Professional Documents
Culture Documents
C. Alternate Methods
The plasma gun barrel has two internal conductors that are
isolated from the power conductors, as they are part of an
isolated plasma-discharge circuit. The plasma gun discharge
circuit receives a firing signal from the arc-flash sensing relay.
The plasma discharge circuit creates a pulse of 15 kV, 5 kA
across the gap within the plasma gun. The plasma caused by
the pulse exits out the top of the gun and is channeled to the
space between the three phase electrodes.
Fig. 4. Arc-containment device. The fault arc on the electrical system creates a voltage
divider between the system impedance and the fault arc
The electrode gap within the arc-containment system must impedance given by Eq. 1,
maintain dielectric integrity under normal system operating
conditions, and must not decrease the equipment’s BIL rating. ⎛ Z arc ⎞
The voltage-withstand capability of the device also must be able Vcapture = Vsys ⎜⎜ ⎟⎟ (1)
to handle impulses from lighting or other high voltages ⎝ Z arc + Z source ⎠
impinging upon the low-voltage system during normal use. This
is especially important, as the device must be resilient against where V sy is the system voltage, Z rcsou e is the source system
nuisance activation. Nuisance activation would adversely affect and conductor impedance, Z arc is the open-air arc impedance,
system reliability and protection. The resiliency can be and V capuret is the arc-capture device impedance. The voltage-
ascertained by voltage-impulse testing. The NEMA standards divider network determines the voltage across the phase-
offer no guidelines on the appropriate BIL (Basic Impulse Level) electrode gap. The plasma created by the trigger arc must break
testing for LV equipment. IEC 60947-1 [5] standard for low- down the dielectric strength of the air between the electrodes so
voltage switchgear and control gear recommends up to an 8 kV, that the available system voltage is sufficient to initiate arcing
2 µsec rise, 50 µsec pulse to test dielectric integrity. Table 13 in current between the main electrodes. The arc is in series with
IEC 60947-1 lists the recommended gaps for the impulse test the source impedance, as shown in the one-line drawing in Fig
voltages. The table states that for a homogenous field, a smooth 6. For a given available bolted-fault current on a system, there is
voltage gradient, such as the gradient supplied by the specific impedance. The IEEE 1584 equations for arcing-fault
electrodes in the arc-containment device, is needed. The currents can be used to calculate the arc resistance. The
minimum required gap for a homogenous field is 3 mm; voltage available to support an arc at the main bus of the
doubling the minimum distance provides additional margin. A equipment can be calculated as a voltage divider with the
test was performed with an immediately available pulse impedance of the arc divided by the total system impedance
generator to verify the general gap estimates. The gap times the system voltage. This inductance and resistance
determines the voltage available at the bus that must be
triggered by the plasma gun. It is more difficult to initiate an arc factor angle and the closing angle determines the maximum
when there is high source impedance (low available fault possible dc offset. The larger the R/L term, the smaller the
current). A larger fraction of the total available voltage is potential offset may be. The R in this equation is a summation of
dropped across the higher source impedance, resulting in lower the source impedance resistance and the arc resistance. The
arcing voltage and lower arcing current. This means that testing exact offset on any one phase depends on the closing angle
the device in a system that delivers low arcing current is a more and system power factor. The magnetic forces can cause
difficult challenge to the ability of the plasma gun discharge damage to current-carrying conductors within transformers and
system to break down the gap. A system able to deliver 10 kA Ibf other equipment. In a highly inductive system the peak current
was chosen to test the low available fault current cases. caused by the dc offset from a bolted fault can exceed two times
the RMS value. The arc within the chamber has the typical
resistive impedance characteristics of an arc. Because of the
resistance of the arc in the chamber, the arc current is lower
than the bolted fault RMS and particularly with respect to the
peak dc offset.
