You are on page 1of 16

EPAC 3100/3500

Numerical distance relay


EPAC 3100/3500
Numerical distance relay with integrated automatic and control functions

Features • Additional overload, overvoltage • Real time calendar clock of fault


and undervoltage protection reports and oscillography.
• Fully numerical distance relay
functions. • IRIG-B port for real-time clock
designed to protect overhead
lines and underground cables. • Power swing blocking. synchronisation.
• Typical operating time 1.25 • Switch-on-to-fault protection. • Substation communications via K-
cycles bus or VDEW (IEC 870-5-103
• Parallel line compensation. protocol).
• Up to six independent zones of
protection. • Weak-infeed and echo operation. • Comprehensive self-checking and
• Check synchronising function. alarms.
• Dual distance protection
algorithms. • Automatic single and/or three- User's tools
• Independent directional pole auto-reclose function. • Front panel display,
overcurrent element for additional • Four independent, user selectable • WinEPAC software (off-line
(back-up) protection. setting groups. setting),
• Quadrilateral characteristic used • Fault location and instrumentation. • WinTPE software (oscillography),
for all type of faults.
• Ten fault reports stored in non • Courier™ communication:
• Comprehensive range of volatile mass memory with PAS&T or CAS:W software
protection schemes. automatic down-loading to a (on-line setting).
• Single and three pole tripping. printer.
• Comprehensive directional earth • Oscillography stored in non
fault (DEF) protection with back-up volatile memory. Average
IDMT element for high resistance capacity of 40 5-second records
earth faults. through data compression.

2
Functions
Phase selector
Fast algorithms compare
superimposed currents.
Conventional algorithms use
overcurrent or impedance criteria.
Fault direction
The fault direction is obtained by
calculating the sign of the
superimposed energy for the fast
algorithms or measuring the phase
shift between the pre-fault voltage
(10 s memory voltage) and the fault
current for the conventional
Figure 1.
EPAC 3100 relay algorithms.
Introduction values, and conventional algorithms Distance-to-fault
using values measured during the measurement
EPAC is a fully numerical protection
equipment designed for distribution fault in the same way as Distance to the fault is measured by
and/or transmission networks that conventional protection. discriminating between the voltage
are solidly earthed, impedance drop on the line and that caused by
This dual algorithm principle allows
earthed or earthed via a Petersen the fault. This removes the error due
the relays to detect all types of faults to the fault resistance irrespective of
coil.
occurring in the network. the load current. A least squares
The relay is fully compatible with the method is used to get the algorithms
VT's or CVT's may be on a line or
ALSTOM K-range of relays and can to converge rapidly.
be integrated into an overall on busbar side.
protection and control system Distance protection
There is a comprehensive selection
utilising its integral serial of protection schemes allowing Six zones of protection for all types
communications facility. single or three pole tripping with or of faults are provided as shown in
Figure 2.
Models available without a signalling channel.
They are:
There are 12 different models Additional protection functions such
according to the features required. as DEF, overload, under and over • Zone 1 forward directional
voltage protection, complement the instantaneous or time-delayed trip
These models are described in a zone.
table, page 16 of this publication: distance protection and allow single
and
Recapitulation of features per or three-pole tripping when the Zone 1X forward directional used
models. impedance point relative to the fault for zone reach control scheme,
is outside the quadrilateral instantaneous or time-delayed trip
Applications
characteristic. zone.
EPAC is suitable for the protection of Figure 2.
overhead lines and underground Relay characteristic
cables and can be used as the main
X
or back-up distance protection for
networks whether they are solidly
earthed, impedance earthed or Zone 4, T4
earthed via a Petersen coil. The
resistance reach coverage value per
Zone 3, T3
zone is perfectly adapted to short ∆R
line and cable protection.
Zone 2, T2
Two independent earth fault factors,
K01 used for zone 1 and K02 for Zone1X, T1

the other zones are particularly Zone1, T1

beneficial to hybrid line R1 R2 R3 R4 R


applications.
Its protection scheme simultaneously Zone 3, T3
reverse
employs fast algorithms, using
superimposed values in order to Zone 5, T5
eliminate load current, which
respond only to fault related phase

3
t • Detection of the 2nd harmonic
I>, T> I>, T> current (inrush current) to protect
I>>, T>> I>>, T>>
against maloperation due to
transformer inrush conditions.
Z5, T5 Z4, T4

