You are on page 1of 9

ARC-FLASH ENERGY MITIGATION BY FAST ENERGY CAPTURE

Copyright Material IEEE


Paper No. PCIC-(_________)

George Roscoe Tom Papallo Marcelo Valdes, PE


IEEE Member IEEE Member IEEE Senior Member
GE Consumer & Industrial GE Consumer & Industrial GE Consumer & Industrial
George.Roscoe@ge.com Tom.Papallo@ge.com Marcelo.Valdes@ge.com

b A s at cr – The predominant technologies for reducing arc-flash I. INTRODUCTION


incident energy today rely on the speed of protective devices,
remote operation, encapsulating arc-flash energy in arc- A. Backgrnou d
resistant enclosures, which channel energy where it is less
dangerous, and on crowbars to divert the arc energy into a Arc-flash protection has emerged as an important
bolted fault. Though more thoughtfully applied than they may consideration in the design and operation of power distribution
have been in the past, none of these methods has provided a systems. The industry has developed several methods and
solution for all situations, particularly in existing installations. products to address the hazard posed by arc-flash energy in
This paper will describe a method and include test results of an new systems. For reducing the arc-flash hazard in existing
arc-flash energy sequestration that is able to divert an arcing systems without complete replacement of equipment, , the
fault’s energy into a specific environment within a half-cycle available solutions are more limited. All of the existing methods
after initiation of the arc. This is achieved without the need to provide solutions that are limited in one extent or another and
introduce bolted fault current like a crowbar or for fast current can incur significant costs in terms of material or operational
interruption, such as a current-limiting fuse. The system risk. The most common low-voltage arc-flash incident-energy or
protection provided has the benefits of arc-resistant switchgear hazard reduction methods are listed and compared in Table 1.
without reliance on equipment sheathing and can be added after
normal equipment is installed. Further advantages include the B. Curent and Time; ht e Effect ponu Arc-Fault Curent
protection system and switchgear’s ability for reuse after an Inteptiru no
arcing event, as well as the ability to easily test without the need
for cumbersome high-current test equipment. The model developed for IEEE 1584-2002 “Guide for
Performing Arc-Flash Hazard Calculations” [1] includes several
Index Terms – Arc-flash, Arc-flash Protection, Arcing Fault empirically derived formulas for predicting arcing current and
Diversion, Crow Bar, Arc-Resistant Switchgear, Fast Arc-flash consequently incident arcing energy. Once a system is
Protection. designed, the fault clearing-time at the expected arcing fault
level is usually the only variable for control of the incident
energy.
Method Detection Mechanism Benefit Drawbacks
Fuses as Direct current Relies on current- Fastest interruption if Ia > Large fuses have CL thresholds > arcing
protective devices energy limiting interruption current-limiting energy current and hence may be slow to react.
threshold Concern over fuse replacement and lack of
other capabilities offered by circuit breakers.
Current-limiting Direct current Relies on current- Fast current interruption Limited in availability relative to fuses and
circuit breakers energy limiting interruption similar to fuses if Ia > subject to similar limitations. May require
current-limiting threshold replacement after limited number of operations.
Not easily available in a broad range of sizes.
Circuit breaker Current; may be Relies on fast fault Provides fast current Not as fast as current-limiting fuses or circuit
with instantaneous combined with light interruption interruption breakers. Use of the instantaneous at arcing
trips detection current levels may negatively affect selectivity.
Requires adjustable-trip circuit breakers.
Arc-resistant None Enclose switchgear Protects in proximity to Enclosure integrity must be maintained. Blast
switchgear volume switchgear from arc flash energy must be exhausted. Complex
and blast energy installation. Does not improve equipment
protection nor may be added to existing
equipment.
Crowbar system Light detection and Fast protection from Protects in proximity to One-time use, may damage distribution
current arc blast and flash switchgear from arc flash equipment and other equipment connected in
and blast energy the system. Localized protection only.
Remote operation None Operator outside arc No impact on system Does not improve downstream or equipment
flash boundary selectivity protection, may be costly and difficult to retrofit
into existing installations.
Temporary Current More sensitive and Reduces incident energy Requires specific capable trip systems and
reduced settings measurement faster temporarily under specific conditions does not provide protection if the event does
not occur during planned activity.

Table 1. Arc-flash energy mitigation methods.


2
A plot of the expected 85–100% arcing current for a low- achieve less than 1.2 cal/cm clearing should be in the half-cycle
voltage switchgear assembly was calculated per the IEEE 1584 range or less (<0.01 s). Tests performed by various
arc-current model. Fig. 1 demonstrates that arcing currents can manufacturers with current-limiting molded-case circuit breakers
be relatively low. A plot of incident energy at 18” working have demonstrated energy levels below those predicted by the
distance, Fig. 2, for a switchgear system illustrates the IEEE 1584 model when devices operate in the half-cycle range.
advantage of fast arcing fault mitigation by interruption or any Nevertheless, these graphs illustrate the need for sensitivity to
other means. low fault currents and achieving arc-fault current mitigation
within a half-cycle to maintain an optimum level of protection.