The other electrical stress on the system is the energy,
2 2
measured by I t. The I t effect on the system is a function of the
instantaneous current integrated over time. The impedance of
2
the arc in the chamber also limits damaging I t effects on the
power distribution system. However, high arcing current flowing
for too long can still cause damage to power distribution system
components and cause unnecessary wear of the arc
containment device. A circuit breaker operating in three to five
cycles from the arcing fault’s inception is fast enough to prevent
damage to system components, as well as minimizing device
wear.
Fig. 6. One-line drawing.
IV. DETECTION SYSTEM
The analysis of the arc voltage at 10 kA determined that the
minimum voltage available between two electrodes was 250 A. Sensing
VRMS at any given time. Testing was then performed at 250 Vdc
to determine the reliability of the plasma gun at the lower, more To initiate an arc fault transfer, use of an arc-fault-current
difficult transfer voltage. The test passed 150/150 sample shots. detection system is required. The system must differentiate
bolted faults and downstream faults from arcing faults in the
E. Electir cal yste
S me
Str s es volume or bus protected. Arc-flash sensing systems are capable
of differentiating between the fault types with light sensors.
Stresses on the power delivery system depend on the Light-based sensing is used for arc-flash detection in various
current traveling through the conductors of the arc-mitigation available commercial systems. To assure positive detection and
device after a successful transfer. Eq. 2 defines the arcing minimize the probability of nuisance firing, current sensing may
current flowing within the arc containment chamber, be used as a confirming signal. Light sensors are simple
Vsys ⎡ −
Rt
⎤ devices; the basic technology has been available for several
I= ⎢sin ( wt + θ − ϕ) − e sin (θ − ϕ) ⎥ (2) decades. Light detection is fast as light is given off within tens of
L
Z sys + Z capture ⎣ ⎦ microseconds of an arc fault initiation. Protective-relay systems
for medium-voltage applications able to operate with light
where Vsys is the system voltage, Zsys is the source system and sensors are commonly available in the industry today.
conductor impedance, Zcapture is the arc impedance, ωt is the When photo sensors are placed within an enclosure, the
sample time in radians, t is time, θ is the arcing current power sensor devices will only sense light within that volume and any
factor angle, ϕ is the closing angle, R is the total system adjacent volume with enough reflected light to trigger the
resistance (including Rsys + Rarc), L is the total system sensor. In order to protect the entire system, light sensors must
inductance, and I is the total current flowing through the arc be placed throughout the equipment where they have access to
containment device. System voltage and the power distribution direct or reflected light from any possible arcing-fault location.
system impedance, consisting of the source and conductor’s This includes the main bus compartment, cable run-ins,
impedance up to the arc chamber, are the other factors that transition sections, and breaker compartments. The location of
determine the arcing current. The total system impedance, current sensors used for confirmation determines the protected
consisting of the power distribution system impedance and the zone electrically. If the entire equipment is to be protected, the
arc’s impedance, then determines the current peak and RMS current sensor must be on the line side of the switchgear and
current that causes stresses on the electrical components the light sensor must be placed in the main equipment
within the system. compartments. Also, a controllable remote device must be
The magnetic repulsion and attraction forces that produce located ahead of the protected volume or bus. For a main
mechanical stress are related to the multiplication of current secondary bus, the main circuit breaker will protect most of the
traveling through each conductor. Eq. 2 illustrates the equipment, as shown in Fig. 7. However, to protect a complete
instantaneous current flowing through system once the arc low-voltage substation it may be necessary to provide a
chamber is conducting current. It is a function of time and each medium-voltage circuit breaker or remote low-voltage main, as
phase is offset by 120 degrees from the others. The exponential shown in Fig. 8.
term with the negative R/L exponent combined with the power
breakers, which do not vent into open air. Low-voltage
equipment breakers use air interrupters. Air circuit breakers
produce significant light from internal arcing while interrupting
XFMR high currents. A light-sensing system must not be triggered by
the light emissions of a properly interrupting circuit breaker.