Z3, T3
• Fault detection and clearance
Z2, T2
during a single-phase cycle in
Z1, T1
progress.
Reverse looking Forward looking
Distance
• The Weak Infeed mode of the
Figure 3. relay is used when the infeed to a
Current start-up line end is too low to detect a
fault. In this mode the relay is
• Zone 2 forward directional time- Carrier aided schemes for two and able to trip single- or three-pole.
delayed trip zone. three terminal feeders:
Protection against high
• Zone 3 forward or reverse • Permissive underreach transfer resistance earth fault
directional time delayed trip zone. tripping scheme (PUTT or PUP
forward), The role of this protection is to
• Zone 4 forward directional time detect resistive earth faults which
delayed trip zone. • Permissive overreach transfer resistance is outside the
• Zone 5 reverse directional time tripping scheme (POTT or POR1), quadrilateral characteristic of the
delayed trip zone. distance protection.
• Accelerated underreach scheme
The back-up overcurrent protection (AUP or PUR), The main protection is realised by a
permits the clearance of faults directional comparison element
• Blocking underreach scheme using zero sequence quantities. Its
beyond zones 4 and 5 using two
(BOR1), back-up earth fault protection is
directional or non-directional time
delayed thresholds as shown in • Blocking overreach scheme provided by an inverse definite
Figure 3. (BOR2). minimum time (IDMT) delayed
element using the zero-sequence
Busbar isolation Tee-line applications may use two directional current or the zero-
Busbar isolation mode is used to different schemes. sequence directional power.
isolate busbars if there is a fault Additional features Directional earth fault
near them in order to reduce the comparison protection (DEF)
fault current quickly. This 4-zone • Switch-on-to-fault (SOTF), using
for 2 or 3 terminals
mode is non-directional as the link overcurrent and distance element
must be broken quickly since the fault detection. Directional comparison protection
fault may originate from a busbar operates in conjunction with one or
• Power Swing Blocking, based on two remote end relays. The DEF
situated in the forward or reverse
measuring the time necessary for protection is able to trip single- or
direction of the protection device as
the three single loops to cross the three-pole using permissive or
shown in Figure 4.
power swing band (R surrounding blocking scheme logic. The
Earth fault direction in the start-up characteristic (Figure 2). transmission channels may be the
isolated or Petersen coil same as those used by the distance
earthed networks • Voltage Transformer Supervision
for the detection of the VT fuse protection or may be independent.
The RNI module allows the EPAC to failure or miniature circuit breaker Tee-line applications may use two
protect overhead lines and operation. different schemes.
underground cables when the
neutral of the network is isolated or Figure 4.
earthed by an impedance or by a Busbar isolation
Petersen coil. The PWH function
(wattmetric element) in the RNI Zone 4
module determines the direction of Zone 3
permanent or intermittent phase-to- Zone 2
earth faults.
Scheme functions
Zone 1
The relay is fitted with a
comprehensive selection of scheme
functions.
R1 R2 R3 R4
Single-ended schemes include:
• Basic scheme logic for stand
alone operation (without
signalling channel),
• Zone 1 extention scheme to permit
high speed reclosure when no
signalling channel is available
(zone reach extention).

4
ANSI/IEE curves IEC curves
1000 1000

100 100
Operating time (s)

Operating time (s)


10 10

Standard inverse

Moderately inverse
1 1
Very inverse
Very inverse

Extremely Extremely
Standard inverse inverse
inverse

0.1 0.1
1 10 100 1 10 100
Current (multiple of Is) Current (multiple of Is)

Moderately inverse ( 0.114 +


0.0515
( I /IE)
0.02
−1 ) ⋅ TM Standard inverse
(( 0.14
I / IE )
0. 02
−1 ) ⋅ TM

Standard inverse ( 0.18 +


5.95
( I /IE)
2
−1
) ⋅ TM Very inverse (( 13.5
I / IE ) − 1
⋅ TM )
Very inverse ( 0.491 +
19.61
( I /IE ) − 1
2 ) ⋅ TM Extremely inverse
(( 80
2
I / IE ) − 1 ) ⋅ TM

Extremely inverse ( 0.1217 +


28.2
( I /IE) − 1
2 ) ⋅ TM
I = earth fault current
IE= set earth fault pick-up value

0.2 ⋅ P ⋅ So
Zero-sequence power protection with inverse definite time: Operating time =
Sr
So = 10 VA; Sr = Ur . Ir; P = programmable factor
Ir = measured residual current; Ur = measured residual voltage

Figure 5.
IDMT curves

IDMT earth fault protection high resistance earth fault remains • Inverse time delayed directional
after a fixed time delay. zero sequence: the value of its
The IDMT directional overcurrent or
time delay varies in relation with
zero sequence power elements are The value of this time delay varies in
the values of the zero sequence
used as back-up protection: relation with the value of the fault
current and voltage and the
current and the type of the inverse
• The IDMT directional overcurrent equation described in Figure 5.
time curve selected, see Figure 5.
protection trips the three poles of
the associated circuit breaker if a

5
HV network with VT EHV network with CVT
Operating 40 Operating 40
Time Time
(ms) (ms)
35 35

30 SIR=30 (typ) 30
SIR=30 (max)
25 SIR=1 (typ) 25
SIR=1 (min)

20 20

15 15
0 10 20 30 40 50 60 70 80 0 10 20 30 40 50 60 70 80
Reach (% ) Reach (% )

Figure 6.
Zone 1 50 Hz operating times for phase to neutral faults

HV network with VT EHV network with CVT


Operating 40 Operating 40
Time Time
(ms) (ms)
35 35

30 SIR=30 (typ) 30
SIR=30 (max)
25 SIR=1 (typ) 25
SIR=1 (min)

20 20

15 15
0 10 20 30 40 50 60 70 80 0 10 20 30 40 50 60 70 80
Reach (% ) Reach (% )

Figure 7.
Zone 1 50 Hz operating times for phase to phase faults

HV network with VT EHV network with CVT


Operating 40 Operating 45
Time Time
(ms) (ms) 40
35

35
30
SIR=30 (typ)
SIR=30 (max) 30
25 SIR=1 (typ)
SIR=1 (min) 25

20
20

15 15
0 10 20 30 40 50 60 70 80 0 10 20 30 40 50 60 70 80
Reach (% ) Reach (% )

Figure 8.
Zone 1 50 Hz operating times for phase-phase-neutral faults

HV network with VT EHV network with CVT


Operating 40 Operating 45
Time Time
(ms) (ms) 40
35

35
30
SIR=30 (typ)
SIR=30 (max) 30
25 SIR=1 (typ)
SIR=1 (min) 25

20
20

15 15
0 10 20 30 40 50 60 70 80 0 10 20 30 40 50 60 70 80
Reach (% ) Reach (% )