C. Alternate Methods

Once it has been determined that exposure to hazardous


levels of incident energy is a risk, PPE (personal protective
equipment) is the last barrier for worker protection. PPE is
designed to shield the worker from the thermal energy of an arc-
flash event. Glasses or a face shield provide eye protection, and
ear protection is typically used to provide some level of hearing
protection. However, current PPE and supplementary protection
does not provide complete defense against all physical harm.
PPE is not intended to provide protection from the effect of
ejected debris, arc blast, or the toxic effect of vaporized
material. Even in the case of thermal injury PPE is only intended
to reduce injury to a curable level, not prevent it completely. Arc-
resistant switchgear shifts the burden of the PPE to the
equipment itself, which should be designed and tested to
recognized industry standards. In the US the standard is IEEE
C37.20.7 D11 [4].
Fig. 1. Arcing current vs. available fault current. Arc-resistant switchgear should provide protection from
incident heat energy, ejected debris, and arc blast as long as
the workers do not have the equipment open. Depending on the
exact arrangement, some level of protection from the toxic effect
of fumes could be provided as well as some protection from the
extreme noise possible during an event. A characteristic of arc-
resistant switchgear is its dependence on the integrity of the
enclosure. An improperly secured panel, door, or cover can
compromise the equipment’s ability to contain the explosion. In
addition, most installations of arc-resistant equipment will
require some sort of flue system to channel energy to the
exterior to the building. This limits where equipment may be
installed and may significantly increase installation costs. In
applications where the system relies solely on the equipment’s
arc-resistant properties, an arc-flash event internal to the
equipment may result in significant damage to the equipment.
The arc-resistance rating may not be sufficient to withstand the
energy of a fault in a tie compartment or section where the
ionized air from a fault initiated on one bus causes both buses
to arc simultaneously, effectively doubling the arc energy and
Fig. 2. Incident energy at various clearing times. increases effects such as pressure and heat. Since arc-
resistance capabilities are dependant on the enclosure, typically
From Figs. 1 and 2 it can be seen that a system able to installed indoor equipment cannot be converted from a normal
deliver a 60 kA bolted fault current through a main circuit NEMA1-type enclosure to arc-resistant after installation.
breaker may deliver ~24–28 kA arcing current over a 32 mm A crowbar is another method available to reduce exposure
gap or 26–30 kA over a 25 mm gap. Arcing fault current will be to arc-flash energy. A crowbar typically consists of a mechanical
significantly lower than the current-limiting threshold of a 3000– device that, when commanded, introduces a minimum-
4000 A fuse. Arcing current may also be below the impedance bolted fault into the system. The expectation is that
instantaneous pickup level of a main circuit breaker in a system the bolted fault will absorb all the available energy and
that has been optimized for maximum selectivity. However, to extinguish the arc. This type of arcing-fault mitigation introduces
obtain a level of energy lower than the HRC-2 (Hazard Risk the maximum possible bolted fault, which may include a large
2
Category) maximum of 8 cal/cm over a broad range of possible DC offset current. This introduces significant thermal and
fault currents, the protection must clear at the typical low- mechanical stress on the entire power delivery system along
voltage power circuit breaker’s clearing time of three cycles with a sudden voltage collapse. Though the method will
(0.05 s) or less. To be at or below HRC-1 maximum levels of 4 extinguish an arcing fault within a half-cycle or less, several
2
cal/cm , the system must clear in the time frame of a molded- cycles of maximum bolted fault current flow through the system
case circuit breaker’s instantaneous (0.025 s) or less. To
until an upstream device clears which raises concerns for the involves no moving parts and is able to fire in a few
integrity of the power distribution system after an event. microseconds. The trigger arc creates a dielectric breakdown
A temporary reduced pickup setting, referred to by various between phase electrodes inside the chamber. The electrodes
names by manufacturers, is a method to reduce worker then maintain the arc through ionized air initially created by the
exposure. This method is similar to alternate setting groups triggering arc. This maintains the alternate current path until the
employed in medium voltage where protective relays may upstream current-interrupting devices remove power.
change settings based on automatic logic driven by system Several practical ramifications of relying on an arc-transfer
topology or manual user controls; thereby allowing users to set device for arc-flash protection should be considered:
a protective device to respond faster when dangerous work is • Does the device lower the BIL rating of the power
planned. This is a good method to optimize the protection that distribution system?
an overcurrent device can provide. Modern trip systems from • What are the effects of operation on the power
multiple manufacturers may be retrofitted into existing circuit delivery system and are there negative unintended
breakers to improve the performance of older devices. However, consequences?
an alternate trip setting cannot accelerate a protective device • Can the device be tested to assure operation after
beyond its mechanical capability. Additionally, such settings do use or installation for extended periods of time?
not provide improved protection for the unexpected event that • Can the device be used multiple times?
occurs when live work is not planned but occurs accidentally
• What are the possible failure modes and can the
during routine operation. Use of alternate settings should be
device be set to compensate for them so that
part of a rigorous maintenance procedure to ensure that the
protection is reliable?
settings are enabled whenever they are needed and disabled
The paper will address these and other concerns.
when normal, more selective protection is desired.
Remote operation, such as remote racking, remote III. PRINCIPLES OF ARC CAPTURE
metering, remote controls combined with modern powerful
diagnostic tools and information, is a way to reduce worker’s A. Arc Transfer
exposure to arc-flash risk. Optimum use of diagnostic tools,
information, and remote operation may reduce the need for Successful arc capture depends on three factors: providing
hands-on maintenance by facilitating condition-based a lower impedance path than the fault path, a more stable circuit
maintenance practices and reducing the frequency with which than the fault arc, and a fast transfer. Arcing current capture and
employees must access equipment. Proper use of these transfer follows the basic law of electric circuits—current will
mechanisms requires planning and forethought. follow the path of least impedance. Fig 3 illustrates the
In summary, various methods exist to minimize exposure to equivalent circuit during an arcing event.
arc-flash energy. Each may have specific benefits in particular
situations; however, each also has its limitations with regard to
ease of application and scope. The method described in the rest
of this paper provides an alternative method to achieve
protection without some of the limitations encountered by other
methods.

