation is already protected by an
upstream fuse. Hence a 4.5kA MCB can
the system are working would lead to overheating of the cable. be used to protect the cabling in that
installation.
If there is such an eventuality the circuit
correctly and that the end breaker will trip the circuit. Additional protection is also provided
user is protected from One issue that is of some concern it
seems, is the short-circuit rating of
at the switchboard through a Residual
Current Device (RCD). This type of
electrical shock or worse! the circuit breaker or miniature circuit
breakers (MCB). The Service Rules for
protection is there to augment other
measures of basic protection. These
each state will direct the installer to the provide protection in the event of an
required prospective short-circuit current active to earth or neutral to earth fault
Without consideration of all these aspects
rating appropriate to that region. This is as they operate before the threshold
there can be a hole in the system and in
simply because there can be considered of 30mA (usually around the 15-25mA
this case it can be a big black hole that
some differences in impedance in the range). That 30mA threshold is where
could cause injury or death.
various soils in and around the states. fibrillation of the heart will occur. 10mA
The basic premise though is that there These ratings range from 6kA up to 10kA RCDs are used in medical installations
is an Earthing system that is considered usually. because they operate before muscular
robust for the application. You are all contraction, the inability to let go, occurs.
aware of the need in our MEN installation The higher the short-circuit rating in
an MCB the better, right? Well not This is especially of concern where there
that an earth stake and an MEN link are electrical devices used in surgery,
correctly installed as a key to the integrity necessarily! Many suppliers in the
domestic market with higher rated short hence the use of the 10mA RCD.
of the whole installation. Ensuring the This protection in relation to muscular
circuit rated MCBs and are espousing
integrity will enable the installation contraction and fibrillation of the heart is
the virtues of their product as the only
protection to do its job correctly: exactly why these RCDs are mandatory
solution.
• Through automatic disconnection of to be installed for all circuits. They are
Did you know that a lower rated short
supply in the advent of a short-circuit an excellent example of safety at its best
circuit current in an MCB is quite
or excessive earth leakage because we have all seen instances
acceptable where there is protection
• Through equipotential bonding of the service supply by an upstream where the RCD has tripped out due to
arrangements that provide mitigation fuse? It’s true! As you can imagine all inadvertent touch of a live part, the knife
of voltage differences between of our services are protected by that in the toaster is a great example. Usually
exposed metal of equipment and upstream fuse for overload and short the person who has perpetuated the
extraneous conductive parts circuit protection to the customer’s crime does not feel a thing as the RCD
premises, meaning that kA rating is trips off the circuit to that device.
• Through an effective low impedance
fault path that can carry earth faults already incorporated at whatever rating is Be aware that an active to neutral fault is
without failure of equipment or wiring deemed necessary for that region. not protected by an RCD.
systems Following on from that you can see that Many installers now install a combined

86 September/October 2016 Issue 4


RCD and MCB, an RCBO (residual and neutral conductor. If left unattended manufacturer or supplier should be able to
current circuit breaker with over current this could eventually lead to a fire and provide documentation to prove that the
protection), for each circuit, providing resultant damage to the premises. These product is designed and manufactured
circuit and people protection at a are very new to Australia but are used to its specific standard. There are around
single circuit level and also easier fault extensively in Europe and the USA as 56 Prescribed articles that need to have
finding when things go wrong, as they they are mandated to be used to protect an Approval Certificate and Number
sometimes do! circuits to bedrooms specifically. before they can be marketed in Australia.
There are also RCD’s that provide In many instances there is also a need “Prescribed” means that each state has
property protection and these are rated to provide basic mechanical protection gazetted those products as a state law.
at 100mA and greater. Because they are for cabling within the installation. This The most common examples are Socket-
above the safe threshold of 30mA they is predominantly achieved by use of outlets, Switches, RCDs and MCBs.
are considered to provide protection electrical conduits whether plastic or steel For all other accessories or appliances
for installations. They are primarily used there may be specific standards
where there is no access or restricted
access by persons and are there to stop " Did you know that applicable and if there are none then the
Basic Safety standard AS/NZS 3820 has
inadvertent active to earth and neutral to
earth faults within installations. a lower rated short to apply. Just to protect yourself as an
installer or an end user you should ask
There are other protection devices such
as Surge Protection Devices to protect
circuit in an MCB is your supplier for documentation on your
purchase to verify that it is to Australian
the installation and the devices installed
within from over-voltage situations. The
quite acceptable where Standards. After all, as the electrical
contractor, you have a responsibility to
most common that we all know is a
lightning strike but it could also be caused
there is protection of select and install electrical equipment
that complies with the essential safety
by a fault in the service lines. Another
type of over-voltage device currently
the service supply by requirements of the Australian standards.
Check out the Wiring Rules, clause 1.7.1,
being used in Europe is called Power an upstream fuse? it’s all there in black and white! Choosing
Overvoltage Protection, or a POP, this is and installing safe and approved
used to monitor the circuit and trip that It's true! " equipment is another form of protection
circuit when irregular high over-voltages directly for you from a liability perspective.
are seen in the wiring system.
to ensure the risk of contact to persons As you can see there are many forms
A new one to the market is an Arc Fault of protection that should be considered
Detection Device, an AFDD, which is is limited or to provide segregation from
other services. Of course there are other when planning, installing or maintaining
there to protect against fires that may an installation. Protect the installation,
be caused by small arcs within cables, means to achieve the required protection
or segregation through distance or protect the products installed, protect
especially cord extension sets but also at the end user or home owner and protect
termination points. You have seen flexible effective barriers, to stop a person ingress
or to shield the cable from inadvertent yourself.
cords that have been squashed in a door
as it closes or even damage to the plug damage. Protection, as I have said if its not on,
and cord behind the bedhead. A sharp Product protection is also important but then its not on!
bend can damage the copper conductors that is not usually the domain of the installer. Gary Busbridge
within and cause either an arc in an active There are specific standards for most Clipsal by Schneider Electrical
or neutral conductor or across an active electrical accessories in the market and the Ref: 1604-Technical-86/87