Figure 9.
Zone 1 50 Hz operating times for 3-phase faults

6
TPE oscillography:
Control system: current loop connection to UR
K-Bus courier (data concentrator)
or VDEW or modem connection

Daughter boards

Rear panel
IRIG-B

- oscillography - protection logic Analogue


- setting groups - measurement board Power
algorithms
supply
12 bits ADC
IRIG.B INTEL 960 TMS 320 C25
Risc E.P. processor 24 samples/cycle
board Microprocessor

A.C. board TMS board

Voltage & current


transformers
Va Vb Vc
TRIP Ia Ib Ic
2 lines-16 digits
LCD screen ALARM In Uctmh (1)
Ubusbar
Optically Output Tripping
RELAY AVAIL. isolated contacts contacts
inputs
Indicator LEDs

Front panel

(1)
Uctmh = mutual compensation

Serial port Serial port


WinEPAC Printer or
(settings) WinTPE (oscillography)

Figure 10.
Block diagram

Additional protection Auto-recloser Check synchronising function


functions
The reclose cycle is initiated by the The check synchronising function
The following additional protection operation of the associated allows reclosure when the voltage
is included in the distance relay. protective function (distance, DEF or on the line and/or the busbar is
back-up) or through opto-isolated below a preset value and when the
Overload protection
inputs (external protection relay). It two parts of the system are in
The overload protection trips three- provides one 1- or 3-pole high synchronism by measuring the angle
phase if at least one of the speed reclosure and up to three and the slip frequency between the
measured currents is higher than a 3-pole delayed auto-reclosures. line voltage and the busbar voltage:
settable threshold for a fixed or
• Live busbar and dead line,
inverse time delay.
• Dead busbar and live line,
Undervoltage protection
• Live busbar and live line,
The undervoltage protection trips
three-phase if at least one of the • OR logic of the three preceeding
measured voltages is lower than a mode.
settable threshold for a fixed time.
Overvoltage protection
The overvoltage protection trips
three-phase if at least one of the
measured voltages is higher than a
settable threshold during a fixed
time.

7
Configuration Each fault report includes time • 16-bit sampling of current values
tagged details of the faulted phases, and 12-bit sampling of voltage
Inputs and outputs values.
trip type and fault location (fault
• 8 or 16 user programmable, distance and apparent resistance).
• filtering and computing of derived
optically isolated inputs Additionally, information on the quantities and protection
depending on the model selected. system frequency, fault currents and algorithms by a real-time signal
voltages values. processor.
• 13, 16, 26 or 32 user
programmable normally open Disturbance records • tripping logic, management of
output contacts depending on the The internal disturbance recorder logic acquisitions and signals.
model selected. has 8 analogue channels to record The oscillography, communication
• 3, 6 or 12 normally open trip current and voltage inputs to the and user interface dialogue are
contacts depending on the model relay and up to 32 digital channels managed by a special board
selected. These contacts may be to record the status of the having a RISC microprocessor
connected directly to the coil of input/output relays. Data INTEL 960.
the circuit breaker. compression allows the recording
and storage in non-volatile memory User interface
• 1 or 2 normally open reclose of an average of forty 5-second The EPAC is programmed and
contacts depending on the model events. The information in the operated through its key-pad and
selected. These contacts may be disturbance recorder is accessed on display, or through its RS-232 link
connected directly to the coil of a personal computer connected to on the front panel of the unit, or via
the circuit breaker. the relay’s front panel or via the the communications unit from a
• 1 or 2 normally closed contacts, communication system to provide a personal computer running the
depending on the model selected, graphical display and to conduct in- programming software WinEPAC.
for watchdog alarm. depth fault analysis, using WinTPE
software. User interface with WinEPAC
Alternative setting groups WinEPAC software is run on the
Four sets of setting groups are WindowsTM interface of which it
provided and stored in a non- uses the graphic capabilities to their
volatile memory. They can be used fullest. All the functions are clearly
to change the relay’s setting to labelled and grouped by theme
screens. WinEPAC is a very
cover abnormal operating
intuitive application and it is quick
conditions. The setting groups can
and easy to learn.
be selected locally via the front
panel display or WinEPAC
software, or remotely via the relay’s
communication system. Two inputs
can be allocated to the selection of Figure 11.
setting groups allowing them to be WinTPE software (WinANALYSE)
changed by means of an external Fault location
system.
The fault location report provides
Ancillary Functions information about the distance to the
The ancillary functions allow the fault and the fault resistance. The
equipment to be used in specific distance to the fault is in miles,
applications. kilometres, ohms or as a percentage Figure 12.
of line length. WinEPAC software
Instrumentation
Fault location can be calculated
The instrumentation functions of the both for single and parallel lines.
equipment can be accessed locally Front panel user interface
via the relay’s front panel display or Power-on diagnostics and self Dialogue through the front panel
the WinEPAC software, or remotely monitoring display offers the same features as
via its communication system. The relay continuously runs self- with the WinEPAC software.
Values of frequency, phase currents checks. In the event of a failure of a Functions are selected using six keys
and voltages, active and reactive device, an alarm is triggered and a on the key-pad. The display is a 2
power, the direction of the load self-diagnostics system enables line, 16 character back-lit LCD
current, and the status of the relay’s quick and easy trouble-shooting. screen.
inputs and outputs are displayed.
Hardware description
Fault reports
The EPAC is a fully numerical relay
When a fault occurs, causing a providing:
relay to trip, a fault report is created
and stored in non-volatile memory. • input circuit with anti-aliasing
filters.
It is possible to view via the relay’s
front panel or the WinEPAC • acquisition of residual quantities
software, or print out, any or all of allowing constant monitoring of Figure 13.
the last ten fault reports. sampled values. Front panel display