II. ARCING FAULT TRANSFER TO AN ALTERNATE


ARCING CURRENT PATH

The principle of arc transfer is to create an alternate current


path to conduct fault current away from an arcing fault. A
crowbar accomplishes this by providing an alternate current
path via a short circuit. The proposed method accomplishes the
same goal by providing an alternate arcing current path. The
mechanism is to generate a second arc within an enclosed, Fig. 3. Arc transfer equivalent circuit.
controlled environment to provide a lower-impedance current
path. The alternate current path conducts the fault current and Transfer time will be affected by the time it takes to sense
causes the original arc in open air or in equipment to extinguish. and trigger the arcing fault capture devices and the
The new arc must have lower impedance than the original arc to commutation time. Minimum fault-current commutation time is
assure that no restrike can occur. The impedance however achieved by limiting the inductance in the transfer circuit.
should not be so low that it causes full bolted-fault inrush Placing the capturing device within the equipment can minimize
currents on the bus. The alternate arc must be enclosed within a impedance, enabling rapid transfer of the fault arc; however the
controlled pressure chamber to prevent a significant release of arc-absorbing device may be electrically connected ahead or
energy into the environment. The enclosed arc is quenched below the fault arc that it is intended to extinguish, as long as
when an upstream overcurrent device quickly stops current flow. the conductor impedance between the arc-capture device and
The open-air or in-equipment arc that may have otherwise the source is not significantly higher than the impedance
lasted for three cycles or more is now limited to about ½ cycle. between the fault arc and the source.
The arc in the protected chamber will have a maximum duration
of three to five cycles, depending on the type of overcurrent B. pe
O n-Air c
Ar Stability .vs Enclosed Arc aSt bility
device used to protect the circuit.
The alternate arcing current path is initiated by ionized air In an enclosed volume an arc is more stable than in open
created by a trigger arc fired within the mitigation device that air. The large volume and venting of the equipment results in
lower temperatures and the phase-conductor geometry results successfully withstood a 14.5 kV, 20 µsec rise, 400 µsec pulse,
in magnetic forces extending the arc. However, when an arc is further proving the viability of the 6 mm gap.
confined to a smaller volume, the arc is easier to maintain. By
transferring fault current to an arc within an enclosed volume D. Triggering via Dielectric e
R ductino thugro h l
P asma
with a specific electrode gap, a stable arc with predictable
properties is created and sustained. The lower-impedance The activation of the system is done via the break down of
transfer circuit forces the open-air arc to be unsustainable. The high dielectric air gap between the phase electrodes with a
original fault arc is quenched by the changing dynamics in the plasma pulse generator, also known as a plasma gun. The
system. plasma gun is similar to an arc welder and is placed directly
under the electrodes. The arc from the plasma gun derives its
C. Energy Dissiap tion thougr h Controlled e
R sistance power from a capacitor array. The energy released by the
plasma gun is approximately 60 J. Fig. 5 is an illustration of the
The electrode gap is a major component of the controlled plasma gun and shows it placed under the three-phase
arc impedance and can be adjusted to fine tune impedance and, electrodes. The plasma gun is isolated from the power system.
hence, optimize behavior in systems with different voltages and The ionized air created by the plasma gun causes a breakdown
different available bolted-fault currents. The electrode’s of the dielectric properties of the air between the electrodes and
geometry is also configured to balance the magnetic forces on arcing current starts to flow.
the arc, preventing the magnetic forces from lengthening the
arc. This creates a stable and predictable arc. Fig. 4 is a model
of the arc-containment device. The containment chamber’s
vented design must cool and contain the arc. Fig. 4 shows the
venting pattern used to cool the gases generated by the internal
arc. The device must cool and vent fast enough to prevent a
buildup of pressure that could otherwise destroy the chamber.

