Professional Documents
Culture Documents
YEAR-END SALE | UP TO 95% OFF YEAR-END SALE | UP TO 95% OFF YEAR-END SALE | UP TO 95% OFF YE
(206) 687-4009 | support@allumiax.com
To configure protective devices such as making a relay setting, having all the
consideration of the fault severity and decision-making time, it is important
to know parameters, rules, and protection zone so that the reliability of the
power system having continuous supply, is not compromised. Without prior
knowledge of relay settings, reliability is affected badly and it can cause a
penalty to the distributor.
Types of Relay
Based on Operating Mechanism:
Electromagnetic (mechanical type)
Based on Application:
Primary
Backup
Read this blog to learn more about Protection Schemes for Electrical
Power Systems.
Overcurrent Relay
Overcurrent is the most used relay protective scheme as compared to others.
Definition:
An overcurrent relay works on sensing current. It operates whenever the
current exceeds a permissible value or pickup value.
Layout:
Types:
Instantaneous OCR Definite time OCR Inverse time OCR
Characteristics of various over-current relays: (a) definite time, (b) IDMT, (c)
very inverse, and (d) extremely inverse.
Common Terms
Pickup Current (Ipu):
Definition:
Minimum amount of current required for the operation of the relay.
Objective:
Power system components work properly at a certain allowed current and
when the magnitude of current exceeds a certain value (as in case of a fault),
it can cause damage to the component and the entire system reliability is
compromised. The relays are designed to operate above these rated currents.
The pickup current is thus set at the maximum allowed current.
Formula:
Ipu = Rated CT output * %current setting
where,
Rated CT output is the rated current at the secondary side of the current
transformer, typically 1A or 5A.
Current Setting:
Definition:
To adjust the pickup current (Ipu) to the desired value.
Objective:
C.T output comes in standard for example: 5A according to IEC and 1A
according to IEEE.
The current setting sets the pickup value according to it so that the relay can
operate at pickup current instead of working at rated C.T output
Objective:
It defines the severity of a fault. According to the severity of the fault, the
relay may decide the time of operation.
For example:
1. if overcurrent occurs the P.S.M would be low, and tripping may take
after some delay
2. if a short circuit occurs then PSM would be high, and tripping would be
instantaneous
Formula:
Objective:
Sometimes it is desired to trip the relay much earlier than the provided time
from its time/PSM curve.
A dial is provided whose value ranges from 0 to 1, with step of 0.05, the dial
is adjusted at the required value and multiplied with the relay operating time
from time/PSM curve to obtain required time of operation
Formula:
top = TSM * time PSM curve time
Time/PSM Curve:
Definition:
Time/PSM curve represents graph between time (y-axis) and PSM (x-axis). It
represents the time of operation of a relay according to PSM, when TSM is 1.
Objective:
The time/PSM curve helps in achieving the time of tripping according to the
severity of overcurrent or fault. The manufacturer provides the relay
time/PSM curve of a relay and it can be created/varied in microprocessor
based relay.
Solved Example:
Considering the following data:
C.T = 100 / 1
TSM = 50%
Solution:
Ipu = 0.8 A
PSM = 10
top = 1s
1. Discrimination by Time:
A constant time setting is given to each relay irrespective of the
magnitude of the current.
The issue with this method is that the relay closest to the source
has the largest delay while it has the maximum fault current that
could flow within the system, which can damage the system due
to a large time delay.
2. Discrimination by Current:
This method is based on the phenomenon that fault current
amplitude varies with a change in impedance between source and
fault.
The main issue with this method is that there should be a good
distance between two breakers as the relay would not be able to
detect faults if the distance between two zones breaker is less.
Here the power system zones are being overlapped due to reason that no
zones remain unprotected.
Primary Protection:
They are concerned with internal fault and are efficient enough to detect a
fault in the least possible time within a zone and gives a trip signal. Primary
protection schemes are usually implemented using differential, distance, and
directional overcurrent protection.
Differential Protection:
Differential protection works on the current matching principle that is two
CTs are connected in a region in such a way that whenever there is a
difference in current within that region, the relay gives a trip signal, else no
tripping.
They are used in power transformers, generators, and bus bar protection
schemes.
Distance Protection:
In transmission lines, it is not possible to implement differential protection.
For transmission line protection, distance protection is used which is based
on ohm’s law that measures voltage and current, if the measured impedance
is less than the transmission line impedance then the relay gives a trip signal.
Backup Protection:
For better reliability purposes, backup protection schemes are used. They are
less efficient than primary protection but are used for the purpose, if primary
protection does not give a trip signal due to some reason in case of fault, the
backup protection trips after some delay. They are also used in detecting
external faults. Backup protection is achieved using overcurrent relay.