8
1 2
27 1 27 1

28 2 28 2

27 1 27 1

28 2 28 2

1
27 1

28 2
27 28

Figure 14.
Rear panel and K-bus connection to the terminal block

Maintenance software
Relay 32 Relay 4 Relay 3 Relay 2 Relay 1
WinEPAC software also includes a
commissioning and maintenance
program to facilitate commissioning
tests and providing guidance for
maintenance personnel.
TERMINAL1

TERMINAL2

Communication protocol
• Communication with the master
station comforms to application
standard ‘VDEW’ - IEC 870-
5/103. The EPAC can therefore Protocol
be interfaced with any product converter
compliant with that standard.
KITZ
• The communications protocol used IEC870-5
with K Series relays is designated RS232 K-Bus
Courier. The Courier language RS485
has been developed specifically Desktop
for the purpose of developing computer
generic PC programs that will, PC
without modification,
communicate with any device Figure 15.
using the Courier language. In Connection to K-bus
the Courier system, all information
resides in the relay. Each time wire pair known as K-Bus. Up to 32 which alter the configuration of the
communication is established with relays may be connected in parallel relay. This prevents any accidental
the relay, the requested across the bus. The K-Bus can be change which could seriously affect
information is sent to the PC. The connected through a protocol the ability of the relay to perform its
protocol includes extensive error converter known as KITZ, either intended functions. The setting, fault
directly or via a modem, to the RS- report and disturbance record
checking routines to ensure that consultations are not protected by
the system remains reliable and 232 port of the PC. The K-Bus is RS-
485 based and runs at 64 kbits/s. password: a password is needed for
secure. resetting only.
The K-Bus connection to the relay is
Relay interconnection shown in Figure 14 . This system Languages
• The VDEW IEC 870-5/103 allows up to 32 relays to be The EPAC user interface may be
interface enables the relays to be accessed through one RS-232 configured in one of four
connected to the master station communication port (Figure 15). languages; these are:
using fibre optic link. The speed Software is available with each KITZ
of this link is 9600 or 19200 to provide access to the relays to • English,
read and change settings. • French,
bits/s depending on the
• German,
configuration. Password protection • Spanish.
• The relay’s communication can be Password protection is provided for
connected via a shielded, twisted all remote or local setting changes

9
1 2 27 1 27 1 [a]
X1 X2 C.T. Shorting links make
28 2 28 2 before [b] disconnect

27 1 27 1 [b] Short terminals


X6 X3 X4
28 2 28 2 [c] Pin terminal [P.C.Btype]
Terminal block
27 1
27 28 28
X5 2 50 Ohm BNC connector
TC Output contact
TS Opto-isolated input

A
7X5 27X6
Phase A voltage 28X6
C B V.T. secondaries
Phase rotation 6X5
Phase B voltage Case earth
Direction of power flow for operation
P2 P1 5X5 K-Bus connection can
A Phase C voltage be either way
S2 S1 8X5
B
C Screen mechanical
terminationonly
28X5 +
1 A - phase A
27X5
IRIG-B input
24X5 +
1 A - phase B
23X5 5X1
TripA 6X1
20X5 + 7X1
1 A - phase C TripB
19X5 8X1
9X1
TripC
10X1
15X5 11X1
1 A - Neutral Reclosing
16X5 + 12X1
1X2
TC1
2X2
3X2
26X5 + TC2
5 A - phase A 4X2
25X5 5X2
TC3
6X2
7X2
22X5 + TC4 8X2
5 A - phase B
21X5 9X2
TC5
10X2
18X5 + 11X2
5 A - phase C TC6
12X2
17X5 13X2
TC7
14X2
14X5 + 15X2
5 A - Neutral TC8
13X5 16X2
TC9 17X2
18X2
19X2
TC10
3X5 + 20X2
Ubar 21X2
TC11
4X5 22X2
23X2
1X5 + TC12
24X2
UCTMH 25X2
2X5 TC13
26X2
27X2
TC14
28X2
1X1
TC15
2X1
TC16 3X1
4X1
9X6
Equipment failure 1
13X1 + 10X6
TS1
14X1
15X1 + 5X3
TS2 TripA 6X3
16X1
7X3
17X1 + TripB
TS3 8X3
18X1 9X3
TripC
19X1 + 10X3
TS4 11X3
20X1 Reclosing
12X3
21X1 + 1X4
22X1 TS5 TC1
2X4
23X1 + 3X4
TS6 TC2
24X1 4X4
5X4
25X1 + TC3
6X4
26X1 TS7 7X4
TC4 8X4
27X1 +
TS8 9X4
28X1 TC5
10X4
TC6 11X4
12X4
13X4
13X3 + TC7
14X4
TS1 15X4
14X3 TC8
16X4
15X3 + 17X4
TS2 TC9
16X3 18X4
17X3 + 19X4
TS3 TC10
18X3 20X4
21X4
19X3 + TC11
TS4 22X4
20X3 23X4
TC12
21X3 + 24X4
TS5 25X4
22X3 TC13
26X4
23X3 + 27X4
TS6 TC14
24X3 28X4
1X3
25X3 + TC15
TS7 2X3
26X3 3X3
TC16
27X3 + 4X3
TS8 15X6
28X3 Equipment failure 2
16X6

Figure 16.
Example of case connection diagram (EPAC 3132)