Fig. 5. Arc flash plasma gun.

The plasma gun barrel has two internal conductors that are
isolated from the power conductors, as they are part of an
isolated plasma-discharge circuit. The plasma gun discharge
circuit receives a firing signal from the arc-flash sensing relay.
The plasma discharge circuit creates a pulse of 15 kV, 5 kA
across the gap within the plasma gun. The plasma caused by
the pulse exits out the top of the gun and is channeled to the
space between the three phase electrodes.
Fig. 4. Arc-containment device. The fault arc on the electrical system creates a voltage
divider between the system impedance and the fault arc
The electrode gap within the arc-containment system must impedance given by Eq. 1,
maintain dielectric integrity under normal system operating
conditions, and must not decrease the equipment’s BIL rating. ⎛ Z arc ⎞
The voltage-withstand capability of the device also must be able Vcapture = Vsys ⎜⎜ ⎟⎟ (1)
to handle impulses from lighting or other high voltages ⎝ Z arc + Z source ⎠
impinging upon the low-voltage system during normal use. This
is especially important, as the device must be resilient against where V sy is the system voltage, Z rcsou e is the source system
nuisance activation. Nuisance activation would adversely affect and conductor impedance, Z arc is the open-air arc impedance,
system reliability and protection. The resiliency can be and V capuret is the arc-capture device impedance. The voltage-
ascertained by voltage-impulse testing. The NEMA standards divider network determines the voltage across the phase-
offer no guidelines on the appropriate BIL (Basic Impulse Level) electrode gap. The plasma created by the trigger arc must break
testing for LV equipment. IEC 60947-1 [5] standard for low- down the dielectric strength of the air between the electrodes so
voltage switchgear and control gear recommends up to an 8 kV, that the available system voltage is sufficient to initiate arcing
2 µsec rise, 50 µsec pulse to test dielectric integrity. Table 13 in current between the main electrodes. The arc is in series with
IEC 60947-1 lists the recommended gaps for the impulse test the source impedance, as shown in the one-line drawing in Fig
voltages. The table states that for a homogenous field, a smooth 6. For a given available bolted-fault current on a system, there is
voltage gradient, such as the gradient supplied by the specific impedance. The IEEE 1584 equations for arcing-fault
electrodes in the arc-containment device, is needed. The currents can be used to calculate the arc resistance. The
minimum required gap for a homogenous field is 3 mm; voltage available to support an arc at the main bus of the
doubling the minimum distance provides additional margin. A equipment can be calculated as a voltage divider with the
test was performed with an immediately available pulse impedance of the arc divided by the total system impedance
generator to verify the general gap estimates. The gap times the system voltage. This inductance and resistance
determines the voltage available at the bus that must be
triggered by the plasma gun. It is more difficult to initiate an arc factor angle and the closing angle determines the maximum
when there is high source impedance (low available fault possible dc offset. The larger the R/L term, the smaller the
current). A larger fraction of the total available voltage is potential offset may be. The R in this equation is a summation of
dropped across the higher source impedance, resulting in lower the source impedance resistance and the arc resistance. The
arcing voltage and lower arcing current. This means that testing exact offset on any one phase depends on the closing angle
the device in a system that delivers low arcing current is a more and system power factor. The magnetic forces can cause
difficult challenge to the ability of the plasma gun discharge damage to current-carrying conductors within transformers and
system to break down the gap. A system able to deliver 10 kA Ibf other equipment. In a highly inductive system the peak current
was chosen to test the low available fault current cases. caused by the dc offset from a bolted fault can exceed two times
the RMS value. The arc within the chamber has the typical
resistive impedance characteristics of an arc. Because of the
resistance of the arc in the chamber, the arc current is lower
than the bolted fault RMS and particularly with respect to the
peak dc offset.
The other electrical stress on the system is the energy,
2 2
measured by I t. The I t effect on the system is a function of the
instantaneous current integrated over time. The impedance of
2
the arc in the chamber also limits damaging I t effects on the
power distribution system. However, high arcing current flowing
for too long can still cause damage to power distribution system
components and cause unnecessary wear of the arc
containment device. A circuit breaker operating in three to five
cycles from the arcing fault’s inception is fast enough to prevent
damage to system components, as well as minimizing device
wear.
Fig. 6. One-line drawing.
IV. DETECTION SYSTEM
The analysis of the arc voltage at 10 kA determined that the
minimum voltage available between two electrodes was 250 A. Sensing
VRMS at any given time. Testing was then performed at 250 Vdc
to determine the reliability of the plasma gun at the lower, more To initiate an arc fault transfer, use of an arc-fault-current
difficult transfer voltage. The test passed 150/150 sample shots. detection system is required. The system must differentiate
bolted faults and downstream faults from arcing faults in the