Filtering the light is an easily achieved workable solution. Light
Relay filters can be designed that block light from interrupting circuit
Main Bus CT breakers as well as from normal ambient conditions.
Light given off by an arcing event at 10 kA, 480 V is in the
range of 200 klux. For reference, typical lighting in an office is 2
Main klux[7], so the light intensity is of the order of 100X brighter than
Breaker normal lighting. Off-the-shelf light sensors normally saturate at
about 1 klux. An implementation with filtration materials that can
tailor the light sensor thresholds anywhere from 1 to 2,000+ klux
using the same light-sensing technology has proven to provide
reliable arcing-fault event indication while filtering light from non-
arcing fault sources. This light sensor filtration method
dramatically reduces the risk of nuisance operation.
Light The detection system is set up to detect high intensity arc
Sensor flashes, such as those from line to line or line to ground on
solidly grounded systems. These types of faults fall in the range
of high current (>5 kA) and are best dealt with by using the arc-
mitigation system as the primary solution. Even if an arc starts
Feeder as a single line-to-ground fault, there is a chance that the arc
Arc will propagate into a three-phase arc [8]. For such events where
there is sufficient current on single line-to-ground fault, the
Device
transfer of the arc is desirable versus the alternative option,
Fig. 7. Arc containment device, sensing and control for which is full-scale propagation. For very low intensity arcing
system protected by LV or local main. currents that may be of low magnitude or intermittent so that not
enough light is produced, other sensing and protection may be
Main Bus CT used that provides satisfactory protection. The article
“Understanding IEEE 1584 Arc Flash Calculations”[8] provides
MV some related discussion.
Breaker
52 .B e
R nspo se Time
Fig. 8. Arc containment device, sensing and control for V. INCIDENT ENERGY IMPROVEMENTS
system protected by MV or remote main.
A comparison of the incident energy allowed by a circuit
The current state of light-detection systems does not take breaker clearing in three cycles versus the arc-absorption
into account failure modes that may occur in low-voltage system transferring the arc in one half-cycle yields significant
equipment. Medium-voltage equipment has vacuum circuit improvements. For a high-resistance-grounded, 480 V system,
an arcing gap of 32 mm and a working distance of 18 in., the arc-absorption device transferred current reliably within the
2
incident energy may be reduced from 6.84 cal/cm to 1.09 expected time.
2
cal/cm . That is equivalent to a reduction from Hazard Risk Measurements were also performed per the low-voltage
Category 2 range to Hazard Risk Category 0. Fig. 2 includes an arc-resistant equipment standard testing protocol, IEEE
incident energy line for arcs lasting three cycles and one half- C37.20.7 D11. The test provided confirmation of the arc-
cycle. For most of the bolted-fault current range of 30 to 100 kA, containment device’s ability to comply with the arc-resistance
a reduction in arc duration from three cycles to one half-cycle equipment standard’s requirements. Arc resistance means that
reduces the incident energy from the Hazard Risk Category 2 the switchgear is capable of containing an arc that forms within
2 2
range of 4–8 cal/cm to less than 1.2 cal/cm or from over 8 its enclosure and does not allow any significant effects of the
2 2
cal/cm to less than 4 cal/cm . arc to project externally from the enclosure where operating or
maintenance personnel may be standing. Successful
VI.TEST RESULTS completion of the test requires that cotton panels mounted a
short distance from the enclosure not ignite, and that no part of
The device has three possible failure mechanisms: the enclosure be forced open or breached by the blast forces
• Inability to transfer the arc because the device’s arc within the enclosure. Typical arc-resistant switchgear requires
impedance is too high relative to the fault’s that the enclosures be vented to release arc-blast energy into a
impedance. flue system or in a direction deemed less dangerous, such as
• Inability to maintain an arc because the system toward the top or rear of the enclosure. The switchgear used for
impedance in series with the device’s impedance is the test was not provided with a path to relieve pressure caused
too high. by arc-blast energy and hence required mitigation of the arc
• Inability to maintain the arc due to excessive pressure energy before sufficient arc-blast energy could be created to
or wear within the arcing device. damage the enclosure or cause excessive heat energy or gases
Tests were preformed to confirm that the arc-containment to exit the enclosure.