10
Technical Data Settings

Ratings Line parameters


Inputs Neutral earthing direct
AC current (In) 1 A and 5 A isolated or Petersen coil earthed network
AC voltage (Vn) 100 V to 120 V in steps of 1V Length of line in km or miles 0.3 to 999.99 km or 0.18 to 621.49 miles in
steps of 0.01
DC auxiliary voltage Nominal (V) Operative range (V)
48 38.4 - 57.6 Range of settings in secondary values. Parameters can be entered in Cartesian co-ordinates, Polar
60 48 - 72 Co-ordinates or Positive sequence impedance/earth ratios.
110 88 - 132
Polar Co-ordinates
125 100 - 150 Positive sequence impedance module, Z1 0.001 to 999 Ω in steps of 0.001 Ω
220 176 - 264 Positive sequence impedance argument 0° to 90° in steps of 1°
250 200 - 275 Zero sequence impedance modules Z01 and Z02 0.001 to +999 Ω in steps of 0.001 Ω
DC opto-isolated input 48 V, 60 V, 110 V, 125 V, Zero sequence impedance argument -- 90° to +90° in steps of 1°
voltage supply 220 V, 250 V
Monitoring Parameters of the Protection Function
Frequency 50/60 Hz
1A rating 5A rating
Permitted ripple 12% superimposed on nominal frequency
Impedance Zone 1, Zone 1X, Zone 2, 0.1 to 200 Ω in steps of 0.01 0,02 to 40 Ω in steps of 0.01
Burdens Zone 3, Zone 4, Zone 5
AC current 0.1 VA at In = 1 A; 0.5 VA at In = 5 A Phase-phase resistance reach (zone 1) 0 to 200 Ω in steps of 0.01 0 to 40 Ω in steps of 0.01
Phase-earth resistance reach (zone 1) 0 to 200 Ω in steps of 0.01 0 to 40 Ω in steps of 0.01
AC voltage 0.1 VA
Resistance reach zone 2 0 to 200 Ω in steps of 0.01 0 to 40 Ω in steps of 0.01
DC auxiliary voltage 25 W under healthy live line conditions, 35 W
Resistance reach zone 3 0 to 200 Ω in steps of 0.01 0 to 40 Ω in steps of 0.01
max.
Start resistance zones 4 and 5 0 to 200 Ω in steps of 0.01 0 to 40 Ω in steps of 0.01
Optically isolated inputs 10 mA per input Zone 3 direction forward/reverse
Step 1 timer, T1 0 to 10 s in steps of 5 ms
Thermal withstand
Steps 2, 3, 4 and 5 timers: T2, T3, T4, T5 0 to 10 s in steps of 10 ms
AC current inputs 4 In continuous
Overcurrent thresholds I> and I>> 0.2 In to 9.99 In in steps of 0.01 In
100 In for 1 s; 30 In for 5 s Directionality of I> and I>> without/forward/reverse
AC voltage inputs 2.2 Vn continuous Step timers T> and T>> 0 to 10 s in steps of 10 ms
2.6 Vn for 10 s
Scheme functions
Reference conditions Tripping type single-phase for zones 1 and 2
Temperature 20 °C single-phase for zone 1
Auxiliary voltage Nominal DC voltage range ordinary three-phase tripping all zones
Frequency 50/60 Hz Scheme logic basic scheme logic
accelerated underreach protection (AUP)
Transformers turns ratios permissive overreach protection (POP or POTT)
CT ratios (Ki) 1 to 20,000 in steps of 1 blocking overreach protection (BOP or BDCP)
VT ratios (Ku) 1 to 20,000 in steps of 1 blocking underreach protection (BUP)
permissive underreach protection (PUB or PUTT)
Contact ratings zone reach control
Tripping and Closing Contacts busbar isolation
Maximum operating voltage 250 Vdc HF acceptance or unblocking none, unblocking, HF acceptance
Make 30 A and carry for 500 ms Carrier send transmission carrier send transmission in zone 1
250 A and carry for 30 ms carrier send transmission in zone 2
carrier send transmission in reverse zone 5
Permitted overload 250 A, 30 ms
Carry 5 A continuous Tee Line The teleaction possibilities for the second
Breaking capacity (L/R < 40 ms) 0.75 A with 48 Vdc teleprotection channel of the Tee line are the
0.3 A with 125 Vdc same as those for the first channel.
0.25 A with 220-250 Vdc
Weak-infeed and echo
Signalling Contacts
Weak-Infeed and echo configuration yes/no
Maximum operating voltage 250 Vdc
Function locking on power swing yes/no
Permitted overload 100 A, 30 ms
Tripping authorisation none/1 pole/3 poles
Carry 5 A continuous Confirmation by insufficient voltage yes/no
Breaking capacity (L/R < 40 ms) 0.75 A with 48 Vdc If yes, under voltage threshold 0.2 Vn to Vn in steps of 0.1 Vn
0.3 A with 125 Vdc Open pole detection threshold 0/0.05 In
0.25 A with 220-250 Vdc Time-delay for tripping 0 to 1 s in steps of 1 ms
Blocking time if start-up drop off 0 to 500 ms in steps of 1 ms
Contact durability
Loaded contact 10,000 operations minimum Power-swing
Unloaded contact 100,000 operations minimum Power swing detection boundary 0 to 25 Ω in steps of 0.01 Ω
Unblocking timer 0 to 30 s in steps of 100 ms
IRIG.B First zone independent on power swing yes/no
All versions 3X3X have a BNC type connector to carry IRIG-B format data for automatic setting and Carrier send blocking on power swing yes/no
synchronising the relay's calendar clock. Carrier receive blocking on power swing yes/no