E. Electir cal yste
S me
Str s es volume or bus protected. Arc-flash sensing systems are capable
of differentiating between the fault types with light sensors.
Stresses on the power delivery system depend on the Light-based sensing is used for arc-flash detection in various
current traveling through the conductors of the arc-mitigation available commercial systems. To assure positive detection and
device after a successful transfer. Eq. 2 defines the arcing minimize the probability of nuisance firing, current sensing may
current flowing within the arc containment chamber, be used as a confirming signal. Light sensors are simple
Vsys ⎡ −
Rt
⎤ devices; the basic technology has been available for several
I= ⎢sin ( wt + θ − ϕ) − e sin (θ − ϕ) ⎥ (2) decades. Light detection is fast as light is given off within tens of
L
Z sys + Z capture ⎣ ⎦ microseconds of an arc fault initiation. Protective-relay systems
for medium-voltage applications able to operate with light
where Vsys is the system voltage, Zsys is the source system and sensors are commonly available in the industry today.
conductor impedance, Zcapture is the arc impedance, ωt is the When photo sensors are placed within an enclosure, the
sample time in radians, t is time, θ is the arcing current power sensor devices will only sense light within that volume and any
factor angle, ϕ is the closing angle, R is the total system adjacent volume with enough reflected light to trigger the
resistance (including Rsys + Rarc), L is the total system sensor. In order to protect the entire system, light sensors must
inductance, and I is the total current flowing through the arc be placed throughout the equipment where they have access to
containment device. System voltage and the power distribution direct or reflected light from any possible arcing-fault location.
system impedance, consisting of the source and conductor’s This includes the main bus compartment, cable run-ins,
impedance up to the arc chamber, are the other factors that transition sections, and breaker compartments. The location of
determine the arcing current. The total system impedance, current sensors used for confirmation determines the protected
consisting of the power distribution system impedance and the zone electrically. If the entire equipment is to be protected, the
arc’s impedance, then determines the current peak and RMS current sensor must be on the line side of the switchgear and
current that causes stresses on the electrical components the light sensor must be placed in the main equipment
within the system. compartments. Also, a controllable remote device must be
The magnetic repulsion and attraction forces that produce located ahead of the protected volume or bus. For a main
mechanical stress are related to the multiplication of current secondary bus, the main circuit breaker will protect most of the
traveling through each conductor. Eq. 2 illustrates the equipment, as shown in Fig. 7. However, to protect a complete
instantaneous current flowing through system once the arc low-voltage substation it may be necessary to provide a
chamber is conducting current. It is a function of time and each medium-voltage circuit breaker or remote low-voltage main, as
phase is offset by 120 degrees from the others. The exponential shown in Fig. 8.
term with the negative R/L exponent combined with the power
breakers, which do not vent into open air. Low-voltage
equipment breakers use air interrupters. Air circuit breakers
produce significant light from internal arcing while interrupting
XFMR high currents. A light-sensing system must not be triggered by
the light emissions of a properly interrupting circuit breaker.
Filtering the light is an easily achieved workable solution. Light
Relay filters can be designed that block light from interrupting circuit
Main Bus CT breakers as well as from normal ambient conditions.
Light given off by an arcing event at 10 kA, 480 V is in the
range of 200 klux. For reference, typical lighting in an office is 2
Main klux[7], so the light intensity is of the order of 100X brighter than
Breaker normal lighting. Off-the-shelf light sensors normally saturate at
about 1 klux. An implementation with filtration materials that can
tailor the light sensor thresholds anywhere from 1 to 2,000+ klux
using the same light-sensing technology has proven to provide
reliable arcing-fault event indication while filtering light from non-
arcing fault sources. This light sensor filtration method
dramatically reduces the risk of nuisance operation.
Light The detection system is set up to detect high intensity arc
Sensor flashes, such as those from line to line or line to ground on
solidly grounded systems. These types of faults fall in the range
of high current (>5 kA) and are best dealt with by using the arc-
mitigation system as the primary solution. Even if an arc starts
Feeder as a single line-to-ground fault, there is a chance that the arc
Arc will propagate into a three-phase arc [8]. For such events where
there is sufficient current on single line-to-ground fault, the
Device
transfer of the arc is desirable versus the alternative option,
Fig. 7. Arc containment device, sensing and control for which is full-scale propagation. For very low intensity arcing
system protected by LV or local main. currents that may be of low magnitude or intermittent so that not
enough light is produced, other sensing and protection may be
Main Bus CT used that provides satisfactory protection. The article
“Understanding IEEE 1584 Arc Flash Calculations”[8] provides
MV some related discussion.
Breaker
52 .B e
R nspo se Time