device was able to operate within a reasonable range of
operating parameters. The propensity for restrike or failure to A. 65 kA Tets at 480 V
transfer the arcing fault may be caused by the arc impedance in
the device being high relative to the original’s fault impedance. Fig. 9 shows the transfer of an arc in a 65 kA, 480 V
To verify the reliability of the arc-transfer and arc-sustaining system. Full transfer of the arc from initiation required 6.9 ms.
mechanism, the device was tested with high- and low-power The dotted part of the sine wave seen in the oscillograph (~3
distribution system impedance. Tests on a system able to cycles) shown in Fig. 9 is three cycles of arc current flowing
deliver 65 kA of bolted-fault current confirm that the initiating arc within the arc-containment chamber, where it was safely
in the chamber reduces impedance sufficiently to commutate contained.
the fault arc into the chamber as expected. Tests in a system
able to only deliver 10 kA bolted-fault current confirm that the
device is able to commutate the current in the chamber and
sustain it to ensure that the fault arc does not have an
opportunity to re-ignite. Additional tests were done on a system
able to deliver 85 kA at 635 V, sustaining the arc for several
cycles to determine the device’s ability to withstand pressure
and electrode wear.
Each of the tests was performed using UL1558 standard-
construction indoor low-voltage switchgear. Light and current
sensing was installed in the switchgear. A light sensor was
placed in each of the breaker compartments and in the cable
compartment. Current transformers were installed on the
incoming bus. Measurements were taken of each line current
and the phase-to-phase voltages. The tests were also
videotaped to document the arc transfer. The arc was created in
a 2000 A breaker compartment by wrapping a trigger wire Fig. 9. Arc-absorber transfer behavior on a 65 kA system.
around the three-phase incoming run-in bus into the
compartment in a manner similar to that used in IEEE 1584 Visual evidence provided by a high-speed camera showed
e
R commended Practice for Arc Flash Incident Energy that 10 ms after fault initiation all visible traces of ionized gas or
Calculations . plasma were gone from the area of the original arc. Using the
Each test was performed four or more times. The 65 kA test IEEE 1584 incident energy formula with an arc-mitigation time of
was completed five times at 480 V to ensure structural integrity 6.9 ms reduced the calculated incident energy to less than 1
2
of the chamber and successful transfer. One way to test the cal/cm . The entire event ended at less than 58 ms with the arc-
reliability of the arc transfer under more difficult transfer mitigation device current lasting about 50 ms. The 50 ms
conditions is to decrease arcing fault gap. Two of the tests were includes the circuit breaker being triggered via its shunt trip,
done with 25 mm gaps, increasing the arcing current and which is slower than an internal flux shifter that would be used if
facilitating restrike at the fault. These tests were also performed the circuit breaker’s trip system had initiated the tripping. The
at 10 kA, making it the most difficult of the arc transfer tests. device’s maximum Ipk was 90 kA between all of the conducted
Other tests were done with gaps as large as 50 mm to simulate tests versus the 150 kA that would be expected for a bolted
an arcing gap that may be found in the internal bus structure of fault. Fig. 10 shows a comparison of the various current and
some low-voltage switchgear. All tests were successful and the energy let-through characteristics for an arcing fault, arc-
containment device current, and bolted-fault current, assuming Test
that all three currents lasted a full three cycles, but the fault Fault Gap, Duration, # of
arcing current lasted less than one-half cycle. Ibf, A Volts, V mm cycles tests
65,000 480 50 3.5 5
10,000 480 25 3.5 2
10,000 480 50 3.5 2
85,000 635 None 3.5 1
IX. BIBLIOGRAPHY