11
Unblocking on residual current Ir yes/no Reversal guard extension
Unblocking percentage threshold kr 10 to 100% in steps of 1 % of Ir Reverse locking extension time-delay 0 to 150 ms in steps of 10 ms
Unblocking on overcurrent Imax yes/no
Fault locator
Unblocking threshold Imax In to 20 In in steps of 0.01 In
Fault locating unit in km or in miles,
Unblocking on negative sequence current yes/no
Accuracy ± 3% of the line length
Unblocking percentage threshold 10 to 100% in steps of 1% of I2
Tripping mode 1 pole/3 poles Disturbance recording
Blocking type none Disturbance recording enabled yes/no
blocking all zones Disturbance recording triggered when
zone 1 blocking analogue thresholds are exceeded yes/no (IA, IB, IC, Ir, UA, UB, UC, UR, F)
zones 1 and 2 blocking Min and max voltage thresholds 0 to 250% Vn in steps of 1% Vn
zones 1, 2 and 3 blocking Min and max current thresholds 0 to 7,000% In in steps of 1% Vn
zone 1 unblocking Min frequency threshold
zones 1 and 2 unblocking If freq. = 50 Hz 45 ≤ Fmin ≤ 50; 50 ≤ Fmax ≤ 55
zones 1, 2 and 3 unblocking If freq. = 60 Hz 55 ≤ Fmin ≤ 60; 60 ≤ Fmax ≤ 65
Pre-fault time 0.1 to 0.5 s in steps of 100 ms
Fuse failure and emergency overcurrent protection Post-fault time 0.1 to 4.5 s in steps of 100 ms
I0 and I2 threshold detection 0 to In in steps of 0.01 In Overload protection
Timer for fuse failure indication 1 to 20 s in steps of 1 s Type of protection none
Ifus> threshold unblocking yes/no fixed thresholds
Ifus> threshold 0.2 In to 9.99 In in steps of 0.01 In inverse curves
Tfus> timer 0 to 10 s in steps of 10 ms Fixed threshold I1 0.5 In to 2 In in steps of 0.01 In
Ifus>> threshold unblocking yes/no Fixed threshold I2 In to 3 In in steps of 0.01 In
Ifus>> threshold 0.2 In to 9.99 In in steps of 0.01 In Fixed threshold I3 1.3 In to 3 In in steps of 0.01 In
Tfus>> timer 0 to 10 s in steps of 10 ms Threshold I1 tripping timer 1 to 100 min in steps of 1 min
Ifr> threshold unblocking yes/no Threshold I2 tripping timer 1 to 100 min in steps of 1 min
Ifr> threshold 0.2 In to 9.99 In in steps of 0.01 In Threshold I3 tripping timer 1 to 100 s in steps of 1 s
Tfr> timer 0 to 10 s in steps of 10 ms Type of inverse curve IEC, ANSI (US)
Auto-recloser blocking by fuse failure tripping yes/no Choice of IEC curve inverse/very inverse/extremely inverse
Choice of ANSI curve moderately inverse/inverse/very
Timer for auto-recloser blocking by the distance protection inverse/extremely inverse
Timer for auto-recloser blocking no/to T2/to T3/to T4/to T5/to T>/to T>> Threshold line current 0.5 In to 2 In in steps of 0.05 In
Multiplier factor 0 to 3.2 In in steps of 0.01 In
Seal-in
Enabled/disabled yes/no Over and under voltage protection
Holding threshold 0.1 In to In in steps of 0.1 In Minimum voltage threshold 0.1 Vn to 0.6 Vn in steps of 0.1 In
Timer for minimum voltage tripping 0 to 20 s in steps of 0.1 s
Auto-recloser Maximum voltage threshold 1.1 to 1.4 Vn in steps of 0.1 Vn
Reclosing mode on 1 pole trip None, 1, 1/3, 1/3/3, 1/3/3/3 Timer for maximum voltage alarm 0 to 20 s in steps of 0.1 s
Reclosing mode on 3 pole trip None, 3, 3/3, 3/3/3, 3/3/3/3 Tripping on maximum voltage yes/no
Reclosing mode on trip by backup protection None, 3, 3/3, 3/3/3, 3/3/3/3
Resistant earth fault protection
High-speed 1 pole dead time 0.1 to 5 s in steps of 0.01 s
Directional comparison protection yes/no
High-speed 3 pole dead time 0.1·k to 500 s in steps of 0.01 s
Residual voltage threshold 0.01 Vn to 0.2 Vn in steps of 0.01 Vn
Low-speed dead time 0.1·k to 500 s in steps of 0.01 s Residual forward current threshold 0.1 In to 4 In in steps of 0.01 In
where k=1 if no synchro-check Tripping type 1 pole/3 poles
where k=2 if voltage check Independent teleaction channel yes/no
where k=4 if synchro-check Type of tripping scheme permissive/blocking
Reclaim time 0.1 to 500 s in steps of 0.1 s Transmission time-delay for teleaction 0 to 1 s in steps of 5 ms
Backup protection reclaim time 0.1 to 500 s in steps of 0.1 s Tee line present yes/no
Duration of closing command 0.1 to 10 s in steps of 10 ms Type of scheme for tee line permissive/blocking
Transmission time-delay for tee line application 0 to 1 s in steps of 5 ms
Check synchronising function Operation timer 0 to 10 s in steps 100 ms
The following types of synchro-check are possible: Activation of back-up protection no, power, current
none Residual current threshold 0.1 In to 4 In in steps of 0.01 In
live line / dead bus UL> / UB< Multiplier factor 0 to 3.2 in steps of 0.01
dead line / live bus UL< / UB> Type of curve IEC, ANSI (US)
live line / live bus UL> / UB> IEC curve type inverse/very inverse/extremely inverse
Check synchronism on high-speed ANSI curve type moderately inverse/inverse/very
three-phase cycle yes/no inverse/extremely inverse
Confirmation time for the live-line and Coefficient of multiplication P (power) 1 to 9 in steps of 1
live bus mode 0.2 to 2.0 s in steps of 0.1 s Auto-recloser of backup protection locked yes/no
Voltage difference 0.1 Vn to Vn in steps of 0.05 Vn
Frequency difference 0.05 to 5 Hz in steps of 0.01 Hz Isolated neutral protection (Peterson coil)
Angle difference 10° to 70° in steps of 5° Network with isolated neutral or impedance yes/no
Selection criteria for loop Acyclic C(A), A(C), B(A), A(B), C(B), B(C)/Cyclic
UL> (line voltage presence threshold) 0.5 Vn to Vn in steps of 0.05 Vn
C(A), A(C)
UB> (bus voltage presence threshold) 0.5 Vn to Vn in steps of 0.05 Vn
Residual current threshold 0.2 In to 5 In steps of 0.1 In
UL< (line voltage absence threshold) 0.1 Vn to 0.4 Vn in steps of 0.05 Vn
Residual voltage threshold 0.1 Vn to Vn in steps of 0.05 Vn
UB< (bus voltage absence threshold) 0.1 Vn to 0.4 Vn in steps of 0.05 Vn
Tripping on maximum residual voltage yes/no
Switch on-to-fault Time-delay for tripping on maximum residual
Switch on to fault threshold In to 9.9 In in steps of 0.1 In voltage 1 to 360 s in steps of 1 s