XFMR The sensing, triggering, and arc-transfer will require some


Relay time. This time may be divided into three segments:
• Time to generate signals of light and current
• Processing time for the relay
• Arc-transfer time
Tests using a commonly available medium-voltage
protective relay with logic capability have demonstrated that
sensors can communicate sufficient light and current
information to the relay in less than 2 ms after initiating fault
current. The relay can issue a firing signal to the arc-absorbing
Main LV device and a trip signal to a circuit breaker in less than 6 ms and
Breaker the arc-transfer time is less than 1 ms. The relay used for the
testing is a powerful multifunction digital processor-based relay.
A dedicated logic device should be able to produce firing and
Light trip signals in less than the 6 ms the relay required. All tests
Sensor performed resulted in a total transfer time under 8 ms.
The sensing time included the effect of the light filtering and
the current confirmation logic. Reducing filtering and not
Feeder employing current confirmation may be used to reduce overall
Arc transfer time as part of a live work procedure. This would
Device temporarily provide a greater level of protection.

Fig. 8. Arc containment device, sensing and control for V. INCIDENT ENERGY IMPROVEMENTS
system protected by MV or remote main.
A comparison of the incident energy allowed by a circuit
The current state of light-detection systems does not take breaker clearing in three cycles versus the arc-absorption
into account failure modes that may occur in low-voltage system transferring the arc in one half-cycle yields significant
equipment. Medium-voltage equipment has vacuum circuit improvements. For a high-resistance-grounded, 480 V system,
an arcing gap of 32 mm and a working distance of 18 in., the arc-absorption device transferred current reliably within the
2
incident energy may be reduced from 6.84 cal/cm to 1.09 expected time.
2
cal/cm . That is equivalent to a reduction from Hazard Risk Measurements were also performed per the low-voltage
Category 2 range to Hazard Risk Category 0. Fig. 2 includes an arc-resistant equipment standard testing protocol, IEEE
incident energy line for arcs lasting three cycles and one half- C37.20.7 D11. The test provided confirmation of the arc-
cycle. For most of the bolted-fault current range of 30 to 100 kA, containment device’s ability to comply with the arc-resistance
a reduction in arc duration from three cycles to one half-cycle equipment standard’s requirements. Arc resistance means that
reduces the incident energy from the Hazard Risk Category 2 the switchgear is capable of containing an arc that forms within
2 2
range of 4–8 cal/cm to less than 1.2 cal/cm or from over 8 its enclosure and does not allow any significant effects of the
2 2
cal/cm to less than 4 cal/cm . arc to project externally from the enclosure where operating or
maintenance personnel may be standing. Successful
VI.TEST RESULTS completion of the test requires that cotton panels mounted a
short distance from the enclosure not ignite, and that no part of
The device has three possible failure mechanisms: the enclosure be forced open or breached by the blast forces
• Inability to transfer the arc because the device’s arc within the enclosure. Typical arc-resistant switchgear requires
impedance is too high relative to the fault’s that the enclosures be vented to release arc-blast energy into a
impedance. flue system or in a direction deemed less dangerous, such as
• Inability to maintain an arc because the system toward the top or rear of the enclosure. The switchgear used for
impedance in series with the device’s impedance is the test was not provided with a path to relieve pressure caused
too high. by arc-blast energy and hence required mitigation of the arc
• Inability to maintain the arc due to excessive pressure energy before sufficient arc-blast energy could be created to
or wear within the arcing device. damage the enclosure or cause excessive heat energy or gases
Tests were preformed to confirm that the arc-containment to exit the enclosure.
device was able to operate within a reasonable range of
operating parameters. The propensity for restrike or failure to A. 65 kA Tets at 480 V
transfer the arcing fault may be caused by the arc impedance in
the device being high relative to the original’s fault impedance. Fig. 9 shows the transfer of an arc in a 65 kA, 480 V
To verify the reliability of the arc-transfer and arc-sustaining system. Full transfer of the arc from initiation required 6.9 ms.
mechanism, the device was tested with high- and low-power The dotted part of the sine wave seen in the oscillograph (~3
distribution system impedance. Tests on a system able to cycles) shown in Fig. 9 is three cycles of arc current flowing
deliver 65 kA of bolted-fault current confirm that the initiating arc within the arc-containment chamber, where it was safely
in the chamber reduces impedance sufficiently to commutate contained.
the fault arc into the chamber as expected. Tests in a system
able to only deliver 10 kA bolted-fault current confirm that the
device is able to commutate the current in the chamber and
sustain it to ensure that the fault arc does not have an
opportunity to re-ignite. Additional tests were done on a system
able to deliver 85 kA at 635 V, sustaining the arc for several
cycles to determine the device’s ability to withstand pressure
and electrode wear.
Each of the tests was performed using UL1558 standard-
construction indoor low-voltage switchgear. Light and current
sensing was installed in the switchgear. A light sensor was
placed in each of the breaker compartments and in the cable
compartment. Current transformers were installed on the
incoming bus. Measurements were taken of each line current
and the phase-to-phase voltages. The tests were also
videotaped to document the arc transfer. The arc was created in
a 2000 A breaker compartment by wrapping a trigger wire Fig. 9. Arc-absorber transfer behavior on a 65 kA system.
around the three-phase incoming run-in bus into the
compartment in a manner similar to that used in IEEE 1584 Visual evidence provided by a high-speed camera showed
e
R commended Practice for Arc Flash Incident Energy that 10 ms after fault initiation all visible traces of ionized gas or
Calculations . plasma were gone from the area of the original arc. Using the
Each test was performed four or more times. The 65 kA test IEEE 1584 incident energy formula with an arc-mitigation time of
was completed five times at 480 V to ensure structural integrity 6.9 ms reduced the calculated incident energy to less than 1
2
of the chamber and successful transfer. One way to test the cal/cm . The entire event ended at less than 58 ms with the arc-
reliability of the arc transfer under more difficult transfer mitigation device current lasting about 50 ms. The 50 ms
conditions is to decrease arcing fault gap. Two of the tests were includes the circuit breaker being triggered via its shunt trip,
done with 25 mm gaps, increasing the arcing current and which is slower than an internal flux shifter that would be used if
facilitating restrike at the fault. These tests were also performed the circuit breaker’s trip system had initiated the tripping. The
at 10 kA, making it the most difficult of the arc transfer tests. device’s maximum Ipk was 90 kA between all of the conducted
Other tests were done with gaps as large as 50 mm to simulate tests versus the 150 kA that would be expected for a bolted
an arcing gap that may be found in the internal bus structure of fault. Fig. 10 shows a comparison of the various current and
some low-voltage switchgear. All tests were successful and the energy let-through characteristics for an arcing fault, arc-
containment device current, and bolted-fault current, assuming Test
that all three currents lasted a full three cycles, but the fault Fault Gap, Duration, # of
arcing current lasted less than one-half cycle. Ibf, A Volts, V mm cycles tests
65,000 480 50 3.5 5
10,000 480 25 3.5 2
10,000 480 50 3.5 2
85,000 635 None 3.5 1