12
Zero sequence active power protection Electro-magnetic compatibility IEC 255-22
Zero sequence active power yes/no High frequency disturbance (255-22-1) 2.5 kV peak between independent circuits and
Secondary current for max. angle case
error of current transformer 1 mA to 4 A in steps of 1 mA 1.0 kV peak across terminals of the same circuit
Angle error of current transformer at I1 --30° à +30° in steps of 1° Electrostatic discharge (255-22-1) 8.0 kV point contact discharge with cover
Secondary current above which the removed
angle error is practically constant 1 mA to 4 A in steps of 1 mA 15 kV discharge in air with cover in place
Angle error of current transformer at I2 --30° to +30° in steps of 1° Electromagnetic interference (immunity) 27 MHz - 1000 MHz 10 V/M,
Residual current threshold for the start-up 1 mA to 4 A in steps of 1 mA 80% modulation at 1 kHz
Angle of the start-up characteristic --180° to +180° in steps of 1° Fast transient disturbance 4.0 kV, 5.0 kHz 1 min. applied to all inputs
K power factor 1 to 10 in steps of 1 Electromagnetic interference on
CT core balance ratio (Kir) 1 to 20000 in steps of 1 logic channel (transmission) NF for 55011 and 55022 Group 1, Class A
Duration of transient earth fault 100 to 500 ms in steps of 10 ms
Electrical environment IEC 255-5
Sensitivity of the distance protection function Impulse voltage withstand 5 kV 1.2 / 50 microseconds; 0.5 J
Current threshold 0.2 In Insulation resistance > 100 MΩ at 500 VDC
Directional sensitivity unlimited for all types of faults Dielectric withstand 2 kV 50 Hz 1 min.
unlimited for 10 s for close faults (memory voltage) Protection index IP52

Accuracy of the distance protection function Atmospheric environment IEC 68-2


For an SIR < 30 and a current Operating temperature --10° to +55°C
of 0.2 to 30 In (zone 1) 5% of adjusted value Storage temperature --40° to +70°C
Other zones 10 % of adjusted value Relative humidity with no condensation 93 %

Operating Time Mechanical environment IEC 255-21


Fastest tripping time 18 ms Vibration category 1
Typical operating time 60 Hz: 22 ms Shock and bump category 1
50 Hz: 25 ms Free fall with packing 2 falls of 0.5 m
≤ 30 ms for SIR =1
≤ 40 ms for SIR = 30

Recapitulation of features / models

Specifications 3111 3112 3113 3116 3121 3122 3123 3126 3131 3132 3133 3136
3511 3512 3513 3516 3521 3522 3523 3526 3531 3532 3533 3536
Distance protection
Six zones of protection ● ● ● ● ● ● ● ● ● ● ● ●
Directional overcurrent
Scheme functions
Power-swing tripping ● ● ● ● ● ● ● ● ● ● ● ●
Single or three pole tripping ● ● ● ● ● ● ● ● ● ● ● ●
Directional earth fault (DEF) ● ● ● ● ● ● ● ● ● ● ● ●
Additional overload, overvoltage
● ● ● ● ● ● ● ● ● ● ● ●
and undervoltage protection
Check synchronising function ● ● ● ● ● ● ● ● ●
Automatic single and/or
● ● ● ● ● ● ● ● ●
three-pole autoreclose function
Four independent user selectable setting groups ● ● ● ● ● ● ● ● ● ● ● ●
Fault location ● ● ● ● ● ● ● ● ● ● ● ●
Ten fault reports stored in ● ● ● ● ● ● ● ● ● ● ● ●
non-volatile mass memory
Automatic down-loading ● ● ● ● ● ● ● ●
of fault reports to a printer
Oscillography stored in non volatile memory ● ● ● ● ● ● ● ●
IRIG-B input for real-time clock synchronisation ● ● ● ●
Substation communications
● ● ● ● ● ● ● ●
via K-Bus, VDEW ou TPE
Front panel LCD display ● ● ● ● ● ● ● ● ● ● ● ●
Programmable inputs 8 16 8 16 8 16 8 16 8 16 8 16
Programmable output contacts 16 32 13 26 16 32 13 26 16 32 13 26
Tripping contacts 3 6 6 12 3 6 6 12 3 6 6 12
Circuit breaker reclosing contacts 0 2 1 2 0 2 1 2 0 2 1 2
Watchdog contacts 1 2 1 2 1 2 1 2 1 2 1 2

13
Information required with order

EPAC 3111/3511 E P 3 B A A D B
EPAC 3112/3512 E P 3 E A A H B
EPAC 3113/3513 E P 3 G A A H B
EPAC 3116/3516 E P 3 H A A H B
EPAC 3121/3521 E P 3 B C D
EPAC 3122/3522 E P 3 E C H
EPAC 3123/3523 E P 3 G C H
EPAC 3126/3526 E P 3 H C H
EPAC 3131/3531 E P 3 B D D
EPAC 3132/3532 E P 3 E D H
EPAC 3133/3533 E P 3 G D H
EPAC 3136/3536 E P 3 H D H
Case:
Flush panel 1
Rack 5

Language:
French 0
English 1
German 2
Spanish 3

Auxiliary voltage:
48 Vdc 1
60 Vdc 2
110 Vdc 3
125 Vdc 4
220 Vdc 5
250 Vdc 6

Acquisition:
1A, 100V/ √ 3 to 120V/ √3, 50 Hz 1
5A, 100V/ √ 3 to 120V/ √3, 50 Hz 2
1A, 100V/ √ 3 to 120V/ √3, 60 Hz 3
5A, 100V/ √ 3 to 120V/ √3, 60 Hz 4

Input supply for the teleprotection:


48 Vdc 1
60 Vdc 2
110 Vdc 3
125 Vdc 4
220 Vdc 5
250 Vdc 6

Communication:
VDEW protocol B
K-Bus/Courier protocol C

Network environment:
Network directly earthed C D
Isolated or with Petersen coil without DEF protection D C
Isolated or with Petersen coil and zero-sequence active power protection without DEF F C

Oscillography:
TPE current loop oscillography F
VDEW oscillography G
K-Bus/Courier oscillography H
TPE/Modem oscillography J

14
Glossary 483.00
465.10
Courier: A communication
304.30
language developed to provide 88.90
generic control, monitoring, data 101.60

151.50
extraction and setting changes on 37.70
57.10

remote devices (primarily on Front view for rack mounting 15.50


Side view
protective relays) within the
substation evironment. 412.50
(with cover fitted)

© 1998 ALSTOM T&D Protection & Contrôle SA


PAS&T: MS Dos interface of the
177.00
Courier language. (4U Nom)

CAS:W: MS Windows interface of


the Courier language. Front view for flush panel
Ø 5 mm earth connection
Rear view

WinEPAC: MS Windows 13 1
application enabling the EPAC to be TMS: Algorithms Standard I/O board Converter
configured and information IRIB.B: Time synchronisation
25 14
Layer 1
uploaded. AC: oscillography & 25 way 'D' connector detail
communications

WinTPE: Group of Windows Daughter boards:


communication

This brochure should only be regarded as a guide. It contents do not constitute an offer for sale, nor advice on any application for any product referred to in it.
applications allowing Terminal block detail
QTR: Analogue inputs 28 way max
communication with the TPE 2000 Additional I/O board 1 2
Each way accepting
disturbance recorder and analysis of Front view (panel removed) 2- M4 Ring terminals
or
fault reports issued by the TPE 000 2- 4.8 x 0.8
Snap-on terminals
and the EPAC. 411.00 or
362.60 1- Ring+
27 28
K-Bus: The 64 kbit/s twitsted pair 24.20 246.05 1- Snap-on terminals

cable used to connect courrier 116.55

compatible devices and transffer


168.00
Courier data. 159.00

KITZ: The interface unit which


8 holes 4.4 4.50
converts between K-Bus and IEC Panel cut-out detail
870 format data.
Figure 17.
IEC 870: An abbreviated term for Arrangement and outline :
the communication standard IEC EPAC panel and rack mounting details
870-5 FT1.2 which is used to
transfer Courier data over modems
and RS232 connections.
Quality assurance : ISO 9001
DESIGN, DEVELOPMENT, PRODUCTION,
Case SALES AND SERVICING (SELECTIVITY
The relay is housed in a multi- STUDYING, CUSTOMER TRAINING, SITE
module MIDOS case suitable for INTERVENTIONS, REPAIR OF SPARE PARTS)
rack or panel mounting, as shown in OF PROTECTION AND CONTROL
Figure 17. EQUIPMENT FOR ELECTRICAL NETWORKS.

Additional information
MS/M 1.6882-B Commissioning
and Maintenance Guide.

15
TRANSCOMP Multimédia - 04 67 92 02 20
N 1.6882-F - 12/98

ALSTOM T&D Protection & Contrôle - 95, rue de la Banquière - BP 75 - 34975 Lattes Cedex FRANCE
Tél : 33 (0)4 67 20 54 54 - Télex : 485 093 F - Fax : 33 (0)4 67 20 54 99 - E-mail: protection.controle@tde.alstom.com

You might also like