Table 2. Tests performed on one arc-containment device


under a variety of conditions.

VII. PRACTICAL CONSIDERATIONS

After each test, the main electrodes were examined. Each


test consumed some material from the main arcing electrodes;
however the arc-containment device was used for several tests
with minor adjustment of the electrodes. This limited adjustment
allowed multiple uses of the same device. The degree of wear
depends on the intensity of the event. Some maintenance
consisting of cleaning of the chamber and adjusting or replacing
the main electrodes may be needed after an event. The overall
structural integrity of the device was not compromised after the
full battery of tests was concluded. The detection and triggering
circuitry are fully reusable and should not require replacement
Fig. 10. 65 kA Ibf, 480 V, HRG, three cycle clearing. after an event. The damage to the electrical equipment was
limited to minimal damage around the immediate area of the
The important comparisons are between the peak current initial arc. The cubicle used for arc initiation, when protected by
2
and I t characteristics of the arc-containment device versus the the device, required no more than cleaning to be put back in
characteristics of the bolted fault that a crowbar arc-fault- operation. Fig. 11 and Fig. 12 display two compartments that
mitigation device would cause. The worst case arc-containment were used for 65 kA arcing fault tests. Fig 11 is a compartment
device peak current is less than 2/3 of the bolted-fault current protected by a circuit breaker operating in three cycles. Fig 12 is
2
and the I t energy is about 1/3 that of a bolted fault on the same a compartment protected by the arc-containment device.
system. The lower values of peak current and energy result in
significantly less mechanical and thermal stress on the power-
distribution system.

B. 10 kA Ibf tests at 480 V

The 10 kA Ibf arc-capture tests were completed to confirm


the ability of the system to transfer the arc into the system in the
presence of collapsed system voltage. As described previously
in this paper, this is due to the lower available breakdown
voltage at the arc-containment device main electrodes. Tests
were performed on a 10 kA system at 480 V. Melting the trigger
wire on this system required 5–6 ms. This resulted in an overall
slower transfer time of about 13 ms due to the additional time
taken by the fault-initiating wire’s melting. When the wire-melting
time is subtracted, a net transfer time of 7–8 ms is observed.
The arc transfer occurred as expected. The observed
difference between the initial fault current and the transferred
arc is minimal, due to the substantial portion of the fault current
carried by the trigger wire prior to fault-arc initiation. This is
because most of the system impedance is higher than the
actual arc impedance, so that the current variation from internal Fig 11. Compartment protected by a circuit breaker.
arc versus external arc is less at higher levels. This test was
successfully completed four times with the described gap
variation.
Table 2 contains a summary of the arc-containment tests
that were performed.
Circuit theory demonstrates that the device is flexible with
regard to where it is connected within the protected system. As
long as the impedance between the device and the arc to be
extinguished is low, the device should function properly. The
ability to install the device in a normal feeder circuit breaker
cubicle, without reliance on modification of the enclosure’s steel,
indicates that the technology is available to existing systems
where other arc-flash-hazard mitigation mechanisms are difficult
to apply without replacement or major modifications of the
equipment and operating characteristics. Since the device may
be located ahead of or downstream from the protected bus,
significant flexibility is possible in configuration topologies,
potentially allowing the technology to be applied in a wide range
of installed systems, as well as new equipment.

IX. BIBLIOGRAPHY

[1] IEE Guide for Performing Arc-flash Haaz rd Calculations ,


IEEE Std 1584-2002.
[2] Standard for Electrical aS fety e R uiq rements for Emple
oy e
Fig 12. Compartment protected by arc containment. Workl p aces , NFPA 70E, 2000.
[3] R.H. Lee. “The other electrical hazard: Electric arc blast
Testing an arc-containment device in the field may be burns.” IEE Trans. Ind. Aplications . Vol. IA-18, pp. 246–
accomplished by connecting a small capacitor bank to the 251, May/June 1982.
electrodes, thus imposing a low voltage on the electrodes. This [4] IEE Guide for Testing Medium-Volat ge Metal-Enclosed
would simulate a low breakdown voltage as would be available Siw tchgear for Intenr al c Ar ing Faulst , IEEE C37.20.7-2001.
during an arcing fault in the system. Firing the plasma gun and [5] o-
wL l vo tage isw tchgear and conl tro gear , IEC 60947-2004-
causing the capacitors to discharge indicates the device’s ability 03.
to initiate an arc at the main electrodes in the presence of low [6] Mauro, J.A. tipO cal Engineering aH ndbook . GE. 1963.
breakdown voltage. This would prove the device’s ability to [7] Kussy, Frank W. and Jack L Warren. Design Fundamentals
trigger and conduct arcing current. A low-energy test would not for Lo- w Voltage Distributino and Conl t ro . New York: Marcel
cause any significant wear on the electrodes. This primary- Dekker, Inc.1987.
voltage test technique is analogous to primary-current injection [8] Jones, Ray A., Danny P. Ligget, Mary Capelli-Schellpfeffer,
testing of a circuit breaker. Testing of the sensing system may Terry Macalady, Lynn F. Saunders, Robert E. Downey, L.
be accomplished using a calibrated light source and confirming Bruce McClung, Arthur Smith, Shahid Jamil, and Vincent J.
that a trigger signal is issued by the relay. A high-current test of Sapporita. “Staged Tests Increase Awareness of Arc-Flash
the current sensor can confirm that the current confirmation and Hazards in Electrical Equipment.” IEE Trans. Ind.
logic is operational. Continuous integrity of the CT can also be Aplications . Vol. 36-2, March/April 2000.
assured by using the CT input for metering at the same arc [9] Lippert, Kevin J, Donald M. Colaberardino, and Clive W.
containment device’s triggering relay. Installing the arc- Kimblin, “Understanding IEEE 1584 Arc Flash Calculations.”
containment device in a rack-out assembly, similar to how a IEE Industry Aplicatino s Magazine . May/June 2005.
feeder circuit breaker is installed in switchgear, would facilitate
testing, installation, maintenance, and replacement of the X. VITAE
device, if required. Testing of the device’s ability to fire may be
accomplished on a racked-out device or on a test bench. Mr. Tom Papallo manages the Innovation Engineering
team for GE’s Industrial’s power distribution business. Mr.
VIII. CONCLUSION Papallo has co-authored several IEEE papers for conferences,
IAS Magazine, and IAS Transactions. Mr. Papallo has over
Testing of the arc-containment device confirmed that fast three dozen patents in circuit breaker design, power system
energy capture by transferring an arcing current from an open- protection, and other subjects. Mr. Papallo holds a degree in
air arc to an enclosed, controlled chamber provides a high Mechanical Engineering from the University of Connecticut.
degree of protection to low-voltage switchgear. Tests confirmed Mr. George Roscoe is a member of GE’s Innovation design
the ability of the device to perform within the requirements of team and has several patents in the field of arc-flash protection
applicable IEEE standards for low-voltage, arc-resistant pending. Mr. Roscoe has a master’s degree in Electric Power
switchgear, without relying on special enclosures or blast- Engineering from Rensselaer Polytechnic Institute and has
pressure conduction methods. Tests also confirmed the ability headed GE’s internal program for arc-flash testing for several
2
to reduce incident energy levels to less than 1 cal/cm at an 18 years.
in. working distance with no barriers between the arc source Mr. Marcelo Valdes is Application Engineering Manager for
and the measurement devices. Furthermore, testing at low- and GE Industrial’s power distribution business and has co-authored
high-available fault current, with larger and small arcing-fault and authored several IEEE papers for conferences, IAS
gaps, confirmed the ability of the device to reliably function magazine, IAS transactions, and other journals. Mr. Valdes has
within a range of low-voltage power-distribution fault currents one patent and several pending in the area of power systems
and equipment arrangements that may be found in many protection and circuit breaker trip design. Mr. Valdes holds a
industrial facilities. degree in electrical engineering from Cornell University.

You might also like